Attachment C_2021 09 30 598-19-127 Construction Documents Drawings V1.pdf

PDF 17 MB Posted

Attached to
Y1DZ--598-19-127 Bldg 104 Renovations
Solicitation number
598-19-127
Issued by

About this file

These construction documents detail a renovation project for Building 104 at the Fort Logan H. Roots VA Healthcare System in North Little Rock, Arkansas. The project involves comprehensive renovation of the first and second floors, including bathroom renovations, floor finish changes, structural support modifications for a copy room, and replacement of the cooling tower supporting Building 104. The building, with a gross area of 10,557 square feet, will primarily be used for law enforcement training, with secondary uses including assembly and business functions. The renovation will reconfigure approximately 4,109 square feet of staff space, 1,495 square feet of circulation areas, 544 square feet of bathrooms, 780 square feet of storage, and 3,630 square feet of utility/mechanical spaces. The project is being managed by the VA's Office of Construction and Facilities Management, with architectural and engineering services provided by JohnsonDanforth & Associates and supporting consultants.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT INFORMATION

RENOVATE BUILDING 104 - LETC

VISN 16: SOUTH CENTRAL VA HEALTH CARE NETWORK

CENTRAL ARKANSAS VETERANS HEALTHCARE SYSTEM

2200 FORT ROOTS DRIVE

NORTH LITTLE ROCK, AR 72114

PROJECT NUMBER: 598-19-127

PROJECT INFORMATION

RENOVATION OF FIRST AND SECOND STORY OF BUILDING 104 ON

THE EJT HEALTHCARE CAMPUS INCLUDING RENOVATION OF

BATHROOMS AND FLOOR FINISH CHANGE AS WELL AS ADDITIONAL

STRUCTURAL SUPPORT OF THE COPY ROOM. CHANGE OF COOLING

TOWER THAT SUPPORTS BUILDING 104 FOR FUTURE MECHANICAL

CHANGES.

BUILDING SUMMARY

GROSS AREA: 10,557 SF

MAIN USE: LAW ENFORCEMENT TRAINING

SECONDARY USES: ASSEMBLY; BUSINESS

AREA BY USE:

STAFF: 4109 SF

CIRCULATION: 1495 SF

BATHROOM: 544 SF

STORAGE: 780 SF

UTIL/MEP: 3630 SF

PROJECT INFORMATION

N

N

U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

Drawing Title

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Building Number

Drawing Number

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

VA FORM 08 - 6231

BUSINESS OCCUPANCY

SPRINKLERED

THESE DRAWINGS ARE NOT TO

BE USED AS THE BASIS FOR

THE ISSUANCE OF A PERMIT,

FOR FIELD LAYOUT,

CONSTRUCTION, BIDDING,

RECORDATION, CONVEYANCE,

SALES.

CONSTRUCTION DOCUMENTS

NOT TO SCALE

CAMPUS MAP

NOT TO SCALE

VICINITY MAP

CONSULTANTS

Revs: Date:

9/

/2

4:

:0

PM

C :\U se rs

\e w ui \D oc um en ts

\L O

C

AL

\5

-1 9-

7_

R en ov B ui ld in g

4-

LE

TC

_A R

C H

_e st he r.w ui .rv t

COVER SHEET CONSTRUCTION

DOCUMENTS

RENOVATE BUILDING 104 - LETC

2021.09.30 JDa JDa

GI001

JDA PROJECT #: 2018.001

RENOVATE BUILDING 104 - LETC

PROJECT No: 598-19-127

FORT LOGAN H. ROOTS

NORTH LITTLE ROCK, AR

CONSTRUCTION DOCUMENTS

598-19-127

FORT ROOTS, NORTH LITTLE ROCK

A/E

2200 N. RODNEY PARHAM ROAD

SUITE 210

LITTLE ROCK, AR 72212

501-404-4811 jda@JohnsonDanforth.com

JohnsonDanforth & Associates

SHEET INDEX

NUMBER NAME 35% SD 07.23.2021

65% DD

08.20.2021

95% CD

09.17.2021

CONSTRUCTION

DOCUMENTS 09.30.2021

GENERAL INFORMATION

GI001 COVER SHEET X X X X

GI002 SYMBOLS & NOTES X X X X

GI003 STANDARD ABBREVIATIONS X X X X

GI004 DEPARTMENTAL USE PLAN X X X X

GC101 ICRA PLANS X X X

GC110 ICRA LEGEND X X X

STRUCTURAL

S001 GENERAL NOTES X X X X

SF101 1ST LEVEL FRAMING PLAN & DETAILS X X X X

ARCHITECTURAL

AD101 BASEMENT FLOOR PLAN - EXISTING/DEMO X X X X

AD102 FIRST FLOOR PLAN - EXISTING/DEMO X X X X

AD103 SECOND FLOOR PLAN - EXISTING/DEMO X X X X

AD111 FIRST FLOOR REFLECTED CEILING PLAN - EXISTING / DEMO X X X

AD112 SECOND FLOOR REFLECTED CEILING PLAN - EXISTING/DEMO X X X

AE101 BASEMENT FLOOR PLAN - NEW X X X X

AE102 FIRST FLOOR PLAN - NEW X X X X

AE103 SECOND FLOOR PLAN - NEW X X X X

AE111 REFLECTED CEILING PLAN - FIRST FLOOR PLAN X X X

AE112 REFLECTED CEILING PLAN - SECOND FLOOR PLAN X X X

AE401 FIRST FLOOR ENLARGED PLAN AND INTERIOR ELEVATIONS X X X

AE402 SECOND FLOOR ENLARGED PLAN AND INTERIOR ELEVATIONS X X X

AE501 DETAILS X X X

AE601 DOOR SCHEDULE X

IN101 FINISH PLANS & SCHEDULE X X X

FIRE PROTECTION

FA102 FIRST LEVEL FIRE ALARM PLAN X X X

FA103 SECOND LEVEL FIRE ALARM PLAN X X X

FX102 FIRST LEVEL FIRE SUPPRESSION PLAN X X X

FX103 SECOND LEVEL FIRE SUPPRESSION PLAN X X X

PLUMBING

PD101 FIRST LEVEL PLAN - SANITARY SEWER AND VENT DEMOLITION X X X X

PD102 FIRST LEVEL PLAN - DOMESTIC WATER DEMOLITION X X X X

PD103 SECOND LEVEL PLAN - SANITARY SEWER AND VENT DEMOLITION X X X X

PD104 SECOND LEVEL PLAN - DOMESTIC WATER DEMOLITION X X X X

PL001 PLUMBING GENERAL NOTES AND LEGEND X X X X

PL101 FIRST LEVEL PLAN - SANITARY SEWER AND VENT X X X

PL102 FIRST LEVEL PLAN - DOMESTIC WATER X X X X

PL103 SECOND LEVEL PLAN - SANITARY SEWER AND VENT X X X X

PL104 SECOND LEVEL PLAN - DOMESTIC WATER X X X X

PJ101 PLUMBING RISER DIAGRAMS X X

PK101 PLUMBING SCHEDULES X X

MECHANICAL

MD100 SITE PLAN - MECHANICAL DEMOLITION X X X X

MD101 FIRST LEVEL PLAN - HVAC DUCTWORK DEMOLITION X X X

MD102 SECOND LEVEL PLAN - HVAC DUCTWORK DEMOLITION X X X

MH001 MECHANICAL GENERAL NOTES AND LEGEND X X X

MH100 SITE PLAN - MECHANICAL X X X

MH101 FIRST LEVEL PLAN - HVAC DUCTWORK X X X

MH102 SECOND LEVEL PLAN - HVAC DUCTWORK X X X

MJ101 MECHANICAL DETAILS X X X

MJ102 MECHANICAL CONTROLS X X

MK101 MECHANICAL SCHEDULES X X X

ELECTRICAL

ED101 BASEMENT LEVEL PLAN - POWER AND SYSTEMS DEMOLITION X X

ED102 FIRST LEVEL RCP - LIGHTING DEMOLITION X X X

ED103 FIRST LEVEL PLAN - POWER AND SYSTEMS DEMOLITION X X X

ED104 FIRST LEVEL PLAN - MECHANICAL POWER DEMOLITION X X X

ED105 SECOND LEVEL RCP - LIGHTING DEMOLITION X X X

ED106 SECOND LEVEL PLAN - POWER AND SYSTEMS DEMOLITION X X X

ED107 SECOND LEVEL PLAN - MECHANICAL POWER DEMOLITION X X X

ED108 SITE PLAN - ELECTRICAL DEMOLITION X X X

ES101 SITE PLAN - ELECTRICAL X X

EL101 FIRST LEVEL PLAN - LIGHTING X X X

EL102 SECOND LEVEL PLAN - LIGHTING X X X

EP101 BASEMENT LEVEL PLAN - POWER AND SYSTEMS X X X

EP102 FIRST LEVEL PLAN - POWER AND SYSTEMS X X X

EP103 FIRST LEVEL PLAN - MECHANICAL POWER X X X

EP104 SECOND LEVEL PLAN - POWER AND SYSTEMS X X X

EP105 SECOND LEVEL PLAN - MECHANICAL POWER X X X

EJ101 ELECTRICAL GENERAL NOTES AND LEGEND X X X

EJ102 ELECTRICAL SCHEDULES X

STRUCTURAL ENGINEER

BERNHARD TME

BUILDING 2, 1 ALLIED DRIVE

SUITE 2600

LITTLE ROCK, AR 72202

FIRE PROTECTION

FP&C CONSULTANTS KC, LLC

1330 BURLINGTON STREET, STE. 200

NORTH KANSAS CITY, MO 64116

MEP ENGINEER

INSIGHT ENGINEERING, PLLC

201 S. CHESTER, SUITE B

LITTLE ROCK, AR 72201

SIMPLE PARTITIONS:

A_4A

INDICATES PARTITION TYPE

INDICATES FIRE/SMOKE RATING (0-4 HRS); _ INDICATES 0 HOURS

INDICATES VARIATION CODE(S)

INDICATES NOMINAL CORE SIZE

FIRE RATINGS:

0 NON-RATED

1 1-HR RATING

2 2-HR RATING

3 3-HR RATING

4 4- HR RATING

VARIATION CODES

A NOT USED

B

SMOKE RESISTANT ASSEMBLY; EXTEND ASSEMBLY TO

DECK ABOVE

R

AT

ED

P

AR

TI

TI

O

N S

A B C

MTL STUDS

SINGLE BD,

BOTH SIDES

BOTTOM OF DECK

CEILING LINE

RE: RCP FOR TYPE(S)

CMU

UL U905

(2 HR)

MTL CH-STUDS

DOUBLE BD (1 SIDE)

SHAFT LINEER (1 SIDE)

UL U415-B

(2 HR)

J K L

MTL STUDS

SINGLE BD,

BOTH SIDES

( PARTIAL HT )

D

MTL CH-STUDS

DOUBLE BD (1 SIDE)

SHAFT LINEER (1 SIDE)

UL U415-A

(1 HR)

N O

N -R

AT

ED

P

AR

TI

TI

O N

S

FURRING / STUDS

SINGLE BD,

ONE SIDE ONLY

WITH TILE

NOTES 1 & 4

PARTITION TYPE NOTES

1. WHERE NO FIRE/SMOKE RATING AND NO ACOUSTIC INSULATION INDICATED, TERMINATE STUDS 4” ABOVE HIGHEST ADJACENT CEILING AND BRACE TOP TRACK AT INTERVALS OF 4’-0” OC (MAX) TO STRUCTURE ABOVE OR ADJACENT.

2. SEE FLOOR PLANS AND INTERIOR ELEVATIONS FOR HEIGHT OF PARTIAL HEIGHT PARTITION ABOVE FINISH FLOOR.

3. BRACE PARTIAL HEIGHT ONE-SIDED PARTITIONS TO ADJACENT PARTITIONS. EXCEPTION: WHEN OVERLAYING RATED

WALLS, BRACE NEW STUDS TO STRUCTURE ONLY.

4. OFFSET FURRING / STUD 1" FROM ADJACENT PARALLEL SURFACE / STRUCTURE, UNLESS NOTED OTHERWISE.

BOTTOM OF DECK

CEILING LINE

RE: RCP FOR TYPE(S)

COMPOSITE PARTITIONS:

DOUBLE LETTERS INDICATE COMPOSITE PARTITION MADE UP OF OTHER

PARTITION TYPES. FOR EXAMPLE KK_4A INDICATES A NON-RATED

PARTITION CONSTRUCTED OF TWO (TYPE 'K') SINGLE-SIDED

PARTITIONS WITH ACOUSTICAL INSULATION AND A SINGLE LAYER OF

GWB ON OUTSIDE FACES

CMU

CORE SIZES:

0 7/8" FURRING

1 1-5/8" STUD

2 2-1/2" STUD

4 3-5/8" STUD / CMU

6 5-1/2" STUD / 5-5/8" CMU

8 7-5/8" CMU

E

MTL STUDS

SINGLE BD,

BOTH SIDES

UL U419

(1 HR)

NM

FURRING / STUDS

SINGLE BD,

ONE SIDE ONLY

WITH TILE

(PARTIAL HT)

C

CEMENTICIOUS BACKER BOARD ON WET WALL SIDE OF

PARTITION WITH PORCELAIN FINISH TILE. SEE ELEVATIONSD

MOISTURE RESISTENT GYPSUM BOARD ON RESTROOM

AND/OR JANITOR CLOSET SIDE(S) OF PARTITION

NOTES 2 NOTES 1, 2,

3 & 4

NOTE 1

E

ACOUSTICAL INSULATION: ACOUSTICAL BLANKET INSUL

FULL HT OF PARTITION, PLUS ACOUSTICAL SEALANT

BEADS AROUND FULL PERIMETER OF PARTITION. STC

RATING OF 45 MINIMUM

- N

OT

U

SE

D

- N

OT

U

SE

D

- N

OT

U

SE

D

- N

OT

U

SE

D

F SMOKE REISTANT ASSEMBLY; EXTEND ASSEMBLY TO

DECK ABOVE + MOISTURE RESISTENT GYPSUM BOARD ON

RESTROOM AND/OR JANITOR CLOSET SIDE OF PARTITION

+ ACOUSTICAL BLANKET INSUL FULL HT OF PARTITION,

PLUS ACOUSTICAL SEALANT BEADS AROUND FULL

PERIMETER OF PARTITION. STC RATING OF 45 MINIMUM.

A

1F157B

D2 / AE512

AE501

AE201

AE201

AE211

20' - 6"

FIRST FLOOR

P-01

SCOPE INDICATORS

DRAWING TITLE

DETAIL CALLOUT

DETAIL INDICATOR FOR SMALL CONDITIONS

ELEVATION INDICATOR, EXTERIOR

ELEVATION INDICATOR,

INTERIOR, MULTIPLE

VIEW

BUILDING SECTION INDICATOR

SPACE IDENTIFICATION

OPENING INDICATOR

WINDOW INDICATOR

EQUIPMENT INDICATOR

SHEET NOTES

PARTITION TYPE INDICATOR

NORTH ARROW

INDICATES PROJECT NORTH

INDICATES TRUE NORTH

EXISTING

INDICATES

COLUMN LINE

DESIGNATION

COLUMN LINE INDICATORS

DRAWING REVISION INDICATOR

EXISTING CONSTRUCTION TO

REMAIN

EXISTING CONSTRUCTION TO BE

REMOVED

NEW CONSTRUCTION

VV ITEM - GOVERNMENT FURNISHED /

GOVERNMENT INSTALLED

VC ITEM - GOVERNMENT

FURNISHED / CONTRACTOR

INSTALLED

ELEVATION INDICATOR

WALL FINISH INDICATOR

CC ITEM - CONTRACTOR FURNISHED /

CONTRACTOR INSTALLED

N

1 1/8" = 1'-0" View Name

A_4A

BA3034

CASEWORK TAG

LETTER PAIR INDICATES CASEWORK FAMILY:

RE: AE511-514 FOR DETAILS

FIRST PAIR OF NUMBERS INDICATES UNIT

WIDTH (I.E. 30")

SECOND PAIR INDICATES COUNTERTOP

HEIGHT (I.E. 34")

TOILET ACCESSORY TAG

XXXX

JSN

A

NEW

INDICATES

COLUMN LINE

DESIGNATION

CEILING HEIGHT INDICATOR

Room name 1A105

9' - 0"

WALL

MOUNTED

MIRROR

(A1066)

WALL MOUNTED

GRABBAR

(TOILET SIDE)

(A5109)

WALL MOUNTED

GRABBAR

(TOILET REAR)

(A5109)

TOILET PAPER

DISPENSER

(A5200)

WALL MOUNTED PAPER TOWEL

DISPENSER (WITH OR WITHOUT

INTEGRAL TRASH RECEPTICLE)

(A5080)

FIRE

EXTINGUISHER IN

FULLY RECESSED

CABINET, UNLESS

OTHERWISE

NOTED

WALL MOUNTED

WATER FOUNTAIN

(UNLESS OTHER

WISE NOTED)

MOP BRACKET WALL MOUNTED

LAVATORY

COUNTER

MOUNTED

LAVATORY

WALL MOUNTED

ROBE HOOK PAIR

(A5145)

WALL MOUNTED

SHOWER SEAT

WALL MOUNTED

SOAP DISPENSER

HAND SANITIZER DISPENSER

(A5070/A5071)

SH

O

W

ER

W

AL

L

MIRROR TO

BE

18"x36" U.N.O.

CENTER

MIRROR

OVER

SINK U.N.O.

TO

R

EF

LE

C

TI

N

G

SU

R

FA

C E

PL

U

M

BI

N G

W

AL

L

12" 42"

6" 36"

TO

IL

ET

S

ID

E

W

AL

L

PL

U

M

BI

N G

W

AL

L

7"

IF A DOUBLE ROLL

DISPENSER IS

PROVIDED,

DIMENSION IS TO ROLL

CLOSEST TO TOILET

TO

F

R O

N T

TO

P

ED

G

E O

F D

EC

K

LI

P

W H

EN

LO

W

ER

ED

"48

TO

H

AN

D

LE

3' -0

TO

T

O P

TO

O

PE

R

AT

IO

N

2' -1

0"

2' -9

C

O U

N

TE

R H

EI

G

H T

SI

D

E W

AL

L

1'-3"

SI

D E

W

AL

L 1'-3"

TO

O

PE

R

AT

IO

N

PTD-1 / PTD-2

FEC

MR-1GB-42 GB-36 TPD-1 / TPD-2 HK-1

SS-1 SD-1 / HSD-1 RCK-1 BCS-1

SP

O

U T

H

EI

G H

T

0'

6"

WALL MOUNTED

POSTURE MIRROR

MR-2

SWING UP GRAB

BAR

RE: 12/A515 FOR

SUPPORTS

GB-30SU

SI

D

E W

AL

L

/ T O

IL

ET

C .L

1' - 6"

2'

TOILET

MOUNTING

LOCATION

TO

IL

ET

S

ID

E

W

AL

L

18"

-1

9"

OFFSET DRAIN

INSULATE HW

& DRAIN

OFFSET DRAIN

INSULATE HW

& DRAIN- -

- N

OT

U

SE

D

- N

OT

U

SE

D

- N

OT

U

SE

D

DISPOSAL, SANITARY

NAPKIN, SS, SURFACE

MOUNTED

(A5090)

SND-1

SHELF; FOLD DOWN;

STAINLESS STEEL

(A5162)

SLF-1

CLOCK, ATOMIC,

BATTERY OPERATED

(F3200)

TELEVISION, FLAT

SCREEN

(M0500)

BOARDS, BULLETIN,

48"Wx48"H

(F3010)

" 44

8"

U .N

.O

4' -0

TELEVISION, COLOR,

BEDSIDE, W/ GRAVITY

FREE SUPPORT ARM

(M0505)

TV/DVD COMBINATION

(M0510)

3' -0

5' -6

VA

R

IE

S

- N

OT

U

SE

D

- N

OT

U

SE

D

- N

OT

U

SE

D

- N

OT

U

SE

D

- N

OT

U

SE

D

- N

OT

U

SE

D

- N

OT

U

SE

D

- N

OT

U

SE

D

- N

OT

U

SE

D

- N

OT

U

SE

D

- N

OT

U

SE

D

- N

OT

U

SE

D

- N

OT

U

SE

D

NEW UNRATED PARTITION

NEW / EXISTING 1 HOUR BARRIER

NEW / EXISTING 1 HOUR SMOKE BARRIER

NEW / EXISTING 2 HOUR BARRIER

NEW / EXISTING SMOKE BARRIER

NEW / EXISTING 2 HOUR SMOKE BARRIER

EXISTING PARTITION TO BE REMOVED

EXISTING PARTITION

U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

Drawing Title

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Building Number

Drawing Number

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

VA FORM 08 - 6231

CONSTRUCTION DOCUMENTS

CONSULTANTS

Revs: Date:

BUSINESS OCCUPANCY

SPRINKLERED

9/

/2

4:

:0

PM

SYMBOLS & NOTES CONSTRUCTION

DOCUMENTS

RENOVATE BUILDING 104 - LETC

FORT ROOTS, NORTH LITTLE ROCK

2021.09.30 JDa JDa

598-19-127

GI002

JDA PROJECT #: 2018.001

A/E

2200 N. RODNEY PARHAM ROAD

SUITE 210

LITTLE ROCK, AR 72212

501-404-4811 jda@JohnsonDanforth.com

JohnsonDanforth & Associates

1 TESTING AGENCIES FOR THE FIRE ASSEMBLIES IDENTIFIED ON THE PARTITION SCHEDULE ARE:

UL – UNDERWRITERS LABORATORY DESIGN NUMBER

GA – GYPSUM ASSOCIATION DESIGN NUMBER

2 PLAN DIMENSIONS ARE TYPICALLY TO GRID LINE, FACE OF STUD, OR FACE OF CONCRETE OR CMU UNLESS NOTED OR INDICATED OTHERWISE. DOORS NOT LOCATED BY PLAN DIMENSIONS ARE LOCATED BY JAMB DETAILS REFERENCED FROM DOOR SCHEDULE.

CRITICAL CLEARANCES ARE DESIGNATED ‘CLR’.

3 THE PARTITION TYPE NOTED BY A SYMBOL CONTINUES BETWEEN CORNERS AND BETWEEN INTERSECTING PARTITIONS. AT OPENINGS, PROVIDE THE SAME PARTITION TYPE ABOVE AND BELOW SUCH OPENING AS THAT ON EITHER SIDE OF THE OPENING. AT PARTITIONS SCHEDULED TO EXTEND TO STRUCTURE ABOVE, EXTEND THE PARTITION AROUND AND ABOVE DUCTS, BEAMS, AND OTHER OBSTRUCTIONS. ALIGN DIFFERENT PARTITION THICKNESSES SO THAT THE FINISHED WALL PLANES CONTINUE UNBROKEN WITHIN EACH ROOM OR CORRIDOR, UNLESS NOTED OTHERWISE. WHERE FACE OF COLUMN FURRING IS SHOWN AS ALIGNING WITH FACE OF PARTITION, CONTINUE PARTITION FACE UNBROKEN PAST THE COLUMN. STANDARD COLUMN FURRING DETAILS LOCATE PARTITION FACE.

4 WHERE GYPSUM BOARD IS NOT SCHEDULED TO EXTEND TO BOTTOM OF STRUCTURE, BOARD MAY TERMINATE 4” ABOVE ABUTTED CEILING ON EACH SIDE. IF NO CEILING IS SCHEDULED, BOARD IN THAT ROOM MUST EXTEND FULL HEIGHT.

5 WHERE PARTITIONS ARE INDICATED AS BEING FIRE-RATED, CONTINUE PARTITIONS UNBROKEN TO BOTTOM OF DECK ABOVE AND ALONG THE ENTIRE PERIMETER OF THE SPACES BEING SEPARATED BY THE FIRE-RATED PARTITIONS. CONTINUE FIRE-RATED PARTITION

SEPARATIONS WITHOUT INTERRUPTION WHERE THEY INTERSECT NON-RATED PARTITIONS.

6 WHERE COLUMNS, MECHANICAL CHASES, PIPING, AND OTHER ELEMENTS ARE LOCATED WITHIN A FIRE-RATED PARTITION, CONTINUE THE GYPSUM BOARD AROUND BOTH SIDES OF THE OBSTRUCTION TO MAINTAIN THE RATED ASSEMBLY. FOR DUCT, PIPE, CONDUIT, AND OTHER PENETRATIONS PASSING THROUGH A FIRE-RATED PARTITION, PROVIDE TIGHT FITTING FIRE-RATED STOPPING ASSEMBLIES EQUAL TO

ASSEMBLY RATING.

7 WHERE SMOKE AND FIRE-RATED PARTITIONS TERMINATE AT EXTERIOR WALLS, FILL VOIDS WITH FIRE-RATED ASSEMBLIES, OR EXTEND TO RATED PARTITIONS TO THE OUTER FACE OF EXTERIOR WALL CONSTRUCTIONS. ENSURE THAT NO FLANKING PATHWAYS EXIST THAT

MIGHT PERMIT SMOKE OR FIRE TO FLOW FROM ONE SIDE OF THE PARTITION TO THE OTHER.

8 PROVIDE CONTINUOUS STANDARD BLOCKING AS DETAILED FOR WALL MOUNTED ELEMENTS AT TOP AND BOTTOM ATTACHMENT POINTS AND AT INTERMEDIATE ATTACHMENT POINTS AS REQUIRED BY THE ELEMENT, INCLUDING, BUT NOT LIMITED TO; ACCESSORIES, RAILINGS, FLOOR-MOUNTED CASEWORK, CURTAIN RODS, WALL PROTECTION, CORNER GUARDS, AND EQUIPMENT WEIGHING LESS THAN 50 POUNDS.

9 PROVIDE HEAVY DUTY BLOCKING AS DETAILED FOR SUPPORT OF HEAVY ELEMENTS, INCLUDING, BUT NOT LIMITED TO; WALL MOUNTED SHELVING AND CABINETRY, HAND RAILS, GRAB BARS, BABY-CHANGING TABLES, LAVATORIES, COUNTER TOPS, MOUNTS FOR TELEVISIONS AND COMPUTER MONITORS, DOOR STOPS, AND EQUIPMENT WEIGHING IN EXCESS OF 50 POUNDS.

10 WHERE ACOUSTICAL INSULATION IS INDICATED FOR PARTITIONS, SEAL TOP, BOTTOM AND SIDES OF EACH FACE AND EDGE OF GYPSUM

BOARD WITH ACOUSTICAL SEALANT WHERE THE BOARD CONTACTS OTHER MATERIALS.

11 BACK-TO-BACK ELECTRICAL BOXES ARE NOT PERMITTED UNLESS BOTH BOXES ARE WRAPPED WITH ADHESIVE WRAPPED INTUMESCENT PUTTY PADS. WHERE JUNCTION, OUTLET, AND SWITCH BOXES OCCUR ON OPPOSITE SIDES OF A PARTITION, EITHER PROVIDE PUTTY PADS FOR BOTH BOXES, OR OFFSET THE BOXES A MINIMUM OF ONE STUD SPACE AND PROVIDE ACOUSTICAL INSULATION BEHIND AND

BETWEEN THEM.

12 IN FIRE-RATED PARTITIONS WITH TOTAL “BLACK BOX” PENETRATIONS IN EXCESS OF 100 SQ. IN. IN 100 SQ. FT., ADDITIONALLY PROTECT BACK OF BOXES WITH RATED ASSEMBLIES APPROVED BY THE AUTHORITY HAVING JURISDICTION.

13 PROVIDE ACOUSTICAL SEALANT AROUND ALL PENETRATIONS THROUGH THE MEMBRANES OF ACOUSTICAL PARTITIONS. PROVIDE FIRE-RATED SEALANT IN LIEU OF ACOUSTICAL SEALANT WHERE REQUIRED TO MAINTAIN FIRE RATING OF ACOUSTIC PARTITIONS.

14 IN SHOWER STALLS AND WALLS BEHIND PLUMBING FIXTURES, PROVIDE TILE BACKER BOARD IN LIEU OF GYPSUM BOARD AT WALLS INDICATED TO RECEIVE CERAMIC TILE. BACKER BOARD TO MATCH GYPSUM BOARD IN TERMS OF THICKNESS AND FIRE-RATING CAPABILITY.

PROVIDE MOISTURE RESISTANT (MR) GYPSUM BOARD IN LIEU OF STANDARD GYPSUM BOARD AT THE FOLLOWING LOCATIONS:

DIRECTLY BEHIND PLUMBING FIXTURES WHERE FINISH IS NOT CERAMIC TILE, AND CEILINGS ABOVE SHOWER STALLS.

15 AT NON-FIRE RATED, NON-ACOUSTIC PARTITIONS THAT DO NOT EXTEND TO STRUCTURE ABOVE, CONTRACTOR HAS OPTION OF EXTENDING STUDS TO STRUCTURE ABOVE OR TERMINATING STUDS 4” ABOVE HIGHEST ADJACENT CEILING AND BRACING TOP TRACK AT

INTERVALS OF 4’-0” OC (MAX) TO STRUCTURE ABOVE.

16 WHERE STUDS EXTEND MORE THAN 3’-0” ABOVE THE GYPSUM BOARD, PROVIDE HORIZONTAL BRACING MIDWAY BETWEEN TOP OF

GYPSUM BOARD AND TOP OF STUDS.

17 AT FURRING PARTITIONS (GYPSUM BOARD ONE SIDE ONLY) PROVIDE HORIZONTAL STUD BRACING OR 18 GA ANGLE CLIPS SECURED TO

STRUCTURAL SUBSTRATE AT 4’-0” OC (MAX). SIMILAR REQUIREMENT AT COLUMN FURRING.

18 MAGNITUDE OF POTENTIAL STRUCTURAL LIVE LOAD DEFLECTION IMPACTING PARTITIONS FOR THIS PROJECT IS 1/2” IN COMPRESSION AND 0” IN EXTENSION, FOR A TOTAL MOVEMENT OF 1/2”. FOR RATED PARTITIONS, THE HEAD-OF-WALL FIRE RESISTIVE ASSEMBLY PROVIDED MUST BE RATED FOR THIS DEGREE OF MOVEMENT. PROVIDE A FIRE-RESISTIVE VARIATION FOR EACH CONDITION (BEAMS, DUCTS, CORNERS, ETC.) ENCOUNTERED AT THE RATED PARTITION HEADS. FOR NON RATED PARTITIONS, SECURE THE TOP TRACK IN A

MANNER THAT ACCOMMODATES DEFLECTION OF THE STRUCTURE ABOVE OR BELOW.

19 FOR DOORS, RELITES, DUCT, AND OTHER OPENINGS WITH ROUGH OPENING DIMENSIONS OF 4’-0” OR WIDER, PROVIDE HEAVY GAUGE KING

STUDS AND A “BOX BEAM” HEADER AS DETAILED IN STANDARD OPENING HEADER DETAILS.

20 PARTITION TYPE IS TO BE B_4a UNO.

TYPICAL PARTITION NOTESPARTITION TYPES CONSTRUCT PER LISTED UL DESIGN NO. OR EQUIVALENT UL DESIGN

EQUIPMENT MOUNTING LEGEND PARTITION PLAN LEGEND

DRAFTING SYMBOLS

STRUCTURAL ENGINEER

BERNHARD TME

BUILDING 2, 1 ALLIED DRIVE

SUITE 2600

LITTLE ROCK, AR 72202

MEP ENGINEER

INSIGHT ENGINEERING, PLLC

201 S. CHESTER, SUITE B

LITTLE ROCK, AR 72201

FIRE PROTECTION

FP&C CONSULTANTS KC, LLC

1330 BURLINGTON STREET, STE. 200

NORTH KANSAS CITY, MO 64116

U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

Drawing Title

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Building Number

Drawing Number

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

VA FORM 08 - 6231

CONSTRUCTION DOCUMENTS

CONSULTANTS

Revs: Date:

BUSINESS OCCUPANCY

SPRINKLERED

9/

/2

4:

:1

PM

C :\U se rs

\e w ui \D oc um en ts

\L O

C

AL

\5

-1 9-

7_

R en ov B ui ld in g

4-

LE

TC

_A R

C H

_e st he r.w ui .rv t

STANDARD ABBREVIATIONS CONSTRUCTION

DOCUMENTS

RENOVATE BUILDING 104 - LETC

FORT ROOTS, NORTH LITTLE ROCK

2021.09.30 JDa JDa

598-19-127

GI003

JDA PROJECT #: 2018.001

A/E

2200 N. RODNEY PARHAM ROAD

SUITE 210

LITTLE ROCK, AR 72212

501-404-4811 jda@JohnsonDanforth.com

JohnsonDanforth & Associates

SJI STEEL JOIST SLIDING WINDOW

SK SKETCH

SKLT SKYLIGHT

SLD WDW HORIZONTAL SLIDING WINDOW

SLDG SLIDING

SLNT SEALANT

SM SHEET METAL

SMK SMOKE

SMS SHEET METAL SCREW

SND SANITARY NAPKIN DISPENSER

SND INS SOUND INSULATION

SNDU SANITARY NAPKIN DISPOSAL

UNIT

SPEC SPECIFICATION

SPKLR SPRINKLER

SPKR SPEAKER

SPLY SUPPLY

SQ SQUARE

SQ IN SQUARE INCH

SQ YD SQUARE YARD

SS SANITARY SEWER OR SERVICE

SINK

SST STAINLESS STEEL

ST STAIRS OR STREET

STC SOUND TRANSMISSION

CLASSIFICATION

STIF STIFFENER

STL STEEL

STL JST STEEL JOIST

STL LNTL STEEL LINTEL

STL PL STEEL PLATE

STL RF DK STEEL ROOF DECK

STL TB STEEL TUB

STL TR STEEL TRUSS

STNLS STAINLESS

STOR STORAGE

STR STRINGERS

STRUCT STRUCTURAL

STRUCT

STL

STRUCTURAL STEEL

SUB SUBSTITUTE

SURF SURFACE

SUSP SUSPENDED

SUSP CLG SUSPENDED CEILING

SV SHEET VINYL

SW SWITCH

SWDR SWING DOOR

SYM SYMBOL

SYNTH SNTHETIC

SYS SYSTEM

T

T TREAD

T&G TONGUE AND GROOVE

T&M TIME AND MATERIALS

TB THROUGH BOLT OR TOWEL BAR

TCA TILE COUNCIL OF AMERICA

TCP TELEPHONE CONTROL PANEL,

TEMPERATURE CONTROL PANEL,

OR TRAFFIC CONTROL PLAN

TD TOWEL DISPENSER

TECH TECHNICAL

TEL TELEPHONE

TEMP TEMPERATURE OR TEMPORARY

TER TERRAZZO

THD THREAD

THERM THERMAL

THK THICKNESS

THRES THRESHOLD

THRU THROUGH

THRUOUT THROUGHOUT

TK BD TACKBOARD

TLT TOILET

TMPD TEMPERED

TMPD GL TEMPERED GLASS

TN TRUE NORTH

TO TOP OF ______

TO FDN TOP OF FOUNDATION

TOB TOP OF BEAM

TOM TOP OF MASONRY

TOP TOP OF PARAPET

TOS TOP OF STEEL

TYP TYPICAL

U

U.N.O. UNLESS NOTED OTHERWISE

U.O.N. UNLESS OTHERWISE NOTED

V

VC VA FURNISHED / CONTRACTOR

INSTALLED

VCT VINYL COMPOSITION TILE OR

VITRIFIED CLAY TILE

VENT VENTILATION

VERT VERTICAL

VIF VERIFY IN FIELD

VV VA FURNISHED / VA INSTALLED

W

W/ WITH

WD WOOD

WP WALL PROTECTION

QTR QUARTER

QTY QUANTITY

QUAD QUADRANT

QUAL QUALITY

R

R RADIUS OR RISER

RA RETURN AIR

RA RETURN AIR

RAD RADIATOR

RB RESILIENT BASE OR RUBBER

BASE

RB HK ROBE HOOK

RBM REINFORCED BRICK MASONRY

RBR RUBBER

RC REMOTE CONTROL

RCP REFLECTED CEILING PLAN

RCVR RECEIVER

RD ROAD OR ROOF DRAIN

REC RECESSED

RECD RECEIVED

RECPT RECEPTACLE

RECT RECTANGLE

REF REFERENCE OR REFRIGERATOR

REFR REFRACTORY REFRIGERATION

OR REFRIGERATION

REFRACTORY

REG REGISTER

REINF REINFORCE, REINFORCED, OR

REINFORCING

REP REPAIR

REPL REPLACE

REQ REQUIRE

REQD REQUIRED

RESIL RESILIENT

RET RETURN

REV REVISION

RF RADIO FREQUENCY

RFG ROOFING

RFI REQUEST FOR INFORMATION

RFP REQUEST FOR PROPOSAL

RH RIGHT HAND

RHMS ROUND HEAD MACHINE SCREW

RHR RIGHT HAND REVERSE

RHWS ROUND HEAD WOOD SCREW

RL ROOF LEADER

RLG RAILING

RM ROOM

RND ROUND

RO ROUGH OPENING

ROW RIGHT OF WAY

RPM REVOLUTIONS PER MINUTE

RS ROUGH SAWN

RT RIGHT

RV ROOF VENT

RVS REVERSE

RWD REDWOOD

RWL RAIN WATER LEADER

S

SA SUPPLY AIR

SALV SALVAGE

SAMP SAMPLE

SAN SANITARY

SAT SUSPENDED ACOUSTICAL TILE

SATC SUSPENDED ACOUSTICAL TILE

CEILING

SB SPLASH BLOCK

SBS STYRENE BUTADIEN STYRENE

SBSTR SUBSTRATE

SC SHADING COEFFICIENT OR SOLID

CORE

SCH SCHOOL

SCHED SCHEDULE, SCHEDULED

SCHEM SCHEMATIC

SCP SCUPPER

SCRN SCREEN

SCT STRUCTURAL CLAY TILE

SCWD SOLID CORE WOOD DOOR

SD SHOP DRAWINGS, SMOKE

DETECTOR, OR SOAP DISPENSER

SDG SIDING

SECT SECTION

SEG SEGMENT

SEL SELECT

SEP SEPARATE

SF SQUARE FOOT (FEET)

SFTWD SOFTWOOD

SGD SLIDING GLASS DOOR

SGL SINGLE

SHR SHOWER

SHR HD SHOWER HEAD

SHRD SHOWER DRAIN

SHT SHEET

SHT MTL

FLASH

SHEET METAL (FLASHING)

SHTHG SHEATHING

SIM SIMILAR

SJ SCORED JOINT

SJ SCORED JOINT

NS NARROW STILE

NUM NUMERAL

O

O OXYGEN

O/H OVER HEAD

O/O OUT TO OUT

OA OUTSIDE AIR OR OVERALL

OC ON CENTER

OCC OCCUPY

OCT OCTAGON

OD OUTSIDE DIAMETER OR OUTSIDE

DIMENSION

OFD OVERFLOW DRAIN

OFF OFFICE

OH OVERHANG

OH DR OVERHEAD (COILING) DOOR

OPH OPPOSIE HAND

OPNG OPENING

OPP OPPOSITE

OPR OPERABLE

OPT OPTIONAL

OR OPERATING ROOM OR OUTSIDE

RADIUS

ORD ORDNANCE OR OVERFLOW ROOF

DRAIN

ORG ORGANIC

ORIG ORIGINAL

ORN ORNAMENTAL

OSHA OCCUPATIONAL SAFETY AND

HEALTH ADMINISTRATION

OUT OUTLET

OZ OUNCE

P

PAR PARALLEL OR PARAPET

PARA PARAGRAPH

PART PARTIAL

PAT PATTERN

PB PUSHBUTTON

PBD PARTICLEBOARD

PC PIECE, POLYCARBONATE OR

PORTLAND CEMENT

PCA PORTLAND CEMENT

ASSOCIATION

PCC PRECAST CONCRETE

PCCP CONCRETE PAVEMENT

PCD PAPER CUP DISPENSER

PCF POUNDS PER CUBIC FOOT

PCP PORTLAND CEMENT PLASTER

PED PEDESTAL

PEN PENETRATE

PEND PENDANT

PERF PERFORATED

PERIM PERIMETER

PERP PERPENDICULAR

PGBD PEGBOARD

PHAR PHARMACY

PHOTO PHOTOGRAPH

PHS PHILLIPS HEAD SCREW

PKG PACKAGE

PL PROPERTYLINE

PL GL PLATE GLASS

PLAM PLASTIC LAMINATE

PLAS PLASTER OR PLASTIC

PLBG PLUMBING

PLYWD PLYWOOD

PMTL PAINTED METAL

PNEU PNEUMATIC

PNL PANEL

PO POST OFFICE PURCHASE ORDER

OR PURCHASE ORDER POST

OFFICE

POLY POLYETHYLENE (PLASTIC)

PR PAIR

PRCST PRECAST

PREFAB PREFABRICATE

PREFIN PREFINISH

PRELIM PRELIMINARY

PREP PREPARATION

PRESS PRESSURE

PREV PREVIOUS

PRKG PARKING

PRMLD PREMOLDED

PROJ PROJECT

PROP PROPERTY

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT PAINT, PNEUMAIC TUBE, OR

PRESSURE TREATED

PTD PAPER TOWEL DISPENSER

PTN PARTITION

PVC POLYVINYL CHLORIDE (PLASTIC)

PVG PAVING

PWR POWER

Q

QA QUALITY ASSURANCE

QC QUALITY CONTROL

QRY QUARRY

QT QUARRY TILE OR QUART

QTB QUARRY TILE BASE

QTF QUARRY TILE FLOOR

LMST LIMESTONE

LNDSCP LANDSCAPE

LR LIVING ROOM

LRG LARGE

LRV LOUVERED ROOF VENT

LS LUMP SUM

LT LIGHT

LT GA LIGHT GAGE

LT WT LIGHTWEIGHT

LTG LIGHTING

LTNG LIGHTNING

LVD LOUVERED

LVR LOUVER

LWC LIGHTWEIGHT CONCRETE

LWIC LIGHTWEIGHT INSULATING

CONCRETE

LYR LAYER

M

MACH MACHINE

MACH RM MACHINE ROOM

MAINT MAINTAIN, MAINTENANCE

MAN MANUAL

MATL MATERIAL

MATV MASTER ANTENNA TELEVISION

SYSTEM

MAX MAXIMUM

MB MACHINE BOLT

MCB METAL CORNER BEAD

MD DECK

ME MECHANICAL ENGINEER

MEAS MEASURE

MECH MECHANICAL

MECH RM MECHANICAL ROOM

MED MEDICAL MEDIUM O MEDIUM

MEDICAL

MEK METHYL ETHYL KETONE

MEL MELAMINE

MEMBO MEMORANDUM

MEZZ MEZZANINE

MF MILL FINISH

MFD MANUFACTURED

MFG MANUFACTURING

MFR MANUFACTURER

MFR REC MANUFACTURER'S

RECOMMENDATION

MGT MANAGEMENT

MH MANHOLE

MIC MICROPHONE

MID MIDDLE

MIL STD MILITARY STANDARD

MIN MINIMUM

MIN MINIMUM MINUTE OR MINUTE

MINIMUM

MIRR MIRROR

MISC MISCELLANEOUS

MISC MISCELLANEOUS

MIT MITER

MKR MARKER

ML METAL LATH

MLDG MOLDING (MOULDING)

MLWK MILLWORK

mm MILLIMETER

MO MASONRY OPENING OR MOTOR

OPERATED

MOD MODEL, MODIFY OR MODULE

MOD BIT MODIFIED BITUMEN

MON MONITOR

MOPR MOP RACK

MR MOISTURE RESISTANT

MS MACHINE SCREW OR MOP SINK

MTD MOUNTED

MTG MOUNTING

MTL METAL

MULL MULLION

MW MICROWAVE

MWP MEMBRANE WATERPROOFING

N

N NORTH

NA NOT APPLICABLE

NAAMM NATIONAL ASSOCIATION OF

ARCHITECTURAL METAL

MANUFACTURERS

NAT NATURAL

NATL NATIONAL

NC NOISE CRITERIA

NCOMBL NONCOMBUSTIBLE

NEC NATIONAL ELECTRICAL CODE

NEG NEGATIVE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NEUT NEUTRAL

NFC NATIONAL FIRE CODE

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NR NOISE REDUCTION

NRC NOICE REDUCTION COEFFICIENT

NRCA NATIONAL ROOFING

CONTRACTORS ASSOCIATION

NRP NONREMOVABLE

H HIGH

H PLAM HIGH PRESSURE PLASTIC

LAMINATE

HAZ MAT HAZARDOUS MATERIALS

HB HOSE BIBB

HC HOLLOW CORE

HCWD HOLLOW CORE WOOD DOOR

HDBD HARDBOARD

HDNR HARDENER

HDO HIGH DENSITY OVERLAY

HDR HEADER

HDW HARDWARE

HDWD HARDWOOD

HEPA HIGH EFFICIENCY PARTICULATE

AIR (FILTER)

HEX HEXAGON

HF HIGH FREQUENCY

HGR HANGAR

HM HOLLOW METAL OR

HECTOMETER

HMD HOLLOW METAL DOOR

HMDF HOLLOW METAL DOOR AND

FRAME

HMF HOLLOW METAL FRAME

HNDRL HANDRAIL

HO HOLD OPEN

HORIZ HORIZONTAL

HOSP HOSPITAL

HP HIGH PRESSURE OR

HORSEPOWER

HQ HEADQUARTERS

HR HOUR

HRS HOURS

HS HEAT-STRENGTHENED (GLASS)

OR HIGH STRENGTH

HSE HOUSE

HSKPG HOUSEKEEPING

HST HOIST

HT HEIGHT

HVAC HEATING, VENTILATION, AND AIR

CONDITIONING

HVY HEAVY

HW HOT WATER

HYD HYDRANT

HYDR HYDRAULIC

I

I INTERSTATE (HIGHWAY) OR

MOMENT OF INERTIA

IAQ INDOOR AIR QUALITY

IBC INTERNATIONAL BUILDING CODE

ID IDENTIFICATION, INSIDE

DIAMETER, OR INTERIOR DESIGN

ID NO IDENTIFICATION NUMBER

ILLUM ILLUMINATION

INCL INCLUDED

IND INDEPENDENT OR INDUSTRIAL

INFO INFORMATION

INSUL INSULATED, INSULATION

INT INTERIOR

INTERCOM INTERCOMMUNICATION

INTL INTERNATIONAL

IRMA INVERTED ROOF MEMBRANE

ASSEMBLY

IWH INSTANANEOUS WATER HEATER

J

J-BOX JUNCTION BOX

JAN JANITOR

K

KD KILN DRIED OR KNOCKED DOWN

KIT KITCHEN

KO KNOCKOUT

KPL KICKPLATE

L

L ANGLE

LAB LABORATORY

LAD LADDER

LAM LAMINATE

LAM GL LAMINATED GLASS

LAU LAUNDRY

LAV LAVATORY

LBR LUMBER

LBS POUND

LD BRG LOAD-BEARING

LDR LEADER

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LH LEFT HAND

LHR LEFT HAND REVERSE OR LATENT

HEAT RATIO

LIB LIBRARY

LIN LINEAR

LINO LINOLEUM

LIQ LIQUID

LKR LOCKER

LKR RM LOCKER ROOM

LKWASH LOCKWASHER

LL LEAD LINED

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

FAC FACTOR

FACIL FACILITY

FAS FASCIA

FAS BD FASCIA BOARD

FCO FLOOR CLEANOUT

FCTY FACTORY

FD FLOOR DRAIN

FDC FIRE DEPARTMENT CONNECTION

FDTN FOUNDATION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FF FINISH FACE

FF EL FINISH FLOOR ELEVATION

FF&E FURNITURE, FIXTURE, AND

EQUIPMENT

FH FLAT HEAD OR FLAT HEAD

SCREWS

FHC FIRE HOSE CABINET

FHMS FLAT HEAD MACHINE SCREW

FHP FULL HEIGHT PARTITION

FHWS FLAT HEAD WOOD SCREW

FIG FIGURE

FIL FILLET

FIN FINISH

FIN FLR FINISH FLOOR

FIN GR FINISH GRADE

FIN WD FINISH WOOD

FIXT FIXTURE

FL FLOORLINE

FLASH FLASHING

FLDG FOLDING

FLEX FLEXIBLE

FLG FLOORING

FLR FLOOR

FLR FIN FLOOR FINISH

FLR SK FLOOR SINK

FLUOR FLUORESCENT

FLUOR FIX FLUORESCEN FIXTURE

FM FACTORY MUTUAL

FM-G FACTORY MUTUAL GLOBAL

FO FINISHED OPENING

FOC FACE OF CONCRETE OR FACE OF

CURB

FOF FACE OF FINISH

FOM FACE OF MASONRY

FOS FACE OF SLAB OR FACE OF CURB

FOUNT FOUNTAIN

FOW FACE OF WALL

FP FIRE PROTECTION OR

FIREPROOF OR FLAT PANEL

DOOR

FPM FEET PER MINUTE

FPS FEET PER SECOND

FR FIRE RATING, FIRE RESISTANT,

OR FRAME

FR SNK FLUSHING RIM SINK

FREQ FREQUENCY

FRMG FRAMING

FRP FIBER REINFORCED POLYESTER

OR FIBERGLASS REINFORCED

PLASTIC

FRZ FREEZER

FS FEDERAL SPECIFICATION

FSTNR FASTENER

FT FEET OR FOOT

FTG FOOTING

FURG FURRING

FURN FURNISH OR FURNITURE

FUT FUT

FWC FABRIC WALL COVERING

G

GA GAGE OR GYPSUM ASSOCIATION

GAL GALLON, GALLONS

GALV GALVANIC OR GALVANIZED

GALV STL GALVANIZED STEEL

GB GRAB BAR

GC GENERAL CONTRACTOR

GD GUARD

GDR GUARD RAIL

GEN GENERAL OR GENERATOR

GFRC GLASS-FIBER-REINFORCED

GFRG GLASS-FIBER-REINFORCED

GFRP GLASS-FIBER-REINFORCED

PLASTIC

GI GALVANIZED IRON

GL GLASS

GL BLK GLASS BLOCK

GLU LAM GLUED LAMINATED WOOD

GR FL GROUND FLOOR

GRAN GRANITE

GRTG GRATING

GSB GYPSUM SHEATHING BOARD

GSM GALVANIZED SHEET METAL

GSU GLAZED STRUCTURAL UNIT

GT GROUT

GUAR GUARANTEE

GUT GUTTER

GYP GYPSUM

GYP BD GYPSUM BOARD

GYP PLAS GYPSUM PLASTER

H

CTR CENTER CONTOUR

CTRL CONTROL

CTV CABLE TELEVISION

CU COPPER C

CU FT CUBIC FEET

CU IN CUBIC INCH

CU YD CUBIC YARD

CURT CURTAIN

CYL CYLINDER

CYL L CTLINDER LOCK

D

D DEPTH OR PENNY (NAIL)

D LABEL CLASS D DOOR

DAT DATUM

DB DECIBEL

DBL DOUBLE

DBL GLZ DOUBLE GLAZE

DC DIRECT CURRENT

DEG DEGREE

DEL DELETE

DEMO DEMOLITION

DEPT DEPARTMENT

DET DETAIL

DF DRINKING FOUNTAIN

DIA DIAMETER

DIAG DIAGONAL DIAGRAM OR

DIAGRAM DIAGONAL

DIFF DIFFERENCE OR DIFFUSER

DIM DIMENSION

DIR DIRECTION

DISP DISPENSER

DIST DISTANCE

DIV DIVIDE OR DIVISION

DL DEAD LOAD

DOC DOCUMENT

DOUG FIR DOUGLAS FIR

DOZ DOZEN

DR DOOR, DRAIN, DRESSING ROOM,

OR DRIVE

DR CL DOOR CLOSER

DR FR DOOR FRAME

DR OPNG DOOR OPENING

DS DOWNSPOUT

DSGN DESIGN

DW DISHWASHER

DWG DRAWING

DWTR DUMBWAITER

E

E EAST

E LABEL CLASS E DOOR

EA EACH

EFF EFFICIENCY

EFS EXTERIOR FINISH SYSTEM

EIFS EXTERIOR INSULATION AND

FINISH SYSTEM

EJ EXPANSION JOINT

EL ELEVATION

ELAST ELASTOMERIC

ELEC ELECTRIC, ELECTRICAL

ELEC DR

OP

ELECTRIC DOOR OPENER

ELEV ELEVATOR

ELEVS ELEVATIONS

EMER EMERGENCY

EMER SHR EMERGENCY SHOWER

ENCL ENCLOSURE

ENGR ENGINEER

ENVIR ENVIRONMENT

EPA ENVIRONMENTAL PROTECTION

AGENCY

EPDM ETHYLENE PROPYLENE DIENE

EPO EMERGENCY POWER OFF

EPS EXPANDED POLYSTYRENE

BOARD (INSULATION)

EQ EQUAL

EQL SP EQUALLY SPACED

EQUIP EQUIPMENT

EQUIV EQUIVALENT

ERD EXISTING ROOF DRAIN

ESC ESCAPE OR ESCUTCHEON

ESCAL ESCALATOR

ESMT EASEMENT

ESP ESPECIALLY

EST ESTIMATE

ETC AND SO FORTH OR ET CETERA

EW EACH WAY

EWC ELECTRIC WATER COOLER

EWS EYE WASH STATION

EXH EXHAUST

EXIST EXISTING

EXP EXPANSION OR EXPOSED

EXP BT EXPANSION BOLT

EXST GR EXISTING GRADE

EXT EXTERIOR, EXTERNAL, OR

EXTINGUISHER

EXT GR EXTERIOR GRADE

F

F FAHRENHEIT OR FEMALE

FA FIRE ALARM

FAB FABRIC

BOT BOTTOM

BR BEDROOM

BRCG BRACING

BRDG BRIDGING

BRDG JST BRIDGING JOIST

BRG BEARING

BRG PL BEARING PLATE

BRKT BRACKET

BRZ BRONZE

BSMT BASEMENT

BTWN BETWEEN

BU BUSHEL

BUR BUILT-UP ROOFING

C

C CELSIUS CHANNEL OR CHANNEL

CELSIUS

C CONC CAST CONCRETE

C LABEL CLASS C DOOR

C TO C CENTER TO CENTER

C/C CONTRACTOR FURNISHED/

CONTRACTOR INSTALLED

C/VA CONTRACTOR FURNISHED/

GOVERNMENT INSTALLED

CAB CABINET

CAC CEILING ATENUATION CLASS

CB CATCH BASIN OR CORNER BEAD

CBB CEMENTITIOUS (BACKER) BOARD

CC CUBIC CENTIMETER

CCTV CLOSED CIRCUIT TELEVISION

CCW COUNTERCLOCKWISE

CD CONSTRUCTION DOCUMENTS OR

CONTRACT DOCUMENTS

CEM CEMENT, CEMENTITIOUS

CEM PLAS CEMENT PLASTER

CER CERAMIC

CF CONTRACTOR FURNISHED

CFLG COUNTERFLASHING

CFM CUBIC FEET PER MINUTE

CFMF COLD-FORMED METAL FRAMING

CFS CUBIC FEET PER SECOND

CG CENTER OF GRAVITY OR

CORNER GUARD

CGSFU CERAMIC GLAZED STRUCTURAL

FACING UNITS

CH BD CHALKBOARD

CHEM CHEMICAL

CHFR CHAMFER

CHK CHECK

CI CAST IRON

CIP CAST-IN-PLACE

CIR CIRCLE

CIRC CIRCULATING, CIRCULAR

CIRC CIRCULAR

CJ CONSTRUCTION JOINT OR

CONTROL JOINT

CL CENTER LIINE

CLDG CLADDING

CLG CEILING

CLG HT CEILING HEIGHT

CLR CLEAR

CM CONSTRUCTION MANAGEMENT

cm2 SQUARE CENTIMETER cm3 CUBIC CENTIMETER

CMU CONCRETE MASONRY UNIT

CNR CORNER

CNTR COUNTER

CO CARBON MONOXIDE,

CERTIFICATE OF OCCUPANCY,

CLEAN OUT, OR COMPANY

co2 CARBON DIOXIDE

COL COLUMN

COM COMMON

COMB COMBINAION, COMBINED

COMM COMMUNICATION

COMP COMPONENT

CONC CONCRETE

CONC FLR CONCRETE FLOOR

COND CONDENSER OR CONDITION

CONF CONFERENCE

CONN CONNECTION

CONSTR CONSTRUCTION

CONT CONTINUOUS, CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

COR COORDINATION OFFICER

CORR CORRIDOR

CPM CRITICAL PATH METHOD

CPRS COMPRESSIBLE

CPT CARPET

CRS COLD ROLLED STEEL

CRSI CONCRETE REINFORCING STEEL

CSB CONCRETE SPLASH BLOCK

CSG CASING

CSI CONSTRUCTION SPECIFICATIONS

INSTITUTE

CSK COUNTER SUNK

CSMT CASEMENT

CSWK CASEWORK

CT CERAMIC TILE

CTB CERAMIC TILE BASE

CTF CERAMIC TILE FLOOR

CTG COATING

A

A LABEL CLASS A DOOR

A/C AIR CONDITIONING

A/C UNIT AIR CONDITIONING UNIT

A/E ARCHITECT/ENGINEER

AAMA AMERICAN ARCHITECTURAL

MANUFACTURERS ASSOCIATION

AB ANCHOR BOLT

ABA ARCHITECTURAL BARRIERS ACT

ABC AGGREGATE BASE COURSE

AC ASBESTOS CEMENT OR

ASPHALTIC CONCRETE

ACI AMERICAN CONCRETE INSTITUTE

ACS DR ACCESS DOOR

ACS FLR ACCESS FLOOR

ACS PNL ACCESS PANEL

ACST ACOUSTIC

ACT ACOUSTICAL CEILING TILE

AD AREA DRAIN

ADA AMERICANS WITH DISABILITIES

ACT

ADB AUTOMATIC DOOR BOTTOM

ADC AUTOMATIC DOOR CLOSER

ADDL ADDITIONAL

ADDN ADDITION

ADH ADHESIVE

ADJ ADJACENT, ADJOINING, OR

ADJUSTABLE

ADMIN ADMINISTRATION

AFC ABOVE FINISHED COUNTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFS ABOVE FINISHED SLAB

AGA AMERICAN GAS ASSOCIATION,

ASSOCIATED GENERAL

CONTRACTORS

AGGR AGGREGATE

AHJ AUTHORITY HAVING JURISDICION

AHR ANCHOR

AHU AIR HANDLING UNIT

AIA AMERICAN INSTITUTE OF

ARCHITECTS

AISC AMERICAN INSTITUTE OF STEEL

CONSTRUCTION

ALT ALTERNATE, ALTERNATIVE

ALT NO ALTERNATE NUMBER

ALUM ALUMINUM

AMP AMPERE

AMT AMOUNT

ANOD ANODIZE

ANSI AMERICAN NATIONAL

STANDARDS INSTITUTE

ANT ANTENNA

APA AMERICAN PLAYWOOD

ASSOCIATION

APPD APPROVED

APPROX APPROXIMATE, APPROXIMATELY

APT APARTMENT

AR AS REQUIRED

ARCH ARCHITECT, ARCHITECTURAL

ASB ASBESTOS

ASI ARCHITECT'S SUPPLEMENTAL

INSTRUCTION

ASKLR AUOMATIC SPRINKLER

ASPH ASPHALT

ASSN ASSOCIATION

ASTM AMERICAN SOCIETY FOR

TESTING AND MATERIALS

ATCH ATTACHMENT

ATM AUTOMATIC TELLER MACHINE

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO-VISUAL

AVE AVENUE

AVG AVERAGE

AW ACID WASTE

AWI ARCHITECTURAL

WOODWORKING INSTITUTE

AWPA AMERICAN WOOD PRESERVERS'S

ASSOCIATION

AWS AMERICAN WELDING SOCIETY

AWT ACOUSTICAL WALL TREATMENT

B

B LABEL CLASS B DOOR

B PL BASE PLATE

BALC BALCONY

BAT BATTEN

BB BULLETIN BOARD

BD BOARD

BD FT BOARD FEET (FOOT)

BEV BEVEL

BHMA BUILDER'S HARDWARE

MANUFACTURER'S ASSOCIATION

BI FLD DR BIFOLDING DOORS

BITUM BITUMINOUS

BKG BACKING

BLD BUILD

BLDG BUILDING

BLKG BLOCKING

BLKT BLANKET

BLVD BOULEVARD

BM BEAM OR BENCHMARK

STRUCTURAL ENGINEER

BERNHARD TME

BUILDING 2, 1 ALLIED DRIVE

SUITE 2600

LITTLE ROCK, AR 72202

MEP ENGINEER

INSIGHT ENGINEERING, PLLC

201 S. CHESTER, SUITE B

LITTLE ROCK, AR 72201

FIRE PROTECTION

FP&C CONSULTANTS KC, LLC

DN

FD

FD

DN

DN

UP

FD

FD

EXISTING CRAWL SPACE HATCH

ELEVATED FROM FLOOR

15' - 3"

33' - 7"

NEW COLUMNS;

REFER TO SF101

215 SF

STORAGE

467 SF

EQUIPMENT

ROOM

3018 SF

CRAWL SPACE

B B

141 SF

OFFICE

142 SF

OFFICE

142 SF

OFFICE

8 SF

CLOSET

212B

112 SF

TELE EQUIP

20 SF

CLOSET

212C

8 SF

CLOSET

212A

31 SF

STORAGE

139 SF

MEN'S

RESTROOM

214 107 SF

WOMEN'S

RESTROOM

7 SF

JANITOR

215A

4 SF

CLOSET

216B

140 SF

GUEST ROOM

3 SF

CLOSET

217B

141 SF

GUEST ROOM

141 SF

OFFICE

141 SF

OFFICE

142 SF

OFFICE

143 SF

OFFICE

125 SF

OFFICE

CONFERENCE

ROOM

203 9 SF

CLOSET

201B

140 SF

GUEST ROOM

6 SF

CLOSET

200B

140 SF

GUEST ROOM

602 SF

CORRIDOR

142 SF

STAIRS

9 SF

CLOSET

209A

9 SF

CLOSET

209B

5 SF

CLOSET

210A

4 SF

CLOSET

210B

9 SF

CLOSET

211A

4 SF

CLOSET

211B

8 SF

CLOSET

208A

10 SF

CLOSET

207B

5 SF

CLOSET

207A

8 SF

CLOSET

208B

6 SF

CLOSET

205B

9 SF

CLOSET

205A

5 SF

CLOSET

206A

9 SF

CLOSET

206B

9 SF

CLOSET

204A

11 SF

CLOSET

201A

10 SF

CLOSET

200A

10 SF

CLOSET

217A

5 SF

CLOSET

216A

DEPARTMENTAL USE PLAN

CIRCULATION

RESTROOM

STAFF

STORAGE

UTIL/MEP

A A

B B

1 2

332 SF

CHASE

C H

AS

E

C O

U N

TE

R

COUNTER

221 SF

CORRIDOR

115A

162 SF

OFFICE

154 SF

STORAGE

6 SF

CLOSET

109A 167 SF

WORKROOM

115B

154 SF

OFFICE

9 SF

CLOSET

111B 142 SF

STAIRS

144 SF

MEN'S

RESTROOM

106 SF

WOMEN'S

RESTROOM

243 SF

CORRIDOR

27 SF

IT / STORAGE

194 SF

TRAINING

24 SF

MECH

104A

30 SF

STORAGE

103A

96 SF

FOYER

100A

47 SF

ENTRY

151 SF

PRINTER ROOM

155 SF

DIRECTOR

150 SF

OFFICE

9 SF

CLOSET

106A

833 SF

TRAINING ROOM

149 SF

LAUNDRY

8 SF

CLOSET

107A

R 2' - 9"

A A

B B

1 2

78 SF

SUPPLY

104B

U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

Drawing Title

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Building Number

Drawing Number

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

VA FORM 08 - 6231

CONSTRUCTION DOCUMENTS

CONSULTANTS

Revs: Date:

BUSINESS OCCUPANCY

SPRINKLERED

9/

/2

4:

:1

PM

DEPARTMENTAL USE PLAN CONSTRUCTION

DOCUMENTS

RENOVATE BUILDING 104 - LETC

FORT ROOTS, NORTH LITTLE ROCK

2021.09.30 TS EW

598-19-127

GI004

JDA PROJECT #: 2018.001

A/E

2200 N. RODNEY PARHAM ROAD

SUITE 210

LITTLE ROCK, AR 72212

501-404-4811 jda@JohnsonDanforth.com

JohnsonDanforth & Associates

STRUCTURAL ENGINEER

BERNHARD TME

BUILDING 2, 1 ALLIED DRIVE

SUITE 2600

LITTLE ROCK, AR 72202

MEP ENGINEER

INSIGHT ENGINEERING, PLLC

201 S. CHESTER, SUITE B

LITTLE ROCK, AR 72201

FIRE PROTECTION

FP&C CONSULTANTS KC, LLC

1330 BURLINGTON STREET, STE. 200

NORTH KANSAS CITY, MO 64116

3/16" = 1'-0"B1 BASEMENT DEPARTMENTAL USE PLAN

3/16" = 1'-0"F1 SECOND LEVEL DEPARTMENTAL USE PLAN

3/16" = 1'-0"D1 FIRST LEVEL DEPARTMENTAL USE PLAN

SCALE: 3/16" = 1'-0"

0 2'-8" 5'-4" 10'-8"

SPACE DESIGN MATRIX

NUMBER NAME Department

TIL ROOM

CODE

PROVIDED

AREA

GROUND LEVEL ICRA PLAN

001 STORAGE STORAGE SRS01 215 SF

002 EQUIPMENT ROOM UTIL/MEP SRSE1 467 SF

003 CRAWL SPACE UTIL/MEP N/A 3018 SF

3 3701 SF

FIRST LEVEL

100 ENTRY CIRCULATION N/A 47 SF

100A FOYER CIRCULATION N/A 96 SF

101 STAIRS CIRCULATION N/A 142 SF

102 JANITOR'S CLOSET UTIL/MEP JANC1 10 SF

103 TRAINING ROOM STAFF CRA1 833 SF

103A STORAGE STORAGE SRS01 30 SF

104 TRAINING STAFF CRA1 194 SF

104A MECH UTIL/MEP N/A 24 SF

104B SUPPLY STORAGE SRS01 78 SF

105 PRINTER ROOM STAFF RPR01 151 SF

106 OFFICE STAFF OFA09 150 SF

106A CLOSET STORAGE SRS01 9 SF

107 LAUNDRY STAFF NULR1 149 SF

107A CLOSET STORAGE SRS01 8 SF

108 OFFICE STAFF OFA09 162 SF

109 STORAGE STORAGE SRS01 154 SF

109A CLOSET STORAGE SRS01 6 SF

110 DIRECTOR STAFF OFA09 155 SF

111 OFFICE STAFF OFA09 154 SF

111B CLOSET STORAGE SRS01 9 SF

112 IT / STORAGE STORAGE SRS01 27 SF

113 MEN'S RESTROOM RESTROOM TLTS1 144 SF

114 WOMEN'S RESTROOM RESTROOM TLTS1 106 SF

115 CORRIDOR CIRCULATION N/A 243 SF

115A CORRIDOR CIRCULATION N/A 221 SF

115B WORKROOM STAFF WRCH1 167 SF

26 3471 SF

SECOND LEVEL

200 GUEST ROOM STAFF OFA09 140 SF

200A CLOSET STORAGE SRS01 10 SF

200B CLOSET STORAGE SRS01 6 SF

201 GUEST ROOM STAFF OFA09 140 SF

201A CLOSET STORAGE SRS01 11 SF

201B CLOSET STORAGE SRS01 9 SF

203 OFFICE STAFF OFA09 332 SF

204 OFFICE STAFF OFA09 125 SF

204A CLOSET STORAGE SRS01 9 SF

205 OFFICE STAFF OFA09 143 SF

205A CLOSET STORAGE SRS01 9 SF

205B CLOSET STORAGE SRS01 6 SF

206 OFFICE STAFF OFA09 142 SF

206A CLOSET STORAGE SRS01 5 SF

206B CLOSET STORAGE SRS01 9 SF

207 OFFICE STAFF OFA09 141 SF

207A CLOSET STORAGE SRS01 5 SF

207B CLOSET STORAGE SRS01 10 SF

208 OFFICE STAFF OFA09 141 SF

208A CLOSET STORAGE SRS01 8 SF

208B CLOSET STORAGE SRS01 8 SF

209 OFFICE STAFF OFA09 141 SF

209A CLOSET STORAGE SRS01 9 SF

209B CLOSET STORAGE SRS01 9 SF

210 OFFICE STAFF OFA09 142 SF

210A CLOSET STORAGE SRS01 5 SF

210B CLOSET STORAGE SRS01 4 SF

211 OFFICE STAFF OFA09 142 SF

211A CLOSET STORAGE SRS01 9 SF

211B CLOSET STORAGE SRS01 4 SF

212 TELE EQUIP UTIL/MEP COMC1 112 SF

212A CLOSET STORAGE SRS01 8 SF

212B CLOSET STORAGE SRS01 8 SF

212C CLOSET STORAGE SRS01 20 SF

213 STAIRS CIRCULATION N/A 142 SF

214 MEN'S RESTROOM RESTROOM TLTS1 139 SF

215 WOMEN'S RESTROOM RESTROOM TLTS1 107 SF

215A JANITOR UTIL/MEP JANC1 7 SF

216 GUEST ROOM STAFF OFA09 140 SF

216A CLOSET STORAGE SRS01 5 SF

216B CLOSET STORAGE SRS01 4 SF

217 GUEST ROOM STAFF OFA09 141 SF

217A CLOSET STORAGE SRS01 10 SF

217B CLOSET STORAGE SRS01 3 SF

218 STORAGE STORAGE SRS01 31 SF

219 CORRIDOR CIRCULATION N/A 602 SF

46 3353 SF

10 SF

JANITOR

CLOSET

FD

FD

B B

3018 SF

CRAWL SPACE

467 SF

EQUIPMENT

ROOM

002215 SF

STORAGE

ICRA CLASS LEGEND

CLASS 4

A A

B B

1 2

221 SF

CORRIDOR

115A

162 SF

OFFICE

154 SF

STORAGE

6 SF

CLOSET

109A 167 SF

WORKROOM

115B

154 SF

OFFICE

9 SF

CLOSET

111B 142 SF

STAIRS

144 SF

MEN'S

RESTROOM

106 SF

WOMEN'S

RESTROOM

243 SF

CORRIDOR

27 SF

IT / STORAGE

194 SF

TRAINING

24 SF

MECH

104A

30 SF

STORAGE

103A

96 SF

FOYER

100A

47 SF

ENTRY

151 SF

PRINTER ROOM

155 SF

DIRECTOR

150 SF

OFFICE

9 SF

CLOSET

106A

833 SF

TRAINING ROOM

149 SF

LAUNDRY

8 SF

CLOSET

107A

10 SF

JANITOR'S

CLOSET

78 SF

SUPPLY

104B

378 SF

CLASS 4

3252 SF

CLASS 3

ICRA CLASS LEGEND

CLASS 3

CLASS 4

A A

B B

1 2

141 SF

OFFICE

142 SF

OFFICE

142 SF

OFFICE

8 SF

CLOSET

212B

112 SF

TELE EQUIP

20 SF

CLOSET

212C

8 SF

CLOSET

212A

31 SF

STORAGE

139 SF

MEN'S

RESTROOM

107 SF

WOMEN'S

RESTROOM

7 SF

JANITOR

215A

4 SF

CLOSET

216B

140 SF

GUEST ROOM

141 SF

GUEST ROOM

141 SF

OFFICE

141 SF

OFFICE

142 SF

OFFICE

143 SF

OFFICE

125 SF

OFFICE

9 SF

CLOSET

201B

140 SF

GUEST ROOM

140 SF

GUEST ROOM

602 SF

CORRIDOR

142 SF

STAIRS

4 SF

CLOSET

216B

3 SF

CLOSET

217B

6 SF

CLOSET

200B

9 SF

CLOSET

209A

9 SF

CLOSET

209B

5 SF

CLOSET

210A

4 SF

CLOSET

210B

9 SF

CLOSET

211A

4 SF

CLOSET

211B

8 SF

CLOSET

208A

10 SF

CLOSET

207B

5 SF

CLOSET

207A

8 SF

CLOSET

208B

6 SF

CLOSET

205B

9 SF

CLOSET

205A

5 SF

CLOSET

206A

9 SF

CLOSET

206B

9 SF

CLOSET

204A

10 SF

CLOSET

200A

10 SF

CLOSET

217A

5 SF

CLOSET

216A

11 SF

CLOSET

201A

ICRA CLASS LEGEND

CLASS 3

CLASS 4

OFFICE

CLOSET

202B

CLOSET

203A

140 SF

10 SF 7 SF 5 SF

CLOSET

203B

8 SF

CLOSET

202A

140 SF

OFFICE

NEW UNRATED PARTITION

NEW / EXISTING 1 HOUR BARRIER

EXISTING PARTITION TO BE REMOVED

EXISTING PARTITION

INDICATES AREAS OUTSIDE PRIMARY

PROJECT WORK AREA

U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

Drawing Title

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Building Number

Drawing Number

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

VA FORM 08 - 6231

CONSTRUCTION DOCUMENTS

CONSULTANTS

Revs: Date:

BUSINESS OCCUPANCY

SPRINKLERED

9/

/2

4:

:4

PM

C :\U se rs

\e w ui \D oc um en ts

\L O

C

AL

\5

-1 9-

7_

R en ov B ui ld in g

4-

LE

TC

_A R

C H

_e st he r.w ui .rv t

ICRA PLANS CONSTRUCTION

DOCUMENTS

RENOVATE BUILDING 104 - LETC

FORT ROOTS, NORTH LITTLE ROCK

2021.09.30 Checker Author

598-19-127

GC101

JDA PROJECT #: 2018.001

A/E

2200 N. RODNEY PARHAM ROAD

SUITE 210

LITTLE ROCK, AR 72212

501-404-4811 jda@JohnsonDanforth.com

JohnsonDanforth & Associates

STRUCTURAL ENGINEER

BERNHARD TME

BUILDING 2, 1 ALLIED DRIVE

SUITE 2600

LITTLE ROCK, AR 72202

MEP ENGINEER

INSIGHT ENGINEERING, PLLC

201 S. CHESTER, SUITE B

LITTLE ROCK, AR 72201

FIRE PROTECTION

FP&C CONSULTANTS KC, LLC

1330 BURLINGTON STREET, STE. 200

NORTH KANSAS CITY, MO 64116

3/16" = 1'-0"F1 GROUND LEVEL ICRA PLAN

3/16" = 1'-0"E1 FIRST LEVEL ICRA PLAN

3/16" = 1'-0"C1 SECOND LEVEL ICRA PLAN

ICRA - GENERAL NOTES

1. ICRA WORK LIMITS ARE TO ENCOMPASS ALL AREAS WITH

REQUIRED WORK ACROSS ALL DISCIPLINES: CONTRACTOR

TO FULLY FAMILIARIZE THEMSELVES WITH THE COMPLETE

SET OF CONSTRUCTION DOCUMENTS AND THE INTENDED

WORK.

2. ICRA CLASS(ES) SHOWN ARE CONCEPTUAL AND MAY BE

USED AS A STARTING POINT FOR THE CONTRACTOR'S

REQUIRED WORK UNDER SPECIFICATION SECTION 01 35 26

"SAFETY REQUIREMENTS".

3. CONTRACTORS ARE ENCOURAGED TO ATTEND ANY AND

ALL SITE VISITS PROVIDED BY THE VA DURING BIDDING TO

FAMILIARIZE THEMSELVES WITH THE AREAS OF WORK.

4. CONTRACTOR SHALL EXAMINE THE FULL SET OF PLANS

AND DETERMINE IF THERE ARE ADDITIONAL AREAS OF

WORK ( AND ASSOCIATED ICRA CLASS(ES) ) DURING

BIDDING.

5. CONTRACTOR IS TO CONSIDER AND INCLUDE MONIES FOR

REQUIRED WORK IN ALL PROJECT AREAS AS PART OF

THEIR BASE BID.

6. IF CONTRACTOR IDENTIFIES POTENTIAL CONFLICTS OR

LIMITATIONS IN THEIR ABILITY TO FULLY COMPLY WITH

ICRA SAFETY REQUIREMENTS CONTAINED IN THE BIDDING

DOCUMENTS, THEY SHALL SEEK RESOLUTION IN WRITING

AS INDICATED IN BIDDING INSTRUCTIONS.

7. PROVIDE CONTAINMENT AS REQUIRED (BY HOSPITAL)

INFECTION CONTROL REPRESENTATIVE FOR WORK

OUTSIDE MAJOR AREA.

8. PROVIDE CONTAINMENT AT THE FLOOR BELOW FOR ANY

WORK IN THE CEILING PLENUM.

9. PROVIDE TEMPORARY DOORS WITH GASKETING TO

PREVENT THE TRANSFER OF DUST OUTSIDE WORK AREA.

10. PROVIDE TEMPORARY EMERGENCY EXITS FROM

CONSTRUCTION ZONES; HOWEVER, ALL GENERAL

CONSTRUCTION TRAFFIC SHOULD BE THROUGH

VESTIBULE.

11. CONTRACTOR TO PROTECT ALL FINISHES INCLUDING (BUT

NOT LIMITED TO) FLOORING, CEILING, WALL SURFACES,

DOORS, AND DOOR FRAMES DURING THE MOVEMENT OF

MATERIALS TO/FROM LIMIT OF WORK. COORDINATE WITH

COR AND SPECIFICATIONS FOR PROCEDURES /

REQUIREMENTS.

PARTITION LEGEND

SCALE: 3/16" = 1'-0"

0 2'-8" 5'-4" 10'-8"

IT IS THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE THE FOLLOWING INFECTION CONTROL PRECAUTIONS DEPENDING UPON THE

AREA CLASS DESIGNATION

TYPE OF CONTRUCTION/PROJECT ACTIVITY TABLE

GROUP 1-LOW RISK

● OFFICE AREAS (NON-

CLINICAL)

PATIENT RISK GROUP TABLE

GROUP 2-MEDIUM RISK

GROUP 3-HIGH RISK GROUP 4-HIGHEST RISK

INFECTION CONTROL MATRIX-CLASS OF PRECAUTIONS: CONSTRUCTION PROJECT BY PATIENT RISK

PATIENT RISK GROUP TYPE A

I I I

III

NOTE: INFECTION CONTROL APPROVAL WILL BE REQUIRED WHEN THE CONSTRUCTION

ACTIVITY AND RISK LEVEL INDICATE THAT CLASS III OR CLASS IV CONTROL PROCEDURES

ARE NECESSARY.LOW RISK GROUP 1

MEDIUM RISK GROUP 2

HIGH RISK GROUP 3

HIGHEST RISK GROUP 4

1. EXECUTE WORK BY METHODS TO MINIMIZE RAISING DUST FROM CONSTRUCTION

OPERATIONS.

2. IMMEDIATELY REPLACE A CEILING TILE DISPLACED FOR VISUAL INSPECTION.

1. INCLUDES ALL ACTIVITIES REQUIRED BY CLASS I.

2. PROVIDE ACTIVE MEANS TO PREVENT AIRBORNE DUST FROM DISPERSING INTO

ATMOSPHERE.

3. WATER MIST WORK SURFACES TO CONTROL DUST WHILE CUTTING.

4. SEAL UNUSED DOORS WITH DUCT TAPE.

5. BLOCK OFF AND SEAL AIR VENTS.

6. REPLACE ADHESIVE WALK-OFF MATS AT ENTRANCE AN EXIT OF WORK AREA.

REPLACE USED MATS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.

7. REMOVE OR ISOLATE HVAC SYSTEM IN AREAS WHERE WORK IS BEING DONE TO

PREVENT CONTAMINATION OF DUCT SYSTEM.

1. INCLUDES ALL ACTIVITIES REQUIRED BY CLASS II.

2. OBTAIN INFECTION CONTROL PERMIT FROM HOSPITAL SAFETY OFFICER OR

FACILITIES MANAGEMENT MAINTENANCE AND ENGINEERING DEPARTMENT BEFORE

CONSTRUCTION BEGINS.

3. REMOVE OR ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO

PREVENT CONTAMINATION OF DUCT SYSTEM.

4. COMPLETE ALL CRITICAL BARRIERS BEFORE CONSTRUCTION BEGINS OR

IMPLEMENT CONTROL CUBE METHOD.

5. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA-EQUIPPED

AIR FILTRATION UNITS.

6. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED

CONTAINERS.

7. COVER TRANSPORT RECEPTACLES OR CARS. TAPE COVERS.

8. WET MOP AND/OR VACUUM WITH HEPA FILTERED VACUUM BEFORE LEAVING WORK

AREAS.

9. REMOVE ISOLATION OF HVAC SYSTEM IN AREAS WHERE WORK IS BEING

PERFORMED.

1. WIPE SURFACES TO REMOVE DUST.

1. WIPE WORK SURFACES WITH

DISINFECTANT.

2. CONTAIN CONSTRUCTION WASTE

BEFORE TRANSPORT IN TIGHTLY

COVERED CONTAINERS.

3. WET MOP AND/OR VACUUM

WORK AREA WITH HEPA

FILTERED VACUUM BEFORE

LEAVING WORK AREAS.

4. REMOVE ISOLATION OF HVAC

SYSTEM IN AREAS WHERE WORK

WAS BEING PERFORMED.

1. REMOVE BARRIER MATERIALS

CAREFULLY TO MINIMIZE

SPREADING OF DIRT AND DEBRIS

ASSOCIATED WITH

CONSTRUCTION.

2. CONTAIN CONSTRUCTION

WASTE BEFORE TRANSPORT IN

TIGHTLY COVERED CONTAINERS.

3. COVER TRANSPORT

RECEPTACLES OR CARTS. TAPE

COVERING.

4. VACUUM WORK WITH HEPA-

FILTERED VACUUMS.

5. WET MOP WITH DISINFECTANT.

6. REMOVE ISOLATION OF HVAC

SYSTEM IN AREAS WHERE WORK

WAS BEING PERFORMED.

1. INCLUDES ALL ACTIVITIES REQUIRED BY CLASS III.

2. OBTAIN INFECTION CONTROL PERMIT FROM HOSPITAL SAFETY OFFICER OR

FACILITIES MANAGEMENT MAINTENANCE AND ENGINEERING DEPARTMENT

BEFORE CONSTRUCTION BEGINS.

3. ISOLATE HVAC SYSTEM IN AREAS WHERE WORK IS BEING DONE TO PREVENT

CONTAMINATION OF DUCT SYSTEM.

4. COMPLETE ALL CRITICAL BARRIERS OR IMPLEMENT CONTROL CUBE METHOD

BEFORE CONSTRUCTION BEGINS.

5. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA-

EQUIPPED AIR FILTRATION UNITS.

6. SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES APPROPRIATELY.

CONSTRUCT ANTEROOM AND REQUIRE ALL PERSONNEL TO PASS-THROUGH

THIS ROOM SO THEY CAN BE VACUUMED USING A HEPA VACUUM CLEANER

BEFORE LEAVING WORK SITE OR THEY CAN WEAR CLOTH OR PAPER

COVERALLS THAT ARE REMOVED EACH TIME THEY LEAVE THE WORK SITE.

7. ALL PERSONNEL ENTERING WORK SITE ARE REQUIRED TO WEAR SHOE

COVERS. SHOE COVERS MUST BE CHANGED EACH TIME THE WORKER EXITS

THE WORK AREA.

8. PLACE ADHESIVE WALK-OFF MATS AT ENTRANCE TO WORK AREA WITH

ANTEROOM. REPLACE PER MANUFACTURER'S RECOMMENDATIONS.

9. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS

INSPECTED EACH BY THE HOSPITAL SAFETY OFFICER, FACILITIES

MANAGEMENT MAINTENANCE AND ENGINEERING DEPARTMENT AND

THOROUGHLY CLEANED BY THE HOSPITAL ENVIRONMENTAL SERVICES

DEPARTMENT OR THEIR CONTRACTED ENVIRONMENTAL SERVICES

COMPANY.

10. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED

CONTAINERS.

11. COVER TRANSPORT RECEPTACLES OR CARS. TAPE COVERING.

12. VACUUM WITH HEPA FILTERED VACUUM. WET MOP WITH DISINFECTANT

AFTER BARRIERS ARE REMOVED.

13. REMOVE ISOLATION OF HVAC SYSTEM IN AREAS WHERE WORK IS BEING

PERFORMED.

1. REMOVE BARRIER MATERIALS

CAREFULLY TO MINIMIZE

SPREADING OF DIRT AND DEBRIS

ASSOCIATED WITH

CONSTRUCTION.

2. CONTAIN CONSTRUCTION WASTE

BEFORE TRANSPORT IN TIGHTLY

COVERED CONTAINERS.

3. COVER TRANSPORT

RECEPTACLES OR CARTS. TAPE

COVERING.

4. VACUUM WORK WITH HEPA-

FILTERED VACUUMS.

5. WET MOP WITH DISINFECTANT

AFTER BARRIERS ARE REMOVED.

6. REMOVE ISOLATION OF HVAC

SYSTEM IN AREAS WHERE WORK

WAS BEING PERFORMED.

DURING CONSTRUCTION PROJECT UPON COMPLETION OF PROJECT

CLASS I

CLASS II

CLASS III

CLASS IV

INSPECTION AND NON-INVASIVE ACTIVITIES

INCLUDES BUT IS NOT LIMITED TO:

● REMOVAL OF CEILING TILES FOR VISUAL INSPECTION LIMITED TO 1

TILE IN 50 SQUARE FEET

● PAINTING (BUT NOT SANDING), WALL COVERING

● ELECTRICAL TRIM WORK, MINOR PLUMBING, AND ACTIVITIES THAT

DO NOT GENERATE DUST OR REQUIRE CUTTING OF WALLS OR

ACCESS TO CEILINGS OTHER THAN FOR VISUAL INSPECTION

TYPE A

SMALL SCALE, SHORT DURATION ACTIVITIES THAT CREATE MINIMAL DUST

INCLUDES BUT IS NOT LIMITED TO:

● INSTALLATION OF TELEPHONE AND COMPUTER CABLING

● ACCESS TO CHASE SPACES

● CUTTING OF WALLS OR CEILING WHERE DUST MIGRATION CAN BE

CONTROLLED

TYPE B

WORK THAT GENERATES A MODERATE TO HIGH LEVEL OF DUST OR

REQUIRES DEMOLITION OR REMOVAL OF ANY FIXED BUILDING

COMPONENTS OR ASSEMBLIES

INCLUDES BUT IS NOT LIMITED TO:

● SANDING OF WALLS FOR PAINTING OR WALL COVERING

● REMOVAL OF FLOOR COVERINGS, CEILING TILES AND CASEWORK

● NEW WALL CONSTRUCTION

● MINOR DUCT WORK OR ELECTRICAL WORK ABOVE CEILINGS

● MAJOR CABLING ACTIVITIES

● ANY ACTIVITY THAT CANNOT BE COMPLETED WITHIN A SINGLE

WORK SHIFT

TYPE C

MAJOR DEMOLITION AND CONSTRUCTION PROJECTS

INCLUDES BUT IS NOT LIMITED TO:

● ACTIVITIES THAT REQUIRE CONSECUTIVE WORK SHIFTS

● REQUIRES HEAVY DEMOLITION OR REMOVAL OF A COMPLETE

CEILING SYSTEM

● NEW CONSTRUCTION

TYPE D

ICRA GENERAL NOTES

● CARDIOLOGY

● ECHOCARDIOLOGY

● ENDOSCOPY-GI

● PHYSICAL THERAPY

● RADIOLOGY/MRI

● NUCLEAR MEDICINE

● RESPIRATORY CARE (EXCEPT

BRONCHOSCOPY AREA)

● CAFETERIA

● OUTPATIENT AREAS-CLINICS AND OFFICES

(EXCEPTION: TRANSPLANT AND ONCOLOGY)

● EMERGENCY ROOM

● POST ANESTHESIA

● CARE UNITS

● LABOR AND DELIVERY

● PEDIATRICS

● ADMISSION/DISCHARGE

AREA

● LABORATORIES

● PHARMACY

● INPATIENT UNITS (NOT

OTHERWISE

SPECIFIED)

● ALL OPERATING ROOMS INCLUDING LABOR AND

DELIVERY

● ANESTHESIA AND PUMP AREAS

● CENTRAL EQUIPMENT/STERILE SUPPLY

● CARDIAC CATHETERIZATION AND ANGIOGRAPHY

AREAS

● INTERVENTIONAL RADIOLOGY

● RADIATION ONCOLOGY

● ALL INTENSIVE CARE UNITS

● NEWBORN NURSERIES, INCLUDING NICU

● DIALYSIS UNIT

● ONCOLOGY-INPATIENT AND OUTPATIENT

● TRANSPLANT-INPATIENT AND OUTPATIENT

● PHARMACY ADMIXTURE

● NEGATIVE PRESSURE ISOLATION ROOMS/AREAS

(INCLUDING BRONCHOSCOPY AREA)

TYPE B

II

II

III

III / IV

TYPE C

II

III

III / IV

III / IV

TYPE D

III / IV

IV

IV

IV

A. PROVIDE CONTAINMENT AS REQUIRED (BY HOSPITAL) INFECTION CONTROL REPRESENTATIVE FOR WORK OUTSIDE MAJOR AREA.

B. PROVIDE CONTAINMENT AT THE FLOOR BELOW FOR ANY WORK IN THE CEILING PLENUM.

C.…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .