Attachment Da - BNL Onelines.pdf

PDF 833 KB Posted

Attached to
Unit Sub-stations
Solicitation number
438602
Issued by

About this file

This document is a Request for Quote (RFQ) for fifteen (15) skid-mounted secondary unit substations to be used at the Electron-Ion Collider (EIC) facility operated by Brookhaven Science Associates, LLC (BSA) under contract with the U.S. Department of Energy (DOE). The RFQ solicits quotes from Minority and Women-Owned Business Enterprises (MWBE) for the specified unit substations. Key details include the solicitation number (438602), response due date, pricing terms, and federal agency involvement. The RFQ and supporting attachments provide technical specifications and requirements for the unit substations. This procurement has been set aside for MWBE firms.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BUILDING # SUBSTATION #

UNIT

SUBSTATION

KVA

OA

MAX

SECONDARY

CURRENT

OA

MAX

SECONDARY

CURRENT

FA

C.B.

QUANTITY

800AF

HOUSE

C.B.

QUANTITY

800AF

MACHINE

C.B.

QUANTITY

1600AF

PS

C.B.

QUANTITY

1600AF

CRYO

1001A

1003A

1004G

1005T

1006G

1006G

1007A

1009A

1010D

1010D

1010E

1010E

1011A

1012C

1012D

1001A

1003A

1004G

1005TA

1006C/D

1006C/D

1007A

1009A

1010C/D

1010C/D

1010E/F

1010E/F

1011A

1012C

1012B

UNIT

SUBSTATION

KVA

FA

PRIMARY

OVERCURRENT

PROTECTION

OUTDOOR NEMA 3R UNIT SUBSTATIONS

TRUE NORTH

ELECTRON-ION COLLIDER

UNDER CONTRACT WITH

UNITED STATES DEPARTMENT OF ENERGY

PLANT ENGINEERING DIVISION

UPTON, NEW YORK 11973

JOB TITLE

JOB NO.

SCALE

ESHG RISK LEVEL

BLDG. NO.

DWN. BY

APP'D. BY

DATE

REV'D BY

DWG. TITLE

DWG. NO.

KEY PLAN

12" = 1'-0" E600

ONELINE DIAGRAM

SCHEDULES

10376646

Author

Legal Entity Name

HDR ARLINGTON

3001 WASHINGTON BLVD., SUITE 200

ARLINGTON, VIRGINIA 22201

Approver

Checker

12/14/23

MARK DATE DESCRIPTION

nehring Text Box This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology

INCOMING 13.8KV

FEEDER

TR-00002

13.8kV, 3⌀, 3W PRI.

2500kVA/3500kVA

480/277V, 3⌀, 4W SEC.

4000A, 480V, 3⌀, 3W

100 kAIC

UNIT SUBSTATION

800AF

800AT

3P ARMS

1600AF

1600AT

3P ARMS

PM 1

PM 2PM 2

800AF

800AT

3P

SPARE

1200AF

175AT

3P

HRG

1600AF

1600AT

3P ARMS

PM 2

MEDIUM VOLTAGE SECTION

TRANSFORMER SECTION

HIGH RESISTANCE GROUND SECTION

LOW VOLTAGE SECTION

A

RC

LIGHTNING

ARRESTER

RC

HRG

PM

AAA

A

RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES

HIGH RESISTANCE GROUND

POWER METER FOR ELECTRICAL SYSTEM MONITORING

ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION

PM 2

KEYNOTES

1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.

2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.

GENERAL NOTES

1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT

SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION

FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS

METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING

AND ZERO SEQUENCE CTS.

SPARE

1600AF

1600AT

3P ARMS

PM 2

A

1600A

EQUIPPED

SPACE

SPD SURGE PROTECTION DEVICE

SPD

R

R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD

ELECTRON-ION COLLIDER

UNDER CONTRACT WITH

UNITED STATES DEPARTMENT OF ENERGY

PLANT ENGINEERING DIVISION

UPTON, NEW YORK 11973

JOB TITLE

JOB NO.

SCALE

ESHG RISK LEVEL

BLDG. NO.

DWN. BY

APP'D. BY

DATE

REV'D BY

DWG. TITLE

DWG. NO.

NOT TO SCALE E601-01A

UNIT SUBSTATION ONELINE

DIAGRAM - BUILDING 1001A

10376646

Edward Lee

Legal Entity Name

HDR ARLINGTON

3001 WASHINGTON BLVD., SUITE 200

ARLINGTON, VIRGINIA 22201

Tommy Lane

Jean Sarsenbayev

11/01/23

NOT TO SCALE1

BUILDING 1001A UNIT SUBSTATION 1001A ONELINE DIAGRAM

MARK DATE DESCRIPTION

11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL

1001A nehring

This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology

TR-00002

13.8kV, 3⌀, 3W PRI.

2500kVA/3300kVA

480/277V, 3⌀, 4W SEC.

4000A, 480V, 3⌀, 3W

100 kAIC

UNIT SUBSTATION

800AF

800AT

3P ARMS

1600AF

1600AT

3P ARMS

PM 1

PM 2PM 2

800AF

800AT

3P

SPARE

1200AF

175AT

3P

HRG

1600AF

1600AT

3P ARMS

PM 2

MEDIUM VOLTAGE SECTION

TRANSFORMER SECTION

HIGH RESISTANCE GROUND SECTION

LOW VOLTAGE SECTION

A

RC

LIGHTNING

ARRESTER

RC

HRG

PM

AAA

A

RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES

HIGH RESISTANCE GROUND

POWER METER FOR ELECTRICAL SYSTEM MONITORING

ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION

PM 2

KEYNOTES

1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.

2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.

GENERAL NOTES

1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT

SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION

FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS

METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING

AND ZERO SEQUENCE CTS.

SPARE

1600AF

1600AT

3P ARMS

PM 2

A

1600A

EQUIPPED

SPACE

SPD SURGE PROTECTION DEVICE

SPD

R

R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD

ELECTRON-ION COLLIDER

UNDER CONTRACT WITH

UNITED STATES DEPARTMENT OF ENERGY

PLANT ENGINEERING DIVISION

UPTON, NEW YORK 11973

JOB TITLE

JOB NO.

SCALE

ESHG RISK LEVEL

BLDG. NO.

DWN. BY

APP'D. BY

DATE

REV'D BY

DWG. TITLE

DWG. NO.

NOT TO SCALE E601-03A

UNIT SUBSTATION ONELINE

DIAGRAM - BUILDING 1003A

10376646

Edward Lee

Legal Entity Name

HDR ARLINGTON

3001 WASHINGTON BLVD., SUITE 200

ARLINGTON, VIRGINIA 22201

Tommy Lane

Jean Sarsenbayev

11/01/23

NOT TO SCALE1

BUILDING 1003A UNIT SUBSTATION 1003A ONELINE DIAGRAM

MARK DATE DESCRIPTION

11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL

1003A nehring

This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology

TR-00002

13.8kV, 3⌀, 3W PRI.

1500kVA/2000kVA

480/277V, 3⌀, 4W SEC.

2500A, 480V, 3⌀, 3W

100 kAIC

UNIT SUBSTATION

800AF

800AT

3P ARMS

1600AF

1600AT

3P ARMS

PM 1

PM 2PM 2

800AF

800AT

3P

SPARE

1200AF

175AT

3P

HRG

1600AF

1600AT

3P ARMS

PM 2

MEDIUM VOLTAGE SECTION

TRANSFORMER SECTION

HIGH RESISTANCE GROUND SECTION

LOW VOLTAGE SECTION

A

RC

LIGHTNING

ARRESTER

RC

HRG

PM

AAA

A

RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES

HIGH RESISTANCE GROUND

POWER METER FOR ELECTRICAL SYSTEM MONITORING

ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION

PM 2

KEYNOTES

1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.

2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.

GENERAL NOTES

1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT

SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION

FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS

METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING

AND ZERO SEQUENCE CTS.

800A

EQUIPPED

SPACE

SPD SURGE PROTECTION DEVICE

SPD

R

R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD

ELECTRON-ION COLLIDER

UNDER CONTRACT WITH

UNITED STATES DEPARTMENT OF ENERGY

PLANT ENGINEERING DIVISION

UPTON, NEW YORK 11973

JOB TITLE

JOB NO.

SCALE

ESHG RISK LEVEL

BLDG. NO.

DWN. BY

APP'D. BY

DATE

REV'D BY

DWG. TITLE

DWG. NO.

NOT TO SCALE E601-04G

UNIT SUBSTATION ONELINE

DIAGRAM - BUILDING 1004G

10376646

Edward Lee

Legal Entity Name

HDR ARLINGTON

3001 WASHINGTON BLVD., SUITE 200

ARLINGTON, VIRGINIA 22201

Tommy Lane

Jean Sarsenbayev

11/01/23

NOT TO SCALE1

BUILDING 1004G UNIT SUBSTATION 1004G ONELINE DIAGRAM

MARK DATE DESCRIPTION

11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL

1004G nehring

This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology

TR-00002

13.8kV, 3⌀, 3W PRI.

2500kVA/3300kVA

480/277V, 3⌀, 4W SEC.

4000A, 480V, 3⌀, 3W

100 kAIC

UNIT SUBSTATION

800AF

800AT

3P ARMS

1600AF

1600AT

3P ARMS

PM 1

PM 2PM 2

800AF

800AT

3P

SPARE

1200AF

175AT

3P

HRG

1600AF

1600AT

3P ARMS

PM 2

MEDIUM VOLTAGE SECTION

TRANSFORMER SECTION

HIGH RESISTANCE GROUND SECTION

LOW VOLTAGE SECTION

A

RC

LIGHTNING

ARRESTER

RC

HRG

PM

AAA

A

RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES

HIGH RESISTANCE GROUND

POWER METER FOR ELECTRICAL SYSTEM MONITORING

ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION

PM 2

KEYNOTES

1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.

2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.

GENERAL NOTES

1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT

SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION

FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS

METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING

AND ZERO SEQUENCE CTS.

SPARE

1600AF

1600AT

3P ARMS

PM 2

A

1600A

EQUIPPED

SPACE

SPD SURGE PROTECTION DEVICE

SPD

R

R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD

ELECTRON-ION COLLIDER

UNDER CONTRACT WITH

UNITED STATES DEPARTMENT OF ENERGY

PLANT ENGINEERING DIVISION

UPTON, NEW YORK 11973

JOB TITLE

JOB NO.

SCALE

ESHG RISK LEVEL

BLDG. NO.

DWN. BY

APP'D. BY

DATE

REV'D BY

DWG. TITLE

DWG. NO.

NOT TO SCALE E601-05T

UNIT SUBSTATION ONELINE

DIAGRAM - BUILDING 1005T

10376646

Edward Lee

Legal Entity Name

HDR ARLINGTON

3001 WASHINGTON BLVD., SUITE 200

ARLINGTON, VIRGINIA 22201

Tommy Lane

Jean Sarsenbayev

11/01/23

NOT TO SCALE1

BUILDING 1005T UNIT SUBSTATION 1005TA ONELINE DIAGRAM

MARK DATE DESCRIPTION

11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL

1005T nehring

This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology

TR-00002

13.8kV, 3⌀, 3W PRI.

1500kVA/2000kVA

480/277V, 3⌀, 4W SEC.

2500A, 480V, 3⌀, 3W

100 kAIC

UNIT SUBSTATION

800AF

800AT

3P ARMS

1600AF

1600AT

3P ARMS

PM 1

PM 2PM 2

800AF

800AT

3P

1200AF

175AT

3P

HRG

MEDIUM VOLTAGE SECTION

TRANSFORMER SECTION

HIGH RESISTANCE GROUND SECTION

LOW VOLTAGE SECTION

RC

LIGHTNING

ARRESTER

RC

HRG

PM

AAA

A

RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES

HIGH RESISTANCE GROUND

POWER METER FOR ELECTRICAL SYSTEM MONITORING

ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION

PM 2

KEYNOTES

1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.

2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.

GENERAL NOTES

1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT

SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION

FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS

METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING

AND ZERO SEQUENCE CTS.

800A

EQUIPPED

SPACE

SPD SURGE PROTECTION DEVICE

SPD

R

R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD

ELECTRON-ION COLLIDER

UNDER CONTRACT WITH

UNITED STATES DEPARTMENT OF ENERGY

PLANT ENGINEERING DIVISION

UPTON, NEW YORK 11973

JOB TITLE

JOB NO.

SCALE

ESHG RISK LEVEL

BLDG. NO.

DWN. BY

APP'D. BY

DATE

REV'D BY

DWG. TITLE

DWG. NO.

NOT TO SCALE E601-06G

UNIT SUBSTATION ONELINE

DIAGRAM - BUILDING 1006G

10376646

Edward Lee

Legal Entity Name

HDR ARLINGTON

3001 WASHINGTON BLVD., SUITE 200

ARLINGTON, VIRGINIA 22201

Tommy Lane

Jean Sarsenbayev

11/01/23

NOT TO SCALE1

BUILDING 1006G UNIT SUBSTATION 1006C ONELINE DIAGRAM

MARK DATE DESCRIPTION

11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL

1006G nehring

This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology

TR-00002

13.8kV, 3⌀, 3W PRI.

2500kVA/3300kVA

480/277V, 3⌀, 4W SEC.

4000A, 480V, 3⌀, 3W

100 kAIC

UNIT SUBSTATION

800AF

800AT

3P ARMS

1600AF

1600AT

3P ARMS

PM 1

PM 2PM 2

800AF

800AT

3P

SPARE

1200AF

175AT

3P

HRG

1600AF

1600AT

3P ARMS

PM 2

MEDIUM VOLTAGE SECTION

TRANSFORMER SECTION

HIGH RESISTANCE GROUND SECTION

LOW VOLTAGE SECTION

A

RC

LIGHTNING

ARRESTER

RC

HRG

PM

AAA

A

RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES

HIGH RESISTANCE GROUND

POWER METER FOR ELECTRICAL SYSTEM MONITORING

ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION

PM 2

KEYNOTES

1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.

2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.

GENERAL NOTES

1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT

SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION

FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS

METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING

AND ZERO SEQUENCE CTS.

SPARE

1600AF

1600AT

3P ARMS

PM 2

A

1600A

EQUIPPED

SPACE

SPD SURGE PROTECTION DEVICE

SPD

R

R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD

ELECTRON-ION COLLIDER

UNDER CONTRACT WITH

UNITED STATES DEPARTMENT OF ENERGY

PLANT ENGINEERING DIVISION

UPTON, NEW YORK 11973

JOB TITLE

JOB NO.

SCALE

ESHG RISK LEVEL

BLDG. NO.

DWN. BY

APP'D. BY

DATE

REV'D BY

DWG. TITLE

DWG. NO.

NOT TO SCALE E601-07A

UNIT SUBSTATION ONELINE

DIAGRAM - BUILDING 1007A

10376646

Edward Lee

Legal Entity Name

HDR ARLINGTON

3001 WASHINGTON BLVD., SUITE 200

ARLINGTON, VIRGINIA 22201

Tommy Lane

Jean Sarsenbayev

11/01/23

NOT TO SCALE1

BUILDING 1007A UNIT SUBSTATION 1007A ONELINE DIAGRAM

MARK DATE DESCRIPTION

11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL

1007A nehring

This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology

TR-00002

13.8kV, 3⌀, 3W PRI.

2500kVA/3300kVA

480/277V, 3⌀, 4W SEC.

4000A, 480V, 3⌀, 3W

100 kAIC

UNIT SUBSTATION

800AF

800AT

3P ARMS

1600AF

1600AT

3P ARMS

PM 1

PM 2PM 2

800AF

800AT

3P

SPARE

1200AF

175AT

3P

HRG

1600AF

1600AT

3P ARMS

PM 2

MEDIUM VOLTAGE SECTION

TRANSFORMER SECTION

HIGH RESISTANCE GROUND SECTION

LOW VOLTAGE SECTION

A

RC

LIGHTNING

ARRESTER

RC

HRG

PM

AAA

A

RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES

HIGH RESISTANCE GROUND

POWER METER FOR ELECTRICAL SYSTEM MONITORING

ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION

PM 2

KEYNOTES

1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.

2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.

GENERAL NOTES

1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT

SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION

FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS

METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING

AND ZERO SEQUENCE CTS.

SPARE

1600AF

1600AT

3P ARMS

PM 2

A

1600A

EQUIPPED

SPACE

SPD SURGE PROTECTION DEVICE

SPD

R

R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD

ELECTRON-ION COLLIDER

UNDER CONTRACT WITH

UNITED STATES DEPARTMENT OF ENERGY

PLANT ENGINEERING DIVISION

UPTON, NEW YORK 11973

JOB TITLE

JOB NO.

SCALE

ESHG RISK LEVEL

BLDG. NO.

DWN. BY

APP'D. BY

DATE

REV'D BY

DWG. TITLE

DWG. NO.

NOT TO SCALE E601-09A

UNIT SUBSTATION ONELINE

DIAGRAM - BUILDING 1009A

10376646

Edward Lee

Legal Entity Name

HDR ARLINGTON

3001 WASHINGTON BLVD., SUITE 200

ARLINGTON, VIRGINIA 22201

Tommy Lane

Jean Sarsenbayev

11/01/23

NOT TO SCALE1

BUILDING 1009A UNIT SUBSTATION 1009A ONELINE DIAGRAM

MARK DATE DESCRIPTION

11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL

1009A nehring

This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology

TR-00002

13.8kV, 3⌀, 3W PRI.

2000kVA/2660kVA

480/277V, 3⌀, 4W SEC.

3200A, 480V, 3⌀, 3W

100 kAIC

UNIT SUBSTATION

800AF

800AT

3P ARMS

1600AF

1600AT

3P ARMS

PM 1

PM 2PM 2

800AF

800AT

3P

SPARE

1200AF

175AT

3P

HRG

1600AF

1600AT

3P ARMS

PM 2

MEDIUM VOLTAGE SECTION

TRANSFORMER SECTION

HIGH RESISTANCE GROUND SECTION

LOW VOLTAGE SECTION

A

RC

LIGHTNING

ARRESTER

RC

HRG

PM

AAA

A

RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES

HIGH RESISTANCE GROUND

POWER METER FOR ELECTRICAL SYSTEM MONITORING

ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION

PM 2

KEYNOTES

1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.

2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.

GENERAL NOTES

1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT

SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION

FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS

METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING

AND ZERO SEQUENCE CTS.

SPARE

1600AF

1600AT

3P ARMS

PM 2

A

1600A

EQUIPPED

SPACE

SPD SURGE PROTECTION DEVICE

SPD

R

R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD

ELECTRON-ION COLLIDER

UNDER CONTRACT WITH

UNITED STATES DEPARTMENT OF ENERGY

PLANT ENGINEERING DIVISION

UPTON, NEW YORK 11973

JOB TITLE

JOB NO.

SCALE

ESHG RISK LEVEL

BLDG. NO.

DWN. BY

APP'D. BY

DATE

REV'D BY

DWG. TITLE

DWG. NO.

NOT TO SCALE E601-10D

UNIT SUBSTATION ONELINE

DIAGRAM - BUILDING 1010D

10376646

Edward Lee

Legal Entity Name

HDR ARLINGTON

3001 WASHINGTON BLVD., SUITE 200

ARLINGTON, VIRGINIA 22201

Tommy Lane

Jean Sarsenbayev

11/01/23

NOT TO SCALE1

BUILDING 1010D UNIT SUBSTATION 1010C ONELINE DIAGRAM

MARK DATE DESCRIPTION

11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL

1010D nehring

This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology

TR-00002

13.8kV, 3⌀, 3W PRI.

1500kVA/2000kVA

480/277V, 3⌀, 4W SEC.

2500A, 480V, 3⌀, 3W

100 kAIC

UNIT SUBSTATION

800AF

800AT

3P ARMS

1600AF

1600AT

3P ARMS

PM 1

PM 2PM 2

800AF

800AT

3P

1200AF

175AT

3P

HRG

MEDIUM VOLTAGE SECTION

TRANSFORMER SECTION

HIGH RESISTANCE GROUND SECTION

LOW VOLTAGE SECTION

RC

LIGHTNING

ARRESTER

RC

HRG

PM

AAA

A

RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES

HIGH RESISTANCE GROUND

POWER METER FOR ELECTRICAL SYSTEM MONITORING

ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION

PM 2

KEYNOTES

1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.

2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.

GENERAL NOTES

1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT

SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION

FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS

METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING

AND ZERO SEQUENCE CTS.

800A

EQUIPPED

SPACE

SPD SURGE PROTECTION DEVICE

SPD

R

R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD

ELECTRON-ION COLLIDER

UNDER CONTRACT WITH

UNITED STATES DEPARTMENT OF ENERGY

PLANT ENGINEERING DIVISION

UPTON, NEW YORK 11973

JOB TITLE

JOB NO.

SCALE

ESHG RISK LEVEL

BLDG. NO.

DWN. BY

APP'D. BY

DATE

REV'D BY

DWG. TITLE

DWG. NO.

NOT TO SCALE E601-10E

UNIT SUBSTATION ONELINE

DIAGRAM - BUILDING 1010E

10376646

Edward Lee

Legal Entity Name

HDR ARLINGTON

3001 WASHINGTON BLVD., SUITE 200

ARLINGTON, VIRGINIA 22201

Tommy Lane

Jean Sarsenbayev

11/01/23

NOT TO SCALE1

BUILDING 1010E UNIT SUBSTATION 1010E ONELINE DIAGRAM

MARK DATE DESCRIPTION

11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL

1010E nehring

This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology

TR-00002

13.8kV, 3⌀, 3W PRI.

2500kVA/3300kVA

480/277V, 3⌀, 4W SEC.

4000A, 480V, 3⌀, 3W

100 kAIC

UNIT SUBSTATION

800AF

800AT

3P ARMS

1600AF

1600AT

3P ARMS

PM 1

PM 2PM 2

800AF

800AT

3P

SPARE

1200AF

175AT

3P

HRG

1600AF

1600AT

3P ARMS

PM 2

MEDIUM VOLTAGE SECTION

TRANSFORMER SECTION

HIGH RESISTANCE GROUND SECTION

LOW VOLTAGE SECTION

A

RC

LIGHTNING

ARRESTER

RC

HRG

PM

AAA

A

RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES

HIGH RESISTANCE GROUND

POWER METER FOR ELECTRICAL SYSTEM MONITORING

ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION

PM 2

KEYNOTES

1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.

2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.

GENERAL NOTES

1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT

SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION

FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS

METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING

AND ZERO SEQUENCE CTS.

SPARE

1600AF

1600AT

3P ARMS

PM 2

A

1600A

EQUIPPED

SPACE

SPD SURGE PROTECTION DEVICE

SPD

R

R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD

ELECTRON-ION COLLIDER

UNDER CONTRACT WITH

UNITED STATES DEPARTMENT OF ENERGY

PLANT ENGINEERING DIVISION

UPTON, NEW YORK 11973

JOB TITLE

JOB NO.

SCALE

ESHG RISK LEVEL

BLDG. NO.

DWN. BY

APP'D. BY

DATE

REV'D BY

DWG. TITLE

DWG. NO.

NOT TO SCALE E601-11A

UNIT SUBSTATION ONELINE

DIAGRAM - BUILDING 1011A

10376646

Edward Lee

Legal Entity Name

HDR ARLINGTON

3001 WASHINGTON BLVD., SUITE 200

ARLINGTON, VIRGINIA 22201

Tommy Lane

Jean Sarsenbayev

11/01/23

NOT TO SCALE1

BUILDING 1011A UNIT SUBSTATION 1011A ONELINE DIAGRAM

MARK DATE DESCRIPTION

11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL

1011A nehring

This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology

TR-00002

13.8kV, 3⌀, 3W PRI.

1000kVA/1330kVA

480/277V, 3⌀, 4W SEC.

1600A, 480V, 3⌀, 3W

100 kAIC

UNIT SUBSTATION

800AF

800AT

3P ARMS

PM 1

PM 2

800AF

800AT

3P

1200AF

175AT

3P

HRG

MEDIUM VOLTAGE SECTION

TRANSFORMER SECTION

HIGH RESISTANCE GROUND SECTION

LOW VOLTAGE SECTION

RC

LIGHTNING

ARRESTER

RC

HRG

PM

AA

A

RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES

HIGH RESISTANCE GROUND

POWER METER FOR ELECTRICAL SYSTEM MONITORING

ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION

PM 2

KEYNOTES

1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.

2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.

GENERAL NOTES

1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT

SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION

FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS

METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING

AND ZERO SEQUENCE CTS.

800A

EQUIPPED

SPACE

SPD SURGE PROTECTION DEVICE

SPD

R

R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD

ELECTRON-ION COLLIDER

UNDER CONTRACT WITH

UNITED STATES DEPARTMENT OF ENERGY

PLANT ENGINEERING DIVISION

UPTON, NEW YORK 11973

JOB TITLE

JOB NO.

SCALE

ESHG RISK LEVEL

BLDG. NO.

DWN. BY

APP'D. BY

DATE

REV'D BY

DWG. TITLE

DWG. NO.

NOT TO SCALE E601-12C

UNIT SUBSTATION ONELINE

DIAGRAM - BUILDING 1012C

10376646

Edward Lee

Legal Entity Name

HDR ARLINGTON

3001 WASHINGTON BLVD., SUITE 200

ARLINGTON, VIRGINIA 22201

Tommy Lane

Jean Sarsenbayev

11/01/23

NOT TO SCALE1

BUILDING 1012C UNIT SUBSTATION 1012C ONELINE DIAGRAM

MARK DATE DESCRIPTION

11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL

1012C nehring

This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology

TR-00002

13.8kV, 3⌀, 3W PRI.

1500kVA/2000kVA

480/277V, 3⌀, 4W SEC.

2500A, 480V, 3⌀, 3W

100 kAIC

UNIT SUBSTATION

800AF

800AT

3P ARMS

PM 1

PM 2

800AF

800AT

3P

1200AF

175AT

3P

HRG

MEDIUM VOLTAGE SECTION

TRANSFORMER SECTION

HIGH RESISTANCE GROUND SECTION

LOW VOLTAGE SECTION

RC

LIGHTNING

ARRESTER

RC

HRG

PM

AA

A

RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES

HIGH RESISTANCE GROUND

POWER METER FOR ELECTRICAL SYSTEM MONITORING

ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION

PM 2

KEYNOTES

1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.

2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.

GENERAL NOTES

1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT

SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION

FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS

METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING

AND ZERO SEQUENCE CTS.

800A

EQUIPPED

SPACE

SPD SURGE PROTECTION DEVICE

SPD

R

R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD

ELECTRON-ION COLLIDER

UNDER CONTRACT WITH

UNITED STATES DEPARTMENT OF ENERGY

PLANT ENGINEERING DIVISION

UPTON, NEW YORK 11973

JOB TITLE

JOB NO.

SCALE

ESHG RISK LEVEL

BLDG. NO.

DWN. BY

APP'D. BY

DATE

REV'D BY

DWG. TITLE

DWG. NO.

NOT TO SCALE E601-12D

UNIT SUBSTATION ONELINE

DIAGRAM - BUILDING 1012D

10376646

Edward Lee

Legal Entity Name

HDR ARLINGTON

3001 WASHINGTON BLVD., SUITE 200

ARLINGTON, VIRGINIA 22201

Tommy Lane

Jean Sarsenbayev

11/01/23

NOT TO SCALE1

BUILDING 1012D UNIT SUBSTATION 1012B ONELINE DIAGRAM

MARK DATE DESCRIPTION

11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL

1012D nehring

This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology

TR-00002

13.8kV, 3⌀, 3W PRI.

1500kVA/2000kVA

480/277V, 3⌀, 4W SEC.

2500A, 480V, 3⌀, 3W

100 kAIC

UNIT SUBSTATION

800AF

800AT

3P ARMS

1600AF

1600AT

3P ARMS

PM 1

PM 2PM 2

800AF

800AT

3P

1200AF

175AT

3P

HRG

MEDIUM VOLTAGE SECTION

TRANSFORMER SECTION

HIGH RESISTANCE GROUND SECTION

LOW VOLTAGE SECTION

RC

LIGHTNING

ARRESTER

RC

HRG

PM

AAA

A

RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES

HIGH RESISTANCE GROUND

POWER METER FOR ELECTRICAL SYSTEM MONITORING

ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION

PM 2

KEYNOTES

1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.

2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.

GENERAL NOTES

1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT

SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION

FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS

METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING

AND ZERO SEQUENCE CTS.

800A

EQUIPPED

SPACE

SPD SURGE PROTECTION DEVICE

SPD

R

R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD

ELECTRON-ION COLLIDER

UNDER CONTRACT WITH

UNITED STATES DEPARTMENT OF ENERGY

PLANT ENGINEERING DIVISION

UPTON, NEW YORK 11973

JOB TITLE

JOB NO.

SCALE

ESHG RISK LEVEL

BLDG. NO.

DWN. BY

APP'D. BY

DATE

REV'D BY

DWG. TITLE

DWG. NO.

NOT TO SCALE E602-06G

UNIT SUBSTATION ONELINE

DIAGRAM - BUILDING 1006G

10376646

Edward Lee

Legal Entity Name

HDR ARLINGTON

3001 WASHINGTON BLVD., SUITE 200

ARLINGTON, VIRGINIA 22201

Tommy Lane

Jean Sarsenbayev

11/01/23

NOT TO SCALE1

BUILDING 1006G UNIT SUBSTATION 1006D ONELINE DIAGRAM

MARK DATE DESCRIPTION

11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL

1006G nehring

This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology

TR-00002

13.8kV, 3⌀, 3W PRI.

2000kVA/2660kVA

480/277V, 3⌀, 4W SEC.

3200A, 480V, 3⌀, 3W

100 kAIC

UNIT SUBSTATION

800AF

800AT

3P ARMS

1600AF

1600AT

3P ARMS

PM 1

PM 2PM 2

800AF

800AT

3P

SPARE

1200AF

175AT

3P

HRG

1600AF

1600AT

3P ARMS

PM 2

MEDIUM VOLTAGE SECTION

TRANSFORMER SECTION

HIGH RESISTANCE GROUND SECTION

LOW VOLTAGE SECTION

A

RC

LIGHTNING

ARRESTER

RC

HRG

PM

AAA

A

RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES

HIGH RESISTANCE GROUND

POWER METER FOR ELECTRICAL SYSTEM MONITORING

ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION

PM 2

KEYNOTES

1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.

2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.

GENERAL NOTES

1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT

SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION

FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS

METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING

AND ZERO SEQUENCE CTS.

SPARE

1600AF

1600AT

3P ARMS

PM 2

A

1600A

EQUIPPED

SPACE

SPD SURGE PROTECTION DEVICE

SPD

R

R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD

ELECTRON-ION COLLIDER

UNDER CONTRACT WITH

UNITED STATES DEPARTMENT OF ENERGY

PLANT ENGINEERING DIVISION

UPTON, NEW YORK 11973

JOB TITLE

JOB NO.

SCALE

ESHG RISK LEVEL

BLDG. NO.

DWN. BY

APP'D. BY

DATE

REV'D BY

DWG. TITLE

DWG. NO.

NOT TO SCALE E602-10D

UNIT SUBSTATION ONELINE

DIAGRAM - BUILDING 1010D

10376646

Edward Lee

Legal Entity Name

HDR ARLINGTON

3001 WASHINGTON BLVD., SUITE 200

ARLINGTON, VIRGINIA 22201

Tommy Lane

Jean Sarsenbayev

11/01/23

NOT TO SCALE1

BUILDING 1010D UNIT SUBSTATION 1010D ONELINE DIAGRAM

MARK DATE DESCRIPTION

11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL

1010D nehring

This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology

TR-00002

13.8kV, 3⌀, 3W PRI.

1500kVA/2000kVA

480/277V, 3⌀, 4W SEC.

2500A, 480V, 3⌀, 3W

100 kAIC

UNIT SUBSTATION

800AF

800AT

3P ARMS

1600AF

1600AT

3P ARMS

PM 1

PM 2PM 2

800AF

800AT

3P

1200AF

175AT

3P

HRG

MEDIUM VOLTAGE SECTION

TRANSFORMER SECTION

HIGH RESISTANCE GROUND SECTION

LOW VOLTAGE SECTION

RC

LIGHTNING

ARRESTER

RC

HRG

PM

AAA

A

RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES

HIGH RESISTANCE GROUND

POWER METER FOR ELECTRICAL SYSTEM MONITORING

ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION

PM 2

KEYNOTES

1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.

2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.

GENERAL NOTES

1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT

SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION

FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS

METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING

AND ZERO SEQUENCE CTS.

800A

EQUIPPED

SPACE

SPD SURGE PROTECTION DEVICE

SPD

R

R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD

ELECTRON-ION COLLIDER

UNDER CONTRACT WITH

UNITED STATES DEPARTMENT OF ENERGY

PLANT ENGINEERING DIVISION

UPTON, NEW YORK 11973

JOB TITLE

JOB NO.

SCALE

ESHG RISK LEVEL

BLDG. NO.

DWN. BY

APP'D. BY

DATE

REV'D BY

DWG. TITLE

DWG. NO.

NOT TO SCALE E602-10E

UNIT SUBSTATION ONELINE

DIAGRAM - BUILDING 1010E

10376646

Edward Lee

Legal Entity Name

HDR ARLINGTON

3001 WASHINGTON BLVD., SUITE 200

ARLINGTON, VIRGINIA 22201

Tommy Lane

Jean Sarsenbayev

11/01/23

NOT TO SCALE1

BUILDING 1010E UNIT SUBSTATION 1010F ONELINE DIAGRAM

MARK DATE DESCRIPTION

11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL

1010E nehring

This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology

File details come from the government source that posted it. Updated .