Attachment J.22 Construction Documents.pdf
PDF 29 MB Posted
- Solicitation number
- Not on record
- Issued by
- District of Columbia Government
About this file
The file is a comprehensive set of construction documents for the District of Columbia Courts' Heating System Upgrade project located at 500 Indiana Avenue NW, Washington, DC. The detailed design package includes architectural, structural, mechanical, electrical, and plumbing drawings for converting the existing steam water system to a new on-site gas boiler heating system in Mechanical Room 1000.
Key technical specifications include installing new boilers (six Fulton Endura EXE condensing boilers), associated pumps, exhaust fans, piping systems, and control infrastructure across multiple building levels from the parking level to the roof. The project involves phased construction with multiple optional work stages, including building shaft installation, mechanical equipment replacement, and comprehensive systems upgrades. The documents provide detailed engineering drawings, equipment schedules, riser diagrams, demolition plans, and technical specifications for electrical, mechanical, and plumbing systems, with an issued date of July 3, 2025 and marked as "Issue for Bid".
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P lo t D at e:
ISSUE DATE:
500 Indiana Ave NW, Washington, DC 20001
VOLUME I OF I
ISSUED FOR:
ISSUE FOR BID
1700 NEW YORK AVENUE NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 smithgroup.com
7/ 3/
:4
7:
A M
DC TO25 Heating System Upgrade 500 Indiana Ave NW, Washington, DC 20001
7/3/2025
District of Columbia Courts
15749.000
THE FOLLOWING PROJECT GENERAL NOTES APPLY TO THE
ENTIRE DRAWING SET AND ARE NOT SPECIFIC TO ANY ONE
DISCIPLINE, UNLESS OTHERWISE NOTED:
1. THE DRAWING SET AND SPECIFICATIONS (PROJECT
MANUAL) ARE COMPLEMENTARY AND ESTABLISH
DETAILED MINIMUM REQUIREMENTS FOR THE DESIGN AND
CONSTRUCTION OF THE PROJECT.
2. THE DRAWING SET CONSISTS OF ALL SHEETS LISTED BY
THE SHEET INDEX. THE WORK DESCRIBED BY THE
DRAWINGS OF ANY ONE DISCIPLINE MAY BE AFFECTED BY
THE WORK DESCRIBED ON DRAWINGS OF ANOTHER
DISCIPLINE AND MAY REQUIRE REFERENCE TO DRAWINGS
OF ANOTHER DISCIPLINE. AS SUCH, DO NOT DISTRIBUTE
OR UTILIZE PARTIAL SETS OF DRAWINGS.
3. COLUMN GRID LINES IDENTIFIED BY A LETTER
DESIGNATION ARE PARALLEL, UNLESS OTHERWISE
NOTED. COLUMN GRID LINES IDENTIFIED BY A NUMBER
DESIGNATION ARE PARALLEL AND ARE PERPENDICULAR
TO THOSE WITH LETTER DESIGNATIONS, UNLESS
OTHERWISE NOTED.
4. DISCIPLINE GENERAL NOTES, SYMBOLS AND DEFINITIONS
APPLICABLE TO EACH DISCIPLINE'S DRAWINGS MAY BE
FOUND AT THE FRONT OF EACH DISCIPLINE'S PORTION OF
THE DRAWING SET AND ARE LISTED IN THE SHEET INDEX.
5. UNLESS INDICATED OTHERWISE, THE 'ARCHITECTURAL'
SERIES DRAWINGS TAKE PRECEDENCE FOR THE FINISHED
APPEARANCE AND LOCATION OF ALL EXPOSED ELEMENTS
OF THE WORK OF ALL TRADES, INCLUDING THAT WORK
WHICH IS ILLUSTRATED PRIMARILY ON DRAWINGS OF
OTHER DISCIPLINES.
6. THE DRAWINGS MAY MAKE REFERENCE TO OR
ILLUSTRATE ITEMS WHICH ARE NOT PART OF THE WORK
OF THE CONTRACT. THESE "NOT IN CONTRACT" ITEMS AS
INDICATED ARE REFERENCED OR ILLUSTRATED FOR THE
CONTRACTOR'S REFERENCE, INFORMATION AND
COORDINATION ONLY.
7. EXISTING CONDITIONS, IF SHOWN, ARE FROM AVAILABLE
RECORD DRAWINGS AND/OR VISUAL FIELD SURVEYS.
VERIFY ACTUAL EXISTING CONDITIONS AT THE SITE PRIOR
TO SUBMITTING A BID. NOTIFY THE ARCHITECT, IN
WRITING AND PRIOR TO SUBMITTING A BID, OF ANY
DISCREPANCIES.
8. TAKE PRECAUTIONS TO MAINTAIN AND PROTECT NEW
WORK AS WELL AS EXISTING SYSTEMS AND ELEMENTS, IF
ANY, WHICH ARE TO REMAIN OR BE SALVAGED. ANY
DAMAGE TO SUCH SYSTEMS AND ELEMENTS SHALL BE
IMMEDIATELY REPAIRED IN A MANNER ACCEPTABLE TO
THE ARCHITECT. IF SATISFACTORY REPAIRS CANNOT BE
MADE, REPLACE SYSTEMS AND ELEMENTS WITH "LIKE
NEW" QUALITY ACCEPTABLE TO THE ARCHITECT, ALL AT
NO ADDITIONAL COST.
9. ALL PARTS OF THE WORK, INCLUDING BUT NOT
LIMITED TO MATERIALS, METHODS, OR ASSEMBLIES,
MUST COMPLY WITH THE REQUIREMENTS OF THE
GOVERNING CODES AND REGULATIONS OF ALL
FEDERAL, STATE AND LOCAL AUTHORITIES HAVING
JURISDICTION OVER THE PROJECT, AS WELL AS
THOSE GREATER REQUIREMENTS INDICATED BY THE
CONTRACT DOCUMENTS. NO PART OF THE CONTRACT
DOCUMENTS MAY BE CONSTRUED TO REQUIRE OR
ALLOW WORK CONTRARY TO A GOVERNING CODE OR
REGULATION.
10. IDENTIFY AND NOTIFY THE ARCHITECT OF CONFLICTS
BETWEEN THE WORK OF DIFFERENT PARTIES AT THE
EARLIEST POSSIBLE DATE SO AS TO ALLOW
REASONABLE AND ADEQUATE TIME FOR THE
CONFLICT TO BE RESOLVED WITHOUT DELAYING THE
WORK. ALL DEVIATIONS FROM THE CONTRACT
DOCUMENTS MUST BE APPROVED IN ADVANCE BY THE
ARCHITECT AND OWNER.
11. REVIEW AND COORDINATE THE WORK OF ALL OTHER
PARTIES PERFORMING WORK AT THE PROJECT,
INCLUDING BUT NOT LIMITED TO, DELEGATED DESIGN
ENTITIES, TRADES AND SUPPLIERS WITH THE
REQUIREMENTS OF THE CONTRACT DOCUMENTS
BEFORE COMMENCING CONSTRUCTION, AND ASSURE
THAT ALL PARTIES ARE AWARE OF ALL
REQUIREMENTS, REGARDLESS OF WHERE THE
REQUIREMENTS OCCUR IN THE CONTRACT
DOCUMENTS, WHICH MIGHT AFFECT THE WORK OF
THAT PARTY.
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
SEALS AND SIGNATURES
ISSUED FOR REV DATE
1700 NEW YORK AVENUE NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e:
Mechanical Room 1000 Heating System Upgrade 500 Indiana Avenue N.W.
Washington, DC 20001
7/ 3/
:4
7:
A M
PROJECT SHEET INDEX
G0.1
15749.000
S T
A R
T S he et
SHEET LIST
SHEET
NUMBER SHEET NAME
GENERAL
G0.0 PROJECT COVER SHEET
G0.1 PROJECT SHEET INDEX
G1.1 ARCH OPTION PLANS
G1.2 HVAC OPTION PLANS
G1.3 HVAC OPTION PLANS
G1.4 ELECTRICAL BASE PLAN
G1.5 ELECTRICAL OPTION PLAN
G1.6 ELECTRICAL OPTION PLAN
G1.7 PLUMBING DRAINAGE, WASTE & VENT OPTION PLAN
G1.8 PLUMBING WATER OPTION PLAN
G1.9 PLUMBING WATER OPTION PLAN
G1.10 PLUMBING GAS OPTION PLAN
STRUCTURAL
S0.1 STRUCTURAL GENERAL NOTES
S1.1 STRUCTURAL FRAMING PART PLANS
S1.2 STRUCTURAL FRAMING PART PLANS
S5.1 STRUCTURAL TYPICAL DETAILS
ARCHITECTURAL
A0.1 ARCHITECTURAL ABBREVIATIONS AND SYMBOLS
A2.1 OVERALL FLOOR PLANS
A2.2 PARKING LVL & C ST MECH ROOM LVL PLAN
A2.3 PARKING LVL & C ST MECH ROOM LVL PLAN
A7.1 ENLARGED FLOOR PLAN - PARKING LEVEL
A7.2 ENLARGED FLOOR PLANS - C STREET LEVEL
A7.3 ENLARGED FLOOR PLANS - JOHN MARSHALL LEVEL
A7.4 ENLARGED FLOOR PLANS - INDIANA LEVEL
A7.5 ENLARGED FLOOR PLANS - SECOND LEVEL
A7.6 ENLARGED FLOOR PLANS - THIRD LEVEL
A7.7 ENLARGED FLOOR PLANS - FOURTH LEVEL
A7.8 ENLARGED FLOOR PLANS - FIFTH LEVEL
A7.9 ENLARGED FLOOR PLANS - ROOF PLANS
A9.1 SHAFT SECTION DETAILS
A9.2 DOOR SCHEDULE & PARTITION DETAILS
FIRE PROTECTION
FP0.1 FIRE PROTECTION ABBREVIATIONS AND SYMBOLS
FPD2.1 PARKING LEVEL FIRE PROTECTION DEMOLITION PLAN
FPD2.2 C STREET THROUGH 5TH LEVEL FIRE PROTECTION DEMOLITION PLANS
FP2.1 PARKING LEVEL FIRE PROTECTION PLAN
FP2.2 C STREET THROUGH 5TH LEVEL FIRE PROTECTION PLANS
MECHANICAL
M0.1 MECHANICAL ABBREVIATIONS AND SYMBOL
MD2.1 PARKING LEVEL FLOOR PLAN - MECHANICAL DEMOLITION
M2.1 PARKING LEVEL FLOOR PLAN - HVAC NEW WORK
M2.2 SIXTH LEVEL FLOOR PLAN - HVAC NEW WORK
M3.1 PARKING LEVEL FLOOR PLAN WEST - HVAC PIPING NEW WORK
M3.2 PARKING LEVEL FLOOR PLAN EAST - HVAC PIPING NEW WORK
M3.3 PARKING LEVEL FLOOR PLAN NORTH - HVAC PIPING NEW WORK
M3.4 SIXTH LEVEL FLOOR PLAN - PIPING NEW WORK
M4.1 PARKING LEVEL BOILER ROOM - ENLARGED VIEW
M4.2 MECHANICAL SECTIONS
M4.3 AHU NEW WORK - HVAC - ENLARGED VIEW
M4.4 C STREET LEVEL PLAN -ENLARGED VIEW
M4.5 JOHN MARSHALL LEVEL PLAN - ENLARGED VIEW
M4.6 INDIANA AVENUE LEVEL PLAN - ENLARGED VIEW
M4.7 SECOND LEVEL FLOOR PLAN -ENLARGED VIEW
M4.8 THIRD LEVEL FLOOR PLAN -ENLARGED VIEW
M4.9 FOURTH LEVEL FLOOR PLAN - ENLARGED VIEW
M4.10 FIFTH LEVEL FLOOR PLAN -ENLARGED VIEW
M4.11 SIXTH LEVEL FLOOR PLAN -ENLARGED VIEW
M5.1 EXISTING HEATING HOT WATER SYSTEM PIPING DIAGRAM
M5.2 NEW HEATING HOT WATER SYSTEM PIPING DIAGRAM
M6.1 MECHANICAL DETAILS
M6.2 MECHANICAL DETAILS
M7.1 MECHANICAL SCHEDULES
M8.1 MECHANICAL CONTROLS - LEGEND
M8.2 MECHANICAL CONTROLS - HEATING HOT WATER CONTROLS DIAGRAM - 1/2
M8.3 MECHANICAL CONTROLS - HEATING HOT WATER CONTROLS DIAGRAM - 2/2
M8.4 MECHANICAL CONTROLS - HEATING HOT WATER POINTS LIST
M8.5 MECHANICAL CONTROLS - HEATING HOT WATER SEQUENCE OF OPERATIONS
M8.6 MECHANICAL CONTROLS - FAN CONTROLS
ELECTRICAL
E0.1 ELECTRICAL SYMBOLS & CIRCUIT SIZING SCHEDULES
ED2.1 PARKING LEVEL THROUGH FIFTH LEVEL FLOOR PLANS - ELECTRICAL DEMOLITION
E2.1 PARKING LEVEL FLOOR PLAN - ELECTRICAL NEW WORK
E2.2 C ST LEVEL THROUGH SIXTH LEVEL FLOOR PLANS - ELECTRICAL NEW WORK
E5.1 ELECTRICAL PARTIAL RISER DIAGRAM, MECHANICAL EQUIPMENT SCHEDULE, AND LIGHTING FIXTURE SCHEDULE
E6.1 ELECTRICAL DETAILS
E7.1 ELECTRICAL PANELBOARD SCHEDULES
E7.2 LIGHTING POWER DENSITY CALCULATIONS
PLUMBING
P1.0 PLUMBING LEGENDS, SYMBOLS & ABBREVIATIONS
PD2.1 PLUMBING DRAINAGE, WASTE & VENT DEMOLITION PLAN
PD3.1 PLUMBING WATER DEMOLITION PLAN
P2.1 PLUMBING DRAINAGE, WASTE & VENT PLAN
P3.1 PLUMBING WATER PLAN
P4.1 PLUMBING NATURAL GAS PLAN
P5.1 PLUMBING NATURAL GAS RISER DIAGRAM
P6.1 PLUMBING DETAILS I
P6.2 PLUMBING DETAILS II
P7.1 PLUMBING SCHEDULES
PROJECT GENERAL NOTES
VICINITY MAP
PROJECT TEAM
OWNER / CLIENT:
DC COURTS
500 INDIANA AVE NW
WASHINGTON DC 20001
202 879 1010
CONTACT:
ENOR WILLIAMS
enor.williams@dcsc.gov
SMITHGROUP
1700 NEW YORK AVE. NW
WASHINGTON / DC / 20006
202 842 2100
WWW.SMITHGROUP.COM
CONTACT
IONEL PETRUS
Ionel.Petrus@smithgroup.com 202 974 0856
ARCHITECT / MEP ENGINEER:
STRUCTURAL ENGINEER:
TYlin
5301 SHAWNEE RD
SUITE 400
ALEXANDRIA, VA 22312
800 837 9779 www.tylin.com
CONTACT
MARGARET COWIE
margaret.cowie@tylin.com 202.333.6230
ISSUE FOR BID 03 JULY 2025
SAW CUT EXISTING CONCRETE SLAB
FOR NEW WASTE PIPING INSTALLATION
AT PARKING LVL 1; REPAIR SLAB TO
MATCH EXISTING.
POST-APPLIED WATERPROOFING PIPE
PENETRATION AFTER NEW GAS PIPE
INSTALLATION AT C ST MECHANICAL
ROOM LEVEL
BUILD NEW FLUE SHAFT; THIS INCLUDES THE DEMOLITION AND RE-CONSTRUCTION OF ANY
AFFECTED SPACES WHICH INCORPORATE BUT ARE NOT LIMITED TO FINISHED FLOOR, GWB
WALLS, BASEBOARDS, DOORS, HARDWARE & CEILINGS. THE SCOPE OF WORK FOR THE FLUE
SHAFT GOES FROM C ST LVL TO THE ROOF.
BUILD NEW FLUE SHAFT; THIS INCLUDES THE DEMOLITION AND RE-CONSTRUCTION OF ANY
AFFECTED SPACES WHICH INCORPORATE BUT ARE NOT LIMITED TO FINISHED FLOOR, GWB
WALLS, BASEBOARDS, DOORS, HARDWARE & CEILINGS. THE SCOPE OF WORK FOR THE FLUE
SHAFT GOES FROM C ST LVL TO THE ROOF.
BUILD NEW FLUE SHAFT; THIS INCLUDES THE DEMOLITION AND RE-CONSTRUCTION OF ANY
AFFECTED SPACES WHICH INCORPORATE BUT ARE NOT LIMITED TO FINISHED FLOOR, GWB
WALLS, BASEBOARDS, DOORS, HARDWARE & CEILINGS. THE SCOPE OF WORK FOR THE FLUE
SHAFT GOES FROM C ST LVL TO THE ROOF.
BUILD NEW FLUE SHAFT; THIS INCLUDES THE DEMOLITION AND RE-CONSTRUCTION OF ANY
AFFECTED SPACES WHICH INCORPORATE BUT ARE NOT LIMITED TO FINISHED FLOOR, GWB
WALLS, BASEBOARDS, DOORS, HARDWARE & CEILINGS. THE SCOPE OF WORK FOR THE FLUE
SHAFT GOES FROM C ST LVL TO THE ROOF.
BUILD NEW FLUE SHAFT; THIS INCLUDES THE DEMOLITION AND RE-CONSTRUCTION OF ANY
AFFECTED SPACES WHICH INCORPORATE BUT ARE NOT LIMITED TO FINISHED FLOOR, GWB
WALLS, BASEBOARDS, DOORS, HARDWARE & CEILINGS. THE SCOPE OF WORK FOR THE FLUE
SHAFT GOES FROM C ST LVL TO THE ROOF.
BUILD NEW FLUE SHAFT; THIS INCLUDES THE DEMOLITION AND RE-CONSTRUCTION OF ANY
AFFECTED SPACES WHICH INCORPORATE BUT ARE NOT LIMITED TO FINISHED FLOOR, GWB
WALLS, BASEBOARDS, DOORS, HARDWARE & CEILINGS. THE SCOPE OF WORK FOR THE FLUE
SHAFT GOES FROM C ST LVL TO THE ROOF.
BUILD NEW FLUE SHAFT; THIS INCLUDES THE DEMOLITION AND RE-CONSTRUCTION OF ANY
AFFECTED SPACES WHICH INCORPORATE BUT ARE NOT LIMITED TO FINISHED FLOOR, GWB
WALLS, BASEBOARDS, DOORS, HARDWARE & CEILINGS. THE SCOPE OF WORK FOR THE FLUE
SHAFT GOES FROM C ST LVL TO THE ROOF.
PROVIDE STACK FLASHING AND POST APPLIED WATERPROOFING AT MECH FLUE AND PIPE
PENETRATIONS.
BUILD NEW 8” CMU WALL ENCLOSURE
AT NEW BOILER ROOM IN PARKING 1
LVL. WALL TO BE FINISHED TO MATCH
EXISTING.
INSTALL (2) 8’-0”X8’-0” ELECTRIC
OPERATED OVERHEAD DOORS FOR
BOILER ROOM SERVICE ACCESS.
INSTALL 36”X84” HM DOOR AT BOILER
ROOM. DOOR TO BE FINISHED TO
MATCH EXISTING.
CAST IN PLACE 4” H CONCRETE PADS
FOR MECHANICAL EQUIPMENT
INFILL FORMER COILING DOOR
OPENING WITH CMU AND MATCH WITH
ADJACENT CONSTRUCTION. WALL TO
BE FINISHED TO MATCH EXISTING.
CAST IN PLACE 4” H CONCRETE PADS
FOR MECHANICAL EQUIPMENT
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
SEALS AND SIGNATURES
ISSUED FOR REV DATE
1700 NEW YORK AVENUE NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e:
Mechanical Room 1000 Heating System Upgrade 500 Indiana Avenue N.W.
Washington, DC 20001
7/ 3/
:4
7:
A M
ARCH OPTION PLANS
G1.1
15749.000
A ut ho r
SCALE: 1" = 50'-0"
PARKING LVL 1 - BASE
SCALE: 1" = 50'-0"
C STREET LVL - BASE
SCALE: 1" = 50'-0"
JOHN MARSHALL LVL - BASE
SCALE: 1" = 50'-0"
INDIANA AVE LVL - BASE
SCALE: 1" = 50'-0"
2ND LVL - BASE
SCALE: 1" = 50'-0"
3RD LVL - BASE
SCALE: 1" = 50'-0"
4TH LVL - BASE
SCALE: 1" = 50'-0"
5TH LVL - BASE
SCALE: 1" = 50'-0"
ROOF PLAN - BASE
BASE
SCALE: 1" = 50'-0"
PARKING LVL 1 - OPTION 1
SCALE: 1" = 50'-0"
PARKING LVL 1 - OPTION 2
OPTION 1
OPTION 2
H.8
H.7
H.4
H.3
H.1
H.8
H.7
H.4
H.3
H.1
H.8
H.7
H.4
H.3
H.1
H.8
H.7
H.4
H.3
H.1
H
J
K
H.8
H.7
H.4H.3
H.1
G.4
5.7
H.8
H.7
H.4
H.3
H.1
H.8
H.7
H.4
H.3
H.1
H
J
K
H.8
H.7
H.4H.3
H.1
G.4
5.7
H.8
H.7
H.4
H.3
H.1
H.8
H.7
H.4
H.3
H.1
H.8
H.7
H.4
H.3
H.1
NORTH
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
1700 NEW YORK AVENUE NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e
Mechanical Room 1000 Heating System Upgrade 500 Indiana Avenue N.W.
Washington, DC 20001
7/ 3/ 2:
:4 P M
HVAC OPTION PLANS
G1.2
15749.000
A ut h or
SCALE: 1/8" = 1'-0"
TO-25 BASE- SECOND LEVEL
SCALE: 1/8" = 1'-0"
TO-25 BASE - SIXTH LEVEL
SCALE: 1/8" = 1'-0"
TO-25 BASE - THIRD LEVEL
SCALE: 1/8" = 1'-0"
TO-25 BASE - FIFTH LEVEL
SCALE: 1/8" = 1'-0"
TO-25 OPTION 1
SCALE: 1/8" = 1'-0"
TO-25 BASE - C STREET LEVEL
SCALE: 1/8" = 1'-0"
TO-25 BASE - FOURTH LEVEL
BASE: BUILD NEW FLUE SHAFT FROM PARKING LEVEL TO SIXTH LEVEL ROOF PENETRATION.
DEMOLISH AND REBUILDING CEILINGS IN THE AFFECTED SPACES ACROSS ALL FLOORS.
REROUTE EXISTING CONDITIONS DUCTWORK AND PIPING TO CONTINUE SERVING ADJACENT SPACES.
OPTION 1: PURCHASE AND INSTALL BOILERS AND PUMPS (EQUIPMENT ONLY).
EXISTING HYDRONIC PIPING AND STEAM PIPING TO REMAIN.
EXISTING HEATING HOT WATER SYSTEMS TO REMAIN AND TO BE FULLY OPERATIONAL.
OPTION 2: INSTALL ALL NEW DIV 23 PROJECT INFASTRUCTURE, INSTALL ALL NEW DIV 22 PIPING.
SCALE: 1/8" = 1'-0"
TO-25 OPTION 2
SCALE: 1/8" = 1'-0"
TO-25 - JOHN MARSHALL LEVEL
SCALE: 1/8" = 1'-0"
TO-25 BASE - INDIANA AVENUE LEVEL
SCALE: 1/8" = 1'-0"
TO-25 BASE - PARKING LEVEL
3 5 6
H
I
J
K
H.8
H.7
H.4H.3
H.1
G.4
5.7 6.2
NORTH
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
1700 NEW YORK AVENUE NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e
Mechanical Room 1000 Heating System Upgrade 500 Indiana Avenue N.W.
Washington, DC 20001
7/ 3/ 2:
:0 P M
HVAC OPTION PLANS
G1.3
15749.000
A ut h or
SCALE: 1/8" = 1'-0"
TO-25 OPTION 3
OPTION 3: DEMOLISH AND REMOVE EXISTING DIV 23, DIV 26, AND DIV 22 INFRASTRUCTURE.
OS OS OS
V
H.8
H.7
H.4
H.3
H.8
H.7
H.4
H.3
H.8
H.7
H.4
H.3
H.8
H.7
H.4
H.3
H.8
H.7
H.4
H.3
H.8
H.7
H.4
H.3
H.8
H.7
H.4
H.3
H.8
H.7
H.4
H.3
G
G
G
G
G
NORTH
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
1700 NEW YORK AVENUE NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e
Mechanical Room 1000 Heating System Upgrade 500 Indiana Avenue N.W.
Washington, DC 20001
7/ 3/ 2:
:1 P M
ELECTRICAL BASE PLAN
G1.4
15749.000
A ut h or
ISSUE FOR BID 03 JULY 2025
03 JULY 2025
BASE:
1. Remove existing lighting fixtures, occupancy sensors, receptacles, and switches that are to be demolished.
2. Disconnect, and reinstall existing lighting fixtures and receptacles that need to be relocated.
3. Purchase and install new lighting switches.
4. Purchase and install new electrical conduits inside of the shaft.
5. Purchase and install disconnect switches for the exhaust fans on the roof.
6. Purchase and install lightning protection system equipment and tie into existing system.
SCALE: 1/4" = 1'-0"
TO-25 BASE - C STREET LEVEL ELECTRICAL POWER AND LIGHTING PLAN
SCALE: 1/4" = 1'-0"
TO-25 BASE - JOHN MARSHALL LEVEL ELECTRICAL POWER AND LIGHTING
PLAN
SCALE: 1/4" = 1'-0"
TO-25 BASE - INDIANA AVENUE LEVEL ELECTRICAL POWER AND LIGHTING
PLAN
SCALE: 1/4" = 1'-0"
TO-25 BASE - SECOND LEVEL ELECTRICAL POWER AND LIGHTING PLAN
SCALE: 1/4" = 1'-0"
TO-25 BASE - THIRD LEVEL ELECTRICAL POWER AND LIGHTING PLAN
SCALE: 1/4" = 1'-0"
TO-25 BASE - FOURTH LEVEL ELECTRICAL POWER AND LIGHTING PLAN
SCALE: 1/4" = 1'-0"
TO-25 BASE - FIFTH LEVEL ELECTRICAL POWER AND LIGHTING PLAN
SCALE: 1/4" = 1'-0"
TO-25 BASE - SIXTH LEVEL ELECTRICAL POWER AND LIGHTING PLAN
T
T T
T T
T
T
J
T
T
T T
T T
T
TJ J J J J J
J J J J
V V
V V
VV
V
V
J
J
J
R R
J
J
JJ
2 3 5 6 7 7.8
H
I
J
K
H.8
H.7
H.4
H.3
H.1
G.4
G.2
5.7 7.1 7.3 7.6 7.9 8.8 9 9.3 10 10.3 11 12 136.2
VAULT A
C ST MECH RM C ST MECH RM
VAULT B
BOILER ROOM
MECH RM 1000
2 3 5 6 7 7.8
H
I
J
K
H.8
H.7
H.4
H.3
H.1
G.4
G.2
5.7 7.1 7.3 7.6 7.9 8.8 9 9.3 10 10.3 11 12 136.2
VAULT A
MECH RM 1000
C ST MECH RM C ST MECH RM
BOILER ROOM
VAULT B
NORTH
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
1700 NEW YORK AVENUE NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e
Mechanical Room 1000 Heating System Upgrade 500 Indiana Avenue N.W.
Washington, DC 20001
7/ 3/ 2:
:1 P M
ELECTRICAL OPTION
PLAN
G1.5
15749.000
A ut h or
03 JULY 2025
OPTION 1
1. Purchase and install new grounding and bonding, power monitoring and control, low-voltage distribution transformers, panelboards, fuses, enclosed switches, and variable-frequency drives.
2. Purchase and install new raceways and boxes for main distribution feeders.
ISSUE FOR BID 03 JULY 2025
SCALE: 3/32" = 1'-0"
TO-25 OPTION 1 - PARKING LEVEL ELECTRICAL POWER PLAN
OPTION 2
1. Purchase and install new low-voltage electrical power conductors and cables, control-voltage electrical power cables, hangers and supports, raceways and boxes, sleeves, identification, wiring devices, lighting control devices, and interior lighting.
SCALE: 3/32" = 1'-0"
TO-25 OPTION 2 - PARKING LEVEL ELECTRICAL POWER PLAN
2 3 5 6 7 7.8
H
I
J
K
H.8
H.7
H.4
H.3
H.1
G.4
G.2
5.7 7.1 7.3 7.6 7.9 8.8 9 9.3 10 10.3 11 12 136.2
BOILER ROOM
NORTH
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
1700 NEW YORK AVENUE NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e
Mechanical Room 1000 Heating System Upgrade 500 Indiana Avenue N.W.
Washington, DC 20001
7/ 3/ 2:
:1 P M
ELECTRICAL OPTION
PLAN
G1.6
15749.000
A ut h or
03 JULY 2025
OPTION 2
1. Purchase and install new low-voltage electrical power conductors and cables, control-voltage electrical power cables, hangers and supports, raceways and boxes, sleeves, identification, wiring devices, lighting control devices, and interior lighting.
OPTION 3
1. Remove existing equipment wiring, disconnect switches, occupancy sensors, and variable frequency drives that are to be demolished.
ISSUE FOR BID 03 JULY 2025
SCALE: 3/32" = 1'-0"
TO-25 OPTION 2 - PARKING LEVEL ELECTRICAL LIGHTING PLAN
3 5 6 7 7.8
I
J
K
H.8
H.7 H.4H.3
H.1
G.4
5.7 7.1 7.3 7.6 7.9 8.8 9 9.3 10 10.3 11 12 13 14 14.3 14.76.2
3 5 6 7 7.8
H
I
J
K
H.8
H.7 H.4H.3
H.1
G.4
5.7 7.1 7.3 7.6 7.9 8.8 9 9.3 10 10.3 11 12 13 14 14.3 14.76.2
C ST MECH ROOM
MECH RM 1000
C ST MECH ROOM
MECH RM 1000
MECH RM 1000
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
SEALS AND SIGNATURES
ISSUED FOR REV DATE
1700 NEW YORK AVENUE NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e
Mechanical Room 1000 Heating System Upgrade 500 Indiana Avenue N.W.
Washington, DC 20001
7/ 3/ 2:
:2 P M
PLUMBING DRAINAGE,
WASTE & VENT OPTION
PLAN
G1.7
15749.000
A ut h or
SCALE: 1/16" = 1'-0"
DRAINAGE, WASTE & VENT BASE
BASE: DEMOLISH EXISTING STORM PIPING IN NEW BOILER ROOM. SAW CUT EXISTING SLAB FOR NEW WASTE PIPING AND FLOOR DRAINS. INSTALL NEW WASTE PIPING, FLOOR DRAINS & STORM PIPING.
SCALE: 1/16" = 1'-0"
DRAINAGE, WASTE & VENT OPTION 2
OPTION 2: INSTALL CONDENSATE PIPING FOR NEW EQUIPMENT.
I
J
K
H.8
H.7 H.4H.3
H.1
G.4
5.7 7.1 7.3 7.6 7.9 8.8 9 9.3 10 10.3 11 12 13 14 14.3 14.76.2
3 5 6 7 7.8
H
I
J
K
H.8
H.7 H.4H.3
H.1
G.4
5.7 7.1 7.3 7.6 7.9 8.8 9 9.3 10 10.3 11 12 13 14 14.3 14.76.2
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
SEALS AND SIGNATURES
ISSUED FOR REV DATE
1700 NEW YORK AVENUE NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e
Mechanical Room 1000 Heating System Upgrade 500 Indiana Avenue N.W.
Washington, DC 20001
7/ 3/ 2:
:2 P M
PLUMBING WATER
OPTION PLAN
G1.8
15749.000
A ut h or
OPTION 1: PURCHASE AND INSTALL DOMESTIC HOT WATER STORAGE TANKS (EQUIPMENT ONLY).
OPTION 2: INSTALL ALL NEW DIV 22 PIPING. PURCHASE AND INSTALL REDUCED PRESSURE ZONE BACKFLOW PREVENTER.
SCALE: 1/16" = 1'-0"
WATER OPTION 1
SCALE: 1/16" = 1'-0"
WATER OPTION 2
I
J
K
H.8
H.7 H.4H.3
H.1
G.4
5.7 7.1 7.3 7.6 7.9 8.8 9 9.3 10 10.3 11 12 13 14 14.3 14.76.2
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
SEALS AND SIGNATURES
ISSUED FOR REV DATE
1700 NEW YORK AVENUE NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e
Mechanical Room 1000 Heating System Upgrade 500 Indiana Avenue N.W.
Washington, DC 20001
7/ 3/ 2:
:2 P M
PLUMBING WATER
OPTION PLAN
G1.9
15749.000
A ut h or
OPTION 3: DEMOLISH AND REMOVE EXISTING DOMESTIC WATER STEAM HEAT EXCHANGERS AND CONNECTED HOT WATER PIPING.
SCALE: 1/16" = 1'-0"
WATER OPTION 3
I
J
K
H.8
H.7 H.4H.3
H.1
G.4
5.7 7.1 7.3 7.6 7.9 8.8 9 9.3 10 10.3 11 12 13 14 14.3 14.76.2
3 5 6 7 7.8
H
I
J
K
H.8
H.7 H.4H.3
H.1
G.4
5.7 7.1 7.3 7.6 7.9 8.8 9 9.3 10 10.3 11 12 13 14 14.3 14.76.2
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
SEALS AND SIGNATURES
ISSUED FOR REV DATE
1700 NEW YORK AVENUE NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e
Mechanical Room 1000 Heating System Upgrade 500 Indiana Avenue N.W.
Washington, DC 20001
7/ 3/ 2:
:3 P M
PLUMBING GAS OPTION
PLAN
G1.10
15749.000
A ut h or
BASE: ISNTALL NEW GAS SERVICE. CAP OPEN ENDS INSIDE OF BUILDING.
OPTION 2: INSTALL ALL NEW DIV 22 PIPING.
SCALE: 1/16" = 1'-0"
GAS BASE
SCALE: 1/16" = 1'-0"
GAS OPTION 2
GENERAL NOTES
1. ALL STRUCTURAL WORK SHALL BE COORDINATED WITH ARCHITECTURAL AND MECHANICAL DRAWINGS AND SHALL CONFORM TO THE PROJECT SPECIFICATIONS, INCLUDING THE 2015 INTERNATIONAL BUILDING CODE AND INTERNATIONAL EXISTING BUILDING CODE AS AMENDED BY THE 207 DCMR 12A AND 12B. THE FOLLOWING STANDARDS WERE USED AS
SPECIFIED IN THE GOVERNING BUILDING CODE:
a. ASCE 7-10 MINIMUM DESIGN LOADS (AND ASSOCIATED CRITERIA) FOR BUILDINGS AND OTHER STRUCTURES
b. ACI 318-14 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE
c. AISC 360-10 SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS
2. CONTRACTOR SHALL PROVIDE TEMPORARY SHORING, BRACING, AND SHEETING AND SHALL MAKE SAFE ALL FLOORS, ROOFS, WALLS, AND ADJACENT PROPERTY AS PROJECT CONDITIONS REQUIRE. SHORING AND SHEETING SHALL BE DESIGNED BY A REGISTERED PROFESSIONAL ENGINEER LICENSED IN THE PROJECT JURISDICTION, HIRED BY THE CONTRACTOR, WHO SHALL SUBMIT SHOP DRAWINGS AND CALCULATIONS FOR THE OWNER'S REVIEW.
3. DIMENSIONS AND ELEVATIONS OF EXISTING CONSTRUCTION GIVEN IN STRUCTURAL DRAWINGS ARE BASED ON INFORMATION CONTAINED IN VARIOUS ORIGINAL DESIGN AND CONSTRUCTION DOCUMENTS PROVIDED BY THE OWNER, AND LIMITED FIELD OBSERVATIONS AND MEASUREMENTS. THE CONTRACTOR SHALL VERIFY ALL INFORMATION PERTAINING TO EXISTING CONDITIONS BY ACTUAL MEASUREMENT AND OBSERVATION AT THE SITE. ALL DISCREPANCIES BETWEEN ACTUAL CONDITIONS AND THOSE SHOWN IN THE CONTRACT DOCUMENTS SHALL BE REPORTED TO THE ENGINEER OF RECORD FOR EVALUATION BEFORE THE AFFECTED CONSTRUCTION IS PUT IN PLACE.
4. THE CONTRACT DRAWINGS AND SPECIFICATIONS ARE COMPLEMENTARY. THESE NOTES HIGHLIGHT RATHER THAN
REPLACE THE SPECIFICATIONS CONTAINED IN THE PROJECT MANUAL.
CONCRETE
1. ALL CONCRETE WORK SHALL CONFORM TO THE FOLLOWING GOVERNING STANDARDS:
A. AMERICAN CONCRETE INSTITUTE (ACI) "BUILDING CODE REQUIREMENTS FOR CONCRETE" (ACI 318)
B. ACI COLLECTION, LATEST EDITION
C. CONCRETE REINFORCING STEEL INSTITUTE (CRSI) "MANUAL OF STANDARD PRACTICE"
2. ALL CONCRETE COMPOSITE ON METAL DECK SHALL BE LIGHT WEIGHT CONCRETE WITH A MINIMUM COMPRESSIVE
STRENGTH OF 4,000 PSI AT 28 DAYS, UNLESS OTHERWISE NOTED.
3. ALL OTHER CONCRETE SHALL BE NORMAL WEIGHT CONCRETE WITH A MINIMUM COMPRESSIVE STRENGTH OF 4,000
PSI AT 28 DAYS, UNLESS OTHERWISE NOTED.
4. CONTRACTOR SHALL SUBMIT A PROJECT-SPECIFIC SIGNED AND SEALED CONCRETE MIX DESIGN FOR EACH CONCRETE TYPE SPECIFIED IN THE CONTRACT DOCUMENTS. WHERE 033000 SPECIFICATIONS HAVE BEEN INCLUDED IN THE CONTRACT DOCUMENTS, REFER TO THAT SPECIFICATION SECTION FOR BALANCE OF MIX DESIGN
REQUIREMENTS (AGGREGATES, ADMIXTURES, W/C RATIO, AIR CONTENT, ETC.)
5. REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A615, GRADE 60 OR A775 EPOXY COATED WHEN CALLED OUT ON PLAN. REINFORCING STEEL SHALL BE DETAILED ACCORDING TO THE ACI "DETAILS AND
DETAILING OF REINFORCEMENT" (ACI 315).
6. REINFORCING STEEL TO BE WELDED TO CONFORM TO ASTM A706 GRADE 60.
7. WELDED WIRE REINFORCEMENT (W.W.R.) SHALL CONFORM TO ASTM A1064, WITH A MINIMUM YIELD STRENGTH OF
65,000 PSI.
8. COORDINATE SIZE AND LOCATION OF ALL OPENINGS AND PIPE SLEEVES WITH ALL OTHER DISCIPLINES. MINIMUM
CONCRETE BETWEEN SLEEVES SHALL BE 6".
9. GENERAL CONTRACTOR SHALL PROVIDE COORDINATED MEP TRADE SUBMITTALS FOR DESIGN TEAM REVIEW OF
PENETRATIONS. ALL TRADES SHALL BE OVERLAID INTO ONE SUBMITTAL TO CAPTURE AND EVALUATE ALL
PENETRATIONS THROUGH SLABS AND WALLS TOGETHER.
10. ALL GROUT SHALL BE NONSHRINK WITH A MINIMUM COMPRESSIVE STRENGTH OF 5000 PSI.
11. MINIMUM CONCRETE COVER FOR REINFORCING STEEL IN CAST-IN-PLACE NON-PRESTRESSED MEMBERS SHALL BE
AS FOLLOWS:
A. ALL CONCRETE CAST AGAINST AND PERMANENTLY IN CONTACT WITH GROUND: 3”
B. ALL CONCRETE EXPOSED TO WEATHER OR IN CONTACT WITH GROUND:
a. 2” (#6 THROUGH #18 BARS)
b. 1-1/2” (#5 BAR, W31 OR D31 WIRE, AND SMALLER)
C. NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND:
a. SLABS, JOISTS, AND WALLS:
• 1-1/2” (#14 THROUGH #18 BARS)
• 3/4" (#11 BAR AND SMALLER)
b. BEAMS, COLUMNS, PEDESTALS, AND TENSION TIES (STIRRUPS, TIES, SPIRALS, HOOPS, AND PRIMARY
REINFORCEMENT): 1-1/2”
D. SHEAR WALLS: SEE ELEVATIONS FOR SPECIFIED CONCRETE COVER.
12. SHOP DRAWINGS SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER FOR REVIEW AND APPROVAL. NO
CONCRETE WORK SHALL COMMENCE WITHOUT APPROVED SHOP DRAWINGS.
13. CLEAN AND ROUGHEN TO 1/4" AMPLITUDE ALL EXISTING CONCRETE SURFACES TO RECEIVE NEW CONCRETE PRIOR
TO PLACEMENT.
14. SEE OTHER DRAWINGS IN THIS PROJECT FOR SIZE AND LOCATIONS OF EQUIPMENT PADS, INSERTS, AND EMBED
ITEMS.
15. REINFORCING DOWELS, WATER STOPS, AND OTHER EMBED ITEMS SHALL BE INSTALLED AND SECURED PRIOR TO
CONCRETE PLACEMENT. "WET-SETTING" OF EMBEDDED ITEMS IS NOT PERMITTED.
16. WELDED WIRE REINFORCEMENT IN COMPOSITE CONSTRUCTION SHALL HAVE TENSION SPLICES AND BE ANCHORED
AT DISCONTINUOUS EDGES, AND SHALL NOT BE SUBSTITUTED WITH ALTERNATIVE MATERIALS INCLUDING BUT NOT
LIMITED TO FIBERS.
STRUCTURAL STEEL
1. ALL STRUCTURAL STEEL WORK SHALL CONFORM TO THE FOLLOWING GOVERNING STANDARDS:
A. AISC 360 "SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS".
B. AISC 303 "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES".
C. AMERICAN WELDING SOCIETY (AWS D1.1) "STRUCTURAL WELDING CODE - STEEL".
D. RESEARCH COUNCIL ON STRUCTURAL CONNECTIONS (RCSC) “SPECIFICATION FOR STRUCTURAL JOINTS
USING HIGH-STRENGTH BOLTS”.
2. ALL STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING ASTM SPECIFICATIONS:
A. WIDE FLANGE BEAMS, COLUMNS, AND STRUCTURAL TEES: ASTM A992.
B. HOLLOW STRUCTURAL SECTIONS: ASTM A500, GRADE C.
C. STRUCTURAL PIPE SECTIONS: ASTM A53, GRADE B.
D. CHANNELS, ANGLES, AND PLATES: ASTM A36 UNLESS OTHERWISE NOTED.
E. BOLTED CONNECTIONS SHALL BE PER ASTM F3125. GRADES ARE TO BE SELECTED AS FOLLOWS:
a. STANDARD BEAM TO BEAM/GIRDER: ASTM F3125, GRADES A325, F1852, A490 OR F2280 BOLTS IN SNUG-
TIGHTENED JOINTS (3/4" DIAMETER MINIMUM WITH HARDENED WASHERS).
F. ANCHOR RODS: ASTM F1554, GRADE 36.
3. STEEL CONNECTIONS SHALL BE STANDARD AISC FRAMED BEAM CONNECTIONS, AND SHALL BE DESIGNED BY A
LICENSED ENGINEER WORKING FOR THE FABRICATOR, WHO SHALL PROVIDE CALCULATIONS, UTILIZING LRFD
LOADS AND PROCEDURES.
A. WHERE CONNECTIONS HAVE BEEN DESIGNED BY A LICENSED ENGINEER, STEEL CONTRACTOR IS
RESPONSIBLE FOR INTEGRATING RESULTS OF ALL CALCULATIONS INTO THE SHOP DRAWINGS.
B. UNLESS OTHERWISE NOTED ON PLAN, PROVIDE CONNECTIONS BASED ON MINIMUM SHEAR CAPACITY REQUIREMENTS IN THE FOLLOWING TABLE WHICH ARE BASED ON AISC SINGLE SHEAR TAB CONNECTIONS.
B. REINFORCING IS TO BE PROVIDED AT CONNECTIONS WHERE CUTS REDUCE THE SHEAR OR MOMENT
CAPACITY BELOW THAT REQUIRED TO SUSTAIN THE REACTION. FLANGES AND WEBS ARE TO BE
REINFORCED WHERE THE LOCAL CAPACITY TO SUSTAIN CONNECTION LOADS ARE INADEQUATE. CUTS OR COPES MAY PREVENT MINIMUM NUMBER OF BOLT ROWS SHOWN ABOVE FROM BEING ACHIEVED, WHICH IS ACCEPTABLE PENDING WRITTEN APPROVAL AND CONFIRMATION THAT MINIMUM SHEAR CAPACITY HAS BEEN
MET.
C. CONNECTIONS SHALL BE DESIGNED FOR SHEAR AND ECCENTRICITY, CONSIDERING THAT THE
CONNECTIONS ARE AN EXTENSION OF THE BEAMS AND GIRDERS.
4. MINIMUM WELD SIZE IS 1/4" FILLET UNLESS NOTED OTHERWISE.
5. ALL BEAMS EXCEPT CANTILEVER BEAMS SHALL BE FABRICATED AND INSTALLED WITH NATURAL CAMBER UP.
CANTILEVER BEAMS SHALL BE FABRICATED AND INSTALLED SO THAT NATURAL CAMBER RAISES CANTILEVER END.
6. FIELD CUTTING OR BURNING OF STEEL IS PROHIBITED EXCEPT WITH THE EXPRESS WRITTEN APPROVAL OF THE
STRUCTURAL ENGINEER OF RECORD (IN WHICH CASE ALL BURNING OF STEEL MUST CONFORM TO THE THERMAL
CUTTING REQUIREMENTS OF AISC AND AWS).
7. WELDING SHALL BE PERFORMED BY CERTIFIED, AWS-QUALIFIED WELDERS. WELDING ELECTRODES FOR CARBON STEEL SHALL BE AWS 5.1, CLASS E70XX. FOR ASTM A572 GRADE 50 KSI PLATE USE ELECTRODE E7018 OR APPROVED EQUAL WELDING ELECTRODES FOR ASTM A276 STAINLESS STEEL, TYPE 304, SHALL CONFORM TO AWS A5.4 FOR SHIELDED METAL ARC WELDING, ELECTRODE CLASS E308; OR AWS A5.9 FOR GAS METAL ARC WELDING, ELECTRODE
CLASS ER308.
8. SHOP PAINT EXPOSED STEEL MEMBERS, STEEL MEMBERS NOT ENCASED IN CONCRETE OR SPRAY FIREPROOFED, AND ALL STEEL MEMBERS AT THE EXTERIOR WALL WITH TNEMEC V10-99 OR APPROVED EQUAL EXCEPT FOR
MEMBERS TO BE HOT DIPPED GALVANIZED.
9. SHOP AND ERECTION DRAWINGS SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER FOR REVIEW AND
APPROVAL. NO FABRICATION OF STEEL SHALL COMMENCE WITHOUT APPROVED SHOP DRAWINGS.
10. SHOP DRAWING SUBMITTALS SHALL FOLLOW THE FOLLOWING SEQUENCE (WITH EACH NOT BEING SUBMITTED UNTIL
THE PREVIOUS ONE IS APPROVED):
A. JOB STANDARDS (BASIS OF DESIGN AND REPRESENTATIVE CALCULATIONS FOR VARIOUS CONNECTION TYPES)
B. ERECTION PLANS
C. PIECE DETAILS AND PIECE-SPECIFIC CONNECTION CALCULATIONS
SPECIAL INSPECTIONS (IBC)
A. INSPECTIONS REQUIRED BY THE LOCAL JURISDICTION SHALL BE PERFORMED BY A TESTING AGENCY PROVIDED BY
THE OWNER FOR THE FOLLOWING ITEMS:
A. INSPECTION OF FABRICATORS (IBC 1704.2.5)
B. STEEL CONSTRUCTION (IBC 1705.2)
a. STRUCTURAL STEEL (IBC 1705.2.1)
1. HIGH STRENGTH BOLTS (AISC 360)
MIN. NUMBER
OF BOLT ROWS
MINIMUM SHEAR CAPACITY REQUIREMENTS
BEAM DEPTH
(NOMINAL)
8", 10"
MIN. SHEAR
CAPACITY ASD
(Kips)
MIN. SHEAR
CAPACITY LRFD
(Kips)
16 24
CONCRETE BLOCK
1. ALL CONCRETE BLOCK WORK SHALL CONFORM TO THE "NATIONAL CONCRETE MASONRY ASSOCIATION TEK MANUAL FOR THE DESIGN AND CONSTRUCTION OF CONCRETE MASONRY", LATEST EDITION, AND "ACI 530-BUILDING CODE
REQUIREMENTS FOR MASONRY STRUCTURES".
2. CONCRETE BLOCK SHALL BE OF LIGHTWEIGHT AGGREGATE AND CONFORM TO THE FOLLOWING STANDARDS:
HOLLOW BLOCK: ASTM C90.
UNLESS OTHERWISE NOTED ON PLANS AND/OR ELEVATIONS, CONCRETE BLOCK UNIT STRENGTH SHALL BE 2000 PSI MIN. (NOTE: CONCRETE BLOCK WITH UNIT STRENGTH HIGHER THAN 2000 PSI GENERALLY REQUIRES LONGER DELIVERY
LEAD TIMES.)
3. ALL MORTAR SHALL BE ASTM C270, TYPE S.
4. ALL GROUT FOR FILLING CELLS SHALL BE ASTM C 476 WITH MINIMUM COMPRESSIVE STRENGTH OF 2000 PSI BUT NOT
LESS THAN THE COMPRESSIVE STRENGTH OF THE MASONRY ASSEMBLY, F'm. WHERE GROUT CELLS DO NOT EXCEED 4"
IN DIAMETER FINE GROUT SHALL BE USED.
5. ALL BLOCK DIMENSIONS INDICATED ON STRUCTURAL PLANS ARE NOMINAL DIMENSIONS. DESIGN OF WALL REINFORCING ASSUMES CONCRETE MASONRY UNITS THAT ARE 16" LONG AND HAVE TWO CORES/CELLS, RESULTING IN
A NOMINAL BAR SPACING OF 8" ON CENTER.
6. ALL CONCRETE BLOCK BELOW GRADE SHALL BE FILLED SOLID WITH GROUT.
7. INSTALL STANDARD WEIGHT LADDER-TYPE JOINT REINFORCEMENT AT 16" ON CENTER (SPACED VERTICALLY).
8. UNLESS NOTED OTHERWISE ALL MASONRY WALLS SHALL BE REINFORCED WITH #4@48" ON CENTER VERTICAL. GROUT
ALL REINFORCED CELLS SOLID. PROVIDE DOWELS TO MATCH VERTICAL REINFORCING AT FOUNDATION.
9. PROVIDE CONTINUOUS BOND BEAM WITH 2-#5 CONTINUOUS MINIMUM AT TOPMOST COURSE OF EACH FLOOR LEVEL
AND AT ALL TOP OF PARAPET CONDITIONS, TYPICAL THROUGHOUT.
10. ALL CMU WALLS (STRUCTURAL AND NON-STRUCTURAL) SHALL BE PERMANENTLY BRACED TO FLOOR SLABS OR
SPANDREL BEAMS AT EACH FLOOR LEVEL. SEE TYPICAL DETAILS FOR BALANCE OF INFORMATION. IF BRACING DETAILS
NOT SHOWN, CONTRACTOR TO PROVIDE PREFERRED DETAIL FOR EOR REVIEW.
NET AREA COMPRESSIVE STRENGTH
OF CONCRETE MASONRY UNIT (PSI)
NET AREA COMPRESSIVE STRENGTH OF MASONRY
ASSEMBLY, F'm (PSI) USING TYPE S MORTAR
2000 2000
STANDARD ABBREVIATIONS
ADD'L ADDITIONAL
ADJ. ADJACENT
A/E DESIGN TEAM OF RECORD
ALT. ALTERNATE
ANCH. ANCHOR
APPROX. APPROXIMATE/APPROXIMATELY
ARCH. ARCHITECT/ARCHITECTURAL
BLDG. BUILDING
BM. BEAM
B.O. BOTTOM OF
BOT. BOTTOM
BRG. BEARING
BSMT. BASEMENT
CANT. CANTILEVER
CFS COLD FORMED STEEL
C.I.P. CAST IN PLACE
C.J. CONTRACTION JOINT
CLG. CEILING
CLR. CLEAR
CMU CONCRETE MASONRY UNIT
COL. COLUMN
COMP. COMPOSITE
CONC. CONCRETE
CONST. CONSTRUCTION
CONT. CONTINUOUS
COORD. COORDINATE/COORDINATION
CONTR. CONTRACTOR
COTR CONTRACT OFFICER'S
TECHNICAL REPRESENTATIVE
CTR. CENTER
DBL. DOUBLE
DEMO DEMOLITION/DEMOLISH
DIA. DIAMETER
DIAG. DIAGONAL
DIM. DIMENSION
D.L. DEAD LOAD
DN. DOWN
DTL. DETAIL
DWG(S) DRAWING(S)
DWL. DOWEL
EA. EACH
E.F. EACH FACE
E.J. EXPANSION JOINT
EL. ELEVATION
ELEC. ELECTRICAL
ELEV. ELEVATOR
EMBED. EMBEDMENT
E.O. EDGE OF
ENGR. ENGINEER
E.O.R. ENGINEER OF RECORD
EQ. EQUAL
E.S. EACH SIDE
E.W. EACH WAY
EXP. EXPANSION
EXT. EXTERIOR
FDN. FOUNDATION
FIN. FINISH
FLR. FLOOR
FRMG. FRAMING
F.S. FAR SIDE
FT. FEET
FTG. FOOTING
GA. GAGE
GALV. GALVANIZED
G.B. GRADE BEAM
HDR. HEADER
HGR. HANGER
HORIZ. HORIZONTAL
H.P. HIGH POINT
HT. HEIGHT
HVAC HEATING, VENTILATION, &
AIR CONDITIONING
I.D. INSIDE DIAMETER
I.F. INSIDE FACE
I.J. ISOLATION JOINT
INFO INFORMATION
INT. INTERIOR
JT. JOINT
K KIP
LB. POUND
L.L. LIVE LOAD
LLBB LONG LEGS BACK-TO-BACK
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
L.P. LOW POINT
L.W. LIGHTWEIGHT
L.W. LONG WAY
MAS. MASONRY
MAX. MAXIMUM
MECH. MECHANICAL
MEP MECH., ELECT., PLUMBING, & FIRE PROTECTION
MFR. MANUFACTURER
MIN. MINIMUM
MISC. MISCELLANEOUS
M.O. MASONRY OPENING
MPII MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS
N.F. NEAR FACE
N.I.C. NOT IN CONTRACT
NO. NUMBER
N.S. NEAR SIDE
N.T.S. NOT TO SCALE
N.W. NORMAL WEIGHT
O.C. ON CENTER
O.D. OUTSIDE DIAMETER
O.F. OUTSIDE FACE
OPNG. OPENING
OPP. OPPOSITE
PC. PIECE
P/C PRECAST
PED. PEDESTAL
PERP. PERPENDICULAR
PL. PLATE
PLF POUNDS PER LINEAR FOOT
PREFAB. PREFABRICATED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
P-T POST-TENSIONED
REINF. REINFORCE(D)/REINFORCEMENT
REQ'D REQUIRED
REV. REVISION
SCHED. SCHEDULE
SECT. SECTION
S.I.F. STEP IN FOOTING
SLBB SHORT LEGS BACK-TO-BACK
SIM. SIMILAR
S.O.G. SLAB ON GRADE
SPEC. SPECIFICATION
SQ. SQUARE
S.S. STAINLESS STEEL
STD. STANDARD
STIFF. STIFFENER
STL. STEEL
S.W. SHORT WAY
SYM. SYMMETRIC
T & B TOP & BOTTOM
TEMP. TEMPORARY/TEMPERATURE
THK. THICK(NESS)
T.O. TOP OF
TR. TRANSFER
TYP. TYPICAL
U.N.O. UNLESS NOTED OTHERWISE
VERT. VERTICAL
W/ WITH
W.P WORK POINT
W.W.R. WELDED WIRE REINFORCEMENT
# NUMBER/SIZE
Ø DIAMETER
STANDARD ABBREVIATIONS FOR EXISTING STRUCTURES
C.I. CAST IRON
(E) EXISTING MEMBER OR DIMENSION
EXIST. EXISTING
T.C. TERRA COTTA
U-P UNDERPINNING
V.I.F. VERIFY IN FIELD
STANDARD ABBREVIATIONS FOR WOOD STRUCTURES
NO. NUMBER
N.S. NEAR SIDE
ACT. ACTUAL
GLULAM GLUE LAMINATED TIMBER
LSL LAMINATED STRAND LUMBER
LVL LAMINATED VENEER LUMBER
NOM. NOMINAL
PSL PARALLEL STRAND LUMBER
P.T. PRESERVATIVE TREATED
R.O. ROUGH OPENING
SQ. SQUARE
T&G TONGUE & GROOVE
HANGER COLUMN ABOVE / BELOW
LEGEND
STEEL BEAM
EXISTING CONCRETE FOOTING, GRADE BEAM, OR PILE CAP
EXISTING BEAM TO BE DEMOLISHED
EXISTING STEEL BEAM
REVISION
STEP IN SLAB
SLAB SLOPE TRANSITION
KEYNOTE
WALL OR CONCRETE BEAM BELOW
CONCRETE ON METAL DECK (SEE SCHEDULE), OPEN
ARROW INDICATES SPAN DIRECTION
SLAB ON GRADE (SEE SCHEDULE)
EXISTING STEEL COLUMN
COLUMN ABOVE / BELOW
S-#
S.O.G.
OPENING IN SLAB
EXISTING OPENING IN EXISTING SLAB
EXISTING WALL, BEAM FLOOR, OR FOUNDATION
(SEE NOTES FOR MATERIAL)
APPROXIMATE EXTENTS OF TRENCHING IN EXISTING
BASEMENT SLAB. SEE TYP. DETAIL ON S-5.1
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
SEALS AND SIGNATURES
ISSUED FOR REV DATE
1700 NEW YORK AVENUE NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e
Mechanical Room 1000 Heating System Upgrade 500 Indiana Avenue N.W.
Washington, DC 20001
7/ 1/
:4
8:
P M
STRUCTURAL GENERAL
NOTES
S0.1
3026.0030352
A ut ho r
SEISMIC LOADS FOR BUILDING NOT CONSIDERED AS PART OF THIS
RENOVATION. PER THE 2015 IEBC THE EXISTING LATERAL LOAD CARRYING
SYSTEM IS ALLOWED TO REMAIN UNALTERED AS THE PROPOSED
MODIFICATIONS WILL INCREASE THE DEMAND-CAPACITY RATIO FOR THE
LATERAL SYSTEM BY FAR LESS THAN THE CODE'S 10 PERCENT THRESHOLD.
SEISMIC DESIGN, EXISTING BUILDING:
EQUIVALENT STATIC FORCE ANALYSIS PROCEDURE
B SEISMIC DESIGN CATEGORY
0.0081 S(d1) 5-% DAMPED SPECTRAL RESPONSE COEFFICIENT AT 1-SECOND PERIODS
0.126 S(ds) 5-% DAMPED SPECTRAL RESPONSE COEFFICIENT AT SHORT PERIODS
D SITE CLASS (ASSUMED)
0.051 S1 1-SECOND PERIOD SPECTRAL RESPONSE ACCELERATION
0.118 Ss SHORT PERIOD SPECTRAL RESPONSE ACCELERATION
1.25 I SEISMIC IMPORTANCE FACTOR
SEISMIC DESIGN, EXISTING BUILDING:
WIND LOADS NOT CONSIDERED IN THE DESIGN FOR THIS SCOPE OF WORK.
WIND CRITERIA IS PROVIDED FOR REFERENCE ONLY.
± 0.18 GCPi INTERNAL PRESSURE COEFFICIENT
B WIND EXPOSURE CATEGORY
1 I WIND IMPORTANCE FACTOR
120 BASIC WIND SPEED
WIND LOAD:
SNOW LOADS NOT CONSIDERED IN THE DESIGN FOR THIS SCOPE OF WORK.
SNOW CRITERIA IS PROVIDED FOR REFERENCE ONLY.
1 Ct THERMAL FACTOR
1.1 Is SNOW LOAD IMPORTANCE FACTOR
1 Ce SNOW EXPOSURE FACTOR
30 PSF Pg GROUND SNOW LOAD
SNOW LOAD:
AND THEREFORE ONLY ELEMENTS BEING MODIFIED HAVE BEEN DESIGNED
*OCCUPANCY TYPE AND LOADING OF E BUILDING ARE NOT CHANGING
50 PSF OFFICE AREA
20 PSF ROOF
LIVE LOADS:
BUILDING CATEGORY: II
GOVERNING CODE: IEBC 2015 WITH 2017 DCMR 12J AMENDMENTS
DESIGN PARAMETER TABLE
ISSUE FOR BID 03 JULY 2027
07/02/2025
3 4 5 5.7 6 6.2 7 7.1 7.3
I
J
K
H.7
H.4
H.3
H.1
H
H.8
(E) S.O.G.
(E) S.O.G.
1 1 1
(2)x500 LB
(2 )x
L
B
(2 )x
L
B
(2 )x
L
B
(2)x800 LB
(2)x550 LB
(2)x200 LB
(2)x400 LB
11 12 13
I
J
K
H.7
H.4
H.3
H.1
H
H.8
(E) S.O.G.
4 5 5.7 6 6.2
I
H.7
H.4
H.3
H.1
H
G.4
G
G.2
H.8
(E
W
(E) W16 (E) W16
(E
W
(E
W
(E
W
(E
W
(E
W
(E) W14
(E) W16
(E) W16
(E) W16
(E
W
(E
W
(E) W8
(E
C
(E) W16
(E) W16
(E) W16
(E) W16
(E) W18
(E) W16
(E) W16
(E) W16
(E) W16
(E) W16
(E) CONC. SLAB ON METAL DECK
W8X24 6
CONN. REACTION = 48 KIPS
CONN. REACTION = 80 KIPS
CONN. REACTION = 38 KIPS
CONN. REACTION = 38 KIPS
CONN. REACTION = 48 KIPS
CONN. REACTION = 80 KIPS
4 5 5.7 6 6.2
I
H.7
H.4
H.3
H.1
H
G.4
G
G.2
H.8
(E
W
(E) W16 (E) W16
(E
W
(E
W
(E
W
(E
W
(E
W
(E) W16
(E) W16
(E) W16
(E
W
(E) W16
(E
W
(E
W
(E) W8
(E
C
(E) W16
(E) W16
(E) W16
(E) W24
(E) W16
(E) W16
(E) W16
(E) W16
(E) W16
(E) W16
(E) CONC. SLAB ON METAL DECK
4 5 5.7 6 6.2
I
H.7
H.4
H.3
H.1
H
G.4
G
G.2
H.8
(E
W
(E) W16 (E) W16
(E
W
(E
W
(E
W
(E
W
(E
W
(E) W16
(E) W16
(E) W16
(E
W
(E) W16
(E
W
(E
W
(E) W8
(E
C
(E) W16
(E) W16
(E) W16
(E) W24
(E) W16
(E) W16
(E) W8
(E) W16
(E) W16
(E
W
(E
W
(E) W16
(E
W
(E) W12
(E) CONC. SLAB ON METAL DECK
1. ALL DEMOLITION, SHORING, BRACING, AND SEQUENCING IS
THE RESPONSABILITY OF THE CONTRACTOR'S ENGINEER.
TEMPORARY BRACING, IF NOTED ON STRUCTURAL DRAWINGS,
IS INTENDED IN A QUALITATIVE, SCHEMATIC AND NON-
COMPREHENSIVE MANNER FOR THE PURPOSES OF OF
ASSISTANCE IN COORDINATION AND GENERAL SCOPE AND
PRICING.
2. ALL DIMENSIONS OF EXISTING STRUCTURE SHALL BE FIELD
VERIFIED BY THE CONTRACTOR. WHERE DIMENSIONS OF NEW
ELEMENTS ARE DEPENDENT ON EXISTING GEOMETRY, THE
CONTRACTOR SHALL PERFORM FIELD SURVEY FOR
VERIFICATION PRIOR TO DEVELOPING SHOP DRAWINGS FOR
NEW ELEMENTS.
3. COORDINATE ALL DIMENSIONS AND ELEVATIONS WITH
ARCHITECT, MEP, AND ALL OTHER PRIME CONTRACTORS.
4. STEEL LINTELS OR SLEEVES ARE REQUIRED AT ALL
MECHANICAL PENETRATIONS THROUGH EXISTING MASONRY
WALLS. REFER TO MEP DRAWINGS FOR LOCATIONS.
5. BASIS OF DESIGN CONSTRUCTION SEQUENCING:
1. CONTRACTOR TO NOTIFY SEOR IF THERE ARE ANY EXISTING
STEEL BEAM WEB PENETRATIONS WITHIN 4 FT OF PROPOSED
NEW CONNECTION LOCATIONS. LOCATION OF BEAM
PENETRATIONS NEAR NEW CONNECTIONS TO BE REVIEWED
AND APPROVED BY SEOR PRIOR TO INSTALLATION OF ANY NEW
STEEL FRAMING.
2. ALL NEW FRAMING AT SLAB OPENINGS SHALL BE INSTALLED
AND INSPECTED PRIOR TO DEMOLITION OF THE SLAB.
6. BASEMENT SLAB WITHIN FOOTPRINT OF ORIGINAL BUILDING IS A
STRUCTURED SLAB 12" THICK WITH BAR REINFORCING, AS
OPPOSED TO A SLAB ON GRADE. TRENCHING IN THIS EXISTING
SLAB REQUIRES STRUCTURAL PATCHING AND REPAIR PER TYPICAL
DETAIL ON S5.1. TRENCHING ONLY PERMITTED WITHIN SLAB; NOT
ACCEPTABLE AT EXISTING PILE CAPS AND/OR SPREAD
FOOTINGS.COORDINATE WITH EXTENTS SHOWN ON PLAN AND
WITH MEP DRAWINGS.
NORTH
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
1700 NEW YORK AVENUE NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e
Mechanical Room 1000 Heating System Upgrade 500 Indiana Avenue N.W.
Washington, DC 20001
SHEET NOTES KEYNOTES
7/ 1/
:4
8:
P M
STRUCTURAL FRAMING
PART PLANS
S1.1
3026.0030352
C M
1/8" = 1'-0"S1.1
1 PARKING LEVEL PARTIAL PLAN
1/8" = 1'-0"S1.1
2 PARKING LEVEL PARTIAL PLAN
1/8" = 1'-0"S1.1
3 C STREET LEVEL FLOOR PLAN
1/8" = 1'-0"S1.1
4 JOHN MARSHALL LEVEL FLOOR PLAN
1/8" = 1'-0"S1.1
5 INDIANA AVENUE LEVEL FLOOR PLAN
MARK DESCRIPTION
1 NEW 4" THICK CONCRETE EQUIPMENT PAD AT
MEP EQUIPMENT. SEE TYPICAL DETAIL ON S5.1
FOR REINFORCING AND MECHANICAL & PLUMBING
DRAWINGS FOR SIZE AND LOCATION. MAXIMUM
EQUIPMENT WEIGHT NOTED ON PLAN.
2 PROVIDE INFILL STEEL FRAMING PER TYPICAL
DETAIL ON S5.1 AT NEW SHAFT OPENINGS
THROUGH EXISTING SLAB ON METAL DECK.
CONNECT NEW CHANNEL FRAMING TO EXISTING
BEAMS.
4 NEW UNFRAMED OPENING IN SLAB ON DECK.
ALIGN PENETRATIONS IN AXIS PARALLEL TO DECK
SPAN (NORTH-SOUTH). SEE TYPICAL DETAIL ON
S5.1 FOR DECK REINFORCING.
MARK DESCRIPTION
5 APPROXIMATE EXTENTS OF TRENCHING IN
STRUCTURED BASEMENT SLAB. SEE TYPICAL
DETAIL ON S5.1 AND MEP DRAWINGS FOR EXACT
LOCATIONS. DO NOT TRENCH AT EXISTING PILE
CAPS OR SPREAD FOOTINGS; V.I.F. LOCATIONS OF
EXISTING FOOTINGS.
6 SUPPORT FOR NEW STEEL PIPES AT C STREET
LEVEL. PROVIDE PIPE ANCHORS DIRECTLY TO
NEW STEEL BEAMS ON EACH SIDE. MAXIMUM
ALLOWABLE POINT LOAD OF 9,000 LB AT EACH
PIPE, (2) LOCATIONS TOTAL.
ISSUE FOR BID 03 JULY 2027
MARK DESCRIPTION
7 EXPOSE EXISTING CONNECTION BETWEEN STEEL
BEAM AND GIRDER AND/OR GIRDER AND COLUMN.
PROVIDE DOCUMENTATION OF CONNECTION TO
EOR FOR EVALUATION. CONTRACTOR TO
PROVIDE DELEGATED DESIGN OF CONNECTION
REINFORCING FOR REQUIRED SHEAR LOADING.
ASSUME EXISTING BOLTED SHEAR CONNECTION
TO BE FULLY WELDED.
4 5 5.7 6 6.2
I
H.7
H.4
H.3
H.1
H
G.4
G
G.2
H.8
(E) W16 (E) W16
(E
W
(E
W
(E
W
(E
W
(E
W
(E) W16
(E) W16
(E) W16
(E
W
(E) W16
(E
W
(E
W
(E) W8
(E
C
(E) W16
(E) W16
(E) W24
(E) W16
(E) W16
(E) W16
(E
W
(E) W16
(E) W16
(E) W16
(E) W16
(E
W
(E) CONC. SLAB ON METAL DECK
4 5 5.7 6 6.2
I
H.7
H.4
H.3
H.1
H
G.4
G
G.2
H.8
(E) W16 (E) W16
(E
W
(E
W
(E
W
(E
W
(E
W
(E) W16
(E) W16
(E) W16
(E
W
(E) W16
(E
W
(E
W
(E) W8
(E
C
(E) W16
(E) W16
(E) W24
(E) W16
(E) W16
(E) W16
(E
W
(E) W16
(E) W16
(E) W16
(E
W
(E) CONC. SLAB ON METAL DECK
4 5 5.7 6 6.2
I
H.7
H.4
H.3
H.1
H
G.4
G
G.2
H.8
(E) W16 (E) W16
(E
W
(E
W
(E
W
(E
W
(E
W
(E) W12
(E) W16
(E) W16
(E
W
(E) W14
(E
W
(E
W
(E) W8
(E
C
(E) W16
(E) W16
(E) W21
(E) W16
(E) W16
(E) W16
(E
W
(E) W16
(E) W16
(E) W16
(E
W
(E) W12
(E) W16
(E) CONC. SLAB ON METAL DECK
4 5 5.7 6 6.2
I
H.7
H.4
H.3
H.1
H
G.4
G
G.2
H.8
(E) W16 (E) W16
(E
W
(E
W
(E
W
(E
W
(E
W
(E) W16
(E) W18
(E) W16
(E
W
(E) W16
(E
W
(E
W
(E) W12
(E
C
(E) W16
(E) W16
(E) W16
(E) W16
(E) W16
(E) W16
(E
W
(E) W16
(E) W16
(E) W8
(E) W16
(E
W
(E
W
(E
W
(E) CONC. SLAB ON METAL DECK
4 5 5.7 6 6.2
I
H.7
H.4
H.3
H.1
H
G.4
G
G.2
H.8
(E) W18 (E) W14
(E
W
(E
W
(E
W
(E
W
(E) W14
(E) W12
(E
W
(E) W14
(E
W
(E) W18
(E) W18 (E) W14
(E) W16
(E) W18
(E) W16
(E) W12
(E) W16
(E
W
(E) W12
(E) W14
(E
W
(E) W14
(E) W12
(E) W6
(E) W6
(E
W
(E
W
(E) W6
(E) W6
(E
W
(E
W
(E
W
(E
W
(E
W
(E) W8
(E) W8
(E) CONC. SLAB ON METAL DECK
1. ALL DEMOLITION, SHORING, BRACING, AND SEQUENCING IS
THE RESPONSABILITY OF THE CONTRACTOR'S ENGINEER.
TEMPORARY BRACING, IF NOTED ON STRUCTURAL DRAWINGS,
IS INTENDED IN A QUALITATIVE, SCHEMATIC AND NON-
COMPREHENSIVE MANNER FOR THE PURPOSES OF OF
ASSISTANCE IN COORDINATION AND GENERAL SCOPE AND
PRICING.
2. ALL DIMENSIONS OF EXISTING STRUCTURE SHALL BE FIELD
VERIFIED BY THE CONTRACTOR. WHERE DIMENSIONS OF NEW
ELEMENTS ARE DEPENDENT ON EXISTING GEOMETRY, THE
CONTRACTOR SHALL PERFORM FIELD SURVEY FOR
VERIFICATION PRIOR TO DEVELOPING SHOP DRAWINGS FOR
NEW ELEMENTS.
3. COORDINATE ALL DIMENSIONS AND ELEVATIONS WITH
ARCHITECT, MEP, AND ALL OTHER PRIME CONTRACTORS.
4. STEEL LINTELS OR SLEEVES ARE REQUIRED AT ALL
MECHANICAL PENETRATIONS THROUGH EXISTING MASONRY
WALLS. REFER TO MEP DRAWINGS FOR LOCATIONS.
5. BASIS OF DESIGN CONSTRUCTION SEQUENCING:
1. CONTRACTOR TO NOTIFY SEOR IF THERE ARE ANY EXISTING
STEEL BEAM WEB PENETRATIONS WITHIN 4 FT OF PROPOSED
NEW CONNECTION LOCATIONS. LOCATION OF BEAM
PENETRATIONS NEAR NEW CONNECTIONS TO BE REVIEWED
AND APPROVED BY SEOR PRIOR TO INSTALLATION OF ANY NEW
STEEL FRAMING.
2. ALL NEW FRAMING AT SLAB OPENINGS SHALL BE INSTALLED
AND INSPECTED PRIOR TO DEMOLITION OF THE SLAB.
6. BASEMENT SLAB WITHIN FOOTPRINT OF ORIGINAL BUILDING IS A
STRUCTURED SLAB 12" THICK WITH BAR REINFORCING, AS
OPPOSED TO A SLAB ON GRADE. TRENCHING IN THIS EXISTING
SLAB REQUIRES STRUCTURAL PATCHING AND REPAIR PER TYPICAL
DETAIL ON S5.1. TRENCHING ONLY PERMITTED WITHIN SLAB; NOT
ACCEPTABLE AT EXISTING PILE CAPS AND/OR SPREAD
FOOTINGS.COORDINATE WITH EXTENTS SHOWN ON PLAN AND
WITH MEP DRAWINGS.
NORTH
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
1700 NEW YORK AVENUE NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e
Mechanical Room 1000 Heating System Upgrade 500 Indiana Avenue N.W.
Washington, DC 20001
SHEET NOTES KEYNOTES
7/ 1/
:4
8:
P M
STRUCTURAL FRAMING
PART PLANS
S1.2
3026.0030352
C M
1/8" = 1'-0"S1.2
1 SECOND LEVEL FLOOR PLAN
1/8" = 1'-0"S1.2
2 THIRD LEVEL FLOOR PLAN
1/8" = 1'-0"S1.2
3 FOURTH LEVEL FLOOR PLAN
1/8" = 1'-0"S1.2
4 FIFTH LEVEL FLOOR PLAN
1/8" = 1'-0"S1.2
5 SIXTH LEVEL FLOOR PLAN
MARK DESCRIPTION
2 PROVIDE INFILL STEEL FRAMING PER TYPICAL
DETAIL ON S5.1 AT NEW SHAFT OPENINGS
THROUGH EXISTING SLAB ON METAL DECK.
CONNECT NEW CHANNEL FRAMING TO EXISTING
BEAMS.
4 NEW UNFRAMED OPENING IN SLAB ON DECK.
ALIGN PENETRATIONS IN AXIS PARALLEL TO DECK
SPAN (NORTH-SOUTH). SEE TYPICAL DETAIL ON
S5.1 FOR DECK REINFORCING.
EXISTING CONCRETE
ON METAL DECK SLAB
1" DRYPACKPROVIDE 1/2" Ø ADHESIVE
ANCHORS DRILLED INTO
EXISTING SLAB @ 3'-0" O.C. TO
BRACE BEAM
BEAM, SEE PLAN
6" NEW OPENING3" EMBEDMENT
NOTES:
1. EITHER DRYPACK OR STEEL SHIM MAY BE PROVIDED PER
CONTRACTOR'S OPTION.
2. PROVIDE ANCHORS ADJACENT TO ALL SLAB EDGES.
ROUGHEN TO 1/4" AMPLITUDE OR
COAT CONTACT SURFACE WITH
LATEX BONDING AGENT
HOOKED #3 DOWEL @
18" O.C. W/ MIN. 2-3/4"
EMBEDMENT IN HY-200
ADHESIVE OR
APPROVED EQUAL
SEE BELOW TABLE
FOR TYPICAL
REINFORCING
U .N
.O
AT SUPPORTED SLAB AT SLAB ON GRADE
NOTES:
1. FOR SIZE AND LOCATION SEE ARCHITECTURAL AND MECHANICAL
DRAWINGS.
2. CONCRETE FOR PADS SHALL BE NORMAL WEIGHT WITH f'c = 4,000 PSI.
3" CL.
M
A X
EQUIPMENT PAD TEMPERATURE AND
SHRINKAGE REINFORCING
REINFORCINGPAD THICKNESS
#3 @ 12" O.C. EACH WAY4"-5"
#4 @ 12" O.C. EACH WAY6"-9"
#5 @ 12" O.C. EACH WAY10"-12"
E X
IS
T
IN
G
C O
N C
R E
T E
O N
S T
E E
L D
E C
K S
L A
B E
X
IS
T
IN
G C
O N
C R
E T
E O
N S
T E
E L
D E
C K
S L
A B
NEW 4" LONG STEEL SHIM PLATE
@ 2'-0" O.C. TO ALIGN WITH RIBS
OF STEEL DECKING
NEW BEAM
NOTE: TACK WELD NEW SHIM PLATE TO BEAM AND STEEL DECK
1" TYP. 1" MIN.
1" TYP.
NEW 4" LONG STEEL SHIM PLATE
@ 2'-0" O.C. TO ALIGN WITH RIBS
OF STEEL DECKING
NEW BEAM
/4
M
IN
/4
M
IN
NOTES:
1. COORDINATE REQUIRED MECHANICAL OPENING PENETRATIONS WITH
MEP AND ARCHITECTURAL DRAWINGS
NEW MECHANICAL OPENING
IN EXISTING SLAB ON DECK,
3' - 0" MAX.
EXISTING DECK SPAN
DIRECTION
M
A X
V .I
.F
C X
.5
C X
.5
C8X11.5
C8X11.5
EXISTING BEAM, V.I.F.
EXISTING BEAM, V.I.F.
NEW CHANNELS SHIMMED
TIGHT TO UNDERSIDE OF
EXISTING SLAB PER TYPICAL
DETAIL
WF STEEL BEAM
DOUBLE ANGLES
HIGH-STRENGTH
BOLTS, SEE GEN.
NOTES
WF BEAM TO WF BEAM
NOTES:
1. CONNECTION DETAILS SHOWN ABOVE ARE SCHEMATIC ONLY. THE CONTRACTOR MAY SUBMIT
ALTERNATE DETAILS FROM THOSE SHOWN ABOVE, BUT IN ANY CASE THE CONTRACTOR IS
RESPONSIBLE FOR PRODUCING STEEL SHOP DRAWINGS IN ACCORDANCE WITH THE PROJECT
GENERAL NOTES AND AISC GUIDELINES. CALCULATIONS SHALL BE SUBMITTED AS REQUIRED IN
THE GENERAL NOTES AND ELSEWHERE IN THE CONTRACT DOCUMENTS.
2. THE CONTRACTOR SHALL DETAIL THE PROJECT CONNECTIONS FOR THE LOADS AS INDICATED
IN THE CONTRACT DOCUMENTS, PER AISC GUIDELINES. THE SCHEMATIC DETAILS ABOVE ARE
NOT SUGGESTIVE OF SPECIFIC CAPACITIES. THE NUMBER AND SIZE OF BOLTS, SIZE AND
LENGTH OF WELDS, AND SIZE OF STEEL PIECES MUST BE DETERMINED PER AISC GUIDELINES
AND THE CONTRACT DOCUMENTS.
3. SEE GENERAL NOTES FOR REQUIRED CAPACITY AT CONNECTIONS.
16" GAUGE SHEET WELDED
TO EACH CELL ALL AROUND
(BY DECKING CONT.)
NOTES:
1. SEE MECHANICAL AND ARCHITECTURAL DRAWINGS FOR OPENING SIZE AND LOCATION.
2. WHERE POSSIBLE; EXTEND DECK CONTINUOUSLY OVER OPENING, REINFORCE AND
CUT DECK WHEN OPENING IS REQUIRED.
3. FOR MULTIPLE PENETRATIONS, ALIGN IN AXIS PARALLEL TO DECK SPAN. PROVIDE MIN
12" CLEAR BETWEEN ADJACENT PENETRATIONS.
S
ID
E O
F O
P N
G
M
IN
E
A C
H
8" MIN. OR EXTEND
3" BEYOND NEXT
FULL METAL DECK
RIB, WHICHEVER IS
GREATER
NO REINF. REQUIRED WHERE "L" IS 2" OR LESS IN DIRECTION PERPENDICULAR TO DECK.
FOR OPENINGS UP TO 13" PERPENDICULAR TO DECK
L=13" MAX. OPENING
V A
R
IE
S
M A
X
LINTEL BOND BEAM BLOCK
HORIZONTAL REINFORCING,
SEE SCHEDULE
BEAM THICKNESS,
SEE SCHEDULE
BEAM DEPTH,
SEE SCHEDULE
CMU BOND BEAM SCHEDULE
LENGTH
BEAM
THICKNESS
BEAM DEPTH
HORIZONTAL
REINF.
SHEAR
REINF.
0'-0" - 4'-0" 6" 8"
(1 COURSE HIGH)
1-#5
NOTES:
1. ALL CMU BOND BEAM BEAMS TO BE GROUTED SOLID FOR FULL LENGTH OF BEAM.
2. ALL OTHER (NON-SPANNING) BOND BEAMS TO BE SINGLE COURSE WITH 2-#4 HORIZONTAL
REINFORCING.
3. VERTICAL PLACEMENT OF HORIZONTAL REINFORCEMENT IN ALL BOND BEAMS SHALL BE 3"
FROM THE BOTTOM OF THE BEAM TO CENTER OF BAR, U.N.O. LINTEL REINFORCEMENT SHALL
BE SUPPORTED BY WIRE CHAIRS.
4. CLEAR DISTANCE BETWEEN PARALLEL BARS SHALL NOT BE LESS THAN THE NOMINAL
DIAMETER OF THE BARS OR 1", WHICHEVER IS GREATER.
4'-8" - 8-0" 8" 8"
(1 COURSE HIGH)
2-#5
SHEAR REINFORCING AS REQUIRED.
PROVIDE 180 DEG. HOOK. OMIT IF
NOT SPECIFIC
T.O. (E) MAT
FOR CONSTRUCTION ACCESS
CONTRACTOR TO COORDINATE
MINIMUN REQUIRED OPENING
LOCALLY CUT OUT TRENCH IN MAT
SLAB TO INSTALL PIPING. AS ALT,
CHIP OUT CONCRETE AROUND
REBAR, LEAVING REBAR IN PLACE
EXISTING MAT
RE-ESTABLISH MAT REINFORCING
WITH NEW REBAR COUPLERS AND
PATCH CONRETE AFTER
INSTALLING PIPING
COORDINATE PIPING
ELEVATION TO RUN
BELOW EXSITING MAT
V .I
.F
WALL OPENING
REINF. AND
DOWELS PER TABLE
2x (2) #5
ADDITIONAL
EACH SIDE OF
OPENING TYP.
REINF. AND
DOWELS PER TABLE
WALL OPENING
2x (2) #5
ADDITIONAL
EACH SIDE OF
OPENING TYP.
S E
E S
C H
E D
U L E
S E
E S
C H
E D
U L E
NOTE: PROVIDE LINTELS AS REQUIRED OVER WALL OPENINGS.
S L A
B
S L A
B
ANCHOR TOP OF CMU WALL TO UNDERSIDE OF SLAB
W/ 3/16" GALV. STEEL U SHAPED CLIP 3"x BY WALL THICKNESS x 8" LONG @ SPACING TO MATCH AND
ALIGN WITH VERTICAL WALL REINFORCING (PTA 422 BY
H & B OR EQUAL) W/ 2-3/8" Ø EXPANSION BOLTS TO
UNDERSIDE OF SLAB. PROVIDE COMPRESSIBLE PAD
BETWEEN TOP OF BLOCK & CLIP
INTERIOR WALLS
NOMINAL CMU
THICKNESS
VERTICAL
REBAR
HORIZONTAL
REBAR
MAXIMUM
HEIGHT (FT)
DOWELS
#4 @ 48"
9 GAGE LADDER
REINFORCING @
16" O.C.
8" 27'-7"
SAME AS
VERTICAL BARS
T.O. SLAB T.O. SLAB
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
SEALS AND SIGNATURES
ISSUED FOR REV DATE
1700 NEW YORK AVENUE NW
SUITE 100
WASHINGTON, DC 20006
202.842.2100 www.smithgroup.com
P lo t D at e
Mechanical Room 1000 Heating System Upgrade 500 Indiana Avenue N.W.
Washington, DC 20001
7/ 1/
:4
8:
P M
STRUCTURAL TYPICAL
DETAILS
S5.1
3026.0030352
A ut ho r
N.T.S.
TYPICAL DETAIL OF BEAM DRYPACKED
BELOW EXISTING SLAB AT NEW OPENING
N.T.S.
TYPICAL EQUIPMENT PAD
N.T.S.
TYPICAL BEAM AND SHIM PLATE
BELOW EXISTING METAL DECK SLAB
N.T.S.
TYPICAL DETAIL FRAMING OUT NEW MEP
OPENING IN EXISTING SLAB ON DECK
N.T.S.
TYPICAL SUGGESTED SHEAR CONNECTIONS AT GRAVITY
LOADS ONLY
N.T.S.
TYPICAL REINFORCEMENT FOR UNFRAMED OPENINGS IN ROOF DECK
N.T.S.
CMU BOND BEAM LINTEL
N.T.S.
TYPICAL TRENCHING AT EXISTING MAT SLAB
N.T.S.
TYPICAL…