The SOP (138-46), effective August 31, 2022, and recertifiable through August 31, 2027, applies to Shop Supervisors, Boiler Plant Operators, and personnel responsible for Boiler Plant service and maintenance. The isolation procedure requires Boiler Plant Operators to turn off one of two valves—either the Emergency Stop Switch located on the Boiler Plant Master Panel or the Isolation Shut Off valve located outside the Boiler Plant Operator's office—whichever is closer. Monthly safety testing of all boilers is mandatory, with test dates recorded in Boiler Plant records and performed in accordance with the VHA Boiler Plant Safety Devices Testing Manual. Operators must be knowledgeable of the location, purpose, and proper function of all safety devices. A hierarchical notification chain exists for non-functional safety devices: Boiler Plant Operators notify the Boiler Plant Supervisor, who notifies the Chief Engineer, who notifies the Medical Center Director. The document references VHA Directive 1810 as governing policy and requires annual review with recertification every five years or when changes are mandated by VHA Notice or Directive. The SOP is signed by Jacob Morrical, Chief of Engineering Service Marion Campus, with distribution to all 138 supervisors.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ISOLATING BOILER PLANT FROM GAS SUPPLY LINE - MARION
SOP 138-46
VA Northern Indiana Health Care System
Signatory Authority:
Chief of Engineering
Responsible Owner:
Engineering
Service Line(s):
Engineering
Effective Date:
August 31, 2022
Recertification Date:
August 31, 2027
1. PURPOSE AND AUTHORITY
a. The purpose of the isolating boiler plant from gas supply line SOP is to establish procedures for the safe and efficient isolation of the Boiler Plant from the gas supply lines at VA Northern Indiana Health Care System (VANIHCS), Marion.
b. It is the VANIHCS policy that the isolation of the Boiler Plant from the gas supply line be in a safe and economical manner that complies with the requirements as listed in the VHA Directive 1810.
c. The Boiler Plant is essential to the functioning of the Medical Center and the operation of boilers requires well-trained operators, properly functioning safety equipment, well maintained boilers and support equipment, and proper operational procedures. This policy applies to the isolating of the Boiler Plant from the gas supply line for Shop Supervisor and all Boiler Plant Operators and others who are responsible for the service and maintenance of the Boiler Plant.
1. PROCEDURES
a. Boiler Plant Operator.
(1) Turn one (1) of two (2) Valves to OFF, both effectively do the same thing; whichever is closer.
(a) The Emergency Stop Switch is located on the Boiler Plant Master Panel
(b) The Isolation Shut Off valve is located outside the Boiler Plant Operator’s office.
b. Testing.
(1) The Boiler Plant Operator shall every month perform all the safety tests for each boiler.
Date of tests shall be noted in the records maintained in the Boiler Plant.
(2) Boiler Plant Operators must ensure that the testing procedures are performed in accordance with the VHA Boiler Plant Safety Devices Testing Manual located in the Boiler
August 31, 2022 SOP 138-46
Plant. Boiler Plant Operators must be knowledgeable of the location, purpose, and proper function of all safety devices.
2. ASSIGNMENT OF RESPONSIBILITIES
a. Engineering.
(1) Boiler Plant Operators.
Is to notify the boiler plant supervisor of any safety devices that are non-functional so that corrective action can be taken.
(2) Boiler Plant Supervisor.
Is to notify the Chief Engineer of any safety devices that are non-functional so that corrective action can be taken.
(3) Chief Engineer.
Is to notify the Medical Center Director of any safety devices that are non-functional.
3. DEFINITIONS
None.
4. REFERENCES
a. VHA Directive 1810, latest edition.
5. REVIEW
This SOP is to be reviewed annually and recertified every five years and including when there are changes to be made according to a VHA Notice or Directive.
6. RECERTIFICATION
This SOP is scheduled for recertification on or before the last working day of August 2027 – 5 years from effective date. In the event of contradiction with national policy, the national policy supersedes and controls.
7. SIGNATORY AUTHORITY
August 31, 2022 SOP 138-46
X Jacob Morrical Chief, Engineering Service Marion Campus
NOTE: The signature remains valid until rescinded by an appropriate administrative action.
DISTRIBUTION: All Supervisors (138)
| ISOLATING BOILER PLANT FROM GAS SUPPLY LINE - MARION |
| 1. PURPOSE AND AUTHORITY |
| a. The purpose of the isolating boiler plant from gas supply line SOP is to establish procedures for the safe and efficient isolation of the Boiler Plant from the gas supply lines at VA Northern Indiana Health Care System (VANIHCS), Marion. |
| b. It is the VANIHCS policy that the isolation of the Boiler Plant from the gas supply line be in a safe and economical manner that complies with the requirements as listed in the VHA Directive 1810. |
| c. The Boiler Plant is essential to the functioning of the Medical Center and the operation of boilers requires well-trained operators, properly functioning safety equipment, well maintained boilers and support equipment, and proper operational proced... |
| 1. PROCEDURES |
| 2. ASSIGNMENT OF RESPONSIBILITIES |
| 3. DEFINITIONS |
| 4. REFERENCES |
| a. VHA Directive 1810, latest edition. |
| 5. REVIEW |
| 6. RECERTIFICATION |
| 7. SIGNATORY AUTHORITY |