Attachment 9 - M Drawings.pdf
PDF 788 KB Posted
- Attached to
- Y1GZ--Construct Replacement Warehouse Prescott VAMC (Minor Construction) Federal contract opportunity
- Solicitation number
- 36E77620R0043
About this file
This federal contract opportunity notice provides details for the Construct Replacement Warehouse Minor Construction project at the Northern Arizona VA Health Care System in Prescott, Arizona. The Department of Veterans Affairs will solicit proposals and award a single firm-fixed-price contract to construct a new approximately 10,930 square foot conditioned warehouse to replace two existing buildings. The new facility will provide efficient loading, unloading, and storage of critical supplies on one floor. Site work will include over 30,000 square feet of paving and 5,000 square feet of hardscape. The solicitation will be a total Service-Disabled Veteran-Owned Small Business set-aside issued as a Request for Proposal evaluated using Lowest Price Technical Acceptable procedures. The estimated value is between $5-10 million. The period of performance is approximately 360 days from notice to proceed. The solicitation will be issued on or around July 27, 2020.
View the file
Other files for this federal contract opportunity
Show all 43
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RS
RL
CWR
CWS
PD
CD
LPC
LPS
MPC
MPS
HPC
HPS
H
T
H
T
RD
RDB
RV
AV
CHP-3
X100
X100
ETR
GENERAL DUCT SYMBOLSVALVE SYMBOLSHVAC PIPING SYMBOLS
PUMP NO. 3
EQUIPMENT ABBREVIATION (PUMP)
ANCHOR
ECCENTRIC REDUCER
RISE OR DROP IN PIPE
STRAINER
FLOAT & THERMOSTATIC TRAP SET W/
PIPING ACCESSORIES
PIPING ACCESSORIES
INVERTED BUCKET TRAP SET INCLUDING
THERMOSTATIC MIXING VALVE
ELBOW DOWN WITH SHUT-OFF VALVE
TEE DOWN WITH SHUT-OFF VALVE (SOV)
TEE UP WITH SHUT-OFF VALVE (SOV)
FLANGE CONNECTION
ELBOW DOWN
ELBOW UP
TEE DOWN
ELBOW UP WITH SHUT-OFF VALVE (SOV)
TEE UP
UNION
PRESSURE REDUCING VALVE
REDUCER
BALL VALVE
GATE VALVE WITH 3/4 " HOSE ADAPTER
CHECK VALVE
ANGLE GLOBE VALVE
BUTTERFLY VALVE
MODULATING CONTROL VALVE
TWO POSITION CONTROL VALVE
THREE-WAY MODULATING CONTROL VALVE
AUTOMATIC FLOW CONTROL VALVE
PRESSURE RELIEF VALVE
GATE VALVE
MANUAL AIR VENT
TEST PLUG (PRESSURE/TEMPERATURE)
GLOBE VALVE
PRESSURE REGULATING VALVE
THREE-WAY TWO POSITION CONTROL VALVE
AUTOMATIC AIR VENT
KEYED NOTE
NEW WORK TO EXISTING WORK CONNECTION POINT
DETAIL NUMBER
SHEET NUMBER
PIPE FITTINGS AND ACCESSORIES
SHEET NUMBER
SECTION NUMBER
CONDENSATE DRAIN (CD)
FD FLOOR DRAIN
FD FIRE DAMPER
FF FINAL FILTER
FHX FLUE GAS/FEEDWATER HEAT EXCHANGER
FM FLOW METER
FOP FUEL OIL PUMP
FOT FUEL OIL TANK
FOHX FUEL OIL HEAT EXCHANGER
FPM FEET PER MINUTE
FPS FEET PER SECOND
FPTU FAN POWERED TERMINAL UNIT
FR FLOOR REGISTER
FRP FIBER REINFORCED POLYESTER
FS FLOW SWITCH
FSTAT FREEZESTAT
FT FEET
FT-LB FOOT-POUND
FTR FIN TUBE RADIATION
FV FACE VELOCITY
NOM NOMINAL
NPLV NON-STANDARD PART LOAD VALUE
NPSH NET POSITIVE SUCTION HEAD
NTS NOT TO SCALE
T
T&PCV TEMPERATURE AND PRESSURE CONTROL VALVE
TAB TESTING, ADJUSTING, BALANCE
TD TEMPERATURE DIFFERENCE
TDH TOTAL DYNAMIC HEAD
TDS TOTAL DISSOLVED SOLIDS
TG TRANSFER GRILLE
TP TRAP
TR TOP REGISTER
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TU TERMINAL UNIT
TWU THRU-WALL UNIT
S
SA SUPPLY AIR
SAD SOUND ATTENUATING DEVICE
SAT SUPPLY AIR TEMPERATURE
SC SHADING COEFFICIENT
SCFM STANDARD CUBIC FEET PER MINUTE
SCI SPINAL CODE INJURY
SCR SILICON CONTROLLED RECTIFIER
SD SMOKE DETECTOR
SD SUPPLY AIR DIFFUSER
SD-1 SCHEMATIC DESIGN (SUBMISSION1)
SD-2 SCHEMATIC DESIGN (SUBMISSION2)
SDPR SMOKE DAMPER
SDR SMOKE DAMPER (RETURN)
SDS SMOKE DAMPER (SUPPLY)
SEN SENSIBLE HEAT
SF SUPPLY FAN
SG SUPPLY AIR GRILLE
SH STEAM HUMIDIFIER
SHC STEAM HEATING COIL
SI SQUARE INCHES
SP STATIC PRESSURE
SP GR SPECIFIC GRAVITY
SPD SUPPLY PROCESS AND DISTRIBUTION
SPRV STEAM PRESSURE REDUCING VALVE
SPS STATIC PRESSURE SENSOR
SQ FT SQUARE FOOT (FEET)
SR SUPPLY AIR REGISTER
SS STAINLESS STEEL
SSHX STEAM TO STEAM HEAT EXCHANGER
SSR SOLID SEPARATOR
ST STEAM TRAP
SUH STEAM UNIT HEATER
SV STEAM PRESSURE REDUCING VALVE
SVS STEAM VENT SILENCER
SWHX STEAM TO WATER HEAT EXCHANGER
R
R/E RETURN OR EXHAUST
RA RETURN AIR
RAD REFRIGERANT AIR DRYER
RAF RADIO FREQUENCY
RAHX ROTARY AIR HEAT EXCHANGER
RAT RETURN AIR TEMPERATURE
RCCH REMOTE CONDENSER CHILLER
RCU RECIPROCATING CHILLER UNIT
RD REFRIGERANT DISCHARGE
RDS ROOM DATA SHEETS
REA RELIEF AIR
RF RETURN FAN
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID LINE
RLA RUN LOAD AMPERE
RO REVERSE OSMOSIS
RPM REVOLUTIONS PER MINUTE
RR RETURN REGISTER
RS REFRIGERANT SUCTION
RTU ROOF TOP UNIT
RV RELIEF VALVE
P
P PUMP
PA PASCAL
PC PUMPED CONDENSATE
PCF POUNDS PER CUBIC FOOT (FEET)
PD PRESSURE DROP
PEF PROPELLER (TYPE) EXHAUST FAN
PF PRE-FILTER
PG PRESSURE GAGE
PGW PROPYLENE GLYCOL-WATER (SOLUTION)
PHC PREHEAT COIL
PPM PARTS PER MILLION
PRS PRESSURE REGULATING (VALVE) STATION
PRV PRESSURE REGULATING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH – ABSOLUTE
PSIG POUNDS PER SQUARE INCH – GAGE
PSS PRIMARY SECONDARY SYSTEM
PSV PRESSURE SAFETY VALVE
PTAC PACKAGED TERMINAL AIR CONDITIONER
O
OA OUTSIDE AIR
OAG OUTSIDE AIR GRILLE
OAI OUTSIDE AIR INTAKE
OD OUTSIDE DIAMETER
OFM OIL FLOWMETER
OR OPERATING ROOM
N
NA NOT APPLICABLE
NC NOISE CRITERIA
NC NORMALLY CLOSED
NG NATURAL GAS
NGFM NATURAL GAS FLOWMETER
NO NORMALLY OPEN
NOAA NATIONAL OCEANIC & ATMOSPHERIC ADMINISTRATION
L
L LITER
L/h LITERS PER HOUR (OR LITERS/HOUR) L/m LITERS PER MINUTE (OR LITERS/MINUTE) L/s LITERS PER SECOND (OR LITERS/SECOND)
LAT LEAVING AIR TEMPERATURE
LBS/HR POUNDS PER HOUR
LF LINEAR FOOT (FEET)
LGT LEAVING GLYCOL TEMPERATURE
LH LATENT HEAT
LPG LIQUID PROPANE GAS
LPR LOW PRESSURE RETURN (STEAM CONDENSATE)
LPRC LOW PRESSURE STEAM RETURN (CLEAN)
LLHX LIQUID TO LIQUID HEAT EXCHANGER
LPS LOW PRESSURE STEAM
LPSC LOW PRESSURE STEAM (CLEAN)
LSD LINEAR SLOT DIFFUSER
LTCP LOCAL TEMPERATURE CONTROL PANEL
LVG LEAVING
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
K kg KILOGRAM kg/HR KILOGRAM PER HOUR kPa KILOPASCAL kW KILOWATT kWh KILOWATT HOUR
J
J INTENTIALLY LEFT BLANK
I
I/O INPUT/OUTPUT
IAQ INDOOR AIR QUALITY
IBT INVERTED BUCKET TRAP
ICF IN-LINE CENTRIFUGAL FAN
ICU INTENSIVE CARE UNIT
ID INSIDE DIAMETER
IFB INTEGRAL FACE AND BYPASS
IN INCHES
IN HG INCHES OF MERCURY
IN WC INCH WATER COLUMN
IN WG INCH WATER GAUGE
IN-LB INCH-POUND
IPLV INTERGRATED PART LOAD VALUE
IRH INTRARED HEATER
IS INSECT SCREEN
IU INDUCTION UNIT
IV INLET VANES
M
M METER, SI UNIT
M/s METERS PER SECOND (OR METERS/SECOND)
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAU MAKE-UP AIR UNIT
MAV MANUAL AIR VENT
MAX MAXIMUM
MB MIXING BOX
MBH 1000 BTUH
MCA MINIMUM BRANCH CIRCUIT AMPACITY
MER MECHANICAL EQUIPMENT ROOM
MERV MINIMUM EFFICIENCY REPORTING VALUE
MH MANHOLE
MHP MOTOR HORSEPOWER
MIN MINIMUM
MM MILLIMETER
MOV MOTOR OPERATED VALVE
MPR MEDIUM PRESSURE RETURN (STEAM CONDENSATE)
MPS MEDIUM PRESSURE STEAM
MRI MAGNETIC RESONANCE IMAGING
MTD MEAN TEMPERATURE DIFFERENCE
MVD MANUAL VOLUME DAMPER
MZ MULTI-ZONE
H
H HUMIDIFER
H&CW HOT & COLD WATER
HAC HOUSEKEEPING AID CLOSET
HB HOSE BIBB
HC HEATING COIL
HD HEAD
HD HOOD
HOA HAND/OFF/AUTOMATIC
HP HEAT PUMP
HP HORSEPOWER
HPDT HIGH PRESSURE DRIP TRAP
HPR HIGH PRESSURE RETURN (STEAM CONDENSATE)
HPS HIGH PRESSURE SUPPLY (STEAM)
HRC HEAT RECOVERY COIL
HRD HEAT RECOVERY DEVICE
HRP HYDRONIC RADIANT (CEILING) PANEL
HRW HEAT RECOVERY WHEEL
HSTAT HUMIDISTAT
HTM HUMIDIFIER TERMINAL
HUM HUMIDIFIER UNIT MOUNTED
HVU HEATING AND VENTILATING UNIT
HW HOT WATER
HWC HOT WATER COIL
HWHC HOT WATER HEATING COIL
HWP HEATING HOT WATER PUMP
HWR HEATING HOT WATER RETURN
HWS HEATING HOT WATER SUPPLY
HWUH HOT WATER UNIT HEATER
HVD HOISTWAY VENT DAMPER
HX HEAT EXCHANGER
HZ HERTZ
G
GA GAUGE
GAL GALLONS
GH GRAVITY HOOD
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GS GALVANIZED STEEL
F
F FAHRENHEIT
F&T FLOAT AND THERMOSTATIC
F/SDPR COMBINATION FIRE SMOKE DAMPER
FA FREE AREA
FC FLEXIBLE CONNECTION
FCU FAN COIL UNIT (4 PIPE)
FCUC FAN COIL UNIT COOLING ONLY
FCUH FAN COIL UNIT HEATING ONLY
FCW FORWARD CURVED WHEEL (FAN)
E
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EC EVAPORATIVE COOLER
ECC ENGINEERING CONTROL CENTER
ECU EVAPORATIVE CONDENSER UNIT
EDH ELECTRIC DUCT HEATER
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EG EXHAUST GRILLE
EGS EMERGENCY GAS SHUTOFF
EGT ENTERING GLYCOL TEMPERATURE
EH EXHAUST HOOD
EJ EXPANSION JOINT
EMD END OF MAIN DRIP (STEAM)
ENT ENTERING
ER EXHAUST REGISTER
ERC ELECTRIC REHEAT COIL
ERP ELECTRIC RADIANT PANEL
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
ETO ETHYLENE OXIDE
ETR EXISTING TO REMAIN
EUH ELECTRIC UNIT HEATER
EWC EVAPORATIVE WATER COOLER
EWT ENTERING WATER TEMPERATURE
EX. EXISTING
D
D DAMPER - AUTOMATIC
D-1 OUTDOOR AIR DAMPER
D-2 RETURN AIR DAMPER
D-3 RELIEF AIR DAMPER
DB DECIBELS
Db DRY-BULB TEMPERATURE
DD-1 DESIGN DEVELOPMENT (SUBMISSION 1)
DD-2 DESIGN DEVELOPMENT (SUBMISSION 2)
DDC DIRECT DIGITAL CONTROLS
DEG DEGREE
DF DIFFUSER
DIA DIAMETER
DIW DEIONIZED WATER
DP DEW POINT TEMPERATURE
DP DIFFUSER PLATE
DPA DIFFERENTIAL PRESSURE ASSEMBLY
DPS DIFFERENTIAL PRESSURE SENSOR
DX DIRECT EXPANSION
DXCC DIRECT EXPANSION COOLING COIL
C
C CENTIGRADE (CELCIUS)
CC COOLING COIL
CCD COOLING COIL CONDENSATE DRAIN
CD CEILING DIFFUSER
CD-1 CONSTRUCTION DOCUMENTS (SUBMISSION 1)
CD-2 CONSTRUCTION DOCUMENTS (SUBMISSION 2)
CENT CENTRIFICAL
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CFT CUBIC FEET
CFP CHEMICAL FEED PUMP
CG CEILING GRILLE
CH CHILLER
CHP CHILLED WATER PUMP
CHW CHILLER WATER
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CI CAST IRON
CM CARBON MONOXIDE
CM CUBIC METER
CM/S CUBIC METER PER SECOND
CO CLEAN OUT
CO2 CARBON DIOXODE
COMP COMPRESSOR UNIT
COP COEFFICIENT OF PERFORMANCE
CP CONDENSATE PUMP
CR CEILING REGISTER
CS CONDENSATE STORAGE TANK
CSG CLEAN STEAM GENERATOR
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONSTANT VOLUME
CW COLD WATER (POTABLE)
CWCC CHILLED WATER COOLING COIL
CWP CONDENSER WATER PUMP
CWR CONDENSER WATER RETURN (TO COOLING
TOWER
CWS CONDENSER WATER SUPPLY (FROM COOLING
TOWER)
B
B BOILER
BD BUTTERFLY DAMPER
BDD BACKDRAFT DAMPER
BDR BASE BOARD RADIATOR
BFP BACKFLOW PREVENTER
BFT BOILER PLANT FIRE TUBE
BG BOTTOM GRILLE
BHP BRAKE HORSEPOWER
BHW HOT WATER HEATING BOILER
BHX BOILER BLOWDOWN HEAT EXCHANGER
BIW BACKWARD INCLINED WHEEL (FAN)
BMT BONE MARROW TRANSPLANT
BR BOTTOM REGISTER
BSC BIOLOGICAL SAFETY CABINETS
BT BLOWOFF TANK
BTC BLOWOFF TANK CONTROL VALVE
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
BWT BOILER PLANT WATER TUBE
EXISTING TO REMAIN
LIMIT OF DEMOLITION
A
A/E ARCHITECT / ENGINEER
AAHX AIR TO AIR HEAT EXCHANGER
AB AIR BLENDER
AAV AUTOMATIC AIR VENT
ACC AIR COOLED CONDENSER
ACCH AIR COOLED CHILLER
ACCU AIR-COOLED CONDENSING UNIT
ACU AIR CONDITIONING UNIT
ACD AUTOMATIC CONTROL DAMPER, MODULATING
ACDTP AUTOMATIC CONTROL DMPR, TWO POSITION
AD ACCESS DOOR
AF AFTER FILTER
AFCV AIR FLOW CONTROL VALVE
AFF ABOVE FINISHED FLOOR
AFMD AIR FLOW MEASURING DEVICE
AFW AIR FOIL WHEEL (FAN)
AHU AIR-HANDLING UNIT
AMP AMPERAGE
AP ACCESS PANEL
APD AIR PRESSURE DROP
ARI AIR CONDITIONING AND REFRIGERATION
INSTITUTE
AS AIR SEPARATOR
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
AW AIR WASHER
AXF AXIAL FLOW
10"x8"
AUTOMATIC BALANCING CONTROL VALVE
WYE STRAINER (WITH BALL VALVE
WATER BALANCE DEVICE
MODULATING CONTROL BUTTERFLY VALVE
CIRCUIT SETTER VALVE
GATE VALVE WITH GLOBE-VALVED BYPASS
PLUG VALVE
CONTROL VALVE (CV) - FLOAT-OPERATED
QUICK-COUPLE HOSE CONNECTOR
WYE STRAINER WITH VALVED DRAIN AND
EXISTING TO BE REMOVED
EXISTING TO REMAIN
BRANCH DUCT WITH 45° RECTANGLE-ROUND
BRANCH FITTING AND MANUAL VOLUME DAMPER
BRANCH DUCT WITH BELL-MOUTH FITTING &
MANUAL VOLUME CONTROL DAMPER
RETURN AIR DUCT DOWN
SUPPLY AIR DUCT UP
RETURN DUCT UP
ELBOW WITH TURNING VANES
TYPE
CFM OF AIR DEVICE
MOTORIZED DAMPER
VOLUME DAMPER
THERMOSTAT
FIRE DAMPER
FIRE SMOKE DAMPER
SMOKE DAMPER
MANUAL VOLUME DAMPER
SQUARE TO ROUND TRANSITION
RISER DESIGNATION
HUMIDISTAT
CD-1
BACKDRAFT DAMPER
SUPPLY AIR DUCT DOWN
DUCT MOUNTED SMOKE DETECTOR
(SD=SUPPLY/RD=RETURN)
NEW RECTANGULAR DUCT (INSIDE
DIMENSIONS: W"xD")
LOUVER
DUCT WITH SOUND LINING
DAMPERS: (BD, FD, FSD, MD, SD, VD)
GAS COCK
HEATING HOT WATER RETURN (HHR)
HEATING HOT WATER SUPPLY (HHS)
REFRIGERANT DISCHARGE BYPASS (RDB)
REFRIGERANT SUCTION (RS)
CHILLED WATER RETURN (CHR)
CONDENSER WATER SUPPLY (CWS)
CONDENSER WATER RETURN (CWR)
REFRIGERANT DISCHARGE (HOT GAS) (RD)
HEAT PUMP WATER RETURN (HPWR)
HEAT PUMP WATER SUPPLY (HPWS)
REFRIGERANT LIQUID (RL)
CHILLED WATER SUPPLY (CHS)
HIGH PRESSURE STEAM CONDENSATE (HPC)
HIGH PRESSURE STEAM SUPPLY (HPS)
MEDIUM PRESSURE STEAM CONDENSATE (MPC)
MEDIUM PRESSURE STEAM SUPPLY (MPS)
LOW PRESSURE STEAM CONDENSATE (LPC)
LOW PRESSURE STEAM SUPPLY (LPS)
CONDENSATE PUMP DISCHARGE (PD)
EXPANSION JOINT
TRIPLE DUTY VALVE WITH PRESSURE PORTS
BALANCING VALVE WITH PRESSURE PORTS
SOLENOID VALVE
STRAINER WITH BLOWOFF
REFRIGERANT VENT (RV)
EJ
PRESSURE AND TEMPERATURE TEST PLUG
VACUUM RELIEF VALVE
PRESSURE / VACUUM SWITCH
LIMIT OF DEMOLITION
CONNECT NEW TO EXISTING
D
INCLINED RISE, IN DIRECTION OF AIR FLOW
INCLINED DROP, IN DIRECTION OF AIR FLOW
R
BACK DRAFT DAMPER
BDD
GLYCOL-WATER HEATING RETURN
GLYCOL-WATER HEATING SUPPLY
MAKE-UP WATER
CHILLED GLYCOL-WATER RETURN
CHILLED GLYCOL-WATER SUPPLY
GHS
GHR
GCR
GCS
MW
GLYCOL-WATER RUN AROUND SUPPLY
GLYCOL-WATER RUN AROUND RETURNGRR
GRS
VACUUM CONDENSATE RETURN
FEEDWATER PUMP DISCHARGE (FWPD)
FEEDWATER PUMP SUCTION (FWPS)
VR
FEEDWATER SAMPLE (DEAERATOR) (FWS)
BOILER WATER SAMPLE (BWS)
CONTINUOUS BLOWDOWN (CBD)
CHEMICAL FEED (CF)
BOILER BLOWOFF (BO)
TUBE CLEANER WATER SUPPLY (TC)
OVERFLOW (OFL)
REFRIGERANT SIGHT GLASS
TEMPERATURE SENSOR
HUMIDITY SENSOR
DUCT W/DAMPERS
DIFFUSERS,GRILLES, FLEX CONNECTIONS
FITTINGS & TRANSITIONS
SOFTENED WATERSW
BRINE & SOFT WATER
REFRIGERANT
PLANT PIPING
STEAM
Y
YR YEAR
W
W WATTS
WAG WASTE ANETHESIA GAS
Wb WET-BULB (TEMPERATURE)
WC WATER COOLED
WCCH WATER COOLED CHILLER
WCCU WATER COOLED CONDENSING UNIT
WCHP WATER COOLED HEAT PUMPS
WCPU WATER COOLED PACKAGED UNIT
WEF WALL EXHAUST FAN
WF WATER FILTER
WFCV WATER FLOW CONTROL VALVE
WFM WATER FLOWMETER
WFMD WATER FLOW MEASURING DEVICE
WG WATER GAGE
WPD WATER SIDE PRESSURE DROP
V
V VALVE
VAF VANE-AXIAL FAN
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER (MANUAL OPPOSED BLADE)
VFD VARIABLE FREQUENCY DRIVE
VHA VETERANS HEALTH ADMINISTRATION
VI VIBRATION ISOLATOR
VIV VARIABLE INLET VANES
VP VACUUM PUMP
VPS VARIABLE PRIMARY SYSTEM
VR VACUUM (STEAM CONDENSATE) RETURN
VSD VARIABLE SPEED DRIVE
VUH VERTICAL UNIT HEATER
U
UC UNDER CUT
UC UNIT COOLER
UH UNIT HEATER
UL UNDERWRITERS LABORATORY
URV UPBLAST UNIT VENTILATOR
& HOSE CONNECTION)
ABBREVIATIONS
SD
VD
FSD
FD
BDD
MZD
BD
ANNOTATION
GENERAL NOTES:
1. MECHANICAL PLANS AND SECTIONS ARE INTENDED TO ACCURATELY ILLUSTRATE THE SCOPE
OF WORK BUT ARE STILL DIAGRAMMATIC IN NATURE.
2. MECHANICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE INSTALLED. THE
CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT ALL SYSTEMS ARE FULLY FUNCTIONAL
AND COMPLIANT WITH APPLICABLE CODES.
3. REFER TO FLOW DIAGRAMS, DETAILS AND SPECIFICATIONS FOR REQUIRED PIPING, VALVES
AND GAUGES.
4. MECHANICAL DRAWINGS REFLECT COORDINATION EFFORTS WITH BUILDING DISCIPLINES
HOWEVER, DO NOT SHOW EVERY OFFSET IN DUCT OR PIPING REQUIRED FOR INSTALLATION.
COORDINATION WITH OTHER TRADES IS REQUIRED. VERIFY ALL EXISTING CONDITIONS PRIOR
TO THE START OF WORK.
5. DUCT SIZES SHOWN REPRESENT INSIDE CLEAR DIMENSIONS. CONTRACTOR SHALL ADJUST
SHEET METAL SIZE TO ACCOUNT FOR LINER THICKNESS WHEN LINER IS ALLOWED PER THE
CONTRACT DOCUMENTS.
6. ALL EXPOSED UNINSULATED PIPING SHALL BE PAINTED PER THE SPECIFICATION SECTION
"PAINTING".
7. PIPING CONNECTIONS TO MECHANCIAL EQUIPMENT SHOWN ON DRAWINGS IS APPROXIMATE.
CONTRACTOR SHALL ADJUST ROUTING TO MATCH APPROVED EQUIPMENT CONNECTIONS AND
MANUFACTURERS RECOMMENDATIONS.
8. COORDINATE FAN COIL (FCU) AND VARIABLE AIR VOLUME (VAV) UNIT RIGHT OR LEFT HAND COIL
CONNECTIONS WITH PIPING PLANS.
9. ALL FLUE AND COMBUSTION AIR PIPING FROM GAS-FIRED EQUIPMENT SHALL BE SIZED BY THE
GAS-FIRED EQUIPMENT MANUFACTURER BASED ON THE SPECIFIC PIPE ROUTING AND
ELEVATIONS FOR THIS PROJECT. REFER TO MANUFACTURERS INSTALLATION MANUAL AND
LOCAL CODE REQUIREMENTS FOR REQUIRED FLUE AND COMBUSTION AIR PIPING MATERIALS.
10. ALL FLOOR MOUNTED HVAC EQUIPMENT SHALL HAVE A 6" TALL HOUSEKEEPING PAD. REFER
TO STRUCTURAL PLANS AND DETAILS FOR CONCRETE PAD CONSTRUCTION.
11. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING FACILITY THAT MUST REMAIN
IN SERVICE 24/7.
12. SEE SHEET G-101 FOR ADDITIONAL INFORMATION REGARDING SCHEDULE AND PHASING
REQUIREMENTS. SCHEDULE WORK TO MINIMIZE DISRUPTION OF SERVICES.
13. COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER'S REPRESENTATIVE BEFORE
THE START OF WORK.
14. VAV ATU HEATING HOT WATER SUPPLY AND RETURN PIPING BRANCHES SHALL BE 3/4" UNLESS
NOTED OTHERWISE ON PLAN.
FSD COMBINATION FIRE / SMOKE DAMPER
TU-1-2
TU # 3
EQUIPMENT ABBREVIATION (PUMP)
AHU SERVED BY
TERMINAL UNIT TAG
MECHANICAL EQUIPMENT TAG
10"x8"ꝋ
NEW OVAL DUCT (INSIDE DIMENSIONS:
W"xD"ꝋ)
DRAWING NUMBER
VA PROJECT NUMBER
DATE
PROJECT TITLE
BUILDING NUMBER
PROJECT LOCATION
CHECKED BY DRAWN BY
APPROVED: PROJECT DIRECTOR
VA FORM 08-6231
Office of Construction and Facilities Management
Dwg.
CONSULTANT INFORMATION
STRUCTURAL / CIVIL ENGINEER
F
H2B, INC.
1225 N. LOOP WEST, SUITE 900
HOUSTON, TX 77008
(713) 864-2900
SHEET TITLE
ARCHITECT
FULLY SPRINKLERED
PROJECT PHASE
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
U.S. Department of Veteran Affairs
F
E
D
C
B
A
E
D
C
B
A
COMMISSIONING
GLHN ARCHITECTS & ENGINEERS, INC.
2939 E. BROADWAY BLVD
TUCSON, AZ 85716
(520) 881-4546
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 W. 161ST STREET
OLATHE, KS 66062
(913) 829-8650
CONSTRUCT REPLACEMENT WAREHOUSEMECHANICAL LEGEND
01/06/2020 JRM CSC
500 AZ-89, PRESCOTT, AZ 86301
165-MG-000
649-414
BID DOCUMENTS
Revision # Date
ARU
AC
AC
AC
AC
165-M-301 50
EG-1
EG-1
T
28"WX28"LX24"H OUTDOOR
CONDENSING UNIT FOR
WALK-IN COOLER ON 3'X3'
CONCRETE PAD
STOR
(FLAMM)
STOR (AMMO)
STOR
(SHRED)
WRAPPING
SV OFFICE
BREAK ROOM
WALK-IN REF.
SECURE
STOR.
IT ROOM
ELEC
CORR
PLOTTING
MECH
UNI TLT
UNI TLT
CORR
HAC
WAREHOUSE
165-M-301
WORKSPACE
CU-DS
DS
DS
CU-DS
AHU
"x
S A
CD-1
CD-1
CD-1
EG-1
EG-1
EG-1
CD-3
CD-3
EG-2
EG-2
EG-2
CD-2
CD-2
RG-2
10"ø RA
8"x8" SA
RG-2
12"ø RA
10"ø RA
8"ø RA
6"ø RA
RG-1
RG-1
8"ø RA
6"ø EA 6"ø EA
12"x12" EA
10"ø EA
12"x6" EA
12"x12" SA
10"x14" EA
10"ø EA
12"ø EA
12"ø EA
10"ø OA
14"x14" RA
CU-ARU
CU-AHU
1 2 4 5
A
B
D
E
F
C
SLV-1
36"x36" EA
36"x36" EA
EXHAUST DUCT UP TO
FAN ON ROOF
EXHAUST DUCT UP TO
FAN ON ROOF
180"x42" OA26"x116" OA
RG-1
RG-1
TT
T
AHU-1
RG-1
EG-3
TRANSFER
GRILLE
DRAWING NUMBER
VA PROJECT NUMBER
DATE
PROJECT TITLE
BUILDING NUMBER
PROJECT LOCATION
CHECKED BY DRAWN BY
APPROVED: PROJECT DIRECTOR
VA FORM 08-6231
Office of Construction and Facilities Management
Dwg.
CONSULTANT INFORMATION
STRUCTURAL / CIVIL ENGINEER
F
H2B, INC.
1225 N. LOOP WEST, SUITE 900
HOUSTON, TX 77008
(713) 864-2900
SHEET TITLE
ARCHITECT
FULLY SPRINKLERED
PROJECT PHASE
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
U.S. Department of Veteran Affairs
F
E
D
C
B
A
E
D
C
B
A
COMMISSIONING
GLHN ARCHITECTS & ENGINEERS, INC.
2939 E. BROADWAY BLVD
TUCSON, AZ 85716
(520) 881-4546
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 W. 161ST STREET
OLATHE, KS 66062
(913) 829-8650
CONSTRUCT REPLACEMENT WAREHOUSEMECHANICAL HVAC PLAN - LEVEL 1
FLOOR PLAN
01/06/2020 JRM CSC
500 AZ-89, PRESCOTT, AZ 86301
165-MH-101
649-414
BID DOCUMENTS
N
SCALE = 1/8" = 1'-0"1
MECHANICAL HVAC PLAN - LEVEL 1 FLOOR PLAN
GENERAL NOTES:
1. COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER’S REPRESENTATIVE.
2. COORDINATE MECHANICAL WORK WITH ALL OTHER TRADES. VERIFY ALL EXISTING
CONDITIIONS BEFORE THE START OF WORK.
3. SCHEDULE WORK TO MINIMIZE DISRUPTION OF SERVICES TO EXISTING FACILITIES.
4. SEE SHEET 165-GI-001 FOR ADDITIONAL INFORMATION WITH REGARDS TO SCHEDULING AND
PHASING REQUIREMENTS.
KEYNOTE LEGEND
1 12"x12" EXHAUST DUCT UP TO EXHAUST FAN ON ROOF ABOVE.
2 10"x14" EXHAUST DUCT UP TO EXHAUST FAN ON ROOF ABOVE.
3 12"Ø EXHAUST DUCT UP TO EXHAUST FAN ON ROOF ABOVE.
4 ROUTE 116"x26" OUTSIDE AIR DUCT FROM ARU-1 AND CONNECT TO PLENUM AT INTAKE LOUVER
SLV-1.
9 MOUNT GRILLE AT 1'-0" AFF. 12"x6" EXHAUST DUCT UP TO EF-2 ON ROOF ABOVE. TRANSITION
TO 10"Ø PRIOR TO ROOF PENETRATION. PROVIDE PROTECTIVE HOUSING FOR EXPOSED DUCT
ON ROOF.
10 180"x42" INTAKE LOUVER. COORDINATE EXACT LOCATION AND WITH ARCHITECTURAL
ELEVATIONS. PROVIDE MOUNTING HARDWARE AND FRAME TO FIT WITHIN ARCHITECTURAL
PANEL SYSTEM.
EF
EF
EF
EF
IH
1 2 4 5
A
B
D
E
F
C
STACK FROM INDUCED
DRAFT FAN AT ARU-1
EF
EF
12"Ø COMBINED WATER
HEATER AND FURNACE
FLUE PIPE.
12" Ø COMBUSTION AIR
DUCTS THROUGH ROOF
DRAWING NUMBER
VA PROJECT NUMBER
DATE
PROJECT TITLE
BUILDING NUMBER
PROJECT LOCATION
CHECKED BY DRAWN BY
APPROVED: PROJECT DIRECTOR
VA FORM 08-6231
Office of Construction and Facilities Management
Dwg.
CONSULTANT INFORMATION
STRUCTURAL / CIVIL ENGINEER
F
H2B, INC.
1225 N. LOOP WEST, SUITE 900
HOUSTON, TX 77008
(713) 864-2900
SHEET TITLE
ARCHITECT
FULLY SPRINKLERED
PROJECT PHASE
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
U.S. Department of Veteran Affairs
F
E
D
C
B
A
E
D
C
B
A
COMMISSIONING
GLHN ARCHITECTS & ENGINEERS, INC.
2939 E. BROADWAY BLVD
TUCSON, AZ 85716
(520) 881-4546
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 W. 161ST STREET
OLATHE, KS 66062
(913) 829-8650
CONSTRUCT REPLACEMENT WAREHOUSEMECHANICAL HVAC PLAN - ROOF
PLAN
01/06/2020 JRM CSC
500 AZ-89, PRESCOTT, AZ 86301
165-MH-102
649-414
BID DOCUMENTS
N
SCALE = 1/8" = 1'-0"1
MECHANICAL HVAC PLAN - BLDG 165 ROOF PLAN
GENERAL NOTES:
1. COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER’S REPRESENTATIVE.
2. COORDINATE MECHANICAL WORK WITH ALL OTHER TRADES. VERIFY ALL EXISTING
CONDITIIONS BEFORE THE START OF WORK.
3. SCHEDULE WORK TO MINIMIZE DISRUPTION OF SERVICES TO EXISTING FACILITIES.
4. SEE SHEET 165-GI-001 FOR ADDITIONAL INFORMATION WITH REGARDS TO SCHEDULING AND
PHASING REQUIREMENTS.
KEYNOTE LEGEND
5 INTERLOCK FAN OPERATION WITH ARU-1 ECONOMIZER.
6 EXHAUST FAN SHALL RUN CONSTANTLY.
7 EXHAUST FAN SHALL RUN WHEN AHU-1 IS IN OPERATION.
8 VARIABLE SPEED EXHAUST FAN SHALL RUN WHEN AHU-1 IS IN ECONOMIZER MODE TO PROVIDE
BUILDING PRESSURE RELIEF.
9 MOUNT GRILLE AT 1'-0" AFF. 12"x6" EXHAUST DUCT UP TO EF-2 ON ROOF ABOVE. TRANSITION TO
10"Ø PRIOR TO ROOF PENETRATION. PROVIDE PROTECTIVE HOUSING FOR EXPOSED DUCT ON
ROOF.
LEVEL 1
0' - 0"
ROOF
36' - 0"
ARU
AC
DISCHARGE PLENUM
DX COOLING COIL
INDUCED DRAFT FAN
GAS BURNER
SUPPLY FAN
PREFILTER 2
INTAKE PLENUM / PREFILTER 1
LEVEL 1
0' - 0"
MEZZANINE T.O.C.
18' - 0"
ROOF EAVE
36' - 0"
CLEANOUT COVER
WITH DRAIN PLUG
NOTES:
1. WEIGHT OF STACK MUST BE SUPPORTED FROM
FLOOR OR BUILDING STRUCTURE. DO NOT SUPPORT
STACK FROM INDUCED DRAFT FAN.
2. RECOMMENDED STACK MATERIAL IS 14 GA. SERIES
STAINLESS STEEL, CONTINUOUSLY BUTT WELDED
EXHAUST STACK.
3. REFER TO MANUFACTURERS RECOMMENDATIONS
FOR STACK AND CAP SIZES.
1 2 3
116"x26" OA
MECH
WH-1
AHU
EG-2
"ø
R A
"x
S A
4 5
B
C
RG-1RG-1
12"x6" EA
OA DUCT DOWN FROM INTAKE
HOOD ON ROOF ABOVE
10"ø EA
10"Ø TRANSFER AIR
14"x14" RA
RETURN AIR PLENUM BELOW AHU.
COORDINATE SIZE WITH AHU OVERALL
DIMENSIONS. PROVIDE SUPPORT
FROM FLOOR, DO NOT USE RETURN
AIR DUCTWORK FOR SUPPORT.
12"Ø FLUE UP
THROUGH ROOF
(2) 12" Ø COMBUSTION
AIR DUCTS THROUGH
ROOF. MOUNT ONE AT
1'-0" AFF, AND THE
OTHER AT 1'-0" BELOW
THE CEILING.
DRAWING NUMBER
VA PROJECT NUMBER
DATE
PROJECT TITLE
BUILDING NUMBER
PROJECT LOCATION
CHECKED BY DRAWN BY
APPROVED: PROJECT DIRECTOR
VA FORM 08-6231
Office of Construction and Facilities Management
Dwg.
CONSULTANT INFORMATION
STRUCTURAL / CIVIL ENGINEER
F
H2B, INC.
1225 N. LOOP WEST, SUITE 900
HOUSTON, TX 77008
(713) 864-2900
SHEET TITLE
ARCHITECT
FULLY SPRINKLERED
PROJECT PHASE
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
U.S. Department of Veteran Affairs
F
E
D
C
B
A
E
D
C
B
A
COMMISSIONING
GLHN ARCHITECTS & ENGINEERS, INC.
2939 E. BROADWAY BLVD
TUCSON, AZ 85716
(520) 881-4546
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 W. 161ST STREET
OLATHE, KS 66062
(913) 829-8650
CONSTRUCT REPLACEMENT WAREHOUSEMECHANICAL SECTIONS AND
ENLARGED PLANS
01/06/2020 JRM CSC
500 AZ-89, PRESCOTT, AZ 86301
165-M-301
649-414
BID DOCUMENTS
SCALE = 1/4" = 1'-0"1
MECHANICAL HVAC SECTION - ARU ELEVATION
GENERAL NOTES:
1. COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER’S REPRESENTATIVE.
2. COORDINATE MECHANICAL WORK WITH ALL OTHER TRADES. VERIFY ALL EXISTING
CONDITIIONS BEFORE THE START OF WORK.
3. SCHEDULE WORK TO MINIMIZE DISRUPTION OF SERVICES TO EXISTING FACILITIES.
4. SEE SHEET 165-GI-001 FOR ADDITIONAL INFORMATION WITH REGARDS TO SCHEDULING AND
PHASING REQUIREMENTS.
SCALE = 1/4" = 1'-0"2
ENLARGED MECHANICAL ROOM 113 PLAN
MAIN EXHAUST OR RETURN
PLAN VIEW
AIR
FLOW AIR
FLOW
PROVIDE VOLUME DAMPER
AT EACH BRANCH DUCT
1/4W OR 4" [100mm]
MIN.
BRANCH DUCT
VD
W
DESIGNER'S NOTES:
BRANCH DUCT TAKE-OFF PLAN VIEW
TURNING VANES
1/4 W OR 4" [100mm] MIN.
A
IR
F L O
W
MAIN SUPPLY
DUCT
AIR
FLOW
AIR
FLOW
AIR
FLOW
VOLUME EXTRACTOR; ADJUSTABLE
FROM FULLY CLOSED POSITION TO
CFM NOTED ON FLOOR PLANS
MAIN
SUPPLY
DUCT
TOP REGISTER
ADJUSTABLE
METAL ROD
OR LINKAGE
PROVIDE VOLUME
DAMPER
PROVIDE VOLUME
DAMPER
SEE FLOOR PLAN FOR
SPLIT DIMENSION
MAIN
SUPPLY
DUCT
SUPPLY REGISTER
OR BRANCH DUCT
A
IR
F L O
W
AIR
FLOW
AIR
FLOW
SUPPLY REGISTER TAKE-OFF
PLAN VIEW
AIR SPLIT DUCT TAKE-OFF PLAN
VIEW
1. THE SUPPLY REGISTER TAKE-OFF MAY BE USED FOR UP UP TO 25% OF THE MAIN DUCT CFM.
THE BRANCH DUCT TAKE-OFF MAY BE USED FOR UP TO 15% OF THE MAIN DUCT CFM ANYTIME
AND UP TO 40% WHEN THE MAIN DUCT VELOCITY IS 1000 FPM [5.1 M/S] OR LESS. THE AIR SPLIT
DUCT TAKE-OFF SHALL BE USED IN ALL OTHER CASES AND MAY BE USED AT ANYTIME.
2. SHOW ALL VOLUME DAMPERS ON FLOOR PLANS.
W
DUCT (WHEN SHOWN)
FACTORY ASSEMBLED
HINGED HOOD WITH
LATCH & BIRD SCREEN
CURB CAP
SEE NOTE 1
SEE NOTE 2
ROOF
TRANSITION DUCT TO
FULL SIZE OF DAMPER
SUPPLIED WITH HOOD
WOOD NAILING
STRIP
PREFABRICATED
ROOF CURB
SEE NOTE 2
GRAVITY BACKDRAFT
DAMPER.
SECURE HOOD TO WOOD NAILING STRIP WITH 3/8" [10mm] CADMIUM PLATED LAG BOLTS NOT
OVER 12" [300mm] ON CENTER.
SECURE ROOF CURB, DUCTWORK AND DAMPER TO ROOF WITH EXPANSION BOLTS
(CONCRETE ROOF) OR RUST RESISTANT BOLTS (MENTAL DECK & BAR JOIST ROOF).
NOTE:
1.
2.
NOTE:
1.
2.
DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR
MULTI-BLADE DAMPERS & ROUND DAMPERS.
INSULATION SEE
SPECIFICATION
DAMPER BLADE
1/8" [6mm]
CLEARANCE
ALL AROUND
OUTSIDE END BEARING
INSIDE END BEARING
HANDLE WITH
LOCKING
QUADRANT
INSULATION
STAND-OFF
1/2" [15mm] ROUND
ROD PIN
DUCT
STIFFEN BLADE
AS REQUIRED
SIDE ELEVATION SECTION
DRAW THRU
BLOW THRU
X
2X
UNIT TYPE A B
WHERE X = STATIC PRESSURE IN PAN
CLEAN OUT
FLOOR SINK
NOTE: 1. CPVC PIPE MAY BE USED ONLY IF APPROVED BY LOCAL VA AND
IS INDOORS AND DOES NOT PASS THROUGH RATED BARRIERS.
2. DIELECTRIC FITTING TO BE USED WHEN TWO DISSIMILAR METALS ARE
TO BE CONNECTED.
PITCH DOWN
TOWARD DRAIN
DRAIN LINE SHALL BE AT LEAST THE SAME SIZE
AS THE NIPPLE ON THE DRAIN PAN
PIPING SHALL BE RIGID COPPER TYPE L OR TYPE
M UNLESS NOTE BELOW IS MET
DRAIN
PAN
DIELECTRIC
FITTING
1" [25mm]
MINIMUM
2" [50mm]
PLUS X
B A
[2 m m
TYPICAL ANCHOR BOLT
NUT & WASHER
PROVIDE #3 BARS 12" [300mm] O.C.
EACH WAY IN THE BASE & DOWEL
BASE TO FLOOR
PROVIDE DOUBLE SLAB
REINFORCING IN BASE AREA
TYPICAL ANCHOR BOLT
NUT & WASHER
NOTE:
L & W DIMENSIONS SHALL BE
6" [150mm] GREATER THAN
THE EQUIPMENT BASE
PLATE.
EQUIPMENT BASE PLATE
EQUIPMENT BASE PLATE
SECTION A-A (BASE NOT POURED WITH SLAB)
SECTION A-A (BASE POURED WITH FLOOR SLAB)
[400mm] 16"
M
IN
[1 m m
L /1
M
IN
[1 m m
L /1
SECTION B-B
WELD HEAD TO PLATE OR
BEND OVER END 5D
PIPE SLEEVE (5D, 3" [75mm]
MIN.)
ANCHOR
BOLT (TYP)
CONCRETE BASE
PLAN
D
FLOOR
[2 m m
W
A
B B
L
A
2D
5D
D
DRAWING NUMBER
VA PROJECT NUMBER
DATE
PROJECT TITLE
BUILDING NUMBER
PROJECT LOCATION
CHECKED BY DRAWN BY
APPROVED: PROJECT DIRECTOR
VA FORM 08-6231
Office of Construction and Facilities Management
Dwg.
CONSULTANT INFORMATION
STRUCTURAL / CIVIL ENGINEER
F
H2B, INC.
1225 N. LOOP WEST, SUITE 900
HOUSTON, TX 77008
(713) 864-2900
SHEET TITLE
ARCHITECT
FULLY SPRINKLERED
PROJECT PHASE
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
U.S. Department of Veteran Affairs
F
E
D
C
B
A
E
D
C
B
A
COMMISSIONING
GLHN ARCHITECTS & ENGINEERS, INC.
2939 E. BROADWAY BLVD
TUCSON, AZ 85716
(520) 881-4546
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 W. 161ST STREET
OLATHE, KS 66062
(913) 829-8650
CONSTRUCT REPLACEMENT WAREHOUSEHVAC DETAILS
01/06/2020 JRM CSC
500 AZ-89, PRESCOTT, AZ 86301
165-M-501
649-414
BID DOCUMENTS
SCALE = NTS1
EXHAUST OR RETURN BRANCH DUCTWORK
SCALE = NTS2
SUPPLY DUCTWORK TAKE - OFFS
SCALE = NTS3
LOW SILHOUETTE EXHAUST OR INTAKE HOOD
SCALE = NTS4
VOLUME DAMPER
SCALE = NTS5
AIR HANDLING UNIT DRAIN TRAP
SCALE = NTS6
CONCRETE EQUIPMENT BASES
DRAWING NUMBER
VA PROJECT NUMBER
DATE
PROJECT TITLE
BUILDING NUMBER
PROJECT LOCATION
CHECKED BY DRAWN BY
APPROVED: PROJECT DIRECTOR
VA FORM 08-6231
Office of Construction and Facilities Management
Dwg.
CONSULTANT INFORMATION
STRUCTURAL / CIVIL ENGINEER
F
H2B, INC.
1225 N. LOOP WEST, SUITE 900
HOUSTON, TX 77008
(713) 864-2900
SHEET TITLE
ARCHITECT
FULLY SPRINKLERED
PROJECT PHASE
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
U.S. Department of Veteran Affairs
F
E
D
C
B
A
E
D
C
B
A
COMMISSIONING
GLHN ARCHITECTS & ENGINEERS, INC.
2939 E. BROADWAY BLVD
TUCSON, AZ 85716
(520) 881-4546
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 W. 161ST STREET
OLATHE, KS 66062
(913) 829-8650
CONSTRUCT REPLACEMENT WAREHOUSEHVAC SCHEDULES
01/06/2020 JRM CSC
500 AZ-89, PRESCOTT, AZ 86301
165-M-601
649-414
BID DOCUMENTS
SPLIT-SYSTEM AIR HANDLER SCHEDULE
MARK
BASIS OF DESIGN
(MANUFACTURER / MODEL) SERVES MOUNTING
EVAPORATOR FAN DX COOLING DATA GAS HEATING DATA ELECTRICAL
WEIGHT
(LBS) NOTES
SUPPLY
(CFM)
OUTSIDE
AIR (CFM) HP
ESP
(IN/WG)
REFR
TYPE
NOMINAL
TONS
TOTAL
(MBH)
SENSIBLE
(MBH)
EAT DB
°F
EAT WB
°F
LAT DB
°F
LAT WB
°F
FUEL
TYPE
CAP
(MBH)
EAT
°F
LAT
°F MCA MOCP VOLTAGE PHASE
AHU 1 GUARDIAN / RGF19060BE12MP13 ADMIN AREAS FLOOR 1,000 85 .5 .65 R-410A 3.0 34.4 22.8 80 67 59 56 NAT GAS 25.0 66 80 10 15 115 1 125 ALL LISTED
AIR ROTATION UNIT SCHEDULE
MARK
BASIS OF DESIGN
(MANUFACTURER / MODEL) LOCATION SERVES
DESIGN
AIRFLOW (CFM)
MIN OA
(CFM)
TSP
(IN/WC) FANS (QTY) MOTOR HP RPM VFD Y/N V/PH
DX COOLING DATA GAS HEATING DATA ELECTRICAL
WEIGHT
(LBS) NOTES
REFR
TYPE
TOTAL
(MBH)
SENSIBLE
(MBH)
COIL
EDB °F
COIL
EWB °F
COIL
LDB °F
COIL
LWB °F
ROWS FUEL TYPE
SENSIBLE
(MBH)
INPUT
(MBH)
OUTPUT
(MBH)
COIL
EAT °F
COIL
LAT °F
INDUCED
DRAFT FAN HP
INDUCED DRAFT
FAN V/PH DISC. TYPE STARTER TYPE VOLTAGE PHASE
ARU 1 APPLIED AIR / GHLIFA-250/100/85 WAREHOUSE FLOOR WAREHOUSE 24,000 9,000 2.1 3 25 901 Yes 460/3 R-410A 607.1 431.8 82.7 60.0 55.2 48.9 2 NATURAL GAS 358.9 1,062 850 55.0 90.0 1/2 115/1 VFD VFD 460 3 8,205 ALL LISTED
CONDENSING UNIT SCHEDULE
MARK
BASIS OF DESIGN
(MANUFACTURER / MODEL) LOCATION SERVES
REFR
TYPE
TOTAL
(MBH) SEER
AMBIENT DB TEMP
(°F)
ELECTRICAL
WEIGHT NOTESMCA MOCP VOLTAGE PHASE
CU-AHU 1 GUARDIAN / RAC14L36B23S EAST AHU 1 R-410A 34.4 12 95 °F 20 30 208 1 150 1, 2, 4
CU-ARU 1 JCI / J50YDC00A4BAA2 NE CORNER ARU 1 R-410A 576.2 95 °F 91 100 460 3 2,345 ALL LISTED
CU-DS 1 SAMSUNG / AC030MXSCCC/AA SE CORNER DS 1 R-410A 18.0 18.8 95 °F 10 15 208 1 90 1, 2, 4
CU-DS 2 SAMSUNG / AC030MXSCCC/AA SE CORNER DS 2 R-410A 18.0 18.8 95 °F 10 15 208 1 90 1, 2, 4
DIFFUSER, REGISTER, AND GRILLE SCHEDULE
MARK
BASIS OF DESIGN
(MANUFACTURER / MODEL) MOUNTING DESCRIPTION
FACE
SIZE NECK SIZE
MAX
N.C.
PRESSURE
DROP (IN/WC) NOTES
EXHAUST
EG-1 TITUS / 355 RS CEILING LOUVERED GRILLE 35° DEFLECTION - 1/2" SPACING 12"x12" SEE PLAN 30 0.24 ALL LISTED
EG-2 TITUS / 355 RS CEILING LOUVERED GRILLE 35° DEFLECTION - 1/2" SPACING 24"x24" SEE PLAN 30 0.24 ALL LISTED
EG-3 TITUS / 355 RS WALL LOUVERED GRILLE 35° DEFLECTION - 1/2" SPACING 14"x8" 12"x6" 30 0.24 ALL LISTED
RETURN
RG-1 TITUS / 50F CEILING EGGCRATE RETURN GRILLE - 1/2" SPACING 24"x12" SEE PLAN 30 0.24 ALL LISTED
RG-2 TITUS / 50F CEILING EGGCRATE RETURN GRILLE - 1/2" SPACING 24"x24" SEE PLAN 30 0.24 ALL LISTED
SUPPLY
CD-1 TITUS / TMS-AA CEILING SQUARE CONE DIFFUSER WITH ROUND NECK 12"x12" 6" 30 0.24 ALL LISTED
CD-2 TITUS / TMS-AA CEILING SQUARE CONE DIFFUSER WITH ROUND NECK 24"x24" 6" 30 0.24 ALL LISTED
CD-3 TITUS / TMS-AA CEILING SQUARE CONE DIFFUSER WITH ROUND NECK 24"x24" 8" 30 0.24 ALL LISTED
EXHAUST FAN SCHEDULE
MARK
BASIS OF DESIGN
(MANUFACTURER / MODEL) LOCATION SERVES MOUNTING TYPE
FAN ELECTRICAL
NOTES
AIR FLOW
(CFM)
SP
(IN/WC) DRIVE
VFD
Y/N HP
MAX
RPM VOLTAGE PHASE
STARTER
TYPE
EF 1 LOREN COOK / ACRU-D VF ROOF WRAPPING ROOF - CURB UPBLAST CENTRIFUGAL 525 0.5 DIRECT No 1/6 1725 115 1 INTEGRAL 1, 2
EF 2 LOREN COOK / IMH ROOF FLAMMABLE STOR ROOF - FRAME UPBLAST SPARK RESIST 300 1.0 BELT No 1/2 1725 115 1 INTEGRAL 1, 2
EF 3 LOREN COOK / ACRU-D VF ROOF MECHANICAL / RR ROOF - CURB UPBLAST CENTRIFUGAL 550 0.5 DIRECT No 1/6 1725 115 1 INTEGRAL 1, 2
EF 4 LOREN COOK / ACRU-D VF ROOF PRINTING ROOF - CURB UPBLAST CENTRIFUGAL 500 0.5 DIRECT No 1/6 1725 115 1 INTEGRAL 1, 2
EF 5 GREENHECK / CUBE-360 ROOF ARU-1 RELIEF ROOF - CURB UPBLAST CENTRIFUGAL 12,000 1.0 BELT No 5 628 460 3 VFD ALL LISTED
EF 6 GREENHECK / CUBE-360 ROOF ARU-1 RELIEF ROOF - CURB UPBLAST CENTRIFUGAL 12,000 1.0 BELT No 5 628 460 3 VFD ALL LISTED
AIR CURTAIN - ELECTRIC HEAT SCHEDULE
MARK LOCATION
BASIS OF DESIGN
(MANUFACTURER / MODEL)
UNIT SPECS ELECTRICAL
NOTES
AIRFLOW
(CFM) HP
MOTOR
QTY
HEATING
CAPACITY
(KW) V/PH
AC 1 100 WAREHOUSE POWERED AIRE / ETD-2-96 7,750 0.75 2 20 460/3 ALL LISTED
AC 2 100 WAREHOUSE POWERED AIRE / ETD-2-96 7,750 0.75 2 20 460/3 ALL LISTED
AC 3 100 WAREHOUSE POWERED AIRE / ETD-2-96 7,750 0.75 2 20 460/3 ALL LISTED
AC 4 100 WAREHOUSE POWERED AIRE / ETD-2-96 7,750 0.75 2 20 460/3 ALL LISTED
1 EQUIPMENT FURNISHED AND INSTALLED BY DIVISION 23 CONTRACTOR.
2 MOUNT UNIT PER MANUFACTURERS RECOMMENDATIONS TO FACE OF WALL AND SUPPORT VERTICALLY.
3 STARTER AND DISCONNECT SWITCH PROVIDED BY DIVISION 26 CONTRACTOR
4 REFER TO SEQUENCE OF OPERATION FOR UNIT CONTROLS
5 PROVIDE WIRING TERMINAL STRIP FOR THERMOSTATIC CONTROL BY BUILDING AUTOMATION SYSTEM. COORDINATE REQUIREMENTS WITH
TEMPERATURE CONTROLS CONTRACTOR
6 PROVIDE WITH DELAY MICROSWITCH WITH ADJUSTABLE DELAY TIMERS PRE-MOUNTED IN THE AIR CURTAIN CONTROL PANEL.
7 PROVIDE UNIT WITH ELECTRIC HEATING ELEMENT.
LOUVER SCHEDULE
MARK
ASSOCIATED
FAN/UNIT
BASIS OF DESIGN
(MANUFACTURER / MODEL) WIDTH HEIGHT
AIRFLOW
(CFM)
MINIMUM FREE
AREA (SF)
AIR VELOCITY
(FPM)
PD
(IN/WC) NOTES
INTAKE
SLV-1 ARU-1 RUSKIN / ELF6375DX 180" 42" 24,000 29.86 804 1.27 ALL LISTED
1. PROVIDE W/ ALUMINUM BIRDSCREEN
2. PROVIDE WITH 2-COAT CLEAR ANODIZED KYNAR FINISH. COLOR AS SELECTED BY ARCHITECT.
3. PROVIDE LOW VOLTAGE MOTORIZED DAMPER INTERLOCKED W/ ASSOCIATED FAN OR UNIT.
4. FRAME TYPE SHALL MATCH WALL CONSTRUCTION, COORDINATE WITH ARCHITECT.
1 PROVIDE MANUAL BALANCING DAMPER AT TAP TO MAIN DUCT. IF TAP IS ABOVE INACESSIBLE CEILING, PROVIDE OPPOSED BLADE DAMPER FOR GRILLES AND RADIAL DAMPERS
IN DIFFUSERS WITH ROUND NECK AT FACE OF DEVICE.
2 FRAME TYPE TO MATCH CEILING OR WALL CONSTRUCTION, COORDINATE WITH ARCHITECTURAL PLANS AND REFLECTED CEILING PLAN.
3 BRANCH DUCT SIZE SHALL BE SAME AS NECK SIZE UNLESS OTHERWISE SHOWN ON DRAWINGS.
4 PROVIDE INSULATED PLENUM AND NECK.
5 ALL ALUMINUM CONSTRUCTION
INTAKE/RELIEF HOOD SCHEDULE
MARK
BASIS OF DESIGN
(MANUFACTURER / MODEL) DESCRIPTION
ASSOCIATED
UNIT
PRESSURE DROP
(FT-W.C.)
SIZE
(IN) NOTES
INTAKE
IH 1 GREENHECK / GR-10 LOW SILHOUETTE AIRFLOW INTAKE AHU-1 0.30 10 ALL LISTED
1 PROVIDE WITH 1/4" GRID ALUMINUM BIRDSCREEN.
2 PROVIDE MANUFACTURERS STANDARD INSULATED ROOF CURB WITH MINIMUM HEIGHT OF 8".
3 PROVIDE INTERNAL MOTOR OPERATED DAMPER INTERLOCKED WITH ASSOCIATED EQUIPMENT.
1 PROVIDE FACTORY MOUNTED DISCONNECT SWITCH
2 PROVIDE MANUFACTURERS GRAVITY BACKGRAFT DAMPER, ROOF CURB, AND ALUMINUM BIRDSCREEN.
3 PROVIDE WITH INTEGRAL VFD
1 COORDINATE LOCATIONS FOR ALL REFRIGERANT PIPING DEVICES WITH THE MANUFACTURER TO MAINTAIN SERVICEABILITY AND ACCESSIBILITY.
2 PROVIDE FACTORY MOUNTED DISCONNECT, STARTER, HAIL GUARDS, AND SINGLE POINT POWER CONNECTION.
3 PROVIDE WITH 4-PIPE, FOUR STAGE COOLING, RAWAL VALVE, LOW AMBIENT KIT, PHASE MONITOR KIT, AND SINGLE POINT POWER CONNECTION.
4 UNIT CABINET SHALL BE POWDER PAINTED STEEL.
1 PROVIDE FACTORY MOUNTED DISCONNECT INSTALLED ON SERVICE SIDE OF UNIT.
2 DIVISION 21 CONTRACTOR SHALL PROVIDE SMOKE DETECTORS IN SUPPLY AND RETURN AIR DISCHARGE PLENUMS.
3 ELEVATION: 5300 FEET ASL. COIL CAPACITIES AND AIRFLOWS SHOWN INCLUDE ALTITUDE CORRECTION VALUES.
4 PROVIDE WITH ECONOMIZER, OUTSIDE AIR AND RETURN AIR DAMPERS.
5 UNIT SHALL INCLUDE MANUFACTURER PROVIDED SERVICE PLATFORMS FOR EQUIPMENT COMPONENTS.
COOLING ONLY DUCTLESS SPLIT-SYSTEM AIR HANDLER SCHEDULE
MARK
BASIS OF DESIGN
(MANUFACTURER / MODEL) SERVES MOUNTING
SUPPLY
(CFM)
DX COOLING DATA ELECTRICAL
WEIGHT
(LBS) NOTES
REFR
TYPE
NOMINAL
TONS
TOTAL
(MBH)
SENSIBLE
(MBH)
EAT
DB °F
EAT
WB °F
LAT
DB °F
LAT
WB °F MCA MOCP VOLTAGE PHASE
DS 1 SAMSUNG / AC030MNTDCH/AA IT ROOM WALL 350 R-410A 1.5 18.0 12.2 80 67 55 52 10 15 208 1 ALL LISTED
DS 2 SAMSUNG / AC030MNTDCH/AA ELEC ROOM WALL 350 R-410A 1.5 18.0 12.2 80 97 55 52 10 15 208 1 ALL LISTED
1 PER MANUFACTURERS RECOMMENDATIONS, CONTRACTOR SHALL VERIFY WITH EQUIPMENT SUPPLIER EXACT ROUTING AND SIZE OF INSULATED REFRIGERANT PIPING.
2 PROVIDE DISCONNECT SWITCH FOR EVAPORATOR SECTION AND CONDENSING SECTION.
3 PROVIDE WITH MANUFACTURERS WALL MOUNTED THERMOSTAT AND INTEGRAL CONDENSATE PUMP.
4 SEE CONDENSING UNIT SCHEDULE FOR SINGLE POINT POWER CONNECTION REQUIREMENTS.
1 PER MANUFACTURERS RECOMMENDATIONS, CONTRACTOR SHALL VERIFY WITH EQUIPMENT SUPPLIER EXACT ROUTING AND SIZE OF INSULATED REFRIGERANT PIPING.
2 PROVIDE DISCONNECT SWITCH FOR EVAPORATOR AND CONDENSING SECTION.
3 DX COOLING COOL BASIS OF DESIGN: GUARDIAN MODEL # CM36BBCA1.
M
CT
M
M
M
M
CHW
HW
DX
M
HW
IFB
ELEC
M
SD
M
SD
AFS
T
H
H
L
H
L
FRZ
T
P
T
H
H
L
H
L
O
H L
ABBREVIATIONS
AI ANALOG INPUT
A
AFS AIRFLOW STATION
BI BINARY INPUT
B
BO BINARY OUTPUT
BP BUILDING PRESSURE
AF AFTER FILTER
CC COOLING COIL
C
CHW CHILLED WATER
CP CIRCULATING PUMP
DX DIRECT EXPANSION
D
DP DIFFERENTIAL PRESSURE
EA EXHAUST AIR
E
EF EXHAUST FAN
CT CURRENT TRANSMITTER
FF FINAL FILTER
F
GF GAS FURNACE
G
HC HEATING COIL
H
ER ENERGY RECOVERY
BPC BUILDING PRESSURE CONTROL
HW HOT WATER
HGB HOT GAS BYPASS
IFB INTEGRAL FACE AND BYPASS
I
LAT LEAVING AIR TEMPERATURE
L
LWT LEAVING WATER TEMPERATURE
HGB HOT GAS BYPASS
ACV AIRFLOW CONTROL VALVE
AHU AIR HANDLING UNIT
EAT ENTERING AIR TEMPERATURE
EWT ENTERING WATER TEMPERATURE
MAT MIXED AIR TEMPERATURE
M
MOA MINIMUM OUTSIDE AIR
ECM ELECTRONICALLY COMMUTATED MOTOR
NG NATURAL GAS
N
DD DIRECT DRIVE
OA OUTSIDE AIR
O
OCC OCCUPANCY
OX OXYGEN
OXS OXYGEN SENSOR
PCC PRECOOLING COIL
P
PHC PREHEAT COIL
PF PREFILTER
BAC BUILDING AUTOMATION CONTROL
RA RETURN AIR
R
R/E RETURN/EXHAUST
R/R RETURN/RELIEF
SA SUPPLY AIR
S
SF SUPPLY FAN
SD SMOKE DAMPER
RF RETURN FAN
FSD FIRE SMOKE DAMPER
TCP TEMPERATURE CONTROL PANEL
T
TA TRANSFER AIR
TMV THERMOSTATIC MIXING VALVE
TCV TEMPERATURE CONTROL VALVE
UV ULTRAVIOLET
U
VFD VARIABLE FREQUENCY DRIVE
V
SYMBOLS
EQUIPMENT
CHILLED WATER COIL
DIRECT EXPANSION
COIL
HOT WATER COIL
HOT WATER INTEGRAL
FACE-AND-BYPASS COIL
ELECTRIC HEATING
COIL
GAS FURNACE
HUMIDIFIER DISPERSION
GRID
MODULATING OPPOSED
BLADE DAMPER
MODULATING PARALLEL
BLADE DAMPER
SMOKE DAMPER
BACKDRAFT DAMPER
VAV ATU MODULATING
DAMPER
2-POSITION OPPOSED
BLADE DAMPER
2-POSITION PARALLEL
BLADE DAMPER
FILTER
BLOWER FAN
PLENUM FAN
PUMP
CURRENT TRANSMITTER
2-WAY MODULATING
CONTROL VALVE
THERMOSTATIC MIXING VALVE
3-WAY MODULATING
CONTROL VALVE
SENSORS & DEVICES
DUCTWORK
PIPING
ZONE
NEGATIVE SPACE
DIFFERENTIAL PRESSURE
SENSOR
POSITIVE SPACE DIFFERENTIAL
PRESSURE SENSOR
ZONE OCCUPANCY SENSOR
ZONE HUMIDITY SENSOR
ZONE TEMPERATURE SENSOR
AQUASTAT
FLOW METER
PRESSURE SENSOR
TEMPERATURE SENSOR
SUPPLY AIR DUCT
STATIC PRESSURE
SENSOR
RETURN/EXHAUST AIR DUCT
STATIC PRESSURE SENSOR
DIFFERENTIAL PRESSURE
SENSOR
DAMPER POSITION INDICATOR
HUMIDITY SENSOR
FREEZESTAT
TEMPERATURE SENSOR
SMOKE DETECTOR
AIRFLOW STATION
VOC VOLITILE ORGANIC COMPOUND
VOC VOLITILE ORGANIC COMPOUND
AIRFLOW SENSOR
RHC REHEAT COIL
XX XXXX
POINT TYPE
POINT NAME
AV ANALOG VIRTUAL
BV BINARY VIRTUAL
MECHANICAL CONTROLS LEGEND
AO ANALOG OUTPUT
POINTS LIST - BUILDING MONITORING
POINT ID POINT DESCRIPTION HARDWARE POINT SOFTWARE POINTS DISPLAY DEFAULT TRENDING TRENDING ALARM NOTES
AI AO BI BO AV BV LOOP SCHED. TREND ALARM GRAPHIC SETPOINT INTERVAL STORAGE STATUS
ADVANCED UTILITY METERING
ELECTRICITY X X X A,B
DOMESTIC WATER FLOW X X X A,B
OUTSIDE AIR TEMPERATURE X X X A,B
OUTSIDE AIR RELATIVE HUMIDITY X X X A,B
WEATHER STATION
BDP BUILDING DIFFERENTIAL PRESSURE X X 0.03 INWG 15 MIN. X X
OAT OUTSIDE AIR TEMPERATURE X X - 15 MIN. X A,B
OAH OUTSIDE AIR HUMIDITY X X - 15 MIN. X A,B
OADP OUTSIDE AIR DEWPOINT X X - 15 MIN. X A,B
SPACE TEMPERATURE MONITORING
MECH. STORAGE 115 X X X
NOTES:
A. SEE SPECIFICATION SECTION 251010 - ADVANCED UTILITY METERING SYSTEM
B. TCC SHALL COORDINATE ENERGY MONITORING POINTS WITH SECTION 25010.
PROJECT DESIGN CONDITIONS
CLIMATE CONDITONS
WEATHER STATION: 2009 ASHRAE CLIMATE DATA / Prescott Love Field, AZ
ASHRAE CLIMATE ZONE 4B
HEATING 99.6% (F DB): 17.5 ˚F (99.6% H DB)
HUMIDIFICATION 99.6% (DP/ HR / MCDB -1.9 ˚F / 6.0 / 36.9 ˚F
COOLING 0.4% (DB / MCWB) 94.3 ˚FDb / 61.2 ˚FWb
DEHUMIDIFICATION 0.4% (DP / HR / MCDB) 63.4 ˚FDb / 105.6 / 70.9 ˚FWb
MAX. AMBIENT DB TEMP (50 YRS) 105.7 ˚F
MIN. AMBIENT DB TEMP (50 YRS) -5.9 ˚F
BUILDING OPERATING HOURS (VERIFY WITH STATION):
MONDAY - FRIDAY 7:30 a.m. - 6 p.m.
SATURDAY 7:30 a.m. - 6 p.m.
SUNDAY 7:30 a.m. - 6 p.m.
SPACE / UNIT DESCRIPTIONS SET POINTS SPACE OPERATING HOURS NOTES
COOLING HEATING HUMIDIFICATION OCCUPIED / NIGHT SETBACK ROOM
OCC. UNOCC. OCC. UNOCC. Max. Min. AIR
M-F SAT. SUN. BALANCE
˚F Db ˚F Db ˚F Db ˚F Db %RH %RH (o) (+) (-) (- -) (+ +)
HVAC DESIGN MANUAL
75 78 70 68 60% 30% (+) 1-4
NON PATIENT ROOMS - SUPPORT AREAS
CONFERENCE ROOM 75 78 70 68 60% 20% (o) 1-4
BREAKROOM / LOUNGE 75 78 70 68 60% 20% (-) 1-4
OFFICES 75 78 70 68 60% 20% (o) 1-4
TOILETS - PUBLIC (PERIMETER) NA NA NA NA NA NA (- -) 1-4
GENERAL STORAGE NA NA NA NA NA NA (- -)
LOADING DOCK NA NA 60 NA NA NA (o)
NON PATIENT ROOMS - MISCELLANEOUS AREAS
COPY/PRINTING ROOM (LARGE) 75 78 70 68 NA NA (o) 1-4
ELECTRICAL EQUIPMENT ROOMS (EER)
ELECTRICAL EQUIPMENT CLOSETS WITHOUT INTERNAL HEAT GAIN NA NA NA NA NA NA NA 1-4
SATELLITE AND MAIN ELECTRICAL ROOMS WITH INTERNAL HEAT GAIN 86 NA 40 NA NA NA (o) 1-4
HOUSEKEEPING AID CLOSET (HAC) NA NA NA NA NA NA (- -) 1-4
LOADING DOCK NA NA 60 NA NA NA (o) 1-4
MECHANICAL EQUIPMENT ROOMS 84 NA 50 NA NA NA (o) 1-4
WALK-IN REFRIGERATOR AND FREEZERS NA NA NA NA NA NA NA 1-4
NOTES:
1 ZONE LEVEL OCCUPANCY HOUR SCHEDULE SHALL BE PER BUILDING OPERATING HOURS UNLESS OTHERWISE SCHEDULED.
2 ZONE LEVEL SET POINT CONDITIONS SHALL BE AS SCHEDULED UNLESS OTHERWISE SCHEDULED OR NOTED FOR ROOM SPECIFIC SPACE CONDITIONS.
4 DIVISION 23 CONTRACTOR TO PROVIDE ROOM AIR BALANCE AS SHOWN. AIR BALANCE SHALL BE NEUTRAL FOR NON-CRITICAL SPACES NOT SHOWN IN SCHEDULE.
DRAWING NUMBER
VA PROJECT NUMBER
DATE
PROJECT TITLE
BUILDING NUMBER
PROJECT LOCATION
CHECKED BY DRAWN BY
APPROVED: PROJECT DIRECTOR
VA FORM 08-6231
Office of Construction and Facilities Management
Dwg.
CONSULTANT INFORMATION
STRUCTURAL / CIVIL ENGINEER
F
H2B, INC.
1225 N. LOOP WEST, SUITE 900
HOUSTON, TX 77008
(713) 864-2900
SHEET TITLE
ARCHITECT
FULLY SPRINKLERED
PROJECT PHASE
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
U.S. Department of Veteran Affairs
F
E
D
C
B
A
E
D
C
B
A
COMMISSIONING
GLHN ARCHITECTS & ENGINEERS, INC.
2939 E. BROADWAY BLVD
TUCSON, AZ 85716
(520) 881-4546
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 W. 161ST STREET
OLATHE, KS 66062
(913) 829-8650
CONSTRUCT REPLACEMENT WAREHOUSEHVAC CONTROLS
01/06/2020 JRM CSC
500 AZ-89, PRESCOTT, AZ 86301
165-M-701
649-414
BID DOCUMENTS
T
DX
RA INLET
(1-SIDE)
OA
SA OUTLET
(3-SIDES)
2-STAGE
BURNER
DP
INSIDE OUTSIDE
LH
FRZ
M
M VFD
M
SD
GAS
BURNER
DX
T
T
T
AO MIXED AIR DAMPERS
PRE-FILTER STATUS
BO
AO
BI
SF START/STOP
SF VFD SPEED
SF VFD FAULT
BO STAGE 1
AO DX CO
AI SA LAT
BI SA SMOKE DETECTOR
AI MA TEMP
AIZONE TEMP
BI FREEZESTAT
COMPONENT CONTROL LOOPS
SUPPLY FAN CONTROL- VFD
When the HOA switch is in hand position, the variable speed supply fans shall operate at a speed set manually by the operator at the user interface of the drive.
When the HOA switch is in off position, the fan shall be off.
When the HOA switch is in auto position, the variable speed supply fans shall operate subject to the unit enable signal, and unit operating modes.
OCCUPIED MODE:
At fan startup, the fans shall energize and slowly ramp up to the fan speed required to maintain the supply airflow setpoint as determined during system startup.
UNOCCUPIED MODE:
The fan shall be OFF.
On a call for cooling/heating or override signal from the zone level, the fan shall operate as if in occupied mode until the call is cleared or the override is removed.
FILTER MONITORING - HOURS
The unit filters shall be monitored for preventative maintenance and diagnostic purposes.
ALL MODES:
The controller shall monitor the fan runtime to provide maintenance reminder at 50% of filter elapsed time (1100 hours) and an alarm at 100% elapsed time (2200 hours).
DIRECT EXPANSION COOLING COIL - MODULATING
OCCUPIED MODE:
UNOCCUPIED MODE:
The coil shall modulate off.
On a call for cooling or override signal from the zone level, the coil shall operate as if in occupied mode until the call is cleared or the override is removed.
GAS HEAT - 2-STAGE
OCCUPIED MODE:
UNOCCUPIED MODE:
The gas heating shall shut-off.
On a call for heating or override signal from the zone sensor the heating shall operate as if in occupied mode until the call is cleared or the override is removed.
SEQUENCE OF OPERATIONS
AIR ROTATION UNIT (ARU-1)
REPLACEMENT WAREHOUSE
GENERAL DESCRIPTION
The air rotation unit, ARU-1, described by this sequence of operations consist(s) of a variable speed supply fan array, DX cooling coil, and indirect gas fired heat exchanger which provides air-conditioning for the warehouse as shown on the drawings.
OPERATING MODES
OCCUPIED MODE
The ARU shall be in occupied mode per the project design conditions schedule shown on M-701
UNOCCUPIED MODE
The ARU shall be in unoccupied mode for all periods not included in the occupied hours of operation. Overrides of the unoccupied schedule are defined at the zone level control.
CONTROL SETPOINT RESETS
SUPPLY AIR TEMPERATURE RESET - TRIM AND
RESPOND - COOLING ONLY
Supply Air Temperature Reset: When the zone temperature is within its setpoints, the supply air temperature setpoint shall reset to 55°F.
SAFETIES, OVERRIDES AND
INTERLOCKS
SMOKE DETECTOR INTERLOCK
The unit shall be disabled via hard wired interlock at the fan start circuit on activation of a system smoke detector.
FIRE ALARM CONTROL PANEL INTERLOCK
The unit shall be disabled via hard wired interlock at the fan start circuit upon receipt of signal from the fire alarm control panel.
FIRE SPRINKLER WATERFLOW ALARM
INTERLOCK
The unit shall be disabled via hard wired interlock at the fan start circuit upon receipt of waterflow signal from the fire sprinkler alarm panel.
AI DX STA
BO STAGE 2
BI SF STATUS
AIOA TEMP
BI
The controller shall measure the mixed air temperature and stage the
2 heating stages to maintain the zone heating setpoint. To prevent short cycling, there shall be a user definable (adj.) delay between stages, and each stage shall have a user definable
(adj.) minimum runtime.
ECONOMIZER
MINIMUM OUTSIDE AIR VENTILATION
The controller shall measure the zone temperature and modulate the economizer dampers in sequence to maintain a setpoint 2°F less than the zone cooling setpoint. The outside air dampers shall maintain a minimum adjustable position of 37% (or 9000 CFM) open whenever occupied.
The economizer shall be enabled whenever:
• Outside air temperature is less than 65°F (adj.).
• AND the outside air temperature is less than the return air temperature.
• AND the supply fan status is on.
The economizer shall close whenever:
• Mixed air temperature drops from 45°F to 40°F (adj.).
• OR on loss of supply fan status.
The outside air damper shall close and the return air damper shall open when the unit is off.
The outside air dampers shall maintain a minimum position (adj.) during building occupied hours and be closed during unoccupied hours.
The controller shall measure the zone temperature and modulate the cooling coil valve to maintain its cooling setpoint.
The cooling shall be enabled whenever:
• Outside air temperature is greater than 60°F (adj.).
• AND the economizer (if present) is disabled or fully open.
• AND the zone temperature is above cooling setpoint.
• AND the supply fan status is on.
• AND the heating is not active.
AI BLDG STATIC PRESSURE
BUILDING STATIC PRESSURE CONTROL
The controller shall measure building static pressure and modulate the supply fan VFD speed to maintain a building static pressure setpoint of .05in H2O (adj.). The supply fan
VFD speed shall not drop below 20% (adj.).
Alarms shall be provided as follows:
• High Building Static Pressure: If the building air static pressure is 25% (adj.) greater than setpoint.
• Low Building Static Pressure: If the building air static pressure is 25% (adj.) less than setpoint.
POINTS LIST - ARU-1
POINT NAME
HARDWARE POINTS SOFTWARE POINTS SHOWN ON
AI AO BI BO SETPOINT AV BV LOOP SCHED TREND ALARM GRAPHIC
SUPPLY AIR
BUILDING STATIC PRESSURE X X X
DX CO - CC MOD'G COMPR "N" CONTROL OUTPUT X X X
SF STATUS X X X
SF START/STOP X X X
SF VFD FAULT X X X
SF VFD SPEED X X X
SA LAT X X X
SA STATIC PRESSURE X X X
HIGH STATIC SHUTDOWN X X X X
SA SMOKE DETECTOR X X X X
MIXED AIR
MA TEMP X X X
EMERGENCY SHUTDOWN N/A X X X
BUILDING DIFFERENTIAL PRESSURE SETPOINT 0.03 in w.g. X X X
RA STATIC PRESSURE SETPOINT NOTE 1 X X
SA LAT SETPOINT 55˚F X X
ALARMS DESCRIPTION ALARM ALARM DELAY
HIGH RETURN AIR TEMPERATURE IF THE RETURN AIR TEMPERATURE IS GREATER THAN 90˚F (ADJ.) X 10 MIN.
LOW RETURN AIR TEMPERATURE IF THE RETURN AIR TEMPERATURE IS LESS THAN 45˚F (ADJ.) X 10 MIN.
HIGH SUPPLY AIR TEMPERATURE IF THE SUPPLY AIR TEMPERATURE IS 5˚F GREATER THAN ITS SETPOINT (ADJ.) X 10 MIN.
LOW SUPPLY AIR TEMPERATURE IF THE SUPPLY AIR TEMPERATURE IS 5˚F LESS THAN ITS SETPOINT (ADJ.) X 10 MIN.
HIGH RETURN AIR STATIC PRESSURE IF THE RETURN AIR STATIC PRESSURE IS 25% GREATER THAN SETPOINT (ADJ.) X 6 MIN.
LOW RETURN AIR STATIC PRESSURE IF THE RETURN AIR STATIC PRESSURE IS 25% LESS THAN SETPOINT (ADJ.) X 6 MIN.
HIGH SUPPLY AIR STATIC PRESSURE IF THE SUPPLY AIR STATIC PRESSURE IS 25% GREATER THAN SETPOINT (ADJ.) X 6 MIN.
LOW SUPPLY AIR STATIC PRESSURE IF THE SUPPLY AIR STATIC PRESSURE IS 25% LESS THAN SETPOINT (ADJ.) X 6 MIN.
HIGH BUILDING STATIC PRESSURE IF THE BUILDING STATIC PRESSURE IS 25% GREATER THAN SETPOINT (ADJ.) X 10 MIN.
LOW BUILDING STATIC PRESSURE IF THE BUILDING STATIC PRESSURE IS 25% LESS THAN SETPOINT (ADJ.) X 10 MIN.
SUPPLY FAN FAILURE COMMANDED ON, BUT THE STATUS IS OFF X 10 MIN.
SUPPLY FAN IN HAND COMMANDED OFF, BUT THE STATUS IS ON X 10 MIN.
SUPPLY FAN RUNTIME EXCEEDED STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.) X 10 MIN.
PREFILTER CHANGE REQUIRED PREFILTER HAS BEEN IN USE FOR MORE THAN 2200 HOURS (ADJ.) X 10 MIN.
NOTES:
1 SEE STANDARD TRENDING POINTS LIST SCHEDULE ON SHEET M-701 FOR APPLICABLE TREND INTERVALS
2 SEE EQUIPMENT SCHEDULES FOR SETPOINT VALUES
3 SEE PROJECT DESIGN CONDITIONS SCHEDULE FOR SETPOINT VALUES
DX STA - CC MODULATING COMPR "N" STATUS X X X
GAS HEAT - STAGE-1 X X X
GAS HEAT - STAGE-2 X X X
ECONOMIZER DAMPER CONTROL X X X
DRAWING NUMBER
VA PROJECT NUMBER
DATE
PROJECT TITLE
BUILDING NUMBER
PROJECT LOCATION
CHECKED BY DRAWN BY
APPROVED: PROJECT DIRECTOR
VA FORM 08-6231
Office of Construction and Facilities Management
Dwg.
CONSULTANT INFORMATION
STRUCTURAL / CIVIL ENGINEER
F
H2B, INC.
1225 N. LOOP WEST, SUITE 900
HOUSTON, TX 77008
(713) 864-2900
SHEET TITLE
ARCHITECT
FULLY SPRINKLERED
PROJECT PHASE
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
U.S. Department of Veteran Affairs
F
E
D
C
B
A
E
D
C
B
A
COMMISSIONING
GLHN ARCHITECTS & ENGINEERS, INC.
2939 E. BROADWAY BLVD
TUCSON, AZ 85716
(520) 881-4546
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 W. 161ST STREET
OLATHE, KS 66062
(913) 829-8650
CONSTRUCT REPLACEMENT WAREHOUSEHVAC CONTROLS
01/06/2020 JRM CSC
500 AZ-89, PRESCOTT, AZ 86301
165-M-702
649-414
BID DOCUMENTS
SCALE = NTS1
AIR ROTATION UNIT CONROLS DIAGRAM
ELEC
SA
BI DOOR POSITION
BI FAN STATUS
BO HEATER ENABLE
POINTS LIST SCHEDULE (AC-X)
HARDWARE POINTS SOFTWARE POINTS SHOWN ON
POINT NAME AI AO BI BO AV BV LOOP SCHED TREND ALARM GRAPHIC
FAN
FAN STATUS X X X
DOOR POSITION X X
HEATING ELEMENT
HEATER ENABLE X X X
OUTDOOR AIR TEMP X X X
ALARMS DESCRIPTION ALARM ALARM DELAY
COMMON ALARMS MANUFACTURER'S UNITARY STANDARD ALARMS X 10 MIN.
NOTES:
1 SEE STANDARD TRENDING POINTS LIST SCHEDULE ON SHEET M-701 FOR APPLICABLE TREND INTERVALS
N.O.
SEQUENCE OF OPERATIONS
AIR CURTAIN (AC-X)
GENERAL DESCRIPTION
The air curtains with electric heat provide an air barrier between the warehouse and outdoors when warehouse doors are commanded open as shown on the drawings.
OPERATING MODES
STANDARD MODE
The air curtain shall be in standard mode when the outdoor air temperature is above 45degF.
HEATING MODE
The air curtain shall be in heating mode when the outdoor…