Attachment III Final Drawings -HVAC-Elec Bldg 107.pdf
PDF 9 MB Posted
- Solicitation number
- 12905B22R0007
About this file
This is a solicitation for a firm fixed price construction contract to repair or replace HVAC and electrical components at two buildings at the USDA Carl Hayden Bee Research Center in Tucson, Arizona. The work includes providing all labor, materials, equipment, transportation, and supervision to complete renovations in compliance with applicable building codes. The requirement is prepared under FAR Part 36 for construction contracts. It will be solicited as a 100% small business set-aside for NAICS 236220 with a size standard of $39.5M. The estimated value is between $500,000 and $1,000,000. The solicitation will be posted to SAM.gov on March 17th, 2022. Interested parties must register in SAM.gov to be eligible for award. Questions may be submitted by email with the reference number 12905B22R0007 by a specified date.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UPUPUPUP
U
S
D
A
-- USDA
NO. DATE BY DESCRIPTION
REVISIONS
Agricultural Research Service
DWG. NO.
SHEET OF
PROJECT MANAGER EPM
DESIGNER
CHECKED BY
DRAWN BY REAL PROPERTY
SAFETY & HEALTH
RPR
SPECIFICATION NO.
DATE
HLA CAROLYN WILLIAMS
LOUVIERE, STRATTON & YOKEL, LLC
8484 GEORGIA AVENUE, SUITE 650, SILVER
SPRING, MD 20910
(301) 588-1500
BURNS & McDONNELL
8201 NORMAN CENTER DR. SUITE 300
BLOOMINGTON, MN 55437
(952) 656-6003
G-001
COVER SHEET
USDA CARL HAYDEN BEE RESEARCH CENTER - TUCSON, AZ
HLA
LEA
LEA
07/13/2021
U.S. DEPARTMENT OF AGRICULTURE
CARL HAYDEN BEE RESEARCH CENTER
AGRICULTURAL RESEARCH SERVICE
PACIFIC WEST AREA
JULY 13, 2021
GENERAL
G-001 COVER SHEET
G-002 ABBREVIATIONS & GENERAL NOTES
ARCHITECTURAL
A-100 BASEMENT DEMOLITION REFLECTED CEILING PLAN
A-110 BASEMENT NEW WORK REFLECTED CEILING PLAN
A-111 GROUND FLOOR NEW WORK REFLECTED CEILING PLAN
A-601 SCHEDULES
MECHANICAL
M-001 MECHANICAL NOTES, LEGEND, SYMBOLS & ABBREVIATIONS
MD100 MECHANICAL DEMOLITION PLAN - BASEMENT
MD101 MECHANICAL DEMOLITION PLAN - FIRST FLOOR
MD200 MECHANICAL PIPING DEMOLITION - BASEMENT
MD201 MECHANICAL PIPING DEMOLITION - FIRST FLOOR
MD202 MECHANICAL ENLARGED PIPING DEMOLITION - FIRST FLOOR
MH100 MECHANICAL PLAN - BASEMENT
MH101 MECHANICAL PLAN - FIRST FLOOR
MP100 MECHANICAL PIPING PLAN - BASEMENT
MP101 MECHANICAL PIPING PLAN - FIRST FLOOR
MP401 MECHANICAL ENLARGED PIPING PLAN - BASEMENT
MP402 MECHANICAL ENLARGED PIPING PLAN - FIRST FLOOR
M-501 MECHANICAL DETAILS
M-601 MECHANICAL SCHEDULES
PLUMBING
P-001 PLUMBING NOTES, LEGEND, SYMBOLS & ABBREVIATIONS
P-101 PLUMBING PLAN - FIRST FLOOR
ELECTRICAL
E-001 ELECTRICAL NOTES AND ABBREVIATIONS
E-002 ELECTRICAL NOTES AND ABBREVIATIONS
ED101 ELECTRICAL FIRST FLOOR DEMOLITION PLAN
ED102 ELECTRICAL BASEMENT DEMOLITION PLAN
ED601 DEMOLITION ONE-LINE DIAGRAM
ED602 DEMOLITION PANELBOARD SCHEDULE
ES100 ELECTRICAL SITE PLAN
E-101 ELECTRICAL FIRST FLOOR PLAN
E-102 ELECTRICAL FIRST FLOOR LABORATORIES PLAN
E-103 ELECTRICAL BASEMENT PLAN
E-104 ELECTRICAL BASEMENT REFLECTED CEILING PLAN
E-105 BUILDING 108 FLOOR PLAN
E-601 ELECTRICAL ONE-LINE DIAGRAM
E-602 ELECTRICAL PANELBOARD SCHEDULES
E-603 ELECTRICAL PANELBOARD SCHEDULES
E-604 BUILDING 108 PANELBOARD SCHEDULES
DRAWING INDEX
SITE PLAN KEY PLANVICINITY MAP SEAL
FINAL SUBMISSION
HVAC AND ELECTRIC MODIFICATIONS
PROJECT LOCATION PROJECT AREA
BLDG 107
BLDG 108
GREENHOUSE
NTSNTS
LSY PROJECT NO. 20037.01
07/13/21 LEA FINAL SUBMISSION
TUCSON, ARIZONA
1. DO NOT START CONSTRUCTION UNTIL ALL REQUIRED PERMIT APPROVALS ARE OBTAINED.
2. VISIT THE SITE PRIOR TO CONSTRUCTION TO VERIFY CONDITIONS RELATING TO CONSTRUCTION. THOROUGHLY EXAMINE AND BE FAMILIAR
WITH THE DRAWINGS, DRAWING NOTES AND SPECIFICATIONS. FIELD VERIFY ALL DIMENSIONS PRIOR TO ORDERING MATERIALS. DO NOT
SCALE THE DRAWINGS.
3. NOTIFY THE PROJECT OFFICER OF ANY DISCREPANCIES, OMISSIONS, OR CONFLICTS IN THE CONSTRUCTION DOCUMENTS.
4. FURNISH AND INSTALL ALL ITEMS SHOWN OR IMPLIED ON THE DRAWINGS UNLESS OTHERWISE NOTED.
5. MAINTAIN THE CONSTRUCTION SITE IN A CLEAN AND ORDERLY MANNER.
6. DIMENSIONS SHOWN ON THE DRAWINGS ARE FROM FINISH FACE OF PARTITION UNLESS OTHERWISE NOTED.
7. INFORMATION CONTAINED IN THESE DRAWINGS IS BASED ON LIMITED FIELD MEASUREMENTS AND MAY REQUIRE ADJUSTMENTS OR
MODIFICATIONS TO CONFIRM WITH EXISTING CONDITIONS. IN CASES WHERE CHANGES IN DETAIL ARE NECESSARY, THESE DRAWINGS SHALL
BE USED TO SHOW DESIGN INTENT ONLY. PERFORM WORK, SHOWN OR IMPLIED, THAT IS NECESSARY TO CARRY OUT THE INTENT OF THE
DRAWINGS AND SPECIFICATIONS OR IS CUSTOMARILY PERFORMED AS IF FULLY AND CORRECTLY SET FORTH AND DESCRIBED IN THE
DRAWINGS AND SPECIFICATIONS.
8. COORDINATE WORK SCHEDULE THROUGH THE EPM. SCHEDULE WORK TO MINIMIZE DISRUPTION TO OCCUPANTS OF THE
BUILDING.
9. PROTECT EXISTING BUILDING ELEMENTS NOT INDICATED FOR REMOVAL FROM DEMOLITION AND CONSTRUCTION ACTIVITIES. DAMAGE
RESULTING FROM CONSTRUCTION ACTIVITIES SHALL BE REPAIRED TO ORIGINAL CONDITION.
10. FILL OPENINGS CREATED BY THE REMOVAL OF DUCTWORK, PIPING DEVICES, ETC. WITH MATERIAL EQUIVALENT TO THE ADJACENT
CONSTRUCTION.
11. ALL PENETRATIONS, BOTH NEW & EXISTING THROUGH FIRE RATED WALLS & FLOOR SLABS SHALL BE PROPERLY SEALED WITH AN APPROVED
& LISTED FIRE STOPPING MATERIAL. SUBMIT MANUFACTURER'S CATALOG DATA & INSTALLATION DETAILS FOR FIRE STOPPING TO THE
EPM FOR REVIEW & APPROVAL BY THE FIRE MARSHAL PRIOR TO INSTALLATION. EXISTING FLOOR SLABS ARE ASSUMED TO
BE XX-HOUR FIRE RATED CONSTRUCTION AND CORRIDOR WALLS ARE ASSUMED TO BE XX-HOUR FIRE RATED CONSTRUCTION.
12. SHUTDOWN OF UTILITIES FOR THE WORK SHALL BE PERFORMED ONLY BY USDA PERSONNEL, AND SHALL BE EXECUTED AFTER REGULAR
WORKING HOURS. REQUESTS FOR UTILITY SHUTDOWNS SHALL BE SUBMITTED TO THE EPM, IN WRITING, TWENTY-ONE (21)
DAYS PRIOR TO THE REQUIRED SHUTDOWN.
13. ON SITE STORAGE IS LIMITED TO THAT AVAILABLE WITHIN THE LIMITS OF CONSTRUCTION.
14. PROVIDE TEMPORARY BUMPERS AND DUST PROTECTION TO PROTECT PUBLIC AREAS FROM CONSTRUCTION ACTIVITIES. TEMPORARY
BARRIERS SHALL BE CONSTRUCTED OF TAPED GYPSUM DRYWALL ON METAL STUDS. IF AN APPROVED SPRINKLER SYSTEM IS NOT INSTALLED
IN ACCORDANCE WITH NFPA 241, SECTION 8.6.2, SEPARATE THE CONSTRUCTION SITE FROM OCCUPIED PORTIONS OF THE STRUCTURES BY
WALLS HAVING A 1-HOUR FIRE RESISTANCE RATING.
15. PERFORM EXCESSIVELY NOISY AND DISRUPTIVE CONSTRUCTION TASKS & UTILITY SHUTDOWNS (AS DEFINED BY THE EPM)
DURING NOISE HOURS (7:00PM - 7:30AM), OR ON WEEKENDS.
16. LAY OUT LOCATION OF ALL PARTITIONS AND BENCHES FOR APPROVAL BY THE EPM PRIOR TO THE ERECTION OF PARTITIONS.
17. CEILING CLOSE-IN, WALL CLOSE-IN, AND FINAL INSPECTION TO BE PERFORMED PRIOR TO OCCUPANCY. COORDINATE SCHEDULING OF
INSPECTIONS WITH CONSTRUCTION WORK.
18. CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE WITH ALL DISCIPLINES (FURNITURE, CIT, ETC) AND ALL VENDORS (MAGNET, RF, ETC).
19. CONTRACTOR SHALL ISOLATE CONSTRUCTION AREA FROM OTHER AREAS THROUGHOUT CONSTRUCTION.
GENERAL NOTES:
DETAIL NUMBER
DRAWING NUMBER
WHERE DETAIL IS
DRAWN
SECTION NUMBER
DRAWING NUMBER
WHERE DETAIL IS
DRAWN
ELEVATION NUMBER
DRAWING NUMBER
WHERE ELEVATION IS
DRAWN
REVISION NUMBER
REVISION CLOUD
WALL TYPE NUMBER,
SEE SHT. A-601
DOOR NUMBERROOM NUMBER
X
X
X
X
X
X
X
X X
XXX
XXXXXX
XX WINDOW NUMBER
AFF
X' - X" CEILING HEIGHT
CLAY TILE
TERRAZZO
BRICK
CONCRETE
PRECAST
CONCRETE
PLYWOOD
HARDWOOD
WOOD BLOCKING
SHIM
METAL
GYPSUM BOARD
& PLASTER
INSULATION
BATT
RIGID
ACOUSTICAL
INSULATION
TILE
U
S
D
A
-- USDA
NO. DATE BY DESCRIPTION
REVISIONS
Agricultural Research Service
DWG. NO.
SHEET OF
PROJECT MANAGER EPM
DESIGNER
CHECKED BY
DRAWN BY REAL PROPERTY
SAFETY & HEALTH
RPR
SPECIFICATION NO.
DATE
HLA CAROLYN WILLIAMS
LOUVIERE, STRATTON & YOKEL, LLC
8484 GEORGIA AVENUE, SUITE 650, SILVER
SPRING, MD 20910
(301) 588-1500
BURNS & McDONNELL
8201 NORMAN CENTER DR. SUITE 300
BLOOMINGTON, MN 55437
(952) 656-6003
G-002
ABBREVIATIONS & GENERAL NOTES
USDA CARL HAYDEN BEE RESEARCH CENTER - TUCSON, AZ
HLA
LEA
LEA
07/13/2021
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VEST VESTIBULE
VIF VERIFY IN FIELD
VIN VINYL
VWC VINYL WALL COVERING
W WIDE, WEST
W/ WITH
W/O WITHOUT
WB WHITEBOARD
WD WOOD
WDO WINDOW
WR WATER RESISTANT
LABORATORY ABBREVIATIONS
AL AIR LOCK
BP BACK PANEL
CORR CORROSIVES
CS CUP SINK
CYL CYLINDER
D DATA RECEPTACLE
DCRD DROP CORD
DI DEIONIZED WATER
ES EMERGENCY SHOWER
EW EYE WASH
FLAM FLAMMABLE
FPED FOOT PEDALS
GFI GROUND FAULT INTERRUPTER
HB HIGH BENCH
IVF ILLUMINATED FILM VIEWER
IVT INTRAVENEOUS TRACK
LB LOW BENCH
LN2 LIQUID NITROGEN
MHG MAGNAHELIC GAUGE
N2 GASEOUS NITROGEN
NARC NARCOTICS CABINET
O2 OXYGEN
PPE PERSONAL PROTECTION EQUIPMENT
PTL PASS THROUGH LOCKERS
PWF PURE WATER FIXTURE
RO REVERSE OSMOSIS
SG SPLASH GUARD
SHR SHOWER
UC UNDER COUNTER
VHP VAPROX HYDROGEN PEROXIDE
VPI VISUAL PRESSURE INDICATOR
LABORATORY EQUIPMENT ABBREVIATIONS
ATS ANIMAL TRANSFER STATION
BFLR BOTTLE FILLER
BSC BIOSAFETY CABINET
BSC A2.4 4' CLASS II, TYPE A2 BIOSAFETY CABINET
BSC A2.6 6' CLASS II, TYPE A2 BIOSAFETY CABINET
BSC B2.4 4' CLASS II, TYPE B2 BIOSAFETY CABINET
BSC B2.6 6' CLASS II, TYPE B2 BIOSAFETY CABINET
CFS CHLORINE FLUSH STATION
CIS CHLORINE INJECTION STATION
CRW CAGE @ RACK WASHER
EOXS ETHYLENE OXIDE STERILIZER
FBB FLUIDIZED BED BIOFILTER
ICE ICE MACHINE
INC INCUBATOR
PTC PASS THROUGH CABINET
PTC (V) VENTILATED PASS THROUGH CABINET
STER STERILIZER
LABORATORY UTILITY SERVICE ABBREVIATIONS
A AIR
AGV AIR, GAS, VACUUM
C CARBON
CA COMPRESSED AIR
CO2 CARBON DIOXIDE
CW COLD WATER
G GAS
HW HOT WATER
PW PURIFIED WATER
V VACUUM
HR HOUR
HT HEIGHT
ID INSIDE DIAMETER
INSL INSULATION
INST INSTALL(ATION)
INT INTERIOR
KBT KEYBOARD TRAY
L LENGTH
LB POUND
LG LARGE
LP LOW POINT
LU LEG UNIT
M METER
MAG MAGNETIC
MAT MATERIAL
MAX MAXIMUM
MDF MEDIUM DENSITY FIBERBOARD
MECH MECHANICAL
MED MEDIUM
MET METAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MOA MULTI OUTLET ASSEMBLY
MON MONITOR
MR MOISTURE RESISTANT
MTD MOUNTED
MTL METAL
N NITROGEN
N/A NOT APPLICABLE
NIC NOT IN CONTRACT
NO NUMBER
NP NEW PANEL
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED, CONTRACTOR INSTALLED
OFOI OWNER FURNISHED, OWNER INSTALLED
OH OPPOSITE HAND
ORD OVERFLOW ROOF DRAIN
ORIG ORIGINAL
P POWER RECEPTACLE
PART PARTICLE BOARD
PCST PRECAST
PLAM PLASTIC LAMINATE
PLUMB PLUMBING
PLYWD PLYWOOD
PNL(S) PANEL(S)
PRXR PROXIMITY READER
PT PRESSURE TREATED
PTD PAINT, PAINTED
PTN PARTITION
PWR POWER
RCP REFLECTED CEILING PLAN
REF REFERNECE
REFRIG REFRIGERATOR
REQ REQUIRED
RM ROOM
S SOUTH
SA SOUND ATTENUATION
SAB SOUND ATTENUATION BLANKET
SAL SALVAGE
SCWD SOLID CORE WOOD DOOR
SECT SECTION
SF SQUARE FOOT
SHF SHELF
SHT SHEET
SIM SIMILAR
SK SINK
SM SQUARE METER
SM SMALL
SMR SURFACE MOUNTED RACEWAY
SPEC SPECIFICATION(S)
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
STDP STAND PIPE
STL STEEL
STOR STORAGE
STR STRUCTURAL, STRUCTURE
SUSP SUSPENDED
SVF SEAMLESS VINYL FLOORING
TB TACK BOARD
TD TRENCH DRAIN
TEMP TEMPORARY
THK THICK
TO TOP OF
TOC TOP OF CURB
TOS TOP OF STEEL
TYP TYPICAL
UNO UNLESS NOTE OTHERWISE
UTY UTILITY
GENERAL ABBREVIATIONS
& AND
ADDN ADDITIONAL
ADMIN ADMINISTRATION
AFF ABOVE FINISHED FLOOR
ALT ALTERNATIVE
ALUM ALUMINUM
AP ACCESS PANEL
APPROX. APPROXIMATE
ARCH ARCHITECTURAL
ARW ACID RESISTANT WASTE
ATC ACOUSTICAL TILE CEILING
BD BOARD
BLDG BUILDING
BLKG BLOCKING
BM BEAM
BO BOTTOM OF
BOT BOTTOM
BRKT BRACKET
C CENTER LINE
CAB CABINET
CFCI CONTRACTOR FURNISHED, CONTRACTOR
INSTALLED
CJ CONTROL JOINT
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
COMP COMPRESSIBLE
CONC CONCRETE
CONST CONSTRUCTION
CONT CONTINUOUS, CONTINUATION
CONTRA CONTRACTOR
CPT CARPET
CT CERAMIC TILE
CTR CENTER
CTRTOP COUNTER TOP
DEMO DEMOLISH, DEMOLITION
DIA DIAMETER
DIM DIMENSION
DMB DRY MARKER BOARD
DN DOWN
DR DOOR
DTL DETAIL
DWG DRAWING(S)
E EAST
EA EACH
EJ EXPANSION JOINT
EL, ELEV ELEVATION
ELEC ELECTRICAL
EP ELECTRICAL PANEL
EQ EQUAL
EQUIP EQUIPMENT
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EXH EXHAUST
EXIST EXISTING
EXP EXPANSION
EXST EXISTING
EXT EXTERIOR
FAAP FIRE ALARM ANNUCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FAPS FIRE ALARM PULL STATION
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISHED FLOOR
FHC FIRE HOSE CABINET
FL FLASHING
FLR FLOOR
FP FILLER PANEL
FRT FIRE RETARDENT TREATED
FT FOOT, FEET
GA GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GFCI GOVERNMENT FURNISHED, CONTRACTOR
INSTALLED
GFGI GOVERNMENT FURNISHED, GOVERNMENT
INSTALLED
GH GROMMET HOLE
GL GLASS
GOV GOVERNMENT
GWB GYPSUM WALL BOARD
GYP BD GYPSUM WALL BOARD
H HIGH
HB HOSE BIB
HC HANDICAP
HDW HARDWARE
HDWD HARDWOOD
HEPA HIGH EFFICIENCY PARTICULATE AIR FILTER
HM HOLLOW METAL
HORIZ HORIZONTAL
HP HIGH POINT
ABBREVIATIONS:
L
NOTE: ALL ABBREVIATIONS MAY NOT BE USED SYMBOLS
MATERIALS
DEMO RCP LEGEND:
ATC CLNG, ETR REMOVE ATC CLNG
GWB CLNG, ETR REMOVE GWB
CLNG
LIGHT FIXTURES, ETR
REMOVE LIGHT
FIXTURES, SEE
ELEC
SUPPLY DIFFUSER,
ETR
REMOVE SUPPLY
DIFFUSER, SEE MEP
RETURN REGISTER,
ETR
REMOVE RETURN
REGISTER, SEE MEP
EXHAUST REGISTER,
ETR
REMOVE EXHAUST
REGISTER, SEE MEP
DOWNLIGHT, ETR
REMOVE
DOWNLIGHT, SEE
ELEC
A. REMOVE EXISTING NON-STRUCTURAL ELEMENTS WITHIN THE PROJECT SITE EXCEPT WHERE INDICATED BY NOTE OR SYMBOL AS EXISTING TO
REMAIN. SEE MEP DRAWINGS FOR EXTENT OF MEP DEMOLITION.
B. DEMOLITION DRAWING SHOWS GENERAL EXTENT OF REQUIRED WORK. REMOVE FIXTURES, FITTINGS, DEVICES, ETC. REQUIRED TO PREPARE THE
PROJECT SITE TO RECEIVE NEW WORK. SEE NEW WORK DRAWINGS FOR ADDITIONAL INFORMATION.
C. PERFORM SELECTIVE DEMOLITION FOR WORK SHOWN ELSEWHERE IN THE CONTRACT DOCUMENTS THAT REQUIRES DEMOLITION NOT SHOWN
ON DEMOLITION DRAWINGS. SUCH WORK SHALL INCLUDE, BUT IS NOT LIMITED TO THE FOLLOWING:
1. CORE DRILLING, CONC CUTTING AND REMOVAL OF WALLS AND SLABS AS NECESSARY TO INSTALL MECHANICAL, ELECTRICAL AND
PLUMBING WORK. REFER TO MEP DRAWINGS TO COORDINATE REQUIRED DEMOLITION WORK.
2. REMOVE & REINSTALL SUSPENDED ATC CEILING AS REQUIRED TO PERFORM MEP WORK. SEE MEP DRAWINGS FOR EXTENT OF ABOVE
CEILING WORK.
D. PHASE DEMOLITION AND PROVIDE TEMPORARY FACILITIES AS REQUIRED TO MAINTAIN MEP AND LIFE SAFETY SYSTEMS SERVING OCCUPIED
SPACES IN FULL OPERATING CONDITION. COORDINATE PLAN FOR MAINTENANCE OF THESE SYSTEMS WITH (EPM) ENGINEERING PROJECT
MANAGER.
E. COORDINATE REMOVAL OF TELEPHONES, PA SYSTEMS, INTERCOMS, DATA SYSTEMS, ETC. WITH EPM.
F. MAINTAIN BUILDING IN WEATHER TIGHT CONDITION.
G. PROVIDE TEMPORARY BRACING REQUIRED TO SUPPORT BUILDING ELEMENTS TO REMAIN AND REQUIRED TO MAINTAIN THE PROJECT SITE IN A
SAFE CONDITION.
H. WHERE REMOVAL OF FINISHES IS REQUIRED FROM SURFACES TO REMAIN AS SUBSTRATE FOR NEW FINISHES, USE REMOVAL METHODS WHICH
RESULT IN SUBSTRATE SUITABLE FOR NEW FINISHES.
I. ALL CONSTRUCTION DEBRIS (THIS INCLUDES RECYCLABLE AND NON RECYCLABLE) ARE TO BE RECYCLED THROUGH USDA'S CONSTRUCTION
DEBRIS AND SCRAP METAL DUMPSTERS
J. ALL LOOSE FURNISHINGS AND EQUIPMENT NOT SHOWN TO BE REMOVED SHALL BE TURNED OVER TO USDA. THE USDA'S LOCATION
SUPERVISOR RESERVES THE RIGHT TO SALVAGE ANY ITEM OF EQUIPMENT OR MATERIAL.
K. STORE SALVAGED MATERIALS INTENDED FOR REUSE IN PROJECT AREA AND PROTECT SAME FROM DAMAGE.
L. ALL ITEMS INDICATED WITH A DASHED LINE ARE TO BE REMOVED UNO.
M. MAINTAIN CLEAR ACCESS CORRIDORS TO BUILDING EXITS SERVING OCCUPIED AREAS OUTSIDE AREA OF DEMOLITION AT ALL TIMES.
N. ASBESTOS CONTAINING MATERIAL (ACM) MAY BE PRESENT IN THE FLOOR TILE MASTIC, METAL PARTITIONS, PIPE FITTINGS OF THE HOT, COLD, CHILLED WATER, AND STEAM SYSTEMS INCLUDING CONDENSATE LINES, SUPPLY AND RETURN WATER SYSTEMS PIPING INSULATION, AND HOT
WATER LINES. OTHER HAZARDOUS MATERIALS, INCLUDING BUT NOT LIMITED TO MERCURY RESIDUE IN PLUMBING DRAIN TRAPS, MERCURY IN
FLUORESCENT BULBS, PCB CONTAINING LIGHT BALLASTS, ETC MAY ALSO BE ENCOUNTERED. IF ACM OR OTHER HAZARDOUS MATERIALS ARE
FOUND IN PROJECT AREA & DISTURBED BY CONSTRUCTION ACTIVITIES. STOP WORK IMMEDIATELY & CONTACT USDA LOCATION SUPERVISOR.
GENERAL DEMOLITION NOTES:
1 2 3 4 5 6 7 8 9
A
B
C
D
E
LAB
LAB
STORAGE
019ELECTROPHYSIOLOGY
ADMIN
STORAGE
STORAGE
BREAK
ROOM
STORAGE
STORAGE
012A
LAB
TOILET
STORAGE
STORAGE
VESTIBULE
STAIRWELL
B-3
BOILER
ROOM
B-4
TELEPHONE
B-6
MECHANICAL
ROOM
B-2
FITNESS
ROOM
CORRIDOR
NKEY PLAN: 1/64" = 1'-0"
U
S
D
A
-- USDA
NO. DATE BY DESCRIPTION
REVISIONS
Agricultural Research Service
DWG. NO.
SHEET OF
PROJECT MANAGER EPM
DESIGNER
CHECKED BY
DRAWN BY REAL PROPERTY
SAFETY & HEALTH
RPR
SPECIFICATION NO.
DATE
HLA CAROLYN WILLIAMS
LOUVIERE, STRATTON & YOKEL, LLC
8484 GEORGIA AVENUE, SUITE 650, SILVER
SPRING, MD 20910
(301) 588-1500
BURNS & McDONNELL
8201 NORMAN CENTER DR. SUITE 300
BLOOMINGTON, MN 55437
(952) 656-6003
A-100
BASEMENT DEMOLITION REFLECTED CEILING PLAN
USDA CARL HAYDEN BEE RESEARCH CENTER - TUCSON, AZ
HLA
LEA
LEA
07/13/2021
DEMO RCP KEY NOTES: (TYPICAL )X
X DESIGNATE DEMOLITION ACTIVITY BY ROOM
1/8" = 1'-0"A-100
BASEMENT DEMOLITION RCP31
0'8' 4' 8' 16'
1/8" = 1' - 0"
01 REMOVE EXISTING ATC CEILING AND GRID. REPAIR AND PATCH TO
MATCH WALL AND SLAB WHERE REMOVAL OF CEILING AND GRID
CAUSES DAMAGE.
02 REMOVE EXISTING GYP CEILING AND SUPPORTS. REPAIR AND PATCH
TO MATCH WALL WHERE REMOVAL OF CEILING AND STUDS CAUSES
DAMAGE.
RCP GENERAL NOTES:
A. PROVIDE ACOUSTICAL TILE CEILINGS AS PER MANUFACTURERS RECOMMENDATIONS.
B. WHERE NEW CEILINGS ARE INDICATED, MEASURE EACH CEILING AREA AND ESTABLISH LAYOUTS TO BALANCE BORDER WIDTHS AT OPPOSITE
EDGES OF EACH CEILING. AVOID USE OF LESS THAN HALF THE WIDTH UNITS AT BORDERS, UNLESS NOTED OTHERWISE. SYMMETRICALLY LOCATE
GRID LAYOUTS IN EACH SPACE.
C. SUPPORT CEILING SUSPENSION SYSTEM FROM STRUCTURE ABOVE, NOT FROM DUCTWORK, METAL DECK, EQUIPMENT OR PIPING. SPACE
HANGERS NOT MORE THAN 6" FROM ENDS AND NOT MORE THAN 4'-0" FEET ON CENTERS ON RUNNERS.
D. INSTALL WALL MOLDINGS AT THE PERIMETER OF EACH ACOUSTICAL CEILING AREA AND AT LOCATIONS WHERE EDGES OF UNITS WOULD
OTHERWISE BE EXPOSED.
E. LOCATE SPRINKLER HEADS IN THE MIDDLE OF EACH CEILING PANEL.
F. CENTER ALL DIFFUSERS IN ACOUSTICAL PANELS.
G. THIS DRAWING INDICATES LOCATION OF CEILING MOUNTED AND CEILING PENETRATING ITEMS, FOR ADDITIONAL INFORMATION SEE MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS.
H. IN LABORATORIES, CENTER LIGHT FIXTURES ON EDGE OF BENCH.
I. CEILING GRID SHALL BE CENTERED IN ROOM UNLESS OTHERWISE NOTED.
RCP LEGEND:
ATC CLNG, ETR 2'-0" X 2'-0" ATC
CLNG
GWB CLNG, ETR GWB CLNG
LIGHT FIXTURES, ETR LIGHT FIXTURES,
SEE ELEC
SUPPLY DIFFUSER,
ETR
SUPPLY DIFFUSER,
SEE MEP
RETURN REGISTER,
ETR
RETURN REGISTER,
SEE MEP
EXHAUST REGISTER,
ETR
EXHAUST
REGISTER, SEE MEP
DOWNLIGHT, ETR DOWNLIGHT, SEE
ELEC
1 2 3 4 5 6 7 8 9
A
B
C
D
E
LAB
LAB
STORAGE
ELECTROPHYSIOLOGY
ADMIN
STORAGE
STORAGE
CORRIDOR
BREAK
ROOM
STORAGE
STORAGE
012A
LAB
TOILET
STORAGE
STORAGE
VESTIBULE
STAIRWELL
B-3
BOILER
ROOM
B-4
TELEPHONE
B-6
MECHANICAL
ROOM
B-2
FITNESS
ROOM
NKEY PLAN: 1/64" = 1'-0"
U
S
D
A
-- USDA
NO. DATE BY DESCRIPTION
REVISIONS
Agricultural Research Service
DWG. NO.
SHEET OF
PROJECT MANAGER EPM
DESIGNER
CHECKED BY
DRAWN BY REAL PROPERTY
SAFETY & HEALTH
RPR
SPECIFICATION NO.
DATE
HLA CAROLYN WILLIAMS
LOUVIERE, STRATTON & YOKEL, LLC
8484 GEORGIA AVENUE, SUITE 650, SILVER
SPRING, MD 20910
(301) 588-1500
BURNS & McDONNELL
8201 NORMAN CENTER DR. SUITE 300
BLOOMINGTON, MN 55437
(952) 656-6003
A-110
BASEMENT NEW WORK REFLECTED CEILING PLAN
USDA CARL HAYDEN BEE RESEARCH CENTER - TUCSON, AZ
HLA
LEA
LEA
07/13/2021
1/8" = 1'-0"A-110
BASEMENT NEW WORK RCP31
0'8' 4' 8' 16'
1/8" = 1' - 0"
01 INSTALL NEW ATC CEILING; CENTER GRID ON ROOM. SEE FINISH
SCHEDULE AND SPECIFICATIONS FOR MORE INFORMATION.
02 ALL CEILINGS ARE ETR ON THE GROUND FLOOR; NO CEILINGS WILL BE
DEMOLISHED OR ADDED AS PART OF NEW WORK.
03 INSTALL NEW LIGHT FIXTURE CENTERED ON TILE; SEE E-SERIES
DRAWINGS FOR MORE INFORMATION.
04 INSTALL NEW LIGHT FIXTURE CENTERED ON ROOM; SEE E-SERIES
DRAWINGS FOR MORE INFORMATION.
05 NEW MECHANICAL EQUIPMENT IN CEILING. SEE M-SERIES DRAWINGS
FOR MORE INFORMATION ON RETURN/SUPPLY AIR DUCTS AND
GRILLES, TYP.
KEY NOTES:(TYPICAL )X
X DESIGNATE NEW WORK ACTIVITY BY ROOM
1 2 3 4 5 6 7 8 9
A
B
C
D
E
STAIRWELL
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
STAIRWELL
LIBRARY
BREAK
ROOM
STUDENT
COMPUTER
RM
STUDENT
COMPUTER
RM
LABORATORY
LABORATORY
LABORATORY
LABORATORY
LIBRARY
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
PREPARATION
LABORATORY
LABORATORY
STORAGE
LABORATORY
LABORATORY
LABORATORY
ANNEX
LABORATORY
LABORATORY
GENERAL
OFFICE
OFFICE
DIRECTORS
OFFICE
SECRETARY
OFFICE
VESTIBULE
MEN'S
TOILET
WOMEN'S
TOILET
TOILET
CORRIDOR
LOBBY
C O
R R
ID
O
R
CORRIDOR
C O
R R
ID
O
R
VESTIBULE
TRANSFER
ROOM
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
JANITORS
CLOSET
VESTIBULE
UNISEX
TOILET
05 05
05 05
NKEY PLAN: 1/64" = 1'-0"
RCP GENERAL NOTES:
A. PROVIDE ACOUSTICAL TILE CEILINGS AS PER MANUFACTURERS RECOMMENDATIONS.
B. WHERE NEW CEILINGS ARE INDICATED, MEASURE EACH CEILING AREA AND ESTABLISH LAYOUTS TO BALANCE BORDER WIDTHS AT OPPOSITE
EDGES OF EACH CEILING. AVOID USE OF LESS THAN HALF THE WIDTH UNITS AT BORDERS, UNLESS NOTED OTHERWISE. SYMMETRICALLY LOCATE
GRID LAYOUTS IN EACH SPACE.
C. SUPPORT CEILING SUSPENSION SYSTEM FROM STRUCTURE ABOVE, NOT FROM DUCTWORK, METAL DECK, EQUIPMENT OR PIPING. SPACE
HANGERS NOT MORE THAN 6" FROM ENDS AND NOT MORE THAN 4'-0" FEET ON CENTERS ON RUNNERS.
D. INSTALL WALL MOLDINGS AT THE PERIMETER OF EACH ACOUSTICAL CEILING AREA AND AT LOCATIONS WHERE EDGES OF UNITS WOULD
OTHERWISE BE EXPOSED.
E. LOCATE SPRINKLER HEADS IN THE MIDDLE OF EACH CEILING PANEL.
F. CENTER ALL DIFFUSERS IN ACOUSTICAL PANELS.
G. THIS DRAWING INDICATES LOCATION OF CEILING MOUNTED AND CEILING PENETRATING ITEMS, FOR ADDITIONAL INFORMATION SEE MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS.
H. IN LABORATORIES, CENTER LIGHT FIXTURES ON EDGE OF BENCH.
I. CEILING GRID SHALL BE CENTERED IN ROOM UNLESS OTHERWISE NOTED.
RCP LEGEND:
ATC CLNG, ETR 2'-0" X 2'-0" ATC
CLNG
GWB CLNG, ETR GWB CLNG
LIGHT FIXTURES, ETR LIGHT FIXTURES,
SEE ELEC
SUPPLY DIFFUSER,
ETR
SUPPLY DIFFUSER,
SEE MEP
RETURN REGISTER,
ETR
RETURN REGISTER,
SEE MEP
EXHAUST REGISTER,
ETR
EXHAUST
REGISTER, SEE MEP
DOWNLIGHT, ETR DOWNLIGHT, SEE
ELEC
U
S
D
A
-- USDA
NO. DATE BY DESCRIPTION
REVISIONS
Agricultural Research Service
DWG. NO.
SHEET OF
PROJECT MANAGER EPM
DESIGNER
CHECKED BY
DRAWN BY REAL PROPERTY
SAFETY & HEALTH
RPR
SPECIFICATION NO.
DATE
HLA CAROLYN WILLIAMS
LOUVIERE, STRATTON & YOKEL, LLC
8484 GEORGIA AVENUE, SUITE 650, SILVER
SPRING, MD 20910
(301) 588-1500
BURNS & McDONNELL
8201 NORMAN CENTER DR. SUITE 300
BLOOMINGTON, MN 55437
(952) 656-6003
A-111
GROUND FLOOR NEW WORK REFLECTED CEILING PLAN
USDA CARL HAYDEN BEE RESEARCH CENTER - TUCSON, AZ
HLA
LEA
LEA
07/13/2021
1/8" = 1'-0"A-111
GROUND FLOOR NEW WORK RCP31
0'8' 4' 8' 16'
1/8" = 1' - 0"
KEY NOTES:(TYPICAL )X
X DESIGNATE NEW WORK ACTIVITY BY ROOM
01 INSTALL NEW ATC CEILING; CENTER GRID ON ROOM. SEE FINISH
SCHEDULE AND SPECIFICATIONS FOR MORE INFORMATION.
02 ALL CEILINGS ARE ETR ON THE GROUND FLOOR; NO CEILINGS WILL BE
DEMOLISHED OR ADDED AS PART OF NEW WORK.
03 INSTALL NEW LIGHT FIXTURE CENTERED ON TILE; SEE E-SERIES
DRAWINGS FOR MORE INFORMATION.
04 INSTALL NEW LIGHT FIXTURE CENTERED ON ROOM; SEE E-SERIES
DRAWINGS FOR MORE INFORMATION.
05 NEW MECHANICAL EQUIPMENT IN CEILING. SEE M-SERIES DRAWINGS
FOR MORE INFORMATION ON RETURN/SUPPLY AIR DUCTS AND
GRILLES, TYP.
NA NOT APPLICABLE
ATC-1 ACOUSTICAL TILE CEILING
FINISH LEGEND:
U
S
D
A
-- USDA
NO. DATE BY DESCRIPTION
REVISIONS
Agricultural Research Service
DWG. NO.
SHEET OF
PROJECT MANAGER EPM
DESIGNER
CHECKED BY
DRAWN BY REAL PROPERTY
SAFETY & HEALTH
RPR
SPECIFICATION NO.
DATE
HLA CAROLYN WILLIAMS
LOUVIERE, STRATTON & YOKEL, LLC
8484 GEORGIA AVENUE, SUITE 650, SILVER
SPRING, MD 20910
(301) 588-1500
BURNS & McDONNELL
8201 NORMAN CENTER DR. SUITE 300
BLOOMINGTON, MN 55437
(952) 656-6003
A-601
SCHEDULES
USDA CARL HAYDEN BEE RESEARCH CENTER - TUCSON, AZ
HLA
LEA
LEA
07/13/2021
ROOM NO ROOM NAME AREA BASE WALL FLOOR CEILING COMMENTS
019 STORAGE 51 SF NA NA NA ATC-1 PATCH TO MATCH WALLS AS NECESSARY TO REPAIR DAMAGE FROM DEMOLITION.
020 ELECTROPHYSIOLOGY 345 SF NA NA NA ATC-1 PATCH TO MATCH WALLS AS NECESSARY TO REPAIR DAMAGE FROM DEMOLITION.
021 ADMIN STORAGE 152 SF NA NA NA ATC-1 PATCH TO MATCH WALLS AS NECESSARY TO REPAIR DAMAGE FROM DEMOLITION.
016 STORAGE 140 SF NA NA NA ATC-1 PATCH TO MATCH WALLS AS NECESSARY TO REPAIR DAMAGE FROM DEMOLITION.
011 STORAGE 183 SF NA NA NA ATC-1 PATCH TO MATCH WALLS AS NECESSARY TO REPAIR DAMAGE FROM DEMOLITION.
012A STORAGE 176 SF NA NA NA ATC-1 PATCH TO MATCH WALLS AS NECESSARY TO REPAIR DAMAGE FROM DEMOLITION.
014 STORAGE 93 SF NA NA NA ATC-1 PATCH TO MATCH WALLS AS NECESSARY TO REPAIR DAMAGE FROM DEMOLITION.
ACOUSTICAL TILE CEILING
ARMSTRONG
ATC-1 ULTIMA HIGH NRC. TILE WHITE, GRID: WHITE
ROOM FINISH SCHEDULE
FINISH SCHEDULE
PIPE SYMBOLS
PIPE ELBOW
PIPE DOWN
PIPE UP
PIPE CONTINUATION
HVAC LEGEND
M
CONTROL DAMPER, MOTOR
OPERATED
MANUAL BALANCE DAMPER
BD
BACKDRAFT DAMPER
AD
AD
ACCESS DOOR (AD)
ACCESS PANEL (AP)
S
AD
S
DAMPERS:
FIRE (F) -
SMOKE (S) -
FIRE SMOKE (F/S) -
AD
SECURITY BARS
FLEXIBLE DUCT CONNECTION
RECTANGLUAR ELBOW WITH
TURNING VANES
RECTANGULAR TEE WITH
TURNING VANES
RECTANGULAR RADIUS ELBOW
R RISE IN RESPECT TO AIR-FLOW
D DROP IN RESPECT TO AIR-FLOW
SQUARE OR RECTANGULAR TO
ROUND TRANSITION
SUPPLY AIR OR OUTSIDE AIR
RECTANGULAR DUCT SECTION
RETURN AIR RECTANGULAR
DUCT SECTION
EXHAUST AIR RECTANGULAR
DUCT SECTION
ROUND FLEXIBLE DUCT
(5'-0" MAX LENGTH)
SQUARE OR RECTANGULAR
SUPPLY DIFFUSER
RETURN AIR DIFFUSER
EXHAUST AIR DIFFUSER
T THERMOSTAT
CO2 CARBON DIOXIDE SENSOR
H HUMIDISTAT
LINEAR SLOT DIFFUSER
VAV- VARIABLE AIR VOLUME
TERMINAL BOX
(3'-0") FINNED TUBE RADIATION.
LENGTH OF ELEMENT SHOWN
IN PARENTHESIS
ESS EMERGENCY SHUT-OFF SWITCH
M MOTOR
FCP FAN CONTROL PANEL
AIRFLOW ARROW
BA BREATHING AIR DROP
CA COMPRESSED AIR DROP
SUPPLY AIR OR OUTSIDE AIR
ROUND DUCT SECTION
RETURN AIR ROUND DUCT
SECTION
EXHAUST AIR ROUND DUCT
SECTION
DP DIFFERENTIAL PRESSURE
SENSOR
S STATIC PRESSURE SENSOR
OCC OCCUPANCY SENSOR
ROUND & RECTANGULAR DUCT
TAKEOFF
CO CARBON MONOXIDE SENSOR
PIPE LINE ACCESSORIES
3-WAY VALVE
2-WAY VALVE
ANGLE VALVE
AV
AUTOMATIC AIR VENT
ASSEMBLY
BFP
BACKFLOW PREVENTION
ASSEMBLY
BALANCING VALVE / CIRCUIT
SETTER
BALL VALVE
BLIND FLANGE
BUTTERFLY VALVE
CHECK VALVE
FLEX CONNECTION
FLOW ARROW
FM FLOW METER
GATE VALVE
GLOBE VALVE
HOSE GATE DRAIN VALVE
IF
INSULATING FLANGE
MV
MANUAL AIR VENT ASSEMBLY
- SEE SPECIFICATIONS FOR
APPROPRIATE VALVE TYPE
M METER
M MOTORIZED CONTROL VALVE
OS&Y
OUTSIDE SCREW & YOKE VALVE
PIPE WITH HEAT TRACE
PLUG VALVE
PRESSURE GUAGE
SELF CONTAINED PRESSURE
REDUCING (REGULATING)
VALVE
PUMP
REDUCER (CONCENTRIC)
RELIEF, SAFETY OR THERMAL
RELIEF VALVE
REMOVABLE CAP
REMOVABLE PLUG
S STRAINER
SUCTION DIFFUSER
TEST CONNECTION
THERMOMETER
UNION
Y-TYPE STRAINER
SRC SPRING RETURN CLOSED BALL
VALVE
PIPELINE ABBREVIATIONS
MECHANICAL ABBREVIATIONS GENERAL NOTES:
DETAIL / ENLARGED
CALLOUT SYMBOL
A
M-001
INDICATES
LIMITS OF
DETAIL/SECTION
DETAIL/SECTION
DESIGNATOR
SHEET WHERE
DETAIL/SECTION IS
SHOWN
DETAIL/SECTION TITLE
TITLE
A1
LOCATION WHERE
DETAIL / SECTION
IS SHOWN ON
SHEET
SECTION CUT SYMBOL
A
M-001
INDICATES PERSPECTIVE
AND LIMITS OF SECTION
SECTION
DESIGNATOR
DRAWING WHERE
SECTION IS SHOWN
CONSTRUCTION INTERFACE
DEMOLITION
EXISTING
NEW
EXISTING
(E) EXISTING
NEW
(D) DEMOLITION
AIR DISTRIBUTION DEVICE
IDENTIFICATION
AIR FLOW NECK SIZE
QUANTITY
SYSTEM TYPE SPEC. TYPE
SA-A
(2)175-8Ø
1. LEGEND IS GENERAL IN NATURE AND MAY INDICATE MORE INFORMATION THAN IS APPLICABLE TO PROJECT. SEE PLANS FOR
SPECIFIC SYMBOLS AND ABBREVIATIONS.
2. PROVIDE ALL MATERIALS, VALVES, HANGERS, ETC. AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE MECHANICAL SYSTEMS AS INDICATED ON THE DRAWINGS, AS SPECIFIED, AND AS REQUIRED BY CODE.
3. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS, CONTRACT DOCUMENTS, AND APPLICABLE CODES AND REGULATIONS.
4. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH STRUCTURAL, CIVIL, ELECTRICAL WORK, ETC., SHOWN ON OTHER
CONTRACT DOCUMENT DRAWINGS.
5. UNLESS OTHERWISE INDICATED MAINTAIN A MINIMUM OF 6'-8" CLEARANCE TO UNDERSIDE OF PIPES, CONDUITS, ETC., THROUGHOUT ACCESS ROUTES AND IN MECHANICAL ROOMS.
6. LOCATE ALL MECHANICAL EQUIPMENT FOR UNOBSTRUCTED ACCESS TO UNIT ACCESS PANELS, CONTROLS, AND VALVING.
7. VERIFY DIMENSIONS AND CONNECTION SIZE WITH FURNISHED EQUIPMENT.
8. ALL ELEVATIONS ARE ABOVE FINISHED FLOOR TO BOTTOM OF DUCT, PIPE, OR PIPE INSULATION UNLESS NOTED OTHERWISE.
9. ALL DUCTWORK DIMENSIONS REFER TO INSIDE CLEAR AREA.
10. DUCT STATIC PRESSURE CLASSIFICATION: UNLESS OTHERWISE INDICATED, CONSTRUCT DUCTS ON THE DISCHARGE SIDE OF FANS AND ACU TO HAVE 1.0 IN. W.C. POSITIVE PRESSURE AND DUCTS ON THE INLET SIDE OF EQUIPMENT TO HAVE 1.0 IN. W.C.
NEGATIVE PRESSURE CLASSIFICATIONS. DUCTS ON OUTLET SIDE OF AHU'S SHALL HAVE 3.0 INCH POSITIVE PRESSURE CLASS
DUCT.
11. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR CREATION OF MECHANICAL COORDINATION DRAWINGS BASED ON ACTUAL
FIELD CONDITIONS PRIOR TO DEMOLITION AND NEW WORK.
12. COORDINATE ALL WALL AND ROOF PENETRATIONS WITH STRUCTURAL AND ARCHITECTURAL PLANS.
13. INSTALL TEMPERATURE CONTROLS AT 48" ABOVE FINISHED FLOOR AND COORDINATE WITH OTHER DEVICES LOCATED ON WALLS.
COORDINATE WITH ARCHITECTURAL WALL FINISHES.
14. LABORATORY OCCUPANCY SENSORS SHALL BE PROVIDED BY DIVISION 23. WIRE OCCUPANCY SENSOR BACK TO EXISTING DELTA
CONTROLLER.
15. UNLESS NOTED OTHERWISE, THE MECHANICAL CONTRACTOR SHALL REMOVE FROM THE PROPERTY ALL PIPE AND EQUIPMENT HANGERS, SUPPORTS, STRAPS, STANDS, ETC., ASSOCIATED WITH ANY WORK IDENTIFIED TO BE DEMOLISHED OR REMOVED IN THESE PLANS. THE MECHANICAL CONTRACTOR SHALL PROPERLY DISPOSE OF ALL EQUIPMENT AND MATERIALS PER FEDERAL
AND LOCAL LAWS.
16. CONTRACTOR SHALL AIR BALANCE ALL GRILLES TO CFM'S SHOWN ON PLANS.
17. MOUNT ALL OVERHEAD MECHANICAL EQUIPMENT AND FIXTURES WEIGHING 31 POUNDS OR MORE TO SUPPORTS THAT SHALL RESIST FORCES OF 0.5 TIMES THE EQUIPMENT WEIGHT IN ANY HORIZONTAL DIRECTION AND 1.5 TIMES THE EQUIPMENT WEIGHT IN
THE DOWNWARD DIRECTION.
BLWDN BLOWDOWN
CD CONDENSATE DRAIN
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CR CONDENSATE RETURN
CT CHEMICAL TREATMENT
CTB COOLING TOWER BLOWDOWN
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
D DEMOLITION
DI DEIONIZED WATER
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
HPS HIGH PRESSURE STEAM
HWR HOT WATER RETURN
HWS HOT WATER SUPPLY
LPS LOW PRESSURE STEAM
MPS MEDIUM PRESSURE STEAM
MW MAKEUP WATER (AFTER BACKFLOW
PREVENTER)
N NITROGEN
NG NATURAL GAS
O OXYGEN
PCR PUMPED CONDENSATE RETURN
V VACUUM
IH INFRARED HEATER
IN. W.C INCHES WATER COLUMN
L LOUVER
LAT LEAVING AIR TEMPERATURE
LR LONG RADIUS
LWT LEAVING WATER TEMPERATURE
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAU MAKEUP AIR UNIT
MFR MANUFACTURER
MJ MECHANICAL JOINT
MW MAKE-UP WATER (AFTER BACKFLOW
PREVENTER)
NC NORMALLY CLOSED (FAIL POSITION)
NG NATURAL GAS
NO NORMALLY OPEN (FAIL POSITION)
OA OUTSIDE AIR
OB OPPOSED BLADE
OD OVERFLOW DRAIN
PB PARALLEL BLADE
PCW PROCESS COLD WATER
PFX PLATE AND FRAME HEAT EXCHANGER
PSIA POUNDS PER SQUARE INCH ABSOLUTE
PSIG POUNDS PER SQUARE INCH GAUGE
RA RETURN AIR
RED REDUCER-REDUCING
RG REFRIGERANT HOT GAS DISCHARGE
RL REFRIGERANT LIQUID
RMJ RESTRAINED MECHANICAL JOINT
RS REFRIGERANT SUCTION
SA SUPPLY AIR
SCH SCHEDULE
SCR SPRING RETURN CLOSED
SHR SHORT RADIUS
SP STATIC PRESSURE SENSOR
SR SUPPLY REGISTER
ST STEAM TRAP
STM STEAM
SW SOCKET WELD
TA TRANSFER AIR
TOA TREATED OUTSIDE AIR
TOC TOP OF CONCRETE
TOD TOP OF DUCT
TOS TOP OF STEEL
UH UNIT HEATER
V VENT
VAV VARIABLE AIR VOLUME
VFD VARIABLE FREQUENCY DRIVE
VRF VARIABLE REFRIGERANT FLOW
WB WET BULB
WE WELD END
WN WELD NECK
(D) DEMOLISHED
(E) EXISTING
12"Ø ROUND DUCT DIMENSION
24x12 RECTANGULAR DUCT DIMENSION (INCHES)
ACU AIR CONDITIONING UNIT
AFF ABOVE FINISHED FLOOR
AFMS AIR FLOW MEASURING STATION
AHU AIR HANDLING UNIT
ARF ABOVE RAISED FLOOR
AS AIR SEPARATOR
BBO BOILER BLOW-OFF
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BP BOOSTER PUMP
BS BRANCH SELECTOR (VRF SYSTEM)
CF CEILING FAN
CFM CUBIC FEET PER MINUTE
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CL CENTER LINE OF PIPE ELEVATION
CONC CONCENTRIC
COND COOLING COIL CONDENSATE DRAIN
CRAC COMPUTER ROOM AIR CONDITIONER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
DB DRY BULB
DH DEHUMIDIFIER
DN DOWN
DRG DIFFUSER, REGISTER, GRILLE
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EG EXHAUST GRILLE
EL ELEVATION
ELL ELBOW
EMCS ENERGY MANAGEMENT CONTROL SYSTEM
ER AUST REGISTER
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
EWT ENTERING WATER TEMPERATURE
FCU FAN COIL UNIT
FD FEEDWATER
FF FLAT FACED
FO FLAT OVAL
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
HWB HEATING HOT WATER BOILER
HWP HEATING HOT WATER PUMP
HWR HEATING HOT WATER RETURN
HWS HEATING HOT WATER SUPPLY
I.E. INVERT ELEVATION
IA INSTRUMENT AIR
U
S
D
A
-- USDA
NO. DATE BY DESCRIPTION
REVISIONS
Agricultural Research Service
DWG. NO.
SHEET OF
PROJECT MANAGER EPM
DESIGNER
CHECKED BY
DRAWN BY REAL PROPERTY
SAFETY & HEALTH
RPR
SPECIFICATION NO.
DATE
R.DARNELL
LOUVIERE, STRATTON & YOKEL, LLC
8484 GEORGIA AVENUE, SUITE 650, SILVER
SPRING, MD 20910
(301) 588-1500
BURNS & McDONNELL
8201 NORMAN CENTER DR. SUITE 500
BLOOMINGTON, MN 55437
(952) 656-6003
FINAL SUBMISSION07/13/21
CAROLYN WILLIAMS
RLP
M-001
MECHANICAL NOTES, LEGEND, SYMBOLS & ABBREVIATIONS
USDA CARL HAYDEN BEE RESEARCH CENTER - TUCSON, AZ
A.GIANPETRO
M.CAIN
R.PEARSON
07/13/2021
3 4 5 6 7 8 9
B
C
D
E
72"x14" (E) RA
42"x14" (E) RA
7"x15" (E) RA
15"x26" (E) RA
10"x7" (E) RA
10"x6" (E) SA
15"x10" (E) SA
24"x13" (E) SA
12"x12" (E) SA
26"x15" (E) RA
26"x15" (E) RA
32"x12" (E) SA
8"x10" (E) SA
14"x10" (E) RA
10"x8" (E) RA
12"x8" (E) RA
15"x26" (E) RA UP
15"x12" (E) SA UP
24"x13" (E) SA UP
26"x15" (E) RA UP8"x10" (E) SA UP
MECHANICAL
ROOM
B-2
BOILER ROOM
B-4
TELEPHONE
B-6
STAIRWELL
B-3
FITNESS ROOM
STORAGE
ADMIN STORAGE
ELECTROPHYSIOLOGY
LAB
STORAGE
LAB
STORAGE
LAB
TOILET
STORAGE
STORAGE
CORRIDOR
BREAK ROOM
STORAGE
012A
VESTIBULE
(D) FCU
18"x18" RA
20"x12"
20"x12"
(D) AC UNIT
"x
(E
R A
(TYP. 11)
24"x20" TA
(D)12"x12"EA
GRILLE SA
CAP 10"x10" OA UP
RA
24"x12" RA
(D) FCU
(D) FCU
(D) FCU
(D) 8x8 EA GRILLE
(D) 8x8 SA GRILLE
(D) 8x8 RA GRILLE
24"x18" (E)
SA GRILLE
(E) 24"x24" RA
24"x24" (E) SA
(D) 12x12 RA GRILLE
48"x12" (E) RA GRILLE
(D) FCU
48"x24" (E) RA GRILLE (TYP 4)15"x26" (E) RA
80"x12" (E) OA
(E) AC-1
(E) AHU-1
(E) AC-2
24"x30" (E) OA
U
S
D
A
-- USDA
NO. DATE BY DESCRIPTION
REVISIONS
Agricultural Research Service
DWG. NO.
SHEET OF
PROJECT MANAGER EPM
DESIGNER
CHECKED BY
DRAWN BY REAL PROPERTY
SAFETY & HEALTH
RPR
SPECIFICATION NO.
DATE
R.DARNELL
LOUVIERE, STRATTON & YOKEL, LLC
8484 GEORGIA AVENUE, SUITE 650, SILVER
SPRING, MD 20910
(301) 588-1500
BURNS & McDONNELL
8201 NORMAN CENTER DR. SUITE 500
BLOOMINGTON, MN 55437
(952) 656-6003
FINAL SUBMISSION07/13/21
CAROLYN WILLIAMS
RLP
MD100
MECHANICAL DEMOLITION PLAN - BASEMENT
USDA CARL HAYDEN BEE RESEARCH CENTER - TUCSON, AZ
A.GIANPETRO
M.CAIN
R.PEARSON
07/13/2021
1/8" = 1'-0"1
MECHANICAL DEMOLITION PLAN -
BASEMENT
GENERAL NOTES:
KEYED NOTES:
1. FOR MECHANICAL GENERAL NOTES AND SYMBOLS,
SEE M-001.
2. CONTRACTOR SHALL FIELD VERIFY EXISTING
UTILITIES (DUCTWORK, PIPING, STRUCTURE,
ELECTRICAL, ETC.) ABOVE CEILING PRIOR TO
DEMOLITION AND NEW WORK TO COORDINATE
FINAL LOCATION OF NEW DUCTWORK, PIPING, AND
EQUIPMENT. NEW ROUTING SHOWN ON PLAN IS
PREFERRED ROUTING ONLY AND MAY BE
RELOCATED TO COORDINATE WITH EXISTING
CONDITIONS. RELOCATING EXISTING OR NEW
DUCTWORK/PIPING/EQUIPMENT FROM WHAT IS
SHOWN SHALL BE A NO-COST CHANGE TO THE
GOVERNMENT.
8'4' 16'0
SCALE: 1/8"=1'-0"
1 DEMOLISH EXISTING HVAC IN THIS ROOM.
2 DEMOLISH FAN COIL UNIT BELOW CEILING AND
ALL ASSOCIATED DUCTWORK, GRILLES, AND
DRAIN PIPING. SEE ARCH DWGS FOR CEILING
PATCHING AND REPAIR.
3 DEMOLISH EXISTING SIDEWALL GRILLES AND
ASSOCIATED DUCTWORK. SEE ARCH DWGS FOR
WALL PATCHING AND REPAIR.
4 DEMOLISH AC UNIT MOUNTED IN WALL. SEE
ARCH DWGS FOR WALL PATCHING AND REPAIR.
DEMOLISH FAN COIL UNIT ABOVE CEILING AND
ALL ASSOCIATED DUCTWORK, GRILLES, AND
DRAIN PIPING.
DEMOLISH FAN COIL UNIT ABOVE CEILING AND
ALL ASSOCIATED DUCTWORK AND DRAIN
PIPING. CEILING MOUNTED DIFFUSERS AND
GRILLES TO REMAIN.
TRUE NORTH
C
D
E
16"x16" (E) EA
16"x16" (E) EA 16"x16" (E) EA
15"x12" (E) SA
30"x10" (E) SA
16"x9" (E) SA
16"x16" (E) RA
14"x16" (E) SA
16"ø (E) RA UP
8"x10" (E) SA24"x16" (E) SA
16"x16" (E) EA
16"ø (E) EA UP
LABORATORY
LABORATORY
LABORATORY
LABORATORY
STUDENT
COMPUTER RM
STUDENT
COMPUTER RM
BREAK ROOM
LABORATORY
LABORATORY
LABORATORY
LABORATORY
STORAGE
LABORATORY
"ø
E
S
A 18"x14" (E) SA
THRU ROOF
(TYP ALL HOODS)
TO FCU-7
ON ROOF
14"x16" (E) SA UP
TO FCU-7 ON
ROOF
24"x24" (E) EA UP
THRU ROOF
24"x13" (E) SA
16"x16" (E) RA DN
THRU FLOOR
16"x16" (E) EA UP
THRU ROOF
16"x16" (E) EA
18"x18" (E) EA 18"x18" (E) EA
16"ø (E) EA UP16"ø (E) EA UP
T T T T T
TTT
LABORATORY
T
28"x14" (E) OA UP
1 1
2 (D) ACU-3
(D) ACU-2
(D) ACU-1
(D) ACU-4
(D) ACU-5
(E) ACU-10 (D) ACU-6
(D) ACU-8
(D) ACU-9
16"x14" (E) OA UP
THRU ROOF TO
REMAIN (TYP ALL)
T
U
S
D
A
-- USDA
NO. DATE BY DESCRIPTION
REVISIONS
Agricultural Research Service
DWG. NO.
SHEET OF
PROJECT MANAGER EPM
DESIGNER
CHECKED BY
DRAWN BY REAL PROPERTY
SAFETY & HEALTH
RPR
SPECIFICATION NO.
DATE
R.DARNELL
LOUVIERE, STRATTON & YOKEL, LLC
8484 GEORGIA AVENUE, SUITE 650, SILVER
SPRING, MD 20910
(301) 588-1500
BURNS & McDONNELL
8201 NORMAN CENTER DR. SUITE 500
BLOOMINGTON, MN 55437
(952) 656-6003
FINAL SUBMISSION07/13/21
CAROLYN WILLIAMS
RLP
MD101
MECHANICAL DEMOLITION PLAN - FIRST FLOOR
USDA CARL HAYDEN BEE RESEARCH CENTER - TUCSON, AZ
A.GIANPETRO
M.CAIN
R.PEARSON
07/13/2021
1/8" = 1'-0"1
MECHANICAL DEMOLITION PLAN - FIRST
FLOOR
GENERAL NOTES:
KEYED NOTES:
8'4' 16'0
SCALE: 1/8"=1'-0"
1 DEMOLISH THERMOSTAT AND CONTROL WIRING.
SEE M-101 FOR NEW WORK.
2 DEMOLISH FAN COIL UNIT IN IT'S ENTIRETY.
DEMOLISH INTAKE DUCTWORK TO 16"X14" UP
AND TEMPORARILY CAP FOR CONNECTION TO
DUCTWORK IN NEW WORK. SEE M-101 FOR NEW
WORK.
3 EXISTING EA DUCTWORK SERVING FUME HOOD
AND LABORATORY TO REMAIN.
1. FOR MECHANICAL GENERAL NOTES AND SYMBOLS,
SEE M-001.
2. CONTRACTOR SHALL FIELD VERIFY EXISTING
UTILITIES (DUCTWORK, PIPING, STRUCTURE,
ELECTRICAL, ETC.) PRIOR TO DEMOLITION AND
NEW WORK TO COORDINATE FINAL LOCATION OF
NEW DUCTWORK, PIPING, AND EQUIPMENT. NEW
ROUTING SHOWN ON PLAN IS PREFERRED
ROUTING ONLY AND MAY BE RELOCATED TO
COORDINATE WITH EXISTING CONDITIONS.
RELOCATING EXISTING OR NEW
DUCTWORK/PIPING/EQUIPMENT FROM WHAT IS
SHOWN SHALL BE A NO-COST CHANGE TO THE
GOVERNMENT.
3 4 5 6 7 8 9
A
B
C
D
E
MECHANICAL
ROOM
B-2
STAIRWELL
B-3
BOILER ROOM
B-4
TELEPHONE
B-6
STORAGE
STORAGE
LAB
TOILET
VESTIBULE
STORAGE
012A
STORAGE
BREAK ROOM
CORRIDOR
LAB
ADMIN STORAGE
021STORAGE
FITNESS ROOM
ELECTROPHYSIOLOGY
LAB
STORAGE
(D) FCU
(D) FCU
(D) FCU
(D) FCU
(D) FCU
(D) FCU
3/4" (E) HWS
1" (E) HWS
1 1/4" (E) HWS
1 1/4" (E) HWS
2" (E) CHWR
3" (E) CHWR
1 1/2" (E) HWR
1 1/2" (E) HWR
2 1/2" (E) CHWR
2" (E) CHWS
2" (E) CHWS
1" (E) CHWR
1" (E) CHWS
1" (E) HWR
1" (E) HWS
1 1/4" (E) HWS UP
2" (E) CHWR UP
2" (E) CHWS UP
1 1/2" (E) HWR UP
1 1/4" (E) HWS UP
U
S
D
A
-- USDA
NO. DATE BY DESCRIPTION
REVISIONS
Agricultural Research Service
DWG. NO.
SHEET OF
PROJECT MANAGER EPM
DESIGNER
CHECKED BY
DRAWN BY REAL PROPERTY
SAFETY & HEALTH
RPR
SPECIFICATION NO.
DATE
R.DARNELL
LOUVIERE, STRATTON & YOKEL, LLC
8484 GEORGIA AVENUE, SUITE 650, SILVER
SPRING, MD 20910
(301) 588-1500
BURNS & McDONNELL
8201 NORMAN CENTER DR. SUITE 500
BLOOMINGTON, MN 55437
(952) 656-6003
FINAL SUBMISSION07/13/21
CAROLYN WILLIAMS
RLP
MD200
MECHANICAL PIPING DEMOLITION - BASEMENT
USDA CARL HAYDEN BEE RESEARCH CENTER - TUCSON, AZ
A.GIANPETRO
R.PEARSON
R.PEARSON
07/13/2021
1/8" = 1'-0"1
MECHANICAL PIPING DEMOLITION -
BASEMENT
GENERAL NOTES:
KEYED NOTES:
1. FOR MECHANICAL GENERAL NOTES AND SYMBOLS,
SEE M-001.
2. CONTRACTOR SHALL FIELD VERIFY EXISTING
UTILITIES (DUCTWORK, PIPING, STRUCTURE,
ELECTRICAL, ETC.) ABOVE CEILING PRIOR TO
DEMOLITION AND NEW WORK TO COORDINATE
FINAL LOCATION OF NEW DUCTWORK, PIPING, AND
EQUIPMENT. NEW ROUTING SHOWN ON PLAN IS
PREFERRED ROUTING ONLY AND MAY BE
RELOCATED TO COORDINATE WITH EXISTING
CONDITIONS. RELOCATING EXISTING OR NEW
DUCTWORK/PIPING/EQUIPMENT FROM WHAT IS
SHOWN SHALL BE A NO-COST CHANGE TO THE
GOVERNMENT.
TRUE NORTH
DEMOLISH EXISTING HVAC IN THIS ROOM AND
CAP PIPING.
DEMOLISH FAN COIL UNIT BELOW CEILING AND
ALL ASSOCIATED PIPING BACK TO MAIN AND
CAP. SEE ARCH DWGS FOR CEILING PATCHING
AND REPAIR. DEMOLISH CONDENSATE DRAIN
PIPING.
DEMOLISH FAN COIL UNIT ABOVE CEILING AND
ALL ASSOCIATED PIPING BACK TO MAIN AND
CAP. DEMOLISH CONDENSATE DRAIN PIPING.
DEMOLISH FAN COIL UNIT ABOVE CEILING.
DEMOLISH UNIT PIPING CONNECTIONS AND
TEMPORARILY CAP PIPING FOR CONNECTION TO
NEW FAN COIL UNIT, ACU-12. DEMOLISH
CONDENSATE DRAIN PIPING.
8'4' 16'0
SCALE: 1/8"=1'-0"
2 3 4 5 6 7 8
C
D
MD202
LABORATORY
LABORATORY
LABORATORY
LABORATORY
STORAGE
LABORATORY
LABORATORY
CORRIDOR
STUDENT
COMPUTER RM
BREAK ROOM
STUDENT
COMPUTER RM
LABORATORY
LABORATORY
LABORATORY
LABORATORY
PREPARATION
TRANSFER ROOM
U
S
D
A
-- USDA
NO. DATE BY DESCRIPTION
REVISIONS
Agricultural Research Service
DWG. NO.
SHEET OF
PROJECT MANAGER EPM
DESIGNER
CHECKED BY
DRAWN BY REAL PROPERTY
SAFETY & HEALTH
RPR
SPECIFICATION NO.
DATE
R.DARNELL
LOUVIERE, STRATTON & YOKEL, LLC
8484 GEORGIA AVENUE, SUITE 650, SILVER
SPRING, MD 20910
(301) 588-1500
BURNS & McDONNELL
8201 NORMAN CENTER DR. SUITE 500
BLOOMINGTON, MN 55437
(952) 656-6003
FINAL SUBMISSION07/13/21
CAROLYN WILLIAMS
RLP
MD201
MECHANICAL PIPING DEMOLITION - FIRST FLOOR
USDA CARL HAYDEN BEE RESEARCH CENTER - TUCSON, AZ
A.GIANPETRO
M.CAIN
R.PEARSON
07/13/2021
GENERAL NOTES:
1/8" = 1'-0"1
MECHANICAL PIPING DEMOLITION - FIRST
FLOOR
8'4' 16'0
SCALE: 1/8"=1'-0"
1. FOR MECHANICAL GENERAL NOTES AND SYMBOLS,
SEE M-001.
2. CONTRACTOR SHALL FIELD VERIFY EXISTING
UTILITIES (DUCTWORK, PIPING, STRUCTURE,
ELECTRICAL, ETC.) PRIOR TO DEMOLITION AND
NEW WORK TO COORDINATE FINAL LOCATION OF
NEW DUCTWORK, PIPING, AND EQUIPMENT. NEW
ROUTING SHOWN ON PLAN IS PREFERRED
ROUTING ONLY AND MAY BE RELOCATED TO
COORDINATE WITH EXISTING CONDITIONS.
RELOCATING EXISTING OR NEW
DUCTWORK/PIPING/EQUIPMENT FROM WHAT IS
SHOWN SHALL BE A NO-COST CHANGE TO THE
4 5 6 7
C
(D) 1/2" HWS
(D) 1/2" HWR
(D) 1" CHWS
(D) 1" CHWR
(D) 1/2" HWS
(D) 1/2" HWR
(D) 1" CHWS
(D) 1" CHWR
(D) ACU-4
(D) 1/2" HWS
(D) 1/2" HWR
(D) 1" CHWS
(D) 1" CHWR
(D) 1/2" HWS
(D) 1/2" HWR
(D) 1" CHWS
(D) 1" CHWR
(D) 1/2" HWS
(D) 1/2" HWR
(D) 1" CHWS
(D) 1" CHWR
(D) 1/2" HWS
(D) 1/2" HWR
(D) 1" CHWS
(D) 1" CHWR
(D) 1/2" HWS
(D) 1/2" HWR
(D) 1" CHWS
(D) 1" CHWR
(D) 1/2" HWS
(D) 1/2" HWR
(D) 1" CHWS
(D) 1" CHWR
1/2" (E) HWS
1/2" (E) HWR
1" (E) CHWS
1" (E) CHWR
1 1
(D) ACU-3(D) ACU-2(D) ACU-1 (D) ACU-5
(D) ACU-6(D) ACU-8(D) ACU-9(E) ACU-10
3/4" (E) HWS UP
(TYP ALL)
3/4" (E) HWR UP
(TYP ALL)
1 1/2" (E) CHWS UP
(TYP ALL)
1 1/2" (E) CHWR UP
(TYP ALL)
LABORATORY
LABORATORY
LABORATORY
LABORATORY
LABORATORY
LABORATORY
ANNEX
LABORATORY
STUDENT
COMPUTER RM
BREAK ROOM
LABORATORY
U
S
D
A
-- USDA
NO. DATE BY DESCRIPTION
REVISIONS
Agricultural Research Service
DWG. NO.
SHEET OF
PROJECT MANAGER EPM
DESIGNER
CHECKED BY
DRAWN BY REAL PROPERTY
SAFETY & HEALTH
RPR
SPECIFICATION NO.
DATE
R.DARNELL
LOUVIERE, STRATTON & YOKEL, LLC
8484 GEORGIA AVENUE, SUITE 650, SILVER
SPRING, MD 20910
(301) 588-1500
BURNS & McDONNELL
8201 NORMAN CENTER DR. SUITE 500
BLOOMINGTON, MN 55437
(952) 656-6003
FINAL SUBMISSION07/13/21
CAROLYN WILLIAMS
RLP
MD202
MECHANICAL ENLARGED PIPING DEMOLITION - FIRST FLOOR
USDA CARL HAYDEN BEE RESEARCH CENTER - TUCSON, AZ
A.GIANPETRO
M.CAIN
R.PEARSON
07/13/2021
GENERAL NOTES:
KEYED NOTES:
1/4" = 1'-0"1
MECHANICAL ENLARGED PIPING
DEMOLITION - FIRST FLOOR
0 2' 4' 8'
SCALE: 1/4" = 1'-0"
1 DEMOLISH CHWS, CHWR, HWS, AND HWR PIPING
AND VALVES BACK TO WALL. PROVIDE NEW
ISOLATION VALVE AND TEMPORARILY CAP FOR
CONNECTION TO NEW WORK. DEMOLISH
CONDENSATE DRAIN PIPING TO FLOOR AND
TEMPORARILY CAP FOR CONNECTION TO NEW
WORK. SEE MP101.
EXISTING CHW AND HHW PIPE RISERS FROM
BASEMENT TO FIRST FLOOR LABS TO REMAIN.
EXISTING TO REMAIN.
1. FOR MECHANICAL GENERAL NOTES AND SYMBOLS,
SEE M-001.
2. CONTRACTOR SHALL FIELD VERIFY EXISTING
UTILITIES (DUCTWORK, PIPING, STRUCTURE,
ELECTRICAL, ETC.) PRIOR TO DEMOLITION AND
NEW WORK TO COORDINATE FINAL LOCATION OF
NEW DUCTWORK, PIPING, AND EQUIPMENT. NEW
ROUTING SHOWN ON PLAN IS PREFERRED
ROUTING ONLY AND MAY BE RELOCATED TO
COORDINATE WITH EXISTING CONDITIONS.
RELOCATING EXISTING OR NEW
DUCTWORK/PIPING/EQUIPMENT FROM WHAT IS
SHOWN SHALL BE A NO-COST CHANGE TO THE
GOVERNMENT.
TRUE NORTH
(TYP)
S D
3 4 5 6 7 8 9
B
C
D
E
72"x14" (E) RA
42"x14" (E) RA
7"x15" (E) RA
15"x26" (E) RA
10"x7" (E) RA
10"x6" (E) SA 15"x10" (E) SA
24"x13" (E) SA
12"x12" (E) SA
26"x15" (E) RA
26"x15" (E) RA
32"x12" (E) SA
8"x10" (E) SA
14"x10" (E) RA
10"x8" (E) RA
12"x8" (E) RA
15"x26" (E) RA UP
15"x12" (E) SA UP
24"x13" (E) SA UP
26"x15" (E) RA UP
8"x10" (E) SA UP
MECHANICAL
ROOM
B-2
BOILER ROOM
B-4
TELEPHONE
B-6
STAIRWELL
B-3
FITNESS ROOM
STORAGE
ADMIN STORAGE
ELECTROPHYSIOLOGY
LAB
STORAGE
LAB
STORAGE
011LAB
TOILET
STORAGE
STORAGE
CORRIDOR
BREAK ROOM
STORAGE
012A
VESTIBULE
"x
(E
R A
T
ACU-11
0-6"ø
(E) SA-A
SA-
265-20"x16"
(TYP 10)
295-8"ø
SA-A
75-6"ø
SA-A
115-6"ø
SA-A
115-6"ø
SA-A
50-6"ø
SA-A
115-6"ø
SA-A
115-6"ø
SA-A
145-6"ø
SA-A
185-6"ø
SA-A
(E) 24"x24" RA
75-6"ø
SA-A
50-6"ø
SA-A
ACU-12
48"x24" (E) RA
(TYP 2)
48"x24" (E) RA
(TYP 2)
10"ø OA
16"x12" RA 16"x12" RA
12"x12" RA
8"x8" RA
"x
R A
8"x8" RA
48"x12" (E) RA
"x
S A
12"x12" RA
8"x8" RA
14"x12" SA
"x
S A
12"x10" SA
20"x12" SA
20"x12" SA DN
12"ø OA
8"x8" SA
8"x8" RA
18"x12" SA
10"x10" SA
10"x10" SA
12"x10" SA
12"x12" RA
16"x12" RA T
VOLUME DAMPER (TYP)
EX
(E) AC-1
(E) AC-2
(E) AHU-1
24"x30" (E) OA
15"x26" (E) RA
80"x12" (E) OA
U
S
D
A
-- USDA
NO. DATE BY DESCRIPTION
REVISIONS
Agricultural Research Service
DWG. NO.
SHEET OF
PROJECT MANAGER EPM
DESIGNER
CHECKED BY
DRAWN BY REAL PROPERTY
SAFETY & HEALTH
RPR
SPECIFICATION NO.
DATE
R.DARNELL
LOUVIERE, STRATTON & YOKEL, LLC
8484 GEORGIA AVENUE, SUITE 650, SILVER
SPRING, MD 20910
(301) 588-1500
BURNS & McDONNELL
8201 NORMAN CENTER DR. SUITE 500
BLOOMINGTON, MN 55437
(952) 656-6003
FINAL SUBMISSION07/13/21
CAROLYN WILLIAMS
RLP
MH100
MECHANICAL PLAN - BASEMENT
USDA CARL HAYDEN BEE RESEARCH CENTER - TUCSON, AZ
A.GIANPETRO
M.CAIN
R.PEARSON
07/13/2021
1/8" = 1'-0"1
MECHANICAL PLAN - BASEMENT
8'4' 16'0
SCALE: 1/8"=1'-0"
GENERAL NOTES: KEYED NOTES:
1. FOR MECHANICAL GENERAL NOTES AND SYMBOLS,
SEE M-001.
2. MAINTAIN ALL MANUFACTURER REQUIRED MINIMUM
UNOBSTRUCTED EQUIPMENT CLEARANCES.
3. CONTRACTOR SHALL FIELD VERIFY EXISTING
UTILITIES (DUCTWORK, PIPING, STRUCTURE,
ELECTRICAL, ETC.) ABOVE CEILING PRIOR TO
DEMOLITION AND NEW WORK TO COORDINATE
FINAL LOCATION OF NEW DUCTWORK, PIPING, AND
EQUIPMENT. NEW ROUTING SHOWN ON PLAN IS
PREFERRED ROUTING ONLY AND MAY BE
RELOCATED TO COORDINATE WITH EXISTING
CONDITIONS. RELOCATING EXISTING OR NEW
DUCTWORK/PIPING/EQUIPMENT FROM WHAT IS
SHOWN SHALL BE A NO-COST CHANGE TO THE
GOVERNMENT.
4. ALL DUCTWORK CONNECTIONS TO FAN POWERED
EQUIPMENT SHALL HAVE A FLEXIBLE DUCT
CONNECTOR. TYPICAL.
5. GENERAL CONTRACTOR SHALL ENGAGE USDA SITE
EXISTING CONTROLS VENDOR TO INTEGRATE NEW
MECHANICAL EQUIPMENT INTO EXISTING DELTA
BACnet CONTROLS SYSTEM WITHIN THE SCOPE OF
THIS PROJECT.
ADVANCED CONTROLS CORPORATION
ATTN: BRIAN GARDNER
520-620-6656 X29
520-591-9349 CELL
BRIANG@ADVANCEDCONTROLS.NET
1 RE-BALANCE EXISTING SUPPLY AIR DIFFUSERS
TO 130 CFM - TYPICAL 10.
2 RE-BALANCE EXISTING SUPPLY AIR DIFFUSERS TO
265 CFM.
NEW 24"x12" RA-B GRILLE LAY-IN GRILLE.
ROUTE EQUIPMENT CONDENSATE DRAIN TO
NEAREST FLOOR SINK IN MECHANICAL ROOM B-2.
MAINTAIN MINIMUM 1% SLOPE ON CONDENSATE
DRAIN PIPING.
OA AND RA DUCTS DOWN TO UNIT
MANUFACTURERS AIR MIXING BOX CONNECTIONS.
MOUNT ACU-11 ON 4" CONCRETE EQUIPMENT PAD.
PROVIDE VIBRATION ISOLATION PADS. MAINTAIN
MINIMUM 37" EQUIPMENT CLEARANCES ON COIL
CONNECTION SIDE OF UNIT.
ABANDON EXISTING RA GRILLE IN CEILING.
TRANSITION NEW RA DUCT TO EXISTING RA
GRILLE CONNECTION SIZE.
FIELD ROUTE NEW INSULATED OA DUCT AND
TERMINATE AT EXISTING INTAKE LOUVER IN
BOILER RM EXTERIOR WALL.
FIELD ROUTE NEW INSULATED OA DUCT TO
EXISTING 80"x12" OA PLENUM IN MECHANICAL
ROOM AND CONNECT.
INSTALL NEW DUCT SMOKE DETECTOR INTO
EXISTING SUPPLY AIR DUCT. INTEGRATE INTO
EXISTING LOCAL FIRE ALARM CONTROL PANEL.
BID OPTION NO. 01:
CONTRACT A CERTIFIED TAB CONTRACTOR TO
PERFORM TESTING, ADJUSTMENTS, AND
BALANCING (TAB) ON EXISTING VAV AIR HANDLING
SYSTEM SERVING THE FIRST FLOOR, EXISTING
CHILLED WATER SYSTEM SERVING THE BUILDING,
AND EXISTING HEATING HOT WATER SYSTEM
SERVING THE BUILDING. THIS IS IN ADDITION TO
THE NEW WORK SHOWN ON THE DRAWINGS.
PROVIDE CERTIFIED TAB REPORTS FOR REVIEW
AND COMMENT. REFER TO 23 05 93 FOR TESTING,
ADJUSTING, AND BALANCING REQUIREMENTS.
(TYP)
TRUE NORTH
4 5
BID OPTION #01
BID OPTION #01
1 2
3 4 5 6 7 8
B
C
D
E
16"x16" (E) EA 16"x16" (E) EA 16"x16" (E) EA
15"x12" (E) SA
30"x10" (E) SA
16"x9" (E) SA
16"x16" (E) RA
14"x16" (E) SA
16"ø (E) RA UP
8"x10" (E) SA24"x16" (E) SA
16"x16" (E) EA
16"ø (E) EA UP
LABORATORY
LABORATORY
LABORATORY
LABORATORY
STUDENT
COMPUTER RM
STUDENT
COMPUTER RM
BREAK ROOM
LABORATORY
LABORATORY
LABORATORY
LABORATORY
STORAGE
LABORATORY
"ø
E
S
A
18"x14" (E) SA
THRU ROOF
(TYP ALL)
THRU ROOF
(TYP ALL HOODS)
TO FCU-7
ON ROOF
14"x16" (E) SA UP
TO (E)ACU-7
ON ROOF
24"x13" (E) SA
16"x16" (E) RA DN
THRU FLOOR
16"x16" (E) EA UP
THRU ROOF
16"x16" (E) EA
18"x18" (E) EA 18"x18" (E) EA
16"ø (E) EA UP16"ø (E) EA UP
T T T T T
TTTT
LABORATORY
T
16"x14" (E) OA UP
28"x14" (E) OA
(E)ACU-10
ACU-1 ACU-2 ACU-3 ACU-4
ACU-5
ACU-6
ACU-8
ACU-9
(TYP) 24"x14" OA UP (TYP)
2 (TYP)
(E) FUME
HOOD (TYP)
20"x14" SA
DPDPDPDP
DP DP DP DP DP DP
TO (E) AC-2
CONTROLLER
TO (E) AC-1
CONTROLLER
OCC OCC OCC OCC
OCCOCCOCCOCCOCCOCC
CAPPED (E) EA UP
TO REMAIN
T
500-20"x14"
SA-C
250-18"x10"
SA-C
U
S
D
A
-- USDA
NO. DATE BY DESCRIPTION
REVISIONS
Agricultural Research Service
DWG. NO.
SHEET OF
PROJECT MANAGER EPM
DESIGNER
CHECKED BY
DRAWN BY REAL PROPERTY
SAFETY & HEALTH
RPR
SPECIFICATION NO.
DATE
R.DARNELL
LOUVIERE, STRATTON & YOKEL, LLC
8484 GEORGIA AVENUE, SUITE 650, SILVER
SPRING, MD 20910
(301) 588-1500
BURNS & McDONNELL
8201 NORMAN CENTER DR. SUITE 500
BLOOMINGTON, MN 55437
(952) 656-6003
FINAL SUBMISSION07/13/21
CAROLYN WILLIAMS
RLP
MH101
MECHANICAL PLAN - FIRST FLOOR
USDA CARL HAYDEN BEE RESEARCH CENTER - TUCSON, AZ
A.GIANPETRO
M.CAIN
R.PEARSON
07/13/2021
1/8" = 1'-0"1
MECHANICAL PLAN - FIRST FLOOR
8'4' 16'0
SCALE: 1/8"=1'-0"
GENERAL NOTES:
KEYED NOTES:
1. FOR MECHANICAL GENERAL NOTES AND SYMBOLS,
SEE M-001.
2. MAINTAIN ALL MANUFACTURER REQUIRED MINIMUM
UNOBSTRUCTED EQUIPMENT CLEARANCES.
3. CONTRACTOR SHALL FIELD VERIFY EXISTING
UTILITIES (DUCTWORK, PIPING, STRUCTURE,
ELECTRICAL, ETC.) ABOVE CEILING PRIOR TO
DEMOLITION AND NEW WORK TO COORDINATE
FINAL LOCATION OF NEW DUCTWORK, PIPING, AND
EQUIPMENT. NEW ROUTING SHOWN ON PLAN IS
PREFERRED ROUTING ONLY AND MAY BE
RELOCATED TO COORDINATE WITH EXISTING
CONDITIONS. RELOCATING EXISTING OR NEW
DUCTWORK/PIPING/EQUIPMENT FROM WHAT IS
SHOWN SHALL BE A NO-COST CHANGE TO THE
GOVERNMENT.
4. ALL DUCTWORK CONNECTIONS TO FAN POWERED
EQUIPMENT SHALL HAVE A FLEXIBLE DUCT
CONNECTOR. TYPICAL.
5. GENERAL CONTRACTOR SHALL ENGAGE USDA SITE
EXISTING CONTROLS VENDOR TO INTEGRATE NEW
MECHANICAL EQUIPMENT INTO EXISTING DELTA
BACnet CONTROLS SYSTEM WITHIN THE SCOPE OF
THIS PROJECT.
ADVANCED CONTROLS CORPORATION
ATTN: BRIAN GARDNER
520-620-6656 X29
520-591-9349 CELL
BRIANG@ADVANCEDCONTROLS.NET
1 NEW 24"x14" OA FROM ACU INLET TO EXISTING 14"x16" OA DUCT UP THROUGH ROOF. PROVIDE
FLEXIBLE DUCT CONNECTION AT UNIT.
2 EXISTING EA DUCTWORK SERVING LABORATORY
AND FUME HOODS TO REMAIN. TYPICAL ALL.
3 EXISTING ACU-7 AT ROOF TO REMAIN.
EXISTING ACU-10 AND DUCTWORK TO REMAIN.
INSTALL AND CONNECT NEW ROOM
THERMOSTAT, OCCUPANCY SENSOR, AND
DIFFERENTIAL PRESSURE SENSOR TO EXISTING
DELTA BACnet CONTROLLER SERVING
LABORATORIES.
PROVIDE WITH MANUFACTURERS AIR MIXING
BOX AND MOTORIZED DAMPERS. RA OPENING IN
BOTTOM CONNECTION. CONNECT NEW 14"x16"
OA DUCT TO END OF MIXING BOX.
BID OPTION NO. 01:
CONTRACT A CERTIFIED TAB CONTRACTOR TO
PERFORM TESTING, ADJUSTMENTS, AND
BALANCING (TAB) ON EXISTING VAV AIR
HANDLING SYSTEM SERVING THE FIRST FLOOR,
EXISTING CHILLED WATER SYSTEM SERVING
THE BUILDING, AND EXISTING HEATING HOT
WATER SYSTEM SERVING THE BUILDING. THIS IS
IN ADDITION TO THE NEW WORK SHOWN ON THE
DRAWINGS. PROVIDE CERTIFIED TAB REPORTS
FOR REVIEW AND COMMENT. REFER TO 23 05 93
FOR TESTING, ADJUSTING, AND BALANCING
REQUIREMENTS.
(TYP)
TRUE NORTH
BID OPTION #01
BID OPTION #01
BID OPTION #01
BID OPTION #01
C
D
E
MP401
MECHANICAL
ROOM
B-2
STAIRWELL
B-3
BOILER ROOM
B-4
TELEPHONE
B-6
STORAGE
STORAGE
LAB
TOILET
VESTIBULE
STORAGE
012A
STORAGE
BREAK ROOM
CORRIDOR
LAB
ADMIN STORAGE
STORAGE
FITNESS ROOM
ELECTROPHYSIOLOGY
LAB
STORAGE
ACU-11
ACU-12
1" (E) CHWR
1" (E) CHWS
1" (E) HWR
1" (E) HWS
MOTORIZED CONTROL
VALVE (TYP)
1" HWS
1" CHWS
1" CHWR
1" HWR
U
S
D
A
-- USDA
NO. DATE BY DESCRIPTION
REVISIONS
Agricultural Research Service
DWG. NO.
SHEET OF
PROJECT MANAGER EPM
DESIGNER
CHECKED BY
DRAWN BY REAL PROPERTY
SAFETY & HEALTH
RPR
SPECIFICATION NO.
DATE
R.DARNELL
LOUVIERE, STRATTON & YOKEL, LLC
8484 GEORGIA AVENUE, SUITE 650, SILVER
SPRING, MD 20910
(301) 588-1500
BURNS & McDONNELL
8201 NORMAN CENTER DR. SUITE 500
BLOOMINGTON, MN 55437
(952) 656-6003
FINAL SUBMISSION07/13/21
CAROLYN WILLIAMS
RLP
MP100
MECHANICAL PIPING PLAN - BASEMENT
USDA CARL HAYDEN BEE RESEARCH CENTER - TUCSON, AZ
A.GIANPETRO
M.CAIN
R.PEARSON
07/13/2021
1/8" = 1'-0"1
MECHANICAL PIPING PLAN - BASEMENT
8'4' 16'0
SCALE:…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .