Attachment 12 - T Drawings.pdf

PDF 2 MB Posted

Attached to
Y1GZ--Construct Replacement Warehouse Prescott VAMC (Minor Construction) Federal contract opportunity
Solicitation number
36E77620R0043
Issued by
Department of Veterans Affairs Headquarters

About this file

This document provides details for a federal contract opportunity to construct a replacement warehouse at the Northern Arizona VA Health Care System in Prescott, Arizona. The Department of Veterans Affairs will issue a request for proposal on or about July 27, 2020 seeking a single firm-fixed-price contract for design-build-construction services. Offerors will be evaluated using lowest price technically acceptable procedures. The solicitation is set aside exclusively for Service-Disabled Veteran-Owned Small Businesses. The new approximately 10,930 square foot warehouse facility will replace two existing buildings and provide efficient storage and loading areas. The period of performance is approximately 360 calendar days with a magnitude of construction between $5-10 million. Questions must be submitted in writing by the specified date.

View the file

Other files for this federal contract opportunity

Other files attached to Y1GZ--Construct Replacement Warehouse Prescott VAMC (Minor Construction), newest first.
File Type Posted
36E77620R0043 0006.docx DOCX document
Technical Questions Tracking Sheet - 09-14-2020.pdf PDF
1395.26_Revised Roof Slope Sketch.pdf PDF
Telecom Specs1.pdf PDF
36E77620R0043 0005.docx DOCX document
Monitoring and Discovery Protocol.pdf PDF
Technical Questions Tracking Sheet - 09-09-2020.pdf PDF
Construction Wage Rates - Yavapai - 08-21-2020.pdf PDF
36E77620R0043 0004.docx DOCX document
Item 70 response_Drawing-Montage Commercial Classic.pdf PDF
07 43 00 Wall and Roof Panels.pdf PDF
10 26 00 Wall Protection.pdf PDF
Item 81 response_Fire-rated Ceiling Assembly Detail.pdf PDF
Item 69 response_Drawing-Montage Commercial Classic Gate.pdf PDF
1395.26 Construct Replacement Warehouse_ASI 002 Narrative.pdf PDF
01 00 00 - General Requirements.pdf PDF
Reference C - Question 112 - 067 165-M-301 MECHANICAL SECTIONS AND ENLARGED.pdf PDF
Reference E - Question 113 - DIV 13 SPECIAL CONSTRUCTION.pdf PDF
S05 - Technical Questions Tracking Sheet TO BE PUBLISHED 9-4.pdf PDF
36E77620R0043 0003.docx DOCX document
Reference D - Question 113 - 026 165-SA-001 STRUCTURAL GENERAL NOTES.pdf PDF
Technical Questions Tracking Sheet 36E77620R0043.pdf PDF
36E77620R0043 0002.docx DOCX document
36E77620R0043 - SITE VISIT SIGN IN SHEET - 08-11-2020.pdf PDF
36E77620R0043 0001.docx DOCX document
Attachment 10 - P Drawings.pdf PDF
Attachment 15 - Construction Wage Rates - Yavapai - 06-05-2020.pdf PDF
Copy of Attachment 14 - Division Price Breakdown.xlsx XLSX spreadsheet
Attachment 7 - F Drawings.pdf PDF
Attachment 16 - Contractor Safety _ Env Record Form.docx DOCX document
Attachment 11 - S Drawings.pdf PDF
Attachment 13 - Warehouse Building Soils Report.pdf PDF
Attachment 1 - Volume 01 Specifications REV.pdf PDF
Attachment 9 - M Drawings.pdf PDF
Attachment 4 - A Drawings.pdf PDF
Attachment 3 - Volume 03 Specifications REV.pdf PDF
Attachment 8 - G Drawings.pdf PDF
Attachment 5 - C Drawings Part II.pdf PDF
Attachment 6 - E Drawings.pdf PDF
Attachment 2 - Volume 02 Specifications.pdf PDF
36E77620R0043.docx DOCX document
Attachment 5 - C Drawings Part I.pdf PDF
Attachment 17 - Prescott Site Map.pdf PDF
Show all 43

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BAT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISH FLOOR

BIL BASIC INSULATION LEVEL

BLDG BUILDING

BPIP BOILER PLANT

INSTRUMENTATION PANEL

BRKR BREAKER

BYP BY PASS

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HZ HERTZ

A/C AIR CONDITIONING

A/E ARCHITECT/ENGINEER

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR ARMORED

CABLE

ACC ACCESSIBLE

ADDL ADDITIONAL

ADJ ADJACENT, ADJOINING

ADO AUTOMATIC DOOR OPENER

AF AMPERE FRAME OR AMP FUSE

AFC ABOVE FINISHED COUNTER, AUTOMATIC

FREQUENCY CONTROL, OR

AVAILABLE FAULT CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AH AMPERE HOUR

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

AMB OR A AMBIENT

AMP AMPERE

ARCH ARCHITECT

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

1P SINGLE POLE

1PH SINGLE-PHASE

3P THREE POLE

3PH THREE-PHASE

3W THREE WIRE

4W FOUR WIRE

P POLE

PA PUBLIC ADDRESS

PB PANELBOARD, PULL BOX, OR

PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT UNIT

PCB POLYCHLORINATED BIPHENYL

PEC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PNL PANEL

POD POWER OPERATED DAMPER

PT POTENTIAL TRANSFORMER

PTRV POWER TYPE ROOF VENTILATION

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

SCC SHORT CIRCUIT CAPACITY

SES SERVICE ENTRANCE SECTION

SD SMOKE DETECTOR

SF SQUARE FOOT (FEET)

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SPD SURGE PROTECTIVE DEVICE

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SURF SURFACE

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

G OR GND GROUND OR GENERATOR

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GTB GROUND TERMINAL BOX

IESNA ILLUMINATION ENGINEERING SOCIETY

OF NORTH AMERICA

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

W WATT

WH WATER HEATER

WP WEATHERPROOF

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LM LUMEN

LP LIGHT POLE

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPS

LTCP LOCAL TEMPERATURE CONTROL PANEL

LT LIGHT

LTG LIGHTING

LTG PNL LIGHTING PANEL

LTNG LIGHTNING

LV LOW VOLTAGE

XFER TRANSFER

XFMR TRANSFORMER

XP EXPLOSION PROOF

JB JUNCTION BOX

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT AMPERE

KVAH KILOVOLT AMPERE PER HOUR

KVAR KILOVOLT AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

KWHM KILOWATT HOUR METER

MATV MASS ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MLO MAIN LUGS ONLY

MT MOUNT

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE

MVA MEGAVOLT-AMPERE

MW MEGAWATT

OC ON CENTER

OD OUTSIDE DIAMETER

OL OVERLOAD

N NEUTRAL

NA NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NS NO SCALE

NTS NOT TO SCALE

RCP REFLECTED CEILING PLAN

RCPT RECEPTACLE

REC RECESSED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

REQD REQUIRED

TC TIME CLOCK

TEL TELEPHONE

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

V VOLT

VA VOLT AMPERE

VAR VOLT AMPERE REACTIVE

VFD VARIABLE FREQUENCY DRIVE

VOLT VOLTAGE

UFD UNDERFLOOR DUCT

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

ABBREVIATIONS

A

B

C

C CONDUIT

CAP CAPACITY

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED/

CONTRACTOR INSTALLED

CF/OI CONTRACTOR FURNISHED/OWNER

INSTALLED

CFE CONTRACTOR FURNISHED

EQUIPMENT

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

CKT BRKR CIRCUIT BREAKER

CLF CURRENT LIMITING FUSE

CLG CEILING

CMU CONCRETE MASONRY UNIT

COAX COAX CABLE

COMM COMMUNICATION

CONC CONCRETE

CONT CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CU COPPER

CU FT CUBIC FEET

DB DECIBEL OR DIRECT BURIAL

DC DIRECT CURRENT

DCP DIMMER CONTROL PANEL

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DISC DISCONNECT

DISTR DISTRIBUTION

DISTR PNL DISTRIBUTION PANEL

DN DOWN

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DRSW DOOR SWITCH

DS DISCONNECT SWITCH

DWG DRAWING

EC EMPTY CONDUIT

EG EQUIPMENT GROUND

EL ELEVATION

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMCP EMER. MONITORING CONTROL PANEL

EMER EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

ESMT EASEMENT

ETD EXISTING TO BE DEMOLISHED

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXIST EXISTING

D

E

F

G

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FABL FIRE ALARM BELL

FABX FIRE ALARM BOX

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FI FILM ILLUMINATOR

FIXT FIXTURE

FLA FULL LOAD AMPS

FLEX FLEXIBLE METALLIC CONDUIT

FLUOR FLUORESCENT

FP FIRE PROTECTION

FT FEET OR FOOT

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

H

I

J

K

L

M

N

O

P

STANDARD MOUNTING HEIGHTSANNOTATION

R

S

T

U

V

W

X

ELECTRICAL:

AUDIBLE APPLIANCES (CENTERLINE) 84"

ALARMS 48"

ANNUNCIATOR PANELS 48"

CLOCK OUTLETS (CENTERLINE) 84"

CONTROLS (TOP) 48"

EXIT SIGNS (WALL-MOUNTED, BOTTOM) 80"

FIRE ALARM ANNUNCIATOR PANEL (DISPLAY) 60"

FIRE ALARM BELL (EXTERIOR) 120"

FIRE ALARM CONTROL PANEL/UNIT (DISPLAY) 60"

INTERCOM (AFEA ONLY) 36"

INTERCOMS (TOP) 48"

PANELS & PANELBOARDS (TOP) 72"

PULL STATIONS (HANDLE) 48"

PHOTOCELLS 144"

RECEPTACLES (BOTTOM) 18"

RECEPTACLES (EXTERIOR) 24"

RECEPTACLES (GARAGES) 26"

RECEPTACLES IN EQUIPMENT ROOMS (TOP) 48"

REMOTE INDICATING LIGHT (EQUIPMENT ROOMS) 48"

REMOTE INDICATING LIGHT (FINISHED AREAS) CEILING

SAFETY SWITCHES & STARTERS 48"

SWITCHES (TOP) 48"

TELEPHONE/DATA/TV OUTLETS (BOTTOM) 18"

VISIBLE APPLIANCES (CENTERLINE) 84"

(AFF, AFG UNLESS NOTED OTHERWISE)

IDS INTRUSION DETECTION SYSTEM

GB GIGABIT

MN MASS NOTIFICATION

OI&T OFFICE OF INFORMATION AND

TECHNOLOGY

OSP OUTSIDE PLANT

PACS PHYSICAL ACCESS CONTROL SYSTEM

POE POWER OVER ETHERNET

TR TELECOM ROOM

VAPD VA POLICE DEPARTMENT

VASS VIDEO ASSESSMENT SURVEILLANCE

SYSTEM

CU

M100

M100

MECHANICAL OR FIRE SPRINKLER PLAN NOTE CALL OUT

PLUMBING PLAN NOTE CALL OUT

ELECTRICAL, TECHNOLOGY OR FIRE ALARM PLAN NOTE

CALL OUT

PLUMBING EQUIPMENT DESIGNATION

EQUIPMENT DESIGNATION TAG

OWNER FURNISHED, CONTRACTOR INSTALLED

EQUIPMENT DESIGNATION

NEW WORK TO EXISTING WORK CONNECTION POINT

DETAIL REFERENCE

SECTION CUT DESIGNATION

Z

BC

CB

B

DS

E

EP

LS

KS

NA

NM

SS

PS

PS

IC

CATV

FO

T

T/D

D

S

IC

UC

CCTV

S

WAP

#D/#TV

M

S

V

CR

DB

DB

DM

EL

EO

GB

KP

MD

PB

RE

EC

KT

GO

C

COMMUNICATIONS OUTLET, TYPE AS NOTED

COMMUNICATIONS OUTLET, FLOOR BOX, TYPE AS NOTED

WIRELESS ACCESS POINT, CEILING MOUNTED

COMMUNICATIONS OUTLET, CEILING MTD, TYPE AS NOTED

SPEAKER, WALL MOUNTED

SPEAKER, CEILING MOUNTED

SERVER RACK, TWO-POST, FLOOR MOUNTED

3/4"x4'x8', FIRE-RATED PLYWOOD BACKBOARD

GROUND BAR, TYPE AS NOTED

SERVER RACK, WALL MOUNTED

CABLE TRAY, TYPE AS NOTED

CABLE TELEVISION LINE

FIBEROPTIC LINE

TELEPHONE LINE

TELEPHONE/DATA LINE

DATA LINE

SPEAKER LINE

INTERCOM LINE

INTERCOM, "M" DENOTES MASTER STATION

VOLUME CONTROL, WALL MOUNTED

CODE BLUE PUSHBUTTON STATION

DUTY STATION

STAFF EMERGENCY ASSIST STATION

PATIENT EMERGENCY PULL CORD STATION

STAFF LOCATOR SENSOR

NURSE CALL KEY SWITCH

NURSE CALL VISUAL ANNUNCIATOR PANEL

NURSE CALL MASTER STATION

STAFF STATION (NORMAL, EMERGENCY & CODE BLUE)

DOME LIGHT, WALL MOUNTED

DOME LIGHT, CEILING MOUNTED

ZONE DOME LIGHT

MULTI-SERVICE POWER POLE WITH POWER/DATA,

TYPE AS NOTED AND/OR SCHEDULED

UNDERGROUND COMMUNICATIONS LINE,

CABLING TYPE AS NOTED

MULTI-SERVICE FLOOR BOX/POKE-THRU WITH POWER/DATA,

TYPE AS NOTED AND/OR SCHEDULED

SERVER RACK, FOUR-POST, FLOOR MOUNTED

SERVER CABINET, FLOOR MOUNTED

CLOSED CIRCUIT TELEVISION LINE, MIN. 1" RACEWAY

CARD READER, PROXIMITY TYPE

DOOR BELL PUSHBUTTON

DOOR BELL PUSHBUTTON

DOOR POSITION MONITOR

ELECTRIFIED LOCKING DEVICE, REQUEST TO EXIT SENSOR,

LATCH BOLT MONITOR, AND DOOR POSITION SWITCH

ELECTRIFIED LOCKING DEVICE

GLASS BREAK DETECTOR

INTRUSION DETECTION KEYPAD

INTRUSION DETECTION MOTION DETECTOR

DURESS PUSHBUTTON

REQUEST TO EXIT BUTTON

SINGLE VIEW SECURITY CAMERA

EMERGENCY CALL STATION

RFID KEY TAG READER

GATE OPENER

DUAL VIEW SECURITY CAMERA

180-DEGREE PANORAMIC VIEW SECURITY CAMERA

270-DEGREE PANORAMIC/MULTI-IMAGE VIEW

360-DEGREE PANORAMIC/MULTI-IMAGE VIEW

SECURITY CAMERA

SECURITY CAMERA

PATIENT STATION BED CONNECTOR

PATIENT STATION WITH CODE BLUE

SECURITY SYMBOLS

#D = DATA, # = QUANTITY OF CABLES

#TV = CABLE TELEVISION, # = QUANTITY OF CABLES

#D = DATA, # = QUANTITY OF CABLES

#TV = CABLE TELEVISION, # = QUANTITY OF CABLES

#V = VOICE, # = QUANTITY OF CABLES

#D = DATA, # = QUANTITY OF CABLES

#E = ELEVATOR, # = QUANTITY OF CABLES

#FMS = FACILITY MONITORING SYSTEM,

# = QUANTITY OF CABLES

NURSE CALL SYMBOLS

COMMUNICATION SYMBOLS

#TV = CABLE TELEVISION, # = QUANTITY OF CABLES

#V = VOICE, # = QUANTITY OF CABLES

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

F

SHEET TITLE

ARCHITECT

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

STRUCTURAL / CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH. / ELEC. / PLUMB. / TECH. ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATHE, KS 66062

(913) 829-8650

LANDSCAPE ARCHITECT

ARC STUDIOS INC.

3117 E. FLOWER STREET

TUCSON, AZ 85716

(520) 882-9655

COMMISSIONING

GLHN ARCHITECTS & ENGINEERS, INC.

2939 E. BROADWAY BLVD

TUCSON, AZ 85716

(520) 881-4546

R1 - CONSTRUCT REPLACEMENT

WAREHOUSE

TECHNOLOGY LEGEND

01/06/2020 BEN ABM

500 AZ-89, PRESCOTT, AZ 86301

165-T-000

649-414

BID DOCUMENTS

Revision # Date

IC

CR

GO

S

1" = 30'

903015 600

FO

F O

FO

FO

FO

FO

FO

FO

FO

SS

SS

SS

SS

SS

SS

SS

FO

FO FO

FO

FO

FO

S

DS

DS

DS

D

S

DS

DS

DS

D

SD

SDW W W W

W

W

SD

W

W

W

W

W

G G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G G

G

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

TRAILER AREATRAILER MANEUVER AREA

EXISTING PARKING LOT

DR. KENDALL WAY

UE

UE UE

UE

UE

U E

U E

U E

UE

UE

UE

UE

UEUE

UE UE UE

UE UEUE

UE UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

U E

U E

U E

UE

UE

U E

U E

U E

U E

U E

U E

UE

UE

UE

UE

G

G

UE

UEUE

UE

UEUE

UEUE

UE UE UE UE UE UE

U E

UE

UE

UE

UE

UE

UE

UE

U E

U E

U E

U E

U E

U E

IC-03

CR-03

WP

UE

UE

U E

U E

U E

U E

UE UE

UE

U C

U C

U C

U C

U C

UE

U E

U E U

E

UE

UE UE UE UE UE UE

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

F

SHEET TITLE

ARCHITECT

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

STRUCTURAL / CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH. / ELEC. / PLUMB. / TECH. ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATHE, KS 66062

(913) 829-8650

LANDSCAPE ARCHITECT

ARC STUDIOS INC.

3117 E. FLOWER STREET

TUCSON, AZ 85716

(520) 882-9655

COMMISSIONING

GLHN ARCHITECTS & ENGINEERS, INC.

2939 E. BROADWAY BLVD

TUCSON, AZ 85716

(520) 881-4546

R1 - CONSTRUCT REPLACEMENT

WAREHOUSE

TECHNOLOGY SITE PLAN

01/06/2020 BEN ABM

500 AZ-89, PRESCOTT, AZ 86301

165-TS-101

649-414

BID DOCUMENTS

1" = 30'-0"

TECHNOLOGY SITE PLAN

N

1 PROVIDE NEW MINIMUM 48"x48"x48" HANDHOLE WITH A MINIMUM TIER

22 COVER FOR UNDERGROUND COMMUNICATIONS LINE. REFER TO

DETAIL 2, SHEET 165-T-501.

2 PROVIDE NEW CONCRETE ENCASED COMMUNICATIONS DUCT BANK.

REFER TO DETAIL 1, SHEET 165-T-501.

3. ROUTE UP SIDE OF BUILDING AND OVERHEAD TO BUILDING 70 MAIN IT

ROOM. PAINT CONDUITS TO MATCH EXISTING BUILDING COLOR.

4. BUILDING 70 MAIN TELECOM ROOM.

5. INTERLOCK GATE CONTROLS WITH GATE ACCESS CARD READER AND

REMOTE GATE OPENER LOCATED INSIDE BUILDING.

6. VEHICLE DETECTION LOOP. COORDINATE CONNECTION INTO GATE

OPERATING SYSTEM CONTROLS.

GENERAL NOTES:

1 COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER'S

REPRESENTATIVE.

2 COORDINATE TECHNOLOGY WORK WITH ALL OTHER TRADES. VERIFY

ALL EXISTING CONDITIONS BEFORE THE START OF WORK.

3 SEE SHEET 165-G-001 FOR ADDITIONAL INFORMATION REGARDING

SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK ON

EXISTING EQUIPMENT AND IN EXISTING BUILDINGS TO MINIMIZE

DISTRUPTION OF SERVICES.

4 DRAWINGS ARE DIAGRAMMATIC ONLY AND REPRESENT THE

GENERAL SCOPE OF WORK. REVIEW THE GENERAL NOTES,

SPECIFICATIONS AND PLANS FOR ADDITIONAL REQUIREMENTS THAT

MAY NOT BE SPECIFICALLY CALLED OUT IN THIS PORTION OF THE

CONSTRUCTION DOCUMENTS. NOTIFY THE CONTRACTING OFFICER'S

REPRESENTATIVE (COR) OF ANY CONFLICTS OR DISCREPENCIES

PRIOR TO SUBMISSION OF BID.

5 DRAWINGS AND SPECIFICATIONS GOVERN WHERE THEY EXCEED

CODE REQUIREMENTS.

6 UTILITIES PRESENTED ON THESE DRAWINGS ARE SHOWN BASED ON

THE BEST AVAILABLE INFORMATION. FIELD VERIFY THE EXACT

LOCATIONS IN THE FIELD PRIOR TO COMMENCING CONSTRUCTION.

CONTRACTOR SHALL NOTIFY LOCAL UTILITY LOCATING SERVICES AT

LEAST 48 HOURS BEFORE PROCEEDING WITH ANY EXCAVATION.

7 DAMAGE TO ANY EXISTING UTILITIES SHALL BE REPAIRED IN

ACCORDANCE WITH THE VA'S STANDARD CONSTRUCTION

SPECIFICATIONS AT NO ADDITIONAL COST.

8 TAKE NECESSARY PRECAUTIONS TO PROTECT ROOT SYSTEMS OF

SHRUBS, PLANTS, AND TREES ALONG THE AREA OF EXCAVATION.

9 DISPOSE OF ALL DEMOLISHED MATERIAL OFF-SITE.

TECHNOLOGY PLAN NOTES:#

S

IC

S

S

IC V

S

S S

S S

S

S

S

A

B

C

D

1 32

IC-02

IC-01

M

4 5

F

E

WAREHOUSE

STORAGE (AMMUNITION)

PLOTTING

WALK-IN REF.

STORAGE (SHRED)

STORAGE (FLAM.)

SECURE STOR.

SV OFFICE

UNISEX TOILET

UNISEX TOILET

HAC

WAREHOUSE

WRAPPING

PLOTTING

RECYCLING AREA

SECURE STOR.

BREAK ROOM

IT ROOM

ELECTRICAL

CORRIDOR

MECHANICAL

CORRIDOR

HAC

WORKSPACE

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

F

SHEET TITLE

ARCHITECT

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

STRUCTURAL / CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH. / ELEC. / PLUMB. / TECH. ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATHE, KS 66062

(913) 829-8650

LANDSCAPE ARCHITECT

ARC STUDIOS INC.

3117 E. FLOWER STREET

TUCSON, AZ 85716

(520) 882-9655

COMMISSIONING

GLHN ARCHITECTS & ENGINEERS, INC.

2939 E. BROADWAY BLVD

TUCSON, AZ 85716

(520) 881-4546

R1 - CONSTRUCT REPLACEMENT

WAREHOUSE

INTERCOM AND PUBLIC ADDRESS

FIRST FLOOR PLAN

01/06/2020 BEN ABM

500 AZ-89, PRESCOTT, AZ 86301

165-TI-101

649-414

BID DOCUMENTS

1/8" = 1'-0"

INTERCOM AND PUBLIC ADDRESS

FIRST FLOOR PLAN

N

GENERAL NOTES:

1 COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER'S

REPRESENTATIVE.

2 COORDINATE TECHNOLOGY WORK WITH ALL OTHER TRADES. VERIFY

ALL EXISTING CONDITIONS BEFORE THE START OF WORK.

3 SEE SHEET 165-G-001 FOR ADDITIONAL INFORMATION REGARDING

SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK ON

EXISTING EQUIPMENT AND IN EXISTING BUILDINGS TO MINIMIZE

DISTRUPTION OF SERVICES.

4. REFER TO TECHNOLOGY SITE PLAN, DRAWING 165-TS-101 FOR

ADDITIONAL INTERCOM DEVICES.

1. PUBLIC ADDRESS/MASS NOTIFICATION SYSTEM PROPOSED ZONE 1.

PROVIDE BULL HORN SPEAKERS AT CEILING AT APPROXIMATELY 30'-0"

AFF FOR AUDIBILITY OVER WAREHOUSE NOISE. QUANTITY OF

SPEAKERS SHOWN IS NOT REPRESENTATIVE OF THE QUANTITY

REQUIRED FOR THIS ZONE AND IS SHOWN FOR ILLUSTRATIVE

PURPOSES ONLY.

2. PUBLIC ADDRESS/MASS NOTIFICATION SYSTEM PROPOSED ZONE 2.

PROVIDE DROP CEILING MOUNTED SPEAKERS. REFER TO

ARCHITECTURAL DRAWINGS FOR CEILING HEIGHTS.

TECHNOLOGY PLAN NOTES:#

FACP

A

B

C

D

1 3

3D

3D

3D

3D

2FMS

3D +48"

3D +48"

3D +48"

3D +48"

2FMS

+48"

WAP

WAP

3D

3D

WAP

WAP

TO COMMUNICATIONS

HANDHOLE. RE 165-TS-101

ROUTE UP IN

WALL TO IT

ROOM 106.

+12'-0"

+12'-0"

+12'-0"+12'-0"

4 5

F

E

2FMS

3D

165-T-401

WAP

1TV/1D

3D 3D

165-T-401

3D

3D 3D

+80"

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

F

SHEET TITLE

ARCHITECT

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

STRUCTURAL / CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH. / ELEC. / PLUMB. / TECH. ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATHE, KS 66062

(913) 829-8650

LANDSCAPE ARCHITECT

ARC STUDIOS INC.

3117 E. FLOWER STREET

TUCSON, AZ 85716

(520) 882-9655

COMMISSIONING

GLHN ARCHITECTS & ENGINEERS, INC.

2939 E. BROADWAY BLVD

TUCSON, AZ 85716

(520) 881-4546

R1 - CONSTRUCT REPLACEMENT

WAREHOUSE

COMMUNICATIONS FIRST FLOOR

PLAN

01/06/2020 BEN ABM

500 AZ-89, PRESCOTT, AZ 86301

165-TN-101

649-414

BID DOCUMENTS

1/8" = 1'-0"

COMMUNICATIONS

FIRST FLOOR PLAN

N

GENERAL NOTES:

1 COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER'S

REPRESENTATIVE.

2 COORDINATE TECHNOLOGY WORK WITH ALL OTHER TRADES. VERIFY

ALL EXISTING CONDITIONS BEFORE THE START OF WORK.

3 SEE SHEET 165-G-001 FOR ADDITIONAL INFORMATION REGARDING

SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK ON

EXISTING EQUIPMENT AND IN EXISTING BUILDINGS TO MINIMIZE

DISTRUPTION OF SERVICES.

4 COORDINATE LOCATIONS OF ALL WIRELESS ACCESS POINTS (WAP)

WITH NAVAHCS VA OI&T PRIOR TO ROUGH-IN.

TECHNOLOGY PLAN NOTES:

1 COORDINATE EXACT LOCATION OF FACILITY MONITORING SYSTEM

DATA CONNECTION WITH GOVERNMENT PRIOR TO ROUGH-IN.

EL

MD

KP

DM MD MDDM DM MD

MD MD MD

MD

DM

MD

MD

GO

CR

EL

GB GB

RE

RE

A

B

C

D

1 32

CR-02

ID-01 ID-01 ID-01 ID-01

ID-01 ID-01 ID-01

ID-01

ID-02

C-06

4 5

F

E

ID-02

C-05

WP

C-05 C-05

C-02

C-05

C-01

C-03 C-03 C-03 C-03

C-04

WAREHOUSE

WRAPPING

STORAGE (AMMUNITION)

RECYCLING AREA

WALK-IN REF.

STORAGE (SHRED)

STORAGE (FLAM.)

SECURE STOR.

IT ROOM

ELECTRICAL

CORRIDOR

UNISEX TOILET

UNISEX TOILET

MECHANICAL

CORRIDOR

WORKSPACE

WAREHOUSE

WRAPPING

STORAGE (AMMUNITION)

PLOTTING

RECYCLING AREA

WALK-IN REF.

STORAGE (SHRED)

STORAGE (FLAM.)

SV OFFICE

BREAK ROOM

UNISEX TOILET

UNISEX TOILET

MECHANICAL

CORRIDOR

HAC

WORKSPACE

CR-01

C-01

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

F

SHEET TITLE

ARCHITECT

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

STRUCTURAL / CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH. / ELEC. / PLUMB. / TECH. ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATHE, KS 66062

(913) 829-8650

LANDSCAPE ARCHITECT

ARC STUDIOS INC.

3117 E. FLOWER STREET

TUCSON, AZ 85716

(520) 882-9655

COMMISSIONING

GLHN ARCHITECTS & ENGINEERS, INC.

2939 E. BROADWAY BLVD

TUCSON, AZ 85716

(520) 881-4546

R1 - CONSTRUCT REPLACEMENT

WAREHOUSE

SECURITY FIRST FLOOR PLAN

01/06/2020 BEN ABM

500 AZ-89, PRESCOTT, AZ 86301

165-TY-101

649-414

BID DOCUMENTS

1/8" = 1'-0"

SECURITY FIRST FLOOR PLAN

N

GENERAL NOTES:

1 COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER'S

REPRESENTATIVE.

2 COORDINATE SECURITY WORK WITH ALL OTHER TRADES. VERIFY

ALL EXISTING CONDITIONS BEFORE THE START OF WORK.

3 SEE SHEET 165-G-001 FOR ADDITIONAL INFORMATION REGARDING

SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK ON

EXISTING EQUIPMENT AND IN EXISTING BUILDINGS TO MINIMIZE

DISTRUPTION OF SERVICES.

4 REFER TO TECHNOLOGY SITE PLAN, SHEET NUMBER 165-TS-101 FOR

ADDITIONAL SECURITY DEVICE LOCATIONS.

TECHNOLOGY PLAN NOTES:

1 INSTALL REMOTE GATE OPENER FURNISHED WITH GATE OPERATOR.

PROVIDE MINIMUM 1" CONDUIT OUT TO GATE OPERATOR AND WIRING

PER MANUFACTURER'S RECOMMENDATIONS.

LEVEL 1

0' - 0"

E

LEVEL 1

0' - 0"

EE

PHYSICAL ACCESS

CONTROL SYSTEM

(PACS)

PHYSICAL ACCESS

CONTROL SYSTEM

(PACS)

INTRUSION

DETECTION SYSTEM

(IDS)

INTRUSION

DETECTION SYSTEM

(IDS)

PACS BATTERY

CABINET

PACS BATTERY

CABINET

IDS BATTERY

CABINET

IDS BATTERY

CABINET

165-NL1-2

14(TYP.)

LEVEL 1

0' - 0"

E

LEVEL 1

0' - 0"

EE

HCM

48-PORT PP

HCM

48-PORT PP

HCM

PA-MN SYSTEM

RACK-MTD UPS

BATTERY

RACK-MTD UPS

RACK-MTD UPS

BATTERY

RACK-MTD UPS

VCM VCM VCM VCM

48-PORT PP

HCM

48-PORT PP

HCM

48-PORT PP

HCM

48-PORT PP

HCM

48-PORT PP

HCM

48-PORT PP

HCM

HCM

HCM

FO PP

HCM

FO PP

HCM

FO PP

HCM

FO PP

HCM

HCM

POE SWITCH

HCM

POE SWITCH

HCM

POE SWITCH

HCM

POE SWITCH

HCM

POE SWITCH

HCM

POE SWITCH

HCM

RACK-MTD UPS

RACK-MTD UPS

BATTERY

RACK-MTD UPS

BATTERY

165-NL1-2

LIGHT FIXTURE

13(TYP.)

4 4 4

(TYP.)

"x

/4

12 (TYP.)

10 (TYP.)

7 (TYP.)

8 (TYP.)

9 (TYP.)

(TYP.) (TYP.)

14(TYP.)

E

165-T-401

165-T-401

VASS/PA

DATA

FIBER/DATA

IDS

IDS

PACS

PACS

GROUND

BAR

MATV165-NL1-2

E

"x

/4

"x

/4

24"x1 1/4"

24"x1 1/4"

IDS

IDS

PACS

PACS

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

F

SHEET TITLE

ARCHITECT

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

STRUCTURAL / CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH. / ELEC. / PLUMB. / TECH. ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATHE, KS 66062

(913) 829-8650

LANDSCAPE ARCHITECT

ARC STUDIOS INC.

3117 E. FLOWER STREET

TUCSON, AZ 85716

(520) 882-9655

COMMISSIONING

GLHN ARCHITECTS & ENGINEERS, INC.

2939 E. BROADWAY BLVD

TUCSON, AZ 85716

(520) 881-4546

R1 - CONSTRUCT REPLACEMENT

WAREHOUSE

TECHNOLOGY ENLARGED FLOOR

PLANS

01/06/2020 BEN ABM

500 AZ-89, PRESCOTT, AZ 86301

165-T-401

649-414

BID DOCUMENTS

GENERAL NOTES:

1 COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER'S

REPRESENTATIVE.

2 COORDINATE TECHNOLOGY WORK WITH ALL OTHER TRADES. VERIFY

ALL EXISTING CONDITIONS BEFORE THE START OF WORK.

3 SEE SHEET 165-G-001 FOR ADDITIONAL INFORMATION REGARDING

SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK ON

EXISTING EQUIPMENT AND IN EXISTING BUILDINGS TO MINIMIZE

DISRUPTION OF SERVICES.

TECHNOLOGY PLAN NOTES:

1. MOUNT GROUND BAR AT 6'-6" AFF. REFER TO DETAIL 9, SHEET 165-

T-501 AND DETAIL 2, SHEET 165-T-601 FOR ADDITIONAL INFORMATION.

2. PROVIDE (4) 4" E-Z PATH RE-ENTERABLE, FIRE-RATED SLEEVES, OR

APPROVED EQUIVALENT, FROM ABOVE CORRIDOR CEILING INTO IT

ROOM.

3. PROVIDE LADDER TRAY AS SHOWN.

4. PROVIDE 19” WIDE, 45RU, HEAVY-DUTY FLOOR-MOUNTED RACK,

BLACK IN COLOR.

5. PROVIDE RACK MOUNTED 48-PORT PATCH PANELS FOR TERMINATION

OF DATA CAT 6A CABLES. QUANTITY SHOWN IS ESTIMATED, PROVIDE

PATCH PANELS REQUIRED FOR CABLING PLUS 50% GROWTH.

6. PROVIDE A 2RU HORIZONTAL CABLE MANAGER (HCM) ABOVE AND

BELOW EACH PATCH PANEL.

7. PROVIDE MINIMUM 2RU HORIZONTAL CABLE MANAGERS ABOVE AND

BELOW EACH GOVERNMENT FURNISHED, GOVERNMENT INSTALLED

POE SWITCH. COORDINATE EXACT REQUIREMENTS WITH COR.

8. PROVIDE FULL HEIGHT, SINGLE-SIDED VERTICAL CABLE MANAGER ON

EACH SIDE OF EACH RACK.

9. PROVIDE UNINTERRUPTIBLE POWER SUPPLIES (UPS) PER DIVISION 27

SPECIFICATIONS. REFER TO SYSTEM RISER DIAGRAMS ON DRAWING

165-T-601 FOR ADDITIONAL INFORMATION.

10. PROVIDE 24-PORT FIBER ENCLOSURE WITH FIBER ADAPTERS FOR

INCOMING FIBER-OPTIC CABLING. REFER TO DETAIL 1, DRAWING 165-

T-601 FOR ADDITIONAL INFORMATION. COORDINATE EXACT

REQUIREMENTS WITH VA COR. PROVIDE MINIMUM 1RU HORIZONTAL

CABLE MANAGER ABOVE AND BELOW EACH ENCLOSURE.

11. PROVIDE WALL-MOUNTED, ANGLED SIDE AND END SUPPORTS AS

REQUIRED FOR PROPER SUPPORT OF LADDER TRAY.

12. PROVIDE 6RU TALL SUPPORT BRACKETS TO SECURELY CONNECT

CABLE TRAY TO TOP OF RACKS.

13. PROVIDE CABLE RUNWAY RADIUS DROP AS REQUIRED FOR ROUTING

CABLING TO VERTICAL CABLE MANAGERS AND DATA RACKS.

14. PROVIDE 4’X8’X3/4" FIRE-RATED PLYWOOD ON ALL WALLS FROM 6”

AFF TO 8'-6" AFF.

15. ROUTE TELECOM SERVICE ENTRANCE CONDUITS INTO OUT TO

TELECOMMUNICATIONS HANDHOLE TO BUILDING 70. REFER TO

DETAILS 1/165-TS-101, 1/165-TN-101, AND 1/165-T-601 FOR ADDITIONAL

INFORMATION.

16. DEDICATED WALL SPACE FOR PHYSICAL ACCESS CONTROL AND

INTRUSION DETECTION SYSTEM CONTROL AND BATTERY

CABINET(S). PROVIDE CABINET(S) AS REQUIRED FOR A FULLY

OPERATIONAL SYSTEM IN ACCORDANCE WITH THE SPECIFICATIONS.

17. DEDICATED WALL SPACE FOR MASS ANTENNA TELEVISION SYSTEM

HEAD-END CABINET. PROVIDE CABINET(S) AS REQUIRED FOR A

FULLY OPERATIONAL SYSTEM IN ACCORDANCE WITH THE

SPECIFICATIONS AND RISER DIAGRAMS.

1/2" = 1'-0"

IT ROOM 106

DATA ROOM SECTION - PLAN WEST

1/2" = 1'-0"

IT ROOM 106

DATA ROOM SECTION - PLAN EAST

1/2" = 1'-0"

IT 106 (DATA RACKS)

PARTIAL FLOOR PLAN

1/2" = 1'-0"

IT 106 (LADDER TRAYS)

PARTIAL FLOOR PLAN

WAP

3D

1TV/1D

2FMS

1 2

3 4

PROVIDE 1-1/4" RACEWAY,

UNLESS NOTED OTHERWISE.

PROVIDE INSULATION

BUSHING AT ENTRANCE TO

BACKBOX.

PROVIDE SINGLE-GANG,

2-PORT FACEPLATE WITH

IDENTIFICATION WINDOWS.

NOTE:

COORDINATE EXACT LOCATION OF OUTLET WITH ARCHITECTURAL PLANS. LOCATION OF

OUTLET SHALL NOT CONFLICT WITH MOUNTING BRACKETS OR OTHER TRADES.

PERMANENTLY LABEL ALL WALL JACKS IN THE FOLLOWING MANNER: BUILDING-FLOOR-JACK

NUMBER-ROOM NUMBER OF CLOSET. EXAMPLE: 1-1-33-148B (BUILDING 1, FLOOR 1, JACK 33, CLOSET ROOM NUMBER 148B). JACK NUMBER INDICATES THE PUNCH DOWN POSITION OF THE

CLOSET CONNECTION. ALL JACKS ON THE SAME PLATE SHALL HAVE THE SAME NUMBER

WHERE POSSIBLE. LABEL ALL CABLES AT EACH END WITH THEIR RESPECTIVE NUMBER.

PROVIDE INSULATING

BUSHING ON ALL

PATHWAYS TO

COMMUNICATIONS

BACKBOXES.

PROVIDE 4-11/16" X 4-11/16" X

2-1/8" DOUBLE-GANG

BACKBOX WITH

SINGLE-GANG PLASTER RING.

PROVIDE HORIZONTAL CABLING

PER SPECIFICATIONS WITH RJ45

CONNECTOR FOR DATA

CONNECTIONS. TERMINATE

CABLE IN TR AT RACK-MOUNTED

48-PORT MODULAR PATCH

PANELS. (TYPICAL)

PROVIDE TIER 22 LOCKABLE COVER

WITH "TELECOMMUNICATIONS"

IMPRINTED IN LID.

HANDHOLE (SEE SPECIFICATIONS)

1" 1"2"

1 1/2" TYP

" 5 /8

[1 m m

2"[51mm]

MIN

1/4" DIA.

MOUNTING

HOLES TYP. OF

(4)

3" DEEP FIBERGLASS

CHANNEL SAME

LENGTH AS CU BUSS

3/8" DIA. HOLE

TYP. OF (6)

1/2"DIA. x2"L. BOLT

TYP. OF (2)

1/2" NUT

1/2" LOCK WASHER

1/2" STANDARD WASHER

1/2" FENDER WASHERS (EACH SIDE)

1/4"

THICK CU

BUSS

2'-0" MIN

1/4" DIA. HOLE

TYP OF (8)

SECTION

STEEL

EXPANSION

ANCHOR

1"

GENERAL NOTE:

1. ALL HARDWARE SHOWN SHALL BE STAINLESS STEEL.

2. PROVIDE 1 MOUNTING POINT PER 12" OF BAR LENGTH.

3. HOLES MAY BE ADDED IF REQUIRED.

NOTE:

PERMANENTLY LABEL ALL WALL JACKS IN THE FOLLOWING MANNER: BUILDING-FLOOR-JACK

NUMBER-ROOM NUMBER OF CLOSET. EXAMPLE: 1-1-33-148B (BUILDING 1, FLOOR 1, JACK 33, CLOSET ROOM NUMBER 148B). JACK NUMBER INDICATES THE PUNCH DOWN POSITION OF THE

CLOSET CONNECTION. ALL JACKS ON THE SAME PLATE SHALL HAVE THE SAME NUMBER

WHERE POSSIBLE. LABEL ALL CABLES AT EACH END WITH THEIR RESPECTIVE NUMBER.

PROVIDE HORIZONTAL CABLING

PER SPECIFICATIONS WITH RJ45

CONNECTOR FOR DATA

CONNECTIONS. TERMINATE

CABLE IN TR AT RACK-MOUNTED

48-PORT MODULAR PATCH

PANELS. (TYPICAL)

PROVIDE INSULATING

BUSHING ON ALL PATHWAYS

TO COMMUNICATIONS

BACKBOXES.

PROVIDE SINGLE-GANG,

6-PORT FACEPLATE WITH

IDENTIFICATION WINDOWS.

PROVIDE MINIMUM 1-1/4"

RACEWAY, UNLESS NOTED

OTHERWISE. PROVIDE

INSULATION BUSHING AT

ENTRANCE TO BACKBOX.

PROVIDE 4-11/16" X 4-11/16" X

2-1/8" DOUBLE-GANG

BACKBOX WITH SINGLE-GANG

PLASTER RING.

FILL ALL UNUSED PORTS

WITH BLANK INSERTS. MATCH

COLOR OF FACEPLATE. (TYP.)

CLEAN 19mm (3/4")

CRUSHED ROCK

LINE SIDES OF

EXCAVATION WITH

13.6 KG (30 LBS.)

FELT PAPER

GRADE, FEATHER & TAMP

BACKFILL TO CREATE FLUSH

INSTALLATION AND POSITIVE

DRAINAGE AWAY FROM BOX

PROVIDE SINGLE-GANG,

2-PORT FACEPLATE WITH

IDENTIFICATION WINDOWS.

PROVIDE MINIMUM 1-1/4"

RACEWAY, UNLESS NOTED

OTHERWISE. PROVIDE

INSULATION BUSHING AT

ENTRANCE TO BACKBOX.

PROVIDE 4-11/16" x 4-11/16" x 2-1/8" DOUBLE-GANG

BACKBOX WITH

SINGLE-GANG PLASTER

RING.

PROVIDE HORIZONTAL CABLING

PER SPECIFICATIONS WITH RJ45

CONNECTOR FOR DATA

CONNECTION. TERMINATE CABLE

IN TR AT RACK-MOUNTED 48-PORT

MODULAR PATCH PANELS.

(TYPICAL)

PROVIDE INSULATING

BUSHING ON ALL PATHWAYS

TO COMMUNICATIONS

BACKBOXES.

PROVIDE COAX CABLING PER

SPECIFICATIONS WITH COAX

F-CONNECTOR. MATCH

ADAPTER COLOR TO

FACEPLATE.

NOTE:

COORDINATE EXACT LOCATION OF OUTLET WITH ARCHITECTURAL PLANS. LOCATION OF

OUTLET SHALL NOT CONFLICT WITH MOUNTING BRACKETS OR OTHER TRADES. PERMANENTLY

LABEL ALL WALL JACKS IN THE FOLLOWING MANNER: BUILDING-FLOOR-JACK NUMBER-ROOM

NUMBER OF CLOSET. EXAMPLE: 1-1-33-148B (BUILDING 1, FLOOR 1, JACK 33, CLOSET ROOM

NUMBER 148B). JACK NUMBER INDICATES THE PUNCH DOWN POSITION OF THE CLOSET

CONNECTION. ALL JACKS ON THE SAME PLATE SHALL HAVE THE SAME NUMBER WHERE

POSSIBLE. LABEL ALL CABLES AT EACH END WITH THEIR RESPECTIVE NUMBER.

PROVIDE HORIZONTAL CABLING

PER SPECIFICATIONS WITH RJ45

CONNECTOR FOR DATA

CONNECTIONS. TERMINATE

CABLE IN TR AT RACK-MOUNTED

48-PORT MODULAR PATCH

PANELS. PROVIDE SUFFICIENT

CABLE TO ALLOW REMOVAL/

ACCESS TO 2-PORT SURFACE

MOUNT BOX.

PROVIDE 2-PORT SURFACE

MOUNT BOX WITH

IDENTIFICATION WINDOWS

WITHIN BACKBOX.

PROVIDE INSULATING

BUSHING ON ALL PATHWAYS

TO COMMUNICATIONS

BACKBOXES.

PROVIDE MINIMUM 1" RACEWAY

TO EACH PROTECTED

CONNECTION.

RECESSED LOCATIONS: PROVIDE

DOUBLE-GANG PLASTER RING

AND BLANK FACEPLATE COVER.

SURFACE LOCATIONS: PROVIDE

SURFACE MOUNT JUNCTION BOX

COVER.

LABEL COVER WITH JACK

NUMBERS.

PROVIDE MINIMUM 1-1/4"

RACEWAY, UNLESS NOTED

OTHERWISE. PROVIDE

INSULATION BUSHING AT

ENTRANCE TO BACKBOX.

PROVIDE 6" X 6" X 2-1/2"

DOUBLE-GANG BACKBOX.

NOTE:

PERMANENTLY LABEL ALL WALL JACKS IN THE FOLLOWING MANNER: BUILDING-FLOOR-JACK

NUMBER-ROOM NUMBER OF CLOSET. EXAMPLE: 1-1-33-148B (BUILDING 1, FLOOR 1, JACK 33, CLOSET ROOM NUMBER 148B). JACK NUMBER INDICATES THE PUNCH DOWN POSITION OF THE

CLOSET CONNECTION. ALL JACKS ON THE SAME PLATE SHALL HAVE THE SAME NUMBER

WHERE POSSIBLE. LABEL ALL CABLES AT EACH END WITH THEIR RESPECTIVE NUMBER.

GROUNDING BAR DETAIL

NOT TO SCALE

6-PORT, 4-DATA, TELE-

COMMUNICATIONS OUTLET (TCO) DETAIL:

NOT TO SCALE

STANDARD

2-PORT TV MONITOR OUTLET DETAIL:

NOT TO SCALE

2-PORT, 2-DATA

WIRELESS ACCESS POINT (WAP) DETAIL:

NOT TO SCALE

TELECOMMUNICATIONS

UNDERGROUND HANDHOLE - TURF AREAS

NOT TO SCALE

DUCT BANK DETAIL

NOT TO SCALE

2-PORT, 2-DATA, PROTECTED TELE-

COMMUNICATIONS OUTLET (TCO) DETAIL:

NOT TO SCALE

(3")

2-WAY DUCT LINE

GENERAL NOTES:

1.

2.

3.

4.

CONCRETE SHALL BE 2000 P.S.I. @ 28 DAYS, OR AS SPECIFIED.

PROVIDE #4 REINFORCING RODS ON TOP AND BOTTOM OF DUCTS

WHEN CROSSING OR PLACED IN ROADWAYS.

MINIMUM COVER TO TOP OF ENVELOPE SHALL BE 610mm (24") OR AS

OTHERWISE SPECIFIED IN SECTION 26 05 41. PROVIDE METALLIC

TRACER TAPE 6" ABOVE CONCRETE DUCT.

PROVIDE VIRGIN 2400LB (MINIMUM) SEQUENTIAL MULE TAPE IN ALL

SPARE CONDUITS. EXTEND MULE TAPE A MINIMUM OF 6' OUTSIDE OF

CONDUITS AT EACH END.

(3")

76mm m m m m

76mm

(3")

76mm

(T Y

P

(2

M

IN

m m

3D

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

F

SHEET TITLE

ARCHITECT

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

STRUCTURAL / CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH. / ELEC. / PLUMB. / TECH. ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATHE, KS 66062

(913) 829-8650

LANDSCAPE ARCHITECT

ARC STUDIOS INC.

3117 E. FLOWER STREET

TUCSON, AZ 85716

(520) 882-9655

COMMISSIONING

GLHN ARCHITECTS & ENGINEERS, INC.

2939 E. BROADWAY BLVD

TUCSON, AZ 85716

(520) 881-4546

R1 - CONSTRUCT REPLACEMENT

WAREHOUSE

TECHNOLOGY DETAILS

01/06/2020 BEN ABM

500 AZ-89, PRESCOTT, AZ 86301

165-T-501

649-414

CR EL

DOOR POSITION

SWITCH (PROVIDE (2)

FOR DOUBLE-DOOR).

PROVIDE DOUBLE-GANG

BACKBOX WITH

SINGLE-GANG PLASTER

RING FOR CARD READER.

LOCATION PER PLANS.

FLOOR

UNDERGROUND CONCRETE

PULLBOX - TURF AREAS

NOT TO SCALE

FLUSH MOUNTED OUTLET

BOX. COORDINATE

LOCATION TO MATCH

CAMERA WIRING LOCATION

ACCESS.

1" CONDUIT TO

NEAREST CABLE TRAY

WALL

MOUNTING HEIGHT

PER SCHEDULE OR AS

NOTED ON DRAWINGS

WALL MOUNT BRACKET

PER SCHEDULE

CABLING PER RISER

DIAGRAM

EXPANSION ANCHORS

WITH STAINLESS STEEL

SECURITY FASTENERS

CAMERA PER

SCHEDULE

LIGHT POLE SHAFT.

CABLING PER RISER

DIAGRAM.

CAMERA POLE ADAPTER

MOUNTING STRAPS.

MINIMUM 3/4" LIQUID-TIGHT

FLEXIBLE METAL CONDUIT

WITH STRAIN RELIEF IN

POLE.

MOUNTING HEIGHT

PER SCHEDULE OR AS

NOTED ON DRAWINGS.

POLE ADAPTER PLATE

AND ARM FOR CAMERA.

CAMERA PER

SCHEDULE.

MAX. 48" AFF

OR MATCH

LIGHT SWITCH

DUAL HEIGHT, GATE

ACCESS CONTROL PEDESTAL BASE DETAIL

NOT TO SCALE

MOUNTING HEIGHT

PER SCHEDULE OR AS

NOTED ON DRAWINGS.

EXTERIOR WALL CORNER.

MINIMUM 3/4" LIQUID-TIGHT FLEXIBLE METAL

CONDUIT TO JUNCTION BOX WITH STAINLESS STEEL

COVER, SECURITY SCREWS, AND GASKET. MINIMIZE

CONDUIT LENGTH AND LOCATE JUNCTION BOX ON

SIDE OR REAR OF BUILDING.

CAMERA PER

SCHEDULE.

1" CONDUIT TO SYSTEM HEAD-END. CABLING

PER RISER DIAGRAM.

CORNER MOUNT ADAPTER AND BOTTOM

ENTRY ARM FOR CAMERA. SECURELY

FASTEN CORNER MOUNT ADAPTER TO

BUILDING STRUCTURE.

PROVIDE DOUBLE-GANG

BACKBOX WITH SINGLE-GANG

PLASTER RING FOR REQUEST

TO EXIT DOOR MOTION

DETECTOR.

COORDINATE

CONNECTION TO

ELECTRIC STRIKE OR

ELECTRIC

HINGE/LOCKSET WITH

ARCHITECTURAL DOOR

HARDWARE SCHEDULE.

PROVIDE CONNECTION

AS REQUIRED.

DOOR

PROVIDE 6"X6"X4" DEEP

JUNCTION BOX WITH HINGED

COVER. LOCATE ON

SECURE SIDE OF DOOR.

PROVIDE 1" CONDUIT

BACK TO ACCESS

CONTROL PANEL.

3/4" CONDUIT

(TYPICAL, UNO)

ACCESSIBLE CEILING

LAY-IN CEILING

SECURE RACEWAY TO

STRUCTURE.

ROUTE MINIMUM 1"

RACEWAY AND CABLING

BACK TO SECURITY

SYSTEM HEAD-END

EQUIPMENT IN

COMMUNICATIONS ROOM.

DOME CAMERA

PROVIDE MINIMUM 18" OF

SECURITY CAMERA CABLING

INSIDE BOX WITH DIRECT

CONNECTION TO SECURITY

CAMERA.

PROVIDE MINIMUM 4-11/16" X

4-11/16" X 2-1/8" DOUBLE-GANG

BACKBOX WITH DOUBLE-GANG

PLASTER RING.

CEILING TILE ADJUSTABLE

BOX HANGER

TYPICAL CARD READER/

ELECTRIFIED LOCKING DEVICE DETAIL

NOT TO SCALE

LAY-IN CEILING VIDEO SURVEILLANCE

CAMERA INSTALLATION DETAIL

NOT TO SCALE

EXTERIOR

LIGHT POLE MOUNTED CAMERA DETAIL

NOT TO SCALE

TYPICAL INTERIOR OR

EXTERIOR WALL-MOUNTED CAMERA DETAIL

NOT TO SCALE

EXTERIOR WALL

CORNER-MOUNTED CAMERA DETAIL

NOT TO SCALE

(4) CONCRETE BRICKS

51mmx203mmx406mm

(2"x8"x16")

CONDUIT(S) WITH BELL ENDS

(TYP). SIZE, QUANTITY AND

WIRING AS INDICATED ON PLANS

CLEAN 19mm (3/4")

CRUSHED ROCK

GRADE, FEATHER & TAMP

BACKFILL TO CREATE FLUSH

INSTALLATION AND POSITIVE

DRAINAGE AWAY FROM BOX

V A

R

IE

S (1

PULLBOX (SEE SPECIFICATIONS)

LINE SIDES OF EXCAVATION

WITH 13.6 KG (30 LBS.) FELT

PAPER

(12") m m

305mm

GENERAL NOTES:

1. BACKFILL, CONCRETE, REINFORCING STEEL, AND ANCHOR BOLTS ARE

SHOWN FOR REFERENCE ONLY. POLE BASE STRUCTURAL REQUIREMENTS

SHALL BE DESIGNED AND SEALED BY A PROFESSIONAL ENGINEER

LICENSED IN THE PROJECT STATE AND SUBMITTED AS PART OF THE

SUBMITTAL PROCESS.

m m

M

IN

(2

M

IN

PVC CONDUIT

PVC CONDUIT ADAPTER

COUPLING

RIGID STEEL CONDUIT

PROVIDE 36"Lx36"Wx4"D

CONCRETE MOW PAD AT

GRADE.

BASE COVER PLATE

FINISHED GRADE

PEDESTAL, WEATHER HOODS,

AND DEVICES PER SCHEDULES.

GALVANIZED ANCHOR BOLTS &

HEX NUTS. PROVIDE LEVELING

SHIMS OR HEX NUTS.

UNDISTURBED SOIL OR SELECT,

COMPACTED BACKFILL. SEE

NOTE BELOW.

CONCRETE BASE &

REINFORCING STEEL. SEE

NOTE BELOW.

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

F

SHEET TITLE

ARCHITECT

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

STRUCTURAL / CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH. / ELEC. / PLUMB. / TECH. ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATHE, KS 66062

(913) 829-8650

LANDSCAPE ARCHITECT

ARC STUDIOS INC.

3117 E. FLOWER STREET

TUCSON, AZ 85716

(520) 882-9655

COMMISSIONING

GLHN ARCHITECTS & ENGINEERS, INC.

2939 E. BROADWAY BLVD

TUCSON, AZ 85716

(520) 881-4546

R1 - CONSTRUCT REPLACEMENT

WAREHOUSE

TECHNOLOGY DETAILS

01/06/2020 BEN ABM

500 AZ-89, PRESCOTT, AZ 86301

165-T-502

649-414

DM

EL

MD

RE

KP

DM

GB

MD

KP

DM

CR

GO

S S S

V

S S S

J

J

1. PERFORM ALL WORK IN ACCORDANCE WITH THE SPECIFICATIONS AND THE

NAVAHCS STRUCTURED CABLING AND FIBER OPTICS GUIDELINES.

2. PROVIDE FIBER-OPTIC ADAPTERS AS REQUIRED IN BUILDING 70 FOR THE

TERMINATION OF ALL FIBER-OPTIC CABLING.

3. COORDINATE THE COLORS OF ALL STRUCTURED CABLING AND FIBER-OPTIC

CABLING WITH NAVAHCS OI&T. ALL OI&T CABLING SHALL BE GREEN, SECURITY

CABLING SHALL BE BLUE, AND FIRE ALARM CONTROL (FACP) SHALL BE RED.

4. COORDINATE WITH VA OI&T TO CONFIGURE FIRE ALARM CONTROL FIBER-OPTIC

(FACP) TO MAINTAIN CAMPUS LOOP CONFIGURATION. MODIFY FACP CABLING IN

BUILDING 70 AS REQUIRED TO MAINTAIN A LOOP SYSTEM.

1 2

3 4

HORIZONTAL

CABLING

PATCH

PANEL

HORIZONTAL

CABLING

PATCH

PANEL

TELECOM

GROUND BAR TGB

TO ELECTRICAL

MAIN SERVICE

GROUND

WHERE ACCESSIBLE, BOND TGB

TO BUILDING STEEL WITHIN

COMMUNICATIONS ROOM.

PROVIDE SEPARATE, MINIMUM #6 AWG

STRANDED BONDING CONDUCTOR FROM

EACH RACK AND EQUIPMENT ENCLOSURE

TO TGB. (TYPICAL)

PROVIDE MINIMUM #6 AWG STRANDED

BONDING CONDUCTOR FROM CABLE TRAY

TO TGB.

PROVIDE MINIMUM #6 AWG STRANDED

BONDING CONDUCTOR OR BONDING

STRAP

BETWEEN SECTIONS AND JUNCTIONS OF

CABLE TRAYS. (TYPICAL)

PROVIDE BONDING BUSHING AT

CONDUIT END AND MINIMUM #6

AWG

STRANDED BONDING CONDUCTOR

TO CABLE TRAY.

PROVIDE MINIMUM #6 AWG STRANDED

BONDING CONDUCTOR FROM CABLE

TRAY TO FIRE STOP CABLE PENETRATION

ON EACH SIDE OF WALL.

ZONE 2: BREAK ROOM 102,

PLOTTING 108, WRAPPING 117

CORRIDOR 109

SPEAKER WIRING (TYPICAL)

ZONE 3: FIRST

FLOOR OVERALL

ZONE 1: WAREHOUSE 101

LOCAL WALL-MOUNTED

VOLUME CONTROL

(TYPICAL)

CATEGORY 6A CABLE

MULTI-CONDUCTOR CABLE

2-STRAND FIBER-OPTIC PATCH CABLE

POWER

PB

LEGEND:

120V

120V

PB

PB

WAREHOUSE FLOOR

AND

BUILDING PERIMETER

INTRUSION DETECTION

SYSTEM. KEYPAD,

MOTION DETECTORS,

DOOR MONITORS, AND

GLASS BREAK

DETECTORS PER PLANS.

(TYPICAL)120V

PA-MN

SYSTEM

HEAD-END

EQUIPMENT

120V

COORDINATE CONNECTION

TO VA NETWORK WITH VA

OI&T

PROVIDE UPS PER

SPECIFICATIONS.

PROVIDE UPS

PER

SPECIFICATIONS

RACK-

MOUNTED

UPS

PROPOSED PUBLIC

ADDRESS-MASS

NOTIFICATION

ZONE LAYOUT

PB

VEHICLE DETECTION

PAVEMENT LOOP

VEHICLE DETECTION

PAVEMENT LOOP

TRUCK DOCK

ENTRANCE GATE

V

V

VAPD

FIBER-OPTIC

ENCLOSURE

VA OI&T

FIBER-OPTIC

ENCLOSURE

VA OI&T

FIBER-OPTIC

ENCLOSURE

FACP

FIBER-OPTIC

ENCLOSURE

POE GB

NETWORK

SWITCH

POE GB

NETWORK

SWITCH

RACK-MOUNTED

UPS

RACK-MOUNTED

UPS BATTERY

CABINET

PROVIDE MINIMUM 24-STRAND

FIBER-OPTIC ENCLOSURE AND

FIBER-OPTIC ADAPTERS AS REQUIRED.

INCREASE ENCLOSURE SIZE AS REQUIRED

TO SUPPORT A 50% EXPANSION OF

INCOMING OSP FIBER-OPTIC CABLING.

PROVIDE HORIZONTAL CABLE MANAGERS

ABOVE AND BELOW EACH ENCLOSURE.

(TYPICAL)

FURNISH FIBER-OPTIC PATCH CABLES OF

THE SAME FIBER/CONNECTOR TYPE AND

PERFORMANCE CHARACTERISTICS FOR

INTERCONNECTION OF THE FIBER

BACKBONE TO THE NETWORK SWITCHES.

INSTALLATION BY VA OI&T. COORDINATE

EXACT QUANTITY AND LENGTH OF EACH

CABLE WITH VA OI&T.

PROVIDE (2) 4-STRAND OM1, MULTI-MODE

FIBER-OPTIC CABLES IN 1" CONDUIT FROM

FIBER-OPTIC ENCLOSURE TO FIRE ALARM

CONTROL PANEL.

NETWORK SWITCHES FURNISHED AND

INSTALLED BY VA OI&T. PROVIDE

HORIZONTAL CABLE MANAGERS

ABOVE AND BELOW EACH SWITCH.

COORDINATE EXACT QUANTITY WITH

VA OI&T.

FURNISH HORIZONTAL CABLING PATCH

CABLES FOR INTERCONNECTION OF THE

NETWORK SWITCHES TO THE FACILITY

HORIZONTAL CABLING. INSTALLATION BY

VA OI&T. FURNISH SUFFICIENT QUANTITY

TO CONNECT EACH OUTLET WITHIN

FACILITY PLUS 10% SPARE. COORDINATE

EXACT LENGTH WITH VA OI&T.

PROVIDE RACK-MOUNTED 120V,

1.8KW/1.92KVA UNINTERRUPTIBLE

POWER SUPPLY (UPS) WITH 1-HOUR

RACK-MOUNTED BATTERY BACKUP.

COORDINATE EXACT REQUIREMENTS

WITH VA OI&T.

PROVIDE (2) 4" CONDUITS, (1) WITH (4) 1"

INNERDUCTS FROM IT ROOM BACK TO

BUILDING 70 IT ROOM. PROVIDE PULL

CORD IN ALL UNUSED DUCTS.

(2) 4-STRAND OM1, MULTI-MODE

FIBER-OPTIC CABLE WITH ST

CONNECTORS FOR NAVAHCS FACP

6-STRAND OS1, SINGLE-MODE

FIBER-OPTIC CABLE WITH ST

CONNECTORS FOR NAVAHCS VAPD

12-STRAND OM3, MULTI-MODE OSP

RATED FIBER-OPTIC CABLE WITH LC

CONNECTORS FOR NAVAHCS OI&T

12-STRAND OS1, SINGLE-MODE OSP

RATED FIBER-OPTIC CABLE WITH LC

CONNECTORS FOR NAVAHCS OI&T

PROVIDE 48-PORT MODULAR PATCH

PANELS WITH RJ45 CONNECTIONS AS

REQUIRED FOR COMMUNICATIONS

OUTLETS IN FACILITY. PROVIDE

ADDITIONAL PATCH PANELS TO SUPPORT

A 50% EXPANSION. PROVIDE HORIZONTAL

CABLE MANAGERS ABOVE AND BELOW

EACH PATCH PANEL.

TYPICAL COMMUNICATIONS OUTLET.

ROUTE CABLING IN CONDUIT AND

CABLE TRAY TO IT ROOM.

VASS SECURITY

CAMERA PATCH

PANEL

VASS POE GB

SWITCH

RACK-MOUNTED

UPS

PHYSICAL

ACCESS

CONTROL

CABINET(S)

PACS BATTERY

CABINET(S)

INTRUSION

DETECTION

SYSTEM

CABINET(S)

IDS BATTERY

CABINET(S)

FIRE ALARM

RELAY(S)

COORDINATE

CONNECTION TO VAPD

FIBER ENCLOSURE WITH

VA OI&T

COORDINATE

CONNECTION TO VAPD

FIBER ENCLOSURE WITH

VA OI&T

CARD READERS AND

ASSOCIATED DEVICES PER

PLANS. (TYPICAL)

EMERGENCY PHARMACY

CACHE INTRUSION

DETECTION SYSTEM.

KEYPAD, MOTION

DETECTORS, AND DOOR

MONITORS PER PLANS.

(TYPICAL)

GATE OPENER CONTROLS

GATE CARD READERS

VASS CAMERAS PER PLANS

(TYPICAL)

BUILDING 165, MAIN IT ROOM 212

TECHNOLOGY RISER DIAGRAM

NO SCALE

TECHNOLOGY GROUNDING

AND BONDING RISER DIAGRAM

NO SCALE

FLOORTR - COMMS ROOM CORRIDOR

PUBLIC ADDRESS-MASS NOTIFICATION

SYSTEM (PA-MN) RISER DIAGRAM

NO SCALE

TR - COMMS ROOM FIRST FLOOR

SECURITY RISER DIAGRAM

NO SCALE

TR - COMMS ROOM SECOND FLOOR

TECHNOLOGY RISER DIAGRAM GENERAL NOTES:

S S S

SS

S

J J1TV/1D 1TV/1D

TYPICAL MATV

OUTLET

TR - COMMS ROOM

ROUTE TO DATA

PATCH PANEL

(TYPICAL)

MATV BRANCH

CABLE

FLOOR

FUTURE MATV

TRUNK CABLE

MATV SYSTEM

ENCLOSURE WITH

AMPLIFER AND

SPLITTER

CATV CATV CATV CATV

CATV CATV

D D

D

MASTER ANTENNA TELEVISION

SYSTEM (MATV) RISER DIAGRAM

NO SCALE

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

F

SHEET TITLE

ARCHITECT

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

STRUCTURAL / CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH. / ELEC. / PLUMB. / TECH. ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATHE, KS 66062

(913) 829-8650

LANDSCAPE ARCHITECT

ARC STUDIOS INC.

3117 E. FLOWER STREET

TUCSON, AZ 85716

(520) 882-9655

COMMISSIONING

GLHN ARCHITECTS & ENGINEERS, INC.

2939 E. BROADWAY BLVD

TUCSON, AZ 85716

(520) 881-4546

R1 - CONSTRUCT REPLACEMENT

WAREHOUSE

TECHNOLOGY RISER DIAGRAMS

01/06/2020 BEN ABM

500 AZ-89, PRESCOTT, AZ 86301

165-T-601

649-414

CR

MD

MD

MD

M

IC

IC

IC

AUTO TRUCK

AUTO TRUCK

PROVIDE ALL WIRING BETWEEN MASTER STATION AND SECONDARY STATIONS PER MANUFACTURERS RECOMMENDATIONS. PROVIDE MINIMUM 3/4" CONDUIT FOR ABOVE GROUND AND MINIMUM 1" CONDUIT FOR BELOW GROUND WIRING.3.

MOUNTING HEIGHT TO MEET ADA COMPLIANCE2.

PROVIDE POWER SUPPLIES AND CABLING AS REQUIRED FOR A COMPLETE OPERATIONAL SYSTEM.1.

NOTES:

2, 3

(2) SURFACE MOUNT SECONDARY VIDEO INTERCOM STATION WITH DIGITAL PAN/TILT/ZOOM

CAMERA, CALL BUTTON AND MICROPHONE WITH STAINLESS STEEL SURFACE MOUNT BOX.

MOUNT ON DUAL HEIGHT PEDESTAL WITH PACS CARD READER. RE: PACS CARD READER

SCHEDULE THIS DRAWING FOR ADDITIONAL INFORMATION.

OUTDOOR

42" AFG TO

CENTER OF AUTO

INTERCOM AND

84" AFG TO

CENTER OF

TRUCK INTERCOM

PEDESTAL

RE: DETAIL

7/165-T-502

SECONDARY INTERCOM

STATION

AIPHONE:

(2) JP-DV

IC-03

2, 3

SURFACE MOUNT SECONDARY VIDEO INTERCOM STATION WITH DIGITAL PAN/TILT/ZOOM

CAMERA, CALL BUTTON AND MICROPHONE.

OUTDOOR

WALL MOUNT AT

48"

TO UNIT CENTER

WALL

SECONDARY INTERCOM

STATION

AIPHONE:

JP-DV

IC-02

1, 2, 3

MASTER VIDEO INTERCOM STATION WITH LCD SCREEN, SPEAKER, MONITOR BUTTON AND

DOOR RELEASE BUTTON. CAPABLE OF INTERFACING WITH (4) SECONDARY STATIONS.

MASTER STATION SHALL PROVIDE POWER TO ALL SECONDARY STATIONS.

INDOOR

WALL MOUNT AT

48"

TO UNIT TOP

WALL

MASTER INTERCOM STATION

WITH VIDEO SCREEN

AIPHONE:

JP-4MED

IC-O1

NOTESCOMMENTSLOCATION

MOUNTING

HEIGHT

MOUNTING

TYPE

DESCRIPTION

BASIS OF DESIGN:

MANUFACTURER AND MODEL

FORM FACTOR

SYMBOL

TYPE

TYPE

VIDEO INTERCOM/DOORBELL SCHEDULE

PROVIDE ALL ACCESSORIES AS REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM COMPATIBLE WITH THE EXISTING CAMPUS PACS SYSTEM. PROVIDE ALL UPGRADES TO THE EXISTING PACS SYSTEM TO INCORPORATE NEW DEVICES.1.

NOTES:

(2) DUAL AUTHENTICATION CARD READERS WITH KEYPAD

COMPATIBLE WITH EXISTING NAVAHCS CAMPUS CARD READER

SYSTEM, WITH WEATHER HOOD, BUILT-IN HEATER, AND GASKET

FOR COLD-WEATHER. PROVIDE DUAL 42" AUTO/ 84" TRUCK

HEIGHT PEDESTAL. PEDESTAL SHALL BE CONSTRUCTED OF

HEAVY DUTY, 11 GAUGE STEEL WITH LEVELING MOUNTING

BOLTS AND BASE COVER, SAFETY YELLOW IN COLOR. PROVIDE

WEATHER HOOD HOUSING SUITABLE FOR MOUNTING OF CARD

READER AND VIDEO INTERCOM/DOORBELL DEVICES. RE:

VIDEO/INTERCOM DOORBELL SCHEDULE THIS DRAWING FOR

ADDITIONAL INFORMATION..

BLACK

85mA AVG/

220mA PEAK

AT 12VDC

4" MAXIMUM

MATCH EXISTING

VA CARD READER

SYSTEM

INDOOR/

OUTDOOR,

IP55 RATED

42" AFG TO

CENTER OF AUTO

READER AND 84"

AFG TO CENTER

OF TRUCK

READER

PEDESTAL

RE: DETAIL

7/165-T-502

OUTDOOR PEDESTAL MOUNT

DUAL CARD READER

CR-03

DUAL AUTHENTICATION CARD READER WITH KEYPAD

COMPATIBLE WITH EXISTING NAVAHCS CAMPUS CARD READER

SYSTEM, WITH WEATHER HOOD, BUILT-IN HEATER, AND GASKET

FOR COLD-WEATHER.

BLACK

85mA AVG/

220mA PEAK

AT 12VDC

4" MAXIMUM

MATCH EXISTING

VA CARD READER

SYSTEM

INDOOR/

OUTDOOR,

IP55 RATED

48" TO TOP OF

BOX ABOVE

FINISHED

FLOOR/GRADE

WALL.

RE: DETAIL

2/165-T-502

OUTDOOR CARD READERCR-02

DUAL AUTHENTICATION CARD READER WITH KEYPAD

COMPATIBLE WITH EXISTING NAVAHCS CAMPUS CARD READER

SYSTEM.

BLACK

85mA AVG/

220mA PEAK

AT 12VDC

4" MAXIMUM

MATCH EXISTING

VA CARD READER

SYSTEM

INDOOR/

OUTDOOR,

IP55 RATED

48" TO TOP OF

BOX ABOVE

FINISHED FLOOR

WALL.

RE: DETAIL

2/165-T-502

CARD READERCR-01

NOTESCOMMENTSCOLORPOWERREAD RANGEMODELSLOCATION

MOUNTING

HEIGHT

MOUNTING

TYPE

DESCRIPTIONFORM FACTOR

SYMBOL

TYPE

TYPE

PHYSICAL ACCESS CONTROL SYSTEM (PACS) CARD READER SCHEDULE

COORDINATE LENS(ES) FOCAL LENGTH(S) AND AIMING WITH OWNER.2.

PROVIDE ALL ACCESSORIES AS REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM COMPATIBLE WITH THE EXISTING CAMPUS VASS SYSTEM. PROVIDE ALL UPGRADES TO EXISTING VASS SYSTEM TO INCORPORATE NEW SURVEILLANCE CAMERAS.1.

NOTES:

1, 2

SINGLE 3-AXIS GIMBAL INDIVIDUAL ADJUSTABLE

CAMERA WITH SENSOR, DAY/NIGHT, CLEAR DOME,

VANDAL RESISTANT, ETHERNET IP-BASED DIGITAL

CAMERA WITH RJ45 CONNECTION TO VIDEO

SURVEILLANCE SYSTEM.

WHITE

POWER OVER

ETHERNET

REMOTE FOCUS,

MOTORIZED

PAN/TILT/ZOOM,

VARIFOCAL LENS

1 x 1/3" / 2 MP (MIN)

COMPATIBLE WITH VA

CAMPUS HEAD-END VIDEO

ASSESSMENT AND

SURVEILLANCE SYSTEM

OUTDOOR,

MINIMUM

IP66 RATED

LIGHT POLE,

15'-0"

ABOVE FINISHED

GRADE

LONG EXTENSION

MOUNT W/ LIGHT

POLE ADAPTER.

RE: DETAIL

5/165-T-502

SINGLE VIEW,

COMPACT MINI DOME

C-06

1, 2

(4) 3-AXIS GIMBAL INDIVIDUAL ADJUSTABLE

CAMERAS WITH SENSORS, DAY/NIGHT, CLEAR

DOME, VANDAL RESISTANT, ETHERNET IP-BASED

DIGITAL CAMERA WITH RJ45 CONNECTION TO

VIDEO SURVEILLANCE SYSTEM.

WHITE

POWER OVER

ETHERNET

REMOTE FOCUS,

VARIFOCAL LENS

4 x 1/3" / 2 MP (MIN)

COMPATIBLE WITH VA

CAMPUS HEAD-END VIDEO

ASSESSMENT AND

SURVEILLANCE SYSTEM

OUTDOOR,

MINIMUM

IP66 RATED

WALL,

12'-0"

ABOVE FINISHED

FIRST FLOOR

LEVEL

WALL BRACKET

MOUNT W/ CORNER

ADAPTER.

RE: DETAIL

6/165-T-502

270 DEGREE

(4) CUSTOMIZABLE VIEW,

COMPACT DOME

C-05

1, 2

SINGLE 2-AXIS GIMBAL CAMERA WITH MULTIPLE

SENSORS, DAY/NIGHT, CLEAR DOME, VANDAL

RESISTANT, ETHERNET IP-BASED DIGITAL CAMERA

WITH RJ45 CONNECTION TO VIDEO SURVEILLANCE

SYSTEM.

WHITE

POWER OVER

ETHERNET

REMOTE FOCUS,

VARIFOCAL LENS

4 x 1/3" / 2 MP (MIN)

COMPATIBLE WITH VA

CAMPUS HEAD-END VIDEO

ASSESSMENT AND

SURVEILLANCE SYSTEM

INDOOR,

MINIMUM IP65

RATED

FLUSH TO CEILING

CEILING SURFACE.

RE: DETAIL

3/165-T-502

360 DEGREE

PANORAMIC VIEW,

COMPACT DOME

C-04

1, 2

SINGLE 2-AXIS GIMBAL CAMERA WITH MULTIPLE

SENSORS, DAY/NIGHT, CLEAR DOME, VANDAL

RESISTANT, ETHERNET IP-BASED DIGITAL CAMERA

WITH RJ45 CONNECTION TO VIDEO SURVEILLANCE

SYSTEM.

WHITE

POWER OVER

ETHERNET

REMOTE FOCUS,

VARIFOCAL LENS

4 x 1/3" / 2 MP (MIN)

COMPATIBLE WITH VA

CAMPUS HEAD-END VIDEO

ASSESSMENT AND

SURVEILLANCE SYSTEM

INDOOR,

MINIMUM IP65

RATED

30'-0" ABOVE

FINISHED FLOOR

CEILING PENDANT

MOUNT

360 DEGREE

PANORAMIC VIEW,

COMPACT DOME

C-03

1, 2

SINGLE 2-AXIS GIMBAL CAMERA WITH MULTIPLE

LENSES, DAY/NIGHT, CLEAR DOME, VANDAL

RESISTANT, ETHERNET IP-BASED DIGITAL CAMERA

WITH RJ45 CONNECTION TO VIDEO SURVEILLANCE

SYSTEM.

WHITE

POWER OVER

ETHERNET

REMOTE FOCUS,

VARIFOCAL LENS

4 x 1/3" / 2 MP (MIN)

COMPATIBLE WITH VA

CAMPUS HEAD-END VIDEO

ASSESSMENT AND

SURVEILLANCE SYSTEM

INDOOR,

MINIMUM IP65

RATED

WALL, 12'-0"

ABOVE FINISHED

FLOOR

WALL BRACKET

MOUNT.

RE: DETAIL

4/165-T-502

180 DEGREE

PANORAMIC VIEW,

COMPACT DOME

C-02

1, 2

SINGLE 3-AXIS GIMBAL INDIVIDUAL ADJUSTABLE

CAMERA WITH LENS, DAY/NIGHT, CLEAR DOME,

VANDAL RESISTANT, ETHERNET IP-BASED DIGITAL

CAMERA WITH RJ45 CONNECTION TO VIDEO

SURVEILLANCE SYSTEM.

WHITE

POWER OVER

ETHERNET

REMOTE FOCUS,

VARIFOCAL LENS

1 x 1/3" / 2 MP (MIN)

COMPATIBLE WITH VA

CAMPUS HEAD-END VIDEO

ASSESSMENT AND

SURVEILLANCE SYSTEM

INDOOR,

MINIMUM IP65

RATED

FLUSH TO CEILING

CEILING SURFACE.

RE: DETAIL

3/165-T-502

SINGLE VIEW,

COMPACT MINI DOME

C-01

NOTESCOMMENTSCOLORPOWERLENS TYPE

IMAGER/SENSOR

QTY/SIZE,

RESOLUTION

MODELSLOCATION

MOUNTING

HEIGHT

MOUNTING

TYPE

DESCRIPTIONFORM FACTOR

SYMBOL

TYPE

TYPE

VIDEO ASSESSMENT AND SURVEILLANCE SYSTEM (VASS) CAMERA SCHEDULE

PROVIDE ALL ACCESSORIES AS REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM COMPATIBLE WITH THE EXISTING CAMPUS PACS SYSTEM. PROVIDE ALL UPGRADES TO THE EXISTING PACS SYSTEM TO INCORPORATE NEW DEVICES.1.

NOTES:

PASSIVE INFRA-RED (PIR) MOTION DETECTOR FOR 360-DEGREE

COVERAGE.

WHITE

22mA

AT 12VDC

360 DEGREE,

35'-0"

DIAMETER

COMPATIBLE WITH

VA CAMPUS

HEAD-END

INTRUSION

DETECTION SYSTEM

INDOOR

FLUSH TO

CEILING,

12'-0" ABOVE

FINISHED FLOOR

CEILINGMOTION DETECTORID-03

LONG RANGE, MICROWAVE AND PASSIVE INFRA-RED (PIR)

MOTION DETECTOR FOR NARROW AREA COVERAGE.

WHITE

22mA

AT 12VDC

APPROX.

5 DEGREE,

98'-0" LONG X

9'-6" WIDE

COMPATIBLE WITH

VA CAMPUS

HEAD-END

INTRUSION

DETECTION SYSTEM

INDOOR

10'-0" ABOVE

FINISHED FLOOR

WALL

LONG RANGE MOTION

DETECTOR

ID-02

LONG RANGE, MICROWAVE AND PASSIVE INFRA-RED (PIR)

MOTION DETECTOR FOR WIDE AREA COVERAGE.

WHITE

22mA

AT 12VDC

APPROX.

90 DEGREE,

69'-0" LONG X

69'-0" WIDE

COMPATIBLE WITH

VA CAMPUS

HEAD-END

INTRUSION

DETECTION SYSTEM

INDOOR

10'-0" ABOVE

FINISHED FLOOR

WALL

LONG RANGE MOTION

DETECTOR

ID-01

NOTESCOMMENTSCOLORPOWERCOVERAGEMODELSLOCATION

MOUNTING

HEIGHT

MOUNTING

TYPE

DESCRIPTIONFORM FACTOR

SYMBOL

TYPE

TYPE

INTRUSION DETECTION SYSTEM (IDS) MOTION DETECTOR SCHEDULE

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

F

SHEET TITLE

ARCHITECT

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

STRUCTURAL / CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH. / ELEC. / PLUMB. / TECH. ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATHE, KS 66062

(913) 829-8650

LANDSCAPE ARCHITECT

ARC STUDIOS INC.

3117 E. FLOWER STREET

TUCSON, AZ 85716

(520) 882-9655

COMMISSIONING

GLHN…