Attachment B - Tank Specifications.pdf
PDF 878 KB Posted
- Attached to
- AST, UST, Tank and Generator Inspection Services Federal contract opportunity
- Solicitation number
- 36C26025Q0048
About this file
This is a tank specifications document containing detailed information about multiple underground storage tank (UST) systems at VA Medical Centers in Seattle and Tacoma, Washington.
The document details several tanks across different facilities, including both operational and decommissioned tanks. At the Seattle VA Medical Center (1660 S Columbian Way), there are multiple tanks including four exempt heating fuel tanks installed in 1964 and five removed tanks from 1951. The Tacoma VA Medical Center (9600 Veterans Drive) has two operational diesel tanks for emergency power generation - one 25,000-gallon tank installed in 2007 with sacrificial anode and interior lining protection, and one 15,000-gallon double-walled fiberglass tank installed in 1985. The facility also has two closed-in-place leaded gasoline tanks from 1964, two exempt heating fuel tanks from 1978 (30,000 gallons each), and two removed diesel tanks from 1987. All operational tanks have various safety features including spill prevention, overfill protection, and leak detection systems.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C26025Q0048 0002.pdf | ||
| 36C26025Q0048 0001.pdf | ||
| 36C26025Q0048.docx | DOCX document | |
| Attachment A - Monthly Reporting Example.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Underground Storage Tank System Summary UST ID: 4268
Tank Summary
Tank Name Tank Status Tank Install Date
A Exempt 12/31/1964
B Exempt 12/31/1964
2 Exempt 12/31/1964
1 Exempt 12/31/1964
1-R Removed 6/22/1992
3 Removed 3/1/1951
D Removed 3/1/1951
GAS TANK Removed 3/1/1951
4 Removed 3/1/1951
Site Name: Parent - VA MEDICAL CENTER Glossary UST ID: 4268 Facility/Site ID: 9726741 Latitude: 47.56305 Active Tag(s): N/A Address: 1660 S COLUMBIAN WAY Longitude: -122.30825 Responsible Unit: Headquarters
SEATTLE, WA 98108 County: King
Tank Installation:
Tank Status Date: Piping Installation:8/6/1996
12/31/1964
Tank Name: A
Business License Endorsement Expiration:
Tank Information Piping Information
Material:
Construction:
Corrosion Protection:
Manifolded Tank:
Release Detection:
Tank Manufacturer:
Spill Prevention:
Overfill Prevention:
Actual Capacity:
Capacity Range:
Steel
Sacrificial Anode
Material:
Construction:
Corrosion Protection:
SFC* at Tank:
SFC* at Dispenser/Pump:
Primary Release Detection:
Secondary Release Detection:
Pumping System:
Piping Manufacturer:
*SFC = Steel Flex Connector
Secondary Containment
Tank Permanently Closed Date:
Tank Upgrade:
Compartment Substance Stored Substance Used Capacity
1 Heating Fuel
ExemptTank Status:
Page 1 of 5Report Generated: 4/9/2024Toxics Cleanup Program
Tank Installation:
Tank Status Date: Piping Installation:8/6/1996
12/31/1964
Tank Name: B
Business License Endorsement Expiration:
Tank Information Piping Information
Material:
Construction:
Corrosion Protection:
Manifolded Tank:
Release Detection:
Tank Manufacturer:
Spill Prevention:
Overfill Prevention:
Actual Capacity:
Capacity Range:
Steel
Sacrificial Anode
Material:
Construction:
Corrosion Protection:
SFC* at Tank:
SFC* at Dispenser/Pump:
Primary Release Detection:
Secondary Release Detection:
Pumping System:
Piping Manufacturer:
*SFC = Steel Flex Connector
Secondary Containment
Tank Permanently Closed Date:
Tank Upgrade:
Compartment Substance Stored Substance Used Capacity
1 Heating Fuel
ExemptTank Status:
Tank Installation:
Tank Status Date: Piping Installation:8/6/1996
12/31/1964
Tank Name: 2
Business License Endorsement Expiration:
Tank Information Piping Information
Material:
Construction:
Corrosion Protection:
Manifolded Tank:
Release Detection:
Tank Manufacturer:
Spill Prevention:
Overfill Prevention:
Actual Capacity:
Capacity Range:
Steel
Sacrificial Anode
Material:
Construction:
Corrosion Protection:
SFC* at Tank:
SFC* at Dispenser/Pump:
Primary Release Detection:
Secondary Release Detection:
Pumping System:
Piping Manufacturer:
*SFC = Steel Flex Connector
Secondary Containment
Tank Permanently Closed Date:
Tank Upgrade:
Compartment Substance Stored Substance Used Capacity
1 Heating Fuel
Page 2 of 5Report Generated: 4/9/2024Toxics Cleanup Program
Tank Status Date: Piping Installation:8/6/1996
12/31/1964
Tank Name: 1
Business License Endorsement Expiration:
Tank Information Piping Information
Material:
Construction:
Corrosion Protection:
Manifolded Tank:
Release Detection:
Tank Manufacturer:
Spill Prevention:
Overfill Prevention:
Actual Capacity:
Capacity Range:
Steel Material:
Construction:
Corrosion Protection:
SFC* at Tank:
SFC* at Dispenser/Pump:
Primary Release Detection:
Secondary Release Detection:
Pumping System:
Piping Manufacturer:
*SFC = Steel Flex Connector
Secondary Containment
Tank Permanently Closed Date:
Tank Upgrade:
Compartment Substance Stored Substance Used Capacity
1 Heating Fuel
ExemptTank Status:
Tank Installation:
Tank Status Date: Piping Installation:8/25/2008
6/22/1992
Tank Name: 1-R
Business License Endorsement Expiration: 6/30/2003
Tank Information Piping Information
Material:
Construction:
Corrosion Protection:
Manifolded Tank:
Release Detection:
Tank Manufacturer:
Spill Prevention:
Overfill Prevention:
Actual Capacity:
Capacity Range:
Fiberglass Reinforced Plastic
Double Wall Tank
Corrosion Resistant
Manual Inventory Control (daily)
Single Wall Spill Bucket
Automatic Shutoff (fill pipe)
111 TO 1,100 Gallons
Material:
Construction:
Corrosion Protection:
SFC* at Tank:
SFC* at Dispenser/Pump:
Primary Release Detection:
Secondary Release Detection:
Pumping System:
Piping Manufacturer:
*SFC = Steel Flex Connector
Coated Steel
Double Wall Pipe
Corrosion Resistant
Tank Permanently Closed Date: 5/7/2008
5/30/1998Tank Upgrade:
Compartment Substance Stored Substance Used Capacity
1 Unleaded Gasoline Motor Fuel for Vehicles
RemovedTank Status:
Page 3 of 5Report Generated: 4/9/2024Toxics Cleanup Program
Tank Status Date: Piping Installation:4/20/2007
3/1/1951
Tank Name: 3
Business License Endorsement Expiration: 6/30/2003
Tank Information Piping Information
Material:
Construction:
Corrosion Protection:
Manifolded Tank:
Release Detection:
Tank Manufacturer:
Spill Prevention:
Overfill Prevention:
Actual Capacity:
Capacity Range:
Fiberglass Reinforced Plastic
Single Wall Tank
Corrosion Resistant
Vapor Monitoring
Single Wall Spill Bucket
Automatic Shutoff (fill pipe)
6,000 Gallons
5,000 to 9,999 Gallons
Material:
Construction:
Corrosion Protection:
SFC* at Tank:
SFC* at Dispenser/Pump:
Primary Release Detection:
Secondary Release Detection:
Pumping System:
Piping Manufacturer:
*SFC = Steel Flex Connector
Fiberglass
Single Wall Pipe
Corrosion Resistant
Automatic Line Leak Detector (ALLD)
Non-Safe Suction
Tank Permanently Closed Date: 5/12/2008
5/30/1998Tank Upgrade:
Compartment Substance Stored Substance Used Capacity
1 Diesel Emergency Power Generation 6,000 Gallons
RemovedTank Status:
Tank Installation:
Tank Status Date: Piping Installation:8/6/1996
3/1/1951
Tank Name: D
Business License Endorsement Expiration: 2/1/1994
Tank Information Piping Information
Material:
Construction:
Corrosion Protection:
Manifolded Tank:
Release Detection:
Tank Manufacturer:
Spill Prevention:
Overfill Prevention:
Actual Capacity:
Capacity Range:
Steel
Single Wall Tank
Sacrificial Anode
Statistical Inventory Reconciliation
Material:
Construction:
Corrosion Protection:
SFC* at Tank:
SFC* at Dispenser/Pump:
Primary Release Detection:
Secondary Release Detection:
Pumping System:
Piping Manufacturer:
*SFC = Steel Flex Connector
Steel
Single Wall Pipe
Sacrificial Anode
Groundwater Monitoring
Non-Safe Suction
Tank Permanently Closed Date:
Tank Upgrade:
Compartment Substance Stored Substance Used Capacity
Page 4 of 5Report Generated: 4/9/2024Toxics Cleanup Program
Tank Status Date: Piping Installation:1/25/2007
3/1/1951
Tank Name: GAS TANK
Business License Endorsement Expiration:
Tank Information Piping Information
Material:
Construction:
Corrosion Protection:
Manifolded Tank:
Release Detection:
Tank Manufacturer:
Spill Prevention:
Overfill Prevention:
Actual Capacity:
Capacity Range:
Steel
Single Wall Tank
Sacrificial Anode
Statistical Inventory Reconciliation
111 TO 1,100 Gallons
Material:
Construction:
Corrosion Protection:
SFC* at Tank:
SFC* at Dispenser/Pump:
Primary Release Detection:
Secondary Release Detection:
Pumping System:
Piping Manufacturer:
*SFC = Steel Flex Connector
Steel
Single Wall Pipe
Sacrificial Anode
Groundwater Monitoring
Non-Safe Suction
Tank Permanently Closed Date: 12/18/2006
Tank Upgrade:
Compartment Substance Stored Substance Used Capacity
1 Unleaded Gasoline Motor Fuel for Vehicles
RemovedTank Status:
Tank Installation:
Tank Status Date: Piping Installation:8/6/1996
3/1/1951
Tank Name: 4
Business License Endorsement Expiration: 6/30/1999
Tank Information Piping Information
Material:
Construction:
Corrosion Protection:
Manifolded Tank:
Release Detection:
Tank Manufacturer:
Spill Prevention:
Overfill Prevention:
Actual Capacity:
Capacity Range:
Single Wall Tank
Sacrificial Anode
Vapor Monitoring
Single Wall Spill Bucket
Automatic Shutoff (fill pipe)
2,000 Gallons
1,101 to 2,000 Gallons
Material:
Construction:
Corrosion Protection:
SFC* at Tank:
SFC* at Dispenser/Pump:
Primary Release Detection:
Secondary Release Detection:
Pumping System:
Piping Manufacturer:
*SFC = Steel Flex Connector
Coated Steel
Single Wall Pipe
Sacrificial Anode
Vapor Monitoring
Non-Safe Suction
Tank Permanently Closed Date:
5/30/1998Tank Upgrade:
Compartment Substance Stored Substance Used Capacity
1 Diesel Emergency Power Generation 2,000 Gallons
Page 5 of 5Report Generated: 4/9/2024Toxics Cleanup Program
Underground Storage Tank System Summary UST ID: 620128
Tank Name Tank Status Tank Install Date
DIESEL Operational 4/25/2007
Site Name: Energy Plant Bldg 100 Glossary UST ID: 620128 Facility/Site ID: 9726741 Latitude: 47.56305 Active Tag(s): A4100 Address: 1660 S COLUMBIAN WAY Longitude: -122.30825 Responsible Unit: Headquarters
SEATTLE, WA 98108 County: King
Tank Installation:
Tank Status Date: Piping Installation:6/30/2019
4/25/2007
Tank Name: DIESEL
Business License Endorsement Expiration: 6/30/2024
Tank Information Piping Information
Material:
Construction:
Corrosion Protection:
Manifolded Tank:
Release Detection:
Tank Manufacturer:
Spill Prevention:
Overfill Prevention:
Actual Capacity:
Capacity Range:
Steel
Single Wall Tank
Sacrificial Anode and Interior Lining
Automatic Tank Gauging
Single Wall Spill Bucket
Automatic Shutoff (fill pipe)
25,000 Gallons
Material:
Construction:
Corrosion Protection:
SFC* at Tank:
SFC* at Dispenser/Pump:
Primary Release Detection:
Secondary Release Detection:
Pumping System:
Piping Manufacturer:
*SFC = Steel Flex Connector
Steel
Single Wall Pipe
Sacrificial Anode
Safe Suction (No Leak Detection)
Safe Suction
Tank Permanently Closed Date:
Tank Upgrade:
Compartment Substance Stored Substance Used Capacity
1 Diesel Emergency Power Generation 25,000 Gallons
OperationalTank Status:
Page 1 of 1Report Generated: 3/3/2024Toxics Cleanup Program
Underground Storage Tank System Summary UST ID: 620127
Tank Name Tank Status Tank Install Date
C Operational 1/1/1985
Site Name: VA Generator Bldg 16 Glossary UST ID: 620127 Facility/Site ID: 9726741 Latitude: 47.56305 Active Tag(s): A5443 Address: 1660 S COLUMBIAN WAY Longitude: -122.30825 Responsible Unit: Headquarters
SEATTLE, WA 98108 County: King
Tank Installation:
Tank Status Date: Piping Installation:8/6/1996
1/1/1985
Tank Name: C
Business License Endorsement Expiration: 6/30/2024
Tank Information Piping Information
Material:
Construction:
Corrosion Protection:
Manifolded Tank:
Release Detection:
Tank Manufacturer:
Spill Prevention:
Overfill Prevention:
Actual Capacity:
Capacity Range:
Fiberglass Reinforced Plastic
Double Wall Tank
Corrosion Resistant
Automatic Tank Gauging
Single Wall Spill Bucket
Overfill Alarm
15,000 Gallons
20,000 to 29,999 Gallons
Material:
Construction:
Corrosion Protection:
SFC* at Tank:
SFC* at Dispenser/Pump:
Primary Release Detection:
Secondary Release Detection:
Pumping System:
Piping Manufacturer:
*SFC = Steel Flex Connector
Flexible Piping
Double Wall Pipe
Corrosion Resistant
Safe Suction (No Leak Detection)
Non-Safe Suction
Tank Permanently Closed Date:
5/30/1998Tank Upgrade:
Compartment Substance Stored Substance Used Capacity
1 Diesel Emergency Power Generation 15,000 Gallons
OperationalTank Status:
Page 1 of 1Report Generated: 3/3/2024Toxics Cleanup Program
Underground Storage Tank System Summary UST ID: 620130
Tank Name Tank Status Tank Install Date
1 Operational 1/1/1976
Site Name: Sub Station Bldg E129 Glossary UST ID: 620130 Facility/Site ID: 94796432 Latitude: 47.14140 Active Tag(s): A5299 Address: 9600 Veterans Dr. Longitude: -122.56857 Responsible Unit: Headquarters
TACOMA, WA 98493 County: Pierce
Tank Installation:
Tank Status Date: Piping Installation:8/6/1996
1/1/1976
Tank Name: 1
Business License Endorsement Expiration: 6/30/2024
Tank Information Piping Information
Material:
Construction:
Corrosion Protection:
Manifolded Tank:
Release Detection:
Tank Manufacturer:
Spill Prevention:
Overfill Prevention:
Actual Capacity:
Capacity Range:
Steel
Single Wall Tank
Impressed Current
Automatic Tank Gauging
Single Wall Spill Bucket
Overfill Alarm
5,000 Gallons
2,001 to 4,999 Gallons
Material:
Construction:
Corrosion Protection:
SFC* at Tank:
SFC* at Dispenser/Pump:
Primary Release Detection:
Secondary Release Detection:
Pumping System:
Piping Manufacturer:
*SFC = Steel Flex Connector
Other
Double Wall Pipe
Corrosion Resistant
Safe Suction (No Leak Detection)
Safe Suction
Tank Permanently Closed Date:
10/3/1995Tank Upgrade:
Compartment Substance Stored Substance Used Capacity
1 Diesel Emergency Power Generation 5,000 Gallons
OperationalTank Status:
Page 1 of 1Report Generated: 4/9/2024Toxics Cleanup Program
VHAPORCrockD1 Underline
Underground Storage Tank System Summary UST ID: 4748
Tank Name Tank Status Tank Install Date
6 Closed in Place 12/31/1964
7 Closed in Place 12/31/1964
8 Exempt 1/1/1978
9 Exempt 1/1/1978
3 Removed 4/2/1987
2 Removed 1/1/1987
Site Name: Parent - VA MEDICAL HOSPITAL Glossary UST ID: 4748 Facility/Site ID: 94796432 Latitude: 47.14140 Active Tag(s): N/A Address: 9600 Veterans Drive Longitude: -122.56857 Responsible Unit: Headquarters
TACOMA, WA 98493 County: Pierce
Tank Installation:
Tank Status Date: Piping Installation:8/6/1996
12/31/1964
Tank Name: 6
Business License Endorsement Expiration:
Tank Information Piping Information
Material:
Construction:
Corrosion Protection:
Manifolded Tank:
Release Detection:
Tank Manufacturer:
Spill Prevention:
Overfill Prevention:
Actual Capacity:
Capacity Range:
Steel
Sacrificial Anode
111 TO 1,100 Gallons
Material:
Construction:
Corrosion Protection:
SFC* at Tank:
SFC* at Dispenser/Pump:
Primary Release Detection:
Secondary Release Detection:
Pumping System:
Piping Manufacturer:
*SFC = Steel Flex Connector
Steel
Tank Permanently Closed Date:
Tank Upgrade:
Compartment Substance Stored Substance Used Capacity
1 Leaded Gasoline
Closed in PlaceTank Status:
Page 1 of 4Report Generated: 4/9/2024Toxics Cleanup Program
Tank Status Date: Piping Installation:8/6/1996
12/31/1964
Tank Name: 7
Business License Endorsement Expiration:
Tank Information Piping Information
Material:
Construction:
Corrosion Protection:
Manifolded Tank:
Release Detection:
Tank Manufacturer:
Spill Prevention:
Overfill Prevention:
Actual Capacity:
Capacity Range:
Steel
Sacrificial Anode
111 TO 1,100 Gallons
Material:
Construction:
Corrosion Protection:
SFC* at Tank:
SFC* at Dispenser/Pump:
Primary Release Detection:
Secondary Release Detection:
Pumping System:
Piping Manufacturer:
*SFC = Steel Flex Connector
Steel
Tank Permanently Closed Date:
Tank Upgrade:
Compartment Substance Stored Substance Used Capacity
1 Leaded Gasoline
Closed in PlaceTank Status:
Tank Installation:
Tank Status Date: Piping Installation:7/22/2008
1/1/1978
Tank Name: 8
Business License Endorsement Expiration:
Tank Information Piping Information
Material:
Construction:
Corrosion Protection:
Manifolded Tank:
Release Detection:
Tank Manufacturer:
Spill Prevention:
Overfill Prevention:
Actual Capacity:
Capacity Range:
Steel
Single Wall Tank
Single Wall Spill Bucket
30,000 Gallons
30,000 to 49,999 Gallons
Material:
Construction:
Corrosion Protection:
SFC* at Tank:
SFC* at Dispenser/Pump:
Primary Release Detection:
Secondary Release Detection:
Pumping System:
Piping Manufacturer:
*SFC = Steel Flex Connector
Tank Permanently Closed Date:
Tank Upgrade:
Compartment Substance Stored Substance Used Capacity
1 Heating Fuel Space or Process Heating 30,000 Gallons
Page 2 of 4Report Generated: 4/9/2024Toxics Cleanup Program
Tank Status Date: Piping Installation:7/22/2008
1/1/1978
Tank Name: 9
Business License Endorsement Expiration:
Tank Information Piping Information
Material:
Construction:
Corrosion Protection:
Manifolded Tank:
Release Detection:
Tank Manufacturer:
Spill Prevention:
Overfill Prevention:
Actual Capacity:
Capacity Range:
Steel
Single Wall Tank
Single Wall Spill Bucket
30,000 Gallons
20,000 to 29,999 Gallons
Material:
Construction:
Corrosion Protection:
SFC* at Tank:
SFC* at Dispenser/Pump:
Primary Release Detection:
Secondary Release Detection:
Pumping System:
Piping Manufacturer:
*SFC = Steel Flex Connector
Tank Permanently Closed Date:
Tank Upgrade:
Compartment Substance Stored Substance Used Capacity
1 Heating Fuel Space or Process Heating 30,000 Gallons
ExemptTank Status:
Tank Installation:
Tank Status Date: Piping Installation:8/6/1996
4/2/1987
Tank Name: 3
Business License Endorsement Expiration: 6/30/2002
Tank Information Piping Information
Material:
Construction:
Corrosion Protection:
Manifolded Tank:
Release Detection:
Tank Manufacturer:
Spill Prevention:
Overfill Prevention:
Actual Capacity:
Capacity Range:
Steel
Single Wall Tank
Sacrificial Anode
Manual Inventory Control (daily)
Single Wall Spill Bucket
Automatic Shutoff (fill pipe)
111 TO 1,100 Gallons
Material:
Construction:
Corrosion Protection:
SFC* at Tank:
SFC* at Dispenser/Pump:
Primary Release Detection:
Secondary Release Detection:
Pumping System:
Piping Manufacturer:
*SFC = Steel Flex Connector
Flexible Piping
Double Wall Pipe
Corrosion Resistant
Safe Suction (No Leak Detection)
Tank Permanently Closed Date:
5/3/1999Tank Upgrade:
Compartment Substance Stored Substance Used Capacity
1 Diesel Emergency Power Generation
Page 3 of 4Report Generated: 4/9/2024Toxics Cleanup Program
Tank Status Date: Piping Installation:8/6/1996
1/1/1987
Tank Name: 2
Business License Endorsement Expiration: 6/30/2002
Tank Information Piping Information
Material:
Construction:
Corrosion Protection:
Manifolded Tank:
Release Detection:
Tank Manufacturer:
Spill Prevention:
Overfill Prevention:
Actual Capacity:
Capacity Range:
Steel
Single Wall Tank
Sacrificial Anode
Manual Inventory Control (daily)
Single Wall Spill Bucket
Automatic Shutoff (fill pipe)
500 Gallons
111 TO 1,100 Gallons
Material:
Construction:
Corrosion Protection:
SFC* at Tank:
SFC* at Dispenser/Pump:
Primary Release Detection:
Secondary Release Detection:
Pumping System:
Piping Manufacturer:
*SFC = Steel Flex Connector
Flexible Piping
Single Wall Pipe
Corrosion Resistant
Safe Suction (No Leak Detection)
Tank Permanently Closed Date:
5/3/1999Tank Upgrade:
Compartment Substance Stored Substance Used Capacity
1 Diesel Emergency Power Generation 500 Gallons
Page 4 of 4Report Generated: 4/9/2024Toxics Cleanup Program
File details come from the government source that posted it. Updated .