No Date Bldg# Repair
Part Each
1 5725 N/A 1
2 6120 N/A 1
3 6707 N/A 1
4 6708 Battery 2ea
(KB12180)
5 6827 N/A 1
6 6907 N/A 1
7 6910 N/A 1
8 7232 N/A 1
9 204 N/A 1
10 713 N/A 1
11 882
Battery 2ea
(KB12180),
Battery 2ea
(KB1270)
12 1018 N/A 1
13 1287 N/A 1
14 1296 N/A 1
15 1431 N/A 1
16 1432 N/A 1
17 5120 N/A 1
18 6322 N/A 1
19 6323 N/A 1
20 6326 N/A 1
21 6703 N/A 1
ATTACHMENT #4 (TECHNICAL EXHIBIT 04)
Historical Data for Service Call
Service Call (Duty Hour)
We found out the MNS strobe open circuit trouble #3 due to wire problem (M13:P005). We repaired the strobe#3 wire line. System is back to normal. / Requested Fire Department.
4-Feb-20
We found out the smoke detector missing trouble in RM 107 on FACP (M97:S021). We can not repair the trouble due to no occupant. We will repaire this trouble after we make the schedule with fire inspector. / Requested Fire Department.
We found out the MNS strobe open circuit #1 trouble on FACP due to wire problem (M98:P005). We repaired the MNS strobe wire line. System is back to normal. / Requested Fire Department.
We found out the RPS-1000 panel battery trouble on FACP due to low voltage (M15). We replaced the battery (12v 18Ah 2ea) for FM panel and battery (12V 7Ah 2ea) for PM panel by Firecops bench stock. System is back to normal. / Requested Fire Department.
4-Feb-20
We checked the fire alarm panel and BT system due to systems checking. We found out the normal condition in fire alarm panel and BT system. This building is under renovation. / Requested Fire Department.
We found out the fire pump room low temperature trouble on fire pump controll panel. We checked and adjusted the temperature switch. There is battery trouble for fire pump. / Requested Fire Department.
We found out the strobe power trouble on FACP due to malfunction power panel. We checked and reset the main board. System is back to normal. / Requested Fire Department.
We checked the wet pipe system with fire inspector. We found out the normal condition on wet pipe system.
System is back to normal. / Requested Fire Department.
Works
3-Feb-20
We found out the fire strobe open circuit trouble #1 due to wire problem (M12:P001). We repaired the strobe#1 wire line. System is back to normal. / Requested Fire Department.
We found out the activated duct smoke detector alarm due to malfunction duct detector (M34). We repaired the duct smoke detector on 2F. / Requested Fire Department.
We found out the activated supervisory signal in RM 225 due to user cooking (M02:S040). We cleaned and reset the smoke detector in RM 225. System is back to normal. / Requested Fire Department.
We found out the 5F RPS-1000 panel battery trouble on FACP due to low voltage (M15). We replaced the battery (12v 18ah 2ea) by Firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the duct smoke detector CAL trouble in rooftop due to defective duct smoke detector (M08:S023).
We repaired the duct smoke detector in rooftop. System is back to normal. / Requested Fire Department.
We found out the activated supervisory signal in RM 522 due to user cooking (M05:S050). We cleaned and reset the smoke detector in RM 522. System is back to normal. / Requested Fire Department.
We found out the activated supervisory signal in RM 517 due to user cooking (M05:S005). We cleaned and reset the smoke detector in RM 517. System is back to normal. / Requested Fire Department.
We checked the wet pipe system with fire inspector. We found out the normal condition on wet pipe system.
System is back to normal. / Requested Fire Department.
We found out the fire strobe open circuit trouble #2 due to relay problem (M98:P003). We repaired the relay for fire strobe#2. System is back to normal. / Requested Fire Department.
We found out the activated wet pipe system in RM 628 due to electrical fire. We replaced the sprinkler head and smoke detectors (2ea) in RM 628. This building remains the elevator and ground troubles. / Requested Fire Department.
We found out the fire pump running supervisory on FACP due to fire alarm in S-6322 (M97:M047). We checked and reset the fire pump controll panel. System is back to normal. / Requested Fire Department.
We checked the sprinkler leaking pipe on 8F with Kohome contractor. We found out the water leaking on sprinkler brench line on 8F. Need to submit the FEWR for repaire it./ Requested Fire Department.
We found out the activated supervisory signal in RM 227 living room due to user cooking (M02:S034). We cleaned and reset the smoke detector in RM 227. System is back to normal. / Requested Fire Department.
Part Each
Service Call (Duty Hour)
Works
22 7324 Battery 2ea
(KB12350)
23 1022 N/A 1
24 1431 Battery 2ea
(KB1270)
25 2061 N/A 1
26 2096 Battery 2ea
(KB12180)
27 5904 N/A 1
28 6322
Battery2ea
(KB12350)
Battery2ea
(KB12180)
29 6703 Battery 2ea
(KB12180)
30 6705 N/A 1
31 6800 N/A 1
32 6910 N/A 1
33 7121 N/A 1
34 510 N/A 1
35 809 N/A 1
36 1290 N/A 1
37 1291 N/A 1
38 1644 N/A 1
39 2061 N/A 1
40 5171 N/A 1
41 5904 N/A 1
42 6091 N/A 1
43 6322 N/A 1
We found out the activated supervisory signal on FACP due to generator running (D445). We checked and silenced the FACP. The FACP will be normal condition after generator stop. / Requested Fire Department.
We found out the activated supervisory signal on FACP due to elevator#1 power shunt off (M13:M026). We checked and silenced the FACP. This trouble will be repaired by elevator contractor. / Requested Fire Department.
We found out the open circuit trouble for speaker circuit#4 (M22) on FACP. We checked and silenced the FACP.
The trouble will be repaired by warranty contractor. / Requested Fire Department.
We found out the water leaking on pre-action valve in MECH RM. We checked and reset the pre-action system, but we can not repair the pre-action system due to defective pre-action system. Need to submit the FEWR for repair it. / Requested Fire Department.
We found out the activated supervisory signal on FACP due to elevator power shunt off (M08: M036 and M044).
We checked and silenced the FACP. This trouble will be repaired by elevator contractor. / Requested Fire Department.
6-Feb-20
We found out the activated supervisory signal on FACP due to elevator power shunt off (M05:M019). We checked and silenced the FACP. This trouble will be repaired by elevator contractor. / Requested Fire Department.
We found out the activated wet pipe system on FACP due to broken sprinkler head (M33:M36). We replaced the sprinkler head with spare head, and reset the wet pipe system. System is back to normal. / Requested Fire Department.
We found out the activated smoke detector in RM 206 on FACP due to water damage (M33:051). We repaired and reset the smoke detector. System is back to normal. / Requested Fire Department.
We found out the activated tamper switch for back flow preventor on FACP (M33:052). We adjusted the tamper switch. System is back to normal. / Requested Fire Department.
We found out the AC power loss trouble on FACP due to malfunction main board. We checked and reset the FACP. System is back to normal. / Requested Fire Department.
We found out the main panel battery trouble on FACP due to low voltage (M34). We replaced the battery (12v 35ah 2ea) by Firecops bench stock. System is back to normal. / Requested Fire Department.
5-Feb-20
We found out the no reply signal on BT system. We checked and repaired the BT system with D-21. System is back to normal. / Requested Fire Department.
We found out the broken power board and battery trouble on FACP due to defective power board and low voltage (M34). We replaced the power board by used material, and battery (12v 7ah 2ea) by Firecops bench stock.
System is back to normal. / Requested Fire Department.
5-Feb-20
We found out the supervisoy signal on FACP due to elevator power shut off. We checked and silenced the FACP.
The trouble will be repaired by elevator contractor. / Requested Fire Department.
We found out the 1F AMP panel battery trouble on FACP due to low voltage (M12). We replaced the battery (12v 18ah 2ea) by Firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the open circuit trouble for speaker circuit#4 (M22) on FACP. We checked and silenced the FACP.
The trouble will be repaired by warranty contractor / Requested Fire Department.
We found out the 1F and 2F IBS strobe panel battery trouble on IBS main panel due to low voltage. We replaced the battery (12v 18ah 2ea) on 1F and battery (12v 35ah 2ea) on 2F by Firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the 2F AMP panel battery trouble on FACP due to low voltage (M22). We replaced the battery (12v 18ah 2ea) by Firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the activated supervisory signal in RM 513 due to user cooking (M05:S018). We cleaned and reset the smoke detector in RM 513. System is back to normal. / Requested Fire Department.
We found out the fire strobe open circuit trouble #1 due to wire problem (M98:P005). We repaired the strobe#1 wire line. System is back to normal. / Requested Fire Department.
We found out the activated supervisory signal in RM 414 due to user cooking (M04:S015). We cleaned and reset the smoke detector in RM 414. System is back to normal. / Requested Fire Department.
We found out the fire strobe open circuit trouble #1 due to wire problem (M98:P001). We repaired the strobe#1 wire line. System is back to normal. / Requested Fire Department.
Part Each
Service Call (Duty Hour)
Works
44 6326 N/A 1
45 6800 N/A 1
46 7121 N/A 1
47 7321 N/A 1
48 7424 N/A 1
49 12410 N/A 1
50 800 N/A 1
51 1038 N/A 1
52 1484 N/A 1
53 2022 N/A 1
54 6326 N/A 1
55 6701 N/A 1
56 6704 N/A 1
57 7315 Battery 2ea
(KB12180)
58 12600 Battery 2ea
(KB12120)
59 1038 N/A 1
60 2061 N/A 1
61 2061 Battery 2ea
(KB12120)
62 2096 Battery 2ea
(KB12180)
63 6320 N/A 1
64 6322 N/A 1
65 6326 N/A 1
66 6704 Battery2ea
(KB12180)
We found out the battery trouble for 5F RPS-1000 panel on FACP due to low voltage (M15). We replaced the battery (12v 18ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the activated supervisory signal in RM 323 due to user cooking (M03:S047). We cleaned and reset the smoke detector in RM 323. System is back to normal. / Requested Fire Department.
We found out the battery trouble for RPS-1000 panel on FACP due to low voltage. We replaced the battery (12v 18ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the battery trouble for IBS strobe panel(M2-19) in 2F ELEC RM 218.We replaced the battery (12V 12ah 2ea) by firecops bench stock. System is back to normal in IBS power panel. But main panel remains the
10-Feb-20
We found out the activated dry pipe system on FACP due to water leaking on sprinkler pipe. We reset the dry pipe system after DPW repair the water leaking pipe. System is back to normal. / Requested Fire Department.
We found out the map fault trouble on FACP due to malfunction main board. We checked and reset the main board on FACP. System is back to normal. / Requested Fire Department.
We found out the battery trouble for 1F audio panel on IBS system due to low voltage. We replaced the battery (12v 12ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the battery trouble for 4F VIP-50 panel on FACP due to low voltage (M25). We replaced the battery (12v 18ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We checked the smoke detector in living room in RM 711 due to user submit the DMO. We checked and repaired the smoke detector and motion sensor. System is back to normal. / Requested Fire Department.
We found out the activated supervisory signal on FACP due to elevator #1 and #2 power shunt off (M08: M036 and M044). We checked and silenced the FACP. This trouble will be repaired by elevator contractor. / Requested Fire Department.
7-Feb-20
We found out the activated temper supervisory signal on FACP due to wrong position (M33:M01). We repaired the temper switch for foam system test valve. System is back to normal. / Requested Fire Department.
We found out the activated dry pipe system due to pipe line broken. We checked the Dry pipe system. Dry pipe line will be repaired by DPW. We will reset the dry pipe system after DPW working done. / Requested Fire Department.
7-Feb-20
We found out the ground fault trouble for strobe circuit on IBS main panel. We checked and silenced the IBS main panel. Need to submit the FEWR for repair it. / Requested Fire Department.
We found out the activated water pressure switch(M33:007) in MECH RM on FACP because frozen pipe. We repaired the water pipe line. System is back to normal. / Requested Fire Department.
We found out the open circuit troubles for speaker circuit on FACP. We checked and silenced the FACP. We will repair by submitted FEWR. / Requested Fire Department.
We found out the activated supervisory signal in RM 310 due to user cooking (M03:S027). We cleaned and reset the smoke detector in RM 310. System is back to normal. / Requested Fire Department.
6-Feb-20 We found out the activated pressure switch on wet pipe system on FACP due to malfunction. We adjusted the pressure switch. System is back to normal. / Requested Fire Department.
We found out the IBS strobe open circuit trouble #1 due to wire problem (M98:P005). We repaired the IBS strobe#1 wire line. System is back to normal. / Requested Fire Department.
We found out the fire strobe open circuit #1 trouble on FACP due to wire problem (M98:P001). We repaired the fire strobe#1 wire line. System is back to normal. / Requested Fire Department.
We found out the activated tamper switch (M33:M020) on FACP. We adjusted the tamper switch. System is back to normal. / Requested Fire Department.
We found out the fire strobe open circuit trouble due to wire problem (M34:P001). We repaired the strobe wire line. System is back to normal. / Requested Fire Department.
We found out the ground fault trouble on FACP due to water leaking (L01M125). We checked and reset the FACP. System is back to normal. / Requested Fire Department.
We found out the activated pressure switch on wet pipe system on FACP due to water leaking of sprinkler pipe on 8F. We checked and disabled the water pressure switch (M97:M036). We will enable the pressure switch after sprinkler pipe on 8F repair. / Requested Fire Department.
Part Each
Service Call (Duty Hour)
Works
67 6705 N/A 1
68 6708 Battery2ea
(KB12350)
69 510 N/A 1
70 513 Battery 2ea
(KB12180)
71 1810 IDP-Relay
1ea
72 2061 N/A 1
73 3032 N/A 1
74 6004 Battery 10ea
(KB12350)
75 6910(1) N/A 1
76 6910(2) N/A 1
77 6915 N/A 1
78 7240 N/A 1
79 7320 N/A 1
80 7436 N/A 1
81 7436 Battery 2ea
(KB12180)
82 118 N/A 1
83 360 N/A 1
84 713 N/A 1
85 857 N/A 1
86 2061
Battery 2ea
(KB12070)
Battery 4ea
(KB12120)
87 2096
Battery 2ea
(KB12070)
Battery 6ea
(KB12120)
88 6150 N/A 1
11-Feb-20
We found out the fire strobe open circuit trouble #1 due to wire problem (M34:P001). We repaired the strobe#1 wire line. System is back to normal. / Requested Fire Department.
We found out the fire strobe open circuit trouble #3 due to wire problem (M34:P005). We repaired the strobe#3 wire line. System is back to normal. / Requested Fire Department.
We found out the audio short trouble on IBS system due to battery problem. We replaced the battery (12v 18ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
12-Feb-20
We found out the activated wet pipe system on FACP due to water hammer. We checked and reset the wet pipe system with fire department. System is back to normal. / Requested Fire Department.
We found out the no AUX power for sounder base trouble in RM 413 on FACP due to detached sounder base (M03:S019). We repaired the sounder base in RM 413. System is back to normal. / Requested Fire Department.
We found out the MNS strobe open circuit trouble #1 due to wire problem (M98:P005). We repaired the IBS strobe#1 wire line. System is back to normal. / Requested Fire Department.
We found out the activated fire alarm on FACP due to malfunction manual pull station (M33:P002). We repaired the manual pull ststion. System is back to normal. / Requested Fire Department.
We found out the audio short troubles on IBS system due to battery problem (main, 1F and 5F). We replaced the battery (12v 12ah 4ea, 12v 7ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the activated supervisory of ELEV. shunt and AC power loss trouble signal due to ELEC.
contractor maintenance. We silenced the FACP. System will be restored contractor working done. / Requested Fire Department.
We found out the audio short troubles on IBS system due to battery problem (main, 2F, 4F, 6F and 8F). We replaced the battery (12v 35ah 10ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the trouble signal in RM 820 because user cooking (M08:S061). We cleaned and reset the smoke detector. System is back to normal. / Requested Fire Department.
We found out the activated supervisory signal in RM 211 due to user cooking (M02:S024). We cleaned and reset the smoke detector in RM 211. System is back to normal. / Requested Fire Department.
We found out the smoke detector missing trouble in RM 827 on FACP due to user remove (M08:S039). We cleaned and attached the smoke detector in RM 827. System is back to normal. / Requested Fire Department.
We found out the audio short trouble on IBS system due to wire problem. We repaired the audio wire line.
System is back to normal. / Requested Fire Department.
10-Feb-20 We found out the smoke detector missing trouble in RM 513 on FACP due to user remove (M05:S018). We cleaned and attached the smoke detector in RM 513. System is back to normal. / Requested Fire Department.
We found out the battery trouble for 4F RPS-1000 panel on FACP due to low voltage (M14). We replaced the battery (12v 35ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
11-Feb-20
We found out the activated supervisory signal on FACP due to elevator power shunt off. We checked and silenced the FACP. This supervisory will be normal condition after elevator repair. / Requested Fire Department.
We found out the battery trouble for RPS-1000 panel on FACP due to low voltage (M10). We replaced the battery (12v 18ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the extra fault trouble on FACP due to defective relay module (M33:M002). We replaced the relay module by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the map fault trouble on FACP due to program error. We checked and silenced the FACP. Need to submit the FEWR for repair it. / Requested Fire Department.
We found out the audio short troubles on IBS system due to battery problem (main, 3F, 5F, 7F). We replaced the battery (12v 12ah 6ea, 12v 7ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the water pressure switch trouble on BT system due to wire problem (Unit 1196, Zid#5). We repaired the BT signal line in relay board. System is back to normal. / Requested Fire Department.
Part Each
Service Call (Duty Hour)
Works
89 6325 N/A 1
90 6907 N/A 1
91 6910 N/A 1
92 12-Feb-20 7211 N/A 1
93 577
Battery 2ea
(KB12350)
Battery 4ea
(KB12120)
94 577
Battery 2ea
(KB12350)
Battery 10ea
(KB12180)
95 857 N/A 1
96 6001 Battery 2ea
(KB12350)
97 6002 Battery 4ea
(KB12350)
98 6003
Battery 8ea
(KB12350)
Battery 2ea
(KB12120)
99 6907 N/A 1
100 6005 Battery 2ea
(KB12350)
101 6006 N/A 1
102 6006
Battery 12ea
(KB12350)
Battery 2ea
(KB12120)
103 6151 N/A 1
104 6323 Battery 6ea
(KB12180)
105 6325 Battery 2ea
(KB12180)
106 6326 Battery 2ea
(KB12181)
107 6915 N/A 1
108 7315 N/A 1
109 572 N/A 1
110 711 N/A 1
14-Feb-20
We found out the audio short troubles on IBS system due to battery problem (8F). We replaced the battery (12v 18ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the audio short troubles on IBS system due to battery problem (1F). We replaced the battery (12v 18ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the activated supervisory signal in RM 621 due to user cooking (M06:S053). We cleaned and reset the smoke detector in RM 621. System is back to normal. / Requested Fire Department.
We found out the IBS system power turned off, and disabled the zone on BT system. We repaired the IBS system, and enabled the BT system. System is back to normal. / Requested Fire Department.
We found out the ground fault trouble on FACP due to water leaking in MECH RM. The ground fault was cleared after water leaking repair. System is back to normal. / Requested Fire Department.
We found out the activated fire alarm for waterflow SW(M1:15) in MECH RM on FACP. We reset the FACP.
System is back to normal. / Requested Fire Department.
14-Feb-20
We found out the audio short troubles on IBS system due to battery problem (4F). We replaced the battery (12v 35ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the activated supervisory signal on FACP due to elevator #2 power shunt off (M07:M029). We checked and silenced the FACP. This trouble will be repaired by elevator contractor. / Requested Fire Department.
We found out the audio short troubles on IBS system due to battery problem (Main, 1F, 4F, 6F and 8F). We replaced the battery (12v 35ah 12ea, 12v 12ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the 1F FA/MNS speaker #3 shorted circuit trouble due to wire problem (M31:P005). We repaired the FA/MNS speaker #3 wire line. System is back to normal. / Requested Fire Department.
We found out the audio short troubles on IBS system due to battery problem (1F, 4F and 6F). We replaced the battery (12v 18ah 6ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
13-Feb-20
We found out the on and off battery troubles on FA system due to battery problem (main, 1F, 2F and 3F). We replaced the battery (12v 12ah 4ea, 12v 35ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the on and off battery troubles on IBS system due to battery problem (main, 1F, 2F and 3F). We replaced the battery (12v 18ah 10ea, 12v 35ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the activated water pressure switch on FACP due to defective wet pipe valve (M33:P019). We repaired the wet pipe system. System is back to normal. / Requested Fire Department.
We found out the audio short trouble on IBS system due to battery problem (6F). We replaced the battery (12v 35ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the audio short troubles on IBS system due to battery problem (2F and 8F). We replaced the battery (12v 35ah 4ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the audio short troubles on IBS system due to battery problem (main, 1F, 2F and 8F). We replaced the battery (12v 12ah 2ea, 12v 35ah 8ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the activated supervisory signal in RM 820 due to user cooking (M08:S061). We cleaned and reset the smoke detector in RM 820. System is back to normal. / Requested Fire Department.
We found out the MNS strobe open circuit trouble #1 due to wire problem (M11:P001). We repaired the MNS strobe#1 wire line. System is back to normal. / Requested Fire Department.
We found out the activated supervisory signal in RM 513 due to user cooking (M05:S018). We cleaned and reset the smoke detector in RM 513. System is back to normal. / Requested Fire Department.
We found out the activated supervisory signal in RM 821 due to user cooking (M08:S058). We cleaned and reset the smoke detector in RM 821. System is back to normal. / Requested Fire Department.
We found out the activated supervisory signal in RM 814 due to user cooking (M08:S015). We cleaned and reset the smoke detector in RM 814. System is back to normal. / Requested Fire Department.
Part Each
Service Call (Duty Hour)
Works
111 6006 N/A 1
112 6323 N/A 1
113 6701 Battery 2ea
(KB12180)
114 6704 Battery 2ea
(KB12180)
115 6704
Battery 2ea
(KB12350)
Battery 2ea
(KB12180)
116 6705 Battery 2ea
(KB12180)
117 6706 Battery 2ea
(KB12180)
118 6707
Battery 2ea
(KB12350)
Battery 2ea
(KB12180)
119 6915 N/A 1
120 12375 N/A 1
121 400 N/A 1
122 725 N/A 1
123 857 N/A 1
124 1287 N/A 1
125 6703 Battery 6ea
(KB12180)
126 6708
Battery 4ea
(KB12350)
Battery 4ea
(KB12180)
127 7434 N/A 1
128 7436 N/A 1
129 483 N/A 1
130 711 N/A 1
131 1287 N/A 1
132 2090 Battery 2ea
(KB12180)
19-Feb-20
We found out the 2F horn and strobe open circuit trouble on FACP due to wire problem (M34: P003). We repaired the horn and strobe wire line. System is back to normal. / Requested Fire Department.
We checked the sprinkler water pressure alarm signal on BT system due to no reply to D-21. We tested the sprinkler water pressure switch alarm with D-21. System is back to normal. / Requested Fire Department.
We found out the fire pump controller trouble on FACP due to defective battery for fire pump. We checked and silenced the FACP. We will repair the fire pump controller trouble by submitted FEWR. / Requested Fire Department.
We found out the audio short trouble on IBS system due to battery problem on 2F. We replaced the battery (12v 18ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
18-Feb-20
We found out the activated fire alarm for manual pull station on FACP. We reset the Fire alarm signal for manual pull station (M2-3) and replaced the manual pull staion (M2-6) by used material due to defective device. System remains some troubles. / Requested Fire Department.
We found out the player fault trouble on FACP due to system error. We checked and reset the main board on FACP. System is back to normal. / Requested Fire Department.
We found out the activated wet pipe system due to water leaking at AUX drain line in hanger. We repaired the AUX pipe line for wet pipe system. System is back to normal. / Requested Fire Department.
We found out the fire pump trouble on FACP due to defective battery for fire pump. We checked and silenced the FACP. We will repair the fire pump trouble by submitted FEWR. / Requested Fire Department.
We found out the audio short troubles on IBS system due to battery problem (2F and 4F). We replaced the battery (12v 18ah 6ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the audio short troubles on IBS system due to battery problem (1F and 2F). We replaced the battery (12v 35ah 4ea, 12v 18ah 4ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the audio short trouble on IBS system due to wire problem in MDP #2. We repaired the wire line in MDP #2 panel. System is back to normal. / Requested Fire Department.
We found out the fire strobe open circuit #1 trouble on FACP due to wire problem (M34: P001). We repaired the wire line for fire strobe circuit #1. System is back to normal. / Requested Fire Department.
We found out the audio short trouble on IBS system due to battery problem (6F). We replaced the battery (12v 18ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the 3F speaker panel battery trouble on FACP due to battery problem (M23). We replaced the battery (12v 18ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the audio short troubles on IBS system due to battery problem (2F, 3F and 6F). We replaced the battery (12v 35ah 2ea, 12v 18ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the audio short trouble on IBS system due to battery problem (1F). We replaced the battery (12v 18ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the audio short trouble on IBS system due to battery problem (2F). We replaced the battery (12v 18ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
17-Feb-20
We found out the audio short troubles on IBS system due to battery problem (2F and 6F). We replaced the battery (12v 35ah 2ea, 12v 18ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the activated supervisory signal in RM 712 due to user cooking (M07:S021). We cleaned and reset the smoke detector. System is back to normal. / Requested Fire Department.
We found out the activated fire alarm for waterflow SW(M97:M022) in MECH RM #124 on FACP. We reset the FACP. System is back to normal. / Requested Fire Department.
17-Feb-20
We found out the activated supervisory signal on FACP due to elevator #2 power shunt off (M07:M029). We checked and silenced the FACP. This trouble will be repaired by elevator contractor. / Requested Fire Department.
We found out the activated supervisory signal in RM 612 due to user take shower (M06:S021). We cleaned and reset the smoke detector. System is back to normal. / Requested Fire Department.
Part Each
Service Call (Duty Hour)
Works
133 2908 Battery 2ea
(KB1270)
134 6326 N/A 1
135 6907 N/A 1
136 6910 N/A 1
137 857 N/A 1
138 6002 Battery 4ea
(KB12350)
139 6006 N/A 1
140 6324 N/A 1
141 6326 N/A 1
142 6704 N/A 1
143 6706 N/A 1
144 6907 N/A 1
145 7111 N/A 1
146 20-Feb-20 7526 N/A 1
147 5711 N/A 1
148 6002 N/A 1
149 6003 N/A 1
150 6006 N/A 1
151 6151 N/A 1
152 6319 N/A 1
153 6326 N/A 1
154 6705 N/A 1
We found out the activated fire alarm on FACP due to manual pull station in storage #103 activation by occupant.
We replaced the manual pull station by used material (M1-25). System is back to normal. / Requested Fire Department.
21-Feb-20
We found out the fire strobe # 1 open circuit trouble on FACP due to wire problem (M98: P001). We repaired the fire strobe #1 wire line. System is back to normal. / Requested Fire Department.
We found out the activated supervisory signal on FACP due to generator running by contractor (M33: M028).
We checked and silenced the FACP. The supervisory signal will be normal condition after contractor finish the work. / Requested Fire Department.
We found out the activated supervisory signal on FACP due to generator running by contractor (M33: M028).
We checked and silenced the FACP. The supervisory signal will be normal condition after contractor finish the work. / Requested Fire Department.
We found out the activated supervisory signal on FACP due to elevator #2 power shunt off (M07:M029). We checked and silenced the FACP. This trouble will be repaired by elevator contractor. / Requested Fire Department.
We found out the fire and MNS speaker # 3 short circuit trouble on FACP due to wire problem (M31: P005). We repaired the fire and MNS speaker #3 wire line. System is back to normal. / Requested Fire Department.
We found out the supervisory signal on FACP due to VESDA detector problem (M33: M028). We repaired the VESDA smoke detector. System is back to normal. / Requested Fire Department.
We found out the some troubles on FACP due to wire problem. We checked and silenced the FACP. We will repair the some troubles by submitted FEWR. / Requested Fire Department.
We found out the activated supervisory signal in RM 816 due to user shower (M08:S008). We cleaned and reset the smoke detector. System is back to normal. / Requested Fire Department.
20-Feb-20
We found out the activated wet pipe system due to clapper for wet pipe valve did not close properly (M33:P019).
We repaired the clapper for wet pipe system. System is back to normal. / Requested Fire Department.
We found out the audio short trouble on IBS system due to battery problem on 6F. We replaced the battery (12v 35ah 4ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the activated supervisory signal on FACP due to elevator #2 power shunt off (M07:M029). We checked and silenced the FACP. This trouble will be repaired by elevator contractor. / Requested Fire Department.
We found out the audio short trouble on IBS system due to battery problem on 2F. We replaced the battery (12v 18ah 2ea) by used material. System is back to normal. / Requested Fire Department.
We found out the some troubles on FACP due to wire problem. We checked and silenced the FACP. We will repair the some troubles by submitted FEWR. / Requested Fire Department.
We found out the activated supervisory signal in RM 518 due to user cooking (M05:S002). We cleaned and reset the smoke detector. System is back to normal. / Requested Fire Department.
We found out the activated supervisory signal in RM 132 due to user cooking (M97:S040). We cleaned and reset the smoke detector. System is back to normal. / Requested Fire Department.
We found out the activated supervisory signal in RM 515 due to user cooking (M05:S015). We cleaned and reset the smoke detector. System is back to normal. / Requested Fire Department.
We found out the fire strobe open circuit #1 trouble on FACP due to wire problem (M98: P001). We repaired the wire line for fire strobe circuit #1. System is back to normal. / Requested Fire Department.
19-Feb-20
We found out the audio short trouble on IBS system due to battery problem on 3F. We replaced the battery (12v 7ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the some troubles on FACP due to wire problem. We checked and silenced the FACP. We will repair the some troubles by submitted FEWR. / Requested Fire Department.
We found out the activated supervisory signal in RM 424 due to user cooking (M04:S043). We cleaned and reset the smoke detector. System remains some trouble. / Requested Fire Department.
We found out the activated supervisory signal in RM 526 due to user cooking (M05:S037). We cleaned and reset the smoke detector. System remains some trouble. / Requested Fire Department.
Part Each
Service Call (Duty Hour)
Works
155 6915 N/A 1
156 7111 N/A 1
157 511 N/A 1
158 1644 N/A 1
159 1750 N/A 1
160 2061 N/A 1
161 5420 N/A 1
162 6006 N/A 1
163 6324 N/A 1
164 6325 N/A 1
165 6326 N/A 1
166 6907(1) N/A 1
167 6907(2) N/A 1
168 7112 VCM 1ea 1
169 7436 N/A 1
170 112(1) Battery 2ea
(KB1270)
171 112(2) Break Rod
2ea
172 204 N/A 1
173 6006 N/A 1
174 6324(1) N/A 1
175 6324(2) N/A 1
176 6326 N/A 1
We found out the fire strobe # 1 open circuit trouble on FACP due to wire problem (M34: P001). We repaired the fire strobe #1 wire line. System is back to normal. / Requested Fire Department.
25-Feb-20
We found out the battery trouble for main panel on FACP due to low voltage. We replaced the battery (12v 7ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the break rod for wet chemical missing on manual pull station due to broken rod. We replaced the break rod on manual pull station (2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
25-Feb-20
We found out the break rod for wet chemical missing on manual pull station due to broken rod. We replaced the break rod on manual pull station (2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the activated supervisory signal on FACP due to elevator #2 power shunt off (M07:M029). We checked and silenced the FACP. This trouble will be repaired by elevator contractor. / Requested Fire Department.
We found out the activated fire alarm on FACP due to pressure switch activation (M97: M036). We adjusted the water pressure switch, and cleaned the retard chamber orifice line. System is back to normal. / Requested Fire Department.
We found out the sprinkler head cover missing on 1F, 4F and 5F. We attached the sprinkler head cover by spare head cover. System is back to normal. / Requested Fire Department.
We found out the activated supervisory signal in RM 131 due to user cooking (M97: S037). We cleaned and reset the smoke detector. / Requested Fire Department.
We found out the audio short trouble on IBS system due to battery problem in 4F panel. We checked and silenced the IBS system due to no bench stock (12v 18ah). We will replace the battery after bench stock comes in. / Requested Fire Department.
We found out the 4F fire alarm and trouble on BT system due to wire problem (Unit#964 and zid#4). We repaired the wire line on BT system. System is back to normal. / Requested Fire Department.
We found out the some troubles on FACP due to wire problem. We checked and silenced the FACP. We will repair the some troubles by submitted FEWR. / Requested Fire Department.
We found out the smoke detector missing trouble on FACP due to user remove (M06: S040). We attached the smoke detector in RM 625. System is back to normal. / Requested Fire Department.
We found out the activated supervisory signal in RM 728 due to user cooking (M07: S031). We cleaned and reset the smoke detector. System is back to normal. / Requested Fire Department.
We found out the audio chain fault trouble on FACP due to defective audio board. We replaced the audio board on FACP by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the smoke detector missing trouble on FACP due to user remove (M03: S059 and M08: S039). We attached the smoke detector in RM 319 and 827. System is back to normal. / Requested Fire Department.
We found out the fire strobe # 1 open circuit trouble on FACP due to wire problem (M98: P001). We repaired the fire strobe #1 wire line. System is back to normal. / Requested Fire Department.
24-Feb-20
We found out the low air supervisory for dry pipe valve on 8F on FACP due to defective air compressor (M08:
046). We repaired the air compressor for dry pipe valve. System is back to normal. / Requested Fire Department.
We found out the AC loss power trouble on FACP due to defective board. We checked and reset the FACP.
System is back to normal. But need to replace the FACP board. / Requested Fire Department.
24-Feb-20
We found out the MNS strobe # 1 open circuit trouble on FACP due to wire problem (M14: P001). We repaired the MNS strobe #1 wire line in MPM#2. System is back to normal. / Requested Fire Department.
We found out the activated fire alarm on FACP due to IBS panel burn out. We checked the IBS audio panel on 3F, and silenced the IBS system. Need to submit the FEWR for repair it. / Requested Fire Department.
We found out the speaker open circuit trouble on FACP due to wire problem (A15S01). We checked and silenced the FACP. Need to submit the FEWR for repair it. / Requested Fire Department.
We found out the activated supervisory signal on FACP due to elevator #2 power shunt off (M07:M029). We checked and silenced the FACP. This trouble will be repaired by elevator contractor. / Requested Fire Department.
Part Each
Service Call (Duty Hour)
Works
177 6703 N/A 1
178 6915 N/A 1
179 12401 Battery 2ea
(KB1270)
180 12700 N/A 1
181 12710 N/A 1
182 872 N/A 1
183 1299 Battery
(KB12120)
2ea
184 1644 N/A 1
185 2064 Battery
(KB12120)
1ea
186 6006 N/A 1
187 6320(1) N/A 1
188 6320(2) N/A 1
189 6322 N/A 1
190 6324 N/A 1
191 6326 N/A 1
192 7213 N/A 1
193 12002 N/A 1
194 118 N/A 1
195 5420 N/A 1
196 6006 N/A 1
197 6317 N/A 1
198 6324 N/A 1
27-Feb-20
We found out the defective sprinkler head cover in office area. We repaired the sprinkler head cover in office area (4ea). System is back to normal. / Requested Fire Department.
We found out the speaker open circuit trouble on FACP due to wire problem (A15S01). We checked and silenced the FACP. Need to submit the FEWR for repair it. / Requested Fire Department.
We found out the activated supervisory signal on FACP due to elevator #2 power shunt off (M07:M029). We checked and silenced the FACP. This trouble will be repaired by elevator contractor. / Requested Fire Department.
We found out the activated supervisory signal on FACP due to elevator power shunt off. We checked and silenced the FACP. This trouble will be normal condition after Corone Virus prevention done. / Requested Fire Department.
We found out the some troubles on FACP due to wire problem. We checked and silenced the FACP. We will repair the some troubles by submitted FEWR. / Requested Fire Department.
26-Feb-20
We found out the activated supervisory signal on FACP due to elevator #2 power shunt off (M07:M029). We checked and silenced the FACP. This trouble will be repaired by elevator contractor. / Requested Fire Department.
We found out the activated supervisory signal in RM 817 due to user cooking (M08: S005). We cleaned and reset the smoke detector. / Requested Fire Department.
We found out the audio short trouble on IBS system due to battery problem in 6F panel. We checked and silenced the IBS system due to no bench stock (12v 18ah). We will replace the battery after bench stock comes in. / Requested Fire Department.
We found out the activated supervisory signal in RM 132 due to user cooking (M97: S040). We cleaned and reset the smoke detector. / Requested Fire Department.
We found out the audio short trouble on IBS system due to battery problem in 4F panel. We checked and silenced the IBS system due to no bench stock (12v 18ah). We will replace the battery after bench stock comes in. / Requested Fire Department.
We found out the some troubles on FACP due to wire problem. We checked and silenced the FACP. We will repair the some troubles by submitted FEWR. / Requested Fire Department.
We found out the MNS strobe open circuit trouble #1 due to wire problem (M11:P001). We repaired the IBS strobe#1 wire line. System is back to normal. / Requested Fire Department.
We found out the CAL trouble for smoke detector (M33:S030) in CQ room on FACP. We cleaned the smoke detector. System is back to normal. / Requested Fire Department.
We found out the activated supervisory signal in RM 726 due to user cooking (M07: S037). We cleaned and reset the smoke detector. System is back to normal. / Requested Fire Department.
We found out the activated supervisory signal in RM 420 due to user cooking (M04: S056). We cleaned and reset the smoke detector. System is back to normal. / Requested Fire Department.
We found out the common trouble on FACP due to battery problem in 1F BPS panel. We replaced the battery (12v 7ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the AC power loss trouble on FACP due to power outage. We checked and found out the normal condition after power outage done. System is back to normal. / Requested Fire Department.
We found out the AC power loss trouble on FACP due to power outage. We checked and found out the normal condition after power outage done. System is back to normal. / Requested Fire Department.
26-Feb-20
We found out the ground fault trouble on FACP due to wire problem. We checked and silenced the FACP. This trouble will be repaired by submitted FEWR. / Requested Fire Department.
We found out the battery trouble for BT system due to low voltage. We replaced the battery (12v 12ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the AC loss power trouble on FACP due to defective board. We checked and reset the FACP.
System is back to normal. But need to replace the FACP board. / Requested Fire Department.
We found out the battery trouble for BT system due to low voltage. We replaced the battery (12v 12ah 1ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
25-Feb-20
Part Each
Service Call (Duty Hour)
Works
199 6326 N/A 1
200 6701 N/A 1
201 6704 N/A 1
202 6708 N/A 1
203 6904 N/A 1
204 6910 N/A 1
205 7213 N/A 1
206 2111 N/A 1
207 5725 N/A 1
208 6006 N/A 1
209 6317 N/A 1
210 6325 N/A 1
211 6326 N/A 1
212 6704 N/A 1
213 6907 N/A 1
214 6910 N/A 1
215 7233 N/A 1
216 12001 N/A 1
217 891 Battery 2ea
(KB12350)
218 2098 N/A 1
219 5420 N/A 1
We found out the battery trouble for main panel on FACP due to low voltage. We replaced the battery (12v 35ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department.
We found out the activated water pressure switch on FACP due to malfunction (M33:M027). We checked and reset the FACP. System is back to normal. / Requested Fire Department.
We found out the speaker open circuit trouble on FACP due to wire problem (A15S01). We checked and repaired the speaker wire line on 1F. System is back to normal. / Requested Fire Department.
28-Feb-20
We found out the smoke detector missing trouble in RM 724 due to user remove (M07: S042). We cleaned and attached the smoke detector. System is back to normal. / Requested Fire Department.
We found out the activated supervisory signal in RM 419 due to user cooking (M04: S0059). We cleaned and reset the smoke detector. / Requested Fire Department.
We found out the ground fault trouble on FACP due to wire problem. We checked and silenced the FACP. Need to submit the FEWR for repair it. / Requested Fire Department.
We found out the MNS strobe open circuit #2 trouble due to wire problem (M14:P003). We repaired the IBS strobe#2 wire line. System is back to normal. / Requested Fire Department.
We found out the activated elevator power shunt supervisory in 6F because elevator powered off on FACP. We checked the elevator power turn off condition. This supervisory will be restored by elevator contractor, when they turn on the elevator. / Requested Fire department
28-Feb-20
We found out the battery fault trouble on BT system due to low voltage. We replaced the batteries (12V 12Ah 2ea) by firecops bench stock. System is back to normal. / Requested Fire Department
We found out the missing trouble for monitor module of test heder valve (M97:M26) on FACP due to defective device. We replaced the monitor module by Fire department bench stock. System is back to normal. / Requested Fire Department.
We found out the activated supervisory signal on FACP due to elevator #2 power shunt off (M07:M029). We checked and silenced the FACP. This trouble will be repaired by elevator contractor. / Requested Fire Department.
We found out the activated supervisory signal on FACP due to elevator power shunt off (M97:M049). We checked and silenced the FACP. This trouble will be normal condition after Corone Virus prevention done. / Requested Fire Department.
We found out the activated supervisory signal in RM 512 due to user cooking (M05: S021). We cleaned and reset the smoke detector. / Requested Fire Department.
We found out the some troubles on FACP due to wire problem. We checked and silenced the FACP. We will repair the some troubles by submitted FEWR. / Requested Fire Department.
27-Feb-20
We found out the some troubles on FACP due to wire problem. We checked and silenced the FACP. We will repair the some troubles by submitted FEWR. / Requested Fire Department.
We found out the activated supervisory signal in RM 720 due to user cooking (M07: S056). We cleaned and reset the smoke detector. / Requested Fire Department.
We found out the smoke detector missing trouble in RM 724 due to user remove (M07: S042). We cleaned and attached the smoke detector. System is back to normal. / Requested Fire Department.
We found out the activated supervisory signal in RM 126 due to user cooking (M97: S022). We cleaned and reset the smoke detector. / Requested Fire Department.
We found out the activated supervisory signal in RM 211 due to user cooking (M02: S024). We cleaned and reset the smoke detector. / Requested Fire Department.
We found out the ground fault trouble on FACP due to wire problem. We checked and silenced the FACP. Need to submit the FEWR for repair it. / Requested Fire Department.
We found out the MNS strobe open circuit trouble #1 due to wire problem (M11:P001). We repaired the IBS strobe#1 wire line. System is back to normal. / Requested Fire Department.
Sub Total (FEB 20)
Part Each
Service Call (Duty Hour)
Works
220 6006 N/A 1
221 6317 N/A 1
222 6324 N/A 1
223 6325 N/A 1
224 6326 N/A 1
225 6703 N/A 1
226 6707 N/A 1
227 3-Mar-20 571 Battery 2ea
(KB12170)
228 6001 Battery 2ea
(KB12350)
229 6006 N/A 1
230 6317 N/A 1
231 6322 N/A 1
232 6326 N/A 1
233 6704 N/A 1
234 6809 N/A 1
235 6910 N/A 1
236 7441 N/A 1
237 693 N/A 1
238 5410 Battery 2ea
(KB12350)
239 6006 N/A 1
240 6317 N/A 1
241 6326 N/A 1 We found out the fire pump indicator panel beeping due to generator testing. We checked and silenced the fire pump indicator panel. This trouble will be repaired after generator testing done. / Requested Fire Department.
We found out the activated supervisory signal in RM 227 due to user cooking (M02: S034). We cleaned and reset the smoke detector. System is back to normal. / Requested Fire Department.
We checked the BT system due to no reply signal. We tested and repaired the BT system with D-21. System is back to normal. / Requested Fire Department.
We found out the smoke detector missing trouble in RM 127 due to user remove (M97: S025). We cleaned and attached the smoke detector. / Requested Fire Department.
We checked the BT system due to no reply signal. We tested the BT system with D-21 but the system still is in no reply due to antenna location problem. Need to submit the FEWR for repair it. / Requested Fire Department.
4-Mar-20
We found out the smoke detector CAL trouble on FACP due to detector problem (M33: S054). We cleaned and attached the smoke detector. System is back to normal. / Requested Fire Department.
We found out the 1F AMP panel battery trouble on FACP due to low voltage (M21). But we do not have the battery (18ah), so we replaced the battery (12v 35ah 2ea) instead of battery (12v 18ah) by firecops bench stock.
System is back to normal. / Requested Fire Department.
We found out the activated supervisory signal on FACP due to elevator #2 power shunt off (M07:M029). We checked and silenced the FACP. This trouble will be repaired by elevator contractor. / Requested Fire Department.
We found out the activated supervisory signal on FACP due to elevator power shunt off (M97:M049). We checked and silenced the FACP. This trouble will be normal condition after Corone Virus prevention done.