This document is a Statement of Work (SOW) for a Readjustment Counseling Service Vet Center lease, detailing comprehensive requirements for a new facility. The Department of Veterans Affairs seeks a contiguous, ground-floor clinical space in a professional building located in Savannah, Georgia, between 5,206 and 5,466 rentable square feet. The lease will be fully serviced, including janitorial, security, CCTV monitoring, basic cable, and high-speed internet, with specific technical requirements for various interior spaces such as offices, group counseling rooms, restrooms, a reception area, and support areas.

The SOW specifies detailed design and functionality standards, including ADA compliance, security systems, signage specifications, and technological infrastructure. Key requirements include an entry control system, power-assisted doors, dedicated electrical outlets, sound transmission class ratings, and provisions for veteran privacy and comfort. The lease term is anticipated to be 20 years with a negotiable firm term not exceeding 10 years, and the government estimates tenant improvements between $1-1.5 million. The facility must provide a minimum of 30 parking spaces, with 4 designated handicapped spots, and be located within specified geographic boundaries in Savannah, accessible from 7:00 AM to 6:00 PM.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

10RCS/STA703 VET CENTER Page 1 | 10 Lessor Initials/Date _______________

VERSION DATED 10.04.2024

READJUSTMENT COUNSELING SERVICE - VET CENTER

STATEMENT OF WORK / AGENCY SPECIFIC REQUIREMENTS

NEW REPLACING RELOCATION

The Department of Veterans Affairs is interested in leasing (contiguous) clinical space for a Vet Center.

The space shall be of contiguous space in a professional and aesthetically pleasing building with attractive, professional surroundings, well maintained streets, and public walkways. The space offered shall be located on the ground floor in a quality building of sound and substantial construction, modernized building, or one that has undergone restoration or rehabilitation for use by the Vet Center for furnishings, equipment, and personnel to provide readjustment counseling services.

Vet Centers are established in the community to promote and facilitate ease of access to readjustment counseling for eligible individuals and their families; at minimum, Vet Centers must:

Ensure convenient location with easy access to community locations via all modes of local transportation: public transportation, privately owned vehicle, and pedestrian.

Ensure the availability of parking, to include spaces reserved for disabled individuals.

Ensure availability of readjustment counseling in, or near, the individual’s home community, and, where necessary, by establishing convenient community access points in areas located at some distance from the existing Vet Center.

Ensure available space for informal social interaction among family members and camaraderie among fellow eligible individuals.

Reinforce eligible individuals’ pride in military service through display of Veteran memorabilia that promotes a therapeutic link between them and their personal military and homecoming experiences.

Ensure all eligible individuals and their families have full access to readjustment counseling through regularly scheduled non-traditional Vet Center hours during the evening or on weekends that are planned in coordination with the needs of the local eligible community and the staffing capacity of the local Vet Center.

The Lease shall follow the standard specifications and requirements in the Request for Lease Proposal (RLP) and executed lease contract. If any conflict between standards or regulatory framework is found, the offeror must use the higher standard and follow the more stringent regulation.

The Lease shall be Fully Serviced to include Janitorial, Security and CCTV Monitoring and Maintenance, Basic Cable, and Business High-Speed Internet Wi-Fi; paid for/provided by the Lessor through the annual rent. Additionally, all overtime HVAC usage shall be included in the annual rental rate.

The Lessor shall provide all materials, parts, and labor to complete the below space and room requirements.

ROOM REQUIREMENTS

A. ENTRANCE / EXTERIOR

1. Vestibule provided at public entrance where weather conditions and heat loss are important factors.

2. Entry control system to support VA staff ability to view, communicate, and open the door remotely before allowing access to the space.

3. Door. Power Assisted Front Entrance Door operated by push pad on both sides of the door.

7. Electric. One (1) Exterior 50 AMP outlet with dedicated circuit for the Mobile Vet Center (MVC) enclosed in RV

Power Outlet Box that is Lockable and Weatherproof; location determined by the VA.

10RCS/STA703 VET CENTER Page 2 | 10 Lessor Initials/Date _______________

8. Flag. Flagpole for displaying the US Flag near building or near public main entrance; flag should be properly illuminated during the hours of darkness.

9. Signage. Lighted “EXIT” signs with battery backup.

B. LOBBY

1. Electric. One (1) per wall duplex outlet.

2. Dimmer. One (1) Dimmer Light Switch.

3. Flooring. Luxury Vinyl Tile/Plank (LVT/LVP); continues through hallway corridors.

4. Direct window access.

5. Window Coverings. Horizontal manual roller shades with solar glare and heat reduction.

6. Door. Access Controlled Door to clinical area with full-length glass panel and

7. Key. Access Controlled Door with electronic card access locking mechanism.

8. Corridors minimum of 5 feet in clear width.

9. Vinyl Corner Guards (from top of Vinyl Base) mounted at height 48” in hallways.

10. Drinking Fountain. A wall hung stainless Bottle Filling Station & Single ADA Cooler provided in the waiting area.

Maintenance and filter replacement by the Lessor.

11. Cable TV audio/video wall jack, HDMI, dual Data outlet and quadruplex Electrical outlet.

12. Wall backing and mounting materials for VA furnished television installed by Lessor; location determined by VA.

C. RESTROOM (UNISEX)

1. ADA handicap accessibility to include grab bars at commode.

2. Electric. One (1) GFCI duplex outlet.

3. Duress Alarm. Hardwired transmitter device.

4. Floor. Porcelain Floor Tile.

5. Sound Transmission Class (STC) 45.

6. Door. Power Assisted Door operatized by a push pad on both sides of the door.

7. Door. Solid Core Wood Doors with soundproofing jamb seal, a threshold seal, automatic door bottom, and soft closing door feature.

8. Wall. Porcelain Wall Tile. Tile 4 feet up from the floor, with tile accent strip.

9. Toilet. Commercial Grade with automatic toilet flushers.

10. Toilet Paper Dispenser. Dual roll

11. Vanity with sink and structure to hide exposed plumbing.

12. Mirror. Minimum of 24"x 36" over sink

13. Soap Dispenser. Automated touchless dispenser provided, maintained, and refilled by the Lessor.

14. Paper Towel Dispenser. Automated touchless dispenser provided, maintained, and refilled by the Lessor.

15. Built-in waste outlet.

16. Coat Hooks. Three (3) location determined by the VA.

17. Baby changing station.

D. RECEPTION

1. Data. Two (2) duplex outlets next to quadraplex Electrical outlets.

2. Electric. Two (2) quadraplex outlets next to duplex Data outlets.

3. Electric. Two (2) duplex Electrical outlets at counter height.

4. Duress Alarm. Hardwired transmitter device.

5. Dimmer. One (1) dimmer light switch.

6. Floor. Luxury Vinyl Tile (LVT).

7. Window Coverings. Horizontal manual roller shades with solar glare and heat reduction.

8. Countertop. Solid Surface Countertop utilizing concealed mounting brackets where practicable.

9. Direct access to lobby area.

10RCS/STA703 VET CENTER Page 3 | 10 Lessor Initials/Date _______________

10. Reception area contiguous with the Program Support Assistant; glass door or window to observe the lobby area.

E. OFFICES

1. Data. Two (2) duplex outlets next to quadraplex Electrical outlets. (See diagram)

2. Electric. Two (2) quadraplex outlets next to duplex Data outlets. (See diagram)

3. Electric. Two (2) duplex outlets on the opposite walls. (See diagram)

4. Duress Alarm. Wireless transmitter device.

5. Dimmer. One (1) Dimmer light switch.

6. Floor. Carpet Tile.

7. Window Coverings. Horizontal manual roller shades with solar glare and heat reduction.

8. Door. Solid Core Wood Doors with soundproofing jamb and threshold seals, and automatic door bottom.

9. Key. Master keyed with locking mechanism on inside of frame.

10. Sound Transmission Class (STC) 45.

11. Coat Hooks. Three (3) location determined by the VA.

12. Typical office layout diagram with data and electric placement.

F. GROUP COUNSELING ROOM

1. Data. Four (4) duplex outlets; one on each wall.

2. Electric. Four (4) duplex outlets; one on each wall, next to data outlets.

3. Duress Alarm. Hardwired transmitter device with protective clear cover.

4. Dimmer. One (1) Dimmer light switch.

5. Floor. Carpet Tile.

6. Window Coverings. Horizontal manual roller shades with solar glare and heat reduction.

7. Door. Solid Core Wood Doors with soundproofing jamb and threshold seals, and automatic door bottom.

8. Key. Master keyed with locking mechanism on inside of frame.

9. Sound Transmission Class (STC) 45.

10. Coat Hooks. Three (3) location determined by VA.

11. Cable TV audio/video wall jack, HDMI, dual Data outlet and quadruplex Electrical outlet.

10RCS/STA703 VET CENTER Page 4 | 10 Lessor Initials/Date _______________

12. Wall backing and mounting materials for VA furnished television installed by Lessor; location determined by VA.

G. KITCHEN / EMPLOYEE BREAK ROOM

1. Electric. One (1) duplex GFI outlet for refrigerator.

2. Electric. Two (2) duplex GFI outlets at counter height.

3. Electric. Three (3) duplex outlets, one on each wall, 18” from floor.

4. Floor. Luxury Vinyl Tile (LVT).

5. Wall. Perimeter walls extend from floor slab or 12 inches above the ceiling grid and fill with fiberglass bat insulation.

6. Door. Solid Core Wood Doors with soundproofing jamb and threshold seals, automatic door bottom, and soft closing door feature.

7. Key Control. Controlled access to the space; electronic lock with pin lever or electronic key card entry system and door lock.

8. Sound Transmission Class (STC) 45.

9. Cabinets. Upper and lower kitchen cabinets,

10. Countertop. Minimum 10’ feet solid surface countertop (Quartz or Corian).

11. Sink. Double compartment stainless sink.

12. Garbage Disposal.

13. Dishwasher provided by the Lessor.

14. Microwave Oven (1.7 cu. ft. minimum) provided by the Lessor.

15. Refrigerator (20-25 cu. ft. minimum) with water feed and ice maker provided by the Lessor.

H. JANITORIAL / UTILITY CLOSET

1. Electric. Two (2) duplex GFCI outlets.

2. Key Control. Controlled access to the space; electronic lock with pin lever or electronic key card entry system and door lock.

3. Floor. Sealed concrete floor.

4. Shelving. Adjustable wire shelving on two walls.

5. Sink. Mop Sink.

I. SUPPLY / STORAGE ROOM

1. Data. Two (2) duplex outlets, next to quadraplex electrical outlets.

2. Electric. Two (2) quadraplex outlets, next to data outlets.

3. Electric. Two (2) duplex outlets at counter height.

4. Floor. Luxury Vinyl Tile (LVT).

5. Door. Solid Core Wood Doors with soundproofing jamb and threshold seal, automatic door bottom, soft closing door feature.

6. Key Control. Controlled access to the space; electronic lock with pin lever or electronic key card entry system and door lock.

7. Cabinets. Casework cabinetry and counter provided by VA furniture vendor.

8. Lessor provided and installed independent network switch and IP address to support the Cable television, Business High Speed Internet Wi-Fi Router, and Security Alarm Control Panel; final location determined by VA.

J. TELECOMMUNICATIONS ROOM

1. The Lessor shall provide all equipment, material, parts, and labor to complete the room requirements.

2. Walls. All perimeter walls extend from floor slab to structural system (deck) to prevent up and over access.

3. Fire rated ¾” plywood backboard (rating must be visible) for mounting service provider/security/video and similar equipment.

10RCS/STA703 VET CENTER Page 5 | 10 Lessor Initials/Date _______________

4. Floor. Concrete Floor.

5. Door. Solid Core Wood Door with the veneer to match the existing suite doors.

6. Door. Metal frame with dead lock pin, automatic locking upon entry and exit.

7. No windows or other openings.

8. Overhead lighting in front and back of the network rack.

9. Temperature controlled and maintained at 69 degrees on a 24x7 basis; Lessor provided mini split HVAC system.

10. One (1) 45U network (24wX48dX80h) four post channel rack with vertical cable management (see Appendix B, sheet 37 of the Infrastructure Standard for Telecommunications Spaceshttps://www.cfm.va.gov/til/dguide/OIT- InfrastrucStdTelecommSpaces.pdf for equipment specifications.

11. Rack secured to the floor and seismically braced to the building.

12. Provide a minimum of 3 foot of clearance on front and rear sides of the installed rack.

13. Data racks shall have vertical and horizontal organizers affixed.

14. Two (2) quadraplex Electrical outlets, centrally mounted above ladder rack system.

15. Cable tray ladder rack from the wall to the top of relay rack, allowing for a pathway to conduits and 110 blocks.

16. Category 6A performance category of all installed untwisted shielded pair (UTP) copper distribution elements

(permanent link, patch panels and cables, and work area outlet (WAO) jacks) for network data transmission.

17. UTP patch panels. If flat patch panels are used, provide 1RU (rack unit) of horizontal cable management equipment above and below each patch panel (2RU between patch panels). Horizontal cable managers are not necessary if angled patch panels are used (see Appendix B, sheet 29, plate 2 of the Infrastructure Standard for Telecommunications Spaces).

18. Patch panels placed in the front top 1/3 of the network rack (RUs 31-45).

19. Rack-mounted uninterruptible power supply (UPS) and power distribution unit (PDU) equipment at the bottom of the network rack, beginning at RU1.

20. Four (4) quadraplex Electrical 120V 20A convenience power outlet with NEMA 5-15/20 outlets on each wall;

power to support the network rack.

21. Two (2) each L5-30 locking outlets on separate circuits for redundancy.

22. One (1) single-phase 120V L5-30 input and one (1) single-phase L5-30 output rack-mounted UPS supporting up to

2880VA of equipment load and providing ten (10) minutes of battery backup.

23. Two (2) zero-U vertical rack PDUs with L5-30 inputs and a minimum of six (6) each NEMA 5-15 outlets to support

IT equipment. One rack PDU shall be powered via the UPS.

24. Bonding system compliant with the requirements of ANSI/TIA-607-D to include Primary Bonding Busbar (PBB), Rack Bonding Busbar (RBB), Telecommunications Equipment Bonding Conductor (6 AWG), and Rack Bonding Conductor (6 AWG). Install RBB in the top rear RU position in the network rack. Network rack and cable tray sections shall be bonded. Unit Bonding Conductors (UBCs) and their connection to the RBB and network equipment by others. See Appendix B, sheet 24 of the Infrastructure Standard for Telecommunications Spaces for additional guidance.

25. One conduit pathway from Telecommunications Room point of demarcation to connect the building with AT&T or local exchange carrier.

a. A direct run from the street, where the circuits enter the building, to the wall or rack is preferred.

b. Sizing of conduits must be based on a 40 percent fill.

26. Provide, install, and coordinate with AT&T or the local exchange carrier (LEC) to bring in both fiber and copper infrastructure into the Telecommunications Room. If carrier equipment requires power to ensure the facility has internet during a power outage, install the carrier equipment in the network rack and power via the UPS. Provide and install shelf equipment as necessary to support equipment not designed to be mounted in a standard network rack.

27. All telecommunications services are terminated in the Telecommunications Room.

28. Access to Telecommunications Room restricted to VA OIT or persons authorized by VA OIT; not to include facility

Lessor or any other tenant.

29. Access controls to the space include VA cored lock, access card and PIN number, as a secondary authentication.

30. Ability to scan the badge reader/card reader followed by a PIN # allows for 2 factor authentication.

31. Scramble Pad type PIN readers are recommended.

32. VA Cored Lock. Provide core to VA for VA OIT TR keying, return to Lessor for installation.

33. Simplistic SMIC (small format interchangeable core) SFIC Cores, Keys, Locks type lock, core, and hardware.

https://www.cfm.va.gov/til/telecom.asp https://www.cfm.va.gov/til/dguide/OIT-InfrastrucStdTelecommSpaces.pdf https://www.cfm.va.gov/til/dguide/OIT-InfrastrucStdTelecommSpaces.pdf https://www.cfm.va.gov/til/telecom.asp https://www.cfm.va.gov/til/telecom.asp https://www.cfm.va.gov/til/telecom.asp https://gcc02.safelinks.protection.outlook.com/?url=https%3A%2F%2Fwww.cnclathing.com%2Fguide%2Fwhat-is-sfic-core-understanding-sfic-cores-keys-locks-sfic-vs-lfic-cnclathing&data=04%7C01%7C%7C744c655ca3524a55295908d9e674c969%7Ce95f1b23abaf45ee821db7ab251ab3bf%7C0%7C0%7C637794211682608005%7CUnknown%7CTWFpbGZsb3d8eyJWIjoiMC4wLjAwMDAiLCJQIjoiV2luMzIiLCJBTiI6Ik1haWwiLCJXVCI6Mn0%3D%7C3000&sdata=RpG%2B0GjKnhA5iowhXuA61BZN%2Fex4gnYwTXxY12uuqrg%3D&reserved=0

10RCS/STA703 VET CENTER Page 6 | 10 Lessor Initials/Date _______________

34. Metal frame door with dead lock pin, automatic locking upon entry and exit for a secure room.

35. Automatic door closure installed, with mortise lockset and deadbolt lock according to VA security regulations.

36. Door to the data closet solid core wood or metal door.

37. Intrusion Detection alarm to detect entry into the room with local audible alarm.

38. Motion Intrusion detection alarm system to detects entry into the room with local audible alarm.

39. Intrusion detector essential features:

a. A remote, key operated activation/deactivation switch installed outside the room and adjacent to the room entrance door frame and/or a central alarm ON-OFF control.

b. An automatic reset capability following intrusion detection.

c. Locally sounding alarm, remote visual and/or audio annunciators must be at a location within the facility which ensures 24-hour monitoring.

40. Motion Sensor Lights activate upon entry; sufficient lighting installed for safe passage and to permit Security

Camera identification in the space.

41. Please refer to the OIT Enterprise Facility IT Support Infrastructure Standards for details Infrastructure Standards for Telecommunications Spaces.

K. TELECOMMUNICATIONS DATA OUTLETS (TO CONNECT INTO THE VA NETWORK)

1. Standard Data Outlets: Each data outlet device location will have four (4) Work Area Outlet (WAO) Standard

Density design cable runs that terminate on the high-density rack mounted patch panel in the Telecommunications Room.

2. Wall Mounted Phones: Any jacks for wall mounted phones should have 1 data cable to support VoIP, and be on a 1 port metal plate, and accommodate RJ45. Cabling must be installed according to BISCI standards.

3. All permanent link cabling from the Telecommunications Room to the outlet require continuous runs with no splices and be less than 295’.

4. Patch Panels, jacks, and cables require CAT 6A and shall be tested and certified; test results provided to VA COR.

5. Location of Data Outlets:

a. If construction at the data outlet location is drywall, provide flush-mounted single-gang outlet boxes with four-port base plates and applicable wall device faceplates (cable installed behind drywall).

b. If the construction at the data outlet location is a solid wall, provide surface-mounted single-gang outlet boxes with four-port base plates and applicable wall device faceplates (cable installed in plastic wall mold equipped with protective insulator or sleeve).

6. The Lessor shall provide and install all cable runs throughout the space.

7. A telecommunications services shall be terminated in the facility Telecommunications Room.

8. The Lessor shall follow VA naming and labeling conventions in section 5.1.5, Information Transport Systems

Equipment and Component Labeling, of the Infrastructure Standard for Telecommunications Spaces.

Attached labels at the patch panel and wall plate; easily visible and printed, hand-written labels are prohibited.

L. SECURITY

1. Facility Security Level (FSL)

a. Refer to the Facility Security Level (FSL) requirements exhibit included in the lease award contract.

b. Provide a level of security which reasonably deters unauthorized entry during regular and non-duty hours.

c. Security System Monitoring and Maintenance provided by the Lessor and paid through the annual rent.

d. Tenant shall have security within the tenant space, separate from that of the general building security.

e. Key fobs, card readers, or electronic keypad for employee access.

f. No public access to the offices will be allowed.

2. ENTRY CONTROL SYSTEM

a. Tenant shall have the ability to view, communicate, and open the door remotely before allowing access.

b. Ai Phone Video Master Station

c. Ai Phone Video Door Station; surface mount https://www.cfm.va.gov/til/telecom.asp

10RCS/STA703 VET CENTER Page 7 | 10 Lessor Initials/Date _______________

d. System reports to master station; location determined by VA.

e. Indoor Tone Chime (Qty 3)

3. SECURITY ALARM

a. Lessor shall design, provide equipment, install, maintain, and complete software updates.

b. System to alarm upon illegal entry or loitering and to prevent unauthorized entry.

c. Keypad to disarm the building installed; location determined by VA.

d. Alarm sensors required on all exterior doors and windows.

e. Motion detectors provided in the lobby and the main corridors.

f. Access code updates are included in the lease and coordinated with VA.

g. Security system tested quarterly by the Lessor; a copy of the report sent to VA.

4. CLOSED CIRCUIT TELEVISION SYSTEM (CCTV)

a. Lessor shall design, provide equipment, install, maintain, and complete software updates.

b. System Monitoring and Maintenance provided by the Lessor and paid through the annual rent.

c. 100% browser-based system, requiring no server or software installation.

d. Single cabinet, stand-alone system reports to master station; location determined by VA.

e. Lessor to provide independent network switch and IP address to support the system; location determined by VA (Storage Room).

f. Lessor to provide two (2) tablets with the system software for security monitoring.

g. CCTV system supports the entry control system, 30-day time-lapse video recording, and VA staff ability to view, communicate, and open the door remotely before allowing access to the space.

h. Cameras (exterior) installed to provide unobstructed coverage of pedestrian entrances and exits.

i. Cameras (interior) installed in the lobby, the main corridors, and OIT DATA closet.

j. CCTV system testing and acceptance by the Government is required prior to occupancy.

k. Lessor managed preventive maintenance program for all security systems installed.

5. DURESS ALARM SYSTEM

a. Lessor shall design, provide equipment, install, maintain, and complete software updates for the Duress Alarm system.

b. System reports to master station; location determined by VA.

c. Master station displays the transmitter device location upon call notification.

d. Each transmitter device (hardwired and wireless) individual zoned.

e. Hardwired (restrooms and group rooms). Approximately 7 zones.

f. Wireless. Approximately 15 zones.

g. Audible notification to sound throughout corridors.

h. Duress Alarm System will notify the alarm company which will call the Vet Center to take the necessary action and alert other local authorizes.

6. BUILDING AND ACCESS CONTROL SYSTEMS

a. Lessors are prohibited from connecting any portion of their building and access control systems (BACS) to any Federally Owned or Operated IT Network.

b. BACS include systems providing fire and life safety control, physical access control, building power and energy control, electronic surveillance, and automated HVAC, elevator, or building monitoring and control services (including IP addressable devices, application servers, or network switches).

c. Lessor is prohibited from installing BACS control panels in the Telecommunication Room.

d. The Lessor shall provide an independent network switch and IP address to support the Cable television, Guest Wi-Fi Router, and Security Alarm Control Panel; location determined by VA.

7. TELECOMUNICATIONS ROOM

a. Access to Telecommunications Room restricted to VA OIT or persons authorized by VA OIT; not to include facility Lessor or any other tenant.

10RCS/STA703 VET CENTER Page 8 | 10 Lessor Initials/Date _______________

b. Access controls to the space include VA cored lock, access card and PIN number, as a secondary authentication.

c. Ability to scan the badge reader/card reader followed by a PIN # allows for 2 factor authentication.

d. Scramble Pad type PIN readers are recommended.

e. VA Cored Lock. Provide core to VA for VA OIT TR keying, return to Lessor for installation.

f. Simplistic SMIC (small format interchangeable core) SFIC Cores, Keys, Locks type lock, core, and hardware.

g. Metal frame door with dead lock pin, automatic locking upon entry and exit for a secure room.

h. Automatic door closure installed, with mortise lockset and deadbolt lock according to VA security regulations.

i. Door to the data closet solid core wood or metal door.

j. Intrusion Detection Alarm to detect entry into the room with local audible alarm.

k. Intrusion Detection Alarm system to detect entry into the room with local audible alarm.

l. Motion Intrusion detection alarm system to detects entry into the room with local audible local.

m. Intrusion detector essential features:

i. A remote, key operated activation/deactivation switch installed outside the room and adjacent to the room entrance door frame and/or a central alarm ON-OFF control.

ii. An automatic reset capability following intrusion detection.

iii. Locally sounding alarm, remote visual and/or audio annunciators must be at a location within the facility which ensures 24-hour monitoring.

n. Motion Sensor Lights activate upon entry; sufficient lighting installed for safe passage and to permit

Security Camera identification in the space.

o. Please refer to the OIT Enterprise Facility IT Support Infrastructure Standards for details Infrastructure

Standards for Telecommunications Spaces.

M. FINISHES

1. The Vet Center shall provide a digital Finish/Color Board as a preferred option.

Luxury Vinyl Tile/Plank 5mm thickness + 20mil wear layer for lobby, corridors, and supply storage; Carpet Tile for offices and group rooms; Corian Solid Surface Counter for kitchen and reception; Oil Based Door Stain; Four Paint Colors with two serving as accent color; Restroom Tile flooring wall (4’ from the floor) and accent strip; Acoustical Ceiling panels HIGH-NRC/HIGH-CAC.

2. The Lessor shall provide physical samples for VA final approval.

3. The Lessor shall repaint the space every 5 years. The Lessor shall maintain all wall covering and paint coatings in

“like new” condition for the life of the Lease, except where damaged due to the negligence of the Government.

Repainting of the space shall occur any time during occupancy if the paint is peeling or permanently stained. All repainted surfaces are at the Lessor’s expense, including the moving and returning of furnishings.

4. The Lessor shall replace flooring in the space every 5 years. The Lessor shall repair or replace flooring at any time during the life of the Lease except when damaged due to negligence of the Government. Repairing or replacing the flooring shall occur any time during occupancy if underlayment is exposed, noticeable variations in color or texture, loose tiles, tears, or tripping hazards are present. All repaired or replaced flooring surfaces are at the Lessor’s expense, including the moving and returning of furnishings.

N. SIGNAGE

1. EXTERIOR SIGNAGE AND MAIN ENTRY DOOR

a. VHA Readjustment Counseling Service (RCS) created a Vet Center Exterior Signage Guide to provide guidance on our exterior signage; exterior signs must comply with these standards.

b. VA signage design approval is required prior to fabrication and installation.

c. Provide luminated Vet Center logo exterior signage on building.

https://gcc02.safelinks.protection.outlook.com/?url=https%3A%2F%2Fwww.cnclathing.com%2Fguide%2Fwhat-is-sfic-core-understanding-sfic-cores-keys-locks-sfic-vs-lfic-cnclathing&data=04%7C01%7C%7C744c655ca3524a55295908d9e674c969%7Ce95f1b23abaf45ee821db7ab251ab3bf%7C0%7C0%7C637794211682608005%7CUnknown%7CTWFpbGZsb3d8eyJWIjoiMC4wLjAwMDAiLCJQIjoiV2luMzIiLCJBTiI6Ik1haWwiLCJXVCI6Mn0%3D%7C3000&sdata=RpG%2B0GjKnhA5iowhXuA61BZN%2Fex4gnYwTXxY12uuqrg%3D&reserved=0 https://www.cfm.va.gov/til/dguide/OIT-InfrastrucStdTelecomSpaces.pdf https://www.cfm.va.gov/til/dguide/OIT-InfrastrucStdTelecomSpaces.pdf

10RCS/STA703 VET CENTER Page 9 | 10 Lessor Initials/Date _______________

d. Provide main entry door decal signage.

e. Provide Vet Center logo exterior signage on Marquee.

f. Provide Vet Center logo exterior signage on Monument.

g. Signage shall be legible from main serving road.

h. Signage shall comply with local municipality codes, maximum size in accordance with local building code.

i. Refer to the SOW ASR-B Vet Center Exterior Signage Guide for specifications and requirements associated with the exterior signage.

2. INTERIOR SIGNAGE

a. Provide interior signage for a standard wall sign, ADA compliant braille sign.

b. Refer to SOW ASR-C Interior Signage Guide.

c. VA Signage Design Guide VA Design Signage

d. Mounting heights are 5’-0” to top of sign and 2” from door frame.

O. SOUND TRANSMISSION CLASS (STC)

1. Sound Transmission Class (STC) 45. Sound resistant enclosure designed to assure speech privacy and achieve a minimum of STC 45 in Offices, Group Rooms, Restrooms, and Kitchen.

2. Sound Acoustic Field Study:

a. Lessor shall conduct a post construction Sound Acoustic Field Study.

b. Noise Source shall be placed in each space to measure the decibels in the source space, the adjoining rooms, and corridors to determine the noise transmission delta resulting in the calculated STC rating.

3. Examples which may help achieve a sound resistant enclosure include:

a. Door Thickness 2 ¼”-2 ¾”, Sound Dampening Cores, Glass Insert Doors may require 1” insulated glass with

¼” laminated glass on both sides, soundproofing jamb seal, threshold seal, and automatic door bottom, Acoustical Ceiling Insulation 3 ½”, Acoustical Ceiling Panel Tiles System, Walls floor to deck or 12-18” above ceiling, Walls with two layers 5/8”); Metal Studs 20-24” spacing, and Rockwool Sound insulation or equal.

P. SOUND MASKING SYSTEM

1. Lessor shall design, provide equipment, install, maintain, and complete software updates.

2. Sound masking system to consist of a series of ceiling speakers installed in a grid-like pattern, with a method of controlling the speaker’s output.

3. System shall use small adjustment zones to offer control volume and frequency.

4. System zones to include lobby area, hallways/corridors, and group rooms.

5. System reports to master station; location determined by VA.

Q. SPACE REQUIREMENTS

Approximate room sizes.

https://www.cfm.va.gov/til/dManual/dmSignage.pdf

10RCS/STA703 VET CENTER Page 10 | 10 Lessor Initials/Date _______________

R. CONCEPTUAL FLOOR PLAN

Vet Center External Signage Guide

APRIL 2022

The U.S. Department of Veterans Affairs (VA) Veterans Health Administration (VHA) Readjustment Counseling Service (RCS) created this Vet Center Exterior Signage Guide to provide guidance on all exterior signage related to the Vet Center brand. This guide shall serve as the official directive and final authority for all Vet Center signage standards until a revised version is issued and released.

All exterior sign applications must comply with these standards without exception. Alteration of Vet Center logo colors or design is prohibited unless otherwise stated in the following documentation. All signs must be in accordance with the local code and landlord specifications.

NOTE: VA will approve all signage design schematics prior to fabrication and installation.

Variation shall not exist outside these design specifications without prior authorization. Sign vendor or lessor shall contact the Contracting Officers Representative (COR) for review and approval of any modifications through VA’s Readjustment Counseling Service Communications Office.

Purpose

Purpose 1 Vet Center Exterior Signage Requirements 4 Exterior Signage: Preferred Application 6

Channel Letters on Raceway 6 Channel Letters on Raceway Specifications 7

Exterior Signage: Secondary Applications 8 Lightbox and Multi-Tenant Signs 8 Single Tenant Monument and Pylon Signs 10 Restrictive Tenant Panel Sign 12

No Building, Monument, or Pylon Signage Exterior Panel Sign 14

Door Decal Signage 16

Table of Contents

Vet Center Exterior Signage Guide

1. Install time and design/specifications must be included in bid quote but be listed as separate line items.

2. This service order and installation shall be coordinated with Contracting Officers Representative (COR).

3. The installation shall occur and be completed Monday-Friday between the hours of 8:00 AM-4:30 PM.

4. Deliveries must be scheduled through the COR before installation.

5. Confirmation from vendor shall be sent via email to COR who will inspect that all products are installed 100%. Upon completion of inspection, the COR will email the Contracting Officer authorizing that products have been received complete and that payment can be released.

6. Any damage to the Vet Center facility incurred through the installation process must be repaired within 30 days at the vendor’s expense.

GENERAL REQUIREMENTS

• Lessor shall provide samples for the VA to review and approve prior to fabrication.

• Lessor shall provide Vet Center logo Exterior Signage on the Building Exterior as well as Door Decal signage.

• Lessor shall provide Vet Center logo Exterior Signage on Marquee.

• Lessor shall provide Vet Center logo Exterior Signage, Monument sign.

• Lessor shall develop, provide, deliver, stage/move, and install the new exterior sign.

• Lessor shall provide all the equipment, cabling, labor, materials, and sign.

• Signage shall be legible from main serving road.

• Signage shall comply with local municipality’s codes and specifications.

SIZE: Maximum size in accordance with local building code.

EXTERIOR SIGNAGE REVIEW

C h an n el L et te rs o n R ac ew ay

PREFERRED EXTERIOR SIGNAGE APPLICATION:

CHANNEL LETTERS ON A RACEWAY

Every effort shall be made to construct channel letters on a raceway, as this is the preferred application. In all cases where the channel letters on raceway sign is constructed for a building exterior, the exterior sign should be raceway mounted, with the raceway color matching the face of the building. The power connectors for the logo’s star and red stripe shall be remote mounted with external power links.

LIGHTING: In the case where illuminated signage is not permitted by ordinance, ½” thick stud-mounted acrylic letters shall be used.

Channel Letters on a Raceway Signs

CHANNEL LETTERS ON A RACEWAY

COLOR SPECIFICATIONS FOR CHANNEL LETTERS ON A RACEWAY SIGN

Colors are to be pigmented Translucent Vinyl over White Acrylic Faces with a minimum of 3/8th of an inch white reveal around each colored area. Trim cap and returns shall be white. White LED Illumination. Raceway mounted channel letters with raceway to match building. Each letter should be one piece, with vinyl and white space used to simulate the stencil effect.

BUILD SPECIFICATIONS FOR CHANNEL LETTERS ON A RACEWAY SIGN

MATERIAL SPECIFICATONS FOR CHANNEL LETTERS ON A RACEWAY SIGN

STRIPE AND STAR

8” Deep Cans Remote Mounted wire to main text with connectors

White Trim Cap & White Returns

VET CENTER

5” Deep Cans

White LED Lamps

POWER

CONNECTOR:

Painted to match building facade

ATTACHMENTS:

All attachments to be appropriate to exterior wall construction

RACEWAY:

Raceway 3” x 8” painted to match building facade

Low Voltage Power Supply

Internal Power Connection

Typical Wall Construction

EXTERIOR WALLCHANNEL LETTERS

CHANNEL LETTER

FACES:

Channel letter faces should have a minimum 3/8th of an inch white reveal around the colored overlays.

RED- PANTONE 1797C

CMYK: 13 94 83 3

DARK BLUE- PANTONE 647C

CMYK: 91 63 20 4

LIGHT BLUE- PANTONE 7461C

CMYK: 96 42 6 0

NOTE: The black outline is for visual reference only - trim cap is to be white. Pigmented vinyl or printed translucent vinyl application shall be used. If using printed translucent vinyl applications, the vinyl should be printed with an image-white-image process to ensure color consistency and density when the sign is illuminated. The image should be printed in color, overprinted in white, and overprinted again in color to avoid appearance of color washout when illuminated.

L ig h tb ox a n d

M u lt i-T en an t

SECONDARY EXTERIOR SIGNAGE APPLICATION:

LIGHTBOX AND MULTI-TENANT DESIGN

In the case where the preferred application of the channel letters on a raceway sign is not possible, the secondary application choice is a lightbox and multi-tenant design. Where a lightbox sign is the only choice available, the logo design shall appear as shown in the color specifications for lightbox and multi-tenant design.

LIGHTING: Determined by existing signage.

Lightbox and Multi-Tenant Design Signs

LIGHTBOX AND MULTI-TENANT SIGN

COLOR SPECIFICATIONS FOR LIGHTBOX AND MULTI-TENANT SIGN

BUILD SPECIFICATIONS FOR LIGHTBOX AND MULTI-TENANT SIGN

Pigmented vinyl or printed translucent vinyl application shall be used. If printing the image is required, the colors must match the specifications shown. Sign shall match existing site signage. New polycarbonate or acrylic panels shall be used.

MATERIAL SPECIFICATONS FOR LIGHTBOX AND MULTI-TENANT SIGN

PREFERRED DESIGN - NEW SIGNS

Due to the restrictive nature of sign codes and available space, accomodations have been made to allow a slightly smaller clear space but not to exceed the height or width of the star at scale.

Logo maximized to fit allowable lightbox width.

Clear space around logo cannot exceed the height or width of the star at scale within the lightbox space.

ALLOWABLE EXCEPTIONS: Maximizing Available Space In the case where the logo design cannot expand symmetrically to the size of the lightbox, exceptions are allowed to maximize the logo design in either the height or the width of the lightbox space.

Logo maximized to fit allowable lightbox height.

RED- PANTONE 1797C

CMYK: 13 94 83 3

DARK BLUE- PANTONE 647C

CMYK: 91 63 20 4

LIGHT BLUE- PANTONE 7461C

CMYK: 96 42 6 0

NOTE: The black outline is for visual reference only - trim cap is to be white. Pigmented vinyl or printed translucent vinyl application shall be used. If using printed translucent vinyl applications, the vinyl should be printed with an image-white-image process to ensure color consistency and density when the sign is illuminated. The image should be printed in color, overprinted in white, and overprinted again in color to avoid appearance of color washout when illuminated.

Si n gl e

T en an t

M on u m en t an d

P yl on

SECONDARY EXTERIOR SIGNAGE APPLICATION:

SINGLE TENANT MONUMENT AND PYLON SIGNS

In the case where the preferred application of the channel letters on a raceway sign is not possible, another secondary application choice is a single tenant monument or pylon sign design. The logo design shall appear as shown in the color specifications. If the sign face is wide and short, the vendor shall maximize the size of the logo leaving an appropriate amount of white space around the logo as indicated in the build specifications guidance.

LIGHTING: Determined by existing signage.

Single Tenant Monument and Pylon Signs

SINGLE TENANT MONUMENT AND PYLON SIGN

COLOR SPECIFICATIONS FOR SINGLE TENANT MONUMENT AND PYLON SIGN

Pigmented vinyl or printed translucent vinyl application shall be used. If printing the image is required, the colors must match the specifications shown. Sign shall match existing site signage. New polycarbonate or acrylic panels shall be used.

BUILD SPECIFICATIONS FOR SINGLE TENANT MONUMENT AND PYLON SIGN

MATERIALS FOR SINGLE TENANT MONUMENT AND PYLON SIGN

RED- PANTONE 1797C

CMYK: 13 94 83 3

DARK BLUE- PANTONE 647C

CMYK: 91 63 20 4

LIGHT BLUE- PANTONE 7461C

CMYK: 96 42 6 0

PREFERRED DESIGN - NEW SIGNS

Due to the restrictive nature of sign codes and available space, accomodations have been made to allow a slightly smaller clear space but not to exceed the height or width of the star at scale.

Logo maximized to fit allowable lightbox width.

Clear space around logo cannot exceed the height or width of the star at scale within the lightbox space.

ALLOWABLE EXCEPTIONS: Maximizing Available Space In the case where the logo design cannot expand symmetrically to the size of the lightbox, exceptions are allowed to maximize the logo design in either the height or the width of the lightbox space.

Logo maximized to fit allowable lightbox height.

NOTE: The black outline is for visual reference only - trim cap is to be white. Pigmented vinyl or printed translucent vinyl application shall be used. If using printed translucent vinyl applications, the vinyl should be printed with an image-white-image process to ensure color consistency and density when the sign is illuminated. The image should be printed in color, overprinted in white, and overprinted again in color to avoid appearance of color washout when illuminated.

R es tr ic ti ve

T en an t

P an el

RESTRICTIVE TENANT PANEL SIGNS

In the case where the preferred application of the channel letters on a raceway sign is not possible, a secondary application choice is a restrictive tenant panel sign. When there is nothing but a solid, non-illuminated panel to use (common in office complexes, with multi-tenant panels) the words “Vet Center” shall be used in the appropriate color and font for that sign. Wherever possible, the logo shall be shown. When the logo cannot be used, the words “Vet Center” shall be used.

LIGHTING: Determined by existing signage.

Restrictive Tenant Panel Signs

VET CENTER

RESTRICTIVE TENANT PANEL SIGN

COLOR SPECIFICATIONS FOR RESTRICTIVE TENANT PANEL SIGN

BUILD SPECIFICATIONS FOR RESTRICTIVE TENANT PANEL SIGN

The materials should match the existing signage, and can range from cut vinyl lettering to routed/engraved tenant panels.

MATERIAL SPECIFICATIONS FOR RESTRICTIVE TENANT PANEL SIGN

RED- PANTONE 1797C

CMYK: 13 94 83 3

DARK BLUE- PANTONE 647C

CMYK: 91 63 20 4

LIGHT BLUE- PANTONE 7461C

CMYK: 96 42 6 0

NOTE: The black outline is for visual reference only - trim cap is to be white. Pigmented vinyl or printed translucent vinyl application shall be used. If using printed translucent vinyl applications, the vinyl should be printed with an image-white-image process to ensure color consistency and density when the sign is illuminated. The image should be printed in color, overprinted in white, and overprinted again in color to avoid appearance of color washout when illuminated.

PREFERRED DESIGN - NEW SIGNS

Due to the restrictive nature of sign codes and available space, accomodations have been made to allow a slightly smaller clear space but not to exceed the height or width of the star at scale. When possible, follow the guidelines for logo spacing within the restricitve tenant panel.

Logo maximized to fit allowable lightbox width.

Clear space around logo cannot exceed the height or width of the star at scale within the lightbox space.

ALLOWABLE EXCEPTIONS: Maximizing Available Space In the case where the logo design cannot expand symmetrically to the size of the lightbox, exceptions are allowed to maximize the logo design in either the height or the width of the lightbox space.

Logo maximized to fit allowable lightbox height.

E tr an ce P an el

S ig

EXTERIOR POSTED PANEL SIGN

Where there is no ability to place a channel lettering on raceway sign, monument sign, or pylon sign, thus restricting you to a sign by the entrance door, an exterior posted panel sign shall be used. If space is not available by the entrance door, a non-illuminated post and panel sign shall be constructed outside of the building, near the main entrance. All exterior Vet Center signage within a facililty, i.e. medical building, must comply with regulations set forth by the Americans with Disabilities Act (ADA) and include braille, as required.

LIGHTING: Determined by signage placement.

Suite 1A

Exterior Posted Panel Sign - Entrance Door or Nearby

EXTERIOR POSTED PANEL SIGN - ENTRANCE

DOOR OR NEARBY

COLOR SPECIFICATIONS FOR ENTRANCE PANEL SIGN

Pigmented vinyl or printed translucent vinyl application shall be used. If printing the image is required, the colors must match the specifications shown. Sign shall match existing site signage. New polycarbonate or acrylic panels shall be used.

MATERIAL SPECIFICATIONS FOR ENTRANCE PANEL SIGN

BUILD SPECIFICATIONS FOR ENTRANCE PANEL SIGN

ACCEPTABLE SIGN DESIGN

12”w x 8” h

A 2” d x 12” h x 36” w aluminum post and panel with internal 2” square posts is required. The sign base shall be no less than 24” above grade. (This is not to be confused with a directional sign.)

19” w x 6” h

36”

36”

12”

Suite 1A

RED- PANTONE 1797C

CMYK: 13 94 83 3

DARK BLUE- PANTONE 647C

CMYK: 91 63 20 4

LIGHT BLUE- PANTONE 7461C

CMYK: 96 42 6 0

NOTE: The black outline is for visual reference only - trim cap is to be white. Pigmented vinyl or printed translucent vinyl application shall be used. If using printed translucent vinyl applications, the vinyl should be printed with an image-white-image process to ensure color consistency and density when the sign is illuminated. The image should be printed in color, overprinted in white, and overprinted again in color to avoid appearance of color washout when illuminated.

DOOR DECAL SIGNAGE

The Lessor shall provide signage on the main entrance door. The door decal shall be printed on a clear background. A white poster-like background for the door decal display is unacceptable. The Vet Center Call Center number shall be shown as the numeric 1-877-927-8387 only. Avoid use of the “WAR-VETS” phonewords.

A full-color Vet Center logo shall be used with an accompanying “Connection.

Camaraderie. Community.” slogan in white. Alterations to this brand shall not be made. If other building notices are needed, such as an automatic door symbol, spacing accomodations can be made.

Accompanying font: Zilla Slab preferred; Rockwell is an approved alternative.

Door Decal Signage

D oo r D ec al

S ig n ag e

NOTE: (Above left) Spacing accomodations for automatic door symbol may be made. (Below) The door decal shall be printed on a clear background. A white poster-like background or a white stroke around the lettering is unacceptable.

DOOR DECAL SIGNAGE

COLOR SPECIFICATIONS FOR DOOR DECAL SIGNAGE

Digitally printed on clear vinyl application shall be used. The colors must match the color specifications of the logos.

BUILD SPECIFICATIONS FOR DOOR DECAL SIGNAGE

MATERIAL SPECIFICATIONS FOR DOOR DECAL SIGNAGE

[Vet Center Slogan Logo]

[Vet Center Name] Greatest Vet Center [Vet Center Address] 123 Lane, Greatest City, VA [Core Hours] Open Monday-Friday 8AM-4:30PM Ask about additional hours to meet your needs

[Vet Center Office Phone Number] (012) 345-6789

After Hours Vet Center Call Center

1-877-927-8387

Veterans Crisis Line Call 1-800-273-8255 and

Press 1 to receive confidential support 24 hours a day.

[VA Seal]

RED- PANTONE 1797C

CMYK: 13 94 83 3

DARK BLUE- PANTONE 647C

CMYK: 91 63 20 4

LIGHT BLUE- PANTONE 7461C

CMYK: 96 42 6 0

NOTE: The black background is for visual reference only. An additional white stroke around the letters of the Vet Center slogan logo should not be added for the purposes of the door decal. This differs from other designs used for prominent exterior signage.

Vet Center Internal Signage Guide

JANUARY 2025

VA Signage Design Manual Section 2.3 Mandatory VA Policy & Directive Signage Guidelines https://www.cfm.va.gov/til/dManual/dmSignage.pdf

Sheet Title:

Sheet No.:

VC - 01.01

SIGNAGE TYPE A1

1. TYPE: 1/16” RAISED ACRYLIC

COLOR: BLACK

TEXT: 1” HELVETICA

2. TYPE: GRADE 2 RAISED

BRAILE

COLOR: BLACK

3. TYPE: 1/16” BRUSHED METAL

FACE ACCENT BAR, SET

INTO CLEAR PANEL

COLOR: BRUSHED NICKEL

4. TYPE: 1/16” RAISED ACRYLIC

COLOR: BLACK

TEXT: 5/8” HELVETICA

5. TYPE: 1/8” ACRYLIC PANEL

COLOR: FROSTED W/ WHITE

BACK, 50% TRANSPARENT

6. TYPE: 1/8” ACRYLIC PANEL W/

BRUSHED METAL FACE

COLOR: BRUSHED NICKEL

7. DOUBLE SIDED FOAM TAPE

BETWEEN PANELS AND TO

WALL INSTALLATION

SIDE VIEW

COUNSELOR

116 1

9 1/2"

3/4

2 1 /2"

1/4

4 3 /4"

3/4

9" 1/8"

1/8"

7 3/4"

3/4" 8" 3/4"

7 1 /2"

COUNSELOR

3"

5'

- 0

Sheet No.:

Sheet Title:

VC - 01.01

SIGNAGE TYPE A1

1. TYPE: 1/16" RAISED ACRYLIC

COLOR: BLACK

TEXT: 1" HELVETICA

2. TYPE: GRADE 2 RAISED

BRAILLE

COLOR: BLACK

3. TYPE: 1/16" BRUSHED METAL

FACE ACCENT BAR, SET

INTO CLEAR PANEL

COLOR: BRUSHED NICKEL

4. TYPE: 1/16" RAISED ACRYLIC

COLOR: BLACK

TEXT: 5/8" HELVETICA

5. TYPE: 1/8" ACRYLIC PANEL

COLOR: FROSTED W/ WHITE

BACK, 50 TRANSPARENT

6. TYPE: 1/8" ACRYLIC PANEL W/

BRUSHED METAL FACE

COLOR: BRUSHED NICKEL

7. DOUBLE SIDED FOAM TAPE

BETWEEN PANELS AND

TO WALL INSTALLATION

3" = 1'-0"

SIGN TYPE A1

1/4" = 1'-0"

INSTALLATION DETAIL - TYPE A1

SIDE VIEW

COUNSELOR

116 1

9 1/2"

3/4

2 1 /2"

1/4

4 3 /4"

3/4

9" 1/8"

1/8"

7 3/4"

3/4" 8" 3/4"

7 1 /2"

COUNSELOR

3"

5'

- 0

Sheet No.:

Sheet Title:

VC - 01.01

SIGNAGE TYPE A1

1. TYPE: 1/16" RAISED ACRYLIC

COLOR: BLACK

TEXT: 1" HELVETICA

2. TYPE: GRADE 2 RAISED

BRAILLE

COLOR: BLACK

3. TYPE: 1/16" BRUSHED METAL

FACE ACCENT BAR, SET

INTO CLEAR PANEL

COLOR: BRUSHED NICKEL

4. TYPE: 1/16" RAISED ACRYLIC

COLOR: BLACK

TEXT: 5/8" HELVETICA

5. TYPE: 1/8" ACRYLIC PANEL

COLOR: FROSTED W/ WHITE

BACK, 50 TRANSPARENT

6. TYPE: 1/8" ACRYLIC PANEL W/

BRUSHED METAL FACE

COLOR: BRUSHED NICKEL

7. DOUBLE SIDED FOAM TAPE

BETWEEN PANELS AND

TO WALL INSTALLATION

3" = 1'-0"

SIGN TYPE A1

1/4" = 1'-0"

INSTALLATION DETAIL - TYPE A1

SIGNAGE TYPE A2

1. TYPE: 1/16” RAISED ACRYLIC

COLOR: BLACK

TEXT: 1” HELVETICA

2. TYPE: GRADE 2 RAISED

BRAILE

COLOR: BLACK

3. TYPE: 1/16” BRUSHED METAL

FACE ACCENT BAR, SET

INTO CLEAR PANEL

COLOR: BRUSHED NICKEL

4. TYPE: 1/16” RAISED ACRYLIC

COLOR: BLACK

TEXT: 5/8” HELVETICA

5. TYPE: 1/8” ACRYLIC PANEL

COLOR: FROSTED W/ WHITE

BACK, 50% TRANSPARENT

6. TYPE: 1/8” ACRYLIC PANEL W/

BRUSHED METAL FACE

COLOR: BRUSHED NICKEL

7. DOUBLE SIDED FOAM TAPE

BETWEEN PANELS AND TO

WALL INSTALLATION

8. TYPE: LETERS SET INTO 1/8”

ACRYLIC SLIDE PANEL

COLOR: BLACK TEXT /

BRUSHED NICKEL PANEL

TEXT: 5/8” HELVETICA

SIDE VIEW

1/8"

1/8"

FAMILY

COUNSELING

IN USE

3/4

1 1 /2"

4 3 /4"

1/4

2 1 /2"

3/4

1/

2"

9"

7 3/4" 3/4" 8" 3/4"

9 1/2"

FAMILY

3"

5'

- 0

COUSELING

IN USE

Sheet No.:

Sheet Title:

VC - 01.02

SIGNAGE TYPE A2

1. TYPE: 1/16" RAISED ACRYLIC

COLOR: BLACK

TEXT: 1" HELVETICA

2. TYPE: GRADE 2 RAISED

BRAILLE

COLOR: BLACK

3. TYPE: 1/16" BRUSHED METAL

FACE ACCENT BAR, SET

INTO CLEAR PANEL

COLOR: BRUSHED NICKEL

4. TYPE: 1/16" RAISED ACRYLIC

COLOR: BLACK

TEXT: 5/8" HELVETICA

5. TYPE: 1/8" ACRYLIC PANEL

COLOR: FROSTED W/ WHITE

BACK, 50 TRANSPARENT

6. TYPE: 1/8" ACRYLIC PANEL W/

BRUSHED METAL FACE

COLOR: BRUSHED NICKEL

7. DOUBLE SIDED FOAM TAPE

BETWEEN PANELS AND

TO WALL INSTALLATION

8. TYPE: ACRYLIC LETTERS SET

INTO 1/8" ACRYLIC SLIDE

PANEL

COLOR: BLACK TEXT /

BRUSHED NICKEL PANEL

TEXT: 5/8" HELVETICA

3" = 1'-0"

SIGN TYPE A2

1/4" = 1'-0"

INSTALLATION DETAIL - TYPE A2

SIDE VIEW

1/8"

1/8"

FAMILY

COUNSELING

IN USE

3/4

1 1 /2"

4 3 /4"

1/4

2 1 /2"

3/4

1/

2"

9"

7 3/4" 3/4" 8" 3/4"

9 1/2"

FAMILY

3"

5'

- 0

COUSELING

IN USE

Sheet No.:

Sheet Title:

VC - 01.02

SIGNAGE TYPE A2

1. TYPE: 1/16" RAISED ACRYLIC

COLOR: BLACK

TEXT: 1" HELVETICA

2. TYPE: GRADE 2 RAISED

BRAILLE

COLOR: BLACK

3. TYPE: 1/16" BRUSHED METAL

FACE ACCENT BAR, SET

INTO CLEAR PANEL

COLOR: BRUSHED NICKEL

4. TYPE: 1/16" RAISED ACRYLIC

COLOR: BLACK

TEXT: 5/8" HELVETICA

5. TYPE: 1/8" ACRYLIC PANEL

COLOR: FROSTED W/ WHITE

BA…