These construction documents detail a renovation project for Building 104 at the Fort Logan H. Roots VA Healthcare System in North Little Rock, Arkansas. The project involves comprehensive renovation of the first and second floors, including bathroom renovations, floor finish changes, structural support modifications for a copy room, and replacement of the cooling tower supporting Building 104. The building, with a gross area of 10,557 square feet, will primarily be used for law enforcement training, with secondary uses including assembly and business functions. The renovation will reconfigure approximately 4,109 square feet of staff space, 1,495 square feet of circulation areas, 544 square feet of bathrooms, 780 square feet of storage, and 3,630 square feet of utility/mechanical spaces. The project is being managed by the VA's Office of Construction and Facilities Management, with architectural and engineering services provided by JohnsonDanforth & Associates and supporting consultants.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT INFORMATION
RENOVATE BUILDING 104 - LETC
VISN 16: SOUTH CENTRAL VA HEALTH CARE NETWORK
CENTRAL ARKANSAS VETERANS HEALTHCARE SYSTEM
2200 FORT ROOTS DRIVE
NORTH LITTLE ROCK, AR 72114
PROJECT NUMBER: 598-19-127
PROJECT INFORMATION
RENOVATION OF FIRST AND SECOND STORY OF BUILDING 104 ON
THE EJT HEALTHCARE CAMPUS INCLUDING RENOVATION OF
BATHROOMS AND FLOOR FINISH CHANGE AS WELL AS ADDITIONAL
STRUCTURAL SUPPORT OF THE COPY ROOM. CHANGE OF COOLING
TOWER THAT SUPPORTS BUILDING 104 FOR FUTURE MECHANICAL
CHANGES.
BUILDING SUMMARY
GROSS AREA: 10,557 SF
MAIN USE: LAW ENFORCEMENT TRAINING
SECONDARY USES: ASSEMBLY; BUSINESS
AREA BY USE:
STAFF: 4109 SF
CIRCULATION: 1495 SF
BATHROOM: 544 SF
STORAGE: 780 SF
UTIL/MEP: 3630 SF
PROJECT INFORMATION
N
N
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
Drawing Title
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Building Number
Drawing Number
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
VA FORM 08 - 6231
BUSINESS OCCUPANCY
SPRINKLERED
THESE DRAWINGS ARE NOT TO
BE USED AS THE BASIS FOR
THE ISSUANCE OF A PERMIT,
FOR FIELD LAYOUT,
CONSTRUCTION, BIDDING,
RECORDATION, CONVEYANCE,
SALES.
CONSTRUCTION DOCUMENTS
NOT TO SCALE
CAMPUS MAP
NOT TO SCALE
VICINITY MAP
CONSULTANTS
Revs: Date:
9/
/2
4:
:0
PM
C :\U se rs
\e w ui \D oc um en ts
\L O
C
AL
\5
-1 9-
7_
R en ov B ui ld in g
4-
LE
TC
_A R
C H
_e st he r.w ui .rv t
COVER SHEET CONSTRUCTION
DOCUMENTS
RENOVATE BUILDING 104 - LETC
2021.09.30 JDa JDa
GI001
JDA PROJECT #: 2018.001
RENOVATE BUILDING 104 - LETC
PROJECT No: 598-19-127
FORT LOGAN H. ROOTS
NORTH LITTLE ROCK, AR
CONSTRUCTION DOCUMENTS
598-19-127
FORT ROOTS, NORTH LITTLE ROCK
A/E
2200 N. RODNEY PARHAM ROAD
SUITE 210
LITTLE ROCK, AR 72212
501-404-4811 jda@JohnsonDanforth.com
JohnsonDanforth & Associates
SHEET INDEX
NUMBER NAME 35% SD 07.23.2021
65% DD
08.20.2021
95% CD
09.17.2021
CONSTRUCTION
DOCUMENTS 09.30.2021
GENERAL INFORMATION
GI001 COVER SHEET X X X X
GI002 SYMBOLS & NOTES X X X X
GI003 STANDARD ABBREVIATIONS X X X X
GI004 DEPARTMENTAL USE PLAN X X X X
GC101 ICRA PLANS X X X
GC110 ICRA LEGEND X X X
STRUCTURAL
S001 GENERAL NOTES X X X X
SF101 1ST LEVEL FRAMING PLAN & DETAILS X X X X
ARCHITECTURAL
AD101 BASEMENT FLOOR PLAN - EXISTING/DEMO X X X X
AD102 FIRST FLOOR PLAN - EXISTING/DEMO X X X X
AD103 SECOND FLOOR PLAN - EXISTING/DEMO X X X X
AD111 FIRST FLOOR REFLECTED CEILING PLAN - EXISTING / DEMO X X X
AD112 SECOND FLOOR REFLECTED CEILING PLAN - EXISTING/DEMO X X X
AE101 BASEMENT FLOOR PLAN - NEW X X X X
AE102 FIRST FLOOR PLAN - NEW X X X X
AE103 SECOND FLOOR PLAN - NEW X X X X
AE111 REFLECTED CEILING PLAN - FIRST FLOOR PLAN X X X
AE112 REFLECTED CEILING PLAN - SECOND FLOOR PLAN X X X
AE401 FIRST FLOOR ENLARGED PLAN AND INTERIOR ELEVATIONS X X X
AE402 SECOND FLOOR ENLARGED PLAN AND INTERIOR ELEVATIONS X X X
AE501 DETAILS X X X
AE601 DOOR SCHEDULE X
IN101 FINISH PLANS & SCHEDULE X X X
FIRE PROTECTION
FA102 FIRST LEVEL FIRE ALARM PLAN X X X
FA103 SECOND LEVEL FIRE ALARM PLAN X X X
FX102 FIRST LEVEL FIRE SUPPRESSION PLAN X X X
FX103 SECOND LEVEL FIRE SUPPRESSION PLAN X X X
PLUMBING
PD101 FIRST LEVEL PLAN - SANITARY SEWER AND VENT DEMOLITION X X X X
PD102 FIRST LEVEL PLAN - DOMESTIC WATER DEMOLITION X X X X
PD103 SECOND LEVEL PLAN - SANITARY SEWER AND VENT DEMOLITION X X X X
PD104 SECOND LEVEL PLAN - DOMESTIC WATER DEMOLITION X X X X
PL001 PLUMBING GENERAL NOTES AND LEGEND X X X X
PL101 FIRST LEVEL PLAN - SANITARY SEWER AND VENT X X X
PL102 FIRST LEVEL PLAN - DOMESTIC WATER X X X X
PL103 SECOND LEVEL PLAN - SANITARY SEWER AND VENT X X X X
PL104 SECOND LEVEL PLAN - DOMESTIC WATER X X X X
PJ101 PLUMBING RISER DIAGRAMS X X
PK101 PLUMBING SCHEDULES X X
MECHANICAL
MD100 SITE PLAN - MECHANICAL DEMOLITION X X X X
MD101 FIRST LEVEL PLAN - HVAC DUCTWORK DEMOLITION X X X
MD102 SECOND LEVEL PLAN - HVAC DUCTWORK DEMOLITION X X X
MH001 MECHANICAL GENERAL NOTES AND LEGEND X X X
MH100 SITE PLAN - MECHANICAL X X X
MH101 FIRST LEVEL PLAN - HVAC DUCTWORK X X X
MH102 SECOND LEVEL PLAN - HVAC DUCTWORK X X X
MJ101 MECHANICAL DETAILS X X X
MJ102 MECHANICAL CONTROLS X X
MK101 MECHANICAL SCHEDULES X X X
ELECTRICAL
ED101 BASEMENT LEVEL PLAN - POWER AND SYSTEMS DEMOLITION X X
ED102 FIRST LEVEL RCP - LIGHTING DEMOLITION X X X
ED103 FIRST LEVEL PLAN - POWER AND SYSTEMS DEMOLITION X X X
ED104 FIRST LEVEL PLAN - MECHANICAL POWER DEMOLITION X X X
ED105 SECOND LEVEL RCP - LIGHTING DEMOLITION X X X
ED106 SECOND LEVEL PLAN - POWER AND SYSTEMS DEMOLITION X X X
ED107 SECOND LEVEL PLAN - MECHANICAL POWER DEMOLITION X X X
ED108 SITE PLAN - ELECTRICAL DEMOLITION X X X
ES101 SITE PLAN - ELECTRICAL X X
EL101 FIRST LEVEL PLAN - LIGHTING X X X
EL102 SECOND LEVEL PLAN - LIGHTING X X X
EP101 BASEMENT LEVEL PLAN - POWER AND SYSTEMS X X X
EP102 FIRST LEVEL PLAN - POWER AND SYSTEMS X X X
EP103 FIRST LEVEL PLAN - MECHANICAL POWER X X X
EP104 SECOND LEVEL PLAN - POWER AND SYSTEMS X X X
EP105 SECOND LEVEL PLAN - MECHANICAL POWER X X X
EJ101 ELECTRICAL GENERAL NOTES AND LEGEND X X X
EJ102 ELECTRICAL SCHEDULES X
STRUCTURAL ENGINEER
BERNHARD TME
BUILDING 2, 1 ALLIED DRIVE
SUITE 2600
LITTLE ROCK, AR 72202
FIRE PROTECTION
FP&C CONSULTANTS KC, LLC
1330 BURLINGTON STREET, STE. 200
NORTH KANSAS CITY, MO 64116
MEP ENGINEER
INSIGHT ENGINEERING, PLLC
201 S. CHESTER, SUITE B
LITTLE ROCK, AR 72201
SIMPLE PARTITIONS:
A_4A
INDICATES PARTITION TYPE
INDICATES FIRE/SMOKE RATING (0-4 HRS); _ INDICATES 0 HOURS
INDICATES VARIATION CODE(S)
INDICATES NOMINAL CORE SIZE
FIRE RATINGS:
0 NON-RATED
1 1-HR RATING
2 2-HR RATING
3 3-HR RATING
4 4- HR RATING
VARIATION CODES
A NOT USED
B
SMOKE RESISTANT ASSEMBLY; EXTEND ASSEMBLY TO
DECK ABOVE
R
AT
ED
P
AR
TI
TI
O
N S
A B C
MTL STUDS
SINGLE BD,
BOTH SIDES
BOTTOM OF DECK
CEILING LINE
RE: RCP FOR TYPE(S)
CMU
UL U905
(2 HR)
MTL CH-STUDS
DOUBLE BD (1 SIDE)
SHAFT LINEER (1 SIDE)
UL U415-B
(2 HR)
J K L
MTL STUDS
SINGLE BD,
BOTH SIDES
( PARTIAL HT )
D
MTL CH-STUDS
DOUBLE BD (1 SIDE)
SHAFT LINEER (1 SIDE)
UL U415-A
(1 HR)
N O
N -R
AT
ED
P
AR
TI
TI
O N
S
FURRING / STUDS
SINGLE BD,
ONE SIDE ONLY
WITH TILE
NOTES 1 & 4
PARTITION TYPE NOTES
1. WHERE NO FIRE/SMOKE RATING AND NO ACOUSTIC INSULATION INDICATED, TERMINATE STUDS 4” ABOVE HIGHEST ADJACENT CEILING AND BRACE TOP TRACK AT INTERVALS OF 4’-0” OC (MAX) TO STRUCTURE ABOVE OR ADJACENT.
2. SEE FLOOR PLANS AND INTERIOR ELEVATIONS FOR HEIGHT OF PARTIAL HEIGHT PARTITION ABOVE FINISH FLOOR.
3. BRACE PARTIAL HEIGHT ONE-SIDED PARTITIONS TO ADJACENT PARTITIONS. EXCEPTION: WHEN OVERLAYING RATED
WALLS, BRACE NEW STUDS TO STRUCTURE ONLY.
4. OFFSET FURRING / STUD 1" FROM ADJACENT PARALLEL SURFACE / STRUCTURE, UNLESS NOTED OTHERWISE.
BOTTOM OF DECK
CEILING LINE
RE: RCP FOR TYPE(S)
COMPOSITE PARTITIONS:
DOUBLE LETTERS INDICATE COMPOSITE PARTITION MADE UP OF OTHER
PARTITION TYPES. FOR EXAMPLE KK_4A INDICATES A NON-RATED
PARTITION CONSTRUCTED OF TWO (TYPE 'K') SINGLE-SIDED
PARTITIONS WITH ACOUSTICAL INSULATION AND A SINGLE LAYER OF
GWB ON OUTSIDE FACES
CMU
CORE SIZES:
0 7/8" FURRING
1 1-5/8" STUD
2 2-1/2" STUD
4 3-5/8" STUD / CMU
6 5-1/2" STUD / 5-5/8" CMU
8 7-5/8" CMU
E
MTL STUDS
SINGLE BD,
BOTH SIDES
UL U419
(1 HR)
NM
FURRING / STUDS
SINGLE BD,
ONE SIDE ONLY
WITH TILE
(PARTIAL HT)
C
CEMENTICIOUS BACKER BOARD ON WET WALL SIDE OF
PARTITION WITH PORCELAIN FINISH TILE. SEE ELEVATIONSD
MOISTURE RESISTENT GYPSUM BOARD ON RESTROOM
AND/OR JANITOR CLOSET SIDE(S) OF PARTITION
NOTES 2 NOTES 1, 2,
3 & 4
NOTE 1
E
ACOUSTICAL INSULATION: ACOUSTICAL BLANKET INSUL
FULL HT OF PARTITION, PLUS ACOUSTICAL SEALANT
BEADS AROUND FULL PERIMETER OF PARTITION. STC
RATING OF 45 MINIMUM
- N
OT
U
SE
D
- N
OT
U
SE
D
- N
OT
U
SE
D
- N
OT
U
SE
D
F SMOKE REISTANT ASSEMBLY; EXTEND ASSEMBLY TO
DECK ABOVE + MOISTURE RESISTENT GYPSUM BOARD ON
RESTROOM AND/OR JANITOR CLOSET SIDE OF PARTITION
+ ACOUSTICAL BLANKET INSUL FULL HT OF PARTITION,
PLUS ACOUSTICAL SEALANT BEADS AROUND FULL
PERIMETER OF PARTITION. STC RATING OF 45 MINIMUM.
A
1F157B
D2 / AE512
AE501
AE201
AE201
AE211
20' - 6"
FIRST FLOOR
P-01
SCOPE INDICATORS
DRAWING TITLE
DETAIL CALLOUT
DETAIL INDICATOR FOR SMALL CONDITIONS
ELEVATION INDICATOR, EXTERIOR
ELEVATION INDICATOR,
INTERIOR, MULTIPLE
VIEW
BUILDING SECTION INDICATOR
SPACE IDENTIFICATION
OPENING INDICATOR
WINDOW INDICATOR
EQUIPMENT INDICATOR
SHEET NOTES
PARTITION TYPE INDICATOR
NORTH ARROW
INDICATES PROJECT NORTH
INDICATES TRUE NORTH
EXISTING
INDICATES
COLUMN LINE
DESIGNATION
COLUMN LINE INDICATORS
DRAWING REVISION INDICATOR
EXISTING CONSTRUCTION TO
REMAIN
EXISTING CONSTRUCTION TO BE
REMOVED
NEW CONSTRUCTION
VV ITEM - GOVERNMENT FURNISHED /
GOVERNMENT INSTALLED
VC ITEM - GOVERNMENT
FURNISHED / CONTRACTOR
INSTALLED
ELEVATION INDICATOR
WALL FINISH INDICATOR
CC ITEM - CONTRACTOR FURNISHED /
CONTRACTOR INSTALLED
N
1 1/8" = 1'-0" View Name
A_4A
BA3034
CASEWORK TAG
LETTER PAIR INDICATES CASEWORK FAMILY:
RE: AE511-514 FOR DETAILS
FIRST PAIR OF NUMBERS INDICATES UNIT
WIDTH (I.E. 30")
SECOND PAIR INDICATES COUNTERTOP
HEIGHT (I.E. 34")
TOILET ACCESSORY TAG
XXXX
JSN
A
NEW
INDICATES
COLUMN LINE
DESIGNATION
CEILING HEIGHT INDICATOR
Room name 1A105
9' - 0"
WALL
MOUNTED
MIRROR
(A1066)
WALL MOUNTED
GRABBAR
(TOILET SIDE)
(A5109)
WALL MOUNTED
GRABBAR
(TOILET REAR)
(A5109)
TOILET PAPER
DISPENSER
(A5200)
WALL MOUNTED PAPER TOWEL
DISPENSER (WITH OR WITHOUT
INTEGRAL TRASH RECEPTICLE)
(A5080)
FIRE
EXTINGUISHER IN
FULLY RECESSED
CABINET, UNLESS
OTHERWISE
NOTED
WALL MOUNTED
WATER FOUNTAIN
(UNLESS OTHER
WISE NOTED)
MOP BRACKET WALL MOUNTED
LAVATORY
COUNTER
MOUNTED
LAVATORY
WALL MOUNTED
ROBE HOOK PAIR
(A5145)
WALL MOUNTED
SHOWER SEAT
WALL MOUNTED
SOAP DISPENSER
HAND SANITIZER DISPENSER
(A5070/A5071)
SH
O
W
ER
W
AL
L
MIRROR TO
BE
18"x36" U.N.O.
CENTER
MIRROR
OVER
SINK U.N.O.
TO
R
EF
LE
C
TI
N
G
SU
R
FA
C E
PL
U
M
BI
N G
W
AL
L
12" 42"
6" 36"
TO
IL
ET
S
ID
E
W
AL
L
PL
U
M
BI
N G
W
AL
L
7"
IF A DOUBLE ROLL
DISPENSER IS
PROVIDED,
DIMENSION IS TO ROLL
CLOSEST TO TOILET
TO
F
R O
N T
TO
P
ED
G
E O
F D
EC
K
LI
P
W H
EN
LO
W
ER
ED
"48
TO
H
AN
D
LE
3' -0
TO
T
O P
TO
O
PE
R
AT
IO
N
2' -1
0"
2' -9
C
O U
N
TE
R H
EI
G
H T
SI
D
E W
AL
L
1'-3"
SI
D E
W
AL
L 1'-3"
TO
O
PE
R
AT
IO
N
PTD-1 / PTD-2
FEC
MR-1GB-42 GB-36 TPD-1 / TPD-2 HK-1
SS-1 SD-1 / HSD-1 RCK-1 BCS-1
SP
O
U T
H
EI
G H
T
0'
6"
WALL MOUNTED
POSTURE MIRROR
MR-2
SWING UP GRAB
BAR
RE: 12/A515 FOR
SUPPORTS
GB-30SU
SI
D
E W
AL
L
/ T O
IL
ET
C .L
1' - 6"
2'
TOILET
MOUNTING
LOCATION
TO
IL
ET
S
ID
E
W
AL
L
18"
-1
9"
OFFSET DRAIN
INSULATE HW
& DRAIN
OFFSET DRAIN
INSULATE HW
& DRAIN- -
- N
OT
U
SE
D
- N
OT
U
SE
D
- N
OT
U
SE
D
DISPOSAL, SANITARY
NAPKIN, SS, SURFACE
MOUNTED
(A5090)
SND-1
SHELF; FOLD DOWN;
STAINLESS STEEL
(A5162)
SLF-1
CLOCK, ATOMIC,
BATTERY OPERATED
(F3200)
TELEVISION, FLAT
SCREEN
(M0500)
BOARDS, BULLETIN,
48"Wx48"H
(F3010)
" 44
8"
U .N
.O
4' -0
TELEVISION, COLOR,
BEDSIDE, W/ GRAVITY
FREE SUPPORT ARM
(M0505)
TV/DVD COMBINATION
(M0510)
3' -0
5' -6
VA
R
IE
S
- N
OT
U
SE
D
- N
OT
U
SE
D
- N
OT
U
SE
D
- N
OT
U
SE
D
- N
OT
U
SE
D
- N
OT
U
SE
D
- N
OT
U
SE
D
- N
OT
U
SE
D
- N
OT
U
SE
D
- N
OT
U
SE
D
- N
OT
U
SE
D
- N
OT
U
SE
D
- N
OT
U
SE
D
NEW UNRATED PARTITION
NEW / EXISTING 1 HOUR BARRIER
NEW / EXISTING 1 HOUR SMOKE BARRIER
NEW / EXISTING 2 HOUR BARRIER
NEW / EXISTING SMOKE BARRIER
NEW / EXISTING 2 HOUR SMOKE BARRIER
EXISTING PARTITION TO BE REMOVED
EXISTING PARTITION
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
Drawing Title
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Building Number
Drawing Number
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
VA FORM 08 - 6231
CONSTRUCTION DOCUMENTS
CONSULTANTS
Revs: Date:
BUSINESS OCCUPANCY
SPRINKLERED
9/
/2
4:
:0
PM
SYMBOLS & NOTES CONSTRUCTION
DOCUMENTS
RENOVATE BUILDING 104 - LETC
FORT ROOTS, NORTH LITTLE ROCK
2021.09.30 JDa JDa
598-19-127
GI002
JDA PROJECT #: 2018.001
A/E
2200 N. RODNEY PARHAM ROAD
SUITE 210
LITTLE ROCK, AR 72212
501-404-4811 jda@JohnsonDanforth.com
JohnsonDanforth & Associates
1 TESTING AGENCIES FOR THE FIRE ASSEMBLIES IDENTIFIED ON THE PARTITION SCHEDULE ARE:
UL – UNDERWRITERS LABORATORY DESIGN NUMBER
GA – GYPSUM ASSOCIATION DESIGN NUMBER
2 PLAN DIMENSIONS ARE TYPICALLY TO GRID LINE, FACE OF STUD, OR FACE OF CONCRETE OR CMU UNLESS NOTED OR INDICATED OTHERWISE. DOORS NOT LOCATED BY PLAN DIMENSIONS ARE LOCATED BY JAMB DETAILS REFERENCED FROM DOOR SCHEDULE.
CRITICAL CLEARANCES ARE DESIGNATED ‘CLR’.
3 THE PARTITION TYPE NOTED BY A SYMBOL CONTINUES BETWEEN CORNERS AND BETWEEN INTERSECTING PARTITIONS. AT OPENINGS, PROVIDE THE SAME PARTITION TYPE ABOVE AND BELOW SUCH OPENING AS THAT ON EITHER SIDE OF THE OPENING. AT PARTITIONS SCHEDULED TO EXTEND TO STRUCTURE ABOVE, EXTEND THE PARTITION AROUND AND ABOVE DUCTS, BEAMS, AND OTHER OBSTRUCTIONS. ALIGN DIFFERENT PARTITION THICKNESSES SO THAT THE FINISHED WALL PLANES CONTINUE UNBROKEN WITHIN EACH ROOM OR CORRIDOR, UNLESS NOTED OTHERWISE. WHERE FACE OF COLUMN FURRING IS SHOWN AS ALIGNING WITH FACE OF PARTITION, CONTINUE PARTITION FACE UNBROKEN PAST THE COLUMN. STANDARD COLUMN FURRING DETAILS LOCATE PARTITION FACE.
4 WHERE GYPSUM BOARD IS NOT SCHEDULED TO EXTEND TO BOTTOM OF STRUCTURE, BOARD MAY TERMINATE 4” ABOVE ABUTTED CEILING ON EACH SIDE. IF NO CEILING IS SCHEDULED, BOARD IN THAT ROOM MUST EXTEND FULL HEIGHT.
5 WHERE PARTITIONS ARE INDICATED AS BEING FIRE-RATED, CONTINUE PARTITIONS UNBROKEN TO BOTTOM OF DECK ABOVE AND ALONG THE ENTIRE PERIMETER OF THE SPACES BEING SEPARATED BY THE FIRE-RATED PARTITIONS. CONTINUE FIRE-RATED PARTITION
SEPARATIONS WITHOUT INTERRUPTION WHERE THEY INTERSECT NON-RATED PARTITIONS.
6 WHERE COLUMNS, MECHANICAL CHASES, PIPING, AND OTHER ELEMENTS ARE LOCATED WITHIN A FIRE-RATED PARTITION, CONTINUE THE GYPSUM BOARD AROUND BOTH SIDES OF THE OBSTRUCTION TO MAINTAIN THE RATED ASSEMBLY. FOR DUCT, PIPE, CONDUIT, AND OTHER PENETRATIONS PASSING THROUGH A FIRE-RATED PARTITION, PROVIDE TIGHT FITTING FIRE-RATED STOPPING ASSEMBLIES EQUAL TO
ASSEMBLY RATING.
7 WHERE SMOKE AND FIRE-RATED PARTITIONS TERMINATE AT EXTERIOR WALLS, FILL VOIDS WITH FIRE-RATED ASSEMBLIES, OR EXTEND TO RATED PARTITIONS TO THE OUTER FACE OF EXTERIOR WALL CONSTRUCTIONS. ENSURE THAT NO FLANKING PATHWAYS EXIST THAT
MIGHT PERMIT SMOKE OR FIRE TO FLOW FROM ONE SIDE OF THE PARTITION TO THE OTHER.
8 PROVIDE CONTINUOUS STANDARD BLOCKING AS DETAILED FOR WALL MOUNTED ELEMENTS AT TOP AND BOTTOM ATTACHMENT POINTS AND AT INTERMEDIATE ATTACHMENT POINTS AS REQUIRED BY THE ELEMENT, INCLUDING, BUT NOT LIMITED TO; ACCESSORIES, RAILINGS, FLOOR-MOUNTED CASEWORK, CURTAIN RODS, WALL PROTECTION, CORNER GUARDS, AND EQUIPMENT WEIGHING LESS THAN 50 POUNDS.
9 PROVIDE HEAVY DUTY BLOCKING AS DETAILED FOR SUPPORT OF HEAVY ELEMENTS, INCLUDING, BUT NOT LIMITED TO; WALL MOUNTED SHELVING AND CABINETRY, HAND RAILS, GRAB BARS, BABY-CHANGING TABLES, LAVATORIES, COUNTER TOPS, MOUNTS FOR TELEVISIONS AND COMPUTER MONITORS, DOOR STOPS, AND EQUIPMENT WEIGHING IN EXCESS OF 50 POUNDS.
10 WHERE ACOUSTICAL INSULATION IS INDICATED FOR PARTITIONS, SEAL TOP, BOTTOM AND SIDES OF EACH FACE AND EDGE OF GYPSUM
BOARD WITH ACOUSTICAL SEALANT WHERE THE BOARD CONTACTS OTHER MATERIALS.
11 BACK-TO-BACK ELECTRICAL BOXES ARE NOT PERMITTED UNLESS BOTH BOXES ARE WRAPPED WITH ADHESIVE WRAPPED INTUMESCENT PUTTY PADS. WHERE JUNCTION, OUTLET, AND SWITCH BOXES OCCUR ON OPPOSITE SIDES OF A PARTITION, EITHER PROVIDE PUTTY PADS FOR BOTH BOXES, OR OFFSET THE BOXES A MINIMUM OF ONE STUD SPACE AND PROVIDE ACOUSTICAL INSULATION BEHIND AND
BETWEEN THEM.
12 IN FIRE-RATED PARTITIONS WITH TOTAL “BLACK BOX” PENETRATIONS IN EXCESS OF 100 SQ. IN. IN 100 SQ. FT., ADDITIONALLY PROTECT BACK OF BOXES WITH RATED ASSEMBLIES APPROVED BY THE AUTHORITY HAVING JURISDICTION.
13 PROVIDE ACOUSTICAL SEALANT AROUND ALL PENETRATIONS THROUGH THE MEMBRANES OF ACOUSTICAL PARTITIONS. PROVIDE FIRE-RATED SEALANT IN LIEU OF ACOUSTICAL SEALANT WHERE REQUIRED TO MAINTAIN FIRE RATING OF ACOUSTIC PARTITIONS.
14 IN SHOWER STALLS AND WALLS BEHIND PLUMBING FIXTURES, PROVIDE TILE BACKER BOARD IN LIEU OF GYPSUM BOARD AT WALLS INDICATED TO RECEIVE CERAMIC TILE. BACKER BOARD TO MATCH GYPSUM BOARD IN TERMS OF THICKNESS AND FIRE-RATING CAPABILITY.
PROVIDE MOISTURE RESISTANT (MR) GYPSUM BOARD IN LIEU OF STANDARD GYPSUM BOARD AT THE FOLLOWING LOCATIONS:
DIRECTLY BEHIND PLUMBING FIXTURES WHERE FINISH IS NOT CERAMIC TILE, AND CEILINGS ABOVE SHOWER STALLS.
15 AT NON-FIRE RATED, NON-ACOUSTIC PARTITIONS THAT DO NOT EXTEND TO STRUCTURE ABOVE, CONTRACTOR HAS OPTION OF EXTENDING STUDS TO STRUCTURE ABOVE OR TERMINATING STUDS 4” ABOVE HIGHEST ADJACENT CEILING AND BRACING TOP TRACK AT
INTERVALS OF 4’-0” OC (MAX) TO STRUCTURE ABOVE.
16 WHERE STUDS EXTEND MORE THAN 3’-0” ABOVE THE GYPSUM BOARD, PROVIDE HORIZONTAL BRACING MIDWAY BETWEEN TOP OF
GYPSUM BOARD AND TOP OF STUDS.
17 AT FURRING PARTITIONS (GYPSUM BOARD ONE SIDE ONLY) PROVIDE HORIZONTAL STUD BRACING OR 18 GA ANGLE CLIPS SECURED TO
STRUCTURAL SUBSTRATE AT 4’-0” OC (MAX). SIMILAR REQUIREMENT AT COLUMN FURRING.
18 MAGNITUDE OF POTENTIAL STRUCTURAL LIVE LOAD DEFLECTION IMPACTING PARTITIONS FOR THIS PROJECT IS 1/2” IN COMPRESSION AND 0” IN EXTENSION, FOR A TOTAL MOVEMENT OF 1/2”. FOR RATED PARTITIONS, THE HEAD-OF-WALL FIRE RESISTIVE ASSEMBLY PROVIDED MUST BE RATED FOR THIS DEGREE OF MOVEMENT. PROVIDE A FIRE-RESISTIVE VARIATION FOR EACH CONDITION (BEAMS, DUCTS, CORNERS, ETC.) ENCOUNTERED AT THE RATED PARTITION HEADS. FOR NON RATED PARTITIONS, SECURE THE TOP TRACK IN A
MANNER THAT ACCOMMODATES DEFLECTION OF THE STRUCTURE ABOVE OR BELOW.
19 FOR DOORS, RELITES, DUCT, AND OTHER OPENINGS WITH ROUGH OPENING DIMENSIONS OF 4’-0” OR WIDER, PROVIDE HEAVY GAUGE KING
STUDS AND A “BOX BEAM” HEADER AS DETAILED IN STANDARD OPENING HEADER DETAILS.
20 PARTITION TYPE IS TO BE B_4a UNO.
TYPICAL PARTITION NOTESPARTITION TYPES CONSTRUCT PER LISTED UL DESIGN NO. OR EQUIVALENT UL DESIGN
EQUIPMENT MOUNTING LEGEND PARTITION PLAN LEGEND
DRAFTING SYMBOLS
STRUCTURAL ENGINEER
BERNHARD TME
BUILDING 2, 1 ALLIED DRIVE
SUITE 2600
LITTLE ROCK, AR 72202
MEP ENGINEER
INSIGHT ENGINEERING, PLLC
201 S. CHESTER, SUITE B
LITTLE ROCK, AR 72201
FIRE PROTECTION
FP&C CONSULTANTS KC, LLC
1330 BURLINGTON STREET, STE. 200
NORTH KANSAS CITY, MO 64116
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
Drawing Title
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Building Number
Drawing Number
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
VA FORM 08 - 6231
CONSTRUCTION DOCUMENTS
CONSULTANTS
Revs: Date:
BUSINESS OCCUPANCY
SPRINKLERED
9/
/2
4:
:1
PM
C :\U se rs
\e w ui \D oc um en ts
\L O
C
AL
\5
-1 9-
7_
R en ov B ui ld in g
4-
LE
TC
_A R
C H
_e st he r.w ui .rv t
STANDARD ABBREVIATIONS CONSTRUCTION
DOCUMENTS
RENOVATE BUILDING 104 - LETC
FORT ROOTS, NORTH LITTLE ROCK
2021.09.30 JDa JDa
598-19-127
GI003
JDA PROJECT #: 2018.001
A/E
2200 N. RODNEY PARHAM ROAD
SUITE 210
LITTLE ROCK, AR 72212
501-404-4811 jda@JohnsonDanforth.com
JohnsonDanforth & Associates
SJI STEEL JOIST SLIDING WINDOW
SK SKETCH
SKLT SKYLIGHT
SLD WDW HORIZONTAL SLIDING WINDOW
SLDG SLIDING
SLNT SEALANT
SM SHEET METAL
SMK SMOKE
SMS SHEET METAL SCREW
SND SANITARY NAPKIN DISPENSER
SND INS SOUND INSULATION
SNDU SANITARY NAPKIN DISPOSAL
UNIT
SPEC SPECIFICATION
SPKLR SPRINKLER
SPKR SPEAKER
SPLY SUPPLY
SQ SQUARE
SQ IN SQUARE INCH
SQ YD SQUARE YARD
SS SANITARY SEWER OR SERVICE
SINK
SST STAINLESS STEEL
ST STAIRS OR STREET
STC SOUND TRANSMISSION
CLASSIFICATION
STIF STIFFENER
STL STEEL
STL JST STEEL JOIST
STL LNTL STEEL LINTEL
STL PL STEEL PLATE
STL RF DK STEEL ROOF DECK
STL TB STEEL TUB
STL TR STEEL TRUSS
STNLS STAINLESS
STOR STORAGE
STR STRINGERS
STRUCT STRUCTURAL
STRUCT
STL
STRUCTURAL STEEL
SUB SUBSTITUTE
SURF SURFACE
SUSP SUSPENDED
SUSP CLG SUSPENDED CEILING
SV SHEET VINYL
SW SWITCH
SWDR SWING DOOR
SYM SYMBOL
SYNTH SNTHETIC
SYS SYSTEM
T
T TREAD
T&G TONGUE AND GROOVE
T&M TIME AND MATERIALS
TB THROUGH BOLT OR TOWEL BAR
TCA TILE COUNCIL OF AMERICA
TCP TELEPHONE CONTROL PANEL,
TEMPERATURE CONTROL PANEL,
OR TRAFFIC CONTROL PLAN
TD TOWEL DISPENSER
TECH TECHNICAL
TEL TELEPHONE
TEMP TEMPERATURE OR TEMPORARY
TER TERRAZZO
THD THREAD
THERM THERMAL
THK THICKNESS
THRES THRESHOLD
THRU THROUGH
THRUOUT THROUGHOUT
TK BD TACKBOARD
TLT TOILET
TMPD TEMPERED
TMPD GL TEMPERED GLASS
TN TRUE NORTH
TO TOP OF ______
TO FDN TOP OF FOUNDATION
TOB TOP OF BEAM
TOM TOP OF MASONRY
TOP TOP OF PARAPET
TOS TOP OF STEEL
TYP TYPICAL
U
U.N.O. UNLESS NOTED OTHERWISE
U.O.N. UNLESS OTHERWISE NOTED
V
VC VA FURNISHED / CONTRACTOR
INSTALLED
VCT VINYL COMPOSITION TILE OR
VITRIFIED CLAY TILE
VENT VENTILATION
VERT VERTICAL
VIF VERIFY IN FIELD
VV VA FURNISHED / VA INSTALLED
W
W/ WITH
WD WOOD
WP WALL PROTECTION
QTR QUARTER
QTY QUANTITY
QUAD QUADRANT
QUAL QUALITY
R
R RADIUS OR RISER
RA RETURN AIR
RA RETURN AIR
RAD RADIATOR
RB RESILIENT BASE OR RUBBER
BASE
RB HK ROBE HOOK
RBM REINFORCED BRICK MASONRY
RBR RUBBER
RC REMOTE CONTROL
RCP REFLECTED CEILING PLAN
RCVR RECEIVER
RD ROAD OR ROOF DRAIN
REC RECESSED
RECD RECEIVED
RECPT RECEPTACLE
RECT RECTANGLE
REF REFERENCE OR REFRIGERATOR
REFR REFRACTORY REFRIGERATION
OR REFRIGERATION
REFRACTORY
REG REGISTER
REINF REINFORCE, REINFORCED, OR
REINFORCING
REP REPAIR
REPL REPLACE
REQ REQUIRE
REQD REQUIRED
RESIL RESILIENT
RET RETURN
REV REVISION
RF RADIO FREQUENCY
RFG ROOFING
RFI REQUEST FOR INFORMATION
RFP REQUEST FOR PROPOSAL
RH RIGHT HAND
RHMS ROUND HEAD MACHINE SCREW
RHR RIGHT HAND REVERSE
RHWS ROUND HEAD WOOD SCREW
RL ROOF LEADER
RLG RAILING
RM ROOM
RND ROUND
RO ROUGH OPENING
ROW RIGHT OF WAY
RPM REVOLUTIONS PER MINUTE
RS ROUGH SAWN
RT RIGHT
RV ROOF VENT
RVS REVERSE
RWD REDWOOD
RWL RAIN WATER LEADER
S
SA SUPPLY AIR
SALV SALVAGE
SAMP SAMPLE
SAN SANITARY
SAT SUSPENDED ACOUSTICAL TILE
SATC SUSPENDED ACOUSTICAL TILE
CEILING
SB SPLASH BLOCK
SBS STYRENE BUTADIEN STYRENE
SBSTR SUBSTRATE
SC SHADING COEFFICIENT OR SOLID
CORE
SCH SCHOOL
SCHED SCHEDULE, SCHEDULED
SCHEM SCHEMATIC
SCP SCUPPER
SCRN SCREEN
SCT STRUCTURAL CLAY TILE
SCWD SOLID CORE WOOD DOOR
SD SHOP DRAWINGS, SMOKE
DETECTOR, OR SOAP DISPENSER
SDG SIDING
SECT SECTION
SEG SEGMENT
SEL SELECT
SEP SEPARATE
SF SQUARE FOOT (FEET)
SFTWD SOFTWOOD
SGD SLIDING GLASS DOOR
SGL SINGLE
SHR SHOWER
SHR HD SHOWER HEAD
SHRD SHOWER DRAIN
SHT SHEET
SHT MTL
FLASH
SHEET METAL (FLASHING)
SHTHG SHEATHING
SIM SIMILAR
SJ SCORED JOINT
SJ SCORED JOINT
NS NARROW STILE
NUM NUMERAL
O
O OXYGEN
O/H OVER HEAD
O/O OUT TO OUT
OA OUTSIDE AIR OR OVERALL
OC ON CENTER
OCC OCCUPY
OCT OCTAGON
OD OUTSIDE DIAMETER OR OUTSIDE
DIMENSION
OFD OVERFLOW DRAIN
OFF OFFICE
OH OVERHANG
OH DR OVERHEAD (COILING) DOOR
OPH OPPOSIE HAND
OPNG OPENING
OPP OPPOSITE
OPR OPERABLE
OPT OPTIONAL
OR OPERATING ROOM OR OUTSIDE
RADIUS
ORD ORDNANCE OR OVERFLOW ROOF
DRAIN
ORG ORGANIC
ORIG ORIGINAL
ORN ORNAMENTAL
OSHA OCCUPATIONAL SAFETY AND
HEALTH ADMINISTRATION
OUT OUTLET
OZ OUNCE
P
PAR PARALLEL OR PARAPET
PARA PARAGRAPH
PART PARTIAL
PAT PATTERN
PB PUSHBUTTON
PBD PARTICLEBOARD
PC PIECE, POLYCARBONATE OR
PORTLAND CEMENT
PCA PORTLAND CEMENT
ASSOCIATION
PCC PRECAST CONCRETE
PCCP CONCRETE PAVEMENT
PCD PAPER CUP DISPENSER
PCF POUNDS PER CUBIC FOOT
PCP PORTLAND CEMENT PLASTER
PED PEDESTAL
PEN PENETRATE
PEND PENDANT
PERF PERFORATED
PERIM PERIMETER
PERP PERPENDICULAR
PGBD PEGBOARD
PHAR PHARMACY
PHOTO PHOTOGRAPH
PHS PHILLIPS HEAD SCREW
PKG PACKAGE
PL PROPERTYLINE
PL GL PLATE GLASS
PLAM PLASTIC LAMINATE
PLAS PLASTER OR PLASTIC
PLBG PLUMBING
PLYWD PLYWOOD
PMTL PAINTED METAL
PNEU PNEUMATIC
PNL PANEL
PO POST OFFICE PURCHASE ORDER
OR PURCHASE ORDER POST
OFFICE
POLY POLYETHYLENE (PLASTIC)
PR PAIR
PRCST PRECAST
PREFAB PREFABRICATE
PREFIN PREFINISH
PRELIM PRELIMINARY
PREP PREPARATION
PRESS PRESSURE
PREV PREVIOUS
PRKG PARKING
PRMLD PREMOLDED
PROJ PROJECT
PROP PROPERTY
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PAINT, PNEUMAIC TUBE, OR
PRESSURE TREATED
PTD PAPER TOWEL DISPENSER
PTN PARTITION
PVC POLYVINYL CHLORIDE (PLASTIC)
PVG PAVING
PWR POWER
Q
QA QUALITY ASSURANCE
QC QUALITY CONTROL
QRY QUARRY
QT QUARRY TILE OR QUART
QTB QUARRY TILE BASE
QTF QUARRY TILE FLOOR
LMST LIMESTONE
LNDSCP LANDSCAPE
LR LIVING ROOM
LRG LARGE
LRV LOUVERED ROOF VENT
LS LUMP SUM
LT LIGHT
LT GA LIGHT GAGE
LT WT LIGHTWEIGHT
LTG LIGHTING
LTNG LIGHTNING
LVD LOUVERED
LVR LOUVER
LWC LIGHTWEIGHT CONCRETE
LWIC LIGHTWEIGHT INSULATING
CONCRETE
LYR LAYER
M
MACH MACHINE
MACH RM MACHINE ROOM
MAINT MAINTAIN, MAINTENANCE
MAN MANUAL
MATL MATERIAL
MATV MASTER ANTENNA TELEVISION
SYSTEM
MAX MAXIMUM
MB MACHINE BOLT
MCB METAL CORNER BEAD
MD DECK
ME MECHANICAL ENGINEER
MEAS MEASURE
MECH MECHANICAL
MECH RM MECHANICAL ROOM
MED MEDICAL MEDIUM O MEDIUM
MEDICAL
MEK METHYL ETHYL KETONE
MEL MELAMINE
MEMBO MEMORANDUM
MEZZ MEZZANINE
MF MILL FINISH
MFD MANUFACTURED
MFG MANUFACTURING
MFR MANUFACTURER
MFR REC MANUFACTURER'S
RECOMMENDATION
MGT MANAGEMENT
MH MANHOLE
MIC MICROPHONE
MID MIDDLE
MIL STD MILITARY STANDARD
MIN MINIMUM
MIN MINIMUM MINUTE OR MINUTE
MINIMUM
MIRR MIRROR
MISC MISCELLANEOUS
MISC MISCELLANEOUS
MIT MITER
MKR MARKER
ML METAL LATH
MLDG MOLDING (MOULDING)
MLWK MILLWORK
mm MILLIMETER
MO MASONRY OPENING OR MOTOR
OPERATED
MOD MODEL, MODIFY OR MODULE
MOD BIT MODIFIED BITUMEN
MON MONITOR
MOPR MOP RACK
MR MOISTURE RESISTANT
MS MACHINE SCREW OR MOP SINK
MTD MOUNTED
MTG MOUNTING
MTL METAL
MULL MULLION
MW MICROWAVE
MWP MEMBRANE WATERPROOFING
N
N NORTH
NA NOT APPLICABLE
NAAMM NATIONAL ASSOCIATION OF
ARCHITECTURAL METAL
MANUFACTURERS
NAT NATURAL
NATL NATIONAL
NC NOISE CRITERIA
NCOMBL NONCOMBUSTIBLE
NEC NATIONAL ELECTRICAL CODE
NEG NEGATIVE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NEUT NEUTRAL
NFC NATIONAL FIRE CODE
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NR NOISE REDUCTION
NRC NOICE REDUCTION COEFFICIENT
NRCA NATIONAL ROOFING
CONTRACTORS ASSOCIATION
NRP NONREMOVABLE
H HIGH
H PLAM HIGH PRESSURE PLASTIC
LAMINATE
HAZ MAT HAZARDOUS MATERIALS
HB HOSE BIBB
HC HOLLOW CORE
HCWD HOLLOW CORE WOOD DOOR
HDBD HARDBOARD
HDNR HARDENER
HDO HIGH DENSITY OVERLAY
HDR HEADER
HDW HARDWARE
HDWD HARDWOOD
HEPA HIGH EFFICIENCY PARTICULATE
AIR (FILTER)
HEX HEXAGON
HF HIGH FREQUENCY
HGR HANGAR
HM HOLLOW METAL OR
HECTOMETER
HMD HOLLOW METAL DOOR
HMDF HOLLOW METAL DOOR AND
FRAME
HMF HOLLOW METAL FRAME
HNDRL HANDRAIL
HO HOLD OPEN
HORIZ HORIZONTAL
HOSP HOSPITAL
HP HIGH PRESSURE OR
HORSEPOWER
HQ HEADQUARTERS
HR HOUR
HRS HOURS
HS HEAT-STRENGTHENED (GLASS)
OR HIGH STRENGTH
HSE HOUSE
HSKPG HOUSEKEEPING
HST HOIST
HT HEIGHT
HVAC HEATING, VENTILATION, AND AIR
CONDITIONING
HVY HEAVY
HW HOT WATER
HYD HYDRANT
HYDR HYDRAULIC
I
I INTERSTATE (HIGHWAY) OR
MOMENT OF INERTIA
IAQ INDOOR AIR QUALITY
IBC INTERNATIONAL BUILDING CODE
ID IDENTIFICATION, INSIDE
DIAMETER, OR INTERIOR DESIGN
ID NO IDENTIFICATION NUMBER
ILLUM ILLUMINATION
INCL INCLUDED
IND INDEPENDENT OR INDUSTRIAL
INFO INFORMATION
INSUL INSULATED, INSULATION
INT INTERIOR
INTERCOM INTERCOMMUNICATION
INTL INTERNATIONAL
IRMA INVERTED ROOF MEMBRANE
ASSEMBLY
IWH INSTANANEOUS WATER HEATER
J
J-BOX JUNCTION BOX
JAN JANITOR
K
KD KILN DRIED OR KNOCKED DOWN
KIT KITCHEN
KO KNOCKOUT
KPL KICKPLATE
L
L ANGLE
LAB LABORATORY
LAD LADDER
LAM LAMINATE
LAM GL LAMINATED GLASS
LAU LAUNDRY
LAV LAVATORY
LBR LUMBER
LBS POUND
LD BRG LOAD-BEARING
LDR LEADER
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LH LEFT HAND
LHR LEFT HAND REVERSE OR LATENT
HEAT RATIO
LIB LIBRARY
LIN LINEAR
LINO LINOLEUM
LIQ LIQUID
LKR LOCKER
LKR RM LOCKER ROOM
LKWASH LOCKWASHER
LL LEAD LINED
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
FAC FACTOR
FACIL FACILITY
FAS FASCIA
FAS BD FASCIA BOARD
FCO FLOOR CLEANOUT
FCTY FACTORY
FD FLOOR DRAIN
FDC FIRE DEPARTMENT CONNECTION
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FACE
FF EL FINISH FLOOR ELEVATION
FF&E FURNITURE, FIXTURE, AND
EQUIPMENT
FH FLAT HEAD OR FLAT HEAD
SCREWS
FHC FIRE HOSE CABINET
FHMS FLAT HEAD MACHINE SCREW
FHP FULL HEIGHT PARTITION
FHWS FLAT HEAD WOOD SCREW
FIG FIGURE
FIL FILLET
FIN FINISH
FIN FLR FINISH FLOOR
FIN GR FINISH GRADE
FIN WD FINISH WOOD
FIXT FIXTURE
FL FLOORLINE
FLASH FLASHING
FLDG FOLDING
FLEX FLEXIBLE
FLG FLOORING
FLR FLOOR
FLR FIN FLOOR FINISH
FLR SK FLOOR SINK
FLUOR FLUORESCENT
FLUOR FIX FLUORESCEN FIXTURE
FM FACTORY MUTUAL
FM-G FACTORY MUTUAL GLOBAL
FO FINISHED OPENING
FOC FACE OF CONCRETE OR FACE OF
CURB
FOF FACE OF FINISH
FOM FACE OF MASONRY
FOS FACE OF SLAB OR FACE OF CURB
FOUNT FOUNTAIN
FOW FACE OF WALL
FP FIRE PROTECTION OR
FIREPROOF OR FLAT PANEL
DOOR
FPM FEET PER MINUTE
FPS FEET PER SECOND
FR FIRE RATING, FIRE RESISTANT,
OR FRAME
FR SNK FLUSHING RIM SINK
FREQ FREQUENCY
FRMG FRAMING
FRP FIBER REINFORCED POLYESTER
OR FIBERGLASS REINFORCED
PLASTIC
FRZ FREEZER
FS FEDERAL SPECIFICATION
FSTNR FASTENER
FT FEET OR FOOT
FTG FOOTING
FURG FURRING
FURN FURNISH OR FURNITURE
FUT FUT
FWC FABRIC WALL COVERING
G
GA GAGE OR GYPSUM ASSOCIATION
GAL GALLON, GALLONS
GALV GALVANIC OR GALVANIZED
GALV STL GALVANIZED STEEL
GB GRAB BAR
GC GENERAL CONTRACTOR
GD GUARD
GDR GUARD RAIL
GEN GENERAL OR GENERATOR
GFRC GLASS-FIBER-REINFORCED
GFRG GLASS-FIBER-REINFORCED
GFRP GLASS-FIBER-REINFORCED
PLASTIC
GI GALVANIZED IRON
GL GLASS
GL BLK GLASS BLOCK
GLU LAM GLUED LAMINATED WOOD
GR FL GROUND FLOOR
GRAN GRANITE
GRTG GRATING
GSB GYPSUM SHEATHING BOARD
GSM GALVANIZED SHEET METAL
GSU GLAZED STRUCTURAL UNIT
GT GROUT
GUAR GUARANTEE
GUT GUTTER
GYP GYPSUM
GYP BD GYPSUM BOARD
GYP PLAS GYPSUM PLASTER
H
CTR CENTER CONTOUR
CTRL CONTROL
CTV CABLE TELEVISION
CU COPPER C
CU FT CUBIC FEET
CU IN CUBIC INCH
CU YD CUBIC YARD
CURT CURTAIN
CYL CYLINDER
CYL L CTLINDER LOCK
D
D DEPTH OR PENNY (NAIL)
D LABEL CLASS D DOOR
DAT DATUM
DB DECIBEL
DBL DOUBLE
DBL GLZ DOUBLE GLAZE
DC DIRECT CURRENT
DEG DEGREE
DEL DELETE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL DIAGRAM OR
DIAGRAM DIAGONAL
DIFF DIFFERENCE OR DIFFUSER
DIM DIMENSION
DIR DIRECTION
DISP DISPENSER
DIST DISTANCE
DIV DIVIDE OR DIVISION
DL DEAD LOAD
DOC DOCUMENT
DOUG FIR DOUGLAS FIR
DOZ DOZEN
DR DOOR, DRAIN, DRESSING ROOM,
OR DRIVE
DR CL DOOR CLOSER
DR FR DOOR FRAME
DR OPNG DOOR OPENING
DS DOWNSPOUT
DSGN DESIGN
DW DISHWASHER
DWG DRAWING
DWTR DUMBWAITER
E
E EAST
E LABEL CLASS E DOOR
EA EACH
EFF EFFICIENCY
EFS EXTERIOR FINISH SYSTEM
EIFS EXTERIOR INSULATION AND
FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELAST ELASTOMERIC
ELEC ELECTRIC, ELECTRICAL
ELEC DR
OP
ELECTRIC DOOR OPENER
ELEV ELEVATOR
ELEVS ELEVATIONS
EMER EMERGENCY
EMER SHR EMERGENCY SHOWER
ENCL ENCLOSURE
ENGR ENGINEER
ENVIR ENVIRONMENT
EPA ENVIRONMENTAL PROTECTION
AGENCY
EPDM ETHYLENE PROPYLENE DIENE
EPO EMERGENCY POWER OFF
EPS EXPANDED POLYSTYRENE
BOARD (INSULATION)
EQ EQUAL
EQL SP EQUALLY SPACED
EQUIP EQUIPMENT
EQUIV EQUIVALENT
ERD EXISTING ROOF DRAIN
ESC ESCAPE OR ESCUTCHEON
ESCAL ESCALATOR
ESMT EASEMENT
ESP ESPECIALLY
EST ESTIMATE
ETC AND SO FORTH OR ET CETERA
EW EACH WAY
EWC ELECTRIC WATER COOLER
EWS EYE WASH STATION
EXH EXHAUST
EXIST EXISTING
EXP EXPANSION OR EXPOSED
EXP BT EXPANSION BOLT
EXST GR EXISTING GRADE
EXT EXTERIOR, EXTERNAL, OR
EXTINGUISHER
EXT GR EXTERIOR GRADE
F
F FAHRENHEIT OR FEMALE
FA FIRE ALARM
FAB FABRIC
BOT BOTTOM
BR BEDROOM
BRCG BRACING
BRDG BRIDGING
BRDG JST BRIDGING JOIST
BRG BEARING
BRG PL BEARING PLATE
BRKT BRACKET
BRZ BRONZE
BSMT BASEMENT
BTWN BETWEEN
BU BUSHEL
BUR BUILT-UP ROOFING
C
C CELSIUS CHANNEL OR CHANNEL
CELSIUS
C CONC CAST CONCRETE
C LABEL CLASS C DOOR
C TO C CENTER TO CENTER
C/C CONTRACTOR FURNISHED/
CONTRACTOR INSTALLED
C/VA CONTRACTOR FURNISHED/
GOVERNMENT INSTALLED
CAB CABINET
CAC CEILING ATENUATION CLASS
CB CATCH BASIN OR CORNER BEAD
CBB CEMENTITIOUS (BACKER) BOARD
CC CUBIC CENTIMETER
CCTV CLOSED CIRCUIT TELEVISION
CCW COUNTERCLOCKWISE
CD CONSTRUCTION DOCUMENTS OR
CONTRACT DOCUMENTS
CEM CEMENT, CEMENTITIOUS
CEM PLAS CEMENT PLASTER
CER CERAMIC
CF CONTRACTOR FURNISHED
CFLG COUNTERFLASHING
CFM CUBIC FEET PER MINUTE
CFMF COLD-FORMED METAL FRAMING
CFS CUBIC FEET PER SECOND
CG CENTER OF GRAVITY OR
CORNER GUARD
CGSFU CERAMIC GLAZED STRUCTURAL
FACING UNITS
CH BD CHALKBOARD
CHEM CHEMICAL
CHFR CHAMFER
CHK CHECK
CI CAST IRON
CIP CAST-IN-PLACE
CIR CIRCLE
CIRC CIRCULATING, CIRCULAR
CIRC CIRCULAR
CJ CONSTRUCTION JOINT OR
CONTROL JOINT
CL CENTER LIINE
CLDG CLADDING
CLG CEILING
CLG HT CEILING HEIGHT
CLR CLEAR
CM CONSTRUCTION MANAGEMENT
cm2 SQUARE CENTIMETER cm3 CUBIC CENTIMETER
CMU CONCRETE MASONRY UNIT
CNR CORNER
CNTR COUNTER
CO CARBON MONOXIDE,
CERTIFICATE OF OCCUPANCY,
CLEAN OUT, OR COMPANY
co2 CARBON DIOXIDE
COL COLUMN
COM COMMON
COMB COMBINAION, COMBINED
COMM COMMUNICATION
COMP COMPONENT
CONC CONCRETE
CONC FLR CONCRETE FLOOR
COND CONDENSER OR CONDITION
CONF CONFERENCE
CONN CONNECTION
CONSTR CONSTRUCTION
CONT CONTINUOUS, CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
COR COORDINATION OFFICER
CORR CORRIDOR
CPM CRITICAL PATH METHOD
CPRS COMPRESSIBLE
CPT CARPET
CRS COLD ROLLED STEEL
CRSI CONCRETE REINFORCING STEEL
CSB CONCRETE SPLASH BLOCK
CSG CASING
CSI CONSTRUCTION SPECIFICATIONS
INSTITUTE
CSK COUNTER SUNK
CSMT CASEMENT
CSWK CASEWORK
CT CERAMIC TILE
CTB CERAMIC TILE BASE
CTF CERAMIC TILE FLOOR
CTG COATING
A
A LABEL CLASS A DOOR
A/C AIR CONDITIONING
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AAMA AMERICAN ARCHITECTURAL
MANUFACTURERS ASSOCIATION
AB ANCHOR BOLT
ABA ARCHITECTURAL BARRIERS ACT
ABC AGGREGATE BASE COURSE
AC ASBESTOS CEMENT OR
ASPHALTIC CONCRETE
ACI AMERICAN CONCRETE INSTITUTE
ACS DR ACCESS DOOR
ACS FLR ACCESS FLOOR
ACS PNL ACCESS PANEL
ACST ACOUSTIC
ACT ACOUSTICAL CEILING TILE
AD AREA DRAIN
ADA AMERICANS WITH DISABILITIES
ACT
ADB AUTOMATIC DOOR BOTTOM
ADC AUTOMATIC DOOR CLOSER
ADDL ADDITIONAL
ADDN ADDITION
ADH ADHESIVE
ADJ ADJACENT, ADJOINING, OR
ADJUSTABLE
ADMIN ADMINISTRATION
AFC ABOVE FINISHED COUNTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFS ABOVE FINISHED SLAB
AGA AMERICAN GAS ASSOCIATION,
ASSOCIATED GENERAL
CONTRACTORS
AGGR AGGREGATE
AHJ AUTHORITY HAVING JURISDICION
AHR ANCHOR
AHU AIR HANDLING UNIT
AIA AMERICAN INSTITUTE OF
ARCHITECTS
AISC AMERICAN INSTITUTE OF STEEL
CONSTRUCTION
ALT ALTERNATE, ALTERNATIVE
ALT NO ALTERNATE NUMBER
ALUM ALUMINUM
AMP AMPERE
AMT AMOUNT
ANOD ANODIZE
ANSI AMERICAN NATIONAL
STANDARDS INSTITUTE
ANT ANTENNA
APA AMERICAN PLAYWOOD
ASSOCIATION
APPD APPROVED
APPROX APPROXIMATE, APPROXIMATELY
APT APARTMENT
AR AS REQUIRED
ARCH ARCHITECT, ARCHITECTURAL
ASB ASBESTOS
ASI ARCHITECT'S SUPPLEMENTAL
INSTRUCTION
ASKLR AUOMATIC SPRINKLER
ASPH ASPHALT
ASSN ASSOCIATION
ASTM AMERICAN SOCIETY FOR
TESTING AND MATERIALS
ATCH ATTACHMENT
ATM AUTOMATIC TELLER MACHINE
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO-VISUAL
AVE AVENUE
AVG AVERAGE
AW ACID WASTE
AWI ARCHITECTURAL
WOODWORKING INSTITUTE
AWPA AMERICAN WOOD PRESERVERS'S
ASSOCIATION
AWS AMERICAN WELDING SOCIETY
AWT ACOUSTICAL WALL TREATMENT
B
B LABEL CLASS B DOOR
B PL BASE PLATE
BALC BALCONY
BAT BATTEN
BB BULLETIN BOARD
BD BOARD
BD FT BOARD FEET (FOOT)
BEV BEVEL
BHMA BUILDER'S HARDWARE
MANUFACTURER'S ASSOCIATION
BI FLD DR BIFOLDING DOORS
BITUM BITUMINOUS
BKG BACKING
BLD BUILD
BLDG BUILDING
BLKG BLOCKING
BLKT BLANKET
BLVD BOULEVARD
BM BEAM OR BENCHMARK
STRUCTURAL ENGINEER
BERNHARD TME
BUILDING 2, 1 ALLIED DRIVE
SUITE 2600
LITTLE ROCK, AR 72202
MEP ENGINEER
INSIGHT ENGINEERING, PLLC
201 S. CHESTER, SUITE B
LITTLE ROCK, AR 72201
FIRE PROTECTION
FP&C CONSULTANTS KC, LLC
DN
FD
FD
DN
DN
UP
FD
FD
EXISTING CRAWL SPACE HATCH
ELEVATED FROM FLOOR
15' - 3"
33' - 7"
NEW COLUMNS;
REFER TO SF101
215 SF
STORAGE
467 SF
EQUIPMENT
ROOM
3018 SF
CRAWL SPACE
B B
141 SF
OFFICE
142 SF
OFFICE
142 SF
OFFICE
8 SF
CLOSET
212B
112 SF
TELE EQUIP
20 SF
CLOSET
212C
8 SF
CLOSET
212A
31 SF
STORAGE
139 SF
MEN'S
RESTROOM
214 107 SF
WOMEN'S
RESTROOM
7 SF
JANITOR
215A
4 SF
CLOSET
216B
140 SF
GUEST ROOM
3 SF
CLOSET
217B
141 SF
GUEST ROOM
141 SF
OFFICE
141 SF
OFFICE
142 SF
OFFICE
143 SF
OFFICE
125 SF
OFFICE
CONFERENCE
ROOM
203 9 SF
CLOSET
201B
140 SF
GUEST ROOM
6 SF
CLOSET
200B
140 SF
GUEST ROOM
602 SF
CORRIDOR
142 SF
STAIRS
9 SF
CLOSET
209A
9 SF
CLOSET
209B
5 SF
CLOSET
210A
4 SF
CLOSET
210B
9 SF
CLOSET
211A
4 SF
CLOSET
211B
8 SF
CLOSET
208A
10 SF
CLOSET
207B
5 SF
CLOSET
207A
8 SF
CLOSET
208B
6 SF
CLOSET
205B
9 SF
CLOSET
205A
5 SF
CLOSET
206A
9 SF
CLOSET
206B
9 SF
CLOSET
204A
11 SF
CLOSET
201A
10 SF
CLOSET
200A
10 SF
CLOSET
217A
5 SF
CLOSET
216A
DEPARTMENTAL USE PLAN
CIRCULATION
RESTROOM
STAFF
STORAGE
UTIL/MEP
A A
B B
1 2
332 SF
CHASE
C H
AS
E
C O
U N
TE
R
COUNTER
221 SF
CORRIDOR
115A
162 SF
OFFICE
154 SF
STORAGE
6 SF
CLOSET
109A 167 SF
WORKROOM
115B
154 SF
OFFICE
9 SF
CLOSET
111B 142 SF
STAIRS
144 SF
MEN'S
RESTROOM
106 SF
WOMEN'S
RESTROOM
243 SF
CORRIDOR
27 SF
IT / STORAGE
194 SF
TRAINING
24 SF
MECH
104A
30 SF
STORAGE
103A
96 SF
FOYER
100A
47 SF
ENTRY
151 SF
PRINTER ROOM
155 SF
DIRECTOR
150 SF
OFFICE
9 SF
CLOSET
106A
833 SF
TRAINING ROOM
149 SF
LAUNDRY
8 SF
CLOSET
107A
R 2' - 9"
A A
B B
1 2
78 SF
SUPPLY
104B
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
Drawing Title
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Building Number
Drawing Number
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
VA FORM 08 - 6231
CONSTRUCTION DOCUMENTS
CONSULTANTS
Revs: Date:
BUSINESS OCCUPANCY
SPRINKLERED
9/
/2
4:
:1
PM
DEPARTMENTAL USE PLAN CONSTRUCTION
DOCUMENTS
RENOVATE BUILDING 104 - LETC
FORT ROOTS, NORTH LITTLE ROCK
2021.09.30 TS EW
598-19-127
GI004
JDA PROJECT #: 2018.001
A/E
2200 N. RODNEY PARHAM ROAD
SUITE 210
LITTLE ROCK, AR 72212
501-404-4811 jda@JohnsonDanforth.com
JohnsonDanforth & Associates
STRUCTURAL ENGINEER
BERNHARD TME
BUILDING 2, 1 ALLIED DRIVE
SUITE 2600
LITTLE ROCK, AR 72202
MEP ENGINEER
INSIGHT ENGINEERING, PLLC
201 S. CHESTER, SUITE B
LITTLE ROCK, AR 72201
FIRE PROTECTION
FP&C CONSULTANTS KC, LLC
1330 BURLINGTON STREET, STE. 200
NORTH KANSAS CITY, MO 64116
3/16" = 1'-0"B1 BASEMENT DEPARTMENTAL USE PLAN
3/16" = 1'-0"F1 SECOND LEVEL DEPARTMENTAL USE PLAN
3/16" = 1'-0"D1 FIRST LEVEL DEPARTMENTAL USE PLAN
SCALE: 3/16" = 1'-0"
0 2'-8" 5'-4" 10'-8"
SPACE DESIGN MATRIX
NUMBER NAME Department
TIL ROOM
CODE
PROVIDED
AREA
GROUND LEVEL ICRA PLAN
001 STORAGE STORAGE SRS01 215 SF
002 EQUIPMENT ROOM UTIL/MEP SRSE1 467 SF
003 CRAWL SPACE UTIL/MEP N/A 3018 SF
3 3701 SF
FIRST LEVEL
100 ENTRY CIRCULATION N/A 47 SF
100A FOYER CIRCULATION N/A 96 SF
101 STAIRS CIRCULATION N/A 142 SF
102 JANITOR'S CLOSET UTIL/MEP JANC1 10 SF
103 TRAINING ROOM STAFF CRA1 833 SF
103A STORAGE STORAGE SRS01 30 SF
104 TRAINING STAFF CRA1 194 SF
104A MECH UTIL/MEP N/A 24 SF
104B SUPPLY STORAGE SRS01 78 SF
105 PRINTER ROOM STAFF RPR01 151 SF
106 OFFICE STAFF OFA09 150 SF
106A CLOSET STORAGE SRS01 9 SF
107 LAUNDRY STAFF NULR1 149 SF
107A CLOSET STORAGE SRS01 8 SF
108 OFFICE STAFF OFA09 162 SF
109 STORAGE STORAGE SRS01 154 SF
109A CLOSET STORAGE SRS01 6 SF
110 DIRECTOR STAFF OFA09 155 SF
111 OFFICE STAFF OFA09 154 SF
111B CLOSET STORAGE SRS01 9 SF
112 IT / STORAGE STORAGE SRS01 27 SF
113 MEN'S RESTROOM RESTROOM TLTS1 144 SF
114 WOMEN'S RESTROOM RESTROOM TLTS1 106 SF
115 CORRIDOR CIRCULATION N/A 243 SF
115A CORRIDOR CIRCULATION N/A 221 SF
115B WORKROOM STAFF WRCH1 167 SF
26 3471 SF
SECOND LEVEL
200 GUEST ROOM STAFF OFA09 140 SF
200A CLOSET STORAGE SRS01 10 SF
200B CLOSET STORAGE SRS01 6 SF
201 GUEST ROOM STAFF OFA09 140 SF
201A CLOSET STORAGE SRS01 11 SF
201B CLOSET STORAGE SRS01 9 SF
203 OFFICE STAFF OFA09 332 SF
204 OFFICE STAFF OFA09 125 SF
204A CLOSET STORAGE SRS01 9 SF
205 OFFICE STAFF OFA09 143 SF
205A CLOSET STORAGE SRS01 9 SF
205B CLOSET STORAGE SRS01 6 SF
206 OFFICE STAFF OFA09 142 SF
206A CLOSET STORAGE SRS01 5 SF
206B CLOSET STORAGE SRS01 9 SF
207 OFFICE STAFF OFA09 141 SF
207A CLOSET STORAGE SRS01 5 SF
207B CLOSET STORAGE SRS01 10 SF
208 OFFICE STAFF OFA09 141 SF
208A CLOSET STORAGE SRS01 8 SF
208B CLOSET STORAGE SRS01 8 SF
209 OFFICE STAFF OFA09 141 SF
209A CLOSET STORAGE SRS01 9 SF
209B CLOSET STORAGE SRS01 9 SF
210 OFFICE STAFF OFA09 142 SF
210A CLOSET STORAGE SRS01 5 SF
210B CLOSET STORAGE SRS01 4 SF
211 OFFICE STAFF OFA09 142 SF
211A CLOSET STORAGE SRS01 9 SF
211B CLOSET STORAGE SRS01 4 SF
212 TELE EQUIP UTIL/MEP COMC1 112 SF
212A CLOSET STORAGE SRS01 8 SF
212B CLOSET STORAGE SRS01 8 SF
212C CLOSET STORAGE SRS01 20 SF
213 STAIRS CIRCULATION N/A 142 SF
214 MEN'S RESTROOM RESTROOM TLTS1 139 SF
215 WOMEN'S RESTROOM RESTROOM TLTS1 107 SF
215A JANITOR UTIL/MEP JANC1 7 SF
216 GUEST ROOM STAFF OFA09 140 SF
216A CLOSET STORAGE SRS01 5 SF
216B CLOSET STORAGE SRS01 4 SF
217 GUEST ROOM STAFF OFA09 141 SF
217A CLOSET STORAGE SRS01 10 SF
217B CLOSET STORAGE SRS01 3 SF
218 STORAGE STORAGE SRS01 31 SF
219 CORRIDOR CIRCULATION N/A 602 SF
46 3353 SF
10 SF
JANITOR
CLOSET
FD
FD
B B
3018 SF
CRAWL SPACE
467 SF
EQUIPMENT
ROOM
002215 SF
STORAGE
ICRA CLASS LEGEND
CLASS 4
A A
B B
1 2
221 SF
CORRIDOR
115A
162 SF
OFFICE
154 SF
STORAGE
6 SF
CLOSET
109A 167 SF
WORKROOM
115B
154 SF
OFFICE
9 SF
CLOSET
111B 142 SF
STAIRS
144 SF
MEN'S
RESTROOM
106 SF
WOMEN'S
RESTROOM
243 SF
CORRIDOR
27 SF
IT / STORAGE
194 SF
TRAINING
24 SF
MECH
104A
30 SF
STORAGE
103A
96 SF
FOYER
100A
47 SF
ENTRY
151 SF
PRINTER ROOM
155 SF
DIRECTOR
150 SF
OFFICE
9 SF
CLOSET
106A
833 SF
TRAINING ROOM
149 SF
LAUNDRY
8 SF
CLOSET
107A
10 SF
JANITOR'S
CLOSET
78 SF
SUPPLY
104B
378 SF
CLASS 4
3252 SF
CLASS 3
ICRA CLASS LEGEND
CLASS 3
CLASS 4
A A
B B
1 2
141 SF
OFFICE
142 SF
OFFICE
142 SF
OFFICE
8 SF
CLOSET
212B
112 SF
TELE EQUIP
20 SF
CLOSET
212C
8 SF
CLOSET
212A
31 SF
STORAGE
139 SF
MEN'S
RESTROOM
107 SF
WOMEN'S
RESTROOM
7 SF
JANITOR
215A
4 SF
CLOSET
216B
140 SF
GUEST ROOM
141 SF
GUEST ROOM
141 SF
OFFICE
141 SF
OFFICE
142 SF
OFFICE
143 SF
OFFICE
125 SF
OFFICE
9 SF
CLOSET
201B
140 SF
GUEST ROOM
140 SF
GUEST ROOM
602 SF
CORRIDOR
142 SF
STAIRS
4 SF
CLOSET
216B
3 SF
CLOSET
217B
6 SF
CLOSET
200B
9 SF
CLOSET
209A
9 SF
CLOSET
209B
5 SF
CLOSET
210A
4 SF
CLOSET
210B
9 SF
CLOSET
211A
4 SF
CLOSET
211B
8 SF
CLOSET
208A
10 SF
CLOSET
207B
5 SF
CLOSET
207A
8 SF
CLOSET
208B
6 SF
CLOSET
205B
9 SF
CLOSET
205A
5 SF
CLOSET
206A
9 SF
CLOSET
206B
9 SF
CLOSET
204A
10 SF
CLOSET
200A
10 SF
CLOSET
217A
5 SF
CLOSET
216A
11 SF
CLOSET
201A
ICRA CLASS LEGEND
CLASS 3
CLASS 4
OFFICE
CLOSET
202B
CLOSET
203A
140 SF
10 SF 7 SF 5 SF
CLOSET
203B
8 SF
CLOSET
202A
140 SF
OFFICE
NEW UNRATED PARTITION
NEW / EXISTING 1 HOUR BARRIER
EXISTING PARTITION TO BE REMOVED
EXISTING PARTITION
INDICATES AREAS OUTSIDE PRIMARY
PROJECT WORK AREA
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
Drawing Title
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Building Number
Drawing Number
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
VA FORM 08 - 6231
CONSTRUCTION DOCUMENTS
CONSULTANTS
Revs: Date:
BUSINESS OCCUPANCY
SPRINKLERED
9/
/2
4:
:4
PM
C :\U se rs
\e w ui \D oc um en ts
\L O
C
AL
\5
-1 9-
7_
R en ov B ui ld in g
4-
LE
TC
_A R
C H
_e st he r.w ui .rv t
ICRA PLANS CONSTRUCTION
DOCUMENTS
RENOVATE BUILDING 104 - LETC
FORT ROOTS, NORTH LITTLE ROCK
2021.09.30 Checker Author
598-19-127
GC101
JDA PROJECT #: 2018.001
A/E
2200 N. RODNEY PARHAM ROAD
SUITE 210
LITTLE ROCK, AR 72212
501-404-4811 jda@JohnsonDanforth.com
JohnsonDanforth & Associates
STRUCTURAL ENGINEER
BERNHARD TME
BUILDING 2, 1 ALLIED DRIVE
SUITE 2600
LITTLE ROCK, AR 72202
MEP ENGINEER
INSIGHT ENGINEERING, PLLC
201 S. CHESTER, SUITE B
LITTLE ROCK, AR 72201
FIRE PROTECTION
FP&C CONSULTANTS KC, LLC
1330 BURLINGTON STREET, STE. 200
NORTH KANSAS CITY, MO 64116
3/16" = 1'-0"F1 GROUND LEVEL ICRA PLAN
3/16" = 1'-0"E1 FIRST LEVEL ICRA PLAN
3/16" = 1'-0"C1 SECOND LEVEL ICRA PLAN
ICRA - GENERAL NOTES
1. ICRA WORK LIMITS ARE TO ENCOMPASS ALL AREAS WITH
REQUIRED WORK ACROSS ALL DISCIPLINES: CONTRACTOR
TO FULLY FAMILIARIZE THEMSELVES WITH THE COMPLETE
SET OF CONSTRUCTION DOCUMENTS AND THE INTENDED
WORK.
2. ICRA CLASS(ES) SHOWN ARE CONCEPTUAL AND MAY BE
USED AS A STARTING POINT FOR THE CONTRACTOR'S
REQUIRED WORK UNDER SPECIFICATION SECTION 01 35 26
"SAFETY REQUIREMENTS".
3. CONTRACTORS ARE ENCOURAGED TO ATTEND ANY AND
ALL SITE VISITS PROVIDED BY THE VA DURING BIDDING TO
FAMILIARIZE THEMSELVES WITH THE AREAS OF WORK.
4. CONTRACTOR SHALL EXAMINE THE FULL SET OF PLANS
AND DETERMINE IF THERE ARE ADDITIONAL AREAS OF
WORK ( AND ASSOCIATED ICRA CLASS(ES) ) DURING
BIDDING.
5. CONTRACTOR IS TO CONSIDER AND INCLUDE MONIES FOR
REQUIRED WORK IN ALL PROJECT AREAS AS PART OF
THEIR BASE BID.
6. IF CONTRACTOR IDENTIFIES POTENTIAL CONFLICTS OR
LIMITATIONS IN THEIR ABILITY TO FULLY COMPLY WITH
ICRA SAFETY REQUIREMENTS CONTAINED IN THE BIDDING
DOCUMENTS, THEY SHALL SEEK RESOLUTION IN WRITING
AS INDICATED IN BIDDING INSTRUCTIONS.
7. PROVIDE CONTAINMENT AS REQUIRED (BY HOSPITAL)
INFECTION CONTROL REPRESENTATIVE FOR WORK
OUTSIDE MAJOR AREA.
8. PROVIDE CONTAINMENT AT THE FLOOR BELOW FOR ANY
WORK IN THE CEILING PLENUM.
9. PROVIDE TEMPORARY DOORS WITH GASKETING TO
PREVENT THE TRANSFER OF DUST OUTSIDE WORK AREA.
10. PROVIDE TEMPORARY EMERGENCY EXITS FROM
CONSTRUCTION ZONES; HOWEVER, ALL GENERAL
CONSTRUCTION TRAFFIC SHOULD BE THROUGH
VESTIBULE.
11. CONTRACTOR TO PROTECT ALL FINISHES INCLUDING (BUT
NOT LIMITED TO) FLOORING, CEILING, WALL SURFACES,
DOORS, AND DOOR FRAMES DURING THE MOVEMENT OF
MATERIALS TO/FROM LIMIT OF WORK. COORDINATE WITH
COR AND SPECIFICATIONS FOR PROCEDURES /
REQUIREMENTS.
PARTITION LEGEND
SCALE: 3/16" = 1'-0"
0 2'-8" 5'-4" 10'-8"
IT IS THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE THE FOLLOWING INFECTION CONTROL PRECAUTIONS DEPENDING UPON THE
AREA CLASS DESIGNATION
TYPE OF CONTRUCTION/PROJECT ACTIVITY TABLE
GROUP 1-LOW RISK
● OFFICE AREAS (NON-
CLINICAL)
PATIENT RISK GROUP TABLE
GROUP 2-MEDIUM RISK
GROUP 3-HIGH RISK GROUP 4-HIGHEST RISK
INFECTION CONTROL MATRIX-CLASS OF PRECAUTIONS: CONSTRUCTION PROJECT BY PATIENT RISK
PATIENT RISK GROUP TYPE A
I I I
III
NOTE: INFECTION CONTROL APPROVAL WILL BE REQUIRED WHEN THE CONSTRUCTION
ACTIVITY AND RISK LEVEL INDICATE THAT CLASS III OR CLASS IV CONTROL PROCEDURES
ARE NECESSARY.LOW RISK GROUP 1
MEDIUM RISK GROUP 2
HIGH RISK GROUP 3
HIGHEST RISK GROUP 4
1. EXECUTE WORK BY METHODS TO MINIMIZE RAISING DUST FROM CONSTRUCTION
OPERATIONS.
2. IMMEDIATELY REPLACE A CEILING TILE DISPLACED FOR VISUAL INSPECTION.
1. INCLUDES ALL ACTIVITIES REQUIRED BY CLASS I.
2. PROVIDE ACTIVE MEANS TO PREVENT AIRBORNE DUST FROM DISPERSING INTO
ATMOSPHERE.
3. WATER MIST WORK SURFACES TO CONTROL DUST WHILE CUTTING.
4. SEAL UNUSED DOORS WITH DUCT TAPE.
5. BLOCK OFF AND SEAL AIR VENTS.
6. REPLACE ADHESIVE WALK-OFF MATS AT ENTRANCE AN EXIT OF WORK AREA.
REPLACE USED MATS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
7. REMOVE OR ISOLATE HVAC SYSTEM IN AREAS WHERE WORK IS BEING DONE TO
PREVENT CONTAMINATION OF DUCT SYSTEM.
1. INCLUDES ALL ACTIVITIES REQUIRED BY CLASS II.
2. OBTAIN INFECTION CONTROL PERMIT FROM HOSPITAL SAFETY OFFICER OR
FACILITIES MANAGEMENT MAINTENANCE AND ENGINEERING DEPARTMENT BEFORE
CONSTRUCTION BEGINS.
3. REMOVE OR ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO
PREVENT CONTAMINATION OF DUCT SYSTEM.
4. COMPLETE ALL CRITICAL BARRIERS BEFORE CONSTRUCTION BEGINS OR
IMPLEMENT CONTROL CUBE METHOD.
5. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA-EQUIPPED
AIR FILTRATION UNITS.
6. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED
CONTAINERS.
7. COVER TRANSPORT RECEPTACLES OR CARS. TAPE COVERS.
8. WET MOP AND/OR VACUUM WITH HEPA FILTERED VACUUM BEFORE LEAVING WORK
AREAS.
9. REMOVE ISOLATION OF HVAC SYSTEM IN AREAS WHERE WORK IS BEING
PERFORMED.
1. WIPE SURFACES TO REMOVE DUST.
1. WIPE WORK SURFACES WITH
DISINFECTANT.
2. CONTAIN CONSTRUCTION WASTE
BEFORE TRANSPORT IN TIGHTLY
COVERED CONTAINERS.
3. WET MOP AND/OR VACUUM
WORK AREA WITH HEPA
FILTERED VACUUM BEFORE
LEAVING WORK AREAS.
4. REMOVE ISOLATION OF HVAC
SYSTEM IN AREAS WHERE WORK
WAS BEING PERFORMED.
1. REMOVE BARRIER MATERIALS
CAREFULLY TO MINIMIZE
SPREADING OF DIRT AND DEBRIS
ASSOCIATED WITH
CONSTRUCTION.
2. CONTAIN CONSTRUCTION
WASTE BEFORE TRANSPORT IN
TIGHTLY COVERED CONTAINERS.
3. COVER TRANSPORT
RECEPTACLES OR CARTS. TAPE
COVERING.
4. VACUUM WORK WITH HEPA-
FILTERED VACUUMS.
5. WET MOP WITH DISINFECTANT.
6. REMOVE ISOLATION OF HVAC
SYSTEM IN AREAS WHERE WORK
WAS BEING PERFORMED.
1. INCLUDES ALL ACTIVITIES REQUIRED BY CLASS III.
2. OBTAIN INFECTION CONTROL PERMIT FROM HOSPITAL SAFETY OFFICER OR
FACILITIES MANAGEMENT MAINTENANCE AND ENGINEERING DEPARTMENT
BEFORE CONSTRUCTION BEGINS.
3. ISOLATE HVAC SYSTEM IN AREAS WHERE WORK IS BEING DONE TO PREVENT
CONTAMINATION OF DUCT SYSTEM.
4. COMPLETE ALL CRITICAL BARRIERS OR IMPLEMENT CONTROL CUBE METHOD
BEFORE CONSTRUCTION BEGINS.
5. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA-
EQUIPPED AIR FILTRATION UNITS.
6. SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES APPROPRIATELY.
CONSTRUCT ANTEROOM AND REQUIRE ALL PERSONNEL TO PASS-THROUGH
THIS ROOM SO THEY CAN BE VACUUMED USING A HEPA VACUUM CLEANER
BEFORE LEAVING WORK SITE OR THEY CAN WEAR CLOTH OR PAPER
COVERALLS THAT ARE REMOVED EACH TIME THEY LEAVE THE WORK SITE.
7. ALL PERSONNEL ENTERING WORK SITE ARE REQUIRED TO WEAR SHOE
COVERS. SHOE COVERS MUST BE CHANGED EACH TIME THE WORKER EXITS
THE WORK AREA.
8. PLACE ADHESIVE WALK-OFF MATS AT ENTRANCE TO WORK AREA WITH
ANTEROOM. REPLACE PER MANUFACTURER'S RECOMMENDATIONS.
9. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS
INSPECTED EACH BY THE HOSPITAL SAFETY OFFICER, FACILITIES
MANAGEMENT MAINTENANCE AND ENGINEERING DEPARTMENT AND
THOROUGHLY CLEANED BY THE HOSPITAL ENVIRONMENTAL SERVICES
DEPARTMENT OR THEIR CONTRACTED ENVIRONMENTAL SERVICES
COMPANY.
10. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED
CONTAINERS.
11. COVER TRANSPORT RECEPTACLES OR CARS. TAPE COVERING.
12. VACUUM WITH HEPA FILTERED VACUUM. WET MOP WITH DISINFECTANT
AFTER BARRIERS ARE REMOVED.
13. REMOVE ISOLATION OF HVAC SYSTEM IN AREAS WHERE WORK IS BEING
PERFORMED.
1. REMOVE BARRIER MATERIALS
CAREFULLY TO MINIMIZE
SPREADING OF DIRT AND DEBRIS
ASSOCIATED WITH
CONSTRUCTION.
2. CONTAIN CONSTRUCTION WASTE
BEFORE TRANSPORT IN TIGHTLY
COVERED CONTAINERS.
3. COVER TRANSPORT
RECEPTACLES OR CARTS. TAPE
COVERING.
4. VACUUM WORK WITH HEPA-
FILTERED VACUUMS.
5. WET MOP WITH DISINFECTANT
AFTER BARRIERS ARE REMOVED.
6. REMOVE ISOLATION OF HVAC
SYSTEM IN AREAS WHERE WORK
WAS BEING PERFORMED.
DURING CONSTRUCTION PROJECT UPON COMPLETION OF PROJECT
CLASS I
CLASS II
CLASS III
CLASS IV
INSPECTION AND NON-INVASIVE ACTIVITIES
INCLUDES BUT IS NOT LIMITED TO:
● REMOVAL OF CEILING TILES FOR VISUAL INSPECTION LIMITED TO 1
TILE IN 50 SQUARE FEET
● PAINTING (BUT NOT SANDING), WALL COVERING
● ELECTRICAL TRIM WORK, MINOR PLUMBING, AND ACTIVITIES THAT
DO NOT GENERATE DUST OR REQUIRE CUTTING OF WALLS OR
ACCESS TO CEILINGS OTHER THAN FOR VISUAL INSPECTION
TYPE A
SMALL SCALE, SHORT DURATION ACTIVITIES THAT CREATE MINIMAL DUST
INCLUDES BUT IS NOT LIMITED TO:
● INSTALLATION OF TELEPHONE AND COMPUTER CABLING
● ACCESS TO CHASE SPACES
● CUTTING OF WALLS OR CEILING WHERE DUST MIGRATION CAN BE
CONTROLLED
TYPE B
WORK THAT GENERATES A MODERATE TO HIGH LEVEL OF DUST OR
REQUIRES DEMOLITION OR REMOVAL OF ANY FIXED BUILDING
COMPONENTS OR ASSEMBLIES
INCLUDES BUT IS NOT LIMITED TO:
● SANDING OF WALLS FOR PAINTING OR WALL COVERING
● REMOVAL OF FLOOR COVERINGS, CEILING TILES AND CASEWORK
● NEW WALL CONSTRUCTION
● MINOR DUCT WORK OR ELECTRICAL WORK ABOVE CEILINGS
● MAJOR CABLING ACTIVITIES
● ANY ACTIVITY THAT CANNOT BE COMPLETED WITHIN A SINGLE
WORK SHIFT
TYPE C
MAJOR DEMOLITION AND CONSTRUCTION PROJECTS
INCLUDES BUT IS NOT LIMITED TO:
● ACTIVITIES THAT REQUIRE CONSECUTIVE WORK SHIFTS
● REQUIRES HEAVY DEMOLITION OR REMOVAL OF A COMPLETE
CEILING SYSTEM
● NEW CONSTRUCTION
TYPE D
ICRA GENERAL NOTES
● CARDIOLOGY
● ECHOCARDIOLOGY
● ENDOSCOPY-GI
● PHYSICAL THERAPY
● RADIOLOGY/MRI
● NUCLEAR MEDICINE
● RESPIRATORY CARE (EXCEPT
BRONCHOSCOPY AREA)
● CAFETERIA
● OUTPATIENT AREAS-CLINICS AND OFFICES
(EXCEPTION: TRANSPLANT AND ONCOLOGY)
● EMERGENCY ROOM
● POST ANESTHESIA
● CARE UNITS
● LABOR AND DELIVERY
● PEDIATRICS
● ADMISSION/DISCHARGE
AREA
● LABORATORIES
● PHARMACY
● INPATIENT UNITS (NOT
OTHERWISE
SPECIFIED)
● ALL OPERATING ROOMS INCLUDING LABOR AND
DELIVERY
● ANESTHESIA AND PUMP AREAS
● CENTRAL EQUIPMENT/STERILE SUPPLY
● CARDIAC CATHETERIZATION AND ANGIOGRAPHY
AREAS
● INTERVENTIONAL RADIOLOGY
● RADIATION ONCOLOGY
● ALL INTENSIVE CARE UNITS
● NEWBORN NURSERIES, INCLUDING NICU
● DIALYSIS UNIT
● ONCOLOGY-INPATIENT AND OUTPATIENT
● TRANSPLANT-INPATIENT AND OUTPATIENT
● PHARMACY ADMIXTURE
● NEGATIVE PRESSURE ISOLATION ROOMS/AREAS
(INCLUDING BRONCHOSCOPY AREA)
TYPE B
II
II
III
III / IV
TYPE C
II
III
III / IV
III / IV
TYPE D
III / IV
IV
IV
IV
A. PROVIDE CONTAINMENT AS REQUIRED (BY HOSPITAL) INFECTION CONTROL REPRESENTATIVE FOR WORK OUTSIDE MAJOR AREA.
B. PROVIDE CONTAINMENT AT THE FLOOR BELOW FOR ANY WORK IN THE CEILING PLENUM.
C.…