Attachment_8_-_PC_VFD_-_LOCAL_COLOR_IFC_052026.pdf
PDF 2 MB Posted
- Solicitation number
- 2026-RFP-175
- Issued by
- Pierce County, Tacoma City, Washington
About this file
This is an electrical design specification and site plan document for Pierce County, Washington's Puyallup Watershed Irrigation Efficiencies Project, specifically detailing Variable Frequency Drive (VFD) controller installations at irrigation system sites. The project involves adding VFD controllers and supporting electrical equipment to existing irrigation systems at participating farms within the Clear Creek (Orting Valley) Watershed. The document provides comprehensive electrical specifications for the Local Color Farm site located at 10806 159th Avenue E, Puyallup, WA 98374 (Tax Parcel 0519067701). The electrical work includes installation of a new VFC unit, pump timer controller, pressure transducer, conduit routing, wiring, disconnect switches, and ancillary equipment to modernize existing 5 HP and 30 HP water pump systems. All materials and labor costs for the VFD controller installation and supporting equipment are covered by the Floodplains by Design Grant 5 (Agreement #SEAFBD-2123-PICOPW-00024, Task 5, Deliverable 9) and were prepared for a May 20, 2026 submittal date.
The specifications require all work to comply with the National Electrical Code, local codes, and applicable ANSI and UL standards. Equipment must be manufactured by specified vendors including Cutler Hammer, General Electric, or Square D for circuit breakers; Hubbell, Eagle, or Arrow-Hart for wiring devices; and Hunter, Rainbird, Toro, or Orbit for pump controllers. Participating farms are responsible for costs associated with annual inspection and servicing of VFD installations for a minimum of five years, as well as any needed fencing, site lighting, and security improvements. The VFC units require a one-year manufacturer warranty for repair or replacement, while irrigation control systems require a two-year warranty from project completion. All electrical components must bear UL labels, and specific technical requirements are established for surge protection devices, variable frequency controllers (with 96 percent minimum efficiency), pressure transducers, and control enclosures rated NEMA 4 or 4X depending on location and environmental conditions.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SITE
Alderton
96th St EW A 162
McMillin
R iverside D r E
WA 410
M cC utheon R d E
Pu ya llu p
Ri ve r
Puyallup
Bonney Lake
M cC ut he on R d E
Rhodes Lake Rd E
1. GENERAL ELECTRICAL REQUIREMENTS
A. PROVIDE ELECTRICAL WORK IN ACCORDANCE WITH THE
NATIONAL ELECTRICAL CODE AND ANY LOCAL, STATE AND
NATIONAL CODES, ORDINANCES AND REGULATIONS THAT HAVE
JURISDICTION OR AUTHORITY OVER THE WORK. IF THE
STANDARDS AND CODES CONFLICT WITH EACH OTHER, APPLY
THE MOST STRINGENT.
B. SECURE AND PAY FOR PERMITS, LICENSES AND INSPECTIONS
AS REQUIRED BY LAW FOR THE COMPLETION OF THE WORK.
C. MAINTAIN THE WATERPROOF INTEGRITY OF CONDUIT
PENETRATIONS THROUGH THE ROOF, EXTERIOR WALLS AND
FLOORS.
D. IDENTIFY ELECTRICAL EQUIPMENT IN ACCORDANCE WITH THE
NEC, THE LOCAL AUTHORITIES, AND AS SPECIFIED. USE
LAMINATED THREE-PLY ENGRAVED PLASTIC NAMEPLATES WITH
BLACK SURFACE AND WHITE INTERIOR CORE, AT LEAST 1/16"
THICK ON THE COVER OF EACH BRANCH CIRCUIT PANEL.
E. PROVIDE ALL ELECTRICAL DEVICES AND COMPONENTS LISTED
AND APPROVED BY THE UNDERWRITERS LABORATORIES AND
BEAR THE UL LABEL.
2. ELECTRICAL DEMOLITION
A. DEMOLITION DRAWINGS ARE BASED ON FIELD OBSERVATION
AND EXISTING RECORD DOCUMENTS. VERIFY MEASUREMENTS
AND CIRCUITING ARE AS SHOWN ON DRAWINGS. VERIFY THAT
DEMOLISHED WIRING AND EQUIPMENT SERVE ONLY REMOVED
FACILITIES. REPORT DISCREPANCIES BEFORE DEMOLITION TO
THE OWNER.
B. MAINTAIN EXISTING REMAINING SYSTEMS IN SERVICE TO THE
FULLEST EXTENT POSSIBLE. PROVIDE TEMPORARY WIRING AND
CONNECTIONS TO MAINTAIN EXISTING SYSTEM IN SERVICE
DURING CONSTRUCTION AS REQUIRED BY OWNER.
COORDINATE OUTAGES WITH OWNER AND UTILITY COMPANY.
C. REMOVE ALL UNUSED CONDUIT. REMOVE ALL DISCONNECTED
CIRCUIT CONDUCTORS FROM SOURCE TO DEVICE.
D. REPAIR ADJACENT CONSTRUCTION AND FINISHES EXPOSED OR
DAMAGED DURING DEMOLITION AND EXTENSION WORK. FINISH
RESTORATION SHALL BE IN KIND.
E. MAINTAIN ACCESS TO EXISTING, REMAINING ELECTRICAL
INSTALLATIONS.
F. CLEAN AND REPAIR EXISTING MATERIALS AND EQUIPMENT
WHICH REMAIN OR ARE TO BE REUSED. REPAIR OR REPLACE
IN-KIND EQUIPMENT DAMAGED DURING DEMOLITION.
3. CONDUITS
A. PROVIDE RIGID GALVANIZED STEEL CONDUIT MANUFACTURED IN
ACCORDANCE WITH ANSI C80.1 STANDARDS, AND U.L. 6 LISTED.
PROVIDE THREADED FITTINGS IN ACCORDANCE WITH
ANSI/NEMA FB1. RIGID GALVANIZED STEEL CONDUIT MAY BE
USED IN ALL LOCATIONS. PROVIDE PVC COATED RIGID
GALVANIZED STEEL CONDUIT IN CORROSIVE ENVIRONMENTS OR
WHERE IN CONTACT WITH CONCRETE.
B. PROVIDE INTERMEDIATE METALLIC CONDUIT MANUFACTURED IN
ACCORDANCE WITH ANSI C80.6 STANDARDS, AND U.L. 1242
LISTED. PROVIDE THREADED FITTINGS IN ACCORDANCE WITH
ANSI/NEMA FB1. INTERMEDIATE METALLIC CONDUIT MAY BE
USED IN ALL NON-CORROSIVE LOCATIONS.
C. PROVIDE ELECTRICAL METALLIC TUBING MANUFACTURED IN
ACCORDANCE WITH ANSI C80.3 STANDARDS, AND U.L. 797
LISTED. PROVIDE FITTINGS OF STEEL, DIE CAST ZINC, OR
MALLEABLE IRON, COMPRESSION TYPE WITH INSULATED
THROAT IN ACCORDANCE WITH ANSI C80.3 STANDARDS.
ELECTRICAL METALLIC TUBING MAY BE USED IN
NON-HAZARDOUS, NON-CORROSIVE LOCATIONS NOT SUBJECT
TO SEVERE PHYSICAL DAMAGE.
D. PROVIDE FLEXIBLE METAL CONDUIT MANUFACTURED IN
ACCORDANCE WITH U.L. PROVIDE LIQUID TIGHT CONDUIT WITH
EXTRUDED, POLYVINYL JACKET OVER THE FLEXIBLE METAL.
PROVIDE CADMIUM-PLATED FITTINGS WITH MALLEABLE IRON
BODY AND NUT; CADMIUM STEEL FERRULE; INSULATED THROAT;
INTEGRALLY-CAST, EXTERNAL GROUND LUGS IN ACCORDANCE
WITH NEMA FB1. FLEXIBLE METALLIC CONDUIT MAY BE USED
FOR ALL CONNECTIONS TO EQUIPMENT IN ALL INTERIOR, DRY,
NON-CORROSIVE LOCATIONS. LIQUID TIGHT FLEXIBLE METALLIC
CONDUIT MAY BE USED FOR ALL CONNECTIONS TO EQUIPMENT
NOT SUBJECT TO EXCESSIVE TEMPERATURES. CONDUITS SHALL
BE INSTALLED IN NON-HAZARDOUS LOCATIONS NOT SUBJECT
TO PHYSICAL DAMAGE. LENGTH SHALL BE 6'-0" MAXIMUM.
E. PROVIDE SCHEDULE 40 AND 80 PVC RIGID NONMETALLIC
CONDUIT IN ACCORDANCE WITH NEMA TC-2 AND U.L. 651.
PROVIDE SOLVENT-WELDED, SLIP-ON JOINTS IN ACCORDANCE
WITH NEMA TC3 AND U.L. 514B. RIGID NONMETALLIC CONDUIT
MAY BE USED IN NON-HAZARDOUS LOCATIONS AND INSTALLED
EITHER UNDERGROUND OR ENCASED IN CONCRETE.
F. PROVIDE GROUNDING BUSHINGS COMPLYING WITH W-W-C-581D,
UL STANDARDS 514B AND 467.
G. PROVIDE CADMIUM-PLATED, MALLEABLE IRON HUBS WITH
TAPERED THREADS, A NEOPRENE "O" RING AND AN INSULATED
THROAT.
H. SEAL CONDUIT PENETRATIONS THROUGH U.L. CLASSIFIED
SMOKE AND FIRE WALLS WITH SEALANT THAT MAINTAINS THE
WALLS FIRE RATING.
I. INSTALL PULL STRINGS IN EMPTY CONDUITS. USE
POLYPROPYLENE PLASTIC LINE WITH NOT LESS THAN 200 LB.
TENSILE STRENGTH. LEAVE AT LEAST FIVE FEET OF EXCESS
LINE AT EACH END.
J. ROUTE CONDUITS PARALLEL TO BUILDING LINES. CONCEAL
CONDUITS BELOW GRADE, WITHIN WALLS, OR ABOVE CEILINGS
IN FINISHED AREAS.
K. ROUTE CONDUIT THROUGH ROOF OPENINGS FOR PIPING AND
DUCTWORK WHERE POSSIBLE. OTHERWISE, ROUTE CONDUIT
THROUGH THE ROOF WITH PITCH POCKET. CONDUIT SHALL NOT
PENETRATE DUCTWORK.
4. 600 VOLT WIRES AND CABLES
A. PROVIDE COPPER CONDUCTORS BEARING THE U.L. LABEL.
PROVIDE #12 AWG MINIMUM SIZE CONDUCTORS. CONDUCTORS
#8 OR LARGER SHALL BE STRANDED. CONDUCTORS SHALL BE
INSULATED WITH THERMOPLASTIC INSULATION RATED AT 600
VOLTS AND INSULATED WITH TYPE THHN/THWN OR XHHW
INSULATION.
B. METAL CLAD, TYPE AC OR MC CABLE SYSTEMS SHALL NOT BE
USED.
C. SPLICE ONLY IN JUNCTION OR OUTLET BOXES. PULL ALL
CONDUCTORS INTO A RACEWAY AT THE SAME TIME AND USE
U.L. LISTED, WIRE PULLING LUBRICANT FOR PULLING NO. 4 AWG
AND LARGER WIRE.
D. NEVER SPLICE TOGETHER CONDUCTORS OF DIFFERENT
COLORS.
E. IN EXISTING FACILITIES, MATCH EXISTING CONDUCTOR COLOR
CODING SCHEME. OTHERWISE, USE THE FOLLOWING COLOR
CODE: FOR 277/480V, 3-PHASE WIRING: PHASE A - BROWN,
PHASE B - PURPLE, PHASE C - YELLOW, NEUTRAL - GRAY,
EQUIPMENT GROUNDING CONDUCTOR - GREEN. USE THE
FOLLOWING COLOR CODE FOR 120/208V OR 240V, 3-PHASE
WIRING: PHASE A - BLACK, PHASE B - RED (ON 240/120V, 3Ø, 4W
SYSTEMS THE HIGH VOLTAGE LEG WILL BE PHASE B AND WILL
BE ORANGE), PHASE C - BLUE, NEUTRAL - WHITE, EQUIPMENT
GROUNDING CONDUCTOR - GREEN.
F. MAINTAIN CONSISTENT PHASING OF THE ELECTRICAL
INSTALLATION THROUGHOUT THE POWER DISTRIBUTION
SYSTEM.
5. WIRE CONNECTIONS AND DEVICES
A. PROVIDE 600 VOLT TWIST-ON, INSULATED, CONNECTORS
PROPERLY SIZED AND RESISTANT TO VIBRATION FOR NO. 14
THROUGH NO. 10 GAUGE CONDUCTORS.
B. USE TERMINAL CONNECTORS WITH LUGS ON CONDUCTORS
LARGER THAN NO. 10 GAUGE. PROVIDE A BOLTED CONNECTION
FOR EACH PARALLEL CONDUCTOR.
C. 600 VOLT VINYL TAPE: SCOTCH 88 PREMIUM. VINYL ELECTRICAL
TAPE, 8.5 MIL THICKNESS. INSULATE CONNECTIONS MADE WITH
NON-INSULATED CONNECTORS WITH A MINIMUM OF THREE (3)
LAYERS OF PLASTIC TAPE. HALF-LAP EACH LAYER.
D. SPLICE 600 VOLT CONDUCTORS IN JUNCTION BOXES OR AT
OUTLETS ONLY.
6. OUTLET BOXES
A. PROVIDE NON-METALLIC BOXES IN ACCORDANCE WITH
ANSI/NEMA 0S 2.
B. PROVIDE SHEET METAL BOXES IN ACCORDANCE WITH
ANSI/NEMA OS 1.
C. PROVIDE FERALLOY METAL CAST BOXES , DEEP TYPE,
GASKETED COVER, THREADED HUBS. USE CAST BOXES FOR
DAMP AND OUTDOOR INSTALLATION.
D. PROVIDE ELECTRICAL BOXES IN THE LOCATIONS SHOWN ON
THE PLANS, AND AS REQUIRED FOR SPLICES, TAPS, WIRE
PULLING, EQUIPMENT CONNECTIONS, AND CODE COMPLIANCE.
COORDINATE LOCATIONS WITH EQUIPMENT OR JOB
CONDITIONS.
E. UNLESS OTHERWISE NOTED, LOCATE OUTLET BOXES AT THE
FOLLOWING ELEVATIONS ABOVE FINISHED FLOOR: TOGGLE
SWITCHES - 4'0", RECEPTACLES - 1'6", THERMOSTATS IN OFFICE
AREAS - 4'0", TELEPHONE OUTLETS - 1'6", CIRCUIT PROTECTIVE
DEVICES - 6'6" TO TOP OF ENCLOSURE.
F. COORDINATE MOUNTING HEIGHTS AND LOCATIONS OF OUTLETS
MOUNTED ABOVE COUNTERS, BENCHES AND BACKSPLASHES.
G. PROVIDE RECESSED OUTLET BOXES IN FINISHED AREAS;
SECURE BOXES TO INTERIOR WALL AND PARTITION STUDS.
H. ALIGN WALL-MOUNTED OUTLET BOXES FOR SWITCHES,
THERMOSTATS AND SIMILAR DEVICES.
7. DEVICE, PULL AND JUNCTION BOXES
A. DEVICE, PULL AND JUNCTION BOXES OVER CEILINGS SHALL BE
OF CODE GAUGE GALVANIZED STEEL WITH SHEET STEEL
COVERS. EXPOSED WALL DEVICE, PULL AND JUNCTION BOXES
SHALL BE CAST. DEVICE AND PULL BOXES IN FLOORS SHALL BE
OF GALVANIZED MALLEABLE CAST IRON, WITH GASKET COVERS.
EXPOSED DEVICE, PULL OR JUNCTION BOXES INSTALLED
OUTDOORS, PER NEMA 250, SHALL BE WEATHERPROOF AND
SHALL BE PROVIDED WITH WATERTIGHT GASKET COVERS
FASTENED WITH STAINLESS STEEL SCREWS.
B. PROVIDE HINGE TYPE COVER FOR SHEET METAL BOXES OF 12"
IN ANY DIMENSION.
C. PROVIDE OVERLAPPING COVERS WITH FLUSH-HEAD COVER
RETAINING SCREWS FOR FLUSH MOUNTED BOXES.
D. PULL AND JUNCTION BOXES MUST BE ACCESSIBLE AND NOT
BURIED.
8. WIRING DEVICES
A. PROVIDE HP RATED SWITCHES FOR MOTOR CONTROL OR
DISCONNECT SERVICE WHEN CONTROLLING OR
DISCONNECTING MOTOR LOADS IN EXCESS OF 1/4 HP; 20 AMP
SWITCHES FOR LOADS EXCEEDING 10 AMPS.
B. PROVIDE ARCHITECTURAL GRADE ROTARY DIMMERS RATED
FOR 600 WATT MINIMUM WITH POSITIVE SHUT OFF AND
INTEGRAL RADIO FREQUENCY NOISE FILTERS.
C. PROVIDE 20 AMPERE, DUPLEX, NEMA 5-20R, SPECIFICATION
GRADE RECEPTACLES MINIMUM OR AS OTHERWISE INDICATED.
PROVIDE ISOLATED GROUNDING TYPE WHERE INDICATED.
D. PROVIDE DUPLEX TYPE GROUND FAULT CIRCUIT INTERRUPTING
RECEPTACLES WITH LED INDICATING LIGHT MEETING UL 943
CLASS A WHRE INDICATED ON DRAWINGS. DO NOT USE
FEED-THROUGH FEATURE. INSTALL GFCI DEVICE AT EACH
LOCATION.
E. PROVIDE WIRING DEVICE COLOR AS DIRECTED BY ARCHITECT
OR WHITE ON LIGHT COLORED FINISHES, BROWN ON DARK
COLORED OR WOOD FINISHES. WIRING DEVICES ON
EMERGENCY, CRITICAL OR LIFE SAFETY SYSTEMS SHALL BE
RED.
F. PROVIDE HOSPITAL GRADE DEVICES IN ALL PATIENT CARE
AREAS.
G. COVER PLATES SHALL BE SPECIFICATION GRADE, HIGH IMPACT
NYLON. COVER PLATE COLOR SHALL MATCH WIRING DEVICE.
H. PROVIDE A SINGLE COVERPLATE FOR GANGED SWITCHES
INSTALLED AT ONE LOCATION.
I. PROVIDE WIRING DEVICES MANUFACTURED BY A SINGLE
MANUFACTURER; HUBBELL, EAGLE, OR ARROW-HART.
9. OVER CURRENT PROTECTIVE DEVICES
A. PROVIDE BOLT-ON, THERMAL MAGNETIC MOLDED CASE CIRCUIT
BREAKERS WITH THE NUMBER OF POLES AND THE AMPERE
RATING AS INDICATED ON THE PLANS; CAPABLE OF
INTERRUPTING THE SYMMETRICAL FAULT CURRENT AVAILABLE
TO THEM; MANUFACTURED BY CUTLER HAMMER, GENERAL
ELECTRIC, OR SQUARE D.
B. DO NOT USED SERIES RATING CIRCUIT BREAKERS.
10.SUPPORTING DEVICES
A. SECURELY FASTEN AND SUPPORT EQUIPMENT, CONDUITS AND
RACEWAYS TO THE BUILDING STRUCTURE.
B. CONTINUOUS SLOTTED CHANNEL BY UNISTRUT SIZED AS
REQUIRED FOR LOADS IMPOSED.
C. PROVIDE CONTINUOUSLY THREADED GALVANIZED STEEL
HANGER RODS SIZES REQUIRED ARE FOR LOADS IMPOSED.
D. PROVIDE TWO-HOLE PIPE STRAPS EQUAL TO P2558 SERIES,
GALVANIZED STEEL.
E. PROVIDE BEAM CLAMPS EQUAL TO P2867 SERIES, FOR ALL
APPLICATIONS.
F. PROVIDE RISER CLAMPS EQUAL TO P3130 SERIES.
G. PROVIDE O.Z./GEDNEY TYPE S CABLE SUPPORTS.
H. SUSPEND HORIZONTAL RUNS OF CONDUITS AND RACEWAYS
FROM THE FLOOR AND ROOF CONSTRUCTION BY ROD HANGERS
SPACED AS REQUIRED FOR LOADS IMPOSED BUT NOT MORE
THAN 10'-0" ON CENTERS.
I. FASTEN SINGLE RUNS OF CONDUIT TO THE STRUCTURE WITH
2-HOLE PIPE STRAPS AND BEAM CLAMPS OR HANG ON ROD
HANGERS. SUPPORT MULTIPLE RUNS OF CONDUIT AND
RACEWAYS FROM OR FROM TRAPEZE HANGERS CONSTRUCTED
OF ROD HANGERS AND CHANNELS.
J. INSTALL SUPPORTS TO PERMIT CONDUIT AND RACEWAY
EXPANSION JOINTS TO OPERATE.
K. DO NOT SUPPORT CONDUITS AND RACEWAYS FROM EQUIPMENT
THEY SERVE.
L. PROVIDE VIBRATION DAMPERS TO MINIMIZE TRANSMISSION OF
VIBRATIONS AND NOISES ON TRANSFORMERS AND MOVING
EQUIPMENT.
11.GROUNDING
A. GROUND ELECTRICAL WORK IN ACCORDANCE WITH NEC
ARTICLE 250 AND LOCAL CODES.
B. INSTALL A GREEN-COLORED, EQUIPMENT GROUNDING
CONDUCTOR IN RACEWAYS. SIZE CONDUCTORS IN
ACCORDANCE WITH NEC ARTICLE 250.
C. PROVIDE 3/4"X 10' COPPER CLAD STEEL GROUND RODS
MINIMUM.
D. PROVIDE GROUND CABLES OF STRANDED, BARE COPPER OF
98% CONDUCTIVITY.
E. PROVIDE BURNDY CORP., TYPE NE OR THOMAS & BETTS NO.
3951 SERIES GROUND FITTINGS.
F. INSTALL GROUND CABLES IN CONDUITS ABOVE GRADE OR
DIRECTLY BURIED IN EARTH TO A DEPTH OF NOT LESS THAN 12"
BELOW GRADE. PROVIDE SUFFICIENT MECHANICAL PROTECTION
FOR CABLE.
G. INSTALL GROUND CABLES CONTINUOUSLY BETWEEN
CONNECTIONS. ONLY SPLICE EXCEPT WHERE PERMITTED AND
INDICATED ON THE PLANS. PROVIDE PVC CONDUIT SLEEVES
WHERE GROUND CABLES PASS THROUGH FLOOR SLABS.
12.SURGE PROTECTION DEVICES
A. PROVIDE SURGE PROTECTION DEVICES (SPD) WITH L-L, L-N, L-G,
N-G MODES OF SURGE PROTECTION. PROVIDE A PARALLEL
CONNECTED SPD WITH 120KA PER MODE SURGE CAPACITY,
SINE WAVE TRACKING AND EMI/RFI FILTERING.
B. PROVIDE SPD UL 1449, UL 1283 LISTED AND DESIGNED,
MANUFACTURED AND TESTED IN ACCORDANCE WITH IEEE
C62.41, C62.45, NEMA LS-1, AND NEC 285.6.
C. PROVIDE UNIT WITH CLAMPING VOLTAGE REQUIRED FOR
INSTALLED SYSTEM VOLTAGE.
D. PROVIDE SURGE PROTECTION UTILIZING MATCHED MULTIPLE
METAL OXIDE VARISTORS (MOV) ONLY. PROVIDE SPD WITH 0.5
NANOSECOND RESPONSE TIME.
E. PROVIDE SPD OPERATING RANGE -40 TO 60 DEGREES C, 5-95%
RELATIVE HUMIDITY, NON-CONDENSING, AND 47-63 HERTZ
FREQUENCY.
F. PROVIDE SPD WITH INTERNAL FUSING RATED FOR 200,000 AMPS
INTERRUPTING CAPABILITY.
G. PROVIDE SPD WITH THE FOLLOWING OPTIONS: LED INDICATORS
FOR EACH PHASE; AUDIBLE ALARM WITH ALARM SILENCE; FORM
C, DRY CONTACT FOR REMOTE MONITORING; UNDER-VOLTAGE
DETECTION; PHASE LOSS MONITORING; POWER LOSS
MONITORING; INTEGRAL DISCONNECT SWITCH, AND TRANSIENT
COUNTERS.
H. PROVIDE SPD IN EXTERNAL MOUNT, NEMA 4, INDOOR/OUTDOOR
ENCLOSURE.
I. MOUNT SPD AS CLOSE AS POSSIBLE TO PROTECTED
EQUIPMENT AND MINIMIZE WIRE LENGTH. TWIST INPUT
CONDUCTORS TOGETHER TO REDUCE INDUCTANCE.
J. PROVIDE SPD WITH A 5 YEAR WARRANTY.
13. VARIABLE FREQUENCY CONTROLLERS
A. GENERAL REQUIREMENTS FOR VARIABLE-FREQUENCY MOTOR
CONTROLLERS (VFC) AND ACCESSORIES: UL LISTED AND
LABELED AS DEFINED IN NFPA 70 AND MARKED FOR INTENDED
LOCATION AND APPLICATION. COMPLY WITH NEMA ICS 7, NEMA
ICS 61800-2, AND UL 508A.
B. VFCS SHALL CONSIST OF POWER CONVERTER THAT EMPLOYS
PULSE-WIDTH-MODULATED INVERTER, FACTORY BUILT AND
TESTED IN AN ENCLOSURE, WITH INTEGRAL DISCONNECTING
MEANS AND OVERCURRENT AND OVERLOAD PROTECTION;
LISTED AND LABELED BY UL AS A COMPLETE UNIT; ARRANGED
TO PROVIDE SELF-PROTECTION, PROTECTION, AND
VARIABLE-SPEED CONTROL OF INDUCTION MOTORS BY
ADJUSTING OUTPUT VOLTAGE AND FREQUENCY.
C. PROVIDE MANUFACTURER WARRANTY TO REPAIR OR REPLACE
VFCS THAT FAIL IN MATERIALS OR WORKMANSHIP WITHIN ONE
YEAR FROM DATE OF SUBSTANTIAL COMPLETION.
D. PROVIDE UNITS SUITABLE FOR OPERATION OF NEMA MG 1,
DESIGN A AND DESIGN B MOTORS.
E. OUTPUT RATING: THREE-PHASE; 10 TO 60 HZ WITH VOLTAGE
PROPORTIONAL TO FREQUENCY THROUGHOUT VOLTAGE
RANGE; MAXIMUM VOLTAGE EQUALS INPUT VOLTAGE.
F. UNIT OPERATING REQUIREMENTS:
· MINIMUM EFFICIENCY: 96 PERCENT AT 60 HZ, FULL LOAD.
· MINIMUM SHORT-CIRCUIT CURRENT (WITHSTAND) RATING:
10 KA.
· AMBIENT TEMPERATURE RATING: 32-104 DEG F.
· HUMIDITY RATING: LESS THAN 95 PERCENT
(NONCONDENSING).
· ALTITUDE RATING: NOT EXCEEDING 3300 FEET.
· OVERLOAD CAPABILITY: 1.1 TIMES THE BASE LOAD
CURRENT FOR 60 SECONDS; MINIMUM OF 1.8 TIMES THE
BASE LOAD CURRENT FOR THREE SECONDS.
SPEED REGULATION: PLUS OR MINUS 5 PERCENT.
G. PROVIDE FACTORY INSTALLED INTEGRAL SURGE SUPPRESSION
COMPLYING WITH UL 1449 SPD, TYPE 2.
H. PROVIDE UNIT TRIPPING FOR UNDER- AND OVERVOLTAGE AND
OVERCURRENT, PHASE LOSS AND PHASE REVERSAL.
I. PROVIDE VFC MOTOR OVERLOAD PROTECTION,
MICROPROCESSOR-BASED THERMAL PROTECTION SYSTEM FOR
MONITORING VFCS AND MOTOR THERMAL CHARACTERISTICS.
J. PROVIDE UNIT CAPABLE OF STARTING INTO ROTATING LOADS
SPINNING IN EITHER DIRECTION AND RETURNING MOTOR TO SET
SPEED IN PROPER DIRECTION, WITHOUT CAUSING DAMAGE TO
DRIVE, MOTOR, OR LOAD.
K. INTEGRAL INPUT DISCONNECTING MEANS AND OCPD: UL 489,
INSTANTANEOUS-TRIP CIRCUIT BREAKER WITH PAD-LOCKABLE,
DOOR-MOUNTED HANDLE MECHANISM. RATED NOT LESS THAN
115 PERCENT OF NFPA 70 MOTOR FULL-LOAD CURRENT RATING
OR VFC INPUT CURRENT RATING, WHICHEVER IS LARGER.NC
ALARM CONTACT THAT OPERATES WHEN CIRCUIT BREAKER HAS
TRIPPED.
L. STATUS LIGHTS: DOOR-MOUNTED LED INDICATORS DISPLAYING
CONDITIONS OF POWER ON, RUN, FAULTS, AND OVERLOAD.
M. PANEL-MOUNTED OPERATOR STATION: MANUFACTURER'S
STANDARD FRONT-ACCESSIBLE, SEALED KEYPAD AND
PLAIN-ENGLISH-LANGUAGE DIGITAL DISPLAY; ALLOWS
COMPLETE PROGRAMMING, PROGRAM COPYING, OPERATING,
MONITORING, AND DIAGNOSTIC CAPABILITY.
N. PROVIDE ELECTRICAL INPUT SIGNAL INTERFACES, A MINIMUM
OF TWO PROGRAMMABLE ANALOG INPUTS: 4- TO 20-MA DC AND
SIX MULTIFUNCTION PROGRAMMABLE DIGITAL INPUTS.
O. PROVIDE UNIT WITH 5% INDUCTIVE OUTPUT FILTERING TO
PROTECT MOTOR.
P. PROVIDE VFC UNIT WITH NEMA TYPE 4X ENCLOSURE TO
COMPLY WITH ENVIRONMENTAL CONDITIONS AT INSTALLED
LOCATION.
Q. WALL-MOUNT CONTROLLERS, INSTALL WITH TOPS AT UNIFORM
HEIGHT AND WITH DISCONNECT OPERATING HANDLES NOT
HIGHER THAN 79 INCHES (2000 mm) ABOVE FINISHED FLOOR, UNLESS OTHERWISE INDICATED, AND BY BOLTING UNITS TO
WALL OR MOUNTING ON LIGHTWEIGHT STRUCTURAL-STEEL
CHANNELS BOLTED TO WALL.
R. INSTALL WIRING BETWEEN VFCS, REMOTE DEVICES, AND
CONTROL DEVICES.
S. INSPECT VFC, WIRING, COMPONENTS, CONNECTIONS, AND
EQUIPMENT INSTALLATION FOR DAMAGE.
T. TEST CONTINUITY AND INSULATION RESISTANCE FOR EACH VFC
ELEMENT, COMPONENT, CONNECTING MOTOR SUPPLY, FEEDER,
AND CONTROL CIRCUITS.
U. TEST EACH MOTOR FOR PROPER PHASE ROTATION.
V. CORRECT MALFUNCTIONING UNITS ON-SITE, WHERE POSSIBLE,
AND RETEST TO DEMONSTRATE COMPLIANCE; OTHERWISE,
REPLACE WITH NEW UNITS AND RETEST.
W. TEST AND ADJUST CONTROLS, REMOTE MONITORING, AND
SAFETIES. REPLACE DAMAGED OR MALFUNCTIONING CONTROLS
AND EQUIPMENT.
X. PROGRAM MICROPROCESSORS, SET FIELD-ADJUSTABLE
SWITCHES, RELAYS, TIMERS, OVERLOAD-RELAYS, AND SET
FIELD-ADJUSTABLE PRESSURE SWITCHES.
Y. TRAIN OWNER PERSONNEL TO ADJUST, OPERATE, PROGRAM,
AND MAINTAIN VFCS.
14.PRESSURE TRANSDUCER
A. PROVIDE WATER PRESSURE TRANSDUCER COMPATIBLE WITH
VARIABLE FREQUENCY CONTROLLER UTILIZING WATER HAMMER
RESISTANT PIEZO ELECTRIC TECHNOLOGY. TEMPERATURE
COMPENSATED. STAINLESS STEEL OR BRASS CONSTRUCTION.
THREADED PIPE CONNECTION. IP65 RATED.
B. PRESSURE TRANSDUCER SHALL BE 24 VOLT POWERED.
C. PRESSURE OUTPUT SIGNAL SHALL BE TWO-WIRE, 4-20 MA.
D. PRESSURE RATING SHALL BE 0-100PSI.
15.PUMP TIME CONTROLLERS
A. PROGRAMMABLE RESIDENTIAL GRADE CONTROLLER STATIONS
FOR AUTOMATIC CONTROL VALVES. INCLUDE SWITCH FOR
MANUAL OR AUTOMATIC OPERATION.
B. CONTROL ENCLOSURES: NEMA 250, TYPE 4, WEATHERPROOF,
LOCKABLE, WITH PROVISION FOR GROUNDING.
1. BODY MATERIAL: MOLDED PLASTIC.
2. MOUNTING: SURFACE TYPE FOR WALL OR ENCLOSURE.
C. MANUFACTURERS:
1. HUNTER.
2. RAINBIRD.
3. TORO.
4. ORBIT.
D. CONTROL TRANSFORMER: RECEPTACLE MOUNTABLE, 120VAC
PRIMARY, 24VAC SECONDARY WITH INTERNAL ELECTRONIC
SHORT CIRCUIT PROTECTION.
E. CONTROL OUTPUTS: PROVIDE PROVISIONS FOR CONTROL OF A
MINIMUM OF 12 INDEPENDENT CONTROL VALVES, MASTER
CONTROL VALVE, AND PUMP RUN.
F. PUMP STARTING: PROVIDE PROVISION FOR REMOTE PUMP
STARTING CONTACTS TO COORDINATE WITH A PUMP STARTER
OR VARIABLE FREQUENCY CONTROLLER.
G. TIMING DEVICE: ADJUSTABLE, 24-HOUR, 14-DAY CLOCK, WITH
AUTOMATIC OPERATIONS TO SKIP OPERATION ANY DAY IN
TIMER PERIOD, TO OPERATE EVERY OTHER DAY, OR TO
OPERATE TWO OR MORE TIMES DAILY.
H. MANUAL OR SEMIAUTOMATIC OPERATION: ALLOWS THIS MODE
WITHOUT DISTURBING PRESET AUTOMATIC OPERATION.
I. LITHIUM POLYMER RECHARGEABLE BATTERY AND TRICKLE
CHARGER: AUTOMATICALLY POWERS TIMING DEVICE DURING
POWER OUTAGES.
J. SURGE PROTECTION: METAL-OXIDE-VARISTOR TYPE ON EACH
OUTPUT, INPUT, AND PRIMARY POWER.
K. MOISTURE SENSOR: CONTROLLER WILL BE CAPABLE OF
DELAYING OPERATION BASED ON INSTALLATION OF AN
OPTIONAL MOISTURE SENSOR.
L. CONTROLLER SYSTEM AND COMPONENTS OF IRRIGATION
CONTROLS SHALL BE WARANTEED FOR PROPER OPERATION
AND FREE FROM DEFECTS FOR A PERIOD OF TWO(2) YEARS
FROM PROJECT COMPLETION.
M. EQUIPMENT MOUNTING:
N. INTERIOR: INSTALL CONTROLLER ON INTERIOR WALL. PLACE
AND SECURE ANCHORAGE DEVICES. USE SETTING DRAWINGS,
TEMPLATES, DIAGRAMS, INSTRUCTIONS, AND DIRECTIONS
FURNISHED WITH ITEMS TO BE EMBEDDED.
O. EXTERIOR WALL: INSTALL CONTROLLER IN A NEMA 4X
WEATHERPROOF ENCLOSURE WITH HINGED LOCKABLE COVER.
P. EXTERIOR PUMP STRUCTURE: INSTALL CONTROLLER IN A NEMA
4X WEATHERPROOF ENCLOSURE WITH HINGED LOCKABLE
COVER. MOUNT ENCLOSURE ON SLOTTED GALVANIZED STEEL
SUPPORTS BOLTED OR WELDED TO PUMP SYSTEM STRUCTURE.
LOCATE ENCLOSURE TO ENSURE PROPER ACCESS TO ALLOW
90-DEGREE COVER OPENING AND PROPER OPERATION OF
CONTROLLER.
Q. INSTALL CONTROL CABLE(S) IN CONDUIT.
R. CONNECT WIRING BETWEEN CONTROLLERS, PUMP CONTROLS,
AUTOMATIC CONTROL VALVES, ETC.
S. AFTER ELECTRICAL CIRCUITRY HAS BEEN ENERGIZED, OPERATE
CONTROLLERS AND AUTOMATIC CONTROL VALVES TO CONFIRM
PROPER SYSTEM OPERATION.
T. TEST AND ADJUST CONTROLS AND SAFETIES. REPLACE
DAMAGED AND MALFUNCTIONING CONTROLS AND EQUIPMENT.
U. VERIFY THAT CONTROLLERS ARE INSTALLED AND CONNECTED
IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.
V. VERIFY THAT ELECTRICAL WIRING INSTALLATION COMPLIES
WITH MANUFACTURER'S SUBMITTAL.
W. TRAIN OWNER'S MAINTENANCE PERSONNEL TO ADJUST,
OPERATE, AND MAINTAIN AUTOMATIC CONTROLLERS.
16. DISCONNECT SWITCHES
A. PROVIDE HEAVY DUTY; QUICK-MAKE, QUICK-BREAK, LOAD
INTERRUPTER ENCLOSED SWITCH WITH EXTERNALLY
OPERABLE HANDLE INTERLOCKED TO PREVENT OPENING
FRONT COVER WITH SWITCH IN ON POSITION. HANDLE
LOCKABLE IN ON AND OFF POSITION. PROVIDE CLASS RK FUSE
CLIPS ON FUSIBLE DISCONNECT SWITCHES.
B. UNLESS INDICATED OTHERWISE, PROVIDE GENERAL PURPOSE,
NEMA 1 FOR INDOOR LOCATIONS; AND WEATHERPROOF, NEMA
3R FOR OUTDOOR LOCATIONS; PROVIDE NEMA 4X IN
CORROSIVE LOCATIONS.
C. PROVIDE FUSES IN FUSED DISCONNECT SWITCHES.
D. PROVIDE DISCONNECT SWITCHES, WHERE REQUIRED BY CODE,
WHERE INDICATED ON DRAWINGS, AND WHERE REQUIRED BY
EQUIPMENT MANUFACTURER, IN A LOCATION CONVENIENT FOR
MAINTENANCE ON EACH SWITCH AND ADJACENT EQUIPMENT.
E. PROVIDE FUSED DISCONNECT SWITCHES WHEN REQUIRED TO
MAINTAIN EQUIPMENT MANUFACTURER'S WARRANTY.
F. WALL MOUNT SWITCHES, WHERE POSSIBLE, OR MOUNT ON
UNI-STRUT SUPPORTS.
ELECTRICAL SPECIFICATIONS
1. PROVIDE ALL ELECTRICAL INSTALLATIONS IN ACCORDANCE
WITH THE NATIONAL ELECTRICAL CODE AND ALL LOCAL
AMENDMENTS AND ORDINANCES.
2. ALL CIRCUITS SHALL BE IN CONDUIT.
3. ALL CIRCUITS ARE SHOWN SCHEMATICALLY. THE
CONTRACTOR WILL MAKE FINAL ROUTING DECISIONS.
4. UNLESS NOTED OTHERWISE, PROVIDE 2 #12, #12 GROUND, 3/4"
CONDUIT FOR 20 AMP SINGLE PHASE POWER CIRCUITS.
CIRCUIT RUNS LONGER THAN 100' WILL BE 2#10, #10 GROUND,
3/4" CONDUIT.
GENERAL NOTES
ALL MATERIAL AND LABOR COSTS REQUIRED FOR THE PURCHASE
AND INSTALLATION OF A VFD CONTROLLER AND SUPPORTING
EQUIPMENT AND/OR STRUCTURES TO AN EXISTING IRRIGATION
SYSTEM WILL BE PAID FOR BY FLOODPLAINS BY DESIGN GRANT 5
(AGREEMENT #. SEAFBD-2123-PICOPW-00024; TASK 5;
DELIVERABLE 9). PARTICIPATING PROJECT FARMS ARE
RESPONSIBLE FOR ANY NEEDED FENCING, SITE LIGHTING, AND
SECURITY IMPROVEMENTS. PARTICIPATING FARMS WILL BE
RESPONSIBLE FOR THE COSTS ASSOCIATED FOR AN ANNUAL
INSPECTION AND SERVICING OF THEIR VFD INSTALLATION FOR A
MINIMUM OF FIVE YEARS.
PROJECT NOTE
NEMA 5-20 DUPLEX RECEPTACLE MOUNTED 18" AFF
UNLESS NOTED OTHERWISE.
JUNCTION BOX.
DISCONNECT SWITCH, UNFUSED. SIZE AS SHOWN.
DISCONNECT SWITCH, FUSED. SIZE AS SHOWN.
SURFACE MOUNTED EQUIPMENT.
GROUND ROD.
ARROW INDICATES HOMERUN TO PANEL "A", CIRCUIT
21.
EXISTING OVERHEAD ELECTRICAL LINE.
EXISTING UNDERGROUND ELECTRICAL LINE.
EXISTING OVERHEAD COMMUNICATIONS LINE.
EXISTING UNDERGROUND COMMUNICATIONS LINE.
EXISTING ITEMS TO BE REMOVED.
NEW OVERHEAD ELECTRICAL LINE.
NEW UNDERGROUND ELECTRICAL LINE.
J
A-21
ELECTRICAL LEGEND
A AMPERE
AFF ABOVE FINISHED FLOOR
C CONDUIT
CB CIRCUIT BREAKER
EMT ELECTRICAL METALLIC TUBING
G GROUND
GFCI GROUND FAULT CIRCUIT INTERRUPTING
HP HORSEPOWER
HZ HERTZ
KWH KILOWATT HOUR
LED LIGHT EMITTING DIODE
MLO MAIN LUGS ONLY
NEC NATIONAL ELECTRICAL CODE
PH PHASE
PVC POLYVINYL CHLORIDE
RGS RIGID GALVANIZED STEEL
SPD SURGE PROTECTION DEVICE
SW SWITCH
V VOLT
VA VOLTAMPERE
VFC VARIABLE FREQUENCY CONTROLLER
W WATTS
WP WATERPROOF
XFMR TRANSFORMER
ABBREVIATIONS
OE
E
OC
C
E
NE
UE
GENERAL NOTES
RText (RText)
Pierce County Agricultre Program Pierce County
9850 64TH STREET WEST
UNIVERSITY PLACE, WA 98467-1078
DATE APPROVEDBYREVISIONNO.
Know what's below.
before you dig.Call
R
DESIGNED BY:
DATE PLOTTED:
DRAWN BY:
CHECKED BY:
SURVEYED BY:
DATE SURVEYED:
N/A
May 20, 2026
100% SUBMITTAL
www.huitt-zollars.com
1700 7th Avenue, Suite 2075 Seattle, Washington 98101-1360
206.324.5500
N
SCALE (IN FEET)
0 2500 5000 10000
HORZ
CLEAR CREEK (ORTING VALLEY) WATERSHED
VFD ADDITION TO IRRIGATION SYSTEM
LOCAL COLOR FARM
VICINITY MAP
J. ROBERTS
R. TAM
V. LY
FARM NAME: LOCAL COLOR
SITE ADDRESS 10806 159TH AVE E
PUYALLUP, WA 98374
SITE TAX
PARCEL:
0519067701
PIERCE
COUNTY
CONTACT:
DEAN MCCLARY
(253) 798 6221 dean.mcclary@piercecountywa.gov
FARM OWNER
CONTACT:
EMILY TZENG, BRIAN LOVE
(443) 350 7107
05/20/2026
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
OE
M
B
E
E
E
E
E
E
E
E
E
EXISTING METER,
ELECTRICAL LOAD CENTER
AND RECEPTACLE ON POLE
EX. WATER
INTAKE AND
VALVE
PORTABLE
PUMP AREA
EXISTING DIRT ROAD
EXISTING UTILITY POLE
WITH 3X 15KVA
TRANSFORMERS
EXISTING UTILITY
POLE WITH
TRANSFORMER
EXISTING ADJACENT
POLE W/ BIRDHOUSE.
SHOWN FOR
REFERENCE ONLY.
EXISTING PUMP
CIRCUIT IN 1" Ø
BURIED CONDUIT
APPROX. 300 LF
EXISTING PUMP
COMBINATION
STARTER AND
DISCONNECT ON
4"X4" POST
EXISTING PUMP CONNECTION AND COMBINATION STARTER AND
DISCONNECT ON 4"X4" POST
EXISTING UTILITY POLE WITH
TRANSFORMER
EX 1" Ø CONDUIT
PUYALLUP RIVER
EX. D
IRT ROAD
OE
OE
OE
OE
OE
OE
OE
OE
W
B
E
E
E
E
PORTABLE
PUMP AREA
EXISTING DIRT ROAD
EXISTING PUMP CONNECTION
AND COMBINATION STARTER AND
DISCONNECT ON 4"X4" POST
EXISTING UTILITY
POLE WITH
TRANSFORMER
EXISTING PERMANENT
2" WATER INTAKE AND
VALVE
EX 1" Ø
CONDUIT
RText (RText)
Pierce County Agricultre Program Pierce County
9850 64TH STREET WEST
UNIVERSITY PLACE, WA 98467-1078
DATE APPROVEDBYREVISIONNO.
Know what's below.
before you dig.Call
R
DESIGNED BY:
DATE PLOTTED:
DRAWN BY:
CHECKED BY:
SURVEYED BY:
DATE SURVEYED:
N/A
May 20, 2026
100% SUBMITTAL
www.huitt-zollars.com
1700 7th Avenue, Suite 2075 Seattle, Washington 98101-1360
206.324.5500
J. ROBERTS
R. TAM
V. LY
CLEAR CREEK (ORTING VALLEY) WATERSHED
VFD ADDITION TO IRRIGATION SYSTEM
LOCAL COLOR FARM
N
SCALE (IN FEET)
0 10 20 40
HORZ
NNTS
OVERALL SITE PLAN
ELECTRICAL PLAN
NOT TO SCALE
ELECTRICAL DIAGRAM
EXISTING OVERHEAD
ELECTRICAL SERVICE TO POLE
MOUNTED TRANSFORMERS
EXISTING
METER BASE
AND UTILITY
METER
EXISTING
100 A 240/120V 3Ø, 4W, LOAD
CENTER
EX PUMP
CONTROL
STARTER/
DISC SW
NEW
VFC
EXISTING CIRCUIT
EXISTING 5HP WATER PUMP ON
PORTABLE PUMP SUPPORT BASE
EXTEND 3#10, #10 TYPE SO CORD
TO NEW VFC.
NEW PUMP TIMER CONTROLLER
EXISTING PUMP CIRCUIT
CONNECTION FLEXIBLE CORD
AND PLUG SHALL REMAIN.
EXTEND 3#10, #10G, TYPE SO CORD TO
EXISTING PUMP STARTER/DISCONNECT
SWITCH COORDINATE LUG TYPE WITH
EXISTING OUTLET.
2#12,#12G TO PUMP RUN CONTACTS
EXTEND NEW CONTROLLER POWER
CIRCUIT AND POWER SUPPLY TO GFCI
RECEPTACLE IN ENCLOSURE
EXISTING 1" PVC FEEDER
UNDERGROUND TO PUMP
SKID COMBINATION STARTER
MOUNT NEW VFC AND PUMP TIMER
CONTROLLER IN 24"WX36"HX12"D, NEMA 4
STEEL ENCLOSURE WITH HINGED LOCKING
DOOR. MOUNT TO EXISTING PUMP SKID
WITH UNISTRUT SUPPORTS
H - O - A
NEW PRESSURE TRANSDUCER
MOUNTED TO EXISTING PIPING.
COORDINATE LOCATION WITH
PIPING AND MANUFACTURER
REQUIRMENTS EXTEND
3#12.#12G, 1/2"C TO VFC
EXISTING PUMP SKID MODIFICATION
ELECTRICAL PLAN
WATER
INLET
W
AT
ER
O
U
TL
ET
EXISTING 30 HP WATER
PUMP AND MOTOR
EXISTING PORTABLE
PUMP SUPPORT BASE
NEW PRESSURE TRANSDUCER
MOUNTED TO EXISTING PIPING.
COORDINATE LOCATION WITH
PIPING AND MANUFACTURER
REQUIRMENTS EXTEND 3#12.#12G,
1/2"C TO VFC
MOUNT NEW VFC AND PUMP TIMER
CONTROLLER IN 24"WX36"HX12"D, NEMA 4
STEEL ENCLOSURE WITH HINGED LOCKING
DOOR. MOUNT TO EXISTING PUMP SKID
WITH UNISTRUT SUPPORTS
NOT TO SCALE
PLUMBER WILL EXTEND THE
EXISTING OUTLET PIPING AS
NECESSARY TO ACCOMMODATE
THE PROPER INSTALLATION OF THE
NEW PRESSURE TRANSDUCER.
05/20/2026