Attachment C.pdf

PDF 73 KB Posted

Attached to
St Clair Shores Fire Station 1 and Police Dept Furniture Purchase and Install.
Solicitation number
SCS-FD-PD-FURNITURE-2025
Issued by
Macomb County, Michigan

About this file

This document is a Room Finish Schedule and Wall Types specification sheet for the City of St. Clair Shores New Fire Headquarters project located at 26700 Harper Ave in St. Clair Shores, Michigan. The detailed architectural drawing provides comprehensive information about room finishes, wall construction types, and surface treatments for various rooms within the new fire station, including specific specifications for floor materials, wall surfaces, base treatments, and ceiling finishes for each room numbered from 101 to 253.

The document includes extensive technical details about partition series, wall construction methods, fire ratings, and acoustic performance requirements. Room finishes range from carpet (CPT) and luxury vinyl tile (LVT) to exposed painted concrete and specialized epoxy-painted surfaces, particularly in functional areas like the apparatus bay, decontamination room, and hot zones. The specification sheet provides precise instructions for wall construction, including metal stud spacing, gypsum board requirements, insulation specifications, and fire-rated partition guidelines, with particular attention to sound attenuation and fire safety considerations for different areas within the fire station.

View the file

Other files

File Type Posted
Attachment A.pdf PDF
Attachment H.pdf PDF
Attachment B.pdf PDF
Attachment E.pdf PDF
PD-FD-Furniture-Specs-2025.pdf PDF
Attachment D.pdf PDF
Attachment F.pdf PDF
Attachment G.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A PARTITION�SERIES�'A'

1"�=�1'-0"

7�5/8"

UNDERSIDE�OF�FLOOR�OR�ROOF

REFER�TO�STRUCTURAL�FOR�

REQUIRED�CONNECTION

CEILING�AS�SCHEDULED

-�CONCRETE�MASONRY�-�REFER

TO�STRUCTURAL�FOR�REINFORCING

BASE�AS�SCHEDULED

11�5/8"

5�5/8"

3�5/8"

0A12

0A8

0A6

0A4

UL�U906

UL�U905

UL�U905

1A6

1A8

1A12

GROUT�MASONRY�WALL�

TOP�COURSE�SOLID

PARTITION�SERIES�'B'

1"�=�1'-0"

-�5/8"�GYP.�BOARD�(BOTH�SIDES)

-�MTL.�STUDS�@�16"�OC

-�FIBER�BATT�ACOUSTICAL�INSULATION

(NOTE:�USE�IMPACT�RESISTANT�

GYP�AT�ALL�CORRIDORS)

CEILING�AS�SCHEDULED

BASE�AS�SCHEDULED

B

4" �M

IN

3�5/8"�MTL.�KICKERS�TO�UNDERSIDE�

OF�ROOF�TRUSS�ABOVE�@�32"�O.C.

DEFLECTION�TRACK,�TYP.�3/4"�

STRUCT.�DEFLECTION�ALLOWANCE.

0B3

0B2

4�7/8"

UL�U419

0B4

0B6

5�1/4"

7�1/4"

1B3

1B2

1B4

1B6

UL�U419

UL�U419

UL�U419

METAL�RUNNER�CHANNEL�

(SECURED�TO�FLOOR)

SEALANT�(BOTH�SIDES)

3�3/4"

(WHERE�GYP�DOES�NOT�

GO�TO�DECK�ABOVE)

UNDERSIDE�OF�FLOOR�OR�ROOF

-�5/8"�GYP.�BOARD�

-�MTL.�FURRING�CHANNEL�@�16"�OC

(NOTE:�USE�IMPACT�RESISTANT�

GYP�AT�ALL�CORRIDORS)

M

IN4"

0F1

0F0

0F2

0F3

3�1/8"

4�1/4"

1�1/2"

2�1/4"

FACE�OF�WALL�CONSTRUCTION�

REFER�TO�PLAN

UNDERSIDE�OF�FLOOR�OR�ROOF

CEILING�AS�SCHEDULED

BASE�AS�SCHEDULED

METAL�RUNNER�CHANNEL�

(SECURED�TO�FLOOR)

SEALANT

PARTITION�SERIES�'F'

1"�=�1'-0"F

GENERAL�NOTES:

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

A.

B.

C.

D.

"WALL"�AND�"PARTITION"�ARE�USED�TO�DENOTE�EITHER�WALLS�OR�PARTITIONS�AND�ARE�USED�

INTERCHANGEABLY

REFER�TO�STRUCTURAL�FOR�ALL�REQUIRED�REINFORCING�AND�FOR�WALL�CONNECTIONS�TO�

FLOORS�AND�ROOFS

AT�FIRE�RATED�WALLS�FILL�ALL�VOIDS,�PENETRATIONS�ETC.�AND�SEAL�-�REFER�TO�DRAWING�

A0-02�LIFE�SAFETY�PLANS�&�CODE�INFORMATION�FOR�ALL�PARTITION�FIRE�RATINGS

WHERE�A�WALL�RUNS�PARALLEL�TO�THE�DIRECTION�OF�A�ROOF�TRUSS�AND�DOES�NOT�ALIGN�

UNDERNEATH�A�TRUSS�-�PROVIDE�MTL.�STUD�BRIDGING�BETWEEN�THE�ROOF�TRUSSES�@�48"�

O.C.�MAX.�TO�ATTACH�TO

REFER�TO�ROOM�FINISH�SCHEDULE�FOR�WALL�FINISHES�AND�WAL�BASE

PARTITION�TYPE

SUBSTITUTE�TILE�BACKING�BOARD�AT�LOCATIONS�TO�RECEIVE�A�TILE�WALL�FINISH

ALL�NON-LOAD�BEARING�METAL�WALL�FRAMING�SHALL�BE�BASED�ON�TOTAL�STUD�HEIGHT

AT�INTERSECTIONS�OF�DIS-SIMILAR�PARTITION�TYPES,�THE�HIGHEST�RATED�PARTITION�IS�TO�

RUN�THROUGH�THE�INTERSECTION�TO�MAINTAIN�ENCLOSURE

FIRE-RATED�PARTITIONS�SHALL�BE�CONSTRUCTED�ACCORDING�TO�THE�FIRE�TEST�INDICATED.�

NO�SUBSTITUTIONS�OF�MATERIALS�OR�DEVIATIONS�FROM�CONSTRUCTION�ARE�ALLOWED.�

ADDITIONAL�LAYERS�MAY�BE�REQUIRED�FOR�ACOUSTICAL�OR�OTHER�REASONS�AND�MUST�BE�

EXECUTED�AS�SHOWN

STC�RATINGS�ARE�MINIMUM�ACOUSTICAL�PERFORMANCE�REQUIREMENT.�SPECIFIC�

ACOUSTICAL�TESTS�ARE�GIVEN�FOR�REFERENCE�ONLY.�SOUND�ATTENUATION�BLANKET�

THICKNESS�SHALL�BE�AS�FOLLOWS:

1�1/2"�FOR�PARTITIONS�WITH�1�5/8"�AND�2�1/2"�STUDS�(INCLUDING�SHAFTWALLS)

3"�FOR�PARTITIONS�WITH�3�5/8",�4"�OR�6"�STUDS�UON

3"�FOR�SHAFTWALLS�WITH�4"�OR�6"�STUDS�UON

AS�REQUIRED�FOR�FIRE�RATING

12. AT�ALL�FIRE�RATED�WALL�CONSTRUCTION,�PROVIDE�SIGNAGE�ABOVE�THE�ADJACENT�

ACCESSIBLE�CEILING�THAT�STATES:�"FIRE�AND/OR�SMOKE�BARRIER�-�PROTECT�ALL�OPENINGS."� THE�LETTERS�ARE�TO�BE�3"�HIGH�MIN.�AND�ARE�TO�BE�STENCILED�IN�PAINT�DIRECTLY�ONTO� THE�WALL.�LOCATE�THE�SIGNS� 30'-0"�O.C.�MAXIMUM.�AND�NO�MORE�THAN�15'-0"�FROM�THE�

END�OF�EACH�WALL.�[703.7]

GRAPHIC�TAG

#X#

PARTITION�SERIES

SIZE�DESIGNATOR�

(SEE�TABLE�BELOW)

S=SMOKE�PARTITION

0=NON�RATED

1=1-HR�FIRE�RATED

2=2-HR�FIRE�RATED

3=30�MIN�FIRE�RATED

ASSEMBLY�RATING

MATERIAL DESIGNATION�SIZE ACTUAL�SIZE

3�5/8" 5�5/8" 7�5/8" 11�5/8"

SPACING

1�5/8" 2�1/2" 3�5/8" 4" 6"

MASONRY

STEEL�STUDS

FURRING 0

7/8" 1�5/8" 2�1/2" 3�5/8"

SHAFTWALL

C-H�STUDS

2�1/2" 4" 6"

N/A

16"�OC

16"�OC

24"�OC

ROOM�FINISH�LEGEND

AF ATHLETIC�FLOORING

ACT ACOUSTIC�TILE�AND�GRID�CEILING�SYSTEM

CONC CONRETE

CPT CARPET

CT CERAMIC�TILE

EP EPOXY�FLOORING

EP�PNT EPOXY�PAINT

LVT LUXURY�VINYL�TILE�FLOORING

PC EXPOSED�PRECAST�CONCRETE�PLANK�CEILING

PT PORCELAIN�TILE

PNT PAINT

RB RESILIENT�WALL�BASE

SS SOLID�SURFACING

VCT VINYL�COMPOSITION�TILE

MP FORMED�METAL�CEILING�PANEL

ROOM�FINISH�GENERAL�NOTES

A.

B.

C.

REFER�TO�REFLECTED�CEILING�PLANS,�INTERIOR�ELEVATIONS,�AND�FINISH�FLOOR�PLANS�FOR�LOCATIONS�OF�MATERIAL�/�PAINT�

TRANSITIONS.

REFER�TO�MATERAL�FINISH�&�COLOR�SCHEDULE,�SPECIFICATION�SECTION�000200.

PROVIDE�REDUCER�STRIP�AT�FLOOR�MATERIAL�TRANSITIONS�AS�NEEDED,�REFER�TO�THRESHOLD�DETAILS�AND�DOOR�SCHEDULE.

ROOM�FINISH�KEY�NOTES

1. NOTE

PARTNERS�in�Architecture,�PLCPARTNERS�in�Architecture,�PLC

DRAWN�BY

CHECKED�BY

Statement�of�Intellectual�Property

65�Market�Street Mount�Clemens,�MI�48043 P�586.469.3600 F�586.469.3607

PROJECT�NO.

APPROVED�BY

PROJECT�NAME

OWNER

SHEET�NAME

KEY�PLAN

ISSUES�/�REVISIONS

SHEET�NO.

CONSULTANT

The�ideas,�concepts,�drawings�and�thoughts�conveyed� herein�are�the�intellectual�property�of�PARTNERS�in� Architecture,�PLC,�65�Market�Street,�Mount�Clemens,�MI,� 48043�(P586.469.3600).�This�set�of�drawings,�in�whole�or� in�part,�may�not�be�reproduced,�without�the�written�consent� of�PARTNERS�in�Architecture,�PLC.�This�information�is� protected�under�U.S.�Copyright�Law,�all�rights�reserved.

©�Copyright�2024

NORTH

PARTNERS

THIS�DRAWING�IS�NOT�TO�BE�USED�FOR�

CONSTRUCTION�UNLESS�ISSUED�BELOW�

SPECIFICALLY�FOR��"CONSTRUCTION"

6/14/2024�4:22:44�PM D:\_revit local\23�147�SCS�FD�Central�CD_DGwozdzDHM3H.rvt A0-04

City�of�St.�Clair�Shores

SCS�New�Fire Headquarters

DJG

DJG

23-147

26700�Harper�Ave St�Clair�Shores,�MI�48081

DG

Room�Finish Schedule,�Wall�Types, Signage

Room�Finish�Schedule

ROOM

NO. ROOM�NAME FLOOR BASE

WALLS

CEILING ROOM�FINISH�KEY�NOTESNORTH EAST SOUTH WEST

101 VESTIBULE CPT-1 RB-1 -- PNT-1 PNT-1 PNT-1 ACT-1

102 LOBBY RTF-1,2,3 RB-1 PNT PNT PNT PNT EXPOSED�-�PNT-X

103 RECEPTION CPT-2,3 RB-1 PNT-1 PNT-4 PNT-1 PNT-1 ACT-1

104 OFFICE CPT-4 RB-1 PNT-1 PNT-4 PNT-1 PNT-1 ACT-1

105 CHIEF'S�OFFICE CPT-4 RB-1 PNT-1 PNT-4 PNT-1 PNT-1 ACT-1

106 CORRIDOR CPT-2,3 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 ACT-1

107 CONFERENCE CPT-4,5,6 RB-1 PNT-1 PNT-4 PNT-1 PNT-1 ACT-1

108 CODE�LIBRARY CPT-2,3 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 ACT-1

109 STAIR PC-1�/�SN-1 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 EXPOSED�-�PNT-X

110 AIRLOCK PC-1 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 EXPOSED�-�PNT-X

111 HOT�ZONE PC-1 RB-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 EXPOSED�-�PNT-X

112 WC PT-1 CT-1 CT-2,3�/�PNT-1 CT-2,3�/�PNT-1 CT-2,3�/�PNT-1 CT-2,3�/�PNT-1 PNT-2

113 ELEC PC-1 RB-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 EXPOSED�-�PNT-X

114 OFFICE CPT-4 RB-1 PNT-1 PNT-1 PNT-1 PNT-4 ACT-1

115 EMS PC-1 RB-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 EXPOSED�-�PNT-X

116 OFFICE CPT-4 RB-1 PNT-1 PNT-1 PNT-1 PNT-4 ACT-1

117 TOOL�ROOM PC-1 RB-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 EXPOSED�-�PNT-X

118 OFFICE CPT-4 RB-1 PNT-1 PNT-1 PNT-1 PNT-4 ACT-1

119 JC PC-1 RB-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 EXPOSED�-�PNT-X

120 WC PT-1 -- PT-4 PT-4 PT-4 PT-4 PNT-2

121 HOT�ZONE PC-1 RB-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 EXPOSED�-�PNT-X

122 WC PT-1 -- PT-4 PT-4 PT-4 PT-4 PNT-2

123 AIRLOCK PC-1 RB-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 EXPOSED�-�PNT-X

124 IT/AV CPT-4 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 ACT-1

125 TRAINING CPT-4,5,6 RB-1 PNT-1,5�/�ST-1 PNT-1,5�/�ST-1 PNT-1,5�/�ST-1 PNT-1,5�/�ST-1 ACP-1�/�PNT-X

126 IT PC-1 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 ACT-1

127 UTILITY�(WATER) PC-1 RB-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 EXPOSED�-�PNT-X

150 APPARATUS�BAY PC-1 RB-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 EXPOSED�-�PNT-X

160 ELEC PC-1 RB-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 EXPOSED�-�PNT-X

161 DECON PC-1 RB-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 PNT-X

162 BATH�/�SHOWER PC-1 RB-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 PNT-X

163 LAUNDRY PC-1 RB-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 PNT-X

164 PPE PC-1 RB-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 PNT-X

165 SCBA PC-1 RB-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 EP-PNT-1 PNT-X

201 DAYROOM RTF-1,2,3 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 ACP-1�/�PNT-X

202 DINING�ROOM PT-2 PT-3 PNT-1 PNT-1 PNT-1�/�PNT-4 PNT-1 ACP-1�/�PNT-X

203 KITCHEN PT-2 PT-3 CT�/�PNT-1 CT�/�PNT-1 PNT-1�/�PNT-4 PNT-1 ACP-1�/�PNT-X

204 PANTRY RUBBER RB-1 PNT-1 PNT-1 PNT-1 PNT-1 EXPOSED�-�PNT-X

205 STOR CPT-2,3 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 ACT-1

206 BC�OFFICE CPT-2,3 RB-1 PNT-1 PNT-1 PNT-4 PNT-1 ACT-1

207 STOR RTF-1 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 ACT-1

208 WC PT-1 -- PT-4 PT-4 PT-4 PT-4 PNT-2

210 LAUNDRY�/�JC PC-1 RB-1 CT-2�/�PNT-1 CT-2�/�PNT-1 CT-2��/�PNT-1 CT-2��/�PNT-1 ACT-1

211 CORRIDOR RTF-1,2,3 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 EXPOSED�-�PNT-X

212 REPORT�/�UNION RTF-1 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 ACT-1

213 BATHROOM PT-1 -- PT-4 PT-4 PT-4 PT-4 PNT-2

214 BATHROOM PT-1 -- PT-4 PT-4 PT-4 PT-4 PNT-2

215 BATHROOM PT-1 -- PT-4 PT-4 PT-4 PT-4 PNT-2

216 BATHROOM PT-1 -- PT-4 PT-4 PT-4 PT-4 PNT-2

217 BC�DORM CPT-2,3 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 ACT-1

218 DORMITORY CPT-2,3 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 ACP-1�/�PNT-X

219 STOR RTF-1 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 ACT-1

220 STOR RTF-1 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 ACT-1

250 MEZZANINE SC-1 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 EXPOSED�-�PNT-X

251 FITNESS RAF-1 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 PNT-X

252 STOR RAF-1 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 EXPOSED�-�PNT-X

253 COMPRESSOR�/�STOR SC-1 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 EXPOSED�-�PNT-X

100%�SD 04/18/24

95%�DD�-�Owner�Review 06/07/24

100%�DD 06/14/24

Rayes Typewriter Attachment C (1 of 1) Reference Use Only