Attachment B - Drawings.pdf
PDF 1 MB Posted
- Attached to
- Internet Services
- Solicitation number
- 148135
- Issued by
- Pulaski County, Arkansas
About this file
This is an electrical infrastructure drawing document prepared by Garver, LLC for the Bill and Hillary Clinton National Airport (LIT) in Little Rock, Arkansas, specifically supporting the Airfield Electrical Infrastructure project dated May 2026 with job number 2502987. The drawings depict existing and proposed electrical systems, including cable routing, ductbanks, handholes, and manholes across the airport's airfield operations areas. The document establishes comprehensive construction requirements, including contractor responsibilities for locating and identifying existing cables prior to any modifications, field verification of utility locations, and adherence to Arkansas State Law regarding the Underground Facilities Damage Prevention Act, which mandates two working days advance notification through the Arkansas One-Call System (1-800-482-8998) before excavating with mechanized equipment.
The drawings specify detailed construction notes addressing cable identification and labeling, concrete encasement requirements for conduits under paved areas, protection of existing equipment during construction, dewatering operations, and demolition procedures for obsolete electrical work. The project includes new electrical infrastructure components such as 16-wide 4-inch communication ductbanks, 3-wide 4-inch power ductbanks, and 1-wide 4-inch controls ductbanks to be installed by others under the Central Utility Plant Project. Contractors are responsible for all repair, replacement, and splicing work at no additional cost to the owner and must comply with electrical safety protocols including lockout/tagout procedures, series circuit hazard awareness, and restoration of demolition work areas to match existing conditions.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DRAWN BY:
DATE:
JOB NO.:
DESIGNED BY:
R
EV
D
AT
E
D
ES
C R
IP
TI
O N
BY
BAR IS ONE INCH ON
ORIGINAL DRAWING
IF NOT ONE INCH ON THIS SHEET,
ADJUST SCALES ACCORDINGLY.
0 1"
DRAWING NUMBER
SHEET
NUMBER
MAY 2026
2502987
THIS DOCUMENT, ALONG WITH THE
IDEAS AND DESIGNS CONVEYED
HEREIN, SHALL BE CONSIDERED
INSTRUMENTS OF PROFESSIONAL
SERVICE AND ARE PROPERTY OF
GARVER, LLC. ANY USE,
REPRODUCTION, OR DISTRIBUTION
OF THIS DOCUMENT, ALONG WITH
THE IDEAS AND DESIGN CONTAINED
HEREIN, IS PROHIBITED UNLESS
AUTHORIZED IN WRITING BY
GARVER, LLC OR EXPLICITLY
ALLOWED IN THE GOVERNING
PROFESSIONAL SERVICES
AGREEMENT FOR THIS WORK.
© 2026 GARVER, LLC
LI
T
IS
P
R
FP
S U
PP
O
R T
N
AT
IO
N
AL
A
IR
PO
R T
LI
TT
LE
R
O C
K, A
R
KA
N
SA
S
BI
LL
A N
D H
IL
LA
R Y
C
LI
N
TO
N
Fi le
: L :\2
5\
A3 1-
- L
IT
IS
P
R
FP
S up po rt\
D ra w in gs \L
IT
A irf ie ld E le ct ric al
In fra st ru ct ur e.
dw g L as t S av e:
/6
/2
4:
P
M L as t s av ed b y:
IC
C ra bt re e
La st p lo tte d by : C ra bt re e, Ia ss ac C
C oo pe
r) Pl ot S ty le
: A
EC
m on o.
ct b Pl ot S ca le
: 1 :4
4.
P lo t D at e:
/7
/2
4:
P
M P lo tte r u se d:
B lu eb ea m
P D
F
NAH
ICC
EN-001
SYMBOL ITEM DESCRIPTION CONSTRUCTION NOTES:
1. THE EXISTING AND THE PROPOSED LOCATIONS OF CABLES ARE APPROXIMATE. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD LOCATING AND IDENTIFYING THE EXISTING CABLES TO DETERMINE THEIR EXACT ROUTING. THE CONTRACTOR SHALL PROACTIVELY AND EXPEDITIOUSLY ACCOMPLISH THIS CABLE IDENTIFICATION WORK PRIOR TO PERFORMING ANY MODIFICATIONS TO THE EXISTING CABLES. COORDINATE IDENTIFICATION WORK WITH THE OWNER AND ENGINEER AND MAKE ALL CORRECTIONS, ADDITIONS, ETC. ON THE AS-BUILT
DRAWINGS.
2. THE CONTRACTOR SHALL BE EXTREMELY CAREFUL WHILE EXCAVATING. ANY CABLE OR CONDUIT / DUCT WHICH IS NICKED OR DAMAGED DURING EXCAVATION SHALL BE PROPERLY AND EXPEDITIOUSLY SPLICED OR THE LENGTH OF CABLE AND CONDUIT / DUCT REPLACED. A SPLICE OR CONDUIT / DUCT MARKER SHALL BE INSTALLED AT ALL SPLICE OR OTHER REPAIR LOCATIONS MORE THAN 2' AWAY FROM A LIGHT, SIGN, HANDHOLE, MANHOLE, OR JUNCTION STRUCTURE. ALL REPAIR AND / OR REPLACEMENT WORK AND MATERIALS SHALL BE SUPPLIED AND INSTALLED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER AND TO THE SATISFACTION OF THE
OWNER AND ENGINEER.
3. ALL CABLES SHALL BE CLEARLY IDENTIFIED, LABELED, AND TAGGED AT ALL POINTS WHERE THEY ARE AVAILABLE FOR CONNECTIONS OR INSPECTION, INCLUDING, BUT NOT LIMITED TO MANHOLES, HANDHOLES, PULL BOXES, AND
JUNCTION BOXES.
4. CONDUITS AND DUCTS UNDER PAVED AREAS SHALL BE CONCRETE ENCASED.
5. CONDUITS AND DUCTS UNDER NON-PAVED AREAS SHALL BE NON-ENCASED, UNLESS OTHERWISE NOTED.
6. DURING CONSTRUCTION, PROTECT ALL EQUIPMENT, DUCTS, CONDUITS, CABLES, ETC. THAT ARE TO REMAIN IN PLACE. WHERE EXISTING ITEMS ARE CUT, BROKEN, OR DAMAGED, THE CONTRACTOR SHALL REPLACE OR REPAIR PROACTIVELY AND EXPEDITIOUSLY THE ITEMS WITH THE SAME TYPE OF ORIGINAL MATERIAL AND CONSTRUCTION OR BETTER AT NO ADDITIONAL COST TO THE OWNER AND TO THE SATISFACTION OF THE OWNER AND ENGINEER.
7. CONTRACTOR IS RESPONSIBLE FOR DEWATERING OPERATIONS PRIOR TO ANY WORK.
CAUTION NOTES:
1. UNDERGROUND UTILITIES EXIST WITHIN AND ADJACENT TO THE LIMITS OF CONSTRUCTION. AN ATTEMPT HAS BEEN MADE TO LOCATE THESE UTILITIES ON THE PLANS, HOWEVER, ALL EXISTING UTILITIES MAY NOT BE SHOWN AND THE ACTUAL LOCATIONS OF THE UTILITIES MAY VARY FROM THE LOCATIONS SHOWN. PRIOR TO BEGINNING ANY TYPE OF EXCAVATION, THE CONTRACTOR SHALL CONTACT THE UTILITIES INVOLVED AND MAKE ARRANGEMENTS FOR THE LOCATION OF THE UTILITIES ON THE GROUND. THE CONTRACTOR SHALL MAINTAIN THE UTILITY LOCATION MARKINGS UNTIL THEY ARE NO
LONGER NECESSARY.
2. ARKANSAS STATE LAW, THE UNDERGROUND FACILITIES DAMAGE PREVENTION ACT, REQUIRES TWO WORKING DAYS ADVANCE NOTIFICATION THROUGH THE ARKANSAS ONE-CALL SYSTEM CENTER BEFORE EXCAVATING USING MECHANIZED EQUIPMENT OR EXPLOSIVES (EXCEPT IN THE CASE OF AN EMERGENCY). THE ONE-CALL SYSTEM PHONE NUMBER IS 1-800-482-8998. THE CONTRACTOR IS ADVISED THAT THERE IS A SEVERE PENALTY FOR NOT MAKING THIS CALL. NOT ALL UTILITY COMPANIES ARE MEMBERS OF THE ARKANSAS ONE-CALL SYSTEM; THEREFORE, THE CONTRACTOR IS ADVISED TO CONTACT ALL NON-MEMBER
UTILITIES AS WELL AS THE ONE-CALL SYSTEM.
ELECTRICAL SAFETY NOTES:
1. SERIES CIRCUITS CAN BE DANGEROUS AND / OR FATAL.
2. LOCKOUT / TAGOUT PROCEDURES SHALL BE FOLLOWED.
DEMOLITION NOTES:
1. RESTORE THE DEMOLITION WORK AREAS TO MATCH EXISTING CONDITIONS.
2. LOCATE, IDENTIFY, AND PROTECT EXISTING SERVICES PASSING THROUGH DEMOLITION AREAS AND SERVING OTHER AREAS OUTSIDE THE DEMOLITION LIMITS. MAINTAIN SERVICES TO AREAS OUTSIDE DEMOLITION LIMITS. WHEN SERVICES MUST BE
INTERRUPTED, INSTALL TEMPORARY SERVICES FOR AFFECTED AREAS.
3. MAINTAIN AND PROTECT EXISTING SERVICES WHICH TRANSIT THE AREAS AFFECTED BY SELECTIVE DEMOLITION.
4. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING SYSTEM EQUIPMENT, DEVICES, ETC., TO REMAIN IN USE WHETHER NOTED ON THE PLANS OR NOT. FIELD VERIFY EXISTING ITEMS TO REMAIN IN USE. WIRING FOR EXISTING DEVICES WHICH MUST BE RE-ROUTED OR WHICH ARE PARTIALLY ABANDONED, SHALL BE RECONNECTED TO SERVICE THE REMAINING DEVICES ON THE
CIRCUIT.
5. THE INTENTION OF THE ELECTRICAL DEMOLITION IS TO DISCONNECT AND REMOVE ALL ELECTRICAL WORK MADE VOID BY THE SCOPE OF THE CONSTRUCTION AND ALTERATION. FIELD VERIFY EXACT MATERIAL QUANTITIES REQUIRED TO BE REMOVED.
6. ALL REMOVED MATERIALS, OTHER THAN REMOVED MATERIALS TO BE RELOCATED, OR TURNED OVER TO THE OWNER, SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE PROJECT SITE.
7. ALL EXISTING ELECTRICAL WORK AND ASSOCIATED RACEWAY AND WIRING WHICH HAS BEEN MADE OBSOLETE BY THE WORK AND / OR IS SHOWN DASHED ON THE ELECTRICAL DEMOLITION DRAWINGS, SHALL BE DISCONNECTED AND REMOVED, UNLESS OTHERWISE NOTED. AN ATTEMPT HAS BEEN MADE TO INDICATE ALL OF THIS WORK, BUT TOTAL ACCURACY IS NOT
GUARANTEED.
8. FOR EXISTING ELECTRICAL EQUIPMENT TO BE REMOVED, DEMOLISH ALL EQUIPMENT, DEVICES, CIRCUITS, CONDUITS, BOXES, AND OTHER APPURTENANCES AS REQUIRED FOR A COMPLETE REMOVAL.
9. CUT OFF BOLT PROTRUSIONS, REMOVE ANCHORS, ETC. AT CEILING, FLOOR, OR WALL SURFACES AS REQUIRED. NO SUPPORT
ITEMS SHALL BE LEFT IN PLACE.
10. REMOVE, CAP, AND / OR RELOCATE EQUIPMENT, OUTLETS, CONDUIT, WIRE, ETC., WHETHER INDICATED ON THE DRAWINGS OR NOT, AND AS MAY BECOME NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VISIBLY EXAMINE ALL EXISTING AREAS DESIGNATED FOR REMOVAL OR MODIFICATION TO DETERMINE THE CONDUIT AND THE WIRING THAT WILL REQUIRE CAPPING AND / OR REMOVAL. THE CONTRACTOR SHALL BE HELD TO HAVING
VISITED THE SITE AND TAKEN ALL EXISTING CONDITIONS INTO CONSIDERATION.
11. IN THE DEMOLITION WORK, REMOVE ALL CABLING ASSOCIATED WITH SYSTEMS BEING REMOVED UNDER THIS PROJECT BACK TO SOURCE. NO CABLE SHALL BE LEFT ABANDONED IN PLACE. REMOVE ALL UNUSED AND EMPTY CONDUIT THAT IS EXPOSED OR WITHIN ACCESSIBLE CEILINGS WHICH IS AFFECTED BY AND IS IN THE AREA OF THE WORK OF THIS CONTRACT.
12. WHERE ELECTRICAL EQUIPMENT, CONDUIT, BOXES, AND SUPPORTING HARDWARE ARE REMOVED, PATCH AND FINISH THE SURFACE (WALL AND CEILING) AS REQUIRED TO MATCH THE EXISTING, UNLESS OTHERWISE NOTED.
13. WHERE BURIED CONDUITS EXTENDING OUT OF A CONCRETE SLAB BECOME ABANDONED, CUT AND GRIND THE CONDUITS OFF
FLUSH WITH TOP OF SLAB AND PLUG WITH NON-SHRINK WATERPROOF GROUT FILL.
14. IN WALLS OR FLOORS WHERE A FLUSH DEVICE IS BEING REMOVED, BUT THE WALL OR FLOOR REMAINS OR FOR ANY OUTLET WHICH MUST REMAIN, BUT HAS A DEVICE REMOVED, PROVIDE A BLANK METAL COVER OVER THE OUTLET. MATCH THE COLOR
AND MATERIAL OF EXISTING REMAINING COVERS IN THE ROOM OR SPACE.
15. WHERE WORK IS TO BE PERFORMED ABOVE EXISTING ACCESSIBLE CEILINGS, CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING CEILING TIES AND GRID WITHOUT DAMAGE, STORAGE OF EXISTING TILES AND GRID WHILE WORK IS BEING
PERFORMED, AND INSTALLATION OF EXISTING GRID AND TILES AFTER WORK IS COMPLETED.
WALL OR POST MOUNTED LIGHT FIXTURE,
ELECTRICAL PANEL OR EQUIPMENT
CABINET, SURFACE MOUNTED, 5'-6"
TO TOP OF ENCLOSURE
20 AMP DUPLEX RECEPTACLE,
MTD. 48" AFF, WITH GROUND
WIRE, "GFCI" INDICATES GROUND
FAULT CIRCUIT INTERRUPTER
NEW EQUIPMENT
EXISTING EQUIPMENT
L-861T TAXIWAY EDGE LIGHT
ELECTRICAL DUCT, NUMBER AND
SIZE OF CONDUITS AS INDICATED
DUCT MARKER
HANDHOLE
MANHOLE
ABOVE FINISHED GRADE
AIRCRAFT OPERATIONS AREA
OBJECT FREE AREA
OBSTACLE FREE ZONE
RUNWAY SAFETY AREA
TAXIWAY SAFETY AREA
POINT OF CURVATURE
POINT OF TANGENCY
DIRECT EARTH BURIED
AFG
AOA
OFA
OFZ
RSA
TSA
PC
PT
DEB
WEATHERPROOF
UNLESS OTHERWISE NOTED
WP
UON
4W-4"
H
M
POLYETHYLENE CONDUITPE
CONDUIT CUT/COUPLE POINT
GEOTHERMAL PIPING
UNDER GROUND
ENTERGY PRIMARY
FAA COMMUNICATIONS
DUCTBANK
COMMUNICATIONS
DUCTBANK
M
E
8W -4
"C
FAA
A-FO24
2W -4"C
T
8W -4
"C
18W
-4"C FAA
A-FO24
H
M F4
M F4
M F4
M
F4
H
U G
E
U G
E
U G
E
U G
E
U G
E
U G
E
UGEUGE
UGEUGE
COMMCOMMCOMMCOMM
CO
M
M
M M
M M
M
M H
H
H
H
M
M
UGE
U G
E U
G E
U G
E
U G
E
UG
E
UGE
UG
E
U G
E
U G
E
U G
E
UG
E
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
U G
E
U G
E
UGEU
G
E
UGE
U G
E
UGE
D
H H
H
H H H
H H H
H H
PWR
480V PUMP STA.
PWR
PUMP STA ALARM
F.O.
12STR-ACS 158
F.O.
12STR-ACS 156
F.O.
12STR-ALCMS C
LTS
HMLP2-1,3,5 & 2,4,6
ATT
1200PR COPPER
FAA
100PR COPPER
LTS
HMLP2
ATT
FO
LIT
FO12 ALCMS-A
LIT
FO12 ALCMS-A
LIT
FO12 ALCMS-C
LIT
FO12 ALCMS-C=AMF
LIT
SMFO72
LIT
MMFO72
2W-5"C
ENTERGY PRIMARY
H
2W-5"C
ENTERGY PRIMARY
FAA
100PR COPPER
4W-4"CFAA COMMUNICATION
DRAWN BY:
DATE:
JOB NO.:
DESIGNED BY:
R
EV
D
AT
E
D
ES
C R
IP
TI
O N
BY
BAR IS ONE INCH ON
ORIGINAL DRAWING
IF NOT ONE INCH ON THIS SHEET,
ADJUST SCALES ACCORDINGLY.
0 1"
DRAWING NUMBER
SHEET
NUMBER
MAY 2026
2502987
THIS DOCUMENT, ALONG WITH THE
IDEAS AND DESIGNS CONVEYED
HEREIN, SHALL BE CONSIDERED
INSTRUMENTS OF PROFESSIONAL
SERVICE AND ARE PROPERTY OF
GARVER, LLC. ANY USE,
REPRODUCTION, OR DISTRIBUTION
OF THIS DOCUMENT, ALONG WITH
THE IDEAS AND DESIGN CONTAINED
HEREIN, IS PROHIBITED UNLESS
AUTHORIZED IN WRITING BY
GARVER, LLC OR EXPLICITLY
ALLOWED IN THE GOVERNING
PROFESSIONAL SERVICES
AGREEMENT FOR THIS WORK.
© 2026 GARVER, LLC
LI
T
IS
P
R
FP
S U
PP
O
R T
N
AT
IO
N
AL
A
IR
PO
R T
LI
TT
LE
R
O C
K, A
R
KA
N
SA
S
BI
LL
A N
D H
IL
LA
R Y
C
LI
N
TO
N
0 20' 40' 80' 120'
(IN FEET)
Fi le
: L :\2
5\
A3 1-
- L
IT
IS
P
R
FP
S up po rt\
D ra w in gs \L
IT
A irf ie ld E le ct ric al
In fra st ru ct ur e.
dw g L as t S av e:
/6
/2
4:
P
M L as t s av ed b y:
IC
C ra bt re e
La st p lo tte d by : C ra bt re e, Ia ss ac C
C oo pe
r) Pl ot S ty le
: A
EC
m on o.
ct b Pl ot S ca le
: 1 :4
4.
P lo t D at e:
/7
/2
4:
P
M P lo tte r u se d:
B lu eb ea m
P D
F
NAH
ICC
ES-101
OVERVIEW EXISTING
MCI HANDHOLE
8W-4" KNOCKOUT ON EXISTING
MANHOLE.
EXISTING COMMUNICATIONS
HANDHOLE, LABLED ATT.
ENTERGY PRIMARY
ENTERGY PRIMARY
TO BE REMOVED BY OTHERS
TO BE REMOVED BY OTHERS
TO BE REMOVED BY OTHERS
2W-5"C ENTERGY PRIMARY
EXISTING 30W-4"C TO BE
ABANDONED/DEMOLISHED IN
FUTURE REHABILITATION WORK
EXISTING FAA MANHOLES
REQUIRES VERIFICATION
OF ABANDONMENT
ES-401
ES-402
MDF/IDF
EXISTING WINDSTREAM INTERNET SERVICE
TO BE REMOVED BY OTHERS
8W-4"C AIRPORT
COMMUNICATIONS AND POWER
2W-5"C ENTERGY PRIMARY
M
E
8W -4
"C
FAA
A-FO24
2W -4"C
T
8W -4
"C
18W
-4"C FAA
A-FO24
H
M F4
M F4
M F4
M
F4
H
U G
E
U G
E
U G
E
U G
E
U G
E
U G
E
UGEUGE
UGEUGE
COMMCOMMCOMMCOMM
CO
M
M
M M
M M
M
M H
H
H
H
M
M
UGE
U G
E U
G E
U G
E
U G
E
UG
E
UGE
UG
E
U G
E
U G
E
U G
E
UG
E
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
U G
E
U G
E
UGEU
G
E
UGE
U G
E
UGE
D
H H
H
H H H
H H H
H H
PWR
480V PUMP STA.
PWR
PUMP STA ALARM
LTS
HMLP2-1,3,5 & 2,4,6
ATT
1200PR COPPER
FAA
100PR COPPER
LTS
HMLP2
ATT
FO
LIT
FO12 ALCMS-A
LIT
FO12 ALCMS-C
LIT
SMFO72
LIT
MMFO72
2W-5"C
ENTERGY PRIMARY
H
2W-5"C
ENTERGY PRIMARY
FAA
100PR COPPER
4W-4"CFAA COMMUNICATION
DRAWN BY:
DATE:
JOB NO.:
DESIGNED BY:
R
EV
D
AT
E
D
ES
C R
IP
TI
O N
BY
BAR IS ONE INCH ON
ORIGINAL DRAWING
IF NOT ONE INCH ON THIS SHEET,
ADJUST SCALES ACCORDINGLY.
0 1"
DRAWING NUMBER
SHEET
NUMBER
MAY 2026
2502987
THIS DOCUMENT, ALONG WITH THE
IDEAS AND DESIGNS CONVEYED
HEREIN, SHALL BE CONSIDERED
INSTRUMENTS OF PROFESSIONAL
SERVICE AND ARE PROPERTY OF
GARVER, LLC. ANY USE,
REPRODUCTION, OR DISTRIBUTION
OF THIS DOCUMENT, ALONG WITH
THE IDEAS AND DESIGN CONTAINED
HEREIN, IS PROHIBITED UNLESS
AUTHORIZED IN WRITING BY
GARVER, LLC OR EXPLICITLY
ALLOWED IN THE GOVERNING
PROFESSIONAL SERVICES
AGREEMENT FOR THIS WORK.
© 2026 GARVER, LLC
LI
T
IS
P
R
FP
S U
PP
O
R T
N
AT
IO
N
AL
A
IR
PO
R T
LI
TT
LE
R
O C
K, A
R
KA
N
SA
S
BI
LL
A N
D H
IL
LA
R Y
C
LI
N
TO
N
0 20' 40' 80' 120'
(IN FEET)
Fi le
: L :\2
5\
A3 1-
- L
IT
IS
P
R
FP
S up po rt\
D ra w in gs \L
IT
A irf ie ld E le ct ric al
In fra st ru ct ur e.
dw g L as t S av e:
/6
/2
4:
P
M L as t s av ed b y:
IC
C ra bt re e
La st p lo tte d by : C ra bt re e, Ia ss ac C
C oo pe
r) Pl ot S ty le
: A
EC
m on o.
ct b Pl ot S ca le
: 1 :4
4.
P lo t D at e:
/7
/2
4:
P
M P lo tte r u se d:
B lu eb ea m
P D
F
NAH
ICC
ES-102
OVERVIEW
PROPOSED
MCI HANDHOLE
8W-4" KNOCKOUT ON EXISTING
MANHOLE.
EXISTING COMMUNICATIONS
HANDHOLE, LABLED ATT.
ENTERGY PRIMARY
ENTERGY PRIMARY
TO BE REMOVED BY OTHERS
2W-5"C ENTERGY PRIMARY
NEW 16W-4"C UNDER CONSTRUCTION
GEOTHERMAL ENERGY
PLANT (GEP)
FLUID COOLER
YARD
EXISTING FAA MANHOLES
REQUIRES VERIFICATION
OF ABANDONMENT
ES-401
ES-402
SB1 ELECTRICAL ROOM
MDF/IDF
EXISTING WINDSTREAM INTERNET SERVICE
8W-4"C AIRPORT
COMMUNICATIONS AND POWER
2W-5"C ENTERGY PRIMARY
DN
MV-XFMR-SB1
MV-XFMR-SB7
MV-XFMR-SB5 MV-XFMR-SB4
MVS-SB1
MVS-SB7 MVS-SB5 MVS-SB4
H
H
M
SB1
UP DRAWN BY:
DATE:
JOB NO.:
DESIGNED BY:
R
EV
D
AT
E
D
ES
C R
IP
TI
O N
BY
BAR IS ONE INCH ON
ORIGINAL DRAWING
IF NOT ONE INCH ON THIS SHEET,
ADJUST SCALES ACCORDINGLY.
0 1"
DRAWING NUMBER
SHEET
NUMBER
MAY 2026
2502987
THIS DOCUMENT, ALONG WITH THE
IDEAS AND DESIGNS CONVEYED
HEREIN, SHALL BE CONSIDERED
INSTRUMENTS OF PROFESSIONAL
SERVICE AND ARE PROPERTY OF
GARVER, LLC. ANY USE,
REPRODUCTION, OR DISTRIBUTION
OF THIS DOCUMENT, ALONG WITH
THE IDEAS AND DESIGN CONTAINED
HEREIN, IS PROHIBITED UNLESS
AUTHORIZED IN WRITING BY
GARVER, LLC OR EXPLICITLY
ALLOWED IN THE GOVERNING
PROFESSIONAL SERVICES
AGREEMENT FOR THIS WORK.
© 2026 GARVER, LLC
LI
T
IS
P
R
FP
S U
PP
O
R T
N
AT
IO
N
AL
A
IR
PO
R T
LI
TT
LE
R
O C
K, A
R
KA
N
SA
S
BI
LL
A N
D H
IL
LA
R Y
C
LI
N
TO
N
(IN FEET)
0 2' 4' 12'8'
Fi le
: L :\2
5\
A3 1-
- L
IT
IS
P
R
FP
S up po rt\
D ra w in gs \L
IT
A irf ie ld E le ct ric al
In fra st ru ct ur e.
dw g L as t S av e:
/6
/2
4:
P
M L as t s av ed b y:
IC
C ra bt re e
La st p lo tte d by : C ra bt re e, Ia ss ac C
C oo pe
r) Pl ot S ty le
: A
EC
m on o.
ct b Pl ot S ca le
: 1 :4
4.
P lo t D at e:
/7
/2
4:
P
M P lo tte r u se d:
B lu eb ea m
P D
F
NAH
ICC
ES-401
NEW 16W-4"C DUCTBANK
EXISTING AIRPORT COMMUNICATIONS AND POWER MANHOLE
NEW 12W-4"C COMMUNICATION DUCTBANK, TO BE
INSTALLED BY OTHERS IN CENTRAL UTILITY PLANT PROJECT
(CUP)
2W-5"C ENTERGY PRIMARY
AIRPORT POWER HANDHOLE
EXISTING 30W-4"C TO BE
ABANDONED/DEMOLISHED AS
PART OF FUTURE WORK
EXISTING ENTERGY PRIMARY HANDHOLE
2W-5"C ENTERGY PRIMARY
NEW 3W-4"C POWER DUCTBANK, TO BE INSTALLED BY
OTHERS IN CENTRAL UTILITY PLANT PROJECT (CUP)
NEW 1W-4"C COMMUNICATIONS DUCTBANK, TO BE INSTALLED
BY OTHERS IN CENTRAL UTILITY PLANT PROJECT (CUP)
NEW 8W-4"C + 2W-6"C
POWER DUCTBANK
NEW 6W-2"C
OVERHEAD CONDUIT
MV-XFMR-SB7
MV-XFMR-SB5
MVS-SB7
MDF A
CAB
#6
CAB
#7
CAB
#8
CAB
#9
CAB
#10
CAB
#11
CAB
#1
EXISTING
CRAC-
MDF1
CAB
#2
CAB
#3
CAB
#4
CAB
#5
CAB
#17
CAB
#18
CAB
#19
CAB
#16
CAB
#15
CAB
#14
CAB
#12
CAB
#13
EXISTING
CRAC
MDF2
GROUND
BAR
MDF B
NORTHWEST
STAIR
CORRIDOR
ELECTRICAL
ROOM
ENTRY
ALCOVE
EXISTING
UPS-B
TELECOMMUNICATIONS
WALL MOUNTING BOARD
EXISTING
PANEL
MDF-UPS-A
EXISTING PANEL
MDF-UPS-B
EXISTING
UPS-A
EXISTING PANEL
1PP03
EXISTING
PANEL PG
EXISTING
PANEL EH2
EXISTING
PANEL 1LP03 DRAWN BY:
DATE:
JOB NO.:
DESIGNED BY:
R
EV
D
AT
E
D
ES
C R
IP
TI
O N
BY
BAR IS ONE INCH ON
ORIGINAL DRAWING
IF NOT ONE INCH ON THIS SHEET,
ADJUST SCALES ACCORDINGLY.
0 1"
DRAWING NUMBER
SHEET
NUMBER
MAY 2026
2502987
THIS DOCUMENT, ALONG WITH THE
IDEAS AND DESIGNS CONVEYED
HEREIN, SHALL BE CONSIDERED
INSTRUMENTS OF PROFESSIONAL
SERVICE AND ARE PROPERTY OF
GARVER, LLC. ANY USE,
REPRODUCTION, OR DISTRIBUTION
OF THIS DOCUMENT, ALONG WITH
THE IDEAS AND DESIGN CONTAINED
HEREIN, IS PROHIBITED UNLESS
AUTHORIZED IN WRITING BY
GARVER, LLC OR EXPLICITLY
ALLOWED IN THE GOVERNING
PROFESSIONAL SERVICES
AGREEMENT FOR THIS WORK.
© 2026 GARVER, LLC
LI
T
IS
P
R
FP
S U
PP
O
R T
N
AT
IO
N
AL
A
IR
PO
R T
LI
TT
LE
R
O C
K, A
R
KA
N
SA
S
BI
LL
A N
D H
IL
LA
R Y
C
LI
N
TO
N
(IN FEET)
0 1' 2' 6'4'
Fi le
: L :\2
5\
A3 1-
- L
IT
IS
P
R
FP
S up po rt\
D ra w in gs \L
IT
A irf ie ld E le ct ric al
In fra st ru ct ur e.
dw g L as t S av e:
/6
/2
4:
P
M L as t s av ed b y:
IC
C ra bt re e
La st p lo tte d by : C ra bt re e, Ia ss ac C
C oo pe
r) Pl ot S ty le
: A
EC
m on o.
ct b Pl ot S ca le
: 1 :4
4.
P lo t D at e:
/7
/2
4:
P
M P lo tte r u se d:
B lu eb ea m
P D
F
NAH
ICC
ES-402
16W-4"C UNDERGROUND DUCT
DIVIDED INTO:
12W-4" COMMUNICATIONS
3W-4" POWER
1W-4" CONTROLS
HVAC DUCTS
12W-4"C STUB-UPS WITH 3 MESH
INNERDUCTS, AND SIZED FOR
FUTURE JUNCTION BOX.
MVS-SB7
MV-XFMR-SB7
MV-XFMR-SB5
| LIT Airfield Electrical Infrastructure-EN-001 |
| LIT Airfield Electrical Infrastructure-ES-101 |
| LIT Airfield Electrical Infrastructure-ES-102 |
| LIT Airfield Electrical Infrastructure-ES-401 |
| LIT Airfield Electrical Infrastructure-ES-402 |
File details come from the government source that posted it. Updated .