This document is a product specification sheet for Ruud's Endeavor Line Achiever Plus Series Side-Discharge Universal Heat Pump (RD17AZ model). The heat pump is available in 2 to 5 ton sizes, with cooling efficiencies up to 19 SEER2/12 EER2 and heating efficiencies up to 8.5 HSPF2, using R-410A refrigerant. Key features include a variable speed twin rotary compressor, inverter drive technology, Bluetooth connectivity, quiet operation (as low as 58dB), and EcoNet enabled system configuration. The product offers flexible installation compatibility with various HVAC systems, a compact design with footprint options as low as 36.6" tall and 40.2" wide, and qualifies for federal tax credits up to $2000 for qualified heat pumps. The document includes detailed performance data, electrical specifications, refrigerant line sizing information, and dimensional drawings.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Endeavor® Line Achiever Plus® Series Side-Discharge Universal Heat Pump

FORM NO. P22-824 REV. 1

Heat Pumps

RD17AZ

RD17AZ

Cooling Effi ciencies up to: 19 SEER2/12 EER2 Heating Effi ciencies up to: 8.5 HSPF2 Nominal Sizes: 2 to 5 Ton [7.0 to 17.6 kW] Cooling Capacities 22.8 to 53.0 kBTU [6.7 to 15.5 kW] Refrigerant Type: R-410A

*Proper sizing and installation of equipment is critical to achieve optimal performance. Split system air conditioners and heat pumps must be matched with appropriate coil components to meet Energy Star. Ask your Contractor for details or visit www.energystar.gov.

Table of Contents

RD17AZ

Features & Benefits

Model Number Identification

General Data/Electrical Data

Accessories

Unit Dimensions

Clearances

Refrigerant Line Size Information.........................................9-10

Performance Data

Limited Warranty

Table of Contents

Features and Benefits

Features and Benefits

•Flexible & Universal Install Compatibility:
— �Works with nearly any HVAC System – including Ruud

EcoNet® Enabled systems and non-communicating systems

— �Install with any indoor system component via a Ruud algorithm (IMPORTANT: the indoor system component CFM must match the requirement of the outdoor system component)

— �Install as a Universal Replacement with minimal alterations (coil only – with TXV)

• Space Saver Solution: The RD17AZ - with footprint options as low as 36.6" tall and 40.2" wide – is ideal for when installation locations are constrained; but is also perfect for any system or replacement option where an efficient, streamlined look is desired

• Quiet Operation as low as 58dB1: Offers sound dampening features such as a sound blanket, refrigerant tubing design, fan blade approach and innovative compressor and drive technologies – ensure that as efficiency goes up, sound levels stay low

• EcoNet® Enabled2: Automatic system configuration and optimization

• PlusOne® Diagnostics & Bluetooth®3, 4 Connectivity: With the Ruud Contractor & EcoNet® Apps, built-in technology makes advanced set-up, monitoring, troubleshooting, and repairing the product easier than ever before

• PlusOne® Variable Speed Twin Rotary Compressor & Inverter Drive:

— �Features variable speed operation from 45 to 100% capacity with the EcoNet® Smart Thermostat or with legacy and other thermostats when the utility 1 & 2 jumpers are installed or using the Ruud algorithm5

— �Provides precise temperature control, advanced humidity control and greater efficiency

• Brushless DC Condenser Motors (BLDC): Enhances reliability and allows for easier serviceability

• Swept Wing Fan Technology: Features quieter operation and improved unit acoustics

• 7mm Condenser Copper Coil: Requires less refrigerant allowing for a smaller and lighter footprint while enhancing reliability

• Optional Base Pan Heater: Utilizes a built-in thermostat to regulate the heating operation to prevent ice build-up on the base pan during extreme cold weather conditions

• Traditional Refrigerant Piping: Allows for use of existing refrigerant line sets for further ease of replacement installation flexibility

• 10-Year Conditional Parts Warranty (registration required): Coverage when installed as a heat pump only or as part of a system – with no AHRI matched system requirement

•Qualifies for Federal Incentives (conditions apply):
— �Federal Tax Credit compliant system combinations across

all product tonnages (effective through 12/31/32) – up to $2000 for qualified heat pumps

— �Visit Ruud.com/Federal-Incentives

1��Based on Internal R&D Testing, 2023 Sound levels are also dependent on proper installation and location of outdoor product.

2�When installed as part of a complete AHRI-matched, Ruud EcoNet® Enabled system.

3�The Bluetooth® word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of such marks by Rheem® is under license.

Other trademarks and trade names are those of their respective owners.

4�When installed as part of a complete Ruud system where both the outdoor & indoor components feature Bluetooth® Technology.

5�Two-Stage (70% &100% capacity) operation when installed with legacy and other thermostats when the utility 1 & 2 jumpers are not installed.

The 2-Ton model features a single rotary compressor.

R D 17 A Z 24 A J 3 N A

Brand Product Category SEER2 Region Refrigerant Capacity Major Series Voltage Type Controls Minor Series

R - Ruud D - Side-Discharge Heat Pump

17 - 17 SEER2 A - All Regions Z - R-410A 24 - 24,000 [7.03 kW] A - 1st Design J - 208/230/1/60 3 - 3+ Stage N - Non-Communicating A - 1st Series 36 - 36,000 [10.55 kW] 48 - 48,000 [14.07 kW] 60 - 60,000 [17.58 kW]

Brand PRODUCT CATEGORY SEER2 REGION REFRIGERANT CAPACITY MAJOR SERIES

R - RHEEM/RUUD P - HEAT PUMP 16 - 16 SEER2 A - ALL REGIONS Z - R-410A 18 - 18,000 [5.28 kW] A - 1ST DESIGN

24 - 24,000 [7.03 kW]

30 - 30,000 [8.79 kW]

36 - 36,000 [10.55 kW]

42 - 42,000 [12.31 kW]

48 - 48,000 [14.07 kW]

60 - 60,000 [17.58 kW]

Model Number Identification

RD17AZ

Heat Pumps

[ ] Designates Metric Conversions

AVAILABLE MODELS DESCRIPTION

RD17AZ24AJ3NA Endeavor® Line Achiever Plus® Series 2 Ton R-410A Universal Heat Pump

RD17AZ36AJ3NA Endeavor® Line Achiever Plus® Series 3 Ton R-410A Universal Heat Pump

RD17AZ48AJ3NA Endeavor® Line Achiever Plus® Series 4 Ton R-410A Universal Heat Pump RD17AZ60AJ3NA Endeavor® Line Achiever Plus® Series 5 Ton R-410A Universal Heat Pump

RD17AZ24AJ3NA 17 SEER2 Endeavor® Line Classic Plus® R-410A Heat Pump

RD17AZ36AJ3NA 17 SEER2 Endeavor® Line Classic Plus® R-410A Heat Pump

RD17AZ48AJ3NA 17 SEER2 Endeavor ®Line Classic Plus® R-410A Heat Pump

RD17AZ60AJ3NA 17 SEER2 Endeavor® Line Classic Plus® R-410A Heat Pump

STANDARD EQUIPMENT

R-410A Refrigerant

Rotary Compressor

Field Installed Filter Drier

Low Ambient Control Compressor Sound Cover Low Pressure Control Front Seating Service Valves Internal Pressure Relief Valve Easy Access to Internal Components Optimized Venturi Airflow Powder Coated Paint Rust Resistant Screws QR Code External Gauge Ports

Feature 24 36 48 60 R-410a Refrigerant √ √ √ √ Twin Feature 24 36 48 60

R-410a Refrigerant √ √ √ √

Twin Rotary Compressor √ √ √ √

Compressor Sound Blanket √ √ √ √

Field Installed Filter Drier √ √ √ √

Front Seating Service Valves √ √ √ √

Internal Thermal Overload √ √ √ √

Long Line capability √ √ √ √

Low Ambient capability √ √ √ √

3-4-5 Expanded Valve Space √ √ √

Composite Basepan √ √ √ √

15" Access to Internal Components √ √ √

Quick release louver panel design √ √ √ √

No fasteners to remove along bottom √ √ √ √

Optimized Venturi Airflow √ √ √ √

Single row condenser coil √ √ √ √

Powder coated paint √ √ √ √

Rust resistant screws √ √ √ √

QR code √ √ √ √

External gauge ports √ √ √ √

Service trays √ √ √ √

R-410a Refrigerant

Rotary Compressor

Field Installed Filter Drier

Low Ambient Control

Compressor Sound Cover

Low Pressur Control

Front Seating Service Valves

Internal Pressure Relief Valve

Built-in Low Ambient with EcoNet

Easy Access to Internal Components

Quick release louver panel design

Optimized Venturi Airflow

Powder coated paint

Rust resistant screws

QR code

External gauge ports

NOTE: RD17AZ models are communicating when installed as part of a complete AHRI-matched, Ruud EcoNet® Enabled System

General Data/Electrical Data

RD17AZ

General Data

MODEL NO. RD17AZ24AJ3NA RD17AZ36AJ3NA RD17AZ48AJ3NA RD17AZ60AJ3NA

Nominal Tonnage 2.0T 3.0T 4.0T 5.0T

Valve Connections Liquid Line O.D. – in. 3/8 3/8 3/8 3/8

Suction Line O.D. – in. 3/4 3/4 7/8 7/8

Refrigerant (R410A) furnished oz.¹ 81 116 222 236

Compressor Type Outdoor Coil

Net face area – Outer Coil (Sq. Ft.) 11.0 15.1 17.2 17.2

Net face area – Inner Coil (Sq. Ft.) N/A 15.1 17.2 17.2

Tube diameter – in. 0.276 0.276 0.276 0.276

Number of rows 1 2 3 3

Fins per inch 18 18 16 16

Outdoor Fan Diameter – in. 26 28 24 24

Number of blades 3 3 3 3

Motor hp 1/2 1/2 1/3 1/3

Nos 1 1 2 2

CFM 3175 3575 5150 5600

RPM 550 570 650 700

Watts 115 215 315 365

Shipping weight – lbs. 205 271 354 356

Operating weight – lbs. 146 200 278 280

Electrical Data Line Voltage Data (Volts-Phase-Hz) 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60

Maximum overcurrent protection (amps)² 20.0 25.0 40.0 45.0

Minimum circuit ampacity³ 19.0 24.5 38.0 41.0

Compressor

Rated load amps 9.7 10.4 17.0 22.0

Locked rotor amps 25 52 51 51

Condenser Fan Motor Full load amps 3.0 3.0 2.5 2.5

Locked rotor amps 6.4 6.4 4.1 4.1

¹�Refrigerant charge sufficient for 15 ft. length of refrigerant lines. For longer line set requirements see the installation instructions for information about set length and additional refrigerant charge required.

²HACR type circuit breaker of fuse.

³Refer to National Electrical Code manual to determine wire, fuse and disconnect size requirements.

UNIT SIZE -

VOLTAGE, SERIES

STANDARD

RATING (dBA)

SOUND POWER

AS LOW AS

TYPICAL OCTAVE BAND SPECTRUM (dBA WITHOUT TONE ADJUSTMENT) 125 250 500 1000 2000 4000 8000

RD17AZ24 68 61 45.0 54.7 57.5 58.2 53.9 46.7 38.1

RD17AZ36 69 58 44.7 60.8 62.3 57.2 53.9 54.5 44.8

RD17AZ48 74 61 54.0 58.6 63.8 64.9 60.4 54.8 44.9

RD17AZ60 73 63 53.5 59.0 62.6 63.3 57.9 50.4 44.8

Unit Size - Voltage, Series

Standard Rating (dBA)

SOUND POWER

AS LOW AS

TYPICAL

OCTAVE

BAND

SPECTRUM

(dBA without tone adjustment)

125 250 500 1000 2000 4000 8000

RD17AZ24 68 61 45 54.7 57.5 58.2 53.9 46.7 38.1

RD17AZ36 69 58 44.7 60.8 62.3 57.2 53.9 54.5 44.8

RD17AZ48 74 61 54.0 58.6 63.8 64.9 60.4 54.8 44.9

RD17AZ60 73 63 53.5 59.0 62.6 63.3 57.9 50.4 44.8

Accessories/Weighted Sound Power

RD17AZ

Accessories

MODEL NO. RD17AZ24AJ3NA RD17AZ36AJ3NA RD17AZ48AJ3NA RD17AZ60AJ3NA

Compressor crankcase heater* 44-103663-15 44-103663-15 44-103663-15 44-103663-15

Basepan heater 44-109957-01 44-109958-01 44-109957-01 44-109957-01

Low ambient control Included Standard Included Standard Included Standard Included Standard

Compressor sound cover Included Standard Included Standard Included Standard Included Standard

Compressor hard start kit N/A N/A N/A N/A

Low pressure control Included Standard Included Standard Included Standard Included Standard

High pressure control Included Standard Included Standard Included Standard Included Standard

Liquid Line Solenoid (24 VAC, 50/60 Hz)

Solenoid Valve 200RD2T3TVLC 200RD2T3TVLC 200RD2T3TVLC 200RD2T3TVLC

Solenoid Coil 61-AMG24V 61-AMG24V 61-AMG24V 61-AMG24V

Liquid Line Solenoid (120/240 VAC, 50/60 Hz)

Solenoid Valve 200RD2T3TVLC 200RD2T3TVLC 200RD2T3TVLC 200RD2T3TVLC

Solenoid Coil 61-AMG120/240V 61-AMG120/240V 61-AMG120/240V 61-AMG120/240V

MODEL NO. RD17AZ24AJ3NA RD17AZ36AJ3NA RD17AZ48AJ3NA RD17AZ60AJ3NA

Compressor crankcase 44-103663-15 44-103663-15 44-103663-15 44-103663-15

Basepan heater 44-109957-01 44-109958-01 44-109957-01 44-109957-01

Low ambient control Included Standard Included Standard Included Standard Included Standard

Compressor sound cover Included Standard Included Standard Included Standard Included Standard

Compressor hard start kit N/A N/A N/A N/A

Low pressure control Included Standard Included Standard Included Standard Included Standard

High pressure control Included Standard Included Standard Included Standard Included Standard

Liquid Line Solenoid (24 VAC, 50/60 Hz) Solenoid Valve 200RD2T3TVLC 200RD2T3TVLC 200RD2T3TVLC 200RD2T3TVLC

Solenoid Coil 61-AMG24V 61-AMG24V 61-AMG24V 61-AMG24V

Liquid Line Solenoid (120/240 VAC, 50/60 Hz) Solenoid Valve 200RD2T3TVLC 200RD2T3TVLC 200RD2T3TVLC 200RD2T3TVLC

Solenoid Coil 61-AMG120/240V 61-AMG120/240V 61-AMG120/240V 61-AMG120/240V

Weighted Sound Power Level (dBA)

NOTE: Tested in accordance with AHRI Standard 270-08 (not listed in AHRI)

Unit Dimensions

MODEL

NO.

OPERATING SHIPPING

H (Height) L (Length) W (Width) H (Height) L (Length) W (Width)

INCHES mm INCHES mm INCHES mm INCHES mm INCHES mm INCHES mm

RD17AZ24AJ3NA 36.61 930 40.16 1020 16.38 416 43.31 1100 48.43 1230 22.05 560

RD17AZ36AJ3NA 46.38 1178 42.01 1067 19.29 490 53.94 1370 50.00 1270 25.00 635

RD17AZ48AJ3NA 57.80 1468 40.16 1020 16.38 416 65.16 1655 48.43 1230 22.05 560

RD17AZ60AJ3NA 57.80 1468 40.16 1020 16.38 416 65.16 1655 48.43 1230 22.05 560

MODEL

NO. OPERATING SHIPPING

H (Height) L (Length) W (Width) H (Height) L (Length) W (Width)

INCHES mm INCHES mm INCHES mm INCHES mm INCHES mm INCHES mm

RD17AZ24AJ3NA 36.61 930 40.16 1020 16.38 416 43.31 1100 48.43 1230 22.05 560

RD17AZ36AJ3NA 46.38 1178 42.01 1067 19.29 490 53.94 1370 50 1270 25 635

RD17AZ48AJ3NA 57.8 1468 40.16 1020 16.38 416 65.16 1655 48.43 1230 22.05 560

RD17AZ60AJ3NA 57.8 1468 40.16 1020 16.38 416 65.16 1655 48.43 1230 22.05 560

Illustration A1345-02-00

“W”

“L”

“H”

SERVICE PANELS/

INLET CONNECTIONS/

HIGH AND LOW VOLTAGE

ACCESS ALLOW 24" [61.0 CM]

OF CLEARANCE

Unit Dimensions

[ ] Designates Metric Conversions

Illustration

ST-A1345-29-00

48" 48"

48"

48"

48"

24"

30"

WALL

W A

LL

Clearances

Refrigerant Line Size Information

RD17AZ

17 SEER2 VARIABLE SPEED HEAT PUMPS

UNIT SIZE

ALLOWABLE

LIQUID

LINE SIZE

ALLOWABLE

VAPOR

LINE SIZE

OUTDOOR UNIT ABOVE OR BELOW INDOOR UNIT

EQUIVALENT LENGTH (FEET)

< 25 26-50 51-75 76-100 101-125 126-150

MAXIMUM VERTICAL SEPARATION/CAPACITY MULTIPLIER

2.0 TON

*SEE

NOTE 3

1/4" 5/8" 25/1.00 50/0.99 33/0.98 60/0.97 NR NR

5/16" 5/8" 25/1.00 50/0.99 50/0.98 50/0.97 50/0.96 50/0.95

3/8" 5/8" 25/1.00 50/0.99 50/0.98 50/0.97 50/0.96 50/0.95

1/4" *3/4"* 25/1.00 50/1.00 33/0.99 60/0.99 NR NR

5/16" *3/4"* 25/1.00 50/1.00 50/0.99 50/0.99 50/0.99 50/0.98

3/8" *3/4"* 25/1.00 50/1.00 50/0.99 50/0.99 50/0.99 50/0.98

3 TON

5/16" 5/8" 25/0.99 50/0.97 50/0.95 50/0.93 36/0.91 NR

3/8" 5/8" 25/0.99 50/0.97 50/0.95 50/0.93 50/0.91 NR

5/16" 3/4" 25/1.00 50/0.99 50/0.99 50/0.98 36/0.97 20/0.96

3/8" 3/4" 25/1.00 50/0.99 50/0.99 50/0.98 50/0.97 50/0.96

1/2" 3/4" 25/1.00 50/0.99 50/0.99 50/0.98 50/0.97 50/0.96

4 TON

3/8" 3/4" 25/0.99 50/0.98 50/0.96 50/0.95 50/0.93 50/0.92

1/2" 3/4" 25/0.99 50/0.98 50/0.96 50/0.95 50/0.93 50/0.92

3/8" 7/8" 25/1.00 50/0.99 50/0.99 50/0.98 50/0.98 50/0.97

1/2" 7/8" 25/1.00 50/0.99 50/0.99 50/0.98 50/0.98 50/0.97

5 TON

3/8" 3/4" 25/0.98 50/0.97 50/0.95 50/0.93 46/0.91 NR

1/2" 3/4" 25/0.98 50/0.97 50/0.95 50/0.93 50/0.91 NR

3/8" 7/8" 25/0.99 50/0.99 50/0.98 50/0.97 50/0.96 38/0.95

1/2" 7/8" 25/0.99 50/0.99 50/0.98 50/0.97 50/0.96 50/0.95

3/8" 1-1/8"** 25/1.00 50/1.00 50/1.00 50/0.99 50/0.99 38/0.99

1/2" 1-1/8"** 25/1.00 50/1.00 50/1.00 50/0.99 50/0.99 50/0.99

17 SEER2 VARIABLE SPEED HEAT PUMPS

Unit Size "AllowableLiq-uidLine Size"

"AllowableVap-orLine Size"

"Outdoor Unit ABOVE or BELOW Indoor UnitEquivalent Length (Feet)"

< 25 26-50 51-75 76-100 101-125 126-150

Maximum Vertical Separation/Capacity Multiplier

2.0 Ton *SEE 1/4" 5/8" 25/1.00 50/0.99 33/0.98 60/0.97 NR NR

5/16" 5/8" 25/1.00 50/0.99 50/0.98 50/0.97 50/0.96 50/0.95

3/8" 5/8" 25/1.00 50/0.99 50/0.98 50/0.97 50/0.96 50/0.95

1/4" 3/4"* 25/1.00 50/1.00 33/0.99 60/0.99 NR NR

5/16" 3/4"* 25/1.00 50/1.00 50/0.99 50/0.99 50/0.99 50/0.98

3/8" 3/4"* 25/1.00 50/1.00 50/0.99 50/0.99 50/0.99 50/0.98

3 Ton 5/16" 5/8" 25/0.99 50/0.97 50/0.95 50/0.93 36/0.91 NR

3/8" 5/8" 25/0.99 50/0.97 50/0.95 50/0.93 50/0.91 NR

5/16" 3/4" 25/1.00 50/0.99 50/0.99 50/0.98 36/0.97 20/0.96

3/8" 3/4" 25/1.00 50/0.99 50/0.99 50/0.98 50/0.97 50/0.96

1/2" 3/4" 25/1.00 50/0.99 50/0.99 50/0.98 50/0.97 50/0.96

4 Ton 3/8" 3/4" 25/0.99 50/0.98 50/0.96 50/0.95 50/0.93 50/0.92

1/2" 3/4" 25/0.99 50/0.98 50/0.96 50/0.95 50/0.93 50/0.92

3/8" 7/8" 25/1.00 50/0.99 50/0.99 50/0.98 50/0.98 50/0.97

1/2" 7/8" 25/1.00 50/0.99 50/0.99 50/0.98 50/0.98 50/0.97

5 Ton 3/8" 3/4" 25/0.98 50/0.97 50/0.95 50/0.93 46/0.91 NR

1/2" 3/4" 25/0.98 50/0.97 50/0.95 50/0.93 50/0.91 NR

3/8" 7/8" 25/0.99 50/0.99 50/0.98 50/0.97 50/0.96 38/0.95

1/2" 7/8" 25/0.99 50/0.99 50/0.98 50/0.97 50/0.96 50/0.95

3/8" 1-1/8"** 25/1.00 50/1.00 50/1.00 50/0.99 50/0.99 38/0.99

1/2" 1-1/8"** 25/1.00 50/1.00 50/1.00 50/0.99 50/0.99 50/0.99

NOTES:

1) Do not exceed 150 ft. linear line length.

2) Do not exceed 50 ft. vertical separation between indoor and outdoor units.

3) *3/4" vapor line should only be used for 2 ton systems if outdoor unit is below or at same level as indoor unit to assure proper oil return.

4) **1-1/8" vapor line should only be used for 5 ton systems if outdoor unit is below or at same level as indoor unit to assure proper oil return.

5) Always use the smallest liquid line allowable to minimize refrigerant charge.

6) Applications shaded in light gray indicate capacity multipliers between 0.90 and 0.96 which are not recommended, but are allowed.

7) Applications shaded in dark gray are not recommended due to excessive liquid or suction pressure drop.

RD17AZ

17 SEER2 VARIABLE SPEED HEAT PUMPS

UNIT SIZE

ALLOWABLE

LIQUID

LINE SIZE

ALLOWABLE

VAPOR

LINE SIZE

OUTDOOR UNIT ABOVE OR BELOW INDOOR UNIT

EQUIVALENT LENGTH (METERS)

< 8 9-15 16-23 24-30 31-38 39-46

MAXIMUM VERTICAL SEPARATION/CAPACITY MULTIPLIER

7.0 kW

[2.0 TON]

*SEE

NOTE 3

6.35 [1/4] 15.88 [5/8] 8/1.00 15/0.99 10/0.98 20/0.97 NR NR

7.94 [5/16] 15.88 [5/8] 8/1.00 15/0.99 15/0.98 15/0.97 15/0.96 15/0.95

9.53 [3/8] 15.88 [5/8] 8/1.00 15/0.99 15/0.98 15/0.97 15/0.96 15/0.95

6.35 [1/4] 19.05 [3/4] 8/1.00 15/0.99 10/0.99 20/0.99 NR NR

7.94 [5/16] 19.05 [3/4] 8/1.00 15/0.99 15/0.99 15/0.99 15/0.99 15/0.98

9.53 [3/8] 19.05 [3/4] 8/1.00 15/0.99 15/0.99 15/0.99 15/0.99 15/0.98

10.6 kW

[3 TON]

7.94 [5/16] 15.88 [5/8] 8/0.99 15/0.97 15/0.95 15/0.93 11/0.91 NR

9.53 [3/8] 15.88 [5/8] 8/0.99 15/0.97 15/0.95 15/0.93 15/0.91 NR

7.94 [5/16] 19.05 [3/4] 8/1.00 15/0.99 15/0.99 15/0.98 11/0.97 6/0.96

9.53 [3/8] 19.05 [3/4] 8/1.00 15/0.99 15/0.99 15/0.98 15/0.97 15/0.96

12.70 [1/2] 19.05 [3/4] 8/1.00 15/0.99 15/0.99 15/0.98 15/0.97 15/0.96

14.1 kW

[4 TON]

9.53 [3/8] 19.05 [3/4] 8/0.99 15/0.98 15/0.96 15/0.95 15/0.93 15/0.92

12.70 [1/2] 19.05 [3/4] 8/0.99 15/0.98 15/0.96 15/0.95 15/0.93 15/0.92

9.53 [3/8] 22.23 [7/8] 8/1.00 15/0.99 15/0.99 15/0.98 15/0.98 15/0.97

12.70 [1/2] 22.23 [7/8] 8/1.00 15/0.99 15/0.99 15/0.98 15/0.98 15/0.97

17.6 kW

[5 TON]

9.53 [3/8] 19.05 [3/4] 8/0.98 15/0.97 15/0.95 15/0.93 14/0.91 NR

12.70 [1/2] 19.05 [3/4] 8/0.98 15/0.97 15/0.95 15/0.93 15/0.91 NR

9.53 [3/8] 22.23 [7/8] 8/0.99 15/0.99 15/0.98 15/0.97 15/0.96 12/0.95

12.70 [1/2] 22.23 [7/8] 8/0.99 15/0.99 15/0.98 15/0.97 15/0.96 15/0.95

9.53 [3/8] 28.58 [1-1/8]** 8/1.00 15/0.99 15/0.98 15/0.99 15/0.99 12/0.99

12.70 [1/2] 28.58 [1-1/8]** 8/1.00 15/0.99 15/0.98 15/0.99 15/0.99 15/0.99

17 SEER2 VARIABLE SPEED HEAT PUMPS

Unit Size "Allow- "Allowable- "Outdoor Unit

< 8 15-Aug 16-23 24-30 31-38 39-46

Maximum Ver-

"7.0 kW[2.0 6.35 [1/4] 15.88 [5/8] 8/1.00 15/0.99 10/0.98 20/0.97 NR NR

7.94 [5/16] 15.88 [5/8] 8/1.00 15/0.99 15/0.98 15/0.97 15/0.96 15/0.95

9.53 [3/8] 15.88 [5/8] 8/1.00 15/0.99 15/0.98 15/0.97 15/0.96 15/0.95

6.35 [1/4] 19.05 [3/4] 8/1.00 15/0.99 10/0.99 20/0.99 NR NR

7.94 [5/16] 19.05 [3/4] 8/1.00 15/0.99 15/0.99 15/0.99 15/0.99 15/0.98

9.53 [3/8] 19.05 [3/4] 8/1.00 15/0.99 15/0.99 15/0.99 15/0.99 15/0.98

"10.6 kW[3 7.94 [5/16] 15.88 [5/8] 8/0.99 15/0.97 15/0.95 15/0.93 11/0.91 NR

9.53 [3/8] 15.88 [5/8] 8/0.99 15/0.97 15/0.95 15/0.93 15/0.91 NR

7.94 [5/16] 19.05 [3/4] 8/1.00 15/0.99 15/0.99 15/0.98 11/0.97 6/0.96

9.53 [3/8] 19.05 [3/4] 8/1.00 15/0.99 15/0.99 15/0.98 15/0.97 15/0.96

12.7 [1/2] 19.05 [3/4] 8/1.00 15/0.99 15/0.99 15/0.98 15/0.97 15/0.96

"14.1 kW[4 9.53 [3/8] 19.05 [3/4] 8/0.99 15/0.98 15/0.96 15/0.95 15/0.93 15/0.92

12.7 [1/2] 19.05 [3/4] 8/0.99 15/0.98 15/0.96 15/0.95 15/0.93 15/0.92

9.53 [3/8] 22.23 [7/8] 8/1.00 15/0.99 15/0.99 15/0.98 15/0.98 15/0.97

12.7 [1/2] 22.23 [7/8] 8/1.00 15/0.99 15/0.99 15/0.98 15/0.98 15/0.97

"17.6 kW[5 9.53 [3/8] 19.05 [3/4] 8/0.98 15/0.97 15/0.95 15/0.93 14/0.91 NR

12.7 [1/2] 19.05 [3/4] 8/0.98 15/0.97 15/0.95 15/0.93 15/0.91 NR

9.53 [3/8] 22.23 [7/8] 8/0.99 15/0.99 15/0.98 15/0.97 15/0.96 12/0.95

12.7 [1/2] 22.23 [7/8] 8/0.99 15/0.99 15/0.98 15/0.97 15/0.96 15/0.95

9.53 [3/8] 28.58 [1- 8/1.00 36540 36540 15/0.99 15/0.99 12/0.99

12.7 [1/2] 28.58 [1- 8/1.00 36540 36540 15/0.99 15/0.99 15/0.99

NOTES:

1) Do not exceed 46 meters linear line length.

2) Do not exceed 15 meters vertical separation between indoor and outdoor units.

3) *19.05 mm [3/4 in.] vapor line should only be used for 2 ton systems if outdoor unit is below or at same level as indoor unit to assure proper oil return.

4) **28.58 mm [1-1/8 in.] vapor line should only be used for 5 ton systems if outdoor unit is below or at same level as indoor unit to assure proper oil return.

5) Always use the smallest liquid line allowable to minimize refrigerant charge.

6) Applications shaded in light gray indicate capacity multipliers between 0.90 and 0.96 which are not recommended, but are allowed.

7) Applications shaded in dark gray are not recommended due to excessive liquid or suction pressure drop.

Refrigerant Line Size Information (Con’t.)

Performance Data

RD17AZ

DESIGNATED TESTED COMBINATION (DTC)

OUTDOOR UNIT COIL

TOTAL

CAPACITY

BTU/H [KW]

NET SENSIBLE

BTU/H [KW]

NET LATENT

BTU/H [KW] SEER2 EER2 INDOOR CFM

[L/S]

47 DEGREE

HEATING

CAPACITY

BTU/H [KW]

DEGREE

COP

17 DEGREE

HEATING

CAPACITY

BTU/H [KW]

DEGREE

COP

REGION

IV

HSPF2

RD17AZ24AJ3NA RCFZ2417MTANMC 22,800 [6.7] 16,880 [5.0] 5,920 [1.7] 14.3 9.8 ,750 [354] 22,800 [6.7] 3.30 16,000 [4.7] 2.56 7.5

RD17AZ36AJ3NA RCFZ3621MTANMC 34,200 [10.0] 24,238 [7.1] 9,962 [2.9] 14.3 9.8 1,025 [484] 34,200 [10.0] 3.48 23,000 [6.7] 2.62 7.5

RD17AZ48AJ3NA RCFZ4824MTANMC 45,000 [13.2] 31,760 [9.3] 13,240 [3.9] 14.3 9.8 1,250 [590] 45,000 [13.2] 3.42 33,000 [6.7] 2.66 7.5

RD17AZ60AJ3NA RCFZ6024STANMC 53,000 [15.5] 36,263 [10.6] 16,737 [4.9] 14.3 9.8 1,450 [684] 53,000 [15.5] 3.36 36,500 [10.7] 2.50 7.5

OUTDOOR UNIT COIL TOTAL CAPACITY NET SENSIBLE NET LATENT SEER2 EER2 INDOOR CFM 47 DEGREE HEATING CAPACITY 47 DEGREE COP 17 DEGREE HEATING CAPACITY

RD17AZ24AJ3NA RCFZ2417MTANMC 22800 [6.7] 16880 [5.0] 5920 [1.7] 14.3 9.8 750 [354] 22800 [6.7] 3.3 16000 [4.7]

RD17AZ36AJ3NA RCFZ3621MTANMC 34200 [10.0] 24238 [7.1] 9962 [2.9] 14.3 9.8 1025 [484] 34200 [10.0] 3.48 23000 [6.7]

RD17AZ48AJ3NA RCFZ4824MTANMC 45000 [13.2] 31760 [9.3] 13240 [3.9] 14.3 9.8 1250 [590] 45000 [13.2] 3.42 33000 [6.7]

RD17AZ60AJ3NA RCFZ6024STANMC 53000 [15.5] 36263 [10.6] 16737 [4.9] 14.3 9.8 1450 [684] 53000 [15.5] 3.36 36500 [10.7]

OUTDOOR UNIT AIR HANDLER TOTAL CAPACITY NET SENSIBLE NET LATENT SEER2 EER2 INDOOR CFM 47 DEGREE HEATING CAPACITY 47 DEGREE COP 17 DEGREE HEATING CAPACITY

RD17AZ24AJ3NA RH3VZ2417MTACNJ 22800 [6.7] 17500 [5.1] 5300 [1.6] 17 10 750 [354.0] 22800 [6.7] 3.54 15100 [4.4]

RD17AZ36AJ3NA RH3VZ3621MTACNJ 34200 [10.0] 26200 [7.7] 8000 [2.3] 18 11.7 1025 [483.7] 34200 [10.0] 3.69667072 23000 [6.7]

RD17AZ48AJ3NA RH3VZ4824STACNJ 45500 [13.3] 34900 [10.2] 10600 [3.1] 16 11.7 1275 [601.7] 45500 [13.3] 3.613138618 32000 [9.4]

RD17AZ60AJ3NA RH3VZ6024STACNJ 55500 [16.3] 42600 [12.5] 12900 [3.8] 16 10 1500 [707.9] 55500 [16.3] 3.5 36000 [10.6]

DESIGNATED TESTED COMBINATION (DTC)

OUTDOOR UNIT AIR HANDLER

TOTAL

CAPACITY

BTU/H [KW]

NET SENSIBLE

BTU/H [KW]

NET LATENT

BTU/H [KW] SEER2 EER2 INDOOR

CFM [L/S]

47 DEGREE

HEATING

CAPACITY

BTU/H [KW]

DEGREE

COP

17 DEGREE

HEATING

CAPACITY

BTU/H [KW]

DEGREE

COP

REGION

IV

HSPF2

RD17AZ24AJ3NA RH3VZ3617STACNJ 22,600 [6.6] 17,500 [5.1] 5,300 [1.6] 19.0 10.0 ,725 [342.0] 22,600 [6.6] 2.90 18,700 [5.5] 2.50 8.1

RD17AZ36AJ3NA RH3VZ4821STACNJ 34,200 [10.0] 26,200 [7.7] 8,000 [2.3] 18.0 11.7 1,050 [495.0] 34,200 [10.0] 2.78 31,200 [9.1] 2.30 8.1

RD17AZ48AJ3NA RH3VZ6024STACNJ 45,500 [13.3] 34,900 [10.2] 10,600 [3.1] 17.0 11.7 1,375 [649.0] 45,500 [13.3] 2.94 43,000 [12.6] 2.40 8.1

RD17AZ60AJ3NA RH3VZ6024STACNJ 55,500 [16.3] 42,600 [12.5] 12,900 [3.8] 19.0 10.0 1,500 [707.9] 53,500 [15.7] 2.32 50,000 [14.7] 2.00 8.1

Outdoor Unit Air Handler Total Capacity BTU/H [kW]

Net Sensible BTU/H [kW]

Net Latent BTU/H [kW] SEER2 EER2

Indoor CFM [L/s]

47 Degree Heating Capacity BTU/H [kW] 47 Degree COP

17 Degree Heating Capacity BTU/H [kW] 17 Degree COP Region IV HSPF2

RD17AZ24AJ3NA RH3VZ3617STACNJ 22600 [6.6] 17500 [5.1] 5300 [1.6] 19 10 725 [342.0] 22600 [6.6] 2.9 18700 [5.5] 2.5 8.1

RD17AZ36AJ3NA RH3VZ4821STACNJ 34200 [10] 26200 [7.7] 8000 [2.3] 18 11.7 1050 [495] 34200 [10] 2.78 31200 [9.1] 2.3 8.1

RD17AZ48AJ3NA RH3VZ6024STACNJ 45500 [13.3] 34900 [10.2] 10600 [3.1] 17 11.7 1375 [649] 45500 [13.3] 2.94 43000 [12.6] 2.4 8.1

RD17AZ60AJ3NA RH3VZ6024STACNJ 55500 [16.3] 42600 [12.5] 12900 [3.8] 19 10 1500 [707.9] 53500 [15.7] 2.32 50000 [14.7] 2 8.1

Performance Data @ AHRI Standard Conditions – Cooling

NOTE: �This data includes DTC (Designated Test Combination) ratings and is for reference purposes only. A full listing of official ratings and system match-ups, along with downloadable certificates, can be accessed from the AHRI website: www.ahridirectory.org.

[ ] Designates Metric Conversions

GENERAL TERMS OF LIMITED WARRANTY*

Ruud will furnish a replacement for any part of this product which fails in normal use and service within the applicable period stated, in accordance with the terms of the limited warranty.

*For complete details of the Limited and Conditional Warranties, including applicable terms and conditions, contact your local contractor or the Manufacturer for a copy of the product warranty certifi cate.

Conditional Parts (Registration Required) .................................Ten (10) Years Applies to a heat pump only or system installation. Does not require the heat pump to be part of a properly matched system as specifi ed by the Manufac-turer and the Air Conditioning Heating & Refrigeration Institute (AHRI).

PRINTED IN U.S.A. 2/24 QG FORM NO. P22-824 REV. 1

Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and Local codes, regulations, and practices.

5600 Old Greenwood Road Fort Smith, Arkansas 72908 • www.ruud.com

© 2024 Rheem Manufacturing Company. Ruud trademarks owned by Rheem Manufacturing Company.

In keeping with its policy of continuous progress and product improvement, Ruud reserves the right to make changes without notice.

125 Edgeware Road, Unit 1 Brampton, Ontario • L6Y 0P5 • ruud-canada.ca

QG Job No:
Proof No:
Date:
Form No:
Rev: 1
Model No: RD17AZ
No of Pages:
Mktg Initials:
Date_2:
PM Initials 1:
Date_3:
Mktg Initials_2:
Date_4:
PM Initials 1_2:
Date_5:
New Revision: Off
All New: Off
Purchase Order:
Accounting Code: M1
No: Off
undefined: Off
Yes Form No:
Project:
Rheem: Off
Ruud: Off
Friedrich: Off
Russell By Rheem: Off
Sure Comfort: Off
WeatherKing: Off
Durastar: Off
Fujitsu: Off
Mainline Elite: Off
Mainline Performance: Off
Thermal Zone: Off
Submittal Sheet: Off
NOTES:

File details come from the government source that posted it. Updated .