Attachment_9_-_PC_VFD_-_SIDHU_IFC_052026.pdf
PDF 3 MB Posted
- Solicitation number
- 2026-RFP-175
- Issued by
- Pierce County, Tacoma City, Washington
About this file
This file is an electrical specifications and site plan document prepared by Huitt-Zollars for Pierce County Agriculture Program in Washington, detailing the design requirements for a Variable Frequency Drive (VFD) addition to an irrigation system at the Sidhu Farm located at 15306 96th Street East, Puyallup, WA 98372. The project involves installing a new VFD controller, pump timer controller, pressure transducer, and associated electrical infrastructure to an existing 50-horsepower water pump and motor system. The electrical work includes extending power circuits from the existing 480Y/277V three-phase service, installing a new NEMA 4 steel enclosure to house the VFC and pump timer controller, routing conduit and conductors per National Electrical Code standards, and providing a 120VAC GFCI receptacle in the controller enclosure. The document is dated May 20, 2026 and marked as a 100% submittal.
The specifications establish comprehensive requirements for all electrical components and installations, including detailed standards for conduits (rigid galvanized steel, intermediate metallic, electrical metallic tubing, and PVC), 600-volt wires and cables with copper conductors, wiring devices, overcurrent protective devices, grounding systems, and surge protection devices. The VFC unit must meet specific operational requirements including 96 percent minimum efficiency at 60 hertz full load, capability to handle rotating loads, microprocessor-based thermal protection, and UL 1449 integral surge suppression. All material and labor costs for the VFD controller and supporting equipment are funded through the Floodplains by Design Grant 5 (Agreement #SEAFBD-2123-PICOPW-00024), while participating farms are responsible for annual inspection and servicing costs for a minimum of five years. Pierce County Contact Dean McClary (253) 798-6221 and Farm Owner Kamal Sidhu (253) 651-3755 are identified as primary contacts for the project.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NEMA 5-20 DUPLEX RECEPTACLE MOUNTED 18" AFF
UNLESS NOTED OTHERWISE.
JUNCTION BOX.
DISCONNECT SWITCH, UNFUSED. SIZE AS SHOWN.
DISCONNECT SWITCH, FUSED. SIZE AS SHOWN.
SURFACE MOUNTED EQUIPMENT.
GROUND ROD.
ARROW INDICATES HOMERUN TO PANEL "A", CIRCUIT
21.
EXISTING OVERHEAD ELECTRICAL LINE.
EXISTING UNDERGROUND ELECTRICAL LINE.
EXISTING OVERHEAD COMMUNICATIONS LINE.
EXISTING UNDERGROUND COMMUNICATIONS LINE.
EXISTING ITEMS TO BE REMOVED.
NEW OVERHEAD ELECTRICAL LINE.
NEW UNDERGROUND ELECTRICAL LINE.
J
A-21
ELECTRICAL LEGEND
A AMPERE
AFF ABOVE FINISHED FLOOR
C CONDUIT
CB CIRCUIT BREAKER
EMT ELECTRICAL METALLIC TUBING
G GROUND
GFCI GROUND FAULT CIRCUIT INTERRUPTING
HP HORSEPOWER
HZ HERTZ
KWH KILOWATT HOUR
LED LIGHT EMITTING DIODE
MLO MAIN LUGS ONLY
NEC NATIONAL ELECTRICAL CODE
PH PHASE
PVC POLYVINYL CHLORIDE
RGS RIGID GALVANIZED STEEL
SPD SURGE PROTECTION DEVICE
SW SWITCH
V VOLT
VA VOLTAMPERE
VFC VARIABLE FREQUENCY CONTROLLER
W WATTS
WP WATERPROOF
XFMR TRANSFORMER
ABBREVIATIONS
OE
E
OC
C
E
NE
UE
GENERAL NOTES
96th St E
W A 162
McMillin
R iverside D r E M cC utheon R d E
Sumner
WA 410
Pu ya llu p
Ri ve r
AldertonPuyallup
Bonney Lake
SITE
1. GENERAL ELECTRICAL REQUIREMENTS
A. PROVIDE ELECTRICAL WORK IN ACCORDANCE WITH THE
NATIONAL ELECTRICAL CODE AND ANY LOCAL, STATE AND
NATIONAL CODES, ORDINANCES AND REGULATIONS THAT HAVE
JURISDICTION OR AUTHORITY OVER THE WORK. IF THE
STANDARDS AND CODES CONFLICT WITH EACH OTHER, APPLY
THE MOST STRINGENT.
B. SECURE AND PAY FOR PERMITS, LICENSES AND INSPECTIONS
AS REQUIRED BY LAW FOR THE COMPLETION OF THE WORK.
C. MAINTAIN THE WATERPROOF INTEGRITY OF CONDUIT
PENETRATIONS THROUGH THE ROOF, EXTERIOR WALLS AND
FLOORS.
D. IDENTIFY ELECTRICAL EQUIPMENT IN ACCORDANCE WITH THE
NEC, THE LOCAL AUTHORITIES, AND AS SPECIFIED. USE
LAMINATED THREE-PLY ENGRAVED PLASTIC NAMEPLATES WITH
BLACK SURFACE AND WHITE INTERIOR CORE, AT LEAST 1/16"
THICK ON THE COVER OF EACH BRANCH CIRCUIT PANEL.
E. PROVIDE ALL ELECTRICAL DEVICES AND COMPONENTS LISTED
AND APPROVED BY THE UNDERWRITERS LABORATORIES AND
BEAR THE UL LABEL.
2. ELECTRICAL DEMOLITION
A. DEMOLITION DRAWINGS ARE BASED ON FIELD OBSERVATION
AND EXISTING RECORD DOCUMENTS. VERIFY MEASUREMENTS
AND CIRCUITING ARE AS SHOWN ON DRAWINGS. VERIFY THAT
DEMOLISHED WIRING AND EQUIPMENT SERVE ONLY REMOVED
FACILITIES. REPORT DISCREPANCIES BEFORE DEMOLITION TO
THE OWNER.
B. MAINTAIN EXISTING REMAINING SYSTEMS IN SERVICE TO THE
FULLEST EXTENT POSSIBLE. PROVIDE TEMPORARY WIRING AND
CONNECTIONS TO MAINTAIN EXISTING SYSTEM IN SERVICE
DURING CONSTRUCTION AS REQUIRED BY OWNER.
COORDINATE OUTAGES WITH OWNER AND UTILITY COMPANY.
C. REMOVE ALL UNUSED CONDUIT. REMOVE ALL DISCONNECTED
CIRCUIT CONDUCTORS FROM SOURCE TO DEVICE.
D. REPAIR ADJACENT CONSTRUCTION AND FINISHES EXPOSED OR
DAMAGED DURING DEMOLITION AND EXTENSION WORK. FINISH
RESTORATION SHALL BE IN KIND.
E. MAINTAIN ACCESS TO EXISTING, REMAINING ELECTRICAL
INSTALLATIONS.
F. CLEAN AND REPAIR EXISTING MATERIALS AND EQUIPMENT
WHICH REMAIN OR ARE TO BE REUSED. REPAIR OR REPLACE
IN-KIND EQUIPMENT DAMAGED DURING DEMOLITION.
3. CONDUITS
A. PROVIDE RIGID GALVANIZED STEEL CONDUIT MANUFACTURED IN
ACCORDANCE WITH ANSI C80.1 STANDARDS, AND U.L. 6 LISTED.
PROVIDE THREADED FITTINGS IN ACCORDANCE WITH
ANSI/NEMA FB1. RIGID GALVANIZED STEEL CONDUIT MAY BE
USED IN ALL LOCATIONS. PROVIDE PVC COATED RIGID
GALVANIZED STEEL CONDUIT IN CORROSIVE ENVIRONMENTS OR
WHERE IN CONTACT WITH CONCRETE.
B. PROVIDE INTERMEDIATE METALLIC CONDUIT MANUFACTURED IN
ACCORDANCE WITH ANSI C80.6 STANDARDS, AND U.L. 1242
LISTED. PROVIDE THREADED FITTINGS IN ACCORDANCE WITH
ANSI/NEMA FB1. INTERMEDIATE METALLIC CONDUIT MAY BE
USED IN ALL NON-CORROSIVE LOCATIONS.
C. PROVIDE ELECTRICAL METALLIC TUBING MANUFACTURED IN
ACCORDANCE WITH ANSI C80.3 STANDARDS, AND U.L. 797
LISTED. PROVIDE FITTINGS OF STEEL, DIE CAST ZINC, OR
MALLEABLE IRON, COMPRESSION TYPE WITH INSULATED
THROAT IN ACCORDANCE WITH ANSI C80.3 STANDARDS.
ELECTRICAL METALLIC TUBING MAY BE USED IN
NON-HAZARDOUS, NON-CORROSIVE LOCATIONS NOT SUBJECT
TO SEVERE PHYSICAL DAMAGE.
D. PROVIDE FLEXIBLE METAL CONDUIT MANUFACTURED IN
ACCORDANCE WITH U.L. PROVIDE LIQUID TIGHT CONDUIT WITH
EXTRUDED, POLYVINYL JACKET OVER THE FLEXIBLE METAL.
PROVIDE CADMIUM-PLATED FITTINGS WITH MALLEABLE IRON
BODY AND NUT; CADMIUM STEEL FERRULE; INSULATED THROAT;
INTEGRALLY-CAST, EXTERNAL GROUND LUGS IN ACCORDANCE
WITH NEMA FB1. FLEXIBLE METALLIC CONDUIT MAY BE USED
FOR ALL CONNECTIONS TO EQUIPMENT IN ALL INTERIOR, DRY,
NON-CORROSIVE LOCATIONS. LIQUID TIGHT FLEXIBLE METALLIC
CONDUIT MAY BE USED FOR ALL CONNECTIONS TO EQUIPMENT
NOT SUBJECT TO EXCESSIVE TEMPERATURES. CONDUITS SHALL
BE INSTALLED IN NON-HAZARDOUS LOCATIONS NOT SUBJECT
TO PHYSICAL DAMAGE. LENGTH SHALL BE 6'-0" MAXIMUM.
E. PROVIDE SCHEDULE 40 AND 80 PVC RIGID NONMETALLIC
CONDUIT IN ACCORDANCE WITH NEMA TC-2 AND U.L. 651.
PROVIDE SOLVENT-WELDED, SLIP-ON JOINTS IN ACCORDANCE
WITH NEMA TC3 AND U.L. 514B. RIGID NONMETALLIC CONDUIT
MAY BE USED IN NON-HAZARDOUS LOCATIONS AND INSTALLED
EITHER UNDERGROUND OR ENCASED IN CONCRETE.
F. PROVIDE GROUNDING BUSHINGS COMPLYING WITH W-W-C-581D,
UL STANDARDS 514B AND 467.
G. PROVIDE CADMIUM-PLATED, MALLEABLE IRON HUBS WITH
TAPERED THREADS, A NEOPRENE "O" RING AND AN INSULATED
THROAT.
H. SEAL CONDUIT PENETRATIONS THROUGH U.L. CLASSIFIED
SMOKE AND FIRE WALLS WITH SEALANT THAT MAINTAINS THE
WALLS FIRE RATING.
I. INSTALL PULL STRINGS IN EMPTY CONDUITS. USE
POLYPROPYLENE PLASTIC LINE WITH NOT LESS THAN 200 LB.
TENSILE STRENGTH. LEAVE AT LEAST FIVE FEET OF EXCESS
LINE AT EACH END.
J. ROUTE CONDUITS PARALLEL TO BUILDING LINES. CONCEAL
CONDUITS BELOW GRADE, WITHIN WALLS, OR ABOVE CEILINGS
IN FINISHED AREAS.
K. ROUTE CONDUIT THROUGH ROOF OPENINGS FOR PIPING AND
DUCTWORK WHERE POSSIBLE. OTHERWISE, ROUTE CONDUIT
THROUGH THE ROOF WITH PITCH POCKET. CONDUIT SHALL NOT
PENETRATE DUCTWORK.
4. 600 VOLT WIRES AND CABLES
A. PROVIDE COPPER CONDUCTORS BEARING THE U.L. LABEL.
PROVIDE #12 AWG MINIMUM SIZE CONDUCTORS. CONDUCTORS
#8 OR LARGER SHALL BE STRANDED. CONDUCTORS SHALL BE
INSULATED WITH THERMOPLASTIC INSULATION RATED AT 600
VOLTS AND INSULATED WITH TYPE THHN/THWN OR XHHW
INSULATION.
B. METAL CLAD, TYPE AC OR MC CABLE SYSTEMS SHALL NOT BE
USED.
C. SPLICE ONLY IN JUNCTION OR OUTLET BOXES. PULL ALL
CONDUCTORS INTO A RACEWAY AT THE SAME TIME AND USE
U.L. LISTED, WIRE PULLING LUBRICANT FOR PULLING NO. 4 AWG
AND LARGER WIRE.
D. NEVER SPLICE TOGETHER CONDUCTORS OF DIFFERENT
COLORS.
E. IN EXISTING FACILITIES, MATCH EXISTING CONDUCTOR COLOR
CODING SCHEME. OTHERWISE, USE THE FOLLOWING COLOR
CODE: FOR 277/480V, 3-PHASE WIRING: PHASE A - BROWN,
PHASE B - PURPLE, PHASE C - YELLOW, NEUTRAL - GRAY,
EQUIPMENT GROUNDING CONDUCTOR - GREEN. USE THE
FOLLOWING COLOR CODE FOR 120/208V OR 240V, 3-PHASE
WIRING: PHASE A - BLACK, PHASE B - RED (ON 240/120V, 3Ø, 4W
SYSTEMS THE HIGH VOLTAGE LEG WILL BE PHASE B AND WILL
BE ORANGE), PHASE C - BLUE, NEUTRAL - WHITE, EQUIPMENT
GROUNDING CONDUCTOR - GREEN.
F. MAINTAIN CONSISTENT PHASING OF THE ELECTRICAL
INSTALLATION THROUGHOUT THE POWER DISTRIBUTION
SYSTEM.
5. WIRE CONNECTIONS AND DEVICES
A. PROVIDE 600 VOLT TWIST-ON, INSULATED, CONNECTORS
PROPERLY SIZED AND RESISTANT TO VIBRATION FOR NO. 14
THROUGH NO. 10 GAUGE CONDUCTORS.
B. USE TERMINAL CONNECTORS WITH LUGS ON CONDUCTORS
LARGER THAN NO. 10 GAUGE. PROVIDE A BOLTED CONNECTION
FOR EACH PARALLEL CONDUCTOR.
C. 600 VOLT VINYL TAPE: SCOTCH 88 PREMIUM. VINYL ELECTRICAL
TAPE, 8.5 MIL THICKNESS. INSULATE CONNECTIONS MADE WITH
NON-INSULATED CONNECTORS WITH A MINIMUM OF THREE (3)
LAYERS OF PLASTIC TAPE. HALF-LAP EACH LAYER.
D. SPLICE 600 VOLT CONDUCTORS IN JUNCTION BOXES OR AT
OUTLETS ONLY.
6. OUTLET BOXES
A. PROVIDE NON-METALLIC BOXES IN ACCORDANCE WITH
ANSI/NEMA 0S 2.
B. PROVIDE SHEET METAL BOXES IN ACCORDANCE WITH
ANSI/NEMA OS 1.
C. PROVIDE FERALLOY METAL CAST BOXES , DEEP TYPE,
GASKETED COVER, THREADED HUBS. USE CAST BOXES FOR
DAMP AND OUTDOOR INSTALLATION.
D. PROVIDE ELECTRICAL BOXES IN THE LOCATIONS SHOWN ON
THE PLANS, AND AS REQUIRED FOR SPLICES, TAPS, WIRE
PULLING, EQUIPMENT CONNECTIONS, AND CODE COMPLIANCE.
COORDINATE LOCATIONS WITH EQUIPMENT OR JOB
CONDITIONS.
E. UNLESS OTHERWISE NOTED, LOCATE OUTLET BOXES AT THE
FOLLOWING ELEVATIONS ABOVE FINISHED FLOOR: TOGGLE
SWITCHES - 4'0", RECEPTACLES - 1'6", THERMOSTATS IN OFFICE
AREAS - 4'0", TELEPHONE OUTLETS - 1'6", CIRCUIT PROTECTIVE
DEVICES - 6'6" TO TOP OF ENCLOSURE.
F. COORDINATE MOUNTING HEIGHTS AND LOCATIONS OF OUTLETS
MOUNTED ABOVE COUNTERS, BENCHES AND BACKSPLASHES.
G. PROVIDE RECESSED OUTLET BOXES IN FINISHED AREAS;
SECURE BOXES TO INTERIOR WALL AND PARTITION STUDS.
H. ALIGN WALL-MOUNTED OUTLET BOXES FOR SWITCHES,
THERMOSTATS AND SIMILAR DEVICES.
7. DEVICE, PULL AND JUNCTION BOXES
A. DEVICE, PULL AND JUNCTION BOXES OVER CEILINGS SHALL BE
OF CODE GAUGE GALVANIZED STEEL WITH SHEET STEEL
COVERS. EXPOSED WALL DEVICE, PULL AND JUNCTION BOXES
SHALL BE CAST. DEVICE AND PULL BOXES IN FLOORS SHALL BE
OF GALVANIZED MALLEABLE CAST IRON, WITH GASKET COVERS.
EXPOSED DEVICE, PULL OR JUNCTION BOXES INSTALLED
OUTDOORS, PER NEMA 250, SHALL BE WEATHERPROOF AND
SHALL BE PROVIDED WITH WATERTIGHT GASKET COVERS
FASTENED WITH STAINLESS STEEL SCREWS.
B. PROVIDE HINGE TYPE COVER FOR SHEET METAL BOXES OF 12"
IN ANY DIMENSION.
C. PROVIDE OVERLAPPING COVERS WITH FLUSH-HEAD COVER
RETAINING SCREWS FOR FLUSH MOUNTED BOXES.
D. PULL AND JUNCTION BOXES MUST BE ACCESSIBLE AND NOT
BURIED.
8. WIRING DEVICES
A. PROVIDE HP RATED SWITCHES FOR MOTOR CONTROL OR
DISCONNECT SERVICE WHEN CONTROLLING OR
DISCONNECTING MOTOR LOADS IN EXCESS OF 1/4 HP; 20 AMP
SWITCHES FOR LOADS EXCEEDING 10 AMPS.
B. PROVIDE ARCHITECTURAL GRADE ROTARY DIMMERS RATED
FOR 600 WATT MINIMUM WITH POSITIVE SHUT OFF AND
INTEGRAL RADIO FREQUENCY NOISE FILTERS.
C. PROVIDE 20 AMPERE, DUPLEX, NEMA 5-20R, SPECIFICATION
GRADE RECEPTACLES MINIMUM OR AS OTHERWISE INDICATED.
PROVIDE ISOLATED GROUNDING TYPE WHERE INDICATED.
D. PROVIDE DUPLEX TYPE GROUND FAULT CIRCUIT INTERRUPTING
RECEPTACLES WITH LED INDICATING LIGHT MEETING UL 943
CLASS A WHRE INDICATED ON DRAWINGS. DO NOT USE
FEED-THROUGH FEATURE. INSTALL GFCI DEVICE AT EACH
LOCATION.
E. PROVIDE WIRING DEVICE COLOR AS DIRECTED BY ARCHITECT
OR WHITE ON LIGHT COLORED FINISHES, BROWN ON DARK
COLORED OR WOOD FINISHES. WIRING DEVICES ON
EMERGENCY, CRITICAL OR LIFE SAFETY SYSTEMS SHALL BE
RED.
F. PROVIDE HOSPITAL GRADE DEVICES IN ALL PATIENT CARE
AREAS.
G. COVER PLATES SHALL BE SPECIFICATION GRADE, HIGH IMPACT
NYLON. COVER PLATE COLOR SHALL MATCH WIRING DEVICE.
H. PROVIDE A SINGLE COVERPLATE FOR GANGED SWITCHES
INSTALLED AT ONE LOCATION.
I. PROVIDE WIRING DEVICES MANUFACTURED BY A SINGLE
MANUFACTURER; HUBBELL, EAGLE, OR ARROW-HART.
9. OVER CURRENT PROTECTIVE DEVICES
A. PROVIDE BOLT-ON, THERMAL MAGNETIC MOLDED CASE CIRCUIT
BREAKERS WITH THE NUMBER OF POLES AND THE AMPERE
RATING AS INDICATED ON THE PLANS; CAPABLE OF
INTERRUPTING THE SYMMETRICAL FAULT CURRENT AVAILABLE
TO THEM; MANUFACTURED BY CUTLER HAMMER, GENERAL
ELECTRIC, OR SQUARE D.
B. DO NOT USED SERIES RATING CIRCUIT BREAKERS.
10.SUPPORTING DEVICES
A. SECURELY FASTEN AND SUPPORT EQUIPMENT, CONDUITS AND
RACEWAYS TO THE BUILDING STRUCTURE.
B. CONTINUOUS SLOTTED CHANNEL BY UNISTRUT SIZED AS
REQUIRED FOR LOADS IMPOSED.
C. PROVIDE CONTINUOUSLY THREADED GALVANIZED STEEL
HANGER RODS SIZES REQUIRED ARE FOR LOADS IMPOSED.
D. PROVIDE TWO-HOLE PIPE STRAPS EQUAL TO P2558 SERIES,
GALVANIZED STEEL.
E. PROVIDE BEAM CLAMPS EQUAL TO P2867 SERIES, FOR ALL
APPLICATIONS.
F. PROVIDE RISER CLAMPS EQUAL TO P3130 SERIES.
G. PROVIDE O.Z./GEDNEY TYPE S CABLE SUPPORTS.
H. SUSPEND HORIZONTAL RUNS OF CONDUITS AND RACEWAYS
FROM THE FLOOR AND ROOF CONSTRUCTION BY ROD HANGERS
SPACED AS REQUIRED FOR LOADS IMPOSED BUT NOT MORE
THAN 10'-0" ON CENTERS.
I. FASTEN SINGLE RUNS OF CONDUIT TO THE STRUCTURE WITH
2-HOLE PIPE STRAPS AND BEAM CLAMPS OR HANG ON ROD
HANGERS. SUPPORT MULTIPLE RUNS OF CONDUIT AND
RACEWAYS FROM OR FROM TRAPEZE HANGERS CONSTRUCTED
OF ROD HANGERS AND CHANNELS.
J. INSTALL SUPPORTS TO PERMIT CONDUIT AND RACEWAY
EXPANSION JOINTS TO OPERATE.
K. DO NOT SUPPORT CONDUITS AND RACEWAYS FROM EQUIPMENT
THEY SERVE.
L. PROVIDE VIBRATION DAMPERS TO MINIMIZE TRANSMISSION OF
VIBRATIONS AND NOISES ON TRANSFORMERS AND MOVING
EQUIPMENT.
11.GROUNDING
A. GROUND ELECTRICAL WORK IN ACCORDANCE WITH NEC
ARTICLE 250 AND LOCAL CODES.
B. INSTALL A GREEN-COLORED, EQUIPMENT GROUNDING
CONDUCTOR IN RACEWAYS. SIZE CONDUCTORS IN
ACCORDANCE WITH NEC ARTICLE 250.
C. PROVIDE 3/4"X 10' COPPER CLAD STEEL GROUND RODS
MINIMUM.
D. PROVIDE GROUND CABLES OF STRANDED, BARE COPPER OF
98% CONDUCTIVITY.
E. PROVIDE BURNDY CORP., TYPE NE OR THOMAS & BETTS NO.
3951 SERIES GROUND FITTINGS.
F. INSTALL GROUND CABLES IN CONDUITS ABOVE GRADE OR
DIRECTLY BURIED IN EARTH TO A DEPTH OF NOT LESS THAN 12"
BELOW GRADE. PROVIDE SUFFICIENT MECHANICAL PROTECTION
FOR CABLE.
G. INSTALL GROUND CABLES CONTINUOUSLY BETWEEN
CONNECTIONS. ONLY SPLICE EXCEPT WHERE PERMITTED AND
INDICATED ON THE PLANS. PROVIDE PVC CONDUIT SLEEVES
WHERE GROUND CABLES PASS THROUGH FLOOR SLABS.
12.SURGE PROTECTION DEVICES
A. PROVIDE SURGE PROTECTION DEVICES (SPD) WITH L-L, L-N, L-G,
N-G MODES OF SURGE PROTECTION. PROVIDE A PARALLEL
CONNECTED SPD WITH 120KA PER MODE SURGE CAPACITY,
SINE WAVE TRACKING AND EMI/RFI FILTERING.
B. PROVIDE SPD UL 1449, UL 1283 LISTED AND DESIGNED,
MANUFACTURED AND TESTED IN ACCORDANCE WITH IEEE
C62.41, C62.45, NEMA LS-1, AND NEC 285.6.
C. PROVIDE UNIT WITH CLAMPING VOLTAGE REQUIRED FOR
INSTALLED SYSTEM VOLTAGE.
D. PROVIDE SURGE PROTECTION UTILIZING MATCHED MULTIPLE
METAL OXIDE VARISTORS (MOV) ONLY. PROVIDE SPD WITH 0.5
NANOSECOND RESPONSE TIME.
E. PROVIDE SPD OPERATING RANGE -40 TO 60 DEGREES C, 5-95%
RELATIVE HUMIDITY, NON-CONDENSING, AND 47-63 HERTZ
FREQUENCY.
F. PROVIDE SPD WITH INTERNAL FUSING RATED FOR 200,000 AMPS
INTERRUPTING CAPABILITY.
G. PROVIDE SPD WITH THE FOLLOWING OPTIONS: LED INDICATORS
FOR EACH PHASE; AUDIBLE ALARM WITH ALARM SILENCE; FORM
C, DRY CONTACT FOR REMOTE MONITORING; UNDER-VOLTAGE
DETECTION; PHASE LOSS MONITORING; POWER LOSS
MONITORING; INTEGRAL DISCONNECT SWITCH, AND TRANSIENT
COUNTERS.
H. PROVIDE SPD IN EXTERNAL MOUNT, NEMA 4, INDOOR/OUTDOOR
ENCLOSURE.
I. MOUNT SPD AS CLOSE AS POSSIBLE TO PROTECTED
EQUIPMENT AND MINIMIZE WIRE LENGTH. TWIST INPUT
CONDUCTORS TOGETHER TO REDUCE INDUCTANCE.
J. PROVIDE SPD WITH A 5 YEAR WARRANTY.
13. VARIABLE FREQUENCY CONTROLLERS
A. GENERAL REQUIREMENTS FOR VARIABLE-FREQUENCY MOTOR
CONTROLLERS (VFC) AND ACCESSORIES: UL LISTED AND
LABELED AS DEFINED IN NFPA 70 AND MARKED FOR INTENDED
LOCATION AND APPLICATION. COMPLY WITH NEMA ICS 7, NEMA
ICS 61800-2, AND UL 508A.
B. VFCS SHALL CONSIST OF POWER CONVERTER THAT EMPLOYS
PULSE-WIDTH-MODULATED INVERTER, FACTORY BUILT AND
TESTED IN AN ENCLOSURE, WITH INTEGRAL DISCONNECTING
MEANS AND OVERCURRENT AND OVERLOAD PROTECTION;
LISTED AND LABELED BY UL AS A COMPLETE UNIT; ARRANGED
TO PROVIDE SELF-PROTECTION, PROTECTION, AND
VARIABLE-SPEED CONTROL OF INDUCTION MOTORS BY
ADJUSTING OUTPUT VOLTAGE AND FREQUENCY.
C. PROVIDE MANUFACTURER WARRANTY TO REPAIR OR REPLACE
VFCS THAT FAIL IN MATERIALS OR WORKMANSHIP WITHIN ONE
YEAR FROM DATE OF SUBSTANTIAL COMPLETION.
D. PROVIDE UNITS SUITABLE FOR OPERATION OF NEMA MG 1,
DESIGN A AND DESIGN B MOTORS.
E. OUTPUT RATING: THREE-PHASE; 10 TO 60 HZ WITH VOLTAGE
PROPORTIONAL TO FREQUENCY THROUGHOUT VOLTAGE
RANGE; MAXIMUM VOLTAGE EQUALS INPUT VOLTAGE.
F. UNIT OPERATING REQUIREMENTS:
· MINIMUM EFFICIENCY: 96 PERCENT AT 60 HZ, FULL LOAD.
· MINIMUM SHORT-CIRCUIT CURRENT (WITHSTAND) RATING:
10 KA.
· AMBIENT TEMPERATURE RATING: 32-104 DEG F.
· HUMIDITY RATING: LESS THAN 95 PERCENT
(NONCONDENSING).
· ALTITUDE RATING: NOT EXCEEDING 3300 FEET.
· OVERLOAD CAPABILITY: 1.1 TIMES THE BASE LOAD
CURRENT FOR 60 SECONDS; MINIMUM OF 1.8 TIMES THE
BASE LOAD CURRENT FOR THREE SECONDS.
SPEED REGULATION: PLUS OR MINUS 5 PERCENT.
G. PROVIDE FACTORY INSTALLED INTEGRAL SURGE SUPPRESSION
COMPLYING WITH UL 1449 SPD, TYPE 2.
H. PROVIDE UNIT TRIPPING FOR UNDER- AND OVERVOLTAGE AND
OVERCURRENT, PHASE LOSS AND PHASE REVERSAL.
I. PROVIDE VFC MOTOR OVERLOAD PROTECTION,
MICROPROCESSOR-BASED THERMAL PROTECTION SYSTEM FOR
MONITORING VFCS AND MOTOR THERMAL CHARACTERISTICS.
J. PROVIDE UNIT CAPABLE OF STARTING INTO ROTATING LOADS
SPINNING IN EITHER DIRECTION AND RETURNING MOTOR TO SET
SPEED IN PROPER DIRECTION, WITHOUT CAUSING DAMAGE TO
DRIVE, MOTOR, OR LOAD.
K. INTEGRAL INPUT DISCONNECTING MEANS AND OCPD: UL 489,
INSTANTANEOUS-TRIP CIRCUIT BREAKER WITH PAD-LOCKABLE,
DOOR-MOUNTED HANDLE MECHANISM. RATED NOT LESS THAN
115 PERCENT OF NFPA 70 MOTOR FULL-LOAD CURRENT RATING
OR VFC INPUT CURRENT RATING, WHICHEVER IS LARGER.NC
ALARM CONTACT THAT OPERATES WHEN CIRCUIT BREAKER HAS
TRIPPED.
L. STATUS LIGHTS: DOOR-MOUNTED LED INDICATORS DISPLAYING
CONDITIONS OF POWER ON, RUN, FAULTS, AND OVERLOAD.
M. PANEL-MOUNTED OPERATOR STATION: MANUFACTURER'S
STANDARD FRONT-ACCESSIBLE, SEALED KEYPAD AND
PLAIN-ENGLISH-LANGUAGE DIGITAL DISPLAY; ALLOWS
COMPLETE PROGRAMMING, PROGRAM COPYING, OPERATING,
MONITORING, AND DIAGNOSTIC CAPABILITY.
N. PROVIDE ELECTRICAL INPUT SIGNAL INTERFACES, A MINIMUM
OF TWO PROGRAMMABLE ANALOG INPUTS: 4- TO 20-MA DC AND
SIX MULTIFUNCTION PROGRAMMABLE DIGITAL INPUTS.
O. PROVIDE UNIT WITH 5% INDUCTIVE OUTPUT FILTERING TO
PROTECT MOTOR.
P. PROVIDE VFC UNIT WITH NEMA TYPE 4X ENCLOSURE TO
COMPLY WITH ENVIRONMENTAL CONDITIONS AT INSTALLED
LOCATION.
Q. WALL-MOUNT CONTROLLERS, INSTALL WITH TOPS AT UNIFORM
HEIGHT AND WITH DISCONNECT OPERATING HANDLES NOT
HIGHER THAN 79 INCHES (2000 mm) ABOVE FINISHED FLOOR, UNLESS OTHERWISE INDICATED, AND BY BOLTING UNITS TO
WALL OR MOUNTING ON LIGHTWEIGHT STRUCTURAL-STEEL
CHANNELS BOLTED TO WALL.
R. INSTALL WIRING BETWEEN VFCS, REMOTE DEVICES, AND
CONTROL DEVICES.
S. INSPECT VFC, WIRING, COMPONENTS, CONNECTIONS, AND
EQUIPMENT INSTALLATION FOR DAMAGE.
T. TEST CONTINUITY AND INSULATION RESISTANCE FOR EACH VFC
ELEMENT, COMPONENT, CONNECTING MOTOR SUPPLY, FEEDER,
AND CONTROL CIRCUITS.
U. TEST EACH MOTOR FOR PROPER PHASE ROTATION.
V. CORRECT MALFUNCTIONING UNITS ON-SITE, WHERE POSSIBLE,
AND RETEST TO DEMONSTRATE COMPLIANCE; OTHERWISE,
REPLACE WITH NEW UNITS AND RETEST.
W. TEST AND ADJUST CONTROLS, REMOTE MONITORING, AND
SAFETIES. REPLACE DAMAGED OR MALFUNCTIONING CONTROLS
AND EQUIPMENT.
X. PROGRAM MICROPROCESSORS, SET FIELD-ADJUSTABLE
SWITCHES, RELAYS, TIMERS, OVERLOAD-RELAYS, AND SET
FIELD-ADJUSTABLE PRESSURE SWITCHES.
Y. TRAIN OWNER PERSONNEL TO ADJUST, OPERATE, PROGRAM,
AND MAINTAIN VFCS.
14.PRESSURE TRANSDUCER
A. PROVIDE WATER PRESSURE TRANSDUCER COMPATIBLE WITH
VARIABLE FREQUENCY CONTROLLER UTILIZING WATER HAMMER
RESISTANT PIEZO ELECTRIC TECHNOLOGY. TEMPERATURE
COMPENSATED. STAINLESS STEEL OR BRASS CONSTRUCTION.
THREADED PIPE CONNECTION. IP65 RATED.
B. PRESSURE TRANSDUCER SHALL BE 24 VOLT POWERED.
C. PRESSURE OUTPUT SIGNAL SHALL BE TWO-WIRE, 4-20 MA.
D. PRESSURE RATING SHALL BE 0-100PSI.
15.PUMP TIME CONTROLLERS
A. PROGRAMMABLE RESIDENTIAL GRADE CONTROLLER STATIONS
FOR AUTOMATIC CONTROL VALVES. INCLUDE SWITCH FOR
MANUAL OR AUTOMATIC OPERATION.
B. CONTROL ENCLOSURES: NEMA 250, TYPE 4, WEATHERPROOF,
LOCKABLE, WITH PROVISION FOR GROUNDING.
1. BODY MATERIAL: MOLDED PLASTIC.
2. MOUNTING: SURFACE TYPE FOR WALL OR ENCLOSURE.
C. MANUFACTURERS:
1. HUNTER.
2. RAINBIRD.
3. TORO.
4. ORBIT.
D. CONTROL TRANSFORMER: RECEPTACLE MOUNTABLE, 120VAC
PRIMARY, 24VAC SECONDARY WITH INTERNAL ELECTRONIC
SHORT CIRCUIT PROTECTION.
E. CONTROL OUTPUTS: PROVIDE PROVISIONS FOR CONTROL OF A
MINIMUM OF 12 INDEPENDENT CONTROL VALVES, MASTER
CONTROL VALVE, AND PUMP RUN.
F. PUMP STARTING: PROVIDE PROVISION FOR REMOTE PUMP
STARTING CONTACTS TO COORDINATE WITH A PUMP STARTER
OR VARIABLE FREQUENCY CONTROLLER.
G. TIMING DEVICE: ADJUSTABLE, 24-HOUR, 14-DAY CLOCK, WITH
AUTOMATIC OPERATIONS TO SKIP OPERATION ANY DAY IN
TIMER PERIOD, TO OPERATE EVERY OTHER DAY, OR TO
OPERATE TWO OR MORE TIMES DAILY.
H. MANUAL OR SEMIAUTOMATIC OPERATION: ALLOWS THIS MODE
WITHOUT DISTURBING PRESET AUTOMATIC OPERATION.
I. LITHIUM POLYMER RECHARGEABLE BATTERY AND TRICKLE
CHARGER: AUTOMATICALLY POWERS TIMING DEVICE DURING
POWER OUTAGES.
J. SURGE PROTECTION: METAL-OXIDE-VARISTOR TYPE ON EACH
OUTPUT, INPUT, AND PRIMARY POWER.
K. MOISTURE SENSOR: CONTROLLER WILL BE CAPABLE OF
DELAYING OPERATION BASED ON INSTALLATION OF AN
OPTIONAL MOISTURE SENSOR.
L. CONTROLLER SYSTEM AND COMPONENTS OF IRRIGATION
CONTROLS SHALL BE WARANTEED FOR PROPER OPERATION
AND FREE FROM DEFECTS FOR A PERIOD OF TWO(2) YEARS
FROM PROJECT COMPLETION.
M. EQUIPMENT MOUNTING:
N. INTERIOR: INSTALL CONTROLLER ON INTERIOR WALL. PLACE
AND SECURE ANCHORAGE DEVICES. USE SETTING DRAWINGS,
TEMPLATES, DIAGRAMS, INSTRUCTIONS, AND DIRECTIONS
FURNISHED WITH ITEMS TO BE EMBEDDED.
O. EXTERIOR WALL: INSTALL CONTROLLER IN A NEMA 4X
WEATHERPROOF ENCLOSURE WITH HINGED LOCKABLE COVER.
P. EXTERIOR PUMP STRUCTURE: INSTALL CONTROLLER IN A NEMA
4X WEATHERPROOF ENCLOSURE WITH HINGED LOCKABLE
COVER. MOUNT ENCLOSURE ON SLOTTED GALVANIZED STEEL
SUPPORTS BOLTED OR WELDED TO PUMP SYSTEM STRUCTURE.
LOCATE ENCLOSURE TO ENSURE PROPER ACCESS TO ALLOW
90-DEGREE COVER OPENING AND PROPER OPERATION OF
CONTROLLER.
Q. INSTALL CONTROL CABLE(S) IN CONDUIT.
R. CONNECT WIRING BETWEEN CONTROLLERS, PUMP CONTROLS,
AUTOMATIC CONTROL VALVES, ETC.
S. AFTER ELECTRICAL CIRCUITRY HAS BEEN ENERGIZED, OPERATE
CONTROLLERS AND AUTOMATIC CONTROL VALVES TO CONFIRM
PROPER SYSTEM OPERATION.
T. TEST AND ADJUST CONTROLS AND SAFETIES. REPLACE
DAMAGED AND MALFUNCTIONING CONTROLS AND EQUIPMENT.
U. VERIFY THAT CONTROLLERS ARE INSTALLED AND CONNECTED
IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.
V. VERIFY THAT ELECTRICAL WIRING INSTALLATION COMPLIES
WITH MANUFACTURER'S SUBMITTAL.
W. TRAIN OWNER'S MAINTENANCE PERSONNEL TO ADJUST,
OPERATE, AND MAINTAIN AUTOMATIC CONTROLLERS.
16. DISCONNECT SWITCHES
A. PROVIDE HEAVY DUTY; QUICK-MAKE, QUICK-BREAK, LOAD
INTERRUPTER ENCLOSED SWITCH WITH EXTERNALLY
OPERABLE HANDLE INTERLOCKED TO PREVENT OPENING
FRONT COVER WITH SWITCH IN ON POSITION. HANDLE
LOCKABLE IN ON AND OFF POSITION. PROVIDE CLASS RK FUSE
CLIPS ON FUSIBLE DISCONNECT SWITCHES.
B. UNLESS INDICATED OTHERWISE, PROVIDE GENERAL PURPOSE,
NEMA 1 FOR INDOOR LOCATIONS; AND WEATHERPROOF, NEMA
3R FOR OUTDOOR LOCATIONS; PROVIDE NEMA 4X IN
CORROSIVE LOCATIONS.
C. PROVIDE FUSES IN FUSED DISCONNECT SWITCHES.
D. PROVIDE DISCONNECT SWITCHES, WHERE REQUIRED BY CODE,
WHERE INDICATED ON DRAWINGS, AND WHERE REQUIRED BY
EQUIPMENT MANUFACTURER, IN A LOCATION CONVENIENT FOR
MAINTENANCE ON EACH SWITCH AND ADJACENT EQUIPMENT.
E. PROVIDE FUSED DISCONNECT SWITCHES WHEN REQUIRED TO
MAINTAIN EQUIPMENT MANUFACTURER'S WARRANTY.
F. WALL MOUNT SWITCHES, WHERE POSSIBLE, OR MOUNT ON
UNI-STRUT SUPPORTS.
ELECTRICAL SPECIFICATIONS
1. PROVIDE ALL ELECTRICAL INSTALLATIONS IN ACCORDANCE
WITH THE NATIONAL ELECTRICAL CODE AND ALL LOCAL
AMENDMENTS AND ORDINANCES.
2. ALL CIRCUITS SHALL BE IN CONDUIT.
3. ALL CIRCUITS ARE SHOWN SCHEMATICALLY. THE
CONTRACTOR WILL MAKE FINAL ROUTING DECISIONS.
4. UNLESS NOTED OTHERWISE, PROVIDE 2 #12, #12 GROUND, 3/4"
CONDUIT FOR 20 AMP SINGLE PHASE POWER CIRCUITS.
CIRCUIT RUNS LONGER THAN 100' WILL BE 2#10, #10 GROUND,
3/4" CONDUIT.
GENERAL NOTES
ALL MATERIAL AND LABOR COSTS REQUIRED FOR THE PURCHASE
AND INSTALLATION OF A VFD CONTROLLER AND SUPPORTING
EQUIPMENT AND/OR STRUCTURES TO AN EXISTING IRRIGATION
SYSTEM WILL BE PAID FOR BY FLOODPLAINS BY DESIGN GRANT 5
(AGREEMENT #. SEAFBD-2123-PICOPW-00024; TASK 5;
DELIVERABLE 9). PARTICIPATING PROJECT FARMS ARE
RESPONSIBLE FOR ANY NEEDED FENCING, SITE LIGHTING, AND
SECURITY IMPROVEMENTS. PARTICIPATING FARMS WILL BE
RESPONSIBLE FOR THE COSTS ASSOCIATED FOR AN ANNUAL
INSPECTION AND SERVICING OF THEIR VFD INSTALLATION FOR A
MINIMUM OF FIVE YEARS.
PROJECT NOTE
RText (RText)
Pierce County Agricultre Program Pierce County
9850 64TH STREET WEST
UNIVERSITY PLACE, WA 98467-1078
DATE APPROVEDBYREVISIONNO.
Know what's below.
before you dig.Call
R
DESIGNED BY:
DATE PLOTTED:
DRAWN BY:
CHECKED BY:
SURVEYED BY:
DATE SURVEYED:
N/A
May 20, 2026
100% SUBMITTAL
www.huitt-zollars.com
1700 7th Avenue, Suite 2075 Seattle, Washington 98101-1360
206.324.5500
J. ROBERTS
R. TAM
V. LY
N
SCALE (IN FEET)
0 2500 5000 10000
HORZ
CLEAR CREEK (ORTING VALLEY) WATERSHED
VFD ADDITION TO IRRIGATION SYSTEM
SIDHU FARM
VICINITY MAP
FARM NAME: SIDHU FARM
SITE ADDRESS 15306 96TH ST E
PUYALLUP, WA 98372
SITE TAX PARCEL: 0519061013
PIERCE COUNTY
CONTACT:
DEAN MCCLARY
(253) 798 6221 dean.mcclary@piercecountywa.gov
FARM OWNER
CONTACT:
KAMAL SIDHU
(253) 651 3755
05/20/2026
OE
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
W W
M S
B B
EXISTING UTILITY POLE
WITH TRANSFORMER
EXISTING DIRT ROAD
PORTABLE PUMP
AREA
EXISTING UTILITY POLE
OE
OE
OE
OE
OE
OE
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
O E
W
W
W
W
W
W
W W
M S
B B
6" Ø PERMANENT PIPE
CONNECTION AND
VALVE TO FIELD
EXISTING BLOCK
RETAINING WALLS
EDGE OF
EXISTING
DIRT ROAD
EXISTING 480/277V 3Ø, 4W, 100A
SERVICE DISCONNECT SWITCH
ON WOOD STRUCTURE
APPROXIMATE EDGE
OF PUYALLUP PRIVER
EXISTING 1Ø TRANSFORMER
AND RECEPTACLE
PORTABLE PUMP AREA
EXISTING UTILITY METER
ON WOOD STRUCTURE
EXISTING 250A NEMA 3R
BRANCH PANELBOARD ON
WOOD STRUCTURE
EXISTING 8' WOOD
ELECTRICAL
EQUIPMENT
SUPPORT
STRUCTURE
EXISTING UTILITY POLE
WITH OVERHEAD UTILITY
SERVICE DROP
PIPE CONNECTION FOR
OTHER SYSTEM SHOWN
FOR REFERENCE ONLY
EXISTING UTILITY POLE WITH
3-37KVA TRANSFORMERS
EXISTING 200A NEMA 3R
COMBINATION PUMP STARTER
AND DISCONNECT SWITCH
WITH PIN AND SLEEVE PUMP
RECEPTACLE
EXISTING SP VFC AND PIN
& SLEEVE RECEPTACLE
EXISTING VFC 30A
DISCONNECT SWITCH
RText (RText)
Pierce County Agricultre Program Pierce County
9850 64TH STREET WEST
UNIVERSITY PLACE, WA 98467-1078
DATE APPROVEDBYREVISIONNO.
Know what's below.
before you dig.Call
R
DESIGNED BY:
DATE PLOTTED:
DRAWN BY:
CHECKED BY:
SURVEYED BY:
DATE SURVEYED:
N/A
May 20, 2026
100% SUBMITTAL
www.huitt-zollars.com
1700 7th Avenue, Suite 2075 Seattle, Washington 98101-1360
206.324.5500
J. ROBERTS
R. TAM
V. LY
CLEAR CREEK (ORTING VALLEY) WATERSHED
VFD ADDITION TO IRRIGATION SYSTEM
SIDHU FARM
SCALE (IN FEET)
0 10 20 40
HORZ
NNTS
OVERALL SITE PLAN
ELECTRICAL PLAN
N
NEW VFC EXTEND 3#4, #8G, 1"C
TO EXISTING PUMP
DISCONNECT/STARTER
NEW PRESSURE TRANSDUCER
MOUNTED TO EXISTING PIPING.
COORDINATE LOCATION WITH PIPING
AND MANUFACTURER REQUIRMENTS
EXTEND 3#12.#12G, 1/2"C TO VFC
EXISTING PUMP SKID
ELECTRICAL PLAN
WATER
INLET
W
AT
ER
O
U
TL
ET
EXISTING 50 HP WATER
PUMP AND MOTOR
EXISTING PORTABLE
PUMP SUPPORT BASE
EXISTING OVERHEAD
ELECTRICAL SERVICE TO POLE
MOUNTED TRANSFORMERS
EXISTING
METER BASE
AND UTILITY
METER
EX 100 A
480Y/277V 3Ø, 4W, FUSED
DISC SW
EX PANEL
250A MLO,
480Y/277V, 3P, 4W
EXIST
CIRCUIT
EXISTING 120V
RECEPTACLE
EXIST
CIRCUIT
EXIST
POLE
EX PUMP
CONTROL
STARTER/
DISC SW
EXIST
CIRCUIT
EXIST
POLE
EXISTING OVERHEAD
ELECTRICAL SERVICE TO POLE
MOUNTED TRANSFORMERS
EX 30A
DISCONNECT
SWITCH
ELECTRICAL DIAGRAM
EAST ELEVATION WEST ELEVATION
NEW
VFC
NEW PUMP
TIMER
CONTROLLER
EXTEND 3#1, #6G, 1-1/2"C TO
EXISTING PUMP RECEPTACLE
VIA STARTER/DISCONNECT
SWITCH ENCLOSURE
2#12,#12G TO PUMP
RUN CONTACTS
EXTEND NEW CONTROLLER POWER
CIRCUIT AND POWER SUPPLY TO GFCI
RECEPTACLE IN ENCLOSURE
MOUNT NEW VFC AND PUMP TIMER
CONTROLLER IN 24"WX36"HX12"D, NEMA 4
STEEL ENCLOSURE WITH HINGED LOCKING
DOOR.
PROVIDE 120VAC GFCI RECEPTACLE IN
CONTROLLER ENCLOSURE. EXTEND #12,#12G
TO EXISTING RECEPTACLE CIRCUIT.
EXISTING 30A DISCONNECT
SWITCH,VFC, AND RECEPTACLE
FOR A PUMP NOT IN THE SCOPE
OF THIS PROJECT
EXISTING WP
RECEPTACLE
EXISTING 1Ø
TRANSFORMER
EXISTING PUMP RECEPTACLE
EXISTING 50 HP PUMP POWER
CORD AND PIN AND SLEEVE
PLUG
PROVIDE 50' OF THREE
CONDUCTOR TYPE SO CORD
AND PLUG FOR PRESSURE
TRANSDUCER CONTROL
CONDUCTORS TO VFC
EXISTING PUMP RECEPTACLE
NEW PRESSURE TRANSDUCER RECEPTACLE.
EXTEND 3#12,#12G TO NEW VFC
P M
05/20/2026