Attachment 8 - G Drawings.pdf
PDF 7 MB Posted
- Attached to
- Y1GZ--Construct Replacement Warehouse Prescott VAMC (Minor Construction) Federal contract opportunity
- Solicitation number
- 36E77620R0043
About this file
This notice provides details for an anticipated solicitation for a Design-Bid-Build contract to construct a replacement warehouse at the Northern Arizona VA Health Care System in Prescott, Arizona. The project involves constructing a new approximately 10,930 square foot warehouse to replace existing 1908-era buildings and provide storage, loading, and office space. The solicitation will be a Request for Proposal conducted according to FAR Parts 15, 19, and 36 and evaluated using Lowest Price Technically Acceptable procedures. It will be set aside for Service-Disabled Veteran-Owned Small Businesses and issued on or about July 27, 2020, with a performance period of approximately 360 calendar days. The construction value is estimated between $5-10 million. Questions must be submitted in writing by the specified date.
View the file
Other files for this federal contract opportunity
Show all 43
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DRAWING NUMBER
VA PROJECT NUMBER
DATE
PROJECT TITLE
BUILDING NUMBER
PROJECT LOCATION
CHECKED BY DRAWN BY
APPROVED: PROJECT DIRECTOR
VA FORM 08-6231
Office of Construction and Facilities Management
Dwg.
CONSULTANT INFORMATION
STRUCTURAL / CIVIL ENGINEER
F
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
SHEET TITLE
ARCHITECT
NORTHERN ARIZONA VA HEALTH CARE SYSTEM
MECH. / ELEC. / PLUMB. / TECH. ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FULLY SPRINKLERED
PROJECT PHASE
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
U.S. Department of Veteran Affairs
F
E
D
C
B
A
E
D
C
B
A
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 W. 161ST STREET
OLATHE, KS 66062
(913) 829-8650
COMMISSIONING
GLHN ARCHITECTS & ENGINEERS, INC.
2939 E. BROADWAY BLVD
TUCSON, AZ 85716
(520) 881-4546
R1 - CONSTRUCT REPLACEMENT
WAREHOUSE
COVER SHEET
01/06/2020 RWG ZDL
500 AZ-89, PRESCOTT, AZ 86301
500 AZ-89, PRESCOTT, AZ 86301
BID DOCUMENTS
R1 - CONSTRUCT REPLACEMENT WAREHOUSE
165-G-000
649-414
VA PROJECT NUMBER: 649-414
BID DOCUMENTS
EXTERIOR PERSPECTIVE
LOCATION PLAN
SHEET INDEX
SHEET SEQUENCE SHEET NUMBER SHEET NAME
[06] PLUMBING
56 165 P-000 PLUMBING LEGEND
57 165 PL-101 PLUMBING WASTE LEVEL 1 FLOOR PLAN
58 165 PL-102 PLUMBING WASTE ROOF PLAN
59 165 PP-101 PLUMBING SUPPLY LEVEL 1 FLOOR PLAN
60 165 P-301 PLUMBING RISER DIAGRAMS
61 165 P-302 PLUMBING RISER DIAGRAMS
62 165 P-501 PLUMBING DETAILS
63 165 P-601 PLUMBING SCHEDULES
[07] MECHANICAL
64 165 MG-000 MECHANICAL LEGEND
65 165 MH-101 MECHANICAL HVAC PLAN - LEVEL 1 FLOOR PLAN
66 165 MH-102 MECHANICAL HVAC PLAN - ROOF PLAN
67 165 M-301 MECHANICAL SECTIONS & ENLARGED PLANS
68 165 M-501 MECHANICAL DETAILS
69 165 M-601 MECHANICAL SCHEDULES
70 165 M-701 MECHANICAL CONTROLS
71 165 M-702 MECHANICAL CONTROLS
72 165 M-703 MECHANICAL CONTROLS
[08] ELECTRICAL
73 165 E-000 ELECTRICAL LEGEND
74 165 ES-101 ELECTRICAL SITE PLAN
75 165 EL-101 ELECTRICAL LIGHTING FIRST FLOOR PLAN
76 165 EP-101 ELECTRICAL POWER FIRST FLOOR PLAN
77 165 EP-103 ELECTRICAL ROOF PLAN
78 165 E-501 ELECTRICAL DETAILS
79 165 E-502 ELECTRICAL DETAILS
80 165 E-601 ELECTRICAL ONE-LINE DIAGRAM
81 165 E-602 ELECTRICAL SCHEDULES
82 165 E-603 ELECTRICAL SCHEDULES
[09] TECHNOLOGY
83 165 T-000 TECHNOLOGY LEGEND
84 165 TS-101 TECHNOLOGY SITE PLAN
85 165 TI-101 INTERCOM AND PUBLIC ADDRESS FIRST FLOOR PLAN
86 165 TN-101 COMMUNICATIONS FIRST FLOOR PLAN
87 165 TY-101 SECURITY FIRST FLOOR PLAN
88 165 T-401 TECHNOLOGY PARTIAL FLOOR PLANS
89 165 T-501 TECHNOLOGY DETAILS
90 165 T-502 TECHNOLOGY DETAILS
91 165 T-601 TECHNOLOGY RISER DIAGRAMS
92 165 T-602 TECHNOLOGY SCHEDULES
TOTAL SHEETS: 92
SHEET INDEX
SHEET SEQUENCE SHEET NUMBER SHEET NAME
[03] STRUCTURAL
26 165 SA-001 STRUCTURAL GENERAL NOTES
27 165 SA-010 SPECIAL INSPECTIONS
28 165 SA-030 TYPICAL DETAILS - CONCRETE
29 165 SA-031 TYPICAL DETAILS - CONCRETE
30 165 SB-101 FOUNDATION PLAN
31 165 SB-501 FOUNDATION DETAILS
32 165 SF-102 ROOF FRAMING PLAN
33 165 SF-201 FRAMING ELEVATIONS
34 165 SS-101 RAMPS AND STAIRS
35 165 SS-501 SITE FOUNDATION DETAILS
[04] ARCHITECTURE
36 165 AS-101 ARCHITECTURAL FLOOR PLAN
37 165 AS-111 REFLECTED CEILING PLAN
38 165 AS-121 ROOF PLAN
39 165 AS-201 BUILDING ELEVATIONS
40 165 AS-202 BUILDING ELEVATIONS
41 165 AS-301 BUILDING SECTIONS
42 165 AS-311 WALL SECTIONS
43 165 AS-401 PLAN DETAILS
44 165 AS-411 SECTION DETAILS
45 165 AS-501 DOOR, GLAZING & LOUVER SCHEDULE & DETAILS
46 165 AS-601 MILLWORK DETAILS
47 165 AS-701 FINISH FLOOR PLAN
48 165 AS-702 FF&E FLOOR PLAN, ENLARGED PLANS & INTERIOR ELEVATIONS
49 165 AS-710 INTERIOR SIGNAGE
50 165 AS-711 EXTERIOR SIGNAGE
[05] FIRE PROTECTION
51 165 FA-001 FIRE ALARM GENERAL NOTES, LEGEND, AND DIAGRAMS
52 165 FA-101 FIRST FLOOR FIRE ALARM AUDIBILITY PLAN
53 165 FA-102 FIRST FLOOR FIRE ALARM PLAN
54 165 FX-001 FIRE SUPPRESSION GENERAL NOTES AND SECTION
55 165 FX-101 FIRE SUPPRESSION HAZARD CLASSIFICATION FIRST FLOOR PLAN
SHEET INDEX
SHEET SEQUENCE SHEET NUMBER SHEET NAME
[01] GENERAL
1 165 G-000 COVER SHEET
2 165 G-001 GENERAL INFORMATION
3 165 G-002 ARCHITECTURAL SITE PLAN
4 165 G-010 PARTITION TYPES
5 165 G-100 LIFE SAFETY PLAN - CODE PLAN NARRATIVE
6 165 G-101 LIFE SAFETY PLAN
[02] CIVIL
7 165 VA-000 TOPOGRAPHIC SURVEY
8 165 CD-100 DEMOLITION LAYOUT
9 165 CS-100 SITE LAYOUT
10 165 CS-101 DIMENSIONED SITE LAYOUT
11 165 CS-102 SITE LAYOUT DETAILS
12 165 CG-100 DRAINAGE AREA MAP LAYOUT
13 165 CG-101 GRADING LAYOUT
14 165 CG-102 GRADING DETAILS
15 165 CG-103 STORM WATER POLLUTION PREVENTION PLAN LAYOUT
16 165 CU-100 UTILITY LAYOUT
17 165 CI-001 PAVING DETAILS
18 165 CI-002 PAVING DETAILS
19 165 CI-003 STORM DETAILS
20 165 CI-004 SWPPP DETAILS
21 165 CI-005 UTILITY DETAILS
22 165 CI-006 UTILITY DETAILS
23 165 CI-007 UTILITY DETAILS
24 165 CI-008 GATE DETAILS
25 165 CI-009 GATE DETAILS
AREA PLAN
Revision # Description Date
V
F H
C O U
P
GENERAL NOTESSYMBOLS LEGEND
ARCHITECTURAL ABBREVIATIONS
AREA PLAN
PURPOSE: THE PUBLIC BUILDINGS AMENDMENT ACT OF 1988, PUBLIC LAW (PUB. L.) 100-678 REQUIRES FEDERAL AGENCIES TO FOLLOW NATIONAL RECOGNIZED "MODEL" BUILDING CODES. THE FEDERAL PARTICIPATION IN THE DEVELOPMENT AND USE OF VOLUNTARY STANDARDS, OFFICE OF MANAGEMENT AND BUDGET (OMB) CIRCULAR A-119, REQUIRES ALL EXECUTIVE AGENCIES TO RELY ON VOLUNTARY STANDARDS, BOTH DOMESTIC AND INTERNATIONAL, WHENEVER FEASIBLE, AND TO PARTICIPATE IN VOLUNTARY STANDARD
BODIES.
GENERAL: VA HAS ADOPTED THE LATEST EDITION OF THE FOLLOWING CODES AND STANDARDS AS A MINIMUM FOR ALL PROJECTS PERFORMED IN THE MODERNIZATION, ALTERATION, ADDITION, OR IMPROVEMENT OF ITS REAL PROPERTY AND THE CONSTRUCTION OF NEW STRUCTURES. VA DESIGN MANUALS AND MASTER SPECIFICATIONS SPECIFY OTHER CODES AND STANDARDS THAT VA FOLLOWS ON ITS PROJECTS:
• VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE ON THE TECHNICAL INFORMATION LIBRARY (TIL) (HTTP://WWW.CFM.VA.GOV/TIL/).
• INTERNATIONAL BUILDING CODE (IBC) (ONLY WHEN SPECIFICALLY REFERENCED IN VA DESIGN DOCUMENTS, SEE NOTES BELOW)
• NFPA 101 LIFE SAFETY CODE (SEE NOTES BELOW)
• NFPA NATIONAL FIRE CODES WITH THE EXCEPTION OF NFPA 5000 AND NFPA 900
• OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS.
• VA SEISMIC DESIGN REQUIREMENTS, H-18-8
• NATIONAL ELECTRICAL CODE (NEC)
• INTERNATIONAL PLUMBING CODE (IPC)
• SAFETY CODE FOR ELEVATORS AND ESCALATORS, AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME) A 17.1.
• ASME BOILER AND PRESSURE VESSEL CODE
• ASME CODE FOR PRESSURE PIPING
• ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS) INCLUDING VA SUPPLEMENT, BARRIER FREE DESIGN GUIDE (PG-18-13)
• BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE, AMERICAN CONCRETE INSTITUTE AND COMMENTARY (ACI 318) MANUAL OF STEEL CONSTRUCTION, LOAD AND RESISTANCE FACTOR DESIGN SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS, AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
• ENERGY POLICY ACT OF 2005 (EPACT)
• DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS FOR NEW FEDERAL, COMMERCIAL AND MULTI-FAMILY HIGH-RISE RESIDENTIAL BUILDINGS AND NEW LOW-RISE RESIDENTIAL BUILDINGS, 10 CFR PARTS 433, 434 AND 435.
• FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS: MEMORANDUM OF UNDERSTANDING (MOU)
• EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL ENVIRONMENTAL, ENERGY, AND TRANSPORTATION MANAGEMENT.
• THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE GENERAL REQUIREMENTS SECTION 01010 OF THE VA MASTER CONSTRUCTION SPECIFICATION.
• VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY – ASHRAE STANDARD 62.1- 2004.
• SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE STANDARD 15 – 2007.
LOCAL CODES: AS AN AGENCY OF THE FEDERAL GOVERNMENT, VA IS NOT SUBJECT TO LOCAL IMPOSITION OF CODE ENFORCEMENT PROCEDURES (DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS, FEES, ETC.). VA MUST FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ) AND THUS HAS THE RESPONSIBILITY TO GUARD PUBLIC HEALTH AND SAFETY THROUGH ENFORCING ITS ADOPTED CODES. HOWEVER, LOCAL AUTHORITIES SHOULD BE NOTIFIED ABOUT PLANNED PROJECTS AND GIVEN OPPORTUNITY TO REVIEW
DRAWINGS PROVIDED THAT VA DOES NOT PAY FOR REVIEW OR INSPECTION FEES.
NOTES:
1. NFPA 101 PRIMARILY ADDRESSES LIFE SAFETY AND FIRE PROTECTION FEATURES WHILE THE IBC ADDRESSES A WIDE RANGE OF CONSIDERATIONS, INCLUDING, BUT NOT LIMITED TO, STRUCTURAL STRENGTH, SEISMIC STABILITY, SANITATION, ADEQUATE LIGHT AND VENTILATION, AND ENERGY CONSERVATION. VA BUILDINGS MUST MEET THE REQUIREMENTS OF NFPA 101 AND DOCUMENTS REFERENCED BY NFPA 101 IN ORDER TO COMPLY WITH THE ACCREDITATION REQUIREMENTS OF THE JOINT COMMISSION. THEREFORE, DESIGNS SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF NFPA 101 AND DOCUMENTS REFERENCED THEREIN. DESIGN FEATURES NOT ADDRESSED BY NFPA 101 OR DOCUMENTS REFERENCED THEREIN SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE IBC OR AS OTHERWISE ADDRESSED ABOVE IN THIS PROGRAM GUIDE. FOR DESIGN FEATURES THAT ARE ADDRESSED BY BOTH THE IBC AS WELL AS NFPA 101 OR A DOCUMENT REFERENCED BY NFPA 101, THE REQUIREMENTS OF NFPA 101 OR THE DOCUMENT REFERENCED BY NFPA 101 SHALL BE USED EXCLUSIVELY (THIS APPLIES EVEN IF THE IBC REQUIREMENTS ARE DIFFERENT).
2. CONFLICTS BETWEEN NATIONALLY RECOGNIZED CODES AND STANDARDS AND VA REQUIREMENTS – SHOULD A CONFLICT EXIST BETWEEN VA REQUIREMENTS AND VA ADOPTED NATIONALLY RECOGNIZED CODES AND STANDARDS, THE CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF VA. THE RESOLUTION OF THE CONFLICT SHALL BE MADE BY THE AUTHORITY HAVING JURISDICTION FOR VA TO ENSURE A CONSISTENCY SYSTEM WIDE.
CODES, STANDARDS, AND EXECUTIVE ORDERS
ACS DR ACCESS DOOR
ACS PNL ACCESS PANEL
ACST ACOUSTIC
ACT ACOUSTICAL CEILING TILE
ACT (SP) ACOUSTICAL CEILING TILE (WITH SPRAYED PLASTIC FINISH)
AD AREA DRAIN
ADA AMERICANS WITH DISABILITIES
ADC AUTOMATIC DOOR CLOSER
ADH ADHESIVE
ADMIN ADMINISTRATION
ADB AUTOMATIC DOOR BOTTOM
AFC ABOVE FINISHED COUNTER
AFF ABOVE FINISHED FLOOR
ABG ABOVE FINISHED GRADE
AFS ABOVE FINISHED SLAB
ALUM ALUMINUM
AR AS REQUIRED
ASB ASBESTOS
AWT ACOUSTICAL WALL TREATMENT
BAT BATTEN
BEV BEVEL
BLKT BLANKET
BM BEAM OR BENCHMARK
BOT BOTTOM
BRG BEARING
BRG PL BEARING PLATE
BRKT BRACKET
BTWN BETWEEN
CAC CEILING ATTENUATION CLASS
CB CORNER BEAD
CBB CEMENTITIOUS BACKER BOARD
CCTV CLOSED CIRCUIT TELEVISION
C / C CONTRACTOR FURNISHED / CONTRACTOR INSTALLED
CL CENTER LINE
CMU CONCRETE MASONRY UNIT
CONT CONTINUE OR CONTINUOUS
CR CARD READER
DEMO DEMOLITION
DF DRINKING FOUNTAIN
DIA DIAMETER
ELEC ELECTRIC
EA EACH
EQ EQUAL
EQUIP EQUIPMENT
EXIST EXISTING
EXP EXPANSION OR EXPOSED
EXT EXTINGUISHER
ETR EXISTING TO REMAIN
F FEMALE
FD FLOOR DRAIN
FEC FIRE EXTINGUISHER CABINET
FF FINISH FACE
FF&E FURNITURE, FIXTURE, & EQUIPMENT
FT FEET OR FOOT
FP FIRE PROTECTION OR FIREPROOF
FR FIRE RATING, FIRE RESISTANCE, OR FRAME
FT FEET OR FOOT
FURR FURRING
FV FIELD VERIFY
OC ON CENTER
OPP OPPOSITE
PNL PANEL
PVC POLYVINYL CHLORIDE (PLASTIC)
QA QUALITY ASSURANCE
QC QUALITY CONTROL
QTY QUANTITY
QUAL QUALITY
R RADIUS OR RISER
RCP REFLECTED CEILING PLAN
RECPT RECEPTACLE
REF REFERENCE
REQD REQUIRED
REV REVISION
RM ROOM
RO ROUGH OPENING
S SEALED CONCRETE
SCHED SCHEDULE
SF SQUARE FOOT (FEET)
SIM SIMILAR
SPEC SPECIFICATION
SQ IN SQUARE INCH
SQ YD SQUARE YARD
STRUCT STRUCTURAL
STC SOUND TRANSMISSION CLASS
STD STANDARD
STOR STORAGE
ENERGY REQUIREMENTS
1. DRAWINGS ARE PART OF A COMPLETE DOCUMENTS SET. CONTRACTOR SHALL CONFIRM ALL ITEMS REQUIRED BASED UPON THE OVERALL DESIGN INTENT
OF THE ENTIRE DOCUMENT SET.
2. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING ANY WORK TO CONFIRM THE ACCURACY OF THE DRAWINGS, AND REPORT ANY DISCREPANCIES TO THE ARCHITECT. DO NOT SCALE THE DRAWINGS. FIELD VERIFY ALL DIMENSIONS AND EXISTING STRUCTURAL CONDITIONS.
3. ALL AREAS NOT INVOLVED IN THE SCOPE OF WORK FOR THIS PROJECT SHALL BE KEPT CLEAN AND FREE OF OBSTRUCTIONS AT ALL TIMES.
4. ERECT BARRICADES AND WARNING SIGNS TO DIVERT AND WARN PASSERS-BY OF THE CONSTRUCTION WORK. PROVIDE DUST PROOFING ENCLOSURES TO
SEPARATE WORK AREAS FROM THE EXISTING FACILITIES.
5. ALL TRASH AND DEBRIS TO BE REMOVED ON A DAILY BASIS.
6. PROVIDE PROTECTION FOR ALL EXISTING SURFACES AND CONDITIONS TO REMAIN IN PLACE DURING THE SCOPE OF WORK. SHOULD ANY DAMAGE OCCUR, PATCH AND REPAIR ANY DAMAGE TO ADJACENT FINISHES TO MATCH EXISTING.
7. ANY DAMAGE CAUSED TO THE BUILDING OR OWNER EQUIPMENT SHALL BE REPAIRED OR REPLACED BACK TO ITS ORIGINAL CONDITIONS AT NO ADDITIONAL
COST TO THE OWNER.
8. COVER ALL RETURN AIR GRILLES WITHIN THE AREA OF CONSTRUCTION TO PREVENT PARTICULATE MATERIAL FROM EXHAUSTING INTO SURROUNDING
SPACES.
9. APPROPRIATE LIGHT FIXTURES SHALL BE TEMPORARILY SUSPENDED TO PROVIDE ADEQUATE LIGHTING LEVELS FOR CONSTRUCTION.
10. CONTRACTOR AND SUBCONTRACTORS ARE REQUIRED TO COORDINATE WITH OTHER DISCIPLINES TO INSTALL COMPLETE AND OPERATIONAL SYSTEMS.
DRAWINGS, AS A WHOLE, REPRESENT A COMPLETE SET AND DEPICT REQUIREMENTS FOR COMPLETE AND OPERATIONAL SYSTEMS. INDIVIDUAL DRAWINGS MAY NOT DEPICT COMPLETE AND ACCURATE INFORMATION TO COORDINATE COMPLETE AND OPERATIONAL SYSTEMS, BUT DO SO AS AN ENTIRE DOCUMENT TO BE REFERENCED WITH OTHER INDIVIDUAL DRAWINGS. CONTRACTOR AND SUBCONTRACTORS ARE REQUIRED TO REFERENCE OTHER SHEETS AND SPECIFICATIONS AS AN ENTIRE SET OF CONSTRUCTION DOCUMENTS THAT REFLECT WORK REQUIRED TO ACHIEVE A COMPLETE AND OPERATIONAL GOAL. LACK OF COORDINATION AND REVIEW OF DRAWINGS AND SPECIFICATIONS AS AN ENTIRE DOCUMENT TO INSTALL COMPLETE AND OPERATIONAL SYSTEMS, BEING OBVIOUS AND TYPICAL INDUSTRY STANDARD, IDENTIFIED IN THE DRAWINGS AND SPECIFICATIONS, SHALL NOT BE IN ANY
WAY AN ADDITIONAL COST TO THE GOVERNMENT.
11. CONTRACTOR SHALL SUBMIT A REQUEST, IN WRITING, TO INTERRUPT ANY SUCH SERVICES TO COR (CONTRACTING OFFICER’S REPRESENTATIVE) 48 HOURS IN ADVANCE OF PROPOSED INTERRUPTION. REQUEST SHALL STATE REASON, DATE, EXACT TIME OF, AND APPROXIMATE DURATION OF SUCH INTERRUPTION. MAJOR INTERRUPTIONS OF ANY SYSTEM MUST BE REQUESTED, IN WRITING, AT LEAST 60 CALENDAR DAYS PRIOR TO THE DESIRED TIME AND SHALL BE PERFORMED AS DIRECTED BY THE COR. MAJOR INTERRUPTIONS SHALL BE COORDINATED WITH OTHER MAJOR INTERRUPTIONS AND MAY NOT BE SCHEDULED FOR ONE DISCIPLINE MORE THAN TWICE THROUGHOUT THE OVERALL CONSTRUCTION SCHEDULE UNLESS REQUESTED IN WRITING AND APPROVED BY THE COR. CONTRACTOR WILL BE ADVISED, IN WRITING, OF APPROVAL OF REQUEST, OR OF WHICH OTHER DATE AND/OR TIME SUCH INTERRUPTION WILL CAUSE THE LEAST INCONVENIENCE TO OPERATIONS OF THE MEDICAL CENTER. INTERRUPTION TIME APPROVED BY THE MEDICAL CENTER MAY OCCUR AT TIMES OTHER THAN CONTRACTOR'S NORMAL WORKING HOURS. SCHEDULE INTERRUPTION MAY BE ON WEEKENDS OR LATE HOURS AND MAY NOT BE AN ADDITIONAL COST TO THE GOVERNMENT. COORDINATE ALL INTERRUPTIONS THAT MAY AFFECT THE NORMAL OPERATION OF THE FACILITY WITH THE COR WHEN SUBMITTING THE CONSTRUCTION SCHEDULE OR UPDATES TO THE CONSTRUCTION SCHEDULE.
12. NO ASBESTOS CONTAINING MATERIALS ARE TO BE USED ON THIS PROJECT. SPUR DESIGN, THE A/E OF RECORD, CAN CERTIFY THAT NO ASBESTOS CONTAINING BUILDING MATERIALS (ACBM) OR LEAD BASED PAINT (LBP) PRODUCTS WERE DESIGNED/SPECIFIED AS BUILDING MATERIAL IN ANY OF THE
CONSTRUCTION DOCUMENTS.
ROOM NAME, NUMBER
AND SQUARE FEET
X'-X"
COLUMN GRID
KEYNOTE
WALL OR PARTITION TYPE
PLAN NORTH ARROW WITH TRUE NORTH
ELEVATION INDICATOR,
INTERIOR/EXTERIOR
BUILDING SECTION
INDICATOR
ELEVATION INDICATOR
BREAK, STRAIGHT (SEE SECTION INDICATORS,
BUILDING, WITH BREAK STANDARDS)
DIMENSION LINE
CENTER LINE
1 1/2"
MATCH LINE
N
1A
A
A
CORNER GUARDCG
A101
DETAIL INDICATOR
1 / A101
SIM
Room Name
150 SF
A101
SIM
A101
SIM
WINDOW TYPE
1A
DOOR CLEARANCES
FIXTURE MOUNTING HEIGHTS AND CLEARANCES
MATERIALS LEGEND
THE PROPOSAL RECEIVED FROM THE NAVAHCS CALLED FOR A NEW WAREHOUSE FACILITY TO REPLACE THE EXISTING WAREHOUSE BUILDINGS IN OPERATION SINCE 1908. THE NEW WAREHOUSE FACILITY WILL PROVIDE APPROXIMATELY 10,495 SQUARE FEET (MEASURED FROM INTERIOR FACE OF FINISH) OF CONDITIONED STORAGE SPACE ALONG WITH OFFICE AND
SUPPORT SPACES.
THE NEW WAREHOUSE HAS BEEN SITED IN AN AREA DIRECTED BY THE VA. SPECIAL CARE HAS BEEN TAKEN TO BE
SENSITIVE TO UNDERGROUND UTILITIES LOCATED IN THE AREA OF CONSTRUCTION.
THE NEW WAREHOUSE WILL PROVIDE FOR EFFICIENT LOADING, UNLOADING, AND STORAGE OF MATERIAL WHILE ALSO PROVIDING OFFICE SPACE AND SUPPORT NEEDS THAT ARE CRITICAL TO THE SUPPLY CHAIN LOGISTICS OF THE PRESCOTT VA.
THE SITE CONDITIONS WILL INCLUDE APPROXIMATELY 22,500 SQUARE FEET OF PAVING FOR TRACTOR TRAILER LOADING AND AN ADDITIONAL 2,900 SQUARE FEET OF HARDSCAPE FOR A RECYCLING STORAGE AREA, FORKLIFT RAMP, WHEELCHAIR ACCESS RAMP, AND AN ACCESSIBLE PARKING SPACE ALONG WITH A SMALL GRAVEL LOT FOR PARKING.
A SUMMARY OVERVIEW OF THE PROJECT OBJECTIVES THROUGH NEW CONSTRUCTION INCLUDES:
• HIGH BAY, CLIMATE-CONTROLLED WAREHOUSE STORAGE
• WALK-IN REFRIGERATOR, FOR PALETTIZED GOODS
• DEDICATED AREA FOR PALLET WRAPPING
• A DOCUMENT REPRODUCTION CENTER WITH SPACE FOR DOCUMENT SHREDDING
• A RECHARGING AREA FOR WAREHOUSE LIFT EQUIPMENT
• FLAMMABLE MATERIAL STORAGE
• AMMUNITION STORAGE
• RESTROOMS TO SERVE STAFF AND DELIVERY DRIVERS
PROJECT DESCRIPTION
GA GAGE
GALV GALVANIC OR GALVANIZED
GB GRAB BAR
GD GUARD
GL GLASS
GT GROUT
GWB GYPSUM WALLBOARD
HDR HARDWARE
HM HOLLOW METAL
HORIZ HORIZONTAL
HS HEAT-STRENGTHENED (GLASS)
OR HIGH STRENGTH
HT HEIGHT
IN INCH OR INCHES
KPL KICKPLATE
LAV LAVATORY
LF LINEAR FEET (FOOT)
LVR LOUVER
LF LINEAR FEET (FOOT)
MAX MAXIMUM
MIN MINIMUM
MISC MISCELLANEOUS
MTD MOUNTED
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NRC NOISE REDUCTION COEFFICIENT
T&G TONGUE AND GROOVE
THRU THROUGH
TO TOP OF
TOB TOP OF BEAM
TOM TOP OF MASONRY
TOS TOP OF STEEL
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
UTIL UTILITY
VAR VARIES
V / C VA PROVIDED / CONTRACTOR INSTALLED
V / V VA PROVIDED / VA INSTALLED
W/ WITH
W/O WITHOUT
WC WALL COVERING OR WATER CLOSET
WD WOOD
WDW WINDOW
WR WASTE RECEPTACLE
X BRACE CROSS BRACE
M A
X
M A
X
M A
X
M
IN
18" MIN
1. GENERAL CONTRACTOR TO PROVIDE METAL BLOCKING FOR ALL WALL MOUNTED ACCESSORIES, FIXTURES, AND EQUIPMENT.
2. SPECIFIED MAXIMUMS ARE MEASURED FROM AFTER FINISHED FLOOR TO THE OPERABLE PART OF THE FIXTURE.
3. FIXTURES SHOWN ARE REPRESENTATIONAL ONLY. NOT ALL FIXTURES MAY BE USED. REFER TO SPECIFICATIONS FOR FIXTURE TYPES USED IN THIS PROJECT.
4. FIXTURES MAY OVERLAP WAINSCOT. WHERE APPLICABLE, BACKING TO BE PROVIDED AS SHIM FOR FLUSH APPLICATION. SHIM TO MATCH SCHEDULED WALL FINISH.
6" MAX
9" M
IN
SHOWER
VA TURNING RADIUS BARIATRIC
TURNING RADIUS
DRINKING
FOUNTAIN
PAPER TOWEL
DISPENSER
SANITARY
NAPKIN
DISPENSER
M A
X
WASTE
RECEPTACLE
LAVATORY
WITH MIRROR
ON CENTER
WALL
M A
X
SOAP
DISPENSER
M A
X
M A
X
17 MIN
M
IN
M A
X
18" MIN
WALL
M A
X
M A
X
18" MIN
8" MIN
WALL
LAVATORY
WITH APRON
M A
X
18" MIN
URINAL
WALL
18"
CLEAR FLOOR
60"
CLEAR FLOOR
56"
36" MIN
12" 42" MIN 12"
54" MIN
M
IN
WALLWALL
M A
X
WALL HOOK
CLOCK
WALL
ø 66" ø 72"
FINISHED
FLOOR
CLEAR FLOOR SPACE AT
WATER CLOSETS
M A
X
FIRE
EXTINGUISHER
CABINET
WEIGHT > 40LBS
M A
X
FIRE
EXTINGUISHER
CABINET
WEIGHT < 40LBS
M A
X
M A
X
TOILET SEAT
COVER
DISPENSER
BABY
CHANGING
STATION
60"
CLEAR FLOOR SPACE AT
ADA DRINKING FOUNTAIN
30"
CONCRETE/ PRECAST
CONCRETE
SOIL
SAND, EIFS FINISH COAT, OR
CEMENT PLASTER
BRICK
CMU
STONE
FIBERGLASS SEMI RIGID
INSULATION
FIBERGLASS BATT INSULATION
MINERAL WOOL SEMI RIGID
INSULATION
EXPANDED POLYSTYRENE RIGID
INSULATION
EXTRUDED POLYSTYRENE RIGID
INSULATION
POLYISOCYANURATE RIGID
INSULATION
GYPSUM BOARD
EXTERIOR GYPSUM SHEATHING
EXTERIOR CEMENT BOARD
COATED GLASS MAT WATER RESISTANT GYP BD
PLYWOOD
COVER BOARD
SPRAY-APPLIED CLOSED CELL
INSULATION
ASHRAE 90.1 - 2016 EDITION
BUILDING LOCATION: PRESCOTT, ARIZONA
CLIMATE ZONE (ANNEX 1, TABLE B-1): ZONE 4B
INTERIOR DESIGN CONDITIONS:
THE INTERIOR DESIGN TEMPERATURES USED FOR HEATING AND COOLING LOAD CALCULATIONS SHALL BE THE MAXIMUM AND MINIMUM VALUES FOR THE RESPECTIVE TEMPERATURE CONTROL ZONES AS OUTLINED IN THE PROJECT DESIGN CONDITIONS
SCHEDULE ON THE MECHANICAL CONTROLS DRAWINGS.
BUILDING ENVELOPE REQUIREMENTS (TABLE 5.5-4):
OPAQUE THERMAL ENVELOPE REQUIREMENTS (TABLE 5.5-4):
ROOFS
INSULATION ENTIRELY ABOVE DECK:
METAL BUILDINGS:
ATTIC AND OTHER:
WALLS, ABOVE GRADE
MASS:
METAL BUILDING:
STEEL FRAMED:
WOOD FRAMED AND OTHER:
WALLS, BELOW GRADE
BELOW-GRADE WALL:
FLOORS
MASS:
JOIST/FRAMING:
WOOD-FRAMED AND OTHER:
SLAB-ON-GRADE
UNHEATED SLABS:
HEATED SLABS:
OPAQUE DOORS
SWINGING:
NONSWINGING:
FENESTRATION (TABLE C402.4):
VERTICAL FENESTRATION
U-FACTOR
-NON-METAL FRAMING (ALL):
-METAL FRAMING (FIXED):
-METAL FRAMING (OPERABLE):
-METAL FRAMING (ENTRANCE DOOR):
REQUIRED AS DESIGNED
R-30 c.i. R-36 c.i.
N/A N/A N/A N/A
N/A N/A R-0 + R-15.8 c.i. R-18 c.i.
N/A N/A N/A N/A
R-7.5 c.i. R-7.5 c.i.
N/A N/A N/A N/A N/A N/A
R-15 FOR 24 INCHES R-15 FOR 24 INCHES
N/A N/A
U-0.370 U-0.370 U-0.310 U-0.310
N/A N/A U-0.38 U-0.38 N/A N/A U-0.68 U-0.68
NEW
WAREHOUSE
BUILDING 112
18" MIN.
M
IN
FRONT
APPROACH,
PULL SIDE
36" MIN.
M
IN
HINGE
APPROACH,
PULL SIDE
HINGE
APPROACH,
PULL SIDE
*12" MIN.
M
IN
FRONT
APPROACH,
PUSH SIDE
*12" MIN.**
M
IN
. HINGE
APPROACH,
PUSH SIDE
22" MIN. 24" MIN.*4
8"
M
IN
LATCH
APPROACH,
PULL SIDE
24" MIN.*4
2"
M
IN
. LATCH
APPROACH,
PUSH SIDE
*IF BOTH CLOSER AND LATCH ARE PROVIDED
*54" MIN. IF CLOSER IS PROVIDED
*48" IF CLOSER IS PROVIDED*IF BOTH CLOSER AND LATCH ARE PROVIDED
**48" MIN. IF BOTH CLOSER AND LATCH PROVIDED
FRONT
APPROACH,
PUSH SIDE60
M
IN
M
IN
42" MIN.
DRAWING NUMBER
VA PROJECT NUMBER
DATE
PROJECT TITLE
BUILDING NUMBER
PROJECT LOCATION
CHECKED BY DRAWN BY
APPROVED: PROJECT DIRECTOR
o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
VA FORM 08-6231
Office of Construction and Facilities Management
Dwg.
CONSULTANT INFORMATION
STRUCTURAL / CIVIL ENGINEER
F
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
SHEET TITLE
ARCHITECT
MECH. / ELEC. / PLUMB. / TECH. ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FULLY SPRINKLERED
PROJECT PHASE
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
U.S. Department of Veteran Affairs
F
E
D
C
B
A
E
D
C
B
A
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 W. 161ST STREET
OLATHE, KS 66062
(913) 829-8650
COMMISSIONING
GLHN ARCHITECTS & ENGINEERS, INC.
2939 E. BROADWAY BLVD
TUCSON, AZ 85716
(520) 881-4546
R1 - CONSTRUCT REPLACEMENT
WAREHOUSE
GENERAL INFORMATION
01/06/2020 RWG ZDL
500 AZ-89, PRESCOTT, AZ 86301
165-G-001
649-414
BID DOCUMENTS
V
TRAILER AREATRAILER MANEUVER AREA
NEW WAREHOUSE
(10,947 FOOT PRINT SF)
EXISTING PARKING LOT TO REMAIN
DR. KENDALL WAY
(EXISTING TO REMAIN)
1/ 4"
1'
-0
1/ 4"
1'
-0
DOWNSPOUTGUTTER WITH DOWNSPOUTS,
1/4" / 1'-0" SLOPE, TYPICAL
ACCESS -CONTROLLED
ENTRY GATE
EXISTING PAVING TO REMAIN
EXISTING FENCING TO REMAIN
EXISTING PAVING TO REMAIN
EXISTING PAVING TO REMAIN
EXISTING SIDEWALK TO REMAIN
BUILDING 112
NEW FIRE HYDRANT,
RE: CIVIL
EXISTING FIRE HYDRANT
EXISTING FENCING AND GATE TO REMAIN
EXISTING CHILLING PLANT TO REMAIN
E T
R
ET
R
E T
R
E T
R
E T
R
E T
R
E T
R
ETR
ETR
E T
R
E T
R
ETR
E T
R
OPENS
CARD READER AND
INTERCOM SYSTEM,
RE: ELECTRICAL DWGS
CONDENSING UNITS AND PAD,
REFERENCE CIVIL
GRAVEL PARKING LOT
(APPROX. 5 SPACES)
11' - 0"
E T
R
CONDENSING UNIT AND PAD,
REFERENCE CIVIL
A
LL
S
ID
E S
6" T
Y P
DOWNSPOUT
CONDENSING UNIT AND PAD,
REFERENCE CIVIL
WALL-MOUNTED ROOF ACCESS LADDER
WITH GROUND ACCESS SECURITY GATE,
FALL ARREST CAGE, REST PLATFORM,
AND WALK-THROUGH
MECHANICAL EQUIPMENT,
RE: MECH. TYP.
ARCHITECTURAL SITE PLAN LEGEND
EXISTING LANDSCAPING TO REMAIN
EXISTING PAVING TO REMAIN
EXISTING BUILDING TO REMAIN
NEW PAVING, REFERENCE CIVIL DRAWINGS
NEW WAREHOUSENEW LANDSCAPING
SECURITY FENCING, REFERENCE CIVIL
EXTERIOR SITE LIGHTING, REFERENCE CIVIL, STRUCTURAL
AND ELECTRICAL DRAWINGS
EXISTING TREE TO REMAIN. RE: CIVIL FOR EXTENT OF TREE REMOVAL
EXISTING EXTERIOR SITE LIGHTING TO REMAINETR
GRAVEL PARKING LOT, REFERENCE CIVIL DRAWINGS
1 1/2" METAL HANDRAIL
& GUARDRAIL - PAINT
FINISH, TYPICAL
OF ONE TREAD
EXTEND THE DEPTH
H A
N D
R A
IL
H
E
IG
H T
, T Y
P
G U
A R
D R
A
IL
H E
IG
H
T , T
Y P
1' - 0"
TYP.
4' - 0"
TYP.
4' - 0"
METAL GUARDRAIL & HANDRAIL,
PAINT BLACK, TYPICAL
G U
A R
D R
A
IL
H E
IG
H
T , T
Y P
H A
N D
R A
IL
H
E
IG
H T
, T Y
P
H A
N D
R A
IL
H
E
IG
H T
, T Y
P
G U
A R
D R
A
IL
H E
IG
H
T , T
Y P
C
LE
A
R
1' - 0" 1' - 0"
DRAWING NUMBER
VA PROJECT NUMBER
DATE
PROJECT TITLE
BUILDING NUMBER
PROJECT LOCATION
CHECKED BY DRAWN BY
APPROVED: PROJECT DIRECTOR
o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
VA FORM 08-6231
Office of Construction and Facilities Management
Dwg.
CONSULTANT INFORMATION
STRUCTURAL / CIVIL ENGINEER
F
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
SHEET TITLE
ARCHITECT
MECH. / ELEC. / PLUMB. / TECH. ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FULLY SPRINKLERED
PROJECT PHASE
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
U.S. Department of Veteran Affairs
F
E
D
C
B
A
E
D
C
B
A
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 W. 161ST STREET
OLATHE, KS 66062
(913) 829-8650
COMMISSIONING
GLHN ARCHITECTS & ENGINEERS, INC.
2939 E. BROADWAY BLVD
TUCSON, AZ 85716
(520) 881-4546
R1 - CONSTRUCT REPLACEMENT
WAREHOUSE
ARCHITECTURAL SITE PLAN
01/06/2020 RWG ZDL
500 AZ-89, PRESCOTT, AZ 86301
165-G-002
649-414
BID DOCUMENTS
1" = 20'-0"1
ARCHITECTURAL SITE PLAN
N
1/2" = 1'-0"2
HANDRAIL ELEVATION
1/2" = 1'-0"3
RAMP RAILING ELEVATION
5/8" TYPE 'X' GYP. BD. ON 2 1/2" MTL STUDS @ 16" O.C. ON 8" MTL Z-GIRT WITH
2 1/2" THICK INSULATED METAL PANEL.
TYPE 1
(EXTERIOR)
INTERIOR EXTERIOR
CEILING MATERIAL
AS SCHEDULED
WALL FINISH AS SCHEDULED
5/8" GYP. BD. ON 2 1/2" METAL
STUD FRAMING AT 16" O.C.
BASE AND FLOORING
AS SCHEDULED
C E
IL
IN
G H
E
IG
H T
R E
: R C
P 6"
AIR BARRIER
INSULATED METAL
PANEL SYSTEM
8" METAL Z-GIRT
THERMAL TAPE @ GIRTS
TYPE 2
(EXTERIOR)
SUFFIX
A
DETAILS SUFFIX
A
DETAILS
B B -
INTERIOR EXTERIOR
3/4" LINER PANEL
AIR BARRIER
8" METAL GIRT
THERMAL TAPE @ GIRTS
3/4" M-LINER PANEL UP TO 8'-0" A.F.F. ON 8" MTL Z-GIRT WITH 2 1/2" THICK
INSULATED METAL PANEL.
SUFFIX
A
DETAILS
B
5/8" TYPE 'X' GYP. BD. ON EACH SIDE OF 6" METAL STUDS AT 16" O.C. W/ (STC 45)
SOUND ATTENUATION FIRE BLANKETS. EXTEND FROM FIN. FLR. TO DECK.
RATED 1 HOUR & SMOKE. UL# 419
TYPE 3
(INTERIOR - 1 HR RATED / SMOKE)
5/8" TYPE 'X' GYP. BD. ON EACH SIDE OF 3 5/8" METAL STUDS AT 16" O.C. W/ (STC 45)
SOUND ATTENUATION FIRE BLANKETS. EXTEND FROM FIN. FLR. TO DECK.
RATED 1 HOUR & SMOKE. UL# 419
CEILING MATERIAL
AS SCHEDULED
BASE AND FLOORING
AS SCHEDULED
C E
IL
IN
G H
E
IG
H T
R E
: R C
P
SEAL TO TOP OF SLAB W/
CAULKING ON BOTH SIDES
R-11 SOUND ATTENUATION
FIRE BLANKETS
5/8" GYP. BD. EACH SIDE OF
METAL STUDS AT 16" O.C.
WALL FINISH AS
SCHEDULED
C E
IL
IN
G H
E
IG
H T
R E
: R C
P
SEAL FIRE-RATED
ASSEMBLY
E X
T E
N D
F U
LL
H
E
IG
H T
F O
R T
Y P
E
B
E X
T E
N D
L
IN
E R
P A
N E
L 8'
F
O R
T Y
P E
A
1-HR FIRE-RATED
CEILING ASSEMBLY
SUFFIX
A
DETAILS
B
5/8" TYPE 'X' GYP. BD. ON EACH SIDE OF 6" METAL STUDS AT 16" O.C. W/ (STC 45)
SOUND ATTENUATION FIRE BLANKETS. EXTEND FROM FIN. FLR. TO DECK.
RATED 1 HOUR & SMOKE. UL# 419
TYPE 4
(INTERIOR - 1 HR RATED / SMOKE)
5/8" TYPE 'X' GYP. BD. ON EACH SIDE OF 3 5/8" METAL STUDS AT 16" O.C. W/ (STC 45)
SOUND ATTENUATION FIRE BLANKETS. EXTEND FROM FIN. FLR. TO DECK.
RATED 1 HOUR & SMOKE. UL# 419
1-HR FIRE-RATED
CEILING ASSEMBLY
BASE AND FLOORING
AS SCHEDULED
SEAL TO TOP OF SLAB W/
CAULKING ON BOTH SIDES
R-11 SOUND ATTENUATION
FIRE BLANKETS
5/8" GYP. BD. EACH SIDE OF
METAL STUDS AT 16" O.C.
WALL FINISH AS
SCHEDULED
C E
IL
IN
G H
E
IG
H T
R E
: R C
P
SEAL FIRE-RATED
ASSEMBLY
1-HR FIRE-RATED
CEILING ASSEMBLY
C E
IL
IN
G H
E
IG
H T
R E
: R C
P
1 LAYER 5/8" GYP. BD. ON EACH SIDE OF 3 5/8" METAL STUDS AT 16" O.C.
W/ SOUND ATTENUATION BATTS. EXTEND 1' - 6" ABOVE FINISHED
CEILING FOR CEILING SUPPORT STRUCTURE.
1 LAYER 5/8" GYP. BD. ON ONE SIDE OF 6" METAL STUDS AT 16" O.C. W/
SOUND ATTENUATION BATTS. EXTEND 1' - 6" ABOVE FINISHED CEILING FOR
CEILING SUPPORT STRUCTURE.
TYPE 6
(INTERIOR - NON RATED)
SUFFIX
A
DETAILS
B
R-11 SOUND ATTENUATION
FIRE BLANKETS
5/8" GYP. BD. EACH SIDE OF
METAL STUDS AT 16" O.C.
BASE AND FLOORING
AS SCHEDULED
WALL FINISH AS
SCHEDULED
CEILING MATERIAL
AS SCHEDULED
CEILING SUPPORT STRUCTURE
1 LAYER 5/8" GYP. BD. ON EACH SIDE OF 3 5/8" METAL STUDS AT 16" O.C.
W/ SOUND ATTENUATION BATTS. EXTEND 1' - 6" ABOVE FINISHED
CEILING FOR CEILING SUPPORT STRUCTURE.
1 LAYER 5/8" GYP. BD. ON ONE SIDE OF 6" METAL STUDS AT 16" O.C. W/
SOUND ATTENUATION BATTS. EXTEND 1' - 6" ABOVE FINISHED CEILING FOR
CEILING SUPPORT STRUCTURE.
TYPE 7
(INTERIOR - NON RATED)
SUFFIX
A
DETAILS
B
R-11 SOUND ATTENUATION
FIRE BLANKETS
5/8" GYP. BD. EACH SIDE OF
METAL STUDS AT 16" O.C.
BASE AND FLOORING
AS SCHEDULED
WALL FINISH AS
SCHEDULED
CEILING MATERIAL
AS SCHEDULED
WAREHOUSE SUPPORT SPACE
E X
T E
N D
T O
3'
A
.F .F
C E
IL
IN
G H
E
IG
H T
R E
: R C
P
E X
T E
N D
T O
3'
A
.F .F
WAREHOUSE SUPPORT SPACE
C E
IL
IN
G H
E
IG
H T
R E
: R C
P
1 LAYER 5/8" GYP. BD. ON EACH SIDE OF 3 5/8" METAL STUDS AT 16" O.C.
W/ SOUND ATTENUATION BATTS. EXTEND 6" ABOVE FINISHED CEILING.
1 LAYER 5/8" GYP. BD. ON ONE SIDE OF 6" METAL STUDS AT 16" O.C. W/
SOUND ATTENUATION BATTS. EXTEND 6" ABOVE FINISHED CEILING.
TYPE 5
(INTERIOR - NON RATED)
SUFFIX
A
DETAILS
B
R-11 SOUND ATTENUATION
FIRE BLANKETS
5/8" GYP. BD. EACH SIDE OF
METAL STUDS AT 16" O.C.
BASE AND FLOORING
AS SCHEDULED
WALL FINISH AS
SCHEDULED
CEILING MATERIAL
AS SCHEDULED
1 LAYER 5/8" GYP. BD. ON EACH SIDE OF 3 5/8" METAL STUDS AT 16" O.C.
W/ SOUND ATTENUATION BATTS. EXTEND 1' - 6" ABOVE FINISHED
CEILING FOR CEILING SUPPORT STRUCTURE.
1 LAYER 5/8" GYP. BD. ON ONE SIDE OF 6" METAL STUDS AT 16" O.C. W/
SOUND ATTENUATION BATTS. EXTEND 1' - 6" ABOVE FINISHED CEILING FOR
CEILING SUPPORT STRUCTURE.
TYPE 7
(INTERIOR - NON RATED)
SUFFIX
A
DETAILS
B
R-11 SOUND ATTENUATION
FIRE BLANKETS
5/8" GYP. BD. EACH SIDE OF
METAL STUDS AT 16" O.C.
BASE AND FLOORING
AS SCHEDULED
WALL FINISH AS
SCHEDULED
CEILING MATERIAL
AS SCHEDULED
C E
IL
IN
G H
E
IG
H T
R E
: R C
P 6"
3/4" M-LINER PANEL FULL HEIGHT TO UNDERSIDE OF STRUCTURE ABOVE
ON 8" MTL Z-GIRT WITH 2 1/2" THICK INSULATED METAL PANEL.
INSULATED METAL
PANEL SYSTEM
GENERAL PARTITION NOTES
1. NOT ALL PARTITION TYPES SHOWN HERE MAY BE USED. REFER TO PLANS FOR LOCATION AND TYPES OF EACH
PARTITION.
2. PAINT CONTINUOUS 4" TALL, STENCILED LETTERS, ABOVE CEILING, ON BOTH SIDES OF ALL FIRE AND SMOKE WALLS
DESIGNATING THE PARTITION RATING INDICATED ON THE LIFE SAFETY PLAN.
3. REFER TO FINISH SCHEDULE AND INTERIOR ELEVATIONS FOR LOCATIONS OF ALL WALL TILE.
PROVIDE AND INSTALL CEMENTITIOUS BACKER BOARD IN LIEU OF GWB AT ALL SCHEDULED TILE LOCATIONS. UNLESS
NOTED OTHERWISE, TILE SHALL BE INSTALLED PER TILE COUNCIL OF AMERICA LATEST STANDARDS FOR EACH TYPE OF
BACKING MATERIAL REPRESENTED IN WALL/PARTITION.
4. ALL SUSPENDED WALLS AND PARTITIONS SHALL HAVE GWB WHICH EXTENDS A MINIMUM OF 6" ABOVE THE SUSPENDED
CEILING UNLESS SHOWN AND/OR NOTED OTHERWISE BY THE ARCHITECT.
5. REFER TO STRUCTURAL DRAWINGS FOR ALL LOAD BEARING WALL CONDITIONS IN REGARDS TO STRUCTURAL
REQUIREMENTS.
6. "ALIGN" MEANS SIMILAR COMPONENTS OF CONSTRUCTION, E.G. WALLS, JAMBS, ETC. SHALL ALIGN ACROSS VOIDS AND
JOINTS.
7. PARTITIONS SHALL BE CONTINUOUS OVER DOORS SAME ADJACENT WALLS (UNLESS NOTED OTHERWISE) WHERE DRYWALL CONTINUES ABOVE CEILING AND ABOVE THE CEILING LEVEL UP TO THE STRUCTURE ABOVE. ALL GYPSUM BOARD RETURNS SHALL HAVE CORNER BEADS MINIMUM FLOOR TO CEILING. ALL PENETRATIONS IN DRYWALL CONSTRUCTION ABOVE FINISHED CEILING SHALL BE EFFECTIVELY SEALED TO PREVENT SOUND LEAKAGE AND
SMOKE/FIRE STOPPING TAPE/CAULK AT ALL RATED PARTITIONS.
8. ALL CONSTRUCTION DESIGNATED TO BE SUPPORTED BY ROOF STRUCTURE SHALL BE SUPPORTED BY TOP CHORD OF
STRUCTURAL JOISTS AND NOT FROM THE METAL DECK.
9. COORDINATE WITH MILLWORK DRAWINGS FOR PLACEMENT OF METAL BLOCKING IN WALLS/PARTITIONS.
10. IMPACT RESISTANT GWB, WHERE NOTED, IS OPTIONAL ABOVE 8' AFF AND BEHIND LOCKERS.
11. SEAL THE TOP AND BOTTOM OF WALL AS WELL AS ALL PENETRATIONS WHERE SMOKE PARTITIONS ARE DESIGNATED ON
THE LIFE SAFETY PLAN TO ELIMINATE THE PASSAGE OF SMOKE.
12. ALL PARTITIONS THAT HOST PLUMBING FIXTURES SHALL RECEIVE MOLD / MOISTURE RESISTANT GWB IN LIEU OF
REGULAR GWB.
DRAWING NUMBER
VA PROJECT NUMBER
DATE
PROJECT TITLE
BUILDING NUMBER
PROJECT LOCATION
CHECKED BY DRAWN BY
APPROVED: PROJECT DIRECTOR
o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
VA FORM 08-6231
Office of Construction and Facilities Management
Dwg.
CONSULTANT INFORMATION
STRUCTURAL / CIVIL ENGINEER
F
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
SHEET TITLE
ARCHITECT
MECH. / ELEC. / PLUMB. / TECH. ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FULLY SPRINKLERED
PROJECT PHASE
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
U.S. Department of Veteran Affairs
F
E
D
C
B
A
E
D
C
B
A
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 W. 161ST STREET
OLATHE, KS 66062
(913) 829-8650
COMMISSIONING
GLHN ARCHITECTS & ENGINEERS, INC.
2939 E. BROADWAY BLVD
TUCSON, AZ 85716
(520) 881-4546
R1 - CONSTRUCT REPLACEMENT
WAREHOUSE
PARTITION TYPES
01/06/2020 RWG ZDL
500 AZ-89, PRESCOTT, AZ 86301
165-G-010
649-414
GENERAL INFORMATION
BUILDING 165
REPLACEMENT WAREHOUSE
PRESCOTT, AZ
NEW CONSTRUCTION
CODE COMPLIANCE OF NEW FACILITY
PROJECT STATEMENT OF WORK
FIRE PROTECTION DESIGN MANUAL - SEVENTH EDITION - DECEMBER 2015
NFPA 1: NATIONAL FIRE CODE, 2018 EDITION
NFPA 10: STANDARD FOR PORTABLE FIRE EXTINGUISHERS, 2018 EDITION
NFPA 13: STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2019 EDITION
NFPA 24: STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES, 2019 EDITION
NFPA 30: FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE, 2018 EDITION
NFPA 70: NATIONAL ELECTRICAL CODE, 2017 EDITION
NFPA 72: NATIONAL FIRE ALARM AND SIGNALING CODE, 2019 EDITION
NFPA 80: STANDARD FOR FIRE DOORS AND OTHER OPENING PROTECTIVES, 2019 EDITION
NFPA 90A: STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATING SYSTEMS, 2018 EDITION
NFPA 101: LIFE SAFETY CODE, 2018 EDITION
NFPA 291: RECOMMENDED PRACTICE FOR FIRE FLOW TESTING AND MARKING OF HYDRANTS, 2019 EDITION
NFPA 495: EXPLOSIVE MATERIALS CODE, 2018 EDITION
NFPA 5000: BUILDING CONSTRUCTION AND SAFETY CODE, 2018 EDITION
INTERNATIONAL BUILDING CODE (IBC), 2018 EDITION
PROPERTY NAME & PHYSICAL ADDRESS:
PROJECT CONSTRUCTION PURPOSE:
REASON FOR SUBMITTAL:
CRITERIA USED:
NONE
DECEMBER 18, 2018
DECEMBER 27, 2019
UNITED STATES DEPARTMENT OF VETERANS AFFAIRS - NORTHERN ARIZONA VA
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KS 66062
913.829.8650 (TELEPHONE)
913.829.8690 (TELEFAX)
ANTICIPATED ADDITIONS:
DATE DEVELOPED:
DATE MODIFIED:
OWNER INFORMATION:
CODE CONSULTANT INFORMATION:
SEE TITLE BLOCK
VA FIRE DEPARTMENT
DEPARTMENT OF VA
DEPARTMENT OF VA
IBC OCCUPANCY MIXED USE NONSEPARATED (IBC, SECTION 508.3)
STORAGE (GROUP S-1) OCCUPANCY (IBC, SECTION 311.2)
BUSINESS (GROUP B) OCCUPANCY (IBC, SECTION 304)
NFPA 101 OCCUPANCY MIXED USE NONSEPARATED (NFPA 101, SECTION 6.1.14.3)
GENERAL STORAGE OCCUPANCY (NFPA 101, SECTION 42.1.2.3)
NEW BUSINESS (NFPA 101, SECTION 38.1.2)
DESIGNER’S SEAL:
FIRE SERVICE:
LOCAL BUILDING INSPECTOR:
AUTHORITY HAVING JURISDICTION:
OCCUPANCY GROUP AND TYPE:
TYPE II (000) NFPA 220, TABLE 4.1.1
HEIGHT LIMITATION
ALLOWABLE HEIGHT 4 STORIES (NPFA 5000, TABLE 7.4.1)
ACTUAL HEIGHT 2 STORY, 41 FEET - COMPLIANT
AREA LIMITATION
ALLOWABLE AREA WITHOUT MODIFICATIONS 17,500. (NPFA 5000, TABLE 7.4.1)
ACTUAL AREA 10,947 SQFT – COMPLIANT
FIRE RESISTIVE REQUIREMENTS (IBC, TABLES 601 & 602; UFC 4-211-01, SECTION 3-3.1)
PRIMARY STRUCTURAL FRAME 0-HOUR - REQUIRED - PROVIDED
BEARING WALLS - EXTERIOR 0-HOUR - REQUIRED - PROVIDED
BEARING WALLS - INTERIOR 0-HOUR - REQUIRED - PROVIDED
NON BEARING WALLS - EXTERIOR 0-HOUR - REQUIRED - PROVIDED
NON BEARING WALLS - INTERIOR 0-HOUR - REQUIRED - PROVIDED
FLOOR CONSTRUCTION AND SECONDARY MEMBERS 0-HOUR - REQUIRED - PROVIDED
ROOF CONSTRUCTION AND SECONDARY MEMBERS 0-HOUR - REQUIRED - PROVIDED
TYPE OF CONSTRUCTION:
STRUCTURAL CODE REQUIREMENTS:
REQUIRED - PROVIDED, PER NFPA 101, SECTION 38.3.2 PROTECTION FROM HAZARDSOCCUPANCY SEPARATION:
PASSIVE FIRE SAFETY FEATURES
STORAGE:
INTERIOR WALL AND CEILING FINISHES CLASS A, B, OR C REQUIRED FOR STORAGE AREAS (NFPA 101, SECTION 42.3.3)
- PROVIDED
INTERIOR FLOOR FINISHES IN ALL OTHER AREAS, NO CLASSIFICATION REQUIRED FOR STORAGE AREA (NFPA 101, SECTION 42.3.3.3.2)
- PROVIDED
BUSINESS:
INTERIOR WALL AND CEILING FINISHES CLASS A OR B REQUIRED IN EXITS AND IN EXIT ACCESS CORRIDORS, AND CLASS A, B, OR C IN ALL OTHER AREAS FOR NEW CONSTRUCTION BUSINESS AREAS (NFPA 101, SECTION 38.3.3)
- PROVIDED
INTERIOR FLOOR FINISHES CLASS I OR CLASS II REQUIRED IN EXIT ENCLOSURES AND ALL OTHER INTERIOR FLOOR FINISHES REQUIRED TO MEET THE REQUIREMENTS OF NFPA 101 SECTION 10.2.7.1 OR
10.2.7.2 AS (NFPA 101, SECTION 38.3.3.3) APPLICABLE
- PROVIDED
ROOM SEPARATION IN ACCORDANCE WITH NFPA AND APPLICABLE CRITERIA IS PROVIDED. PER NFPA 495, THE AMMO ROOM SHALL BE SEPARATED BY 1-HOUR FIRE RATED CONSTRUCTION. IN ADDITION, PER NFPA 30, THE FLAMMABLE STORAGE ROOMS SHALL BE SEPARATED BY 1-HOUR FIRE RATED CONSTRUCTION
- PROVIDED (REFER TO LIFE SAFETY SHEETS)
WHERE PROTECTION IS PROVIDED WITH AUTOMATIC EXTINGUISHING SYSTEMS WITHOUT FIRE-RESISTIVE SEPARATION, THE SPACE PROTECTED SHALL BE ENCLOSED WITH SMOKE PARTITIONS IN
ACCORDANCE WITH NFPA 101, SECTION 8.4.
- PROVIDED (SEE CODE PLAN)
NO FIRE RESISTANCE RATING REQUIRED (NFPA 101, SECTION 42.3.6 & 38.3.6.(1))
- NOT PROVIDED
NOT APPLICABLE
STAIRS USED AS A COMPONENT IN THE MEANS OF EGRESS SHALL CONFORM TO THE GENERAL REQUIREMENTS OF SECTION 7.1 AND 7.2.2 OF NFPA 101.
- PROVIDED
NOT APPLICABLE
THROUGH PENETRATIONS OF FIRE RESISTANCE RATED CONSTRUCTION PROTECTED BY AN APPROVED FIRE STOP SYSTEM INSTALLED AS TESTED IN ACCORDANCE WITH ASTM E 814 OR UL 1479 REQUIRED
(NFPA 101, SECTION 8.3.5)
- PROVIDED
INTERIOR FINISH:
ROOM SEPARATION:
HAZARD PROTECTION:
CORRIDORS:
HORIZONTAL EXITS:
STAIRWAYS:
SHAFT ENCLOSURES:
OPENINGS AND PENETRATIONS:
REQUIRED (VA FIRE PROTECTION DESIGN MANUAL SECTION 6.1)
- WET PIPE SPRINKLER SYSTEM PROVIDED
NOT REQUIRED
- NOT PROVIDED
TBD
- NOT PROVIDED
NOT REQUIRED
- NOT PROVIDED
NOT APPLICABLE
NOT APPLICABLE
REQUIRED (NFPA 101, SECTION 38.3.5
- PROVIDED - PER NFPA 10
NOT REQUIRED
- NOT PROVIDED
EQUIPPED WITH DUCT SMOKE DETECTION AND INTERLOCKED WITH DUCT DETECTOR ACTIVATION FOR AIR HANDLING UNIT SHUT DOWN REQUIRED (NFPA 90A)
- PROVIDED
FIRE DAMPERS INSTALLED IN ALL TRANSFER OPENINGS IN FIRE BARRIERS REQUIRED (NFPA 90A, SECTION 5.3.1.2)
- PROVIDED
INTERNALLY OR EXTERNALLY ILLUMINATED EXIT SIGNS ALONG THE PATH OF EGRESS TRAVEL REQUIRED (NFPA 101,SECTIONS 7.10.1.2)
- PROVIDED INTERNALLY ILLUMINATED LED TYPE AND POWERED BY CENTRAL INVERTER SYSTEM
TACTILE EXIT SIGNS AT EACH EXIT DOOR REQUIRING AN EXIT SIGN REQUIRED (NFPA 101, SECTION 7.10.1.3)
- PROVIDED
ILLUMINATION OF MEANS OF EGRESS REQUIRED (NFPA 101, SECTION 42.2.8)
- PROVIDED
EMERGENCY LIGHTING REQUIRED (NFPA 101, SECTIONS 42.2.9, 38.2.9, & 7.9)
- PROVIDED BY BATTERIES WITHIN LIGHT FIXTURES (SEE ELECTRICAL FOR ADDITIONAL DETAIL)
MANUALLY ACTIVATED, EMERGENCY ALARM COMMUNICATION SYSTEM WITH VISIBLE ALARM NOTIFICATION APPLIANCES IN ALL COMMON USE AREAS, EMPLOYEE WORK AREAS, AND PUBLIC USE AREAS TO BE PROVIDED
- PROVIDED
SMOKE DETECTOR ABOVE FIRE ALARM CONTROL UNIT, NOTIFICATION APPLIANCE CIRCUIT POWER EXTENDERS, AND SUPERVISING STATION TRANSMITTING EQUIPMENT REQUIRED (NFPA 72, SECTION 10.4.4)
- PROVIDED
DUCT SMOKE DETECTION ON AIR HANDLING UNITS GREATER THAN 944 L/S (2,000 CFM) SUPPLY AIR CAPACITY REQUIRED (NFPA 90A, SECTION 6.4.2.1(1))
- PROVIDED
FULL AREA SMOKE DETECTION NOT REQUIRED
- NOT PROVIDED
BUILDING 165 (REPLACEMENT WAREHOUSE) SHALL BE TIED INTO THE EXISTING FIBER NETWORK DATA LOOP ON THE VA CAMPUS. UTILIZING 62.5 MICRON MULTI-MODE FIBER OPTIC CABLE, THE FACILITY SHALL BE FULLY
FUNCTIONAL WITH RING CONFIGURATION ON CAMPUS.
NOT REQUIRED
- NOT PROVIDED
REQUIRED
- PROVIDED (REFER TO EP-103)
AUTOMATIC SPRINKLER PROTECTION:
STANDPIPES:
AUTOMATIC FIRE PUMPS:
SPECIAL FIRE SUPPRESSION SYSTEM:
KITCHEN HOOD VENTILATION SYSTEMS:
KITCHEN HOOD SUPPRESSION SYSTEM:
PORTABLE FIRE EXTINGUISHERS:
SMOKE CONTROL:
HVAC SYSTEM:
EXIT SIGNS:
ILLUMINATION OF MEANS OF EGRESS:
EMERGENCY LIGHTING:
FIRE ALARM SYSTEM:
SMOKE DETECTION:
FIRE ALARM REPORTING SYSTEM:
MASS NOTIFICATION SYSTEM:
LIGHTNING PROTECTION:
ACTIVE FIRE SAFETY FEATURES
NOT APPLICABLE
TO BE COORDINATED BY THE GENERAL CONTRACTOR IN CONJUNCTION WITH THE VA AND COR.
CONTRACTOR SHALL PERFORM HYDRANT FLOW TEST PRIOR TO THE DEVELOPMENT OF SHOP DRAWINGS TO ENSURE WATER
SUPPLY IS ADEQUATE.
REFERENCE FX SHEETS FOR ADDITIONAL INFORMATION
FIRE HYDRANT FLOW TEST (HISTORICAL):
WATER SUPPLY INFORMATION:
FIRE DEPARTMENT NEEDS
MEANS OF EGRESS
CALCULATED OCCUPANT LOAD PER OCCUPANCY CLASSIFICATION AND USE (NFPA 101, TABLE 7.3.1.2)OCCUPANT LOAD:
THREE BUILDING EXITS REQUIRED (NFPA 101, SECTIONS 7.4.1.2(1))
- THREE (3) PROVIDED ON FIRST LEVEL AND TWO (2) PROVIDED ON SECOND LEVEL
NUMBER OF EXITS:
USE OCCUPANT LOAD FACTOR GROSS OR NET AREA
STORAGE SPACES 500 SQ. FT. PER PERSON GROSS
BUSINESS – 150 SQ. FT. PER PERSON GROSS
UNCONCENTRATED
BUSINESS – 50 SQ. FT. PER PERSON GROSS
CONCENTRATED
MECHANICAL/ELECTRICAL 500 SQ. FT. PER PERSON GROSS
EQUIPMENT ROOMS
CONFERENCE 15 SQ. FT. PER PERSON NET
ROOMS/ASSEMBLY
TOTAL OCCUPANT LOAD: 44 OCCUPANTS, SEE LIFE SAFETY PLAN FOR OCCUPANT LOAD CALCULATION.
WHERE TWO EXITS OR EXIT ACCESS DOORWAYS ARE REQUIRED, EXITS OR EXIT ACCESS DOORWAYS SEPARATED BY NOT LESS THAN ONE-THIRD THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE AREA SERVED REQUIRED (NFPA 101, SECTION 7.5.1.3.3)
- PROVIDED
CALCULATED MEANS OF EGRESS COMPONENTS SIZING REQUIREMENTS PER COMPONENT REQUIRED (NFPA 101, TABLE 7.3.3.1 & 7.3.4.1)
- PROVIDED
ARRANGEMENT OF EXITS:
MEANS OF EGRESS SIZING:
OCCUPANCY OCCUPANT LOAD OF SPACE MINIMUM NUMBER OF EXITS
OR EXIT ACCESS DOORWAYS
FROM SPACE
LOW AND ORDINARY HAZARD ≤ 500 2
STORAGE
BUSINESS AREAS ≤ 500 2
USE OCCUPANT LOAD FACTOR GROSS OR NET AREA
STAIRWAYS 0.3 INCHES PER PERSON 36 INCHES
RAMPS 0.2 INCHES PER PERSON 36 INCHES
CORRIDORS 0.2 INCHES PER PERSON 36 INCHES
PASSAGEWAYS 0.2 INCHES PER PERSON 36 INCHES
DOORS 0.2 INCHES PER PERSON 36 INCHES
REFER TO ARCHITECTURAL PLANS FOR STAIR AND RAIL REQUIREMENTS
REFER TO ARCHITECTURAL PLANS FOR STAIR AND RAIL REQUIREMENTS
REFER TO ARCHITECTURAL PLANS FOR STAIR AND RAIL REQUIREMENTS
REFER TO ARCHITECTURAL PLANS FOR STAIR AND RAIL REQUIREMENTS
ALLOWABLE TRAVEL DISTANCE
BUSINESS OCCUPANCY 300 FT. (NFPA 101, SECTION 38.2.6.3)
STORAGE (ORDINARY) OCCUPANCY 400 FT. (NFPA 101, TABLE 42.2.6)
ACTUAL
BUSINESS OCCUPANCY REFER TO LIFE SAFETY PLANS
STORAGE (ORDINARY) OCCUPANCY REFER TO LIFE SAFETY PLANS
ALLOWABLE COMMON PATH OF TRAVEL
BUSINESS OCCUPANCY 100 FT. (NFPA 101, SECTION 38.2.5.3.1)
STORAGE (ORDINARY) OCCUPANCY 100 FT. (NFPA 101, TABLE 42.2.5)
ACTUAL
BUSINESS OCCUPANCY REFER TO LIFE SAFETY PLANS
STORAGE (ORDINARY) OCCUPANCY REFER TO LIFE SAFETY PLANS
ALLOWABLE DEAD END CORRIDOR
BUSINESS OCCUPANCY 50 FT (NFPA 101, SECTION 38.2.5.2.1)
STORAGE (ORDINARY) OCCUPANCY 100 FT (NFPA 101, TABLE 42.2.5)
ACTUAL
BUSINESS OCCUPANCY REFER TO LIFE SAFETY PLANS
STORAGE (ORDINARY) OCCUPANCY REFER TO LIFE SAFETY PLANS
STAIRWAY DIMENSIONAL REQUIREMENTS:
RAMP DIMENSIONAL REQUIREMENTS:
HANDRAIL REQUIREMENTS:
GUARD REQUIREMENTS:
MAXIMUM TRAVEL DISTANCE:
COMMON PATH OF TRAVEL:
DEAD END CORRIDOR:
SHALL BE IN COMPLIANCE WITH VA STANDARDS
AT LEAST ONE MEANS OF ALL-WEATHER GROUND ACCESS NO FARTHER THAN 50FT TO AT LEAST ONE EXTERIOR DOOR THAT CAN BE OPENED FROM THE OUTSIDE (NFPA 1, SECTION 18.2.3.2.1)
- PROVIDED
AT LEAST ONE MEANS OF ALL-WEATHER GROUND ACCESS NO FARTHER THAN 150 FT. FROM FIRE DEPARTMENT CONNECTION REQUIRED
- PROVIDED
FIRE DEPARTMENT ACCESS ROADS SUCH THAT ANY PORTION OF THE FACILITY OR ANY PORTION OF AN EXTERIOR WALL OF THE FIRST STORY OF THE BUILDING IS LOCATED NOT MORE THAN 450 FT. FROM FIRE
DEPARTMENT ACCESS ROADS REQUIRED (NFPA 1, SECTION 18.2.3.2.2.1)
- PROVIDED
FIRE APPARATUS ACCESS ROADS MUST HAVE AN UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FT. AND AN UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13.5 FT. REQUIRED (NFPA 1, SECTIONS
18.2.3.4.1.1 & 18.2.3.4.1.2)
- PROVIDED
REQUIRED
- FIRE DEPARTMENT ACCESS CABINET TO BE LOCATED AT LOCATIONS NOTED ON PLANS
THE MAXIMUM DISTANCE TO A FIRE HYDRANT FROM THE CLOSEST POINT ON THE BUILDING SHALL NOT EXCEED 400 FT. (NFPA 1, SECTION 18.5.3)
- PROVIDED
FIRE HYDRANT SPACING SUCH THAT ALL FIRE DEPARTMENT CONNECTIONS ARE WITHIN 150 FT. OF A FIRE HYDRANT REQUIRED
- PROVIDED
THE MAXIMUM DISTANCE BETWEEN FIRE HYDRANTS SHALL NOT EXCEED 500 FT. (NFPA 1, SECTION 18.5.3)
- PROVIDED
A CLEAR SPACE OF 36 OR 60 (FOR HYDRANTS WITH A DIAMETER GREATER THAN 2 1/2 INCHES) INCHES SHALL BE MAINTAINED AROUND THE CIRCUMFERENCE OF FIRE HYDRANTS. (NFPA 1, SECTION 18.5.7)
- PROVIDED
PHYSICAL PROTECTION PROVIDED FOR FIRE HYDRANTS THAT ARE SUBJECT TO IMPACT BY A MOTOR VEHICLE REQUIRED (NFPA 1, SECTION 18.5.8)
- PROVIDED
NOT REQUIRED (NFPA 101)
- NOT PROVIDED
NOT REQUIRED (NFPA 101)
- NOT PROVIDED
PREMISES IDENTIFICATION:
FIRE DEPARTMENT ACCESS:
KEY BOX:
FIRE HYDRANTS:
FIRE SAFETY AND EVACUATION PLANS:
FIRE COMMAND CENTER:
WATER SUPPLY REQUIREMENTS
DRAWING NUMBER
VA PROJECT NUMBER
DATE
PROJECT TITLE
BUILDING NUMBER
PROJECT LOCATION
CHECKED BY DRAWN BY
APPROVED: PROJECT DIRECTOR
o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th s i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
VA FORM 08-6231
Office of Construction and Facilities Management
Dwg.
CONSULTANT INFORMATION
STRUCTURAL / CIVIL ENGINEER
F
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
SHEET TITLE
ARCHITECT
MECH. / ELEC. / PLUMB. / TECH. ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FULLY SPRINKLERED
PROJECT PHASE
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
U.S. Department of Veteran Affairs
F
E
D
C
B
A
E
D
C
B
A
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 W. 161ST STREET
OLATHE, KS 66062
(913) 829-8650
COMMISSIONING
GLHN ARCHITECTS & ENGINEERS, INC.
2939 E. BROADWAY BLVD
TUCSON, AZ 85716
(520) 881-4546
R1 - CONSTRUCT REPLACEMENT
WAREHOUSE
LIFE SAFETY PLAN - CODE PLAN
NARRATIVE
01/06/2020 RWG ZDL
500 AZ-89, PRESCOTT, AZ 86301
165-G-100
649-414
1 OCCUPANT LOAD
SPACE NOT OCCUPIED
BUILDING EXIT
EGRESS PATH
1 HOUR FIRE
2 HOUR FIRE
3 HOUR FIRE
4 HOUR FIRE
1 HOUR FIRE / SMOKE
2 HOUR FIRE / SMOKE
3 HOUR FIRE / SMOKE
4 HOUR FIRE / SMOKE
FEC FIRE EXTINGUISHER CABINET
NFPA 101-2018 EDITION
BUILDING HEIGHT: 1 STORY, 41'-0" HEIGHT
• TOTAL PROJECT SF: 10,947 NET SF
BUILDING IS EQUIPPED WITH A FULLY AUTOMATIC FIRE SPRINKLER SYSTEM THROUGHOUT - TO MEET NFPA 13 REQUIREMENTS
CONSTRUCTION TYPE: (NFPA 220, TABLE 4.1.1):
• TYPE II
OCCUPANCY CLASSIFICATION: MIXED-USE, NON-SEPARATED
• NEW BUSINESS OCCUPANCY (CH. 38)
• NEW STORAGE OCCUPANCY (CH. 42)
TOTAL OCCUPANT LOAD: 44 OCCUPANTS (NFPA 101, TABLE 7.3.1.2, SEE CALCULATIONS BELOW)
EGRESS COMPONENTS
• MINIMUM REQUIRED DOOR WIDTH = 32" MIN.
• MINIMUM REQUIRED WIDTH OF EGRESS COMPONENTS = (44 OCC. X .2"/OCC.) = 8.8"
• MINIMUM REQUIRED STAIR WIDTH = (44 OCC. X .3"/OCC.) = 13.2"
• 44" MIN. WHEN SERVING LESS THAN 2000 OCCUPANTS. (NFPA 101 TABLE 7.2.2.2.1.2)
• MINUMUM REQUIRED NUMBER OF EXITS: 2 EXITS
FIRE RESISTANCE RATINGS (NFPA 220, TABLE 4.1.1):
• COLUMNS: 0 HR
• BEAM, GIRDERS, TRUSSES: 0 HR
• FLOOR/CEILING ASSEMBLIES: 0 HR
• ROOF/CEILING ASSEMBLIES: 0 HR
• EXTERIOR NON-BEARING WALLS: 0 HR
• INTERIOR NON-BEARING WALLS: 0 HR
FIRE-RESISTIVE REQUIREMENTS:
• NON COMBUSTIBLE MATERIALS FOR STRUCTURAL FRAME, FLOORS, ROOF DECK, EXTERIOR NON-BEARING WALLS, AND
INTERIOR NON-BEARING WALLS.
MAXIMUM COMMON PATH OF TRAVEL:
• (STORAGE): 100' (TABLE 42.2.5)
• (BUSINESS): 100' (38.2.5.3.1)
MAXIMUM TRAVEL DISTANCE:
• (STORAGE): 400' (TABLE 42.2.6)
• (BUSINESS): 300' (38.2.6.3)
MAXIMUM DEAD-END CORRIDOR:
• (STORAGE): 100' (TABLE 42.2.5)
• (BUSINESS): 50' (38.2.5.2.1)
FIRE ALARM SYSTEM:
• REQUIRED/PROVIDED AUTOMATIC AND SUPERVISED SYSTEM.
1ST FLOOR - 34 OCCUPANTS
(RM 100) WAREHOUSE - 7728 SF/(500 SF/PERSON) - - - - - - - - - - - - - - - - - - - - - - - - - - - 16 OCC.
(RM 102) BREAK ROOM - 104 SF/(15 SF/PERSON) - - - - - - - - - - - - - - - - - - - - - - - - - - - 07 OCC.
(RM 103) SV OFFICE - 100 SF/(150 SF/PERSON) - - - - - - - - - - - - - - - - - - - - - - - - - - - 01 OCC.
(RM 104) CORRIDOR - 224 SF/(150 SF/PERSON) - - - - - - - - - - - - - - - - - - - - - - - - - - - 02 OCC.
(RM 106) IT ROOM - 100 SF/(150 SF/PERSON) - - - - - - - - - - - - - - - - - - - - - - - - - - - 01 OCC.
(RM 107) ELECTRICAL - 97 SF/(150 SF/PERSON) - - - - - - - - - - - - - - - - - - - - - - - - - - - 01 OCC.
(RM 108) PLOTTING - 339 SF/(150 SF/PERSON) - - - - - - - - - - - - - - - - - - - - - - - - - - - 03 OCC.
(RM 111) UNISEX RR - 91 SF/(150 SF/PERSON) - - - - - - - - - - - - - - - - - - - - - - - - - - - 01 OCC.
(RM 112) UNISEX RR - 91 SF/(150 SF/PERSON) - - - - - - - - - - - - - - - - - - - - - - - - - - - 01 OCC.
(RM 113) MECHANICAL - 324 SF/(500 SF/PERSON) - - - - - - - - - - - - - - - - - - - - - - - - - - - 01 OCC.
(RM 114) STORAGE - 42 SF/(500 SF/PERSON) - - - - - - - - - - - - - - - - - - - - - - - - - - - 01 OCC.
(RM 115) STORAGE - 42 SF/(500 SF/PERSON) - - - - - - - - - - - - - - - - - - - - - - - - - - - 01 OCC.
(RM 116) STORAGE - 91 SF/(500 SF/PERSON) - - - - - - - - - - - - - - - - - - - - - - - - - - - 01 OCC.
(RM 117) WRAPPING - 385 SF/(150 SF/PERSON) - - - - - - - - - - - - - - - - - - - - - - - - - - - 03 OCC.
(RM 118) WORKSPACE - 138 SF/(50 SF/PERSON) - - - - - - - - - - - - - - - - - - - - - - - - - - - 04 OCC.
TOTAL OCCUPANT LOAD = 44 OCCUPANTS
OCCUPANT LOADS (NFPA 101 2018 - TABLE 7.3.1.2)
• BUSINESS USE, CONCENTRATED = 50 SF/PERSON
• BUSINESS USE = 150 SF/PERSON
• ASSEMBLY (LESS CONCENTRATED USE W/O FIXED SEATING) = 15 NET SF/PERSON
• STORAGE USE = 500 SF/PERSON
OCCUPANT LOADS
LIFE SAFETY LEGEND
FIRE RATED WALL SYMBOLS
__ OCC. NUMBER OF OCCUPANTS SERVED BY EXIT COMPONENT
FACU FIRE ALARM CONTROL UNIT
SPACE NOT SPRINKLERED
FDAC FIRE DEPARTMENT ACCESS CABINET
393 SF
WRAPPING
91 SF
STORAGE
(AMMUNITION)
T R
A V
E L
D
IS
T A
N C
E
7778 SF
WAREHOUSE
R
R
338 SF
PLOTTING
RECYCLING
AREA
54 SF
WALK-IN
REF.
42 SF
STORAGE
(SHRED)
42 SF
STORAGE
(FLAM.)
FEC
FEC
TRAVEL DISTANCE = 125' - 06"
29 OCC.FDAC
K E
E P
E G
R E
S S
P A
T H
F R
E E
A
N D
U N
O B
S T
R U
C T
E D
COMMON PATH OF TRAVEL = 90' - 04"
A D
A A
C C
E S
S
IB
LE
R
A M
P
F O
R K
L
IF
T R
A M
P R
E C
IV
IL
DN
DN
D N
DN
FACU
112 SF
SECURE
STOR.
AHU, RE:
MECH DWGS
O
C C
S L O
P E
:2 M
A X
S
LO
P E
:2
M A
X
LANDING
CONCRETE PAD,
RE: CIVIL & STRUCT.
WALK-IN COOLER
CONDENSING UNIT,
RE: MECH. DWGS
DN
T R
A V
E L
D
IS
T A
N C
E
C O
M M
O N
P A
T H
O F
T R
A V
E L
3'
104 SF
BREAK
ROOM
100 SF
SV OFFICE
224 SF
CORRIDOR
99 SF
IT ROOM
96 SF
ELECTRICAL
89 SF
HAC
90 SF
UNISEX
TOILET
90 SF
UNIS…
This is the start of the file's text. The full file is on GovTribe.