Attachment C-1 Plans and Drawings OED Salem Office.pdf
PDF 5 MB Posted
- Solicitation number
- S-DASOBO-00017609
- Issued by
- Oregon
About this file
Summary
This file is a set of electrical plans and drawings (Attachment C-1) prepared for the Oregon Employment Department LED Lighting Upgrade Project at the Salem office located at 605 Cottage Street NE, Salem, OR 97301. The drawings were designed by MKE Engineering and issued as a bid set dated 04/10/2026 under job number 6367. The project encompasses lighting demolition and installation plans across multiple floors of the facility, including basement, first floor, second floor, and roof areas. The plans provide detailed electrical symbols, legends, fixture schedules, and keyed notes specifying the scope of work, which includes demolishing existing light fixtures and associated raceways, modifying existing lighting circuits to accommodate new fixtures, installing wireless area controllers and wall station control devices, and implementing lighting controls with BACnet integration. The drawings indicate both existing fixtures to remain (marked with "E" designation) and existing fixtures to be demolished (shown with dashed lines), requiring contractors to intercept and modify existing circuits as necessary to connect to new light fixture locations.
The contract documents establish specific responsibilities and requirements for the contractor performing the work. General notes specify that contractors must conduct site visits to familiarize themselves with existing conditions prior to bidding, maintain temporary electrical systems during construction as required, protect existing electrical systems and components from damage during demolition, and completely remove abandoned wiring back to source while reusing existing conduit where practical. The owner retains first right of salvage of electrical materials and equipment intended for demolition, with all other removed materials becoming contractor property. Additional requirements include providing a temporary network solution for lighting controls during construction with all fixtures mapped and individually labeled prior to handoff to the owner, maintaining existing egress paths unless directed otherwise by the owner and architect, and verifying existing information from record drawings before proceeding with work due to the inability to guarantee complete accuracy of existing feature documentation.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SINGLE-POINT ELECTRICAL CONNECTION
ELECTRICAL MOTOR CONNECTION
FUSED SAFETY SWITCH
SAFETY SWITCH
POWER/DATA POLE
ELECTRICAL EQUIPMENT CONNECTION
SPECIAL PURPOSE POWER RECEPTACLE [+ 18'']
DOUBLE DUPLEX RECEPTACLE [ABOVE COUNTER]
DUPLEX RECEPTACLE [ABOVE COUNTER]
DOUBLE DUPLEX RECEPTACLE [+ 18'']
LIGHTING RELAY
FOUR-WAY SWITCH [+ 45'']
LOW VOLTAGE SWITCH [+ 45'']
DUPLEX RECEPTACLE [+ 18'']
R
SD
SLV
DIMMER SWITCH [+ 45'']
FLUSH CONTROL PANEL [MAX 6'-6'' TO TOP]
SURFACE CONTROL PANEL [MAX 6'-6'' TO TOP]
METER BASE & SOCKET
J
SURFACE ELECTRICAL PANEL [MAX 6'-6'' TO TOP]
FLUSH ELECTRICAL PANEL [MAX 6'-6'' TO TOP]
OS
P
THREE-WAY SWITCH [+ 45'']
SURFACE MOUNTED EMERGENCY
PENDANT MOUNTED LIGHT FIXTURE
POLE ARM MOUNT LIGHT FIXTURE
CEILING MOUNTED EXIT SIGN
WALL MOUNTED EXIT SIGN [+ 18'' ABOVE DOOR]
S
PENDANT LIGHT FIXTURE
RECESSED LIGHT FIXTURE
RECESSED LIGHT FIXTURE
PENDANT EMERGENCY LIGHT FIXTURE
WALL MOUNTED LIGHT FIXTURE
WALL MOUNTED EMERGENCY LIGHT FIXTURE
CONDUIT WITH
MECHANICAL. EQUIPMENT NOTE MARK
NEUTRAL CONDUCTOR
FEEDER MARK
PLAN NOTE MARK
PHASE CONDUCTOR
GROUND CONDUCTOR
X
X X
BALLAST LOAD TRANSFER
LINEAR WALL MOUNTED EMERGENCY FIXTURE
RECESSED EMERGENCY LIGHT FIXTURE
RECESSED EMERGENCY LIGHT FIXTURE
JUNCTION BOX
SURFACE MOUNTED LIGHT FIXTURE
LINEAR WALL MOUNTED LIGHT FIXTURE
COMBO EXIT SIGN/
EMERGENCY LIGHT [+ 18'' ABOVE DOOR]
CP
SO OCCUPANCY SENSOR SWITCH [+ 45'']
SURFACE MOUNTED EMERGENCY LIGHT FIXTURE
STRIP LIGHT FIXTURE
EMERGENCY STRIP LIGHT FIXTURE
RECESSED DOWNLIGHT
SINGLE-POLE SWITCH [+ 45'']
OCCUPANCY SENSOR ONE WAY CEILING MOUNT
OCCUPANCY SENSOR POWER PACK
PHOTOCELL
(SIGN FACE)
EMERGENCY RELAY
STANDARD MOUNTING HEIGHT UNLESS
OTHERWISE NOTED ON DRAWINGS
[+ XX'']
XXXXX
LIGHT FIXTURE
DISTRIBUTION & EQUIPMENT
POWER DEVICES ABBREVIATIONSLIGHTING DEVICES
REFERENCE SYMBOLS & WIRING
(E) EXISTING TO REMAIN
(F) FUTURE
(R) EXISTING TO BE RELOCATED
(D) EXISTING TO BE DEMOLISHED
AB ABOVE COUNTER BACKSPLASH
AC ALTERNATING CURRENT
A, AMP AMPERES
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC-FAULT CIRCUIT INTERRUPTER
AHJ AUTHORITY HAVING JURISDICTION
AIC EQUIPMENT SHORT CIRCUIT INTERRUPT RATING.
AL ALUMINUM
ALC AUTOMATIC LIGHTING CONTROL
ATS AUTOMATIC TRANSFER SWITCH
AUX AUXILIARY
AWG AMERICAN WIRE GAUGE
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CLG CEILING
CT CURRENT TRANSFORMER
CU COPPER
DC DIRECT CURRENT
DISC DISCONNECT
DIA DIAMETER
DIV DIVISION
DP DISTRIBUTION PANEL
DWG DRAWING
EF EXHAUST FAN
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
FA FIRE ALARM
FAA FIRE ALARM ANNUNCIATOR
FBO FURNISHED BY OTHERS
FC FOOT CANDLES
FLA FULL LOAD AMPERES
FSD FIRE/SMOKE DAMPER
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
HP HORSEPOWER
HTR HEATER
IG ISOLATED GROUND
KCMIL THOUSAND CIRCULAR MILS
KW KILOWATTS
KVA KILOVOLT-AMPERES
LTG LIGHTING
LCP LIGHTING CONTROL PANEL
MAX MAXIMUM
MB MAIN BREAKER
MCA MINIMUM CIRCUIT AMPERES
MDP MAIN DISTRIBUTION PANEL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MSP MAIN SERVICE PANEL
MTD MOUNTED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MFGR'S ASSOCIATION.
NL NIGHT LIGHT
NTS NOT TO SCALE
OFCI OWNER FURNISHED, CONTRACTOR INSTALLED
OFOI OWNER FURNISHED, OWNER INSTALLED
OS OCCUPANCY SENSOR
PH, Ø PHASE
PNL PANEL
PROVIDE TO FURNISH AND INSTALL
SDP SUB DISTRIBUTION PANEL
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TB TERMINAL BOARD
TEL TELEPHONE
TK INSTALL TOE KICK
TYP TYPICAL OF ALL OCCURANCES
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLTS
VA VOLT-AMPERES
VFD VARIABLE FREQUENCY DRIVE
VR VANDAL RESISTANT
W WATT
W/ WITH
W/O WITHOUT
WG WIRE GUARD
WP WEATHERPROOF
XFMR TRANSFORMER
S4
S3
FLUSH AUTOMATIC DOOR ACTUATOR [+45'']
M
C
X X
SINGLE RECEPTACLE [+ 18'']
SHEET REFERENCE MARK
HOMERUN ARROW
LIGHTING CONTACTOR
SURFACE MOUNTED LIGHT FIXTURE
PENDANT MOUNTED EMERGENCY LIGHT FIXTURE
UNDER GROUND
ABOVE GROUND, IN WALL, CEILING, ETC.
LINETYPE LEGEND
NEW EQUIPMENT (TYPICAL)
EXISTING EQUIPMENT (TYPICAL)
DEMOLISHED EQUIPMENT (TYPICAL)
RECESSED EMERGENCY DOWNLIGHT
OS OCCUPANCY SENSOR TWO WAY CEILING MOUNT
OS OCCUPANCY SENSOR 360° CEILING MOUNT
OS OCCUPANCY SENSOR WALL MOUNT
DA
EM
DWG DESCRIPTION
E001 ELECTRICAL LEGEND, SCHEDULES AND NOTES
E100 BASEMENT FLOOR - LIGHTING DEMOLITION PLAN
E110 FIRST FLOOR - LIGHTING DEMOLITION PLAN
E120 SECOND FLOOR - LIGHTING DEMOLITION PLAN
E200 BASEMENT FLOOR - LIGHTING PLAN
E210 FIRST FLOOR - LIGHTING PLAN
E220 SECOND FLOOR - LIGHTING PLAN
E400 ELECTRICAL DETAILS
DRAWING INDEXLIGHTING FIXTURE SCHEDULE
REVISIONS:
O R
EG
O
N E
M
PL
O
YM
EN
T
D
EP
AR
TM
EN
T
C O
TT
AG
E
ST
N E, SA
LE
M , O
R
ISSUE DATE:
MKE JOB #:
DESIGNED BY:
CHECKED BY:
DRAWN BY:
SET TYPE:
SL
TH
TH
BID SET
04/10/26
HQJLQHHULQJ#PNH-LQF.FRP
SA
LE
M O
FF
IC
E
E001
ELECTRICAL LEGEND,
SCHEDULES AND NOTES
SCX70G
Christian HARGROVE Rectangle
UP
A
F
E
D
C
B
(TYP)
GENERAL NOTES:
KEYED NOTES:
1. DEMOLISH EXISTING LIGHT FIXTURE AND RACEWAYS
AS MUCH AS NECESSARY TO ACCOMMODATE
REMOVAL. MAINTAIN CIRCUITING FOR CONNECTION
TO NEW LIGHT FIXTURE LOCATION.
A. CONTRACTOR SHALL VISIT THE SITE AND BECOME
THOROUGHLY FAMILIAR WITH THE EXISTING
CONDITIONS PRIOR TO BIDDING. ELECTRICAL
LIGHTING DEVICES, AND LIGHT FIXTURES SHOWN
DASHED REPRESENT EXISTING TO BE DEMOLISHED.
EXISTING ELECTRICAL LIGHTING DEVICES, AND LIGHT
FIXTURES TO REMAIN ARE SHOWN WITH '(E)'
DESIGNATION OR OTHERWISE SPECIFICALLY NOTED.
B. LABOR AND MATERIALS REQUIRED TO CHANGE THE
EXISTING ELECTRICAL INSTALLATION AS INDICATED
SHALL BE PROVIDED. DRAWINGS ARE DIAGRAMMATIC
AND DO NOT SHOW EXISTING INTERCONNECTING
COMPONENTS.
C. EXCEPT AS MAY BE SPECIFICALLY INDICATED,
OWNER SHALL HAVE FIRST RIGHT OF SALVAGE OF
ELECTRICAL MATERIALS AND EQUIPMENT INTENDED
FOR DEMOLITION. OTHERWISE ELECTRICAL
MATERIALS AND EQUIPMENT REMOVED FROM THE
EXISTING INSTALLATION IN THE COURSE OF
PERFORMING THE INDICATED WORK SHALL BECOME
THE PROPERTY OF THE CONTRACTOR AND SHALL BE
REMOVED FROM THE SITE.
D. CONTRACTOR SHALL PROVIDE NECESSARY LABOR
AND MATERIALS TO MAINTAIN TEMPORARY
ELECTRICAL SYSTEMS AS MAY BE REQUIRED BY
ARCHITECT OR OWNER IN OPERATION DURING THE
CONSTRUCTION PERIOD.
E. EXISTING ELECTRICAL SYSTEMS, CONDUIT AND
WIRING WHICH ARE NOT TO BE DEMOLISHED SHALL
BE PROTECTED FROM DAMAGE DURING THE
DEMOLITION.
F. ABANDONED WIRING SHALL BE REMOVED
COMPLETELY BACK TO SOURCE; EXISTING CONDUIT
MAY BE REUSED IF PRACTICAL, CAPPING OFF
CONDUIT STUBS THAT MAY REMAIN. CONDUIT
PENETRATING WALLS AND FLOORS WHICH ARE TO
REMAIN SHALL BE CUT OFF FLUSH. SEAL
ABANDONED CONDUIT.
G. INFORMATION GIVEN ON THE DRAWINGS IN
REFERENCE TO EXISTING FEATURES HAS BEEN
OBTAINED FROM RECORD DRAWINGS AND RECENT
SITE OBSERVATIONS, BUT CANNOT BE GUARANTEED
TO BE COMPLETELY ACCURATE. VERIFY
INFORMATION BEFORE PROCEEDING WITH ANY
WORK.
1 BASEMENT FLOOR - LIGHTING DEMOLITION PLAN
1/8" = 1'-0" 0' 4' 8' 16'
N
REVISIONS:
O R
EG
O
N E
M
PL
O
YM
EN
T
D
EP
AR
TM
EN
T
C O
TT
AG
E
ST
N E, SA
LE
M , O
R
ISSUE DATE:
MKE JOB #:
DESIGNED BY:
CHECKED BY:
DRAWN BY:
SET TYPE:
SL
TH
TH
BID SET
04/10/26
HQJLQHHULQJ#PNH-LQF.FRP
SA
LE
M O
FF
IC
E
E100
BASEMENT FLOOR - LIGHTING
DEMOLITION PLAN
(E) TELEPHONE
BACKBOARD
UP
UP
DN
DN
A
F
E
D
C
B
(E) PNL MSB
(E) PNL P
(E) PNL D
(TYP)
(E) PNL B
(E) PNL B2
GENERAL NOTES:
KEYED NOTES:
1. DEMOLISH EXISTING LIGHT FIXTURE AND RACEWAYS
AS MUCH AS NECESSARY TO ACCOMMODATE
REMOVAL. MAINTAIN CIRCUITING FOR CONNECTION
TO NEW LIGHT FIXTURE LOCATION.
A. CONTRACTOR SHALL VISIT THE SITE AND BECOME
THOROUGHLY FAMILIAR WITH THE EXISTING
CONDITIONS PRIOR TO BIDDING. ELECTRICAL
LIGHTING DEVICES, AND LIGHT FIXTURES SHOWN
DASHED REPRESENT EXISTING TO BE DEMOLISHED.
EXISTING ELECTRICAL LIGHTING DEVICES, AND LIGHT
FIXTURES TO REMAIN ARE SHOWN WITH '(E)'
DESIGNATION OR OTHERWISE SPECIFICALLY NOTED.
B. LABOR AND MATERIALS REQUIRED TO CHANGE THE
EXISTING ELECTRICAL INSTALLATION AS INDICATED
SHALL BE PROVIDED. DRAWINGS ARE DIAGRAMMATIC
AND DO NOT SHOW EXISTING INTERCONNECTING
COMPONENTS.
C. EXCEPT AS MAY BE SPECIFICALLY INDICATED,
OWNER SHALL HAVE FIRST RIGHT OF SALVAGE OF
ELECTRICAL MATERIALS AND EQUIPMENT INTENDED
FOR DEMOLITION. OTHERWISE ELECTRICAL
MATERIALS AND EQUIPMENT REMOVED FROM THE
EXISTING INSTALLATION IN THE COURSE OF
PERFORMING THE INDICATED WORK SHALL BECOME
THE PROPERTY OF THE CONTRACTOR AND SHALL BE
REMOVED FROM THE SITE.
D. CONTRACTOR SHALL PROVIDE NECESSARY LABOR
AND MATERIALS TO MAINTAIN TEMPORARY
ELECTRICAL SYSTEMS AS MAY BE REQUIRED BY
ARCHITECT OR OWNER IN OPERATION DURING THE
CONSTRUCTION PERIOD.
E. EXISTING ELECTRICAL SYSTEMS, CONDUIT AND
WIRING WHICH ARE NOT TO BE DEMOLISHED SHALL
BE PROTECTED FROM DAMAGE DURING THE
DEMOLITION.
F. ABANDONED WIRING SHALL BE REMOVED
COMPLETELY BACK TO SOURCE; EXISTING CONDUIT
MAY BE REUSED IF PRACTICAL, CAPPING OFF
CONDUIT STUBS THAT MAY REMAIN. CONDUIT
PENETRATING WALLS AND FLOORS WHICH ARE TO
REMAIN SHALL BE CUT OFF FLUSH. SEAL
ABANDONED CONDUIT.
G. INFORMATION GIVEN ON THE DRAWINGS IN
REFERENCE TO EXISTING FEATURES HAS BEEN
OBTAINED FROM RECORD DRAWINGS AND RECENT
SITE OBSERVATIONS, BUT CANNOT BE GUARANTEED
TO BE COMPLETELY ACCURATE. VERIFY
INFORMATION BEFORE PROCEEDING WITH ANY
WORK.
1 FIRST FLOOR - LIGHTING DEMOLITION PLAN
1/8" = 1'-0" 0' 4' 8' 16'
N
REVISIONS:
O R
EG
O
N E
M
PL
O
YM
EN
T
D
EP
AR
TM
EN
T
C O
TT
AG
E
ST
N E, SA
LE
M , O
R
ISSUE DATE:
MKE JOB #:
DESIGNED BY:
CHECKED BY:
DRAWN BY:
SET TYPE:
SL
TH
TH
BID SET
04/10/26
HQJLQHHULQJ#PNH-LQF.FRP
SA
LE
M O
FF
IC
E
E110
FIRST FLOOR - LIGHTING
DEMOLITION PLAN
DN
A
F
E
D
C
B
(E) PNL 2A(E) TELEPHONE
BACKBOARD
(TYP)(E) PNL 2B
GENERAL NOTES:
KEYED NOTES:
1. DEMOLISH EXISTING LIGHT FIXTURE AND RACEWAYS
AS MUCH AS NECESSARY TO ACCOMMODATE
REMOVAL. MAINTAIN CIRCUITING FOR CONNECTION
TO NEW LIGHT FIXTURE LOCATION.
A. CONTRACTOR SHALL VISIT THE SITE AND BECOME
THOROUGHLY FAMILIAR WITH THE EXISTING
CONDITIONS PRIOR TO BIDDING. ELECTRICAL
LIGHTING DEVICES, AND LIGHT FIXTURES SHOWN
DASHED REPRESENT EXISTING TO BE DEMOLISHED.
EXISTING ELECTRICAL LIGHTING DEVICES, AND LIGHT
FIXTURES TO REMAIN ARE SHOWN WITH '(E)'
DESIGNATION OR OTHERWISE SPECIFICALLY NOTED.
B. LABOR AND MATERIALS REQUIRED TO CHANGE THE
EXISTING ELECTRICAL INSTALLATION AS INDICATED
SHALL BE PROVIDED. DRAWINGS ARE DIAGRAMMATIC
AND DO NOT SHOW EXISTING INTERCONNECTING
COMPONENTS.
C. EXCEPT AS MAY BE SPECIFICALLY INDICATED,
OWNER SHALL HAVE FIRST RIGHT OF SALVAGE OF
ELECTRICAL MATERIALS AND EQUIPMENT INTENDED
FOR DEMOLITION. OTHERWISE ELECTRICAL
MATERIALS AND EQUIPMENT REMOVED FROM THE
EXISTING INSTALLATION IN THE COURSE OF
PERFORMING THE INDICATED WORK SHALL BECOME
THE PROPERTY OF THE CONTRACTOR AND SHALL BE
REMOVED FROM THE SITE.
D. CONTRACTOR SHALL PROVIDE NECESSARY LABOR
AND MATERIALS TO MAINTAIN TEMPORARY
ELECTRICAL SYSTEMS AS MAY BE REQUIRED BY
ARCHITECT OR OWNER IN OPERATION DURING THE
CONSTRUCTION PERIOD.
E. EXISTING ELECTRICAL SYSTEMS, CONDUIT AND
WIRING WHICH ARE NOT TO BE DEMOLISHED SHALL
BE PROTECTED FROM DAMAGE DURING THE
DEMOLITION.
F. ABANDONED WIRING SHALL BE REMOVED
COMPLETELY BACK TO SOURCE; EXISTING CONDUIT
MAY BE REUSED IF PRACTICAL, CAPPING OFF
CONDUIT STUBS THAT MAY REMAIN. CONDUIT
PENETRATING WALLS AND FLOORS WHICH ARE TO
REMAIN SHALL BE CUT OFF FLUSH. SEAL
ABANDONED CONDUIT.
G. INFORMATION GIVEN ON THE DRAWINGS IN
REFERENCE TO EXISTING FEATURES HAS BEEN
OBTAINED FROM RECORD DRAWINGS AND RECENT
SITE OBSERVATIONS, BUT CANNOT BE GUARANTEED
TO BE COMPLETELY ACCURATE. VERIFY
INFORMATION BEFORE PROCEEDING WITH ANY
WORK.
DN
1 SECOND FLOOR - LIGHTING DEMOLITION PLAN
1/8" = 1'-0" 0' 4' 8' 16'
N
REVISIONS:
O R
EG
O
N E
M
PL
O
YM
EN
T
D
EP
AR
TM
EN
T
C O
TT
AG
E
ST
N E, SA
LE
M , O
R
ISSUE DATE:
MKE JOB #:
DESIGNED BY:
CHECKED BY:
DRAWN BY:
SET TYPE:
SL
TH
TH
BID SET
04/10/26
HQJLQHHULQJ#PNH-LQF.FRP
SA
LE
M O
FF
IC
E
E120
SECOND FLOOR - LIGHTING
DEMOLITION PLAN
2 ROOF - LIGHTING DEMOLITION PLAN
1/8" = 1'-0" 0' 4' 8' 16'
N
A
F
E
D
C
B
(TYP)
CE C
C
C
C
C C
C
C
C
C
C
C
C
CE
CE CE
CE
CE
CE CE
CE
CECE
CE
C
C
C
CCCCCC
C
CCCC
C
C
C C
C
C
C C
CC
C C
CC
C C
CCCCCC
C C
CC
C
C C
C
C
D
DE
D
DE
X1
(TYP)
(TYP)
LV
LV
(TYP)
LV
LV
LV
1. INTERCEPT AND MODIFY EXISTING LIGHTING CIRCUIT
AS NECESSARY TO CONNECT TO NEW LIGHT
FIXTURES.
2. SURFACE MOUNT WIRELESS AREA CONTROLLER ON
CEILING. PROVIDE CAT 6 CONNECTION TO LIGHTING
CONTROL PATCH PANEL. SEE DETAIL 1 ON E400.
3. PROVIDE WIRELESS WALL STATION CONTROL
DEVICE. INSTALL IN EXISTING SWITCH J-BOX, VERIFY
EXACT LOCATION. WALL STATION REQUIRES 120V
ELECTRICAL CONNECTION. EXTEND EXISTING
NEUTRAL CONDUCTOR AS NECESSARY. SEE DETAIL 3
ON SHEET E400 FOR BUTTON CONFIGURATION.
4. SEE DETAIL 2 ON E400 FOR TYPICAL EMERGENCY
DRIVER WIRING.
5. CONNECT TO UN-SWITCHED LEG OF LIGHTING
CIRCUIT.
KEYED NOTES:
A. CONTRACTOR SHALL VISIT THE SITE AND BECOME
THOROUGHLY FAMILIAR WITH THE EXISTING
CONDITIONS PRIOR TO BIDDING. ELECTRICAL
LIGHTING DEVICES, AND LIGHT FIXTURES SHOWN
DASHED REPRESENT EXISTING TO BE DEMOLISHED.
EXISTING ELECTRICAL LIGHTING DEVICES, AND LIGHT
FIXTURES TO REMAIN ARE SHOWN WITH '(E)'
DESIGNATION OR OTHERWISE SPECIFICALLY NOTED.
B. LABOR AND MATERIALS REQUIRED TO CHANGE THE
EXISTING ELECTRICAL INSTALLATION AS INDICATED
SHALL BE PROVIDED. DRAWINGS ARE DIAGRAMMATIC
AND DO NOT SHOW EXISTING INTERCONNECTING
COMPONENTS.
C. EXCEPT AS MAY BE SPECIFICALLY INDICATED,
OWNER SHALL HAVE FIRST RIGHT OF SALVAGE OF
ELECTRICAL MATERIALS AND EQUIPMENT INTENDED
FOR DEMOLITION. OTHERWISE ELECTRICAL
MATERIALS AND EQUIPMENT REMOVED FROM THE
EXISTING INSTALLATION IN THE COURSE OF
PERFORMING THE INDICATED WORK SHALL BECOME
THE PROPERTY OF THE CONTRACTOR AND SHALL BE
REMOVED FROM THE SITE.
D. CONTRACTOR SHALL PROVIDE NECESSARY LABOR
AND MATERIALS TO MAINTAIN TEMPORARY
ELECTRICAL SYSTEMS AS MAY BE REQUIRED BY
ARCHITECT OR OWNER IN OPERATION DURING THE
CONSTRUCTION PERIOD.
E. EXISTING ELECTRICAL SYSTEMS, CONDUIT AND
WIRING WHICH ARE NOT TO BE DEMOLISHED SHALL
BE PROTECTED FROM DAMAGE DURING THE
DEMOLITION.
F. ABANDONED WIRING SHALL BE REMOVED
COMPLETELY BACK TO SOURCE; EXISTING CONDUIT
MAY BE REUSED IF PRACTICAL, CAPPING OFF
CONDUIT STUBS THAT MAY REMAIN. CONDUIT
PENETRATING WALLS AND FLOORS WHICH ARE TO
REMAIN SHALL BE CUT OFF FLUSH. SEAL
ABANDONED CONDUIT.
G. INFORMATION GIVEN ON THE DRAWINGS IN
REFERENCE TO EXISTING FEATURES HAS BEEN
OBTAINED FROM RECORD DRAWINGS AND RECENT
SITE OBSERVATIONS, BUT CANNOT BE GUARANTEED
TO BE COMPLETELY ACCURATE. VERIFY
INFORMATION BEFORE PROCEEDING WITH ANY
WORK.
H. CONTRACTOR TO MATCH EXISTING EGRESS PATH
UNLESS DIRECTED BY OWNER AND OR ARCHITECT.
LIGHT FIXTURES INDICATED TO BE EQUIPPED WITH
EM BATTERIES ARE DERIVED FROM EXISTING
DOCUMENTATION.
GENERAL NOTES:
1 BASEMENT FLOOR - LIGHTING PLAN
1/8" = 1'-0" 0' 4' 8' 16'
N
REVISIONS:
O R
EG
O
N E
M
PL
O
YM
EN
T
D
EP
AR
TM
EN
T
C O
TT
AG
E
ST
N E, SA
LE
M , O
R
ISSUE DATE:
MKE JOB #:
DESIGNED BY:
CHECKED BY:
DRAWN BY:
SET TYPE:
SL
TH
TH
BID SET
04/10/26
HQJLQHHULQJ#PNH-LQF.FRP
SA
LE
M O
FF
IC
E
E200
BASEMENT FLOOR -
LIGHTING PLAN
DN
DN
A
F
E
D
C
B
CE
CE
(E) TELEPHONE
BACKBOARD
(E) PNL MSB
(E) PNL P
(E) PNL D
(TYP)
(E) PNL B
(E) PNL B2
X1
X1
B
BB
B B
B
A4
C C C
X1
X1
LV
LV
LV
CE
C
LV
LV
C C
C
C
C
D
A4
A4
A4
A4
X1 X1
BE
BE
A4
A4
A4
A4
A4
A4A4
A4A4
A4
A4A4
A4
A4 A4
A4
A4
A4
A4
A4A4 A4
A4
A4
A4
A4
A4
A4 A4
A4
A4
A4 A4
A4
A4
A4
A4
A4
A4
A4
A4
A4E A4
A4E
A4 A4
A4A4
A4A4
A4A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4 A4
A4
A4
X1
A4
A4
A4
A4
A4
A4
A4
A4 A4 A4
A4
A4
A4 A4
A4
A4
A4
A4
A4
A4
A4
A4
A4 A4
A4
A4
A4
A4
A4 A4
A4A4
A4 A4
A4
A2
A4
A2E
A2E
A4EA4EA4E
A4E
A4E
A4E A4E
A4E
A4E A4E A4E
A4E
A4E
C
LVLV
LV
LV
LV
LV
LV
LV
(TYP)
(TYP)
(TYP)
(TYP)
1. INTERCEPT AND MODIFY EXISTING LIGHTING CIRCUIT
AS NECESSARY TO CONNECT TO NEW LIGHT
FIXTURES.
2. SURFACE MOUNT WIRELESS AREA CONTROLLER ON
CEILING. PROVIDE CAT 6 CONNECTION TO LIGHTING
CONTROL PATCH PANEL. SEE DETAIL 1 ON E400.
3. INSTALL LIGHTING CONTROL PATCH PANEL AND
SURFACE MOUNT BACNET INTEGRATION DEVICE. SEE
DETAIL 1 ON SHEET E400.
4. PROVIDE WIRELESS WALL STATION CONTROL
DEVICE. INSTALL IN EXISTING SWITCH J-BOX, VERIFY
EXACT LOCATION. WALL STATION REQUIRES 120V
ELECTRICAL CONNECTION. EXTEND EXISTING
NEUTRAL CONDUCTOR AS NECESSARY. SEE DETAIL 3
ON SHEET E400 FOR BUTTON CONFIGURATION.
5. SEE DETAIL 2 ON E400 FOR TYPICAL EMERGENCY
DRIVER WIRING.
6. CONNECT TO UN-SWITCHED LEG OF LIGHTING
CIRCUIT.
7. PROVIDE WAVELINX PRO UNIVERSAL VOLTAGE
DIMMING SWITCHPACK (RSP-P-010-347) TO CONTROL
CEILING MOUNTED EXHAUST FAN.
KEYED NOTES:
A. CONTRACTOR SHALL VISIT THE SITE AND BECOME
THOROUGHLY FAMILIAR WITH THE EXISTING
CONDITIONS PRIOR TO BIDDING. ELECTRICAL
LIGHTING DEVICES, AND LIGHT FIXTURES SHOWN
DASHED REPRESENT EXISTING TO BE DEMOLISHED.
EXISTING ELECTRICAL LIGHTING DEVICES, AND LIGHT
FIXTURES TO REMAIN ARE SHOWN WITH '(E)'
DESIGNATION OR OTHERWISE SPECIFICALLY NOTED.
B. LABOR AND MATERIALS REQUIRED TO CHANGE THE
EXISTING ELECTRICAL INSTALLATION AS INDICATED
SHALL BE PROVIDED. DRAWINGS ARE DIAGRAMMATIC
AND DO NOT SHOW EXISTING INTERCONNECTING
COMPONENTS.
C. EXCEPT AS MAY BE SPECIFICALLY INDICATED,
OWNER SHALL HAVE FIRST RIGHT OF SALVAGE OF
ELECTRICAL MATERIALS AND EQUIPMENT INTENDED
FOR DEMOLITION. OTHERWISE ELECTRICAL
MATERIALS AND EQUIPMENT REMOVED FROM THE
EXISTING INSTALLATION IN THE COURSE OF
PERFORMING THE INDICATED WORK SHALL BECOME
THE PROPERTY OF THE CONTRACTOR AND SHALL BE
REMOVED FROM THE SITE.
D. CONTRACTOR SHALL PROVIDE NECESSARY LABOR
AND MATERIALS TO MAINTAIN TEMPORARY
ELECTRICAL SYSTEMS AS MAY BE REQUIRED BY
ARCHITECT OR OWNER IN OPERATION DURING THE
CONSTRUCTION PERIOD.
E. EXISTING ELECTRICAL SYSTEMS, CONDUIT AND
WIRING WHICH ARE NOT TO BE DEMOLISHED SHALL
BE PROTECTED FROM DAMAGE DURING THE
DEMOLITION.
F. ABANDONED WIRING SHALL BE REMOVED
COMPLETELY BACK TO SOURCE; EXISTING CONDUIT
MAY BE REUSED IF PRACTICAL, CAPPING OFF
CONDUIT STUBS THAT MAY REMAIN. CONDUIT
PENETRATING WALLS AND FLOORS WHICH ARE TO
REMAIN SHALL BE CUT OFF FLUSH. SEAL
ABANDONED CONDUIT.
G. INFORMATION GIVEN ON THE DRAWINGS IN
REFERENCE TO EXISTING FEATURES HAS BEEN
OBTAINED FROM RECORD DRAWINGS AND RECENT
SITE OBSERVATIONS, BUT CANNOT BE GUARANTEED
TO BE COMPLETELY ACCURATE. VERIFY
INFORMATION BEFORE PROCEEDING WITH ANY
WORK.
H. CONTRACTOR TO MATCH EXISTING EGRESS PATH
UNLESS DIRECTED BY OWNER AND OR ARCHITECT.
LIGHT FIXTURES INDICATED TO BE EQUIPPED WITH
EM BATTERIES ARE DERIVED FROM EXISTING
DOCUMENTATION.
I. CONTRACTOR SHALL PROVIDE A TEMPORARY
NETWORK SOLUTION FOR LIGHTING CONTROLS
DURING CONSTRUCTION. ALL FIXTURES SHALL BE
MAPPED AND INDIVIDUALLY LABELED WITHIN THE
SYSTEM PRIOR TO HANDOFF TO THE OWNER.
GENERAL NOTES:
1 FIRST FLOOR - LIGHTING PLAN
1/8" = 1'-0" 0' 4' 8' 16'
N
REVISIONS:
O R
EG
O
N E
M
PL
O
YM
EN
T
D
EP
AR
TM
EN
T
C O
TT
AG
E
ST
N E, SA
LE
M , O
R
ISSUE DATE:
MKE JOB #:
DESIGNED BY:
CHECKED BY:
DRAWN BY:
SET TYPE:
SL
TH
TH
BID SET
04/10/26
HQJLQHHULQJ#PNH-LQF.FRP
SA
LE
M O
FF
IC
E
E210
FIRST FLOOR -
LIGHTING PLAN
A
F
E
D
C
B
(E) PNL 2A(E) TELEPHONE
BACKBOARD
(TYP)(E) PNL 2B
A4A4
A4
A4A4
A4
A4 A4
A4
A4
A4
A4
A4
A4A4
A4
A4
A4 A4
A4A4A4
CE BE
BB
BB
A4A4A4
A4
A4 A4
A4
A4
A4A4A4
A4
A4A4
A4 A4A4A4A4
A4 A4
A4A4
A4
A4A4
A4
A4
A4
A4A4
A4
A4
A4 A4
A4
A4A4A4 A4 A4 A4
A4A4A4A4
A4 A4 A4 A4
A4A4A4A4
A4 A4 A4 A4
A4A4A4A4
A4 A4 A4 A4
A4 A4 A4
A4A4
A4 A4
A4
A4
A4
A4A4A4
A4
A4 A4A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4 B
BB
BB
B
A4E A4A4 A2E
A2
A2E
A2E
A2 A2
A2EA2
A2
A2
A2
A2
CC
A4
X1
X1
A2
A4
A2E
X1
X1
X1
X1
A4E
A4E
A4E
A4E
A4E
LV
(TYP)
(TYP)
(TYP)
(TYP)
1. INTERCEPT AND MODIFY EXISTING LIGHTING CIRCUIT
AS NECESSARY TO CONNECT TO NEW LIGHT
FIXTURES.
2. SURFACE MOUNT WIRELESS AREA CONTROLLER ON
CEILING. PROVIDE CAT 6 CONNECTION TO LIGHTING
CONTROL PATCH PANEL. SEE DETAIL 1 ON E400.
3. PROVIDE WIRELESS WALL STATION CONTROL
DEVICE. INSTALL IN EXISTING SWITCH J-BOX, VERIFY
EXACT LOCATION. WALL STATION REQUIRES 120V
ELECTRICAL CONNECTION. EXTEND EXISTING
NEUTRAL CONDUCTOR AS NECESSARY. SEE DETAIL 3
ON SHEET E400 FOR BUTTON CONFIGURATION.
4. SEE DETAIL 2 ON E400 FOR TYPICAL EMERGENCY
DRIVER WIRING.
5. CONNECT TO UN-SWITCHED LEG OF LIGHTING
CIRCUIT.
6. PROVIDE WAVELINX PRO UNIVERSAL VOLTAGE
DIMMING SWITCHPACK (RSP-P-010-347) TO CONTROL
CEILING MOUNTED EXHAUST FAN.
KEYED NOTES:
A. CONTRACTOR SHALL VISIT THE SITE AND BECOME
THOROUGHLY FAMILIAR WITH THE EXISTING
CONDITIONS PRIOR TO BIDDING. ELECTRICAL
LIGHTING DEVICES, AND LIGHT FIXTURES SHOWN
DASHED REPRESENT EXISTING TO BE DEMOLISHED.
EXISTING ELECTRICAL LIGHTING DEVICES, AND LIGHT
FIXTURES TO REMAIN ARE SHOWN WITH '(E)'
DESIGNATION OR OTHERWISE SPECIFICALLY NOTED.
B. LABOR AND MATERIALS REQUIRED TO CHANGE THE
EXISTING ELECTRICAL INSTALLATION AS INDICATED
SHALL BE PROVIDED. DRAWINGS ARE DIAGRAMMATIC
AND DO NOT SHOW EXISTING INTERCONNECTING
COMPONENTS.
C. EXCEPT AS MAY BE SPECIFICALLY INDICATED,
OWNER SHALL HAVE FIRST RIGHT OF SALVAGE OF
ELECTRICAL MATERIALS AND EQUIPMENT INTENDED
FOR DEMOLITION. OTHERWISE ELECTRICAL
MATERIALS AND EQUIPMENT REMOVED FROM THE
EXISTING INSTALLATION IN THE COURSE OF
PERFORMING THE INDICATED WORK SHALL BECOME
THE PROPERTY OF THE CONTRACTOR AND SHALL BE
REMOVED FROM THE SITE.
D. CONTRACTOR SHALL PROVIDE NECESSARY LABOR
AND MATERIALS TO MAINTAIN TEMPORARY
ELECTRICAL SYSTEMS AS MAY BE REQUIRED BY
ARCHITECT OR OWNER IN OPERATION DURING THE
CONSTRUCTION PERIOD.
E. EXISTING ELECTRICAL SYSTEMS, CONDUIT AND
WIRING WHICH ARE NOT TO BE DEMOLISHED SHALL
BE PROTECTED FROM DAMAGE DURING THE
DEMOLITION.
F. ABANDONED WIRING SHALL BE REMOVED
COMPLETELY BACK TO SOURCE; EXISTING CONDUIT
MAY BE REUSED IF PRACTICAL, CAPPING OFF
CONDUIT STUBS THAT MAY REMAIN. CONDUIT
PENETRATING WALLS AND FLOORS WHICH ARE TO
REMAIN SHALL BE CUT OFF FLUSH. SEAL
ABANDONED CONDUIT.
G. INFORMATION GIVEN ON THE DRAWINGS IN
REFERENCE TO EXISTING FEATURES HAS BEEN
OBTAINED FROM RECORD DRAWINGS AND RECENT
SITE OBSERVATIONS, BUT CANNOT BE GUARANTEED
TO BE COMPLETELY ACCURATE. VERIFY
INFORMATION BEFORE PROCEEDING WITH ANY
WORK.
H. CONTRACTOR TO MATCH EXISTING EGRESS PATH
UNLESS DIRECTED BY OWNER AND OR ARCHITECT.
LIGHT FIXTURES INDICATED TO BE EQUIPPED WITH
EM BATTERIES ARE DERIVED FROM EXISTING
DOCUMENTATION.
I. CONTRACTOR SHALL PROVIDE A TEMPORARY
NETWORK SOLUTION FOR LIGHTING CONTROLS
DURING CONSTRUCTION. ALL FIXTURES SHALL BE
MAPPED AND INDIVIDUALLY LABELED WITHIN THE
SYSTEM PRIOR TO HANDOFF TO THE OWNER.
GENERAL NOTES:
DN
CE
1 SECOND FLOOR - LIGHTING PLAN
1/8" = 1'-0" 0' 4' 8' 16'
N
REVISIONS:
O R
EG
O
N E
M
PL
O
YM
EN
T
D
EP
AR
TM
EN
T
C O
TT
AG
E
ST
N E, SA
LE
M , O
R
ISSUE DATE:
MKE JOB #:
DESIGNED BY:
CHECKED BY:
DRAWN BY:
SET TYPE:
SL
TH
TH
BID SET
04/10/26
HQJLQHHULQJ#PNH-LQF.FRP
SA
LE
M O
FF
IC
E
E220
SECOND FLOOR -
LIGHTING PLAN
2 ROOF - LIGHTING PLAN
1/8" = 1'-0" 0' 4' 8' 16'
N
REVISIONS:
O R
EG
O
N E
M
PL
O
YM
EN
T
D
EP
AR
TM
EN
T
C O
TT
AG
E
ST
N E, SA
LE
M , O
R
ISSUE DATE:
MKE JOB #:
DESIGNED BY:
CHECKED BY:
DRAWN BY:
SET TYPE:
SL
TH
TH
BID SET
04/10/26
HQJLQHHULQJ#PNH-LQF.FRP
SA
LE
M O
FF
IC
E
E400
ELECTRICAL DETAILS
| Sheets and Views |
| 6367E001-Layout1 |
| 6367E100-Layout1 |
| 6367E110-Layout1 |
| 6367E120-Layout1 |
| 6367E200-Layout1 |
| 6367E210-Layout1 |
| 6367E220-Layout1 |
| 6367E400-Layout |