Attachment Da - BNL Onelines.pdf
PDF 833 KB Posted
- Attached to
- Unit Sub-stations
- Solicitation number
- 438602
- Issued by
-
Department of Energy Office of Science
About this file
This document is a Request for Quote (RFQ) for fifteen (15) skid-mounted secondary unit substations to be used at the Electron-Ion Collider (EIC) facility operated by Brookhaven Science Associates, LLC (BSA) under contract with the U.S. Department of Energy (DOE). The RFQ solicits quotes from Minority and Women-Owned Business Enterprises (MWBE) for the specified unit substations. Key details include the solicitation number (438602), response due date, pricing terms, and federal agency involvement. The RFQ and supporting attachments provide technical specifications and requirements for the unit substations. This procurement has been set aside for MWBE firms.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BUILDING # SUBSTATION #
UNIT
SUBSTATION
KVA
OA
MAX
SECONDARY
CURRENT
OA
MAX
SECONDARY
CURRENT
FA
C.B.
QUANTITY
800AF
HOUSE
C.B.
QUANTITY
800AF
MACHINE
C.B.
QUANTITY
1600AF
PS
C.B.
QUANTITY
1600AF
CRYO
1001A
1003A
1004G
1005T
1006G
1006G
1007A
1009A
1010D
1010D
1010E
1010E
1011A
1012C
1012D
1001A
1003A
1004G
1005TA
1006C/D
1006C/D
1007A
1009A
1010C/D
1010C/D
1010E/F
1010E/F
1011A
1012C
1012B
UNIT
SUBSTATION
KVA
FA
PRIMARY
OVERCURRENT
PROTECTION
OUTDOOR NEMA 3R UNIT SUBSTATIONS
TRUE NORTH
ELECTRON-ION COLLIDER
UNDER CONTRACT WITH
UNITED STATES DEPARTMENT OF ENERGY
PLANT ENGINEERING DIVISION
UPTON, NEW YORK 11973
JOB TITLE
JOB NO.
SCALE
ESHG RISK LEVEL
BLDG. NO.
DWN. BY
APP'D. BY
DATE
REV'D BY
DWG. TITLE
DWG. NO.
KEY PLAN
12" = 1'-0" E600
ONELINE DIAGRAM
SCHEDULES
10376646
Author
Legal Entity Name
HDR ARLINGTON
3001 WASHINGTON BLVD., SUITE 200
ARLINGTON, VIRGINIA 22201
Approver
Checker
12/14/23
MARK DATE DESCRIPTION
nehring Text Box This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology
INCOMING 13.8KV
FEEDER
TR-00002
13.8kV, 3⌀, 3W PRI.
2500kVA/3500kVA
480/277V, 3⌀, 4W SEC.
4000A, 480V, 3⌀, 3W
100 kAIC
UNIT SUBSTATION
800AF
800AT
3P ARMS
1600AF
1600AT
3P ARMS
PM 1
PM 2PM 2
800AF
800AT
3P
SPARE
1200AF
175AT
3P
HRG
1600AF
1600AT
3P ARMS
PM 2
MEDIUM VOLTAGE SECTION
TRANSFORMER SECTION
HIGH RESISTANCE GROUND SECTION
LOW VOLTAGE SECTION
A
RC
LIGHTNING
ARRESTER
RC
HRG
PM
AAA
A
RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES
HIGH RESISTANCE GROUND
POWER METER FOR ELECTRICAL SYSTEM MONITORING
ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION
PM 2
KEYNOTES
1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.
2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.
GENERAL NOTES
1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT
SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION
FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS
METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING
AND ZERO SEQUENCE CTS.
SPARE
1600AF
1600AT
3P ARMS
PM 2
A
1600A
EQUIPPED
SPACE
SPD SURGE PROTECTION DEVICE
SPD
R
R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD
ELECTRON-ION COLLIDER
UNDER CONTRACT WITH
UNITED STATES DEPARTMENT OF ENERGY
PLANT ENGINEERING DIVISION
UPTON, NEW YORK 11973
JOB TITLE
JOB NO.
SCALE
ESHG RISK LEVEL
BLDG. NO.
DWN. BY
APP'D. BY
DATE
REV'D BY
DWG. TITLE
DWG. NO.
NOT TO SCALE E601-01A
UNIT SUBSTATION ONELINE
DIAGRAM - BUILDING 1001A
10376646
Edward Lee
Legal Entity Name
HDR ARLINGTON
3001 WASHINGTON BLVD., SUITE 200
ARLINGTON, VIRGINIA 22201
Tommy Lane
Jean Sarsenbayev
11/01/23
NOT TO SCALE1
BUILDING 1001A UNIT SUBSTATION 1001A ONELINE DIAGRAM
MARK DATE DESCRIPTION
11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL
1001A nehring
This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology
TR-00002
13.8kV, 3⌀, 3W PRI.
2500kVA/3300kVA
480/277V, 3⌀, 4W SEC.
4000A, 480V, 3⌀, 3W
100 kAIC
UNIT SUBSTATION
800AF
800AT
3P ARMS
1600AF
1600AT
3P ARMS
PM 1
PM 2PM 2
800AF
800AT
3P
SPARE
1200AF
175AT
3P
HRG
1600AF
1600AT
3P ARMS
PM 2
MEDIUM VOLTAGE SECTION
TRANSFORMER SECTION
HIGH RESISTANCE GROUND SECTION
LOW VOLTAGE SECTION
A
RC
LIGHTNING
ARRESTER
RC
HRG
PM
AAA
A
RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES
HIGH RESISTANCE GROUND
POWER METER FOR ELECTRICAL SYSTEM MONITORING
ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION
PM 2
KEYNOTES
1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.
2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.
GENERAL NOTES
1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT
SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION
FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS
METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING
AND ZERO SEQUENCE CTS.
SPARE
1600AF
1600AT
3P ARMS
PM 2
A
1600A
EQUIPPED
SPACE
SPD SURGE PROTECTION DEVICE
SPD
R
R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD
ELECTRON-ION COLLIDER
UNDER CONTRACT WITH
UNITED STATES DEPARTMENT OF ENERGY
PLANT ENGINEERING DIVISION
UPTON, NEW YORK 11973
JOB TITLE
JOB NO.
SCALE
ESHG RISK LEVEL
BLDG. NO.
DWN. BY
APP'D. BY
DATE
REV'D BY
DWG. TITLE
DWG. NO.
NOT TO SCALE E601-03A
UNIT SUBSTATION ONELINE
DIAGRAM - BUILDING 1003A
10376646
Edward Lee
Legal Entity Name
HDR ARLINGTON
3001 WASHINGTON BLVD., SUITE 200
ARLINGTON, VIRGINIA 22201
Tommy Lane
Jean Sarsenbayev
11/01/23
NOT TO SCALE1
BUILDING 1003A UNIT SUBSTATION 1003A ONELINE DIAGRAM
MARK DATE DESCRIPTION
11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL
1003A nehring
This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology
TR-00002
13.8kV, 3⌀, 3W PRI.
1500kVA/2000kVA
480/277V, 3⌀, 4W SEC.
2500A, 480V, 3⌀, 3W
100 kAIC
UNIT SUBSTATION
800AF
800AT
3P ARMS
1600AF
1600AT
3P ARMS
PM 1
PM 2PM 2
800AF
800AT
3P
SPARE
1200AF
175AT
3P
HRG
1600AF
1600AT
3P ARMS
PM 2
MEDIUM VOLTAGE SECTION
TRANSFORMER SECTION
HIGH RESISTANCE GROUND SECTION
LOW VOLTAGE SECTION
A
RC
LIGHTNING
ARRESTER
RC
HRG
PM
AAA
A
RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES
HIGH RESISTANCE GROUND
POWER METER FOR ELECTRICAL SYSTEM MONITORING
ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION
PM 2
KEYNOTES
1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.
2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.
GENERAL NOTES
1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT
SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION
FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS
METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING
AND ZERO SEQUENCE CTS.
800A
EQUIPPED
SPACE
SPD SURGE PROTECTION DEVICE
SPD
R
R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD
ELECTRON-ION COLLIDER
UNDER CONTRACT WITH
UNITED STATES DEPARTMENT OF ENERGY
PLANT ENGINEERING DIVISION
UPTON, NEW YORK 11973
JOB TITLE
JOB NO.
SCALE
ESHG RISK LEVEL
BLDG. NO.
DWN. BY
APP'D. BY
DATE
REV'D BY
DWG. TITLE
DWG. NO.
NOT TO SCALE E601-04G
UNIT SUBSTATION ONELINE
DIAGRAM - BUILDING 1004G
10376646
Edward Lee
Legal Entity Name
HDR ARLINGTON
3001 WASHINGTON BLVD., SUITE 200
ARLINGTON, VIRGINIA 22201
Tommy Lane
Jean Sarsenbayev
11/01/23
NOT TO SCALE1
BUILDING 1004G UNIT SUBSTATION 1004G ONELINE DIAGRAM
MARK DATE DESCRIPTION
11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL
1004G nehring
This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology
TR-00002
13.8kV, 3⌀, 3W PRI.
2500kVA/3300kVA
480/277V, 3⌀, 4W SEC.
4000A, 480V, 3⌀, 3W
100 kAIC
UNIT SUBSTATION
800AF
800AT
3P ARMS
1600AF
1600AT
3P ARMS
PM 1
PM 2PM 2
800AF
800AT
3P
SPARE
1200AF
175AT
3P
HRG
1600AF
1600AT
3P ARMS
PM 2
MEDIUM VOLTAGE SECTION
TRANSFORMER SECTION
HIGH RESISTANCE GROUND SECTION
LOW VOLTAGE SECTION
A
RC
LIGHTNING
ARRESTER
RC
HRG
PM
AAA
A
RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES
HIGH RESISTANCE GROUND
POWER METER FOR ELECTRICAL SYSTEM MONITORING
ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION
PM 2
KEYNOTES
1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.
2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.
GENERAL NOTES
1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT
SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION
FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS
METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING
AND ZERO SEQUENCE CTS.
SPARE
1600AF
1600AT
3P ARMS
PM 2
A
1600A
EQUIPPED
SPACE
SPD SURGE PROTECTION DEVICE
SPD
R
R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD
ELECTRON-ION COLLIDER
UNDER CONTRACT WITH
UNITED STATES DEPARTMENT OF ENERGY
PLANT ENGINEERING DIVISION
UPTON, NEW YORK 11973
JOB TITLE
JOB NO.
SCALE
ESHG RISK LEVEL
BLDG. NO.
DWN. BY
APP'D. BY
DATE
REV'D BY
DWG. TITLE
DWG. NO.
NOT TO SCALE E601-05T
UNIT SUBSTATION ONELINE
DIAGRAM - BUILDING 1005T
10376646
Edward Lee
Legal Entity Name
HDR ARLINGTON
3001 WASHINGTON BLVD., SUITE 200
ARLINGTON, VIRGINIA 22201
Tommy Lane
Jean Sarsenbayev
11/01/23
NOT TO SCALE1
BUILDING 1005T UNIT SUBSTATION 1005TA ONELINE DIAGRAM
MARK DATE DESCRIPTION
11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL
1005T nehring
This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology
TR-00002
13.8kV, 3⌀, 3W PRI.
1500kVA/2000kVA
480/277V, 3⌀, 4W SEC.
2500A, 480V, 3⌀, 3W
100 kAIC
UNIT SUBSTATION
800AF
800AT
3P ARMS
1600AF
1600AT
3P ARMS
PM 1
PM 2PM 2
800AF
800AT
3P
1200AF
175AT
3P
HRG
MEDIUM VOLTAGE SECTION
TRANSFORMER SECTION
HIGH RESISTANCE GROUND SECTION
LOW VOLTAGE SECTION
RC
LIGHTNING
ARRESTER
RC
HRG
PM
AAA
A
RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES
HIGH RESISTANCE GROUND
POWER METER FOR ELECTRICAL SYSTEM MONITORING
ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION
PM 2
KEYNOTES
1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.
2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.
GENERAL NOTES
1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT
SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION
FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS
METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING
AND ZERO SEQUENCE CTS.
800A
EQUIPPED
SPACE
SPD SURGE PROTECTION DEVICE
SPD
R
R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD
ELECTRON-ION COLLIDER
UNDER CONTRACT WITH
UNITED STATES DEPARTMENT OF ENERGY
PLANT ENGINEERING DIVISION
UPTON, NEW YORK 11973
JOB TITLE
JOB NO.
SCALE
ESHG RISK LEVEL
BLDG. NO.
DWN. BY
APP'D. BY
DATE
REV'D BY
DWG. TITLE
DWG. NO.
NOT TO SCALE E601-06G
UNIT SUBSTATION ONELINE
DIAGRAM - BUILDING 1006G
10376646
Edward Lee
Legal Entity Name
HDR ARLINGTON
3001 WASHINGTON BLVD., SUITE 200
ARLINGTON, VIRGINIA 22201
Tommy Lane
Jean Sarsenbayev
11/01/23
NOT TO SCALE1
BUILDING 1006G UNIT SUBSTATION 1006C ONELINE DIAGRAM
MARK DATE DESCRIPTION
11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL
1006G nehring
This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology
TR-00002
13.8kV, 3⌀, 3W PRI.
2500kVA/3300kVA
480/277V, 3⌀, 4W SEC.
4000A, 480V, 3⌀, 3W
100 kAIC
UNIT SUBSTATION
800AF
800AT
3P ARMS
1600AF
1600AT
3P ARMS
PM 1
PM 2PM 2
800AF
800AT
3P
SPARE
1200AF
175AT
3P
HRG
1600AF
1600AT
3P ARMS
PM 2
MEDIUM VOLTAGE SECTION
TRANSFORMER SECTION
HIGH RESISTANCE GROUND SECTION
LOW VOLTAGE SECTION
A
RC
LIGHTNING
ARRESTER
RC
HRG
PM
AAA
A
RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES
HIGH RESISTANCE GROUND
POWER METER FOR ELECTRICAL SYSTEM MONITORING
ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION
PM 2
KEYNOTES
1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.
2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.
GENERAL NOTES
1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT
SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION
FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS
METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING
AND ZERO SEQUENCE CTS.
SPARE
1600AF
1600AT
3P ARMS
PM 2
A
1600A
EQUIPPED
SPACE
SPD SURGE PROTECTION DEVICE
SPD
R
R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD
ELECTRON-ION COLLIDER
UNDER CONTRACT WITH
UNITED STATES DEPARTMENT OF ENERGY
PLANT ENGINEERING DIVISION
UPTON, NEW YORK 11973
JOB TITLE
JOB NO.
SCALE
ESHG RISK LEVEL
BLDG. NO.
DWN. BY
APP'D. BY
DATE
REV'D BY
DWG. TITLE
DWG. NO.
NOT TO SCALE E601-07A
UNIT SUBSTATION ONELINE
DIAGRAM - BUILDING 1007A
10376646
Edward Lee
Legal Entity Name
HDR ARLINGTON
3001 WASHINGTON BLVD., SUITE 200
ARLINGTON, VIRGINIA 22201
Tommy Lane
Jean Sarsenbayev
11/01/23
NOT TO SCALE1
BUILDING 1007A UNIT SUBSTATION 1007A ONELINE DIAGRAM
MARK DATE DESCRIPTION
11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL
1007A nehring
This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology
TR-00002
13.8kV, 3⌀, 3W PRI.
2500kVA/3300kVA
480/277V, 3⌀, 4W SEC.
4000A, 480V, 3⌀, 3W
100 kAIC
UNIT SUBSTATION
800AF
800AT
3P ARMS
1600AF
1600AT
3P ARMS
PM 1
PM 2PM 2
800AF
800AT
3P
SPARE
1200AF
175AT
3P
HRG
1600AF
1600AT
3P ARMS
PM 2
MEDIUM VOLTAGE SECTION
TRANSFORMER SECTION
HIGH RESISTANCE GROUND SECTION
LOW VOLTAGE SECTION
A
RC
LIGHTNING
ARRESTER
RC
HRG
PM
AAA
A
RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES
HIGH RESISTANCE GROUND
POWER METER FOR ELECTRICAL SYSTEM MONITORING
ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION
PM 2
KEYNOTES
1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.
2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.
GENERAL NOTES
1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT
SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION
FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS
METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING
AND ZERO SEQUENCE CTS.
SPARE
1600AF
1600AT
3P ARMS
PM 2
A
1600A
EQUIPPED
SPACE
SPD SURGE PROTECTION DEVICE
SPD
R
R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD
ELECTRON-ION COLLIDER
UNDER CONTRACT WITH
UNITED STATES DEPARTMENT OF ENERGY
PLANT ENGINEERING DIVISION
UPTON, NEW YORK 11973
JOB TITLE
JOB NO.
SCALE
ESHG RISK LEVEL
BLDG. NO.
DWN. BY
APP'D. BY
DATE
REV'D BY
DWG. TITLE
DWG. NO.
NOT TO SCALE E601-09A
UNIT SUBSTATION ONELINE
DIAGRAM - BUILDING 1009A
10376646
Edward Lee
Legal Entity Name
HDR ARLINGTON
3001 WASHINGTON BLVD., SUITE 200
ARLINGTON, VIRGINIA 22201
Tommy Lane
Jean Sarsenbayev
11/01/23
NOT TO SCALE1
BUILDING 1009A UNIT SUBSTATION 1009A ONELINE DIAGRAM
MARK DATE DESCRIPTION
11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL
1009A nehring
This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology
TR-00002
13.8kV, 3⌀, 3W PRI.
2000kVA/2660kVA
480/277V, 3⌀, 4W SEC.
3200A, 480V, 3⌀, 3W
100 kAIC
UNIT SUBSTATION
800AF
800AT
3P ARMS
1600AF
1600AT
3P ARMS
PM 1
PM 2PM 2
800AF
800AT
3P
SPARE
1200AF
175AT
3P
HRG
1600AF
1600AT
3P ARMS
PM 2
MEDIUM VOLTAGE SECTION
TRANSFORMER SECTION
HIGH RESISTANCE GROUND SECTION
LOW VOLTAGE SECTION
A
RC
LIGHTNING
ARRESTER
RC
HRG
PM
AAA
A
RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES
HIGH RESISTANCE GROUND
POWER METER FOR ELECTRICAL SYSTEM MONITORING
ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION
PM 2
KEYNOTES
1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.
2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.
GENERAL NOTES
1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT
SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION
FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS
METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING
AND ZERO SEQUENCE CTS.
SPARE
1600AF
1600AT
3P ARMS
PM 2
A
1600A
EQUIPPED
SPACE
SPD SURGE PROTECTION DEVICE
SPD
R
R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD
ELECTRON-ION COLLIDER
UNDER CONTRACT WITH
UNITED STATES DEPARTMENT OF ENERGY
PLANT ENGINEERING DIVISION
UPTON, NEW YORK 11973
JOB TITLE
JOB NO.
SCALE
ESHG RISK LEVEL
BLDG. NO.
DWN. BY
APP'D. BY
DATE
REV'D BY
DWG. TITLE
DWG. NO.
NOT TO SCALE E601-10D
UNIT SUBSTATION ONELINE
DIAGRAM - BUILDING 1010D
10376646
Edward Lee
Legal Entity Name
HDR ARLINGTON
3001 WASHINGTON BLVD., SUITE 200
ARLINGTON, VIRGINIA 22201
Tommy Lane
Jean Sarsenbayev
11/01/23
NOT TO SCALE1
BUILDING 1010D UNIT SUBSTATION 1010C ONELINE DIAGRAM
MARK DATE DESCRIPTION
11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL
1010D nehring
This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology
TR-00002
13.8kV, 3⌀, 3W PRI.
1500kVA/2000kVA
480/277V, 3⌀, 4W SEC.
2500A, 480V, 3⌀, 3W
100 kAIC
UNIT SUBSTATION
800AF
800AT
3P ARMS
1600AF
1600AT
3P ARMS
PM 1
PM 2PM 2
800AF
800AT
3P
1200AF
175AT
3P
HRG
MEDIUM VOLTAGE SECTION
TRANSFORMER SECTION
HIGH RESISTANCE GROUND SECTION
LOW VOLTAGE SECTION
RC
LIGHTNING
ARRESTER
RC
HRG
PM
AAA
A
RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES
HIGH RESISTANCE GROUND
POWER METER FOR ELECTRICAL SYSTEM MONITORING
ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION
PM 2
KEYNOTES
1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.
2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.
GENERAL NOTES
1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT
SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION
FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS
METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING
AND ZERO SEQUENCE CTS.
800A
EQUIPPED
SPACE
SPD SURGE PROTECTION DEVICE
SPD
R
R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD
ELECTRON-ION COLLIDER
UNDER CONTRACT WITH
UNITED STATES DEPARTMENT OF ENERGY
PLANT ENGINEERING DIVISION
UPTON, NEW YORK 11973
JOB TITLE
JOB NO.
SCALE
ESHG RISK LEVEL
BLDG. NO.
DWN. BY
APP'D. BY
DATE
REV'D BY
DWG. TITLE
DWG. NO.
NOT TO SCALE E601-10E
UNIT SUBSTATION ONELINE
DIAGRAM - BUILDING 1010E
10376646
Edward Lee
Legal Entity Name
HDR ARLINGTON
3001 WASHINGTON BLVD., SUITE 200
ARLINGTON, VIRGINIA 22201
Tommy Lane
Jean Sarsenbayev
11/01/23
NOT TO SCALE1
BUILDING 1010E UNIT SUBSTATION 1010E ONELINE DIAGRAM
MARK DATE DESCRIPTION
11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL
1010E nehring
This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology
TR-00002
13.8kV, 3⌀, 3W PRI.
2500kVA/3300kVA
480/277V, 3⌀, 4W SEC.
4000A, 480V, 3⌀, 3W
100 kAIC
UNIT SUBSTATION
800AF
800AT
3P ARMS
1600AF
1600AT
3P ARMS
PM 1
PM 2PM 2
800AF
800AT
3P
SPARE
1200AF
175AT
3P
HRG
1600AF
1600AT
3P ARMS
PM 2
MEDIUM VOLTAGE SECTION
TRANSFORMER SECTION
HIGH RESISTANCE GROUND SECTION
LOW VOLTAGE SECTION
A
RC
LIGHTNING
ARRESTER
RC
HRG
PM
AAA
A
RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES
HIGH RESISTANCE GROUND
POWER METER FOR ELECTRICAL SYSTEM MONITORING
ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION
PM 2
KEYNOTES
1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.
2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.
GENERAL NOTES
1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT
SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION
FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS
METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING
AND ZERO SEQUENCE CTS.
SPARE
1600AF
1600AT
3P ARMS
PM 2
A
1600A
EQUIPPED
SPACE
SPD SURGE PROTECTION DEVICE
SPD
R
R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD
ELECTRON-ION COLLIDER
UNDER CONTRACT WITH
UNITED STATES DEPARTMENT OF ENERGY
PLANT ENGINEERING DIVISION
UPTON, NEW YORK 11973
JOB TITLE
JOB NO.
SCALE
ESHG RISK LEVEL
BLDG. NO.
DWN. BY
APP'D. BY
DATE
REV'D BY
DWG. TITLE
DWG. NO.
NOT TO SCALE E601-11A
UNIT SUBSTATION ONELINE
DIAGRAM - BUILDING 1011A
10376646
Edward Lee
Legal Entity Name
HDR ARLINGTON
3001 WASHINGTON BLVD., SUITE 200
ARLINGTON, VIRGINIA 22201
Tommy Lane
Jean Sarsenbayev
11/01/23
NOT TO SCALE1
BUILDING 1011A UNIT SUBSTATION 1011A ONELINE DIAGRAM
MARK DATE DESCRIPTION
11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL
1011A nehring
This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology
TR-00002
13.8kV, 3⌀, 3W PRI.
1000kVA/1330kVA
480/277V, 3⌀, 4W SEC.
1600A, 480V, 3⌀, 3W
100 kAIC
UNIT SUBSTATION
800AF
800AT
3P ARMS
PM 1
PM 2
800AF
800AT
3P
1200AF
175AT
3P
HRG
MEDIUM VOLTAGE SECTION
TRANSFORMER SECTION
HIGH RESISTANCE GROUND SECTION
LOW VOLTAGE SECTION
RC
LIGHTNING
ARRESTER
RC
HRG
PM
AA
A
RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES
HIGH RESISTANCE GROUND
POWER METER FOR ELECTRICAL SYSTEM MONITORING
ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION
PM 2
KEYNOTES
1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.
2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.
GENERAL NOTES
1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT
SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION
FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS
METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING
AND ZERO SEQUENCE CTS.
800A
EQUIPPED
SPACE
SPD SURGE PROTECTION DEVICE
SPD
R
R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD
ELECTRON-ION COLLIDER
UNDER CONTRACT WITH
UNITED STATES DEPARTMENT OF ENERGY
PLANT ENGINEERING DIVISION
UPTON, NEW YORK 11973
JOB TITLE
JOB NO.
SCALE
ESHG RISK LEVEL
BLDG. NO.
DWN. BY
APP'D. BY
DATE
REV'D BY
DWG. TITLE
DWG. NO.
NOT TO SCALE E601-12C
UNIT SUBSTATION ONELINE
DIAGRAM - BUILDING 1012C
10376646
Edward Lee
Legal Entity Name
HDR ARLINGTON
3001 WASHINGTON BLVD., SUITE 200
ARLINGTON, VIRGINIA 22201
Tommy Lane
Jean Sarsenbayev
11/01/23
NOT TO SCALE1
BUILDING 1012C UNIT SUBSTATION 1012C ONELINE DIAGRAM
MARK DATE DESCRIPTION
11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL
1012C nehring
This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology
TR-00002
13.8kV, 3⌀, 3W PRI.
1500kVA/2000kVA
480/277V, 3⌀, 4W SEC.
2500A, 480V, 3⌀, 3W
100 kAIC
UNIT SUBSTATION
800AF
800AT
3P ARMS
PM 1
PM 2
800AF
800AT
3P
1200AF
175AT
3P
HRG
MEDIUM VOLTAGE SECTION
TRANSFORMER SECTION
HIGH RESISTANCE GROUND SECTION
LOW VOLTAGE SECTION
RC
LIGHTNING
ARRESTER
RC
HRG
PM
AA
A
RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES
HIGH RESISTANCE GROUND
POWER METER FOR ELECTRICAL SYSTEM MONITORING
ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION
PM 2
KEYNOTES
1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.
2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.
GENERAL NOTES
1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT
SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION
FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS
METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING
AND ZERO SEQUENCE CTS.
800A
EQUIPPED
SPACE
SPD SURGE PROTECTION DEVICE
SPD
R
R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD
ELECTRON-ION COLLIDER
UNDER CONTRACT WITH
UNITED STATES DEPARTMENT OF ENERGY
PLANT ENGINEERING DIVISION
UPTON, NEW YORK 11973
JOB TITLE
JOB NO.
SCALE
ESHG RISK LEVEL
BLDG. NO.
DWN. BY
APP'D. BY
DATE
REV'D BY
DWG. TITLE
DWG. NO.
NOT TO SCALE E601-12D
UNIT SUBSTATION ONELINE
DIAGRAM - BUILDING 1012D
10376646
Edward Lee
Legal Entity Name
HDR ARLINGTON
3001 WASHINGTON BLVD., SUITE 200
ARLINGTON, VIRGINIA 22201
Tommy Lane
Jean Sarsenbayev
11/01/23
NOT TO SCALE1
BUILDING 1012D UNIT SUBSTATION 1012B ONELINE DIAGRAM
MARK DATE DESCRIPTION
11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL
1012D nehring
This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology
TR-00002
13.8kV, 3⌀, 3W PRI.
1500kVA/2000kVA
480/277V, 3⌀, 4W SEC.
2500A, 480V, 3⌀, 3W
100 kAIC
UNIT SUBSTATION
800AF
800AT
3P ARMS
1600AF
1600AT
3P ARMS
PM 1
PM 2PM 2
800AF
800AT
3P
1200AF
175AT
3P
HRG
MEDIUM VOLTAGE SECTION
TRANSFORMER SECTION
HIGH RESISTANCE GROUND SECTION
LOW VOLTAGE SECTION
RC
LIGHTNING
ARRESTER
RC
HRG
PM
AAA
A
RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES
HIGH RESISTANCE GROUND
POWER METER FOR ELECTRICAL SYSTEM MONITORING
ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION
PM 2
KEYNOTES
1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.
2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.
GENERAL NOTES
1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT
SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION
FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS
METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING
AND ZERO SEQUENCE CTS.
800A
EQUIPPED
SPACE
SPD SURGE PROTECTION DEVICE
SPD
R
R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD
ELECTRON-ION COLLIDER
UNDER CONTRACT WITH
UNITED STATES DEPARTMENT OF ENERGY
PLANT ENGINEERING DIVISION
UPTON, NEW YORK 11973
JOB TITLE
JOB NO.
SCALE
ESHG RISK LEVEL
BLDG. NO.
DWN. BY
APP'D. BY
DATE
REV'D BY
DWG. TITLE
DWG. NO.
NOT TO SCALE E602-06G
UNIT SUBSTATION ONELINE
DIAGRAM - BUILDING 1006G
10376646
Edward Lee
Legal Entity Name
HDR ARLINGTON
3001 WASHINGTON BLVD., SUITE 200
ARLINGTON, VIRGINIA 22201
Tommy Lane
Jean Sarsenbayev
11/01/23
NOT TO SCALE1
BUILDING 1006G UNIT SUBSTATION 1006D ONELINE DIAGRAM
MARK DATE DESCRIPTION
11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL
1006G nehring
This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology
TR-00002
13.8kV, 3⌀, 3W PRI.
2000kVA/2660kVA
480/277V, 3⌀, 4W SEC.
3200A, 480V, 3⌀, 3W
100 kAIC
UNIT SUBSTATION
800AF
800AT
3P ARMS
1600AF
1600AT
3P ARMS
PM 1
PM 2PM 2
800AF
800AT
3P
SPARE
1200AF
175AT
3P
HRG
1600AF
1600AT
3P ARMS
PM 2
MEDIUM VOLTAGE SECTION
TRANSFORMER SECTION
HIGH RESISTANCE GROUND SECTION
LOW VOLTAGE SECTION
A
RC
LIGHTNING
ARRESTER
RC
HRG
PM
AAA
A
RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES
HIGH RESISTANCE GROUND
POWER METER FOR ELECTRICAL SYSTEM MONITORING
ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION
PM 2
KEYNOTES
1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.
2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.
GENERAL NOTES
1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT
SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION
FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS
METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING
AND ZERO SEQUENCE CTS.
SPARE
1600AF
1600AT
3P ARMS
PM 2
A
1600A
EQUIPPED
SPACE
SPD SURGE PROTECTION DEVICE
SPD
R
R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD
ELECTRON-ION COLLIDER
UNDER CONTRACT WITH
UNITED STATES DEPARTMENT OF ENERGY
PLANT ENGINEERING DIVISION
UPTON, NEW YORK 11973
JOB TITLE
JOB NO.
SCALE
ESHG RISK LEVEL
BLDG. NO.
DWN. BY
APP'D. BY
DATE
REV'D BY
DWG. TITLE
DWG. NO.
NOT TO SCALE E602-10D
UNIT SUBSTATION ONELINE
DIAGRAM - BUILDING 1010D
10376646
Edward Lee
Legal Entity Name
HDR ARLINGTON
3001 WASHINGTON BLVD., SUITE 200
ARLINGTON, VIRGINIA 22201
Tommy Lane
Jean Sarsenbayev
11/01/23
NOT TO SCALE1
BUILDING 1010D UNIT SUBSTATION 1010D ONELINE DIAGRAM
MARK DATE DESCRIPTION
11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL
1010D nehring
This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology
TR-00002
13.8kV, 3⌀, 3W PRI.
1500kVA/2000kVA
480/277V, 3⌀, 4W SEC.
2500A, 480V, 3⌀, 3W
100 kAIC
UNIT SUBSTATION
800AF
800AT
3P ARMS
1600AF
1600AT
3P ARMS
PM 1
PM 2PM 2
800AF
800AT
3P
1200AF
175AT
3P
HRG
MEDIUM VOLTAGE SECTION
TRANSFORMER SECTION
HIGH RESISTANCE GROUND SECTION
LOW VOLTAGE SECTION
RC
LIGHTNING
ARRESTER
RC
HRG
PM
AAA
A
RC SNUBBER CIRCUIT TO PROTECT TRANSFORMER FROM VOLTAGE SPIKES
HIGH RESISTANCE GROUND
POWER METER FOR ELECTRICAL SYSTEM MONITORING
ZERO SEQUENCE CT CONNECTED TO AMMETER FOR GROUND FAULT DETECTION
PM 2
KEYNOTES
1. PROVIDE POWER XPERT 4000 POWER METER FOR POWER MONITORING.
2. PROVIDE POWER XPERT PXM1300 POWER METER FOR POWER MONITORING.
GENERAL NOTES
1. ONELINE DIAGRAM IS NOT INTENDED TO REPRESENT A PROJECT UNIT
SUBSTATION, BUT IS INTENDED TO BE REPRESENTATIVE OF ALL UNIT SUBSTATION
FOR THE PURPOSE OF CONVEYING PROCUREMENT REQUIREMENTS SUCH AS
METERING CAPABILITIES, RC SNUBBER CIRCUITS, HIGH RESISTANCE GROUNDING
AND ZERO SEQUENCE CTS.
800A
EQUIPPED
SPACE
SPD SURGE PROTECTION DEVICE
SPD
R
R SEL-751 RELAY FOR TRIPPING PRIMARY BREAKER ON OVERLOAD
ELECTRON-ION COLLIDER
UNDER CONTRACT WITH
UNITED STATES DEPARTMENT OF ENERGY
PLANT ENGINEERING DIVISION
UPTON, NEW YORK 11973
JOB TITLE
JOB NO.
SCALE
ESHG RISK LEVEL
BLDG. NO.
DWN. BY
APP'D. BY
DATE
REV'D BY
DWG. TITLE
DWG. NO.
NOT TO SCALE E602-10E
UNIT SUBSTATION ONELINE
DIAGRAM - BUILDING 1010E
10376646
Edward Lee
Legal Entity Name
HDR ARLINGTON
3001 WASHINGTON BLVD., SUITE 200
ARLINGTON, VIRGINIA 22201
Tommy Lane
Jean Sarsenbayev
11/01/23
NOT TO SCALE1
BUILDING 1010E UNIT SUBSTATION 1010F ONELINE DIAGRAM
MARK DATE DESCRIPTION
11/01/2023 PRELIMINARY DESIGN 30% REVIEW SUBMITTAL
1010E nehring
This information is controlled by the U.S. Department of Commerce Export Administration Regulation 15 CFR Parts 730-774 as EAR99 Technology
File details come from the government source that posted it. Updated .