This document provides the details of an API 653 out-of-service inspection report for an aboveground storage tank located at Fort Campbell, Kentucky. The inspection was conducted on August 31, 2017 to evaluate the tank's integrity and establish a database for future inspections. The report documents the tank details including size, construction information, coating systems and corrosion protection. It also provides the results of non-destructive testing, measurements, surveys and evaluations performed on the tank's bottom, shell, appurtenances and foundation. Deficiencies identified during the inspection are documented along with corresponding repair recommendations to assure compliance with industry standards and codes.

View the file

Other files for this federal contract opportunity

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

USArmyCorpsofEngineers
OmahaDistrict
API653Out‐of‐Service
InspectionReport
FortCampbell,KY
FacilityNumberA‐6624
TankNumberSabreTank

US Army Corps of Engineers Center of Expertise for Petroleum, Oils, and Lubricants

(USACEPOL‐MCX)
August31,2017

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

TableofContents
ACRONYMSANDABBREVIATIONS ...................................................................................................................................... 4

GENERAL SUMMARY

INSPECTION DATE

STATE REGULATIONS

PREVIOUS INSPECTION DATES

RECOMMENDED FUTURE INSPECTION DATES (CALCULATIONS SHALL BE PROVIDED)

GENERAL TANK INFORMATION

A. GENERAL PROJECT INFORMATION

1. API 653 Inspection

2. Site Information

B. TANK INSPECTION COMMENTS

1. Tank Construction

2. Tank Foundation

3. Tank Bottom

4. Tank Shell

5. Tank Appurtenances

6. Tank Coating

7. Tank Piping System

8. Fire Protection System

9. Secondary Containment

10. Cathodic Protection

C. FINDINGS AND RECOMMENDATIONS

1. MANDATORY REPAIRS per API 653, UFC 3‐460‐01, or AW 78‐24‐27 Standards

APPENDIX A: ENGINEERING CALCULATIONS AND DRAWINGS

A.1 BOTTOM SERVICE LIFE EVALUATION

A.2 SHELL SERVICE LIFE EVALUATION

A.3 SHELL SETTLEMENT EVALUATION

A.4 ULTRASONIC UT DATA

A.5 CONTAINMENT LAYOUT DRAWING

A.6 BOTTOM LAYOUT DRAWING

A.7 SHELL LAYOUT DRAWING

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

A.8 ROOF LAYOUT DRAWING

A.9 OSHA ACCESS STRUCTURE REPORT

APPENDIX B: 3‐D DOCUMENTATION AND ANALYSIS

APPENDIX C: API 653 CHECKLISTS FOR TANK INSPECTIONS

APPENDIX D: PHOTOGRAPHS

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

ACRONYMS AND ABBREVIATIONS

API American Petroleum Institute

ASME American Society of Mechanical Engineers

ASNT American Society of Non‐Destructive Testing

ARD Anti‐rotation device

ATG Automatic Tank Gauge

BBL Barrel

CFR Code of Federal Regulations

CP Cathodic Protection

DFT Dry Film Thickness

HLA High Level Alarm

HLCS High Level Control Shutoff

HHLA High‐High Level Alarm

LLA Low Level Alarm

LLLA Low‐Low Level Alarm

MFL Magnetic Flux Leakage

MT Magnetic Particle Testing

NACE National Association of Corrosion Engineers

NDT Non‐Destructive Testing

NFPA National Fire Protection Association

PSI Pounds per Square Inch

PT Penetrant Testing

P/V Pressure/Vacuum

RP Recommended Practice

PST Product Saver Tank

RT Radiography Testing

TML Thickness Measurement Location

TRV Thermal Relief Valve

UFC Unified Facilities Criteria

UFGS Unified Facilities Guide Specifications

ULS Ultra Low Sulfur

UT Ultrasonic Testing

VT Visual Testing

VPI Valve Position Indicator

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

GENERALSUMMARY
SummaryofInspection
AnAPIStandard653Out‐of‐ServiceinspectionofSabreTank(FacilityA‐6624)atFortCampbellinClarksville,TN.
wascompletedonAugust31,2017toevaluatethetank’sintegrity,collectdata,andestablishadatabaseforfuture
inspectionsandevaluations.Aservicelifeevaluationperformedonthetankshowsitashavinggreaterthan30
yearsofremainingshelllifeundercurrentconditions.Thebottomlifeevaluationperformedonthetankshowsit
ashavinggreaterthan30yearsofremaininglifeundercurrentconditions.InspectionResultsarelistedinsection

C.

API 653 Out-of-Service Inspection Report Fort Campbell, Kentucky

INSPECTION DATE

API Out-of-Service (Internal) Inspection Date: 31 August 2017

Equipment (s) Used:

Ultrasonic Thickness (A-scan/B-scan) Testing Manufacturer: General Electric Model: DMS Go+ Calibration Methods Used: Zeroing Procedure, Copper Coating Calibration Procedure, and Two Point

Calibration Procedure

Tank Bottom Scanner Manufacturer: MFE Enterprises Model: 2412 Mark I Calibration Methods Used: Sensitivity adjacent on manufacturer supplied test plate with simulated anomalies and notch

Tank Bottom Surveying Manufacturer: Hilti Model: Hilti 286210 Rotating Laser PR 25 IF Calibration Methods Used: Main and transverse horizontal axes checks at 20 m < 6 mm

Tank Shell Surveying Manufacturer: Leica Geosystem Model: 3D Disto Calibration Methods Used: Tilt sensor calibration automatically performed with unit set at < 3° and crosshairs calibration using target at a distance > 25 m

Inspector(s): Benyam Berhane

STATE REGULATIONS

State Regulation for API In-Service Tank Inspections N/A State Regulation for API Out-of-Service Tank Inspections N/A

NOTE: If there are no state regulations for tank inspections, then N/A shall reside in-place of the number of years between inspections. If state regulations reside, the recommended future inspection dates shall be based on whichever is more stringent between the API inspector’s calculations and the state regulations.

PREVIOUS INSPECTION DATES

API Out-of-Service (Internal) Inspection Date: 15 February 2008 API In-Service (External) Inspection Date: Unknown/Not Provided

RECOMMENDED FUTURE INSPECTION DATES (CALCULATIONS SHALL BE PROVIDED)

API Out-of-Service (Internal) Inspection Date: 31 August 2037 (31 August 2027 IAW UFC) API In-Service (External) Inspection Date: 31 August 2022

Benyam Berhane Mechanical Engineer/Sr. Inspector InterSpec, LLC API 653 Certified Inspector No. 28492

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

GENERAL TANK INFORMATION

ITEMDESCRIPTION
OwnerU.SArmy
LocationFortCampbell,KY
FacilityNumberA‐6624
TankNumberSabreTank
State/CountryTennessee/USA
CityClarksville
InspectionDate31August2017
TankManufacturerAdamsonConstructionCompany–Richmond,VA
DesignStandardAPISTD650
DateofConstruction1975
TankContentsJP‐8(F‐24)
TankSerialNumberNone
TankDiameter30Feet
ShellHeight24Feet
ProductHeight23Feet
TankCapacity3,000BBL(126,000Gallons)
FoundationConcreteRingwall(OnOiltreatedSandcushiononacompactedSandClay)

Construction

Bottom Lap‐Welded (Cone‐Down)

Shell Butt‐Welded (Cylindrical)

Floating Roof Flat Aluminum Honeycomb IFR

Fixed Roof Lap Welded (Cone‐Up)

Material

Bottom Carbon Steel (unknown specification)

Shell Carbon Steel (unknown specification)

Floating Roof Aluminum (unknown specification)

FixedRoofCarbonSteel(unknownspecification)
CathodicProtectionImpressedCurrent
InteriorCoatingSystemThinFilmEpoxy
ExteriorCoatingSystemThinFilmEpoxy/Polyurethane(CompletedMay2003)
LevelGaugingMTSElectronicTankGaugewithVarec2500MechanicalTapeGauge
OverfillProtection
HydraulicallyOperatedHighLevelShut‐OffValvewithDedicatedFloat
(Setat20.53Feet)
PipingReceipt8"CarbonSteel
Issue4"CarbonSteel
LowSuction3"CarbonSteel
WaterDraw‐Off1"CarbonSteel

Level Alarms

Low‐LevelAlarm:XX (InfoRequested fromPOL POC)
Low‐LowLevelAlarm:N/A(NoLLLA)
High‐LevelAlarm:XX(InfoRequestedfromPOLPOC)
High‐HighLevelAlarm:XX(InfoRequestedfromPOLPOC.MountedonRoof)
High‐LevelControlShutoff:20.53Feet
TypeofInternalFloating
RoofAluminum Honeycomb- with primary and secondary wiper perimeter seals

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

A. GENERAL PROJECT INFORMATION

1. API653Inspection
ThisprojectwillperformAPI653inspectionsofvarioustanksatfacilitiesthroughouttheUnitedStates.
Additionalconsiderationisgiventofederal,state,andlocalregulations,aswellasapplicablemilitary
criteriaandgeneralindustrystandards.

An API Standard 653 Out‐of‐Service (Internal/External) inspection was performed for Saber Tank (FAC A‐6624).

2. SiteInformation
OnAugust28,2017Burns&McDonnellandoursub‐consultant(InterSpec)performedanAPI653Out‐
of‐Service(InternalandExternal)inspectionofSaberTank(FacilityA‐6624)locatedatFortCampbell,
Kentucky.FortCampbellishometothe101stAirborneDivision,5thSpecialForcesGroup,160th
SpecialOperationsAviationRegiment(SOAR),andahostofotherArmyAirAssault,InfantryBattalions,
andsupportteamelements.FortCampbell'smorethan105,000‐acreinstallationislocatedin
southwesternKentuckyandnorthcentralTennesseeinportionsoffourcounties.FortCampbell's
primarymissionistoadvancethecombatreadinessofthe101stAirborneDivision(AirAssault)and
thenon‐divisionalunitspostedattheinstallationthroughtraining,mobilization,anddeployment.

Sabre Tank is used as an aboveground jet fuel storage tank supporting the installation fueling needs.

B. TANK INSPECTION COMMENTS

1. TankConstruction
SaberTank(FACA‐6624)isanominal3,000BBL,30‐footdiameterby24‐foottall,F‐24(JetFuel),
abovegroundverticalstoragetank.ThetankwasconstructedbyAdamsonConstructionCompanyof
Richmond,VAin1975toAPIStandard650.Therewasnomajorrepair/alterationperformedforthis
tanksincethelastout‐of‐serviceinspectionthatwascompletedin2008.Aflataluminumhoneycomb
IFR,levelalarms,highliquidlevelshut‐offsystem,additionalaluminumstillingwells,andinternalpipe
supportmodificationwasnotedassomeofthealterationscompletedsincethe2008inspection.
2. TankFoundation
Thetanksitsonaconcreteringwallfoundationthatisapproximatelythesameelevationasthe
secondarycontainmentfloor.Theavailableoriginalconstructiondetailliststhefoundationtoincludea
four‐inchlayerofoiltreatedsandcushionontopofafour‐inchcompactedsandclay.Thefoundationis
notdesignedwithaleakdetection(tell‐tale)systemthatextendstothecenterofthetank.Accessible
sectionsofthefoundationwerevisuallyevaluatedduringtheinspectionforbrokenconcrete,spalling,
cracks,andvegetationagainstthebottomofthetank.Nospallingandvegetationwerepresent.The
foundationtochimeinterfaceissealed.Moderatesealantdeteriorationispresentthroughout,with an
approximatetotalof95linearfeetofdeterioratedcaulkingidentified.Thetopofthebottomplate
extension(chime)iscoveredinsealantinmostplacesandistrappingwater,resultingincoatingfailure
andcorrosion.Thefoundationtosecondarycontainmentjointsealantisalsodeterioratedwithan
approximatetotalof98linearfeetidentified.Shellsettlementsurveyswereperformedduringthe
inspectioninaccordancewithAnnexBofAPIStandard653.SettlementresultsarelistedinAppendixA.

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

Thereisnoindicationofsignificantsettlement.Overall,thefoundationappearstobeisinsatisfactory
condition(Asmallsectionofthefoundationisaccessibleforinspection).
3. TankBottom
Thenewbottomisconstructedfromcarbonsteelmaterialwithunknownspecification.Thebottomisa
cone‐downdesign,lap‐weldedtogether,consistingoften(10)coursesfillet‐weldedtotheshell.The
bottomhasathinfilminteriorliner.Theinteriorcoatingwasevaluatedfordis‐bonding,adhesion,
deterioration,anddiscolorationandwasfoundtobeunsatisfactory.Isolatedcoatingfailurewasnoted
throughoutthetankbottomandshell‐to‐bottomarea.Aclosevisualinspectionofallthewelded‐on
plateswasperformedforindicationsofcrackedwelds,crackedcoating,andcapillaryeffectsof
residues.Nodeficiencywasnotedwiththewelded‐onplates.Dryfilmthickness(DFT)readings
typicallyrangedbetween9‐21mils,withsomeareasneartheshell‐to‐bottomandbottomlap‐welds
havingahighcoatingthicknessintherangeof30to40mils.
SeveralareasofburnedcoatingfailureswerealsonotedonPlate3and4(SeeTankBottomLayout).
Thiswaslikelyduetoweldingspatterburns,presumablyduringhotworkinsidethetank.Evaluated
thebottom,bottomwelds,andbottom‐to‐shellweldforcorrosion,withnootherdiscrepanciesnoted.
Performedamagneticfluxleakage(MFL)evaluationofthetankbottomtodeterminetheconditionof
theunderside;ninety‐fivepluspercentwasscanned.Noareasindicatingundersidecorrosionwere
located.Anultrasonicinspectionofthebottomsuggestsanominalthicknessof0.250".
4. TankShell
Thetankshellisconstructedfromcarbonsteelmaterialofanunknownspecification.Theshellisof
cylindricaldesign,butt‐weldedtogether,andconsistingoffour(4)courses.Evaluatedtheshellfor
plumbness,roundness,peaking,andbanding;allofwhichwerefoundtobewithintheallowable
tolerancesoftheAPIStandard653.Visuallyinspectedboththeinteriorandexterioroftheshell.
Inspectedthecoatingfordis‐bonding,adhesion,deterioration,anddiscoloration(SeeSection6below).
Thetankshellisequippedwithone24"manholeanda24"flushdeckcleanoutnozzle.Thetankis
equippedwithshellmountedlowlevelalarm,high‐highlevelalarms,aswellasahigh‐levelshut‐off.
Theshellwasevaluatedforremainingmetalthicknessutilizingultrasonictechnology.Theultrasonic
thicknessmeasurementsandthicknessmeasurementlocations(TML)arelistedintheShellPlate
ThicknessMeasurementstableinAppendixA.Aservicelifeevaluationperformedshowstheshellwith
greaterthan30yearsofremaininglifeundercurrentconditions.Theengineeringcalculations,asper
APIStandard653,fortheservicelifeevaluationareshowninAppendixAunder“ServiceLife
Evaluation.”Thetankshellisinsatisfactorymechanicalcondition.
5. TankAppurtenances
a. InternalFloatingRoof
Thetankisequippedwithafullsurfacecontactaluminumhoneycombdesignthatisfitted
withprimaryandsecondarywiperperimeterseals.TheIFRisrestingapproximately73.25"
(measuredattheperimeter)abovethetankbottomandissupportedbysix(6)floatingroof
legs.Ateninchsquarestrikerbearingplatewithroundedcornersisweldedtothetank
bottomforeachIFRsupportleg.Evaluatedtheconditionofthefloatingroofseals.The
primaryIFRperimetersealandsecondaryperimetersealareingoodmechanicalcondition.
Measuredtheannularspaceatseverallocationsfromthetankbottom,andthefloatingroof
isdeterminedtobeproperlycenteredinsidethetank.

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

b. Geodesic Dome Roof N/A

c. Gauging

Thetank’sMTS(Model#MGAMC1P11B5U31400S)ATGisinstalledthroughan8‐inch
carbonsteelgaugewell.Thestillingwellisnotslotted.Thetransmitteroutputsthetank
leveltoacontinuouselectronictankmonitoringsystem(model# G300)manufacturedby
RedLionsControls.TheATGmonitorismountedonthesouthwestsideofthepumphouse
(adjacenttothetanksecondarycontainment).Manualgaugingandsamplingareperformed
throughthefullyslotted8‐inchaluminumwell(NozzleEonfixedRoof).Thetankis
equippedwithanewfloatandtapetypemechanicaltapegaugemanufacturedbyVarec
(Model2500).Themechanicalgaugetapeisfastenedtothetopoftheinternalfloatingroof
(IFR).Duetothisconfiguration,a"bumpcheck"wasnotperformedonthemechanical
gaugehead.Thetapegaugeisnotinstalledtothefloatingroof,perthemanufacturer.The
ProtectosealSeriesNo.42000BwasreplacedwithVarecmodelduringthetankinspection
projectandappearstobeingoodworkingcondition.
d. LevelAlarms
Thehighlevelalarmismountedontheshellandisaccessibleviathecircumferential
mountedstairway.Thehigh‐highlevelalarmismountedonthefixedroofusingtheteninch
NozzleDandutilizestheeight‐inchaluminumstillingwell.The high‐highlevelalarmisa
model704manufacturedbySORMeasurementandControlsandisequippedwithamanual
checkactuatortosimulatehigh‐levelcondition.Thehigh‐highlevelalarmhornandlight
panelaremountedonsoutheastsideofthepumphouse(adjacenttothetanksecondary
containment).Thetankisequippedwithalow‐levelalarm,butnoindependentlow‐low
levelalarmsystemwasinstalled,asrequiredbymilitarycriteria.
e. StairsandPlatforms
Thetank’sfixedroofisaccessiblebyacircumferentialstairwaymountedontheshellofthe
tankwithatopplatform.Thestairandplatformwereinspectedforcorrosionandstructural
soundness.Thestairwayhandrailisconstructedwith¾"roundbarhandrailsandsteel
platethreadswithnon‐slipprofile.Theoverallgeneralconditionofthestairsandplatform
aresatisfactory(withsomeexception–SeeSectionC).
f. GroundingandBonding
Therearetwogroundingcablesconnectedtolugsonthetank’sshell.Thegroundingcables
penetratethroughthesecondarycontainmentfloorpresumablytoagroundingrod.The
internalfloatingroofisbondedtothetankfixedroof.Acoppergroundingbarforpersonnel
staticelectricdischargeisnotmountedonthehandrail(typicallyrequiredbymilitary

criteria).

6. TankCoating
Thetankshell,bottom,roof,stairway,handrails,piping,andappurtenancesarecoated.Theexterior
coatingappearstobeanepoxywithpolyurethanetop.TheexteriorshellcoatingischalkingduetoUV

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

exposureandpossibleminimalUVprotectioninclusionduringthelastexteriorcoating.Similarcoating
failurewasnotedonproductpipingwithinthesecondarycontainment.
7. TankPipingSystem
Thefuelisreceivedthrough8‐inchcarbonsteelpipingthatisfittedwithaninletdiffuser.Thediffuser
isrolledtoacirculartransition,withafinaloutletdiameterofNPS10.Theproductisissuedfromthe
tankthrougha6‐inchcarbonsteelpipethatextends136"intothetank.Otherauxiliarypipingforthe
waterdraw(NPS2)andlowsuction(NPS3)areinstalled,andbothextendtothecentertankbottom
sump.InspectedandevaluatedeachtanknozzleinaccordancewithAPIStandards650and653.
Identifiedthetypeanduseofeachshellnozzleandmeasuredthenozzleneckthicknessonall
accessibleshellnozzles.Evaluatedallnozzlesandreinforcementplatesforleaksandcorrosion.

8. Fire Protection System None

9. SecondaryContainment
Thetanksitsinsideaconcretesecondarycontainmentbasinwithconcretedikewalls.Theoverall
dimensionofthesecondarycontainmentis88.5feetx85.5feet,withaslopedbermwithavertical
heightof50.25".Thesecondarycontainmentisequippedwitha6"draininletandalockeddrainvalve
toadrainagepitapproximately53feetnorthwestofthedraininlet.ThedrainlineisaNPS6carbon
steelpipingwithasixinchreleasevalve.Thedrainlineandthedraininletwerehydrostaticallytested
toinvestigateifthedrainagesystemisliquid‐tight.Thedrainpipeandreleasevalveweretestedwith
waterbypressurizingto10psigusingapumpconnectedtoapipetestingassembly.Thetestwas
conductedinaccordancewiththeapplicablerequirementsofAWWAC600forhydrostatictesting.The
draininletwashydrostaticallytestedforintegritybyfillingtheinletwithwatertoalevelatleast1‐2
inchesabovethetopoftheinletstructure.Thedraininletandreleasevalvedidnotpassthehydrostatic
test(Lost3.5psiginthetwohourtestperiod).Waterescapedthroughthereleasevalveinsidethe
valvepit.Cleaningvalveseatingsurfaceandretestingmayberequired.Thedraininletinitiallyfailed
theoutlinedtestlikelyduetofailedlowerbootsealbetweenthedraininletandtheNPS6drainline
(notaccessible).Thedraininletwasretestedandpassedafteranonsitecontractorappliedajoint
sealantcaulking.
Thesecondarycontainmentwasvisuallyevaluatedduringtheinspectionforbrokenconcrete,spalling,
cracks,andvegetationgrowth.Minorhairlinecracks(temperaturecracks)andsomemoderatecracks
werenotedinthesecondarycontainmentandaredocumentedinthesecondarycontainmentlayout.An
approximatetotalof29linearfeetofcracksinthesecondarycontainmentbermwereidentified.This
includes approximately10feetofcracksthathavebeenpreviouslysealed,5feetontheinnerslopeof
thebermwallsand14feetofcracksonthetopofthesecondarycontainment‐walkingpath.Hairline
cracksandcracksontopofthewalkingpathdonotseriouslyaffectthestrengthoftheconcrete
structures;however,thesecrackscanbepotentialaccesspointsformoistureorwaterseepagethat
couldcorrodethereinforcingsteel(rebar).Severalunsealedsecularholesnotedinthesecondary
containmentfloor(probablyanabandonedorunusedopeningfortracerprobe).Theepoxysealantfor
thesecondarycontainmentconcretefloor/interiorwallexpansionandslabjointhasalmost100%
deterioration/failure.Anapproximatetotalof730linearfeetoftotaljointsealantwasmeasured.The
secondarycontainmentisotherwiseinmostlysatisfactorymechanicalcondition,withtheexceptionof
thediscrepanciesidentifiedabove.Fieldassessmentindicatesthatthesecondarycontainmentisof

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

sufficientsizetocontainatotaltankloss.Thesecondarycontainmentisnotslopedtoallowfor
drainageawayfromthetank.Waterpuddlingwasobservedthroughouttheperimeterofthetankwith
significantdepthattheflushdeckcleanoutarea(inadequatedrainawayfromtank).Coatingfailureand
corrosionwerenotedonthelowerfastenersandcover.
Aformalsecondarycontainmentevaluation,inaccordancewith40CFR112,mayberequiredinorder
tosatisfyfederal,state,andlocalrequirements.Thesecondarycontainmentisequippedwithalockable
secondarycontainmentvalvepostindicator.
10. CathodicProtection
AnimpressedcurrentCathodicProtection(CP)systemisinstalledonthistankwhichisservingboth
thetankbottomandassociatedundergroundpiping.Therectifierwasinstalledin2015andislocated
onthesoutheastsideofthepumphouse.TheCPsystemismanufacturedbyCathodicRectifiers,Inc.
Rectifiers,Inc.(ModelACPwithserial#1184110514).Thisunitisa75volt5ampereair‐cooled
rectifierunit.TheCPsystemislistedashavingamixedmetaloxideanodelooplaidonthesoutheast
cornerofthetankjustoutsidethesecondarycontainmentdike.
Atthetimeoftheinspection,therectifierwaspoweredonandinserviceableoperationcondition.Base
personnelperformedtherequiredtestinganddatalogging.TheJanuary2017reportprovided
indicatedthatSaberTankisreceivingcathodicprotectionbasedonNACEcriterion.Therectifier,anode
junctionbox,andtankjunctionboxallareinsatisfactorycondition.

C. FINDINGS AND RECOMMENDATIONS

Thetankisgenerallynotinaccordancewithcurrentmilitarycriteriaforsomeofthetankappurtenanceand
pipingconfiguration.Therefore,therecommendationsarenotmeanttobringthetankintofullcompliance
withUFC3‐460‐01orAW78‐24‐27standardsbutrathertoidentifytheseitemsfortheowner/user’splaned
upgrades,rehabilitation,andpriorityrepairs.Mandatoryrepairsshouldbecompletedtoassurecompliance
withindustrystandards,aswellasfederalorstatejurisdictionalrequirements.
Duringthisevaluation,thetankbottomwasfoundtobeinagenerallyserviceablecondition,withnoimminent
risktooperationandoverallintegrity.However,therewereseveraldeficienciesthatwerenoted.Thesenoted
deficienciesarelistedbelowinnoparticularorder,withrepairrecommendations.
AllrepairsandmodificationsshouldbeperformedinaccordancewithAPIstandard653,UFC3‐460‐01,DoD
StandardDesign78‐24‐27,andapplicableUFGSspecifications.
1. MANDATORYREPAIRSperAPI653,UFC3‐460‐01,orAW78‐24‐27Standards
Mandatoryrepairsrepresentitemsthatrequireimmediateattention,inordertopreventimminentrisk
tosystemoperators,equipmentintegrity,ortheadjacentenvironment.Thetankshouldremainoutof
serviceuntiltheserepairsarecompleted.

No mandatory repairs were identified for Saber Tank (FAC A‐6624).

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

2. REQUIREDREPAIRStoFullyComplywithAPI653orFederal,State,andLocalCodes
Requiredrepairsrepresentitemsthatshouldbeaddressedinatimelymanner,inordertoprevent
futurepotentialriskstosystemoperators,equipmentintegrity,ortheadjacentenvironment.These
itemsareberequiredbyAPI‐653orfederal,state,andlocalcodes.
a. SecondaryContainmentCracks
OBSERVATION:Unsealedcrackswereidentifiedinthesecondarycontainmentberm(thisincludes
areasthatwerepreviouslysealed).Severalunsealedsecularholeswerenotedinthesecondary
containmentfloor(probablyabandonedorunusedopeningfortracerprobe).
CODEREFERENCE:40CFRSection112.7(c)statesthattheentiresecondarycontainmentsystem,
“includingwallsandfloor,mustbecapableofcontainingoilandmustbeconstructedsothatany
dischargefromaprimarycontainmentsystem...willnotescapecontainmentbeforecleanupoccurs.”
§§112.8(c)(2)and112.12(c)(2)statethatdikedareasmustbe“sufficientlyimpervioustocontainoil.”
RECOMMENDATION:RepairallexposedcracksinthecontainmentwallsbygrindinginaV‐shape
pattern,withatleast¼‐inchwidthatthesurfaceandadepthofatleast¼‐inchandsealingwith
flexibleurethane(e.g.Sikaflex1c)orasimilarapprovedsealant(Quantity:29linearfeet).
b. SecondaryContainmentExpansionJointSealant
OBSERVATION:Thereareareasofweatheredanddeterioratedsealantthroughoutattheexpansion
jointsforthesecondarycontainmentdike,includingthebasinfloortofoundationperimetersealant.
CODEREFERENCE:40CFRSection112.7(c)(Seereferencefromabove)
RECOMMENDATION:Removethedamagedjointsealantandinstallnewbackerrodsandsealantwithin
thecontainment.Thesealantshallbeadequatetoaccommodateajointcompressionequalto50

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

percentofthewidthofthejoint.Thebackerrodshallbecompressiblerodstockofpolyethylene
foam,polyurethanefoam,butylrubberfoam,orotherflexible,non‐absorptivematerial,as
recommendedbythesealantmanufacturer.SealantshallconformtoUFGS079200JointSealant
(Quantity:730linearfeet).
c. SecondaryContainmentBasinPipePenetration
OBSERVATION:TheNPS6productsuctionandNPS8productreceiptpipinghavesealant
deteriorationattheconcretebasinfloorpenetration.Bothpipingpenetratetheconcretebasinfloor
withnosleeveorsleeveseal.
CODEREFERENCE:40CFRSection112.7(c)(Seereferencefromabove)
RECOMMENDATION:UpgradetheconcretebasinpipefloorpenetrationasdetailedinAW78‐24‐27
DrawingCD.02Detail2.Ataminimum,repairthedeterioratedsealantintheexistingpenetration
configuration.(Quantity:2).

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

d. SecondaryContainmentDrainInletPipe
OBSERVATION:Thedraininletandreleasevalvedidnotpassthehydrostatictest(Lost3.5psiginthe
twohourtestperiod).Waterescapedthroughthereleasevalveinsidethevalvepit.Cleaningvalve
seatingsurfaceandretestingmayberequired.Thedraininletinitiallyfailedtheoutlinedtestlikely
duetofailedlowerbootsealbetweenthedraininletandtheNPS6drainline(notaccessible).The
draininletwasretestedandpassedafteranonsitecontractorappliedajointsealantcaulking.
CODEREFERENCE:40CFRSection112.7(c)(Seereferencefromabove)
RECOMMENDATION:UpgradetheconcretedraininletasdetailedinAW78‐24‐27DrawingCD.09
Detail3orsimilar.Ataminimum,thefloordraintypeinletshouldbereplacedtoensureitwillnot
allowwatertobypasswhenthetopsidecaulkingdeteriorates(forexample,shouldhavetwolayers
ofsealingsystem;elastomericseal,andbootseal).

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

e. SecondaryContainmentDrainage/Slope
OBSERVATION:Thesecondarycontainmentisnotslopedtoallowfordrainageawayfromthetank.
Waterpuddlingwasobservedthroughouttheperimeterofthetankwithsignificantdepthattheflush
deckcleanoutarea(inadequatedrainawayfromtank).Coatingfailureandcorrosionwerenotedon
thelowerfastenersandcover.
CODEREFERENCE:NFPA30Section22.11.1andUFC3‐460‐Section8‐14.1.cstates,“aslopeofnot
lessthan1percentawayfromthetankshallbeprovidedforatleast50ft(15m)ortothedikebase,
whicheverisless.”
RECOMMENDATION:Reworkthesecondarycontainmenttoprovidetherequiredslopeawayfromthe

tank.

f. TankGroundingLug
OBSERVATION:Thetankgroundingstrapsareboltedtothetankshell(mechanicaljointonacoated
interface)andhavenoreinforcementplatesorgroundinglugIAWAW78‐24‐27DrawingED.02
Detail2.
CODEREFERENCE:AW78‐24‐27DrawingED.02Detail2.(SeealsoAPI650Section5.8.11.3)
RECOMMENDATION:Exothermicallyweldthegroundingcablestothelugandinstallreinforcementat
theshell,inaccordancewithAW78‐24‐27DrawingED.02Detail2.Note:ifrepairsareelectednotto
bedone,thepaintshouldberemovedwherethecableboltstothelug,toprovideabetterconnection
toground(Quantity:2groundconnections).

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

g. ProductSaverTank(PST)Grounding
OBSERVATION:TheProductSaverTankisnotgroundedattheleganddoesnothaveaventinstalled
inaccordancewithAW78‐24‐27DrawingD.13DetailA1.ThePSTisacoatedcarbonsteeltankwith
atoplid.ThePSTtankhasnomeansofgrounding.
CODEREFERENCE:AW78‐24‐27DrawingD.13DetailA1.InaccordancewithNFPA30,paragraph
6.5.4,“Allequipmentsuchastanks,machinery,andpipingshallbedesignedandoperatedtoprevent
electrostaticignitions.Allmetallicequipmentwhereanignitablemixturecouldbepresentshallbe
bondedorgrounded.Thebondorgroundorbothshallbephysicallyappliedorshallbeinherently
presentbythenatureoftheinstallation.”
RECOMMENDATION:InstallagroundcableandventpipingtotheProductSaverTankinaccordance
withAW78‐24‐27DrawingD.13Detail5(Quantity:1ground,1ventpipe(1¼NPS,2‐feethigh).
h. PilottubingfromHLVtoHLVFloatPilot
OBSERVATION:The½stainlesssteel(SS)tubingfromthehighliquidlevelshut‐offvalve(HLV)toHLV
penetratesthestairwaytread.MinorabrasiontypeofdeteriorationisnotedonallthreeSStubing
(holesmayhavetobeenlargedortubingrerouted).Prongedabrasionwillcausealeakinthetubing
andwillpreventtheHLVsystemfromoperatingproperly.
CODEREFERENCE:API570Section3.1.11contactpoint(Thelocationsatwhichapipeorcomponent
restsonoragainstasupportorotherobjectwhichmayincreaseitssusceptibilitytoexternal
corrosion,fretting,wear,ordeformation).

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

RECOMMENDATION:Enragetheholesinthestairwaytreadsorreroutethetubing.SeeAW78‐24‐27
DrawingD.12Detail2.
i. StairwayPathRestricted
OBSERVATION:ThereislimitedorrestrictedpathonthespiralstairwayduetoHLAandHLV
projectionintowardsthestairway.Thereisnointermediateplatform.Thereisanapproximately
fourteen(14)inchclearancebetweenthehandrailandHLAfloatchamber.Thisreducestheexisting
threadwidth.
CODEREFERENCE:UFC3‐460‐01SectionTable8‐1itemj.OSHAminimumrequiredthreadwidthis
22inches(1920.25(C)(3))
RECOMMENDATION:Installanintermediateplatformorreworkthestairwaytoprovideasufficient
pathpasttheHLAandHLVsystem.
j. AbandonedMountingPlatesforInternalPipingSupport
OBSERVATION:Thereare5rectangular12”x8”abandonedmountingplatesforinternalpiping
supportwithsquaredcorners.Oneofthesemountingplatesiswelded(butted)tothetankbottom
lap‐weld(onPlate#10;shownwithredarrowsbelow).
CODEREFERENCE:AccordingtoAPIStandard653,Paragraph9.10.3.1“Ifotherwelded‐onplatessuch
aswear,isolation,strikerandbearingplates,aretobeaddedtotankbottoms,theyshallbeinstalled
inaccordancewith9.10.1andexaminedinaccordancewith12.1.7.Fortheseadditionalweldedon

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

plates,ifthelapweldspacingrequirementsassetforthinFigure9‐5arenotmet,magneticparticle
(MT)orliquidpenetrant(PT)examinationisrequiredfortheexposedweldsorportionsofwelds
failingtomeetminimumspacingcriteria.SeeAPI653Section12foracceptancerequirements.”
NOTE:MTorPTNDTmethodsrequirethecoatingremovalandsurfacepreparedasrequiredin
ASMESectionVArticle6orArticle7.Theseexaminationsmayhavebeenaccomplishedduringthe
2009tankrepairbutreviewoftheprovideddocumentsdidnotindicatethetestingmethods
performed.Aclosevisualinspectionofthewelded‐onplateandadjacentbottomwelddidnotreveal
anystressedareas(indicationofcrackedweld,crackedcoating,orcapillaryactioneffectsof

residues).

RECOMMENDATION:Futurerepairprojectshouldconsiderremovaloftheseabandonedmounting
platesorperformanexaminationinaccordancewith12.1.7(requirescoatingremovaltodoMTorPT

examination).

k. ShellManholeCoverwithnoHingeorDavitArm
OBSERVATION:Theshellmanholecoverisnotequippedwithahingeordavitarmtofacilitatethe
handlingofthemanholecoverplate.
CODEREFERENCE:APISTD650Section5.8.3.5states“Shellmanholecoversshallhavetwohandles.
Thosecoversweighingmorethan34kg(75lb)shallbeequippedwitheitherahingeordavitto
facilitatethehandlingofthemanholecoverplate.Thedavitsupportarmshallnotbeweldeddirectly
totheshellwithoutareinforcingplate.”AlsoAW78‐24‐27drawingD.10detail3
RECOMMENDATION:InstallashellmanholedavitarmIAWwithAPISTD650andAW78‐24‐27
drawingD.10detail3.

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

l. ShellManholeNeckWeld
OBSERVATION:Three(one‐inchlong)incompletefusionweldswerenotedbetweenthemanholeneck
andflange.
CODEREFERENCE:APISTD653Section9.6“Existingweldundercutdeemedunacceptablebasedon
suitabilityforserviceconsiderationsshallberepairedbyadditionalweldmetal,orgrinding,as

appropriate”

RECOMMENDATION:Notethisisoriginaltankconstructionflaw;basedonsatisfactoryservicehistory,
thisdeficiencycanbedeferredandcompletedwhentheshellmanholeisreworkedfordavitarm
installationoriffutureplansincludeupgradetothe36”manholeperUFCandAW78‐24‐27drawing.
m. TheLowSuctionandWaterDrawNozzleReinforcementPad
OBSERVATION:ThelowsuctionshellpenetrationpipeisNPS3anddoesnothaveareinforcement
pad.Thewaterdrawpipepenetrationopeningisalsonotequippedwithareinforcementpad.
CODEREFERENCE:APISTD650Section5.7.2“Openingsintankshellslargerthanrequiredto
accommodateaNPS2flangedorthreadednozzleshallbereinforcedIAWAPI650.”
RECOMMENDATION:Notethisisoriginaltankconstructiondesign,andbasedonsatisfactoryservice
history,thisdeficiencymaybebedeferredandcompletedwhenfutureupgradeworkisplanned.

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

n. InteriorTankCoating
OBSERVATION:Minortomoderatecoatingfailure(mostlybreaks)wasnotedthroughoutthetank
bottomandisdocumentedinthetankbottomlayout.Severalareasofburnedcoatingfailureswere
alsonotedonPlate3,4,7,8,10andontheshellnearthereceiptandsuctionpipe(SeeTankBottom
Layout).Thiswaslikelyduetoweldingspatterburns,presumablyduringhotworkinsidethetank.
Dryfilmthickness(DFT)readingstypicallyrangedbetween9‐12mils,withsomeareasnearthe
shell‐to‐bottomandbottomlap‐weldswithahighcoatingthicknessintherangeof30‐40mils.The
interiorshellcoatingabovetheIFRandundersideoftheroofisinsatisfactorycondition,with
minimaldiscoloration.Thecoatingthickness(atareasaccessed)isinsatisfactorycondition,with
coatingthicknessintherangeof10‐17mils.
CODEREFERENCE:Allaviation,dieselfuelmarine(F‐76),additive,andlubeoiltank.Interiorsshallbe
100percentcoated,includingfloor,shell,andundersideoftheroof(UFC3‐460‐01Section8‐

3.9(a)(1)).

RECOMMENDATION:PreparethesurfaceofthetankbottomandrepairtheareasofcoatingfailureIAW
UFGS‐099713.15.

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

o. InteriorProductPipingandSupports
OBSERVATION:Theinteriorproductissuenozzle isnotconfiguredasdetailedinAW78‐24‐27
drawingD.84detail4.Thespacingbetweenthetankbottomandanti‐vortexplateis8inchesinstead
ofthe6inchesspecified.Theissuepipingextendstowardsthecenterofthetank(Not½ofthetank
radius).Alltheinteriorpipingsupportsarenotdesignedtohaveadjustableverticalmember(gaps
betweenpipeandsupportsarenotedonbothlowsectionandwaterdrawpiping).TherearenoU‐

bolts.

CODEREFERENCE:AW78‐24‐27drawingD.08detail4anddetail6.
RECOMMENDATION:Adjustormodifytheissuelineasneeded.Futuremodificationshouldconsider
adjustablepipesupportswithTefloncoatedstainlesssteelU‐bolts.

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

p. IFRPipePenetrationGaskets
OBSERVATION:Theinternalfloatingroofstillingwellspenetrationgasketshavedeteriorated(four

gaskets).

CODEREFERENCE:Generalmaintenance/manufacturerinstructionandAPI653Checklistitem
(openinginsealsthatwillpermitvaporemissions)
RECOMMENDATION:Replacethegaskets.Gasketsinsidethetanknozzlesshallbenon‐asbestos,fuel
resistantcomposition,orpreformedtype.ATGWell=18"x18"withNPS8pipe,SampleGaugeWell
=18"x18”withNPS8pipe,LevelAlarmWell18"x18”withNPS8pipeandWaterProbeWell=18"
x18"withNPS2pipe.
3. RECOMMENDEDREPAIRStofullycomplywithUFC3‐460‐01&AW78‐24‐27Standardsoras
PartofRegularMaintenance
Recommendedrepairsrepresentitemsthatshouldbeaddressedinatimelymanner,inorderto
preventfuturepotentialriskstosystemoperators,equipmentintegrity,ortheadjacentenvironment.
a. TankBottomExtension(Chime)
OBSERVATION:Thefoundationtochimeinterfaceissealed.Moderatesealantdeteriorationispresent.
Thetopofthebottomplateextension(chime)iscoveredinsealantinmostplacesandistrapping
water,resultingincoatingfailureandcorrosion.Thereisminortomoderatecoatingfailureand
associatedcorrosion.
CODEREFERENCE:Maintainawaterproofsealatthetankchimeringwallfoundationinterface(UFC
3‐460‐03Section10.3.3).
RECOMMENDATION:Repairareasoffailedsealantbyapplyingapolysulfidemasticsealantcaulking.
NOTE:Donotcaulktheend(side)ofthechime.SeeAW78‐24‐27DrawingD.04Detail3.Repair
coatingonthechimearea.

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

b. ExteriorCoatingFailuresonTank,Appurtenances,andFadedTankMarking
OBSERVATION:TheexteriorshellandroofcoatingarechalkingduetoUVexposureandpossible
minimalUVprotectioninclusionduringthelastexteriorcoating.Similarcoatingfailurewasnotedon
productpipingwithinthesecondarycontainment.Thereismoderatecoatingfailureontheupper
sectionofthetankshell,roof,roofnozzles,andtheperimeterguardrail.Thetankmarkingshave

faded.

CODEREFERENCE:UFC3‐460‐01,Section8‐3.10andSection9‐10
RECOMMENDATION:Mechanicallycleanandrecoatareasofcoatingfailureonthetankshell,roof
piping,andappurtenances.Repairsshouldbeaccomplishedusinganepoxybasedcoatingsystemor
equivalent.ReplacethefadedtankmarkingIAWNFPA30andNATOrequirements.

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

c. VentCorrosionandSomeEdgeSeparation
OBSERVATION:Theventscreenshaveminorcorrosionandsomeedgeseparation.Considerupgrading
alltheventscreens(twooverflow/circulationvents,tworoofcirculationvents,andonecenterroof
vent)withcorrosion‐resistantcoarsemeshbirdscreens.
CODEREFERENCE:API650Section5.8.5.5,“Allfreeventsshallbeprovidedwithcorrosion‐resistant
coarsemeshbirdscreensofamaximumopeningsizeof(19mm[3/4in.]nominalopening)”andAW
78‐24‐27DrawingD.09Detail1and2
RECOMMENDATION:Installcorrosion‐resistantcoarsemeshbirdscreens.
d. TankElectronicATGandWaterProbe
OBSERVATION:THEtankisequippedwithanMTS(Model#MGAMC1P11B5U31400S)TheATGis
installedthroughan8‐inchcarbonsteelgaugewell.Thestillingwellisnotfullyslotted(hasasmall
slitthatisapproximately7"longand¼"wide.Itisalsoweldedtothetankbottomandroof,withno
provisionfortankbottommovement.Thereisnomounting/bearingplateunderthisstillingwell.At
thetimeofinspection,thebottomofthesensorcablewaslodgedtosideofthecarbonsteelstilling
well(magneticweight).Thesensorcablewasadjustedinorderto“freefloat”insidethegaugewell.
ThereissomecoatingfailureontheTankControlUnitpanel.ThiselectronicATGrequiresnitrogen
gassupplytooperate.Thewaterprobeisnotinstalledoverthetankbottomsumpthroughawater
probewell(separatewell).
CODEREFERENCE:UFC3‐460‐01Section8‐8.3andAW78‐24‐27DrawingD.07Detail4
RECOMMENDATION:InstallanATGasstatedintheDLAMemorandumforDirectorDefenseEnergy
SupportCenterforAutomatedTankGauge(ATG)InstallationPolicydatedDecember16,2009.
ModifythestillingwellIAWwithAW78‐24‐27.MountingplateweldingperAPISTD653Section

9.10.3

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

e. MechanicalTapeGauge
OBSERVATION:Theexistingmechanicaltapegauge(ProtectosealSeriesNo.42000B)wasnot
functioningcorrectlyandwasoutofcalibration.AnewVarec(Model2500)mechanicaltapegauge
wasinstalledbytheonsitecontactor.Themechanicalgaugetapeisfastenedtothetopoftheinternal
floatingroof(IFR).Duetothisconfiguration,a"bumpcheck"wasnotperformedonthemechanical
gaugehead.Thetapegaugeshouldnotbeinstalledtothefloatingroof,perthemanufacturer.
CODEREFERENCE:Generalmaintenance/manufacturer’sinstruction
RECOMMENDATION:Calibratethemechanicaltapegaugeafterplacingthetankinservice.Donotturn
theoperationcheckerknobonsystemsthathavenofloatandthataredirectlyconnectedtoafloating
roof.Installasignthatreads,“DONOTOPERATECHECKERKNOB.”Thissignagecanbedisplayed
untilthetapegaugeisreinstalledinaccordancewiththemanufacturer'sinstructions.Themechanical
tapegaugecanberetrofittedbyattachingthetapetoasix‐poundweight(preferablyaluminum),
whichcanbeplacedontopofthefloatingroof.

f. Hold‐Off Distance

OBSERVATION:

Thereisno“holdoffdistance”stenciledorpaintedatthemanualtankgaugeontheroof.
CODEREFERENCE:Generalmaintenance/APISTD653checklistitem(C.1.5.1(d)‐checkformarker
andtabstatinghold‐offdistance).
RECOMMENDATION:Stencilorpaintthe“holdoffdistance”atthemanualtankgaugehatch.

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

g. IndependentLow‐LowLevelAlarm
OBSERVATION:Thetankisnotequippedwithanindependentlow‐lowlevelalarm.Thereisalow
levelalarmsensorinstalledonthesideofthetankshell(seephotobelow).
CODEREFERENCE:UFC4603‐460‐01Table8‐1(k)andAW78‐24‐27DrawingD.12Detail1
RECOMMENDATION:Installanindependentlow‐lowlevelarm.Thelow‐lowlevelalarmswitchshould
actuate1minbeforetheIFRpanbottomsoutwhenthepanlegsaresetatthelowposition.
h. ProductSaverTank(PST)Pump,LevelAlarmandSightGlass
OBSERVATION:TheProductSaverTank(PST)isnotequippedwithanelectricalpump,doesnothave
highlevelalarms,andisnotequippedwithasightglass.Nozzlesutilizethreadedvalvesandnoquick
connectsforfuelremoval.
CODEREFERENCE:AW78‐24‐27DrawingD.13Detail5.IAWUFC3‐460‐01Section3‐6.6.7“Mount
permanentlyinstalledpumpsonsubstantialfoundationsofreinforcedconcretedesignedin
accordancewithHydraulicInstituteStandards.”
RECOMMENDATION:Add10GPMpumpwithaClass1,Div1ratedelectricalcomponents.Consider
replacementofexistingsystemwithanewsysteminaccordancewithAW78‐24‐27.

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

i. LowSuctionPlugValve
OBSERVATION:Thelowsuctionplugvalveisnotequippedwithavalvehandle.Operationisnot
verified,butitappearsnottobefunctioning.
CODEREFERENCE:Generalmaintenance/UFC4603‐460‐01Table8‐1(u)andAPI653Checklistitems
(inspectionforleaks,corrosion,andforpropervalveoperation.
RECOMMENDATION:Replacethemissingvalvehandleandexercisethevalvetoensurepropervalve
operationorreplacethevalve.
j. Internalladder
OBSERVATION:Thereisnointernalladdertoaccessthetopofthefloatingroof.TheIFRcanonlybe
accessedfromtheunderside.(Existingstillingwellconfigurationandundersideofroofmanhole
locationshownonphotos)
CODEREFERENCE:UFC4603‐460‐01Table8‐1(h)andAW78‐24‐27DrawingD.08Detail2
RECOMMENDATION:Installtheinternalladder(inaccordancewithOSHAcriteria)fortanksof5,000
gallons(19000L)orlargerperUFC4603‐460‐01Table8‐1(h)andAW78‐24‐27DrawingD.08
Detail2

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

k. TankReceiptandIssuedonothaveTRVs
OBSERVATION:Thereceiptandissuenozzledonothavethermalreliefvales(TRVs)perAW78‐24‐27
(notesttees,CSvsSSpiping).
CODEREFERENCE:AW78‐24‐27DrawingD.10Detail4.
RECOMMENDATION:Providethermalreliefatreceipthighlevelvalveandissueisolationvalvetomeet
AW78‐24‐27DrawingD.10Detail4.
l. ProductPipingLabelMarking
OBSERVATION:Thetankpipelabelmarkingarefaded(yellowbands)nodirectionalmarking.
CODEREFERENCE:AW78‐24‐27DrawingCD.13Detailx.(refertoMIL‐STD‐161Gforcorrectfueltype)
RECOMMENDATION:Installyellowbandsandyellowproductflowdirection.

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

API 653 Out‐of‐Service Inspection Report Fort Campbell, Kentucky

APPENDIX A: ENGINEERING CALCULATIONS AND DRAWINGS

A.1BOTTOMSERVICELIFEEVALUATION
A.2SHELLSERVICELIFEEVALUATION
A.3SHELLSETTLEMENTEVALUATION
A.4ULTRASONICUTDATA
A.5CONTAINMENTLAYOUTDRAWING
A.6BOTTOMLAYOUTDRAWING
A.7SHELLLAYOUTDRAWING
A.8ROOFLAYOUTDRAWING
A.9OSHAACCESSSTRUCTUREREPORT

Where:

MRT = minimum remaining thickness at the end of the in-service period of operation, in inches.

O r = in-service interval of operation (years to next internal inspection), in years; not to exceed that allowed by 6.4.2.

t o = original plate thickness, in inches.

RT bc = minimum remaining thickness from bottom side corrosion after repairs, in inches.

Rt ip = minimum remaining thickness from internal corrosion after repairs, in inches.

StP r = maximum rate of corrosion not repaired on the top side, in inches per year. StP r =

0 for coated areas of the bottom. The expected service life of the coating must equal or exceed O r to use StP r = 0.

UP r = maximum rate of corrosion on the bottom, in inches per year. To calculate the corrosion rate, use the minimum remaining thicknesses after repairs. Assume a linear rate based on the age of the tanks. UP r = 0 for areas that have effective cathodic protection.

MRT

(inches)

0.1

0.05

0.05

Note: For areas of a bottom that have been scanned by the magnetic flux leakage (or exclusion) process, and do not have effective cathodic protection, the thickness used for calculating UPr must be the lesser of the MFL threshold or the minimum thickness of corrosion areas that are not repaired. The MFL threshold is defined as the minimum remaining thickness to be detected in the areas inspected. The MFL unit used for scanning the bottom does not have a threshold set point. This unit visually displays all anomalies.