This document appears to be a set of mechanical drawings related to the EHRM Infrastructure Upgrades Construction project at the Nashville VAMC (Solicitation Number 36C77624B0029). The drawings, numbered 626-700, provide detailed specifications and technical requirements for the mechanical systems to be installed as part of this construction project. Key details include the federal agency involved (Department of Veterans Affairs Technology Acquisition Center Austin), the project name ("Y1DZ--626-22-700 EHRM Infrastructure Upgrades Construction Nashville"), and the opportunity type (Solicitation). While this document does not directly address the required products or services, it provides critical technical information necessary for contractors to submit responsive bids for the construction work.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
H
C
C
MECHANICAL ABBREVIATION KEY
ABBR: DESCRIPTION:
EA EXHAUST/RELIEF AIR
FD FIRE DAMPER
FSD FIRE/SMOKE DAMPER
MA MIXED AIR
NOT IN CONTRACTNIC
NORMALLY CLOSEDN.C.
NORMALLY OPENN.O.
MIXING VALVEMV
OA OUTSIDE AIR
RA RETURN AIR
SA SUPPLY AIR
SD SMOKE DAMPER
TRANSFER DUCTTD
TERMINAL AIR BOXTAB
TYPICALTYP
NOT ALL SYMBOLS MAY APPLY.
1. THE SIZE OF BRANCH PIPING TO TERMINAL HEATING DEVICES AND COILS SHALL BE 3/4"
UNLESS NOTED OTHERWISE.
2. PIPE DRAIN LINES FROM EQUIPMENT TO NEAREST DRAIN INDICATED ON DRAWINGS.
3. INSTALL ALL REFRIGERANT LIQUID AND SUCTION PIPING SIZED PER EQUIPMENT
MANUFACTURER RECOMMENDATIONS.
PIPING GENERAL NOTES:
1. UNLESS NOTED OTHERWISE, THE SIZE OF EACH BRANCH DUCT TO A TERMINAL AIR BOX
(TAB) SHALL MATCH THE INLET SIZE UNLESS THE BRANCH IS GREATER THAN 6 FEET IN
LENGTH, IN WHICH CASE THE BRANCH DUCT SHALL BE SIZED AT A PRESSURE DROP OF
0.07" W.C. PER 100' OF DUCTWORK.
2. UNLESS NOTED OTHERWISE, THE SIZE OF EACH BRANCH DUCT TO AN AIR TERMINAL SHALL
MATCH THE INLET SIZE.
3. ALIGN TEMPERATURE SENSORS WITH LIGHT SWITCHES AND WHEN IN CLOSE PROXIMITY TO
EACH OTHER.
4. PROVIDE ACCESS DOORS AT ALL DUCT MOUNTED EQUIPMENT.
5. EXISTING AIR INLET AND OUTLET CFM SHOWN ON DRAWINGS ARE FROM EXISTING
DRAWINGS, AND ARE FOR REFERENCE ONLY.
6. CONTRACTOR MAY REUSE PORTIONS OF EXISTING DUCT PROVIDED SIZES AND PRESSURE
CLASSES ARE CORRECT, DUCT IS THOROUGHLY CLEANED AND FREE OF DEFECTS, AND ALL
TRANSVERSE JOINTS, LONGITUDINAL SEAMS, AND DUCT WALL PENETRATIONS ARE SEALED
AS SPECIFIED FOR NEW DUCTWORK.
VENTILATION GENERAL NOTES:
MECHANICAL GENERAL NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, FIRE PROTECTION, PLUMBING, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE
DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS.
DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC.,
AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE
INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING
CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.
2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM
ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR
PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.
3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE
CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO
VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO
VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES
OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING
WITH FABRICATION OR EQUIPMENT ORDERS.
4. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE
REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER
ACCESS.
5. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO
COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR
EXPENSE TO OTHERS.
6. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL
CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF
DESIGN.
7. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY
AUDIO/VISUAL, AND OTHER MECHANICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING
MOUNTED DEVICES, OTHER THAN SPRINKLERS.
8. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS,
FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS
RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND
FINISH.
9. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS WITH THE
GC FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS, ETC. COORDINATE
PANEL TYPE AND COLOR WITH ARCHITECT. NOTIFY THE GC OF THE REQUIRED ACCESS
PANELS PRIOR TO BIDDING.
10. SEAL ALL FLOOR, WALL, AND ROOF PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING,
AND DUCTS PENETRATE. PENETRATIONS THROUGH EXTERIOR WALLS AND ROOF SHALL BE
SEALED AIRTIGHT WITH WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER
FOR OUTDOOR USE.
11. CAULK ALL PIPE AND DUCT PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL,
PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE
TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS
WITHIN ROOMS.
12. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED
OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL
RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.
13. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT
MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND
REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS,
PIPING, DUCTWORK, ETC.
14. DO NOT BLOCK EQUIPMENT SERVICE CLEARANCES.
15. MAINTAIN A MINIMUM WORKING CLEARANCE OF 3’-6” IN FRONT OF ALL ELECTRICAL
EQUIPMENT REQUIRING MAINTENANCE, INSPECTION, AND TESTING INCLUDING BUT NOT
LIMITED TO PANELS, DISTRIBUTION PANELS, SWITCHBOARDS, MOTOR CONTROL CENTERS,
TRANSFORMERS, EQUIPMENT DISCONNECTS AND STARTERS.
16. MAINTAIN THE DEDICATED ELECTRICAL EQUIPMENT SPACE DEFINED BY THE WIDTH / DEPTH
OF ELECTRICAL EQUIPMENT MEASURED FROM THE FLOOR TO A HEIGHT 6’-0” ABOVE THE
EQUIPMENT OR THE STRUCTURAL CEILING, WHICHEVER IS LOWER. SYSTEMS FOREIGN TO
THE ELECTRICAL DISTRIBUTION SYSTEM ARE NOT ALLOWED IN THE DEDICATED
ELECTRICAL SPACE INCLUDING: DUCTWORK, PIPING, ETC.
17. DO NOT SUPPORT EQUIPMENT, PIPING, OR DUCTWORK FROM METAL DECKING OR OTHER
NON-STRUCTURAL BUILDING ELEMENTS. ANCHORS EMBEDDED IN CONCRETE SHALL BE
CRACKED CONCRETE APPROVED IN ACCORDANCE WITH SPECIFICATIONS.
MECHANICAL RENOVATION NOTES:
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND
REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING DUCTWORK AND PIPING IS SHOWN. VERIFY EXISTING CONDITIONS
BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR DUCTWORK AND PIPING BEFORE
FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD
CONDITIONS.
4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF THEIR WORK AND
SHALL NOTIFY THE ARCHITECT/ENGINEER PRIOR TO BIDDING IF OTHER UTILITIES ARE
REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO THEIR AREA OF WORK.
5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF
ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS.
CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING.
6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF
CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL
CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO
BIDDING.
7. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH
NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL
EITHER ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT
DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL
SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
8. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING
CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THAT
REMAIN ACTIVE.
9. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY
REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW
SYSTEMS ARE INSTALLED.
10. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR
TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND
CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY
DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.
11. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENT
THAT HAS BEEN REMOVED.
MECHANICAL PHASING NOTES:
1. REFER TO ARCHITECTURAL DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER TO
ARCHITECT'S INSTRUCTIONS FOR MORE DETAILS AND PHASING SCHEDULES AND FOR
CONCURRENT WORK. MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT
THE INTENT OF THE FINAL DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY
DRAWINGS DO NOT DEPICT THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF
THE PHASING CRITERIA.
2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC.
WITH AFFECTED ADJACENT AREAS.
3. PROVIDE TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ZONE VALVES, ZONE
ALARMS, ETC. AS NEEDED TO MAINTAIN SERVICE TO ALL AREAS DURING ALL PHASES OF
PROJECT.
4. INSTALL TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ETC. AS NECESSARY TO KEEP
ALL OCCUPIED SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT
5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
M101
SIMSIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
1 INDICATES NOTE USED TO DESCRIBE
ADDITIONAL INFORMATION ABOUT
WORK REQUIRED, SPECIFIC TO THE
SHEET AND/OR DETAIL
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE AND TAG KEY:
NEW WORK BY THIS CONTRACTOR (WIDE LINE)
NEW
EXISTING TO BE REMOVED (SHORT DASHED PATTERN)
NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)
EXISTING
EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)
EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
HALFTONING DOES NOT MODIFY SCOPE.
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
TAG UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL
INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL
T101
1 VIEW NAME
SCALE: 1/8" = 1'-0"A101 0 8' 16'4'
N
SHEET NUMBER
THE LINE TYPES SHOWN ARE FOR THE CONVENIENCE OF THE CONTRACTOR. THE CONTRACTOR
SHALL VERIFY RATINGS WITH THE LATEST SET OF ARCHITECTURAL PLANS AND FURNISH ALL
MATERIALS REQUIRED TO COMPLY WITH THOSE RATINGS WHETHER SHOWN OR NOT.
FIRE / SMOKE BARRIER DESIGNATIONS
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
SMOKE BARRIER
1 HOUR FIRE/SMOKE BARRIER
2 HOUR FIRE/SMOKE BARRIER
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES: V3.1, JULY 1, 2021
VA FIRE PROTECTION DESIGN MANUAL: 8TH ED., JUNE 1, 2021
VA PHYSICAL SECURITY AND RESILIENCY DESIGN MANUAL: REV. JULY 1, 2022
VA PLUMBING DESIGN MANUAL: REV. JANUARY 1, 2023
VA HVAC DESIGN MANUAL: REV. NOVEMBER 1, 2022
NFPA 13 INSTALLATION OF SPRINKLER SYSTEMS: 2022 EDITION
NFPA 72 FIRE ALARM AND SIGNALING CODE: 2022 EDITION
NFPA 75 FIRE PROTECTION OF IT EQUIPTMENT: 2020 EDITION
NFPA 99 HEALTHCARE FACILITIES CODE: 2021 EDITION
NFPA 101 LIFE SAFETY CODE: 2021 EDITION
NFPA 2001 CLEAN AGENT FIRE EXTINGUISHING SYSTEMS: 2022 EDITION
INTERNATIONAL BUILDING CODE: 2021 EDITION
INTERNATIONAL MECHANICAL CODE: 2021 EDITION
INTERNATIONAL PLUMBING CODE: 2021 EDITION
APPLICABLE CODES AND STANDARDS
CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS
PROJECT ALTITUDE: 554 FT. ABOVE SEA LEVEL
MECHANICAL DESIGN CONDITIONS:
SUMMER:
WINTER:
OUTDOOR CONDITIONS:
INDOOR DESIGN CONDITIONS:
BASED ON WEATHER DATA FOR: NASHVILLE, TENNESSEE
TR IT EQUIPMENT INLET: 41-95°F DRY BULB, 8-80% RELATIVE HUMIDITY
MCR IT EQUIPMENT INLET: 72-81°F DRY BULB, 8-60% RELATIVE HUMIDITY
TR AND MCR SPACES: 64-81°F DRY BULB, 30-60% RELATIVE HUMIDITY
TE ENVIRONMENT: 41-95°F DRY BULB, 8-80% RH, <82.4°F DEW POINT
REFER TO CONTROL DIAGRAMS FOR ROOM SPECIFICS.
94.8°F DRY BULB, 74.9°F WET BULB
14.8°F DRY BULB
MECHANICAL SYMBOL LIST
SYMBOL: DESCRIPTION:
NOT ALL SYMBOLS MAY APPLY.
DIRECTION OF AIR FLOW
FLEXIBLE DUCT
MANUAL VOLUME DAMPER
RISE IN DIRECTION OF AIR FLOWR
DUCT CAP
DROP IN DIRECTION OF AIR FLOWD
DUCT DOWN
DUCT UP
SUPPLY/OUTSIDE AIR DUCT SECTION
RETURN AIR DUCT SECTION
EXHAUST/RELIEF AIR DUCT SECTION
4-WAY DIFFUSER WITH BLANKOFF IN ONE DIRECTION
SD-1
6/115
AIR TERMINAL PROPERTIES SYMBOL
NECK SIZE/CFM
TERMINAL AIR BOX (REFER TO SCHEDULE)###
### TERMINAL AIR BOX w/REHEAT COIL (REFER TO SCHEDULE)
HUMIDIFIERH
OPPOSED BLADE DAMPER (REFER TO SCHEDULE)
PARALLEL BLADE DAMPER (REFER TO SCHEDULE)
FAN POWERED TERMINAL AIR BOX w/REHEAT COIL
(REFER TO SCHEDULE)
MECHANICAL SYMBOL LIST
SYMBOL: DESCRIPTION:
NOT ALL SYMBOLS MAY APPLY.
CONDENSER WATER RETURNCR
CONDENSER WATER SUPPLYCS
CHILLED WATER RETURNCHR
CHILLED WATER SUPPLYCHS
CD CONDENSATE DRAIN
COLD WATER - POTABLECW
HEATING/CHILLED WATER RETURNHCR
HEATING/CHILLED WATER SUPPLYHCS
HEATING WATER RETURNHWR
HEATING WATER SUPPLYHWS
REFRIGERANT LIQUIDLIQ
REFRIGERANTREF
REHEAT WATER RETURNRWR
REHEAT WATER SUPPLYRWS
REFRIGERANT SUCTIONSUC
PIPE CAP
PIPE DOWN
PIPE UP OR UP/DOWN
PITCH PIPE IN DIRECTION
DIRECTION OF FLOW IN PIPE
CONTROL VALVE (TWO-WAY)
DIELECTRIC CONNECTION
UNION/FLANGE
BALANCING VALVE (NUMBER INDICATES GPM)
SHUTOFF VALVE NORMALLY OPEN
SHUTOFF VALVE NORMALLY CLOSED
THROTTLING VALVE
AUTOMATIC BALANCING VALVE
MIXING VALVE
CONTROL VALVE (THREE-WAY)
SOLENOID VALVE
CHECK VALVE
BACKFLOW PREVENTER
SAFETY/RELIEF VALVE
PRESSURE REDUCING VALVE (LIQUID/GAS)
PRESSURE REDUCING VALVE (STEAM)
TRIPLE DUTY VALVE (ANGLE TYPE)
TRIPLE DUTY VALVE (IN-LINE TYPE)
VACUUM BREAKER
"WYE" - STRAINER
"WYE" - STRAINER W/SHUTOFF VALVE AND HOSE CONNECTION WITH CAP
PUMP
BASKET STRAINER
FLEXIBLE CONNECTION
PRESSURE/TEMPERATURE TEST PLUG
REDUCER - REFERENCE SPECIFICATION
FOR CONCENTRIC/ECCENTRIC AND FOT/FOB
SUCTION DIFFUSER WITH SUPPORT FOOT
AUTOMATIC AIR VENT
MANUAL AIR VENT
DRAIN VALVE WITH HOSE CONNECTION AND CAP
ALIGNMENT GUIDE
PIPE ANCHOR
EXPANSION JOINT
#.#" IS THE EXPANSION TRAVEL INCHES
PRESSURE GAUGE (FURNISHED WITH BALL VALVE)P
DIFFERENTIAL PRESSURE SENSOR
PRESSURE SENSOR (FURNISHED WITH BALL VALVE)P
FLOW METER
FM
FLOW SWITCH
F
FS FLOW SENSOR
EJ-#
OCCUPANCY SENSORO
HUMIDISTAT SENSOR
CARBON MONOXIDE SENSOR
CARBON DIOXIDE SENSOR
H HUMIDISTAT / SENSOR
TEMPERATURE SENSOR WITH WELL
T
THERMOMETER WITH WELL (DIAL TYPE)T
THERMOMETER WITH WELL (FILLED TYPE)
DIFFERENTIAL PRESSURE SENSOR
PRESSURE SENSOR/MONITORP
PRESSURE SENSOR (DUCT MOUNTED)P
THERMOSTAT/SENSORT
TEMPERATURE SENSORT
THERMOSTAT/SENSOR WITH HEAVY DUTY ENCLOSURET
AIRFLOW MEASUREMENT SYMBOL
XX - AHU SYMBOL
Y - SEQUENTIAL NUMBER
XX-Y
MECHANICAL SHEET INDEX
MH000 MECHANICAL COVERSHEET
B01-MH200 BASEMENT LEVEL MECHANICAL PLAN - OVERALL
B01-MH200A BASEMENT LEVEL MECHANICAL PLANS - SECTION A
B01-MH200ACRE BASEMENT LEVEL MECHANICAL PLANS - SECTION ACRE
B01-MH200BE BASEMENT LEVEL MECHANICAL PLANS - SECTION BE
B01-MH200BW BASEMENT LEVEL MECHANICAL PLAN - SECTION BW
B01-MH200CE BASEMENT LEVEL MECHANICAL PLAN - SECTION CE
B01-MH200CW BASEMENT LEVEL MECHANICAL PLAN - SECTION CW
B01-MH200DE BASEMENT LEVEL MECHANICAL PLAN - SECTION DE
B01-MH200DW BASEMENT LEVEL MECHANICAL PLAN - SECTION DW
B01-MH201 FIRST LEVEL MECHANICAL PLAN - OVERALL
B01-MH201A FIRST LEVEL MECHANICAL PLAN - SECTION A
B01-MH201ACRE FIRST LEVEL MECHANICAL PLAN - SECTION ACRE
B01-MH201BE FIRST LEVEL MECHANICAL PLAN - SECTION BE
B01-MH201BW FIRST LEVEL MECHANICAL PLAN - SECTION BW
B01-MH201CE FIRST LEVEL MECHANICAL PLAN - SECTION CE
B01-MH201CW FIRST LEVEL MECHANICAL PLAN - SECTION CW
B01-MH201DE FIRST LEVEL MECHANICAL PLAN - SECTION DE
B01-MH201DW FIRST LEVEL MECHANICAL PLAN - SECTION DW
B01-MH202 SECOND LEVEL MECHANICAL PLAN - OVERALL
B01-MH202A SECOND LEVEL MECHANICAL PLAN - SECTION A
B01-MH202ACRE SECOND LEVEL MECHANICAL PLAN - SECTION ACRE
B01-MH202B SECOND LEVEL MECHANICAL PLAN - SECTION B
B01-MH202C SECOND LEVEL MECHANICAL PLAN - SECTION C
B01-MH202D SECOND LEVEL MECHANICAL PLAN - SECTION D
B01-MH203 THIRD LEVEL MECHANICAL PLAN - OVERALL
B01-MH203A THIRD LEVEL MECHANICAL PLAN - SECTION A
B01-MH203ACRE THIRD LEVEL MECHANICAL PLAN - SECTION ACRE
B01-MH203B THIRD LEVEL MECHANICAL PLAN - SECTION B
B01-MH203C THIRD LEVEL MECHANICAL PLAN - SECTION C
B01-MH203D THIRD LEVEL MECHANICAL PLAN - SECTION D
B01-MH204 FOURTH LEVEL MECHANICAL PLAN - OVERALL
B01-MH204A FOURTH LEVEL MECHANICAL PLAN - SECTION A
B01-MH204ACRE FOURTH LEVEL MECHANICAL PLAN - SECTION ACRE
B01-MH204B FOURTH LEVEL MECHANICAL PLAN - SECTION B
B01-MH204C FOURTH LEVEL MECHANICAL PLAN - SECTION C
B01-MH204D FOURTH LEVEL MECHANICAL PLAN - SECTION D
B01-MH205 FIFTH LEVEL MECHANICAL PLAN - OVERALL
B01-MH205ACRE FIFTH LEVEL MECHANICAL PLAN - SECTION ACRE
B01-MH206 SIXTH LEVEL MECHANICAL PLAN - OVERALL
B01-MH206ACRE SIXTH LEVEL MECHANICAL PLAN - SECTION ACRE
B01-MH207ACRE ROOF LEVEL MECHANICAL PLAN - SECTION ACRE
B01-MH300 SECOND LEVEL ENLARGED MCR MECHANICAL DEMOLITION
B01-MH301 SECOND LEVEL ENLARGED MCR VENTILATION PLAN
B01-MH302 SECOND LEVEL ENLARGED MCR MECHANICAL PIPING PLAN
B01A-MH201 FIRST LEVEL MECHANICAL PLANS
B09-MH200 PARKING GARAGE BASEMENT LEVEL MECHANICAL PLANS
MH400 MECHANICAL DETAILS
MH600 MECHANICAL SCHEDULES
MH700 TEMPERATURE CONTROLS DIAGRAMS AND SEQUENCES
GRAND TOTAL: 50
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
A/E:
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.M
P F
P R
.r v t
/1
/2
:3
:2
A
M
MH000
MECHANICAL COVERSHEET EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24th Avenue South Nashville, TN 37212
626-22-700
N/A
02/16/2024 MatKah CasHos
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
IMEG
101 N SEVENTH STREET
LOUISVILLE, KY 40202
502.415.7814
Revisions: Date:
o.: 223
SECTION BE
SECTION BW
SECTION BW
SECTION DE
SECTION DE
SECTION DW
SECTION DWSECTION CW
SECTION CE
SECTION CW
SECTION A
SECTION CE
SECTION ACRE
SECTION A
SECTION ACRE SECTION BE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
KEYPLAN N
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
A/E:
ACRE
A BW
CE DE
1A
BE
CW DW
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.M
P F
P R
.r v t
/1
/2
:3
:1
A
M
B01-MH200
BASEMENT LEVEL MECHANICAL PLAN -
OVERALL
EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24th Avenue South Nashville, TN 37212
626-22-700
02/16/2024 MatKah CasHos
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
IMEG
101 N SEVENTH STREET
LOUISVILLE, KY 40202
502.415.7814
SCALE: 1" = 20'-0"B01-MH200
1 BASEMENT LEVEL PLAN - OVERALL
SHEET NOTES:
1. THIS SHEET IS FOR REFERENCE ONLY. REFER
TO ENLARGED VIEWS ON SUBSEQUENT
DRAWINGS FOR ADDITIONAL INFORMATION.
2. HATCHED AREAS INDICATE LOCATIONS OF
NEW OR RENOVATED TELECOMMUNICATION
SPACES.
N
0 20' 40'10'
T
TT H
TT H
2 3
4 5 6 7 8 9 10 11 12 13
B
C
D
E
F
G
H
J
TR
D-57A
STORAGE
F-9B
STORGAE
D-13
STORAGE
D-14
BIOMED SHOP
D-15
TOILET
D-16
STORAGE
F-9C
PEN
D-19A
EQUIPMENT
F-7A
CATH LAB # 2
D-19CONTROL ROOM
D-18
CATH LAB # 1
D-17
TC LAB
D-12E
MICRO LAB
D-12
OFFICE
D-12A
GEN WASH
D-09
ANTE RM
D-12B
WORK RM
D-12C
BSLE LAB
D-12D
BD2
D-11
BD1
D-10
CT-1
D-27K
CONTROL
D-27J
CT-2
D-27H
MECH
D-28-B CLEAN LINEN
D-28
TOSHIBA
D-28A
MICRO OFFICE
D-05E
MALE TOILET
D-08MULTIPURPOSE
D-05C FEMALE TOILET
D-07
OFFICE
D-06A
SCREENING
D-06 ELECTRICAL
CLOSET
D-29
BD ELECTRICAL
CLOSET
D-30
HOT LAB
D-40D
TREAT
D-40E
TREAT
D-40F
CHANGING/TOILET
D-27E
STORAGE
D-27F
OFFICE
D-27G
MULTI VIEWING
D-41
MULTI VIEWING
CB-12D D-42
OFFICE
CB-12C D-43
MULTI VIEWING
D-44
MULTI VIEWING
D-45
OFFICE
D-46 Room
D-47
ADP COORD
OFFICE
D-02D
OFFICE
D-02E
ELEC
CLOSET
D-02F
MALE TOILET
D-49
FEMALE TOILET
D-48
BREAK
D-27B
SUPPLY
MAMMOGRAPHY
D-22
DARK RM
D-22A
READING RM
D-21
VESTIBULE
D-20
HC TOILET
D-20A
HC TOILET
D-20B
LOUNGE/LOCKERS
D-58
COMPUTER RM
D-57
CHIEF TECH
D-50
SEC
D-651
SVC CHIEF
D-65
SIG
D-02G
OFFICE
D-02C
OFFICE
D-02B
OFFICE
D-02A
Room
D-01
ADP
TOILET
D-63
STORAGE
D-56
HAC
D-55
RADIOGRAPHIC
FLUOROSCOPIC
D-54
RADIOGRAPHIC
FLUOROSCOPIC
D-53B
CONTROL
D-53C
CONTROL
D-54C Room
A-585
TOILET
TOILET
D-54B
Room
A-588
DRESS
D-53A
DRESS
D-54A
Room
CB-12
CORRIDOR
DRESS
D-52A
DRESS
D-51A
RADIOGRAPHIC
FLUOROSCOPIC
ROOM
A-594
RADIOGRAPHIC
FLUOROSCOPIC
D-52
CONTROL
D-52C
CONTROL
D-51C
HOLDING
D-27D
PASSAGE
D-27
WHL CHR.
STRG
SCRUB/ WORK AREA
D-24B
I.R.
D-24
WAITING
D-27A
CONTROL
D-24A
TOILET
A-606
TOILET
D-51B
TOILET
D-52B
GANTRY
D-40A
TOILET
D-40C
CORRIDOR
Room
A-612
CNTRL RM
D-40B
PET SCAN
D-40
CYTO LAB
D-05
BLK STORAGE
D-05D
CORRIDOR
CB-24
CORRIDOR
CB-11SAW RM
CUTTING RM
D-05A
READING ROOM
D-04
TECH
D-03A
ADP COMPUTER RM
D-03
WAITING
D-02
WAITING SPACE
CB-14A
CORRIDOR
CB-13
CORRIDOR
CB-14
CORRIDOR
CB-10
CORRIDOR
CB-20
CORRIDOR
D-26
OTHER
F-7C
LINEN
D-23
STAIR
NO.4
ELEVATOR
ELEVATOR
S-2
CORRIDOR
CB-19
B01-MH200A
B01-MH200A
B01-MH200A
/4
"C D
REF
COMPUTER RM
D-57
14ø SA x1
R
A
10x14 SA
RG-E
SG-E
TR
D-57A
COMPUTER RM
D-57 x1
R
A
14ø SA
10x14 SA
SS-D57A
SG-E
10x14/150
RG-E
12x12/100
TR
D-57A
COMPUTER RM
D-57
SS-D57A3
3/4"CD
REF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
KEYPLAN N
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
A/E:
ACRE
A BW
CE DE
1A
BE
CW DW
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.M
P F
P R
.r v t
/1
/2
:3
:2
A
M
B01-MH200A
BASEMENT LEVEL MECHANICAL PLANS -
SECTION A
EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24th Avenue South Nashville, TN 37212
626-22-700
02/16/2024 MatKah CasHos
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
IMEG
101 N SEVENTH STREET
LOUISVILLE, KY 40202
502.415.7814
SCALE: 1/16" = 1'-0"B01-MH200A
1 BASEMENT LEVEL MECHANICAL PLAN - SECTION A
SCALE: 1/4" = 1'-0"B01-MH200A
2 BASEMENT LEVEL MECHANICAL DEMOLITION PLAN - TR D-57A
SCALE: 1/4" = 1'-0"B01-MH200A
3 BASEMENT LEVEL VENTILATION PLAN - TR D-57A
SCALE: 1/4" = 1'-0"B01-MH200A
4 BASEMENT LEVEL PIPING PLAN - TR D-57A
SHEET NOTES:
1. DRIP PANS TO BE PROVIDED UNDER ALL
EXISTING HYDRONIC, PLUMBING, AND FIRE
PROTECTION PIPING OVERHEAD IN TR
SPACES. FOR CLARITY, DRIP PANS ARE ONLY
SHOWN ON PLUMBING DRAWINGS.
MECHANICAL CONTRACTOR SHALL
COORDINATE WITH PLUMBING CONTRACTOR
TO VERIFY ALL EXISTING AND NEW PIPING
OVERHEAD ARE PROVIDED WITH DRIP PAN
COVERAGE.
2. DO NOT SPILL CONDENSATE PIPING INTO DRIP
PANS OVER TR SPACES. COORDINATE
INSTALLATION OF REFRIGERANT AND
CONDENSATE PIPING WITH DRIP PAN
LOCATIONS. AVOID PENETRATIONS OF NEW
DRIP PANS. SEAL ANY NECESSARY
PENETRATIONS WATER TIGHT.
3. TEMPERATURE CONTROLS CONTRACTOR
SHALL COORDINATE LOCATION OF ALL DRIP
PANS FOR LEAK DETECTION MONITORING.
4. TEMPERATURE CONTROLS CONTRACTOR
SHALL BE RESPONSIBLE FOR INTEGRATION OF
MONITORING OF ALL TEMPERATURE AND
HUMIDITY SENSORS INTO EXISTING FACILITY
CONTROLS SYSTEM.
5. ELECTRICAL AND TELECOMMUNICATIONS
EQUIPMENT SHOWN FOR REFERENCE ONLY.
KEYNOTES:
1. EXISTING BOTTOM TAPPED RETURN GRILLE TO
REMAIN.
2. EXISTING THERMOSTAT SERVING DEDICATED
VAV BOX TO REMAIN. DISABLE HEATING.
3. INSTALL WALL MOUNTED SPLIT SYSTEM PER
MANUFACTURER'S INSTRUCTIONS.
COORDINATE EXACT LOCATION WITH
ELECTRICAL AND TELECOMMUNICATIONS
CONTRACTORS.
4. REBALANCE EXISTING AIR DEVICE TO CFM
INDICATED.
5. INSTALL NEW COMBINATION
TEMPERATURE/HUMIDITY SENSOR ON WALL
ADJACENT TO LIGHT SWITCH. TCC TO
INTEGRATE SENSOR INTO EXISTING FMCS.
REFER TO SHEET MH700 FOR ADDITIONAL
INFORMATION.
6. ROUTE CONDENSATE DRAIN PIPING ABOVE
CEILING TO HAC. ROUTE PIPING DOWN WALL
AND SPILL INTO MOP BASIN.
7. ROUTE REFRIGERANT LINESET, SIZED PER
MANUFACTURER'S RECOMMENDATIONS, AS
INDICATED. REFER TO SHEET B01-MH201A FOR
CONTINUATION.
8. EXISTING VAV TO BE REBALANCED PER
AIRFLOWS INDICATED. DISABLE HEATING TO
VAV. CONTRACTOR TO VERIFY EXACT
LOCATION OF EXISTING EQUIPMENT.
N
0 16' 32'8'
N
0 4' 8'2'
A.1 A.2 A.3 A.4 A.5 A.6 A.7 A.8 A.9 A.10 A.11
A.A
A.B
A.C
A.D
A.E
CRAWL
MECH EQUIP
F-10
COMPRESSOR RM
F-12
TRANSFORMER
ROOM
F-14
F-11
SHOP
F-9
CB-F4
STORAGE
F-9B
Room
F-13
ELECTRICAL
CLOSET
F-12A
OFFICE
F-11A
FILTER STORAGE
F-6A
OFFICE
F-4
OFFICE
F-3
DUCT SHAFT
ELECTICAL CLOSET
F-2
JANITOR CLST
F-1ELEVATOR LOBBY
CB-F1IRM
OFFICE
F-6B
HOUSEKEEPING
F-6
STORAGE
F-9C
ELEVATOR
FS-2
VACANT
Room
A-400
PEN
D-19A
MAGNETIC RM
Room
FS-1
ELEVATOR
EQUIPMENT
F-7A
MECH EQUIP
CRAWL SPACE
F-8
CONTROL RM
F-11B
HOUSE KEEPING
STORAGE
Room
F-5
STORAGE
TELEPHONE
CLOSET
F-2A
OFFICE
F-9A
OTHER
F-7C
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
KEYPLAN N
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
A/E:
ACRE
A BW
CE DE
1A
BE
CW DW
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.M
P F
P R
.r v t
/1
/2
:3
:2
A
M
B01-MH200ACRE
BASEMENT LEVEL MECHANICAL PLANS -
SECTION ACRE
EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24th Avenue South Nashville, TN 37212
626-22-700
02/16/2024 MatKah CasHos
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
IMEG
101 N SEVENTH STREET
LOUISVILLE, KY 40202
502.415.7814
SCALE: 1/16" = 1'-0"B01-MH200ACRE
1 BASEMENT LEVEL MECHANICAL PLAN - SECTION ACRE
N
0 16' 32'8'
SHEET NOTES:
1. THIS DRAWING SHOWN FOR REFERENCE
ONLY. NO SCOPE IN THIS AREA.
T H
T H
B
14 15 16
17 18 19 20 21 21.5 22 23
TR
E-15
CORRIDOR
CB-18
STORAGE
D-68C
E-10
OFFICE
E-09D
OFFICE
E-09C
OFFICE
E-09B
STORAGE
E-09A
STAFF TOILET
E-08
ELEVATOR
P-9
TOILET
E-12
OFFICE
E-09J
OFFICE
E-09H
OFFICE
E-09G
OFFICE
E-09F
RECIEVING & ISSUE
AREA EQUIPMENT
STORAGE
E-22
ELEVATOR EQUIP
E-13
ELECTRICAL
E-17
PEST CONTROL
OFFICE
E-18
OFFICE
E-22A
MED GAS
E-21
MED GAS
E-20
RECIEVING AND
SHIPPING DOCK
OFFICE
E-11A
E-10A
SWITCH GEAR
E-11
STORAGE
E-23A
STORAGE
E-23
MAIL RM
E-14
EQUP RM
E-19
BUSINESS RM
E-09I
VESTIBULE
E-09
MULTI PURPOSE
E-09E
CORRIDOR
CB-17
CORRIDOR
CB-18
TOILET
E-18B
PEST CONTROL
WORK ROOM
E-18A
B01-MH200BE
B01-MH200BE
B01-MH200BE
REF
ELECTRICAL
E-17
SIGNAL
E-15
OFFICE
E-14A
SIGNAL
E-16 x2
S
A
10x6 SA
22x22 SA
1 1/2"CHR
1 1/2"CHS
3/4"CD1 1/2"CHR
1 1/2"CHS
10x6 RA x6
R A10x6 RA
TR
E-15 x2
S
A
10x6 SA
22x22 SA
SS-E15
SG-1
8x6/50
10x6 RA x6
R A
10x6 RA
TR
E-15
SS-E15
R E
F
3/4"CD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
KEYPLAN N
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
A/E:
ACRE
A BW
CE DE
1A
BE
CW DW
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.M
P F
P R
.r v t
/1
/2
:3
:2
A
M
B01-MH200BE
BASEMENT LEVEL MECHANICAL PLANS -
SECTION BE
EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24th Avenue South Nashville, TN 37212
626-22-700
02/16/2024 MatKah CasHos
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
IMEG
101 N SEVENTH STREET
LOUISVILLE, KY 40202
502.415.7814
SCALE: 1/16" = 1'-0"B01-MH200BE
1 BASEMENT LEVEL MECHANICAL PLAN - SECTION BE
SCALE: 1/4" = 1'-0"B01-MH200BE
2 BASEMENT LEVEL MECHANICAL DEMOLITION PLAN - TR E-15
SCALE: 1/4" = 1'-0"B01-MH200BE
3 BASEMENT LEVEL VENTILATION PLAN - TR E-15
SCALE: 1/4" = 1'-0"B01-MH200BE
4 BASEMENT LEVEL PIPING PLAN - TR E-15
SHEET NOTES:
1. DRIP PANS TO BE PROVIDED UNDER ALL
EXISTING HYDRONIC, PLUMBING, AND FIRE
PROTECTION PIPING OVERHEAD IN TR
SPACES. FOR CLARITY, DRIP PANS ARE ONLY
SHOWN ON PLUMBING DRAWINGS.
MECHANICAL CONTRACTOR SHALL
COORDINATE WITH PLUMBING CONTRACTOR
TO VERIFY ALL EXISTING AND NEW PIPING
OVERHEAD ARE PROVIDED WITH DRIP PAN
COVERAGE.
2. DO NOT SPILL CONDENSATE PIPING INTO DRIP
PANS OVER TR SPACES. COORDINATE
INSTALLATION OF REFRIGERANT AND
CONDENSATE PIPING WITH DRIP PAN
LOCATIONS. AVOID PENETRATIONS OF NEW
DRIP PANS. SEAL ANY NECESSARY
PENETRATIONS WATER TIGHT.
3. TEMPERATURE CONTROLS CONTRACTOR
SHALL COORDINATE LOCATION OF ALL DRIP
PANS FOR LEAK DETECTION MONITORING.
4. TEMPERATURE CONTROLS CONTRACTOR
SHALL BE RESPONSIBLE FOR INTEGRATION OF
MONITORING OF ALL TEMPERATURE AND
HUMIDITY SENSORS INTO EXISTING FACILITY
CONTROLS SYSTEM.
5. ELECTRICAL AND TELECOMMUNICATIONS
EQUIPMENT SHOWN FOR REFERENCE ONLY.
N
0 16' 32'8'
N
0 4' 8'2'
KEYNOTES:
1. REMOVE EXISTING CEILING DEVICE. DEMOLISH
DUCT TO POINT INDICATED AND CAP. SEAL
DUCT AND REPAIR INSULATION AS REQUIRED.
PATCH AND REPAIR OPENING IN WALL TO
MATCH ADJACENT SURFACES AND RATINGS.
2. DEMOLISH EXISTING PIPING BACK TO MAIN
AND CAP.
3. DEMOLISH EXISTING PRECISION COOLING UNIT
AND ASSOCIATED DUCTWORK, PIPING,
SUPPORTS, HANGERS, CONTROLS, WIRING,
ETC. COMPLETE. TURN UNIT AND WALL
MOUNTED SENSOR OVER TO FACILITY.
4. DEMOLISH EXISTING CONDENSATE DRAIN
PIPING AND ALL HANGERS, SUPPORTS, ETC.
DOWN TO DRAIN. EXISTING DRAIN TO REMAIN.
5. INSTALL WALL MOUNTED SPLIT SYSTEM PER
MANUFACTURER'S INSTRUCTIONS.
COORDINATE EXACT LOCATION WITH
ELECTRICAL AND TELECOMMUNICATIONS
CONTRACTORS.
6. CONNECT TO EXISTING DUCT AND PROVIDE
NEW SIDEWALL GRILLE MOUNTED TO END OF
DUCT. REBALANCE EXISTING DEVICES ON
SYSTEM TO ACCOMMODATE CFM IN NEW TR.
REBALANCING SHALL MAINTAIN REQUIRED
SPACE PRESSURIZATIONS.
7. INSTALL NEW COMBINATION
TEMPERATURE/HUMIDITY SENSOR ON WALL
ADJACENT TO LIGHT SWITCH. TCC TO
INTEGRATE SENSOR INTO EXISTING FMCS.
REFER TO SHEET MH700 FOR ADDITIONAL
INFORMATION.
8. ROUTE 3/4" CONDENSATE DRAIN PIPING AS
INDICATED. HOLD TIGHT TO WALL. ROUTE
PIPING DOWN WALL AND SPILL INTO EXISTING
DRAIN. TERMINATE PIPING WITHIN DRAIN.
9. ROUTE REFRIGERANT LINESET, SIZED PER
MANUFACTURER'S RECOMMENDATIONS, AS
INDICATED. REFER TO SHEET B01-MH201BW
FOR CONTINUATION.
B
C
D
E
F
G
H
J
14 15 16 17 18 19 20 21 21.5 22 23
CORRIDOR
CB-18
PROCEDURE RM
D-59
SWITCHBOARD
ROOM
D-67 ELECTRICAL SHOP
STORAGE
D-68A
ELECTRIC SHOP
D-68
ELECTRONICS
D-68B
STAFF
D-65A
STAFF
D-65B
STAFF
D-65C
STAFF
D-65D
STAFF
D-65E
RESIDENT/INTERN
D-65F
CONFERENCE/CLASS
RM
D-65G
RECEPTION & SEC
D-65H
OFFICE
D-71
MULTIPURPOSE
D-73A
ELECTRICAL
ENGINEERING
D-70
CLERICAL OFFICE
D-73B
OFFICE
D-73C
OFFICE
D-73D
STORAGE
D-74A
MAINTAINENCE
FOREMAN
E-07 OFFICE
A/C FOREMAN
E-06
PAINT SHOP
E-05
A/C SHOP
E-27
CARPENTER SHOP
E-04
MACHINE SHOP
E-03
ELEC CLOSET
E-26A
PLUMBING SHOP
E-02
BIOMEDICAL ENGG
STORGAE
E-01B
OFFICE
E-01C
BLDG MGT
LOCKERS
B-03
ENGG LOCKERS
B-04
Room
A-542 Room
A-543
HAC
B-05
RECIEVING AND
CLEANING
E-01A
BIOMED ENG
REPAIRING AND
DEVELOPMENT
E-01
BOILER ROOM
E-25F
BOILER OPERATOR
E-25E
FLAME STORAGE
E-24
OFFICE
E-25C
GROUND & TRANS
E-25D GROUND EQUIP
E-25
CLOSET
E-25A
A/C OPERATIONS
E-25B
SVC RM
E-26
KEY SHOP
D-69
CORRIDOR
CB-17
CORRIDOR
CB-18
OFFICE
D-73Room
A-573
AUTOATED
RADIOGRAPHIC
D-60
CONTROL RM
D-61
CHEST ROOM
D-62
TOILET
D-63
TOILET
D-64
D-66
CORRIDOR
CB-16
CORRIDOR
CB-16B
EMERGENCY
GENERATOR RM
E-25G
EMERGENCY
GENERATOR
E-25H
STAIR
NO.8
ELEVATOR LOBBY
CB-10A
ELEVATOR LOBBY
CB-16D
VESTIBULE
OFFICE
D-74
ELEVATOR
ELEVATOR
S-2
ELEVATOR
P-3
ELEVATOR
P-4
ELEVATOR
P-5
TOILET
MECH
E-5
OFFICE
CORRIDOR
CB-16C
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
KEYPLAN N
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
A/E:
ACRE
A BW
CE DE
1A
BE
CW DW
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.M
P F
P R
.r v t
/1
/2
:3
:3
A
M
B01-MH200BW
BASEMENT LEVEL MECHANICAL PLAN -
SECTION BW
EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24th Avenue South Nashville, TN 37212
626-22-700
02/16/2024 MatKah CasHos
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
IMEG
101 N SEVENTH STREET
LOUISVILLE, KY 40202
502.415.7814
SCALE: 1/16" = 1'-0"B01-MH200BW
1 BASEMENT LEVEL MECHANICAL PLAN - SECTION BW
N
0 16' 32'8'
SHEET NOTES:
1. THIS DRAWING SHOWN FOR REFERENCE
ONLY. NO SCOPE IN THIS AREA.
1 2 3
4 5 6 7 8 9 10 11 12 13 14
K
L
M
N C.I
C.G1 P
TR
A-11
EMBALMING
A-03
REFRIGERATOR
AUTOPSY
A-02
MENS RESTROOM
WOMENS
RESTROOM
CORRIDOR
CB-6
EQUIPMENT
ELEVATOR
A-05
ELEVATOR
S-1
FEMALE TOILET
A-06
CENTRAL STORAGE
A-17G
CHEM SUPER LEAD
TECH
A-17F
OFFICE
A-07
HAC
A-08
PATH CHIEF
A-09
HEMA SUPER
A-17C
LEAD TECH
A-17D
LEAD TECH
A-17E
MULTIPURPOSE
A-17B
MALE TOILET
A-12 MALE TOILET
A-13
BLOOD BANK
A-14
OFFICE
A-14A
ELECTRICAL
CLOSET
A-15BA2
HEMATOLOGY
CHEMISTRY
A-17
SPECIMEN
RECEIVING
URINANALYSIS
COMM CLOSET
A-17A
SEC
A-25H
CHIEF
A-25I
VIEWING/CONFERENCE
A-25J
LABORATORY LOW
LEVEL INVITRO
COUNTING
A-25K
EXAM
A-25L
LAB HIGH LEVEL IN
VITRO COUNTING
A-25M
BIOCHEMISTRY LAB
A-25N
HOT LAB
A-25O
RADIATION SAFETY
& EQUIP RM
A-25P
NUCLEAR
CARDIOLOGY
A-25Q
ELECTRICAL
CLOSET
A-25R
EQUIP STORAGE
A-25S
NUCLEAR IMAGING
A-25T
TELE EQUIP EXPANS
A-22
EXIST TELEPHONE
EQUIP RM
580 ELECTRICAL
CLOSET
A-22A
ANCILLARY LISTING
A-21
FLOW CYTO
A-20A
TISSUE TYP
A-20
OFFICE
A-04B
OFFICE
A-04A
FLOW CYTOMETRY
A-04
ELECTRICAL
CLOSET
A-16
MULTIPURPOSE
A-19A
LAB SEC
A-19
OFFICE
A-19F
OFFICE
A-19E
OFFICE
A-19D
OFFICE
A-19C
EXAM RM
A-OV
HAC
A-25W
FEMALE TOILET
A-25A
MALE TOILET
A-25B
OFFICE HOUSE
STAFF
A-25C
Room
A-18
OFFICE
OFFICE
A-19B
ELECTRICAL
CLOSET
A-27
COMPUTER RM
A-25U
ELECTRICAL
CLOSET
A-26
RCPT & FILES
A-25
Room
A-663
CORRIDOR
CORRIDOR
A-673
CORRIDOR
CB-9D
Room
A-679
CORRIDOR
CB-8
CORRIDOR
CB-9A
CORRIDOR
CB-9
WAITING RM
A-25X
CORRIDOR
CB-10
CORRIDOR
B01-MH200CE
B01-MH200CE
B01-MH200CE
3/4"CD
REF
FEMALE TOILET
A-11
CORRIDOR
FEMALE TOILET
A-10
10x10 EA
10x10 SA
2 1
TR
A-11
CORRIDOR
10x10 SA
10x10 EA
SG-1
8x6/50
SS-A11.1 SS-A11.2
TR
A-11
CORRIDOR
SS-A11.1 SS-A11.2
/4
"C D
3/4"CD
3/4"CD
R
EF
REF
REF
REF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
KEYPLAN N
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
A/E:
ACRE
A BW
CE DE
1A
BE
CW DW
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.M
P F
P R
.r v t
/1
/2
:3
:3
A
M
B01-MH200CE
BASEMENT LEVEL MECHANICAL PLAN -
SECTION CE
EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24th Avenue South Nashville, TN 37212
626-22-700
02/16/2024 MatKah CasHos
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
IMEG
101 N SEVENTH STREET
LOUISVILLE, KY 40202
502.415.7814
SCALE: 1/16" = 1'-0"B01-MH200CE
1 BASEMENT LEVEL MECHANICAL PLAN - SECTION CE
SCALE: 1/4" = 1'-0"B01-MH200CE
2 BASEMENT LEVEL MECHANICAL DEMOLITION PLAN - TR A-11
SCALE: 1/4" = 1'-0"B01-MH200CE
3 BASEMENT LEVEL VENTILATION PLAN - TR A-11
SCALE: 1/4" = 1'-0"B01-MH200CE
4 BASEMENT LEVEL PIPING PLAN - TR A-11
SHEET NOTES:
1. DRIP PANS TO BE PROVIDED UNDER ALL
EXISTING HYDRONIC, PLUMBING, AND FIRE
PROTECTION PIPING OVERHEAD IN TR
SPACES. FOR CLARITY, DRIP PANS ARE ONLY
SHOWN ON PLUMBING DRAWINGS.
MECHANICAL CONTRACTOR SHALL
COORDINATE WITH PLUMBING CONTRACTOR
TO VERIFY ALL EXISTING AND NEW PIPING
OVERHEAD ARE PROVIDED WITH DRIP PAN
COVERAGE.
2. DO NOT SPILL CONDENSATE PIPING INTO DRIP
PANS OVER TR SPACES. COORDINATE
INSTALLATION OF REFRIGERANT AND
CONDENSATE PIPING WITH DRIP PAN
LOCATIONS. AVOID PENETRATIONS OF NEW
DRIP PANS. SEAL ANY NECESSARY
PENETRATIONS WATER TIGHT.
3. TEMPERATURE CONTROLS CONTRACTOR
SHALL COORDINATE LOCATION OF ALL DRIP
PANS FOR LEAK DETECTION MONITORING.
4. TEMPERATURE CONTROLS CONTRACTOR
SHALL BE RESPONSIBLE FOR INTEGRATION OF
MONITORING OF ALL TEMPERATURE AND
HUMIDITY SENSORS INTO EXISTING FACILITY
CONTROLS SYSTEM.
5. ELECTRICAL AND TELECOMMUNICATIONS
EQUIPMENT SHOWN FOR REFERENCE ONLY.
KEYNOTES:
1. REMOVE EXISTING CEILING DEVICE. DEMOLISH
DUCT TO POINT INDICATED AND CAP. SEAL
DUCT AND REPAIR INSULATION AS REQUIRED.
2. REMOVE EXISTING CEILING DEVICE. DEMOLISH
DUCT TO POINT INDICATED AND PREPARE FOR
RECONNECTION.
3. INSTALL WALL MOUNTED SPLIT SYSTEM PER
MANUFACTURER'S INSTRUCTIONS.
COORDINATE EXACT LOCATION WITH
ELECTRICAL AND TELECOMMUNICATIONS
CONTRACTORS.
4. CONNECT TO EXISTING DUCT AND PROVIDE
NEW SIDEWALL GRILLE MOUNTED TO END OF
DUCT. REBALANCE EXISTING DEVICES ON
SYSTEM TO ACCOMMODATE CFM IN NEW TR.
REBALANCING SHALL MAINTAIN REQUIRED
SPACE PRESSURIZATIONS.
5. INSTALL NEW COMBINATION
TEMPERATURE/HUMIDITY SENSOR ON WALL
ADJACENT TO LIGHT SWITCH. TCC TO
INTEGRATE SENSOR INTO EXISTING FMCS.
REFER TO SHEET MH700 FOR ADDITIONAL
INFORMATION.
6. ROUTE CONDENSATE DRAIN PIPING ABOVE
CEILING TO HAC. ROUTE PIPING DOWN WALL
AND SPILL INTO MOP BASIN.
7. ROUTE REFRIGERANT LINESET, SIZED PER
MANUFACTURER'S RECOMMENDATIONS, AS
INDICATED. TURN PIPING UP IN EXISTING
CHASE. REFER TO SHEET B01-MH201CE FOR
CONTINUATION.
N
0 16' 32'8'
N
0 4' 8'2'
6 7 8 9 10 11 12 13 14
C.G1 P
R C.G
C.F
C.E
C.D
C.C
C.1 C.2 C.3 C.4 C.4.1C.4.2C.5 C.5.1 C.6 C.7 C.8 C.9 C.10
FAN RM -4
B-B105
PV CV LAB #1
B-B101I
CONTROL #1
B-B101J
EPS CV LAB #2
B-G127J
CV EQUIP #2
B-B101N
VIEW
B-G127O
CV EQUIP #3
B-B101P
CV LAB #3
B-B101O
SOILED UTIL
B-B101E
MULTIPURPOSE
B-G127S
CLEAN SUPPLY
B-G127R
Room
B-G127Y
CHANGE
COR
B-G127Z
TLT
B-B101G
CLEAN LINEN
B-G127AA
PREP/HOLDING
B-G127T
G-09H
CONTROL #2
B-B101Q
G-09G
OFFICE
G-04
ELEVATOR
P-8
TLT
1-G127W
OFFICE
ON CALL
G-16
DRESSING &
HOLDING
A-161
TOILET
G-15A
TOILET
G-15B
OFFICE
G-07
CONFERENCE RM
G-14
SEC
G-13
CHIEF
G-08
OFFICE
G-11
HAC
G-12
STORAGE
CB-5
WC ALCOVE
SUB STERILE
G-19A
OPERATING RM
GENERAL
G-19 OPERATING RM
GENERAL
G-21
EQUIPMENT
G-20
HOLDING
G-17
CONTROL
G-03
OFFICE
G-02B
OFFICE
G-02A
CLERICAL
G-02
OFFICE
G-02C
G-20A
G-20B
G-20C
HAC
B-B101H
STAIR
NO. 2
FLOW CYTOMETRY
A-04
CORRIDOR
CORRIDOR
CB-4
STRETCHER
ALCOVE
CORRIDOR
Room
A-756
CORRIDOR
CB-2
CORRIDOR
CB-6A
FROZEN SECTION
G-18
ALCOVE
B-G127VALCOVE
B-G127BB
Room
A-766
ALCOVE
B-G127W
ALCOVE
B-G127X
CORRIDOR
B-G127F
CORRIDOR
CB-7
AREAWAY
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
KEYPLAN N
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
A/E:
ACRE
A BW
CE DE
1A
BE
CW DW
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.M
P F
P R
.r v t
/1
/2
:3
:4
A
M
B01-MH200CW
BASEMENT LEVEL MECHANICAL PLAN -
SECTION CW
EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24th Avenue South Nashville, TN 37212
626-22-700
02/16/2024 MatKah CasHos
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
IMEG
101 N SEVENTH STREET
LOUISVILLE, KY 40202
502.415.7814
SCALE: 1/16" = 1'-0"B01-MH200CW
1 BASEMENT LEVEL MECHANICAL PLAN - SECTION CW
SHEET NOTES:
1. THIS DRAWING SHOWN FOR REFERENCE
ONLY. NO SCOPE IN THIS AREA.
N
0 16' 32'8'
14 15 16 17 18 19 20 21 21.5 22 23
24 25 26 27 28
K
L
M
N C.I
C.G1 P
CLEAN CORE
SUPPORT
G-34
STAIR
NO. 1
VEST
B-01R
ANEST WORK RM
B-07
WORK ROOM
G-35
ANTE ROOM 3
B-02A
VESTIBULE
B-01E
STORAGE
B-01F
HAC
B-01H
TOILET
B-01G
STUDY CUBICLES
A-25G
STAFF PHYSICIAN
OFFICE
A-25F
STAFF
NON-PHYSICIAN
OFFICE
A-25E
ELECTRICAL
CLOSET
A-22A
FEMALE TOILET
A-25A
MALE TOILET
A-25B
OFFICE HOUSE
STAFF
A-25C
STAFF LOUNGE
A-25D
EXIST FIRE ALARM
PANELS
A-23
DECONTAMINATION
ROOM
B-02
PREPARATION,
ASSEMBLY &
STERILIZATION
B-02C
CART WASH
MEDICATOR ROOM
STERILE STORAGE
B-02F
ANTE ROOM 2
B-2Ec
ANTE ROOM 1
B-02Ea
SCOPE STAGING
ANTE ROOM
EQUIP-1
B-02G
EQUIP 2
B-02E
CORRIDOR
B-02Eb
STAIR
NO.10
HAC
G-43
OFFICE
C-09
GAS STORAGE
G-44
FEMALE TOILET
C-08B
FEMALE LOCKER
C-08A MECH RM AHU-26
MALE TOILET
C-08D
MALE LOCKER
C-08C
STAFF
MULTIPURPOSE
C-08
OFFICE
C-07W
BARIATRIC POS RM
C-07V
POS RM
C-07U
ELECTRICAL
CLOSET
C-07D
ELECTRICAL
CLOSET
C-07C
CLOSET
C-07B
HAC
C-06
OFFICE
B-01Q
MALE LOCKERS
B-01O
MALE TOILET
B-01P
CLEAN
EQUIP/SUPPLY
C-05
HEART POS RM
C-07F
ELECTRICAL
CLOSET
C-04
CHASE
C-04A
FEMALE TOILET
B-01N
FEMALE LOCKERS
B-01M
HAC
B-01L
SPD CHIEF & ASSIST
C-01K
MED PREP
C-07A
POS RM
C-07T
POS RM
C-07S
NEG RM
C-07R
SHOWER/TOILET
C-07Q
BARIATRIC NEG RM
C-07P
NED RM
C-07O
SPD
C-07N
NEG RM
C-07L
POS RM
C-07K
POS RM
C-07J
POS RM
C-07I
HEART POS RM
C-07H
Room
A-542 Room
A-543
CONSULT/MEDITATION
C-03A
SOILED
C-07G
WAITING
C-03
Room
A-554
Room
A-555
Room
A-556
LOGISTICS ITEM
MGRS
BREAKOUT AREA
LOGISTICS ITEM
MGRS
B-06
ELECTRICAL RM
RCPT & FILES
A-25
CORRIDOR
CB-9A
CORRIDOR
CB-9
CORRIDOR
CB-16E
OFFICE
C-07M
SPD ADMIN
B-011
LOGISTICS SUPV
B-01J
CORRIDOR
CB-21
RECESS
CORRIDOR
CB-1
STAIR
NO. 9
ELEVATOR LOBBY
CB-16D
SPD VESTIBULE
B-01A Room
B-01B
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
KEYPLAN N
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
A/E:
ACRE
A BW
CE DE
1A
BE
CW DW
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.M
P F
P R
.r v t
/1
/2
:3
:4
A
M
B01-MH200DE
BASEMENT LEVEL MECHANICAL PLAN -
SECTION DE
EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24th Avenue South Nashville, TN 37212
626-22-700
02/16/2024 MatKah CasHos
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
IMEG
101 N SEVENTH STREET
LOUISVILLE, KY 40202
502.415.7814
SCALE: 1/16" = 1'-0"B01-MH200DE
1 BASEMENT LEVEL MECHANICAL PLAN - SECTION DE
N
0 16' 32'8'
SHEET NOTES:
1. THIS DRAWING SHOWN FOR REFERENCE
ONLY. NO SCOPE IN THIS AREA.
T H T H
C.G1 P
R C.G
C.F
C.E
C.D
C.C
C.10 C.11 C.12 C.13C.13.1C.14C.15C.15.1 C.16 C.16.2 C.16.3C.17C.17.1C.18 C.19 C.20 C.20.1
TR
D-001
VESTIBULE
CB-22A
OPERATING RM
GENERAL
G-21 SUB STERILE
G-21A
GENERAL
OPERATING RM
G-25
OFFICE
G-02D
OFFICE
G-02E
G-20A
G-20B
G-20C
REC & OR HEAD
NURSES
G-01
ELECTRICAL
CLOSET
G-22
ELECTRICAL
CLOSET
PHONE/ SGNL RM
PHYSICIAN LOUNGE
G-24
STAFF LOUNGE
G-23
ELEVATOR
P-6
ELEVATOR
P-7
MALE TOILET &
SHOWER
G-24A MALE LOCKERS
G-24B
FEMALE TOILET
G-23C
DICTATING
G-23A
FEMALE LOCKERS
G-23D
FEMALE SHOWER
G-23B
NEUROSURGERY OR
G-36
SUB STERILE
G-37
PUMP TECHS PREP
RM
G-36A
EXT RAD CONTROL
G-32
CARDIAC OR 8
G-38
OFFICE
G-31
ORTHOPEDIC OR 7
G-39
CLEAN CORE
CB-3
OPERATING RM
GENERAL
G-26
SUB STERILE
G-26A
SCRUB
CB-3B
OPERATING RM
GENERAL
G-27
EQUIP STORAGE
G-40
PLASTER & SPLINTS
G-41
SUB STERILE
G-42
OFFICE
G-28
EQUIP
G-28A
SCRUB UP ALCOVE
G-30
SCRUB UP ALCOVE
G-29
CLEAN CORE
SCRUB-UP ALCOVE
G-33
SCRUB UP ALCOVE
CB-3C
EMERGENCY
GENERATOR
B-G124B
ELECTRICAL
B-G124A
FAN RM 5
B-G124
RECOVERY
STORAGE
G-56B
SOILED UTILITY
G-56A
RECOVERY
ISOLATION
BEDROOM
G-54
ANTE RM
G-56C
RECOVERY
ISOLATION
BEDROOM
G-52
FEMALE STAFF
TOILET
G-51
PACU
G-50
SICU
G-56
FEMALE STAFF
TOILET
G-55
RECOVERY CLEAN
UTILITY
G-56E
CLEAN LINEN
G-56D
ELECTRICAL
CLOSET
G-49BTELE
G-49C
ALCOVE
G-49
SIGNAL
G-49A
OFFLINE
MONITORING
G-47
ON CALL
G-48
BATH
G-48A
CLOSET
G-46
STAIR
NO.10
HAC
G-43
CORRIDOR
CB-22
CORRIDOR
CB-4
STRETCHER
ALCOVE
WC ALCOVE
CORRIDOR
STRETCH ALCOVE
CB-24A
Room
A-757
CORRIDOR
CB-1
CORRIDOR
CB-2C
CORRIDOR
CB-2B
B01-MH200DW
B01-MH200DW
B01-MH200DW
OFFLINE MONITORING
G-47
CORRIDOR
CB-22
x1
R
A
12x6 RA
12x6 RA x8
R A
FSD
212x6 SA
SD-E
8/180
RG-E
RG-E
SD-E
8/190
VAV-E
24x12 OA
TR
D-001
VESTIBULE
CB-22A
OFFLINE MONITORING
G-47
CORRIDOR
CB-22
x S
A x1
R
A
12x6 SA
12x6 SA
SG-1
8x6/50
SD-1
8/130
SS-D001
x8
R A
VAV-E
SD-E
8/190
RG-E
RG-E
24x12 OA
8x6 SA
TR
D-001
VESTIBULE
CB-22A
OFFLINE MONITORING
G-47
CORRIDOR
CB-22
SS-D001
REF
3/4"CD
3/4"CD
/4
"C D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
KEYPLAN N
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
A/E:
ACRE
A BW
CE DE
1A
BE
CW DW
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.M
P F
P R
.r v t
/1
/2
:3
:5
A
M
B01-MH200DW
BASEMENT LEVEL MECHANICAL PLAN -
SECTION DW
EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24th Avenue South Nashville, TN 37212
626-22-700
02/16/2024 MatKah CasHos
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
IMEG
101 N SEVENTH STREET
LOUISVILLE, KY 40202
502.415.7814
SCALE: 1/16" = 1'-0"B01-MH200DW
1 BASEMENT LEVEL MECHANICAL PLAN - SECTION DW
SCALE: 1/4" = 1'-0"B01-MH200DW
2 BASEMENT LEVEL MECHANICAL DEMOLITION PLAN - TR D-001
SCALE: 1/4" = 1'-0"B01-MH200DW
3 BASEMENT LEVEL VENTILATION PLAN - TR D-001
SCALE: 1/4" = 1'-0"B01-MH200DW
4 BASEMENT LEVEL PIPING PLAN - TR D-001
SHEET NOTES:
1. DRIP PANS TO BE PROVIDED UNDER ALL
EXISTING HYDRONIC, PLUMBING, AND FIRE
PROTECTION PIPING OVERHEAD IN TR
SPACES. FOR CLARITY, DRIP PANS ARE ONLY
SHOWN ON PLUMBING DRAWINGS.
MECHANICAL CONTRACTOR SHALL
COORDINATE WITH PLUMBING CONTRACTOR
TO VERIFY ALL EXISTING AND NEW PIPING
OVERHEAD ARE PROVIDED WITH DRIP PAN
COVERAGE.
2. DO NOT SPILL CONDENSATE PIPING INTO DRIP
PANS OVER TR SPACES. COORDINATE
INSTALLATION OF REFRIGERANT AND
CONDENSATE PIPING WITH DRIP PAN
LOCATIONS. AVOID PENETRATIONS OF NEW
DRIP PANS. SEAL ANY NECESSARY
PENETRATIONS WATER TIGHT.
3. TEMPERATURE CONTROLS CONTRACTOR
SHALL COORDINATE LOCATION OF ALL DRIP
PANS FOR LEAK DETECTION MONITORING.
4. TEMPERATURE CONTROLS CONTRACTOR
SHALL BE RESPONSIBLE FOR INTEGRATION OF
MONITORING OF ALL TEMPERATURE AND
HUMIDITY SENSORS INTO EXISTING FACILITY
CONTROLS SYSTEM.
5. ELECTRICAL AND TELECOMMUNICATIONS
EQUIPMENT SHOWN FOR REFERENCE ONLY.
KEYNOTES:
1. DEMOLISH EXISTING LOUVER. COORDINATE
WALL PATCH AND REPAIR WITH
ARCHITECT/GENERAL TRADES CONTRACTOR.
2. REMOVE EXISTING CEILING DEVICE. DEMOLISH
DUCT TO POINT INDICATED AND PREPARE FOR
RECONNECTION.
3. INSTALL WALL MOUNTED SPLIT SYSTEM PER
MANUFACTURER'S INSTRUCTIONS.
COORDINATE EXACT LOCATION WITH
ELECTRICAL AND TELECOMMUNICATIONS
CONTRACTORS.
4. INSTALL NEW SIDEWALL SUPPLY GRILLE
ABOVE DOOR. ROUTE SA DUCT TO EXISTING
LOW PRESSURE DUCTWORK ABOVE CEILING
AND CONNECT.
5. INSTALL NEW COMBINATION
TEMPERATURE/HUMIDITY SENSOR ON WALL
ADJACENT TO LIGHT SWITCH. TCC TO
INTEGRATE SENSOR INTO EXISTING FMCS.
REFER TO SHEET MH700 FOR ADDITIONAL
INFORMATION.
6. 3/4" CONDENSATE DRAIN PIPING FROM ABOVE.
CONNECT 3/4" CD AT THIS LEVEL TO VERTICAL.
7. ROUTE 3/4" CD AS INDICATED ABOVE CEILING
OF VESTIBULE. ROUTE PIPING DOWN WALL OF
MECHANICAL ROOM AND SPILL TO NEAREST
FLOOR DRAIN. TERMINATE PIPING WITHIN
DRAIN BODY.
8. ROUTE REFRIGERANT LINESET, SIZED PER
MANUFACTURER'S RECOMMENDATIONS, UP
THROUGH FLOOR ABOVE. REFER TO SHEET
B01-MH201DW FOR CONTINUATION.
9. DISCONNECT DUCTWORK IN MECHANICAL
ROOM FROM EXISTING LOUVER. REMOVE
LOUVER AND TURN OVER TO STATION.
PREPARE DUCT FOR RECONNECTION.
10. ROUTE NEW DUCT, FULL SIZE OF EXISTING
DUCTWORK, UP THROUGH NEW ROOF AND
TERMINATE WITH GOOSENECK. BOTTOM OF
OA INLET TO BE MINIMUM 3'-0" ABOVE NEW
ROOF. CONTRACTOR TO FIELD VERIFY
EXISTING DUCT SIZE. COORDINATE ROOF
FLASHING WITH ROOFING CONTRACTOR.
N
0 16' 32'8'
N
0 4' 8'2'
SECTION BE
SECTION BW
SECTION BW
SECTION DE
SECTION DE
SECTION DW
SECTION DWSECTION CW
SECTION CE
SECTION CW
SECTION A
SECTION CE
SECTION ACRE
SECTION A
SECTION ACRE SECTION BE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
KEYPLAN N
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
A/E:
ACRE
A BW
CE DE
1A
BE
CW DW
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.M
P F
P R
.r v t
/1
/2
:3
:0
A
M
B01-MH201
FIRST LEVEL MECHANICAL PLAN - OVERALL EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24th Avenue South Nashville, TN 37212
626-22-700
02/16/2024 MatKah CasHos
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
IMEG
101 N SEVENTH STREET
LOUISVILLE, KY 40202
502.415.7814
SCALE: 1" = 20'-0"B01-MH201
1 FIRST LEVEL PLAN - OVERALL
SHEET NOTES:
1. THIS SHEET IS FOR REFERENCE ONLY. REFER
TO ENLARGED VIEWS ON SUBSEQUENT
DRAWINGS FOR ADDITIONAL INFORMATION.
2. HATCHED AREAS INDICATE LOCATIONS OF
NEW OR RENOVATED TELECOMMUNICATION
SPACES.
N
0 20' 40'10'
H T
T H
T
2 3
4 5 6 7 8 9 10 11 12 13
B
C
D
E
F
G
H
J
TR
D-114S
CORRIDOR
C1-24
EXAM
D-120I
EXAM
D-120E
EXAM
D-120F
EXAM
D-120J
EXAM
D-120K D-120L
MECH RM
D-119
MECH RM
D-119A
MALE TOILET
F-107
FEMALE TOILET
F-106
TOILET
D-114K
TOILET
D-114I
CORRIDOR
A-40
EXAM RM
D-114H
EXAM RM
D-114G
EXAM RM
D-113F
EXAM RM
D-114L
TOILET
D-114R
PHARMACY
D-117C
D-117B
EXAM RM
D-114T
EXAM RM
D-114U
SPD
D-114Q
EXAM RM
D-114P
EXAM RM
D-114M
TOILET
D-117A
TREATMENT
D-117
1D1
D-114V
EXAM RM
D-114W
EXAM RM
D-114O
EXAM RM
D-114N
EXAM RM
D-114X
EXAM RM
D-113
CHASE
D-115A
WAITING
D-114
MALE TOILET
D-115
CHECK-IN
D-114AEXAM RM
D-114B
EXAM RM
D-114C
EXAM RM
D-114D
EXAM RM
D-114E
TRIAGE VESTIBULE
D-114F
ENTRY CORRIDOR
C1-12A
CHECK-ING
A-41
SCREENING
D-113A
EXAM RM
D-113B
EXAM RM
D-113C
EXAM RM
D-113D
TOILET
D-113E
EXAM RM
D-113G
EXAM
D-113H
SCREENING
D-113I
PHONE CARE
D-110
ER EMERGENCY
STORAGE
D-112
TELE CLOSET
D-111
TRAVEL OFFICE
D-106PFT
D-107
HAC
D-108
FEMALE PATIENT
TOILET
D-109
STAIR
NO. 4
GROUP ROOM
D-136BB
EXAM 1
D-136AA
ELEVATOR
A-55
ELEVATOR
A-56
ELECTRICAL
CLOSET
C-101A
DIETICIAN
D-101B
SECY
D-102
CHIEF
D-102D
CLERK
D-102B
SUPERINTEND
D-102C
STORAGE
D-102A
TELE CLOSET
D-103
EXAM 13
D-105R
X-RAY
D-105Q
EXAM 14
D-105S
EXAM 15
D-105T
CORRIDOR
D-137
TLT
D-105PDR GROUP
D-137B
CNTRL/SCHEDULING
D-137E
TLT
D-105V
NURSE WRKRM
D-137A
D-104
EXAM 16
D-105U
EXAM
D-105B
EXAM
D-105C EXAM
D-105E
EXAM 5
D-105F
CHECK-IN
D-105HH
NURSE WORK
D-105GG
EXAM 7
D-136F
SPD
D-136G
SUB-STATION
KITCHEN EQUIP 1D
D-101D
SOIL UTIL
D-105H
EXAM 8
D-105I
EXAM
D-105K
EXAM 10
D-105L
EXAM 11
D-105M
TOILET
D-136T
SCULLERY AND
CARTS
D-101C
CENTRAL TRAY
AREA
D-101
REFR
D-101L
MALE TOILET
D-101J
FEMALE TOILET
A-57
FEMALE LOCKER
D-101K
MALE LOCKER
D-101I
FOOD STORAGE
D-101F
SALAD
PREPARATION
D-101H
REFR
D-101G
TELE CLOSET
D-101E
EXAM 3
A-58
CHASE
A-59
EXAM 2
D-136CC
DOCTOR'S GROUP
D-136D
CORRIDOR
C1-9
CORRIDOR
C1-24
Room
C1-25
PHARMACY WAITING
D-116
CORRIDOR
CD1-4
CORRIDOR
CD1-3
CORRIDOR
CD1-2
CORRIDOR
CD1-1
CORRIDOR
A-74
CORRIDOR
C1-23A
CORRIDOR
C1-7
B01-MH201A
B01-MH201A
B01-MH201A
R E
F
3/4"CD
D-117B
EXAM RM
D-114S ø
S A
12x12 RA x1
R
A
"H
W R
"H
W S
1"HWS
1"HWR
1 1/2"HWS
1 1/2"HWR
ø
S A
TR
D-114S
D-117B ø
S A
12x12 RA
SG-1
8x6/50
SS-D114S.1
SS-D114S.2
TR
D-114S
D-117B
SS-D114S.1
7 3/4"CD
3/4"CD
R E
F
1 1/2"HWS
1 1/2"HWR
R E
F
SS-D114S.2
/4
"C D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
KEYPLAN N
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
A/E:
ACRE
A BW
CE DE
1A
BE
CW DW
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.M
P F
P R
.r v t
/1
/2
:3
:0
A
M
B01-MH201A
FIRST LEVEL MECHANICAL PLAN - SECTION A EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24th Avenue South Nashville, TN 37212
626-22-700
02/16/2024 MatKah CasHos
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
IMEG
101 N SEVENTH STREET
LOUISVILLE, KY 40202
502.415.7814
SCALE: 1/16" = 1'-0"B01-MH201A
1 FIRST LEVEL MECHANICAL PLAN - SECTION A
SCALE: 1/4" = 1'-0"B01-MH201A
2 FIRST LEVEL MECHANICAL DEMOLITION PLAN - TR D-114S
SCALE: 1/4" = 1'-0"B01-MH201A
3 FIRST LEVEL VENTILATION PLAN - TR D-114S
SCALE: 1/4" = 1'-0"B01-MH201A
4 FIRST LEVEL PIPING PLAN - TR D-114S
N
0 16' 32'8'
N
0 4' 8'2'
SHEET NOTES:
1. DRIP PANS TO BE PROVIDED UNDER ALL
EXISTING HYDRONIC, PLUMBING, AND FIRE
PROTECTION PIPING OVERHEAD IN TR
SPACES. FOR CLARITY, DRIP PANS ARE ONLY
SHOWN ON PLUMBING DRAWINGS.
MECHANICAL CONTRACTOR SHALL
COORDINATE WITH PLUMBING CONTRACTOR
TO VERIFY ALL EXISTING AND NEW PIPING
OVERHEAD ARE PROVIDED WITH DRIP PAN
COVERAGE.
2. DO NOT SPILL CONDENSATE PIPING INTO DRIP
PANS OVER TR SPACES. COORDINATE
INSTALLATION OF REFRIGERANT AND
CONDENSATE PIPING WITH DRIP PAN
LOCATIONS. AVOID PENETRATIONS OF NEW
DRIP PANS. SEAL ANY NECESSARY
PENETRATIONS WATER TIGHT.
3. TEMPERATURE CONTROLS CONTRACTOR
SHALL COORDINATE LOCATION OF ALL DRIP
PANS FOR LEAK DETECTION MONITORING.
4. TEMPERATURE CONTROLS CONTRACTOR
SHALL BE RESPONSIBLE FOR INTEGRATION OF
MONITORING OF ALL TEMPERATURE AND
HUMIDITY…