This document is a Technical Inspection Report (Rapporto di Prova dell'Ispezione Tecnica) for an HVAC system inspection, written in Italian and English. The form is designed to comprehensively assess the hygienic and operational conditions of an air handling unit (AHU) and its associated ductwork. Key inspection areas include microbiological monitoring of dust, verification of plant component conditions, air flow measurements before and after filter systems, and workplace environment assessments.
The report provides detailed checkboxes and measurement spaces for evaluating critical parameters such as particulate deposit levels, mold growth, sediment presence, filter pressure drop, air flow rates, and microclimatic conditions (temperature, relative humidity, air velocity). It also includes sections for measuring bacterial and fungal loads in dust samples, with specified contamination limits of 30,000 UFC/g for bacteria and 15,000 UFC/g for fungi. The form emphasizes potential health risks from bacteria and fungi transported through air conditioning systems, highlighting the importance of thorough HVAC system inspections for worker health and safety.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ALLEGATO 6/Enclosure 6 - Rapporto di Prova dell'Ispezione Tecnica/Technical Inspection Report
DATE/DATE: _________________ TECNICO/TECHNICIAN: ________________________________ EDIFICIO/BLDG: ____________________________________
IDENTIFICAZIONE IMPIANTO/PLANT IDENTIFICATION (Identificare le componenti ispezionate e l'ubicazione/Identify the plant component inspected and their location)
LIMITI SITO ISPEZIONATO*
PARTICOLATO DEPOSITATO NELLE CONDOTTE 1 g/m2
CRESCITA DI MUFFE ASSENTE
CIRCOSRITTA E
MODERATA
ESTESA
E/O
DIFFUSA
ASSENTE
SEDIMENTI, DETRITI, RESTI DI ORIGINE ANIMALE ASSENTI PRESENTI - ASSENTI
CADUTA DI CARICO
NOMINALE DEI
FILTRI PULITI
CADUTA DI
CARICO RILEVATA
CON
MANOMETRO
DIFFERENZIALE
IL FILTRO
E'
ESAUSTO?
SI/NO
TEMPO PREVISTO DI ESAURIMENTO DEL FILTRO -
SITO/I ANOMALIA
VERIFICA DELLA PRESENZA DI SORGENTI CONTAMINATI INTERNE
L'uso di tutti gli ambienti climatizzati corrisponde a quanto previsto da progetto di impianto?
PORTATA DELL'ARIA AI TERMINALI DI MANDATA
La misura, a campione, della portata dell'aria ai terminali di mandata d'immissione corrisponde a quella prevista da progetto di impianto?
PARAMETRI MICROCLIMATICI (T, UR, V)*
I parametri microclimatici rientrano nei valori previsti per gli ambienti monitorati?
CARICA BATTERICA
UFC/g POLVERE
LIMITE DI
CONTAMINAZION
E BATTERICA
30.000 UFC/g
CARICA FUNGINA
UFC/g POLVERE
LIMITE DI
CONTAMINAZION
E FUNGINA
15.000 UFC/g
I BATTERI E I FUNGHI PRESENTI NELLE DIVERSE COMPONENTI
DELL'IMPIANTO POSSONO ESSERE TRASPORTATI DAL FLUSSO
D'ARIA NEGLI AMBIENTI CLIMATIZZATI E RAPPRESENTARE UN
RISCHIO PER LA SALUTE DEI LAVORATORI
VERIFICA DELLE CONDIZIONI IGIENICHE (CONDOTTE, UTA, SERRANDE) / VERIFY THE HYGIENIC CONDITIONS (DUCTS, AHU, SHUTTER)
*Specificare il sito ispezionato e la sua ubicazione nell'edificio
_________________________ g/m2
MISURAZIONE DELLA PORTATA DELL'ARIA A MONTE E A VALLE DEI CORPI FILTRANTI / AIR FLOW MEASUREMENT BEFORE AND AFTER THE FILTERS
LA DIFFERENZA DI PRESSIONE DELL'ARIA RILEVATA PRIMA E
DOPO I CORPI FILTRANTI DELL'UTA E' INDICATIVA DELL'ENTITA'
DELL'INTASAMENTO DEI FILTRI DERIVANTE DALLA PRESENZA DI
POLVERE E SPORCIZIA
NOTE
NOTE
NOSI
VERIFICHE NEGLI AMBIENTI DI LAVORO / INSPECTIONS AT WORK SITES
MONITORAGGIO MICROBIOLOGICO DELL'IMPIANTO: POLVERE / MICROBIOLOGICAL MONITORING OF THE PLANT: DUST
IN CASO DI RISPOSTA NEGATIVA
*T: Temperatura, UR: Umidita' Relativa, V: Velocita' dell'Aria