This is a Preliminary Hazardous Materials Survey Report prepared by Atlas Technical Consultants LLC for the Detroit Public Schools Community District regarding the planned demolition of Pulaski Elementary School located at 19725 Strasburg Street, Detroit, Michigan 48205. The survey was conducted from August 7, 2026, through August 26, 2026, by State of Michigan licensed asbestos inspectors to identify asbestos-containing building materials (ACBMs) and inventory universal waste and regulated materials prior to demolition activities. The inspection included a comprehensive visual survey of all accessible areas of the main building, portable classrooms, and boiler house, with bulk samples collected and analyzed by an NVLAP-accredited laboratory using polarized-light microscopy methodology in accordance with OSHA Asbestos Construction Industry Standards, EPA Asbestos NESHAP, and AHERA requirements. The report documents 150 sampled material locations across the facility, with quantities ranging from individual items to thousands of square feet or linear feet of various building materials.
The survey results identified multiple asbestos-containing materials requiring abatement prior to demolition, including friable materials such as pipe insulation (30-42% chrysotile and amosite content), boiler insulation (55% chrysotile with 10% amosite content), mill board (26% chrysotile), and safe door insulation (50% chrysotile), as well as non-friable materials including floor tiles, mastics, caulking, and vapor paper containing trace to 3.5% asbestos content. Additionally, the report identified 2,300+ universal waste items requiring proper removal and disposal in accordance with RCRA regulations, including fluorescent light bulbs and ballasts, thermostats, computer equipment, fire extinguishers, and assumed PCB transformers in flooded basement areas. The report notes that flooded basement and boiler house areas were inaccessible during the survey, and contractors bidding on demolition should conduct independent assessments to verify quantities and treat any newly discovered suspect materials as presumed asbestos-containing material (PACM) in accordance with applicable federal and state regulations.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PRELIMINARY HAZARDOUS MATERIALS SURVEY REPORT
FOR PLANNED DEMOLITION
PULASKI ELEMENTARY SCHOOL
19725 STRASBURG STREET
DETROIT, MICHIGAN 48205
REPORT DATE: SEPTEMBER 9, 2026
PREPARED FOR:
MR. JAMIE CONN
PROJECT MANAGER - CAPITAL PROJECTS; PMP
DETROIT PUBLIC SCHOOLS COMMUNITY DISTRICT
SUPPORT SERVICES COMPLEX, BUILDING C
1601 FARNSWORTH STREET
DETROIT, MICHIGAN 48211
PREPARED BY:
Atlas Technical Consultants LLC 46555 Humboldt Drive, Suite 100 Novi, Michigan 48377
Atlas Project No.: 188BS26395
September 9, 2026
MR. JAMIE CONN
PROJECT MANAGER - CAPITAL PROJECTS; PMP
DETROIT PUBLIC SCHOOLS COMMUNITY DISTRICT
SUPPORT SERVICES COMPLEX, BUILDING C
1601 FARNSWORTH STREET
DETROIT, MICHIGAN 48211
Subject: Preliminary Hazardous Materials Survey Report For Planned Demolition Pulaski Elementary School
19725 Strasburg Street Detroit, Michigan 48205 Atlas Project No 188BS26395
Dear Mr. Conn:
Atlas is pleased to present this report detailing the findings of the preliminary hazardous materials survey performed at the above-referenced site in preparation for the planned demolition of the structure(s). The purpose of this sampling was to identify and collect samples of suspect asbestos containing building materials (ACBM’s) and conduct an inventory of universal waste and other regulated materials to develop a specification for the abatement and demolition activities.
The pre-demolition hazardous materials survey was conducted from August 7, 2026, through August 26, 2026. State of Michigan licensed asbestos inspectors Kari Lamprich (A60513) and Kenneth Borden (A65450) completed the survey of the subject property. The sampling was conducted in accordance with sampling criteria specified in the Occupational Safety and Health Administration’s (OSHA) Asbestos Construction Industry Standard (29 CFR 1926.1101), EPA Asbestos NESHAP (40 CFR Part 61, Subpart M), and the Asbestos Hazard and Emergency Response Act of 1987 (AHERA).
If you have any questions, please call us at 248.669.5140.
Respectfully submitted, ATLAS TECHNICAL CONSULTANTS LLC
Jennifer Fashbaugh Kari Lamprich Building Sciences Program Manager State of Michigan Asbestos Inspector (A60513)
CONTENTS
1. INTRODUCTION
1.1 Purpose
1.2 Pre-Demolition Asbestos Survey
1.3 Universal Waste and Other Regulated Materials
2. PRE-DEMOLITION ASBESTOS SURVEY
2.1 Homogeneous Areas
2.2 Hazard Assessment Factors
2.3 Laboratory Analytical Methodology
2.4 Sampling Results
3. UNIVERSAL WASTE AND OTHER REGULATED MATERIALS
4. CONCLUSIONS AND RECOMMENDATIONS
4.1 Asbestos Containing Materials
4.2 Universal Waste and Other Regulated Materials
4.3 Inaccessible Areas
5. ASSUMPTIONS AND LIMITATIONS
TABLES
Table 1 Suspect Asbestos Containing Materials and Results Table 2 Universal Waste and Other Regulated Materials
APPENDICES
Appendix A Subject Property Photolog Appendix B Sample Location Map Appendix C Asbestos Laboratory Report
Pulaski Elementary School / Atlas Project No. 188BS26395
1. INTRODUCTION
Atlas Technical Consultants LLC (Atlas) was retained by the Detroit Public Schools Community District (DPSCD) to provide industrial hygiene services with respect to the planned demolition at Pulaski Elementary School (Subject Property) located at 19725 Strasburg Street, Detroit, Michigan 48205.
1.1 Purpose
The purpose of this project was to identify asbestos containing materials and universal waste/other regulated materials at the Subject Property that will require abatement prior to the planned demolition activities.
1.2 Pre-Demolition Asbestos Survey
The scope of the Pre-Demolition asbestos survey included the following:
• Review of existing asbestos reports for the building(s), if available;
• Review of demolition drawings, if available;
• Survey of the property building(s);
• Identification of accessible suspect asbestos-containing materials (ACMs); and
• Collection and analysis of bulk samples of suspect friable and non-friable materials.
All accessible areas of the buildings were visually inspected for the presence of building materials that are suspected to contain asbestos. Bulk samples of suspect ACMs were collected and placed into individual containers for transport to a National Voluntary Lab Accreditation Program (NVLAP)-accredited laboratory for analysis. Materials typically known as non-asbestos items (i.e.
fibrous glass, foam rubber, wood, etc.) were not sampled. The asbestos inspection consisted of the following three basic procedures:
• Conducting a visual inspection of the structures;
• Identifying homogeneous areas (HAs) of suspect surfacing, thermal system insulation, and/or miscellaneous materials; and
• Sampling accessible, friable and non-friable suspect materials.
A photolog of the Subject Property is included in Appendix A. A sample location map of the asbestos bulk samples collected is included in Appendix B. The asbestos laboratory analytical report is included in Appendix C.
1.3 Universal Waste and Other Regulated Materials
Atlas conducted a visual inspection of the buildings during the pre-demolition hazardous material assessment to identify the type, location and estimated quantity of regulated materials and universal wastes that may be generated during the demolition of the building. Removal and disposal of the materials identified below shall be in accordance with federal, state and local requirements as per the Resource Conservation and Recovery Act (RCRA). Contractors that remove the materials listed below should ensure that proper manifests, disposal and/or recovery is documented and provided to the Owner. Identified Regulated Materials and Universal Wastes are summarized in Table 2 below.
2. PRE-DEMOLITION ASBESTOS SURVEY
2.1 Homogeneous Areas
Prior to collecting any samples, homogenous areas (HAs) were identified. A homogeneous sampling area can be described as one or more areas of material that are similar in appearance and texture and that have the same apparent installation date, appearance, and function. The actual number of samples collected from each homogeneous sampling area may vary, based on the type of material and the professional opinion of the inspector.
2.2 Hazard Assessment Factors
From the list of suspect homogeneous areas, a physical assessment was performed for each material on the list. A physical assessment includes evaluating the condition, assessing the potential for disturbance, and determining the friability of each material. By definition, "friable" materials are those that can be crumbled or reduced to powder by hand pressure when dry. Each material identified was further classified into one of three categories: surfacing materials, thermal systems insulation (TSI) and miscellaneous materials. Each of the three categories have specific sampling requirements, outlined below.
Surfacing Materials: Refers to spray-applied or troweled surfaces such as plaster ceilings and walls, fireproofing, textured paints, textured plasters, and spray-applied acoustical surfaces.
Thermal System Insulation: Refers to insulation used to inhibit heat gain or loss on pipes, boilers, tanks, ducts, and various other building components.
Miscellaneous Materials: Refers to friable and non-friable products and materials that do not fit in any of the above two categories such as resilient floor coverings, baseboards, mastics, adhesives, roofing material, caulking, glazing, and siding. This category also contains wallboard and ceiling tile.
2.3 Laboratory Analytical Methodology
Bulk samples were analysed by Environmental Testing Laboratories, Inc. (ETL) in Romulus, Michigan using polarized-light microscopy (PLM) and dispersion staining (Method Reference: 40 CFR Part 763, Volume 47, No. 103, May 27, 1982 pg. 23376) EPA Method 600/R-93/116.
This laboratory participates in the NVLAP accreditation program (NVLAP #201028-0), a quality assurance program for PLM analysis, and is accredited by the National Institute of Standards and Technology (NIST) as well as accreditation requirements under 15 CFR Part 25.
A photolog of the subject property is included in Appendix A. A map of the asbestos bulk sample locations is included in Appendix B. A copy of the asbestos laboratory analytical report and corresponding chain-of-custody are included in Appendix C.
2.4 Sampling Results
A material that contains greater than one percent (>1%) of asbestos fibers as defined by the EPA and OSHA (29 CFR 1926.1101) as an asbestos-containing material (ACM) must be handled according to federal and state regulations. Friable materials reported to contain one percent or less of asbestos fibers are required to be considered as ACM by the EPA, unless the “Point Counting” method of analysis and quantification is used to denote the percentages. Although the EPA does not regulate materials that are reported to be 1% or less, OSHA still regulates work practices and worker exposures for materials disturbed containing trace levels of asbestos (OSHA Guidance Document, November 24, 2003, (Compliance Requirements for Renovations Work Involving Materials Containing Less than 1% Asbestos).
The following table provides a summary of accessible suspect and confirmed ACMs that may be impacted during the planned demolition activities:
TABLE 1 Suspect Asbestos Containing Materials and Results
Sample ID No. Description Location Quantity (LF/SF) Present
Asbestos/Type (2)
Friable Yes/No
(1)
Main Building
1-FT-A,B,C
12-inch by 12-inch beige mottle floor tile and associated yellow/brown mastic
FS-1, 3, 5, 9 3,000 sf ND No
2-CP-A,B,C 2-foot by 4-foot white ceiling panels with medium fissure and pinholes FS-1, 17 800 sf ND Yes
3-BM-A,B,C Gray CMU block and associated gray mortar FS-30 62,000 sf ND No
4-CB-A,B,C 4-inch black cove base and associated brown mastic FS-1, 22, 22A 200 lf ND No
5-CG-A,B,C Yellow carpet glue FS-1 600 sf ND No
6-WG-A,B,C Exterior/perimeter black window glaze Exterior windows throughout 1,000 Windows ND No
7-RI-A,B,C Pink rolled in insulation underneath silver backing with black tar adhesive FS-1 100 sf ND Yes
8-IC-A,B,C Red firestop throughout Classrooms, corridors, FS-50, throughout penetrations 200 sf ND No
9-PI-A,B,C Aircell corrugated carboard like material straight pipe
FS-15, 18, 23, 31, 39, 50, 51,
54 7,000 lf 30% Chrysotile Yes
10-IC-A,B,C Beige fire stop throughout Classrooms, corridors, FS-50, throughout penetrations 150 sf ND No
11-PI-A,B,C White mag block insulation straight pipe FS-50, 56 5,000 lf 8% Chrysotile
4% Amosite Yes
12-Omitted
13-PF-A,B,C Off-white aircell fittings FS-15, 18, 23, 31, 39, 50, 51, 54 700 each 42% Chrysotile Yes
14-WBS-A,B,C Off-white wallboard system FS-1 450 sf ND Yes
15-CT-A,B,C 1-foot by 1-foot ceiling tiles and associated brown glue pods First Floor corridors 1, 2, 3 7,000 sf ND Yes
16-WG-A,B,C Green felt window glaze, office cabinets
Throughout cabinets in office and classrooms UNQ ND No
17-IC-A,B,C White caulking around wood trim on doors FS-1 2 each ND No
TABLE 1 Suspect Asbestos Containing Materials and Results
Sample ID No. Description Location Quantity (LF/SF) Present
Asbestos/Type (2)
Friable Yes/No
(1)
18-BM-A,B,C Tan brick and associated gray mortar Throughout 62,000 sf ND No
19-FT-A,B,C 9-inch by 9-inch black floor tile with black coating Corridors 1, 2, 3 3,000 sf
1.25% Chrysotile (tile)
ND (mastic) No
20-FT-A,B,C 9-inch by 9-inch brown floor tile with black coating Corridors 1, 2, 3 3,000 sf
1.5% Chrysotile (tile)
ND (mastic) No
21-PL-A,B,C White leveler compound over gray plaster in hallways and stairwells V-1, 2, 3, 6 800 sf ND No
22-IC-A,B,C Black caulking on blue windows Windows throughout 1,000 windows ND No
23-IC-A,B,C Gray caulking, trim and CMU around windows Throughout 1,000 windows ND No
24-VP-A,B,C Vapor paper underneath wood floors - First floor
FS-2, 7, 7A, 8, 10, 10A,
10B,11, 12 8,000 sf 2% Chrysotile No
25-FM-A,B,C Black floor mastic on wood floors - First floor
FS-2, 7, 7A, 8, 10, 10A,
10B,11, 12 8,000 sf 2% Chrysotile No
26-CA-A,B,C Brown construction adhesive and associated corkboard in classrooms Throughout classrooms 3,000 sf ND No
27-TZ-A,B,C Terrazzo flooring, reddish brown V-1, V-4, V-6, FS-15, 18, 31 2,500 sf ND No
28-GM-A,B,C Ceramic tile grout and mortar stairwell All stairs 500 sf ND No
29-FS-A,B,C Beige floor sheeting at security desk Corridor 1 30 sf ND No
30-RI-A,B,C Radiator insulation, yellow fiberglass insulation with brown adhesive V-1, 2, 4 50 sf ND Yes
31-MB-A,B,C Mill board associated with vestibule area vents V-1, 2, 4 50 sf 26% Chrysotile Yes
32-WG-A,B,C Brown felt window glaze associated with lattice windows in doors Throughout UNQ ND No
33-FT-A,B,C
9-inch by 9-inch brown with dark brown and beige streaks and black mastic
FS-4 300 sf 3% Chrysotile (tile)
1.5% Chrysotile (mastic)
No
34-FT-A,B,C 18-inch by 12-inch black floor tiles and black mastic FS-4 150 sf
2% Chrysotile (tile) 1.25% Chrysotile
(mastic) No
35-GM-A,B,C Gray grout marble seal along wall Bathrooms Floor 1 and 2 350 sf ND No
36-WG-A,B,C Brown felt window glaze in gym FS-30 Doors 3 Each ND No
37-WG-A,B,C Brown felt in 2 by 2 panels in wood doors Doors throughout 20 doors each ND No
38-FT-A,B,C 12-inch by 12-inch gray mottle floor tile and associated yellow mastic FS-6 230 sf ND Yes
39-FT-A,B,C 12-inch by 12-inch yellow mottle floor tile and associated black mastic FS-6 230 sf ND No
40-FT-A,B,C 12-inch by 12-inch blue mottle floor tile and associated black mastic FS-6 230 sf ND No
41-FT-A,B,C 12-inch by 12-inch green mottle floor tile and associated black mastic FS-6 230 sf ND No
42-FT-A,B,C 12-inch by 12-inch red mottle floor tile and associated beige mastic FS-6, 16 230 sf ND No
43-CG-A,B,C Yellow carpet glue FS-22, 22A, 22C 800 sf ND No
TABLE 1 Suspect Asbestos Containing Materials and Results
Sample ID No. Description Location Quantity (LF/SF) Present
Asbestos/Type (2)
Friable Yes/No
(1)
44-GM-A,B,C
1-inch by 1-inch, 2-inch by 2-inch, and 1-inch by 2-inch ceramic tiles and associated grout FS-7B, 7C, 7D 1,000 sf ND No
45-IC-A,B,C White caulking around sinks in bathrooms FS-7C, 7D 20 sf ND No
46-GM-A,B,C 5-inch by 5-inch ceramic tile & grout Floor 1 and 2 Stairs 200 sf ND No
47-CT-A,B,C 2-foot by 2-foot ceiling tiles and associated adhesive V-2 175 sf ND Yes
48-SU-A,B,C Off-white sink undercoating, beige FS-9 1 each 4% Chrysotile No
49-WG-A,B,C Reddish brown window glaze, FS- 16A FS-16A 35 LF ND No
50-ED-A,B,C Electrical panel board FS-9, 50 25 Panels ND No
51-IC-A,B,C Gray caulking around blue trim FS-16A 200 lf ND No
52-CC-A,B,C Concrete FS-16A 350 sf ND No
53-GP-A,B,C Carpet glue on rug/carpet FS-16 75 sf ND No
54-FT-A,B,C 12-inch by 12-inch cream mottle floor tile and mastic FS-17 150 sf ND No
55-CB-A,B,C 4-inch cove base and associated brown adhesive FS-17 75 lf ND No
56-SI-A,B,C White block safe door insulation FS-22D 30 sf 50% Chrysotile Yes
57-FS-A,B,C Brown floor sheeting FS-22D 150 sf ND No
58-FC-A,B,C Red fire curtain FS-25 1 each ND No
59-FC-A,B,C Black fire curtain FS-25 1 each ND No
60-VP-A,B,C Black vapor paper underneath wood on stage FS-25 600 sf ND No
61-FT-A,B,C
9-inch by 9-inch reddish brown floor tile and associated brown mastic FS-25 1,500 sf 2% Chrysotile (tile)
ND (mastic) No
62-FT-A,B,C 12-inch by 12-inch brown mottle floor tile and mastic FS-25 15 sf ND No
63-IC-A,B,C Beige caulking at windows FS-25 50 lf ND No
64-GM-A,B,C Blue speckled multicolored floor in FS-28 bathroom FS-28 550 sf ND No
65-CP-A,B,C 2-foot by 2-foot wallboard ceiling panels FS-28 550 sf ND Yes
66-VP-A,B,C Black vapor paper underneath wood FS-30 2,400 sf 1.25% Chrysotile No
67-FM-A,B,C Black floor mastic FS-30 2,400 sf Trace Chrysotile No
68-IC-A,B,C Silver caulking associated with the serving area FS-28 20 lf ND No
69-VD-A,B,C Black vibration dampener - FS-30 Radiators FS-30 4 Each ND No
70-DS-A,B,C Gray duct seam sealant FS-29 100 sf ND No
71-IC-A,B,C Gray caulking painted blue around doors to the exterior Exterior doors 14 each ND No
TABLE 1 Suspect Asbestos Containing Materials and Results
Sample ID No. Description Location Quantity (LF/SF) Present
Asbestos/Type (2)
Friable Yes/No
(1)
72-Omitted
73-CG-A,B,C Brown carpet glue FS-33 1,085 sf ND No
74-IC-A,B,C Off-white building seam caulking First floor by FS 20, Corridor 16 lf 3% Chrysotile No
75-FT-A,B,C 12-inch by 12-inch dark blue mottle floor tile and mastic black FS-45 350 sf ND No
76-FT-A,B,C 12-inch by 12-inch gray mottle floor tile and mastic black FS-45 350 sf ND No
77-WS-A,B,C Off-white textured wall sheeting over cork boards FS-34, 46 20 each ND No
78-FM-A,B,C Black floor mastic, second floor
FS-34, 35, 36, 37, 38, 41, 46,
47, 57, 58, 59, 60, 61, 62, 63, 64, 66 12,500 sf 2% Chrysotile No
79-CT-A,B,C Ceiling tiles and associated brown glue pods Floor 2 ceiling 7,000 sf
2% Chrysotile (glue)
ND (tile) Yes
80-GM-A,B,C Beige Ceramic wall tiles and associated gray grout Across FS-44, Corridors 4, 5, 6 15,000 sf ND No
81-GM-A,B,C Red ceramic tile and associated gray grout Stairwells 600 sf ND No
82-FS-A,B,C Brown floor sheeting FS-42 140 sf ND No
83-FT-A,B,C 9-inch by 9-inch black floor tile and mastic Floor 2 Corridors 4, 5, 6 6,000 sf ND No
84-DI-A,B,C
White painted grayish woven ducting wrap over off-white mud in mechanical room
FS-50 150 sf 40% Chrysotile Yes
85-VD-A,B,C White canvas vibration dampener FS-50 20 each 20% Chrysotile No
86-VD-A,B,C Yellow vibration dampener FS-50 15 each ND No
87-VD-A,B,C Red vibration dampener FS-50 10 each ND No
88-DI-A,B,C Silver ducting wrap over yellow fiberglass in Mechanical room FS-50 300 sf ND Yes
89-CB-A,B,C Cork board and associated brown mastic Classrooms Each room ND No
90-RM-A,B,C Black roof flashing Roof 15,000 sf ND No
91-RC-A,B,C Rolled roofing over perlite, vapor barrier, and fiberglass Roof – west 35,000 sf ND No
92-EC-A,B,C Gray exterior caulking around side roof vents Roof 2,000 lf ND No
93-RT-A,B,C Black roofing tar Roof 35,000 sf ND No
94-EC-A,B,C Blueish gray caulking on blue/teal trim seams Roof 1,000 lf ND No
95-RM-A,B,C Silver flashing at top vents Roof 3,500 lf ND No
96-RM-A,B,C Silver flashing perimeter roof Roof 15,000 sf ND No
97-RB-A,B,C Radiator backing board Floor 2: Vestibules (some previously removed) 600 sf 20% Chrysotile No
98-WG-A,B,C Exterior black window glaze Exterior 1,000 windows ND No
TABLE 1 Suspect Asbestos Containing Materials and Results
Sample ID No. Description Location Quantity (LF/SF) Present
Asbestos/Type (2)
Friable Yes/No
(1)
99-EC-A,B,C Beige caulking around exterior windows Exterior windows 1,000 windows ND No
100-EC-A,B,C
Off-white caulking, upper perimeter window over foam and yellow fiberglass insulation
Exterior windows 1,000 windows ND No
101-EC-A,B,C Gray exterior expansion caulking on brick over Styrofoam
Exterior, Door 7, Parking lot, Across from FS-25 200 lf ND No
102-EC-A,B,C Off-white door caulking painted blue Entrance doors 14 each 2% Chrysotile No
103-ST-A,B,C Black stair tread Entrance doors 15 sf ND No
104-WG-A,B,C Exterior blue glazing associated with exterior greenhouse Exterior FS-16A 45 LF ND No
105-EC-A,B,C Exterior gray replacement seam caulking Exterior FS-16A 275 lf ND No
106-FS-A,B,C Red firestop penetration putty Exterior penetrations 2 sf ND No
107-EC-A,B,C
Exterior off-white caulking associated with lights at vestibule entrances
Exterior vestibules 20 sf 3% Chrysotile No
108-TC-A,B,C Exterior transite light covering Door 7 2 each ND No
109-CC-A,B,C Exterior concrete windowsills Throughout 1,000 windows ND No
110-BM-A,B,C Exterior tan brick and associated mortar Throughout 62,000 sf ND No
111-TS-A,B,C Exterior black tar seam, above windows Throughout exterior windows 1,000 windows ND No
112-VB-A,B,C Exterior black vapor barrier on concrete foundation Exterior throughout 35,000 sf ND No
113-CC-A,B,C
Concrete composite - Foundation, mortar on foundation, sidewalk, entry steps, patch concrete
Exterior throughout 40,000 sf ND No
114-FT-A,B,C 12-inch by 12-inch tan mottle floor tile and associated brown/tan mastic FS-52 700 sf ND No
115-FT-A,B,C
12-inch by 12-inch gray speckled repair floor tile and associated black mastic
FS-45 40 sf ND No
116-FB-A,B,C White fire brick inside kiln FS-33A 35 sf ND No
117-TZ-A,B,C Terrazzo flooring, cream with red V-4, All bathrooms 3,000 sf ND No
118-CG-A,B,C Yellow carpet glue FS-22, 22A 1,500 sf ND No
119-CB-A,B,C Chalk boards Throughout classrooms UNQ ND No
120-PI-A,B,C
Duplex straight pipe under woven wrap and paper wrap with black liner
FS-15, 18, 23, 31, 39, 50, 51,
54, Corridor 1, 2, 3 - Debris 5,000 lf
35% Chrysotile (paper wrap)
40% Chrysotile (liner)
Yes
121-FB-A,B,C Brown fiberboard Sides of radiators, Floors 1 and 2 200 sf ND No
122-RI-A,B,C Yellow fiberglass radiator insulation, top of radiators Throughout 200 sf ND Yes
123-IC-A,B,C Brown caulking on metal trim on interior doors FS-23 20 lf 12% Chrysotile No
TABLE 1 Suspect Asbestos Containing Materials and Results
Sample ID No. Description Location Quantity (LF/SF) Present
Asbestos/Type (2)
Friable Yes/No
(1)
124-CT-A,B,C Tan glue pods and associated peg board style ceiling tiles Floor 2 ceiling 7,000 sf ND No
125-CB-A,B,C 12-inch by 12-inch corkboard tiles FS-47 50 sf ND No
126-CA-A,B,C Off-white construction adhesive behind white board FS-34 150 Pods ND No
127-CA-A,B,C Dark brown construction adhesive behind corkboards Throughout classrooms 400 pods ND No
128-CA-A,B,C Beige construction adhesive behind corkboards Throughout classrooms 400 Pods ND No
129-PI-A,B,C Large diameter Aircell piping insulation Across from FS-66 70 lf 30% Chrysotile Yes
130-IC-A,B,C White caulking around toilets and sinks Floor 2 150 lf ND No
131-RB-A,B,C Radiator fiber board backing Floor 2: 34, 52, 53, 61, 62, 63, 64 65, 66 (some radiators previously removed)
1,200 sf 3% Chrysotile No
132-EC-A,B,C Exterior caulk, black, underneath blue metal around windows Exterior window frame's 1,000 windows ND No
133-DI-A,B,C White woven ducting wrap over yellow fiberglass FS-50, Duct insulation 3,000 lf ND Yes
134-CB-A,B,C Corkboard wall system and associated black tar FS-50 4,000 sf
1.25% Chrysotile (tar)
ND (cork) No
135-GK-A,B,C Brown gasket on HVAC FS-50 100 sf ND No
136-FI-A,B,C
Excelsior insulation board on wall and associated black tar construction adhesive
FS-50 100 sf ND No
137-EC-A,B,C Black caulking, perimeter roof Roof 15,000 sf ND No
138-FP-A,B,C Black flashing patch, perimeter roof Roof 1,000 sf ND No
139-FP-A,B,C Gray flashing patch, perimeter roof Roof 1,000 sf ND No
140-RP-A,B,C Black roof patching material Roof 500 sf ND No
141-VB-A,B,C Black vapor barrier and black tar mastic Roof 100 sf 32% Chrysotile No
142-RM-A,B,C
Metal sheeting over reinforced rubber and brown/black vapor barrier Roof 50 sf 30% Chrysotile No
143-RC-A,B,C Rolled roofing over drywall, vapor barrier, and polyisocyanurate (ISO) Roof 100 sf ND No
Portable Classrooms
1-CP-A,B,C 2-foot by 4-foot ceiling panels with pinholes Portable 1, 2 2,000 sf ND Yes
2-CG- A,B,C Yellow carpet Glue Portable 1 1,450 sf ND No
3-DWS-A,B,C
Drywall system - off-white drywall, brown paper tape, off white joint compound Portable 1, 2, 3, 4 6,000 sf ND Yes
4-CB-A,B,C 6-inch Cove Base Black with beige mastic Portable 1 165 lf ND No
5-RI-A,B,C Rolled Insulation - Yellow Throughout - behind drywall 6,000 sf ND Yes
TABLE 1 Suspect Asbestos Containing Materials and Results
Sample ID No. Description Location Quantity (LF/SF) Present
Asbestos/Type (2)
Friable Yes/No
(1)
6-FT-A,B,C 12-inch by 12-inch tan mottle floor tile and associated blue & black mastic Portable 2, 4 3,000 sf ND No
7-FS-A,B,C Red Fire Stop Portable 2 5 sf ND No
8-FS-A,B,C Beige Fire Stop Portable 2 5 sf ND No
9-CP-A,B,C 2-foot by 4-foot ceiling panels with pinholes and fissures Portable 4 2,000 sf ND Yes
10-CA-A,B,C Tan/Beige Construction adhesive Exterior Portables, behind exterior backing 7,000 sf ND No
11-CB-A,B,C 4-inch brown cove base and associated beige mastic Portable 2, 4 350 lf ND No
12-RS-A,B,C Roof Shingles Roof 4,000 sf ND No
13-VB-A,B,C Vapor Barrier Roof 4,000 sf ND No
14-FT-A,B,C
12-inch by 12-inch tan mottle floor tile with gray streaks over 12-unch by 12-inch white mottle floor tile with blue gray streaks Portable 3 150 sf ND No
15-EC-A,B,C Exterior black caulk / tar Around the roof vents 10 sf ND No
Boiler House
1-WG-A,B,C Off-white Interior Window Glaze Interior windows 70 windows 1.75% Chrysotile No
2-CMU-A,B,C Gray CMU and associated gray mortar
Electrical room and Boiler House
5,000 sf – not including flooded area ND No
3-BI-A,B,C Boiler Insulation - Fiber Glass under white painted gray fabric wrap Type A boiler 300 sf ND Yes
4-BI-A,B,C
Boiler Insulation Patch - White wrap patch with yellow fiberglass and off-white mud Type A boiler 30 sf ND Yes
5-HI-A,B,C Boiler Hatch Insulation Type A boiler 40 sf 12% Chrysotile Yes
6-BI-A,B,C
Boiler Insulation white mag insulation under gray painted fabric wrap
Type C Boiler 300 sf
55% Chrysotile (boiler insulation)
45% Chrysotile (mag)
10% Amosite (mag)
Yes
7-PI,A,B,C Boiler patch - white wrap patch with off-white mud Type C Boiler 35 sf
55% Chrysotile (mud)
45% Chrysotile (powder)
10% Amosite (powder)
Yes
8-HI-A,B,C Boiler Hatch insulation refractory off white Type C Boiler 40 sf ND Yes
9-BM-A,B,C Beige brick and gray mortar Exterior 5,000 sf ND No
10-LS-A,B,C Limestone windowsill & door pedestals Exterior 70 windows ND No
11-CC-A,B,C Composite concrete - Foundation, Pedestal step, Sidewalk Exterior 2,300 sf ND No
12-EC-A,B,C Exterior window caulk - Brown Exterior windows 70 windows 3.25% Chrysotile No
TABLE 1 Suspect Asbestos Containing Materials and Results
Sample ID No. Description Location Quantity (LF/SF) Present
Asbestos/Type (2)
Friable Yes/No
(1)
13-WG-A,B,C Off-white exterior window glaze Exterior windows 70 windows ND No
14-EC-A,B,C Gray painted brown exterior door caulking Exterior doors 3 each 3.5% Chrysotile No
15-EC-A,B,C Sliver Roof Flashing Roof 200 sf 3% Chrysotile No
16-EC-A,B,C Dark Gray Roof Flashing Roof 30 sf 5% Chrysotile No
17-RC-A,B,C Rolled tar over fiberglass and brown vapor barrier Roof 1,500 sf ND No
ASSUMED
144-GK Pipe Gaskets Basement/ Boiler House / Tunnels * 20 Each ASSUMED No
145-EW Electrical woven wraps Basement/ Boiler House / Tunnels * 300 LF ASSUMED Yes
146-T Transite in electrical panels Basement/ Boiler House / Tunnels * 200 SF ASSUMED Yes
147-FD Fire Doors Basement / Boiler Room / Tunnel / Fan Rooms * 9 Each ASSUMED No
148-FB Fire Brick Basement Coal Room * 320 SF ASSUMED No
149-PF Mudded Pipe Fitting Basement / Boiler House/ Tunnels * 600 Fittings ASSUMED Yes
150-PI Straight Pipe Insulation Basement/ Boiler House / Tunnels * 4,000 LF ASSUMED Yes
Key: SF = Square Feet; LF = Linear Feet; CF = Cubic Feet; CY = Cubic Yards; UNQ = Unquantified; ND = No Asbestos Detected.
*Boiler Room/Basement/Tunnel areas were flooded and not accessible at the time of this survey. Also, access to some areas within the structure was not possible or limited due to unsafe conditions so additional suspect materials not identified in this report may be present within the building.
Materials and quantities listed are estimates for bidding purposes. The approximate quantity of ACM and materials contaminated with asbestos were estimated and Contractors that intend to bid on removal of this material should not rely on the exact quantities estimated in this report. Contractors should conduct an assessment of the property to determine the time and effort required to complete the scope of work for the proper removal and disposal of ACM and asbestos contaminated materials. Due to the likelihood that general debris may contain asbestos, the Contractor should dispose of room contents as ACM waste.
In the event additional suspect material is discovered during demolition activities, this material should be treated as presumed asbestos-containing material (PACM) in accordance with regulations 29 CFR 1926.1101 and 1910.1001 and other applicable state and local regulations and either sampled to confirm or nullify asbestos content or be treated as ACM and handled accordingly.
3. UNIVERSAL WASTE AND OTHER REGULATED MATERIALS
Atlas conducted a visual inspection of the building during the pre-demolition hazardous material assessment to identify the type, location and estimated quantity of regulated materials and universal wastes that may be generated during the demolition of the building. Removal and disposal of the materials identified below shall be in accordance with federal, state and local requirements as per the Resource Conservation and Recovery Act (RCRA). Contractors that remove the materials listed below should ensure that proper manifests, disposal and/or recovery is documented and provided to the Owner.
Identified Universal Waste and Other Regulated Materials are summarized in Table 2 below.
TABLE 2 Universal Waste and Other Regulated Materials
Material Type Quantity Locations Main Building
Exit Signs 6 Throughout School
Fluorescent Light Bulbs 2,100 Throughout School
Fluorescent Light Ballasts/Fixtures 879 Throughout School
Misc. Chemical Containers (5-gallon size) 6 Throughout School
Thermostats 50 Throughout School
Security Alarm/System 25 Throughout School
TV Screen 49 Throughout School
Computer Monitor 44 Throughout School
Computer Tower 19 Throughout School
Refrigerator/Freezer 3 Kitchen
Fire Extinguisher 19 Throughout School
Snow Blower 1 Vestibule 6
PCB Transformers ASSUMED 4-6 Basement / Electrical Room (areas were flooded)
Portable Classrooms Refrigerator 1 Portables
Battery 30 Portables
TV Screen 15 Portables
Computer Monitor 15 Portables
Exit Sign 12 Portables
Fire Extinguisher 4 Portables
TABLE 2 Universal Waste and Other Regulated Materials
Material Type Quantity Locations
Fluorescent Light Bulb 200 Portables
Fluorescent Light Ballast 50 Portables
Thermostat 5 Portables
Boiler House Battery 50 Boiler house
Exit Sign 2 Boiler house
Fire Extinguisher 2 Boiler house
Thermostat 4 Boiler house
4. CONCLUSIONS AND RECOMMENDATIONS
4.1 Asbestos Containing Materials
The results of laboratory testing during the pre-demolition asbestos survey conducted at the property indicate that several types of building materials sampled were found to contain asbestos (ACM) and will require removal prior to demolition activities. There were also several materials were found to contain trace asbestos (<1%). While these materials are not considered to be ACM, OSHA standard 1926.1101 has sections that apply to asbestos materials with trace asbestos.
Contractors that may perform work onsite to remove identified asbestos containing materials should review the report, along with estimated quantities prior to completing cost estimates. If any additional materials are discovered during demolition/demolition activities that have not been identified in this report should be assumed to contain asbestos until sampling and analysis proves otherwise.
It should be noted that while some of the asbestos-containing materials were intact, there were also materials that have deteriorated or been vandalized and badly damaged. Some building areas are weathered, vandalized, flooded or piled with furniture therefore waste streams could be comingled and difficult to separate. Thermal Systems Insulation (TSI), mainly pipe insulation, has been stripped from piping and other building materials have collapsed due to structural issues and debris is found throughout on the ground. Additionally, the basement, boiler room and tunnel system were flooded at the time of the survey.
If ACM cannot be removed safely prior to demolition, the Contractor performing the work should comply with all requirements of OSHA and all building materials should be treated as ACM waste and disposed according to the requirements of NESHAP. If materials identified to contain asbestos can be removed safely, they should be removed prior to demolition by a licensed abatement company.
Access to some areas within the structure were limited due to unsafe conditions and materials not identified in this report may be present within the building. The approximate quantity of asbestos materials and materials contaminated with asbestos were estimated and Contractors that intend to bid on removal of this material should not rely on the exact quantities estimated in this report. Contractors should conduct an assessment of the property to determine the time and effort required to complete the scope of work for the proper removal and disposal of asbestos and asbestos contaminated materials.
Non-friable ACM’s shall not be subjected to abrasion, grinding, sanding or any other processes during renovation activities which will render these non-friable materials friable.
Based on the NESHAP (National Emission Standards for Hazardous Air Pollutants) non-friable Category I ACM and Category I non-friable PACM roofing materials that are asphalt/tar based can be demolished with a building so long as it is in good condition and will not be cut, pounded, sanded, or grinded during demolition, and that measures are taken to ensure that it does not become friable, at which point will be considered RACM. This material can also be disposed off-site in a Class III, construction and demolition (C&D) debris, landfill within the framework of local/state regulations. In addition, all roofing materials shall not be recycled if they contain Category I ACM.
4.2 Universal Waste and Other Regulated Materials
Universal Waste and Other Regulated Materials remain in the school and should be properly collected, containerized, manifested, and disposed in accordance with federal, state and local requirements as per the Resource Conservation and Recovery Act (RCRA). Contractors that remove these materials should ensure that proper manifests, disposal and/or recovery is documented and provided to the Owner.
It should be noted that while some of these materials were intact, there were also materials that have deteriorated or been vandalized and broken. Some building areas are weathered, vandalized, flooded, or piled with furniture therefore waste streams could be comingled and difficult to separate.
4.3 Inaccessible Areas
Asbestos containing pipe insulation and mudded fittings may be present above ceilings or behind walls and in areas throughout the building that are not visible. The total linear footage of pipe insulation was estimated based on the understanding of piping systems in buildings and could fluctuate.
The basement, boiler room, and tunnels were flooded and could not be accessed at the time of survey. Other building areas were not structurally safe or were piled with debris and could not be entered. Quantities were estimated for bidding purposes. Additional suspect materials not identified in this report or revised quantities of other identified materials would be necessary.
5. ASSUMPTIONS AND LIMITATIONS
The results, findings, conclusions, and recommendations expressed in the report are based only on conditions that were noted during the pre-demolition inspection conducted by Atlas from August 7, 2026, through August 26, 2026. Conditions within the building may change over time.
Selection of sample locations and frequency of sampling were based on EPA Guidance documents, Atlas’s observations, and the assumption that building vintage and demolition history information presented to Atlas allowed the proper designation of homogenous materials for each building.
The findings of this report represent Atlas’s professional judgment; no other warranty is expressed or implied. Please note that lighting was limited, there was extensive debris and structural damage within rooms and hallways, areas were flooded or had standing water within the structure that could have impaired our ability to access or view surfaces or materials.
This document does not contain the elements necessary for an Abatement Work plan, and this document does not contain, nor should it take the place of, technical specifications for ACM removal.
Our professional services have been performed, our findings obtained, and our conclusions and recommendations prepared in accordance with customary principles and practices in the fields of environmental science and engineering. This statement is in lieu of other statements either expressed or implied. This report does not warrant against changes to material from future operations or conditions, nor does it warrant against operations or conditions against present ACM material in locations not investigated. The scope of services performed in execution of this evaluation may not be appropriate to satisfy the needs of other users and use or re-use of this document or the findings, conclusions, or recommendations is at the risk of said user.
The report represents the conditions during which the survey was performed and locations where the suspect asbestos samples were collected. Inferences were based on the results of the sampling and related testing to form a professional opinion of conditions in areas beyond those from which the samples were collected. No warranty, expressed or implied, is made.
Suspect asbestos samples were submitted for analysis at an NVLAP-accredited laboratory via polarized light microscopy. The report represents the conditions during which the survey was performed and locations where the suspect asbestos samples were collected. Inferences were based on the results of the sampling and related testing to form a professional opinion of conditions in areas beyond those from which the samples were collected. No warranty, expressed or implied, is made. This report is prepared to assist the building owner, architect, construction manager, general contractors, and potential measures in locating the referenced hazardous materials. The limitations of the survey may not qualify this report to be adequate for all regulatory applications. Atlas’s recommendations are based in part on federal, state, local regulations, and guidelines. Atlas does not undertake responsibility for reporting to any local, state, or federal public agencies of conditions at the site that may present a potential danger to public health or safety. Atlas recommends that the Client comply with regulations and response actions in accordance with federal, state, and local regulations.
APPENDIX A
Subject Property Photolog
Photographic Documentation – Pulaski Main Bldg
DPSCD Pulaski Elementary School Pre-Demolition Atlas Project No. 188BS26395 1
Photo 1.
Entrance to FS-1
Photo 2.
FS-1
Photo 3.
FS-1-A
Photo 4.
FS-1B
Photo 5.
FS-2
Photo 6.
FS-3
Atlas Project No. 188BS26395 2
Photo 7.
Vest 1
Photo 8.
FS-4
Photo 9.
FS-4A
Photo 10.
FS-5
Photo 11.
FS-5A
Photo 12.
FS-5B
Atlas Project No. 188BS26395 3
Photo 13.
FS-5C
Photo 14.
FS-6
Photo 15.
FS-7
Photo 16.
FS-7A
Photo 17.
FS-7B
Photo 18.
FS-7C
Atlas Project No. 188BS26395 4
Photo 19.
FS-7D
Photo 20.
FS-8
Photo 21.
Vest 2
Photo 22.
FS-9
Photo 23.
FS-9
Photo 24.
FS-10
Atlas Project No. 188BS26395 5
Photo 25.
FS-10A
Photo 26.
FS-10B
Photo 27.
Vest 3
Photo 28.
FS-11
Photo 29.
FS-12
Photo 30.
FS-13 (Cannot Access)
Atlas Project No. 188BS26395 6
Photo 31.
FS-14
Photo 32.
FS-15
Photo 33.
FS-15
Photo 34.
FS-16
Photo 35.
FS-16
Photo 36.
FS-16A
Atlas Project No. 188BS26395 7
Photo 37.
FS-17
Photo 38.
FS-18
Photo 39.
FS-19
Photo 40.
FS-20
Photo 41.
FS-21
Photo 42.
FS-21A
Atlas Project No. 188BS26395 8
Photo 43.
FS-22
Photo 44.
FS-22A
Photo 45.
FS-22B
Photo 46.
FS-22C
Photo 47.
FS-22D
Photo 48.
FS-23
Atlas Project No. 188BS26395 9
Photo 49.
Vest 4
Photo 50.
FS-24
Photo 51.
FS-25
Photo 52.
FS-25
Photo 53.
FS-25A
Photo 54.
FS-24A
Atlas Project No. 188BS26395 10
Photo 55.
FS-26
Photo 56.
FS-27
Photo 57.
Vest 6
Photo 58.
FS-28
Photo 59.
FS-28
Photo 60.
FS-28A
Atlas Project No. 188BS26395 11
Photo 61.
FS-28B
Photo 62.
FS-29
Photo 63.
FS-30
Photo 64.
Photo 65.
Photo 66.
FS-30A
Atlas Project No. 188BS26395 12
Photo 67.
FS-30B
Photo 68.
VEST - 8
Photo 69.
FS-30C
Photo 70.
FS-30D
Photo 71.
FS-31
Photo 72.
FS-32
Atlas Project No. 188BS26395 13
Photo 73.
FS-33
Photo 74.
FS-33A
Photo 75.
FS-34
Photo 76.
FS-35
Photo 77.
FS-36
Photo 78.
FS-37
Atlas Project No. 188BS26395 14
Photo 79.
FS-38
Photo 80.
FS-39
Photo 81.
FS-40
Photo 82.
FS-41
Photo 83.
FS-41A
Photo 84.
FS-42
Atlas Project No. 188BS26395 15
Photo 85.
FS-42A
Photo 86.
FS-43
Photo 87.
FS-44
Photo 88.
FS-45
Photo 89.
FS-46
Photo 90.
FS-47
Atlas Project No. 188BS26395 16
Photo 91.
FS-48
Photo 92.
FS-49
Photo 93.
FS-50
Photo 94.
FS-51
Photo 95.
FS-52
Photo 96.
FS-53
Atlas Project No. 188BS26395 17
Photo 97.
FS-54
Photo 98.
FS-55
Photo 99.
FS-56
Photo 100.
FS-57
Photo 101.
FS-58
Photo 102.
FS-59
Atlas Project No. 188BS26395 18
Photo 103.
FS-60
Photo 104.
FS-61
Photo 105.
FS-62
Photo 106.
FS-63
Photo 107.
FS-64
Photo 108.
FS-65
Atlas Project No. 188BS26395 19
Photo 109.
FS-66
Photo 110.
FS-50 Debris on the ground
Photo 111.
Photo 112.
Photo 113.
FS-50 Debris in trash can
Photo 114.
Atlas Project No. 188BS26395 20
Photo 115.
Photo 116.
Photo 117.
Photo 118.
Photo 119.
Photo 120.
FS-50 Debris on the ground.
Atlas Project No. 188BS26395 21
Photo 121.
Debris on throughout the floor
Photo 122.
Snowblower in Vest 6
Photo 123.
Debris in the gym closet
Photo 124.
Debris in the bathroom’s
Photo 125.
Photo 126.
Atlas Project No. 188BS26395 22
Photo 127.
Photo 128.
Photo 129.
Clutter and debris, Corridor 2
Photo 130.
Photo 131.
Photo 132.
Atlas Project No. 188BS26395 23
Photo 133.
Debris in the corridor’s
Photo 134.
Photo 135.
Photo 136.
Photo 137.
Photo 138.
Atlas Project No. 188BS26395 24
Photo 139.
Photo 140.
Photo 141.
Photo 142.
Photo 143.
Debris in the boiler building on catwalk
Photo 144.
Photographic Documentation – Pulaski Boiler House
View of exterior building
FS-1 Inside
Photographic Documentation – Pulaski Boiler House
FS-2A
FS – 2B
View of inside boiler house
Photo 10.
View of inside boiler house
Photo 11.
View of the roof
Photographic Documentation - Pulaski Portables
FS-1A
FS-1B
FS-2A
Photographic Documentation - Pulaski Portables
VFS-3
FS-4
FS-4A
APPENDIX B
Sample Location Map
Asbestos Bulk Sampling Location Map
19725 Strasburg ST, Detroit MI 48205
PROJECT NUMBER:188BS26395
DRAWN BY: KB REVIEWED BY Atlas
FIGURE: 1
DATE: 09.08.2026
4 6 5 5 5 H u m b o l d t D r i v e , S u i t e 1 0 0 N o v i , M i c h i g a n 4 8 3 7 7 P h : ( 2 4 8 ) 6 6 9 - 5 1 4 0 ~ F a x : ( 2 4 8 ) 6 6 9 - 5 1 4 7
19725 Strasburg ST, Detroit MI 48205
PROJECT NUMBER:188BS26395
DRAWN BY: KB REVIEWED BY Atlas
FIGURE: 2
DATE: 09.08.2026
4 6 5 5 5 H u m b o l d t D r i v e , S u i t e 1 0 0
19725 Strasburg ST, Detroit MI 48205
PROJECT NUMBER:188BS26395
DRAWN BY: KB REVIEWED BY Atlas
FIGURE: 3
DATE: 09.08.2026
4 6 5 5 5 H u m b o l d t D r i v e , S u i t e 1 0 0
19725 Strasburg ST, Detroit MI 48205
PROJECT NUMBER:188BS26395
DRAWN BY: KB REVIEWED BY Atlas
FIGURE: 4
DATE: 09.08.2026
4 6 5 5 5 H u m b o l d t D r i v e , S u i t e 1 0 0
19725 Strasburg ST, Detroit MI 48205
PROJECT NUMBER:188BS26395
DRAWN BY: KB REVIEWED BY Atlas
FIGURE: 5
DATE: 09.08.2026
4 6 5 5 5 H u m b o l d t D r i v e , S u i t e 1 0 0
19725 Strasburg ST, Detroit MI 48205
PROJECT NUMBER:188BS26395
DRAWN BY: KB REVIEWED BY Atlas
FIGURE: 1
DATE: 09.08.2026
4 6 5 5 5 H u m b o l d t D r i v e , S u i t e 1 0 0
19725 Strasburg ST, Detroit MI 48205
PROJECT NUMBER:188BS26395
DRAWN BY: KB REVIEWED BY Atlas
FIGURE: 7
DATE: 09.08.2026
4 6 5 5 5 H u m b o l d t D r i v e , S u i t e 1 0 0
Asbestos Bulk Interior
Boiler House
Pulaski: 19725 Strasburg Street Detroit MI 48205
PROJECT NUMBER:188BS26395
DRAWN BY: KB REVIEWED BY Atlas
FIGURE: 1
DATE: 8.31.2026
4 6 5 5 5 H u m b o l d t D r i v e , S u i t e 1 0 0
Asbestos Bulk Exterior
Boiler House
Pulaski: 19725 Strasburg St Detroit MI 48205
PROJECT NUMBER:188BS26395
DRAWN BY: KB REVIEWED BY Atlas
FIGURE: 2
DATE: 8.31.2026
4 6 5 5 5 H u m b o l d t D r i v e , S u i t e 1 0 0
Asbestos Bulk Interior
Pulaski 19725 Strasburg St. Detroit MI 48205
PROJECT NUMBER:188BS26395
DRAWN BY: KB REVIEWED BY Atlas
FIGURE: 1
DATE: 8.28.2026
4 6 5 5 5 H u m b o l d t D r i v e , S u i t e 1 0 0
Asbestos Bulk Exterior
Pulaski 19725 Strasburg St. Detroit MI 48205
PROJECT NUMBER:188BS26395
DRAWN BY: KB REVIEWED BY Atlas
FIGURE2:
DATE: 8.28.2026
4 6 5 5 5 H u m b o l d t D r i v e , S u i t e 1 0 0
APPENDIX C
Asbestos Laboratory Report
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive Romulus, Michigan 48174
(734) 955-6600
Fax: (734) 955-6604
To:
Attention:
Atlas - Novi
46555 Humboldt Dr. Suite 100
Novi, Michigan 48377
Project Location:
DPSCD - Pulaski (Main Building)
19725 Strasburg Street, Detroit, MI
Client Project: 188BS26395
294415ETL Job:
Jennifer Fashbaugh
Report Issued: 09/08/2026
Lab Sample Number Client Sample Number Sample Type CompletedSampled Analyst
1924380 Asbestos1-FT-A 09/03/2026 Asha Davidson08/27/2026
1924381 Asbestos1-FT-B 09/03/2026 Asha Davidson08/27/2026
1924382 Asbestos1-FT-C 09/03/2026 Asha Davidson08/27/2026
1924383 Asbestos2-CP-A 09/03/2026 Asha Davidson08/27/2026
1924384 Asbestos2-CP-B 09/03/2026 Asha Davidson08/27/2026
1924385 Asbestos2-CP-C 09/03/2026 Asha Davidson08/27/2026
1924386 Asbestos3-BM-A 09/03/2026 Asha Davidson08/27/2026
1924387 Asbestos3-BM-B 09/03/2026 Asha Davidson08/27/2026
1924388 Asbestos3-BM-C 09/03/2026 Asha Davidson08/27/2026
1924389 Asbestos4-CB-A 09/03/2026 Asha Davidson08/27/2026
1924390 Asbestos4-CB-B 09/03/2026 Asha Davidson08/27/2026
1924391 Asbestos4-CB-C 09/03/2026 Asha Davidson08/27/2026
1924392 Asbestos5-CG-A 09/03/2026 Asha Davidson08/27/2026
1924393 Asbestos5-CG-B 09/03/2026 Asha Davidson08/27/2026
1924394 Asbestos5-CG-C 09/03/2026 Asha Davidson08/27/2026
1924395 Asbestos6-WG-A 09/03/2026 Asha Davidson08/27/2026
This report is intended for use solely by the individual or entity to which it is addressed. This report may not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. It may contain information that is privileged, confidential and otherwise exempt by law from disclosure. If the reader of this information is not the intended recipient or an employee of its intended recipient, you are herewith notified that any dissemination, distribution or copying of this information is strictly prohibited. If you have received this information in error, please notify ETL immediately. Thank you.
Lab Sample Number Client Sample Number Sample Type CompletedSampled Analyst
1924396 Asbestos6-WG-B 09/03/2026 Asha Davidson08/27/2026
1924397 Asbestos6-WG-C 09/03/2026 Asha Davidson08/27/2026
1924398 Asbestos7-RI-A 09/03/2026 Teagan Murphy08/27/2026
1924399 Asbestos7-RI-B 09/03/2026 Teagan Murphy08/27/2026
1924400 Asbestos7-RI-C 09/03/2026 Teagan Murphy08/27/2026
1924401 Asbestos8-IC-A 09/03/2026 Teagan Murphy08/27/2026
1924402 Asbestos8-IC-B 09/03/2026 Teagan Murphy08/27/2026
1924403 Asbestos8-IC-C 09/03/2026 Teagan Murphy08/27/2026
1924404 Asbestos9-PI-A 09/03/2026 Teagan Murphy08/27/2026
1924405 Asbestos9-PI-B 09/03/2026 Teagan Murphy08/27/2026
1924406 Asbestos9-PI-C 09/03/2026 Teagan Murphy08/27/2026
1924407 Asbestos10-IC-A 09/03/2026 Teagan Murphy08/27/2026
1924408 Asbestos10-IC-B 09/03/2026 Teagan Murphy08/27/2026
1924409 Asbestos10-IC-C 09/03/2026 Teagan Murphy08/27/2026
1924410 Asbestos11-PI-A 09/03/2026 Teagan Murphy08/27/2026
1924411 Asbestos11-PI-B 09/03/2026 Teagan Murphy08/27/2026
1924412 Asbestos11-PI-C 09/03/2026 Teagan Murphy08/27/2026
1924413 Asbestos13-PF-A 09/03/2026 Asha Davidson08/27/2026
1924414 Asbestos13-PF-B 09/03/2026 Asha Davidson08/27/2026
1924415 Asbestos13-PF-C 09/03/2026 Asha Davidson08/27/2026
1924416 Asbestos14-WBS-A 09/03/2026 Asha Davidson08/27/2026
1924417 Asbestos14-WBS-B 09/03/2026 Asha Davidson08/27/2026
1924418 Asbestos14-WBS-C 09/03/2026 Asha Davidson08/27/2026
1924419 Asbestos15-CT-A 09/03/2026 Asha Davidson08/27/2026
1924420 Asbestos15-CT-B 09/03/2026 Asha Davidson08/27/2026
1924421 Asbestos15-CT-C 09/03/2026 Asha Davidson08/27/2026
This report is intended for use solely by the individual or entity to which it is addressed. This report may not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. It may contain information that is privileged, confidential and otherwise exempt by law from disclosure. If the reader of this information is not the intended recipient or an employee of its intended recipient, you are herewith notified that any dissemination, distribution or copying of this information is strictly prohibited. If you have received this
1924422 Asbestos16-WG-A 09/03/2026 Asha Davidson08/27/2026
1924423 Asbestos16-WG-B 09/03/2026 Asha Davidson08/27/2026
1924424 Asbestos16-WG-C 09/03/2026 Asha Davidson08/27/2026
1924425 Asbestos17-IC-A 09/04/2026 James Farinas08/27/2026
1924426 Asbestos17-IC-B 09/04/2026 James Farinas08/27/2026
1924427 Asbestos17-IC-C 09/04/2026 James Farinas08/27/2026
1924428 Asbestos18-BM-A 09/04/2026 James Farinas08/27/2026
1924429 Asbestos18-BM-B 09/04/2026 James Farinas08/27/2026
1924430 Asbestos18-BM-C 09/04/2026 James Farinas08/27/2026
1924431 Asbestos19-FT-A 09/03/2026 Teagan Murphy08/27/2026
1924432 Asbestos19-FT-B 09/03/2026 Teagan Murphy08/27/2026
1924433 Asbestos19-FT-C 09/03/2026 Teagan Murphy08/27/2026
1924434 Asbestos20-FT-A 09/03/2026 Teagan Murphy08/27/2026
1924435 Asbestos20-FT-B 09/03/2026 Teagan Murphy08/27/2026
1924436 Asbestos20-FT-C 09/03/2026 Teagan Murphy08/27/2026
1924437 Asbestos21-PL-A 09/04/2026 Teagan Murphy08/27/2026
1924438 Asbestos21-PL-B 09/04/2026 Teagan Murphy08/27/2026
1924439 Asbestos21-PL-C 09/04/2026 Teagan Murphy08/27/2026
1924440 Asbestos22-IC-A 09/04/2026 Teagan Murphy08/27/2026
1924441 Asbestos22-IC-B 09/04/2026 Teagan Murphy08/27/2026
1924442 Asbestos22-IC-C 09/04/2026 Teagan Murphy08/27/2026
1924443 Asbestos23-IC-A 09/04/2026 Teagan Murphy08/27/2026
1924444 Asbestos23-IC-B 09/04/2026 Teagan Murphy08/27/2026
1924445 Asbestos23-IC-C 09/04/2026 Teagan Murphy08/27/2026
1924446 Asbestos24-VP-A 09/04/2026 Teagan Murphy08/27/2026
1924447 Asbestos24-VP-B 09/04/2026 Teagan Murphy08/27/2026
This report is intended for use solely by the individual or entity to which it is addressed. This report may not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. It may contain information that is privileged, confidential and otherwise exempt by law from disclosure. If the reader of this information is not the intended recipient or an employee of its intended recipient, you are herewith notified that any dissemination, distribution or copying of this information is strictly prohibited. If you have received this
1924448 Asbestos24-VP-C 09/04/2026 Teagan Murphy08/27/2026
1924449 Asbestos25-FM-A 09/04/2026 James Farinas08/27/2026
1924450 Asbestos25-FM-B 09/04/2026 James Farinas08/27/2026
1924451 Asbestos25-FM-C 09/04/2026 James Farinas08/27/2026
1924452 Asbestos26-CA-A 09/04/2026 James Farinas08/27/2026
1924453 Asbestos26-CA-B 09/04/2026 James…