Attachment J.2 - API Post Repair-CMB-FAC 7205-FY19.pdf

PDF 5 MB Posted

Attached to
SP-POL-CMP-INSPECT-FY24-CMB Federal contract opportunity
Solicitation number
W9128F24Q0017
Issued by
Department of the Army Corps of Engineers Engineering District Omaha

About this file

This document is an API 653 inspection report for storage Tank A7205 located at Fort Campbell, Kentucky. The report details 23 repairs and upgrades completed on the tank, including replacing the grounding system, containment sealant, water draw-off piping, tank stairs, manways, vents, internal access ladder, perimeter handrails, internal floating roof seals, tank coatings, internal steel plates, level alarm systems, roof manway, scaffold supports, stilling wells, thermal relief piping and connections, slip-on flanges, plug valve, internal piping, pipeline coatings, hardware, and data plate. Inspection intervals are also provided, with the next in-service inspection scheduled for 2024 and out-of-service inspection for 2039. This report determines the tank is suitable for return to service following the repairs.

The related federal contract opportunity is solicitation number W9128F24Q0017 for SP-POL-CMP-INSPECT-FY24-CMB with the Department of the Army Corps of Engineers Omaha District for petroleum, oils and lubricants inspection and compliance services.

View the file

Other files for this federal contract opportunity

Other files attached to SP-POL-CMP-INSPECT-FY24-CMB, newest first.
File Type Posted
Attachment J.3 -API Post Repair-FAC A6624-FY19.pdf PDF
Attachment A - General Installation Security Requirements.docx DOCX document
Attachment J.1 - FAC 7205 API 653 OOS Insp FY17.pdf PDF
Attachment D - Monthly Contractors Progress Management and Status Report.xlsx XLSX spreadsheet
Attachment I - API External Inspection Report Template.docx DOCX document
Attachment J.4 - FAC A6624 API 653 OOS Insp FY17.pdf PDF
W9128F24Q0017 Solicitation.pdf PDF
Attachment B - Ft. Campbell Tank Info.xlsx XLSX spreadsheet
Attachment C - Tank Data Sheet.xlsx XLSX spreadsheet

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

US Army Corps of Engineers Omaha District

API 653 Repair Inspection Report - Final

Fort Campbell Facility Number 7205 (Oasis Rapid Fuel)

Tank Number A7205

US Army Corps of Engineers Center of Expertise for Petroleum, Oils and Lubricants

(USACE POL-MCX)

14 June 2019

API 653 Repair Inspection Tank A7205 Fort Campbell, KY

Table of Contents

ACRONYMS AND ABBREVIATIONS

SUITABILITY FOR SERVICE MEMORANDUM

TANK REPAIRS

1. Exothermically Welded Connections to the Grounding Lugs

2. Containment Area Sealant

3. Water Draw-Off System

4. Tank Stairs

5. 24” Manway

6. Roof Vents

7. Internal Access Ladder

8. Roof Perimeter Handrail

9. Internal Floating Roof Seals

10. Tank Coatings

11. Internal Steel Plates

12. High and High-High Level Alarm System

13. Low and Low-Low Level Alarms

14. Roof Manway

15. Scaffold Cable Supports

16. Stilling Wells

17. Thermal Relief Piping/Threaded Connections

18. Slip-on Flanges

19. DB&B Plug Valve – Thermal Relief

20. Internal Piping

21. Pipeline Coatings

22. Carbon Steel Hardware

23. Tank Data Plate

APPENDIX A: ENGINEERING DRAWINGS

Bottom Thickness

Bottom Critical Zone Thickness

ACRONYMS AND ABBREVIATIONS

API

ASME

ASNT

ATG

American Petroleum Institute

American Society of Mechanical Engineers

American Society of Non-Destructive Testing

Automatic Tank Gauge

BBL Barrel

CFR Code of Federal Regulations

CP Cathodic Protection

DFT Dry Film Thickness

HLA High Level Alarm

HLCS High Level Control Shutoff

HHLA High-High Level Alarm

LLA Low Level Alarm

LLLA Low-Low Level Alarm

MFL Magnetic Flux Leakage

MT Magnetic Particle Testing

NACE National Association of Corrosion Engineers

NDT Non-Destructive Testing

NFPA National Fire Protection Association

PSI Pounds per Square Inch

PT Penetrant Testing

P/V Pressure/Vacuum

RP Recommended Practice

PST Product Saver Tank

RT Radiography Testing

TML Thickness Measurement Location

TRV Thermal Relief Valve

UFC Unified Facilities Criteria

UFGS Unified Facilities Guide Specifications

ULS Ultra-Low Sulfur

UT Ultrasonic Testing

VT Visual Testing

SUITABILITY FOR SERVICE

MEMORANDUM

STORAGE TANK NO. A2705

Out-of-Service API 653 Tank Inspection and Repair

Contract No. W9128F-14-R-0048-RFP-63 Fort Campbell, KY

Tank A7205 was inspected 14 June 2019. An API 653 Repair Inspection was performed by Darrin Laughlin.

This tank report is an Appendix to the original API 653 tank report.

The tank is in suitable condition for return to service.

Mandatory Repairs

No mandatory repairs were required.

Other Repairs and Maintenance

1. Tank grounding repaired/upgraded

2. Containment area sealant repaired/replaced

3. Water draw-off system replaced

4. Tank stairs upgraded

5. Shell manway repaired (davit arm)

6. Roof vents replaced

7. Internal access ladder installed

8. Perimeter roof handrail installed

9. IFR repaired

10. Tank coatings repaired

11. Internal steel plates removed

12. High and High-High Level Alarms installed

13. Low and Low-Low Level Alarms replaced

14. Roof manway replaced

15. Scaffold cable supports installed on fixed roof

16. Stilling wells replaced

17. Thermal relief piping and threaded connections replaced

18. Slip-on flanged replaced

19. DB&B plug valve installed in thermal relief

20. Interior piping repaired/replaced

21. Pipeline coatings repaired

22. Carbon steel hardware replaced with stainless

23. New data plate provided g6pmxrjw Sticky Note Please change to "On this date DD MMM YY, the tank is in suitable condition for return to service."

G6CDQASM

Sticky Note CP system repair?

Low suction piping?

Add these to the list if they were completed.

Inspection Intervals

The next In-Service Inspection should occur in 5 years, and the next In-Service Inspection with UT thickness measurements should occur in 13 years in accordance with API 653.

The next Out-of-Service inspection should occur in 20 years.

This storage tank suitability for service evaluation has been completed in accordance with the requirements of API Standard 653, 5th Edition, Addendum 1, April 2018.

Prepared by:

Darrin A Laughlin US Tank Inspection Manager AmSpec API 653 Certified Inspector No. 29230

G6CDQASM

Provide dates for next inspections

TANK REPAIRS

1. Exothermically Welded Connections to the Grounding Lugs

OBSERVATION: New grounding lugs were installed

2. Containment Area Sealant

OBSERVATION: Sealant throughout containment was repaired/replaced

3. Water Draw-Off System

OBSERVATION: New water draw off piping was installed in a new 2” nozzle

4. Tank Stairs

OBSERVATION: Width of stairs was increased around high and high-high alarms

5. 24” Manway

OBSERVATION: New davit arm installed on 24” manway

6. Roof Vents

OBSERVATION: Perimeter roof vents were replaced

G6CDQASM

Is this a galvanized bolt and hook as per the DoD Standard AW 78-24-27?

7. Internal Access Ladder

OBSERVATION: A new internal access ladder was installed

8. Roof Perimeter Handrail

OBSERVATION: A new perimeter handrail was installed

Are these IFR hatch bolts stainless per the RFP?

9. Internal Floating Roof Seals

OBSERVATION: New primary and secondary wiper seals were installed. New seals were also installed on all IFR penetrations.

10. Tank Coatings

OBSERVATION: Damaged interior coatings were repaired, and the exterior was recoated

11. Internal Steel Plates

OBSERVATION: Unnecessary internal steel plates were removed

12. High and High-High Level Alarm System

OBSERVATION: New high and high-high level systems were installed

Were the coatings under the column base plate repaired per SOW item 1.2.1.2.21.c? Does not appear so.

13. Low and Low-Low Level Alarms

OBSERVATION: New low and low-low level systems were installed

14. Roof Manway

OBSERVATION: Circular roof manway was removed and patched, and a rectangular hatch was installed

15. Scaffold Cable Supports

OBSERVATION: Scaffold cable supports were installed on the tank roof

16. Stilling Wells

OBSERVATION: Carbon steel stilling wells were replaced with aluminum

Verify all roof flange bolts are stainless. Blind flanges for future SPAWAR work need to be stainless to allow easy removal at a later date.

17. Thermal Relief Piping/Threaded Connections

OBSERVATION: New piping was installed with socket welded connections

18. Slip-on Flanges

OBSERVATION: Slip-on flanges were replaced with weld-neck flanges

19. DB&B Plug Valve – Thermal Relief

OBSERVATION: DB&B plug valve was installed in thermal relief piping

20. Internal Piping

OBSERVATION: Internal piping was replaced

This repair should have been repairing the thermal relief system on the DB&B plug valve, not installing DB&B plug valve in thermal relief piping. Provide photo showing the completed work and correct heading if this was properly done.

21. Pipeline Coatings

OBSERVATION: All pipelines within the containment area were recoated

22. Carbon Steel Hardware

OBSERVATION: All carbon steel hardware was replaced with stainless steel

Issue and relief flange hardware was not specified in the RFP. Per item 1.2.1.2.25.a of the SOW "Provide and install stainless steel bolts, nuts and washers on shell manway, and all roof flanges and hatches in accordance with UFGS 33 52 43.13."

23. Tank Data Plate

OBSERVATION: A new data plate was provided for the tank

APPENDIX A: ENGINEERING DRAWINGS

Bottom Thickness The tank bottom is constructed of 11, 1/4”-thick, carbon steel plates, assumed to be A283-C. An MFL scan on the tank bottom revealed no areas of product-side or soil-side corrosion.

Bottom Critical Zone Thickness An MFL scan performed in the critical zone revealed no areas of product-side or soil-side corrosion.

Switch R10 & R11.

W9128F-14-R-0048-RFP-63-API-653-Tank-Repairs-and-Coatings-Fort-Campbell
ACRONYMS AND ABBREVIATIONS
TANK REPAIRS
1. Exothermically Welded Connections to the Grounding Lugs
2. Containment Area Sealant
3. Water Draw-Off System
4. Tank Stairs
5. 24” Manway
6. Roof Vents
7. Internal Access Ladder
8. Roof Perimeter Handrail
9. Internal Floating Roof Seals
10. Tank Coatings
11. Internal Steel Plates
12. High and High-High Level Alarm System
13. Low and Low-Low Level Alarms
14. Roof Manway
15. Scaffold Cable Supports
16. Stilling Wells
17. Thermal Relief Piping/Threaded Connections
18. Slip-on Flanges
19. DB&B Plug Valve – Thermal Relief
20. Internal Piping
21. Pipeline Coatings
22. Carbon Steel Hardware
23. Tank Data Plate
APPENDIX A: ENGINEERING DRAWINGS
Bottom Thickness
Bottom Critical Zone Thickness
Drawing1 Layout1 (1)
Drawing1 Layout2 (1)
Drawing1 Layout3 (1)