Attachment E - Drawings (ELECT).pdf

PDF 4 MB Posted

Attached to
Replace Hospital Nurse Call, MATV, & Public Address System Federal contract opportunity
Solicitation number
36C26224B0002
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22

About this file

This federal contract solicitation seeks proposals to replace the nurse call, MATV, and public address systems at the VA San Diego Healthcare System campus. The current systems are antiquated and failing. Work includes general construction, alterations, mechanical and electrical work, and utility system upgrades at Buildings 1 and 11. Proposals are due by an unspecified date. The contractor must furnish all labor, materials, equipment, transportation, training, and supervision to complete the project in accordance with solicitation terms and conditions, specifications, drawings, and applicable codes. The Department of Veterans Affairs Veterans Health Administration VISN 22 is the contracting agency. The replacement systems must prevent delays or failures in emergency notifications and patient responses on the functioning hospital campus.

View the file

Other files for this federal contract opportunity

Show all 15

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

E001

ELECTRICAL GENERAL NOTES, LEGEND,

SYMBOLS AND ABBREVIATIONS

1. PENETRATION OF CONDUITS, RACEWAYS AND WIRING THROUGH FIRE RATED WALLS, FLOOR AND CEILINGS SHALL BE FIRE-STOPPED IN ACCORDANCE WITH SPECIFICATION SECTION 07 84 00. FIRE STOPPING MATERIALS AND

METHODS SHALL BE A U.L. LISTED ASSEMBLY.

2. METHODS AND MATERIALS SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE (NEC). EQUIPMENT SHALL BE IN ACCORDANCE WITH THE STANDARDS OF NEMA AND ANSI. EQUIPMENT SHALL BE NEW AND LISTED BY U.L. AND INSTALLED IN ACCORDANCE WITH THE CONDITIONS STATED IN THAT LISTING.

3. BEFORE ENERGIZING, EQUIPMENT SHALL BE TESTED TO BE FREE OF GROUNDS AND SHORTS.

4. ALL EQUIPMENT SHALL BE PROPERLY GROUNDED IN STRICT ACCORDANCE WITH THE LATEST EDITION OF NATIONAL ELECTRIC CODE (NEC). PROVIDE EQUIPMENT GROUNDING CONDUCTORS. CONDUIT CANNOT BE USED AS

THE ONLY MEANS OF GROUNDING.

5. FIXTURES AND EQUIPMENT SHALL BE SUPPORTED/MOUNTED TO COMPLY WITH THE SEISMIC REQUIREMENTS OF

THE IBC AND ASCE 7.

6. CONTRACTOR SHALL COORDINATE ELECTRICAL WORK WITH OTHER TRADES.

7. "PROVIDE" MEANS "FURNISH AND INSTALL".

8. ALL ELECTRICAL CONSTRUCTION WORK, METHODS AND MATERIALS SHALL BE IN COMPLIANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE (NEC) AND APPLICABLE GOVERNMENT AND VETERANS

ADMINISTRATION RULES AND REGULATIONS.

9. ALL ABOVE CEILING RACEWAYS, OUTLETS, J.B's AND PULL BOXES SHALL BE HUNG ON THE STRUCTURAL BEAM OR

CONCRETE SLAB. WALL MOUNTING IS NOT PERMITTED.

10. PROVIDE ADDITIONAL ACCESS PANEL, AS REQUIRED, ON HARD CEILING FOR ELECTRICAL DEVICES, EQUIPMENT, JUNCTION BOXES, ETC.

11. ALL CONDUIT RUNS SHALL BE CONCEALED AND RUN ABOVE IN THE INTERSTITIAL SPACE AND PENETRATE THOUGH

THE INTERSTITIAL SPACE FLOOR TO THE ROOM.

12. SEAL ALL ELECTRICAL PENETRATIONS THOUGH FIRE RATED WALL AND CEILING WITH UL APPROVED FIRE STOP SEALANT. SEAL ALL OTHER WALL AND CEILING PENETRATIONS WITH FLEXIBLE NON-HARDENING ELECTRICAL PUTTY. IN JUNCTION BOXES, SEAL THE INSIDE OF THE CONDUIT WITH FLEXIBLE NON-HARDENING ELECTRICAL

PUTTY, UNLESS OTHERWISE NOTED.

13. ALL ELECTRICAL POWER FEEDERS, BRANCH CIRCUITS, CONTROL AND SIGNAL CIRCUITS SHALL BE IN CONDUIT OR CABLE TRAY. ALL WIRES SHALL BE MECHANICALLY PROTECTED. UNPROTECTED WIRES ARE NOT ALLOWED. ALL POWER FEEDERS AND BRANCH CIRCUITS SHALL BE RAN IN CONDUITS FROM TO CABLE TRAY IN THE INTERSTITIAL SPACE; THEN FROM CABLE TRAY VIA CONDUITS INTO THE ROOMS. NO FREE WIRE AREAS ARE ALLOWED.

N/A NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATION

NO. NUMBER

NOM NOMINAL

NTS NOT TO SCALE

O.L. OVERLOAD

P POLE

PA PUBLIC ADDRESS

PH PHASE

PNL PANEL

PVC POLYVINYL CHLORIDE

PWR POWER

(R) RELOCATE

RECEPT RECEPTACLE

RM ROOM

RPS REMOTE POWER SUPPLY

SCHED SCHEDULE

ST STREET

STP SHIELDED TWISTED WIRE PAIR

SW SWITCH

SWBD SWITCHBOARD

TBD TO BE DETERMINED

TELE/TEL. TELEPHONE

TELECOM TELECOMMUNICATION

TEMP TEMPORARY

TERM TERMINAL

TV TELEVISION

TYP TYPICAL

U/G UNDERGROUND

UBC UNIFORM BUILDING CODE

UL UNDERWRITERS LABORATORIES

UON UNLESS OTHERWISE NOTED

V VOLT

VA VOLTS AMPS

VAMC VETERENS AFFAIRS MEDICAL CENTER

VOIP VOICE OVER INTERNET PROTOCOL

W WIRE

WP WEATHERPROOF

+12"A.F.F. MOUNTING HEIGHT ABOVE FINISHED FLOOR

OR GRADE

A/AMP AMPERE

AFF ABOVE FINISHED FLOOR

ANSI AMERICAN NATIONAL STANDARDS INSTITUTE

AWG AMERICAN WIRE GAUGE

B.C. BARE COPPER

BLDG BUILDING

C CONDUIT

CAT CATALOG

CKT CIRCUIT

CLG CEILING

CO CONTRACTING OFFICER

COMM COMMUNICATION

CONN CONNECTED

COR CONTRACTING OFFICER REPRESENTATIVE

CU COPPER

DIST DISTRIBUTION

DWG DRAWING

ELEC'L ELECTRICAL

ELECT ELECTRIC

ELEV ELEVATION

EMT ELECTRICAL METALLIC TUBING

EQUIP EQUIPMENT

EXIST/(E) EXIST

FLR FLOOR

FT FOOT, FEET

GND GROUND

GOV GOVERNMENT

HT HEIGHT

IBC INTERNATIONAL BUILDING CODE

J.B. JUNCTION BOX

LOC LOCATION

LTG LIGHT

MAX MAXIMUM

MECH'L MECHANICAL

MIN MINIMUM

MISC MISCELLANEOUS

MTD MOUNTED

MTG MOUNTING

(N) NEW

R. BLAYLOCK JR

SP

GENERAL NOTES ELECTRICAL ABBREVIATIONS

DETAIL NUMBER

DRAWING NUMBER ON WHICH DETAIL IS DRAWN

SP

LEGEND

XX###

JUNCTION BOX

CONDUIT OR WIRE RUN EXPOSED OR ABOVE THE CEILING

CONDUIT OR WIRE RUN UNDERGROUND

HATCHED GRAY THIN LINE INDICATES DEMOLISH PER DRAWING NOTES

BOLD LINE INDICATES NEW WORK

GRAY THIN LINE INDICATES EXISTING WORK

TV COAXIAL CABLE OUTLET

SPEAKER-PUBLIC ADDRESS/PAGING

PAGING STATION

EQUIPMENT RACK

NURSE CALL CENTRAL MONITORING STATION

NURSE CALL DUTY STATION

NOTE REFERENCE

JJ

TV

R0X

PS

N

N

CMS

DTY

TV COAXIAL CABLE OUTLET CEILING MOUNTED-C

CAMERA

CCTV CLOSE CIRCUIT TV

TV

R. BLAYLOCK JRRevisions: Date: R. BLAYLOCK JR

14. THE CONTRACTOR SHALL PROVIDE A COMPREHENSIVE FIELD SURVEY OF THE SITE. THIS SURVEY SHALL DOCUMENT EXISTING EQUIPMENT, AND RELATED MATERIAL, LOCATIONS AND BE SUBMITTED TO THE VA PRIOR TO COMMENCEMENT OF THE WORK. IN MANY CASES, THE EQUIPMENT MAY BE CONCEALED IN WALLS, CEILINGS OR INTERSTITIAL SPACES. EQUIPMENT, WIRING, CONDUIT AND OTHER MATERIALS SHOWN ON THE PLANS ARE APPROXIMATE ONLY AND SHALL NOT BE RELIED ON. FOR BIDDING PURPOSES, THE CONTRACTOR SHALL ALLOW A

MINIMUM OF A 50 FT RADIUS AROUND EQUIPMENT LOCATION.

ST A T E O F CA L I F ORN I A

RE

G

IS

TE

RED PROFESS IONAL ENGINEERA U

GUST I NE K . L EUNG

E L E C T R I C A L

CMS CENTRAL MONITORING SYSTEM

PPE PERSONAL PROTECTIVE EQUIPMENT

WALL MOUNTED PAGING SPEAKER

AMBIENT NOISE MICROPHONE

VOLUME CONTROLVC

WS

AM

UPDNUPDN

BRIDGE

36" HIGH WALL

36" HIGH WALL

VOID

050-1-1

ALCOVE

VOID

062-1-1

VOID

068-1-1

VOID

052-1-1

VOID

074-1-1

VOID

010-1-1

VOID

028-1-1

VOID

027-1-1

VOID

026-1-1

VOID

023-1-1

VOID

049-1-1

WAITER

DW3-1-1

VOID

024-1-1

N

1 DTY

EY101

BUILDING 1 - FIRST FLOOR NURSE

CALL PLAN

NORTH

SCALE: NONEEY101

1 BLDG. 1, FIRST FLOOR PLAN

Project Number:

Building Number:

Drawing Number:

Project Title:

Location:

Issue Date: Checked: Drawn:

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase:ARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

K F DAVIS

ENGINEERING, INC

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.COM

(925) 743-8884

H :\R ev it

T em p Fo ld er

\V

AS

D _R ep la ce N ur se

C al l M

AT

V

PA

_v

_r on

.b la yl oc k.

rv t

G. FERNANDEZ

REPLACE HOSPITAL NURSE CALL,

MATV, AND PUBLIC ADDRESS

664-18-331

SAN DIEGO, CA

Revisions: Date: 02/02/2024

100% SUBMITTAL

ASBESTOS CONTAINING MATERIALS EXIST THROUGHOUT THIS

FACILITY AND IN THE ABOVE CEILING SPACES. THE

CONTRACTOR SHALL TAKE EVERY PRECAUTION NECESSARY

TO PROTECT PERSONS FROM EXPOSURE. THESE

SAFEGUARDS WILL INCLUDE:

1. ALL CONTRACTORS PERSONNEL WHO WILL BE ENTERING

THE ABOVE CEILING SPACES AND/OR REMOVING ANY

CEILINGS, WALLS OR CEILING TILES SHALL BE TRAINED IN

THE IDENTIFICATION OF, AND HANDLING OF, ASBESTOS

CONTAINING MATERIALS. THIS TRAINING SHALL BE A 40

HOUR ASBESTOS TRAINING CLASS, AS APPROVED BY THE

VA, WITH CERTIFICATION.

2. ALL CONTRACTORS PERSONNEL WHO WILL BE ENTERING

THE ABOVE CEILING SPACES AND/OR REMOVING ANY

CEILINGS, WALLS OR CEILING TILES SHALL OBTAIN AND

WEAR, AT ALL TIMES, PERSONAL PROTECTIVE EQUIPMENT

(PPE) INCLUDING, BUT NOT LIMITED TO, RESPIRATORS

PRIOR TO ENTRY INTO ABOVE CEILING SPACES.

3. PRIOR TO ENTRY INTO ABOVE CEILING SPACES,

CONTRACTOR PERSONNEL SHALL UNDERGO AND SUBMIT,

A MEDICAL EVALUATION FOR USE OF A RESPIRATOR.

4. ANY WORK BELOW THE CEILING SUCH AS REMOVAL OF

CEILING TILES, GYPSUM BOARD CEILINGS, PA SPEAKERS

OR OTHER DISTURBANCE OF CELING OR WALL MATERIALS

SHALL BE PERFORMED WITH PROPER BARRICADES

INCLUDING THE USE OF CONTAINMENT CUBES. ALL SUCH

PROTECTIVE BARRICADES SHALL BE PROVIDED BY THE

CONTRACTOR.

THE ARCHITECT-ENGINEER AND HIS/HER CONSULTANTS

SHALL HAVE NO RESPONSIBILITY FOR THE DISCOVERY,

PRESENCE, HANDLING, REMOVAL OR DISPOSAL OF, OR

EXPOSURE OF PERSONS TO HAZARDOUS MATERIALS, IN ANY

FORM AT THE PROJECT SITE. THE CONTRACTOR IS SOLELY

RESPONSIBLE FOR JOB SITE SAFETY WHICH INCLUDES ALL

TRAINING AND SAFEGUARDS NECESSARY TO PROTECT

HIS/HER EMPLOYEES, VA PERSONNEL VISITORS AT THE SITE

AND ANY OTHER PERSONS.

ASBESTOS WARNING

SHEET NOTES

GENERAL NOTES

R. KORTE

1.

2.

PROVIDE RAULAND RESPONDER 5 NURSE CALL DUTY

STATION MODEL 353100 OR APPROVED EQUAL.

COORDINATE EXACT LOCATION WITH COR. RUN CAT6A

CABLE TO THE DEVICE.

DEVICE LOCATIONS ARE DIAGRAMMATIC. CONTRACTOR

IS TO COORDINATE EXACT LOCATION WITH THE COR.

ALL NURSE CALL DEVICES SHALL BE RAULAND

RESPONDER 5.

3. CONNECT NEW NURSE CALL DEVICE TO EXISTING

NURSE CALL RESPONDER 5 SYSTEM. PROVIDE WIRING

& CONDUIT PER DEVICE MANUFACTURER'S

RECOMMENDATION. RUN THE CIRCUIT BEHIND WALLS

AND IN INTERSTITIAL SPACE.

4.

5.

THE CONTRACTOR IS ADVISED THAT EQUIPMENT,

PIPING AND OTHER UTILITIES EXIST WITHIN THE

INTERSTITIAL SPACE. IT IS THE CONTRACTOR'S SOLE

RESPONSIBILITY TO DETERMINE THE BEST ROUTING

FOR ALL NEW CONDUITS AND/OR CABLE TRAYS.

THE 1ST FLOOR LOCAL NURSE CALL SUBPANEL IS IN

TEL/COM DATA ROOM 1190

ST A T E O F CA L I F ORN I A

RE

G

IS

TE

RED PROFESS IONAL ENGINEERA U

GUST I NE K . L EUNG

E L E C T R I C A L

N

N

N

N

D

TY

D

TY

DTY

DTY

3148B

STORAGE

ROOM

SCOPE

ROOM

CLEAN

3148A

ROOM

DIRTY

ROOM

READING

HEALTHCARE

OCCUPANCY

(21,377 sf)

BUSINESS

OCCUPANCY

(21,750 sf)

BUSINESS

OCCUPANCY

(7,102 sf)

HEALTHCARE

OCCUPANCY

(9,617 sf)

HEALTHCARE

OCCUPANCY

(11,280 sf)

SHOWER

2 BED RM

2 BED RM

2 BED RM 3372

2 BED RM

2 BED RM

UTILITY

CLEAN

3363A

UTILITY

SOILED

4 BED RM

BREAK

WAITING

3357A

STORAGE

EQUIPMENT

3357B

TOILET

4 BED RM

UTILITY

CLEAN

3353A

UTILITY

SOILED

2 BED RM

2 BED RM

4 BED RM

STATION

NURSE

TOI.

STATION

NURSE

EQUIP RM

CLEAN

ROOM

MED 3342

2 BED RM

2 BED RM

LINEN

CLEAN

RM

MEDICATION

CORRIDOR

CORRIDOR

SHOWER

SHOWER

SHOWER

SHOWER

SHOWER

PHYSICIANS

OFFICE

HAC

OFFICE

RECEPTION

CONFERENCE

RM

PATIENT

BED ROOM

PATIENT

BED ROOM

SHOWER

ROOM

MED

SHOWER

WORK RM

CORRIDOR

PHARMACY

WAITING

PHYSICIANS

OFFICE

SW8-1

STAIR

OFFICE

OFFICE

CORR.

OFFICE

SOCIAL

WORKER

OFF.

RESIDENT

ON CALL

SHOWER

SHOWER

ALCOVE

OFFICE

SHOWER

CORRIDOR

STATION

NURSE

PATIENT

BED ROOM

SHOWER

ROOM 1

OPERATING

UTILITY

SOILED

3397A

KITCHEN

PATIENT

BED ROOM

SHOWER

OFFICE

PHYS.

PHYS.

CORR.

3308A

OFFICE

3308B

OFFICE

TOI.

WORK ROOM

RESIDENT 3316

WORK ROOM

RESIDENT

3317A

OFFICE

OFFICE

COMPUTER

SHOWER

HAC

PHYS.

PHYSICIAN

SLEEP RM

PHYSICIAN 3308C

STOR.

GENERAL

TOI.

TOI.

3402A

T AND L

CALL

ON-

CALL

ON-

CALL

ON-

CALL

ON-

CALL

ON-

CALL

ON-

CALL

ON-

CALL

ON-

CALL

ON-

CALL

ON-

CALL

ON-

OFFICE 3280A

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

3282A

OFFICE

3276B

OFFICE

3276A

OFFICE

OFFICE

OFFICE

3275B

OFFICE

OFFICE

3269A

OFFICE

3273C

OFFICE

OFFICE

OFFICE

3255A

OFFICE

3275A

OFFICE

3251A

OFFICE

OFFICE

OFFICE

3262A

OFFICE

OFFICE

OFFICE

3267A

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

3246A

OFFICE3221

OFFICE

OFFICE

3217B

MECH. 3217

OFFICE

3217A

OFFICE 3216

OFFICE

3202A

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE3193

OFFICE

OFFICE

OFFICE

OFFICE

3186A

OFFICE

3186B

OFFICE

3185A

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE 3170

OFFICE

3162F

OFFICE

3162E

OFFICE

3162D

OFFICE

3162C

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE 3008

OFFICE

3008A

OFFICE3007

OFFICE

OFFICE

OFF.

3162G

RM

ONFERENCE

EXAM

EXAM

EXAM

EXAM

EXAM

EXAM

CONTRACTOR

EXAM

EXAM

EXAM

OFFICE

OFFICE

3231A

OFFICE

OFFICE

OFFICE

OFFICE

EXAM

OFFICE

OFFICE

OFFICE

CORR.

CORR.

CORR.

CORR.

CORR.

CORR.

CORR.

CORR.

ROOM 2

OPERATING

ROOM 3

OPERATING

ROOM 4

OPERATING 3150

ROOM 6

OPERATING

ROOM 5

OPERATING

STOR.

EQUIP.

3 BED RM

3 BED RM3127

1 BED RM

RM

1 BED

RM

1 BED

BREAKRM

3162A

BREAKRM

SUPPLY

STERILE

CONF RM

CONF RM

LOUNGE

SLEEP RM

CONF RM

CONF RM

CORR.

RESTRM

MEN

WOMEN

BED RM

BED RM

BED RM

BED RM

STATION

NURSE

UTILITY

CLEAN

249A

UTILITY

CLEAN

CORR.

3273B

CORR.

KITCHEN

3286A

WAITING

SHOWER

SHOWER

SHOWER

SHOWER

SHOWER

LAB

UTILITY

CLEAN

UTILITY

SOILED

CORR.

CORR.

NURSE STATION

CORR.

SLEEP RM

ON-CALL

3174A

SLEEP RM

ON-CALL

3174B

SLEEP RM

ON-CALL

PHYSICIANS

OFFICE

SHOWER

PHYSICIAN

TOI.

MALE/

FEMALE

TOI.

SHOWER

SHOWER

TOI

TOI

WAITING

TOILET

3209A

RM

CLEAN

3207A

T AND L

3207B

OFFICE

BEDS (5)

PHYSICIAN

CORR.

PHYSICIAN

PHYSICIAN

PHYSICIAN

3018A

PHYSICIAN

HAC

ANTI RM

3214A

RM

CLEAN

OFFICE

TOI.

HAC

SHOWER

TOI.

TOI.

SWING

SHOWER

TOI.

LAB

TOI.

PHYSICIAN

STOR.

GEN.

CONFERENCE

TOI.

3132A

UTILITY

HAC

T AND L

ANTI RM

AIR LOCK

STATION

NURSE

CORR.

RM

EXAM

ROOM

REST

SW7-1

STAIR

SW3-1

STAIR

SW4-1

STAIR

SW5-1

STAIR

SW6-1

STAIR

TOI.

SHOWER

TOI.

TOI.

TOI.

TOI.

TOI

EXAM

KITCHEN

NUTRITION 3130

PREP

MED

SHOWER

SHOWER

SHOWER

SHOWER

TOI.

TOI.

GENERAL

STORAGE

SHOWER

SHOWER3315

SHOWER

SHOWER

SHOWER

3003A

TOI.(M)

TOI.(F)

MED PREP

CORR.

PHYSICIAN

PHYSICIAN

CORR.

3214A-1

AIR LOCK

EQUIPMENT

STORAGE

SW6-1

NO

S1

NO S4NO S3NO S2

NO P3NO P2NO

P1

NO P6NO P5NO P4

UP

RAMP

UPDN UPDN

9'-11 15__

" 9'-11 15__

3E SKY

89 7 6

BED (5)

FEC

FEC

OPEN TO BELOW

OPEN TO BELOW

OPEN TO BELOW

OPEN TO BELOW

K

BIO

K

K

K

1.

2.

EY102

BUILDING 1 - THIRD FLOOR NURSE

CALL PLAN

SCALE: NONEEY102

1 BLDG. 1, THIRD FLOOR

NORTH

Project Number:

Building Number:

Drawing Number:

Project Title:

Location:

Issue Date: Checked: Drawn:

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase:ARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

K F DAVIS

ENGINEERING, INC

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.COM

(925) 743-8884

H :\R ev it

T em p Fo ld er

\V

AS

D _R ep la ce N ur se

C al l M

AT

V

PA

_v

_r on

.b la yl oc k.

rv t

G. FERNANDEZ

REPLACE HOSPITAL NURSE CALL,

MATV, AND PUBLIC ADDRESS

664-18-331

SAN DIEGO, CA

Revisions: Date: 02/02/2024

100% SUBMITTAL

ASBESTOS CONTAINING MATERIALS EXIST THROUGHOUT THIS

FACILITY AND IN THE ABOVE CEILING SPACES. THE

CONTRACTOR SHALL TAKE EVERY PRECAUTION NECESSARY

TO PROTECT PERSONS FROM EXPOSURE. THESE

SAFEGUARDS WILL INCLUDE:

1. ALL CONTRACTORS PERSONNEL WHO WILL BE ENTERING

THE ABOVE CEILING SPACES AND/OR REMOVING ANY

CEILINGS, WALLS OR CEILING TILES SHALL BE TRAINED IN

THE IDENTIFICATION OF, AND HANDLING OF, ASBESTOS

CONTAINING MATERIALS. THIS TRAINING SHALL BE A 40

HOUR ASBESTOS TRAINING CLASS, AS APPROVED BY THE

VA, WITH CERTIFICATION.

2. ALL CONTRACTORS PERSONNEL WHO WILL BE ENTERING

THE ABOVE CEILING SPACES AND/OR REMOVING ANY

CEILINGS, WALLS OR CEILING TILES SHALL OBTAIN AND

WEAR, AT ALL TIMES, PERSONAL PROTECTIVE EQUIPMENT

(PPE) INCLUDING, BUT NOT LIMITED TO, RESPIRATORS

PRIOR TO ENTRY INTO ABOVE CEILING SPACES.

3. PRIOR TO ENTRY INTO ABOVE CEILING SPACES,

CONTRACTOR PERSONNEL SHALL UNDERGO AND SUBMIT,

A MEDICAL EVALUATION FOR USE OF A RESPIRATOR.

4. ANY WORK BELOW THE CEILING SUCH AS REMOVAL OF

CEILING TILES, GYPSUM BOARD CEILINGS, PA SPEAKERS

OR OTHER DISTURBANCE OF CELING OR WALL MATERIALS

SHALL BE PERFORMED WITH PROPER BARRICADES

INCLUDING THE USE OF CONTAINMENT CUBES. ALL SUCH

PROTECTIVE BARRICADES SHALL BE PROVIDED BY THE

CONTRACTOR.

THE ARCHITECT-ENGINEER AND HIS/HER CONSULTANTS

SHALL HAVE NO RESPONSIBILITY FOR THE DISCOVERY,

PRESENCE, HANDLING, REMOVAL OR DISPOSAL OF, OR

EXPOSURE OF PERSONS TO HAZARDOUS MATERIALS, IN ANY

FORM AT THE PROJECT SITE. THE CONTRACTOR IS SOLELY

RESPONSIBLE FOR JOB SITE SAFETY WHICH INCLUDES ALL

TRAINING AND SAFEGUARDS NECESSARY TO PROTECT

HIS/HER EMPLOYEES, VA PERSONNEL VISITORS AT THE SITE

AND ANY OTHER PERSONS.

ASBESTOS WARNING

SHEET NOTES

GENERAL NOTES

R. KORTE

PROVIDE RAULAND RESPONDER 5 NURSE CALL DUTY

STATION MODEL 353100 OR APPROVED EQUAL.

COORDINATE EXACT LOCATION WITH COR. RUN CAT6A

CABLE TO THE DEVICE.

DEVICE LOCATIONS ARE DIAGRAMMATIC. CONTRACTOR

IS TO COORDINATE EXACT LOCATION WITH THE COR.

ALL NURSE CALL DEVICES SHALL BE RAULAND

RESPONDER 5.

3. CONNECT NEW NURSE CALL DEVICE TO EXISTING

NURSE CALL RESPONDER 5 SYSTEM. PROVIDE WIRING

& CONDUIT PER DEVICE MANUFACTURER'S

RECOMMENDATION. RUN THE CIRCUIT BEHIND WALLS

AND IN INTERSTITIAL SPACE

4.

5.

THE CONTRACTOR IS ADVISED THAT EQUIPMENT,

PIPING AND OTHER UTILITIES EXIST WITHIN THE

INTERSTITIAL SPACE. IT IS THE CONTRACTOR'S SOLE

RESPONSIBILITY TO DETERMINE THE BEST ROUTING

FOR ALL NEW CONDUITS AND/OR CABLE TRAYS.

THE THIRD FLOOR LOCAL NURSE CALL SUBPANEL IS IN

3RD FLOOR WEST INTERSTITIAL SPACE AREA

ST A T E O F CA L I F ORN I A

RE

G

IS

TE

RED PROFESS IONAL ENGINEERA U

DN

OFFICE

TOILET

MALE

LOCKERS

MALE

ROOM

CONFERENCE

AREA

STORAGE

OFFICE

STORAGE

STERILE

CART HOLDING AREA

STERILE STORAGE

CORRIDOR

OFFICE

SERVICES

BUILDING

RM.

ELEC.

B174A

LOUNGE

LOCKERS

FEMALE

TOILET

FEMALE

LOCKERS

MALE

TOILET

MALE

JANITOR

CART AREA

ROOM

VENDOR

AND BREAKOUT

CLEAN RECEIVING

CORRIDOR

DETERGENT

DECONTAMINATION

SOILED /

ANTE ROOM

PROCESSING

SCOPE

DRYING

TRANSFER

CART WASH

CARTWASH

AUTOMATIC

WASH

INSTRUMENT

STORAGE

BULK

DISPATCH

HALLWAY

TOILET

FEMALE

LOCKERS

FEMALE

SIGNAL ROOM

DATA/TELE

ETO

STORAGE

AREA

STAGING

DRUGS

RM.

JANITOR

B173C

OFFICE

OFFICE

UP

DUMB

DW1-B-1

FEC

B190

A/C SHOP

B190A

A/C SHOP

B254

A/C SHOP

B252

OFFICES(S)

B253

A/C SHOP

B255

PIPE SHOP

B191

STORAGE

B251

MECHANICAL

B200

ELECTRONICS

B177L

STORAGE

GENERAL

B177K

STORAGE

OIT

B177J

STORAGE

GENERAL

B128

KITCHEN

B177F

UTILITY

B177E

STORAGE

EQUIPMENT

B177H

RECEIVING

B236

AUTOPSY

B247

OFFICE

B248

OFFICE

B249

OFFICE(S)

B176

OFFICE(T)

B177B

CORR.

B171A

OFFICE(T)

B117P

CORR.

B173

STORAGE

OXYGEN

B177C

CORR.

B177A

CORR.

B177N

STORAGE

GENERAL

B177D

STORAGE

GENERAL

B191R

CORRIDOR

B194

STOR.

GENERAL

B194A

STOR.

GENERAL

B245

STOR.

MORGUE

B244

STOR.

MORGUE

B235

REFERIGER. B241

OFFICE

B234

OFFICE

B232B

OFFICE

B181

REFER.

B138

REFER.

B137

REFER.

B213

BIOMED

B250

OFFICE(S)

B232A

OFFICE

B233

OFFICE(T)

B177M

CORR. B117B

CORR.

B232

OFFICE(T)

B231

MECHANICAL

B136

REFER.

B183A

STOR.

GENERAL

B183

STOR.

GENERAL

B129

OFFICE(S)

B130

OFFICE(S)

B166

ELECTRICAL

B188

ELECTRICAL

B167

EQUIPMENT

OIT

B165

TELEPHONE

B165A

OIT STOR.

B176

OFFICE

B131

OFFICE(S)

B126

CONFERENCE

B127

OFFICE(S)

B126D

OFFICE(S)

B127A-1

OFFICE(S)

B132

OFFICE(S)

B126C

OFFICE(S)

B114A

OFFICE(S)

B114

OFFICE(S)

B115

OFFICE(S)

B134

MANAGEMENT

RECORDS

B122

DISHWASHING

B119

WASH

CAR

B184

STOR.

GENERAL

B185

STOR.

GENERAL

B128B

STOR.

GENERALB186

STOR.

GENERAL

B140A

REFER.

B140

CORR.

B143

LAB

B142A

LAB

B142

LAB

B142E

LAB

B147

RESIDENT B156A

LAB

B156A

LAB

B198

ELECTRIC SHOP

B240

CORR.

B212

CORR.

B204

CORR.

B210

CARPENTRY

B210C

MECHANICAL

B141

MICROSCOPE FACILITY

CORE ELECTRON

B142D

LAB

B142B

SUPPLY

STERILE

B144

LOCKER(F)

B145

CONF. RM /OFFICE(S)

PHARMACY

B144A

LOCKER(F)

B149

LOCKER(M)

B152

OFFICE

PHARMACOECO.

BB152A

OFFICE(S)

B125

CORR.

B123

PREP

B157

VAULT

B153

STOR.

VAULT

B121

CORR.

B152E

ED. TRAINING OFF.(S)

DIR. PHARM.

B152D

DATA APPS.ANALYSIS OFF.(S)

DIR. PHARM.

B155

ADMIN.0FFICE

PHARMACY

B160

KITCHEN

B155C

SVC OFF.(S)

CHIEF PHARM.

B159B

OFFICE

B159A

OFFICE

B217

STOR.

EQUIPMENT

B223B

OFFICE(T)

B218

OFFICE(S)

B246

CORR.

B100

LOBBY

B156

AREA

PHARMACY

B215

STORAGE

B215A

STORAGE

B215B

CORRIDOR

B215B

CORRIDOR

B128C

OFFICE(S)

DIET INFO.

B117

CORRIDOR

B191J

STORAGE

GENERAL

B191G

STORAGE

OIT

B191P

STORAGE

GENERAL

B1000

CENTER OFFICE

IT SERVICE

B171

OFFICE

B201A

KITCHEN

B200A

STOR.

GENERAL

B205

KEYS

B216

LINEN

SOIL

B217A

STOR.

EQUIPMENT

SW6-B-1

STAIRS

SW7-B-1

STAIRS

SW8-B-1

STAIRS

B206

OFFICE(S)

B189B

STOR.

GENERAL

B198A

OFFICE(S)

SW1-B-1

STAIR

B191Q

CORR.

B191H

STORAGE

GENERAL

B214

OFFICE

B211

OFFICE

B217B

ELEC

B217C

ELEC

B212B

CORR.

B162

SERVICE OFFICE(S)

ENVIRONMENTAL

B210B

MECHANICAL

B210A

OFFICE(S)

B220

STOR.

GENERAL

B224

STOR.

HAC

B229

OPERATIONS

MGR. OFF.

B108A

STOR.

GENERAL

B101

LOBBY

B108B

STOR.

EQUIPMENT

B109

CORRIDOR

B108C

STOR.

EQUIPMENT

SW13-B-1

STAIRS

B201

STOR.

MAINTENANCE

B202

SIGNAGE

B239

CORR.

B238

CORR.

B158

STAIR

B182

KITCHEN

STOR.

B146

SHOWER(F)

B189A

STOR.

B125A

MALE TOI.

B133

FEMALE TOI.

B176A

MALE TOI.

B176B

MALE TOI.

W9-B-1

STAIR

B180

MECH.

B135A

HAC

B148

SHOWER(M)

B149A

LOCKER(M)

B149B

MECH.

B155B

OFF.OFF.(S)

ADMIN.

B155E

CORR.

B155F

CORR.

B154

CORR.

B172C

OFFICE

B196

ELEC. RM

S5-B-1

PET ELEV

B212A

CORR.

B191A

MALE TOI.

B191B

MALE TOI.

B242

MALE TOI.

B243

FEMALE TOI.

B128A

MGR. OFFICE(S)

CLINICAL NUTRITION

B128D

STOR.

GENERAL

SW11-B-1

STAIRS

SW12-B-1

STAIRS

B191K

STORAGE

GENERAL

B191E

UPPERB191D

STORAGE

GENERAL

B191C

STORAGE

B191F

STORAGE UPPER

GENERAL

B191C

STORAGE LOWER

GENERAL

B237

HAC

B232C

RECEPTION

B230A

TELECOM

B108

MECHANICAL

B152B

SAFETY OFF.(S)

DIR. MED.

B155A

PHARM. SVC OFF.(S)

ASS. CHIEF

B135

MECH.

B126B

OFFICE

B126A

OFF.(S) NUTRITION FOOD SER.

ED. SECT.

B191M

CORR.

B191L

STOR.

B152C

COOR.OFF.(S)

U.O.P. REGIONAL

B141A

CORR.

B230

OFFICE

B224A

CORR.

B222

MALE TOI.

B187

HAS

B225

CORRIDOR

B104

TOILET

B172C

STOR.

SPS SUPPLY

B125B

CORR.

SW10-B-1

LIFT

B120

STORAGE

B125C

CORR.

B144B

DRESSING RM

B155G

CORR.

TUNNEL

STORAGE

B195B

CART WASH

B102A

HSK

B227

MALE TOILET

B107

FEMALE TOILET

B106

CORRIDOR

CORRIDOR

B111

B116

SPS

STORAGE

B112

SPS

ADMINISTRATION

OFFICE(S)B110

DECON

B102

SPS

PREP

AREAB105

STERILIZER

B102B

GAS ETO

B102C MENS LOCKER

B228

CORRIDOR

BREAK ROOM

B226

SPS

STERILE

STORAGEB197

UTILITY AND EQUIPMENT STORAGE

B223

VACANT STORAGE

PATIENT

EFFECTSB223C

GENERAL STORAGE

B223D

CORRIDOR

B191N

GENERAL

STORAGE

B195C

MATERIAL MANAGEMENT OFFICE

B172A

EQUIPMENT STORAGE

B112A

SPS

SUPPLY

STORAGEB172B

EQUIPMENT STORAGE

B172D

EQUIPMENT

STORAGE

B117

GENERAL STORAGE

B175I

B223A

ELECTRICAL

UP

UPDNUPDN

B142C

DARK RM

ELEVATOR

S1

ELEVATOR

S2

ELEVATOR

S3

ELEVATOR

S4

TV

M&O OFFICE

(FUTURE TV

SHOP)

TV

TV

TV

TVTV

TV

TV

TV

2TV

-C

ET101

BUILDING 1 - BASEMENT MATV

PLAN

NORTH

1/16" = 1'-0"ET101

1 BLDG. 1, BASEMENT FLOOR PLAN

R. BLAYLOCK JR

1.

2.

3.

PROVIDE NEW RG-6 COAXIAL CABLE AND TV OUTLET TO

ALL TV's IN ALL AREAS AS SHOWN IN THIS FLOOR LEVEL

4. RUN COAXIAL CABLE ABOVE THE IN INTERSTITIAL SPACE

AND CONCEALED BEHIND FINISH WALLS, UNLESS

OTHERWISE NOTED.

PROVIDE NEW TV FEED TO THE M&O OFFICE. COORDINATE

TV OUTLET EXACT LOCATION WITH THE COR.

PROVIDE NEW TV FEED TO THE FUTURE TV SHOP.

COORDINATE TV OUTLET EXACT LOCATION WITH THE COR.

Project Number:

Building Number:

Drawing Number:

Project Title:

Location:

Issue Date: Checked: Drawn:

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase:ARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

K F DAVIS

ENGINEERING, INC

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.COM

(925) 743-8884

H :\R ev it

T em p Fo ld er

\V

AS

D _R ep la ce N ur se

C al l M

AT

V

PA

_v

_r on

.b la yl oc k.

rv t

G. FERNANDEZ

REPLACE HOSPITAL NURSE CALL,

MATV, AND PUBLIC ADDRESS

664-18-331

SAN DIEGO, CA

Revisions: Date: 02/02/2024

100% SUBMITTAL

ASBESTOS CONTAINING MATERIALS EXIST THROUGHOUT THIS

FACILITY AND IN THE ABOVE CEILING SPACES. THE

CONTRACTOR SHALL TAKE EVERY PRECAUTION NECESSARY

TO PROTECT PERSONS FROM EXPOSURE. THESE

SAFEGUARDS WILL INCLUDE:

1. ALL CONTRACTORS PERSONNEL WHO WILL BE ENTERING

THE ABOVE CEILING SPACES AND/OR REMOVING ANY

CEILINGS, WALLS OR CEILING TILES SHALL BE TRAINED IN

THE IDENTIFICATION OF, AND HANDLING OF, ASBESTOS

CONTAINING MATERIALS. THIS TRAINING SHALL BE A 40

HOUR ASBESTOS TRAINING CLASS, AS APPROVED BY THE

VA, WITH CERTIFICATION.

2. ALL CONTRACTORS PERSONNEL WHO WILL BE ENTERING

THE ABOVE CEILING SPACES AND/OR REMOVING ANY

CEILINGS, WALLS OR CEILING TILES SHALL OBTAIN AND

WEAR, AT ALL TIMES, PERSONAL PROTECTIVE EQUIPMENT

(PPE) INCLUDING, BUT NOT LIMITED TO, RESPIRATORS

PRIOR TO ENTRY INTO ABOVE CEILING SPACES.

3. PRIOR TO ENTRY INTO ABOVE CEILING SPACES,

CONTRACTOR PERSONNEL SHALL UNDERGO AND SUBMIT,

A MEDICAL EVALUATION FOR USE OF A RESPIRATOR.

4. ANY WORK BELOW THE CEILING SUCH AS REMOVAL OF

CEILING TILES, GYPSUM BOARD CEILINGS, PA SPEAKERS

OR OTHER DISTURBANCE OF CELING OR WALL MATERIALS

SHALL BE PERFORMED WITH PROPER BARRICADES

INCLUDING THE USE OF CONTAINMENT CUBES. ALL SUCH

PROTECTIVE BARRICADES SHALL BE PROVIDED BY THE

CONTRACTOR.

THE ARCHITECT-ENGINEER AND HIS/HER CONSULTANTS

SHALL HAVE NO RESPONSIBILITY FOR THE DISCOVERY,

PRESENCE, HANDLING, REMOVAL OR DISPOSAL OF, OR

EXPOSURE OF PERSONS TO HAZARDOUS MATERIALS, IN ANY

FORM AT THE PROJECT SITE. THE CONTRACTOR IS SOLELY

RESPONSIBLE FOR JOB SITE SAFETY WHICH INCLUDES ALL

TRAINING AND SAFEGUARDS NECESSARY TO PROTECT

HIS/HER EMPLOYEES, VA PERSONNEL VISITORS AT THE SITE

AND ANY OTHER PERSONS.

ASBESTOS WARNING

LEGEND

SHEET NOTES

GENERAL NOTES

PROVIDE SPLITTERS AND TAPS AS NECESSARY TO

BRANCH OUT THE LINE GOING TO THE TV's.

PROVIDE AMPLIFIERS AND / OR ATTENUATORS AS

NECESSARY TO OBTAIN A CLEAR RECEPTION ON ALL

TV's.

ST A T E O F CA L I FORN I A

RE

G

IS

TE

RED PROFESS IONAL ENGINEERA U

M&O OFFICE

(FUTURE TV

SHOP)

AC-62

AC-38

UP

B-201B

UP

B-190B

UP

B-1000A

B-191F

B-191D B-191E

TUNNEL

BS1

ELEV

BS2

ELEV

BS3

ELEV

BS4

ELEV

P1

ELEV

P2

ELEV

P3

ELEV

P4

ELEV

P5

ELEV

P6

ELEV

ELEVATOR

NO S3

ELEVATOR

NO S2

ELEVATOR

NO P3

ELEVATOR

NO P2

ELEVATOR

NO P1

ELEVATOR

NO S4

ELEVATOR

NO S1

TO FIRST FLOOR

INTERSTITIAL

TV

TV

TVTVTV

TVTV

TV

1 (TYP)

TV

TV

TO

BLDG 11

TV

TV

TV

BUILDING 1 - BASEMENT -

INTERSTITIAL PLAN

NORTH

1/16" = 1'-0"ET101

1 BLDG. 1, BASEMENT FLOOR INTERSTITIAL PLAN

Project Number:

Building Number:

Drawing Number:

Project Title:

Location:

Issue Date: Checked: Drawn:

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase:ARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

K F DAVIS

ENGINEERING, INC

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.COM

(925) 743-8884

H :\R ev it

T em p Fo ld er

\V

AS

D _R ep la ce N ur se

C al l M

AT

V

PA

_v

_r on

.b la yl oc k.

rv t

G. FERNANDEZ

REPLACE HOSPITAL NURSE CALL,

MATV, AND PUBLIC ADDRESS

664-18-331

SAN DIEGO, CA

Revisions: Date: 02/02/2024

100% SUBMITTAL

ASBESTOS CONTAINING MATERIALS EXIST THROUGHOUT THIS

FACILITY AND IN THE ABOVE CEILING SPACES. THE

CONTRACTOR SHALL TAKE EVERY PRECAUTION NECESSARY

TO PROTECT PERSONS FROM EXPOSURE. THESE

SAFEGUARDS WILL INCLUDE:

1. ALL CONTRACTORS PERSONNEL WHO WILL BE ENTERING

THE ABOVE CEILING SPACES AND/OR REMOVING ANY

CEILINGS, WALLS OR CEILING TILES SHALL BE TRAINED IN

THE IDENTIFICATION OF, AND HANDLING OF, ASBESTOS

CONTAINING MATERIALS. THIS TRAINING SHALL BE A 40

HOUR ASBESTOS TRAINING CLASS, AS APPROVED BY THE

VA, WITH CERTIFICATION.

2. ALL CONTRACTORS PERSONNEL WHO WILL BE ENTERING

THE ABOVE CEILING SPACES AND/OR REMOVING ANY

CEILINGS, WALLS OR CEILING TILES SHALL OBTAIN AND

WEAR, AT ALL TIMES, PERSONAL PROTECTIVE EQUIPMENT

(PPE) INCLUDING, BUT NOT LIMITED TO, RESPIRATORS

PRIOR TO ENTRY INTO ABOVE CEILING SPACES.

3. PRIOR TO ENTRY INTO ABOVE CEILING SPACES,

CONTRACTOR PERSONNEL SHALL UNDERGO AND SUBMIT,

A MEDICAL EVALUATION FOR USE OF A RESPIRATOR.

4. ANY WORK BELOW THE CEILING SUCH AS REMOVAL OF

CEILING TILES, GYPSUM BOARD CEILINGS, PA SPEAKERS

OR OTHER DISTURBANCE OF CELING OR WALL MATERIALS

SHALL BE PERFORMED WITH PROPER BARRICADES

INCLUDING THE USE OF CONTAINMENT CUBES. ALL SUCH

PROTECTIVE BARRICADES SHALL BE PROVIDED BY THE

CONTRACTOR.

THE ARCHITECT-ENGINEER AND HIS/HER CONSULTANTS

SHALL HAVE NO RESPONSIBILITY FOR THE DISCOVERY,

PRESENCE, HANDLING, REMOVAL OR DISPOSAL OF, OR

EXPOSURE OF PERSONS TO HAZARDOUS MATERIALS, IN ANY

FORM AT THE PROJECT SITE. THE CONTRACTOR IS SOLELY

RESPONSIBLE FOR JOB SITE SAFETY WHICH INCLUDES ALL

TRAINING AND SAFEGUARDS NECESSARY TO PROTECT

HIS/HER EMPLOYEES, VA PERSONNEL VISITORS AT THE SITE

AND ANY OTHER PERSONS.

ASBESTOS WARNING

GENERAL NOTES

R. KORTE

ET101A

SHEET NOTES

1 TV OUTLET IS SHOWN FOR REFERENCE ONLY AND WILL NOT

BE INSTALLED IN THIS FLOOR LEVEL. TV OUTLET WILL BE

INSTALLED IN THE INTERSTITIAL FLOOR LEVEL BELOW THE

INTERSTITIAL SPACE. COORDINATE EXACT LOCATION WITH

THE COR

PROVIDE SPLITTER AND RG6 COAXIAL CABLE TO EACH TV

OUTLET

PROVIDE RG-6 COAXIAL CABLE

EXISTING MATV BOX. THE CONTRACTOR IS TO VERIFY THE

EXACT LOCATION OF THE EQUIPMENT. RECONDUCTOR ALL

LINES FROM THIS POINT TO ALL TV'S WITH RG-6 CABLES

U.O.N.

RECONDUCTOR WITH RG-11 COAXIAL CABLE

1. THE CONTRACTOR IS ADVISED THAT EQUIPMENT, PIPING AND

OTHER UTILITIES EXIST WITHIN THE INTERSTITIAL SPACE. IT IS

THE CONTRACTOR'S SOLE RESPONSIBILITY TO DETERMINE

THE BEST ROUTING FOR ALL NEW CONDUITS AND/OR CABLE

TRAYS.

2. PROVIDE 3/4" CONDUIT FOR ALL COAXIAL CABLE RUNS.

ST A T E O F CA L I FORN I A

RE

G

IS

TE

RED PROFESS IONAL ENGINEERA U

BRIDGE

36" HIGH WALL

36" HIGH WALL

VOID

050-1-1

ALCOVE

VOID

062-1-1

VOID

068-1-1

VOID

052-1-1

VOID

074-1-1

VOID

010-1-1

VOID

028-1-1

VOID

027-1-1

VOID

026-1-1

VOID

023-1-1

VOID

049-1-1

WAITER

DW3-1-1

VOID

024-1-1

TV

TV

TV

TV

TV

TV

CCTV

5 6

TV

ET102

BUILDING 1 - FIRST FLOOR MATV

PLAN

NORTH

SCALE: NONEET102

1 BLDG. 1, FIRST FLOOR PLAN

PROVIDE NEW RG-6 COAXIAL CABLE TO ALL TVs

LOCATED IN THE CHAPEL.

NOT USED

ENSURE CHAPEL CLOSE CIRCUIT TV (CCTV) WIRING REMAIN

CONNECTED TO THE 7TH FLOOR CENTRAL TV DISTRIBUTION

SYSTEM.

4 THIS AREA HAS BEEN CONVERTED TO WAITING AREA,

RM 1220

5 POSSIBLE CHASE LOCATION WHERE CCTV CIRCUIT SYSTEM

RAISES TO 7TH FLOOR.

6 COORDINATE WITH VA TO DETERMINE THE EXACT CCTV

ROUTING.

R. BLAYLOCK JR

AREA NOT IN CONTRACT.

R. BLAYLOCK JR

Project Number:

Building Number:

Drawing Number:

Project Title:

Location:

Issue Date: Checked: Drawn:

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase:ARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

K F DAVIS

ENGINEERING, INC

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.COM

(925) 743-8884

H :\R ev it

T em p Fo ld er

\V

AS

D _R ep la ce N ur se

C al l M

AT

V

PA

_v

_r on

.b la yl oc k.

rv t

G. FERNANDEZ

REPLACE HOSPITAL NURSE CALL,

MATV, AND PUBLIC ADDRESS

664-18-331

SAN DIEGO, CA

Revisions: Date: 02/02/2024

100% SUBMITTAL

ASBESTOS CONTAINING MATERIALS EXIST THROUGHOUT THIS

FACILITY AND IN THE ABOVE CEILING SPACES. THE

CONTRACTOR SHALL TAKE EVERY PRECAUTION NECESSARY

TO PROTECT PERSONS FROM EXPOSURE. THESE

SAFEGUARDS WILL INCLUDE:

1. ALL CONTRACTORS PERSONNEL WHO WILL BE ENTERING

THE ABOVE CEILING SPACES AND/OR REMOVING ANY

CEILINGS, WALLS OR CEILING TILES SHALL BE TRAINED IN

THE IDENTIFICATION OF, AND HANDLING OF, ASBESTOS

CONTAINING MATERIALS. THIS TRAINING SHALL BE A 40

HOUR ASBESTOS TRAINING CLASS, AS APPROVED BY THE

VA, WITH CERTIFICATION.

2. ALL CONTRACTORS PERSONNEL WHO WILL BE ENTERING

THE ABOVE CEILING SPACES AND/OR REMOVING ANY

CEILINGS, WALLS OR CEILING TILES SHALL OBTAIN AND

WEAR, AT ALL TIMES, PERSONAL PROTECTIVE EQUIPMENT

(PPE) INCLUDING, BUT NOT LIMITED TO, RESPIRATORS

PRIOR TO ENTRY INTO ABOVE CEILING SPACES.

3. PRIOR TO ENTRY INTO ABOVE CEILING SPACES,

CONTRACTOR PERSONNEL SHALL UNDERGO AND SUBMIT,

A MEDICAL EVALUATION FOR USE OF A RESPIRATOR.

4. ANY WORK BELOW THE CEILING SUCH AS REMOVAL OF

CEILING TILES, GYPSUM BOARD CEILINGS, PA SPEAKERS

OR OTHER DISTURBANCE OF CELING OR WALL MATERIALS

SHALL BE PERFORMED WITH PROPER BARRICADES

INCLUDING THE USE OF CONTAINMENT CUBES. ALL SUCH

PROTECTIVE BARRICADES SHALL BE PROVIDED BY THE

CONTRACTOR.

THE ARCHITECT-ENGINEER AND HIS/HER CONSULTANTS

SHALL HAVE NO RESPONSIBILITY FOR THE DISCOVERY,

PRESENCE, HANDLING, REMOVAL OR DISPOSAL OF, OR

EXPOSURE OF PERSONS TO HAZARDOUS MATERIALS, IN ANY

FORM AT THE PROJECT SITE. THE CONTRACTOR IS SOLELY

RESPONSIBLE FOR JOB SITE SAFETY WHICH INCLUDES ALL

TRAINING AND SAFEGUARDS NECESSARY TO PROTECT

HIS/HER EMPLOYEES, VA PERSONNEL VISITORS AT THE SITE

AND ANY OTHER PERSONS.

ASBESTOS WARNING

LEGEND

SHEET NOTES

GENERAL NOTES

R. BLAYLOCK JR

1.

2.

3.

PROVIDE NEW RG-6 COAXIAL CABLE AND TV OUTLET TO

ALL TV's IN ALL AREAS AS SHOWN IN THIS FLOOR LEVEL

4. RUN COAXIAL CABLE ABOVE THE IN INTERSTITIAL SPACE

AND CONCEALED BEHIND FINISH WALLS, UNLESS

OTHERWISE NOTED.

PROVIDE SPLITTERS AND TAPS AS NECESSARY TO

BRANCH OUT THE LINE GOING TO THE TV's.

PROVIDE AMPLIFIERS AND / OR ATTENUATORS AS

NECESSARY TO OBTAIN A CLEAR RECEPTION ON ALL

TV's.

ST A T E O F CA L I F ORN I A

RE

G

IS

TE

RED PROFESS IONAL ENGINEERA U

A1003

ELEVATOR

NO P6

ELEVATOR

NO P5

STAIR

NO 6

STAIR

NO 2

STAIR

NO 1

STAIR

NO 5

STAIR

NO 4

STAIR

NO 3

STAIR

NO 7STAIR

NO 8

ELEVATOR

NO S3

ELEVATOR

NO P4

A1008

STAIR

NO 11

A1009

A1016 STAIR

SW11A-1I

A1017

A1001

A1000

STAIR

NO 10A

A1002

A1005

A1018

STAIR

NO 12A

A1006

A1015

A1014

STAIR

NO 9A

A1011A

A1013A1012A1011

A1004

STAIR

NO 13

A1007A1010

STAIR

NO 9

ELEVATOR

NO S2

A1003A

ELEVATOR

NO P3

ELEVATOR

NO P2

ELEVATOR

NO P1

ELEVATOR

NO S4

ELEVATOR

NO S1

TV

TV

TV

TV

TV

TO SECOND FLOOR

INTERSTITIAL

TV

TV

1(TYP)

REPLACE HOSPITAL NURSE CALL,

MATV, AND PUBLIC ADDRESS

664-18-331

SAN DIEGO, CA

NORTH

SCALE: NONEET102A

1 BLDG. 1, FIRST FLOOR INTERSTITIAL PLAN

R. BLAYLOCK JR

AREA NOT IN CONTRACT.

BUILDING 1 - FIRST FLOOR -

INTERSTITIAL PLANINTERSTITIAL PLAN 95% SUBMITTAL

Project Number:

Building Number:

Drawing Number:

Project Title:

Location:

Issue Date: Checked: Drawn:

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase:ARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

K F DAVIS

ENGINEERING, INC

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.COM

(925) 743-8884

H :\R ev it

T em p Fo ld er

\V

AS

D _R ep la ce N ur se

C al l M

AT

V

PA

_v

_r on

.b la yl oc k.

rv t

G. FERNANDEZ

REPLACE HOSPITAL NURSE CALL,

MATV, AND PUBLIC ADDRESS

664-18-331

SAN DIEGO, CA

Revisions: Date: 02/02/2024

100% SUBMITTAL

ASBESTOS CONTAINING MATERIALS EXIST THROUGHOUT THIS

FACILITY AND IN THE ABOVE CEILING SPACES. THE

CONTRACTOR SHALL TAKE EVERY PRECAUTION NECESSARY

TO PROTECT PERSONS FROM EXPOSURE. THESE

SAFEGUARDS WILL INCLUDE:

1. ALL CONTRACTORS PERSONNEL WHO WILL BE ENTERING

THE ABOVE CEILING SPACES AND/OR REMOVING ANY

CEILINGS, WALLS OR CEILING TILES SHALL BE TRAINED IN

THE IDENTIFICATION OF, AND HANDLING OF, ASBESTOS

CONTAINING MATERIALS. THIS TRAINING SHALL BE A 40

HOUR ASBESTOS TRAINING CLASS, AS APPROVED BY THE

VA, WITH CERTIFICATION.

2. ALL CONTRACTORS PERSONNEL WHO WILL BE ENTERING

THE ABOVE CEILING SPACES AND/OR REMOVING ANY

CEILINGS, WALLS OR CEILING TILES SHALL OBTAIN AND

WEAR, AT ALL TIMES, PERSONAL PROTECTIVE EQUIPMENT

(PPE) INCLUDING, BUT NOT LIMITED TO, RESPIRATORS

PRIOR TO ENTRY INTO ABOVE CEILING SPACES.

3. PRIOR TO ENTRY INTO ABOVE CEILING SPACES,

CONTRACTOR PERSONNEL SHALL UNDERGO AND SUBMIT,

A MEDICAL EVALUATION FOR USE OF A RESPIRATOR.

4. ANY WORK BELOW THE CEILING SUCH AS REMOVAL OF

CEILING TILES, GYPSUM BOARD CEILINGS, PA SPEAKERS

OR OTHER DISTURBANCE OF CELING OR WALL MATERIALS

SHALL BE PERFORMED WITH PROPER BARRICADES

INCLUDING THE USE OF CONTAINMENT CUBES. ALL SUCH

PROTECTIVE BARRICADES SHALL BE PROVIDED BY THE

CONTRACTOR.

THE ARCHITECT-ENGINEER AND HIS/HER CONSULTANTS

SHALL HAVE NO RESPONSIBILITY FOR THE DISCOVERY,

PRESENCE, HANDLING, REMOVAL OR DISPOSAL OF, OR

EXPOSURE OF PERSONS TO HAZARDOUS MATERIALS, IN ANY

FORM AT THE PROJECT SITE. THE CONTRACTOR IS SOLELY

RESPONSIBLE FOR JOB SITE SAFETY WHICH INCLUDES ALL

TRAINING AND SAFEGUARDS NECESSARY TO PROTECT

HIS/HER EMPLOYEES, VA PERSONNEL VISITORS AT THE SITE

AND ANY OTHER PERSONS.

ASBESTOS WARNING

LEGEND

GENERAL NOTES

ET102A

SHEET NOTESSHEET NOTESSHEET NOTESSHEET NOTES

1 TV OUTLET IS SHOWN FOR REFERENCE ONLY AND WILL NOT

BE INSTALLED IN THIS INTERSTITIAL FLOOR LEVEL. TV OUTLET

WILLBE INSTALLED IN THE LEVEL BELOW THE INTERSTITIAL

SPACE. COORDINATE EXACT LOCATION WITH THE COR

PROVIDE SPLITTER AND RG6 COAXIAL CABLE TO EACH TV

OUTLET

PROVIDE RG-6 COAXIAL CABLE

EXISTING MATV BOX. THE CONTRACTOR IS TO VERIFY THE

EXACT LOCATION OF THE EQUIPMENT. RECONDUCTOR ALL

LINES FROM THIS POINT TO ALL TV'S WITH RG-6 CABLES

U.O.N.

RECONDUCTOR WITH RG-11 COAXIAL CABLE

1.

2.

THE CONTRACTOR IS ADVISED THAT EQUIPMENT, PIPING AND

OTHER UTILITIES EXIST WITHIN THE INTERSTITIAL SPACE. IT IS

THE CONTRACTOR'S SOLE RESPONSIBILITY TO DETERMINE

THE BEST ROUTING FOR ALL NEW CONDUITS AND/OR CABLE

TRAYS.

PROVIDE 3/4" CONDUIT FOR ALL COAXIAL CABLE RUNS.

ST A T E O F CA L I F ORN I A

RE

G

IS

TE

RED PROFESS IONAL ENGINEERA U

STAIR

CORRIDOR

ELEVATORELEVATORELEVATORELEVATOR

ELEVATORELEVATORELEVATOR

ELEVATORELEVATORELEVATOR

HSK

W/D W/DW/D

234 SF

OFFICE

2227 (R)

116 SF

OFFICE

2227B (R)

SALLYPORT

VESTIBULE

TV

TV

TV

TV

TV

1 6

ET103

BUILDING 1 - SECOND FLOOR MATV

PLAN

SCALE: NONEET103

1 BLDG. 1, SECOND FLOOR PLAN

NORTH

PROVIDE NEW RG-6 COAXIAL CABLE TO ALL TV's IN ALL

PROJECT AREAS ON THE SECOND FLOOR.

NOT USED

NEW RG-6 CABLE EXISTS IN THESE AREAS. TIE THE

AREA EXISTING CABLING INTO NEW FLOOR CABLE

SYSTEM.

4 IT ROOM. ALL TV CONNECTIONS FOR THIS AREA

TERMINATE HERE.

5 NEW AREA

R. BLAYLOCK JR

AREA NOT IN CONTRACT.

R. BLAYLOCK JR

Project Number:

Building Number:

Drawing Number:

Project Title:

Location:

Issue Date: Checked: Drawn:

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase:ARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

K F DAVIS

ENGINEERING, INC

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.COM

(925) 743-8884

H :\R ev it

T em p Fo ld er

\V

AS

D _R ep la ce N ur se

C al l M

AT

V

PA

_v

_r on

.b la yl oc k.

rv t

G. FERNANDEZ

REPLACE HOSPITAL NURSE CALL,

MATV, AND PUBLIC ADDRESS

664-18-331

SAN DIEGO, CA

Revisions: Date: 02/02/2024

100% SUBMITTAL

ASBESTOS CONTAINING MATERIALS EXIST THROUGHOUT THIS

FACILITY AND IN THE ABOVE CEILING SPACES. THE

CONTRACTOR SHALL TAKE EVERY PRECAUTION NECESSARY

TO PROTECT PERSONS FROM EXPOSURE. THESE

SAFEGUARDS WILL INCLUDE:

1. ALL CONTRACTORS PERSONNEL WHO WILL BE ENTERING

THE ABOVE CEILING SPACES AND/OR REMOVING ANY

CEILINGS, WALLS OR CEILING TILES SHALL BE TRAINED IN

THE IDENTIFICATION OF, AND HANDLING OF, ASBESTOS

CONTAINING MATERIALS. THIS TRAINING SHALL BE A 40

HOUR ASBESTOS TRAINING CLASS, AS APPROVED BY THE

VA, WITH CERTIFICATION.

2. ALL CONTRACTORS PERSONNEL WHO WILL BE ENTERING

THE ABOVE CEILING SPACES AND/OR REMOVING ANY

CEILINGS, WALLS OR CEILING TILES SHALL OBTAIN AND

WEAR, AT ALL TIMES, PERSONAL PROTECTIVE EQUIPMENT

(PPE) INCLUDING, BUT NOT LIMITED TO, RESPIRATORS

PRIOR TO ENTRY INTO ABOVE CEILING SPACES.

3. PRIOR TO ENTRY INTO ABOVE CEILING SPACES,

CONTRACTOR PERSONNEL SHALL UNDERGO AND SUBMIT,

A MEDICAL EVALUATION FOR USE OF A RESPIRATOR.

4. ANY WORK BELOW THE CEILING SUCH AS REMOVAL OF

CEILING TILES, GYPSUM BOARD CEILINGS, PA SPEAKERS

OR OTHER DISTURBANCE OF CELING OR WALL MATERIALS

SHALL BE PERFORMED WITH PROPER BARRICADES

INCLUDING THE USE OF CONTAINMENT CUBES. ALL SUCH

PROTECTIVE BARRICADES SHALL BE PROVIDED BY THE

CONTRACTOR.

THE ARCHITECT-ENGINEER AND HIS/HER CONSULTANTS

SHALL HAVE NO RESPONSIBILITY FOR THE DISCOVERY,

PRESENCE, HANDLING, REMOVAL OR DISPOSAL OF, OR

EXPOSURE OF PERSONS TO HAZARDOUS MATERIALS, IN ANY

FORM AT THE PROJECT SITE. THE CONTRACTOR IS SOLELY

RESPONSIBLE FOR JOB SITE SAFETY WHICH INCLUDES ALL

TRAINING AND SAFEGUARDS NECESSARY TO PROTECT

HIS/HER EMPLOYEES, VA PERSONNEL VISITORS AT THE SITE

AND ANY OTHER PERSONS.

ASBESTOS WARNING

LEGEND

SHEET NOTES

GENERAL NOTES

R. BLAYLOCK JR

6 WORK IN THIS AREA WILL BE SCHEDULED WITH THE COR.

THIS IS AN INPT PSYCH UNIT. TAMPER PROOF SCREWS

WILL BE USED HERE

1.

2.

3.

PROVIDE NEW RG-6 COAXIAL CABLE AND TV OUTLET TO

ALL TV's IN ALL AREAS AS SHOWN IN THIS FLOOR LEVEL

4. RUN COAXIAL CABLE ABOVE THE IN INTERSTITIAL SPACE

AND CONCEALED BEHIND FINISH WALLS, UNLESS

OTHERWISE NOTED.

PROVIDE SPLITTERS AND TAPS AS NECESSARY TO

BRANCH OUT THE LINE GOING TO THE TV's.

PROVIDE AMPLIFIERS AND / OR ATTENUATORS AS

NECESSARY TO OBTAIN A CLEAR RECEPTION ON ALL

TV's.

ST A T E O F CA L I F ORN I A

RE

G

IS

TE

RED PROFESS IONAL ENGINEERA U

A2023

NO 6

STAIR

NO 5

STAIR

NO 4

STAIR

NO 3

STAIR

NO 2

STAIR

NO 8

STAIR

NO 7

STAIR

NO 1

A2001

A2025

A2000

STAIR

NO 9

A2018

ELEVATOR

NO S1

ELEVATOR

NO S2

ELEVATOR

NO S3

ELEVATOR

NO S4

A2001A

ELEVATOR

NO P1

ELEVATOR

NO P2

ELEVATOR

NO P3

ELEVATOR

NO P4

ELEVATOR

NO P5

ELEVATOR

NO P6

A2003

STAIR

NO 12

A2024

A2005

A2010

A2006

STAIR

NO 11

STAIR

NO 10

A2015

A2012

A2021

A2016

A2022

A2018.1

A2002

A2006.1A2021.1

TO THIRD FLOOR

INTERSTITIAL

TV

TV

TV

TV

TV

1(TYP)

SCALE: NONEET103A

1 BLDG. 1, SECOND FLOOR INTERSTITIAL PLAN

NORTH

R. BLAYLOCK JR

LEGEND

AREA NOT IN CONTRACT.

BUILDING 1 - SECOND FLOOR -

INTERSTITIAL PLAN

Project Number:

Building Number:

Drawing Number:

Project Title:

Location:

Issue Date: Checked: Drawn:

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase:ARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

K F DAVIS

ENGINEERING, INC

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.COM

(925) 743-8884

H :\R ev it

T em p Fo ld er

\V

AS

D _R ep la ce N ur se

C al l M

AT

V

PA

_v

_r on

.b la yl oc k.

rv t

G. FERNANDEZ

REPLACE HOSPITAL NURSE CALL,

MATV, AND PUBLIC ADDRESS

664-18-331

SAN DIEGO, CA

Revisions: Date: 02/02/2024

100% SUBMITTAL

ASBESTOS CONTAINING MATERIALS EXIST THROUGHOUT THIS

FACILITY AND IN THE ABOVE CEILING SPACES. THE

CONTRACTOR SHALL TAKE EVERY PRECAUTION NECESSARY

TO PROTECT PERSONS FROM EXPOSURE. THESE

SAFEGUARDS WILL INCLUDE:

1. ALL CONTRACTORS PERSONNEL WHO WILL BE ENTERING

THE ABOVE CEILING SPACES AND/OR REMOVING ANY

CEILINGS, WALLS OR CEILING TILES SHALL BE TRAINED IN

THE IDENTIFICATION OF, AND HANDLING OF, ASBESTOS

CONTAINING MATERIALS. THIS TRAINING SHALL BE A 40

HOUR ASBESTOS TRAINING CLASS, AS APPROVED BY THE

VA, WITH CERTIFICATION.

2. ALL CONTRACTORS PERSONNEL WHO WILL BE ENTERING

THE ABOVE CEILING SPACES AND/OR REMOVING ANY

CEILINGS, WALLS OR CEILING TILES SHALL OBTAIN AND

WEAR, AT ALL TIMES, PERSONAL PROTECTIVE EQUIPMENT

(PPE) INCLUDING, BUT NOT LIMITED TO, RESPIRATORS

PRIOR TO ENTRY INTO ABOVE CEILING SPACES.

3. PRIOR TO ENTRY INTO ABOVE CEILING SPACES,

CONTRACTOR PERSONNEL SHALL UNDERGO AND SUBMIT,

A MEDICAL EVALUATION FOR USE OF A RESPIRATOR.

4. ANY WORK BELOW THE CEILING SUCH AS REMOVAL OF

CEILING TILES, GYPSUM BOARD CEILINGS, PA SPEAKERS

OR OTHER DISTURBANCE OF CELING OR WALL MATERIALS

SHALL BE PERFORMED WITH PROPER BARRICADES

INCLUDING THE USE OF CONTAINMENT CUBES. ALL SUCH

PROTECTIVE BARRICADES SHALL BE PROVIDED BY THE

CONTRACTOR.

THE ARCHITECT-ENGINEER AND HIS/HER CONSULTANTS

SHALL HAVE NO RESPONSIBILITY FOR THE DISCOVERY,

PRESENCE, HANDLING, REMOVAL OR DISPOSAL OF, OR

EXPOSURE OF PERSONS TO HAZARDOUS MATERIALS, IN ANY

FORM AT THE PROJECT SITE. THE CONTRACTOR IS SOLELY

RESPONSIBLE FOR JOB SITE SAFETY WHICH INCLUDES ALL

TRAINING AND SAFEGUARDS NECESSARY TO PROTECT

HIS/HER EMPLOYEES, VA PERSONNEL VISITORS AT THE SITE

AND ANY OTHER PERSONS.

ASBESTOS WARNING

LEGEND

GENERAL NOTES

R. BLAYLOCK JR

ET103A

SHEET NOTESSHEET NOTESSHEET NOTESSHEET NOTES

1 TV OUTLET IS SHOWN FOR REFERENCE ONLY AND WILL NOT

BE INSTALLED IN 2ND FLOOR INTERSTITIAL LEVEL. TV OUTLET

WILLBE INSTALLED IN THE LEVEL BELOW THE INTERSTITIAL

SPACE. COORDINATE EXACT LOCATION WITH THE COR

PROVIDE SPLITTER AND RG6 COAXIAL CABLE TO EACH TV

OUTLET

PROVIDE RG-6 COAXIAL CABLE

EXISTING MATV BOX. THE CONTRACTOR IS TO VERIFY THE

EXACT LOCATION OF THE EQUIPMENT. RECONDUCTOR ALL

LINES FROM THIS POINT TO ALL TV'S WITH RG-6 CABLES

U.O.N.

RECONDUCTOR WITH RG-11 COAXIAL CABLE

1. THE CONTRACTOR IS ADVISED THAT EQUIPMENT, PIPING AND

OTHER UTILITIES EXIST WITHIN THE INTERSTITIAL SPACE. IT IS

THE CONTRACTOR'S SOLE RESPONSIBILITY TO DETERMINE

THE BEST ROUTING FOR ALL NEW CONDUITS AND/OR CABLE

TRAYS.

2. PROVIDE 3/4" CONDUIT FOR ALL COAXIAL CABLE RUNS.

STA T E O F CA L I FORN I A

RE

G

I S

TE

RED PROFESS IONAL ENGINEERA U

3148B

STORAGE ROOM

SCOPE

ROOM

CLEAN

3148A

ROOM

DIRTY

ROOM

READING

HEALTHCARE

OCCUPANCY

(21,377 sf)

BUSINESS

OCCUPANCY

(21,750 sf)

BUSINESS

OCCUPANCY

(7,102 sf)

HEALTHCARE

OCCUPANCY

(9,617 sf)

HEALTHCARE

OCCUPANCY

(11,280 sf)

SHOWER

2 BED RM

2 BED RM

2 BED RM 3372

2 BED RM

2 BED RM

UTILITY

CLEAN

3363A

UTILITY

SOILED

4 BED RM

BREAK

WAITING

3357A

STORAGE

EQUIPMENT

3357B

TOILET

4 BED RM

UTILITY

CLEAN

3353A

UTILITY

SOILED

2 BED RM

2 BED RM

4 BED RM

STATION

NURSE

TOI.

STATION

NURSE

EQUIP RM

CLEAN

ROOM

MED 3342

2 BED RM

2 BED RM

LINEN

CLEAN

RM

MEDICATION

CORRIDOR

CORRIDOR

SHOWER

SHOWER

SHOWER

SHOWER

SHOWER

PHYSICIANS

OFFICE

HAC

OFFICE

RECEPTION

CONFERENCE

RM

PATIENT

BED ROOM

PATIENT

BED ROOM

SHOWER

ROOM

MED

SHOWER

WORK RM

CORRIDOR

PHARMACY

WAITING

PHYSICIANS

OFFICE

SW8-1

STAIR

OFFICE

OFFICE

CORR.

OFFICE

SOCIAL

WORKER

OFF.

RESIDENT

ON CALL

SHOWER

SHOWER

ALCOVE

OFFICE

SHOWER

CORRIDOR

STATION

NURSE

PATIENT

BED ROOM

SHOWER

ROOM 1

OPERATING

UTILITY

SOILED

3397A

KITCHEN

PATIENT

BED ROOM

SHOWER

OFFICE

PHYS.

PHYS.

CORR.

3308A

OFFICE

3308B

OFFICE

TOI.

WORK ROOM

RESIDENT 3316

WORK ROOM

RESIDENT

3317A

OFFICE

OFFICE

COMPUTER

SHOWER

HAC

PHYS.

PHYSICIAN

SLEEP RM

PHYSICIAN 3308C

STOR.

GENERAL

TOI.

TOI.

3402A

T AND L

CALL

ON-

CALL

ON-

CALL

ON-

CALL

ON-

CALL

ON-

CALL

ON-

CALL

ON-

CALL

ON-

CALL

ON-

CALL

ON-

CALL

ON-

OFFICE 3280A

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

3282A

OFFICE

3276B

OFFICE

3276A

OFFICE

OFFICE

OFFICE

3275B

OFFICE

OFFICE

3269A

OFFICE

3273C

OFFICE

OFFICE

OFFICE

3255A

OFFICE

3275A

OFFICE

3251A

OFFICE

OFFICE

OFFICE

3262A

OFFICE

OFFICE

OFFICE

3267A

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

3246A

OFFICE3221

OFFICE

OFFICE

3217B

MECH. 3217

OFFICE

3217A

OFFICE 3216

OFFICE

3202A

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE3193

OFFICE

OFFICE

OFFICE

OFFICE

3186A

OFFICE

3186B

OFFICE

3185A

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE 3170

OFFICE

3162F

OFFICE

3162E

OFFICE

3162D

OFFICE

3162C

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE 3008

OFFICE

3008A

OFFICE3007

OFFICE

OFFICE

OFF.

3162G

RM

ONFERENCE

EXAM

EXAM

EXAM

EXAM

EXAM

EXAM

CONTRACTOR

EXAM

EXAM

EXAM

OFFICE

OFFICE

3231A

OFFICE

OFFICE

OFFICE

OFFICE

EXAM

OFFICE

OFFICE

OFFICE

CORR.

CORR.

CORR.

CORR.

CORR.

CORR.

CORR.

CORR.

ROOM 2

OPERATING

ROOM 3

OPERATING

ROOM 4

OPERATING 3150

ROOM 6

OPERATING

ROOM 5

OPERATING

STOR.

EQUIP.

3 BED RM

3 BED RM3127

1 BED RM

RM

1 BED

RM

1 BED

BREAKRM

3162A

BREAKRM

SUPPLY

STERILE

CONF RM

CONF RM

LOUNGE

SLEEP RM

CONF RM

CONF RM

CORR.

RESTRM

MEN

WOMEN

BED RM

BED RM

BED RM

BED RM

STATION

NURSE

UTILITY

CLEAN

249A

UTILITY

CLEAN

CORR.

3273B

CORR.

KITCHEN

3286A

WAITING

SHOWER

SHOWER

SHOWER

SHOWER

SHOWER

LAB

UTILITY

CLEAN

UTILITY

SOILED

CORR.

CORR.

NURSE STATION

CORR.

SLEEP RM

ON-CALL

3174A

SLEEP RM

ON-CALL

3174B

SLEEP RM

ON-CALL

PHYSICIANS

OFFICE

SHOWER

PHYSICIAN

TOI.

MALE/

FEMALE

TOI.

SHOWER

SHOWER

TOI

TOI

WAITING

TOILET

3209A

RM

CLEAN

3207A

T AND L

3207B

OFFICE

BEDS (5)

PHYSICIAN

CORR.

PHYSICIAN

PHYSICIAN

PHYSICIAN

3018A

PHYSICIAN

HAC

ANTI RM

3214A

RM

CLEAN

OFFICE

TOI.

HAC

SHOWER

TOI.

TOI.

SWING

SHOWER

TOI.

LAB

TOI.

PHYSICIAN

STOR.

GEN.

CONFERENCE

TOI.

3132A

UTILITY

HAC

T AND L

ANTI RM

AIR LOCK

STATION

NURSE

CORR.

RM

EXAM

ROOM

REST

SW7-1

STAIR

SW3-1

STAIR

SW4-1

STAIR

SW5-1

STAIR

SW6-1

STAIR

TOI.

SHOWER

TOI.

TOI.

TOI.

TOI.

TOI

EXAM

KITCHEN

NUTRITION 3130

PREP

MED

SHOWER

SHOWER

SHOWER

SHOWER

TOI.

TOI.

GENERAL

STORAGE

SHOWER

SHOWER3315

SHOWER

SHOWER

SHOWER

3003A

TOI.(M)

TOI.(F)

MED PREP

CORR.

PHYSICIAN

PHYSICIAN

CORR.

3214A-1

AIR LOCK

EQUIPMENT

STORAGE

SW6-1

NO

S1

NO S4NO S3NO S2

NO P3NO P2NO

P1

NO P6NO P5NO P4

UP

RAMP

UPDN UPDN

9'-11 15__

" 9'-11 15__

3E SKY

89 7 6

BED (5)

FEC

FEC

OPEN TO BELOW

OPEN TO BELOW

OPEN TO BELOW

OPEN TO BELOW

K

BIO

K

K

K

TV

TV

TV

TV

TV

TV

N

TV

TV TV TV TV TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

-C

-C

-C

-C -C -C -C -C -C

-C

-C

-C

-C

-C

-C

3(TYP)

ET104

BUILDING 1 - THIRD FLOOR

NORTH

SCALE: NTSET104

1 BLDG. 1, THIRD FLOOR

R. BLAYLOCK JR

LEGEND

AREA NOT IN CONTRACT.

PROVIDE PROVISION FOR CONNECTION FOR THE

RENOVATION AREA.

PROVIDE NEW RG-6 COAXIAL CABLE TO ALL TV's IN ALL

PROJECT AREAS ON THE THIRD FLOOR.

R. BLAYLOCK JR

Project Number:

Building Number:

Drawing Number:

Project Title:

Location:

Issue Date: Checked: Drawn:

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase:ARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

K F DAVIS

ENGINEERING, INC

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.COM

(925) 743-8884

H :\R ev it

T em p Fo ld er

\V

AS

D _R ep la ce N ur se

C al l M

AT

V

PA

_v

_r on

.b la yl oc k.

rv t

G. FERNANDEZ

REPLACE HOSPITAL NURSE CALL,

MATV, AND PUBLIC ADDRESS

664-18-331

SAN DIEGO, CA

Revisions: Date: 02/02/2024

100% SUBMITTAL

ASBESTOS CONTAINING MATERIALS EXIST THROUGHOUT THIS

FACILITY AND IN THE ABOVE CEILING SPACES. THE

CONTRACTOR SHALL TAKE EVERY PRECAUTION NECESSARY

TO PROTECT PERSONS FROM EXPOSURE. THESE

SAFEGUARDS WILL INCLUDE:

1. ALL CONTRACTORS PERSONNEL WHO WILL BE ENTERING

THE ABOVE CEILING SPACES AND/OR REMOVING ANY

CEILINGS, WALLS OR CEILING TILES SHALL BE TRAINED IN

THE IDENTIFICATION OF, AND HANDLING OF, ASBESTOS

CONTAINING MATERIALS. THIS TRAINING SHALL BE A 40

HOUR ASBESTOS TRAINING CLASS, AS APPROVED BY THE

VA, WITH CERTIFICATION.

2. ALL CONTRACTORS PERSONNEL WHO WILL BE ENTERING

THE ABOVE CEILING SPACES AND/OR REMOVING ANY

CEILINGS, WALLS OR CEILING TILES SHALL OBTAIN AND

WEAR, AT ALL TIMES, PERSONAL PROTECTIVE EQUIPMENT

(PPE) INCLUDING, BUT NOT LIMITED TO, RESPIRATORS

PRIOR TO ENTRY INTO ABOVE CEILING SPACES.

3. PRIOR TO ENTRY INTO ABOVE CEILING SPACES,

CONTRACTOR PERSONNEL SHALL UNDERGO AND SUBMIT,

A MEDICAL EVALUATION FOR USE OF A RESPIRATOR.

4. ANY WORK BELOW THE CEILING SUCH AS REMOVAL OF

CEILING TILES, GYPSUM BOARD CEILINGS, PA SPEAKERS

OR OTHER DISTURBANCE OF CELING OR WALL MATERIALS

SHALL BE PERFORMED WITH PROPER BARRICADES

INCLUDING THE USE OF CONTAINMENT CUBES. ALL SUCH

PROTECTIVE BARRICADES SHALL BE PROVIDED BY THE

CONTRACTOR.

THE ARCHITECT-ENGINEER AND HIS/HER CONSULTANTS

SHALL HAVE NO RESPONSIBILITY FOR THE DISCOVERY,

PRESENCE, HANDLING, REMOVAL OR DISPOSAL OF, OR

EXPOSURE OF PERSONS TO HAZARDOUS MATERIALS, IN ANY

FORM AT THE PROJECT SITE. THE CONTRACTOR IS SOLELY

RESPONSIBLE FOR JOB SITE SAFETY WHICH INCLUDES ALL

TRAINING AND SAFEGUARDS NECESSARY TO PROTECT

HIS/HER EMPLOYEES, VA PERSONNEL VISITORS AT THE SITE

AND ANY OTHER PERSONS.

ASBESTOS WARNING

LEGEND

SHEET NOTES

GENERAL NOTES

R. BLAYLOCK JR

1.

2.

3.

PROVIDE NEW RG-6 COAXIAL CABLE AND TV OUTLET TO

ALL TV's IN ALL AREAS AS SHOWN IN THIS FLOOR LEVEL

4. RUN COAXIAL CABLE ABOVE THE IN INTERSTITIAL SPACE

AND CONCEALED BEHIND FINISH WALLS, UNLESS

OTHERWISE NOTED.

PROVIDE SPLITTERS AND TAPS AS NECESSARY TO

BRANCH OUT THE LINE GOING TO THE TV's.

PROVIDE AMPLIFIERS AND / OR ATTENUATORS AS

NECESSARY TO OBTAIN A CLEAR RECEPTION ON ALL

TV's.

STA T E O F CA L I F ORN I A

RE

G

IS

TE

RED PROFESS IONAL ENGINEERA U

GUST I NE K . L EUNG

3 COORDINATE WITH VAMC ON FINAL LOCATION

NO 7

STAIR

NO 8

STAIR

NO 1

STAIR

NO 2

STAIR

NO 3

STAIR

NO 4

STAIR

NO 5

STAIR

NO 6

A3001A.2

A3001A.1

A3001A.4

A3001A.3

A3001

A3001A

ELEVATOR

NO P6

ELEVATOR

NO P5

ELEVATOR

NO P4

ELEVATOR

NO P3

ELEVATOR

NO P2

ELEVATOR

NO P1

ELEVATOR

NO S4

ELEVATOR

NO S3

ELEVATOR

NO S2

ELEVATOR

NO S1

A3018.3

A3018.4

A3018.2

STAIR

NO 9

A3018

A3018.1

A3000

A3002.1

A3005

A3003

A3004.1

STAIR

NO 12A3016

A3010

A3006.1

A3006.2

A3006.3

A3006.4

A3006

STAIR

NO 11

A3021

A3021.2 A3021.1

A3021.4

STAIR

NO 10

A3012

A3015

A3022

A3023

A3024

A3025

A3021.3

TO FOURTH FLOOR

INTERSTITIAL

TV

TV

TV

TV

TV TV TV TV TV TV TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

1(TYP)

C :\U se rs

\a sh re st ha \D oc um en ts

\V

AS

D _R ep la ce N ur se

C al l M

AT

V

PA

_v

_a ni l.s hr es th a9 M

D 6R

.rv t

4/ 9/

:2

7:

A M

NORTH

Revisions: Date:

SCALE: NTSET104A

1 BLDG. 1, THIRD FLOOR INTERSTITIAL PLAN

1 2

BUILDING 1 - THIRD FLOOR -

INTERSTITIAL PLAN

AREA NOT IN CONTRACT.

Project Number:

Building Number:

Drawing Number:

Project Title:

Location:

Issue Date: Checked: Drawn:

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase:ARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

K F DAVIS

ENGINEERING, INC

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.COM

(925) 743-8884

H :\R ev it

T em p Fo ld er

\V

AS

D _R ep la ce N ur se

C al l M

AT

V

PA

_v

_r on

.b la yl oc k.

rv t

G. FERNANDEZ

REPLACE HOSPITAL NURSE CALL,

MATV, AND PUBLIC ADDRESS

664-18-331

SAN DIEGO, CA

Revisions: Date: 02/02/2024

100% SUBMITTAL

ASBESTOS CONTAINING MATERIALS EXIST THROUGHOUT THIS

FACILITY AND IN THE ABOVE CEILING SPACES. THE

CONTRACTOR SHALL TAKE EVERY PRECAUTION NECESSARY

TO PROTECT PERSONS FROM EXPOSURE. THESE

SAFEGUARDS WILL INCLUDE:

1. ALL CONTRACTORS PERSONNEL WHO WILL BE ENTERING

THE ABOVE CEILING SPACES AND/OR REMOVING ANY

CEILINGS, WALLS OR CEILING TILES SHALL BE TRAINED IN

THE IDENTIFICATION OF, AND HANDLING OF, ASBESTOS

CONTAINING MATERIALS. THIS TRAINING SHALL BE A 40

HOUR ASBESTOS TRAINING CLASS, AS APPROVED BY THE

VA, WITH CERTIFICATION.

2. ALL CONTRACTORS PERSONNEL WHO WILL BE ENTERING

THE ABOVE CEILING SPACES AND/OR REMOVING ANY

CEILINGS, WALLS OR CEILING TILES SHALL OBTAIN AND

WEAR, AT ALL TIMES, PERSONAL PROTECTIVE EQUIPMENT

(PPE) INCLUDING, BUT NOT LIMITED TO, RESPIRATORS

PRIOR TO ENTRY INTO ABOVE CEILING SPACES.

3. PRIOR TO ENTRY INTO ABOVE CEILING SPACES,

CONTRACTOR PERSONNEL SHALL UNDERGO AND SUBMIT,

A MEDICAL EVALUATION FOR USE OF A RESPIRATOR.

4. ANY WORK BELOW THE CEILING SUCH AS REMOVAL OF

CEILING TILES, GYPSUM BOARD CEILINGS, PA SPEAKERS

OR OTHER DISTURBANCE OF CELING OR WALL MATERIALS

SHALL BE PERFORMED WITH PROPER BARRICADES

INCLUDING THE USE OF CONTAINMENT CUBES. ALL SUCH

PROTECTIVE BARRICADES SHALL BE PROVIDED BY THE

CONTRACTOR.

THE ARCHITECT-ENGINEER AND HIS/HER CONSULTANTS

SHALL HAVE NO RESPONSIBILITY FOR THE DISCOVERY,

PRESENCE, HANDLING, REMOVAL OR DISPOSAL OF, OR

EXPOSURE OF PERSONS TO HAZARDOUS MATERIALS, IN ANY

FORM AT THE PROJECT SITE. THE CONTRACTOR IS SOLELY

RESPONSIBLE FOR JOB SITE SAFETY WHICH INCLUDES ALL

TRAINING AND SAFEGUARDS NECESSARY TO PROTECT

HIS/HER EMPLOYEES, VA PERSONNEL VISITORS AT THE SITE

AND ANY OTHER PERSONS.

ASBESTOS WARNING

LEGEND

GENERAL NOTES

R. KORTE

ET104A

SHEET NOTESSHEET NOTESSHEET NOTESSHEET NOTES

1 TV OUTLET IS SHOWN FOR REFERENCE ONLY AND WILL NOT

BE INSTALLED IN…

This is the start of the file's text. The full file is on GovTribe.