Kansas City
10561 Barkley Street, STE 100 Overland Park, KS 66212 t: +1 800.404.7677 e: hello@introba.com www.introba.com
SITE MAP GENERAL NOTES
PROFESSIONAL SEAL
APPLICABLE CODES & REGULATIONS
AERIAL PHOTOGRAPH OF EXISTING CONDITIONS
DRAWING INDEX
100%
CONSTRUCTION
DOCUMENT
11/12/2025
G001
COVER SHEET
100%
CONSTRUCTION
DOCUMENT
STATE OF KANSAS
PARSONS STATE HOSPITAL & TRAINING CENTER
AIR COOLED CHILLER REPLACEMENT
2601 GABRIEL AVE, PARSONS, KS, 67357
BUILDING NUMBER 5700-00020
X-1496
• 2018 INTERNATIONAL BUILDING CODE (IBC)
• 2018 INTERNATIONAL RESIDENTIAL CODE (IRC)
• 2018 INTERNATIONAL EXISTING BUILDING CODE (IEBC)
• 2018 INTERNATIONAL MECHANICAL CODE (IMC)
• 2018 INTERNATIONAL PLUMBING CODE (IPC)
• 2018 INTERNATIONAL FUEL CODE (IFGC)
• INTERNATIONAL ENERGY CONSERVATION CODE (IECC), 2006 EDITION OR ASHRAE 90.1-2007
• 2017 NFPA 70, NATIONAL ELECTRICAL CODE (NEC)
• KANSAS STATE BOILER CODE (K.S.A 22-913 ET SEQ)
TRUE
NORTH
TRUE
NORTH
HICKORY
COTTAGE
HICKORY
COTTAGE
00 - GENERAL
G001 COVER SHEET
23 - MECHANICAL
M000 MECHANICAL LEGEND, ABBREVIATIONS, AND GENERAL NOTES
MD100 MECHANICAL - DEMO PLAN BASEMENT
MD101 MECHANICAL - DEMO PLAN LEVEL 1
M100 MECHANICAL - NEW WORK PLAN BASEMENT
M101 MECHANICAL - NEW WORK PLAN LEVEL 1
M500 MECHANICAL - DETAILS
M600 MECHANICAL - SCHEDULES
26 - ELECTRICAL
E000 ELECTRICAL POWER NOTES, LEGENDS & ABBREVIATIONS
ED100 ELECTRICAL POWER - DEMO PLAN BASEMENT
E100 ELECTRICAL POWER - NEW WORK PLAN BASEMENT
Total sheets: 11
Lisa Akagi - Introba LDA PE KS Seal Signed
M
M
M
S
T
P
M
M
T
DPSL H
T
T
DPT
T
AVG
T T
FS
MECHANICAL ABBREVIATIONS
ACU AIR CONDITIONING UNIT
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
AL ACOUSTIC LINING
ARCH ARCHITECT/ARCHITECTURAL
ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATING
AND AIR-CONDITIONING ENGINEERS
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
AW ACID WASTE
BLDG BUILDING
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BOS BOTTOM OF STEEL
BRD BAROMETRIC RELIEF DAMPER
CAV CONSTANT AIR VOLUME
CC COOLING COIL
CDW CONDENSER WATER
CFM CUBIC FEET PER MINUTE
CHW CHILLED WATER
CLG CEILING
CBC CALIFORNIA BUILDING CODE
CH CHILLER
CI CAST IRON
CT COOLING TOWER
CU COPPER
CL CENTERLINE
COL COLUMN
CONC CONCRETE
CONT CONTINUATION
CW COLD WATER
DB DRY BULB
DH DEHUMIDIFIER
DIM DIMENSION
DIA DIAMETER
DN DOWN
DWG DRAWING
(E) EXISTING
(ER) EXISTING TO BE RELOCATED
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EL ELEVATION
ELEC ELECTRICAL
ET EXPANSION TANK
EW EMERGENCY EYEWASH
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
(F) FUTURE
FCU FAN COIL UNIT
FD FIRE DAMPER
FFE FINISHED FLOOR ELEVATION
FLR FLOOR
FM FLOW METER
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
FPM FEET PER MINUTE
FS FLOW SWITCH
FSD COMBINATION FIRE SMOKE DAMPER WITH ACCESS
FT FEET
GPM GALLONS PER MINUTE
GR GRADE
GV GRAVITY VENTILATOR
HC HEATING COIL
HHW HEATING HOT WATER
HORIZ HORIZONTAL
HVAC HEATING, VENTILATING AND AIR CONDITIONING
HW HOT WATER
HX HEAT EXCHANGER
ID INSIDE DIAMETER
IN. INCHES
KW KILOWATT
LAT LEAVING AIR TEMPERATURE
LWT LEAVING WATER TEMPERATURE
LB POUND WEIGHT
MAX MAXIMUM
MFR MANUFACTURER
MIN MINIMUM
(N) NEW
N/A NOT APPLICABLE
NC NORMALLY CLOSED
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NG NATURAL GAS
NO NORMALLY OPEN
NPT NATIONAL PIPE THREAD
NTS NOT TO SCALE
OA OUTSIDE AIR
OPNG OPENING
P PUMP
POC POINT OF CONNECTION
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIA PSI - ABSOLUTE
PSIG PSI - GAUGE
PVC POLYVINYL CHLORIDE
QTY QUANTITY
(R) REMOVE
RA RETURN AIR
RAH RECIRC AIR HANDLER
RC REHEAT COIL
REF ROOF EXHAUST FAN
SA SUPPLY AIR / SOUND ATTENUATOR
SC SCRUBBER
SCFM STANDARD CUBIC FEET PER MINUTE
SCHD SCHEDULE
SD SMOKE DETECTOR
SF SUPPLY FAN
SIM SIMILAR
SMACNA SHEET METAL AND AIR CONDITIONING
CONTRACTORS NATIONAL ASSOCIATION
SMEF SMOKE EXHAUST FAN
SPEC(S) SPECIFICATION(S)
SS STAINLESS STEEL
ST SOUND ATTENUATOR TRAP
STD(S) STANDARD(S)
TA TRANSFER AIR
TE TEMPERATURE ELEMENT
TEMP TEMPERATURE
TI TEMPERATURE INDICATOR
TOS TOP OF STEEL
TYP TYPICAL
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
V VOLTS
VAV VARIABLE AIR VOLUME
VB VACUUM BREAK
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VTR VENT THROUGH ROOF
VVR VARIABLE VOLUME UNIT WITH REHEAT
W WIDTH
W/O WITHOUT
WB WET BULB
WH WATER HEATER
WLD WELDED
WT WEIGHT
M6.02
DETAIL DESIGNATION
SHEET NUMBER
CH
EQUIPMENT TYPE
EQUIPMENT NUMBER
REVISION CLOUD AND DELTA
POINT OF DISCONNECTION
POINT OF CONNECTION
SYMBOLS AND
ANNOTATION
PRESSURE REDUCING VALVE
PRESSURE REDUCING VALVE GAS
PRESSURE REDUCING VALVE - LINE
FEED
2-WAY CONTROL VALVE, 2-POS
2-WAY CONTROL VALVE, MODULATING
3-WAY CONTROL VALVE, 2-POS
3-WAY CONTROL VALVE, MODULATING
BALL VALVE
BUTTERFLY VALVE
BUTTERFLY VALVE W/OPERATOR
CHECK VALVE
CIRCUIT SETTER
DRAIN VALVE
FLOAT VALVE
T&P RELIEF VALVE
THERMOSTATIC MIXING VALVE
VALVE
WYE STRAINER
WAY STRAINER WITH BLOW OFF
MANUAL AIR VALVE
PLUG VALVE
SOLENOID VALVE
VALVES AND HYDRONIC
ACCESSORIES
CW DOMESTIC COLD WATER
CHWS CHILLED WATER SUPPLY
CHWR CHILLED WATER RETURN
RSL REFRIGERANT SUCTION LINE
RLL REFRIGERANT LIQUID LINE
PIPE DROP
PIPE RISE
PIPE BRANCH RISE
PIPE BRANCH DROP
PIPE BRANCH TEE
PIPE TEE RISE
PIPE TEE DROP
CAPPED PIPE
TEMP GUAGE
PRESSURE GUAGE
UNION
FLEX CONNECTOR
PETES PLUG
VACUUM BREAKER
PIPE GUIDE
PIPE ANCHOR
PIPE LINE DESIGNATIONS
PIPE
CONTROL VALVES & ACTUATORS
SENSORS
MOTORIZED ACTUATOR, 2 POSITION
MOTORIZED ACTUATOR, MODULATING
THERMOSTATIC ACTUATOR
AUTOMATIC AIR VENT
BTU METERTEMPERATURE SENSOR
TEMPERATURE SENSOR WITH
THERMOWELL
TEMPERATURE SENSOR AVERAGING
HYDRONIC FLOW METER
PUMP
HEAT EXCHANGER
PRESSURE TRANSDUCER
HYDRONIC EQUIPMENT (DIAGRAMS)
HYDRONIC LEVEL SENSOR
DIFFERENTIAL PRESSURE SENSOR
AIR COOLED CHILLER
PLANT EQUIPMENT
CPFEXPANSION TANK AIR SEPARATOR
FLOW SWITCH
MECHANICAL LEGEND
- BALL VALVE 2 1/2" AND BELOW
- BUTTERFLY VALVE 3" AND ABOVE
SHUT-OFF VALVE TYPE
CIRCUIT SETTER
BTU METER
EXISTING / DEMOLITION
EXISTING EQUIPMENT, DUCT, PIPE
EXISTING PIPE TO BE REMOVED
EXISTING DUCT OR EQUIPMENT
TO BE REMOVED
NEW EQUIPMENT DUCT PIPE
MECHANICAL GENERAL NOTES
1. ALL EQUIPMENT, DUCTS, PIPING, AND OTHER DEVICES AND MATERIALS INSTALLED OUTSIDE OF
THE BUILDING OR OTHERWISE EXPOSED TO THE WEATHER SHALL BE COMPLETELY
WEATHERPROOFED.
2. PENETRATIONS OF PIPES, CONDUITS, ETC. IN WALLS REQUIRING PROTECTED OPENINGS SHALL
BE FIRE STOPPED.
3. FIRE STOP MATERIAL SHALL BE A UL-LISTED ASSEMBLY APPROVED BY THE FIRE MARSHAL.
4. DESIGN DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS ELBOWS OR
OTHER ELEMENTS WHICH MAY BE REQUIRED. CONTRACTOR SHALL PROVIDE ALL
ACCESSORIES AS NECESSARY FOR A COMPLETE INSTALLATION, WITH NO ADDITIONAL COST
TO THE OWNER.
5. ALL ELBOWS, FITTINGS, ETC., IN PIPING REQUIRED TO CLEAR ALL JOB OBSTRUCTIONS ARE NOT
NECESSARILY INDICATED. ALL NECESSARY TRANSITIONS, FITTINGS AND OFFSETS ARE
REQUIRED WHETHER SHOWN OR NOT.
6. BECAUSE OF THE LIMITED SPACE AVAILABLE TO INSTALL ALL OF THE MECHANICAL WORK,
COORDINATION BETWEEN THE VARIOUS TRADES IS OF THE UTMOST IMPORTANCE. SEE
SPECIFICATION 230100 FOR REQUIRED COORDINATION DRAWINGS.
7. THE CONTRACTOR SHALL COORDINATE STAGING AND SCHEDULING WITH THE OWNER'S
REPRESENTATIVE.
8. DEMOLISH ALL PIPING, EQUIPMENT, ETC., SHOWN TO BE REMOVED, IN ITS ENTIRETY,
INCLUDING ALL HANGERS AND SUPPORTS.
9. THE CONTRACTOR SHALL VERIFY ALL REFRIGERANT PIPING SIZING AND ROUTINGS WITH THE
EQUIPMENT MANUFACTURER. THE CONTRACTOR SHALL ALSO PROVIDE ALL REQUIRED
REFRIGERANT ACCESSORIES AS RECOMMENDED BY THE EQUIPMENT MANUFACTURER FOR
COMPLETE AND FULLY FUNCTIONAL SYSTEMS
10. THE CONTRACTOR SHALL CONNECT THE NEW PORTION OF THE CHILLED WATER SYSTEM TO
THE OWNER'S EXISTING BUILDING CONTROL SYSTEM. REFER TO THE SPECIFICATIONS FOR
ADDITIONAL REQUIREMENTS.
11. REFRIGERANT SERVICE PORTS LOCATED OUTDOORS SHALL BE FITTED WITH LOCKING TYPE
TAMPER RESISTANT CAPS OR SHALL BE PROTECTED FROM UNAUTHORIZED ACCESS BY AN
ACCEPTABLE MEANS.
12. THE OWNER SHALL MAINTAIN ALL SALVAGE RIGHTS OF EQUIPMENT AND MATERIALS REMOVED.
ALL EQUIPMENT AND MATERIALS NOT CLAIMED BY THE OWNER SHALL BE REMOVED FROM THE
PREMISES BY THIS CONTRACTOR.
13. HYDRONIC PIPING SHALL COMPLY WITH CHAPTER 12 OF THE 2018 INTERNATIONAL
MECHANICAL CODE.
14. PRIOR TO PERMIT BEING FINALIZED, A COMPLETE REPORT OF THE TESTING AND ADJUSTING
SHALL BE PROVIDED TO THE OWNER OR OWNER’S REPRESENTATIVE AND FACILITIES
OPERATOR AND FORM TESTING AND ADJUSTING SHALL BE COMPLETED AND PROVIDED TO THE
INSPECTOR.
15. PRIOR TO PERMIT BEING FINALIZED, A COMPLETE REPORT OF THE COMMISSIONING PROCESS
SHALL BE PROVIDED TO THE OWNER OR OWNER'S REPRESENTATIVE AND FACILITIES
OPERATOR, AND FORM VERIFICATION SHALL BE COMPLETED AND PROVIDED TO THE
INSPECTOR.
Kansas City
10561 Barkley Street, STE 100 Overland Park, KS 66212 t: +1 800.404.7677 e: hello@introba.com www.introba.com
© INTROBA, INC. 2025
WHEN THIS DRAWING IS
REPRODUCED AT ORIGINAL
SCALE THIS BAR = 1 INCH
The Professional Designer of Record (DOR), whose signature and personal seal appear on this document, assumes responsibility only for what appears hereon, and disclaims responsibility for all other plans, specifications, estimates, reports, documents or instruments not sealed by the Professional DOR relating to, or intended to be used for, any part or parts of the project to which this document refers. Prints sealed by the DOR bear the embossed or wet seal of the DOR across the signature and date. Copies of this document, as signed and sealed, have been retained by the
Professional DOR. The Professional DOR will not be responsible for subsequent changes to this document, unless the changes are made by the DOR or with the
DOR's written authorization.
1 INCH
ARCHITECTURE &
ENGINEERING
1 62 3 4 5
E
D
C
B
A
D E
P A
R T
M E
N T
O F
A
D M
IN
IS
T R
A T
IO
N
O F
F
IC
E
C
IL
IT
IE
S
P R
O C
U R
E M
E N
T
N A
G E
M E
N T
D E
S
IG
N
C O
N S
T R
U C
T
IO
C
M
P L
IA
N
C E
S
W
H
R R
IS
O
N
S U
IT
E
P E
K A
K
A N
S A
S
P
O N
E
-2
-8
LISA D. AKAGI
PE - 22870
G
A B
R
IE
L A
V E
P
A R
S O
N S
K
S
B U
IL
D
IN
G
N U
M B
E R
-0
P A
R S
O N
S S
T A
T E
H O
S P
IT
A
L
T R
A
IN
IN
G
C E
N T
E R
A
IR
C O
O L E
D C
H
IL
L E
R R
E P
L A
C E
M E
N T
IS
S
U E
D A
T E
/1
/2
D E
S
IG
N E
D B
Y
L D
A
100% CONSTRUCTION
DOCUMENT
S T
A T
E O
F K
A N
S A
S
M000
MECHANICAL LEGEND,
ABBREVIATIONS, AND
GENERAL NOTES
X-1496
PE22870
12/19/2025
UP
BASEMENT
01B
(E) 4" CHWR TO REMAIN
(E) AHU. TO REMAIN
(E) HEAT EXCHANGER
(E) P-1
(E) 4" CHWS TO REMAIN
(E) 2" CHWR TO REMAIN
(E) 2" CHWS TO REMAIN
(E) 2" CHWS TO REMAIN
(E) 2" CHWR TO REMAIN
(E) 4" CHWS TO REMAIN
(E) 4" CHWR TO REMAIN
(E) RS
(E) RL
(E) 2-1/2" CHWS TO REMAIN
(E) 4" CHWS TO REMAIN
(E) 4" CHWS TO REMAIN
(E)3/4" CW FILL FROM
EXISTING BACKFLOW
PREVENTER
(E) EXPANSION TANK
TO REMIAN
(E) AIR SEPARATOR
4 (E) CHEMICAL FEED POT
TO REMIAN
(E) 2" CHWS TO REMAIN
(E) 3/4" CHWR TO REMAIN
(E) 4" CHWR
(E) 2" CHWR
Kansas City
10561 Barkley Street, STE 100 Overland Park, KS 66212 t: +1 800.404.7677 e: hello@introba.com www.introba.com
© INTROBA, INC. 2025
WHEN THIS DRAWING IS
REPRODUCED AT ORIGINAL
SCALE THIS BAR = 1 INCH
The Professional Designer of Record (DOR), whose signature and personal seal appear on this document, assumes responsibility only for what appears hereon, and disclaims responsibility for all other plans, specifications, estimates, reports, documents or instruments not sealed by the Professional DOR relating to, or intended to be used for, any part or parts of the project to which this document refers. Prints sealed by the DOR bear the embossed or wet seal of the DOR across the signature and date. Copies of this document, as signed and sealed, have been retained by the
Professional DOR. The Professional DOR will not be responsible for subsequent changes to this document, unless the changes are made by the DOR or with the
DOR's written authorization.
1 INCH
ARCHITECTURE &
ENGINEERING
1 62 3 4 5
E
D
C
B
A
D E
P A
R T
M E
N T
M
IN
IS
T R
A T
IO
N
O F
F
IC
E
C
IL
IT
IE
S
P R
O C
U R
E M
E
N A
G E
M E
N T
D E
S
IG
N
C O
N S
T R
U C
T
IO
M
P L
IA
N
C E
R R
IS
O
N
S U
IT
E
P E
K A
K
A N
S A
S
O N
E
-2
-8
LISA D. AKAGI
PE - 22870
G
A B
R
IE
L A
V E
P
A R
S O
N S
K
S
B U
IL
D
IN
G
N U
M B
E R
-0
P A
R S
O N
S S
T A
T E
H O
S P
IT
A
L
T R
A
IN
IN
G
C E
N T
E R
A
IR
C O
O L E
D C
H
IL
L E
R R
E P
L A
C E
M E
N T
IS
S
U E
D A
T E
/1
/2
D E
S
IG
N E
D B
Y
L D
A
100% CONSTRUCTION
DOCUMENT
S T
A T
E O
F K
A N
S A
S
MD100
MECHANICAL - DEMO PLAN
BASEMENT
X-1496
2'0' 1' 4'2'0' 1' 4'
1/4" = 1'-0"
MECHANICAL - DEMO - BASEMENT PLAN - DEMO
1. REMOVE EXISTING HEAT EXCHANGERS, ALL
REFRIGERANT PIPING, INSULATION, HANGERS,
VALVES, AND RELATED ACCESSORIES.
2. REMOVE EXISTING CHW CIRCULATING PUMP,
PIPING, INSULATION, HANGERS, VALVES AND
ALL RELATED ACCESSORIES.
3. REMOVE EXISTING AIR SEPARATOR, PIPING,
INSULATION, HANGERS, VALVES, AND ALL
RELATED ACCESSORIES.
4. EXISTING CHEMICAL TREATMENT FEEDER TO
REMAIN.
5. EXISTING EXPANSION TANK TO REMAIN.
6. CONNECT TO EXISTING COLD WATER LINE AND
BACKFLOW PREVENTER PREVIOUSLY
PROVIDING CW MAKE-UP FOR SYSTEM.
7. CONTRACTOR TO VERIFY EXACT LOCATION,
DUTY OF EXISTING PIPE, ELEVATION BEFORE
PROCEEDING WITH NEW WORK. CONTRACTOR
TO MAKE NECESSARY FIELD ADJUSTMENT TO
ACCOMPLISH SCOPE OF WORK SHOWN ON
DRAWINGS.
SHEET KEYNOTES#
D N
RESTR'M/1-2
OFFICE/1-2
CORR.
LAUNDRY
JAN.
OFFICE/1-2
RESTR'M/1-2
RESTR'M/1-2
RESTR'M/1-2
RESTR'M/1-2
BEDR'M/1-2STAFF RMSUPPLY RM
ACC-1
(E) RS
(E) RL
(E) ACC-11
Kansas City
10561 Barkley Street, STE 100 Overland Park, KS 66212 t: +1 800.404.7677 e: hello@introba.com www.introba.com
© INTROBA, INC. 2025
WHEN THIS DRAWING IS
REPRODUCED AT ORIGINAL
SCALE THIS BAR = 1 INCH
The Professional Designer of Record (DOR), whose signature and personal seal appear on this document, assumes responsibility only for what appears hereon, and disclaims responsibility for all other plans, specifications, estimates, reports, documents or instruments not sealed by the Professional DOR relating to, or intended to be used for, any part or parts of the project to which this document refers. Prints sealed by the DOR bear the embossed or wet seal of the DOR across the signature and date. Copies of this document, as signed and sealed, have been retained by the
Professional DOR. The Professional DOR will not be responsible for subsequent changes to this document, unless the changes are made by the DOR or with the
DOR's written authorization.
1 INCH
ARCHITECTURE &
ENGINEERING
1 62 3 4 5
E
D
C
B
A
D E
P A
R T
M E
N T
M
IN
IS
T R
A T
IO
N
O F
F
IC
E
C
IL
IT
IE
S
P R
O C
U R
E M
E
N A
G E
M E
N T
D E
S
IG
N
C O
N S
T R
U C
T
IO
M
P L
IA
N
C E
R R
IS
O
N
S U
IT
E
P E
K A
K
A N
S A
S
O N
E
-2
-8
LISA D. AKAGI
PE - 22870
G
A B
R
IE
L A
V E
P
A R
S O
N S
K
S
B U
IL
D
IN
G
N U
M B
E R
-0
P A
R S
O N
S S
T A
T E
H O
S P
IT
A
L
T R
A
IN
IN
G
C E
N T
E R
A
IR
C O
O L E
D C
H
IL
L E
R R
E P
L A
C E
M E
N T
IS
S
U E
D A
T E
/1
/2
D E
S
IG
N E
D B
Y
L D
A
100% CONSTRUCTION
DOCUMENT
S T
A T
E O
F K
A N
S A
S
MD101
MECHANICAL - DEMO PLAN
LEVEL 1
X-1496
1/4" = 1'-0"
MECHANICAL - DEMO- LEVEL 1 - DEMO
1. REMOVE EXISTING AIR-COOLED CHILLER, ALL
REFRIGERANT PIPING, INSULATION, HANGERS,
VALVES, AND RELATED ACCESSORIES.
SHEET KEYNOTES#
2'0' 1' 4'2'0' 1' 4'
BASEMENT
01B
(E) 4" CHWR
(E) AHU
(E) 4" CHWS
(E) 2" CHWR
(E) 2" CHWS
(E) 2" CHWS
(E) 2" CHWR
(E) 4" CHWS
(E) 4" CHWR
(E) 2-1/2" CHWS
(E) 4" CHWS
(E) 4" CHWS
(E)3/4" CWS FILL FROM EXISTING
BACKFLOW PREVENTER
(E) EXPANSION TANK
(E) CHEMICAL FEED POT
RSL
RLL
AS
P
(E) 3/4" CHWR
3 1
HX
(E)4" CHWR
4" CHWR
4" CHWS
(E) 2" CHWR
Kansas City
10561 Barkley Street, STE 100 Overland Park, KS 66212 t: +1 800.404.7677 e: hello@introba.com www.introba.com
© INTROBA, INC. 2025
WHEN THIS DRAWING IS
REPRODUCED AT ORIGINAL
SCALE THIS BAR = 1 INCH
The Professional Designer of Record (DOR), whose signature and personal seal appear on this document, assumes responsibility only for what appears hereon, and disclaims responsibility for all other plans, specifications, estimates, reports, documents or instruments not sealed by the Professional DOR relating to, or intended to be used for, any part or parts of the project to which this document refers. Prints sealed by the DOR bear the embossed or wet seal of the DOR across the signature and date. Copies of this document, as signed and sealed, have been retained by the
Professional DOR. The Professional DOR will not be responsible for subsequent changes to this document, unless the changes are made by the DOR or with the
DOR's written authorization.
1 INCH
ARCHITECTURE &
ENGINEERING
1 62 3 4 5
E
D
C
B
A
D E
P A
R T
M E
N T
M
IN
IS
T R
A T
IO
N
O F
F
IC
E
C
IL
IT
IE
S
P R
O C
U R
E M
E
N A
G E
M E
N T
D E
S
IG
N
C O
N S
T R
U C
T
IO
M
P L
IA
N
C E
R R
IS
O
N
S U
IT
E
P E
K A
K
A N
S A
S
O N
E
-2
-8
LISA D. AKAGI
PE - 22870
G
A B
R
IE
L A
V E
P
A R
S O
N S
K
S
B U
IL
D
IN
G
N U
M B
E R
-0
P A
R S
O N
S S
T A
T E
H O
S P
IT
A
L
T R
A
IN
IN
G
C E
N T
E R
A
IR
C O
O L E
D C
H
IL
L E
R R
E P
L A
C E
M E
N T
IS
S
U E
D A
T E
/1
/2
D E
S
IG
N E
D B
Y
L D
A
100% CONSTRUCTION
DOCUMENT
S T
A T
E O
F K
A N
S A
S
M100
MECHANICAL - NEW WORK
PLAN BASEMENT
X-1496
1/4" = 1'-0"
MECHANICAL - NEW WORK - BASEMENT PLAN
SHEET KEYNOTES#
1. INSTALL NEW CHILLED WATER PUMP P-1 ON
EXISTING PAD. MAKE ALTERATIONS TO PAD TO
FIT EQUIPMENT FURNISHED CONNECT EXISTING
CHILLED WATER PIPING AND ADJUST ROUTING
TO FIT EQUIPMENT FURNISHED. FOR
INSTALLATION, REFER TO DETAIL 4/M500.
2. INSTALL NEW AIR SEPARATOR TO EXISTING
PIPING. MAKE ANY ADJUSTMENTS TO FIT
EQUIPMENT FURNISHED. CONNECT EXISTING
CHILLED WATER PIPING AND ADJUST ROUTING
TO FIT EQUIPMENT FURNISHED. FOR
INSTALLATION, REFER TO DETAIL 3/M500.
3. INSTALL NEW HEAT EXCHANGER ON EXISTING
PAD. MAKE ALTERATIONS TO PAD AS NEEDED
TO FIT EQUIPMENT FURNISHED. CONNECT
EXISTING CHILLED WATER PIPING AND NEW
REFRIGERANT PIPING AND ADJUST ROUTING TO
FIT EQUIPMENT FURNISHED. SEE DETAIL 1/M500
FOR PIPING ACCESSORIES REQUIRED.
4. INSTALL NEW REFRIGERANT PIPE BETWEEN
NEW CHILLER CONDENSER AND PLATE AND
FRAME HEAT EXCHANGER EVAPORATOR.
ROUTE REFRIGERANT PIPING THRU EXISTING
SLEEVES IN WALL AND PER INSTALL DETAIL
2/M500. INCLUDE ALL ACCESSORIES SHOWN IN
DETAIL 1/M500.
5. REFRIGERANT PIPE SIZES NOT SHOWN. PIPING
SHALL BE SIZED BY THE CONTRACTOR BASED
ON FINAL SHOP DRAWING LAYOUT AND SHALL
BE COORDINATED WITH MANUFACTURER
AND/OR THE INSTALLATION AND OPERATION
MANUALS.
2'0' 1' 4'2'0' 1' 4'
DN
N
DN
D N
WDWD
BEDR'M/1-2
C0RR.
RESTR'M/1-2
C0RR.
CLOSET
KITCHEN/1-2
12A
OFFICE/1-2
REC RM/1-2
STORAGEMEDS/1-2
CORR.
SOILED
LINEN
LAUNDRY
AIDE'S RR
JAN.
AIDE'S STATION CORR.
LIV RM/1-2
STAIRWAY
CLOSET
CLOSET
ACTIVITIES/1-2
BEDR'M/1-2
BEDR'M/1-2
BEDR'M/1-2
BEDR'M/1-2
BEDR'M/1-2
BEDR'M/1-2
BEDR'M/1-2
DW
OFFICE/1-2
RESTR'M/1-2
RESTR'M/1-2
BEDR'M/1-2
BEDR'M/1-2
BEDR'M/1-2
RESTR'M/1-2
RESTR'M/1-2
RESTR'M/1-2
BEDR'M/1-2
BEDR'M/1-2STAFF RMSUPPLY RM
59 / 11.8"
35"
59 / 11.8"
35"
BEDR'M/1-2
BEDR'M/1-2
BEDR'M/1-2
BEDR'M/1-2
BEDR'M/1-2
BEDR'M/1-2
DN
ACC-1
RSL
RLL
NEW ACC-11
Kansas City
10561 Barkley Street, STE 100 Overland Park, KS 66212 t: +1 800.404.7677 e: hello@introba.com www.introba.com
© INTROBA, INC. 2025
WHEN THIS DRAWING IS
REPRODUCED AT ORIGINAL
SCALE THIS BAR = 1 INCH
The Professional Designer of Record (DOR), whose signature and personal seal appear on this document, assumes responsibility only for what appears hereon, and disclaims responsibility for all other plans, specifications, estimates, reports, documents or instruments not sealed by the Professional DOR relating to, or intended to be used for, any part or parts of the project to which this document refers. Prints sealed by the DOR bear the embossed or wet seal of the DOR across the signature and date. Copies of this document, as signed and sealed, have been retained by the
Professional DOR. The Professional DOR will not be responsible for subsequent changes to this document, unless the changes are made by the DOR or with the
DOR's written authorization.
1 INCH
ARCHITECTURE &
ENGINEERING
1 62 3 4 5
E
D
C
B
A
D E
P A
R T
M E
N T
M
IN
IS
T R
A T
IO
N
O F
F
IC
E
C
IL
IT
IE
S
P R
O C
U R
E M
E
N A
G E
M E
N T
D E
S
IG
N
C O
N S
T R
U C
T
IO
M
P L
IA
N
C E
R R
IS
O
N
S U
IT
E
P E
K A
K
A N
S A
S
O N
E
-2
-8
LISA D. AKAGI
PE - 22870
G
A B
R
IE
L A
V E
P
A R
S O
N S
K
S
B U
IL
D
IN
G
N U
M B
E R
-0
P A
R S
O N
S S
T A
T E
H O
S P
IT
A
L
T R
A
IN
IN
G
C E
N T
E R
A
IR
C O
O L E
D C
H
IL
L E
R R
E P
L A
C E
M E
N T
IS
S
U E
D A
T E
/1
/2
D E
S
IG
N E
D B
Y
L D
A
100% CONSTRUCTION
DOCUMENT
S T
A T
E O
F K
A N
S A
S
M101
MECHANICAL - NEW WORK
PLAN LEVEL 1
X-1496
8'0' 4' 16'
1/8" = 1'-0"
MECHANICAL - NEW WORK - LEVEL 1
1. INSTALL NEW AIR-COOLED CHILLER ON
EXISTING CONCRETE PAD. INSTALL NEW
REFRIGERANT PIPING, INSULATION, HANGERS,
VALVES, AND RELATED ACCESSORIES. ROUTE
NEW REFRIGERANT PIPING THROUGH EXISTING
SLEEVES IN WALL.
SHEET KEYNOTES#
SHUT OFF VALVE,
(TYP), SEE SPEC FOR
TYPE
CALIBRATED BALANCE
VALVE (TYP)
3/4" DRAIN VALVE, NIPPLE,
AND CAP (TYP)
CONCENTRIC REDUCER (IF
REQUIRED)
ECCENTRIC INCREASER (IF
REQUIRED)
CONCENTRIC REDUCER
(IF REQUIRED)
STRAINER WITH
BLOWDOWN VALVE,
NIPPLE, AND CAP
SOURCE
M
M 2-WAY MODULATING
CONTROL VALVE
SYSTEM
PRESSURE AND TEMPERATURE TEST
PLUGS (TYP). INSTALL AT SAME
ELEVATION.
RELIEF VALVE PIPED TO FLOOR
DRAIN (2 TYP)
NOTE:
PIPING ARRANGEMENT IN AND OUT OF HEAT EXCHANGER MAY VARY
BETWEEN MANUFACTURERS. CONTRACTOR SHALL MAKE ALL PIPING
CONNECTIONS IN ACCORDANCE TO SPECIFIC MANUFACTURER'S GUIDELINES.
HX
MANUAL AIR
VENT (TYP)
UNION OR FLANGE (TYP)
CHWS
CHWR
RLL
RSL
OAKUM PACKING
BITUMASTIC SEAL
HOT PITCH SEAL FOR
EXTERIOR BELOW GRADE
HYDRO-STATIC CLOSURE
("LINK-SEAL")
CORE DRILL OPENING
STEEL PIPE
REFER TO
SPECIFICATIONS FOR
PIPE REQUIREMENTS
OUTSIDE WALL
LONG
RADIUS
ELBOW
ADJUSTABLE PIPE
SUPPORT LEG
LEVEL PUMP AND FILL
WITH NON-SHRINK
GROUT
3/4" DRAIN VALVE W/
HOSE CONNECTION
GROUTABLE
FABRICATED
STEEL BASE PLATE
NOTES:
1. PUMP MOUNTED PER MANUFACTURER'S RECOMMENDATION.
2. LONG-RADIUS PIPE ELBOWS REQUIRED PER SPECIFICATIONS.
3. SUCTION DIFFUSER MAY BE USED IN LIEU OF STRAINER, STRAIGHT
PIPE, BEND AND REDUCER. ONLY WHEN SPACE DOES NOT PERMIT
STRAIGHT PIPE LENGTH AT INLET
4. REFER TO SPECIFICATION SECTION 230548 FOR DETAILS.
5. GROUT BASE AFTER PIPE INSTALLATION AND SYSTEM IS FILLED.
6. INERTIA BASE SHALL BE SIZED TO SUPPORT PUMP AND SUCTION
ELBOW.
7. REFER TO SINGLE LINE DIAGRAMS FOR PIPE SIZES.
8. PROVIDE MINIMUM FIVE (5) DIAMETERS OF STRAIGHT PIPE.
9. IF STRAIGHT PIPE IS GREATER THAN TWENTY (20) PIPE DIAMETERS OF
SUCTION PIPE, ROUTE FROM BELOW FLAT SIDE OF REDUCER TO BE ON
TOP SIDE OF PIPE.
10. PUMP IS CONSTANT FLOW. ADJUST CHILLED WATER SUPPLY
TEMPERATURE WITH A MIXING BYPASS ADDING CHILLED WATER
RETURN FLOW TO THE CHILLED WATER SUPPLY FLOW, LOWERING THE
CHILLED WATER SUPPLY TEMPERATURE DURING PART LOAD USAGE.
FLOW THROUGH HEAT EXCHANGER AND THE PUMP SHALL REMAIN
CONSTANT.
P
COUPLING GUARD
PUMP
MOTOR
CONCENTRIC
REDUCER
(WHERE REQUIRED)
NEOPRENE FLEX
CONNECTOR W/
CONTROL CABLE
CHECK VALVE
BALANCING VALVE
SHUT-OFF VALVE
PRESSURE
GAUGE
1/2"ø
NEEDLE
VALVE
(TYP.)
STRAINER W/
BLOWDOWN
SHUT-OFF
VALVE
PIPE HANGER W/
VIBRATION ISOLATION
5" CONCRETE
PAD
FINISHED
FLOOR
3 10 11
INERTIA BASE SEE
SPECIFICATION FOR
REQUIREMENTS
NEOPRENE PAD
(TYP.)
A
3/4" HOSE-END VALVE W/CAP
TO DRAIN
CHILLED WATER RETURN LINE
SHUTOFF VALVE (TYP),
SEE SPEC FOR TYPE
(E) AIR VENT
(E) PIPING
TO PUMP
SUCTION,
(TYP)
FLR
AS
UNION (TYP)
A
CW
(E) SAFETY
RELIEF
VALVE
(E) HIGH CAPACITY
AUTOMATIC AIR VENT
SET TO 10PSI ABOVE
SYSTEM PRESSURE
(E) EXPANSION TANK
DOWNSTREAM PIPE AND ACCESSORIES EXISTING TO REAMAIN
UPSTREAM PIPE AND ACCESSORIES EXISTING TO REMAIN
AIR-COOLED CHILLER
CONDENSING UNIT
CHILLER EVAPORATOR
HEAT EXCHANGER
RLL
RSL
FROM PUMP
TO BUILDING
KEYNOTES
1. REFRIGERANT PIPE SIZED PER
MANUFACTURER'S RECOMMENDATION.
4" CHWR
4" CHWS
Kansas City
10561 Barkley Street, STE 100 Overland Park, KS 66212 t: +1 800.404.7677 e: hello@introba.com www.introba.com
© INTROBA, INC. 2025
WHEN THIS DRAWING IS
REPRODUCED AT ORIGINAL
SCALE THIS BAR = 1 INCH
The Professional Designer of Record (DOR), whose signature and personal seal appear on this document, assumes responsibility only for what appears hereon, and disclaims responsibility for all other plans, specifications, estimates, reports, documents or instruments not sealed by the Professional DOR relating to, or intended to be used for, any part or parts of the project to which this document refers. Prints sealed by the DOR bear the embossed or wet seal of the DOR across the signature and date. Copies of this document, as signed and sealed, have been retained by the
Professional DOR. The Professional DOR will not be responsible for subsequent changes to this document, unless the changes are made by the DOR or with the
DOR's written authorization.
1 INCH
ARCHITECTURE &
ENGINEERING
1 62 3 4 5
E
D
C
B
A
D E
P A
R T
M E
N T
M
IN
IS
T R
A T
IO
N
O F
F
IC
E
C
IL
IT
IE
S
P R
O C
U R
E M
E
N A
G E
M E
N T
D E
S
IG
N
C O
N S
T R
U C
T
IO
M
P L
IA
N
C E
R R
IS
O
N
S U
IT
E
P E
K A
K
A N
S A
S
O N
E
-2
-8
LISA D. AKAGI
PE - 22870
G
A B
R
IE
L A
V E
P
A R
S O
N S
K
S
B U
IL
D
IN
G
N U
M B
E R
-0
P A
R S
O N
S S
T A
T E
H O
S P
IT
A
L
T R
A
IN
IN
G
C E
N T
E R
A
IR
C O
O L E
D C
H
IL
L E
R R
E P
L A
C E
M E
N T
IS
S
U E
D A
T E
/1
/2
D E
S
IG
N E
D B
Y
L D
A
100% CONSTRUCTION
DOCUMENT
S T
A T
E O
F K
A N
S A
S
M500
MECHANICAL - DETAILS &
CONTROL
X-1496
NTS
PLATE AND FRAME HEAT EXCHANGER PIPING DIAGRAM 2-WAY VALVE
12" = 1'-0"
PIPE THROUGH EXTERIOR WALL
NTS
END SUCTION BASE MOUNTED PUMP ON ISOLATORS DETAIL
NTS
AIR SEPARATOR AND EXPANSION TANK (FLOOR MOUNTED) PIPING DETAIL
CHILLED WATER SYSTEM SEQUENCE OF OPERATION
THE CHILLED WATER SYSTEM HAS AN EXISTING CONTROL SEQUENCE. FOR MORE INFORMATION ABOUT THE EXISTING CONTROL SYSTEM, THE CONTRACTOR SHALL CONTACT THE PSH HVAC SUPERVISOR NATHAN FORKNER AT 620-448-3236 (OFFICE) OR 620-423-9784 (MOBILE PHONE). THE CHILLED WATER SYSTEM IS CONNECTED TO A BUILDING MANAGEMENT SYSTEM (BMS). FOR MORE INFORMATION ON THE BMS SYSTEM CONTACT C&C GROUP, 2534 N PATTERSON AVE, SUITE 100, SPRINGFIELD, MO. 65803. THE CONTACT IS ROBERT LUTGEN AT 417-368-1660.
PROVIDE THE FOLLOWING DATA AND CONTROL POINTS AND COMMUNICATE THESE TO BMS:
• SUPPLY CHILLED WATER TEMPERATURE SETPOINT *
• SUPPLY CHILLED WATER TEMPERATURE *
• RETURN CHILLED WATER TEMPERATURE *
• OUTSIDE AIR TEMPERATURE *
• OUTSIDE AIR TEMPERATURE ENABLE COMMAND SETPOINT *
• CHILLER COMMAND *
• CHILLER STATUS WITH NUMBER OR % OF COMPRESSORS RUNNING *
• PUMP COMMAND
• PUMP STATUS
* FROM CHILLER CONTROLS PROVIDED WITH EQUIPMENT FURNISHED.
NTS
CHILLER PIPING DIAGRAM
Kansas City
10561 Barkley Street, STE 100 Overland Park, KS 66212 t: +1 800.404.7677 e: hello@introba.com www.introba.com
© INTROBA, INC. 2025
WHEN THIS DRAWING IS
REPRODUCED AT ORIGINAL
SCALE THIS BAR = 1 INCH
The Professional Designer of Record (DOR), whose signature and personal seal appear on this document, assumes responsibility only for what appears hereon, and disclaims responsibility for all other plans, specifications, estimates, reports, documents or instruments not sealed by the Professional DOR relating to, or intended to be used for, any part or parts of the project to which this document refers. Prints sealed by the DOR bear the embossed or wet seal of the DOR across the signature and date. Copies of this document, as signed and sealed, have been retained by the
Professional DOR. The Professional DOR will not be responsible for subsequent changes to this document, unless the changes are made by the DOR or with the
DOR's written authorization.
1 INCH
ARCHITECTURE &
ENGINEERING
1 62 3 4 5
E
D
C
B
A
D E
P A
R T
M E
N T
M
IN
IS
T R
A T
IO
N
O F
F
IC
E
C
IL
IT
IE
S
P R
O C
U R
E M
E
N A
G E
M E
N T
D E
S
IG
N
C O
N S
T R
U C
T
IO
M
P L
IA
N
C E
R R
IS
O
N
S U
IT
E
P E
K A
K
A N
S A
S
O N
E
-2
-8
LISA D. AKAGI
PE - 22870
G
A B
R
IE
L A
V E
P
A R
S O
N S
K
S
B U
IL
D
IN
G
N U
M B
E R
-0
P A
R S
O N
S S
T A
T E
H O
S P
IT
A
L
T R
A
IN
IN
G
C E
N T
E R
A
IR
C O
O L E
D C
H
IL
L E
R R
E P
L A
C E
M E
N T
IS
S
U E
D A
T E
/1
/2
D E
S
IG
N E
D B
Y
L D
A
100% CONSTRUCTION
DOCUMENT
S T
A T
E O
F K
A N
S A
S
M600
MECHANICAL - SCHEDULES
X-1496
ACC 1 YORK YLAA0101 AIR COOLED SCROLL AT GRADE OUTSIDE HICKORY CHILLED WATER R454B 100 100 97.77 54 44 233 9.5 5 2 17 10 95 12' X 8' X 8' 5000 467 113 208 3 1, 2
ID # CAPACITY (MBH) EWT (°F) LWT (°F) FLOW (GPM) MAX WPD (FT) AMPS KW VOLTS PHASE
MARK
MFR MODEL TYPE LOCATION SERVICE
REFR
TYPE
DESIGN AMBIENT
TEMP (°F) NOM TONS
EVAPORATOR
MIN # OF COMPRESSORS MIN # OF CIRCUITS MIN IPLV (EER)
MAX FULL LOAD
EFF (EER)
MAX SOUND
PRESS
MAX SIZE LxWxH
(FT)
MAX OPERATING
WEIGHT (LBS)
ELECTRICAL DATA
NOTES
2 CHILLER EVAPORATOR SHALL BE A BRAZED PLATE AND FRAME HEAT EXCHANGER LOCATED REMOTELY IN THE MECHANICAL ROOM. SEE SCHEDULE BELOW.
1 CHILLER SHALL BE DELIVERED WITH A SINGLE POINT POWER CONNECTION AND DISCONNECT IN THE CHILLER CONTROL PANEL.
NOTES:
AIR COOLED CHILLER SCHEDULE
AS 1
BELL &
GOSSETT R-4F CENTRIFUGAL
HICKORY
BASEMENT
MECHANICAL
ROOM
CHILLED
WATER 246 2 1
ID #
MARK
MFR. MODEL TYPE LOCATION SERVICE FLOW (GPM) MAX WATER PD (FT) NOTES
2. SUPPLY A SEPARATOR THAT HAS A MINIIMUM % OF AIR ELEMINATION IF 70% AT A % OF MAXIMUM FLOW OF 0.82.
1. PROVIDE WITH HIGH CAPACITY AUTOMATIC AIR VENT.
NOTES:
AIR SEPARATOR SCHEDULE
P 1
BELL &
GOSSETT 1510
BASE MOUNTED
END SUCTION
HICKORY BASEMENT
MECHANICAL ROOM
CHILLED
WATER 246 60 3 / 2.5 6.45 70 1800 7.5 208 3 1,2
ID # HP VOLTS PHASE
MARK
MFR. MODEL TYPE LOCATION SERVICE
WATER
FLOW
(GPM)
TDH
(FT)
MIN INLET /
OUTLET
SIZES (IN)
MIN NPSH
REQD (FT)
MIN EFF
MOTOR
SPEED
(RPM)
ELECTRICAL DATA
NOTES
2. UTILIZE EXISTING STARTER/DISCONNECT WITH THE ENW PUMP.
1. REFER TO DETAIL 4/M500 FOR INSTALLATION REQUIREMENTS, INCLUDING VIBRATION ISOLATION.
NOTES:
PUMP SCHEDULE
(1) HEAT EXCHANGER TO BE PROVIDED BY THE AIR COOLED CHILLER MANUFACTURER, WITH THE AIR COOLED CHILLER.
(2) INCLUDE FLOOR MOUNT BRACKET.
(3) CONTRACTOR TO PROVIDE 4" HIGH HOUSEKEEPING PAD.
(4) TO MATCH THE PROVIDED AIR-COOLED CHILLER.
NOTES:
* CELLS WITH SHADED BACKGROUNDS ARE UNASSIGNED OR UNDER REVIEW
MECHANICAL - HEAT EXCHANGER (PLATE AND FRAME) SCHEDULE
TYPE EQUIPMENT NUMBER MANUFACTURER MODEL
LOCATION
SERVICE
REFRIGERANT SIDE BUILDING LOAD SIDE PLATES DIMENSIONS
OPERATING WEIGHT (LB) NOTES
CAPACITY (BTUH) ET (°F) LT (°F) GPM WPD (FT WC) MEDIUM CAPACITY EWT (°F) LWT (°F) FLOW (GPM) WPD (FT WC) MEDIUM MATERIAL NO. OF PLATES MAX NO. OF PLATES L W H
HX 1 ALFA-LAVA ACH-502DQ-142AH-F HICKORY BASEMENT MECHANICAL ROOM CHILLED WATER NOTE 4 NOTE 4 NOTE 4 NOTE 4 NOTE 4 R454R 97 54.0 44.0 233.0 10.0 WATER SS 145 270 15" 13" 30" 200 1,2,3
M
K
AM
IQ
ELECTRICAL SYMBOLS AND LEGEND
RECEPTACLES / POWERWALL CEILING
NOTE: ALL RECEPTACLE OUTLETS ON WALLS ARE MOUNTED AT 18" AFF, UON.
LETTER RATING
A B D F G H J K L
M N P R S T
X Z
125V, 1Ø, 30A, 2P, 3W 125V, 1Ø, 50A, 2P, 3W 125/250V, 1Ø, 20A, 3P, 4W 125/250V, 1Ø, 30A, 3P, 4W 125/250V, 3Ø, 20A, 3P, 4W 125/250V, 3Ø, 30A, 3P, 4W 250V, 1Ø, 20A, 2P, 3W 250V, 1Ø, 30A, 2P, 3W
250V, 1Ø, 50A, 2P, 3W 250V, 3Ø, 20A, 3P, 4W 250V, 3Ø, 30A, 3P, 4W 250V, 3Ø, 50A, 3P, 4W 480V, 3Ø, 30A, 3P, 4W 125V, 1Ø, 20A, 2P, 3W
125V, 1Ø, 20A, 2P, 3W 480V, 3Ø, 20A, 3P, 4W
NEMA
5-30R 5-50R 14-20R 14-30R
L21-20R L21-30R 6-20R 6-30R
6-50R 15-20R 15-30R 15-50R
L16-30R 5-20R
5-20R L16-20R
WITH 5-30P PLUG
WITH 5-50P PLUG
WITH 14-20P PLUG
WITH 14-30P PLUG
WITH L21-20P PLUG
WITH L21-30P PLUG
WITH 6-20P PLUG
WITH 6-30P PLUG
'L' INDICATES ASSOCIATED RECEPTACLE IS
LOCKING TYPE, PROVIDE MATCHING PLUG
FOR EACH RECEPTACLE
WITH 6-50P PLUG
WITH 15-20P PLUG
WITH 15-30P PLUG
WITH 15-50P PLUG
WITH L12-30P PLUG
ISOLATED GROUND WITH INTEGRAL
TRANSIENT SUPPRESSOR AND DEDICATED
GREEN/YELLOW CONDUCTOR BACK TO
GROUND BUS AT PANEL
DEDICATED CIRCUIT
WITH L16-20R PLUG
SPECIAL RECEPTACLE DESCRIPTION SCHEDULE
NOTE: NUMBER OF WIRES INCLUDE GROUND
EXISTING / DEMOLITION
EXISTING EQUIPMENT / RACEWAYS TO REMAIN
EXISTING EQUIPMENT / RACEWAYS TO BE REMOVED
NEW EQUIPMENT / RACEWAYS
EXISTING TO REMAIN
EXISTING TO BE REMOVED
NEW EQUIPMENT, LIGHTING FIXTURE OR DEVICE
SINGLE LINE DIAGRAM
X X
E-6
P
A
E-6
GENERAL ELECTRICAL SYMBOLSRECESSED SURFACE
DISCONNECT SWITCH, 30 AMP MINIMUM UNLESS NOTED
OTHERWISE
FREE STANDING SWITCHBOARD, MOTOR CONTROL
CENTER OR DISTRIBUTION BOARD
A-1,3,5
RACEWAYS AND WIRINGFLOOR WALL CEILING
CONDUIT CONCEALED IN CEILING OR WALL SPACE
J
J
J
J
SIMPLEX RECEPTACLES
JUNCTION BOX 4" SQUARE MINIMUM FOR WALL
OR CEILING MOUNTED
DUPLEX RECEPTACLES
SPECIAL RECEPTACLES (DUPLEX &
QUADRUPLEX), REFER TO SPECIAL
RECEPTACLE SCHEDULE, THIS SHEET
GROUND FAULT CIRCUIT INTERRUPTING
RECEPTACLES
JUNCTION BOX SIZE AS REQUIRED FOR
NUMBER OF WIRES OR RACEWAYS
EEE
X33
+4'-6"
MH=4'-6"
A-1 A-1A-1
FIRE TREATED PLYWOOD BACKBOARD 3/4"X96" HIGH X
LENGTH AS INDICATED
ELECTRICAL EQUIPMENT DESIGNATION DESIGNED
"EQ01"
REFERENCE TO NOTE "1" ON SAME SHEET
MECHANICAL EQUIPMENT DESIGNATION "P-1"
INDICATED
EQUIPMENT NAME OR NUMBER
MOUNTING HEIGHT FROM FINISHED FLOOR TO
CENTERLINE OF OUTLET OR EQUIPMENT
MOUNTING HEIGHT FROM FINISHED FLOOR TO BOTTOM
OF OUTLET OR EQUIPMENT
DETAIL REFERENCE NUMBER "1" ON DRAWING "E-6"
SECTION OR ELEVATION REFERENCE LETTER "A" ON
DRAWING "E-6"
INDICATES HOMERUN WITH THREE CIRCUITS AND A
SEPARATE NEUTRALS
CONDUIT RUN EXPOSED
CONDUIT RUN UNDERGROUND OR CONCEALED IN
FLOOR SPACE
EXISTING CONDUIT TO REMAIN
CONDUIT RISING UP FROM RUN
CONDUIT DROPPING DOWN FROM RUN
HOMERUN TO PANELBOARD, CABINET OR TERMINAL
BACKBOARD AS INDICATED
FUSED DISCONNECT SWITCH, 30 AMP MINIMUM UNLESS
NOTED OTHERWISE
COMBINATION DISCONNECT SWITCH MOTOR STARTED
MOTOR, 5 HP INDICATED
TRANSFORMER
RELAY OR EQUIPMENT CABINET AS INDICATED ON
PLAN
LIGHTING OR POWER PANEL BOARD
T
GROUNDING SYSTEMFLOOR WALL
GROUND PLATE, FLAT TAPPED SIDE TO BE FLUSH WITH
FURNISHED SURFACE. CADWELD B164-2Q OR
EQUIVALENT
G
TG
G
TG
GROUND BUS
TECHNICAL GROUND BUS
G
EXOTHERMIC GROUND CONNECTION
GROUND WIRE
GROUND ROD
GROUND ROD TEST WELL
S
G
CIRCUIT BREAKER, 3 POLE UNLESS NOTED OTHERWISE
MOTOR STARTER WITH OVERCURRENT PROTECTION, 3
POLE UNLESS NOTED OTHERWISE
MOTOR STARTER WITH FUSED AND DISCONNECT SWITCH,
3 POLE UNLESS NOTED OTHERWISE
GROUND FAULT RELAY
SHUNT TRIP RELAY
DRAW-OUT CIRCUIT BREAKER
NON-FUSED DISCONNECT SWITCH, 30 AMP, 3P UNLESS
NOTED OTHERWISE
FUSED DISCONNECT SWITCH, 3 POLE UNLESS NOTED
OTHERWISE
DEMAND TYPE KWH METER
DEMAND TYPE KWH METER WITH ENCLOSURE
PROVISION FOR UTILITY COMPANY KWH METER
KIRK-KEY INTERLOCK BETWEEN DEVICES
AUTOMATIC TRANSFER SWITCH WITH GENERATOR
STARTING AND TRANSFER SWITCH STATUS CONTACTS
CURRENT TRANSFORMER (CT)
AMMETER
ELECTRONIC METER
SEPARABLE CONNECTOR(S)
EMERGENCY GENERATOR, AS NOTED ON SINGLE LINE
DIAGRAM
GROUND
AUTOMATIC TRANSFER SWITCH WITH BY-PASS
ISOLATION, GENERATOR STARTING CONTACTS AND
TRANSFER SWITCH STATUS CONTACT
TRANSFORMER , AS NOTED ON SINGLE LINE DIAGRAM
ISOLATION TRANSFORMER , AS NOTED ON SINGLE LINE
DIAGRAM
CIRCUIT BREAKER BUS TAP
VFD VARIABLE FREQUENCY DRIVE
SURGE PROTECTIVE DEVICE
PNL
PNL
PNL
PNL PNL
PNL
PANELBOARD WITH LUGS ONLY. UP TO 84 CIRCUITS
IN A SINGLE CABINET. REFER TO PANEL SCHEDULE
FOR ADDITIONAL INFORMATION
PANELBOARD WITH MAIN CIRCUIT BREAKER. UP TO 84
CIRCUITS IN A SINGLE CABINET. REFER TO PANEL
SCHEDULE FOR ADDITIONAL INFORMATION.
PANELBOARD WITH MAIN CIRCUIT BREAKER AND
FEED THROUGH GUTTER AND FEEDER TAP IN
GUTTER. UP TO 84 CIRCUITS IN A SINGLE CABINET.
REFER TO PANEL SCHEDULE FOR ADDITIONAL
INFORMATION.
PANELBOARD WITH MAIN CIRCUIT BREAKER AND
FEED THROUGH GUTTER AND FEEDER TAP IN
GUTTER. UP TO 84 CIRCUITS IN EACH CABINET. REFER
TO PANEL SCHEDULE FOR ADDITIONAL INFORMATION.
A. GENERAL REQUIREMENTS
1. DEFINITIONS FOR TERMS USED IN THE ELECTRICAL DOCUMENTS:
a. DRAWINGS = LATEST VERSION OF THE PROJECT DRAWINGS UNLESS NOTED OTHERWISE
b. SPECIFICATIONS = LATEST VERSION OF THE OF THE PROJECT MANUAL OR SPECIFICATIONS
UNLESS NOTED OTHERWISE
c. CONTRACT DOCUMENTS = LATEST VERSION OF THE PROJECT DRAWINGS AND PROJECT
SPECIFICATIONS
d. CONTRACTOR = ANY OR ALL OF THE FOLLOWING, CONSTRUCTION MANAGER, GENERAL
CONTRACTOR AND ALL OF THEIR SUB-CONTRACTORS, FABRICATORS AND SUPPLIERS
2. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF THE ELECTRICAL SYSTEMS WITH THE
WORK OF ALL OTHER TRADES, ARCHITECT AND THEIR CONSULTANTS, CIVIL, STRUCTURAL AND
OWNER AS WELL AS ANY FABRICATOR OR SUPPLIER FOR APPLICABLE TRADES.
3. SPECIFICATIONS ARE AN INTEGRAL PART OF THE CONTRACT DOCUMENTS AND SHALL BE USED IN
CONJUNCTION WITH ELECTRICAL DRAWINGS.
4. THE CONTRACTOR IS RESPONSIBLE FOR MANNING THE PROJECT TO MEET THE PROJECT
SCHEDULE AND FOR MEANS, METHODS, AND TECHNIQUES OF CONSTRUCTION. THE DESIGN TEAM
ASSUMES NO RESPONSIBILITY.
B. GENERAL PROVISIONS:
1. SUBMISSION OF A BID BY THE CONTRACTOR IS NOTIFICATION THAT THE CONTRACTOR HAS
RECEIVED A COMPLETE SET OF CONSTRUCTION DOCUMENTS, SPECIFICATIONS, ANY AND ALL
ADDENDUMS FROM ALL TRADES AND HAS REVIEWED ALL DOCUMENTS. ALL WORK NOT
NECESSARILY RESTRICTED TO THESE DOCUMENTS BUT REQUIRED TO PROVIDE A COMPLETE AND
FUNCTIONING ELECTRICAL SYSTEM HAS BEEN INCLUDED IN THE BID.
2. THESE CONSTRUCTION DOCUMENTS DO NOT DEFINE SCOPE OF CONTRACTS. ELECTRICAL
SYSTEMS AND CONTROLS SHALL BE COMPLETE AND FUNCTIONAL. REFER TO CONSTRUCTION
MANAGER, GENERAL CONTRACTOR, OR OWNER FOR DEFINITION OF SCOPES WITHIN THESE
DOCUMENTS.
3. IT IS THE INTENT OF THESE PLANS AND SPECIFICATIONS THAT A COMPLETE AND WORKABLE
ELECTRICAL INSTALLATION BE PROVIDED FOR ALL THE EQUIPMENT DESCRIBED OR SHOWN AS
BEING IN THIS CONTRACT. TOWARD THIS END, CONTRACTOR SHALL FURNISH ALL LABOR AND
TOOLS NECESSARY, FURNISH AND INSTALL ALL APPARATUS, MATERIALS, AND EQUIPMENT IN A
MANNER COMPLYING WITH ALL APPLICABLE CODES, INCLUDING ITEMS REQUIRED BUT NOT
NECESSARILY SHOWN, SUCH AS LAMPS, COUPLINGS, HANGERS, BRACKETS, CLAMPS, BOXES,
CONNECTORS, AND HARDWARE.
4. THESE DOCUMENTS ARE PART OF A COMPLETE SET OF CONSTRUCTION DOCUMENTS. THE
CONSTRUCTION DOCUMENTS DO NOT SHOW EVERY ITEM OR COMPONENT REQUIRED TO PROVIDE
A COMPLETE AND OPERABLE ELECTRICAL SYSTEM. CONTRACTOR SHALL MAKE USE OF ALL
CONSTRUCTION DOCUMENTS TO DETERMINE FULL SCOPE AND FURNISH AND INSTALL ALL
SPECIFIED AND APPROPRIATE INCIDENTAL AND ACCESSORY ITEMS NOT INDICATED BUT REQUIRED
TO PROVIDE FOR A COMPLETE AND FINISHED ELECTRICAL SYSTEM.
5. CATALOG NUMBERS WHEN INDICATED ON DRAWINGS ARE TO ESTABLISH A MANUFACTURER AND
SHALL BE USED IN CONJUNCTION WITH SPECIFICATIONS. WHERE CATALOGUE NUMBER AND
SPECIFICATIONS ARE IN CONFLICT THE MOST STRINGENT INTERPRETATION SHALL BE USED.
6. ALL CONDUCTORS SHALL BE COPPER, TYPE "THWN/THHN" WITH 90 DEGREE INSULATION. ALL LUGS SHALL BE 75 DEGREE MINIMUM. ALL CONDUIT SHALL BE EMT OR ERMC AS PER SPECIFICATIONS.
USE OF FLEX IS NOT ALLOWED EXCEPT UP TO 6 FOOT FOR FINAL CONNECTION TO LIGHTING
FIXTURES OR VIBRATING EQUIPMENT.
7. BEFORE SUBMITTING THE BID PROPOSAL, CONTRACTOR SHALL VISIT THE JOB SITE TO FULLY FAMILIARIZE HIMSELF WITH THE SITE CONDITIONS, REQUIREMENTS, INCLUDING ALL NECESSARY
ADDITIONAL SCOPE OF WORK, WHETHER SHOWN ON DRAWING(S) OR NOT, BUT REQUIRED FOR
PROVIDING A COMPLETE AND FUNCTIONING ELECTRICAL SYSTEM.
8. CONTRACTOR SHALL REFER TO MECHANICAL DRAWINGS AND WIRING DIAGRAMS FOR ITEMS AND
DEVICES TO BE FURNISHED, INSTALLED AND/OR CONNECTED FOR A COMPLETE AND OPERABLE
HEATING, VENTILATION AND AIR CONDITIONING (HVAC) SYSTEM. VERIFY EXACT LOCATION OF HVAC
EQUIPMENT AND CONDUIT TERMINATION AT EQUIPMENT WITH MECHANICAL CONTRACTOR.
9. THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC IN NATURE AND INDICATE THE LOCATION OF
OUTLETS AND EQUIPMENT THOUGH NOT NECESSARILY INDICATING THE ACTUAL ROUTES OF
CONDUITS, THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS PROPER COORDINATION WITH
THE WORK OF OTHER TRADES AND SPACE WILL PERMIT. IT IS NOT WITHIN THE SCOPE OF THE
DRAWINGS TO SHOW ALL NECESSARY OFFSETS, BENDS, PULL BOXES AND OBSTRUCTIONS. THE
DRAWINGS ARE NOT INTENDED TO BE SCALED.
10. ELECTRICAL RACEWAYS SHALL BE INSTALLED AS HIGH AS POSSIBLE AND TIGHT AGAINST THE DECK ABOVE IS PREFERRED. ACCESS TO PULL BOXES AND JUNCTION BOXES SHALL BE MAINTAINED AND OFFSETS TO RACEWAY INSTALLATION MAY BE INSTALLED AS REQUIRED TO MAINTAIN ACCESS AND
TRANSITION BACK TO THE DECK ABOVE AFTER PASSING THROUGH.
11. ALL EXTERIOR CONDUITS ROUTED IN GRADE SHALL BE TERMINATED WITH MECHANICAL SEALS TO
PREVENT MOISTURE FROM ENTERING BUILDING OR PAD MOUNTED ENCLOSURES. BOTH CONDUIT
ENDS SHALL BE SEALED. CONDUITS FROM BELOW GRADE SHALL BE SEALED UTILIZING FITTING SIMILAR TO OR EQUAL TO OZ/GEDNEY TYPE 'FSK' THRU-WALL FITTING WITH 'FSKA' MEMBRANE
ADAPTER CLAMP. REFER TO SPECIFICATIONS FOR PENETRATION SEALS AND REQUIREMENTS.
12. INSTALL NO MORE THAN EQUIVALENT OF THREE 90-DEGREE BENDS IN CONDUIT RUN EXCEPT FOR CONTROL WIRING CONDUITS, FOR WHICH NO MORE THAN EQUIVALENT OF TWO 90-DEGREE FEWER
BENDS ARE PERMITTED.
13. ALL PERMITS SHALL BE PROCURED FROM ALL LEGALLY CONSTITUTED AUTHORITIES, ARRANGE FOR ALL INSPECTION AND PAY ALL COSTS FOR FEES AND TESTS IN CONNECTION THEREWITH, COMPLY
WITH CODES. PRESENT THE SIGNED CERTIFICATE OF FINAL INSPECTION TO THE OWNER'S
REPRESENTATIVE PRIOR TO PRESENTING THE WORK FOR FINAL ACCEPTANCE.
14. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS FOR SUBMITTALS, ACCEPTABLE
MATERIALS, COORDINATION REQUIREMENTS, TESTING, STARTUP, TRAINING AND PROJECT
CLOSEOUT.
15. PROVIDE A CODE APPROVED DISCONNECT SWITCH OR BREAKER WITHIN SIGHT OF EVERY MOTOR.
FOR LOCATION OF DISCONNECT SWITCH, COORDINATE WITH EQUIPMENT SUPPLIER TO DETERMINE THE BEST LOCATION ON SITE WHILE REMAINING ACCESSIBLE. THE DISCONNECT MEANS MAY BE
INSTALLED ON THE EQUIPMENT, BUT SHALL NOT BE LOCATED ON ACCESS PANELS OR COVER
MANUFACTURERS LABELING.
16. CONTRACTOR SHALL TEST ALL WIRING AND CONNECTIONS FOR CONTINUITY, GROUNDS, SHORT
CIRCUITS, AND OTHER DEFECTS BEFORE ANY EQUIPMENT OR FIXTURES ARE CONNECTED
THERETO. CABLES SHALL BE CHECKED FOR CONTINUITY, SHORTS, INSULATION RESISTANCE, AND
PROPER PHASING.
17. PROVIDE PULL ROPE IN ALL EMPTY RACEWAYS. RACEWAYS SHALL BE TAGGED WITH LOCATION OF
OPPOSITE END OF RACEWAY AND INCLUDE PROPOSED FUTURE USE OF RACEWAY.
18. ROUTING OF RACEWAYS FEEDERS AND HOMERUNS ARE NOT INDICATED ON THESE DOCUMENTS
AND MUST BE DETERMINED BY CONTRACTOR IN COOPERATION WITH THE WORK OF OTHER
TRADES.
19. NO MORE THAN THREE CIRCUITS PER HOME RUN. DO NOT COMBINE HOMERUNS WITHOUT PRIOR
APPROVAL.
20. NO INTERMEDIATE SPLICING OF FEEDERS OR BRANCH CIRCUITS SHALL BE DONE WITHOUT PRIOR
APPROVAL.
21. ALL SINGLE PHASE, SINGLE POLE LOADS TO HAVE DEDICATED NEUTRALS. LABEL NEUTRAL
CONDUCTORS WITH CORRESPONDING CIRCUIT NUMBER AT EACH PULL BOX, JUNCTION BOX,
HANDHOLE, AND OTHER SPLICE POINT. USE OF BREAKER TIES IS NOT PERMITTED. SHARING OF
NEUTRALS IS NOT PERMITTED.
22. MINIMUM SIZE FOR INTERIOR BRANCH CONDUIT SHALL BE ¾” CONDUIT
23. WHERE CIRCUIT NUMBERS ARE SHOWN, WITHOUT CONDUIT AND WIRE INDICATIONS, CONDUCTOR
SIZE SHALL EQUAL BRANCH OVERCURRENT PROTECTION SIZE. REFER TO CONDUIT AND
CONDUCTOR LEGEND FOR MINIMUM RACEWAY SIZES
24. PROVIDE FIREPROOFING FOR ALL FLOOR PENETRATIONS AND FOR ALL WALL PENETRATIONS
THROUGH MULTIPLE CONDUITS PENETRATING FIRE RATED WALLS OR FLOOR SLABS SHALL BE
SEPARATED BY 2" AND THE OPENING AROUND THE CONDUIT SEALED WITH UL LISTED FIRE RATED CAULK AS REQUIRED BY UL LISTED ASSEMBLY. FIREPROOFING SYSTEM SHALL MEET OR EXCEED
THE RATING OF THE PENETRATED STRUCTURE.
25. DEVICES OR BOXES INSTALLED IN FIRE RATED PARTITIONS OR SLABS SHALL BE INSTALLED IN
COMPLIANCE WITH UL LISTED ASSEMBLY THAT MEETS OR EXCEEDS THE FIRE RATING OF THE
PARTITION OR SLAB.
26. WHERE UNDERGROUND RACEWAYS TURN UP INTO CABINETS, EQUIPMENT, ETC. OR ON TO POLES, THE ELBOW REQUIRED AND THE STUB-OUT OF THE SLAB OR EARTH SHALL BE GALVANIZED RIGID
STEEL.
C. SITE WORK:
1. EXISTING UNDERGROUND UTILITY LOCATIONS ARE UNKNOWN. CONTRACTOR SHALL COORDINATE
PROPOSED ROUTING WITH WORK OF OTHER TRADES AND INCLUDE HAND DIGGING TO REDUCE
IMPACT ON EXISTING SYSTEMS. COORDINATE WITH OWNER AND FIELD VERIFY ALL EXISTING SITE CONDITIONS PRIOR TO BEGINNING WORK. ANY EXISTING SYSTEMS (I.E. IRRIGATION, WATER, GAS, SEWER, ETC.) IMPACTED, SHALL BE REPAIRED/RESTORED TO ORIGINAL STATE.
2. RESTORE OR REPAIR ANY DISTURBED HARDSCAPE OR LANDSCAPE REQUIRED TO INSTALL NEW
WORK TO ITS ORIGINAL STATE UPON COMPLETION.
D. POWER:
1. PROVIDE CONCRETE PADS (MINIMUM 4" HIGH OR AS INDICATED) FOR ALL FLOOR MOUNTED
ELECTRICAL EQUIPMENT INSTALLED IN EQUIPMENT ROOMS AND IN AREAS SUSCEPTIBLE TO BEING
WET OR HOSED DOWN. SUBMIT PAD DETAIL PLANS INCLUDING DIMENSIONS FOR APPROVAL.
2. ALL DISCONNECT SWITCHES SHALL BE PAD-LOCKABLE IN THE "OFF" POSITION.
3. VERIFY AND COORDINATE EXACT LOCATION, POWER REQUIREMENTS AND METHOD OF
CONNECTION OF ALL MECHANICAL EQUIPMENT AND PERTINENT ITEMS AND DEVICES PRIOR TO
INSTALLATION OF ELECTRICAL SYSTEM.
4. PROVIDE A MINIMUM OF 12" SEPARATION BETWEEN POWER AND COMMUNICATION CONDUITS,
WHERE THEY ARE INSTALLED IN PARALLEL OR IN THE SAME TRENCH.
E. GROUNDING:
1. THE EQUIPMENT GROUNDING CONDUCTOR SHALL RUN CONTINUOUS FROM PANEL TO LAST OUTLET.
THIS WIRE SHALL BE PIGTAILED TO BOX AND DEVICE. ALL EQUIPMENT GROUNDING CONDUCTORS
SHALL BE INSULATED GREEN CONDUCTORS.
2. PROVIDE EQUIPMENT GROUNDING CONDUCTOR IN ALL BRANCH CIRCUITS.
3. BOXES WITH CONCENTRIC, ECCENTRIC OR OVER SIZED KNOCK-OUTS SHALL BE PROVIDED WITH
BONDING BUSHINGS AND JUMPERS. JUMPERS SHALL BE SIZED IN ACCORDANCE WITH NEC TABLE
250.122 AND LUGGED TO THE BOX.
GENERAL ELECTRICAL NOTES
F. PENETRATIONS:
1. PENETRATIONS IN WALLS REQUIRING PROTECTED OPENINGS MUST BE FIRESTOPPED WITH AN
APPROVED MATERIAL. SPACE BETWEEN PENETRATING MATERIALS (DESCRIBED BELOW) MUST BE
DESIGNED TO PREVENT THE SPREAD OF HOT FLAME OR GASES.
2. COPPER OR FERROUS PIPES OR CONDUITS MAY PENETRATE THE WALLS OR PARTITIONS,
PROVIDED THEY ARE FIRESTOPPED USING UL LISTED ASSEMBLY.
3. OPENINGS FOR STEEL ELECTRICAL OUTLET BOXES NOT EXCEEDING 16 SQUARE INCHES ARE
PERMITTED PROVIDED OPENINGS DO NOT AGGREGATE MORE THAN 100 SQUARE INCHES OR 100
SQUARE FEET OF WALL OF PARTITIONS. OUTLET BOXES ON OPPOSITE SIDES OF WALLS OR
PARTITIONS MUST BE SEPARATED BY A HORIZONTAL DISTANCE OF 24 INCHES.
G. IDENTIFICATION
1. REFER TO SPECIFICATIONS FOR IDENTIFICATION MATERIALS AND APPLICATION REQUIREMENTS.
2. ALL DISCONNECT DEVICES SHALL BE LABELED WITH VOLTAGE AND DEVICE BEING SERVED.
3. ALL EMPTY RACEWAYS SHALL BE IDENTIFIED WITH PROPOSED SERVICE AND LOCATION OF
OPPOSITE END OF RACEWAY. WHERE RACEWAYS ARE LOCATED BELOW GRADE PROVIDE BRASS
STAKE AND IDENTIFY LOCATION ON AS CONSTRUCTED DOCUMENTS WITH MEASUREMENTS FROM
BUILDING ELEMENTS OR GPS COORDINATES.
4. PAINT COUPLINGS, CONNECTORS AND ENTIRE CONDUIT WITHIN 6” OF JUNCTION BOX, CABINET OR
ENCLOSURE FOR THE FOLLOWING ELECTRICAL SYSTEMS:
a. NORMAL POWER – SILVER (UNPAINTED)
b. FIRE ALARM – RED
5. CONTRACTOR SHALL IDENTIFY ALL LOW VOLTAGE POWER CABLE FEEDERS IN PULL BOXES,
SWITCHBOARDS, PANELBOARDS AND AT ALL TERMINATIONS OF FEEDERS. EACH POWER CABLE
FEEDER TAG OR LABEL SHALL BE SECURELY FASTENED ON EACH FEEDER AND SHALL INCLUDE
FEEDER DESIGNATION AS SHOWN ON THE IDENTIFICATION NOTES. LABELS SHALL BE NON-
FERROUS TAGS OR PRESSURE SENSITIVE LABELS; VINYL CLOTH SELF-ADHESIVE, WRAP-AROUND TYPE; PRE-NUMBERED PLASTIC COATED OR WRITE-ON TYPE LABEL WITH CLEAR PLASTIC SELF-
ADHESIVE COVER FLAP. ACCEPTABLE MANUFACTURERS ARE BRADY, BUCHANAN, MIDLAND ROSS,
T&B, PANDUIT, OR APPROVED EQUAL.
H. COORDINATION
1. THERE IS NO ASSURANCE THAT THE LOCATION OF SUBSTRUCTURES SHOWN ON THIS DRAWING ARE ACCURATE, OR THAT ALL EXISTING SUBSTRUCTURES ARE SHOWN ON THESE DRAWINGS. THE
CONTRACTOR IS RESPONSIBLE FOR PROTECTING ALL SUBSTRUCTURES WHETHER SHOWN OR NOT.
ANY DAMAGE TO THE EXISTING SUBSTRUCTURES SHALL BE REPAIRED AT THE CONTRACTOR'S
EXPENSE.
2. CONTRACTOR IS RESPONSIBLE FOR REVIEW OF ALL CONSTRUCTION DOCUMENT, FIELD
CONDITIONS AND WORK OF OTHER TRADES. BEFORE PROCEEDING WITH CONSTRUCTION, THE
CONTRACTOR VERIFY SHALL ROUGH-IN, VOLTAGE AND CONSTRUCTION REQUIREMENTS FOR ALL
ELECTRICAL CONNECTED COMPONENTS INCLUDING ITEMS PROVIDED BY OWNER OR OTHER
TRADES.
3. CONTRACTOR IS RESPONSIBLE FOR COORDINATING CONDUCTOR SIZES AND QUANTITIES WITH LUGS PROVISIONS AT ALL POINTS OF TERMINATION PRIOR TO RELEASE OF ELECTRICAL GEAR.
WHERE COORDINATION BETWEEN LUGS SIZES AND CONDUCTORS CAN NOT BE ACCOMMODATED
OR IS IMPRACTICAL, PROVIDE STEP-DOWN COMPRESSION ADAPTERS. CABLE PIN SIZE MAY NOT BE
REDUCED IN EXCESS OF ONE CABLE SIZE WITHOUT PRIOR APPROVAL.
4. REASONABLE EFFORTS HAVE BEEN MADE TO COORDINATE THE ELECTRICAL REQUIREMENTS OF THE EQUIPMENT SPECIFIED IN OTHER DIVISIONS WITH THE ELECTRICAL SYSTEMS SERVING THAT
EQUIPMENT. DIFFERENCES AMONG MANUFACTURERS OF EQUIPMENT MAKE IT IMPOSSIBLE TO
PRODUCE A SINGLE ELECTRICAL DESIGN WHICH WILL SATISFY THE VARYING ELECTRICAL
REQUIREMENTS OF THOSE MANUFACTURERS. CONSEQUENTLY, THE CONTRACTOR SHALL
COORDINATE THE ELECTRICAL REQUIREMENTS OF THE EQUIPMENT ACTUALLY FURNISHED ON THIS
PROJECT AND PROVIDE THE ELECTRICAL SYSTEMS REQUIRED BY THAT EQUIPMENT. THIS
COORDINATION EFFORT SHALL BE COMPLETED PRIOR TO THE INSTALLATION OF EITHER THE
EQUIPMENT OR THE ELECTRICAL SYSTEMS SERVING THAT EQUIPMENT.
5. CONTRACTOR IS RESPONSIBLE FOR COORDINATION WITH THE BUILDING CONTROL SYSTEMS FOR
120 VOLT POWER TO BUILDING CONTROL SYSTEMS COMPONENTS. REFERENCE MECHANICAL
SEQUENCE OF OPERATION AND COMMISSIONING DOCUMENTS FOR ADDITIONAL INFORMATION.
6. THE CONTRACTOR IS RESPONSIBLE FOR DISTRIBUTION OF COMPLETE CONSTRUCTION DOCUMENTS
TO OTHER TRADES AND SUPPLIERS UNDER THEIR JURISDICTION
7. ELECTRICAL WORKSPACE LAYOUTS ARE BASED UPON GENERIC EQUIPMENT SIZES. CONTRACTOR
IS RESPONSIBLE FOR MAINTAINING REQUIRED WORKING SPACE IN FRONT OF ALL GEAR BASED
UPON ACTUAL GEAR SIZES. IN ADDITION TO WORKING SPACE CONTRACTOR IS RESPONSIBLE FOR
MAINTAINING DEDICATED ELECTRICAL SPACE ABOVE ALL ELECTRICAL EQUIPMENT. DEDICATED
ELECTRICAL SPACE IS TO BE CLEAR FOR 6 FOOT ABOVE EQUIPMENT OR TO THE STRUCTURE
WHICHEVER IS LOWER. NO PIPING, DUCTS, LEAK PROTECTION APPARATUS OR OTHER EQUIPMENT FOREIGN TO THE ELECTRICAL INSTALLATION SHALL BE LOCATED IN THE DEDICATED ELECTRICAL
ZONE.
J. DEMOLITION:
1. EXISTING CONDITIONS INDICATED ON DOCUMENTS ARE BASED UPON REVIEW OF AVAILABLE
RECORD DOCUMENTS AND VISUAL FIELD SURVEY AND ARE FOR REFERENCE ONLY. CONTRACTOR
SHALL VERIFY ACTUAL EXISTING CONDITIONS PRIOR TO COMMENCING WORK.
2. SURVEY EXISTING CONDITIONS, INVENTORY AND RECORD THE CONDITION OF ITEMS TO BE
REMOVED AND REINSTALLED.
3. RECORD EXISTING CONDITION BY USE OF MEASURED DRAWINGS, PRECONSTRUCTION
PHOTOGRAPHS, AND/OR VIDEO TAPES. RECORD CONDITION OF AREAS ADJACENT TO DEMOLITION
IN ADDITION TO AREAS TO BE DEMOLISHED.
4. CONTRACTOR TO COORDINATE WITH OWNER PRIOR TO DEMOLITION. UTILIZE RECORD OF
EXISTING CONDITIONS REPORT TO DETERMINE WITH OWNERS INPUT ITEMS TO BE SALVAGED,
RECYCLED OR REUSED. WHILE REMOVING ITEMS USE CAUTION TO PREVENT DAMAGE TO
SALVAGED OR REUSED ITEMS OR STRUCTURE.
5. WHERE UTILITIES, FEEDERS, RACEWAYS PASS THROUGH AREAS OR WALLS TO BE DEMOLISHED, DETERMINE SOURCE, FUNCTION AND LOAD PRIOR TO DEMOLITION. IF THESE ARE SERVING AREAS OR LOADS THAT ARE TO REMAIN, PROVIDE PROVISIONS FOR RELOCATING PRIOR TO DEMOLITION.
6. AREAS OR LOADS THAT ARE TO REMAIN, PROVIDE PROVISIONS FOR RELOCATING PRIOR TO
DEMOLITION. SOURCE OR FIRST UP STREAM DEVICE TO REMAIN IN SERVICE.
7. REMOVE ALL ABANDONED RACEWAY, CABLES, AND EQUIPMENT FROM AREAS TO BE
DEMOLISHED/REMODELED UNLESS NOTED OTHERWISE. DEMOLITION TO INCLUDE POWER,
LIGHTING FIRE ALARM DEVICES AND RACEWAYS, COMMUNICATION DEVICES AND RACEWAYS, LOW
VOLTAGE AND CONTROL SYSTEMS.
8. WHERE RACEWAYS ENTER OR EXIT SLABS OR PARTITIONS TO REMAIN, CUT RACEWAYS FLUSH
WITH FINISH SURFACE, REMOVE CONDUCTORS AND PREPARE FOR REFINISH OF AREA.
9. VERIFY THAT ALL UTILITIES HAVE BEEN DISCONNECTED AND MADE SAFE PRIOR TO COMMENCING
DEMOLITION.
10. CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL, RELOCATION OR PROTECTION OF ALL
ABOVE AND BELOW GROUND EXISTING IMPROVEMENTS.
K. AS CONSTRUCTED DOCUMENTS
1. CONTRACTOR IS RESPONSIBLE FOR KEEPING A COMPLETE SET OF CONSTRUCTION DOCUMENTS
SHOWING ACTUAL LOCATIONS, CIRCUITING INFORMATION, PRODUCT CATALOG NUMBERS,
DEVIATIONS AND CONCEALED LOCATIONS FOR WORK DIMENSIONED FROM CENTER OF COLUMNS
AND REFERENCED FLOOR HEIGHT. THESE AS CONSTRUCTED DOCUMENTS SHALL BE KEPT
UPDATED AND AVAILABLE ON SITE. UPON REQUEST THESE DOCUMENTS SHALL BE PROVIDED FOR
REVIEW BY THE ENGINEER WHILE ON SITE.
Kansas City
10561 Barkley Street, STE 100 Overland Park, KS 66212 t: +1 800.404.7677 e: hello@introba.com www.introba.com
© INTROBA, INC. 2025
WHEN THIS DRAWING IS
REPRODUCED AT ORIGINAL
SCALE THIS BAR = 1 INCH
The Professional Designer of Record (DOR), whose signature and personal seal appear on this document, assumes responsibility only for what appears hereon, and disclaims responsibility for all…