B08_Attach_3_PGLSR_Construction_Drawings.pdf

PDF 7 MB Posted

Attached to
PUNTA GORDA LIGHTHOUSE REHABILITATION
Solicitation number
140L1222R0002
Issued by

About this file

This document package includes construction drawings and specifications for the Punta Gorda Lighthouse Rehabilitation project.

The project involves repair, restoration, stabilization, and seismic strengthening of the historic Punta Gorda Light Station structures. Work includes rehabilitation of the lighthouse tower and lantern room, as well as the adjacent oil house building. Structural repairs and seismic upgrades are designed to comply with the California Historic Building Code. Construction documents consist of architectural, civil, and structural drawings along with general notes providing project details, material requirements, testing and inspection protocols, and repair specifications.

The scope of work encompasses concrete repair and reinforcement replacement, structural steel repairs, full restoration of cast iron elements, and underpinning of existing foundation walls. The documents provide demolition plans, existing conditions information, repair details, and requirements for material submittals, testing and special inspections. Notes indicate that shoring and temporary supports are the contractor's responsibility. The project is funded by and construction managed by the Department of Interior Bureau of Land Management California office.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S E

H P ro je c t

C h e ck ed B y

D ra w n

B y

P ro je ct

S ta tu s

Is su e D at e

This drawing is an instrument of service and shall remain the property of Short Elliott Hendrickson, Inc.

(SEH). This drawing, concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of SEH.

Submission or distribution of this drawing to meet official or regulatory requirements or for purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH.

S ho rt E lli ot t H ed ric ks on , I nc

A ll

R ig ht s

R es er ve d

C O

P Y

R

IG

H T

3/

/2

2:

:5

P

M

COVER SHEET

G000

P u n ta

G o rd a

L ig h t

S ta ti o n R e h a b il it a ti o n

P et ro lia

, C A

LM

L

JH

/M

M

U N

IT

E D

S T A

T E S D

E P

A R

T M

E N

T O

F T

H E I N

T E R

IO

R

B U

R E A

U O

F L

A N

D M

A N

A G

E M

E N

T F

IN

A

L C

O N

S T

R U

C T

IO

N

D O

C U

M E

N T

S

.2

6.

S E

H P ro je c t

C h e ck ed B y

D ra w n

B y

P ro je ct

S ta tu s

Is su e D at e

This drawing is an instrument of service and shall remain the property of Short Elliott Hendrickson, Inc.

(SEH). This drawing, concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of SEH.

Submission or distribution of this drawing to meet official or regulatory requirements or for purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH.

S ho rt E lli ot t H ed ric ks on , I nc

A ll

R ig ht s

R es er ve d

C O

P Y

R

IG

H T

3/

/2

2:

:5

P

M

COVER SHEET

G000

P u n ta

G o rd a

L ig h t

S ta ti o n R e h a b il it a ti o n

P et ro lia

, C A

LM

L

JH

/M

M

U N

IT

E D

S T A

T E S D

E P

A R

T M

E N

T O

F T

H E I N

T E R

IO

R

B U

R E A

U O

F L

A N

D M

A N

A G

E M

E N

T F

IN

A

L C

O N

S T

R U

C T

IO

N

D O

C U

M E

N T

S

.2

6.

3/

/2

2:

:5

P

M

Punta Gorda Light Station Rehabilitation

Petrolia, CA 95558

UNITED STATES DEPARTMENT OF THE INTERIOR

BUREAU OF LAND MANAGEMENT

FINAL CONSTRUCTION DOCUMENTS

AREA REFERENCE MAP

DRAWING INDEX

ARCHITECTURAL

STRUCTURAL

A121 FLOOR PLAN & ROOF PLAN - OIL HOUSE

A211 EXTERIOR ELEVATIONS - LIGHTHOUSE

A212 EXTERIOR ELEVATIONS - LIGHTHOUSE

A221 EXTERIOR ELEVATIONS - OIL HOUSE

A311 BUILDING SECTIONS - LIGHTHOUSE

A321 BUILDING SECTIONS - OIL HOUSE

A001 GENERAL INFORMATION / ABBREVIATIONS AND LEGENDS

A051 ARCHITECTURAL SITE PLAN

A071 DEMOLITION PLANS - LIGHTHOUSE

A072 DEMOLITION PLANS - OIL HOUSE

A111 FLOOR PLANS - LIGHTHOUSE

A112 ROOF PLAN - LIGHTHOUSE

G000 COVER SHEET

S121 OIL HOUSE BUILDING FLOOR PLAN

S122 OIL HOUSE BUILDING ROOF PLAN

S211 LIGHTHOUSE BUILDING ELEVATIONS

S212 LIGHTHOUSE BUILDING ELEVATIONS

S213 LIGHTHOUSE BUILDING ELEVATIONS

S214 LIGHTHOUSE BUILDING ELEVATIONS

S221 OIL HOUSE BUILDING ELEVATIONS

S222 OIL HOUSE BUILDING ELEVATIONS

S223 OIL HOUSE BUILDING ELEVATIONS

S224 OIL HOUSE BUILDING ELEVATIONS

S311 RETAINING WALL & FOUNDATION DETAILS

S312 CONCRETE WALL & ROOF DETAILS

S321 REPAIR DETAILS

S001 TITLE AND SHEET INDEX

S002 GENERAL NOTES

S003 GENERAL NOTES

S004 GENERAL NOTES

S005 GENERAL NOTES

S011 TYPICAL DETAILS

SD121 OIL HOUSE BUILDING FIRST FLOOR DEMOLITION PLAN

SD122 OIL HOUSE BUILDING ROOF DEMOLITION PLAN

SD221 OIL HOUSE BUILDING WEST DEMOLITION ELEVATION

S111 LIGHTHOUSE BUILDING FLOOR PLAN

S112 LIGHTHOUSE BUILDING ROOF PLAN

S113 LANTERN ROOM PLANS

S120 OIL HOUSE BUILDING FOUNDATION PLAN

CIVIL

GENERAL

C 101 EXISTING CONDITIONS

C 102 CONSTRUCTION STAGING

C 103 DRAINAGE IMPROVEMENT PLAN

SHORT ELLIOTT HENDRICKSON

R ev is io n Is su e

R ev

D es cr ip tio n D at e

R ev is io n Is su e

R ev

D es cr ip tio n D at e

LOCATION MAP

PROJECT

LOCATION

PROJECT

LOCATION

EXISTING LIGHTHOUSE BUILDING

EXISTING KING RANGE

NATIONAL CONSERVATION

AREA SIGN

EXISTING CONCRETE PATH

CENTERLINE OF EXISTING DIRT PATH

EXISTING OIL HOUSE

EXISTING CONCRETE PAD

EXISTING CONCRETE PATH

EXISTING CONCRETE PAD

CENTERLINE OF EXISTING DIRT PATH

CENTERLINE OF EXISTING DIRT PATH

SE

H

Pr oj ec t #

Ch ec ke d

By Dr aw n

By

Pr oj ec t S ta tu s Iss ue D at e

This drawing is an instrument of service and shall remain the property of Short Elliott Hendrickson, Inc.

(SEH). This drawing, concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of SEH.

Submission or distribution of this drawing to meet official or regulatory requirements or for purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH. Sh or t E llio tt H ed ric ks on

, In c.

Al l R igh ts

Re se rve d

CO

PY

RI

GH

T

Pu nt a G or da

L ig ht S ta tio n Re ha bi lit at io n

Pe tro lia , C

A

W B

UN

ITE

D S

TA

TE

S D

EP

A

RT

M

EN

T

O F

TH

E

IN

TE

RI

O

R

BU

RE

A

U O

F

LA

N D

M A

N A

G

EM

EN

T

X:

\A

E\ B\

BL

MN

S\

\99 C ivi l\5

-fin al-ds gn

\51 -d ra wi ng s\P lan sh ee ts\

CD

s\E xis tin g C on dit ion s.d wg

3/

/20

1:

:36

P M

Pu nt a G or da

L ig ht S ta tio n Re ha bi lit at io n

Pe tro lia , C

A

TN

UN

ITE

D S

TA

TE

S D

EP

A

RT

M

EN

T

O F

TH

E

IN

TE

RI

O

R

BU

RE

A

U O

F

LA

N D

M A

N A

G

EM

EN

T

FI

NA

L C

ON

ST

RU

CT

IO

N

DO

CU

ME

NT

S

.26

.20

Re vis io n

Iss ue

Re v.

De sc rip tio n

Da te

Re vis io n

Iss ue

Re v.

De sc rip tio n

Da te feetscale

30 6030

EXISTING CONDITIONS

C 101

HORIZONTAL DATUM:

CALIFORNIA ZONE 1 (0401) STATE PLANE COORDINATE SYSTEM

NAD 1983 (CONUS) GEOID18

BASED ON GPS OBSERVATIONS.

DISTANCES SHOWN HEREON ARE GROUND DISTANCES, US SURVEY FEET,

SCALED ABOUT CONTROL POINT NO 1. TO CONVERT TO GRID DISTANCES

MULTIPLY BY THE COMBINED FACTOR OF 0.9999488842.

VERTICAL DATUM:

NORTH AMERICAN VERTICAL DATUM OF 1988 (NAVD88)

BASED ON STATIC GNSS OBSERVATIONS PROCESSED THROUGH NATIONAL

GEODETIC SURVEY (NGS) ONLINE POSITIONING USER SERVICES (OPUS)

NOTES:

1. FIELD WORK WAS COMPLETED ON JANUARY 14, 2021.

CONTROL POINT TABLE

POINT NO. NORTHING EASTING ELEV. DESCRIPTION

1 1985764.18 5903257.30 25.90

CP_RPC

2 1982967.47 5905561.69 28.42

CP_RPC

3 1982838.49 5905708.81 26.31

CP_RPC

4 1982825.70 5905747.11 27.10

CP_X

EXISTING LIGHTHOUSE BUILDING

EXISTING KING RANGE

NATIONAL CONSERVATION

AREA SIGN

EXISTING CONCRETE PATH

CENTERLINE OF EXISTING DIRT PATH

EXISTING OIL HOUSE

EXISTING CONCRETE PAD

EXISTING CONCRETE PATH

EXISTING CONCRETE PAD

CENTERLINE OF EXISTING DIRT PATH

CENTERLINE OF EXISTING DIRT PATH

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

TEMPORARY HIGH-VISIBILITY FENCE

TEMPORARY HIGH-VISIBILITY FENCE

9.7%

LEVEL GROUND FOR STORAGE

AND EQUIPMENT PARKING

GATE

GATE

SE

H

Pr oj ec t #

Ch ec ke d

By Dr aw n

By

Pr oj ec t S ta tu s Iss ue D at e

This drawing is an instrument of service and shall remain the property of Short Elliott Hendrickson, Inc.

(SEH). This drawing, concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of SEH.

Submission or distribution of this drawing to meet official or regulatory requirements or for purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH. Sh or t E llio tt H ed ric ks on

, In c.

Al l R igh ts

Re se rve d

CO

PY

RI

GH

T

Pu nt a G or da

L ig ht S ta tio n Re ha bi lit at io n

Pe tro lia , C

A

W B

UN

ITE

D S

TA

TE

S D

EP

A

RT

M

EN

T

O F

TH

E

IN

TE

RI

O

R

BU

RE

A

U O

F

LA

N D

M A

N A

G

EM

EN

T

X:

\A

E\ B\

BL

MN

S\

\99 C ivi l\5

-fin al-ds gn

\51 -d ra wi ng s\P lan sh ee ts\

CD

s\C on str uc tio n S tag ing .dw g

/20

1:

:58 P

M

Pu nt a G or da

L ig ht S ta tio n Re ha bi lit at io n

Pe tro lia , C

A

TN

UN

ITE

D S

TA

TE

S D

EP

A

RT

M

EN

T

O F

TH

E

IN

TE

RI

O

R

BU

RE

A

U O

F

LA

N D

M A

N A

G

EM

EN

T

FI

NA

L C

ON

ST

RU

CT

IO

N

DO

CU

ME

NT

S

.26

.20

Re vis io n

Iss ue

Re v.

De sc rip tio n

Da te

Re vis io n

Iss ue

Re v.

De sc rip tio n

Da te feetscale

30 6030

CONSTRUCTION STAGING

C 102

49.81

40.59

MATCH EX

GRADE TO DRAIN

TO DAYLIGHT

EXISTING

OIL HOUSE

50.20

6.0'

47.77

47.64

47.48

48.01

50.05

50.44

47.93

41.97

PERIMETER DRAIN, SEE DETAIL THIS SHEET

23.6 LF 4" PERFORATED

PIPE @ 1.0%

INVERT = 38.27

MATCH EXISTING

INSTALL

" x

" GALVANIZED HARDWARE

CLOTH WIRE MESH RODENT PROTECTION

WITH STAINLESS STEEL HOSE CLAMP

90° BEND TURNED DOWN 22.5°

INVERT = 43.15

34.6 LF 4" PERFORATED PIPE @ 1.0%

90° BEND TURNED DOWN 22.5°

INVERT =43.50

27.5 LF 4" PERFORATED PIPE @ 1.0%

INVERT = 38.23 MATCH EXISTING

INSTALL

" x

" GALVANIZED HARDWARE CLOTH WIRE MESH

RODENT PROTECTION WITH STAINLESS STEEL HOSE CLAMP

EXISTING STAIRS TO REMAIN

EXISTING RETAINING

WALL TO BE

RECONSTRUCTED, SEE

STRUCTURAL

EXISTING SIDEWALK

TO BE

RECONSTRUCTED,

SEE STRUCTURAL

LIMITS OF CONSTRUCTION

6.0'

4.0'

2.0'

MATCH EXISTING

4:1 MAX SLOPE

R3.0'

5.0'

4" 22.5° VERTICAL BEND

INVERT = 38.5

9.1 LF 4" PERFORATED PIPE @ 51.0%

4" 22.5° VERTICAL BEND

INVERT = 38.5

9.8 LF 4" PERFORATED PIPE @ 51.0%

TEMPORARY SILT FENCE

TEMPORARY

HIGH-VISIBILITY

FENCE

X

X

X

X

X

EXISTING

LIGHT

HOUSE

54.87

54.68

54.12

MATCH EX

GRADE TO DRAIN TO DAYLIGHT

55.02

55.77

55.63

54.95

54.48

3.0'

3.0'

EXISTING KING RANGE

NATIONAL CONSERVATION

AREA SIGN

EXISTING SIDEWALK

TO REMAIN

LIMITS OF CONSTRUCTION

MATCH EXISTING

4:1 MAX SLOPE

R6.0'

2.0'

TEMPORARY SILT FENCE

TEMPORARY HIGH-VISIBILITY FENCE

X

X

X

X

X

X feetscale

5 105

2.5

SE

H

Pr oj ec t #

Ch ec ke d

By

Dr aw n By

Pr oj ec t S ta tu s Iss ue D at e

This drawing is an instrument of service and shall remain the property of Short Elliott Hendrickson, Inc.

(SEH). This drawing, concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of SEH.

Submission or distribution of this drawing to meet official or regulatory requirements or for purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH. Sh or t E llio tt H ed ric ks on

, In c.

Al l R igh ts

Re se rve d

CO

PY

RI

GH

T

Pu nt a G or da

L ig ht S ta tio n Re ha bi lit at io n

Pe tro lia , C

A

W B

UN

ITE

D S

TA

TE

S D

EP

A

RT

M

EN

T

O F

TH

E

IN

TE

RI

O

R

BU

RE

A

U O

F

LA

N D

M A

N A

G

EM

EN

T

X:

\A

E\ B\

BL

MN

S\

\99 C ivi l\5

-fin al-ds gn

\51 -d ra wi ng s\P lan sh ee ts\

CD

s\1

2_ Dr ain ag e I mp ro ve me nt pla n.d wg

/20

1:

:25 P

M

Pu nt a G or da

L ig ht S ta tio n Re ha bi lit at io n

Pe tro lia , C

A

TN

UN

ITE

D S

TA

TE

S D

EP

A

RT

M

EN

T

O F

TH

E

IN

TE

RI

O

R

BU

RE

A

U O

F

LA

N D

M A

N A

G

EM

EN

T

FI

NA

L C

ON

ST

RU

CT

IO

N

DO

CU

ME

NT

S

.26

.20

Re vis io n

Iss ue

Re v.

De sc rip tio n

Da te

Re vis io n

Iss ue

Re v.

De sc rip tio n

Da te

C 103

PERIMETER DRAIN

NTS

BUILDING FOOTING

SEE STRUCTURAL PLAN

24"

VARIES

4"

6"

4" DIA. PERFORATED PVC

(SLOPE 0.5% MIN.)

4"

6" 6"

2.0% M

IN.

PROPOSED GRADE

6"

EXISTING GRADE

CLEAN, FREE

DRAINING AASHTO

NO. 57 AGGREGATE

DRAINAGE IMPROVEMENT PLAN

DIMENSIONS FOR SLOTTED PIPE

PIPE SIZE 4"

SLOT LENGTH 1-1/16"

MAXIMUM SLOT WIDTH 0.032"

SLOT CENTERS 0.413"

OPEN AREA (PER FOOT) 1.90 IN2

PIPE MUST CONFORM TO REQUIREMENTS OF ASTM DESIGNATION F949. THERE SHALL BE NO EVIDENCE OF SPLITTING, CRACKING, OR BREAKING WHEN THE PIPE IS TESTED PER ASTM TEST METHOD D2412 IN ACCORDANCE WITH F949 SECTION

7.5 AND ASTM F794 SECTION 8.5. CONTECH A-2000 SLOTTED PIPE (OR EQUAL).

PHYSICAL REQUIREMENTS FOR SEPARATOR FABRIC

PROPERTY

CLASS B

TEST

METHOD

ELONGATION

< 50%

ELONGATION

> 50%

GRAB STRENGTH, N (LBS) 800 (180) 510 (115)

ASTM D 4632

PUNCTURE RESISTANCE, N (LBS) 310 (70) 180 (40)

ASTM D 4833

TRAPEZOIDAL TEAR STRENGTH, N (LBS) 310 (70) 180 (40)

ASTM D 4533

APPARENT OPENING SIZE, mm; (US SIEVE SIZE) AOS < 0.3 mm (US SIEVE SIZE NO. 50)

ASTM D 4751

PERMITTIVITY, SEC-1

0.02 ASTM D 4491

PERMEABILITY, CM/SEC

k FABRIC > k SOIL FOR ALL CLASSES ASTM D 4491

ULTRAVIOLET DEGRADATION AT 500 HOURS 50% STRENGTH RETAINED FOR ALL CLASSES ASTM D 4355

SEPARATOR FABRIC

SURROUNDING

AGGREGATE,

OVERLAP 12" MIN ON TOP

SECTION

REFERENCE:

DETAIL

REFERENCE:

DETAIL

REFERENCE:

REVISION

IDENTIFICATION:

S3.4

DETAIL NUMBER

SHEET NUMBER

S3.4

S3.4

WALL

ELEVATION:

WALL

SECTION:

BUILDING

SECTION:

S3.4

DETAIL NUMBER

SHEET NUMBER

S3.4

S3.4

S3.4

REVISION NUMBER REVISION SHEET NUMBER1 RS-12

MATERIALS

SHOWN ON

PLANS:

CAST-IN-PLACE CONCRETE

EXISTING CONCRETE

CONCRETE MASONRY UNITS

BRICK MASONRY UNITS

STEEL MEMBERS

WOOD OR METAL STUDS

MATERIALS

SHOWN ON

DETAILS:

CAST-IN-PLACE

CONCRETE

IN SECTION

C.I.P. CONCRETE

IN ELEVATION

EXISTING

CONCRETE

IN SECTION

CONCRETE

MASONRY UNITS

IN PLAN

CONCRETE

MASONRY UNITS

IN SECTION

CMU OR

BRICK

IN ELEVATION

BRICK

MASONRY UNITS

IN SECTION

WIDE FLANGE

SECTION

CHANNEL

SECTION

TUBE

SECTION

PIPE

SECTION

ANGLE

SECTION

METAL STUD

OR JOIST

WOOD STUD

OR JOIST

STUD WALL w/

PLYWOOD

SHEATHING

CONTIN

WOOD

MEMBER

WOOD

BLOCKING

GLU-LAM

SECTION

TRUSS

JOIST

SAND ROCK EARTH

KEY NOTES: C1 KEY NOTE NUMBER

A.B. ANCHOR BOLT

ACI AMERICAN CONCRETE INSTITUTE

A.D. AREA DRAIN

ADDL ADDITIONAL

ADJ ADJACENT

A.F.F. ABOVE FINISH FLOOR

AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION

ALT ALTERNATE

APPROX APPROXIMATELY OR APPROXIMATE

ARCH ARCHITECT OR ARCHITECTURAL

ASPH ASPHALT

ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS

A.C. ASPHALTIC CONCRETE, AIR CONDITION

BAL BALANCE

B.L. BOTTOM LOWER

BLDG BUILDING

BLK BLOCK

BLKG BLOCKING

BM BEAM

B.O. BOTTOM OF

BOT BOTTOM

B.P. BREAK POINT

BRD BOARD

BRG BEARING

BRKT BRACKET

BTWN BETWEEN

B.U. BOTTOM UPPER

C CHANNEL

CBC CALIFORNIA BUILDING CODE

C.I.P. CAST IN PLACE

C.J. CONSTRUCTION OR CONTROL JOINT

CLG CEILING

CL CENTER LINE

CLR CLEAR

CMU CONCRETE MASONRY UNIT

COL COLUMN

CONC CONCRETE

CONN CONNECTION

CONSTR CONSTRUCTION

CONTIN CONTINUOUS

C.J.P. COMPLETE JOINT PENETRATION

CTR CENTER

CTRD CENTERED

CTRSNK COUNTERSINK

d PENNY WEIGHT

DBL DOUBLE

DEPR DEPRESSION

D.F. DOUGLAS FIR

DIA or DIAMETER

DIAG DIAGONAL

DIM DIMENSION

DL DEAD LOAD

DN DOWN

do DITTO

D.W.F. DEFORMED WIRE FABRIC

DWG DRAWING

(E) EXISTING

EA EACH

E.F. EACH FACE

E.J. EXPANSION JOINT

EL ELEVATION

ELEC ELECTRICAL

ELEV ELEVATOR

EMBED EMBEDMENT

E.N. EDGE NAIL

ENCL ENCLOSURE

ENGR ENGINEER

E.O. EDGE OF

E.O. MAS EDGE OF MASONRY

E.O. PL EDGE OF PLATE

E.O. SLAB EDGE OF SLAB

EQ EQUAL

EQPT EQUIPMENT

E.W. EACH WAY

EXP EXPANSION

EXT EXTERIOR

F.D. FLOOR DRAIN

FDN FOUNDATION

F.F. FINISH FLOOR

FIN FINISH

FLR FLOOR

F.O. FACE OF

F.O. CONC FACE OF CONCRETE

F.O. MAS FACE OF MASONRY

F.O. STUD FACE OF STUD

FRMG FRAMING

F.S. FAR SIDE

FT FOOT OR FEET

FTG FOOTING

GA GAGE

GALV GALVANIZED

G.B. GRADE BEAM

GLB GLUED LAMINATED BEAM

GLC GLUED LAMINATED COLUMN

GR GRADE

GYP GYPSUM

HDR HEADER

HGR HANGER

HK HOOK

HORIZ HORIZONTAL

H.P. HIGH POINT

H.R. HARD ROCK

HSS HOLLOW STRUCTURAL SECTION

HT HEIGHT

I MOMENT OF INERTIA

I.D. INSIDE DIAMETER

I.F. INSIDE FACE

INFO INFORMATION

INSUL INSULATION

INT INTERIOR

JST JOIST

JT JOINT

KIPS 1000 POUNDS

KSF KIPS PER SQUARE FOOT

L ANGLE

LBS POUNDS

LL LIVE LOAD

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

LONGIT LONGITUDINAL

L.P. LOW POINT

L.S. LOW SHRINKAGE

LSL LAMINATED STRAND LUMBER

LT LIGHT

LVL LAMINATED VENEER LUMBER

LTWT LIGHT WEIGHT

MACH MACHINE

MAS MASONRY

MATL MATERIAL

MAX MAXIMUM

M.B. MACHINE BOLT

MC MISCELLANEOUS CHANNEL

M.D. MID-DEPTH

MECH MECHANICAL

M.F. MOMENT FRAME

MFR MANUFACTURER

MIN MINIMUM

MISC MISCELLANEOUS

MTL METAL

(N) NEW

N.A. NOT APPLICABLE

N.I.C. NOT IN CONTRACT

NO. NUMBER

N.P. NO PROFILE

N.S. NEAR SIDE

N.T.S. NOT TO SCALE

o.c. ON CENTER

O.D. OUTSIDE DIAMETER

O.F. OUTSIDE FACE

O.H. OPPOSITE HAND

OPNG OPENING

OPP. OPPOSITE

OSB ORIENTED STRAND BOARD

O.W.S.G. OPEN WEB STEEL GIRDER

O.W.S.J. OPEN WEB STEEL JOIST

PAR PARAPET

PC PIECE

P/C PRECAST

PCF POUND PER CUBIC FOOT

P.D.F. POWDER DRIVEN FASTENER

P.D.P. POWDER DRIVEN PIN

PL PROPERTY LINE OR PLATE

PLF POUNDS PER LINEAR FOOT

PLY PLYWOOD

PLYWD PLYWOOD

P.J.P. PARTIAL JOINT PENETRATION

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PSL PARALLEL STRAND LUMBER

P/T POST-TENSIONED

P.T. PRESSURE TREATED

P.T.D.F. PRESSURE TREATED DOUGLAS FIR

R RADIUS

R.D. ROOF DRAIN

RDWD REDWOOD

REF REFERENCE

REINF REINFORCING

REQD REQUIRED

REV REVISION

RF ROOF

RM ROOM

R.O. ROUGH OPENING

S SECTION MODULUS

S.A.D. SEE ARCHITECTURAL DRAWINGS

S.C.D. SEE CIVIL DRAWINGS

SCHED SCHEDULE

S.E.D. SEE ELECTRICAL DRAWINGS

SF SQUARE FEET

SHT SHEET

SHTG SHEATHING

SIM SIMILAR

S.J. SHRINKAGE JOINT, SEISMIC JOINT OR SLIP JOINT

S.L.D. SEE LANDSCAPE DRAWINGS

S.M.D. SEE MECHANICAL DRAWINGS

S.M.F. SPECIAL MOMENT FRAMES

S.M.S. SHEET METAL SCREW

S.O.G. SLAB ON GRADE

SP SPACE OR SPACING

S.P.D. SEE PLUMBING DRAWINGS

SPEC SPECIFICATION

SQ. SQUARE

S.S.D. SEE STRUCTURAL DRAWINGS

STAGG STAGGERED

STD STANDARD

STIFF STIFFENER

STL STEEL

STRUCT STRUCTURAL

SYM SYMMETRIC

T & B TOP AND BOTTOM

T & G TONGUE AND GROOVE

T.B. TIE BEAM

THK THICK

THRU THROUGH

T.L. TOP LOWER

T.O. TOP OF

T.O.T.S. TOP OF TOPPING SLAB

T.O. CONC TOP OF CONCRETE

T.O. PAR TOP OF PARAPET

T.O. PLY TOP OF PLYWOOD

T.O. PL TOP OF PLATE

T.O. SLAB TOP OF SLAB

T.O. STL TOP OF STEEL

TRANS TRANSVERSE

TS TUBE STEEL

T.U. TOP UPPER

TYP TYPICAL

UBC UNIFORM BUILDING CODE

U.N.O. UNLESS NOTED OTHERWISE

V.B. VAPOR BARRIER

VENT VENTILATION

VERT VERTICAL

V.I.F. VERIFY IN FIELD

W WIDE FLANGE

w/ WITH w/o WITHOUT

WD WOOD

WF WIDE FLANGE

W.P. WORK POINT

W.P.J. WEAKENED PLANE JOINT

WT WEIGHT OR STRUCTURAL T

W.W.F. WELDED WIRE FABRIC

45 Fremont Street, 28th Floor

San Francisco, CA 94105

415.989.1004 | kpff.com

S T R U C T U R A

L

MO

NAG

M N

AM

ES

A J

No. 3957R E

G

IS

TE

RED

PROFESSIONAL

EN

G

IN

E

E R

AI

NROFILACFOETAT

S

S E

H P ro je c t

C h e ck ed B y

D ra w n

B y

P ro je ct

S ta tu s

Is su e D at e

This drawing is an instrument of service and shall remain the property of Short Elliott Hendrickson, Inc.

(SEH). This drawing, concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of SEH.

Submission or distribution of this drawing to meet official or regulatory requirements or for purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH.

S ho rt E lli ot t H ed ric ks on , I nc

A ll

R ig ht s

R es er ve d

C O

P Y

R

IG

H T

P#: 2000199.00

3/

/2

4:

:0

P

M

TITLE AND SHEET INDEX

S001

P u n ta

G o rd a

L ig h t

S ta ti o n R e h a b il it a ti o n

P et ro lia

, C A

62 D A

A R

U N

IT

E D

S T A

T E S D

E P

A R

T M

E N

T O

F T

H E I N

T E R

IO

R

B U

R E A

U O

F L

A N

D M

A N

A G

E M

E N

T

LIGHT STATION

REHABILITATION

PETROLIA, CA

ABBREVIATIONS

SYMBOLS SHEET INDEX

D E S

IG

N

D O C U M E N T S

F

IN

A L

C O N S T R U C

TI

O N

D O C U M E N T S

S001 TITLE AND SHEET INDEX √ √

S002 GENERAL NOTES √ √

S003 GENERAL NOTES √ √

S004 GENERAL NOTES √ √

S005 GENERAL NOTES - √

S011 TYPICAL DETAILS √ √

SD121 OIL HOUSE BUILDING FIRST FLOOR DEMOLITION PLAN - √

SD122 OIL HOUSE BUILDING ROOF DEMOLITION PLAN - √

SD221 OIL HOUSE BUILDING WEST DEMOLITION ELEVATION - √

S111 LIGHTHOUSE BUILDING FLOOR PLAN √ √

S112 LIGHTHOUSE BUILDING ROOF PLAN √ √

S113 LANTERN ROOM PLANS √ √

S120 OIL HOUSE BUILDING FOUNDATION PLAN - √

S121 OIL HOUSE BUILDING FLOOR PLAN √ √

S122 OIL HOUSE BUILDING ROOF PLAN √ √

S211 LIGHTHOUSE BUILDING ELEVATIONS √ √

S212 LIGHTHOUSE BUILDING ELEVATIONS √ √

S213 LIGHTHOUSE BUILDING ELEVATIONS √ √

S214 LIGHTHOUSE BUILDING ELEVATIONS - √

S221 OIL HOUSE BUILDING ELEVATIONS √ √

S222 OIL HOUSE BUILDING ELEVATIONS √ √

S223 OIL HOUSE BUILDING ELEVATIONS √ √

S224 OIL HOUSE BUILDING ELEVATIONS - √

S311 RETAINING WALL & FOUNDATION DETAILS √ √

S312 CONCRETE WALL & ROOF DETAILS - √

S321 REPAIR DETAILS - √

# TITLE

SHEET INDEX

ISSUE LOG

ISSUE LOG KEY

' √ ' ISSUED AS PART OF A SET

' — ' NOT A PART OF ISSUED SET

' * ' ISSUED FOR INFORMATION ONLY

' o ' PREVIOUSLY SUBMITTED FOR PLAN CHECK

& PROVIDED FOR INFORMATION ONLY D

A

TE

R ev is io n Is su e

R ev

D es cr ip tio n D at e

SHORT ELLIOTT HENDRICKSON

F

IN

A L C

ON

ST

RU

CT

IO

N

DO

CU

ME

NT

S

.2 6.

GENERAL

DIMENSIONS REFER TO ROUGH CONCRETE SURFACES, FACE OF STUDS, FACE OF CONCRETE

BLOCK, TOP OF SHEATHING, OR TOP OF SLAB, UNLESS OTHERWISE INDICATED. THE CONTRACTOR

SHALL VERIFY ALL DIMENSIONS PRIOR TO THE START OF CONSTRUCTION. THE GOVERNMENT

SHALL BE NOTIFIED OF ANY DISCREPANCIES OR INCONSISTENCIES.

ALL DRAWINGS ARE CONSIDERED TO BE A PART OF THE CONTRACT DOCUMENTS. THE

CONTRACTOR SHALL BE RESPONSIBLE FOR THE REVIEW AND COORDINATION OF ALL DRAWINGS

AND SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES THAT OCCUR

SHALL BE BROUGHT TO THE ATTENTION OF THE GOVERNMENT PRIOR TO THE START OF

CONSTRUCTION SO THAT A CLARIFICATION CAN BE ISSUED. ANY WORK PERFORMED IN CONFLICT

WITH THE CONTRACT DOCUMENTS OR ANY CODE REQUIREMENTS SHALL BE CORRECTED BY THE

CONTRACTOR AT HIS OWN EXPENSE AND AT NO EXPENSE TO THE GOVERNMENT.

NOTES AND DETAILS ON THE STRUCTURAL DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL

NOTES AND TYPICAL DETAILS. WHERE NO DETAILS ARE GIVEN, CONSTRUCTION SHALL BE AS

SHOWN FOR SIMILAR WORK.

ALL WORK SHALL CONFORM TO THE MINIMUM STANDARDS OF THE FOLLOWING CODES:

2019 CALIFORNIA BUILDING CODE, WHICH COMPRISES TITLE 24, PART 2 OF THE CALIFORNIA CODE

OF REGULATIONS, AS ADOPTED BY THE CALIFORNIA BUILDING STANDARDS COMMISSION REFERRED

TO HERE AS "THE CALIFORNIA BUILDING CODE, 2019 EDITION" OR "THE CODE", AND ANY OTHER

REGULATING AGENCIES WHICH HAVE AUTHORITY OVER ANY PORTION OF THE WORK, INCLUDING

THE STATE OF CALIFORNIA DIVISION OF INDUSTRIAL SAFETY, AND THOSE ADDITIONAL CODES AND

STANDARDS INCLUDING, BUT NOT LIMITED TO, THE FOLLOWING INCORPORATED CODES LISTED

BELOW, AND IN THESE STRUCTURAL NOTES AND SPECIFICATIONS.

2019 CALIFORNIA EXISTING BUILDING CODE, TITLE 24, PART 10.

2019 CALIFORNIA HISTORICAL BUILDING CODE, TITLE 24, PART 8.

AMERICAN SOCIETY OF CIVIL ENGINEERS: ASCE 7-16 MINIMUM DESIGN LOADS FOR BUILDINGS AND

OTHER STRUCTURES INCLUDING SUPPLEMENT NO. 1 AND 2.

AMERICAN CONCRETE INSTITUTE (ACI): ACI 318-14 BLDG. CODE REQUIREMENTS FOR STRUCTURAL

CONCRETE AND REQUIREMENTS FOR STRUCTURAL CONCRETE AND COMMENTARY

AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC): STEEL CONSTRUCTION MANUAL 15TH

EDITION

AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC): AISC 360-16 SPECIFICATION FOR

STRUCTURAL STEEL BUILDINGS

AMERICAN WELDING SOCIETY: AWS D1.1:2015 STRUCTURAL WELDING CODE - STEEL

AMERICAN WELDING SOCIETY: AWS D1.4:2017 STRUCTURAL WELDING CODE - REINFORCING

AMERICAN WELDING SOCIETY: AWS D1.8:2016 STRUCTURAL WELDING CODE - SEISMIC SUPPLEMENT

ASTM SPECIFICATIONS ON THE STRUCTURAL DRAWINGS SHALL BE OF THE LATEST VERSION,

UNLESS OTHERWISE NOTED.

REFER TO THE ARCHITECTURAL DRAWINGS FOR THE FOLLOWING:

DIMENSIONS NOT SHOWN ON THE STRUCTURAL DRAWINGS.

SIZE AND LOCATION OF ALL FLOOR AND ROOF OPENINGS, EXCEPT AS NOTED.

SIZE AND LOCATION OF ALL INTERIOR AND EXTERIOR NON-BEARING PARTITIONS.

SIZE AND LOCATION OF ALL DOOR AND WINDOW OPENINGS, EXCEPT AS NOTED.

SIZE AND LOCATION OF ALL CONCRETE CURBS, EQUIPMENT PADS, PITS, FLOOR DRAINS, SLOPES, DEPRESSED AREAS, CHANGE IN LEVEL, CHAMFERS, GROOVES, INSERTS, ETC.

FLOOR AND ROOF FINISHES.

THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED

STRUCTURE. THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL

PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE DURING CONSTRUCTION.

SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO, BRACING AND SHORING FOR LOADS

DUE TO CONSTRUCTION EQUIPMENT, ETC. OBSERVATION VISITS TO THE SITE BY THE GOVERNMENT

SHALL NOT INCLUDE INSPECTION OF THE AFOREMENTIONED ITEMS.

CONTRACTOR SHALL INVESTIGATE THE SITE, DURING CLEARING AND EARTHWORK OPERATIONS,

FOR FILLED EXCAVATIONS OR BURIED STRUCTURES, SUCH AS CESSPOOLS, CISTERNS,

FOUNDATIONS, ETC. IF ANY SUCH STRUCTURES ARE FOUND, THE GOVERNMENT SHALL BE

NOTIFIED IMMEDIATELY.

GENERAL (CONTINUED)

OPENINGS, POCKETS, ETC., LARGER THAN 6" SHALL NOT BE PLACED IN CONCRETE SLABS, DECKS, OR WALLS, UNLESS SPECIFICALLY DETAILED ON THE STRUCTURAL DRAWINGS. NOTIFY THE

GOVERNMENT WHEN DRAWINGS BY OTHERS SHOW OPENINGS, POCKETS, ETC., LARGER THAN 6"

NOT SHOWN ON THE STRUCTURAL DRAWINGS, BUT WHICH ARE LOCATED IN STRUCTURAL

MEMBERS. FOR ANY FURTHER RESTRICTIONS ON OPENINGS IN STRUCTURAL ELEMENTS, SEE

APPLICABLE SECTIONS BELOW.

CONSTRUCTION MATERIAL SHALL BE SPREAD OUT IF PLACED ON FRAMED ROOF OR FLOOR. LOAD

SHALL NOT EXCEED THE DESIGN LIVE LOAD PER SQUARE FOOT. PROVIDE ADEQUATE SHORING

AND/OR BRACING WHERE THE STRUCTURE HAS NOT ATTAINED THE DESIGN STRENGTH.

SPECIFICATIONS AND DETAILING OF ALL WATERPROOFING AND DRAINAGE ITEMS, ALTHOUGH

SOMETIMES INDICATED ON THE STRUCTURAL DRAWINGS FOR GENERAL INFORMATION PURPOSES

ONLY, ARE SOLELY THE DESIGN RESPONSIBILITY OF OTHERS.

SHOP DRAWINGS, SPECIAL INSPECTIONS, AND MATERIAL SAMPLING AND TESTING, WHEN

REQUIRED, ARE SPECIFIED IN THEIR RESPECTIVE TABLES IN THE GENERAL NOTES AND IN THE

SPECIFICATIONS.

PROJECT SCOPE

THIS PROJECT INCLUDES REPAIR, RESTORATION, STABILIZATION, AND SEISMIC STRENGTHENING OF

THE HISTORIC PUNTA GORDA LIGHT STATION. SEISMIC STRENGTHENING IS BASED ON THE

REQUIREMENTS CONTAINED IN THE CALIFORNIA HISTORIC BUILDING CODE. IT WAS DETERMINED

FOR THIS PROJECT THAT SEISMIC STRENGTHENING OF THE SUPERSTRUCTURE IS NOT REQUIRED.

DESIGN

DESIGN CONFORMS TO THE CALIFORNIA HISTORIC BUILDING CODE, 2019 EDITION

LIVE LOADS:

ROOF (FLAT) 20 PSF

ROOF (SLOPED 4/12) 20 PSF

GROUND FLOOR 40 PSF

GALLERY (100 PSF MAX) 1.5*LIVE LOAD OF AREA SERVED

WIND ANALYSIS:

BASIC WIND SPEED, V3S (CBC FIGURE 1609) VULT = 92 mph

EXPOSURE (CBC SECTION 1609.4.3) = D

INTERNAL PRESSURE COEFF, GCPI (ASCE TABLE 26.13-1) GCPI = ±0.55

SEISMIC ANALYSIS:

SEISMIC IMPORTANCE FACTOR, I (ASCE TABLE 1.5-2) I = 1.0

RISK CATEGORY (CBC TABLE 1604.5) = II

SITE LOCATION, LATTITUDE ................... 40.294963°N

SITE LOCATION, LONGITUDE .................. 124.35060°W

SPECTRA ACCEL, SHORT PERIOD, SS (CBC FIGURE 1613.2.1(1)) SS = 2.086 g

SPECTRA ACCEL., LONG PERIOD, S1 (CBC FIGURE 1613.2.1(2)) S1 = 1.056 g

SITE CLASSIFICATION (CBC SECTION 1613.2.2) = D

DESIGN RESP, SHORT PERIOD, SDS (CBC SECTION 1613.2) SDS = 1.391 g

DESIGN RESP, LONG PERIOD, SD1 (CBC SECTION 1613.2) SD1 = 1.197 g

SEISMIC DESIGN CATEGORY (CBC TABLE 1613.2.5(1)&(2)) = E

LATERAL SYST (ASCE TABLE 12.2-1) BEARING WALL SYSTEM,

ORDINARY REINFORCED CONCRETE SHEAR

WALLS

RESPONSE MODIFICATION FACTOR, R = 4

SYSTEM OVERSTRENGTH FACTOR, ΩO = 2.5

DEFLECTION AMP FACTOR, Cd = 4

SEISMIC RESPONSE COEFFICIENT, CS (CHBC 8-706.1.1) CS = 0.26

LIGHTHOUSE BLDG BASE SHEAR, V V = 36.3 Kips (N-S) V = 36.3 Kips (E-W)

OIL HOUSE BLDG BASE SHEAR, V V = 30.9 Kips (N-S)

V = 30.9 Kips (E-W)

SEISMIC ANALYSIS PROCEDURE: STATIC LATERAL FORCE

PROCEDURE

ANALYSIS/DESIGN: USING HAND CALCULATIONS

EXISTING CONSTRUCTION

EXISTING CONSTRUCTION AND STRUCTURAL CONDITION IS BASED ON THE PUNTA GORDA

LIGHTSTATION REHABILITATION REPORT PREPARED BY SEH AND KPFF, DATED FEBRUARY 12, 2021, AND STRUCTURAL OBSERVATION AND ASSESSMENT REPORT PREPARED BY SHORELINE

ENGINEERING DATED SEPTEMBER 8, 2020. THE CONTRACTOR SHALL VERIFY ALL EXISTING

CONDITIONS AND SHALL NOTIFY THE GOVERNMENT OF ALL EXCEPTIONS BEFORE PROCEEDING

WITH THE WORK.

THE EXISTING STRUCTURES BEING STABLILIZED ARE ON THE NATIONAL RECORD OF HISTORIC

PLACES AND CAREFUL ATTENTION SHALL BE TAKEN TO PROTECT THESE STRUCTURES IN PLACE

DURING CONSTRUCTION. THE REMOVAL, CUTTING, DRILLING, ETC. OF EXISTING WORK SHALL BE

PERFORMED WITH GREAT CARE AND SMALL TOOLS IN ORDER NOT TO JEOPARDIZE THE

STRUCTURAL INTEGRITY OF THE BUILDING. IF EXISTING STRUCTURAL MEMBERS THAT ARE NOT

INDICATED FOR REMOVAL INTERFERE WITH THE NEW WORK, THE GOVERNMENT SHALL BE NOTIFIED

IMMEDIATELY, AND APPROVAL OBTAINED, BEFORE REMOVAL OF THE EXISTING MEMBERS.

THE CONTRACTOR SHALL SAFELY SHORE EXISTING CONSTRUCTION WHEREVER EXISTING

SUPPORTS ARE REMOVED TO ALLOW INSTALLATION OF THE NEW WORK. THE EXISTING

CONSTRUCTION SHALL BE CONNECTED AND/OR EMBEDDED INTO THE NEW CONSTRUCTION AS

SHOWN OR SPECIFIED.

FOUNDATIONS

FOUNDATIONS CONFORM TO THE RECOMMENDATIONS OF THE GEOTECHNICAL REPORT

ENTITLED:"LIMITED GEOTECHNICAL EVALUATION REPORT" PUNTA GORDA LIGHT STATION

HUMBOLDT COUNTY, CALIFORNIA," PREPARED BY TERRACON, DATED FEBRUARY 2, 2021.

MAXIMUM SOIL PRESSURE = 1500 PSF DL + LL

= 2000 PSF DL + LL + LATERAL

RETAINING WALLS

EQUIVALENT FLUID PRESSURE (FOR DRAINED WALLS)

ACTIVE CONDITION (UNRESTRAINED)

LEVEL BACKFILL = 43 PCF

SURCHARGE = 0.31S PSF*

SEISMIC INCREMENT = 8H^2 PSF**

AT-REST CONDITION (RESTRAINED)

LEVEL BACKFILL = 64 PCF

SURCHARGE = 0.47S PSF*

SEISMIC INCREMENT = 8H^2 PSF**

COEFFICIENT OF FRICTION = 0.33

PASSIVE EARTH PRESSURE = 330 PCF

(IGNORE TOP 6 INCHES)

* S = LIVE LOAD SURCHARGE (PSF)

** H = HEIGHT OF RETAINED SOIL (FT)

REFER TO THE GEOTECHNICAL REPORT FOR ADDITIONAL RECOMMENDATIONS NOT LISTED

BELOW. ALL SITE GRADING, EXCAVATIONS, FILLS, AND SOIL PREPARATION SHALL CONFORM TO

THE GEOTECHNICAL REPORT AND ALL WORK SHALL BE DONE UNDER THE OBSERVATION OF THE

GEOTECHNICAL ENGINEER.

THE CONTRACTOR SHALL PROVIDE FOR THE DESIGN AND INSTALLATION OF ALL CRIBBING,

SHEATHING, AND SHORING REQUIRED AND SHALL BE SOLELY RESPONSIBLE FOR ALL EXCAVATION

PROCEDURES INCLUDING LAGGING, SHORING, AND THE PROTECTION OF ADJACENT PROPERTY,

STRUCTURES, STREETS, AND UTILITIES IN ACCORDANCE WITH ALL NATIONAL, STATE, AND LOCAL

SAFETY ORDINANCES.

45 Fremont Street, 28th Floor

San Francisco, CA 94105

415.989.1004 | kpff.com

S T R U C T U R A

L

MO

NAG

M N

AM

ES

A J

No. 3957R E

G

IS

TE

RED

PROFESSIONAL

EN

G

IN

E

E R

AI

NROFILACFOETAT

S

S E

H P ro je c t

C h e ck ed B y

D ra w n

B y

P ro je ct

S ta tu s

Is su e D at e

This drawing is an instrument of service and shall remain the property of Short Elliott Hendrickson, Inc.

(SEH). This drawing, concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of SEH.

Submission or distribution of this drawing to meet official or regulatory requirements or for purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH.

S ho rt E lli ot t H ed ric ks on , I nc

A ll

R ig ht s

R es er ve d

C O

P Y

R

IG

H T

P#: 2000199.00

3/

/2

5:

:3

P

M

GENERAL NOTES

S002

P u n ta

G o rd a

L ig h t

S ta ti o n R e h a b il it a ti o n

P et ro lia

, C A

62 D A

A R

U N

IT

E D

S T A

T E S D

E P

A R

T M

E N

T O

F T

H E I N

T E R

IO

R

B U

R E A

U O

F L

A N

D M

A N

A G

E M

E N

T

G E N E R A L N O T E S

R ev is io n Is su e

R ev

D es cr ip tio n D at e

SHORT ELLIOTT HENDRICKSON

F

IN

A L C

ON

ST

RU

CT

IO

N

DO

CU

ME

NT

S

.2 6.

ENGINEERED/COMPACTED/SELECT FILL

STRUCTURAL FILL BELOW FOOTINGS SHALL BE COMPACTED TO 90% RELATIVE COMPACTION AS

DETERMINED BY THE ASTM D1557 COMPACTION TEST METHOD AND UNDER THE OBSERVATION OF

THE GEOTECHNICAL ENGINEER. STRUCTURAL FILL SHALL HAVE A MINIMUM DEPTH AS INDICATED

IN THE GEOTECHNICAL REPORT BENEATH ALL FOOTINGS.

SLABS ON GRADE

AT AREAS UNDER UNOCCUPIED SLABS ON GRADE, PROVIDE 4"/6" COMPACTED CALTRANS CLASS 2

AGGREGATE BASE. AGGREGATE BASE SHALL BE ROLLED TO A SMOOTH SURFACE.

BACKFILL

ALL EXCAVATIONS SHALL BE PROPERLY BACKFILLED. DO NOT PLACE BACKFILL BEHIND

RETAINING WALLS BEFORE THE CONCRETE OR GROUT HAS ATTAINED FULL DESIGN STRENGTH.

THE CONTRACTOR SHALL BRACE OR PROTECT ALL BUILDING AND PIT WALLS BELOW GRADE

FROM LATERAL LOADS UNTIL THE ATTACHING FLOORS ARE COMPLETELY IN PLACE AND HAVE

ATTAINED FULL STRENGTH. THE CONTRACTOR SHALL PROVIDE FOR THE DESIGN, PERMITS, AND

INSTALLATION OF SUCH BRACING.

FOOTING BACKFILL AND UTILITY TRENCH BACKFILL WITHIN THE BUILDING AREA SHALL BE

MECHANICALLY COMPACTED IN LAYERS IN ACCORDANCE WITH THE GEOTECHNICAL REPORT AND

OBSERVED BY THE GEOTECHNICAL ENGINEER OR GOVERNMENT. FLOODING WILL NOT BE

PERMITTED.

GEOTECHNICAL ENGINEER OBSERVATION LETTER

THE GEOTECHNICAL ENGINEER SHALL PREPARE A LETTER FOR THE GOVERNMENT GIVING AN

OPINION REGARDING CONFORMANCE OF THE FOOTING EXCAVATIONS,

ENGINEERED/COMPACTED/SELECT FILL COMPACTION, SUBGRADE PREPARATION, AND

BACKFILLING WITH THE REQUIREMENTS CONTAINED IN THE GEOTECHNICAL REPORT.

UNDERPINNING

THE DESIGN AND CONSTRUCTION OF UNDERPINNING AND BULK HEADING FOR EARTH RETENTION

DURING EXCAVATION SHALL BE BY AN EXPERIENCED SUBCONTRACTOR WHO SPECIALIZES IN THIS

TYPE OF WORK. UNDERPINNING, SHORING, LAGGING, ETC., SHALL BE DESIGNED BY A

PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF CALIFORNIA AND HIRED BY THE

UNDERPINNING/BULK HEADING CONTRACTOR.

FOUNDATIONS (CONTINUED)

FOOTINGS

FOOTINGS SHALL EXTEND TO SUCH DEPTH AS TO BEAR UPON FIRM, UNDISTURBED NATIVE SOIL

OR ENGINEERED/COMPACTED/SELECT FILL. ALL ABANDONED FOOTINGS, UTILITIES, ETC. SHALL

BE REMOVED. ALL FOOTINGS SHALL BE FOUNDED AT A DEPTH AT LEAST 24" BELOW THE LOWEST

ADJACENT GRADE OR PAD GRADE/SUB GRADE/BOTTOM OF SLAB ON GRADE. FOOTING DEPTHS

SHOWN ON THE STRUCTURAL DRAWINGS ARE MINIMUM DEPTHS. FOOTINGS MAY BE POURED IN

NEAT EXCAVATED TRENCHES.

EXCAVATIONS FOR FOOTINGS SHALL BE OBSERVED BY THE GEOTECHNICAL ENGINEER PRIOR TO

PLACING REINFORCING AND CONCRETE. THE CONTRACTOR SHALL NOTIFY THE GOVERNMENT

WHEN THE EXCAVATIONS ARE READY FOR OBSERVATION.

REINFORCING STEEL

REINFORCING STEEL DETAILING, FABRICATION, AND PLACEMENT SHALL CONFORM TO THE

"CALIFORNIA BUILDING CODE", CHAPTER 19; THE "MANUAL OF STANDARD PRACTICE OF THE

CONCRETE REINFORCING STEEL INSTITUTE", LATEST EDITION; AND THE "BUILDING CODE

REQUIREMENTS FOR STRUCTURAL CONCRETE AND COMMENTARY", ACI 318-14; UNLESS

OTHERWISE NOTED.

ALL REBAR SHALL BE HOT-DIPPED GALVANIZED (HDG)

STANDARDS:

REINFORCING STEEL SHALL CONFORM TO THE FOLLOWING STANDARDS:

DEFORMED BARS, #3 ASTM A615, GR 40

DEFORMED BARS, #4 AND LARGER ASTM A615, GR 60

WELDED REINFORCEMENT, WHEN SPECIFIED ASTM A706, GR 60

WELDED WIRE FABRIC, WWF (SMOOTH WIRE) ASTM A1064

SMOOTH WIRE IN WWF ASTM A1064

REINFORCING STEEL (CONTINUED)

LAP BARS 48 DIAMETERS, 24" MINIMUM, UNLESS OTHERWISE NOTED

LAP WIRE FABRIC 6" MINIMUM.

LAP CIRCULAR HOOP REINFORCEMENT 48 BAR DIAMETERS, 12" MINIMUM.

LAP SPIRAL REINFORCEMENT 2 TURNS.

FOR EPOXY COATED REINFORCING, WHEN SPECIFIED, LAP AS NOTED IN SPECIFIC DETAILS.

MECHANICAL SPLICES: WHERE NOTED ON PLANS, PROVIDE THREADED COUPLERS CAPABLE OF

DEVELOPING AT LEAST 125% OF THE SPECIFIED YIELD STRENGTH OF THE REINFORCING STEEL.

COUPLERS SHALL BE TYPE 2, AS PER ACI 318-14 SECTION 18.2.7. THREADED COUPLERS SHALL BE

AS MANUFACTURED BY ERICO COMPANY, OR APPROVED EQUAL WITH A CURRENT EVALUATION

REPORT FROM AN APPROVED SOURCE.

FORM SAVER: FORM SAVERS ARE TO BE USED WHERE NOTED ON THE DRAWINGS. IN ADDITION,

FORM SAVERS MAY BE SUBSTITUTED IN LIEU OF DOWELS AT CONSTRUCTION JOINTS. WHERE

SUBSTITUTED, CONTRACTOR TO SUBMIT FOR REVIEW PRIOR TO CONSTRUCTION. FORM SAVERS

SHALL BE CAPABLE OF DEVELOPING AT LEAST 125% OF THE SPECIFIED YIELD STRENGTH OF THE

REINFORCING STEEL. FORM SAVERS SHALL BE TYPE 2, AS PER ACI 318-14 SECTION 18.2.7. FORM

SAVERS SHALL BE AS MANUFACTURED BY ERICO INC (IAPMO ES ER-0129) OR APPROVED EQUAL

WITH A CURRENT EVALUATION REPORT FROM AN APPROVED SOURCE.

WELDING: WHERE WELDING OF REINFORCING BARS IS APPROVED BY THE GOVERNMENT, IT

SHALL BE DONE BY AWS CERTIFIED WELDERS USING E80XX OR APPROVED ELECTRODES.

WELDING PROCEDURES SHALL CONFORM TO THE REQUIREMENTS OF THE "STRUCTURAL

WELDING CODE - REINFORCING STEEL", AWS-D1.4

CLEAR DISTANCES, STEEL TO FORMS, UNLESS NOTED OTHERWISE:

EXTERIOR WALL SURFACES, SLABS EXPOSED TO WEATHER, #5 AND

SMALLER

2-1/2"

EXTERIOR WALL SURFACES, SLABS EXPOSED TO WEATHER, #6 AND

LARGER

2-1/2"

COLUMN TIES, BEAM TIES 1-1/2"

CLEAR DISTANCE BETWEEN BARS 2"

SLABS ON ROLLED GRADE 2-1/2"

FORMED SURFACES IN CONTACT WITH EARTH 2-1/2"

UNFORMED SURFACES IN CONTACT WITH EARTH 3"

SHOP DRAWINGS SHALL BE SUBMITTED TO THE GOVERNMENT FOR REVIEW PRIOR TO

FABRICATION. SHOP DRAWINGS SHALL INCLUDE ELEVATIONS OF ALL BEAMS AND COLUMNS

SHOWING BAR AND LAP LOCATIONS. SEE SHOP DRAWING SUBMITTAL REQUIREMENTS ELSEWHERE

IN GENERAL NOTES. SUBMIT MILL CERTIFICATES FOR REINFORCING STEEL PRIOR TO REBAR

PLACEMENT.

WELDED WIRE FABRIC, WWF (SMOOTH WIRE) ASTM A1064

SMOOTH WIRE IN WWF ASTM A1064

DEFORMED WIRE FABRIC, DWF (DEFORMED BAR) ASTM A1064

DEFORMED WIRE IN DWF ASTM A1064

SPIRAL REINFORCEMENT, SMOOTH ASTM A615

SPIRAL REINFORCEMENT, DEFORMED ASTM A615

EPOXY COATED REINFORCEMENT, WHEN SPECIFIED ASTM A775 & A615

HOT-DIPPED GALVANIZED REINFORCEMENT ASTM A767

PLACING: ALL STEEL REINFORCEMENT SHALL BE SECURELY TIED IN PLACE SO AS TO MAINTAIN

THEIR EXACT POSITION BEFORE AND DURING THE PLACEMENT OF CONCRETE. REINFORCING

STEEL SHALL BE SECURELY TIED IN PLACE WITH #16 ANNEALED IRON WIRE. BARS IN BEAMS AND

SLABS SHALL BE SUPPORTED ON WELL-CURED CONCRETE BLOCKS OR APPROVED PLASTIC

TIPPED METAL CHAIRS, AS SPECIFIED BY CRSI MANUAL OF STANDARD PRACTICE, MSP-1.

ACCESSORIES FOR EPOXY-COATED REINFORCING, WHERE SHOWN ON PLANS, SHALL BE AS

NOTED IN THE SPECIFICATIONS. WIRE FABRIC IN SLABS SHALL BE SECURELY FASTENED TO

SUPPORTING DEVICES TO MAINTAIN THEIR POSITION DURING CONCRETE PLACEMENT.

CONCRETE WORK

FORMS SHALL BE PROPERLY CONSTRUCTED CONFORMING TO CONCRETE SURFACES AS SHOWN

ON THE DRAWINGS, SUFFICIENTLY TIGHT TO PREVENT LEAKAGE, SUFFICIENTLY STRONG, AND

BRACED TO MAINTAIN THEIR SHAPE AND ALIGNMENT UNTIL NO LONGER NEEDED TO SUPPORT

THE CONCRETE. FORMS FOR EXPOSED CONCRETE SHALL BE PLYWOOD, USING SHEETS AS

LARGE AS POSSIBLE, WITH ALL JOINTS TIGHTLY FITTED AND BLOCKED, AND SHALL PRODUCE A

FINISHED CONCRETE SURFACE WHICH IS SMOOTH, TRUE, AND FREE FROM BLEMISHES

ACCORDING TO ACCEPTED STANDARDS FOR ARCHITECTURAL CONCRETE.

FORMS AND SHORING SHALL NOT BE REMOVED UNTIL THE CONCRETE HAS ATTAINED SUFFICIENT

STRENGTH TO WITHSTAND ALL LOADS TO BE IMPOSED WITHOUT EXCESSIVE STRESS, CREEP, OR

DEFLECTION. SEE SPECIFICATIONS FOR SHORING REQUIREMENTS.

CONCRETE SHALL BE READY MIXED CONFORMING TO ASTM C94. CEMENT SHALL BE PORTLAND

CEMENT TYPE II, CONFORMING TO ASTM C150. ALL HARDROCK (H.R.) CONCRETE USED IN

SUSPENDED SLABS AND SLABS ON GRADE SHALL BE DESIGNED FOR LOW SHRINKAGE (L.S.).

ACCEPTABLE COARSE AGGREGATES FOR LOW SHRINKAGE CONCRETE INCLUDE KAISER

CLAYTON, GRANITE ROCK, LIMESTONE, SECHELT, OR ORCAS AGGREGATES. FINE AGGREGATES

ACCEPTABLE FOR LOW SHRINKAGE CONCRETE INCLUDE SECHELT, ORCAS, OR GRANITE ROCK

SANDS. ALTERNATIVE AGGREGATES MAY BE SUBMITTED PROVIDED THEY PROVIDE A CONCRETE

MIX WITH A SHRINKAGE LIMITATION OF 0.040% AFTER 28 DAYS OF DRYING. SUBMIT TEST DATA TO

THE GOVERNMENT FOR REVIEW.

USE MAXIMUM SIZE AGGREGATE AS NOTED BELOW.

USE 3/8" MAXIMUM AGGREGATE WHERE NECESSARY FOR PROPER PLACING, SUCH AS IN THIN OR

CONGESTED SECTIONS, ETC. SUPERPLASTICIZERS MAY BE USED TO IMPROVE WORKABILITY IN

THIN OR CONGESTED SECTIONS. INCORPORATE SUPERPLASTICIZERS INTO CONCRETE MIX

DESIGNS.

FLYASH SHALL CONSIST OF POZZOLANIC ADMIXTURES CONFORMING TO ASTM C618, CLASS F,

AND SHALL BE USED IN QUANTITIES NOTED BELOW. SEE SPECIFICATIONS FOR ADDITIONAL

REQUIREMENTS.

ADMIXTURES USED IN CONCRETE SHALL CONFORM TO THE FOLLOWING ASTM STANDARDS,

SHALL BE USED IN DOSAGES RECOMMENDED BY THE MANUFACTURER, AND SHALL NOT CONTAIN

MORE CHLORIDE THAN IS FOUND IN THE MUNICIPAL DRINKING WATER SUPPLY. LIQUID VOLUME

IN ASTM C494, TYPE C ADMIXTURES SHALL BE ADDED TO WATER CONTENT AND WATER CEMENT

RATIO CALCULATIONS.

WATER REDUCERS ASTM C494, TYPE A

MID-RANGE WATER REDUCERS ASTM C494, TYPE A/F

HIGH-RANGE WATER REDUCERS ASTM C494, TYPE F

HYDRATION STABILIZERS (RETARDERS) ASTM C494, TYPE B AND D

ACCELERATORS ASTM C494, TYPE C

AIR ENTRAINING AGENTS ASTM C260

CORROSION INHIBITORS ASTM C494, TYPE C

SHRINKAGE REDUCING ADMIXTURES ASTM C494, TYPE F

VISCOSITY MODIFYING ADMIXTURES ASTM C494, TYPE S

SILICA FUME ASTM C1240

CRYSTALLINE WATERPROOFING NO ASTM STANDARD

POST-INDUSTRIAL, RECYCLED CO₂ NO ASTM STANDARD

CEMENTITIOUS MATERIAL (CM) CONTENT INCLUDES ALL CEMENT AND SUPPLEMENTAL

CEMENTITIOUS MATERIALS (SCM)

CONTRACTOR SHALL SUBMIT FOR REVIEW OF THE GOVERNMENT THE CONCRETE MIXES

PROPOSED FOR USE, DESIGNED BY THE CONCRETE SUPPLIER AND REVIEWED BY AN APPROVED

TESTING LABORATORY.

CONCRETE WORK (CONTINUED)

REFER TO ARCHITECTURAL DRAWINGS FOR DETAILS AT DOOR AND WINDOW OPENINGS, FLOOR

TYPE HINGES, ETC., AND FOR LOCATION OF SLEEVES, PIPES, AND OTHER EMBEDDED ITEMS.

OPENINGS THROUGH SLABS OR WALLS NOT SHOWN ON THE STRUCTURAL DRAWINGS WHICH

WOULD INTERRUPT REINFORCING BARS SHALL NOT BE MADE WITHOUT APPROVAL OF THE

GOVERNMENT.

DEBRIS SHOULD BE ENTIRELY REMOVED FROM FORMS PRIOR TO CONCRETE PLACEMENT.

HORIZONTAL CONSTRUCTION JOINTS SHALL BE LOCATED AS SHOWN ON THE STRUCTURAL

DRAWINGS, AND THE HARDENED CONCRETE SURFACES SHALL BE CLEANED BY SAND-BLASTING

OR OTHER APPROVED MEANS TO EXPOSE FIRMLY EMBEDDED AGGREGATES PRIOR TO POURING

ADDITIONAL CONCRETE IN CONTACT WITH THESE SURFACES. VERTICAL CONSTRUCTION JOINTS

THROUGH BEAMS OR SLABS SHALL BE LOCATED ONLY AS SHOWN ON STRUCTURAL DRAWINGS.

45 Fremont Street, 28th Floor

San Francisco, CA 94105

415.989.1004 | kpff.com

S T R U C T U R A

L

MO

NAG

M N

AM

ES

A J

No. 3957R E

G

IS

TE

RED

PROFESSIONAL

EN

G

IN

E

E R

AI

NROFILACFOETAT

S

S E

H P ro je c t

C h e ck ed B y

D ra w n

B y

P ro je ct

S ta tu s

Is su e D at e

This drawing is an instrument of service and shall remain the property of Short Elliott Hendrickson, Inc.

(SEH). This drawing, concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of SEH.

Submission or distribution of this drawing to meet official or regulatory requirements or for purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH.

S ho rt E lli ot t H ed ric ks on , I nc

A ll

R ig ht s

R es er ve d

C O

P Y

R

IG

H T

P#: 2000199.00

3/

/2

5:

:3

P

M

GENERAL NOTES

S003

P u n ta

G o rd a

L ig h t

S ta ti o n R e h a b il it a ti o n

P et ro lia

, C A

62 D A

A R

U N

IT

E D

S T A

T E S D

E P

A R

T M

E N

T O

F T

H E I N

T E R

IO

R

B U

R E A

U O

F L

A N

D M

A N

A G

E M

E N

T

G E N E R A L N O T E S

R ev is io n Is su e

R ev

D es cr ip tio n D at e

SHORT ELLIOTT HENDRICKSON

F

IN

A L C

ON

ST

RU

CT

IO

N

DO

CU

ME

NT

S

.2 6.

CONDUIT, WHEN EMBEDDED IN CONCRETE SLABS, SHALL BE SPACED WITH ONE CONDUIT

DIAMETER CLEAR (LARGER CONDUIT) OR 1 INCH CLEAR, WHICHEVER IS GREATER, BETWEEN

ADJACENT CONDUITS OR REBAR. CONDUIT SHALL NOT BE LOCATED DIRECTLY OVER AND

PARALLEL TO REBAR. EMBEDDED CONDUIT CAN BE TIED TO REBAR WHEN ORIENTED

PERPENDICULAR TO THEM, PROVIDED THE LOCATION OF REBAR IS NOT AFFECTED BY THE

CONDUIT. CONDUIT WITHOUT CLEARANCE NOTED ABOVE SHALL BE SUBMITTED TO THE

GOVERNMENT FOR REVIEW PRIOR TO INSTALLATION. ADDED TRIM REINFORCEMENT WILL BE

REQUIRED WHERE CLEARANCES CANNOT BE MET, SUCH AS ELECTRIC PANEL ROOMS.

SLEEVES, WHEN INSTALLED IN CONCRETE, SHALL BE SPACED WITH ONE SLEEVE DIAMETER

(LARGER SLEEVE) CLEAR BETWEEN ADJACENT SLEEVES, REBAR, OR 1 INCH, WHICHEVER IS

GREATER. SLEEVES MAY NOT TOUCH REBAR OR OTHER SUPPORT HARDWARE. PROVIDE

CLEARANCE BETWEEN SLEEVES AND REINFORCING FOR TYPICAL SLAB EDGE CONDITIONS.

ADDED TRIM REINFORCEMENT IS REQUIRED PER THE TYPICAL SLAB OPENING DETAIL WHEN

SLEEVES EXCEED 12" DIAMETER OR ARE PLACED IN GROUPS WHERE THE OUT-TO-OUT

DIMENSION EXCEEDS 12" IN ANY DIRECTION. SLEEVE PLACEMENT SHALL NOT INTERFERE WITH

THE REBAR PLACEMENT WITHOUT THE APPROVAL OF THE GOVERNMENT.

THE CONTRACTOR SHALL INFORM THE GOVERNMENT AT LEAST 3 DAYS PRIOR TO POURING ANY

STRUCTURAL CONCRETE SO THAT THE GOVERNMENT MAY HAVE THE OPPORTUNITY OF

REVIEWING THE WORK PRIOR TO CONCRETE PLACEMENT.

ALL CONCRETE EXCEPT SLABS ON GRADE 6" THICK OR LESS SHALL BE MECHANICALLY VIBRATED

SO AS TO COMPLETELY FILL THE FORMS WITHOUT CAUSING UNDUE SEGREGATION.

FOR 28 DAY STRENGTHS:

TAKE 4 6" DIAMETER X 12" LONG TEST CYLINDERS FROM EACH 150 YARDS, OR FRACTION

THEREOF, POURED IN ANY ONE DAY. CYLINDERS SHALL BE SECURED AND TESTED BY AN

INDEPENDENT TESTING AGENCY; ONE TO BE TESTED AT 7 DAYS FOR INFORMATION, TWO AT 28

DAYS FOR ACCEPTANCE, AND HOLD ONE IN RESERVE.

THE CONTRACTOR SHALL REMOVE AND REPLACE ANY CONCRETE WHICH FAILS TO ATTAIN

SPECIFIED STRENGTH IN 28 DAYS IF SO DIRECTED BY THE GOVERNMENT. ANY DEFECTS IN THE

HARDENED CONCRETE SHALL BE SATISFACTORILY REPAIRED OR THE HARDENED CONCRETE

SHALL BE REPLACED.

CONCRETE WORK (CONTINUED)

CONCRETE SHALL HAVE THE FOLLOWING CHARACTERISTICS:

CONCRETE LOCATION MAX AGGREGATE

STRENGTH

@ 28 DAYS

(PSI)

MIN

SLUMP¹

(IN)

MIN CM

CONTENT

(SACKS)

MAX WATER

CONTENT¹

(GALS)

MAX

WATER/

CEMENT

RATIO

FLYASH

CONTENT

MIN, MAX

FOOTINGS⁴ 1-1/2" HR 4000 3.5 6.0 36 0.60 20,35

LEAN CONCRETE⁴ 3/8" HR 500 6 2.0 36 0.60 0,0

SLAB ON GRADE⁴ 1"x#4 HR-LS 3000 3.5 5.0 33 0.45 15,25

WALLS/PILASTERS⁴ 1"x#4 HR 4000 3.5 6.0 35 0.55 15,25

SUSPENDED SLAB⁴ 1"x#4 HR-LS 4000 3.5 6.0 33 0.45 15,25

NOTES:

¹ SLUMP SHALL BE THE MINIMUM CONSISTENT WITH PROPER PLACING. ACHIEVE SLUMP WITH

WATER REDUCING ADMIXTURES (ASTM C-494 TYPE A, F, OR A/F) FOR DESIRED WORKABILITY.

² USE HIGH RANGE WATER REDUCING ADMIXTURE (SUPERPLASTICIZER) AS NEEDED.

³ USE WATER REDUCING ADMIXTURES OR MID-RANGE WATER REDUCING ADMIXTURES FOR

DESIRED WORKABILITY.

⁴ USE RECYCLED CARBON DIOXIDE (CO2) SOURCED FROM AN EMITTER, CHEMICALLY

MINERALIZED INTO CONCRETE MIX. USE 4.0% CO2 PER CWT CEMENT MATERIAL (NOT

CEMENTITIOUS).

STRUCTURAL STEEL AND MISCELLANEOUS IRON

STRUCTURAL STEEL AND MISCELLANEOUS METAL SHALL BE DETAILED, FABRICATED, AND ERECTED

IN ACCORDANCE WITH AISC 325. FABRICATORS AND ERECTORS SHALL BE AISC CERTIFIED.

STANDARDS:

ALL STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING ASTM DESIGNATIONS, U.N.O.

WF SHAPES A992

WT SHAPES A992

HP SHAPES A992

M AND S SHAPES A36

STEEL PIPE A53, GRADE B (Fy = 35 KSI)

HSS ROUND A500, GRADE C (Fy = 46 KSI)

HSS RECTANGULAR AND SQUARE A500, GRADE C (Fy = 50 KSI)

ANGLES, C-SHAPES, MC-SHAPES A36

OTHER STEEL PLATES AND BARS A36

UNLESS OTHERWISE SHOWN OR NOTED STIFFENER PLATES SHALL BE 3/8" THICK MINIMUM.

ALL STEEL ELEMENTS EXPOSED TO WEATHER SHALL BE GALVANIZED, GALVANIZE ACCORDING TO

ASTM A123, HOT DIP PROCESS.

ERECTION CLIPS, TEMPORARY BRACING, AND SHORING REQUIRED BY THE CONTRACTOR ARE NOT

SHOWN. CONTRACTOR SHALL COMPLY WITH ALL OSHA REQUIREMENTS.

ADDITIONAL MISCELLANEOUS METAL ITEMS SUCH AS EMBEDS, RAILINGS, AND SUPPORTS FOR

INTERIOR FINISHES MAY BE SHOWN ON DRAWINGS PREPARED BY OTHERS, SEE ARCHITECTURAL

DRAWINGS.

SHOP DRAWINGS SHALL BE SUBMITTED TO THE GOVERNMENT FOR REVIEW PRIOR TO FABRICATION

THE TESTING AGENCY SHALL SEND COPIES OF STRUCTURAL TESTING AND INSPECTION REPORTS

DIRECTLY TO THE GOVERNMENT.

BOLTED CONNECTIONS:

UNLESS OTHERWISE NOTED, ALL STEEL TO STEEL BOLTED CONNECTIONS SHALL BE BOLTED WITH

HIGH STRENGTH BOLTS PER THE "SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR

A490 BOLTS", BY THE RESEARCH COUNCIL ON STRUCTURAL CONNECTIONS (RCSC).

1. UNLESS OTHERWISE NOTED, BOLTS IN CONNECTIONS SHALL BE BEARING TYPE WITH THREADS

EXCLUDED FROM THE SHEAR PLANE USING ASTM A325 BOLTS UNLESS SPECIFICALLY NOTED

OTHERWISE. ALL BOLTS IN BEARING TYPE CONNECTIONS MAY BE SNUG TIGHTENED PER RCSC.

2. STEEL WASHERS SHALL CONFORM TO ASTM F436 OR F959. NUTS SHALL CONFORM TO ASTM

A563.

3. UNLESS NOTED OTHERWISE, ANCHOR BOLTS AND/OR ANCHOR RODS SHALL CONFORM TO

ASTM F1554 GRADE 36.

4. OTHER BOLTED CONNECTIONS SHALL BE BOLTED WITH UNFINISHED BOLTS ACCORDING TO

ASTM A307.

WELDED CONNECTIONS:

ALL WELDED CONNECTIONS SHALL BE WELDED IN ACCORDANCE WITH THE "STRUCTURAL WELDING

CODE - STEEL (AWS-D1.1). ALL WELDING SHALL BE DONE WITH ELECTRODES HAVING A MINIMUM

TENSILE STRENGTH OF 70 KSI, UNLESS NOTED OTHERWISE. SHIELDED METAL ARC WELDING (SMAW)

ELECTRODES SHALL BE LOW-HYDROGEN TYPE. UNLESS OTHERWISE NOTED.

1. ALL WELDERS SHALL BE QUALIFIED IN ACCORDANCE WITH AWS D1.1 FOR ALL WELDS THEY WILL

BE PERFORMING.

2. THE WELD LENGTHS CALLED FOR ON THE STRUCTURAL DRAWINGS ARE THE NET EFFECTIVE

LENGTH REQUIRED. WHERE FILLET WELD SYMBOL IS GIVEN WITHOUT INDICATION OF SIZE, USE

THE MINIMUM SIZE WELDS AS SPECIFIED IN AISC 360, SECTION J2.2B.

METAL STAIRS

SHOP DRAWINGS AND DESIGN CALCULATIONS SHALL BE PREPARED IN CONFORMANCE WITH CBC

REQUIREMENTS AND SIGNED BY A CIVIL OR STRUCTURAL ENGINEER LICENSED IN THE STATE OF

CALIFORNIA, AND SHALL BE SUBMITTED TO THE GOVERNMENT FOR REVIEW PRIOR TO

FABRICATION. THE REVIEW OF CALCULATIONS AND SHOP DRAWINGS BY THE GOVERNMENT SHALL

NOT RELIEVE THE CONTRACTOR OF PROVIDING STAIRS WHICH ARE OF THE REQUIRED STRENGTH

AND WITHIN CODE COMPLIANCE.

EPOXY FOR CONCRETE

EPOXY SHALL BE SET-XP AS MANUFACTURED BY SIMPSON STRONG-TIE COMPANY INC. (ICC

EVALUATION REPORT ESR-2508) OR APPROVED EQUAL WITH A CURRENT ICC REPORT. ALL DRILLED

HOLES SHALL BE SIZED ACCORDING TO THE MANUFACTURER'S RECOMMENDATIONS.

EXPANSION ANCHORS

EXPANSION ANCHORS SHALL BE KB-TZ AS MANUFACTURED BY HILTI, INC. (ICC EVALUATION REPORT

ESR-1917) OR APPROVED EQUAL WITH A CURRENT ICC REPORT. ALL DRILLED HOLES SHALL BE

SIZED ACCORDING TO THE MANUFACTURER'S RECOMMENDATIONS.

STRUCTURAL STEEL AND MISCELLANEOUS IRON (CONTINUED)

3. ALL WELDING SHALL BE PERFORMED IN CONFORMANCE WITH A WRITTEN WELDING

PROCEDURE SPECIFICATION (WPS). SUBMIT ALL WPS'S APPLICABLE TO THE PROJECT FOR

REVIEW LISTING SPECIFIC ELECTRODES TO BE USED. THE SUBMITTAL SHALL INCLUDE AN INDEX

OF ALL PROCEDURES, SHALL IDENTIFY THE ACTUAL ELECTRODE TO BE USED FOR EACH

PROCEDURE, AND SHALL INCLUDE ELECTRODE DATA SHEETS DESCRIBING THE PRODUCTS, THE

LIMITATIONS OF USE, THE RECOMMENDED WELDING PARAMETERS, AND STORAGE AND

EXPOSURE REQUIREMENTS. FOR WPS'S THAT ARE NOT PRE-QUALIFIED PER AWS D1.1, SUBMIT

PROCEDURE QUALIFICATION RECORD WITH WPS.

4. RUN-OFF TABS PER AWS D1.1 ARE REQUIRED FOR COMPLETE JOINT PENETRATION (C.J.P.)

GROOVE WELDS. ALL WELDS ARE TO BE STARTED AND COMPLETED ON THE RUN-OFF TABS AS

MUCH AS PRACTICABLE. DO NOT END WELDS AT COPE HOLE LOCATIONS. USE OF WELD DAMS IS

NOT ALLOWED.

5. THE MINIMUM PREHEAT AND INTERPASS TEMPERATURES OF AWS D.1 SECTION 3.5 MUST BE

FOLLOWED.

6. ALL C.J.P. GROOVE WELDS IN MEMBERS AND CONNECTIONS SHALL BE MADE WITH A FILLER

METAL HAVING A MINIMUM CHARPY V-NOTCH TOUGHNESS OF 20 FT-LBS AT 40 DEGREES F AS

DETERMINED BY AWS CLASSIFICATION OR MANUFACTURER'S CERTIFICATION.

7. ALL BUTT WELDS ARE COMPLETE JOINT PENETRATION WELDS.

8. COMPLETE PENETRATION WELDS AND PARTIAL PENETRATION WELDS SHALL BE EXAMINED BY

ULTRASONIC TESTING. ALL TESTING AND INSPECTION SHALL CONFORM TO CBC

REQUIREMENTS. REFER TO THE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

45 Fremont Street, 28th Floor

San Francisco, CA 94105

415.989.1004 | kpff.com

S T R U C T U R A

L

MO

NAG

M N

AM

ES

A J

No. 3957R E

G

IS

TE

RED

PROFESSIONAL

EN

G

IN

E

E R

AI

NROFILACFOETAT

S

S E

H P ro je c t

C h e ck ed B y

D ra w n

B y

P ro je ct

S ta tu s

Is su e D at e

This drawing is an instrument of service and shall remain the property of Short Elliott Hendrickson, Inc.

(SEH). This drawing, concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of SEH.

Submission or distribution of this drawing to meet official or regulatory requirements or for purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH.

S ho rt E lli ot t H ed ric ks on , I nc

A ll

R ig ht s

R es er ve d

C O

P Y

R

IG

H T

P#: 2000199.00

3/

/2

5:

:3

P

M

GENERAL NOTES

S004

P u n ta

G o rd a

L ig h t

S ta ti o n R e h a b il it a ti o n

P et ro lia

, C A

62 D A

A R

U N

IT

E D

S T A

T E S D

E P

A R

T M

E N

T O

F T

H E I N

T E R

IO

R

B U

R E A

U O

F L

A N

D M

A N

A G

E M

E N

T

G E N E R A L N O T E S

R ev is io n Is su e

R ev

D es cr ip tio n D at e

SHORT ELLIOTT HENDRICKSON

F

IN

A L C

ON

ST

RU

CT

IO

N

DO

CU

ME

NT

S

.2 6.

MATERIAL SAMPLING AND TESTING

WHEN INDICATED WITH AN "X", THE FOLLOWING MATERIALS SHALL BE SAMPLED AND/OR TESTED

BY A CERTIFIED INSPECTOR FROM AN ESTABLISHED TESTING AGENCY IN ACCORDANCE WITH THE

PROJECT SPECIFICATIONS, GENERAL NOTES, OR PREVAILING BUILDING CODE, WHICHEVER IS

MORE STRINGENT. ALL MATERIAL SAMPLING AND TESTING SHALL BE PERFORMED IN

ACCORDANCE WITH ASTM REQUIREMENTS. FOR ADDITIONAL INFORMATION ON MATERIAL

SAMPLING AND TESTING, REFER TO THE PROJECT SPECIFICATIONS AND THE SPECIFIC GENERAL

NOTES SECTIONS. THE TESTING AGENCY SHALL SEND COPIES OF ALL STRUCTURAL TESTING

REPORTS DIRECTLY TO THE GOVERNMENT. ANY MATERIALS WHICH FAIL TO MEET THE PROJECT

SPECIFICATIONS SHALL IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE GOVERNMENT.

ITEM REQUIRED REMARKS

HELICAL PILES LOAD TEST

CONCRETE, REINFORCING

MILL CERTIFICATE IN

LIEU OF SAMPLES

CONCRETE, CYLINDERS X

STRUCTURAL STEEL, ULTRASONIC TESTING X

FOR CJP WELDS WHERE

NOTED

EXPANSION ANCHOR INSTALLATION X TORQUE TEST

EPOXY ANCHOR INSTALLATION X PULL TEST

DEFERRED APPROVALS

WHEN INDICATED WITH A "X", THE FOLLOWING ITEMS HAVE BEEN SHOWN OR INDICATED ON

STRUCTURAL OR ARCHITECTURAL DRAWINGS TO CONVEY THE DESIGN INTENT ONLY. FINAL SIZES

AND DETAILS SHALL BE DETERMINED BY THE CONTRACTOR. THE CONTRACTOR'S BID SHALL BE

BASED UPON FINAL SIZES AND DETAILS. DEFERRED APPROVAL ITEMS SHALL HAVE SHOP

DRAWINGS AND…

This is the start of the file's text. The full file is on GovTribe.