B08_Attachment_3_100CD_USGS_OAG_A3_CERC-Drawings.pdf
PDF 8 MB Posted
- Attached to
- CERC A3 Main Building Stabilization Federal contract opportunity
- Solicitation number
- 140G0121R0030
About this file
This document package includes plans and specifications for the CERC A3 Main Building Stabilization project. The solicitation is being conducted by the Department of the Interior US Geological Survey Office of Acquisitions and Grants.
The project involves structural stabilization and facade repairs to an existing one-story masonry and steel research building located at the Columbia Environmental Research Center in Columbia, Missouri. Key work includes underpinning existing footings, installing new micropiles, replacing deteriorated concrete slabs, repointing and replacing brick facades, realigning and reanchoring windows, and repairing the roof system. Mechanical plans show replacement of underground ductwork serving existing VAV boxes. The documents provide demolition plans, new construction plans, wall sections and details, and specifications for mechanical, structural, and architectural scopes of work.
View the file
Other files for this federal contract opportunity
Show all 22
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
E. NEW HAVEN RD.
E. SUGAR GROVE RD.
USGS
FOUNDATION SEED DR.
FISH
LAKE
US HW
Y 63
U N
IV
E
R S
IT
Y
L N
PROJECT BUILDING
S
R O
LL
IN
G H
IL
LS
R D
UNITED STATES GEOLOGICAL SURVEY COLUMBIA ENVIRONMENTAL RESEARCH CENTER CAMPUS’S MAIN BUILDING (A3) LOCATED IN COLUMBIA, MISSOURI. THE ONE-STORY MASONRY AND STEEL BUILDING, BUILT CIRCA 1968, FEATURES A SLAB-ON-GRADE FLOOR WITH A PARTIAL BASEMENT. THE BUILDING CONSISTS OF A 34,019 SQUARE FOOT RESEARCH LABORATORY WITH A PARTIAL BASEMENT CONTAINING OFFICES, RESEARCH LABORATORY
ROOMS AND THE 6,500 SQUARE FOOT RESEARCH WET LABORATORY.
OVER TIME, ESPECIALLY IN THE LAST 10 – 15 YEARS, THE BUILDING HAS EXPERIENCED SEVERAL SIGNS OF POSSIBLE STRUCTURAL FATIGUE AND SLAB SETTLEMENT IN THE NORTHERN MOST CORNERS OF THE FIRST FLOOR
AND BASEMENT.
THE SCOPE OF WORK INCLUDES, BUT IS NOT LIMITED TO THE FOLLOWING:
SCOPE OF WORK IS LOCATED AT THE NORTH EAST CORNER OF THE BUILDING. STRUCTURAL PILES
WILL BE ADDED TO SHORE UP THE FOUNDATIONS UNDERGROUND ALONG THE LENGTH OF NORTH
AND EAST PERIMETER AT THE CORNER.
REMOVE HIGH PLASTIC CLAYS BENEATH THE SLABS, RE-PREPARE THE SUBGRADE SOIL BY MOISTURE
CONDITIONING AND COMPACT AND RECONSTRUCT SLAB. REPLACE BELOW-SLAB MECHANICAL AIR
DUCT SYSTEM.
REBUILD TOP SEVERAL COURSES OF LOAD-BEARING CMU AND BRICK MASONRY WALLS WHERE
MISALIGNED. RE-ANCHOR MASONRY WALL TO PRECAST CONCRETE ROOF PLANKS.
REMOVE, RE-ANCHOR AND REINSTALL EXISTING ALUMINUM AND GLASS WINDOWS.
REMOVE AND REPLACE SECTIONS OF FOAMED-IN-PLACE ROOFING SYSTEM AT PERIMETER OF THE
BUILDING. REPLACE METAL COPINGS AND FLASHING.
REPLACE INTERIOR PARTITIONS WITH NEW METAL STUD PARTITION WALLS.
REPLACE EXISTING INTERIOR LIGHTING, CONTROLS, POWER AND DATA, NEW INTERIOR FLOOR, WALL
AND CEILING.
REMOVE AND REPLACE PORTIONS OF EXISTING CONCRETE WALK AFFECTED BY THE WORK, RESTORE
SITE LAWN AREAS AFFECTED BY THE WORK.
CONCRETE
FOAMED-IN-PLACE ROOF
SYSTEM INSULATION
EXISTING TO REMAINEARTH
PRECAST CONCRETE
STEEL
AREA WORK NOTED
NOT IN SCOPE
GRAVEL
BRICK
CMU
ADJ
AFF
AP
APPROX
ARCH
B.O.
CJ
CL
CLG
COL
CONC
CONST
CONTR
CONT
CPT
CO
CT
DIA
DIM
DN
DTL
DWG
EA
EX
FLR
FOB
GL
HDWR
HORIZ
INFO
INSUL
INT
JT
LAM
LAV
ADJUSTABLE
ABOVE FINISHED FLOOR
ACCESS PANEL
APPROXIMATELY
ARCHITECTURAL
BOTTOM OF
CONTROL JOINT
CENTER LINE
CEILING
COLUMN
CONCRETE
CONSTRUCTION
CONTRACTOR
CONTINUOUS
CARPET
CLEAN OUT
CERAMIC TILE
DIAMETER
DIMENSION
DOWN
DETAIL
DRAWING
EACH
EXISTING
FLOOR
FACE OF BRICK
GLASS
HARDWARE
HORIZONTAL
INFORMATION
INSULATION
INTERIOR
JOINT
LAMINATED
LAVATORY
MATL
MAX
MECH
MFR
MIN
MTD
MTL
NIC
NTS
OC
OPNG
PLAM
PR
PTD
REQ'D
REV
RM
RO
SECT
SHT
SIM
SPEC
SQ
SS
STD
STL
T.O.
TYP
U.N.O.
VERT
VIF
W/
W/O
WCO
WD
MATERIAL
MAXIMUM
MECHANICAL
MANUFACTURER
MINIMUM
MOUNTED
METAL
NOT IN CONTRACT
NOT TO SCALE
ON CENTER
OPENING
PLASTIC LAMINATE
PAIR
PAINTED FINISH
REQUIRED
REVISION
ROOM
ROUGH OPENING
SECTION
SHEET
SIMILAR
SPECIFICATION
SQUARE
STAINLESS STEEL
STANDARD
STEEL
TOP OF
TYPICAL
UNLESS NOTED
OTHERWISE
VERTICAL
VERIFY IN FIELD
WITH
WITHOUT
WALL CLEANOUT
WOOD
A101
SIM
Name
Elevation101
A101
SIM
1i
1t
CALL OUT
TAG
DOOR TAG
SECTION CUT
TAG
LEVEL MARKER
WALL TYPE TAG
WINDOW TAG
A101
SIM
INTERIOR
ELEVATION TAG
EXTERIOR
ELEVATION TAG
A101
NORTH
ARROW
CENTERLINE
Room name
ROOM TAG
(Name, Number, Square Footage)
B
GRID LINE, GRID
BUBBLE
00 NOTE
DRAWING
KEYNOTE
DEMO WALL NEW WALL
3 1/2" SOUND ATTENUATED
BATT INSULATION. RUN TO
STRUCTURE ABOVE
MTL. STUDS AT 16" O.C.
NOTE: FRAME METAL STUDS
AROUND UTILITIES.
SCHEDULED BASE, BOTH SIDES
ACOUSTIC SEALANT, BOTH SIDES
SCHEDULED FLOOR
DEFLECTION TRACK
5/8" GYP BD
SCHEDULED CEILING
PENETRATIONS, V.I.F.
BASE
PLAN
HEAD
ACOUSTIC SEALANT, BOTH
SIDES
UL
STC
R-VALUE
WALL
TYPE
STUD
TYPE
STUD
GAUGE
WALL
WIDTH
NOTES
approx 50
P2a 3-5/8" 25 4-7/8"
TYPICAL METAL STUD INTERIOR PARTITION
WALL TO STRUCTURE
BE Project No.
Drawn By:
Drawing No.
Drawing Title t 312.440.2300 f 312.440.2303 www.baileyedward.com
35 East Wacker Dr Suite 2800 Chicago, IL 60601-2308
©2018 Bailey Edward Design Design Firm License No. 184-001962
Structural Engineer IMEG Corp.
15 Sunnen Dr. Suite 104 St. Louis, MO 63143 314-645-1132
SHEET
COVER SHEET
G100
USGS OAG A3 MAIN
BUILDING STABILIZATION
18018
KH
Columbia Environmental Research Center (CERC) 4200 E New Haven Rd.
Columbia, MO 65201
LOCATION MAP
Columbia Environmental Research Center (CERC) 4200 E New Haven Rd.
Columbia, MO 65201
USGS OAG A3 MAIN BUILDING STABILIZATION
EXISTING BUILDING SUMMARY
SCOPE OF WORK SUMMARY
HATCH PATTERN LEGEND ABBREVIATIONS
SYMBOLS LEGEND
ARCHITECTURAL
A100 08 OF 14 FLOOR PLANS - NEW AND SITE MAP
A600 09 OF 14 ENLARGED FLOOR PLANS AND ELEVATIONS- NEW
A700 10 OF 14 WALL SECTIONS & DETAILS
A701 11 OF 14 REFERENCE DWG - WINDOW SECTIONS AND DETAILS
A702 12 OF 14 REFERENCE DWG - TYPICAL EXTERIOR WALL SECTION
GENERAL
DRAWING NO. SHEET NO. DESCRIPTION
G100 01 OF 14 COVER SHEET
G101 02 OF 14 EXISTING CONDITION PHOTOS
DEMO ARCHITECTURAL
D100 07 OF 14 FLOOR PLANS AND ELEVATIONS - DEMO
STRUCTURAL
S0.0 03 OF 14 GENERAL NOTES
S1.0 04 OF 14 BASEMENT FLOOR PLAN
S1.1 05 OF 14 FIRST FLOOR PLAN
S2.0 06 OF 14 SECTION AND DETAILS
SHEET INDEX
MECHANICAL
M100 13 OF 14 MECHANICAL PLANS - DEMO
M101 14 OF 14 MECHANICAL PLANS - NEW
ROOM FINISH SCHEDULE
ROOM NAME & NO. FLOOR FINISH BASE FINISH WALL FINISH CEILING FINISH DOOR & FRAME COMMENTS
OFFICE 54 BY OWNER RB-01 PT-01 ACT-1 N/A
OFFICE 52 BY OWNER RB-01 PT-01 ACT-1 N/A
DIRECTOR'S OFFICE 51A BY OWNER RB-01 PT-01 ACT-1 PT-03 REINSTALL AND REFINISH DOOR AND FRAME TO OFFICE 51A
OFFICE 51B BY OWNER RB-01 PT-01 ACT-1 N/A
OFFICE 51C BY OWNER RB-01 PT-01 ACT-1 PT-03 REINSTALL AND REFINISH DOOR AND FRAME TO OFFICE 51C
CONFERENCE & LUNCH ROOM EXIST. EXIST. PT-02 ACT-1 N/A
ROOM FINISH DESCRIPTION SCHEDULE
MATERIAL TYPE /
CODE MATERIAL DESCRIPTION MATERIAL MANUFACTURER (BASIS OF DESIGN)
MANUFACTURER MODEL,
SIZE & COLOR MATERIAL REMARKS
ACT-1 ACOUSTICAL CEILING TILE ARMSTRONG CIRRUS 2X2 - WHITE CLIMAPLUS 15/16" T-BAR GRID WHITE
PT-01 LATEX PAINT LOW VOC SHERWIN-WILLIAMS MATCH EXISTING PAINT COLOR AND SHEEN TO MATCH OFFICE ROOM # 51A
PT-02 LATEX PAINT LOW VOC SHERWIN-WILLIAMS MATCH EXISTING PAINT COLOR AND SHEEN TO MATCH OFFICE ROOM # 51A
PT-03 LATEX PAINT LOW VOC SHERWIN-WILLIAMS MATCH EXISTING PAINT COLOR AND SHEEN TO MATCH OFFICE ROOM # 51A
RB-01 RUBBER BASE JOHNSONITE/TARKETT 4" H COORDINATE INSTALLATION WITH FLOORING INSTALLATION
NOTES:
PAINT ALL WALL SURFACES WITHIN ROOMS TYPICAL AS SCHEDULED.
NOT TO SCALE
PARTITION WALL WITH STC RATING
REVISION
MARK DESCRIPTION DATE
3 ISSUE FOR 100% CD 06/18/2021
khard Stamp
CONNECT TO NEW BELOW
GRADE DUCTS BEYOND TO
THESE EXISTING VAV BOX
AND DUCTS, VIF, SEAL AND
REINSULATE AS REQUIRED
*OCCURS AT BASEMENT
LEVEL, SEE KEY PLAN
FOR GENERAL LOCATION
EXISTING VAV BOX AND
PIPING TO REMAIN
01.03
01.0401.0401.04
01.01
02.10
02.19
02.18
WINDOW BEHIND
ELEC. TO REMAIN.
1 2
5 6
AT ROOF
AT BASEMENT
N
02.06
02.08
02.11
02.10
01.01
SEE SHEET D100
02.19
02.18
02.17
02.06
02.11
02.10
01.01
02.08
SEE SHEET D100
02.17
02.06
01.01
02.08
02.10
02.11
01.03
SEE SHEET D100
02.18
02.19
02.10
02.11
01.03
02.07
SEE SHEET D100
02.06
01.03
02.06
02.11
02.08
SEE SHEET D100
02.05
02.10
02.05
02.10 02.09
SEE SHEET D100
01.03
02.06
02.11
02.10
02.08
SEE SHEET D100
01.01
02.06
02.11
02.08
02.10
01.01
SEE SHEET D100
02.19
02.18
02.06
02.11
02.08
02.10
SEE SHEET D100
02.06
02.11
02.10
01.01
02.06
02.07
SEE SHEET D100
01.03
SEE SHEET A700 FOR
DETAILED WINDOW
SECTION AT STEEL
ANGLE.
02.10
02.05
SEE SHEET D100
02.10
SEE SHEET A700 FOR
DETAILED WINDOW
SECTION AT STEEL
ANGLE.
02.05
02.10
02.05
02.10
BE Project No.
Drawn By:
Drawing No.
Drawing Title t 312.440.2300 f 312.440.2303 www.baileyedward.com
35 East Wacker Dr Suite 2800 Chicago, IL 60601-2308
©2018 Bailey Edward Design Design Firm License No. 184-001962
Structural Engineer IMEG Corp.
15 Sunnen Dr. Suite 104 St. Louis, MO 63143 314-645-1132
SHEET
EXISTING CONDITION
PHOTOS
G101
USGS OAG A3 MAIN
BUILDING STABILIZATION
18018
SA
Columbia Environmental Research Center (CERC) 4200 E New Haven Rd.
Columbia, MO 65201
NEW DUCT WORK
ELEC. CONDUIT AND BOX
KEY PLAN NORTH EXTERIOR
NORTH EXTERIOR- T-WALL
EAST EXTERIOR VIEW
EAST EXT. T-WALL AT DOOR
EAST ROOF
T-WALL COPING
INTERIOR OFFICE 52
INTERIOR OFFICE 54
EAST WALK AND ENTRY
3 NORTH EXTERIOR COPING
EAST EXTERIOR
COPING AT BRICK
PRECAST PILLAR
ROOF COPING
WINDOW HEAD DETAIL
WINDOW HEAD DETAIL
INTERIOR OFFICE 51A
INTERIOR OFFICE 51C
KEYNOTES - DEMO
01.01 EXTERIOR WALLS NEED TO BE PROTECTED DURING DEMOLITION AND
CONSTRUCTION, TYP.
01.03 WOOD TRELLIS TO BE REMOVED AND SALVAGED BY USGS PRIOR TO
DEMO.
01.04 ELECTRICAL CONDUIT AND BOXES, SECURITY CAMERAS AND OTHER
DEVICES TO BE REMAIN. ELECTRICAL SERVICES TO THE BUILDING
ARE NOT TO BE INTERRUPTED DURING DEMO.
02.05 DEMOLISH EXISTING CEILING GRID, ACT PANELS AND LIGHTS.
PROTECT, REINSTALL EXISTING SPRINKLERS AND CEILING DEVICES.
02.06 DEMOLISH EXISTING METAL GRAVEL STOP, FLASHING AND BLOCKING.
02.07 DEMOLISH FOAMED-IN-PLACE ROOFING SYSTEM COATING AND
INSLULATION TO EXIST DECK, VIF, ALONG GRAVEL.
02.08 DEMOLISH BRICK FACADE AND REPLACE WITH NEW BRICKS AND
BRICK TIES. NEW BRICKS ARE TO MATCH EXISTING IN SIZE, COLOR
AND TEXTURE, SEE ARCH. SECTION AND DETAIL SHEET FOR MORE
INFORMATION.
02.09 SAWCUT AND DEMOLISH EXISTING APPROX. 12'X 12' (VIF) CONCRETE
PADS ALONG DOORS.
02.10 REMOVE WINDOWS TO BE SALVAGED FOR REALIGNMENT IN FACADE.
02.11 REMOVE PRECAST PANELS ABOVE WINDOW TO BE SALVAGED FOR
REALIGNMENT IN FACADE.
02.17 EXISTING PRECAST PANEL BETWEEN WINDOWS TO REMAIN. PROTECT
PRECAST PANEL DURING REMOVAL AND REINSTALLATION OF
WINDOWS AND PRECAST ABOVE.
02.18 EXPOSED EXISTING CONCRETE FOUNDATION WALL TO REMAIN.
02.19 EXISTING SLOPED METAL SILL TO REMAIN. MATCH FINISH AS
REQUIRED.
REVISION
MARK DESCRIPTION DATE
3 ISSUE FOR 100% CD 06/18/2021
1. NEITHER THE PROFESSIONAL ACTIVITIES OF THE ENGINEER, NOR THE PRESENCE OF THE ENGINEER OR HIS
OR HER EMPLOYEES AND SUBCONSULTANTS AT THE CONSTRUCTION SITE, SHALL RELIEVE THE
CONTRACTOR AND ANY OTHER ENTITY OF THEIR OBLIGATIONS, DUTIES, AND RESPONSIBILITIES INCLUDING, BUT NOT LIMITED TO, CONSTRUCTION MEANS, METHODS, SEQUENCE, TECHNIQUES, OR PROCEDURES NECESSARY FOR PERFORMING, SUPERINTENDING, OR COORDINATING ALL PORTIONS OF THE WORK OF
CONSTRUCTION IN ACCORDANCE WITH THE CONTRACT DOCUMENTS AND ANY HEALTH OR SAFETY
PRECAUTIONS REQUIRED BY ANY REGULATORY AGENCIES. THE ENGINEER AND HIS OR HER PERSONNEL HAVE NO AUTHORITY TO EXERCISE ANY CONTROL OVER ANY CONSTRUCTION CONTRACTOR OR OTHER
ENTITY OR THEIR EMPLOYEES IN CONNECTION WITH THEIR WORK OR ANY HEALTH OR SAFETY
PRECAUTIONS. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE JOBSITE SAFETY. THE ENGINEER AND THE ENGINEER'S CONSULTANTS SHALL BE MADE ADDITIONAL INSUREDS UNDER THE CONTRACTOR'S
GENERAL LIABILITY INSURANCE POLICY.
2. STRUCTURAL DRAWINGS INCLUDE DESIGN REQUIREMENTS AND DIMENSIONS FOR STRUCTURAL INTEGRITY BUT DO NOT SHOW ALL DETAIL DIMENSIONS TO FIT INTRICATE ARCHITECTURAL AND MECHANICAL DETAILS.
CONTRACTOR SHALL SO CONSTRUCT THE WORK SO THAT IT WILL CONFORM TO THE CLEARANCES
REQUIRED BY ARCHITECTURAL, MECHANICAL AND ELECTRICAL DESIGN.
3. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED STRUCTURE.
UNLESS NOTED OTHERWISE, THEY DO NOT INDICATE THE MEANS OR METHODS OF CONSTRUCTION.
4. DETAILS AND NOTES ON THE STRUCTURAL DRAWINGS ARE INTENDED TO BE TYPICAL FOR SIMILAR
SITUATIONS ELSEWHERE.
5. ESTABLISH AND VERIFY ALL OPENINGS AND INSERTS FOR MECHANICAL, ELECTRICAL, AND PLUMBING WITH APPROPRIATE TRADE CONTRACTORS. OPENING SIZES AND LOCATIONS SHOWN FOR DUCTS, PIPES, INSERTS AND OTHER PENETRATIONS WHEN SHOWN ARE FOR GENERAL INFORMATION ONLY AND SHALL BE
VERIFIED PRIOR TO FORMING.
6. DIMENSIONS, NOTES, AND DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND
TYPICAL DETAILS.
7. WHERE NEW CONSTRUCTION INTERFACES WITH EXISTING CONDITIONS, FIELD VERIFY EXISTING
DIMENSIONS, MEMBER SIZES AND ELEVATIONS SHOWN ON THE DRAWINGS PRIOR TO STARTING
CONSTRUCTION. ALL DISCREPANCIES SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE
ARCHITECT.
8. REFER TO ARCHITECTURAL DRAWINGS FOR THE FOLLOWING:
A. SIZE AND LOCATION OF ALL DOOR AND WINDOW OPENINGS, UNLESS NOTED OTHERWISE.
B. SIZE AND LOCATIONS OF ALL INTERIOR AND EXTERIOR MASONRY WALLS.
C. SIZE AND LOCATION OF ALL CONCRETE CURBS, FLOOR DRAINS, SLOPES, DEPRESSED AREAS, CHANGES
IN LEVEL, CHAMFERS, GROOVES, INSERTS, ETC.
D. SIZE AND LOCATION OF ALL FLOOR AND ROOF OPENINGS UNLESS NOTED OTHERWISE.
E. FLOOR, WALL AND ROOF FINISHES.
F. STAIR FRAMING AND DETAILS. ALSO REFER TO STAIR MANUFACTURER'S APPROVED SHOP DRAWINGS.
G. DIMENSIONS NOT SHOWN ON STRUCTURAL DRAWINGS.
H. FIRE PROTECTION REQUIREMENTS.
9. BEFORE SUBMITTING A PROPOSAL FOR THIS WORK, EACH BIDDER SHALL VISIT THE PREMISES AND BECOME FULLY ACQUAINTED WITH THE EXISTING CONDITIONS, TEMPORARY CONSTRUCTION REQUIRED, QUANTITIES AND TYPES OF EQUIPMENT, ETC. THE BID SHALL INCLUDE ALL SUMS REQUIRED TO DO THE WORK WITHIN THE EXISTING CONDITIONS. DISRUPTION OF NORMAL ACTIVITIES IN THE WORK AREA SHALL
BE KEPT TO A MINIMUM.
10. SHOP DRAWINGS PREPARED BY SUPPLIERS, SUBCONTRACTORS, AND OTHERS SHALL BE REVIEWED AND COORDINATED PRIOR TO SUBMITTING TO THE ARCHITECT. EACH SHOP DRAWING SUBMITTED SHALL BE STAMPED, INITIALED AND DATED INDICATING REVIEW BY THE CONSTRUCTION MANAGER/GENERAL
CONTRACTOR.
11. SHOP DRAWINGS PREPARED BY THE SUBCONTRACTORS, SUPPLIERS, AND OTHERS SHALL BE REVIEWED BY THE ARCHITECT ONLY FOR GENERAL CONFORMANCE WITH DESIGN CONCEPT ONLY. REVIEW BY THE ARCHITECT SHALL NOT BEGIN WITHOUT THE PRIOR COORDINATION AND REVIEW BY THE GENERAL CONTRACTOR. WORK SHALL NOT BEGIN WITHOUT REVIEW BY THE ARCHITECT. NOTATIONS MADE BY THE ARCHITECT ON THE SHOP DRAWINGS DO NOT RELIEVE THE CONTRACTOR FROM COMPLYING WITH THE
REQUIREMENTS OF THE DRAWINGS AND SPECIFICATIONS.
12. OPTIONS ARE FOR THE CONTRACTOR'S CONVENIENCE. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL NECESSARY CHANGES RESULTING FROM CHOOSING AN OPTION AND SHALL COORDINATE ALL DETAILS.
THE COST OF ADDITIONAL DESIGN WORK NECESSITATED BY SELECTION OF AN OPTION SHALL BE BORNE
BY THE CONTRACTOR.
GENERAL NOTES
CONCRETE
1. ALL CONCRETE WORK SHALL CONFORM TO THE LATEST EDITION OF THE AMERICAN CONCRETE INSTITUTE
PUBLICATIONS: ACI 117, ACI 301, ACI 305.1, ACI 306.1, ACI 308.1, ACI 315 AND ACI 318 UNLESS NOTED
OTHERWISE ON THE DRAWINGS.
2. CUTTING OF REINFORCING WHICH CONFLICTS WITH EMBEDDED OBJECTS IS NOT ACCEPTABLE.
3. CORE DRILLING CONCRETE IS NOT PERMITTED UNLESS NOTED OTHERWISE OR APPROVED IN WRITING BY THE ARCHITECT. NOTIFY THE ARCHITECT IN ADVANCE OF CONDITIONS NOT SHOWN ON THE DRAWINGS.
4. CONFIRM WITH ARCHITECT THAT MATERIALS TO BE EMBEDDED ARE SUITABLE FOR EMBEDMENT IN
CONCRETE.
5. NO ALUMINUM SHALL BE ALLOWED IN THE CONCRETE WORK UNLESS COATED TO PREVENT ALUMINUM-
CONCRETE REACTION.
6. ALL SLABS-ON-GRADE AND PADS SHALL HAVE A MINIMUM OF 6x6 - W1.4xW1.4 WELDED WIRE REINFORCING (WWR) CENTERED IN THE SLAB THICKNESS. LAP WWR MINIMUM 2 PANELS AT EDGES AND ENDS AND
PROVIDE ADDITIONAL REINFORCING WHERE SHOWN ON THE DRAWINGS.
7. SLOPE SLABS TO DRAINS OR FOR POSITIVE DRAINAGE IF NO DRAINS ARE PRESENT, AND PROVIDE
DEPRESSIONS WHERE SHOWN ON THE STRUCTURAL AND/OR ARCHITECTURAL DRAWINGS, WITHOUT
REDUCING THE THICKNESS OF SLAB INDICATED. FOR SLAB-ON-GRADE DEPRESSIONS GREATER THAN 1", REFER TO DETAIL FOR ADDITIONAL REINFORCING.
8. ALL CONSTRUCTION JOINTS BETWEEN ADJACENT CONCRETE POURS OR BETWEEN CONCRETE AND MASONRY SHALL BE KEYED. JOINTS MUST BE KEPT FREE OF DIRT, DEBRIS, FORM OILS, ETC., TO ASSURE
PROPER BOND WITH ADJACENT POUR OR MASONRY CONSTRUCTION.
9. DO NOT PLACE PIPES, DUCTS, REGLETS OR CHASES IN STRUCTURAL CONCRETE OR COMPOSITE FLOOR
SYSTEMS WITHOUT APPROVAL OF THE STRUCTURAL ENGINEER THROUGH THE ARCHITECT.
10. CONCRETE SHALL NOT BE PERMITTED TO DROP MORE THAN 5 FEET.
11. MIX - SLAB ON GRADE CONC:
COARSE AGGREGATE 100% PASSING 1 1/2" SIEVE
FINE AGGREGATE 100% PASSING 3/8" SIEVE
SLUMP 4” TO 6”
MAXIMUM W/C RATIO 0.50
AIR CONTENT NOT APPLICABLE
OTHER REQUIREMENTS USE WATER REDUCING ADMIXTURE
TO ACHIEVE SLUMP SPECIFIED
12. MIX - MASONRY FILL CONC:
COARSE AGGREGATE 100% PASSING 1/2" SIEVE
FINE AGGREGATE 100% PASSING NO. 8 SIEVE
SLUMP 5” TO 8”
MAXIMUM W/C RATIO 0.50
AIR CONTENT NOT APPLICABLE
1. CODES:
INTERNATIONAL BUILDING CODE (IBC) 2018
AMERICAN CONCRETE INSTITUTE BUILDING CODE REQUIREMENTS FOR STRUCTURAL
CONCRETE (ACI 318-08)
AMERICAN CONCRETE INSTITUTE BUILDING CODE REQUIREMENTS FOR MASONRY
STRUCTURES (ACI 530-08)
AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) SPECIFICATION FOR
STRUCTURAL STEEL BUILDINGS
ALLOWABLE STRENGTH DESIGN (ASD)(AISC 360-05) THIRTEENTH EDITION, 2005
2. DESIGN LOADS:
OCCUPANCY CATEGORY II
BACKFILL
EQUIVALENT FLUID PRESSURE 70 PCF
SEISMIC
SOIL CLASSIFICATION D
SPECTRAL RESPONSE ACCELERATION, Ss 0.015 g SPECTRAL RESPONSE ACCELERATION, S1 0.008 g SHORT PERIOD DESIGN ACCELERATION, Sds 0.213 g LONG PERIOD DESIGN ACCELERATION, Sd1 0.096 g
IMPORTANCE FACTOR 1.00
SEISMIC DESIGN CATEGORY C
SEISMIC FORCE RESISTING SYSTEM REINFORCED MASONRY SHEAR WALLS
WIND - PARAMETERS
BASIC WIND SPEED 115 MPH
IMPORTANCE FACTOR 1.00
EXPOSURE CLASS C
LIVE LOADS
CORRIDOR AND PUBLIC SPACE 100 PSF UNREDUCIBLE
OFFICE 75 PSF REDUCIBLE
PARTITIONS 20 PSF UNREDUCIBLE
STAIRS 100 PSF UNREDUCIBLE
SNOW LOADS
GROUND SNOW LOAD 20 PSF
SNOW EXPOSURE FACTOR 1.0
THERMAL FACTOR 1.0
IMPORTANCE FACTOR 1.0
3. MINIMUM FROST PROTECTION DEPTH FROM ADJACENT GRADE:
EXTERIOR FOOTING ADJACENT TO HEATED AREA -2'-6"
EXTERIOR FOOTINGS IN UNHEATED AREA -2'-6"
4. SPECIFIED 28-DAY CONCRETE COMPRESSIVE STRENGTHS (f'c)
TYPICAL - UNLESS NOTED OTHERWISE 4000 PSI
5. CONCRETE REINFORCING STEEL SHALL BE HIGH STRENGTH NEW BILLET STEEL CONFORMING TO THE
FOLLOWING STANDARDS:
DEFORMED BARS ASTM A615, GRADE 60 Fy = 60 KSI WELDED WIRE REINFORCING ASTM A185 Fy = 65 KSI
6. MATERIALS FOR CONCRETE UNIT MASONRY SHALL CONFORM TO THE FOLLOWING STANDARDS:
CONCRETE MASONRY UNITS ASTM C90
MORTAR MATERIALS ASTM C270, TYPE S
GROUT FOR MASONRY ASTM C476
REINFORCING STEEL FOR MASONRY ASTM A615, GRADE 60 (UNO)
PLATE AND BENT BAR ANCHORS ASTM A36
SHEET METAL ANCHORS AND TIES ASTM A1008
WIRE MESH TIES ASTM A185
WIRE TIES AND ANCHORS ASTM A951
ANCHOR BOLTS FOR MASONRY ASTM A307, GRADE A
7. MINIMUM 28 DAY COMPRESSIVE STRENGTHS FOR MASONRY (f'm):
DESIGN ASSEMBLY STRENGTH, f'm 1500 PSI
INDIVIDUAL CONCRETE MASONRY UNITS 1900 PSI
MORTAR FOR MASONRY (TYPE S REQUIRED) 1800 PSI
GROUT FOR MASONRY 2000 PSI
DESIGN CRITERIA
13. THE COST OF ADDITIONAL DESIGN WORK DUE TO ERRORS OR OMISSIONS BY THE CONTRACTOR IN
CONSTRUCTION SHALL BE BORNE BY THE CONTRACTOR.
14. ANY ENGINEERING DESIGN PROVIDED BY OTHERS AND SUBMITTED FOR REVIEW OR RECORD SHALL BEAR THE STAMP AND SIGNATURE OF A PROFESSIONAL STRUCTURAL ENGINEER REGISTERED IN THE STATE OF
MISSOURI.
15. CONTRACTOR SHALL INVESTIGATE SITE DURING CLEARING AND EARTHWORK OPERATIONS FOR FILL MATERIAL OR BURIED STRUCTURES SUCH AS CESSPOOLS, CISTERNS AND FOUNDATIONS. IF ANY SUCH
MATERIAL OR STRUCTURES ARE FOUND, ARCHITECT SHALL BE NOTIFIED IMMEDIATELY.
UNDERPINNING NOTES
1. UNDERPIN EXISTING FOOTINGS AND PLACE NEW MICROPILES AS SHOWN ON THE FOUNDATION PLAN AND
DETAILS.
2. POURED CONCRETE WALL UNDERPINNING PROCEDURE SHALL BE AS FOLLOWS:
A. WHERE NOTED ON THE PLANS AND DETAILS, UNDERPINNING SHALL BE PERFORMED IN SEPARATE
OPERATIONS NOT TO EXCEED 6'-0" IN LENGTH.
B. PLACE HORIZONTAL REINFORCING BARS WITH 90-DEGREE BENDS SO THAT THEY MAY BE
STRAIGHTENED TO LAP WITH BARS OF ADJACENT UNDERPINNING SECTIONS.
C. PLACE CONCRETE OF NEW WALL TO WITHIN 3"-4" OF THE UNDERSIDE OF EXISTING FOOTING WHERE APPLICABLE. AFTER 2 DAYS PACK FINAL 3"-4" WITH DRY GROUT. USE SAME GROUT SPECIFIED UNDER STEEL BASE PLATES GIVEN IN SPECIFICATION SECTION 05 12 23. GROUT IS TO SET AT LEAST 7 DAYS BEFORE ADJACENT SECTION IS EXCAVATED. SHORE AND BRACE EACH SECTION AS SOON AS FORMS ARE REMOVED. WHEN EXCAVATION IS STARTED IN ANY SECTION, ALL WORK IN THAT SECTION MUST BE
COMPLETED PROMPTLY AND PRIOR TO STARTING ANOTHER SECTION IN THE IMMEDIATE AREA.
D. REPEAT THIS PROCEDURE IN ALTERNATE 6'-0" SECTIONS UNTIL UNDERPINNING IS COMPLETE.
3. DURING UNDERPINNING OPERATION, CONTRACTOR SHALL BRACE AND SHORE WITH JACKS EXISTING FOOTING OR WALL AS REQUIRED TO PREVENT MOVEMENT OF EXISTING BUILDING. THE SHORING SHALL BE SELECTED TO WITHSTAND THE DESIGN FORCES INDICATED ON THE DRAWINGS. THE SHORING JACKS ARE
TO BE LEFT IN PLACE AND CAST INTO THE CONCRETE UNDERPINNING POUR.
4. CONTRACTOR SHALL SUBMIT A SCHEDULE OF UNDERPINNING OPERATIONS FOR REVIEW OF THE
ARCHITECT AND ENGINEER.
5. CONTRACTOR SHALL SURVEY EXISTING FOOTING ELEVATIONS PRIOR TO, DURING, AND AFTER
UNDERPINNING OPERATIONS TO MONITOR POTENTIAL MOVEMENTS. SURVEY RESULTS SHALL BE
SUBMITTED TO THE ARCHITECT AND ENGINEER.
1. STEEL HELICAL PILES SHALL BE ACCURATELY CENTERED AT THE PROPER LOCATIONS AND INSTALLED PLUMB. INSTALL TO THE FOLLOWING TOLERANCES: PILE CENTER WITHIN 3” LATERALLY AND 1/2” VERTICALLY FROM SPECIFIED LOCATION AND ELEVATION, AND SHAFT ALIGNMENT WITHIN 1 DEGREE OF
SPECIFIED ANGLE.
2. SPECIAL INSPECTION AGENCY SHALL KEEP A RECORD OR LOG OF EACH PILE AS INSTALLED SHOWING LOCATION, TOP AND BOTTOM ELEVATIONS, DIAMETERS, DATE INSTALLED, TYPE OF STRATA ENCOUNTERED
AND ANY OTHER PERTINENT INFORMATION.
3. PILE DESIGN SHALL BE DESIGNED TO MEET THE SPECIFIED LOADING AS SHOWN ON PLAN AND THE
DEFLECTION CRITERIA OF 1/2” DIFFERENTIAL AND 1” TOTAL SETTLEMENTS.
4. HELICAL PILE CONTRACTOR SHALL SUBMIT DESIGN CALCULATIONS AND SHOP DRAWINGS STAMPED AND CERTIFIED BY A LICENSED ENGINEER IN THE STATE WHERE THE PROJECT IS LOCATED. SHOP DRAWINGS SHALL BE SUBMITTED FOR REVIEW BY THE ARCHITECT/ENGINEER AND SHALL INCLUDE HELICAL PILE
COMPONENTS, CORROSION PROTECTION SYSTEM, PILE TOP ATTACHMENT AND HELIX DETAILS.
STEEL HELICAL PILES - ALTERNATE OPTION
1. MICROPILES SHALL BE ACCURATELY CENTERED AT THE PROPER LOCATIONS AND INSTALLED PLUMB.
INSTALL TO THE FOLLOWING TOLERANCES: PILE CENTER WITHIN 3” FROM SPECIFIED LOCATION, PILE-HOLE ALIGNMENT WITHIN 2%, TOP ELEVATION WITHIN +1” AND -2” FROM SPECIFIED ELEVATION AND CENTER OF
CORE REINFORCEMENT WITHIN 3/4” FROM CENTERLINE OF PILING.
2. THE ELEVATION IDENTIFYING THE BOTTOM OF THE MICROPILE IS AN APPROXIMATE LENGTH FOR CONSISTENT BIDDING PURPOSES ONLY. THE ACTUAL LENGTH WILL BE DETERMINED IN THE FIELD FROM THE ACTUAL ELEVATION OF THE BEARING STRATUM. THE SPECIAL INSPECTION AGENCY SHALL DETERMINE THE FINAL BEARING ELEVATIONS REQUIRED TO MEET THE PILE LOADS, BASED ON THE CONDITIONS
ENCOUNTERED DURING INSTALLATION.
3. SPECIAL INSPECTION FIRM SHALL KEEP A RECORD OR LOG OF EACH PILE AS INSTALLED SHOWING LOCATION, TOP AND BOTTOM ELEVATIONS, SHAFT DIAMETERS, DATE INSTALLED, TYPE OF STRATA ENCOUNTERED, RATED LOAD CAPACITY, GROUT PRESSURE ATTAINED AND ANY OTHER PERTINENT
INFORMATION.
4. MICROPILE DESIGN SHALL BE DESIGNED TO MEET THE SPECIFIED LOADING AS SHOWN ON PLAN AND THE
DEFLECTION CRITERIA OF 1/2” DIFFERENTIAL AND 1” TOTAL SETTLEMENTS.
5. MICROPILE CONTRACTOR SHALL SUBMIT DESIGN CALCULATIONS AND SHOP DRAWINGS STAMPED AND CERTIFIED BY A LICENSED ENGINEER IN THE STATE WHERE THE PROJECT IS LOCATED. SHOP DRAWINGS SHALL BE SUBMITTED FOR REVIEW BY THE ARCHITECT/ENGINEER AND SHALL INCLUDE MICROPILE COMPONENTS, CORROSION PROTECTION SYSTEM, MICROPILE TOP ATTACHMENT AND BOND LENGTH
DETAILS.
HIGH CAPACITY DRILLED AND GROUTED MICROPILES
1. CROSS REFERENCE ARCHITECTURAL AND STRUCTURAL DRAWINGS TO ASSURE PROPER DIMENSIONS AND PLACEMENT OF ALL ANCHOR BOLTS, INSERTS, NOTCHES, EDGES IN GRADE BEAMS, FOUNDATION WALLS AND
PIERS.
2. FOUNDATION DESIGN BASED ON GEOTECHNICAL ENGINEERING REPORT DATED AUGUST 24, 2018 BY
GEOTECHNOLOGY, INC. REPORT IS INCLUDED IN THE PROJECT MANUAL.
3. ALL EXCAVATIONS SHALL BE PROPERLY AND SAFELY BACKFILLED. CONTRACTOR SHALL BRACE OR PROTECT ALL WALLS BELOW GRADE FROM LATERAL LOADS UNTIL SUPPORTING FLOOR IS COMPLETELY IN PLACE AND HAS ATTAINED FULL STRENGTH. CONTRACTOR SHALL PROVIDE FOR DESIGN, PERMITS, AND INSTALLATION OF SHORING AND/OR SHEETING. BACKFILLING IS NOT PERMITTED FOR FOUNDATION WALLS UNTIL SUPPORTED SLAB ABOVE IS IN PLACE OR THE WALL IS ADEQUATELY BRACED TO RESIST LATERAL LOADS.
4. UNLESS NOTED OTHERWISE, ALL FOOTINGS SHALL BE CENTERED UNDER WALLS, PIERS OR COLUMNS.
5. PROVIDE SAW CUT CONTROL JOINTS IN ALL SLABS-ON-GRADE. LOCATE JOINTS ALONG COLUMN LINES WITH INTERMEDIATE JOINTS SPACED PER THE TABLE BELOW, UNLESS NOTED OTHERWISE. CONTROL JOINTS SHALL BE CONTINUOUS, NOT STAGGERED OR OFFSET. SLAB PANELS SHALL HAVE A MAXIMUM LENGTH TO WIDTH RATIO OF 1.5 TO 1. PROVIDE ADDITIONAL CONTROL JOINTS AT ALL RE-ENTRANT CORNERS FORMED IN
SLAB ON GRADE.
FOUNDATIONS/SLAB-ON-GRADE
SLAB ON GRADE
THICKNESS
MAX JOINT
SPACING
4" 12'-0"
6. CONTRACTOR SHALL PROVIDE FOR DE-WATERING OF EXCAVATIONS FROM SURFACE WATER, GROUND WATER
OR SEEPAGE.
7. CONTRACTOR SHALL PROVIDE FOR DESIGN AND INSTALLATION OF ALL CRIBBING, SHEETING, AND SHORING
REQUIRED TO SAFELY RETAIN EARTH BANKS AS REQUIRED.
8. EXCAVATIONS FOR NEW PILES AND UNDER SLAB SHALL BE INSPECTED AND APPROVED BY THE SOILS TESTING FIRM PRIOR TO PLACING CONCRETE. CONTRACTOR SHALL NOTIFY SOILS TESTING FIRM WHEN EXCAVATION IS READY FOR INSPECTION. TESTING FIRM IS TO SUBMIT LETTER OF COMPLIANCE TO THE OWNER.
9. FOOTING BACKFILL AND UTILITY TRENCH BACKFILL WITHIN BUILDING AREA SHALL BE MECHANICALLY
COMPACTED IN 8" LAYERS AND TO THE APPROVAL OF THE SOILS TESTING FIRM.
10. ALL ABANDONED FOOTINGS, UTILITIES, AND OTHER STRUCTURES THAT INTERFERE WITH NEW CONSTRUCTION
SHALL BE REMOVED.
11. NO CONCRETE SHALL BE PLACED ONTO OR AGAINST SUBGRADES CONTAINING FREE WATER, FROST, ICE, OR
SNOW.
12. DURING WINTER CONSTRUCTION, ALL FOOTINGS SHALL BE PROTECTED FROM FROST PENETRATION UNTIL THE
BUILDING IS ENCLOSED AND TEMPORARY HEAT IS PROVIDED.
13. ALL UNACCEPTABLE MATERIAL AND ORGANIC MATERIAL SHALL BE REMOVED FROM BELOW ALL PROPOSED SLABS-ON-GRADE AND THE EXPOSED NATURAL SOIL SHALL BE PROOF ROLLED AND THE COMPACTION VERIFIED BY A QUALIFIED INDEPENDENT SOILS TESTING FIRM PRIOR TO PLACING FILL. AREAS EXHIBITING
WEAKNESS SHALL BE REMOVED AND REPLACED BY ACCEPTABLE COMPACTED FILL.
14. THE AT-GRADE FIRST FLOOR EXISTING SLAB APPEARS TO HAVE SETTLED CAUSING SLAB CRACKING AND MOVEMENT OF THE INTERIOR PARTITION WALLS. INADEQUATE COMPACTION OF THE EXISTING BASEMENT WALL OVERDIG BACKFILL IS MOST LIKELY THE CAUSE. CONTRACTOR TO EXCAVATE BENEATH THE FIRST FLOOR SLAB AS INDICATED ON PLAN, REPLACE ANY HIGHLY PLASTIC CLAY, RE-PREPARE THE SUBGRADE SOILS BY MOISTURE-CONDITIONING AND RECOMPACTING, AND RECONSTRUCT THE SLAB. IF THE BASEMENT WALL OVERDIG BACKFILL IS POORLY COMPACTED, IT WILL BE REQUIRED TO EXCAVATE A PORTION OR ALL OF THE BACKFILL MATERIAL AND REPLACE THIS MATERIAL IN THIN LEFTS PER THE GEOTECHNICAL REPORT.
1. EXTREME CARE SHALL BE EXERCISED WHEN EXCAVATING OR GRADING ADJACENT TO EXISTING
STRUCTURES OR IMPROVEMENTS TO NOT DAMAGE OR UNDERMINE FOUNDATIONS, WALLS, SLABS,
UTILITIES, ETC.
2. THE MOISTURE CONTENT OF ONSITE CLAYEY SOILS AT THE TIME OF COMPACTION SHALL BE BETWEEN
2-3% ABOVE OPTIMUM MOISTURE CONTENT.
3. ANY IMPORT FILL SOIL REQUIRED SHALL HAVE A LOW POTENTIAL FOR EXPANSION AND SHALL BE
APPROVED BY THE OWNER'S GEOTECHNICAL ENGINEER OR OTHER SOIL TESTING FIRM
REPRESENTATIVE AS REQUIRED PRIOR TO IMPORTING.
4. ALL UNACCEPTABLE MATERIAL AND ORGANIC MATERIAL SHALL BE REMOVED FROM BELOW ALL PROPOSED SLABS-ON-GRADE AND OUTSIDE THE EXTERIOR OF THE BUILDING WHERE THE SOIL IS DISTURBED FOR PILE INSTALLATION. THE EXPOSED NATURAL SOIL SHALL BE PROOF-ROLLED AND THE COMPACTION VERIFIED BY AN INSPECTION AGENCY PRIOR TO PLACING FILL. AREAS EXHIBITING
WEAKNESS SHALL BE REMOVED AND REPLACED BY ACCEPTABLE COMPACTED FILL.
5. ALL SITE WORK SHALL BE PERFORMED UNDER THE INSPECTION OF THE SPECIAL INSPECTION FIRM.
VARIATIONS IN SITE CONDITIONS AND THE GEOTECHNICAL REPORT SHALL BE REPORTED TO THE
ARCHITECT/STRUCTURAL ENGINEER FOR CLARIFICATIONS PRIOR TO PROCEEDING.
EARTHWORK
BE Project No.
Expiration Date of Seal: 12/31/2022
Drawn By:
Drawing No.
Drawing Title t 312.440.2300 f 312.440.2303 www.baileyedward.com
35 East Wacker Dr Suite 2800 Chicago, IL 60601-2308
©2018 Bailey Edward Design Design Firm License No. 184-001962
Structural Engineer IMEG Corp.
15 Sunnen Dr. Suite 104 St. Louis, MO 63143 314-645-1132
SHEET
-J u n -2
:2
:2
A M
C R e v it L o c a l F ile s \S
.0
U S
G S
B u ild in g S ta b ili z a ti o n
-C s u jit k u m a r.
n .p a d h a n
.r v t
GENERAL NOTES
S0.0
USGS OAG A3 MAIN
BUILDING STABILIZATION
18018
WHL
Columbia Environmental Research Center (CERC) 4200 New Haven Road
Columbia, Missouri
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE
THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG CORP. © 2021 IMEG CORP.
15 SUNNEN DR, SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com
18003021.00
REVISION
MARK DESCRIPTION DATE
HGFEDC J KD1C5B8B3BA
E1 E9
4.5
4.7
B2 B9 H1 H7D2 D9
6.5
5.6
HGFEDC J KD1C5B8B3BA
E1 E9
4.5
4.7
B2 B9 H1 H7D2 D9
6.5
5.6
ELEVATOR
UNEXCAVATED
8" CONCRETE WALL, TYP
(E) 4" SLAB ON GRADE
WITH WELDED WIRE
FABRIC
UNEXCAVATED
AREA TO BE EXCAVATED
ABOVE FOR SLAB AND
SOIL REMEDIATION
REMOVAL AND DUCT
REPLACEMENT
BE Project No.
Expiration Date of Seal: 12/31/2022
Drawn By:
Drawing No.
Drawing Title t 312.440.2300 f 312.440.2303 www.baileyedward.com
35 East Wacker Dr Suite 2800 Chicago, IL 60601-2308
©2018 Bailey Edward Design Design Firm License No. 184-001962
Structural Engineer IMEG Corp.
15 Sunnen Dr. Suite 104 St. Louis, MO 63143 314-645-1132
SHEET
-J u n -2
:2
:2
A M
C R e v it L o c a l F ile s \S
.0
U S
G S
B u ild in g S ta b ili z a ti o n
-C s u jit k u m a r.
n .p a d h a n
.r v t
BASEMENT FLOOR
PLAN
S1.0
USGS OAG A3 MAIN
BUILDING STABILIZATION
18018
WHL
Columbia Environmental Research Center (CERC) 4200 New Haven Road
Columbia, Missouri
N
O R HT
1/8" = 1'-0"1
BASEMENT FLOOR PLAN
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE
THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG CORP. © 2021 IMEG CORP.
15 SUNNEN DR, SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com
18003021.00
REVISION
HGFEDC J KD1C5B8B3BA
E1 E9
4.5
4.7
B2 B9 H1 H7D2 D9
6.5
5.6
S2.0
(E) 4" SLAB ON GRADE
NEW 4" SLAB ON GRADE
WITH 6x6 - W2.1xW2.1
TOP OF SLAB ELEVATION
TO MATCH EXISTING.
EXISTING 10" CONCRETE
FOUNDATION WALL UNDER
LOAD BEARING MASONRY
AND FACE BRICK
EXISTING 8" THICK x 14" WIDE
CONTINUOUS FOOTING
TOP OF EXISTING FOOTING
EL (-2'-8" VIF)
TYP
SEE GEOTECH REPORT AND
GENERAL NOTES FOR
EXCAVATION AND COMPACTION
REQUIREMENTS AT SOIL
DISTURBED BY MICROPILE
INSTALLATION
NEW PATIO SLAB TO
REPLACE EXISTING. SEE
ARCHITECTURAL FOR SIZE
AND ELEVATION. MATCH
THICKNESS WITH EXISTING.
SEE GEOTECH REPORT AND
GENERAL NOTES FOR
EXCAVATION AND
COMPACTION REQUIREMENTS
AT SOIL DISTURBED BY
MICROPILE INSTALLATION
NOTES:
1. INDICATES RECOMMENDED AREA OF SLAB ON GRADE TO BE
REMOVED AND REPLACED. REMOVE HIGH PLASTIC CLAYS
BENEATH THE SLAB, RE-PREPARE THE SUBGRADE SOILS BY MOISTURE
CONDITIONING AND RECOMPACTING, AND RECONSTRUCT SLAB. REFER TO 1, 2
AND 3/S2.0 FOR DETAILS. REFER TO EXCAVATION SPECIFICATION, GENERAL
NOTES, AND GEOTECHNICAL REPORT FOR ADDITIONAL INFORMATION.
2. REPLACE CRACKED/DAMAGED MASONRY WALLS WITH NEW 6" WIDE METAL
STUD PARTITION WALLS. BRACE TOP OF WALL TO PRECAST ROOF
STRUCTURE AND PROVIDE DEFLECTION TRACK. REFER TO ARCHITECTURAL
DRAWINGS FOR DETAILS.
3. INDICATES NEW HELICAL PIER OR MICROPILE DESIGNED TO HANDLE 20
KIPS OF VERTICAL SERVICE LEVEL LOAD EACH. MAXIMUM SPACING TO BE
6' - 0" OC MAX ALONG LENGTH OF PERIMETER WALL. REFER TO DETAIL 5/S2.0.
4. REFER TO 4/S2.0 FOR TOP OF PERIMETER WALL REPAIR DETAIL AT AREA OF
WORK. REFER TO ARCHITECTURAL DRAWINGS FOR SCOPE AREA.
N
O R HT
1/8" = 1'-0"1
FIRST FLOOR PLAN
BE Project No.
Expiration Date of Seal: 12/31/2022
Drawn By:
Drawing No.
Drawing Title t 312.440.2300 f 312.440.2303 www.baileyedward.com
35 East Wacker Dr Suite 2800 Chicago, IL 60601-2308
©2018 Bailey Edward Design Design Firm License No. 184-001962
Structural Engineer IMEG Corp.
15 Sunnen Dr. Suite 104 St. Louis, MO 63143 314-645-1132
SHEET
-J u n -2
:2
:2
A M
C R e v it L o c a l F ile s \S
.0
U S
G S
B u ild in g S ta b ili z a ti o n
-C s u jit k u m a r.
n .p a d h a n
.r v t
FIRST FLOOR PLAN
S1.1
USGS OAG A3 MAIN
BUILDING STABILIZATION
18018
WHL
Columbia Environmental Research Center (CERC) 4200 New Haven Road
Columbia, Missouri
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE
THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG CORP. © 2021 IMEG CORP.
15 SUNNEN DR, SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com
18003021.00
REVISION
EXISTING 4" SLAB TO BE REPLACED
WITH NEW 4" SLAB REINFORCED
WITH 6x6 - W2.1xW2.1 WWR
EXCAVATED AND RECONDITIONED
SOILS. REFER TO PLAN AND GENERAL
NOTES FOR REQUIREMENTS.
EXISTING CONCRETE WALL AND FOOTING
NOTES:
1. DEPTH INDICATED IS AN ESTIMATION FOR BIDDING PURPOSES ONLY.
EXACT DEPTH TO BE DETERMINED ONCE SLAB DEMO IS COMPLETE AND
EXCAVATION HAS STARTED. CONTRACTOR TO PROVIDE UNIT COST FOR
ADDITIONAL CUBIC YARD OF EXCAVATION AND BACKFILL REQUIRED IF
EXCAVATION AND BACKFILL IS GREATER THAN WHAT IS SHOWN ON THE
DRAWINGS. EXCAVATION AND SOIL REPLACEMENT TO BE MONITORED
BY SOIL TESTING AGENCY.
(E) BASEMENT WALL
(N O
T E
CONTRACTOR TO TAKE CARE NOT TO UNDERMINE EXISTING PERIMETER
FOOTING OR EDGE OF INTERIOR REMAINING SLAB WITH OVER-EXCAVATION
UNDER SLAB. CONTRACTOR TO MAINTAIN A 1:1 SLOPE FROM CORNER OF
BOTTOM OF FOOTING OR SLAB IF EXCAVATION IS NEEDED BELOW
FOOTING. IF THIS IS NOT POSSIBLE, ADDITIONAL SHORING OR SHEET PILING
MAY BE REQUIRED TO STABILIZE EXISTING FOOTING.
EXISTING 8" ROOF PLANK. SHORE
DURING REMOVAL OF EXISTING
MASONRY BLOCK. CONTACT EOR
IF SHORING LOADS ARE NEEDED.
EXISTING FACE BRICK
REMOVE AND REPLACE
PER ARCH DRAWINGS
NEW MASONRY BOND BEAM GROUTED SOLID
WITH NEW BLOCK BELOW GROUTED AT
LOCATIONS OF EXISTING WALL GROUT
NEW #3 DOWEL NEXT TO WHERE
EXISTING #3 DOWEL OCCURS OR @
24" OC MAX. DRILL THROUGH
EXISTING ANGLE. INSTALL THROUGH
TOP OF PRECAST, FILL WITH GROUT,
AND TOP CAP OF REINFORCING WITH
GROUT PLUG.
(E) L4x4x5/16 x CONT TO REMAIN
(E) #3 BAR AT UNKNOWN
SPACING. CONTRACTOR TO
LOCATE AND TO MAINTAIN
INTEGRITY OF BAR DURING
CMU DEMO
(VIF)
4 5/8"
EXISTING MASONRY WALL
REINFORCING TO REMAIN
L6x4x3/8 (LLV) x CONT. SPLICED IN
10'-0" SECTIONS WITH 3/4"Ø HILTI
KWIK BOLT 3 WITH 4 3/4" MIN
EMBEDMENT. HOLD TIGHT TO
BOTTOM OF PRECAST PLANK.
S2.0
N E
W E
X
IS
T
IN
G
EXISTING CONCRETE
WALL AND FOOTING
NEW MICROPILES OR HELICAL
PILES, SEE PLAN FOR SPACING,
ENSURE SOIL IS PRESENT ON
INSIDE OF BUILDING DURING PILE
INSTALLATION
1/2" EXPANSION JOINT
MATERIAL
NEW SLAB ON GRADE
SEE PLAN
NEW DUCT WORK TO
REPLACE EXISTING.
CONTRACTOR TO PROTECT
DURING CONSTRUCTION AND
ANCHOR TO SOIL TO
PREVENT FUTURE UPLIFT
EXISTING MASONRY AND
FACE BRICK WALL
6"
SMOOTH DOWEL BARS - SEE
SCHEDULE. DRILL INTO
EXISTING
EXISTING CONCRETE SLAB
UNBONDED
SLAB ON GRADE
SEE TYPICAL
DETAILS
SLAB
THICKNESS
4"
SMOOTH DOWEL
BAR
1/2"Ø x 1'-4" @ 18" OC
VAPOR BARRIER -
SEE SPECS
SAWCUT JOINT WITHIN
24 HOURS OF CONCRETE
PLACEMENT
SLAB ON GRADE
SEE PLAN
NOTES:
1. SEE CAST-IN-PLACE CONCRETE GENERAL NOTES CONCERNING LOCATION OF
JOINTS.
2. REFERENCE SPECIFICATIONS FOR MATERIAL AND COMPACTION REQUIREMENTS.
S E
E P
L A
N
T H
IC
K
N E
S S t)
1/4" t/
M
IN
IM
U
M
ENGINEERED FILL
VAPOR BARRIER - SEE SPECS
SLAB ON GRADE - SEE PLAN
REINFORCING - SEE PLAN
/3 t)
S E
E P
L A
N T
H
IC
K N
E S
S t)
NEW MOISTURE CONDITIONED AND
COMPACTED SOIL MINIMUM 3 FT
EXPECTED. REFER TO DETAIL 1/S2.0
10' - 0"
2' - 0" TYP EA END
MASONRY WALL WINDOW WINDOW MASONRY WALLMASONRY
WALL
SPLICE LOCATION
PRECAST PLANK
NEW STEEL ANGLE
TYP
1/2" MAX
BE Project No.
Expiration Date of Seal: 12/31/2022
Drawn By:
Drawing No.
Drawing Title t 312.440.2300 f 312.440.2303 www.baileyedward.com
35 East Wacker Dr Suite 2800 Chicago, IL 60601-2308
©2018 Bailey Edward Design Design Firm License No. 184-001962
Structural Engineer IMEG Corp.
15 Sunnen Dr. Suite 104 St. Louis, MO 63143 314-645-1132
SHEET
-J u n -2
:2
:2
A M
C R e v it L o c a l F ile s \S
.0
U S
G S
B u ild in g S ta b ili z a ti o n
-C s u jit k u m a r.
n .p a d h a n
.r v t
SECTIONS AND
DETAILS
S2.0
USGS OAG A3 MAIN
BUILDING STABILIZATION
18018
WHL
Columbia Environmental Research Center (CERC) 4200 New Haven Road
Columbia, Missouri
1/4" = 1'-0"1
FOUNDATION SECTION
3/4" = 1'-0"4
ROOF PERIMETER
WALL CMU REPAIR DETAIL
3/4" = 1'-0"5
NEW PILE DETAIL
3/4" = 1'-0"2
NEW TO EXISTING SLAB DETAIL
3/4" = 1'-0"3
TYPICAL SLAB ON GRADE DETAILS
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE
THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG CORP. © 2021 IMEG CORP.
15 SUNNEN DR, SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com
18003021.00
3/4" = 1'-0"6
ROOF PERIMETER WALL
NEW LEDGE ANGLE ELEVATION REVISION
MARK DESCRIPTION DATE
ENGINEERED FILL
AREA NOT IN SCOPE OF WORK
EXISTING WALL TO BE DEMOLISHED
EXISTING WALL TO REMAIN
EXISTING DOOR AND FRAME TO REMAIN
EXISTING DOOR AND FRAME TO BE
DEMOLISHED
EXISTING TO BE DEMOLISHED
INDICATES EXTENT OF DEMOLITION WORK
REQUIRED BY KEYNOTE
HGF J K
E1 E9
4.5
4.7
H1 H7
CHANGE ROOM UTILITIES
UTILITIES
UNEXCAVATED
4'
9'
3'
6'
12' - 6" 15' - 10" 15' - 10" 5" 12' - 10" 6' - 6" 20' - 1"
A700
A700
3"
EXCAVATE AND FILL
ABOVE, SEE FIRST
FLOOR
DEMO DUCT WORK BELOW
GROUND FLOOR SLAB, SEE
MEP SHEETS.
UNEXCAVATED
UNEXCAVATED
TYP
TYP
01.02
CORRIDOR
A700
TYP
A700
TYP
HGF J K
E1 E9
4.5
4.7
H1 H7
RECEPTION
AREA
MAIN
ENTRANCE
CORRIDOR
WOMEN'S
RR
CONFERENCE AND
LUNCH ROOM
DIRECTOR'S
OFFICE
WATER
QUALITY LAB
MAIL ROOM
OFFICE
OFFICE
OFFICEOFFICEOFFICEOFFICEOFFICE
WET LABORATORY
02.04
02.04
12' - 6" 1' - 8" 15' - 10" 15' - 10" 5" 12' - 10" 6' - 6" 20' - 1" 7"
4'
7" 4'
9'
3'
6'
D100
D1006
A700
A700
02.09
02.09
02.10
TYP
02.10
(ABOVE)
02.10
02.1002.1002.1002.1002.1002.1002.10
02.1002.10
02.1002.10
02.1002.10
02.10
SEE G101
FOR PHOTO
TYP
01.03
01.04
A700
A700
TYP
TYP
51A
51B
51C
54 52
02.03
02.03
HG J K
4.5
4.7
H1 H7
D1006
D100
A700
4'
7" 4'
9'
3'
6'
15' - 10" 5" 12' - 10" 6' - 6" 20' - 1" 7"
3' - 0"
02.06
02.07
A700
TYP
TYP
01.0301.03
A700
TYP
A700
TYP
HG J K
4.5
4.7
H1 H7
D100
CORRIDOR
WOMEN'S
RR
CONFERENCE AND
LUNCH ROOM
WATER
QAULITY LAB
MAIL ROOM
OFFICEOFFICEOFFICE
WET LABORATORY
TYP.
02.05
02.05
4'
7" 4'
9'
3'
6'
15' - 10" 5" 12' - 10" 6' - 6" 20' - 1" 7"
A700
A700
TYP
TYP
DIRECTOR'S
OFFICE
OFFICE
OFFICE
OFFICEOFFICE 51A
51B
51C
54 52
A700
TYP
A700
TYP
GROUND FLOOR
0"
ROOF
10' - 0"
H G FJK E1E9H1H7
02.06
02.08
TYP.
A700
01.01
02.10
TYP.
02.11
TYP.
D100
TYPTYP
A700
TYP.
TYP.
TYP
GRADE LINE
-7 1/8" V.I.F.
2345 4.54.7
02.06
02.08
TYP.
01.01
A700
02.10
TYP.
02.11
TYP.EXISTING ELECTRICAL TO REMAIN,
PROTECT AS REQUIRED. WINDOW BEHIND
TO REMAIN. SEE G101 FOR PHOTO.
D100
TYP.
CANOPY ENTRANCE
BEYOND
TYP.
TYP.
A700
TYP.
TYP.
1. OBTAIN FROM THE OWNER THEIR CURRENT HAZARDOUS MATERIALS REPORT
PRIOR TO COMMENCING WITH THE WORK. NO DEMOLITION ON-SITE SHALL
PROCEED WITHOUT THIS WRITTEN CONFIRMATION FROM THE OWNER THAT NO
ASBESTOS-CONTAINING MATERIALS EXIST IN THE EXISTING ROOFING. IF THE
OWNER'S REPORT INDICATES OTHERWISE, COORDINATE WITH THE OWNER THE
APPROPRIATE PROCEDURES FOR REMOVAL AND DISPOSAL OF ANY HAZARDOUS
MATERIALS IN COMPLIANCE WITH THE APPROPRIATE CODES, REGULATIONS AND
AUTHORITIES HAVING JURISDICTION AND ALSO THE OWNER'S REQUIREMENTS.
2. THE CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH THE
EXISTING CONDITIONS PRIOR TO COMMENCING DEMOLITION. THE CONTRACTOR
SHALL NOTIFY THE OWNER OF ANY AND ALL DISCREPANCIES BETWEEN THE
DEMOLITION SCOPE AND ACTUAL CONDITIONS PRIOR TO PROCEEDING WITH THE
WORK. NOTIFY THE OWNER IMMEDIATELY IF HAZARDOUS MATERIALS ARE
IDENTIFIED. DO NOT PROCEED WITH THE WORK UNTIL THE HAZARDOUS
MATERIALS HAVE BEEN REMOVED.
3. REFER TO NEW WORK DRAWINGS FOR ADDITIONAL REQUIREMENTS.
4. UNLESS SPECIFICALLY NOTED OTHERWISE ALL ASSEMBLIES AND COMPONENTS
INDICATED TO BE DEMOLISHED SHALL BE DEMOLISHED COMPLETELY.
5. ALL COMPONENTS INDICATED TO BE DEMOLISHED SHALL BE DISPOSED OF AS
REQUIRED BY THE CONTRACTOR PRIOR TO DEMOLITION, COORDINATE WITH THE
OWNER ANY MISCELLANEOUS SALVAGED MATERIALS. COORDINATE WITH THE
OWNER REMOVAL OF SALVAGED ITEMS TO BE PERFORMED BY THE OWNERS OWN
LABOR FORCES.
6. TEMPORARILY STORE ON SITE MATERIALS COMPONENTS OR ITEMS TO BE
REUSED AS DIRECTED BY THE OWNER, IN LOCATIONS ACCEPTABLE TO THE
OWNER.
7. SURVEY, CATALOGUE AND PROVIDE TEMPORARY PACKING OR WRAPPING OF
MATERIALS COMPONENTS OR ITEMS TO BE TEMPORARILY REMOVED AND REUSED
IN THE FINAL CONSTRUCTION, AS REQUIRED. PROVIDE ALL NECESSARY
PROTECTION AGAINST MOISTURE, IMPACT, AND ANY OTHER TYPE OF POTENTIAL
DAMAGE.
8. CONTRACTOR SHALL REMOVE ALL TRASH AND DEBRIS DAILY. DEMOLITION
WORK SHALL REMAIN SAFE & CLEAN FOR THE BUILDING'S OCCUPANTS &
CONSTRUCTION WORKERS. OCCUPIED AREAS ADJACENT TO THE PROJECT WORK
AREAS SHALL BE KEPT CLEAN AND SHALL NOT BE DISTURBED AT ALL TIMES
DURING THE WORK.
9. EXISTING CONSTRUCTION IS BASED UPON INFORMATION PROVIDED BY THE
OWNER AND LIMITED FIELD REVIEW BY THE ARCHITECT. FIELD VERIFICATION BY
THE CONTRACTOR PRIOR TO COMMENCEMENT OF CONSTRUCTION IS REQUIRED.
10. PROTECT EXISTING EQUIPMENT AND DEVICES, ETC. LOCATED ON EXISTING
SURFACES TO REMAIN. REMOVE AND REINSTALL EXISTING ITEMS THAT ARE
REMOVABLE FOR SCHEDULED WORK, AS REQUIRED. EXISTING ITEMS THAT ARE
NOT REMOVABLE SHALL BE CAREFULLY PROTECTED DURING THE WORK.
11. THE CONTRACTOR SHALL COORDINATE THE SCHEDULE FOR THE WORK WITH
THE OWNERS SECURITY AND STAFF BOTH PRIOR TO THE WORK AND AT
COMPLETION OF EACH PORTION OF THE WORK WHERE THE OWNER SHALL
OBTAIN ACCESS TO THE COMPLETED WORK AREA. THE CONTRACTOR SHALL ALSO
COORDINATE WITH THE OWNER FOR ANY FINAL WORK PERFORMED BY THE
OWNER AND OTHER MISCELLANEOUS EQUIPMENT, DEVICES OR OTHER
MODIFICATIONS PERFORMED BY THE OWNER.
12. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING A SECURE
WORK AREA THROUGH OUT THE WORK. THE CONTRACTOR SHALL MAINTAIN
CONTROL AND ACCOUNT FOR ALL MATERIALS AND TOOLS BROUGHT ON TO THE
SITE. THE CONTRACTOR SHALL, AT NO TIME DURING THE WORK, ALLOW
CONSTRUCTION MATERIALS AND TOOLS TO BECOME UNACCOUNTED FOR AND IN
THE POSSESSION OF OTHERS. SEE SPECIFICATIONS SECTION 01010, SUMMARY OF
WORK AND GENERAL REQUIREMENTS FOR ADDITIONAL REQUIREMENTS.
13. THE CONTRACTOR SHALL FIELD VERIFY AND DOCUMENT EXISTING
CONDITIONS PRIOR TO STARTING CONSTRUCTION.
14. FIELD SURVEY AND RECORD LOCATIONS OF EXISTING INTERIOR PARTITIONS
PRIOR TO DEMOLITION FOR USE LOCATING NEW PARTITIONS AS NOTED ON THE
ENLARGED GROUND FLOOR PLAN.
15. PATCH TO MATCH, FILL, SAND AND LEVEL EXISTING WALL SURFACES TO
REMAIN TO PROVIDE SMOOTH, FLAT SURFACE PREP FOR SCHEDULED FINISHES
AS REQUIRED, TYP. PATCH TO MATCH EXISTING INTERIOR WINDOW SURROUNDS
FOLLOWING WINDOW REMOVALS AND REINSTALLATIONS, THE SAME, TYP.
16. PROTECT EXISTING INTERIOR SURFACES, FINISHES, FIXTURES, FURNISHINGS,
WALL AND CEILING MOUNTED DEVICES, ETC. NOT SHOWN TO BE MODIFIED
ADJACENT TO THE AREA OF WORK AND WITHIN EXISTING AREAS ACCESSED
DURING THE WORK. REPLACE TO MATCH EXISTING AND REPAIR/REFINISH
EXISTING SURFACES FULL WIDTH AND HEIGHT TO NEXT CORNER AS REQUIRED.
17. PROTECT THE EXISTING EXTERIOR WALL FROM DAMAGE THROUGHOUT THE
WORK. PROVIDE TEMPORARY PROTECTIONS TO EXISTING MASONRY WALLS,
WINDOWS. GLASS UNITS, PROJECTING ELEMENTS, ETC. AS REQUIRED.
GROUND FLOOR
0"
ROOF
10' - 0"
02.10 TYP.
02.06
02.11 TYP.
01.01
02.08 TYP.
A700
TYP
TYP.
TYP.
02.17 TYP.
02.19
TYP.02.18
GRADE LINE
-7 1/8" V.I.F.
TYP.
A700
TYP
BE Project No.
Drawn By:
Drawing No.
Drawing Title t 312.440.2300 f 312.440.2303 www.baileyedward.com
35 East Wacker Dr Suite 2800 Chicago, IL 60601-2308
©2018 Bailey Edward Design Design Firm License No. 184-001962
Structural Engineer IMEG Corp.
15 Sunnen Dr. Suite 104 St. Louis, MO 63143 314-645-1132
SHEET
FLOOR PLANS AND
ELEVATIONS - DEMO
D100
USGS OAG A3 MAIN
BUILDING STABILIZATION
18018
KH
Columbia Environmental Research Center (CERC) 4200 E New Haven Rd.
Columbia, MO 65201
DEMOLITION PLAN LEGEND
1/8" = 1'-0"
BASEMENT PLAN - DEMO
0 4' 8' 16'
1/8" = 1'-0"
GROUND FLOOR - DEMO
1/8" = 1'-0"
ROOF - DEMO
1/8" = 1'-0"
GROUND FLOOR RCP - DEMO
1/8" = 1'-0"
PARTIAL ELEVATION - NORTH - DEMO
1/8" = 1'-0"
PARTAIL ELEVATION - EAST - DEMO
KEYNOTES - DEMO
01.01 EXTERIOR WALLS NEED TO BE PROTECTED DURING DEMOLITION AND
CONSTRUCTION, TYP.
01.02 COMPUTER SERVICE TO REMAIN WHILE UNDER CONSTRUCTION. MAINTAIN
COOLING TEMPERATURE FOR IT SERVER ROOM THROUGHOUT ALL ROOF
CONSTRUCTION.
01.03 WOOD TRELLIS TO BE REMOVED AND SALVAGED BY USGS PRIOR TO DEMO.
01.04 ELECTRICAL CONDUIT AND BOXES, SECURITY CAMERAS AND OTHER DEVICES TO
BE REMAIN. ELECTRICAL SERVICES TO THE BUILDING ARE NOT TO BE
INTERRUPTED DURING DEMO.
02.03 REMOVE DOORS AND FRAMES DURING DEMO AND REINSTALL EXISTING DOOR
AND HARDWARE. CHECK SWING.
02.04 DEMOLISH EXISTING SLAB. REMOVE HIGH PLASTIC CLAYS BENEATH THE SLABS,
RE-PREPARE THE SUBGRADE SOILS BY MOISTURE CONDITIONING AND
RECOMPACTING, AND RECONSTRUCT SLAB, SEE STRUCT. DWGS.
02.05 DEMOLISH EXISTING CEILING GRID, ACT PANELS AND LIGHTS. PROTECT,
REINSTALL EXISTING SPRINKLERS AND CEILING DEVICES.
02.06 DEMOLISH EXISTING METAL GRAVEL STOP, FLASHING AND BLOCKING.
02.07 DEMOLISH FOAMED-IN-PLACE ROOFING SYSTEM COATING AND INSLULATION TO
EXIST DECK, VIF, ALONG GRAVEL.
02.08 DEMOLISH BRICK FACADE AND REPLACE WITH NEW BRICKS AND BRICK TIES. NEW
BRICKS ARE TO MATCH EXISTING IN SIZE, COLOR AND TEXTURE, SEE ARCH.
SECTION AND DETAIL SHEET FOR MORE INFORMATION.
02.09 SAWCUT AND DEMOLISH EXISTING APPROX. 12'X 12' (VIF) CONCRETE PADS ALONG
DOORS.
02.10 REMOVE WINDOWS TO BE SALVAGED FOR REALIGNMENT IN FACADE.
02.11 REMOVE PRECAST PANELS ABOVE WINDOW TO BE SALVAGED FOR REALIGNMENT
IN FACADE.
02.17 EXISTING PRECAST PANEL BETWEEN WINDOWS TO REMAIN. PROTECT PRECAST
PANEL DURING REMOVAL AND REINSTALLATION OF WINDOWS AND PRECAST
ABOVE.
02.18 EXPOSED EXISTING CONCRETE FOUNDATION WALL TO REMAIN.
02.19 EXISTING SLOPED METAL SILL TO REMAIN. MATCH FINISH AS REQUIRED.
GENERAL NOTES - DEMOLITION
3/8" = 1'-0"
TYP. WINDOW DEMO
REVISION
MARK DESCRIPTION DATE
AREA OF FLOOR SLAB AND FILL REMOVAL
AND REPLACE WITH NEW.
NEW WALL
EXISTING WALL TO REMAIN
EXISTING DOOR AND FRAME TO REMAIN
NEW DOOR AND FRAME
AREA NOT IN SCOPE OF WORK
HGFEDC J KD1C5B8B3BA
E1 E9
4.5
4.7
B2 B9 H1 H7D2 D9
6.5
19' - 7" 20' - 3" 15' - 10" 15' - 10" 15' - 10" 15' - 10" 15' - 10" 19' - 9" 20' - 1"
5.6
4" DIA. PIPE COLUMN4" DIA. PIPE COLUMN
4" DIA. PIPE COLUMN
5'
4'
9'
3'
6'
/4
9'
9'
ELEV.
UP
UP
MECH.
UP
UP
-10' - 8"
-13' - 5"
-10' - 8"
-13' - 5"
5' - 4"
3' - 4"
4'
5'
5'
4'
UNEXCAVATED
UNEXCAVATED
AREA OF WORK
HGFEDC J KD1C5B8B3BA
E1 E9
4.5
4.7
B2 B9 H1 H7D2 D9
6.5
AA1 AA2
5.6
0"
DN
32' - 6" 6' - 7" 19' - 7" 7' - 0" 6" 10' - 2"
2' - 2" 5"
7' - 6" 8' - 4"
1' - 10" 1' - 7"
11' - 6" 11"
1' - 8"
12' - 6" 1' - 8" 15' - 10" 15' - 10" 5" 12' - 10" 6' - 6" 20' - 1"
5'
4'
9'
3'
6'
/4
9'
9'
4" DIA. PIPE COLUMN
4" DIA. PIPE COLUMN
DN
MECH.
ELEV.
RECEPTION
MAIN
ENTRANCE
A600
A6006
TWO SIDED ELEVATOR OPENS TO OUTSIDE
WET LABORATORY
PATIO / SIDE
ENTRANCE FOR
CONTRACTOR
ACCESS
32.0332.03
MAIN LOBBY PUBLIC
STAIR TO BASEMENT
AREA OF WORK
AREA OF INTERIOR WORK
32.0132.01
32.01
32.0132.01
WOOD TRELLIS TO BE
SALVAGED BY USGS
PRIOR TO DEMO
32.02
32.02
32.02
A. GENERAL
1. DETAILS SHOWN ARE INDICATIVE OF THE CHARACTER, PROFILES, MATERIALS AND SYSTEMS REQUIRED FOR THE
WORK INCLUDING THOSE CONDITIONS NOT COVERED BY SPECIFIC DETAILS.
2. WHERE THE DESIGN INTENT CANNOT BE DETERMINED BY THE CONTRACTORS FROM THE DRAWINGS OR
SPECIFICATIONS. CONSULT THE CONTRACTING OFFICER BEFORE PROCEEDING WITH THE WORK.
3. ALL ITEMS, EQUIPMENT, APPLIANCES, AND APPARATUS SHALL REMAIN THE PROPERTY OF THE USGS. VERIFY THOSE ITEMS TO REMAIN AND CAREFULLY DISASSEMBLE, SALVAGE AND/OR STORE ON SITE OR AS DIRECTED BY THE USGS. DO NOT DISPOSE OF ANY ITEMS WITHOUT CONFIRMATION. CONTRACTOR SHALL PROVIDE USGS WITH 30 DAYS NOTICE FOR APPROPRIATE GOVERNMENT AGENCIES TO BE ABLE TO DISASSEMBLE, SALVAGE AND STORE THEIR
ROOF TOP EQUIPMENT.
4. WHERE DRAWING INDICATES "REPAIR" OR "REPLACE", UNLESS NOTED OTHERWISE, DO SO WITH IN-KIND MATERIALS THAT MATCH THE EXISTING CONDITIONS WITH RESPECT TO MATERIAL, TYPE, THICKNESS, FINISH AND/OR TEXTURE.
5. THE ARCHITECT AND USGS SHALL BE THE JUDGE OF THE RELATIVE HISTORIC SIGNIFICANCE OF ANY FEATURE. NO ELEMENT SHALL BE ALTERED, REMOVED, REUSED OR TAKEN FROM THE PREMISES WITHOUT PRIOR APPROVAL OF THE
ARCHITECT AND USGS.
6. CONTRACTORS SHALL NOT PROCEED WITH ANY ADDITIONAL WORK OR WORK THAT MIGHT RESULT IN AN ADDITIONAL COST TO THE OWNER WITHOUT PRIOR WRITTEN APPROVAL FROM THE USGS CONTRACTING OFFICER.
7. TESTS AND INSPECTIONS DURING CONSTRUCTION TO BE PROVIDED BY THE CONTRACTOR AT THE CONTRACTOR’S SOLE COST. REFERENCE SPECIFICATION SECTION 01 10 00, ‘SUMMARY, SECTION 01 40 00, “QUALITY REQUIREMENTS,”
AND THE TECHNICAL SPECIFICATIONS SECTIONS FOR REQUIREMENTS.
B. DIMENSIONING
1. DO NOT SCALE DRAWINGS. WHERE THERE APPEARS TO BE A CONFLICT BETWEEN DIMENSIONS OR WHERE DIMENSIONS CANNOT BE DETERMINED FROM THE DRAWINGS, CONSULT THE CONTRACTING OFFICER BEFORE
PROCEEDING WITH THE WORK.
2. EXISTING BUILDING DIMENSIONS ARE SHOWN FOR REFERENCE ONLY. EXISTING DIMENSIONS IN FIELD MAY VARY.
VERIFY ALL EXISTING DIMENSIONS IN FIELD.
C. ROOF – GENERAL
1. PROVIDE 4'X4' MIN. ROOFING SYSTEM MOCK-UPS AT ROOFS A, B, AND E. LOCATION TO BE SELECTED BY ARCHITECT.
3. THE ROOF SHALL BE A COMPLETE ENCLOSURE SYSTEM, PROVIDING MOISTURE, THERMAL AND VAPOR BARRIERS.
THESE SHALL INCLUDE ALL CONNECTIONS, ANCHORS, FASTENERS, COPING, INSULATION, AND SEALANTS.
7. ALL MATERIALS, WHICH MAY CAUSE STAINING, DISCOLORING, DEGRADATION OR OTHER DETRIMENTAL EFFECTS
WHEN IN CONTACT SHALL BE EFFECTIVELY ISOLATED FROM EACH OTHER.
8. THE COLOR, CHARACTER, AND FINISH OF THE ROOF AND EDGE METAL MATERIALS SHALL MATCH THE ARCHITECT’S
SAMPLES AND IN-KIND TO EXISTING CONDITIONS.
D. STAGING AREA
1. COORDINATE STAGING AREA REQUIREMENTS AND USE WITH OWNER'S FACILITY STAFF. PROTECT EXISTING
BUILDINGS HARDSCAPE AND LANDSCAPE AT STAGING AREA AS REQUIRED.
USGS OAG A3
MAIN BUILDING
MAIN
ENTRANCE
SIDE ENTRANCE
STAGING AREAAREA OF WORK
BE Project No.
Drawn By:
Drawing No.
Drawing Title t 312.440.2300 f 312.440.2303 www.baileyedward.com
35 East Wacker Dr Suite 2800 Chicago, IL 60601-2308
©2018 Bailey Edward Design Design Firm License No. 184-001962
Structural Engineer IMEG Corp.
15 Sunnen Dr. Suite 104 St. Louis, MO 63143 314-645-1132
SHEET
FLOOR PLANS - NEW
AND SITE MAP
A100
USGS OAG A3 MAIN
BUILDING STABILIZATION
18018
KH
Columbia Environmental Research Center (CERC) 4200 E New Haven Rd.
Columbia, MO 65201
0 6" 1'
NEW WORK PLAN LEGEND
1/16" = 1'-0"
BASEMENT FLOOR PLAN
1/16" = 1'-0"
GROUND FLOOR PLAN
KEYNOTES - NEW WORK
32.01 REMOVE EXISTING LAWN AND TOPSOIL AT AREA OF WORK AT FAÇADES.
REMOVE FULL WIDTH OF FAÇADE AND DISTANCE FROM FAÇADE AS
REQUIRED FOR THE WORK. STOCKPILE EXISTING TOPSOIL FOR REUSE.