B08_Solicitation_Attachment_2_Plans_Delfino_and_Eggleston_Wastewater.pdf
PDF 5 MB Posted
- Attached to
- CAPE COD NS - REPLACE DEFLINO & EGGLESTON SEPTIC Federal contract opportunity
- Solicitation number
- 140P4326R0002
About this file
These are construction drawings for the Cape Cod National Seashore, specifically for replacing septic systems at two locations: 880 Cable Road (Delfino property) and 320 Nellie Road (Eggleston property) in Barnstable County, Massachusetts. The 10-sheet set includes civil, electrical, and detailed septic system design plans prepared by Great West Engineering (prime/civil), Schofield Freeman, Inc. (environmental/geotechnical), and Outermost Land Survey, Inc. (survey).
The project involves installing new septic tank/nitrate treatment systems and soil absorption systems at both properties, including abandoning existing cesspools, installing new electrical connections, and following Massachusetts Department of Environmental Protection regulations. Each location will receive a 1500-gallon two-compartment concrete tank with an AX20 Advantex filter, Cultec Recharger 180HD chambers for soil absorption, and a new septic system control panel. The electrical plans detail connecting the new systems to existing electric panels, with specific instructions for utility coordination, power disconnection, and reconnection requirements.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P4326R0002_Amd_0003.pdf | ||
| Sol_140P4326R0002_Amd_0002.pdf | ||
| Sol_140P4326R0002_Amd_0001.pdf | ||
| Sol_140P4326R0002.pdf | ||
| B08_Solicitation_Attachment_3_DOL_Wage_Determination_MA20260001.pdf | ||
| B08_Solicitation_Attachment_1_Specs_Replace_Septic_Delfino_and_Eggleston_2.pdf | ||
| B08_Solicitation_Attachment_4_Construction_Contract_Administration.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PKG.
NO. SHEET
OF 10
TITLE OF PROJECT
CACO REPLACE SEPTIC SYSTEM
LOCATION WITHIN PARK
DELFINO AND EGGLESTON
NAME OF PARK
CAPE COD NATIONAL SEASHORE
COUNTY
BARNSTABLE
REGION
ATLANTIC EAST
STATE
MASSACHUSETTS
UNITED STATES
DEPARTMENT OF THE INTERIOR
NATIONAL PARK SERVICE
NORTH EAST REGION
A/E FIRM
PRIME/CIVIL:
GREAT WEST ENGINEERING
HELENA, MT
ENVIRONMENTAL/GEOTECHNICAL:
SCHOFIELD FREEMAN, INC
ORLEANS, MA
SURVEY:
OUTERMOST LAND SURVEY INC.
BREWSTER, MA
CONSTRUCTION DRAWINGS DRAWING NO.
MASSACHUSETTS
EASTERN
Mark Sheet InitialDateREVISIONQUALITY DESIGN CERTIFICATION
Project Manager Date
Prepared in Accordance with Design Development (Title I)
OR
Variance from Design Development (Title I) Approved by Superintendent on
OR
Construction Drawing Not Preceded by Design Development (Title I)
Drawing No.
Drawing No.
PROJECT SITE
NE REGIONAL MAP
CONNECTICUT
RHODE
ISLAND
MASSACHUSETTS
FRANKLIN
BERKSHIRE
HAMPSHIRE
HAMPDEN
WORCESTER
MIDDLESEX
ESSEX
NORFOLK
SUFFOLK
PLYMOUTH
BRISTOL
BARNSTABLE
DUKES
NANTUCKET
ATLANTIC OCEAN
EASTHAM
WELLFLEET
BARNSTABLE
COUNTY
CAPE COD
NATIONAL
SEASHORE
Sheet List Table Sheet # Sub Sheet Sheet Title
1 G1 COVER
2 G2 NOTES, LEGEND, AND ABBREVIATIONS
3 C1 DELFINO WASTEWATER IMPROVEMENTS
4 C2 EGGLESTON WASTEWATER
IMPROVEMENTS
5 C3 SEPTIC DETAILS
6 C4 SEPTIC DETAILS
7 E0 LEGEND, SYMBOLS, & ABBREVIATIONS
8 E1 ELECTRICAL 880 CABLE ROAD
9 E2 ELECTRICAL 320 NELLIE ROAD
10 E3 ELECTRICAL SCHEDULES
W
S
P
T
R
T
O
EA
R
E
F
L
E
S
O
T
N
U
N
H
A
H
E
O
L
C O
M M
ON
CASSAMF
ENIGESSI
COLLETTE ANDERSON
CIVIL
NO. 59770
TIS EERG
RE D
NOT TO SCALE
MULTICORELINK:G2 NOTES-G2
MULTICORELINK:G2 NOTES-G2
MULTICORELINK:C1 DELFINO PLAN-C1
MULTICORELINK:C1 DELFINO PLAN-C1
MULTICORELINK:C2 EGGLESTON PLAN-C2
MULTICORELINK:C2 EGGLESTON PLAN-C2
MULTICORELINK:C2 EGGLESTON PLAN-C2
MULTICORELINK:C3 SEPTIC DETAILS-C3
MULTICORELINK:C3 SEPTIC DETAILS-C3
MULTICORELINK:C3 SEPTIC DETAILS-C4
DESIGNED:
TECH. REVIEW:
DATE:
SUB SHEET NO. TITLE OF SHEET DRAWING NO.
PKG.
NO. SHEET
OF 10
A/E FIRM
PRIME/CIVIL:
GREAT WEST ENGINEERING
HELENA, MT
ENVIRONMENTAL/GEOTECHNICAL:
SCHOFIELD FREEMAN, INC
ORLEANS, MA
SURVEY:
OUTERMOST LAND SURVEY, INC
BREWSTER, MA
W
S
P
T
R
T
O
EA
R
E
F
L
E
S
O
T
N
U
N
H
A
H
E
O
L
C O
M M
ON
CASSAMF
ENIGESSI
COLLETTE ANDERSON
CIVIL
NO. 59770
TIS EERG
RE D
LH
FA
MM
5/28/2025
G2
CAPE COD NATIONAL SEASHORE
DELFINO AND EGGLESTON WASTEWATER
ABBREVIATIONS
NOTES, LEGEND, & --
GENERAL NOTES
1. TOPOGRAPHIC SURVEY WAS PREPARED BY OUTERMOST LAND SURVEY, INC. ON OCTOBER 9,
2024.
2. THE CONTRACTOR SHALL COMPLY WITH ALL CONDITIONS CONTAINED IN RELEVANT PERMITS, INCLUDING THOSE ISSUED BY THE MASSACHUSETTS DEPARTMENT OF ENVIRONMENTAL
PROTECTION (MASSDEP).
3. THE CONTRACTOR SHALL SUBMIT, FOR APPROVAL OF THE CONTRACTING
OFFICER/CONTRACTING OFFICER REPRESENTATIVE/ALTERNATE COR, A DETAILED
CONSTRUCTION SCHEDULE AND OUTLINE OF CONSTRUCTION METHODOLOGIES, INCLUDING
EXCAVATION AND DEWATERING, FOR CONSTRUCTION OF THE PROPOSED ACTIVITIES INCLUDING
RESTORATION OF THE PROPOSED STAGING AREAS PRIOR TO CONSTRUCTION.
4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR NOTIFYING THE GOVERNMENT AT LEAST TEN
(10) BUSINESS DAYS PRIOR TO MAJOR PROJECT MILESTONES. THIS INCLUDES BUT IS NOT
LIMITED TO, START UP OR RESTART OF ANY WORK, EXCAVATION, SYSTEM INSTALLATION, OR
TESTING.
5. ALL SIGNS ARE TO BE PROTECTED BY THE CONTRACTOR. CONTRACTOR SHALL REPLACE SIGNS
DAMAGED OR DISPLACED DURING CONSTRUCTION AT THE CONTRACTOR'S EXPENSE, UNLESS
OTHERWISE NOTED.
6. THE CONTRACTOR SHALL NOT DAMAGE VEGETATION OUTSIDE OF THE WORK LIMITS.
7. THE CONTRACTOR SHALL INSTALL TREE PROTECTION AND TEMPORARY FENCING TO PROTECT
TREES IMPACTED BY CONSTRUCTION, BUT NOT DESIGNATED FOR REMOVAL BY THE
CONTRACTING OFFICER/CONTRACTING OFFICER REPRESENTATIVE/ALTERNATE COR. ALL COST
SHALL BE INCIDENTAL TO THE PROJECT.
8. TREE TRIMMING AND TREE REMOVAL SHALL BE COMPLETED BY A CERTIFIED ARBORIST. ALL
TREES AND LIMBS OF INTEREST SHALL BE MARKED AND APPROVED FOR TRIMMING OR
REMOVAL. CONTRACTOR TO COORDINATE WITH ENGINEER AND CONTRACTING
OFFICER/CONTRACTING OFFICER REPRESENTATIVE/ALTERNATE COR BEFORE PROCEEDING
WITH TREE TRIMMING OR REMOVAL.
9. REQUIRED EROSION AND SEDIMENTATION CONTROLS SHOWN ON THE PLAN IS APPROXIMATE.
THE CONTRACTOR SHALL DETERMINE THE ACTUAL TYPE AND LOCATION OF THE EROSION AND
SEDIMENTATION CONTROL, SUBJECT TO TO THE APPROVAL OF THE CONTRACTING
OFFICER/CONTRACTING OFFICER REPRESENTATIVE/ALTERNATE COR. THE CONTRACTOR SHALL
SUBMIT AN EROSION AND SEDIMENT CONTROL PLAN DETAILING PROPOSED MEASURE AND
QUALITY CONTROL PLAN TO ENSURE PROPER INSTALLATION AND MAINTENANCE. THE
CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR INSPECTING AND MAINTAINING EROSION
AND SEDIMENTATION CONTROL MEASURES, INCLUDING INSTALLATION, REPOSITIONING, AND
REMOVAL AS NEEDED THROUGH THE DURATION OF CONSTRUCTION. THE GOVERNMENT WILL
REVIEW THE CONTRACTORS QUALITY CONTROL PROCESS AND CONFIRM THAT THE
INSTALLATION ALIGNS WITH THE APPROVED SHOP DRAWINGS, BUT WILL NOT DONDUCT DIRECT
INSPECTIONS OF THE INSTALLATIONS.
10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE STABILITY OF THE STRUCTURE DURING
CONSTRUCTION ACTIVITIES.
11. THE CONTRACTOR SHALL TAKE PRECAUTIONS TO PREVENT DAMAGE TO WORK OR EQUIPMENT
BY HIGH WATER OR BY STORMS. THE CONTRACTING OFFICER/CONTRACTING OFFICER
REPRESENTATIVE/ALTERNATE COR MAY PROHIBIT CONSTRUCTION ACTIVITIES AT ANY TIME
WHEN IN HIS/HER JUDGMENT HIGH WATERS OR STORM CONDITIONS ARE UNFAVORABLE OR
UNSUITABLE, OR AT ANY TIME REGARDLESS OF THE WEATHER WHEN PROPER PRECAUTIONS
ARE NOT BEING TAKEN TO SAFEGUARD PREVIOUSLY CONSTRUCTED WORK OR WORK IN
PROGRESS. IN THE CASE OF DAMAGE CAUSED BY FAILURE OF THE CONTRACTOR TO TAKE
ADEQUATE PRECAUTIONS, THE CONTRACTOR SHALL REPAIR OR REPLACE EQUIPMENT/WORK
DAMAGED AND SHALL MAKE SUCH REPAIRS OR REBUILD PARTS OF THE DAMAGED WORK AS
DIRECTED BY THE CONTRACTING OFFICER/CONTRACTING OFFICER
REPRESENTATIVE/ALTERNATE COR, AT NO ADDITIONAL COST TO THE GOVERNMENT.
12. ALL CONSTRUCTION VEHICLES AND EQUIPMENT INCLUDING OFFICE TRAILERS AND RESIDENTIAL TRAILERS THAT ENTER THE PARK AND ARE STAGED IN ASSOCIATION WITH THIS PROJECT WILL
BE INSPECTED BY THE CONTRACTING OFFICER/CONTRACTING OFFICER
REPRESENTATIVE/ALTERNATE COR PRIOR TO THEIR ENTRY INTO THE PARK FOR MUD, WEEDS,
AND OTHER UNWANTED SUBSTANCES. SEE PROJECT SPECIFICATIONS FOR ADDITIONAL PARK
REQUIREMENTS AND REGULATIONS.
13. THE CONTRACTOR SHALL SUBMIT A PROPOSED STAGING AREA PLAN TO THE CONTRACTING
OFFICER/CONTRACTING OFFICER REPRESENTATIVE/ALTERNATE COR FOR APPROVAL. AT A
MINIMUM, THE STAGING AREA PLAN SHALL IDENTIFY STAGING EROSION CONTROL MEASURES,
AND PROPOSED RESTORATION. THE EROSION CONTROL DETAILS SHALL CONTAIN DETAILS FOR
A REFUELING SITE AND STABILIZED CONSTRUCTION ENTRANCE. THE CONTRACTOR SHALL
RESTORE THE PROPOSED STAGING AREAS TO PRECONSTRUCTION CONDITIONS AFTER THE
WORK IS COMPLETE. THE CONTRACTOR SHALL NOT STORE, HANDLE AND/OR DISPOSE OF
HAZARDOUS MATERIALS WITHIN THE WORK AREA OR STAGING AREA. DERIVED WASTE SHALL
BE REMOVED AND DISPOSED IN ACCORDANCE WITH FEDERAL AND STATE REGULATIONS. ALL
ROCK, SAND, GRAVEL, FILL OR OTHER FOREIGN SUBSTRATE MATERIAL STORED IN STAGING
AREAS MUST BE STORED ON TOP OF FILTER FABRIC TO FACILITATE RECOVERY AND PREVENT
DEGRADATION OF NATIVE SOILS DURING SITE CLEANUP. NO FOREIGN SAND, TOPSOIL, LOAM OR
OTHER FOREIGN SUBSTRATE MAY BE ADDED TO STAGING AREAS DURING SITE CLEANUP AND
REGRADING WITHOUT PRIOR APPROVAL FROM THE CONTRACTING OFFICER/CONTRACTING
OFFICER REPRESENTATIVE/ALTERNATE COR. EXISTING PAVEMENT SHALL BE SWEPT CLEAN OR
RESTORED TO EXISTING CONDITIONS BY OTHER MEANS TO THE SATISFACTION OF THE
CONTRACTING OFFICER/CONTRACTING OFFICER REPRESENTATIVE/ALTERNATE COR. ANY
CLEAN UP OF HAZARDOUS MATERIAL SHALL INCLUDE NOTIFICATIONS, MANIFESTS, REPORTS,
AND DISPOSAL. ALL COSTS ASSOCIATED WITH THE PROPOSED STAGING AREAS (INCLUDING
EROSION CONTROL, REFUELING SITE, STABILIZED CONSTRUCTION ENTRANCES, AND
RESTORATION) SHALL BE INCIDENTAL TO THE PROJECT.
14. NO TRUCKS OR TRACKED VEHICLES SHALL BE REFUELED ON SITE. NO FUEL SHALL BE STORED
ON SITE.
15. PROPERTIES ARE LOCATED OFF PARK OWNED PUBLIC ROADWAYS. THE CONTRACTOR SHALL
PROVIDE TEMPORARY BARRICADES, SIGNAGE AND OTHER FORMS OF PROTECTION AS
REQUIRED TO PROTECT NPS PERSONNEL AND THE GENERAL PUBLIC FROM INJURY DUE TO
CONSTRUCTION ACTIVITIES. CONTRACTOR SHALL COMPLY WITH THE MANUAL ON UNIFORM
CONTROL DEVICES (MUTCD) FOR ALL TRAFFIC CONTROL DEVICES.
16. DO NOT DAMAGE ADJACENT PROPERTIES (INCLUDING FENCES). THE CONTRACTOR SHALL
PROMPTLY REPAIR ANY DAMAGE TO ADJACENT PROPERTIES AT NO ADDITIONAL COST TO THE
GOVERNMENT.
17. THE CONTRACTOR SHALL CONDUCT CONSTRUCTION OPERATIONS IN A MANNER TO ENSURE
MINIMUM INTERFERENCE WITH ROADS, TRAILS, WALKS AND OTHER FACILITIES. DO NOT CLOSE, BLOCK, OR OBSTRUCT ROADS, WALKS, OR OTHER FACILITIES WITHOUT NPS WRITTEN
PERMISSION. PROVIDE ALTERNATE ROUTES AROUND CLOSED OR OBSTRUCTED TRAFFIC WAYS
(INCLUDING SIDEWALKS, ETC.). ASSUME REQUIRED SAFETY AND ACCESS MEASURES
NECESSARY TO PROTECT THE PUBLIC DURING CONSTRUCTION OPERATIONS.
18. THE CONTRACTOR SHALL ENSURE THAT ALL PERSONNEL OPERATING HEAVY EQUIPMENT ARE
TRAINED AND AUTHORIZED. EQUIPMENT SHALL BE INSPECTED DAILY AND ANY DEFICIENCIES
SHALL BE ADDRESSED BEFORE USE. SAFE OPERATING DISTANCES SHALL BE MAINTAINED FROM
EQUIPMENT. ALL EQUIPMENT SHALL BE EQUIPPED WITH FUNCTIONING BACKUP ALARMS, AND
SPOTTER SHALL BE USED IN CONGESTED AREAS.
19. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL MASS DEP INSPECTIONS, THIRD PARTY
ENGINEERING INSPECTIONS, AND PERMIT CLOSE OUT. CONTRACTOR SHALL COORDINATE WITH
RESPONSIBLE PARTIES. ALL COST SHALL BE INCIDENTAL TO THE PROJECT.
20. ALL ACCESS PORTS AND COVERS SHALL BE INSTALLED AND MAINTAINED ON GRADE TO ALLOW
FOR MAINTENANCE OF THE SYSTEM.
UTILITY NOTES
1. LOCATION OF UNDERGROUND UTILITIES SHOWN ON THE PLANS ARE APPROXIMATE. OWNER
AND CONSULTANTS ASSUME NO RESPONSIBILITY FOR THE LOCATIONS AND ACCURACY OF
UTILITIES INDICATED ON THE PLANS. THE CONTRACTOR SHALL LOCATE, CLEARLY MARK AND
MAINTAIN EXISTING UTILITIES ON THE SITE PRIOR TO WORK START UP. CALL THE DIG SAFE AT
(888) 344-7233 OR 811 PRIOR TO WORK START UP. IN ADDITION TO DIG SAFE, CONTRACTOR
SHALL PROVIDE A SURVEY USING GROUND PENETRATING RADAR PRIOR TO WORKING AT THE
SITE. ANY HIDDEN UTILITIES SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTING
OFFICER.
2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROTECTION OF ALL UTILITIES AND
REPAIR OF UTILITIES IF DAMAGED. REPAIR SHALL BE DONE AT NO ADDITIONAL COST TO NPS.
ALL WORK IN UTILITY EASEMENTS SHALL BE PERFORMED ACCORDING TO THE REQUIREMENTS
OF THE GOVERNING AGENCY.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION AND DESIGN AS NECESSARY
OF ALL PERMANENT AND TEMPORARY UTILITY RELOCATIONS, INTERIOR, UNDERGROUND, AND
OVERHEAD. THERE ARE NO PLANNED UTILITY IMPACTS AS A PART OF THIS PROJECT. IF
UTILITIES ARE IMPACTED DUE TO CONTRACTOR NEGLIGENCE, SERVICE SHALL BE IMMEDIATELY
RESTORED.
4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SCHEDULING, WORK ORDERS, AND
PERMITS WITH EVERSOURCE. CONTRACTOR SHALL COORDINATE ANY POWER SHUTDOWN TO
PERFORM NECESSARY LOCKOUT/TAGOUT REQUIREMENTS.
5. ALL WORK PERFORMED UNDER THIS CONTRACT SHALL BE IN ACCORDANCE WITH FEDERAL,
STATE AND LOCAL OSHA REGULATIONS.
6. ALL SYSTEM COMPONENTS SHALL BE MARKED WITH MAGNETIC MARKING TAPE. INSTALL
LOCATING TAPE DURING BACKFILLING AT 18 INCHES TO 24 INCHES ABOVE CENTERLINE OF
SYSTEM COMPONENTS.
SPILL PREVENTION AND RESPONSE PROCEDURE
1. ANY DISCHARGE OF WASTE OR OTHER POLLUTANT TO THE ENVIRONMENT REQUIRES
IMMEDIATE NOTIFICATION TO THE PARK BY DIALING 911.
2. ANY INCIDENT OF CONTAMINATION RESULTING FROM THE IMPROPER DISCHARGE OF
POLLUTANTS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR OR OTHER PARTIES THAT
THE GOVERNMENT DETERMINES TO BE RESPONSIBLE FOR THE CONTAMINATION. PURSUANT TO
THE STATE LAWS AND REGULATIONS, THE GOVERNMENT MAY REQUIRE THE CONTRACTOR AND
OTHER RESPONSIBLE PARTIES TO REMEDIATE ANY INCIDENTS THAT MAY ADVERSELY IMPACT
GROUNDWATER OR SURFACE WATER QUALITY.
3. THE CONTRACTOR SHALL MAINTAIN ON THE SITE APPROPRIATE MATERIALS TO CONTAIN AND
RECOVER OILS AND OTHER POLLUTANTS TO PREVENT RELEASE INTO THE ENVIRONMENT.
4. REFUELING OF EQUIPMENT SHALL OCCUR AT A MINIMUM OF 100 FT. AWAY FROM ANY STREAM.
SITE SPECIFIC NOTES
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING PROPOSED WORK WITH THE
CONTRACTING OFFICER/CONTRACTING OFFICER REPRESENTATIVE/ALTERNATE COR,
PROVIDING ADEQUATE CONTROLS FOR SITE SAFETY, AND MINIMIZING IMPACTS. UNDER NO
CIRCUMSTANCES SHALL THE CONTRACTOR INITIATE ACTIVITIES THAT WILL RESTRICT ACCESS
OF EMERGENCY VEHICLES WITHOUT PRIOR AUTHORIZATION FROM THE CONTRACTING
OFFICER/CONTRACTING OFFICER REPRESENTATIVE/ALTERNATE COR.
2. ALL CONSTRUCTION ACCESS PATH MATERIALS SHALL BE REMOVED AFTER CONSTRUCTION AND
ORIGINAL GRADES SHALL BE RESTORED. THE CONTRACTOR SHALL RE-VEGETATE AND
STABILIZE ALL AREAS DISTURBED BY CONSTRUCTION ACTIVITIES.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR HEALTH AND SAFETY OF ALL ITS EMPLOYEES, SUBCONTRACTORS, AND VENDORS WORKING ON THE PROJECT.
4. THE CONTRACTOR SHALL MAINTAIN ON SITE AT ALL TIMES A SET OF RECORD DRAWINGS AND SPECIFICATIONS THAT SHALL BE UPDATED ON A DAILY BASIS AND SHALL BE SUBMITTED TO THE
CONTRACTING OFFICER/CONTRACTING OFFICER REPRESENTATIVE/ALTERNATE COR AT THE
COMPLETION OF THE CONSTRUCTION. RECORD DRAWINGS SHALL INCLUDE THE LOCATIONS
AND REFERENCED DIMENSIONS OF ALL BURIED AND RELOCATED UTILITIES. FINAL SUBMISSION
OF RECORD DRAWINGS SHALL BE ELECTRONIC AND IN ACCORDANCE WITH THE
SPECIFICATIONS. HAND DRAWN REDLINED RECORD DRAWINGS SHALL NOT BE ACCEPTED FOR
THE FINAL SUBMITTAL.
5. THE CONTRACTOR SHALL SECURE THE WORK SITE FROM UNAUTHORIZED PERSONNEL WITH
FENCING OR OTHER METHODS APPROVED BY THE CONTRACTING OFFICER/CONTRACTING
OFFICER REPRESENTATIVE/ALTERNATE COR.
6. PRIOR TO CONSTRUCTION ACTIVITIES, CONTRACTOR SHALL LOCATE CONTROL POINTS AND
ESTABLISH THE CONSTRUCTION LAYOUT. THE CONTRACTOR SHALL PROVIDE A CONSTRUCTION
LAYOUT IN SUFFICIENT DETAIL, THEREBY ENABLING THE CONTRACTOR TO CONSTRUCT THE
PROJECT IN CONFORMITY WITH THE PLANS AND SPECIFICATIONS. SURVEY SHALL BE PROVIDED
BY THE CONTRACTOR. THE CONTRACTING OFFICER/CONTRACTING OFFICER
REPRESENTATIVE/ALTERNATE COR WILL NOT AUTHORIZE CONSTRUCTION ACTIVITIES TO BEGIN
UNTIL THE CONTRACTOR SATISFIES THAT ALL GROUND CONTROL HAS BEEN ESTABLISHED, TIED
DOWN, AND DULY RECORDED.
7. CONTRACTOR SHALL INSURE ALL WORK PERMITS ARE SECURED AND HARDCOPIES ARE ON SITE
FOR REVIEW PRIOR TO CONSTRUCTION.
8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE MAINTENANCE AND PROTECTION OF
PEDESTRIAN AND VEHICULAR TRAFFIC AS REQUIRED BY THE CONTRACT DOCUMENTS.
ABBREVIATIONS
@ AT
& AND
APPROX APPROXIMATE
C.C.N.S. CAPE COD NATIONAL SEASHORE
CL, ℄ CENTERLINE
CO CONTRACTING OFFICER
COR CONTRACTING OFFICER
REPRESENTATIVE
EG EXISTING GROUND
ELEV ELEVATION
FG FINISHED GRADE
HORIZ HORIZONTAL
LOD LIMIT OF DISTURBANCE
NHP NATIONAL HISTORICAL PARK
NHESP NATIONAL HERITAGE AND
ENDANGERED SPECIES PROGRAM
NPS NATIONAL PARK SERVICE
NTS NOT TO SCALE
PI POINT OF INTERSECTION
PVI POINT OF VERTICAL INTERSECTION
STA STATION
STD STANDARD
TYP TYPICAL
VERT VERTICAL
O H
P O
H P
O H
P O
H P
O H
P
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
SS
SS
SS
SS
N: 2777343.2470 E: 1077163.1366
N: 2777320.5655 E: 1077193.1251
N: 2777369.5003 E: 1077144.7155
N: 2777359.3763 E: 1077145.6488
20 10 0 20 40
SCALE OF FEET
NOTES:
DESIGNED:
TECH. REVIEW:
DATE:
SUB SHEET NO. TITLE OF SHEET DRAWING NO.
PKG.
NO. SHEET
OF 10
A/E FIRM
PRIME/CIVIL:
GREAT WEST ENGINEERING
HELENA, MT
ENVIRONMENTAL/GEOTECHNICAL:
SCHOFIELD FREEMAN, INC
ORLEANS, MA
SURVEY:
OUTERMOST LAND SURVEY, INC
BREWSTER, MA
W
S
P
T
R
T
O
EA
R
E
F
L
E
S
O
T
N
U
N
H
A
H
E
O
L
C O
M M
ON
CASSAMF
ENIGESSI
COLLETTE ANDERSON
CIVIL
NO. 59770
TIS EERG
RE D
LH
FA
MM
5/28/2025
C1
CAPE COD NATIONAL SEASHORE
DELFINO AND EGGLESTON WASTEWATER
880 CABLE ROAD
IMPROVEMENTS
DELFINO WASTEWATER --
PLAN VIEW OF DELFINO WASTEWATER IMPROVEMENTS
1. ALL CONSTRUCTION TO CONFROM WITH 310 CMR 15.000
AND ALL OTHER APPLICABLE LOCAL, STATE AND FEDERAL
CODES AND REGULATIONS.
2. FINISH COVER OVER COMPONENTS IS NOT TO EXCEED 3'
PER 310 CMR 15.000.
3. ORENCO AX20 TANK NOT TO BE PLACED WITHIN A 50'
RADIUS OF A PRIVATE WELL. DRAINFIELD NOT TO BE
PLACED WITHIN 100' OF A PRIVATE WELL, PER 310 CMR
15.000.
4. CONTRACTOR SHALL RETAIN AND PROTECT TREES WITH
TRUNK DIAMETER OVER 3".
5. CONTRACTOR SHALL INSTALL ALL SEWER LINES AT A
MINIMUM 2% SLOPE.
6. NO GARBAGE GRINDERS SHALL BE ALLOWED AS
COMPONENTS TO THE SEPTIC SYSTEM.
7. ALL SEWER PIPE SHALL BE SDR35 PVC.
880 CABLE RD
ASSESSORS
PARCEL 23-48
C.C.N.S.
F.F.E. = 43.8'
DEEP HOLE DATA
DEPTH ELEV.
0.00'
5.0'
13.0'
30.3'
29.3'
28.88'
27.38'
25.3'
DEPTH ELEV.
0.00'
4.0'
11.0'
34.75'
33.3'
30.75'
23.75'
PERFORMED BY: LAURA A. SCHOFIELD, SE
WITNESSED BY: SEAN CARNEY, DEP
TEST DAY: 11/8/2024
NO GROUND WATER
OBSERVED DURING TESTING
CABLE ROAD
PROPOSED SEPTIC TANK/NITRATE
TREATMENT SYSTEM
C3
PROPOSED SOIL
ABSORPTION SYSTEM
C3
ABANDON EXISTING
CESSPOOL, FILL WITH
CLEAN BACKFILL
PORCH
EXISTING SEPTIC
TANK
EXISTING SOIL
ABSORPTION SYSTEM
0 OCEANVIEW DR
TOWN OF EASTHAM
(VACANT)
BLOCK 6
UNITED STATES OF
AMERICAN
160.0'
N 08° 54' 25" W
160.0' S 08° 54' 25" E
120.0'S 81° 05' 35" W
120.0' N 81° 05' 35" E
EXISTING WELL,
ABANDON AFTER
CONNECTING TO
WATER MAIN
EXISTING WELL
EXISTING WELL
DIRT DRIVEWAY
ATLAN
TIC
O C
EAN
O C
EAN
VIEW
D R
IVE
CABLE ROAD
LOCUS
NAUSET LIGHT
BEACH ROAD
LOCUS MAP
EXISTING SEPTIC
TANK
100'
100'
TH #1
TH #2
1.0'
1.42'
2.92'
TH #1
17.3'
FILL
SANDY LOAM
10YR5/6
BW
SANDY LOAM
10YR5/8
C1
LOAMY SAND
10YR5/8
A/E
SANDY LOAM/LOAMY SAND
10YR5/3 / 10YR6/2
C2
LOAMY SAND
10YR6/6
1.42'
TH #2
BW
LOAMY SAND
10YR5/8
C1
LOAMY SAND
7.5YR4/6
C2
SAND
10YR6/6
PERC RATE @ 30"
<2 MIN./IN.
EDGE OF CLEARING
860 CABLE ROAD
ADNER FAMILY
HOLDING TRUST
900 CABLE RD
CHRIS PARTICELLI TRUST
INSTALL 1" CORPORATION AND NEW 1" PE WATER
SERVICE FROM 12" (DI) WATER MAIN TO LOCATION OF
PROPOSED CURB STOP. EXACT LOCATION OF CURB
STOP TO BE DETERMINED DURING CONSTRUCTION
CONNECT TO EXISTING
SERVICE LINE CUT, CAP, AND ABANDON EXISTING
LINE CONNECTING TO WELL
BENCHMARK:
SPIKE IN ASPHALT
EL.=42.15 (NAVD 88)
PROPOSED SOIL
ABSORPTION TRENCHING
C4
RETAIN AND PROTECT FENCING
DESIGN CALCULATIONS
ESTIMATED HYDRAULIC LOADING:
3 BEDROOM DWELLING X 110 GPD = 330 GPD REQUIRED
GARBAGE GRINDER IS NOT ALLOWED WITH THIS DESIGN
SEPTIC TANK SIZE:
AVERAGE DAILY FLOW 330 GPD X 2 DAYS = 660 GALLONS REQUIRED
USE 1500 GALLON TANK
SOIL ABSORPTION SYSTEM (S.A.S.):
PERC RATE = <2 MIN/IN - CLASS I SOIL
EFFLUENT LOADING RATE= 0.74 GPD/SF
LEACHING AREA: 330 GPD / 0.74 GPD/SF = 446 SF REQUIRED
CULTEC SYSTEM: RECHARGER 180 HD
TRENCH CONFIGURATION:
MASSACHUSETTS ALLOWABLE EFFECTIVE LEACHING AREA= 8.9 SF/LF
8 CHAMBERS X 6.3 LF/CHAMBER X 8.9 SF/LF = 448.6 SF PROVIDED
NO GROUND WATER
OBSERVED DURING TESTING
INSTALL SEWER CLEAN
OUT/SAMPLING POINT
BEFORE 45° ELBOW
INV OUT: 33.5'
(ASSUMED)
INV IN: 31.3'
INV IN: 29.9'
INV OUT: 32.3'
INSTALL SEWER
CLEAN OUT BEFORE
45° ELBOW CUT, CAP, AND ABANDON EXISTING
SEWER SERVICE CONNECTING TO
THE CESSPOOL
PUMP OUT STANDING
SLUDGE WITH AN
APPROVED SEPTIC HAULER
EDGE OF ASPHALT
SSSS SS SS SS27.5
N: 2800341.1594 E: 1069563.4650
N: 2800340.7410 E: 1069553.3066
N: 2800333.9310 E: 1069507.1932
N: 2800296.3774 E: 1069505.3258
20 10 0 20 40
SCALE OF FEET
NOTES:
DESIGNED:
TECH. REVIEW:
DATE:
SUB SHEET NO. TITLE OF SHEET DRAWING NO.
PKG.
NO. SHEET
OF 10
A/E FIRM
PRIME/CIVIL:
GREAT WEST ENGINEERING
HELENA, MT
ENVIRONMENTAL/GEOTECHNICAL:
SCHOFIELD FREEMAN, INC
ORLEANS, MA
SURVEY:
OUTERMOST LAND SURVEY, INC
BREWSTER, MA
W
S
P
T
R
T
O
EA
R
E
F
L
E
S
O
T
N
U
N
H
A
H
E
O
L
C O
M M
ON
CASSAMF
ENIGESSI
COLLETTE ANDERSON
CIVIL
NO. 59770
TIS EERG
RE D
LH
FA
MM
5/28/2025
C2
CAPE COD NATIONAL SEASHORE
DELFINO AND EGGLESTON WASTEWATER
320 NELLIE ROAD
IMPROVEMENTS
EGGLESTON WASTEWATER --
PLAN VIEW OF EGGLESTON WASTEWATER IMPROVEMENTS
1. ALL CONSTRUCTION TO CONFROM WITH 310 CMR 15.000
AND ALL OTHER APPLICABLE LOCAL, STATE AND
FEDERAL CODES AND REGULATIONS.
2. FINISH COVER OVER COMPONENTS IS NOT TO EXCEED
3' PER 310 CMR 15.000.
3. SITE WITHIN NHESP ZONE.
4. ORENCO AX20 TANK NOT TO BE PLACED WITHIN A 50'
RADIUS OF A PRIVATE WELL. DRAINFIELD NOT TO BE
PLACED WITHIN 100' OF A PRIVATE WELL, PER 310 CMR
15.000.
4. CONTRACTOR SHALL RETAIN AND PROTECT TREES WITH
TRUNK DIAMETER OVER 3".
5. CONTRACTOR SHALL INSTALL ALL SEWER LINES AT A
MINIMUM 2% SLOPE.
6. NO GARBAGE GRINDERS SHALL BE ALLOWED AS
COMPONENTS TO THE SEPTIC SYSTEM.
7. ALL SEWER PIPE SHALL BE SDR35 PVC.
DEEP HOLE DATA
DEPTH ELEV.
0.00'
0.58'
2.17'
10.0'
64.5'
63.92'
62.33'
54.5'
DEPTH ELEV.
0.00'
1.75'
11.0'
62.5'
60.75'
11.0'
PERFORMED BY: LAURA A. SCHOFIELD, SE
WITNESSED BY: SEAN CARNEY, DEP & GARY LOCKE, WELLFLEET ASST.
TEST DAY: 11/08/2024
NO GROUND WATER
OBSERVED DURING TESTING
NO GROUND WATER
OBSERVED DURING TESTING
NELLIE ROAD
PROPOSED SEPTIC TANK/NITRATE
TREATMENT SYSTEM 1
C3
PROPOSED SOIL
ABSORPTION
SYSTEM
C3
PORCH
EXISTING SOIL
ABSORPTION SYSTEM
88.8'
N 11° 03' 40" W
88.8' S 11° 03' 40" E
100.0' S 78° 56' 20" W
100.0' N 78° 56' 20" E
NHESP LINE
GRAVEL DRIVEWAY
LOCUS MAP
EXISTING SEPTIC
TANK
RTE. 6
LECOUNT
HOLLOW
RD.
NELLIE RD.
WILSON AVE.
O C
EAN
VIEW
D R
LOCUS
ATLAN
TIC
O C
EAN
WILSON AVENUE
N 66° 20' 20" E
N 75° 34' 40" E
S 01° 49' 32" E
S 78° 56' 20" W
S 11° 03' 40" E
72.8'
68.4'
23.3'
75.0'
102.5'
GRAVEL DRIVEWAY
EXISTING SEPTIC
TANK
EXISTING WELL
EXISTING WELL
100'
310 NELLIE RD
C.C.N.S.
F.F.E. = 85.9'
340 WILSON AVE
SANDRA T. SOTOLOTTO
325 NELLIE RD
CAPE COD NATIONAL
SEASHORE
PARCEL 30-637
CAPE COD NATIONAL
SEASHORE
319 NELLIE RD
KENNETH MAREK
PARCEL 30-639
CAPE COD NATIONAL
SEASHORE
PARCEL 30-647
CAPE COD NATIONAL
SEASHORE
320 NELLIE RD
C.C.N.S.
F.F.E. = 79.2'
EDGE OF CLEARING
DEPTH ELEV.
0.00'
0.83'
2.0'
12.0'
0.00'
10.0'
NO GROUND WATER OBSERVED
DURING TESTING
TH #1
E
LOAMY SAND
10YR6/2
BW
LOAMY SAND
10YR5/6
TH #2
TH #3
TH #2
TH #1
TH #3C
SAND
10YR6/8
E
LOAMY SAND
10YR6/2
BW
LOAMY SAND
10YR5/8
C
SAND
10YR6/4
0.58' 61.92'
PERC RATE @ 27"
<2 MIN./IN.
E
LOAMY SAND
10YR6/3
BW
LOAMY SAND
10YR5/8
C
SAND
10YR6/6
EXISTING ELECTRICAL
PROPOSED SOIL
ABSORPTION
TRENCHING
C4
INSTALL SEWER
CLEAN OUT BEFORE
TWO 45° ELBOWS
INSTALL SEWER CLEAN
OUT/ SAMPLING POINT
BEFORE TWO 45° ELBOWS
INV OUT: 70.0'
(ASSUMED) CONTRACTOR
SHALL VERIFY
INV IN: 62.9'
INV OUT: 63.9'
ABANDON EXISTING CESSPOOL,
FILL WITH CLEAN BACKFILL
INV IN: 54.6'
DESIGN CALCULATIONS
ESTIMATED HYDRAULIC LOADING:
3 BEDROOM DWELLING X 110 GPD = 330 GPD REQUIRED
GARBAGE GRINDER IS NOT ALLOWED WITH THIS DESIGN
SEPTIC TANK SIZE:
AVERAGE DAILY FLOW 330 GPD X 2 DAYS = 660 GALLONS REQUIRED
USE 1500 GALLON TANK
SOIL ABSORPTION SYSTEM (S.A.S.):
PERC RATE = <2 MIN/IN - CLASS I SOIL
EFFLUENT LOADING RATE= 0.74 GPD/SF
LEACHING AREA: 330 GPD / 0.74 GPD/SF = 446 SF REQUIRED
CULTEC SYSTEM: RECHARGER 180 HD
TRENCH CONFIGURATION:
MASSACHUSETTS ALLOWABLE EFFECTIVE LEACHING AREA= 8.9 SF/LF
8 CHAMBERS X 6.3 LF/CHAMBER X 8.9 SF/LF = 448.6 SF PROVIDED
CUT, CAP, AND
ABANDON EXISTING
SEWER SERVICE TO
EXISTING CESSPOOL
MULTICORELINK:C3 SEPTIC DETAILS-C3
MULTICORELINK:C3 SEPTIC DETAILS-C3
TOP VIEW
SCALE: 1"=2.5'
Y G W
G W
I Y
D
RSV
MIN. 19"Ø TANK OPENING
2"Ø DISCHARGE LINE
SLOPE(MIN. 1/4"/FT)
24"Ø FIBERGLASS RISER WITH 24"
GASKETED FIBERGLASS LID WITH S.S.
BOLTS, TANK SHIELD AND SIMPLEX
PUMPING SYSTEM (TANK SHIELD NOT
SHOWN FOR DRAWING CLARITY)
2"Ø RETURN LINE
SLOPE (MIN. 1/4"/FT)
1"Ø TRANSPORT LINE
24"Ø FIBERGLASS RISER
WITH 24" GASKETED
FIBERGLASS LID WITH S.S.
BOLTS AND TANK SHIELD
INLET
TO DRAINFIELD
90"
.5
1500 GALLON
TWO-COMPARTMENT
CONCRETE TANK
SIDE VIEW
SCALE: 1"=2.5'
24"Ø FIBERGLASS RISER
WITH 24" GASKETED
FIBERGLASS LID WITH S.S.
BOLTS AND TANK SHIELD
INLET
AX20 ADVANTEX FILTER
RECIRCULATING SPLITTER
VALVE (RSV) WITH QUICK
DISCONNECT
CLICKTIGHT PUMP AND FLOATS
CONNECTION (SPLICE BOX, SBEX,
NOT SHOWN)
TO CONTROL PANEL
FLOW-THROUGH PORT
BIOTUBE PUMP VAULT
MODEL PVU68-2425-L
FLOAT FUNCTIONS
HIGH LEVEL ALARM
OVERRIDE TIMER ON/OFF
LLA/RO
END VIEW
SCALE: 1"=2.5'
HIGH HEAD PUMP
MODEL PF300511
BIOTUBE FILTER (24")
FLOAT ASSEMBLY
MODEL MF3P
1"Ø DISCHARGE ASSY.
MODEL HV100
2"Ø VENT
24"Ø FIBERGLASS RISER
WITH 24" GASKETED
FIBERGLASS LID WITH S.S.
BOLTS, TANK SHIELD AND
SIMPLEX PUMPING SYSTEM
TO DRAINFIELD
INSTALLED LENGTH ADJUSTMENT = 1.0' (0.3 m)
ALL RECHARGER 180HD HEAVY DUTY UNITS ARE
MARKED WITH A COLOR STRIPE FORMED INTO THE
PART ALONG THE LENGTH OF THE CHAMBER.
1.87
1.07 0.73
*MAY ALSO BE USED AS AN INTERMEDIATE UNIT
TO EXTEND THE LENGTH OF A RUN.
6" [152 mm] DIA.
INSPECTION PORT
MODEL R STARTER/STAND ALONE
LARGE RIBSMALL RIB
MODEL E END*
LARGE RIBSMALL RIB
4.57
INSTALLED LENGTH = 3.95
38.0" [964mm] 38.0" [964mm]
NOTES:
1. CONTRACTOR SHALL INSTALL LEVEL AND COMPACTED BASE WITH 6" OF CRUSHED STONE
THAT HAS BEEN PLACED TO MINIMIZE UNEVEN SETTLING.
2. SEPTIC TANK SHALL HAVE A MINIMUM COVER OF 9".
ATTACH ADDITIONAL CHAMBER
BY INTERLOCKING THE RIBS
CULTEC NO. 410 FILTER FABRIC,
FABRIC ROLL WIDTH = 5'
SEPTIC TANK/NITRATE TREATMENT SYSTEM DETAIL
DESIGNED:
TECH. REVIEW:
DATE:
SUB SHEET NO. TITLE OF SHEET DRAWING NO.
PKG.
NO. SHEET
OF 10
A/E FIRM
PRIME/CIVIL:
GREAT WEST ENGINEERING
HELENA, MT
ENVIRONMENTAL/GEOTECHNICAL:
SCHOFIELD FREEMAN, INC
ORLEANS, MA
SURVEY:
OUTERMOST LAND SURVEY, INC
BREWSTER, MA
W
S
P
T
R
T
O
EA
R
E
F
L
E
S
O
T
N
U
N
H
A
H
E
O
L
C O
M M
ON
CASSAMF
ENIGESSI
COLLETTE ANDERSON
CIVIL
NO. 59770
TIS EERG
RE D
LH
FA
MM
5/28/2025
C3
CAPE COD NATIONAL SEASHORE
DELFINO AND EGGLESTON WASTEWATER
SEPTIC DETAILS --
C3
SOIL ABSORPTION SYSTEM DETAIL2
C3
AdvanTex AX20 Mode 1A
CULTEX RECHARGER 180HD
NOTES:
1. PLACE 18" LONG #4 REBAR AT THE FOUR CORNERS OF THE DRAINFIELD.
2. DISTRIBUTION LINE SHALL BE SLOPED AT 0.005 FEET PER FOOT.
3. HOLE SPACING SHALL EVENLY SPACED ALONG TOW ROWS RUNNING THE LENGTH OF THE LINE, ON EACH SIDE, MIDWAY BETWEEN THE INVERT AND CENTER-LINE WHICH SEPARATES THE UPPER AND LOWER HALVES OF THE PIPE.
4. TRANSITION CONNECTIONS OF SEWER MATERIALS SHALL BE MADE BY ADAPTER FITTINGS OR ONE-PIECE MOLDED
RUBBER COUPLINGS WITH APPROPRIATE BUSHINGS FOR THE RESPECTIVE MATERIALS. ALL FITTINGS MUST BE AT
LEAST OF EQUIVALENT DURABILITY AND STRENGTH OF THE PIPE ITSELF.
5. ALL INFILL SHALL BE PER MASSDEP 310 CMR 15.255.
12" TO 36"
3:1 MAXIMUM
SLOPE
2" SCH 40 PVC TRANSPORT LINE
EFFLUENT DISCHARGE
TO DRAINFIELD
4" DISTRIBUTION LATERAL4" ENDCAP
FINISH GROUND
3'
37.6'
3'
FLOW FROM SEPTIC TANK
DOWNSLOPE
DIRECTION
2" SCH. 40 PVC
INSPECTION TUBE WITH THREADED
CAP, INSTALL WITHIN 3" OF FINISH
GROUND
BACKFILL
ESTABLISH NATIVE VEGETATIVE
COVER WITH SEED OR SOD
3:1 OR FLATTER SLOPE, MAINTAIN POSITIVE
DRAINAGE FROM CENTER OF DRAIN FIELD
TRENCHING AND RECHARGER
180 HD NOT SHOWN
CULTEC NO. 410 FILTER FABRIC,
FABRIC ROLL WIDTH = 5' UNDISTURBED GROUND
INSPECTION TUBE WITH THREADED
CAP, INSTALL WITHIN 3" OF FINISH
GROUND
DESIGNED:
TECH. REVIEW:
DATE:
SUB SHEET NO. TITLE OF SHEET DRAWING NO.
PKG.
NO. SHEET
OF 10
A/E FIRM
PRIME/CIVIL:
GREAT WEST ENGINEERING
HELENA, MT
ENVIRONMENTAL/GEOTECHNICAL:
SCHOFIELD FREEMAN, INC
ORLEANS, MA
SURVEY:
OUTERMOST LAND SURVEY, INC
BREWSTER, MA
W
S
P
T
R
T
O
EA
R
E
F
L
E
S
O
T
N
U
N
H
A
H
E
O
L
C O
M M
ON
CASSAMF
ENIGESSI
COLLETTE ANDERSON
CIVIL
NO. 59770
TIS EERG
RE D
LH
FA
5/28/2025
C4
CAPE COD NATIONAL SEASHORE
DELFINO AND EGGLESTON WASTEWATER
SEPTIC DETAILS --
SOIL ABSORPTION SYSTEM TRENCHING DETAIL1
C4
TYPICAL DRAINFIELD PLAN VIEW
NOT TO SCALE
DISTRIBUTION PIPE SECTION VIEW
NOT TO SCALE
SECTION VIEW AA
NOT TO SCALE
A A
GENERAL ELECTRICAL NOTES
1. REFER TO ELECTRICAL SPECIFICATIONS FOR FURTHER
DETAIL AS TO SCOPE, MATERIALS, AND EXECUTION OF
ELECTRICAL WORK.
2. ALL MEDIUM VOLTAGE WIRING DESIGN IS BASED ON 90°
CELSIUS CONDITIONS FOR COPPER CONDUCTORS. ALL LOW
VOLTAGE WIRING DESIGN IS BASED ON 75° CELSIUS
CONDITIONS FOR COPPER CONDUCTORS OF TYPE
THHN/THWN UNLESS OTHERWISE STATED.
3. ELECTRICAL CONTRACTOR TO SIZE ALL WIRING NOT
EXPLICITLY SHOWN ON DRAWINGS ACCORDING TO THE
REQUIREMENTS OF NATIONAL ELECTRICAL CODE (NEC) FOR
THE SPECIFIC APPLICATION AND CONDITIONS.
4. ALL CONDUCTORS SHALL BE COPPER (MINIMUM SIZE #12
AWG UNLESS SPECIFICALLY NOTED OTHERWISE).
5. THE ELECTRICAL CONTRACTOR SHALL CONFORM WITH ALL
LOCAL CODES AND ORDINANCES, THE NATIONAL
ELECTRICAL CODE, AND ANY ADDITIONAL JURISDICTIONS
RELATING TO THE WORK.
6. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND
INSTALL ALL CONDUIT, WIRE, SERVICES, SWITCHBOARDS,
AND VARIABLE FREQUENCY DRIVE'S REQUIRED FOR A
COMPLETE AND OPERATIONAL ELECTRICAL SYSTEM.
7. IN THE EVENT OF A CONFLICT OR INCONSISTENCY BETWEEN
ITEMS INDICATED ON THE PLANS AND/OR SPECIFICATIONS,
OR WITH CODE REQUIREMENTS, THE NOTE, SPECIFICATION
OR CODE WHICH PRESCRIBES AND ESTABLISHES THE MORE
COMPLETE JOB OR HIGHER STANDARD SHALL PREVAIL.
8. ALL ELECTRICAL EQUIPMENT EXPOSED TO THE CLIMATE
SHALL BE WEATHERPROOF.
9. ALL ELECTRICAL EQUIPMENT IN THIS PROJECT SHALL BE U.L.
LISTED.
10. ALL UNDERGROUND CONDUIT SHALL BE INSTALLED AT 36"
BELOW FINISHED GRADE MINIMUM UNLESS OTHERWISE
NOTED.
11. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE
FOR LOCATING EXISTING UNDERGROUND FACILITIES AND
PROTECTING THESE FACILITIES FROM DAMAGE.
12. THE ELECTRICAL CONTRACTOR SHALL ROUTE CONDUITS AS
REQUIRED BY FIELD CONDITIONS AND PER N.E.C.
13. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE
FOR REPAIRING ANY DAMAGE TO EXISTING UNDERGROUND
FACILITIES.
14. CONTRACTOR SHALL PROVIDE ALL NEEDED CHANNELS,
ANGLES, AND ANY OTHER MATERIALS REQUIRED TO
SUPPORT LUMINAIRES, CONDUIT, AND ELECTRICAL
EQUIPMENT IN THE LOCATIONS SHOWN ON THE DRAWINGS.
15. CONTRACTOR SHALL NOT CUT ANY STRUCTURAL MEMBERS
OR USE ANY ATTACHMENTS THAT WOULD IMPAIR THEIR
STRENGTH.
16. CONTRACTOR SHALL DESIGN SUPPORTS IN BETWEEN THE
STRUCTURAL SUPPORT MEMBERS AND SUBMIT THE DESIGN
AS A SHOP DRAWING SUBMITTAL.
17. INSTRUMENTATION IS SHOWN IN THE GENERAL VICINITY OF
THE INTENDED LOCATION AND MAY NOT NECESSARILY
MATCH LOCATIONS ON THE PLANS. VERIFY ACTUAL
LOCATIONS OF INSTRUMENTS AND RUN ASSOCIATED
CONDUITS AS REQUIRED.
18. ALL EXPOSED CONDUITS TO BE GALVANIZED RIGID STEEL
CONDUIT FOR DRY LOCATIONS AND PVC COATED
GALVANIZED RIGID STEEL CONDUIT IN WET LOCATION
UNLESS OTHERWISE STATED ON THE PLANS.
ELECTRICAL ABBREVIATIONS
(D) DEMOLISH
(E) EXISTING
(F) FUTURE
(N) NEW
(R) RELOCATE
A AMPERES, ANALOG SIGNAL
AC ALTERNATING CURRENT
AF AMPERES FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPERES INTERRUPTING CAPACITY
AT AMPERES TRIP
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BFG BELOW FINISHED GRADE
C CONDUIT
CB CIRCUIT BREAKER
CCT CORRELATED COLOR TEMPERATURE
CO CONDUIT ONLY
CP CONTROL PANEL
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CU COPPER
DC DIRECT CURRENT
DSB DISTRIBUTION SWITCHBOARD
EF EXHAUST FAN
ELEV ELEVATION
ETM ELAPSED TIME METER
FCB FEEDER CIRCUIT BREAKER
FIT FLOW INDICATING TRANSMITTER
FLEX FLEXIBLE
FLUOR FLUORESCENT
FPP FIBER OPTIC PATCH PANEL
FPR FEEDER PROTECTION RELAY
FVNR FULL VOLTAGE NON-REVERSING STARTER
G, GND GROUND
GFCI GROUND FAULT CIRCUIT INTERRUPTER
H HALOGEN
HH HANDHOLE
HID HIGH INTENSITY DISCHARGE
HMI HUMAN MACHINE INTERFACE
HOA HAND / OFF / AUTOMATIC
HP HORSEPOWER
HPS HIGH PRESSURE SODIUM
HS HAND SWITCH
INCAND INCANDESCENT
JB, JBOX JUNCTION BOX
KAIC KILOAMPERES INTERRUPTING CAPACITY
KVA KILOVOLT-AMPERE
KW KILOWATT
KWH KILOWATT-HOUR
LED LIGHT EMITTING DIODE
LCP LOCAL CONTROL PANEL
LIT LEVEL INDICATING TRANSMITTER
LOS LOCKOUT STOP SWITCH
LSH LEVEL SWITCH HIGH
LSLL LEVEL SWITCH LOW-LOW
LV LOW VOLTAGE
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCCB MOLDED CASE CIRCUIT BREAKER
MCP MOTOR CIRCUIT PROTECTOR
MH METAL HALIDE, MANHOLE
MIN MINIMUM
MLO MAIN LUG ONLY
MPC MINI POWER CENTER
MPR MOTOR PROTECTION RELAY
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NO. NUMBER
NTS NOT TO SCALE
P POLE
PB PUSHBUTTON, PULLBOX
PCS PVC COATED STEEL
PCV PRESSURE CONTROL VALVE
PDIT PRESSURE DIFFERENTIAL INDICATING TRANSMITTER
PE PHOTOELECTRIC
PFR PHASE FAILURE RELAY
PH PHASE
PIT PRESSURE INDICATING TRANSMITTER
PLC PROGRAMMABLE LOGIC CONTROLLER
PQM POWER QUALITY MONITOR
PSH PRESSURE SWITCH HIGH
PT POTENTIAL TRANSFORMER
PTC POSITIVE TEMPERATURE COEFFICIENT RESISTOR
REC, RECEPT RECEPTACLE
RIO REMOTE I/O
RGS RIGID GALVANIZED STEEL
SCCR SHORT CIRCUIT CURRENT RATING
SCE SOUTHERN CALIFORNIA EDISON
SPD SURGE PROTECTION DEVICE
SSS SOLID STATE STARTER (SOFT STARTER)
STA STATION
SWBD SWITCHBOARD
TEMP TEMPERATURE
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
V VOLT(S)
VA VOLT-AMPERE
VCP VENDOR CONTROL PANEL
VFD VARIABLE FREQUENCY DRIVE
W WATT, WIRE
WP WEATHERPROOF
XFMR TRANSFORMER
SYMBOL NOTES
1. THIS DRAWING CONTAINS INDUSTRY STANDARD SYMBOLS. NOT ALL SYMBOLS
SHOWN ARE USED ON THIS PROJECT.
2. FOR HOA SWITCHES, "XOO" INDICATES THAT THE TOP CONTACT IS CLOSED WHEN
THE SWITCH IS SET TO HAND MODE, AND ALL OTHER SWITCH CONTACTS ARE OPEN;
"OXO" INDICATES THAT THE MIDDLE CONTACT IS CLOSED WHEN THE SWITCH IS SET
TO OFF MODE, AND ALL OTHER SWITCH CONTACTS ARE OPEN; "OOX" INDICATES
THAT THE BOTTOM CONTACT IS CLOSED WHEN SWITCH IS IN AUTOMATIC MODE, ALL
OTHER SWITCH CONTACTS ARE OPEN.
ANSI/IEEE C37.2 STANDARD DEVICE NUMBERS
THE FOLLOWING IS A LIST OF TYPICAL DEVICE NUMBERS. SEE ANSI/IEEE C37.2 FOR A
COMPLETE LIST OF DEVICES.
11 MULTI-FUNCTION DEVICE
27 UNDERVOLTAGE RELAY
32 DIRECTIONAL POWER RELAY OR REVERSE POWER RELAY
37 UNDERCURRENT OR UNDERPOWER RELAY
42 RUNNING CIRCUIT BREAKER
47 PHASE SEQUENCE OR PHASE-BALANCE VOLTAGE RELAY
50 INSTANTANEOUS OVERCURRENT RELAY
51 AC INVERSE TIME OVERCURRENT RELAY
52 AC CIRCUIT BREAKER
55 POWER FACTOR RELAY
57 SHORT-CIRCUITING OR GROUNDING DEVICE
59 OVERVOLTAGE RELAY
67 AC DIRECTIONAL OVERCURRENT RELAY
86 LOCKOUT RELAY
87 DIFFERENTIAL PROTECTIVE RELAY
SYMBOL DESCRIPTION
ELECTRICAL SYMBOLS - SCHEMATIC DIAGRAMS
O/L
CONTACT
TIMED CONTACT, CONTACT ACTION REVERSES ON
ENERGIZATION (ON DELAY)
TIMED CONTACT, CONTACT ACTION REVERSES ON
DE-ENERGIZATION (OFF DELAY)
PUSH BUTTON SINGLE CIRCUIT MOMENTARY CONTACT
LIMIT SWITCH
SELECTOR SWITCH
HOA: HAND-OFF-AUTO (HOA SHOWN IN HAND MODE)
HO: HAND-OFF
HOR: HAND-OFF-REMOTE
R-O: REMOTE-OFF
SEE SYMBOLE NOTE 2.
MOTOR OVERLOAD DEVICE CONTACTS
PILOT LIGHT
A= AMBER, G= GREEN, R= RED, W= WHITE
CONTROL RELAY
TIME DELAY RELAY
MOTOR OR STARTER COIL
SOLENOID OPERATED VALVE
ELAPSED TIME METER
FUSE
CONTROL POWER TRANSFORMER
GROUND
MOTOR SPACE HEATER
AUTOHAND
OFF
OOX
NORMALLY
OPEN
NORMALLY
CLOSED
LEVEL SWITCH
PRESSURE SWITCH
TEMPERATURE SWITCH
OXO
XOO
FLOW SWITCH
CONDUIT & WIRE FOR FIRE ALARM SYSTEMF F
SYMBOL
A-3
SYMBOL DESCRIPTION
ELECTRICAL SYMBOLS - PLANS
DISCONNECT SWITCH
PANELBOARD
FLEXIBLE CONDUIT CONNECTION
(FROM COUPLING/STUB-UP OR JBOX)
CONDUIT BENDS AWAY FROM OBSERVER
CONDUIT BENDS TOWARD OBSERVER
HOMERUN TO PANEL "A", CIRCUIT 3
GROUNDING CONDUCTOR 30" BELOW GRADE
CONDUIT OR DUCT BANK IN SLAB OR UNDERGROUND
CONDUIT REFERENCE
A = ANALOG SIGNAL C = CONTROL
D = DATA LINK F = FIBER OPTIC
P = POWER T = TELEPHONE
LIGHTING LUMINAIRE CONTROLLED BY SWITCH a
JUNCTION BOX
DUPLEX RECEPTACLE (WP, GFCI AS INDICATED)
HANDHOLE OR PULL BOX
EXIT LIGHT
SMOKE DETECTOR
FIRE ALARM MANUAL PULL STATION
FIRE ALARM STROBE
POLE MOUNTED LUMINAIRE
TELEPHONE OUTLET
CONDUIT SEAL
F
DUCT SMOKE DETECTOR
CONDUIT & WIRE FOR ELECTRONIC KEY PAD TO PLCR RR
FACP FIRE ALARM CONTROL PANEL
SWITCH (3 = 3-WAY SWITCH, 4 = 4-WAY SWITCH, ETC.)
KP ELECTRONIC KEYPAD
F
DS
J
S3 a
P001
GND GND
J
F
A
LUMINAIRE REFERENCE
SEE LUMINAIRE SCHEDULE FOR DETAILS
LUMINAIRE TYPE
LAMP WATTAGE
EXPOSED CONDUIT
WALL MOUNTED LUMINAIRE
CONDUIT STUBBED AND CAPPED
LOCAL CONTROL SWITCH
THERMOSTATT
SYMBOL DESCRIPTIONDEVICE
ELECTRICAL SYMBOLS - SINGLE LINE DIAGRAM
SOLID STATE STARTER (SOFT STARTER)
FUSED DISCONNECT SWITCH WITH CURRENT LIMITING FUSES
VARIABLE FREQUENCY DRIVE
MOTOR OVERLOAD HEATER
DRY TYPE TRANSFORMER
POTENTIAL TRANSFORMER
CURRENT TRANSFORMER
FUSE
LOW VOLTAGE CIRCUIT BREAKER
MCCB UNLESS OTHERWISE NOTED
MOTOR, 40 HORSEPOWER
GROUNDING ELECTRODE
NON-FUSED DISCONNECT SWITCH, 30A/3P UON
VALVE MOTOR AND ACTUATOR
MAGNETIC MOTOR STARTER
FVNR1 = FULL VOLTAGE NON-REVERSING, NEMA SIZE 1
RV2S2W = REDUCED VOLTAGE 2-SPEED, 2-WINDING
FUSED DISCONNECT SWITCH, 30A/3P UON
FVNR1
M METER, ELECTRIC UTILITY GRADE UON
IRON CORE TRANSFORMER
PROTECTION RELAY
SEE ANSI/IEEE C37.2 STANDARD DEVICE NUMBERS LIST
MEDIUM VOLTAGE CIRCUIT BREAKER, DRAW-OUT TYPE
SEE ANSI/IEEE C37.2 STANDARD DEVICE NUMBERS LIST
THIS SHEET
SSS
VFD
TD1
CR1 AR1
R
ETM
M
SURGE PROTECTION DEVICESPD
POWER QUALITY MONITORPQM
SOLID STATE TRIPSST
LIGHTING LUMINAIRE CONTROLLED BY SWITCH a W/ EMERGENCY BATTERY PACKa
EMERGENCY LIGHT
INTRUSION SWITCHIS
MOTOR (NUMBER INDICATES HORSEPOWER)
COMBINATION STARTER & DISCONNECT SWITCH
MOTOR PROTECTION RELAYMPR
QUAD RECEPTACLE (WP, GFCI AS INDICATED)
THERMISTOR
WALL MOUNTED OCCUPANCY SENSOR
CEILING MOUNTED OCCUPANCY SENSOR
M
M
ELECTRIC VEHICLE CHARGER
WALL MOUNTED DIMMERD
+t°
600AF
400AT
GROUND WELL
DATA OUTLET
VOICE/DATA OUTLET
LIGHTNING AND SURGE ARRESTOR
DESIGNED:
TECH. REVIEW:
DATE:
SUB SHEET NO. TITLE OF SHEET DRAWING NO.
PKG.
NO. SHEET
OF 10
A/E FIRM
PRIME/CIVIL:
GREAT WEST ENGINEERING
HELENA, MT
ENVIRONMENTAL/GEOTECHNICAL:
SCHOFIELD FREEMAN, INC
ORLEANS, MA
SURVEY:
OUTERMOST LAND SURVEY, INC
BREWSTER, MA
W.T. MOORE
D. PHAN
W.T. MOORE
07/01/2025 CAPE COD NATIONAL SEASHORE
DELFINO AND EGGLESTON WASTEWATER
E0 SYMBOLS AND ABBREVIATIONS
ELECTRICAL LEGEND, --
duan.phan Image
O H
P O
H P
O H
P O
H P
O H
P
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
SS
SS
SS
SS
1 0.5 0 20 40
SCALE OF FEET
DESIGNED:
TECH. REVIEW:
DATE:
SUB SHEET NO. TITLE OF SHEET DRAWING NO.
PKG.
NO. SHEET
OF 10
A/E FIRM
PRIME/CIVIL:
GREAT WEST ENGINEERING
HELENA, MT
ENVIRONMENTAL/GEOTECHNICAL:
SCHOFIELD FREEMAN, INC
ORLEANS, MA
SURVEY:
OUTERMOST LAND SURVEY, INC
BREWSTER, MA
W.T. MOORE
D. PHAN
W.T. MOORE
07/01/2025 CAPE COD NATIONAL SEASHORE
DELFINO AND EGGLESTON WASTEWATER
E1 ELECTRICAL DESIGN
DELFINO --
DELFINO ELECTRICAL PLAN
880 CABLE RD
CABLE ROAD
SEPTIC TANK/NITRATE
TREATMENT SYSTEM,
SEE C1
SOIL ABSORPTION
SYSTEM, SEE C1
ABANDON EXISTING
CESSPOOL, SEE C1
PORCH
EXISTING SEPTIC
TANK
EXISTING SOIL
ABSORPTION SYSTEM
0 OCEANVIEW DR
TOWN OF EASTHAM
(VACANT)
BLOCK 6
UNITED STATES OF
AMERICAN
EXISTING WELL,
SEE C1
EXISTING WELL
EXISTING WELLDIRT DRIVEWAY
ATLAN
TIC
O C
EAN
O C
EAN
VIEW
D R
IVE
CABLE ROAD
LOCUS
NAUSET LIGHT
BEACH ROAD
LOCUS MAP
EXISTING SEPTIC
TANK
TH #1
TH #2
860 CABLE ROAD
ADNER FAMILY
HOLDING TRUST
900 CABLE RD
CHRIS PARTICELLI TRUST
EXISTING ELECTRIC
PANEL, 240/120V, 1ɸ
(NOTE 2)
EXISTING
ELECTRIC
METER
EXISTING
ELECTRIC
UTILITY POLE
SEPTIC SYSTEM
CONTROL PANEL
(NOTE 1)
2- #10, 1- #10G, 1"C 6- #14, 1- #14G, 1"C
HAND HOLE,
18"x 12"
NOTES:
1. INSTALL SEPTIC SYSTEM CONTROL PANEL WITHIN SIGHT
OF THE TANK, AND ON A POST APART FROM EXTERIOR
WALL TO AVOID MOTOR CONTACTOR DISRUPTIVE SOUND
WHEN ENGAGING AND DISENGAGING.
2. INSTALL NEW CIRCUIT BREAKER AND FEEDER TO SERVE
SEPTIC TANK/NITRATE TREATMENT SYSTEM. IF POWER
DISCONNECT IS REQUIRED TO INSTALL NEW CIRCUIT
BREAKER, SUBMIT A DISCONNECT REQUEST WITH
EVERSOURCE. CUSTOMER SERVICE LINE IS (800) 286-2828.
CONTRACTOR IS RESPONSIBLE FOR ALL FEES.
RECONNECT POWER THE SAME DAY.
2- #10, 1- #10G, 1"C
Well
Septic System per as-built
SSSS SS SS SS
1 0.5 0 20 40
SCALE OF FEET
DESIGNED:
TECH. REVIEW:
DATE:
SUB SHEET NO. TITLE OF SHEET DRAWING NO.
PKG.
NO. SHEET
OF 10
A/E FIRM
PRIME/CIVIL:
GREAT WEST ENGINEERING
HELENA, MT
ENVIRONMENTAL/GEOTECHNICAL:
SCHOFIELD FREEMAN, INC
ORLEANS, MA
SURVEY:
OUTERMOST LAND SURVEY, INC
BREWSTER, MA
W.T. MOORE
D. PHAN
W.T. MOORE
07/01/2025 CAPE COD NATIONAL SEASHORE
DELFINO AND EGGLESTON WASTEWATER
E2 ELECTRICAL DESIGN
EGGLESTON --
EGGLESTON ELECTRICAL PLAN
NELLIE ROAD
SEPTIC TANK/NITRATE
TREATMENT SYSTEM,
SEE C2
SOIL ABSORPTION
SYSTEM, SEE C2
PORCH
EXISTING SOIL
ABSORPTION SYSTEM
NHESP LINE
LOCUS MAPEXISTING SEPTIC
TANK
RTE. 6
LECOUNT
HOLLOW
RD.
NELLIE RD.
WILSON AVE.
O C
EAN
VIEW
D R
LOCUS
ATLAN
TIC
O C
EAN
WILSON AVENUE
GRAVEL DRIVEWAY
EXISTING SEPTIC
TANK
EXISTING WELL
EXISTING WELL
310 NELLIE RD
340 WILSON AVE
SANDRA T. SOTOLOTTO
325 NELLIE RD
CAPE COD NATIONAL
SEASHORE
319 NELLIE RD
KENNETH MAREK
320 NELLIE RD
TH #2
TH #1
TH #3
EXISTING
ELECTRIC
METER
EXISTING ELECTRIC
PANEL, 240/120V, 1ɸ
(NOTE 2)
GRAVEL DRIVEWAY
SEPTIC SYSTEM
CONTROL PANEL
(NOTE 1)
2- #10, 1- #10G, 1"C 6- #14, 1- #14G, 1"C
EXISTING
CESSPOOL,
SEE C2
2- #10, 1- #10G, 1"C
NOTES:
1. INSTALL SEPTIC SYSTEM CONTROL PANEL WITHIN SIGHT
OF THE TANK, AND ON A POST APART FROM EXTERIOR
WALL TO AVOID MOTOR CONTACTOR DISRUPTIVE SOUND
WHEN ENGAGING AND DISENGAGING.
2. INSTALL NEW CIRCUIT BREAKER AND FEEDER TO SERVE
SEPTIC TANK/NITRATE TREATMENT SYSTEM. IF POWER
DISCONNECT IS REQUIRED TO INSTALL NEW CIRCUIT
BREAKER, SUBMIT A DISCONNECT REQUEST WITH
EVERSOURCE. CUSTOMER SERVICE LINE IS (800) 286-2828.
CONTRACTOR IS RESPONSIBLE FOR ALL FEES.
RECONNECT POWER THE SAME DAY.
1. INSTALL NEW CIRCUIT BREAKER. IF POWER DISCONNECT
IS REQUIRED TO INSTALL NEW CIRCUIT BREAKER, SUBMIT
A DISCONNECT REQUEST WITH EVERSOURCE. CUSTOMER
SERVICE LINE IS (800) 286-2828. CONTRACTOR IS
RESPONSIBLE FOR ALL FEES. RECONNECT POWER THE
SAME DAY.
NOTES:
DESIGNED:
TECH. REVIEW:
DATE:
SUB SHEET NO. TITLE OF SHEET DRAWING NO.
PKG.
NO. SHEET
OF 10
A/E FIRM
PRIME/CIVIL:
GREAT WEST ENGINEERING
HELENA, MT
ENVIRONMENTAL/GEOTECHNICAL:
SCHOFIELD FREEMAN, INC
ORLEANS, MA
SURVEY:
OUTERMOST LAND SURVEY, INC
BREWSTER, MA
W.T. MOORE
D. PHAN
W.T. MOORE
07/01/2025 CAPE COD NATIONAL SEASHORE
DELFINO AND EGGLESTON WASTEWATER
E3 SCHEDULES
ELECTRICAL --
(NOTE 1) (NOTE 1)
DELFINO PANELBOARD (EXISTING) EGGLESTON PANELBOARD (EXISTING)
| Sheets and Views |
| G1 COVER |