Attachment_AREVISED_Drawings.pdf
PDF 1 MB Posted
- Attached to
- Agriculture Center Roof Replacement
- Solicitation number
- B-2-26-28
- Issued by
- Brevard County, Clewiston City, Florida
About this file
This file consists of revised architectural drawings for the Agriculture Center Roof Replacement project located at 3695 Lake Drive, Cocoa, Florida 32926. The drawings depict the design specifications and technical details for the removal and replacement of the modified bitumen roof system at the facility. The document provides the visual representation and construction guidelines necessary for contractors to understand the scope of work, including the configuration of roofing materials, flashing details, penetration treatments, and all associated hardware required for the complete roof replacement project. The drawings serve as the primary technical reference document that contractors must follow to ensure compliance with the project specifications and successful completion of the work.
The revised drawings establish the standard by which all roofing materials, labor, and installation methods will be evaluated and performed. These architectural documents are essential for bid preparation, allowing contractors to accurately assess material quantities, labor requirements, and equipment needs for the removal of the existing roof system and installation of the new modified bitumen roof. The drawings supersede any previous versions and represent the final design intent that all bidders must use as the basis for their cost estimates and project scheduling.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Notice_of_Award.pdf | ||
| Bid_Tabulation__Intent_to_Award.pdf | ||
| Bid_Tabulation__Names_Only.pdf | ||
| Addendum_2.pdf | ||
| Addendum_1.pdf | ||
| Attachment_D__Draft_Contract.pdf | ||
| Attachment_ADrawings.pdf | ||
| Attachment_C__Substitution_Form.pdf | ||
| INV__SPECS.pdf | ||
| Attachment_BSpecifications_Project_Manual.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
R.D.
R.D.
R.D.
R.D.
R.D.
R.D.
R.D.
HVAC
HVAC
HVAC
HVAC
HVAC
A
CL
CL CL
CL
CL
CLCL
CL
D.S.
D.S.
D.S.
D.S.
D.S.
D.S.
D.S.
D.S.
D.S.
D.S.
D.S.
CL
CL
DESIGNATED
ROOF ASSEMBLY
SLOPE
LEGEND:
X
SOIL PIPE
EXHAUST FAN
NOT INCLUDEDN.I.C.
ROOF DRAIN
R.D.
DOWNPOUT
D.S.
ANTENNAA
CHANGE IN
ELEVATION
CONDENSATE LINECL
HVAC UNITHVAC
OVERFLOW
SCUPPER
SPLASH PAN
WALK PAD
GENERAL NOTES:
1. ALL PLANS ARE NOT TO SCALE UNLESS NOTED
OTHERWISE.
2. DIMENSIONS SHOWN ARE APPROXIMATE.
CONTRACTOR SHALL FIELD VERIFY ALL
DIMENSIONS PRIOR TO BID.
3. ROOF PENETRATIONS, EQUIPMENT, QUANTITIES
AND LOCATIONS ARE APPROXIMATE, FIELD
VERIFY PRIOR TO BID.
4. DRAWINGS CANNOT BE USED WITHOUT PBA
DESIGN GROUP INVOLVEMENT.
NEW CONSTRUCTION SCOPE:
1. TYPICAL: PATCH AREAS OF LIGHT WEIGHT
CONCRETE SURFACES AFTER TEAR-OFF AND
FILL ALL HOLES, DIVETS, SAW CUT LINES WITH
SECUROCK GYPSUM/CONCRETE PATCH REPAIR
OR OTHER PRODUCT APPROVED BY THE
ROOFING MEMBRANE MANUFACTURER.
2. TYPICAL: INSTALL NEW INSULATION, NEW COVER
BOARD AND A (2) PLY MODIFIED BITUMEN ROOF
SYSTEM. NEW INSULATION TO BE MINIMUM R=25.
3. TYPICAL: TOP OF ALL SOIL PIPES SHALL BE A
MINIMUM OF 8" ABOVE THE NEW FINISHED ROOF
SYSTEM. EXTEND AS NEEDED.
4. TYPICAL: FLASH ALL SOIL PIPES AND
PENETRATIONS (STEEL, ALUMINUM, CAST IRON,
GALVANIZED OR PVC PIPES) WITH
MANUFACTURER'S APPROVED FLASHING
SYSTEM AND FOLLOW MANUFACTURER'S
INSTRUCTIONS.
5. TYPICAL: HVAC, ELECTRICAL AND LOW VOLTAGE
SYSTEMS ARE TO REMAIN IN OPERATION DURING
CONSTRUCTION. IF EQUIPMENT MUST BE
BRIEFLY DISCONNECTED TO ACCOMPLISH THE
WORK, ALL COSTS FOR RECONNECTION ARE TO
BE INCLUDED IN THE BASE BID AS REQUIRED BY
THE AUTHORITY HAVING JURISDICTION.
6. TYPICAL: PATCH ANY HOLES IN WALL WHERE
DOWNSPOUT BRACKET FASTENERS HAVE BEEN
REMOVED AND PAINT PATCHES AND WALL
APPROXIMATE 24" WIDE BEHIND DOWNSPOUT
PRIOR INSTALLING. COLOR TO MATCH ADJACENT
FINISHES. CONTRACTOR TO REQUIRE A
LICENSED PAINTER TO CLEAN, PRESSURE WASH,
REPAIR AND PAINT TO PERFORM THE WORK.
7. TYPICAL: INSTALL CURB ADAPTERS AND CURB
EXTENSIONS AS REQUIRED BY THE AUTHORITY
HAVING JURISDICTION.
NEW CONSTRUCTION PLAN KEY
NOTES:
REPLACE WOOD NAILERS WHERE DAMAGED WITH
NEW PRESSURE TREATED WOOD MEMBER. SIZE
AND WIDTH TO MATCH EXISTING.
RE-FASTEN EXISTING 2x CONTINUOUS NAILERS AT
PERIMETER OF ROOF AND PARAPET WALL.
INSTALL NEW 2x PRESSURE TREATED NAILERS AT
PERIMETER OF ROOF, WIDTH AND SIZE TO MATCH
EXISTING, HEIGHT OF NAILERS TO MATCH NEW
INSULATION AND COVER BOARD AT ROOF EDGE.
INSTALL NEW 2x PRESSURE TREATED NAILERS AT
PERIMETER OF PARAPET WALL, WIDTH AND SIZE TO
MATCH EXISTING. MAINTAIN 8" (MIN.) HEIGHT ABOVE
NEW ROOF AND TOP OF PARAPET WALL.
SCOPE ALL EXISTING ROOF DRAIN LINE
APPROXIMATE 20'-0" TO VERIFY THE LINE IS CLEAR.
SUBMIT VIDEO FOR EACH DRAIN. REFER TO
SPECIFICATIONS FOR VIDEO REQUIREMENTS.
CONTRACTOR TO REQUIRE A DRAIN LINE VIDEO
CAMERA DIAGNOSTIC SERVICE TO PERFORM THE
WORK.
INSTALL ALL NEW PRE-FABRICATED SUMP AT ROOF
DRAIN LOCATIONS.
INSTALL NEW CRICKETS. MINIMUM 1/4 IN 12 SLOPE.
MAINTAIN 8" (MIN.) AT HIGHEST POINT OF CRICKET
TO TOP OF PARAPET WALL.
INSTALL ALL NEW EDGE METAL GRAVEL STOP
FASCIA.
INSTALL ALL NEW OVERFLOW METAL SCUPPERS.
INSTALL ALL NEW METAL COUNTER-FLASHING.
INSTALL ALL NEW METAL COPING.
CLEAN AND PRESSURE WASH STUCCO WALL
ABOVE ALL METAL COUNTER-FLASHING LOCATIONS
AND PAINT. PAINT TO MATCH EXISTING COLOR.
INSTALL ALL NEW GUTTERS.
INSTALL NEW GUTTER SCREENS AT ALL NEW
GUTTERS.
INSTALL ALL NEW DOWNSPOUTS.
PAINT SEALANT ABOVE METAL COUNTER-FLASHING.
INSTALL ALL NEW CONCRETE SPLASH BLOCKS AT
DOWNSPOUT LOCATIONS AND SECURE TO WALL.
REFER TO DETAIL A/A6.11.
INSTALL NEW GUARD RAILING SYSTEM.
INSTALL WALK PADS AROUND ALL MECHANICAL
EQUIPMENT, GUARD RAILING SYSTEM, SPLASH
PANS, METAL TRAY AT ANTENNA LOCATION AND
TOP AND BOTTOM LANDINGS OF LADDER.
CLEAN WALLS WHERE ROOF BITUMEN RESIDUE HAS
BEEN STAINED BY NEW ROOF CONSTRUCTION.
PAINT WALL BELOW NEW METAL COPING AT ENTIRE
PERIMETER WHERE EXPOSED TO VIEW DUE TO
NEW HEIGHT CHANGE. PAINT WALL BELOW
GUTTERS WHERE EXPOSED TO VIEW. PAINT
APPROXIMATE 12" (MIN.).
ROUTE CONDENSATE LINE INTO GUTTER WHERE
INDICATED.
INSTALL NEW CONCRETE PAVERS AT PVC
CONDENSATE LINES.
INSTALL NEW SPLASH PANS WHERE INDICATED.
REFER TO DETAIL B/A6.12.
INSTALL NEW MIL-FINISH ALUMINUM LADDER(S).
REINSTALL METAL TRAY AND C.M.U. BLOCKING AND
ANTENNA.
RE-FLASH ALL ROOF DRAINS.
CLEAN AND PAINT ALL ROOF DRAIN BOWLS,
CLAMPING RINGS AND DOMES.
PROVIDE NEW PVC CONDENSATE DRAIN LINE AND
EXTEND TO NEAREST ROOF DRAIN.
MAINTAIN 8" MINIMUM FROM FINISH ROOF TO TOP
OF PARAPET.
SEE DETAIL FOR DIAGONAL DOWNSPOUT
REQUIREMENTS.
WHERE NEW INSULATION HEIGHT EXCEEDS THE
EXISTING OPENING OF THE OVERFLOW SCUPPER
REFER TO DETAIL 3, 4 & B/A6.8.
32NEW ROOF ASSEMBLY
DESCRIPTION KEY NOTES:
- EXISTING CORRUGATED VENTED
METAL DECK.
- EXISTING 3" +/- TO 6" +/-
EPS INSULATION.
- EXISTING 2 1/2" +/- LIGHT WEIGHT
CONCRETE.
- APPLY NEW
ADHESIVE.
A
A
NEW ROOF ASSEMBLYN1
B
C
D
B C
- INSTALL NEW INSULATION.
- INSTALL NEW COVER
BOARD.
- INSTALL NEW (2) PLY
MODIFIED BITUMEN
ROOFING SYSTEM.
E
F
G
D
E
F
G
4 1/2" +/- EXISTING EXPANDED POLYSTYRENE (EPS ) INSULATION
0.8/INCH
(N1)
R-VALUE TABLE
1/2" NEW COVER BOARD 0.5
TOTAL 31 AVG.
2 1/2" +/- EXISTING LIGHT WEIGHT CONCRETE
3.8/INCH
2" NEW POLYISOCYANURATE INSULATION 11.4
MINIMUM R-VALUE R=25
MATERIAL DESCRIPTION VALUE TOTAL
17.1 AVG.
2 AVG.
0.5
11.4
Scale: AS NOTED
DATE:
(C) THESE DRAWINGS & THEIR
CONTENTS ARE THE SOLE
PROPERTY OF PBA DESIGN GROUP, INC..
USE OR COPY OF
ALL OR ANY PORTIONS IS BY
CONTRACT ONLY; UNAUTHORIZED
USE WILL BE PROSECUTED.
PBA DESIGN GROUP, INC..
SHEET NO.
ISSUE RECORD:
MAY 6, 2026
BI
D
A N
D C
O N
ST
RU
C
TIO
N
PR
O
JE
C T
A D
D
RE
SS
: 3
LA
KE
D R.
C O
C O
A , F
LO
RI
D A
J
A
SO
N S
T.
T
A M
PA
, F
L w w w .p ba d es ig ng ro up .c om
A R
B R
E V
A R
D C o A
G B
U
IL
D
IN
G R
O O
F R
E P
LA
C E M
E N
T
DRAWN BY: S.F.
CHECKED BY: H.P./J.B./M.C.
A5.1
NEW
CONSTRUCTION
ROOF PLAN
A6.5
NEW CONSTRUCTION ROOF PLAN
No Scale:
N1N1
N1
N1
1 2
20 21
20 21
20 21
A6.5
A6.5
A6.1
A6.1
A6.2
A6.11
A6.4
A6.4
A6.4
A6.5
A6.5
A6.6
A6.6
A6.6
A6.7
A6.7
A6.7
(TYP.)
A6.8
A6.8
A6.8
A6.8
A6.9
A6.9
A6.10
A6.11
A6.11
A6.12
A6.3
A6.3
25 25
7 7
45°
45°
A6.4
A6.4
A6.5
A6.5
A6.5
A6.5
A6.5
A6.5
A6.5
A6.5
A6.3
(TYP.)
(TYP.)
13 141314
(TYP.)
(TYP.)
A6.3
(TYP.)
A6.3
(TYP.)
A6.6
A6.6
A6.6
A6.12
A6.12
N1
A6.11
A6.5
(TYP.)
A6.5
(TYP.)
A6.5
(TYP.)
A6.11
A6.11
A6.11
A6.7
A6.7
A6.7
(TYP.)
A6.7
A6.7
A6.7
(TYP.)
(TYP.) (3)
SIDES.
(TYP.) ALL
SIDES.
A A6.1
(TYP.)
(TYP.)
A A6.1
(TYP.)
101216
101216
(TYP.)
(TYP.)
19(TYP.)
1 06-18-2026ADDENDUM #2
At ta ch m en t A
- R
EV
IS
ED
D ra w in gs
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text No.
AutoCAD SHX Text
DATE
SOLDER
DESCRIPTION KEY NOTES:
- GRAVEL STOP SHALL BE 24 GAUGE MIL-FINISHED
STAINLESS-STEEL.
- CANT IN METAL GRAVEL STOP HEIGHT SHALL
MATCH HEIGHT OF ROOF MEMBRANE PLIES ONLY
AT LOW END OF ROOF. ANGLE WILL DEPEND ON
HEIGHT OF PLIES.
- PRIME TOP AND BOTTOM OF HORIZONTAL LEG
WITH BRUSH ONLY.
- PROVIDE CANT AT END.
- PROVIDE END CLOSURE EACH SIDE.
A
B
C
D
- EXPANSION JOINT COVER OR
COUNTER-FLASHING ABOVE.
- EDGE TO BE HEMMED AND APPLY NEW SEALANT.
- PRE-DRILL HOLES IN METAL PRIOR TO FASTENING
WITH SCREWS OR EXPANSION FASTENERS.
PROVIDE 1/4" DIA. ALLOY NAIL DRIVE EXPANSION
FASTENERS OR 3/16" DIA. STAINLESS STEEL
TAPCONS WITH METAL BACKED EPDM WASHER
AT CONCRETE SUBSTRATES. FOR WOOD
SUBSTRATES PROVIDE #12 STAINLESS STEEL
5/16" H.W.H. (HEX WASHER HEAD) WITH METAL
BACK EPDM WASHER.
- PROVIDE END CLOSURE AT END OF
COUNTER-FLASHING.
REFER TO AWS D9.1/D9.1M:2018 - SHEET METAL
CODE FOR SOLDERING GUIDELINES.
NOTES:
1. CONTINUOUS CLEAT IS NOT SHOWN FOR
CLARITY BUT CLEAT SHALL BE ONE GAUGE
HEAVIER THAN FASCIA THICKNESS.
2. PROVIDE MOCK-UP FOR APPROVAL.
3. ALL JOINTS ARE TO BE FULLY SOLDERED AND
MECHANICALLY ATTACHED.
4. USE 2B MIL-FINISH STAINLESS-STEEL.
F
G
H
E
4" (M
IN
PE
R
FI
EL
D
CO
ND
IT
IO
N.
" O
R
AS
N
EE
DE
D.
4"
24" (TYP.)
" O
R
AS
N
EE
DE
D.
24" (TYP.)
4" (M
IN
4" (M
IN.)
4" (M
IN.)
PE
R
FI
EL
D
CO
ND
IT
IO
N.
4"
A
B
C
A
B
C
D E
F
F
G
G
H
H
D E
EDGE METAL FASCIA DETAIL AT END OF WALL1
A6.4 No Scale: TYPICAL
DESCRIPTION KEY NOTES:
- EXISTING WALL.
- EXISTING 2x WOOD NAILERS. 2x PLIES MAY
VARY IN HEIGHT, WIDTH AND
CONFIGURATION PER FIELD CONDITIONS.
a. FOR RE-ATTACHMENT OF EXISTING
WOOD TO STRUCTURAL CONCRETE
SUBSTRATES USE 1/4" DIAMETER
STAINLESS-STEEL DEFORMED SHANK
FASTENERS @ 12" O/C. (MAX.) IN
STAGGERED FASHION. PRE-DRILL HOLES
PRIOR INSTALLING FASTENERS.
PROVIDE 1" EMBEDMENT INTO
SUBSTRATE.
b. FOR RE-ATTACHMENT OF EXISTING
WOOD TO METAL FRAMING SUBSTRATES
USE #15 STAINLESS-STEEL INSULATION
SCREWS @ 12" O/C. (MAX.) IN
STAGGERED FASHION. PROVIDE 1"
EMBEDMENT INTO SUBSTRATE. LENGTH
TO BE DETERMINED IN THE FIELD.
c. FOR RE-ATTACHMENT OF EXISTING
WOOD TO WOOD SUBSTRATES USE
STAINLESS-STEEL PNEUMATIC GUN
NAILS @ 12" O/C. (MAX.) IN STAGGERED
FASHION.
- EXISTING 1x OR 2x WOOD FASCIA.
RE-ATTACH TO SUBSTRATE. SEE NOTES
ABOVE FOR PROPER ATTACHMENT TO
SUBSTRATE.
- NEW PRESSURE TREATED 2x NAILERS.
HEIGHT TO MATCH NEW INSULATION AND
COVER BOARD TOTAL THICKNESS.
- PROVIDE PRESSURE TREATED 1x's OR
PRESSURE TREATED SHIMS TO ADJUST
HEIGHT AS NEEDED.
NOTE: CONDITIONS MAY VARY ONCE
CONSTRUCTION HAS BEEN OPENED.
B
A
C
D
E
A
B
D
E
WOOD NAILER RE-ATTACHEMNT DETAILA
A6.4 No Scale: TYPICAL
LOW GRAVEL STOP FASCIA DETAIL AT GUTTER2
A6.4 Scale: N.T.S. TYPICAL
NOTES:
1. MAY REQUIRE (2) PIECE METAL FASCIA.
FIELD VERIFY PRIOR FABRICATION.
2. PROVIDE MOCK-UP FOR APPROVAL.
- NEW INSULATION AND COVER BOARD. SEE
PLAN FOR REQUIRED R-VALUE INSULATION.
- NEW BASE SHEET. EXTEND OVER NAILERS
AND WALL DOWN AS SHOWN.
- INSTALL NEW GUTTER BRACKET.
- INSTALL NEW GUTTER.
- INSTALL NEW METAL CLEAT.
- INSTALL NEW METAL GRAVEL STOP FASCIA.
PRIME HORIZONTAL LEG OF METAL TOP AND
BOTTOM WITH BRUSH - DO NOT ROLL PRIMER.
- INSTALL NEW STRIPPING PLY.
- INSTALL NEW CAP SHEET.
- APPLY NEW LIQUID FLASHING SEALANT AND
APPLY GRANULES.
- ALTERNATE: "L" SHAPE CLEAT.
DESCRIPTION KEY NOTES:
- EXISTING CONCRETE/C.M.U. WITH STUCCO FINISH.
- EXISTING EPS INSULATION WITH LIGHT WEIGHT
CONCRETE OVER CORRUGATED METAL DECK.
- EXISTING 2x NAILER (RE-ANCHOR). SEE DETAIL A/A6.4 FOR REQUIREMENTS. NUMBER OF 2x PLIES VARY PER
ROOF.
- NEW PRESSURE TREATED 2x NAILER. WIDTH TO
MATCH EXISTING. ATTACH NEW NAILER TO EXISTING
WITH 3" LONG STAINLESS-STEEL NAILS @ 16" O/C.
(MAX.) STAGGERED WITH PNEMATIC NAIL GUN.
- ATTACH NEW PRESSURE TREATED PLYWOOD
PLYWOOD SHIMS TO MATCH HEIGHT OF INSULATION
AND COVER BOARD. ATTACHED WITH 2" LONG
STAINLESS-STEEL NAILS @ 16" O/C. (MAX.)
STAGGERED WITH PNEMATIC NAIL GUN.
B
A
C
D
4"(MIN.)
4"(MIN.)
SEALANT DETAIL
I
H
A
B
C
D E
F
SLOPE
G 1/2" GAP
(TYP.)
E
F
G
H
I
J
K
L
G
M
N
O
H
J
N
N
K
L M
O
4"
TY
P.
24" (TYP.)
FI
EL
D
VE
RI
FY
WIDTH
AS REQ'D.
DESCRIPTION KEY NOTES:
- METAL COPING SHALL BE 24 GAUGE MIL
FINISHED STAINLESS-STEEL.
- SOLDER ALL JOINTS.
- EDGE TO BE HEMMED AND APPLY NEW SEALANT.
- PRE-DRILL HOLES IN METAL PRIOR TO FASTENING
WITH SCREWS OR EXPANSION FASTENERS.
PROVIDE 1/4" DIA. ALLOY NAIL DRIVE EXPANSION
FASTENERS OR 3/16" DIA. STAINLESS STEEL
TAPCONS WITH METAL BACKED EPDM WASHER.
A
B
C
D
REFER TO AWS D9.1/D9.1M:2018 - SHEET
METAL CODE FOR SOLDERING GUIDELINES.
4"
(TYP.)
TY
P.
24" (TYP.)
FI
EL
D
VE
RI
FY
WIDTH
AS REQ'D.
C
D
C
B
A
A
- EXTEND METAL COPING ABOVE WHERE METAL
COPING OR GRAVEL STOP IS REQUIRED OR
EXISTING - MAX. HEIGHT 16" OR LESS.
- PROVIDE COUNTER-FLASHING. SEE DETAIL ON
SHEET A6.6.
- EXTEND COUNTER-FLASHING 4" BEYOND.
- PROVIDE END CAP AT COUNTER-FLASHING.
E
E
B
E
C
D
D
METAL COPING DETAIL AT END OF WALL3
A6.4 Scale: N.T.S. TYPICAL
F
F
F
4" (M
IN.)
4"
G
G
G
H
H
H
I
I
I
SOLDER
NOTES:
1. PROVIDE MOCK-UP FOR APPROVAL.
2. ALL JOINTS ARE TO BE FULLY SOLDERED AND
MECHANICALLY ATTACHED.
3. USE 2B MIL-FINISH STAINLESS-STEEL.
PAINT APPROX. 12"
WIDE CONTINUOUS
AT ENTIRE EXTRIOR
PERIMETER ONLY.
Scale: AS NOTED
DATE:
(C) THESE DRAWINGS & THEIR
CONTENTS ARE THE SOLE
PROPERTY OF PBA DESIGN GROUP, INC..
USE OR COPY OF
ALL OR ANY PORTIONS IS BY
CONTRACT ONLY; UNAUTHORIZED
USE WILL BE PROSECUTED.
PBA DESIGN GROUP, INC..
SHEET NO.
ISSUE RECORD:
MAY 6, 2026
BI
D
A N
D C
O N
ST
RU
C
TIO
N
PR
O
JE
C T
A D
D
RE
SS
: 3
LA
KE
D R.
C O
C O
A , F
LO
RI
D A
J
A
SO
N S
T.
T
A M
PA
, F
L w w w .p ba d es ig ng ro up .c om
A R
B R
E V
A R
D C o A
G B
U
IL
D
IN
G R
O O
F R
E P
LA
C E M
E N
T
DRAWN BY: S.F.
CHECKED BY: H.P./J.B./M.C.
A6.4
DETAILS
1 06-18-2026ADDENDUM #2
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text No.
METAL COPING OR METAL FASCIA LAYOUT DETAILA
A6.5 Scale: N.T.S. TYPICAL
METAL WORK NOTES:
1. ADD METAL SKIRTS TO WALL FACE UNDER
COPING TO EXTEND FACE TO COVER NAILERS
WHERE NEEDED.
2. LINE UP COVER PLATES WHERE SKIRT METAL
IS USED.
3. DRIVE CLEAT JOINT COVER LOCATIONS SHALL
BE DETERMINED BY THE LENGTH OF THE
BUILDING AND TAKE INTO ACCOUNT THE
COPING MITER AT THE CORNERS AND SPACE
JOINT COVERS IN A UNIFORMLY MANNER OR
EQUALLY SPACED AS NEEDED.
4. PROVIDE MOCK-UP FOR APPROVAL.
24" EQ. EQ. EQ. 24"
24"
SHORT
PIECE. 24"
24" LONG PIECE. 24"
MID-PIECE. LONG PIECE.
SHORT
PIECE. LONG PIECE.
ACCEPTED UNIFORMLY
METAL WORK
NOT UNIFORMLY METAL
WORK (NOT ACCEPTED)
NOT UNIFORMLY METAL
WORK (NOT ACCEPTED)
METAL WORK NOT UNIFORMLY
LAID OUT. METAL WORK
SHOWS SHORTER PIECES
TOWARDS AT THE END.
JOINT.JOINT.
JOINT.JOINT.
JOINT.JOINT.
METAL WORK NOT UNIFORMLY
LAID OUT. METAL WORK
SHOWS SHORTER PIECE AT
THE CENTER.
BASE FLASHING DETAIL AT PARAPET WALL2
A6.5 Scale: N.T.S. TYPICAL
ONE PIECE CONSTRUCTION
TWO PIECE CONSTRUCTION
SOLDER.
FILL IN PIECE
NOTES:
1. CLEAT MITER PIECE TO WITHIN 12" OF OUTSIDE CORNER.
2. SOLDER "FILL IN" PIECE INTO PLACE OR USE ONE PIECE CONSTRUCTION.
3. SOLDER MITER AND MECHANICALLY ATTACHED.
4. STANDING SEAM JOINTS ARE NOT ACCEPTABLE.
5. MITERS SHALL SLOPE TO ROOF MATCHING COPING.
6. USE 2B MIL-FINISH STAINLESS-STEEL.
REFER TO AWS D9.1/D9.1M:2018 - SHEET METAL CODE FOR SOLDERING
GUIDELINES.
SLOPESLOPE
SLOPE SLOPE
24" (MAX.) EQUAL. 24" (MAX.) EQUAL.
3/4
(M
IN
1/2
(M
IN
WIDTH PER
FIELD
CONDITIONS.
METAL COPING MITER DETAIL3
A6.5 Scale: N.T.S. TYPICAL
NOTES:
1. REFER TO METAL COPING DETAIL AT PARAPET WALL
FOR ALL REQUIREMENTS REGARDING ALL METAL
WORK AND ANCHORAGE AT TOP OF PARAPET WALL
AND ADDITIONAL REQUIREMENTS.
2. NO FASTENERS SHALL PENETRATE THE BASE
FLASHING ON TOP OF THE PARAPET.
3. MEMBRANE FLASHING'S ARE TO BE 8" MIN.
SLOPE
SLOPE
F
G
H
DESCRIPTION KEY NOTES:
- EXISTING PARAPET WALL.
- EXISTING BLOCKING/NAILER FIELD
VERIFY.
- NEW 2x BLOCKING/NAILER.
- EXISTING ROOF DECK WITH NEW
INSULATION. SEE ROOF ASSEMBLIES
FOR ADDITIONAL REQUIREMENTS.
- PROVIDE NEW PERLITE CANT SET IN
ADHESIVE.
- PRIME WALL AND NAILER.
- INSTALL NEW BASE SHEET. BASE SHEET
SHALL GO UP AND OVER THE PARAPET
WALL AND EXTEND 2" BELOW THE
BLOCKING/NAILER AS SHOWN.
- NEW STRIPPING-PLY.
- PROVIDE NEW MODIFIED BITUMEN
CAP SHEET. CAP SHEET SHALL GO UP
THE PARAPET WALL AND STOP
SHORTLY AT BLOCKING/NAILER.
- INSTALL NEW MEMBRANE FLASHING
- INSTALL NEW METAL CLEAT.
- ONCE CLEAT HAS BEEN INSTALLED
PROVIDE A SELF-ADHERED
MEMBRANE SHEET CONTINUOUS TO
LAP OVER THE VERTICAL LEG OF
CLEAT AND CAP SHEET AS INDICATED.
- INSTALL NEW METAL COPING. FOR ALL
METAL WORK, GAUGES, METAL TYPE,
FINISHES AND FASTENER, SIZE, TYPE
AND SPACING REFER TO "METAL
COPING DETAIL AT PARAPET WALL"
FOR ADDITIONAL REQUIREMENTS.
- PAINT APPROX. 12" WIDE CONTINUOUS AT
ENTIRE EXTERIOR OF PERIMETER ONLY.
B
D
A
C
E
A
A
B
B
C
C
D
D
G
I
J
K
E L
2"
NEW 24 GAUGE MIL
FINISHED
STAINLESS-STEEL.
E F
G H
I
J
K
G H
M
L
L
M
8" (M
IN
METAL COPING DETAIL AT PARAPET WALL1
A6.5 Scale: N.T.S. TYPICAL
EXTEND FACE
AS REQUIRED.
DRIVE CLEAT PARTIALLY
SHOWN.
STEP #2
SLOPE
ROOF SIDE
1" 1"
1/2"
4" (MIN.)
ALTERNATE NAILER
CONDITION
2"
12"
DRIVE CLEAT
JOINT COVER
BACKUP PLATE
STEP #1
STEP #3
STEP #4
1/2" GAP.
1"
1"
6"
LAP.
2" (M
IN
1/2
3/4
12" (MIN.)
3/4" (MIN.)
4" (M
IN
4" (MIN.)
WIDTH OF METAL
COPING & DRIVE
CLEAT PER FIELD
CONDITIONS.
DESCRIPTION KEY NOTES:
- FACE OF C.M.U./CONCRETE WALL.
- EXISTING WOOD NAILER/BLOCKING.
- RE-FASTEN EXISTING WOOD NAILER/BLOCKING TO EXISTING
C.M.U./CONCRETE WALL WITH 1/4" DIA. STAINLESS-STEEL
DEFORMED SHANK SPIKE TYPE FASTENERS @ 12" O/C.
(MAX.) STAGGERED WITH 1" (MIN.) EMBEDMENT.
- INSTALL NEW 2x PRESSURE TREATED NAILER/BLOCKING
CONTINUOUS FASTENED TO EXISTING NAILER/BLOCKING
WITH 3" LONG STAINLESS-STEEL RING SHANK PNEUMATIC
GUN NAILS @ 6" O/C. (MAX.) STAGGERED OR USE 3" LONG
STAINLESS-STEEL SCREWS - WOOD TO WOOD.
- ATTACH NEW 1x2 PRESSURE TREATED SHIM CONTINUOUS ATTACHED TO 2x NAILER/BLOCKING.
- INSTALL NEW UNDERLAYMENT. UNDERLAYMENT SHALL GO
UP AND OVER THE PARAPET WALL AND EXTEND 2" BELOW
THE NAILER/BLOCKING AS SHOWN.
- INSTALL NEW FLASHING MEMBRANE. FLASHING MEMBRANE
SHALL GO UP THE PARAPET WALL AND STOP SHORTLY AT
NAILER/BLOCKING.
- INSTALL NEW 22 GAUGE MIL-FINISH STAINLESS-STEEL
CONTINUOUS CLEAT. ATTACH CLEAT WITH 12 GAUGE x 1 1/2"
LONG 3/8" HEAD (MIN.) STAINLESS-STEEL RING SHANK NAILS
@ 6" O/C. (MAX.) STAGGERED.
- INSTALL NEW SELF-ADHERING MEMBRANE OVER WALL AND
FACE OF CLEAT.
- INSTALL NEW 24 GAUGE MIL-FINISH STAINLESS-STEEL BACK
UP PLATE 12" LONG (MIN.) AT METAL COPING JOINT
LOCATIONS.
- APPLY (2) RIBBONS OF SEALANT TOP AND BOTTOM (BOTH
SIDES) OF BACK UP PLATE.
- INSTALL NEW 24 GAUGE MIL-FINISH STAINLESS-STEEL
CONTINUOUS METAL COPING COVER.
- INSTALL NEW 24 GAUGE MIL-FINISH STAINLESS-STEEL
DRIVE CLEAT JOINT COVER. TURN DOWN DRIVE CLEAT TO
COVER FACES OF METAL COPING AND CRIMP METAL TO
ENGAGE DRIP EDGE.
METAL COPING NOTES:
1. VERTICAL LEGS OF COPING SHALL BE A
MINIMUM OF 4". COPING LAPS SHALL BE 6"
MINIMUM.
2. CONTINUOUS CLEATS ARE REQUIRED.
3. BACKUP PLATES ARE REQUIRED AND ARE TO
BE LOCATED AT DRIVE CLEAT LOCATIONS.
4. CLOSE CLEAT RECEIVERS TIGHT TO CLEAT
CONTINUOUSLY.
5. PROVIDE SLOPE TO ROOF OF 2" IN 12". ADD
SHIMS AS REQUIRED.
6. ADD NAILERS TO PARAPET WALL TO MAINTAIN
8" ABOVE THE ROOF SURFACE.
7. IF NAILERS ARE EXISTING AND MAINTAINS 8"
ABOVE THE ROOF SURFACE, NAILERS ARE TO
BE REATTACHED.
8. ADD METAL SKIRTS TO WALL FACE UNDER
COPING TO EXTEND FACE TO COVER NAILERS.
9. LINE UP COVER PLATES WHERE SKIRT METAL
IS USED.
5. LAP VERTICAL LEGS OF COPING 2" MINIMUM.
8. DO NOT USE DRIVE CLEATS ON STEEP SLOPE
WALLS.
9. USE LAP JOINTS FOR COPING THAT SLOPES
END TO END. LAP COPING COVER SHALL BE 6"
MINIMUM AND SHALL BE INSTALLED IN
DIRECTION OF FLOW.
10.CLEAT JOINTS SHALL ABUT AND SHALL BE
LOCATED MID-WAY AT COPING COVER.
11.DRIVE CLEAT JOINT COVER LOCATIONS SHALL
BE DETERMINED BY THE LENGTH OF THE
BUILDING AND TAKE INTO ACCOUNT THE
COPING MITER AT THE CORNERS AND SPACE
JOINT COVERS IN A UNIFORMLY MANNER OR
EQUALLY SPACED AS NEEDED.
12.PROVIDE MOCK-UP FOR APPROVAL.
13.SEE DETAIL A/A6.5 FOR METAL WORK LAYOUT.
14.USE 2B MIL-FINISH STAINLESS-STEEL.
F
G
H
B
D
A
C
E
I
J
K
L
M
N
DESCRIPTION KEY NOTES CONTINUE BELOW:
- FASTEN ROOF SIDE OF NEW METAL COPING
VERTICAL LEG WITH #12 x 2" LONG
STAINLESS-STEEL HEX HEAD DRIVE SCREWS
WITH STAINLESS-STEEL CAPPED EPDM
WASHER @ 24" O/C. (MAX.)
ROOF SIDE
ROOF SIDE
ROOF SIDE
A
B
C
D E
F
G
H
I
J
2" (M
IN
B
C
E
D
A
A
B
C
D
E
D F G I
JK K
H
WIDTH OF METAL
BACKUP PLATE PER
FIELD CONDITIONS.
L
M
FOLD FLANGE
BACK.
N
L
NEW 24 GAUGE MIL
FINISHED
STAINLESS-STEEL.
N
N
Scale: AS NOTED
DATE:
(C) THESE DRAWINGS & THEIR
CONTENTS ARE THE SOLE
PROPERTY OF PBA DESIGN GROUP, INC..
USE OR COPY OF
ALL OR ANY PORTIONS IS BY
CONTRACT ONLY; UNAUTHORIZED
USE WILL BE PROSECUTED.
PBA DESIGN GROUP, INC..
SHEET NO.
ISSUE RECORD:
MAY 6, 2026
BI
D
A N
D C
O N
ST
RU
C
TIO
N
PR
O
JE
C T
A D
D
RE
SS
: 3
LA
KE
D R.
C O
C O
A , F
LO
RI
D A
J
A
SO
N S
T.
T
A M
PA
, F
L w w w .p ba d es ig ng ro up .c om
A R
B R
E V
A R
D C o A
G B
U
IL
D
IN
G R
O O
F R
E P
LA
C E M
E N
T
DRAWN BY: S.F.
CHECKED BY: H.P./J.B./M.C.
A6.5
DETAILS
1 06-18-2026ADDENDUM #2
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text No.
| Sheets and Views |
| A5.1 |
| A6.5 Details-A6.5.pdf |
| Sheets and Views |
| A6.5 |
| A6.4 Details-A6.4.pdf |
| Sheets and Views |
| A6.4 |