The document contains electrical drawings for the EHRM infrastructure upgrades construction project at the Nashville VAMC. The drawings provide detailed specifications and layouts for the electrical work required as part of this construction project. Key details include the project ID, drawing numbers, and the date the drawings were created. No additional information about the required products, services, or solicitation timeline is provided in this attachment.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL ABBREVIATIONS
ABBREVIATION DESCRIPTION
REFER TO OTHER SCHEDULES AND NOTES FOR ADDITIONAL ABBREVIATIONS.
MOUNTING HEIGHT TO CENTERLINE (ABOVE FINISHED FLOOR)
AMPERE
AMPERE FRAME
ABOVE FINISHED FLOOR
ALUMINUM
AMPERE TRIP
CEILING
CRITICAL BRANCH CIRCUIT DESIGNATION
CIRCUIT BREAKER
CORRELATED COLOR TEMPERATURE
COPPER
DATA (WHEN APPLIED TO COMMUNICATIONS OUTLET)
DEMO (WHEN APPLIED TO EXISTING/DEMO ITEMS)
EXISTING
ELECTRICALLY OPERATED
ENERGY REDUCING MAINTENANCE SWITCH
FUSE
FULL LOAD AMPS
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FAULT ALARM
GROUND FAULT PROTECTION
HORSEPOWER
KILOAMPERE INTERRUPTING CAPACITY
KILOVOLT AMPERE
KILOWATT
MAXIMUM
MINIMUM CIRCUIT AMPS
MAIN CIRCUIT BREAKER
MINIMUM
MAIN LUGS ONLY
MANUALLY OPERATED
NORMALLY CLOSED
NON-FUSED
NOT IN CONTRACT
NORMALLY OPEN
POLES
PARTIAL
RELOCATE
SHORT CIRCUIT CURRENT RATING
SURGE PROTECTIVE DEVICE
SHUNT TRIP
TYPICAL
UNLESS NOTED OTHERWISE
VOICE
WALL PHONE
WIRE
WITHSTAND AND CLOSE RATING
WEATHER RESISTANT
TRANSFORMER
ZONE SELECTIVE INTERLOCKING
A
AF
AFF
AL
AT
C
CR
CB
CCT
CU
D
D
E
EO
ERMS
F
FLA
G, GFCI
GFA
GFP
HP
KAIC
KVA
KW
MAX
MCA
MCB
MIN
MLO
MO
NC
NF
NIC
NO
P
PART
R
SCCR
SPD
ST
TYP
UNO
V
W
W
WCR
WR
XFMR
ZSI
A. BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 75' SHALL UTILIZE #10 AWG CONDUCTORS.
RECEPTACLE BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 150' SHALL UTILIZE #8 AWG
CONDUCTORS.
B. FOR ALL CONDUIT AND OTHER ITEMS PENETRATING A FIRE RATED WALL, PROVIDE UL LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL CONSTRUCTION ASSEMBLY AND COMPLIANT WITH ASTM E814. INSTALL SYSTEM IN STRICT COMPLIANCE WITH THE FIRE STOPPING MANUFACTURER’S U.L. APPROVED DETAIL. WHERE EXISTING WALLS ARE BEING UPGRADED TO FIRE RATED WALLS OR THE FIRE RATING IS BEING MODIFIED, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM FOR ALL NEW AND EXISTING PENETRATIONS. REFER TO THE ARCHITECTURAL LIFE
SAFETY PLANS FOR LOCATIONS OF FIRE RATED WALLS.
C. NEW ROOF MOUNTED EQUIPMENT SHALL BE BONDED TO EXISTING BUILDING LIGHTNING PROTECTION SYSTEM IF ONE EXISTS. PROVIDE AIR TERMINALS ON TOP OF EQUIPMENT AND BOND TO EXISTING SYSTEM PER NFPA 780 AND UL 96A REQUIREMENTS. PROVIDE UL INSPECTION AND/OR LPI SYSTEM INSPECTION AS REQUIRED TO OBTAIN UL MASTER LABEL RECERTIFICATION, UL MASTER LABEL AND/OR LPI SYSTEM
CERTIFICATE.
D. ANY ITEMS DAMAGED BY THE CONTRACTOR SHALL BE REPLACED BY THE CONTRACTOR, AT NO ADDITIONAL
COST TO THE OWNER.
E. NEW WIRING DEVICES AND ASSOCIATED COVERPLATES SHALL MATCH EXISTING FINISH OF SIMILAR
INSTALLED DEVICES.
F. THE SELECTED EQUIPMENT AIC RATINGS ARE BASED ON THE IMPEDANCES FOR CONDUCTORS AND TRANSFORMERS USED IN THE CALCULATIONS. IF DIFFERENT EQUIPMENT OR DIFFERENT CONFIGURATIONS
ARE SELECTED FOR INSTALLATION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING
ADEQUATELY RATED EQUIPMENT THAT MEETS APPLICABLE SELECTIVE COORDINATION GOALS AND
PROVIDES SIMILAR INCIDENT ENERGY RISK OF ARC FLASH HAZARDS.
G. PROVIDE AN INSULATED CONTINUOUS COPPER CONDUCTOR, NOT SMALLER THAN #10, TO BOND ALL
NORMAL AND ESSENTIAL ELECTRICAL SYSTEM PANELBOARDS TOGETHER THAT SERVE THE SAME
INDIVIDUAL PATIENT VICINITY AS DEFINED IN NEC 517.14.
H. ALL CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, INCLUDING LIGHTING AND WALL RECEPTACLES, SHALL BE MECHANICALLY PROTECTED PER NEC 517.31(C)(3). NON-FLEXIBLE RACEWAY SHALL BE USED FOR CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, EXCEPT THAT THE FINAL CONNECTION TO VIBRATING EQUIPMENT OR LIGHT FIXTURES IF THE TOTAL LENGTH OF FLEXIBLE RACEWAY IS 6' OR LESS ACROSS THE
ENTIRE CIRCUIT LENGTH.
I. PROVIDE ADDITIONAL SUPPORTS AS REQUIRED TO INDEPENDENTLY SUPPORT ALL EXISTING TO REMAIN
CABLING.
(GENERAL NOTES SHALL APPLY TO ALL SHEETS)
ELECTRICAL GENERAL NOTES:
A. THE INTENT OF THE DEMOLITION DRAWINGS IS TO DEFINE THE SCOPE OF ELECTRICAL DEMOLITION WORK.
EXISTING ELECTRICAL SYSTEMS (DEVICES, FIXTURES, EQUIPMENT, WIRING, AND RACEWAYS INCLUDING DATA/COMMUNICATION SYSTEMS). EXISTING ELECTRICAL SYSTEMS SERVING ADJACENT AREAS SHALL REMAIN UNLESS OTHERWISE INDICATED. RE-SUPPORT EXISTING CONDUITS AND CABLES THAT MUST
REMAIN. REFER TO FLOORPLANS FOR INDICATION OF DEMOLITION TYPE FOR EACH AREA:
• DEMOLITION AREAS INDICATED WITH LIMITS OF DEMOLITION DEFINED:
1. EXISTING ELECTRICAL, LIGHTING, FIRE ALARM, NURSE CALL, ECT... SYSTEMS WITHIN LIMITS
OF DEMOLITION SHALL BE REMOVED UNLESS OTHERWISE INDICATED. SYSTEMS OUTSIDE
THE LIMITS OF DEMOLITION THAT ARE IMPACTED BY THE DEMOLITION SHALL BE MODIFIED
TO OPERATE AS REQUIRED.
B. ITEMS INDICATED WITH A SUBSCRIPT 'E' SHALL BE EXISTING TO REMAIN (E-EXISTING). ITEMS INDICATED WITH A SUBSCRIPT 'D' OR SHOWN DASHED SHALL BE REMOVED (D-DEMOLITION). ITEMS INDICATED WITH A SUBSCRIPT 'R' SHALL BE REMOVED, STORED, AND REINSTALLED PER NEW WORK (R-RELOCATION).
C. THESE DRAWINGS DO NOT IDENTIFY EACH INDIVIDUAL ITEM TO BE REMOVED. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING ITEMS WHICH MUST BE REMOVED TO FACILITATE NEW CONSTRUCTION.
SEE ARCHITECTURAL PLANS FOR EXACT LIMITS OF DEMOLITION AND CONSTRUCTION. THESE PLANS ARE BASED ON PAST PROJECT DRAWINGS AND SITE OBSERVATIONS. THE DRAWINGS ARE PROVIDED TO THE CONTRACTOR AS AN AID IN DETERMINING THE EXTENT OF WORK REQUIRED FOR DEMOLITION AND TO PROVIDE GENERAL INFORMATION ABOUT EXISTING SYSTEMS. THESE DRAWINGS MAY NOT BE ACCURATE IN ALL AREAS. THE CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH EXISTING
CONDITIONS AND IS ENCOURAGED TO REVIEW FACILITY DRAWINGS PRIOR TO THE BID DATE.
D. THE OWNER SHALL HAVE FIRST SALVAGE RIGHTS TO ALL ITEMS REMOVED. IF OWNER REFUSES SALVAGE, CONTRACTOR IS RESPONSIBLE FOR DISPOSAL.
E. WHERE EXISTING WALLS ARE TO BE REMOVED, ALL ASSOCIATED ELECTRICAL EQUIPMENT SHALL BE REMOVED. DISCONNECT POWER SO THAT DEVICES AND EQUIPMENT MAY BE REMOVED WITH WALLS. SEE
ARCHITECTURAL DRAWINGS FOR WALLS TO BE REMOVED. ABANDON CONCEALED CONDUITS WHERE
WALLS ARE NOT REMOVED. CONCEALED CONDUITS MAY BE REUSED WHERE AVAILABLE. WHERE EXISTING CIRCUITING/CABLING IS TO BE DEMOLISHED AND NOT REUSED, REMOVE CONDUCTORS AND ASSOCIATED ACCESSIBLE RACEWAYS/CONDUIT BACK TO THE SOURCE. WHERE EXISTING ELECTRICAL CONDUITS SERVING CIRCUITS TO BE DEMOLISHED ARE EMBEDDED IN CONCRETE FLOORS OR WALLS, CONDUITS MAY BE ABANDONED IN PLACE. EXISTING CONDUCTORS SHALL BE REMOVED BACK TO SOURCE AND CONDUITS SHALL BE CUT AT SURFACE OF CONCRETE AND FILLED. EXISTING BACK BOXES AND CONDUITS REMAINING FROM DEVICES BEING REMOVED MAY BE UTILIZED FOR NEW DEVICES WHERE LOCATIONS PERMIT.
REMOVE AND PATCH WHERE BOXES ARE NOT REUSED.
F. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL ELECTRICAL DEMOLITION ITEMS. DISCONNECT AND REMOVE ELECTRICAL DEVICES, EQUIPMENT AND ASSOCIATED WIRING AS REQUIRED TO ACCOMMODATE NEW WORK. IF THE CONTRACTOR IS UNCLEAR REGARDING A SPECIFIC ITEM TO REMAIN OR BE REMOVED, THE CONTRACTOR SHALL SEEK CLARIFICATION FROM THE ARCHITECT.
G. SYSTEMS SERVING ADJACENT AREAS AND ITEMS THAT REMAIN SHALL BE MAINTAINED AT ALL TIMES.
MODIFY SYSTEMS AS REQUIRED THROUGHOUT CONSTRUCTION TO MAINTAIN CONTINUITY OF SERVICE. DO
NOT INTERRUPT SERVICE WITHOUT OWNER'S PRIOR WRITTEN APPROVAL. LIMIT DURATION OF
INTERRUPTION ONLY TO THE TIME NECESSARY FOR DISCONNECTION AND IMMEDIATE RECONNECTION.
INTERRUPTION TO SERVICE DEEMED BY OWNER AS ESSENTIAL MAY REQUIRE PREMIUM TIME AND SHALL BE INCLUDED WITH THE BID. EXTREME CARE SHALL BE TAKEN BY THE CONTRACTOR TO IDENTIFY EXISTING SYSTEM COMPONENTS ASSOCIATED WITH THESE SERVICES. APPROPRIATE METHODS OF MARKING THESE SHALL OCCUR TO ELIMINATE THE POSSIBILITY OF ACCIDENTAL INTERRUPTION. FOR CONDUIT AND CABLING THAT CAN REMAIN, PROVIDE SUPPORT AS REQUIRED. RELOCATE EXISTING JUNCTION BOXES THAT
BECOME INACCESSIBLE DUE TO NEW WORK.
H. COORDINATE DEMOLITION WITH THE WORK OF OTHER TRADES. PROVIDE TEMPORARY POWER AND
LIGHTING AS REQUIRED TO ALLOW THE WORK OF OTHER TRADES TO PROCEED.
I. PROTECT EXISTING ELECTRICAL EQUIPMENT THAT REMAINS. IF DAMAGED OR DISTURBED IN THE COURSE OF THE WORK, REMOVE DAMAGED PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL CAPACITY, QUALITY, AND FUNCTIONALITY.
J. PATCH AND REPAIR OPENINGS IN EXISTING WALLS AND FLOORS RESULTANT FROM SPECIFIED ELECTRICAL DEMOLITION. PATCH SHALL MATCH EXISTING CONSTRUCTION, FIRE RATING, AND FINISH. SEE
ARCHITECTURAL SPECIFICATIONS FOR MEANS AND METHODS.
K. THIS PROJECT WILL BE PHASED. SEE PROJECT MANUAL AND ARCHITECTURAL PLANS FOR DETAILS.
SYSTEM SERVICES TO AREAS NOT IN THE CURRENT PHASE OF CONSTRUCTION SHALL BE MAINTAINED AT
ALL TIMES.
L. WHERE DEMOLITION OF EQUIPMENT INVOLVES REMOVAL OF EQUIPMENT LOCATED ON CONCRETE HOUSEKEEPING PADS, PADS SHALL ALSO BE REMOVED AND FLOOR/GRADE SHALL BE FINISHED TO MATCH
ADJACENT SURFACE.
M. ALL UNLABELED ELECTRICAL DEVICES WITH CIRCUITRY OR DEVICES MODIFIED DURING CONSTRUCTION THAT EXIST IN ALL ROOMS WHERE THERE IS WORK WITHIN SCOPE SHALL BE CIRCUIT TRACED AS NEEDED
WITH A LABEL PROVIDED.
(ELECTRICAL DEMOLITION NOTES APPLY TO ALL ELECTRICAL DEMOLITION PLANS AND
ALL ELECTRICAL DEMOLITION WORK)
ELECTRICAL DEMOLITION GENERAL NOTES:
A. TELECOMMUNICATIONS GROUNDING BARS ARE SHOWN FOR REFERENCE ONLY. REFER TO
TELECOMMUNICATION DRAWINGS FOR ADDITIONAL BONDING AND GROUNDING REQUIREMENTS.
(ELECTRICAL GROUNDING NOTES APPLY TO ALL ELECTRICAL SHEETS)
ELECTRICAL GROUNDING GENERAL NOTES:
A. NEW FIRE-ALARM SYSTEM COMPONENTS SHALL BE INDIVIDUALLY ADDRESSABLE AND BE COMPATIBLE WITH, AND OPERATE AS, AN EXTENSION OF EXISTING NOTIFIER NFS2-3030 SYSTEM. EXPAND, MODIFY, AND SUPPLEMENT EXISTING EQUIPMENT AND PROGRAMMING AS NECESSARY TO EXTEND EXISTING FUNCTIONS TO THE NEW POINTS. SYSTEM AND COMPONENTS SHALL MATCH THE EXISTING MANUFACTURER AND TYPE.
COORDINATE WITH MANUFACTURER FOR REQUIRED COMPONENTS.
B. PROVIDE SUBMITTALS TO ARCHITECT INCLUDING PRODUCT DATA AND SHOP DRAWINGS. SUBMITTALS SHALL SHOW EVIDENCE OF REVIEW BY AUTHORITIES HAVING JURISDICTION. PROVIDE PRODUCT DATA FOR EACH
TYPE OF PRODUCT BEING INSTALLED. COMPLY WITH NFPA 72.
C. PROVIDE ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES THAT ARE LISTED AND LABELED AS DEFINED IN NFPA 70 BY A QUALIFIED TESTING AGENCY, AND MARKED FOR INTENDED LOCATION AND APPLICATION. OBTAIN CERTIFICATION ACCORDING TO NFPA 72 BY A UL-LISTED ALARM COMPANY.
D. PERSONNEL SHALL BE TRAINED AND CERTIFIED BY MANUFACTURER FOR INSTALLATION OF UNITS REQUIRED FOR THIS PROJECT, AND SHALL BE DIRECTLY SUPERVISED BY A NICET LEVEL III TECHNICIAN. COMPLY WITH
NFPA 72 FOR INSTALLATION OF FIRE-ALARM EQUIPMENT.
E. MAINTAIN EXISTING EQUIPMENT FULLY OPERATIONAL UNTIL NEW EQUIPMENT HAS BEEN TESTED AND ACCEPTED. IF EXISTING EQUIPMENT CANNOT BE MAINTAINED IN OPERATION OR REQUIRES INTERRUPTION OF FOUR HOURS OR LONGER, PROVIDE TEMPORARY PROVISIONS OR GUARD SERVICE IN A MANNER ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION. NOTIFY OWNER NO FEWER THAN SEVEN DAYS IN ADVANCE OF PROPOSED INTERRUPTIONS, AND ONLY AFTER RECEIVING WRITTEN PERMISSION FROM OWNER. LABEL INACTIVE EQUIPMENT AS "NOT IN SERVICE" UNTIL ACTIVATED OR REMOVED. AFTER ACCEPTANCE OF NEW
FIRE-ALARM SYSTEM, REMOVE EXISTING DISCONNECTED FIRE-ALARM EQUIPMENT AND WIRING.
F. SMOKE DAMPERS SHALL BE CONNECTED TO ACTUATE UPON DETECTION OF SMOKE WITHIN THE AREA OR DUCT AND SHALL SHUT-DOWN THE ASSOCIATED FAN SOURCE. DUCT DETECTION SHALL BE CONNECTED TO
ACTUATE SMOKE DAMPERS AND SHUT-DOWN THE ASSOCIATED FAN SOURCE.
G. INSTALL REMOTE STATUS INDICATORS AND TEST SWITCH NEAR EACH SMOKE DETECTOR AND EACH SPRINKLER WATER-FLOW SWITCH AND VALVE-TAMPER SWITCH THAT IS NOT READILY VISIBLE FROM NORMAL
VIEWING POSITION OR NOT READILY ACCESSIBLE.
H. AVOID INSTALLING SMOKE DETECTION HEADS UNTIL FINAL CLEANUP OF ALL TRADES IS COMPLETE. IF THIS IS UNAVOIDABLE, PROTECT DETECTORS AND PROVIDE CLEANING PRIOR TO FINAL FIRE ALARM TESTING.
I. LOCATE DEVICES PER NFPA 72 AND ADA.
J. SYNCHRONIZE NEW STROBES AND EXISTING STROBES WITHIN COMMON VIEW. MAINTAIN SYNCHRONIZATION
OF EXISTING STROBES.
K. PERFORM FIELD TESTS, WITNESSED BY AUTHORITIES HAVING JURISDICTION. ENGAGE A FACTORY-
AUTHORIZED SERVICE REPRESENTATIVE TO INSPECT COMPONENTS, ASSEMBLIES, AND EQUIPMENT INSTALLATIONS, INCLUDING CONNECTIONS, AND TO ASSIST IN TESTING. CONDUCT VISUAL INSPECTION PRIOR TO TESTING. COMPLY WITH ALL TESTING PROCEDURES REQUIRED BY NFPA 72. TESTING SHALL INCLUDE NEW SYSTEM EQUIPMENT/FUNCTIONS AND REQUIRED EXISTING SYSTEM EQUIPMENT/FUNCTIONS. FIRE-ALARM SYSTEM WILL BE CONSIDERED DEFECTIVE IF IT DOES NOT PASS TESTS AND INSPECTIONS. ENGAGE A FACTORY-AUTHORIZED SERVICE REPRESENTATIVE TO TRAIN OWNER'S MAINTENANCE PERSONNEL TO
ADJUST, OPERATE, AND MAINTAIN FIRE-ALARM SYSTEM.
L. INSTALL CABLES IN EMT CONDUIT. CONCEAL CONDUIT EXCEPT IN UNFINISHED SPACES.
M. PROVIDE 120V AC SERVICE TO REMOTE POWER SUPPLIES AND AMPLIFIERS.
N. PROVIDE LOW AIR PRESSURE SWITCH OPERATION ON A DRY PIPE OR PREACTION SPRINKLER SYSTEM.
PROVIDE AN ALARM-INITIATING CONNECTION TO AUTOMATIC SPRINKLER SYSTEM WATER FLOW ALARM
DEVICES.
O. DELEGATED DESIGN SUBMITTAL SHALL BE PERFORMED BY A NICET CERTIFIED AND LICENSED PROFESSIONAL ENGINEER. ENGINEER SHALL VISIT THE SITE TO SURVEY AND DESIGN THE SYSTEM. SHOP DRAWINGS SHALL BE
STAMPED BY A PE IN THE STATE WHERE THE PROJECT IS LOCATED.
A. SHOP DRAWINGS SHALL INCLUDE DETAILED CALCULATIONS FOR THE ENTIRE SYSTEM, INCLUDING
VOLTAGE DROP CALCULATIONS, DETECTOR COVERAGE, SOUND-PRESSURE LEVELS, STROBE LIGHT
LEVELS, BATTERY SIZING CALCULATIONS, ETC.
P. PROVIDE TEMPORARY HEAT DETECTORS IN THE CONSTRUCTION AREA TO MEET CODE REQUIREMENTS.
Q. BASIC ALARM PERFORMANCE REQUIREMENTS: UNLESS OTHERWISE INDICATED, MANUAL OPERATION OF A
PULL STATION, AUTOMATIC ALARM OPERATION OF A HEAT DETECTOR, OPERATION OF A SPRINKLER FLOW DEVICE, OR VERIFIED AUTOMATIC ALARM OPERATION OF A SMOKE DETECTOR INITIATES THE FOLLOWING:
A. NOTIFICATION APPLIANCE OPERATION.
B. IDENTIFICATION AT THE FACP AND IF REQUIRED THE REMOTE ANNUNCIATOR OF THE ZONE ORIGINATING
THE ALARM.
C. TRANSMISSION OF AN ALARM SIGNAL TO THE REMOTE ALARM RECEIVING STATION.
D. SHUTDOWN OF FANS AND/OR OTHER AIR-HANDLING EQUIPMENT.
E. CONTROL OF SMOKE DAMPERS IN AIR DUCTS OF SYSTEM.
R. ALARM SILENCING, SYSTEM RESET AND INDICATION: CONTROLLED BY SWITCHES IN THE FACP AND IF
APPLICABLE THE REMOTE ANNUNCIATOR.
S. REMOVAL OF AN ALARM INITIATING DEVICE AND/OR A NOTIFICATION APPLIANCE INITIATES THE FOLLOWING:
A. A "TROUBLE" SIGNAL INDICATION AT THE FACP AND IF APPLICABLE THE REMOTE ANNUNCIATOR FOR THE
DEVICE OR ZONE INVOLVED.
B. TRANSMISSION OF TROUBLE SIGNAL TO REMOTE ALARM RECEIVING STATION.
FIRE ALARM GENERAL NOTES:
(GENERAL NOTES SHALL APPLY TO ALL SHEETS)
R
EG IS T E R E D E N G IN E E R
N 2
O. 0 0 1 1 8 0
AGRICULTURE
C E O M M E R C
TRACY J. HAUSER
S T A T E O F T E NNES S EE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22328
02/16/2024
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.E
T
R
.r v t
/1
/2
:2
:4
P
M
E000
ELECTRICAL SYMBOLS AND ABBREVIATIONS EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24TH Avenue South Nashville, TN 37212
626-22-700
02/16/2024 RJA ZTR
ELECTRICAL FIXTURE
SYMBOLS
PLAN SYMBOL NAME
JUNCTION BOX - FLOOR
RECEPTACLE - DOUBLE DUPLEX
- CONV
RECEPTACLE - DOUBLE DUPLEX
- EMERGENCY (RED) - CONV
RECEPTACLE - DUPLEX - CONV
RECEPTACLE - DUPLEX - CONV -
GFCI
RECEPTACLE - DUPLEX -
EMERGENCY (RED) - CONV
ELECTRICAL FIXTURE SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
ELECTRICAL GROUND BAR PROVIDE LENGTH AS REQUIRED TO ACCOMMODATE TERMINATIONS, MINIMUM 20" IN LENGTH. REFER TO
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
EMERGENCY POWER OFF
SWITCH
GENERAL:
PROVIDE STI (SAFETY TECHNOLOGY INTERNATIONAL, INC) MODEL S2-271PO-EN SURFACE MOUNT EPO SWITCH AND PROTECTIVE COVER, OR PRIOR APPROVED EQUIVALENT, AT APPROXIMATE LOCATIONS INDICATED ON PLANS.
PROVIDE ELECTRICAL COMPONENTS FOR A COMPLETE SYSTEM, INCLUDING ALL NECESSARY RELAYS, TRANSFORMERS, AND SHUNTING DEVICES. COORDINATE BACK BOX AND CONDUIT REQUIREMENTS WITH
MANUFACTURER.
JUNCTION BOX - CEILING PROVIDE ONE (1) 4" SQUARE, 2-1/8" DEEP JUNCTION BOX WITH SINGLE GANG TRIM RING AND BLANK WALL PLATE WITH ONE (1) 1” CONDUIT TO ABOVE ACCESSIBLE CEILING WHERE NOT INSTALLED IN ACCESSIBLE CEILING. WHERE SHOWN ADJACENT TO CEILING RECEPTACLES ON FLOOR PLANS, PROVIDE MAXIMUM 8” BETWEEN BACK BOXES.
WHERE SHOWN AS PART OF BRANCH CIRCUIT, PROVIDE CONDUCTORS WITHIN CONDUIT TO SOURCE. REFER TO
FLOOR PLANS FOR BRANCH CIRCUIT DESIGNATION.
JUNCTION BOX - WALL PROVIDE ONE (1) 4" SQUARE, 2-1/8" DEEP JUNCTION BOX WITH SINGLE GANG TRIM RING AND BLANK WALL PLATE WITH ONE (1) 1” CONDUIT TO ABOVE FINISHED CEILING WHERE NOT INDICATED OTHERWISE. WHERE SHOWN ADJACENT TO RECEPTACLES ON FLOOR PLANS, PROVIDE MAXIMUM 12” BETWEEN BACK BOXES. WHERE SHOWN AS PART OF BRANCH CIRCUIT, PROVIDE CONDUCTORS WITHIN CONDUIT TO SOURCE INDICATED ON FLOOR PLANS.
RECEPTACLE - NEMA PROVIDE ONE (1) 4" SQUARE, 2 1/8" DEEP JUNCTION BOX WITH 1 GANG TRIM RING. PROVIDE CONDUIT TO ELECTRICAL SOURCE SIZED AS INDICATED BELOW. REFER TO FLOOR PLANS FOR ELECTRICAL SOURCE AND NEMA
DESIGNATION. PROVIDE DEVICE, FEEDER, AND CIRCUIT BREAKER AS LISTED BELOW:
•NEMA 15-20 & L15-20: 3-#12, #12 GND IN 3/4" CONDUIT; 20A 3 POLE CIRCUIT BREAKER
•NEMA 5-30 & L5-30: 2-#10, #10 GND IN 3/4" CONDUIT; 30A, 1 POLE CIRCUIT BREAKER
•NEMA 21-20 & L21-20: 4-#12, #12 GND IN 3/4" CONDUIT; 20A, 3 POLE CIRCUIT BREAKER
RECEPTACLE - NEMA OUTLET -
CEILING MOUNTED
PROVIDE ONE (1) 4" SQUARE, 2 1/8" DEEP JUNCTION BOX WITH 1 GANG TRIM RING. PROVIDE CONDUIT TO ELECTRICAL SOURCE SIZED AS INDICATED BELOW. REFER TO FLOOR PLANS FOR ELECTRICAL SOURCE AND NEMA
DESIGNATION. PROVIDE DEVICE, FEEDER, AND CIRCUIT BREAKER AS LISTED BELOW:
•NEMA 6-20 & L6-20: 2-#12, #12 GND IN 3/4" CONDUIT; 20A, 2 POLE CIRCUIT BREAKER
•NEMA 15-20 & L15-20: 3-#12, #12 GND IN 3/4" CONDUIT; 20A 3 POLE CIRCUIT BREAKER
•NEMA 5-30 & L5-30: 2-#10, #10 GND IN 3/4" CONDUIT; 30A, 1 POLE CIRCUIT BREAKER
•NEMA 21-20 & L21-20: 4-#12, #12 GND IN 3/4" CONDUIT; 20A, 3 POLE CIRCUIT BREAKER
FIRE ALARM SYMBOLS
PLAN SYMBOL NAME
DETECTOR - SYSTEM SMOKE -
CEILING
FIRE ALARM CONTROL PANEL -
SURFACE MOUNT
MANUAL PULL STATION
STROBE - WALL
VOICE/TONE SPEAKER AND
STROBE COMBINATION - WALL
FIRE ALARM SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
DETECTOR - SYSTEM DUCT
SMOKE DETECTOR
PROVIDE SYSTEM DUCT SMOKE DETECTOR IN ACCESSIBLE LOCATION. PROVIDE REMOTE STATUS INDICATOR AND
TEST STATION AND COORDINATE ASSOCIATED MOUNTING LOCATION WITH OWNER.
FIRE ALARM CONTROL PANEL -
SURFACE MOUNT
CIRCUIT CONTROL PANEL TO 20A 120V BRANCH CIRCUIT IN ASSOCIATED LIFE SAFETY BRANCH PANEL (INSTALL CIRCUIT BREAKER LOCK ON BRANCH BREAKER). REFER TO FLOOR PLANS FOR BRANCH CIRCUIT DESIGNATION.
PROVIDE SYSTEM SMOKE DETECTOR AT CEILING WITHIN 5 FEET OF PANEL (UNLESS SHOWN WITH ROOM
DETECTION COVERAGE ON PLAN). PROVIDE TWO (2) VOICE CONNECTIONS TO FACP.
FIRE SPRINKLER VALVE TAMPER
SWITCH
PROVIDE FIRE SPRINKLER VALVE TAMPER SWITCH AT FIRE SPRINKLER SERVICE AND ALL FIRE SPRINKLER ZONE
VALVES THROUGHOUT PROJECT.
FIRE SPRINKLER WATER FLOW
SWITCH
PROVIDE FIRE SPRINKLER WATER FLOW SWITCH AT FIRE SPRINKLER SERVICE AND ALL FIRE SPRINKLER ZONE
VALVES THROUGHOUT PROJECT.
SMOKE DAMPER OR FIRE/SMOKE
DAMPER
CIRCUIT FIRE FIRE/SMOKE DAMPERS PROVIDED BY MECHANICAL CONTRACTOR TO 20A 120V BRANCH CIRCUITS IN ASSOCIATED LIFE SAFETY BRANCH PANEL (INSTALL CIRCUIT BREAKER LOCK ON BRANCH BREAKERS). EACH BRANCH CIRCUIT SHALL SERVE A MAXIMUM OF 20 DAMPERS. PROVIDE INDIVIDUAL CIRCUITS FOR EACH AIR HANDLING UNIT ZONE. REFER TO MECHANICAL PLANS FOR ASSOCIATED ZONES. CONTROL EACH DAMPER INDIVIDUALLY WITH ADDRESSABLE CONTROL MODULES FROM FIRE ALARM SYSTEM. LABEL EACH RELAY WITH THE NAME OF THE AIR HANDLING UNIT SERVING THE SMOKE ZONE AND WITH THE WORDS "SMOKE DAMPER CONTROL".
PROVIDE REMOTE STATUS INDICATOR AND TEST STATION FOR DETECTOR AND COORDINATE ASSOCIATED MOUNTING LOCATION WITH OWNER. REFER TO MECHANICAL FLOOR PLANS FOR DAMPER LOCATIONS.
ELECTRICAL MISC SYMBOLS
PLAN SYMBOL NAME
BRANCH CIRCUIT CONCEALED IN
CEILING OR WALL
BRANCH CIRCUIT CONCEALED IN
FLOOR OR BELOW GRADE
CLEARANCE SPACE
CONDUIT BREAK
CONDUIT DOWN
CONDUIT STUB-OUT
CONDUIT UP
HOMERUN TO PANEL
G = GFCI CIRCUIT
(PART) = PARTIAL CIRCUIT
SWITCHED RECEPTACLE
ELECTRICAL MISC SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
LIGHTING CONTROL TAG REFER TO LIGHTING CONTROL SCHEDULE FOR ADDITIONAL INFORMATION.
LIGHTING FIXTURE
SYMBOLS
PLAN SYMBOL NAME
DOWNLIGHT FIXTURE
EMERGENCY HATCH
EMERGENCY LIGHTING - WALL
EXIT SIGN - CEILING
CHEVRONS AS SHOWN
EXIT SIGN - WALL
INDUSTRIAL STRIP LIGHT
TROFFER - RECESSED
TROFFER - SURFACE MOUNT
VANITY LIGHT
WALL PACK - EXTERIOR
ELECTRICAL EQUIPMENT
SYMBOLS
PLAN SYMBOL NAME
AUTOMATIC TRANSFER SWITCH
BUSWAY
DISTRIBUTION PANEL
ENCLOSED CIRCUIT BREAKER -
SURFACE
ENCLOSED DISCONNECT
SWITCH - NON-FUSED
LOAD CENTER - SURFACE
LOW VOLTAGE PANEL
PANELBOARD - SURFACE
SWITCHBOARD
TRANSFORMER - DRY TYPE
UPS TRANSFORMER
ONE LINE SYMBOL
PLAN SYMBOL NAME
AUTOMATIC TRANSFER SWITCH
CONTINUATION
DIGITAL METER
DISCONNECT SWITCH
DRAW-OUT CIRCUIT BREAKER
ENCLOSED CIRCUIT BREAKER
GENERATOR
GENERATOR CONNECTION BOX
GROUND BAR
GROUNDING ELECTRODE
KEY INTERLOCK
MOTOR STARTER
PANEL BOARD
SURGE PROTECTIVE DEVICE
SWITCHBOARD
SWITCHBOARD/SWITCHGEAR
SWITCHBOARD/SWITCHGEAR -
DOUBLE TUB
TRANSFORMER
UPS PANEL
UTILITY METER
LIGHTING DEVICE SYMBOLS
PLAN SYMBOL NAME
LIGHT SWITCH
SWITCH - 3 WAY
SWITCH - DIMMER
SWITCH - KEY OPERATED
SWITCH - VACANCY SENSOR
Revisions: Date:
EAB
LB
HB
ECB-L
ECB-R
ECLB2
ECLB
ECLB3
T-142
T-127
T-141
HPBA
LHPBA
ABEQFB
CHPBA
GHPBA
LLBA
MDP
MAIN
T-20
ELLBA
EHPBB
BDB
BDB-1
T-39
BDA
T-174
BD6
BD6-3
BD7
T-67
BEMBB
T-66
ECLLA
BEMBB1
T-65
LC1
EAC
HC
ECLC
ECC
ECLC-1
LC
T-6
BC1
BEM33
BC2
BEMCC
EMG
EMG
LP5
BC3
T-5
BEMC
BEM3
LDD
T-34
BSLS
BEMC1
LP9 BAA(CB9C)
BA5
BA4
SWBD2
T-178
BA8
BEQM1
BEMA1
BEM1
T-186
LP1
BEMA
T-56
BEM9
EQQ1
B47
EQQB
BEMD
T-185
BDAD
T-184
BEQM
BD8
EABB
ECLBB
ECBB
LBB2
LBB
HBB
BDX1
T-63
LBB1
ECLBB1
BDC
BB
EQM
SWBD1
BEM
BEMP
EQQA
IRM-UPS
BEM
BEMB
BB2
T-47
BEQL
BB3
BB1
T-48
EA
EC
EQ EQL
GP
T-43
T-42
EDP
EAL
T-33
SWBD
MSBA
MSBB
A
EHPBC
HLBA
LCC
HC
ECF
ECLCC
EACC
LCC1
T-172
ECBBLCC T-136
BCSP
BCS1
BEMP1
BEMPA21
BEMPA1
T-1
EL
ED
EDS
BEMG
BEM8
T-62
MDA
E
B01 - E400
B01 - E300
B01 - E400
B01 - E400
B01 - E300
B01 - E400
B01 - E300
0B-TR-A11-A
0B-TR-A11-B
0B-TR-D001-A
0B-TR-D001-B
0B-TR-D57A-A
0B-TR-D57A-B
0B-TR-E15-A
0B-TR-E15-B
MDB
E
BEE1
BEMX
BEML
BEMG-1
EQQMTS EQQBMTS WCM
MTS B-44
MTS
FACP
E
EXISTING NOTIFIER NFS-3030
EXISTING FIRE CONTROL ROOM
R
EG IS T E R E D E N G IN E E R
N 2
O. 0 0 1 1 8 0
AGRICULTURE
C E O M M E R C
TRACY J. HAUSER
S T A T E O F T E NNES S EE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22328
KEYPLAN N
ACRE
A BW
CE DE
1A
BE
CW DW
02/16/2024
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.E
T
R
.r v t
/1
/2
:2
:5
P
M
B01-EN200
BASEMENT LEVEL FLOOR PLAN - OVERALL -
ELECTRICAL
EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24TH Avenue South Nashville, TN 37212
626-22-700
B01
02/16/2024 RJA ZTR
SCALE: 1" = 20'-0"B01-EN200
1 BASEMENT LEVEL FLOOR PLAN - OVERALL - ELECTRICAL N
020' 20' 40'
SHEET NOTES:
1. EXISTING ELECTRICAL EQUIPMENT INDICATED FOR REFERENCE.
GENERAL NOTES:
A. ELECTRICAL DISTRIBUTION EQUIPMENT SHOWN ON THIS PLAN IS EXISTING TO
REMAIN UNLESS SHOWN IN AN ENLARGED ROOM CALLOUT. REFER TO ASSOCIATED
ENLARGED ROOM PLAN FOR DEMOLISHED AND NEW ELECTRICAL DISTRIBUTION
EQUIPMENT.
B01 - E401
B01 - E301
B01 - E401
B01 - E301
B01 - E401
B01 - E301
B01 - E401
01-TR-D101-A
01-TR-D101-B
T-166
T-129
HP1A
EHLA
CLL1ALL1A
ELL1A
T-148
1LA
1LA2
1HA
1ECLA
1ECA
EAA
1LA3
T-8T-9
1ECD
1EQL
1EQ
1ECD1
2ECC1
T-1ECC1
1ECC1
1HC
1EAC
1ECLC
1ECC
1LC1
1LC
T-12
T-13
1C2
1C1
LP6
1EMC
1C3
1EM3
T-80
T-81 T-153
T-193
T-154
1A4-2
1A4
HL1A
1EM7-7
1EM7
1EMA1
1ECBB
1HBB
T-83
T-140
1DX1
1DX
1D5
T-82
T-122 T-143
1KA
1K1
1EAK
1EQK
T-123
1EQK1
D119A
HP1D
T-55
T-165
LP1B
LL1B
CLL1B
HP1B
T-109
T-201
T-130
T-182
1EMBB-A
1CU
1EMBB
GH3
MLS
MCR
SWBD N EXISTING
1HDD
1E4R
1E3
1E2
1E1
1EME
1EM5
T-49
T-53
01-TR-A116-A
01-TR-A116-B
01-TR-D114-A
01-TR-D114-B
01-TR-E103A-B
01-TR-E103A-A
CU-E15
(BELOW)
CU-E103A
(ABOVE)
PARALLELING RM E25H
EXISTING PARALLELING GEAR
ATS-11
ATS-10
ATS 7
ATS -8
ATS-9
ATS-6
CU-A116
CU-A11.2
(BELOW)
CU-A11.1
(ABOVE)
B01 - E301
WR
0B-TR-A11-B-2
WR
01-TR-E103A-B-2
R
EG IS T E R E D E N G IN E E R
N 2
O. 0 0 1 1 8 0
AGRICULTURE
C E O M M E R C
TRACY J. HAUSER
S T A T E O F T E NNES S EE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22328
KEYPLAN N
ACRE
A BW
CE DE
1A
BE
CW DW
02/16/2024
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.E
T
R
.r v t
/1
/2
:2
:0
P
M
B01-EN201
FIRST LEVEL FLOOR PLAN - OVERALL -
ELECTRICAL
EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24TH Avenue South Nashville, TN 37212
626-22-700
B01
02/16/2024 RJA ZTR
SCALE: 1" = 20'-0"B01-EN201
1 FIRST LEVEL FLOOR PLAN - OVERALL - ELECTRICAL
020' 20' 40'
N
Revisions: Date:
SHEET NOTES:
1. EXISTING ELECTRICAL EQUIPMENT INDICATED FOR REFERENCE.
GENERAL NOTES:
A. ELECTRICAL DISTRIBUTION EQUIPMENT SHOWN ON THIS PLAN IS EXISTING TO
REMAIN UNLESS SHOWN IN AN ENLARGED ROOM CALLOUT. REFER TO ASSOCIATED
ENLARGED ROOM PLAN FOR DEMOLISHED AND NEW ELECTRICAL DISTRIBUTION
B01 - E402
B01 - E402
B01 - E302
B01 - E402
B01 - E302
2LA1
2LA
2EALA
2EAA
2ECLA
2ECLA1
T-15
2HA
2ECA
2ECA-A
T-207
T-14
(E)LHP2
(E)LLP2
(E)LL2A
(E)HL2A
(E)T-151
(E)T-203
(E)T-202
LL2B-1
LL2B-2
HL2B
T-107
02-TR-B217-B
02-TR-B217-A
2ECLC-1
2ECLC
T-19
2ECC
2HC
2EAC
T-84
T-18
2LC
2EALC
2CRS2
2EQ
2CA
2C3-1
2C3-2
2C1
2C2
2CRS1
2LSS
2CRS
T-152
2BA
2B2-1
2B2-2
PPB
EMP-2
EMPB
2CR1
2LS
2LS1
T-189
T-188
T-113
EMP1
EMPA
2AA
LP2
T-147
T-180
T-181
2A1
2A3 (1-2)
2CRN-2
2CRN-1
2A2
2LSN
2EAB
2HB
2ECB
2LB-2
2LB
2EALB
2ECLB
T-16
T-35
T-17
02-TR-A221-B
02-TR-A221-A
CU-D114S.1
CU-D57A
CU-A221A
(ABOVE) WR
WR
WR
CU-A323A
(BELOW)
B01 - E406
B01 - E407
UPS-B
UPS-A DP-TR-B1
DP-TR-B2
TR-B
ATS-MCR-A ATS-MCR-B ATS-TR-A
DP-MCR-B
DP-MCR-A
DP-ACRES-TR-A
DPC-TR-2A
DPC-TR-1A
(E)GDP
(E)TR-EM-A
B01 - E305
B01 - E405
2A3 (1-2)-67
2A3 (1-2)-67
2A3 (1-2)-67
CU-D114S.2
02-TR-D201-B
02-TR-D201-A
A-TR-F212
B-TR-F212
R
EG IS T E R E D E N G IN E E R
N 2
O. 0 0 1 1 8 0
AGRICULTURE
C E O M M E R C
TRACY J. HAUSER
S T A T E O F T E NNES S EE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22328
KEYPLAN N
ACRE
A B
C D
02/16/2024
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.E
T
R
.r v t
/1
/2
:2
:0
P
M
B01-EN202
SECOND LEVEL FLOOR PLAN - OVERALL -
ELECTRICAL
EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24TH Avenue South Nashville, TN 37212
626-22-700
B01
02/16/2024 RJA ZTR
SCALE: 1" = 20'-0"B01-EN202
1 SECOND LEVEL FLOOR PLAN - OVERALL - ELECTRICAL
020' 20' 40'
N
Revisions: Date:
SHEET NOTES:
1. EXISTING ELECTRICAL EQUIPMENT INDICATED FOR REFERENCE.
GENERAL NOTES:
A. ELECTRICAL DISTRIBUTION EQUIPMENT SHOWN ON THIS PLAN IS EXISTING TO
REMAIN UNLESS SHOWN IN AN ENLARGED ROOM CALLOUT. REFER TO ASSOCIATED
B01 - E403
B01 - E303
B01 - E403
B01 - E303
B01 - E403
B01 - E303
LL3A-2
LL3A-1
EHP3A
HL3A
LL3L-2
LL3L-1
HL3B
EHP3B
ELL3D
CLL3B
T-104
T-103 T-163
3ECH
3EAH
3A1
3A2
3EC-S2
3EC-S1
3EA
3AA
3A3-S1
3A3-S2
3BA
3EM2
3B1 3B2
T-121
3EMB
3CR
3C1 3SLS
3CRC1T-149
3C
3C3-2
3C3-1
3CA
3LC2
3EAC
3HC
3ECC
3ECLC
3LC1
3LC
T-25
T-200
T-24
3ECA
3HA 3LA
3LECA
3ECLA
3EAA
T-199
T-20
T-21
3ECLB
3HB
3EAB
3EALB
3ECB
3ECLB-1
3LB
3LB2
T-22
T-23
03-TR-C371-A
03-TR-C371-B
03-TR-B320-B
03-TR-B320-A
CU-NE.1
CU-NE.2
HP-A281
CU-EE.1
CU-EE.2
CU-B320.2
CU-B320.1
CU-B217.2
CU-B217.1
CU-D001
CU-D101.2
CU-C371A
CU-D201.2
ACU-1
ACU-2
WR
WR
ELL3A
T-138
TR
F-313
B01 - E305
B01 - E405
(ABOVE)
(BELOW)
(ABOVE)
(BELOW)
EX. RTU
CU-D101.1
CU-D201.1
3B1-26
CU-D201.3
3LC2-6
03-TR-A323-A
03-TR-A323-B
A-TR-F313
B-TR-F313
R
EG IS T E R E D E N G IN E E R
N 2
O. 0 0 1 1 8 0
AGRICULTURE
C E O M M E R C
TRACY J. HAUSER
S T A T E O F T E NNES S EE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22328
KEYPLAN N
ACRE
A B
C D
02/16/2024
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.E
T
R
.r v t
/1
/2
:2
:1
P
M
B01-EN203
THIRD LEVEL FLOOR PLAN - OVERALL -
ELECTRICAL
EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24TH Avenue South Nashville, TN 37212
626-22-700
B01
02/16/2024 RJA ZTR
SCALE: 1" = 20'-0"B01-EN203
1 THIRD LEVEL FLOOR PLAN - OVERALL - ELECTRICAL
020' 20' 40'
N
1. NEW MCR ROOF AND ALL MECHANICAL EQUIPMENT ON ROOF SHALL BE
TIED INTO THE EXISTING BUILDINGS LIGHTNING PROTECTION SYSTEM.
REFER TO SPECIFICATION 264100 FOR ADDITIONAL REQUIRMENTS.
2. EXISTING ELECTRICAL EQUIPMENT INDICATED FOR REFERENCE.
3. MECHANICAL EXTERIOR MOUNTED EQUIPMENT AND ASSOCIATED 'WR' GFCI
RECEPTACLES ALONG WITH CIRCUIT INFORMATION AND EQUIPMENT TAGS
ARE INDICATED ON THIS PLAN. THIS INFORMATION IS NEW WORK.
Revisions: Date:
SHEET NOTES:
GENERAL NOTES:
A. ELECTRICAL DISTRIBUTION EQUIPMENT SHOWN ON THIS PLAN IS EXISTING TO
REMAIN UNLESS SHOWN IN AN ENLARGED ROOM CALLOUT. REFER TO ASSOCIATED
B01 - E405
B01 - E305
B01 - E404
B01 - E304
B01 - E404
B01 - E304
B01 - E404
B01 - E304
04-TR-A416-B
04-TR-A416-A
(E)CCLL4
(E)ELL4A
(E)LL4A
(E)HP4A
(E)T-102
(E)T-161
ELL4D
CLL4B
HP4B
LHP4
LL4L
T-101
T-159
4HAT-26
4LA T-27
4ECA
4ECLA
4ECLB
4ECLB-1
4EAB
4LB
4HB
4ECB
4EALB
T-28
T-29
T-30
T-31
4HC
4ECC 4ECLC
4LC
T-169
4EMB
4CR
4EMB-A
T-181
4BA
4B2
4EM2
(E)4CA
(E)4C3-1
(E)4C3-2
4C1
4C2
4B3
4L5L
4L5
4CR1
T-191
T-190
4A3
4A2
4A1
4EALN
4AA
T-168
T-167
4EQLN
04-TR-G406-A
04-TR-G406-B
04-TR-C449-A
04-TR-C449-B
CU-A416
WR
CU-G406
WR
04-TR-G406-B-8
4LA-15
B-TR-F413
A-TR-F413
1 1
2 2
R
EG IS T E R E D E N G IN E E R
N 2
O. 0 0 1 1 8 0
AGRICULTURE
C E O M M E R C
TRACY J. HAUSER
S T A T E O F T E NNES S EE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22328
KEYPLAN N
ACRE
A B
C D
02/16/2024
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.E
T
R
.r v t
/1
/2
:2
:1
P
M
B01-EN204
FOURTH LEVEL FLOOR PLAN - OVERALL -
ELECTRICAL
EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24TH Avenue South Nashville, TN 37212
626-22-700
B01
02/16/2024 RJA ZTR
SCALE: 1" = 20'-0"B01-EN204
1 FOURTH LEVEL FLOOR PLAN - OVERALL - ELECTRICAL
020' 20' 40'
N
Revisions: Date:
1. EXISTING ELECTRICAL EQUIPMENT INDICATED FOR REFERENCE.
2. MECHANICAL EXTERIOR MOUNTED EQUIPMENT AND ASSOCIATED 'WR' GFCI
RECEPTACLES ALONG WITH CIRCUIT INFORMATION AND EQUIPMENT TAGS
ARE INDICATED ON THIS PLAN. THIS INFORMATION IS NEW WORK.
SHEET NOTES:
GENERAL NOTES:
A. ELECTRICAL DISTRIBUTION EQUIPMENT SHOWN ON THIS PLAN IS EXISTING TO
REMAIN UNLESS SHOWN IN AN ENLARGED ROOM CALLOUT. REFER TO ASSOCIATED
(E)T-99
(E)T-162
(E)EHP5A
(E)CLL5A
(E)HL5A
(E)LL5A
(E)ELL5A
(E)T-100
B01 - E305
ELL5E
CCL5B
HL5B
T-175
T-117
T-97
LL5K
T-164
T-134
A-TR-F512B
B01 - E405
B-TR-F512B
R
EG IS T E R E D E N G IN E E R
N 2
O. 0 0 1 1 8 0
AGRICULTURE
C E O M M E R C
TRACY J. HAUSER
S T A T E O F T E NNES S EE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22328
KEYPLAN N
ACRE
A B
C D
02/16/2024
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.E
T
R
.r v t
/1
/2
:2
:1
P
M
B01-EN205
FIFTH LEVEL FLOOR PLAN - OVERALL -
ELECTRICAL
EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24TH Avenue South Nashville, TN 37212
626-22-700
B01
02/16/2024 RJA ZTR
08' 8' 16'
N
SCALE: 1/8" = 1'-0"B01-EN205
1 FIFTH LEVEL FLOOR PLAN - OVERALL - ACRES
SHEET NOTES:
1. EXISTING ELECTRICAL EQUIPMENT INDICATED FOR REFERENCE.
GENERAL NOTES:
1. ELECTRICAL DISTRIBUTION EQUIPMENT SHOWN ON THIS PLAN IS EXISTING TO
REMAIN UNLESS SHOWN IN AN ENLARGED ROOM CALLOUT. REFER TO ASSOCIATED
ENLARGED ROOM PLAN FOR DEMOLISHED AND NEW ELECTRICAL DISTRIBUTION
EQUIPMENT
(E)LHP6
(E)ELL6A
(E)LL6A
(E)T-95 (E)T-160
(E)HL6A
(E)CCL6A
CLL6B
LL6E
T-158
T-94
HL6B
T-93
B01 - E405
B01 - E305
TR
F-615
A-TR-F615
B-TR-F615
CU-F615CU-F512B
CU-F413
CU-F313
CU-F212
WR
1 1
1 1 12
B-TR-F615-33
R
EG IS T E R E D E N G IN E E R
N 2
O. 0 0 1 1 8 0
AGRICULTURE
C E O M M E R C
TRACY J. HAUSER
S T A T E O F T E NNES S EE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22328
KEYPLAN N
ACRE
A B
C D
02/16/2024
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.E
T
R
.r v t
/1
/2
:2
:1
P
M
B01-EN206
SIXTH LEVEL FLOOR PLAN - OVERALL -
ELECTRICAL
EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24TH Avenue South Nashville, TN 37212
626-22-700
B01
02/16/2024 RJA ZTR
SCALE: 1/8" = 1'-0"B01-EN206
1 SIXTH LEVEL FLOOR PLAN - OVERALL - ELECTRICAL
08' 8' 16'
N
08' 8' 16'
N
SCALE: 1/8" = 1'-0"B01-EN206
2 ACRES ROOF LEVEL - NEW PLAN - ELECTRICAL
SHEET NOTES:
1. ALL MECHANICAL EQUIPMENT ON ROOF SHALL BE TIED INTO THE EXISTING
BUILDING LIGHTNING PROTECTION SYSTEM. REFER TO SPECIFICATION
264100 FOR REQUIRMENTS.
2. PROVIDE WEATHERPROOF GFCI RECEPTACLE WITHIN 25 FEET OF THE NEW
CONDENSING UNIT. PROVIDE PEDESTAL MOUNTING IF THERE IS NO OTHER
SURFACE TO INSTALL DEVICE TO MEET THIS REQUIREMENT.
3. MECHANICAL EXTERIOR MOUNTED EQUIPMENT AND ASSOCIATED 'WR' GFCI
RECEPTACLES ALONG WITH CIRCUIT INFORMATION AND EQUIPMENT TAGS
ARE INDICATED ON THIS PLAN. THIS INFORMATION IS NEW WORK.
GENERAL NOTES:
1. ELECTRICAL DISTRIBUTION EQUIPMENT SHOWN ON THIS PLAN IS EXISTING TO
REMAIN UNLESS SHOWN IN AN ENLARGED ROOM CALLOUT. REFER TO ASSOCIATED
ENLARGED ROOM PLAN FOR DEMOLISHED AND NEW ELECTRICAL DISTRIBUTION
EQUIPMENT
B01 - E401
B01 - E301
A1-TR-139
H E
L2 E 1
L1 E
T-A1-TR-139
FACP - ANNEX
NFS-320 -EXISTING
T-L2 E
R
EG IS T E R E D E N G IN E E R
N 2
O. 0 0 1 1 8 0
AGRICULTURE
C E O M M E R C
TRACY J. HAUSER
S T A T E O F T E NNES S EE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22328
KEYPLAN N
ACRE
A BW
CE DE
1A
BE
CW DW
02/16/2024
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.E
T
R
.r v t
/1
/2
:2
:2
P
M
B01A - EN201
FIRST LEVEL FLOOR PLAN - OVERALL -
ELECTRICAL
EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24TH Avenue South Nashville, TN 37212
626-22-700
B01A
02/16/2024 RJA ZTR
SCALE: 1/8" = 1'-0"B01A - EN201
1 FIRST LEVEL FLOOR PLAN - OVERALL - ELECTRICAL
08' 8' 16'
SHEET NOTES:
1. EXISTING ELECTRICAL PANELS TO REMAIN. EXISTING PANEL INDICATED FOR
REFERENCE. REFER TO ONE LINE FOR ADDITIONAL INFORMATION.
GENERAL NOTES:
1. EXISTING DISTRIBUTION EQUIPMENT IN ELECTRICAL ROOM SHOWN ON THIS PLAN
FOR REFERENCE. REFER TO ASSOCIATED ENLARGED ROOM PLAN FOR DEMOLISHED
AND NEW ELECTRICAL DISTRIBUTION EQUIPMENT.
J
GRASS AREA
TO BE CLEANED
CONC. PAVEMENT
REWORK HANDICAP PARKING
HOSE BIB
Parking Control Gate
P
SD
C35528
C35529
SD
FS
TS
FIRE EXTINGUISHER
CABINET
F.E.C.
16-SPACES
18.5' X 9'
15-SPACES
18.5' X 8.5'
18.5' X 8'10"
28-SPACES
.5 ' X
-S P A C
E S
18.5' X 8'8"
20-SPACES
18.5' X 9'
5-SPACES
18.5' X 8'8"
24-SPACES
-S
P A C
E S
' X
'6
-S P A C
E S
'6
X
'6
26-YELLOW SPACES
4-GREEN SPACES
8' X 18'6"
4-GREEN SPACES
26-YELLOW SPACES
8' X 18'6"
RAMP UP
TO LEVEL 'P1'
#1
#2#3#4
STOR.#5#6
STOR. #10
#9
#8
#7
AAMM STOR.
PROS. STOR.RENAL. STOR.CANTEEN STOR.
NUC. MEDFMS STOR.
PLUMB./ELEC.
IRM STOR.
FMS STOR.
Canteen Stor.
EL
ED
EM
ER
G Y
A
TS
N R M
G L
G H
EL
L
A
TS
A
TS
P
A N E
LS
R E C
IV
E R /D
R
IV
E R S
T
O T A L
P O
W E R S
U P P
LY
M U
LT
IP
LE
X E R
K E Y B O
A R D E
X T
B N C T
E R M
IN
A L
P U S H T
ER
M
IN
A
LW
IR
E W
A Y
X X X X
X X
X X
X
X X X X X X X X
X X X X X X X X X X
X X
X XX X XXXX XX
B09 - E400
B09 - E400
ATS - 6
ED
EL
ELL
T - 119 (ABOVE)
T - 120 (ABOVE)
GL
GH
CU-PG1
48"
WR
GL-40
R
EG IS T E R E D E N G IN E E R
N 2
O. 0 0 1 1 8 0
AGRICULTURE
C E O M M E R C
TRACY J. HAUSER
S T A T E O F T E NNES S EE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22328
KEYPLAN N
ACRE
A BW
CE DE
1A
BE
CW DW
02/16/2024
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.E
T
R
.r v t
/1
/2
:2
:2
P
M
B09 - EN200
BASEMENT LEVEL GARAGE FLOOR PLAN -
OVERALL - ELECTRICAL
EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24TH Avenue South Nashville, TN 37212
626-22-700
B09
02/16/2024 RJA ZTR
SCALE: 1/16" = 1'-0"B09 - EN200
1 BASEMENT LEVEL FLOOR PLAN - OVERALL - TELECOMMUNICATIONS
N016' 16' 32'
SHEET NOTES:
1. EXISTING ELECTRICAL EQUIPMENT INDICATED FOR REFERENCE.
GENERAL NOTES:
1. ELECTRICAL DISTRIBUTION EQUIPMENT SHOWN ON THIS PLAN IS EXISTING TO
REMAIN UNLESS SHOWN IN AN ENLARGED ROOM CALLOUT. REFER TO ASSOCIATED
ENLARGED ROOM PLAN FOR DEMOLISHED AND NEW ELECTRICAL DISTRIBUTION
JJ
T
D D D
D D
DD
D
D D
1 1
LIMITS OF DEMOLITION
DDD
D
D
D
D
D D
D
LIMITS OF DEMOLITION
AC
48" E
LIMITS OF DEMOLITION
R
D
D
D D
DD
D
D
D
EXISTING FIRE ALARM
CONDUITS TO BE RELOCATED EXISTING FIRE ALARM
CONDUITS TO BE RELOCATED
R
EG IS T E R E D E N G IN E E R
N 2
O. 0 0 1 1 8 0
AGRICULTURE
C E O M M E R C
TRACY J. HAUSER
S T A T E O F T E NNES S EE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22328
02/16/2024
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.E
T
R
.r v t
/1
/2
:2
:2
P
M
B01 - E300
ENLARGED ELECTRICAL ROOMS - DEMO -
BASEMENT
EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24TH Avenue South Nashville, TN 37212
626-22-700
B01
02/16/2024 RJA ZTR
2' 0' 2' 4'
SCALE: 1/2" = 1'-0"B01 - E300
1 BASEMENT LEVEL SECTION CE - DEMOLITION PLAN - TR A-10 & 11
N
SCALE: 1/2" = 1'-0"B01 - E300
2 BASEMENT LEVEL SECTION A ELECTRICAL DEMOLITION PLAN - TR-D-57A
SCALE: 1/2" = 1'-0"B01 - E300
3 BASEMENT LEVEL SECTION BE DEMOLITION PLAN - TR-E-15
GENERAL NOTES:
A. REFER TO GENERAL DEMOLITION NOTES ON E000 FOR ADDITIONAL
INFORMATION.
2' 0' 2' 4' 2' 0' 2' 4' 2' 0' 2' 4'
SHEET NOTES:
1. DISCONNECT EXHAUST FAN AND ASSOCIATED CONTROL AS REQUIRED.
REMOVE CONDUIT AND CONDUCTORS BACK TO POWER SOURCE.
2. RELOCATE EXISTING FIRE ALARM POWER MODULES AND (12) EXISTING FIRE
ALARM CONDUITS TO THE ADJACENT ELECTRICAL ROOM. REFER TO
PHOTOS OF EXISTING CONDITIONS, DETAILS 4/E301 AND 5/E301.
3. DISCONNECT EXISTING MECHANICAL EQUIPMENT AND REMOVE ALL POWER
CONNECTIONS AND CONDUCTORS BACK TO POWER SOURCE.
COORDINATE WITH REMOVAL OF EQUIPMENT.
4. REMOVE EXISTING 60A DISCONNECT. REMOVE CONDUIT AND CONDUITS
BACK TO PANEL ECLBB LOCATED IN ROOM D-02G.
NOT TO SCALEB01 - E300
4 TR-E-15 EAST WALL PHOTO OF EXISTING FA CONDUITS
NOT TO SCALEB01 - E300
5 TR-E-15 EAST WALL PHOTO OF EXISTING FA CONDUITS
T
F F
D
D
D D
LIMITS OF DEMOLITION
LIMITS OF DEMOLITION
D
D
D
D
D
D
D
SECURITY ACCESS
CONTROL PANEL
LIMITS OF DEMOLITION
LIMITS OF DEMOLITION
D D
D D D
SSE
D
D D DD
D
D
H-3
D
D
E
D
D D
E E
CU-SSE
D
D
D
D
D
D D
L2-43
L2-78 L2-78 L2-78 L2-78
L2-47 L2-45
H-3
H-3 H-3
H-3
H-3H-3
H-3 H-3
D
E
WR
E
E
E
E E
E
D
D D
D D D
L1-2 (D)
L2 E
L1 E
T-L2 E
H E
EX. ELEC RM
E
SSE
D
W R
W
E
R
EG IS T E R E D E N G IN E E R
N 2
O. 0 0 1 1 8 0
AGRICULTURE
C E O M M E R C
TRACY J. HAUSER
S T A T E O F T E NNES S EE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22328
02/16/2024
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.E
T
R
.r v t
/1
/2
:3
:3
P
M
B01 - E301
ENLARGED ELECTRICAL ROOM - DEMO -
LEVEL 01
EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24TH Avenue South Nashville, TN 37212
626-22-700
B01
02/16/2024 RJA ZTR
SCALE: 1/2" = 1'-0"B01 - E301
1 ELECTRICAL DEMO - ENLARGED PLAN - TR D-114S
SCALE: 1/2" = 1'-0"B01 - E301
3 ELECTRICAL DEMO - ENLARGED PLAN - TR E-103
N
SCALE: 1/2" = 1'-0"B01 - E301
2 ELECTRICAL DEMO - ENLARGED PLAN - TR A-116
SCALE: 1/2" = 1'-0"B01 - E301
4 ELECTRICAL DEMO - ENLARGED PLAN - TR E-D101
SCALE: 3/8" = 1'-0"B01 - E301
5 ELECTRICAL DEMO- ENLARGED PLAN - ANNEX -TR 139
03' 3' 6'
SHEET NOTES:
1. DEMOLISH EXISTING CONDENSING UNIT, ASSOCIATED DISCONNECT,
CONDUIT AND CONDUCTORS BACK TO POWER SOURCE.
2. DEMOLISH EXISTING INDOOR UNIT, ASSOCIATED DISCONNECT, CONDUIT
AND CONDUCTORS BACK TO POWER SOURCE.
2' 0' 2' 4' 2' 0' 2' 4'
2' 0' 2' 4' 2' 0' 2' 4'
GENERAL NOTES:
A. REFER TO GENERAL DEMOLITION NOTES ON E000 FOR ADDITIONAL
INFORMATION.
LIMITS OF DEMOLITION
TR
D-201
LIMITS OF DEMOLITION
LIMITS OF DEMOLITION
R
EG IS T E R E D E N G IN E E R
N 2
O. 0 0 1 1 8 0
AGRICULTURE
C E O M M E R C
TRACY J. HAUSER
S T A T E O F T E NNES S EE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22328
02/16/2024
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.E
T
R
.r v t
/1
/2
:2
:2
P
M
B01 - E302
ENLARGED ELECTRICAL ROOM - DEMO -
LEVEL 02
EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24TH Avenue South Nashville, TN 37212
626-22-700
B01
02/16/2024 RJA ZTR
2' 0' 2' 4'
N
SCALE: 1/2" = 1'-0"B01 - E302
2 ELECTRICAL DEMO - ENLARGED PLAN - TR B-217
SCALE: 1/2" = 1'-0"B01 - E302
3 ELECTRICAL DEMO - ENLARGED PLAN - TR-D201
SCALE: 1/2" = 1'-0"B01 - E302
1 ELECTRICAL DEMO - ENLARGED PLAN - TR A-221
GENERAL NOTES:
A. REFER TO GENERAL DEMOLITION NOTES ON E000 FOR ADDITIONAL
JJ
LIMITS OF DEMOLITION
LIMITS OF DEMOLITION
3EM2-2
E
T-3CR
R
3CR
D
R-FIRE ALARM RELAY PNL
D
D
D
D D
D
D
LIMITS OF DEMOLITION
3ECC- 7,9,11
3ECLC-10
EXISTING PNEUMATIC TUBE SYSTEM
TO BE RELOCATED
R
EG IS T E R E D E N G IN E E R
N 2
O. 0 0 1 1 8 0
AGRICULTURE
C E O M M E R C
TRACY J. HAUSER
S T A T E O F T E NNES S EE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22328
02/16/2024
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.E
T
R
.r v t
/1
/2
:2
:2
P
M
B01 - E303
ENLARGED ELECTRICAL ROOM - DEMO -
LEVEL 03
EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24TH Avenue South Nashville, TN 37212
626-22-700
B01
02/16/2024 RJA ZTR
SCALE: 1/2" = 1'-0"B01 - E303
1 ELECTRICAL DEMO - ENLARGED PLAN - TR A-323A
SCALE: 1/2" = 1'-0"B01 - E303
2 ELECTRICAL DEMO - ENLARGED PLAN - TR B-320
SCALE: 1/2" = 1'-0"B01 - E303
3 ELECTRICAL DEMO - ENLARGED PLAN - TR C-371
SHEET NOTES:
1. PANEL '3CR' TO BE PHASED FOR DEMOLITION/RELOCATION . REFER TO 1 /
B01-E403 FOR NEW LOCATION. CONTRACTOR TO INSTALL NEW PANEL '3CR'
AT NEW LOCATION. PROVIDE WITH A NEW FEED FROM PANEL '2CR' ( ROOM
BELOW - PROVIDE NEW 3P BREAKER IN AVAILABLE SPACE 71,73,75 TO
MATCH EXISTING RATINGS )TO MATCH EXISTING T-3CR CONDUCTORS.
SECONDARY CONDUCTOR FROM T-3CR TO MATCH EXISTING CONDUCTOR.
PRIOR TO DEMOLISHING EXISTING PANEL COORDINATE WITH COR TO MOVE
EXISTING '3CR' CIRCUITS TO NEW '3CR'. WORK EXPECTED TO BE
COMPLETED AFTER NORMAL WORKING HOURS TO AVOID INTERRUPTION TO
PATIENT SERVICES AND HOSPITAL OPERATIONS. PROVIDE UPDATED PANEL
SCHEDULE.
A. BIDDING NOTES FOR PANEL 3CR:
a. 3 PHASE 480/277V PANEL FED FROM ROOM B-207: 100A MCB PANEL
WITH THE FOLLOWING BREAKERS: (1) 20A 3P BREAKER ,(1) 50A 3P
BREAKER AND (12) 20A 1P BREAKERS
b. TRANSFORMER T-3CR (T-119) IS A 30KVA 3 PHASE TRANSFORMER
480V TO 208V.
2. TRANSFORMER 'T -3CR' TO BE PHASED FOR DEMOLITION/RELOCATION.
REFER TO 1 / B01-E403 FOR NEW LOCATION. CONTRACTOR TO INSTALL NEW
TRANSFORMER AND NEW FEEDER FROM PANEL '2CR' BELOW TO MATCH
EXISTING T-3CR FEEDER PRIOR TO DEMOLISHING EXISTING TRANSFORMER.
3. EXISTING FIRE ALARM RELAYS AND BMS SYSTEM TO BE RELOCATED. WORK
TO BE PHASED WITH MINIMAL DOWNTIME. COORDINATE WITH COR FOR ALL
VENDOR REQUIREMENTS.
4. RELOCATE EXISTING FIRE ALARM JUNCTION BOX FROM WALL BEING
DEMOLISHED.
5. EXISTING 120V, 1-PHASE AND 480V, 3-PHASE CONNECTIONS FOR PNEUMATIC
TUBE SYSTEM TO BE RELOCATED TO ALLOW FOR NEW DOOR INTO NEW TR
ROOM.
2' 0' 2' 4'
GENERAL NOTES:
A. REFER TO GENERAL DEMOLITION NOTES ON E000 FOR ADDITIONAL
INFORMATION.
N
LIMITS OF DEMOLITION
LIMITS OF DEMOLITION
(E)4C3-1
(E)4C3-2
LIMITS OF DEMOLITION
(E)4CA
R
EG IS T E R E D E N G IN E E R
N 2
O. 0 0 1 1 8 0
AGRICULTURE
C E O M M E R C
TRACY J. HAUSER
S T A T E O F T E NNES S EE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22328
02/16/2024
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.E
T
R
.r v t
/1
/2
:3
:0
P
M
B01 - E304
ENLARGED ELECTRICAL ROOM - DEMO -
LEVEL 04
EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24TH Avenue South Nashville, TN 37212
626-22-700
B01
02/16/2024 RJA ZTR
SCALE: 1/2" = 1'-0"B01 - E304
1 ELECTRICAL DEMO - ENLARGED PLAN - TR A-416
SCALE: 1/2" = 1'-0"B01 - E304
2 ELECTRICAL DEMO - ENLARGED PLAN - TR G-406
SCALE: 1/2" = 1'-0"B01 - E304
3 ELECTRICAL DEMO - ENLARGED PLAN - TR C-449
2' 0' 2' 4'
N
Revisions: Date:
GENERAL NOTES:
A. REFER TO GENERAL DEMOLITION NOTES ON E000 FOR ADDITIONAL
T
(E)LLP2
(E)LL2A
(E)LHP2
(E)HL2A
(E)T-151(E)T-203(E)T-202
LIMITS OF DEMOLITION
D
D
D
D
ELL3A
LL3A-2
LL3A-1
T-138
EHP3A
HL3A
D
D
LIMITS OF DEMOLITION
(E)CCLL4
(E)T-XXX
(E)T-161
(E)T-XXX
(E)T-102(E)HP4A
(E)LL4A
(E)ELL4A
D
D
LIMITS OF DEMOLITION
D
(E)LL5A
(E)ELL5A
(E)T-100 (E)T-99
(E)EHP5A
(E)T-162
(E)HL5A (E)CLL5A
D
D
DD
LIMITS OF DEMOLITION
(E)LHP6(E)ELL6A
(E)LL6A
(E)T-160(E)T-95 (E)HL6A (E)CCL6A
D
D
D
LIMITS OF DEMOLITION
R
EG IS T E R E D E N G IN E E R
N 2
O. 0 0 1 1 8 0
AGRICULTURE
C E O M M E R C
TRACY J. HAUSER
S T A T E O F T E NNES S EE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22328
02/16/2024
A u to d e s k D o c s /2
N a s h v ill e E
H R
M /6
-7
.B
.E
T
R
.r v t
/1
/2
:3
:0
P
M
B01 - E305
ENLARGED ELECTRICAL ROOM - DEMO -
ACRES BLDG
EHRM INFRASTRUCTURE
UPGRADES DESIGN
1310 24TH Avenue South Nashville, TN 37212
626-22-700
B01
02/16/2024 RJA ZTR
SCALE: 1/2" = 1'-0"B01 - E305
1 ELECTRICAL DEMO - ENLARGED PLAN - TR F-212
SCALE: 1/2" = 1'-0"B01 - E305
2 ELECTRICAL DEMO - ENLARGED PLAN - TR F-313
SCALE: 1/2" = 1'-0"B01 - E305
3 ELECTRICAL DEMO - ENLARGED PLAN - TR F-413
SCALE: 1/2" = 1'-0"B01 - E305
4 ELECTRICAL DEMO - ENLARGED PLAN - TR F-512B
SCALE: 1/2" = 1'-0"B01 - E305
5 ELECTRICAL DEMO - ENLARGED PLAN - TR F-615
2' 0' 2' 4'
N
Revisions: Date:
GENERAL NOTES:
A. REFER TO GENERAL DEMOLITION NOTES ON E000 FOR ADDITIONAL
E S
E S
E S
F
F
E S
L21-20
0B-TR-A11-A
0B-TR-A11-B
S1
S1
TR
TR
A-11
SS-A11.2SS-A11.1
0B-TR-A11-A-2
0B-TR-A11-A-2
0B-TR-A11-A-1
0B-TR-A11-B-1
0B-TR-A11-A-1
0B-TR-A11-A-1
0B-TR-A11-B-1
0B-TR-A11-A-1
0B-TR-A11-B-1
L21-20
0B-TR-A11-A-14,16,18
0B-TR-A11-B-7,9,11
L21-20 L21-20 L21-20 L21-20
0B-TR-A11-A-8,10,12
0B-TR-A11-B-4,6,8
0B-TR-A11-B-10,12,140B-TR-A11-A-7,9,11
0B-TR-A11-A-6
0B-TR-A11-A-2
0B-TR-A11-A-2
S1
S1
CR CR CR
AC
0B-TR-A11-A-4
L21-20 L21-20
0B-TR-D57A-A
0B-TR-D57A-B
S1
S1
TRTR
D-57A
SS-D57A
0B-TR-D57A-A-2
0B-TR-D57A-A-2
0B-TR-D57A-A-8
0B-TR-D57A-B-1
0B-TR-D57A-A-8
0B-TR-D57A-B-10B-TR-D57A-A-8
0B-TR-D57A-B-1
0B-TR-D57A-A-8
0B-TR-D57A-B-3,5,7
0B-TR-D57A-A-9,11,13
0B-TR-D57A-A-10,12,14
0B-TR-D57A-B-9,11,13
L21-20 L21-20
0B-TR-D57A-A-1
0B-TR-D57A-A-2
0B-TR-D57A-A-2
S1
S1
CR CR
AC
0B-TR-D57A-A-7
EXISTING PANEL
0B-TR-E15-B-3,5,7
0B-TR-E15-A
0B-TR-E15-B
0B-TR-E15-A-9,11,13
TR
S1
S1
TR
E-15
SS-E15
0B-TR-E15-B-1
0B-TR-E15-A-8
0B-TR-E15-A-8
0B-TR-E15-B-1
0B-TR-E15-A-8
0B-TR-E15-B-10B-TR-E15-A-8
0B-TR-E15-A-2
0B-TR-E15-A-2
0B-TR-E15-B-1
0B-TR-E15-B-2,4,6
0B-TR-E15-A-10,12,14
0B-TR-E15-A-1
S1
S1
0B-TR-E15-A-2
0B-TR-E15-A-2
L21-20 L21-20 L21-20L21-20
CR CR
0B-TR-E15-A-7AC
L21-20 L21-20
0B-TR-D001-A
0B-TR-D001-B
S1 S1
TR
TR
D-001
SS-D001
0B-TR-D001-A-8
0B-TR-D001-B-1
0B-TR-D001-A-8
0B-TR-D001-A-2 0B-TR-D001-A-2
0B-TR-D001-B-1
0B-TR-D001-A-8
0B-TR-D001-A-80B-TR-D001-B-1
0B-TR-D001-A-9,11,13
0B-TR-D001-B-3,5,7
0B-TR-D001-A-10,12,14
0B-TR-D001-B-9,11,13
L21-20 L21-20
A3EMA3
0B-TR-D001-B-1
X3
WR
W1
0B-TR-D001-A-1
0B-TR-D001-A-2 0B-TR-D001-A-2
S1 S1
4…