Attachment 7 - F Drawings.pdf

PDF 582 KB Posted

Attached to
Y1GZ--Construct Replacement Warehouse Prescott VAMC (Minor Construction) Federal contract opportunity
Solicitation number
36E77620R0043
Issued by
Department of Veterans Affairs Headquarters

About this file

This solicitation is for the construction of a replacement warehouse facility at the Northern Arizona VA Health Care System in Prescott, Arizona. The Department of Veterans Affairs intends to award a single firm-fixed-price contract for design-bid-build services to construct a new approximately 10,930 square foot conditioned warehouse, along with associated site work including nearly 30,000 square feet of paving and over 5,000 square feet of hardscape. The solicitation will be a total SDVOSB set-aside with an anticipated value between $5-10 million and a performance period of approximately 360 calendar days. Proposals are due on or around July 27, 2020 in response to request for proposal number 36E77620R0043.

View the file

Other files for this federal contract opportunity

Other files attached to Y1GZ--Construct Replacement Warehouse Prescott VAMC (Minor Construction), newest first.
File Type Posted
36E77620R0043 0006.docx DOCX document
Technical Questions Tracking Sheet - 09-14-2020.pdf PDF
36E77620R0043 0005.docx DOCX document
1395.26_Revised Roof Slope Sketch.pdf PDF
Telecom Specs1.pdf PDF
Technical Questions Tracking Sheet - 09-09-2020.pdf PDF
Construction Wage Rates - Yavapai - 08-21-2020.pdf PDF
Monitoring and Discovery Protocol.pdf PDF
Item 70 response_Drawing-Montage Commercial Classic.pdf PDF
07 43 00 Wall and Roof Panels.pdf PDF
36E77620R0043 0004.docx DOCX document
Item 69 response_Drawing-Montage Commercial Classic Gate.pdf PDF
1395.26 Construct Replacement Warehouse_ASI 002 Narrative.pdf PDF
01 00 00 - General Requirements.pdf PDF
10 26 00 Wall Protection.pdf PDF
Item 81 response_Fire-rated Ceiling Assembly Detail.pdf PDF
Reference C - Question 112 - 067 165-M-301 MECHANICAL SECTIONS AND ENLARGED.pdf PDF
Reference E - Question 113 - DIV 13 SPECIAL CONSTRUCTION.pdf PDF
Reference D - Question 113 - 026 165-SA-001 STRUCTURAL GENERAL NOTES.pdf PDF
S05 - Technical Questions Tracking Sheet TO BE PUBLISHED 9-4.pdf PDF
36E77620R0043 0003.docx DOCX document
Technical Questions Tracking Sheet 36E77620R0043.pdf PDF
36E77620R0043 0002.docx DOCX document
36E77620R0043 - SITE VISIT SIGN IN SHEET - 08-11-2020.pdf PDF
36E77620R0043 0001.docx DOCX document
Attachment 15 - Construction Wage Rates - Yavapai - 06-05-2020.pdf PDF
Copy of Attachment 14 - Division Price Breakdown.xlsx XLSX spreadsheet
Attachment 12 - T Drawings.pdf PDF
Attachment 10 - P Drawings.pdf PDF
Attachment 13 - Warehouse Building Soils Report.pdf PDF
Attachment 16 - Contractor Safety _ Env Record Form.docx DOCX document
Attachment 11 - S Drawings.pdf PDF
Attachment 8 - G Drawings.pdf PDF
Attachment 1 - Volume 01 Specifications REV.pdf PDF
Attachment 9 - M Drawings.pdf PDF
Attachment 4 - A Drawings.pdf PDF
Attachment 3 - Volume 03 Specifications REV.pdf PDF
Attachment 2 - Volume 02 Specifications.pdf PDF
36E77620R0043.docx DOCX document
Attachment 5 - C Drawings Part I.pdf PDF
Attachment 17 - Prescott Site Map.pdf PDF
Attachment 5 - C Drawings Part II.pdf PDF
Attachment 6 - E Drawings.pdf PDF
Show all 43

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. PROVIDE A NEW ADDRESSABLE FIRE ALARM AND

DETECTION SYSTEM.

2. THE FIRE ALARM SYSTEM DRAWING DETAILS ARE

REPRESENTED BY THE SERIES OF FA DRAWINGS. THE FA

SERIES DRAWINGS MUST BE INTERPRETED IN THEIR

ENTIRETY FOR CONSTRUCTION AND INSTALLATION

REQUIREMENTS; NO SINGLE FA SERIES DRAWING

CONTAINS ALL INFORMATION RELATING TO THE FIRE ALARM

SYSTEM DESIGN INTENT OR SPECIFICATION.

3. THE FIRE ALARM SYSTEM SHALL MEET THE APPLICATION,

INSTALLATION, PERFORMANCE REQUIREMENTS IN

ACCORDANCE WITH VA FIRE PROTECTION DESIGN MANUAL,

THE NATIONAL ELECTRICAL CODE (NEC) 2017, NATIONAL

FIRE ALARM SIGNALING CODE (NFPA 72) 2019, INSTALLATION

OF AIR CONDITIONING AND VENTILATION SYSTEMS (NFPA

90A) 2018, AS WELL AS STATE AND LOCAL BUILDING CODES

AND STANDARDS.

4. THE CONTRACTOR SHALL CAREFULLY REVIEW

APPLICABLE CRITERIA AND STANDARDS, THESE DRAWINGS,

AND THE PROJECT SPECIFICATIONS FOR IMPORTANT

QUALIFICATION, DEFINITION, SUBMITTAL, PRODUCT,

INSTALLATION, AND TESTING REQUIREMENTS.

5. PRIOR TO BEGINNING ANY CONSTRUCTION, THE

CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION

OF ALL DIMENSIONS, MEASUREMENTS, AND LOCATIONS OF

DEVICES, UTILITIES, EQUIPMENT AND OTHER

OBSTRUCTIONS THAT MAY AFFECT THE OVERALL DESIGN

LAYOUT.

6. INITIATING DEVICE CIRCUITS (IDC) SHALL BE INSTALLED

UTILIZING CLASS "B" CONFIGURATION AND SHALL NOT BE T-

TAPPED.

7. SIGNALING LINE CIRCUITS (SLC) SHALL BE INSTALLED

UTILIZING CLASS "B" CONFIGURATION AND MAY BE T-

TAPPED.

8. NOTIFICATION APPLIANCE CIRCUITS (NAC) SHALL BE

INSTALLED UTILIZING CLASS "B" CONFIGURATION AND

SHALL NOT BE T-TAPPED.

9. BATTERY BACKUP FOR THE SYSTEM SHALL PROVIDE

SUFFICIENT POWER TO OPERATE THE SYSTEM UNDER

QUIESCENT LOAD FOR A MINIMUM OF 24 HOURS AND, AT

THE END OF THAT PERIOD, SHALL BE CAPABLE OF

OPERATING ALL ALARM NOTIFICATION APPLIANCES USED

FOR EVACUATION OR TO DIRECT AID TO THE LOCATION OF

AN EMERGENCY FOR 5 MINUTES.

10. THE AUDIBLE NOTIFICATION SYSTEM SHALL MEET ALL

AUDIBILITY CRITERIA AS REQUIRED BY NFPA 72.

11. ALL HORNS, WHEN WALL MOUNTED, SHALL HAVE THEIR

TOPS AT HEIGHTS NOT LESS THAN 90" ABOVE FINISHED

FLOOR AND BELOW THE FINISHED CEILINGS AT DISTANCES

OF NOT LESS THE 6".

12. PROVIDE SYNCHRONIZATION OF VISUAL NOTIFICATION

APPLIANCE CIRCUITS WHERE MORE THAN TWO DEVICES

ARE IN ANY FIELD OF VIEW.

13. THE INDICATED INTENSITIES FOR THE VISUAL

NOTIFICATION APPLIANCES REFLECT THE EFFECTIVE

INTENSITIES REQUIRED. PROVIDE VISUAL NOTIFICATION

APPLIANCE DISTANCE CALCULATIONS IF THE INSTALLED

NOTIFICATION APPLIANCES DEVIATE FROM THE DESIGN

DOCUMENTS.

14. WHERE CEILING-MOUNT HORN/STROBES ARE SHOWN,

THEY SHALL BE SUSPENDED SO THAT THE LENS IS NOT

MORE THAN 30 FT ABOVE FINISHED FLOOR PER NFPA

72:18.5.5.4.6.

15. ALL STROBE AND COMBINATION HORN/STROBE, WHEN

WALL MOUNTED, SHALL BE LOCATED SUCH THAT THE

ENTIRE LENS IS NOT LESS THAN 80" AND NOT GREATER

THAN 96" ABOVE THE FINISHED FLOOR.

16. MOUNT SMOKE DETECTORS ON THE BOTTOM OF THE

CEILING / DECK (NOT ON THE BOTTOM OF STRUCTURAL

MEMBERS) AND LOCATED MORE THAN THREE FEET FROM

AIR SUPPLY DIFFUSERS, AS INDICATED IN NFPA 72.

17. PROVIDE ELECTRONIC MONITORING OF ALL

WATERFLOW, PRESSURE, AND TAMPER SWITCHES FOR THE

FIRE SUPPRESSION SYSTEMS.

18. THE OPERABLE PART OF MANUAL STATIONS SHALL NOT

BE LESS THAN 42" AND NOT MORE THAN 48" ABOVE

FINISHED FLOOR LEVEL, AND LOCATED WITHIN 60" OF THE

EXIT DOORWAY.

GENERAL NOTES

FACU

F

WF

FIRE ALARM CONTROL UNIT

FIRE ALARM LEGEND

SPD SURGE PROTECTIVE DEVICE

FIRE ALARM PULL STATION

AIM ADDRESSABLE INPUT MODULE

WATERFLOW SWITCH

VS VALVE SUPERVISORY SWITCH

s SMOKE DETECTOR - SPOT TYPE

HORN

HORN STROBE

STROBE - WALL MOUNT

STROBE - CEILING MOUNT

SYMBOL MODIFIERS

C ncd

WP

CEILING MOUNTED

CANDELA RATING

WEATHER PROOF

s SMOKE DETECTOR / SENSOR FOR DUCT

REMOTE ALARM INDICATING AND TEST SWITCHRTS

FIRST FLOOR

FACU

SPD

s F AIM

WF

AIM

VS

120VAC DEDICATED

BRANCH CIRCUIT

62.5 MICRON MULTI-MODE FIBER OPTIC CABLE SHALL PROVIDE

FIRE ALARM CONNECTIVITY TO EXISTING CAMPUS RING

CONFIGURATION. TWO (2) FIBER OPTICAL CABLES CONSISTING

OF 4-STRAND OM1 FIBER UTILIZING ST CONNECTORS.

11 ALL OTHER TROUBLES • • • •

A B C D E F G H I J K L M

2 WATERFLOW SWITCH • • • • • • •

3 SMOKE DETECTOR • • • • • •

• PERFORM OPERATION/REPORT DEVICE STATUS

SUPERVISORY SIGNALS A B C D E F G H I J K L M

4 VALVE TAMPER SWITCH • • • •

TROUBLE CONDITIONS A B C D E F G H I J K L M

6 FIRE ALARM CONTROL PANEL AC POWER FAILURE • • • •

7 FIRE ALARM CONTROL PANEL LOW BATTERY • • • •

8 OPEN CIRCUIT • • • •

9 GROUND FAULT • • • •

10 NOTIFICATION APPLIANCE CIRCUIT SHORTED • • • •

SYSTEM OUTPUTS

TR

AN

SM

IT

F

IR

E

SU

PE

R

VI

SO

R Y

SI

G

N

AL

T O

S U

PE

R

VI

SI

N G

S

TA

TI

O

N

SYSTEM INPUTS C

O

N

TR

O L

U N

IT

A

N N

U N

C

IA

TI

O

N

AC

TU

AT

E

C O

M M

O N

A

LA

R M

S

IG

N

AL

IN

D

IC

AT

O R

AC

TU

AT

E

AU

D

IB

LE

A

LA

R M

S

IG

N

AL

AC

TU

AT

E

C O

M M

O N

S U

PE

R

VI

SO

R Y

SI

G

N

AL

IN

D

IC

AT

O R

AC

TU

AT

E

AU

D

IB

LE

S U

PE

R

VI

SO

R Y

SI

G

N

AL

AC

TU

AT

E

C O

M M

O N

T R

O U

BL

E

SI

G

N

AL

IN

D

IC

AT

O R

AC

TU

AT

E

AU

D

IB

LE

T R

O U

BL

E

SI

G

N

AL

N O

TI

FI

C

AT

IO

N

AC

TU

AT

E

AU

D

IB

LE

N O

TI

FI

C

AT

IO

N

A

PP

LI

AN

C

ES

AC

TU

AT

E

VI

SI

BL

E

N O

TI

FI

C

AT

IO

N

A

PP

LI

AN

C

ES

D

IS

PL

AY

/P R

IN

T

C H

AN

G

E O

F

ST

AT

U

S

TR

AN

SM

IT

F

IR

E

AL

AR

M

S

IG

N

AL

T O

S U

PE

R

VI

SI

N G

S

TA

TI

O

N

TR

AN

SM

IT

F

IR

E

TR

O U

BL

E

SI

G

N

AL

T O

S U

PE

R

VI

SI

N G

S

TA

TI

O

N

R

EQ

U

IR

ED

S

AF

ET

Y C

O N

TR

O

LS

SH

U

TD

O

W N

(H

VL

S) F

AN

/A

R U

FIRE ALARMS A B C D E F G H I J K L M

1 MANUAL PULL STATION • • • • • •

5 DUCT DETECTOR • •• •

SH

U

TD

O

W N

A

SS

O C

IA

TE

D H

VA

C

U N

IT

N

N

N

N

HORN HORN/STROBE

SUPPLY AIR DIFFUSER OR

RETURN AIR OPENING

SMOKE DETECTOR

SMOKE

DETECTORS

TO

O

PE

R

AB

LE

P

AR

T

5' MAX.

BO

TT

O M

O F

LE

N

S

" M

IN

TO

P

O F

LE

N

S

" M

AX

TO

P

O F

D

EV

IC

E

" M

IN

TO

P

O F

D

EV

IC

E

6" M

IN

36" MIN.

4" M

IN

" M

AX

4" MIN.

MANUAL PULL

STATION

FACU

Poole Fire Protection 19910 West 161st Street

Olathe, KS 66062

913.829.8650 office 913.829.8690 fax www.poolefire.com

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

on e-ei gh th in ch o ne fo ot on e-qu ar te r i nc h on e fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e-ha lf in ch es o ne fo ot th re e in ch es o ne fo ot

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

STRUCTURAL / CIVIL ENGINEER

F

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

SHEET TITLE

ARCHITECT

MECHANICAL / ELECTRICAL / PLUMBING /

TECHNICAL ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100 FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

R1 - CONSTRUCT REPLACEMENT

WAREHOUSE

FIRE ALARM GENERAL NOTES,

LEGEND, AND DIAGRAMS

01/06/2020 DBN SAB

500 AZ-89, PRESCOTT, AZ 86301

165-FA001

649-414

BID DOCUMENTS

N.T.S.1 FIRE ALARM RISER DIAGRAM

N.T.S.3 FIRE ALARM INPUT/OUTPUT MATRIX

N.T.S.2 FIRE ALARM DEVICE MOUNTING DETAILS

Revision # Date 51 OF 92

F

E

D

C

B

A

1 2 3 4 5

HAC

IT ROOM

WAREHOUSE

WALK-IN

REF.

STORAGE

(FLAM.)

STORAGE

(SHRED)

WRAPPING

UNISEX

TOILET

STORAGE

(AMMUNITION)

RECYCLING

AREA

MECHANICAL

PLOTTING

UNISEX

TOILET

111118

WORKSPACE

SV

OFFICE

C O

R R

ID

O

R

CORRIDOR

SECURE

STOR.

ELECTRICAL

BREAK

ROOM

REQUIRED AUDIBILITY LEGEND

30dB AMBIENT SPL 45dB EXPECTED SPL 54dB AMBIENT SPL 69dB EXPECTED SPL 91dB AMBIENT SPL 106dB EXPECTED SPL

Poole Fire Protection 19910 West 161st Street

Olathe, KS 66062

913.829.8650 office 913.829.8690 fax www.poolefire.com

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

on e-ei gh th in ch o ne fo ot on e-qu ar te r i nc h on e fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e-ha lf in ch es o ne fo ot th re e in ch es o ne fo ot

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

STRUCTURAL / CIVIL ENGINEER

F

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

SHEET TITLE

ARCHITECT

MECHANICAL / ELECTRICAL / PLUMBING /

TECHNICAL ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100 FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

R1 - CONSTRUCT REPLACEMENT

WAREHOUSE

FIRST FLOOR FIRE ALARM

AUDIBILITY PLAN

01/06/2020 DBN SAB

500 AZ-89, PRESCOTT, AZ 86301

165-FA101

649-414

BID DOCUMENTS

1/8" = 1'-0"1 FIRST FLOOR FIRE ALARM AUDIBILITY PLAN N

AUDIBILITY DESIGN

1. BECAUSE OF UNPREDICTABLE BACKGROUND NOISES AND

PROJECT CONDITIONS, THE AUDIBILITY DESIGN GOALS SHALL

BE CONFIRMED BY MEASUREMENT WITH CALIBRATED TEST

EQUIPMENT. IF RESULTS INDICATE THAT ADDITIONAL

NOTIFICATION APPLIANCES ARE REQUIRED, THE CONTRACTOR

SHALL ADD THEM AT NO ADDITIONAL COST.

2. THE EXPECTED AMBIENT SOUND LEVELS ARE INDICATED ON

PLANS.

Revision # Date 52 OF 92

F

WP

15cd cd cd cd cd cd cd

15cd

C

15cd

C15cd

15cd

C

30cd

30cd cd

15cd

30cd

F30cd

W P cd

FACU

s

VSVSWF

s

F

E

D

C

B

A

1 2 3 4 5

HAC

IT ROOM

WAREHOUSE

WALK-IN

REF.

STORAGE

(FLAM.)

STORAGE

(SHRED)

WRAPPING

UNISEX

TOILET

STORAGE

(AMMUNITION)

RECYCLING

AREA

MECHANICAL

PLOTTING

UNISEX

TOILET

WORKSPACE

SV

OFFICE

C O

R R

ID

O

R

CORRIDOR

SECURE

STOR.

ELECTRICAL

BREAK

ROOM

FACU

F

WF

FIRE ALARM CONTROL UNIT

FIRE ALARM LEGEND

SPD SURGE PROTECTIVE DEVICE

FIRE ALARM PULL STATION

AIM ADDRESSABLE INPUT MODULE

WATERFLOW SWITCH

VS VALVE SUPERVISORY SWITCH

s SMOKE DETECTOR - SPOT TYPE

HORN

HORN STROBE

STROBE - WALL MOUNT

STROBE - CEILING MOUNT

SYMBOL MODIFIERS

C ncd

WP

CEILING MOUNTED

CANDELA RATING

WEATHER PROOF

s SMOKE DETECTOR / SENSOR FOR DUCT

REMOTE ALARM INDICATING AND TEST SWITCHRTS

Poole Fire Protection 19910 West 161st Street

Olathe, KS 66062

913.829.8650 office 913.829.8690 fax www.poolefire.com

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

on e-ei gh th in ch o ne fo ot on e-qu ar te r i nc h on e fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e-ha lf in ch es o ne fo ot th re e in ch es o ne fo ot

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

STRUCTURAL / CIVIL ENGINEER

F

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

SHEET TITLE

ARCHITECT

MECHANICAL / ELECTRICAL / PLUMBING /

TECHNICAL ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100 FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

R1 - CONSTRUCT REPLACEMENT

WAREHOUSE

FIRST FLOOR FIRE ALARM PLAN

01/06/2020 DBN SAB

500 AZ-89, PRESCOTT, AZ 86301

165-FA102

649-414

BID DOCUMENTS

1/8" = 1'-0"1 FIRST FLOOR FIRE ALARM PLAN N

Revision # Date 53 OF 92

1. THE DESIGN AND INSTALLATION OF THE FIRE PROTECTION,

FIRE SUPPRESSION SYSTEM MUST BE IN ACCORDANCE WITH

U.S. DEPARTMENT OF VETERANS AFFAIRS FIRE PROTECTION

DESIGN MANUAL, SEVENTH EDITION, DECEMBER 2015; NFPA

13: STANDARD FOR THE INSTALLATION OF SPRINKLER

SYSTEMS, 2019 EDITION; NFPA 24: STANDARD FOR THE

INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND THEIR

APPURTENANCES, 2019 EDITION, AND NFPA 291:

RECOMMENDED PRACTICE FOR FIRE FLOW TESTING AND

MARKING OF HYDRANTS, 2019 EDITION.

2. THESE DRAWINGS ARE DIAGRAMMATIC AND CONCEPTUAL

IN NATURE, INTENDED TO CONVEY THE SCOPE OF WORK AND

GENERAL ARRANGEMENTS OF THE SYSTEM. COORDINATE

THE SYSTEM LAYOUT WITH ALL OTHER DISCIPLINES. ALL

CHANGES SHALL MEET THE DESIGN CRITERIA OUTLINED ON

THESE PLANS, MEET THE CRITERIA OF NFPA 13, THE

SPECIFICATIONS, AND BE DOCUMENTED ON THE AS-BUILT

PLANS.

3. SPRINKLER CONTRACTOR SHALL COORDINATE LOCATIONS

OF FIRE PROTECTION COMPONENTS INCLUDING PIPING,

ALARMS, DRAINS, SPRINKLERS, TEST POINTS, ETC., WITH ALL

ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND

ELECTRICAL COMPONENTS. OBSTRUCTIONS TO SPRINKLER

DISCHARGE SHALL BE CONSIDERED DURING INSTALLATION.

DO NOT INSTALL SPRINKLER PIPING BELOW EQUIPMENT OR

WITHIN CLEARANCE SPACES FOR MECHANICAL AND

ELECTRICAL EQUIPMENT. SPRINKLERS SHALL BE INSTALLED

UNDER OBSTRUCTIONS IN ACCORDANCE WITH NFPA 13.

4. MATERIALS AND ACCESSORIES NECESSARY MUST BE

INSTALLED IN ACCORDANCE WITH THE APPLICABLE NFPA

CODES AND STANDARDS, PROJECT SPECIFICATIONS, AND BE

UL LISTED OR FM APPROVED FOR FIRE PROTECTION USE,

UNLESS OTHERWISE NOTED.

5. ALL VALVES INSIDE TO BE PROVIDED WITH ELECTRONIC

TAMPER SWITCHES WIRED TO THE FACU. VALVES IN NORMAL

CLOSED POSITION SHALL BE PROVIDED WITH TAMPER TO

ACTIVATE IN THREE TURNS OR LESS. ALL VALVES OUTSIDE

TO BE SUPERVISED WITH LOCK AND CHAIN.

6. ALL HANGERS MUST BE PROVIDED AND INSTALLED IN

ACCORDANCE WITH NFPA 13.

7. THE INSPECTOR'S TEST VALVES MUST BE LOCATED NO

MORE THAN 7 FEET AFF.

8. APPLICABLE UL CONSTRUCTION DETAILS AND SYSTEMS

SHALL BE USED WHERE FIRE RATED BARRIERS ARE

PENETRATED BY SPRINKLER PIPING.

9. ALL VALVES (DRAINS, INSPECTOR'S TEST, CONTROL) MUST

BE IDENTIFIED AS REQUIRED BY NFPA 13.

10. PIPING MUST BE ARRANGED FOR FLUSHING. READILY

REMOVABLE FITTINGS MUST BE PROVIDED AT THE END OF

ALL CROSS MAINS.

11. ALL PENDENT SPRINKLERS MUST BE INSTALLED IN THE

CENTER OF THE CEILING TILES.

12. DRAINS MUST BE LOCATED TO PROVIDE DRAINAGE IN

ACCORDANCE WITH NFPA 13 (2016 EDITION). ALL DRAINS AND

TEST CONNECTIONS MUST DISCHARGE TO THE EXTERIOR OF

THE BUILDING ON TO A SPLASH BLOCK OR PAVEMENT, AND

SHALL NOT DISCHARGE ACROSS PATHS OF EGRESS.

13. ALL SPRINKLER SYSTEM ALARM INITIATING AND

SUPERVISORY DEVICES MUST BE CONNECTED TO THE FIRE

ALARM SYSTEM.

14. ADDITIONAL SPRINKLERS MAY BE REQUIRED UNDER DUCT

WORK TO PROVIDE ADEQUATE COVERAGE PER NFPA 13.

15. A LISTED RELIEF VALVE MUST BE PROVIDED IN

ACCORDANCE WITH NFPA 13, SECTION 8.1.2 FOR THE

SPRINKLER SYSTEM.

16. AN AIR VENT MUST BE PROVIDED IN ACCORDANCE WITH

NFPA 13, SECTION 8.1.5 AND SECTION 16.7 FOR THE

SPRINKLER SYSTEM.

17. THE AIR ROTATION UNIT (ARU) SHALL BE CENTERED

APPROXIMATELY BETWEEN FOUR ADJACENT SPRINKLERS.

THE AIR ROTATION UNIT (ARU) SHALL BE INTERLOCKED TO

SHUT DOWN IMMEDIATELY UPON A WATERFLOW ALARM IN

ACCORDANCE WITH NFPA 13, SECTION 19.2.7.

18. THE SEISMIC DESIGN CATEGORY FOR THE FACILITY IS C

AND PER H-18-8 VA SEISMIC DESIGN REQUIREMENTS,

PRESCOTT (VAMC) IS ASSIGNED WITH A Ss (SPECTRAL

RESPONSE ACCELERATION) OF 0.304, A S1 (ONE SECOND

PERIOD SPECTRAL ACCELERATION) OF 0.088 AND SEISMICITY

OF MEDIUM LOW. PROVIDE SEISMIC BRACING IN

ACCORDANCE WITH NFPA 13.

19. PROVIDE CLEARANCE AROUND ALL PIPING EXTENDING

THROUGH WALLS AND FLOORS IN ACCORDANCE WITH NFPA

13, SECTION 18.4.

20. ALL SEISMIC BRACING SHALL BE DESIGNED AND

SUBMITTED FOR APPROVAL WITH THE SHOP DRAWING

SUBMITTAL, INCLUDING DRAWINGS AND CALCULATIONS.

FIRE SUPPRESSION GENERAL NOTES

WATER FLOW

SWITCH

PRESSURE

GAUGE

INSPECTOR'S TEST AND

DRAIN VALVE WITH RELIEF

VALVE DISCHARGE TO

EXTERIOR OF BUILDING

PIPE OUT TO FIRE

DEPARTMENT CONNECTION

WITH BALL-DRIP VALVE AT

ELBOW

BUTTERFLY VALVE

(NORMALLY CLOSED)

CHECK VALVE

BACKFLOW PREVENTION

ASSEMBLY

PROVIDE CLEARANCE AROUND THE PIPE IN

ACCORDANCE WITH NFPA 13, SECTION 18.4

PROVIDE RESTRAINT FOR THE

UNDERGROUND FITTINGS IN ACCORDANCE

WITH NFPA 13, SECTION 6.6. PROVIDE ONE

FOOT OF CLEARANCE FROM THE BOTTOM OF

THE FOOTING TO THE TOP OF THE SUPPLY

PIPE AND NO FITTINGS BENEATH FOOTINGS

OR FOUNDATION IN ACCORDANCE WITH NFPA

13, SECTION 6.4.3.

2" PIPE CONNECTION FOR

DOMESTIC WATER SUPPLY

6" LEAD-IN

Poole Fire Protection 19910 West 161st Street

Olathe, KS 66062

913.829.8650 office 913.829.8690 fax www.poolefire.com

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

on e-ei gh th in ch o ne fo ot on e-qu ar te r i nc h on e fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e-ha lf in ch es o ne fo ot th re e in ch es o ne fo ot

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

STRUCTURAL / CIVIL ENGINEER

F

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

SHEET TITLE

ARCHITECT

MECHANICAL / ELECTRICAL / PLUMBING /

TECHNICAL ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100 FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

R1 - CONSTRUCT REPLACEMENT

WAREHOUSE

FIRE SUPPRESSION GENERAL

NOTES AND SECTION

01/06/2020 DBN DRF

500 AZ-89, PRESCOTT, AZ 86301

165-FX001

649-414

BID DOCUMENTS

1/2" = 1'-0"1 FIRE SUPPRESSION RISER SECTION

Revision # Date 54 OF 92

HAC

IT ROOM

WAREHOUSE

WALK-IN

REF.

STORAGE

(FLAM.)

STORAGE

(SHRED)

WRAPPING

UNISEX

TOILET

STORAGE

(AMMUNITION)

116117

RECYCLING

AREA

MECHANICAL

AREA TO BE

PROTECTED BY DRY

TYPE SPRINKLERS

FIRE SUPPRESSION

RISER

FIRE DEPARTMENT

CONNECTION

SEE CIVIL DRAWINGS FOR

CONTINUATION

BACKFLOW PREVENTION

ASSEMBLY FORWARD

FLOW TEST CONNECTION

WITH HOSE VALVES

PLOTTING

FX001

SPRINKLER SYSTEM

SUPPLY PIPE

LOCAL WATERFLOW

ALARM (HORN/STROBE) TO

BE PROVIDED BY

SPRINKLER CONTRACTOR

UNISEX

TOILET

111118

WORKSPACE

F

E

D

C

B

A

1 2 3 4 5

SV

OFFICE

C O

R R

ID

O

R

CORRIDOR

SECURE

STOR.

ELECTRICAL

BREAK

ROOM

W P cd

HAZARD CLASSIFICATION LEGEND

LIGHT HAZARD

(0.10 GPM/FT² OVER 1,500 FT² WITH

100 GPM EXTERIOR HOSE DEMAND)

ORDINARY HAZARD GROUP 2

(0.20 GPM/FT² OVER 2,500 FT² WITH

250 GPM EXTERIOR HOSE DEMAND)

STORAGE HAZARD

(ESFR SPRINKLERS WITH 250 GPM EXTERIOR HOSE

DEMAND, CLASS IV, 30 FT MAXIMUM STORAGE)

ORDINARY HAZARD GROUP 1

(0.15 GPM/FT² OVER 2,500 FT² WITH

250 GPM EXTERIOR HOSE DEMAND)

N

Poole Fire Protection 19910 West 161st Street

Olathe, KS 66062

913.829.8650 office 913.829.8690 fax www.poolefire.com

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

on e-ei gh th in ch o ne fo ot on e-qu ar te r i nc h on e fo ot th re e-ei gh th s in ch o ne fo ot on e-ha lf in ch o ne fo ot th re e-qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e-ha lf in ch es o ne fo ot th re e in ch es o ne fo ot

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

STRUCTURAL / CIVIL ENGINEER

F

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

SHEET TITLE

ARCHITECT

MECHANICAL / ELECTRICAL / PLUMBING /

TECHNICAL ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100 FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

R1 - CONSTRUCT REPLACEMENT

WAREHOUSE

FIRE SUPPRESSION HAZARD

CLASSIFICATION FIRST FLOOR

PLAN

01/06/2020 DBN DRF

500 AZ-89, PRESCOTT, AZ 86301

165-FX101

649-414

BID DOCUMENTS

1/8" = 1'-0"1 FIRST FLOOR FIRE SUPPRESSION PLAN

NOTES:

1. THE SPRINKLER SYSTEM DESIGN CRITERIA SHALL BE BASED

UPON NFPA 13, TABLE 23.5.1, USING ESFR SPRINKLERS WITH

MAXIMUM STORAGE HEIGHT OF 30 FEET, MAXIMUM CEILING

HEIGHT OF 40 FEET, WITH 25.2 K-FACTOR SPRINKLERS AT

MINIMUM OPERATING PRESSURE OF 25 PSI.

2. THE ESFR SPRINKLER SYSTEM DESIGN AND INSTALLATION

SHALL BE IN ACCORDANCE WITH NFPA 13, SECTION 14.2.11 IN

REGARDS TO OBSTRUCTIONS TO SPRINKLER DISCHARGE.

Revision # Date 55 OF 92