Attachment 6 - E Drawings.pdf

PDF 3 MB Posted

Attached to
Y1GZ--Construct Replacement Warehouse Prescott VAMC (Minor Construction) Federal contract opportunity
Solicitation number
36E77620R0043
Issued by
Department of Veterans Affairs Headquarters

About this file

This document provides details for a federal contract opportunity to construct a replacement warehouse at the Northern Arizona VA Health Care System in Prescott, Arizona. The Department of Veterans Affairs seeks to award a firm-fixed-price contract through a Request for Proposal as a total Service-Disabled Veteran-Owned Small Business set-aside to construct a new approximately 10,930 square foot warehouse facility. The new warehouse will replace existing structures and provide efficient storage and loading areas for critical supply needs. The contract period of performance is approximately 360 calendar days with the solicitation to be issued on or around July 27, 2020 and a magnitude of construction between $5 million and $10 million. Questions must be submitted in writing by the specified date.

View the file

Other files for this federal contract opportunity

Other files attached to Y1GZ--Construct Replacement Warehouse Prescott VAMC (Minor Construction), newest first.
File Type Posted
36E77620R0043 0006.docx DOCX document
Technical Questions Tracking Sheet - 09-14-2020.pdf PDF
1395.26_Revised Roof Slope Sketch.pdf PDF
Telecom Specs1.pdf PDF
36E77620R0043 0005.docx DOCX document
Monitoring and Discovery Protocol.pdf PDF
Technical Questions Tracking Sheet - 09-09-2020.pdf PDF
Construction Wage Rates - Yavapai - 08-21-2020.pdf PDF
36E77620R0043 0004.docx DOCX document
Item 70 response_Drawing-Montage Commercial Classic.pdf PDF
07 43 00 Wall and Roof Panels.pdf PDF
10 26 00 Wall Protection.pdf PDF
Item 81 response_Fire-rated Ceiling Assembly Detail.pdf PDF
Item 69 response_Drawing-Montage Commercial Classic Gate.pdf PDF
1395.26 Construct Replacement Warehouse_ASI 002 Narrative.pdf PDF
01 00 00 - General Requirements.pdf PDF
Reference C - Question 112 - 067 165-M-301 MECHANICAL SECTIONS AND ENLARGED.pdf PDF
Reference E - Question 113 - DIV 13 SPECIAL CONSTRUCTION.pdf PDF
S05 - Technical Questions Tracking Sheet TO BE PUBLISHED 9-4.pdf PDF
36E77620R0043 0003.docx DOCX document
Reference D - Question 113 - 026 165-SA-001 STRUCTURAL GENERAL NOTES.pdf PDF
Technical Questions Tracking Sheet 36E77620R0043.pdf PDF
36E77620R0043 0002.docx DOCX document
36E77620R0043 - SITE VISIT SIGN IN SHEET - 08-11-2020.pdf PDF
36E77620R0043 0001.docx DOCX document
Attachment 12 - T Drawings.pdf PDF
Attachment 10 - P Drawings.pdf PDF
Attachment 15 - Construction Wage Rates - Yavapai - 06-05-2020.pdf PDF
Copy of Attachment 14 - Division Price Breakdown.xlsx XLSX spreadsheet
Attachment 7 - F Drawings.pdf PDF
Attachment 16 - Contractor Safety _ Env Record Form.docx DOCX document
Attachment 11 - S Drawings.pdf PDF
Attachment 13 - Warehouse Building Soils Report.pdf PDF
Attachment 1 - Volume 01 Specifications REV.pdf PDF
Attachment 9 - M Drawings.pdf PDF
Attachment 4 - A Drawings.pdf PDF
Attachment 3 - Volume 03 Specifications REV.pdf PDF
Attachment 8 - G Drawings.pdf PDF
Attachment 5 - C Drawings Part II.pdf PDF
Attachment 2 - Volume 02 Specifications.pdf PDF
36E77620R0043.docx DOCX document
Attachment 5 - C Drawings Part I.pdf PDF
Attachment 17 - Prescott Site Map.pdf PDF
Show all 43

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

M/G 400A/3P

M/G 400A/3P

UE

C

PC

R

TS

T

100/3

100/3/70

100/3/70/1

100/3/CB

PP

J

GF

OR

OR

OR

AM

VM

DM

ST

KK

GFR

M

SPD

R

BAT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISH FLOOR

BIL BASIC INSULATION LEVEL

BLDG BUILDING

BPIP BOILER PLANT

INSTRUMENTATION PANEL

BRKR BREAKER

BYP BY PASS

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HZ HERTZ

A/C AIR CONDITIONING

A/E ARCHITECT/ENGINEER

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR ARMORED

CABLE

ACC ACCESSIBLE

ADDL ADDITIONAL

ADJ ADJACENT, ADJOINING

ADO AUTOMATIC DOOR OPENER

AF AMPERE FRAME OR AMP FUSE

AFC ABOVE FINISHED COUNTER, AUTOMATIC

FREQUENCY CONTROL, OR

AVAILABLE FAULT CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AH AMPERE HOUR

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

AMB OR A AMBIENT

AMP AMPERE

ARCH ARCHITECT

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

1P SINGLE POLE

1PH SINGLE-PHASE

3P THREE POLE

3PH THREE-PHASE

3W THREE WIRE

4W FOUR WIRE

P POLE

PA PUBLIC ADDRESS

PB PANELBOARD, PULL BOX, OR

PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT UNIT

PCB POLYCHLORINATED BIPHENYL

PEC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PNL PANEL

POD POWER OPERATED DAMPER

PT POTENTIAL TRANSFORMER

PTRV POWER TYPE ROOF VENTILATION

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

SCC SHORT CIRCUIT CAPACITY

SES SERVICE ENTRANCE SECTION

SD SMOKE DETECTOR

SF SQUARE FOOT (FEET)

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SURF SURFACE

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

G OR GND GROUND OR GENERATOR

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GTB GROUND TERMINAL BOX

IESNA ILLUMINATION ENGINEERING SOCIETY

OF NORTH AMERICA

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

W WATT

WH WATER HEATER

WP WEATHERPROOF

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LM LUMEN

LP LIGHT POLE

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPS

LTCP LOCAL TEMPERATURE CONTROL PANEL

LT LIGHT

LTG LIGHTING

LTG PNL LIGHTING PANEL

LTNG LIGHTNING

LV LOW VOLTAGE

XFER TRANSFER

XFMR TRANSFORMER

XP EXPLOSION PROOF

JB JUNCTION BOX

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT AMPERE

KVAH KILOVOLT AMPERE PER HOUR

KVAR KILOVOLT AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

KWHM KILOWATT HOUR METER

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MLO MAIN LUGS ONLY

MT MOUNT

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE

MVA MEGAVOLT-AMPERE

MW MEGAWATT

OC ON CENTER

OD OUTSIDE DIAMETER

OL OVERLOAD

N NEUTRAL

NA NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NS NO SCALE

NTS NOT TO SCALE

RCP REFLECTED CEILING PLAN

RCPT RECEPTACLE

REC RECESSED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

REQD REQUIRED

TC TIME CLOCK

TEL TELEPHONE

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

V VOLT

VA VOLT AMPERE

VAR VOLT AMPERE REACTIVE

VFD VARIABLE FREQUENCY DRIVE

VOLT VOLTAGE

UFD UNDERFLOOR DUCT

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

ABBREVIATIONS

A

B

C

C CONDUIT

CAP CAPACITY

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED/

CONTRACTOR INSTALLED

CF/OI CONTRACTOR FURNISHED/OWNER

CFE CONTRACTOR FURNISHED

EQUIPMENT

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

CKT BRKR CIRCUIT BREAKER

CLF CURRENT LIMITING FUSE

CLG CEILING

CMU CONCRETE MASONRY UNIT

COAX COAX CABLE

COMM COMMUNICATION

CONC CONCRETE

CONT CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CU COPPER

CU FT CUBIC FEET

DB DECIBEL OR DIRECT BURIAL

DC DIRECT CURRENT

DCP DIMMER CONTROL PANEL

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DISC DISCONNECT

DISTR DISTRIBUTION

DISTR PNL DISTRIBUTION PANEL

DN DOWN

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DRSW DOOR SWITCH

DS DISCONNECT SWITCH

DWG DRAWING

EC EMPTY CONDUIT

EG EQUIPMENT GROUND

EL ELEVATION

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMCP EMER. MONITORING CONTROL PANEL

EMER EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

ESMT EASEMENT

ETD EXISTING TO BE DEMOLISHED

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXIST EXISTING

D

E

F

G

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FABL FIRE ALARM BELL

FABX FIRE ALARM BOX

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FI FILM ILLUMINATOR

FIXT FIXTURE

FLA FULL LOAD AMPS

FLEX FLEXIBLE METALLIC CONDUIT

FLUOR FLUORESCENT

FP FIRE PROTECTION

FT FEET OR FOOT

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

H

I

J

K

L

M

N

O

P

STANDARD MOUNTING HEIGHTSANNOTATION

CIRCUITING SYMBOLS

R

S

T

U

V

W

X

CU

M100

M100

MECHANICAL OR FIRE SPRINKLER PLAN NOTE CALL OUT

PLUMBING PLAN NOTE CALL OUT

ELECTRICAL, TECHNOLOGY OR FIRE ALARM PLAN NOTE

CALL OUT

PLUMBING EQUIPMENT DESIGNATION

EQUIPMENT DESIGNATION TAG

OWNER FURNISHED, CONTRACTOR INSTALLED

EQUIPMENT DESIGNATION

NEW WORK TO EXISTING WORK CONNECTION POINT

DETAIL REFERENCE

SECTION CUT DESIGNATION

ELECTRICAL:

AUDIBLE APPLIANCES (CENTERLINE) 84"

ALARMS (TOP) 48"

ANNUNCIATOR PANELS (TOP) 48"

CLOCK OUTLETS (CENTERLINE) 84"

CONTROLS (TOP) 48"

EXIT SIGNS (WALL-MOUNTED, BOTTOM) 80"

FIRE ALARM ANNUNCIATOR PANEL (DISPLAY) 60"

FIRE ALARM BELL (EXTERIOR) 120"

FIRE ALARM CONTROL PANEL/UNIT (DISPLAY) 60"

INTERCOM (AFEA ONLY) 36"

INTERCOMS (TOP) 48"

PANELS & PANELBOARDS (TOP) 72"

PULL STATIONS (TOP) 48"

PHOTOCELLS 144"

RECEPTACLES (BOTTOM) 18"

RECEPTACLES, EXTERIOR (BOTTOM) 24"

RECEPTACLES, GARAGES (BOTTOM) 26"

RECEPTACLES IN EQUIPMENT ROOMS (TOP) 48"

REMOTE INDICATING LIGHT, EQUIPMENT ROOMS (TOP) 48"

REMOTE INDICATING LIGHT, FINISHED AREAS (TOP) CEILING

SAFETY SWITCHES & STARTERS 48"

SWITCHES (TOP) 48"

TELEPHONE/DATA/TV OUTLETS (BOTTOM) 18"

VISIBLE APPLIANCES (CENTERLINE) 84"

(AFF, AFG UNLESS NOTED OTHERWISE)

WIRING DEVICE SYMBOLS

POWER EQUIPMENT SYMBOLS

LIGHTING SYMBOLS

LP1

A1

LIGHT FIXTURE, CEILING MOUNTED

a

LIGHTING TRACK WITH TRACK LIGHT FIXTURES

LIGHT FIXTURE, POLE MOUNTED

LIGHT FIXTURE, WALL MOUNTED

EMERGENCY BATTERY PACK LIGHT FIXTURE,

WALL MOUNTED

EMERGENCY BATTERY PACK LIGHT FIXTURE,

CEILING MOUNTED

EXIT SIGN, WALL MOUNTED, FACE/ARROWS AS INDICATED

EXIT SIGN, CEILING MOUNTED, FACE/ARROWS AS INDICATED

ELECTRICAL ONE-LINE DIAGRAM SYMBOLS

EMERGENCY LIGHT FIXTURE, CEILING MOUNTED

A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT

FIXTURE SCHEDULE

a = SWITCHED BY SWITCH "a"

NL = NIGHT LIGHT

= ARROW INDICATES AIMING DIRECTION

A1E = LIGHT FIXTURE TYPE "A1E" REFER TO LIGHT

FIXTURE SCHEDULE

a = SWITCHED BY SWITCH "a"

NL = NIGHT LIGHT

A1E a

A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT

FIXTURE SCHEDULE

a = SWITCHED BY SWITCH "a"

A1 a

A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT

FIXTURE SCHEDULE

A1

A1

A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT

FIXTURE SCHEDULE

X1E

X1E

X1E = LIGHT FIXTURE TYPE "X1E" REFER TO LIGHT

FIXTURE SCHEDULE

Y1E

X1E = LIGHT FIXTURE TYPE "X1E" REFER TO LIGHT

FIXTURE SCHEDULE

Y1E

Y1E = LIGHT FIXTURE TYPE "Y1E" REFER TO

LIGHT FIXTURE SCHEDULE

Y1E = LIGHT FIXTURE TYPE "Y1E" REFER TO LIGHT

FIXTURE SCHEDULE

HOMERUN TO PANELBOARD, ARROWS INDICATE

NUMBER OF CIRCUITS, TICK MARKS INDICATE

NUMBER OF CONDUCTORS. DESIGNATIONS ARE

PANELBOARD AND CIRCUIT NUMBERS.

UNSWITCHED HOT CONDUCTORS SHOWN LEADING

NEUTRAL CONDUCTOR

NEUTRAL CONDUCTOR

SWITCHED HOT CONDUCTORS SHOWN TRAILING

GROUND CONDUCTOR

EQUIPMENT GROUNDING CONDUCTOR IN RACEWAY

ISOLATED GROUNDING CONDUCTOR IN RACEWAY

CONCEALED RACEWAY

EXPOSED RACEWAY

RACEWAY TURNING DOWN

RACEWAY TURNING UP

EQUIPMENT TERMINATION

CONCEALED RACEWAY

LIGHT FIXTURE, BOLLARDA1

A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT

FIXTURE SCHEDULE

RECEPTACLE, SIMPLEX, NEMA 5-20R, UNO

RECEPTACLE, DUPLEX, NEMA 5-20R, UNO

RECEPTACLE, DOUBLE-DUPLEX, NEMA 5-20R, UNO

RECEPTACLE, DUPLEX, CEILING MOUNTED, NEMA 5-20R, UNO

RECEPTACLE, SPECIAL PURPOSE

RECEPTACLE, TWIST-LOCK

RECEPTACLE, DUPLEX, FLOOR MOUNTED, NEMA 5-20R, UNO

RECEPTACLE, DUPLEX, DROP CORD, NEMA 5-20R, UNO

RECEPTACLE, MOUNTED 6" ABOVE COUNTER,

TYPE AS INDICATED ABOVE

RECEPTACLE DESIGNATIONS AS FOLLOWS:

C = CLOCK HANGER

E = EMERGENCY POWER

GF = GROUND FAULT CIRCUIT INTERRUPTER

IG = ISOLATED GROUND

S = SWITCHED

TR = TAMPER RESISTANT

WP = WEATHER PROOF COVER

WR = WEATHER RESISTANT

XP = EXPLOSION PROOF

SWITCH, SINGLE POLE

SWITCH DESIGNATIONS AS FOLLOWS:

2 = TWO-POLE WALL SWITCH

3 = THREE-WAY WALL SWITCH

4 = FOUR-WAY WALL SWITCH

D = DIMMER SWITCH

OS# = OCCUPANCY SENSOR WALL SWITCH, REFER

TO OCCUPANCY SENSOR SCHEDULE

P = SINGLE-POLE, SINGLE-THROW PILOT LIGHT

WALL SWITCH

K = KEYED WALL SWITCH

M = MOTOR RATED SWITCH

WP = WEATHER PROOF SWITCH AND COVER

OCCUPANCY SENSOR, CEILING MOUNTED

POWER PACK FOR LIGHTING CONTROL

JUNCTION BOX

RECEPTACLE ON EMERGENCY POWER

RECEPTACLE, ISOLATED GROUND TYPE

OS# = OCCUPANCY SENSOR WALL SWITCH, REFER

TO OCCUPANCY SENSOR SCHEDULE

MULTI-OUTLET, SURFACE RACEWAY, 24" ON CENTER,

NEMA 5-20R, UNO

SWITCHBOARD, MOTOR CONTROL CENTER OR

DISTRIBUTION PANELBOARD ON HOUSEKEEPING PAD

PANELBOARD, RECESS MOUNTED

PANELBOARD, SURFACE MOUNTED

TRANSFORMER

DISCONNECT SWITCH, NON-FUSED, 100/3 INDICATES

AMPERES/POLES, CB = CIRCUIT BREAKER TYPE

DISCONNECT SWITCH, FUSED, 100/3/70 INDICATES

AMPERES/POLES/FUSE, CB = CIRCUIT BREAKER TYPE

COMBINATION DISCONNECT SWITCH WITH MOTOR

STARTER 100/3/70/1 INDICATES AMPERES/POLES/FUSE/

NEMA STARTER SIZE, NF = NON-FUSED, CB = CIRCUIT

BREAKER TYPE

MAGNETIC MOTOR STARTER, NEMA SIZE AS NOTED,

3-POLE, UNO

CONTACTOR

PHOTOCELL

RELAY

TIME SWITCH

LOW-VOLTAGE TRANSFORMER

PUSH BUTTON, TYPE AS NOTED

LIGHTNING PROTECTION SYMBOLS

LIGHTNING PROTECTION AIR TERMINAL

LIGHTNING PROTECTION CABLE CONNECTION

LIGHTNING PROTECTION GROUND ROD

LIGHTNING PROTECTION CONDUCTOR

AUTOMATIC TRANSFER SWITCH

TYPE AND RATINGS AS INDICATED

TX#

600AF

3P

500AT

400AS

3P

225AF

275KW STANDBY

480Y/277V, 3PH, 4W

GENERATOR, SEPARATELY DERIVED

SOURCE, TYPE AND RATINGS AS INDICATED

275KW STANDBY

480Y/277V, 3PH, 4W

GENERATOR, NON-SEPARATELY DERIVED

SOURCE, TYPE AND RATINGS AS INDICATED

DRAWOUT CIRCUIT

BREAKER, RATINGS

AS INDICATED

600AF

3P

500AT

CIRCUIT BREAKER,

RATINGS AS

INDICATED

LPS-R

FUSED DISCONNECT

SWITCH, RATINGS

AS INDICATED

400AS

3P

225AF

LPS-R

COMBINATION FUSED

SWITCH AND STARTER,

RATINGS AS

PANELBOARD,

SINGLE-SECTION,

RATINGS PER

SCHEDULES

PANELBOARD,

MULTI-SECTION,

RATINGS PER

SCHEDULES

NEMA 1

AMMETER

VOLTMETER

COMBINATION DIGITAL

SHUNT-TRIP RELAY

KIRK-KEY INTERLOCK

GROUND-FAULT RELAY

UTILITY METER

RELAY

SURGE PROTECTION

AMMETER/VOLTMETER

DEVICE

AUTOMATIC TRANSFER SWITCH WITH BYPASS

TYPE AND RATINGS AS INDICATED

VARIABLE FREQUENCY

DRIVE WITH

DISCONNECT, RATINGS

GROUND CONNECTION

POTENTIAL TRANSFORMER

CURRENT TRANSFORMER

GROUND CONNECTION

WITH TEST WELL

CONTACT, OPEN

CONTACT, CLOSED

MOTOR

FEEDER TAGCAPACITOR

LIGHTNING ARRESTER

HEATER

VARIABLE FREQUENCY DRIVE WITH DISCONNECT

SWITCH 100/3/70 INDICATES AMPERES/POLES/FUSE

SIZE, NF = NON-FUSED, CB = CIRCUIT BREAKER TYPE

225A 3P

NEMA 1

INDICATED

COMBINATION CIRCUIT

BREAKER AND

STARTER, RATINGS AS

INDICATED AS INDICATED

225A 3P

UNDERGROUND ELECTRIC LINE

MULTI-SERVICE FLOOR BOX/POKE-THRU WITH POWER/DATA,

TYPE AS NOTED AND/OR SCHEDULED

CABINET, RECESS MOUNTED

CABINET, SURFACE MOUNTED

RECEPTACLE, DUPLEX, GROUND-FAULT CIRCUIT

INTERRUPTER, NEMA 5-20R, UNO

MULTI-SERVICE POWER POLE WITH POWER/DATA,

TYPE AS NOTED AND/OR SCHEDULED

200A 3P

ATS#

200A 3P

ATS#

TRANSFORMER

TX#

TRANSFORMER,

SHIELDED

S

S

INSTALLED

RECEPTACLES ABOVE COUNTERTOPS (TOP) 44"

MUSHROOM TYPE PUSH BUTTON, TYPE AS NOTED

SPD = SURGE PROTECTION DEVICE

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

F

SHEET TITLE

ARCHITECT

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

STRUCTURAL / CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH. / ELEC. / PLUMB. / TECH. ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATHE, KS 66062

(913) 829-8650

LANDSCAPE ARCHITECT

ARC STUDIOS INC.

3117 E. FLOWER STREET

TUCSON, AZ 85716

(520) 882-9655

COMMISSIONING

GLHN ARCHITECTS & ENGINEERS, INC.

2939 E. BROADWAY BLVD

TUCSON, AZ 85716

(520) 881-4546

R1 - CONSTRUCT REPLACEMENT

WAREHOUSE

ELECTRICAL LEGEND

01/06/2020 BEN ABM

500 AZ-89, PRESCOTT, AZ 86301

165-E-000

649-414

BID DOCUMENTS

Revision # Date

J

1" = 30'

903015 600

FO

F O

FO

FO

FO

FO

FO

FO

FO

SS

SS

SS

SS

SS

SS

SS

FO

FO FO

FO

FO

FO

S

DS

DS

DS

D

S

DS

DS

DS

D

SD

SDW W W W

W

W

SD

W

W

W

G G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G G

G

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

TRAILER AREATRAILER MANEUVER AREA

EXISTING PARKING LOT

DR. KENDALL WAY

UE

UE UE

UE

UE

U E

U E

U E

UE

UE

UE

UE

UEUE

UE UE UE

UE UEUE

UE UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

U E

U E

U E

UE

UE

U E

U E

U E

U E

U E

UE

UE

UE

UE

G

G

UE

ETR

ETR

ETR

ETR

ETR

ETR

ETR

ETR

ETR ETR

ETR

ETR

S4D

S4A

S4A

S4D

S4A

ETR

ETR

ETR

ETR

ETR

ETR

ETR

ETR

ETR

ETR

ETR

ETR

HH-6

(ETR)

TANKS

U E

U E

U E

U E

UE

UE

UE

UE

MH

MH

UEUE

UE

UE

U E

U E

U E

PM-39

(ETR)

PM-45

(NEW)

PM-8

(ETR)

PM-7

(ETR)

HH-9

(ETR)

W M

W M

MAIN DISTRIBUTION PANEL

(165-NDB)

UC

UE

UE

U E

U E

U E

U E

UE UE

165-E-501

(TYP.)

U C

U C

U C

U C

U C

G

G

G G

G

S

IV

A

MV

165-NL1-1

165-NL1-1

U E

U E

U E

U E

UEUEUE

U E

BF

UE

U E

U E

UE UE UE UE UE UE

S4A

U E

UE

S4A S4A

165-NH1-1

U E

U E

U E

U E

U E

U E

U E

U E

UE

UE

UE

UE

UE

U E

U E

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

F

SHEET TITLE

ARCHITECT

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

STRUCTURAL / CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH. / ELEC. / PLUMB. / TECH. ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATHE, KS 66062

(913) 829-8650

LANDSCAPE ARCHITECT

ARC STUDIOS INC.

3117 E. FLOWER STREET

TUCSON, AZ 85716

(520) 882-9655

COMMISSIONING

GLHN ARCHITECTS & ENGINEERS, INC.

2939 E. BROADWAY BLVD

TUCSON, AZ 85716

(520) 881-4546

R1 - CONSTRUCT REPLACEMENT

WAREHOUSE

ELECTRICAL SITE PLAN

01/06/2020 BEN ABM

500 AZ-89, PRESCOTT, AZ 86301

165-ES-101

649-414

BID DOCUMENTS

1" = 30'-0"

ELECTRICAL SITE PLAN

N

GENERAL NOTES:

1 COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER'S

REPRESENTATIVE.

2 COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES. VERIFY

ALL EXISTING CONDITIONS BEFORE THE START OF WORK.

3 SEE SHEET 165-G-001 FOR ADDITIONAL INFORMATION REGARDING

SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK ON EXISTING

EQUIPMENT AND IN EXISTING BUILDINGS TO MINIMIZE DISRUPTION OF

SERVICES.

4 DRAWINGS ARE DIAGRAMMATIC ONLY AND REPRESENT THE GENERAL SCOPE

OF WORK. REVIEW THE GENERAL NOTES, SPECIFICATIONS AND PLANS FOR

ADDITIONAL REQUIREMENTS THAT MAY NOT BE SPECIFICALLY CALLED OUT IN

THIS PORTION OF THE CONSTRUCTION DOCUMENTS. NOTIFY THE

CONTRACTING OFFICER'S REPRESENTATIVE (COR) OF ANY CONFLICTS OR

DISCREPENCIES PRIOR TO SUBMISSION OF BID.

5 DRAWINGS AND SPECIFICATIONS GOVERN WHERE THEY EXCEED CODE

REQUIREMENTS.

6 UTILITIES PRESENTED ON THESE DRAWINGS ARE SHOWN BASED ON

THE BEST AVAILABLE INFORMATION. FIELD VERIFY THE EXACT

LOCATIONS IN THE FIELD PRIOR TO COMMENCING CONSTRUCTION.

CONTRACTOR SHALL NOTIFY LOCAL UTILITY LOCATING SERVICES AT

LEAST 48 HOURS BEFORE PROCEEDING WITH ANY EXCAVATION.

7 DAMAGE TO ANY EXISTING UTILITIES SHALL BE REPAIRED IN ACCORDANCE

WITH THE VA'S STANDARD CONSTRUCTION SPECIFICATIONS AT NO

ADDITIONAL COST.

8 TAKE NECESSARY PRECAUTIONS TO PROTECT ROOT SYSTEMS OF SHRUBS,

PLANTS, AND TREES ALONG THE AREA OF EXCAVATION.

9 DISPOSE OF ALL DEMOLISHED MATERIAL OFF-SITE.

ELECTRICAL PLAN NOTES

1 PROVIDE NEW 500KVA TRANSFORMER AND TRANSFORMER

HOUSEKEEPING PAD. PROVIDE PAD DIMENSIONS PER MANUFACTURER'S

RECOMMENDATIONS. PROVIDE GROUND ROD WITHIN TRANSFORMER

PRIMARY CABINET OPENING AND #2/0 COPPER GROUND CONNECTION

FROM ROD TO #2/0 COPPER GROUND RING WITH (2) GROUND RODS AT

OPPOSITE CORNERS. REFER TO ELECTRICAL ONE-LINE DIAGRAM, SHEET

165-E-601 FOR ADDITIONAL INFORMATION.

2 PROVIDE NEW CONCRETE-ENCASED DUCT BANK AND FEEDERS FROM

NEW TRANSFORMER TO EXISTING TRANSFORMER AS INDICATED ON

DETAIL 1, SHEET 165-E-501 AND ELECTRICAL ONE-LINE DIAGRAM, SHEET

165-E-601.

3 PROVIDE POWER TO GATE OPERATOR. COORDINATE EXACT

REQUIREMENTS WITH GATE MANUFACTURER.

4 COORDINATE EXACT ROUTING AND BURY DEPTH OF NEW MEDIUM

VOLTAGE DUCT BANK WITH EXISTING BURIED UTILITIES. MAINTAIN

MINIMUM BURY DEPTH AS NOTED IN THE DUCT BANK DETAIL.

PP

PP

TC

PP

PP

PP

PP

A

B

C

D

1 3

PLOTTING

WAREHOUSE

WRAPPING

STORAGE (AMMUNITION)

STORAGE (SHRED)

A1D

A1D

A1D A1D

F4F1

OS1

RC1

W1E

W1E W1E

W1

W1

W1E

W1E

D1

D1E

D1

D1

X1E

F1

F1

F1 F1

T T T

W2 W2 W2

T

T

RC1

OS1

T T

4 5

F

OS1

OS1

D1D1E

G1

LV1

D1 D1

E

165-NH1-1

X1E

W1

HAC

OS1

WORKSPACE

MECHANICAL

STORAGE (FLAM.)

A1D

A1D

A1D

RC1

LVD

IT ROOM

ELECTRICAL

SECURE STOR.

CORRIDOR

CORRIDOR

D1E

D1

D1E

D1

WALK-IN REF.

BREAK ROOM

SV OFFICE

OS2

OS2

A1D

A1D

LVOD

RC1

A1D

RC1

LVOD

F1E

F1E

F1E

F1E

OS1

W1

165-NH1-1

W1

W1W1W1

165-NH1-1

165-NH1-1

P1D

P1DEP1DP1DE

P1D

P1DE P1D P1DE P1D

P1DE

P1DP1DE

P1DP1DE

P1DP1DE

P1D

PS PS

X1EX1E

C1

165-NH1-1

A1D

F1E F1E F1E F1E

UNISEX TOILET

UNISEX TOILET

F1 F1

RC1

V1

V1

LV1

OS1

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

F

SHEET TITLE

ARCHITECT

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

STRUCTURAL / CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH. / ELEC. / PLUMB. / TECH. ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATHE, KS 66062

(913) 829-8650

LANDSCAPE ARCHITECT

ARC STUDIOS INC.

3117 E. FLOWER STREET

TUCSON, AZ 85716

(520) 882-9655

COMMISSIONING

GLHN ARCHITECTS & ENGINEERS, INC.

2939 E. BROADWAY BLVD

TUCSON, AZ 85716

(520) 881-4546

R1 - CONSTRUCT REPLACEMENT

WAREHOUSE

ELECTRICAL LIGHTING

FIRST FLOOR PLAN

01/06/2020 BEN ABM

500 AZ-89, PRESCOTT, AZ 86301

165-EL-101

649-414

BID DOCUMENTS

1/8" = 1'-0"

ELECTRICAL LIGHTING

FIRST FLOOR PLAN

N

ELECTRICAL PLAN NOTES

1 REFER TO DETAIL 10, SHEET 165-E-501 FOR WIRING DIAGRAM OF

ALL TYPICAL ROOM CONTROLLERS WITH SWITCHES, OCCUPANCY

SENSORS AND DAYLIGHT SENSORS.

2 REFER TO DETAIL 10, SHEET 165-E-501 FOR WIRING DIAGRAM OF

ALL TYPICAL ROOM CONTROLLERS WITH SWITCHES, OCCUPANCY

SENSORS AND DAYLIGHT SENSORS. LOCATE CONTROLLER IN

ADJACENT ACCESSIBLE CEILING.

3 PROVIDE RIGID METAL CONDUIT TO LIGHT FIXTURE WITHIN

FLAMMABLE STORAGE ROOM AND TO LIGHT SWITCH. ROUTE

CONDUIT OUT THROUGH TOP OF ROOM AND PROVIDE SEAL-OFF

FITTING BEFORE EXTENDING TO LIGHT SWITCH. DO NOT ROUTE

ANY OTHER CIRCUITS THROUGH THIS ROOM.

4 CIRCUIT TO EXIT SIGNS SHALL BE UNSWITCHED, TAKEN OFF

AHEAD OF THE POWER PACK.

GENERAL NOTES:

1 COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER'S

REPRESENTATIVE.

2 COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES. VERIFY

ALL EXISTING CONDITIONS BEFORE THE START OF WORK.

3 SEE SHEET 165-G-001 FOR ADDITIONAL INFORMATION REGARDING

SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK ON

EXISTING EQUIPMENT AND IN EXISTING BUILDINGS TO MINIMIZE

DISRUPTION OF SERVICES.

J J J

FACP

J

A

B

C

D

1 3

WAREHOUSE

WRAPPING

STORAGE (SHRED)

114 STORAGE (FLAM.)

STORAGE (AMMUNITION)

+48"

+48" +48" +48"

+48" +48"

+48"+48"

+48"

WP/WR

WP/WR

WP/WRWP/WR

+48"

+48"

1 1

+48"

+48"

WP/WR

WP/WR

WP/WR

165-NL1-1

165-NL1-1

165-NH1-1

9,11,13

165-NDB

+48"

165-NH1-1

2,4,6

60/3

165-NH1-1

8,10,12

60/3

165-NH1-1

14,16,18

60/3

165-NH1-1

20,22,24

60/3

165-NL1-1

165-NL1-1

165-NL1-1

4 165-NL1-1

165-NL1-1

30/3/3R

+48"

4 5

F

165-NL1-1

165-NL1-1

165-NL1-1

165-NL1-1

E

165-NL1-1

165-NL1-1

165-NL1-1

DIV. 23

+48"

165-EP-101

2SECURE STOR.

WALK-IN REF.

RECYCLING AREA

+40"

165-NL1-1

165-NL1-1

165-NL1-1

165-NL1-1

165-NL1-1

PLOTTING

HAC

UNISEX TOILET

UNISEX TOILET

WORKSPACE

IT ROOM

ELECTRICAL

165-NL1-1

57,59,61

165-NL1-1

38,40,42

165-NL1-1

32,34,36

SV OFFICE

BREAK ROOM

MECHANICAL

SPD

SPD

SPD

SPD

165-NL1-1

165-NL1-1

165-NL1-1

165-NL1-1

+48"

165-NL1-1

+40"

165-NL1-1

+40"

165-NL1-1

+40"

165-NL1-1

CU-DS

CU-DS

CU-ARU

AHU

CU-AHU

30/2/3R

165-NL1-1

35,37

30/2/3R

30/2/3R

MM DS

DS

165-NL1-1

48,50

165-NL1-1

44,46

165-NL1-1

48,50

165-NL1-1

44,46

(PART) (PART)

165-NDB

165-NL1-1

165-NL1-1

165-NL1-1

165-NL1-1

165-NL1-1

165-NL1-1

SPD

ARU

RP-1

WH-1 ET-1

165-NL1-1

M

165-NL1-1

M

165-NL1-1

165-NL1-1

165-NL1-1

CORRIDOR

CORRIDOR

WP/WR

DIV. 23

AC

AC

AC

AC

M

165-NL1-1

165-NL1-1

E

165-NL1-1

165-NH1-1

XFMR

165-NL2-1

165-NDB

165-NL1-2

165-NL1-2

2165-NL1-2

ELECTRICAL

IT ROOM

IDS

IDS

PACS

PACS

MATV

165-NL1-2

165-NL1-2

165-NL1-2

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

F

SHEET TITLE

ARCHITECT

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

STRUCTURAL / CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH. / ELEC. / PLUMB. / TECH. ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATHE, KS 66062

(913) 829-8650

LANDSCAPE ARCHITECT

ARC STUDIOS INC.

3117 E. FLOWER STREET

TUCSON, AZ 85716

(520) 882-9655

COMMISSIONING

GLHN ARCHITECTS & ENGINEERS, INC.

2939 E. BROADWAY BLVD

TUCSON, AZ 85716

(520) 881-4546

R1 - CONSTRUCT REPLACEMENT

WAREHOUSE

ELECTRICAL POWER

FIRST FLOOR PLAN

01/06/2020 BEN ABM

500 AZ-89, PRESCOTT, AZ 86301

165-EP-101

649-414

BID DOCUMENTS

1/8" = 1'-0"

ELECTRICAL POWER FIRST FLOOR PLAN

N

# ELECTRICAL PLAN NOTES

1 PROVIDE RECEPTACLE FOR COILING OVERHEAD DOOR.

COORDINATE EXACT MOUNTING HEIGHT WITH GARAGE DOOR

INSTALLER.

2 PROVIDE POWER TO, AND INSTALL, HYDRAULIC LIFT CONTROL BOX.

COORDINATE EXACT LOCATION OF CONTROL BOX WITH HYDRAULIC

LIFT INSTALLER.

3 PROVIDE POWER TO HYDRAULIC LIFT PUSH BUTTON FURNISHED BY

HYDRAULIC LIFT MANUFACTURER.

4 PROVIDE WALL MOUNTED REACH TRUCK CHARGER WITH SB350

CONNECTOR. COORDINATE EXACT REQUIREMENTS WITH

FORKLIFT MANUFACTURER. COORDINATE EXACT MOUNTING

HEIGHT WITH GOVERNMENT.

5 PROVIDE NEMA L16-20R TWIST LOCKING RECEPTACLE.

COORDINATE EXACT REQUIREMENTS WITH BALER

MANUFACTURER. COORDINATE EXACT MOUNTING HEIGHT WITH

GOVERNMENT.

6 COORDINATE EXACT MOUNTING HEIGHT WITH INTERCOM MASTER

STATION. REFER TO DETAIL 1, SHEET 165-TI-101 FOR ADDITIONAL

INFORMATION.

7 PROVIDE POWER AND DISCONNECTING MEANS TO

REFRIGERATOR/REEFER. COORDINATE EXACT REQUIREMENTS

WITH MANUFACTURER.

8 PROVIDE 12"x24"xAPPROXIMATELY 5' H FLOOR-MOUNTED CHANNEL

STRUT FRAME FOR EQUIPMENT RECEPTACLES.

9 PROVIDE POWER FOR INTERCOM DEVICE. COORDINATE EXACT

LOCATION WITH DIVISION 27 CONTRACTOR.

GENERAL NOTES:

1 COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER'S

REPRESENTATIVE.

2 COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES. VERIFY

ALL EXISTING CONDITIONS BEFORE THE START OF WORK.

3 SEE SHEET 165-G-001 FOR ADDITIONAL INFORMATION REGARDING

SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK ON

EXISTING EQUIPMENT AND IN EXISTING BUILDINGS TO MINIMIZE

DISRUPTION OF SERVICES.

Revision # Date

1/4" = 1'-0"

ELECTRICAL ROOM 107 & IT ROOM 106

PARTIAL FLOOR PLAN

N

A

B

C

D

1 32

165-E-502

165-E-502

165-E-502

165-E-502

(TYP.)

(TYP.)

165-E-502

(TYP.)

4 5

F

165-E-502

165-E-502

(TYP.)

(TYP.)

165-E-502

(TYP.)

165-E-502

(TYP.)

E

RECYCLING AREA

EF

EF

EF

EF

EF

EF

165-NL1-1

165-NL1-1

IH

165-NL1-1

165-NL1-1

165-NH1-1

15,17,19

165-NH1-1

21,23,25

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

F

SHEET TITLE

ARCHITECT

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

STRUCTURAL / CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH. / ELEC. / PLUMB. / TECH. ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATHE, KS 66062

(913) 829-8650

LANDSCAPE ARCHITECT

ARC STUDIOS INC.

3117 E. FLOWER STREET

TUCSON, AZ 85716

(520) 882-9655

COMMISSIONING

GLHN ARCHITECTS & ENGINEERS, INC.

2939 E. BROADWAY BLVD

TUCSON, AZ 85716

(520) 881-4546

R1 - CONSTRUCT REPLACEMENT

WAREHOUSE

ELECTRICAL ROOF PLAN

01/06/2020 BEN ABM

500 AZ-89, PRESCOTT, AZ 86301

165-EP-102

649-414

BID DOCUMENTS

1/8" = 1'-0"

ELECTRICAL ROOF PLAN

N

GENERAL NOTES:

1 COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER'S

REPRESENTATIVE.

2 COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES. VERIFY

ALL EXISTING CONDITIONS BEFORE THE START OF WORK.

3 SEE SHEET 165-G-001 FOR ADDITIONAL INFORMATION REGARDING

SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK ON

EXISTING EQUIPMENT AND IN EXISTING BUILDINGS TO MINIMIZE

DISRUPTION OF SERVICES.

ELECTRICAL PLAN NOTES:

1 DISCONNECT INTEGRAL TO UNIT.

Switch

LMRC-211

Dimming Room

Controller Neutral Wht

Unswitched

Hot Blk 120/277 Grn

Earth Ground

Normal Lights

V io

G ry

Vio Gry

Class 2 0-10 Volt Control Wiring

Leg #1

LMDM-101

WATTSTOPPER

LMLS-400

Photosensor

LMDC-100

CH1PC CH2 CH3 CH4 COM COM 24V GND

REMOTE OVERRIDE

(3) #12, (1)#12G, 3/4"C

TYPICAL

LOW-VOLTAGE PHOTOCELL.

REFER TO PLANS FOR

LOCATION.

CH1

NC

CH3

CH4

N

H

O

C

N

NO

CH2

120 - 277V

C

O

TIMESWITCH

CH2CH1 CH3 CH4

C

NC

NO

C

NC

NO

C

NC

NO

C

165-NH2-1 - 11

NOTES:

1. PROVIDE 365/7 DAY ASTRONOMICAL,

4-CHANNEL LIGHTING CONTROLLER.

PROVIDE 120V OR 277V POWER FROM

UNSWITCHED PORTION OF A CONTROLLED

LIGHTING CIRCUIT.

2. PROVIDE 30A, MECHANICALLY HELD,

ELECTRICALLY CONTROLLED LIGHTING

CONTACTORS WITH NUMBER OF POLES AS

SHOWN.

CONTACTOR C1

SET CHANNEL 1, "BUILDING

PERIMETER" FOR PHOTOCELL

ON, TIMESWITCH OFF AND

TIMESWITCH ON, PHOTOCELL

OFF FOR OPERATION OF

LIGHTS FOR EVENING AND

MORNING HOURS.

COORDINATE EXACT TIMES

WITH OWNER.

305mm m m

LINE SIDES OF EXCAVATION

WITH 13.6 KG (30 LBS.) FELT

PAPER

PULLBOX (SEE SPECIFICATIONS)

FINISHED PAVING

CLEAN 19mm (3/4")

CRUSHED ROCK

CONDUIT(S) WITH BELL

ENDS (TYP). SIZE,

QUANTITY AND WIRING

AS INDICATED ON PLANS

(4) CONCRETE BRICKS

51mmx203mmx406mm

(2"x8"x16")

(12")

(1

V

A R

IE

S

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS

AND USING THE RECOMMENDED MOUNTING HARDWARE.

DRYWALL BORDER

LUMINAIRE.

REFER TO

SCHEDULE

CEILING CROSS BEAM

GYPSUM BOARD

CEILING CROSS BEAM

LUMINAIRE MANUFACTURER'S

MOUNTING HARDWARE

REFER TO SPECIFICATION SECTION

26 51 00

LUMINAIRE.

REFER TO

SCHEDULE

GYPSUM BOARD (TYP)

CEILING MAIN BEAM

FIXTURE WHIP FROM

JUNCTION BOX

(1829mm (6') LONG

MAX.)

3 TWIST MINIMUM

(TYP)

LUMINAIRE SUSPENSION

WIRES REFER TO

SPECIFICATION

SECTION 26 51 00

DRYWALL CEILING

CROSS TEE, TYP.

HANGER WIRE AND MOUNTING

CHANNEL ATTACHED TO STRUCTURE

REFER TO SPECIFICATION SECTION

26 51 00

CEILING MAIN

BEAM.

DRYWALL CEILING

CROSS TEE, TYP.

GYPSUM

BOARD

WIRE TIE THROUGH

MOUNTING CHANNEL &

CROSS BEAM, TYP.

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS

AND USING THE RECOMMENDED MOUNTING HARDWARE.

LOCKING SQUARE

WASHER & NUT

6.35mm (1/4") SCREW

JUNCTION BOX

INTEGRAL GALVANIZED LIPPED

STEEL MOUNTING CHANNEL

FIXTURE WHIP FROM JUNCTION BOX

(1829mm (6') LONG MAX)

CEILING HANGER WIRE

ARCHITECTURAL

CEILING GRID

HANGER WIRE AND MOUNTING

CHANNEL ATTACHED TO STRUCTURE

REFER TO SPECIFICATION SECTION

26 51 00

ARCHITECTURAL

CEILING GRID

ACOUSTICAL

CEILING

TILE (TYP)

ARCHITECTURAL

CEILING GRID

WIRE TIE THROUGH

MOUNTING CHANNEL &

CROSS BEAM, TYP.

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS

AND USING THE RECOMMENDED MOUNTING HARDWARE.

LOCKING SQUARE

WASHER & NUT

6.35mm (1/4") SCREW

JUNCTION BOX

INTEGRAL GALVANIZED LIPPED

STEEL MOUNTING CHANNEL

FIXTURE WHIP FROM JUNCTION BOX

(1829mm (6') LONG MAX)

CEILING HANGER WIRE

INTEGRAL

GALVANIZED

LIPPED STEEL

MOUNTING

CHANNEL

WASHER &

LOCKNUT

9.52mm (3/8") MIN

GALVANIZED THREADED

ROD, TYP.

LOCKING SQUARE

WASHER & LOCKNUT

LENGTH AS REQUIRED

GENERAL NOTES:

1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING CHANNEL

LONGER THAN 915mm (36") SHALL BE INSTALLED WITH A CENTER

SUPPORT ROD.

2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED

METHOD PER SPECIFICATION 26 05 33, RACEWAY AND BOXES

FOR ELECTRICAL SYSTEMS. FIELD VERIFY EXACT CONDITIONS.

3. FOR TRAPEZE INSTALLATIONS IN SEISMIC AREAS REFER TO

SPECIFICATION SECTION 13 05 41, SEISMIC RESTRAINT

REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.

REFER TO PLANS FOR

QUANTITY & SIZE OF

CONDUITS

INTEGRAL

GALVANIZED

LIPPED STEEL

MOUNTING

CHANNEL

CONDUIT CLAMP. SIZE

AS REQUIRED

1. CONCRETE SHALL BE 2000 P.S.I. @ 28 DAYS, OR AS SPECIFIED.

2. PROVIDE #4 REINFORCING RODS ON TOP AND BOTTOM OF DUCTS WHEN

CROSSING OR PLACED IN ROADWAYS.

3. MINIMUM COVER TO TOP OF ENVELOPE SHALL BE 610mm (24") OR AS

OTHERWISE SPECIFIED IN SECTION 26 05 41.

4. PROVIDE MINIMUM 152mm (6") SPACE BETWEEN POWER AND

TELECOMMUNICATION DUCTS. INCREASE SIZE AS REQUIRED.

5. INNERDUCT QUANTITY AND SIZE AS INDICATED ON PLANS.

76mm 3"

76mm 3"

76mm 3" m m m m

4-WAY DUCT LINE

76mm

76mm m m

3"

3"

76mm

3" m m m m

WIRE TIE OR SCREW

BAR HANGER TO CROSS

BEAM TYP.

CEILING MAIN

BEAM

CEILING

CROSS BEAM

FIXTURE WHIP FROM

JUNCTION BOX (1829mm (6')

LONG MAX)

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS

AND USING THE RECOMMENDED MOUNTING HARDWARE.

RECESSED CAN

LUMINAIRE

CEILING BEAM

RECESSED CAN

LUMINAIRE

REFER TO

SCHEDULE.

GYPSUM

BOARD (TYP)

LUMINAIRE

BAR HANGERS

CEILING HANGER

WIRE, TYP.

LUMINAIRE SUSPENSION WIRES

REFER TO SPECIFICATION SECTION 26 51 00

(3

FINISHED GRADE

CONCRETE BASE &

REINFORCING STEEL,

SEE NOTE BELOW.

25mm (1") EMPTY

CONDUIT WITH CAP

(WHERE SHOWN ON

PLANS)

#4 BARE COPPER GROUND

6069mm(20'-0") COILED

BELOW BASE

GENERAL NOTES:

1. BACKFILL, CONCRETE, REINFORCING STEEL, AND ANCHOR BOLTS ARE

SHOWN FOR REFERENCE ONLY. STRUCTURAL DESIGN IS SHOWN ON

STRUCTURAL DRAWINGS.

2. REFER TO SPECIFICATION SECTION 26 56 00 FOR MOUNTING AND

LEVELING REQUIREMENTS.

(2

UNDISTURBED SOIL OR

SELECT BACKFILL

COMPACTED, SEE NOTE

BELOW.

PVC CONDUIT ADAPTER

COUPLING

RIGID STEEL CONDUIT

PVC CONDUIT

ANCHOR BOLTS PER POLE

MANUFACTURER'S REQUIREMENTS

WITH LEVELING NUTS ABOVE &

BELOW BASE PLATE

LIGHT POLE PER LIGHT

FIXTURE SCHEDULE

2-PIECE BOLT COVER PLATE.

POLE GROUNDING STUD

76x127mm (3"x5") REINFORCED

HAND HOLE WITH TAMPER

RESISTANT SCREWS. PROVIDE

IN-LINE SCREW-TYPE FUSE

HOLDER(S) WITH FUSE(S).

m m M

IN

m m M

IN

TOP OF HANDLE

6'-6" AFF MAXIMUM

4'-0" +/- AFF

FRONT VIEWSIDE VIEW

DISCONNECT SWITCH, CIRCUIT

BREAKER ENCLOSURE, OR

MOTOR CONTROLLER

CHANNEL STRUT POST BASE W

(4) 1/4" EXPANSION ANCHORS.

(TYPICAL)

PROVIDE RIGID CONDUIT TO

MECHANICAL/PLUMBING

EQUIPMENT. CONVERT TO

FLEXIBLE CONDUIT WITH BOND

WIRE FOR FINAL CONNECTION TO

EQUIPMENT.

FLOOR

STRUCTURAL CEILING

CHANNEL STRUT SUPPORT

FRAME.

1'-7" (MIN.)

OPTION 3: CHANNEL STRUT

ANGLE BRACKET SUPPORT

FOR EACH SUPPORT LEG WITH

1/2" FLOOR EXPANSION

ANCHOR.

PROVIDE RIGID CONDUIT BACK

TO ELECTRICAL SOURCE.

NOTE:

1. DISCONNECT SWITCHES, CIRCUIT BREAKER ENCLOSURES, MOTOR CONTROLLERS & VARIABLE FREQUENCY DRIVES, AND CONTROL CABINETS MAY BE DIRECTLY MOUNTED TO STRUCTURAL WALLS, OR TO MECHANICAL EQUIPMENT WHEN PERMITTED BY THE MECHANICAL EQUIPMENT MANUFACTURER AND WHERE IT DOES NOT BLOCK ACCESS OR OPERATION OF THE EQUIPMENT. WHERE A SUITABLE STRUCTURAL WALL IS NOT AVAILABLE, PROVIDE SUPPORT FRAME AND CONNECT THE SUPPORT FRAME WITH A MINIMUM OF (4) POINTS OF CONTACT TO THE BUILDING STRUCTURE TO PROVIDE A RIGID ASSEMBLY. OPTION 1, 2, OR 3 MAY BE UTILIZED TO PROVIDE THE ADDITIONAL (2) POINTS OF CONTACT IN ADDITION TO

THE (2) POINTS OF CONTACT AT THE FLOOR.

OPTION 1: EXTEND CHANNEL

STRUT FRAME TO STRUCTURAL

CEILING AND CONNECT TO STEEL

STRUCTURE OR CONCRETE

SLAB.

S T

R U

C T

U R

A L W

A L L

OPTION 2: PROVIDE CHANNEL

STRUT FRAME TO WALL AND

CONNECT TO STRUCTURE OF

WALL.

1. DAYLIGHT SENSORS SHALL CONTROL ALL LIGHT FIXTURES LOCATED WITHIN THE DAYLIGHT ZONES OF THE WINDOWS. FIXTURES

SHALL AUTOMATICALLY DIM BASED ON AMOUNT OF DAYLIGHT.

2. OCCUPANCY SENSORS SHALL CONTROL ALL LIGHTS WITHIN THE SPACE.

3. SWITCH $-LVOD SHALL PROVIDE AUTOMATIC OFF, MANUAL ON AND DIMMING CONTROL OF ALL FIXTURES WITHIN THE SPACE.

1. REFER TO OCCUPANCY SENSOR AND SWITCH SCHEDULE FOR ADDITIONAL INFORMATION. COMPONENTS SHOWN ARE FOR BASIS OF DESIGN MANUFACTURER. FOR OTHER MANUFACTURERS, PROVIDE A COMPLETE AND FUNCITIONING SYSTEM.

2. NOT ALL LIGHT FIXTURES, OCCUPANCY SENSORS, DAY LIGHT SENSORS, AND LIGHT SWITCH CONTROL DEVICES ARE SHOWN, REFER TO PLANS FOR LOCATIONS OF ALL DEVICES. PROVIDE WIRING BETWEEN ALL FIXTURES AND DEVICES FOR A COMPLETE AND FUNCTIONING SYSTEM. GROUND CONDUCTOR NOT SHOWN, PROVIDE GROUND CONDUCTOR IN ALL RACEWAYS.

NOTE:

SEQUENCE OF OPERATIONS:

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

F

SHEET TITLE

ARCHITECT

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

STRUCTURAL / CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH. / ELEC. / PLUMB. / TECH. ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATHE, KS 66062

(913) 829-8650

LANDSCAPE ARCHITECT

ARC STUDIOS INC.

3117 E. FLOWER STREET

TUCSON, AZ 85716

(520) 882-9655

COMMISSIONING

GLHN ARCHITECTS & ENGINEERS, INC.

2939 E. BROADWAY BLVD

TUCSON, AZ 85716

(520) 881-4546

R1 - CONSTRUCT REPLACEMENT

WAREHOUSE

ELECTRICAL DETAILS

01/06/2020 BEN ABM

500 AZ-89, PRESCOTT, AZ 86301

165-E-501

649-414

BID DOCUMENTS

NOT TO SCALE

UNDERGROUND CONCRETE PULLBOX- TURF AREAS

NOT TO SCALE

LUMINAIRE MOUNTING - GYPBOARD CEILING

NOT TO SCALE

EXIT SIGN MOUNTING - GYPBOARD CEILING

NOT TO SCALE

EXIT SIGN MOUNTING - LAY - IN CEILING

NOT TO SCALE

CONDUIT TRAPEZE MOUNTING DETAIL

NOT TO SCALE

DUCT BANK DETAIL

NOT TO SCALE

DOWNLIGHT MOUNTING - GYPBOARD CEILING

NOT TO SCALE

POLE BASE DETAIL- TURF AREAS

NOT TO SCALE

ELECTRICAL EQUIPMENT MOUNTING DETAIL

NOT TO SCALE

TYPICAL ROOM CONTROLLER - LIGHTING CONTROL WIRING DIAGRAM

NOT TO SCALE

TIME SWITCH - LIGHTING CONTROL DIAGRAM

BONDING CONDUCTOR

PIPE BONDING STRAP

CLAMP, SIZE AS REQUIRED

FOR PIPE

LIGHTNING PROTECTION

CONDUCTOR

UNIVERSAL PARALLEL

CABLE SPLICER

BUTT END STRAIGHT

CABLE SPLICER

PARALLEL CABLE

SPLICER

LIGHTNING PROTECTION

BONDING CONDUCTOR

TO BONDS

CABLE TO SURFACE

EXOTHERMIC CONNECTION

(FIELD INSTALLED), GRIND TO

BARE STEEL SURFACE

MAIN LIGHTNING CONDUCTOR

TO GROUND ROD

STEEL COLUMN

CABLE TO SURFACE

EXOTHERMIC CONNECTION

(FIELD INSTALLED), GRIND TO

BARE STEEL SURFACE

TO THROUGH ROOF

CONNECTION

JGW

M

IN

IM

U

M

24"MINIMUM

W

ALL

GRADE

GROUND ROD

CABLE TO GROUND

ROD CLAMP

1" SCHEDULE 40 PVC

RACEWAY

LIGHTNING PROTECTION

CONDUCTOR

M

IN

IM

U

M

PARAPET WALL

ROOF

AIR TERMINAL

ADHESIVE TYPE AIR TERMINAL

BASE MOUNTED VERTICALLY

LIGHTNING PROTECTION

CONDUCTOR

ADHESIVE STYLE

CABLE FASTENER

ADHESIVE STYLE CABLE

FASTENER MOUNTED TO

ROOF

LIGHTNING PROTECTION

CONDUCTOR

CABLE FASTENER WITH

STAINLESS STEEL

HARDWARE, CAULK

PENETRATIONS

BONDING PLATE MOUNTED

WITH STAINLESS STEEL

FASTENERS, CAULK

PENETRATIONS

M

IN

IM

U

M

LIGHTNING PROTECTION

CONDUCTOR

FLAT SURFACE AIR TERMINAL

BASE MOUNTED WITH

STAINLESS STEEL FASTENERS,

CAULK PENETRATIONS

TOP OF EQUIPMENT

AIR TERMINAL

THROUGH ROOF CABLE

CONNECTING ASSEMBLY

ROOF PENETRATION FLASHING

BOOT

LIGHTNING PROTECTION

CONDUCTOR

LIGHTNING PROTECTION

CONDUCTOR

M

IN

IM

U

M

ADHESIVE STYLE

CABLE FASTENER

LIGHTNING PROTECTION

CONDUCTOR

ADHESIVE TYPE AIR TERMINAL

AIR TERMINAL

FLAT ROOF

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

F

SHEET TITLE

ARCHITECT

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

STRUCTURAL / CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH. / ELEC. / PLUMB. / TECH. ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATHE, KS 66062

(913) 829-8650

LANDSCAPE ARCHITECT

ARC STUDIOS INC.

3117 E. FLOWER STREET

TUCSON, AZ 85716

(520) 882-9655

COMMISSIONING

GLHN ARCHITECTS & ENGINEERS, INC.

2939 E. BROADWAY BLVD

TUCSON, AZ 85716

(520) 881-4546

R1 - CONSTRUCT REPLACEMENT

WAREHOUSE

ELECTRICAL DETAILS

01/06/2020 BEN ABM

500 AZ-89, PRESCOTT, AZ 86301

165-E-502

649-414

BID DOCUMENTS

NOT TO SCALE

VENT THRU ROOF DETAIL

NOT TO SCALE

SPLICERS/CONDUCTORS

NOT TO SCALE

COLUMN GROUNDING DETAIL

NOT TO SCALE

DOWNLEAD TO GRND ROD

NOT TO SCALE

TYPICAL PARAPET AIR TERMINAL

NOT TO SCALE

MECHANICAL UNIT BONDING TERMINAL

NOT TO SCALE

AIR TERMINAL ON EQUIPMENT

NOT TO SCALE

TYPICAL THROUGH ROOF CONNECTION

NOT TO SCALE

TYPICAL FLAT ROOF AIR TERMINAL

LV1

LVOD

OS1

T

PS

OS1

OS2

RC1

PP

WALL SWITCH SENSOR REQUIRES NEUTRAL CONDUCTOR FOR OPERATION1.

NOTES:

DO NOT INSTALL LINE VOLTAGE SENSORS ON GFCI PROTECTED CIRCUITS.E.

ALL SENSORS SHALL HAVE AN ADJUSTABLE TIME DELAY RANGE OF 30 SECONDS TO 30 MINUTES, UNLESS NOTED OTHERWISE.D.

VERIFY COLOR(S) FOR WALL SWITCHES WITH ARCHITECT.C.

PROVIDE ALL SENSORS FROM SAME MANUFACTURER.B.

SENSOR LAYOUT BASED ON COVERAGE PATTERNS OF MANUFACTURERS INDICATED ABOVE. ADJUSTS QUANTITIES AND LOCATIONS FOR ALTERNATE MANUFACTURERS.A.

GENERAL NOTES:

SINGLE-POLE, AUTO-OFF IN-WALL TIMER WITH ADJUSTABLE TIMING

FROM 5 MINUTES TO 12 HOURS AND VISUAL AND AUDIBLE WARNING.

MINUTES

MANUALN/A120/277VWATTSTOPPER: TS-400-W

LINE VOLTAGE, 1-BUTTON DUAL TECHNOLOGY OCCUPANCY LIGHT

SWITCH.

MINUTES

MANUALN/A120/277VWATTSTOPPER: DW-100-U

LOW VOLTAGE, 2-BUTTON DIMMING DIGITAL DUAL TECHNOLOGY

OCCUPANCY SENSOR LIGHT SWITCH COMPATIBLE WITH DIGITAL ROOM

CONTROLLER WITH CAT5E NETWORKING.

MINUTES

MANUALN/A

24V DC

INPUT

WATTSTOPPER: LMDW-102-U

LOW VOLTAGE, 1-BUTTON DIGITAL LIGHT SWITCH COMPATIBLE WITH

DIGITAL ROOM CONTROLLER WITH CAT5E NETWORKING.

N/AMANUALN/A

24V DC

INPUT

WATTSTOPPER: LMSW-101-U

CEILING MOUNTED, DUAL TECHNOLOGY DIGITAL OCCUPANCY SENSOR

COMPATIBLE WITH DIGITAL ROOM CONTROLLER WITH CAT5E

NETWORKING.

MINUTES

AUTO

MINIMUM 28', 360 DEGREE

RADIAL COVERAGE AT 9'

MOUNTING HEIGHT

24V DC

INPUT

WATTSTOPPER: LMDC-100-U

CEILING MOUNTED, DUAL TECHNOLOGY DIGITAL OCCUPANCY SENSOR

COMPATIBLE WITH DIGITAL ROOM CONTROLLER WITH CAT5E

NETWORKING.

MINUTES

MANUAL

MINIMUM 28', 360 DEGREE

RADIAL COVERAGE AT 9'

MOUNTING HEIGHT

24V DC

INPUT

WATTSTOPPER: LMDC-100-U

CEILING MOUNTED, AUTOMATIC DIMMING DIGITAL PHOTOSENSOR

COMPATIBLE WITH DIGITAL ROOM CONTROLLER WITH CAT5E

NETWORKING AND WITH FULL RANGE DIMMING WITH FOOTCANDLE

SETPOINTS FROM 20-60 FC. SET SENSOR FOR 35 FC.

N/AN/AN/A

24V DC

INPUT

WATTSTOPPER: LMLS-400-U

ONE RELAY/ZONE DIGITAL ROOM CONTROLLER WITH 0-10V DIMMING

OUTPUT AND CAT5E NETWORKING WITH CONTROL DEVICES.

N/AN/AN/A

120/277V, 24V DC,

0-10V DC

DIMMING

WATTSTOPPER: LMRC-211-U

NOTESDESCRIPTION

TIME

DELAY

ON MODECOVERAGEVOLTAGE

BASIS OF DESIGN:

MANUFACTURER AND MODEL

SYMBOL

TYPE

OCCUPANCY SENSOR AND SWITCH SCHEDULE

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

F

SHEET TITLE

ARCHITECT

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

STRUCTURAL / CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH. / ELEC. / PLUMB. / TECH. ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATHE, KS 66062

(913) 829-8650

LANDSCAPE ARCHITECT

ARC STUDIOS INC.

3117 E. FLOWER STREET

TUCSON, AZ 85716

(520) 882-9655

COMMISSIONING

GLHN ARCHITECTS & ENGINEERS, INC.

2939 E. BROADWAY BLVD

TUCSON, AZ 85716

(520) 881-4546

R1 - CONSTRUCT REPLACEMENT

WAREHOUSE

ELECTRICAL SCHEDULES

01/06/2020 BEN ABM

500 AZ-89, PRESCOTT, AZ 86301

165-E-602

649-414

BID DOCUMENTS

LIGHT FIXTURE SCHEDULE

TYPE

BASIS OF DESIGN:

MANUFACTURER AND MODEL

MOUNTING

LAMP BALLAST/DRIVER

DESCRIPTION NOTES

TYPE LUMENS

COLOR

TEMP

TYPE VOLTAGE

INPUT

WATTS

INPUT

VA

A1D

WILLIAMS 50 STATIC SERIES:

50G-S24-L33/835-S-AF12125-DIM-UNV

LAY-IN GRID

CEILING PER DTL 9,

SHEET 165-E-501

INTEGRAL

WHITE LED

3300 lm 3500 K

0-10V LOW VOLTAGE

DIMMABLE

ELECTRONIC LED

DRIVER

277 V 26 W 29 VA

2'X4' RECESSED STATIC LED LIGHT FIXTURE WITH

WHITE TRIM AND FROSTED ACRYLIC SHIELDING AND

DIMMABLE DRIVER.

D1

WILLIAMS 6DR SERIES:

6DR-L10/835-DRV-UNV-O-M-OF-N-F2

LAY-IN GRID/ GYP.

BOARD CEILING

INTEGRAL

WHITE LED

1000 lm 3500 K

0-10V LOW VOLTAGE

DIMMABLE

ELECTRONIC LED

DRIVER

277 V 9 W 10 VA

6" MEDIUM DISTRIBUTION DOWNLIGHT WITH CLEAR

SEMI-SPECULAR REFLECTOR FINISH.

D1E

WILLIAMS 6DR SERIES:

6DR-L10/835-EM/10W-DIM-UNV-O-M-OF-WET/CC-N-F2

LAY-IN GRID/ GYP.

BOARD CEILING

INTEGRAL

WHITE LED

1000 lm 3500 K

0-10V LOW VOLTAGE

DIMMABLE

ELECTRONIC LED

DRIVER

277 V 9 W 10 VA

SAME AS TYPE "D1", EXCEPT WITH 90-MINUTE

BATTERY BACKUP AND INTEGRAL

SELF-TEST/DIAGNOSTICS.

F1

WILLIAMS 76 SERIES:

76-4-L32/840-WG-7611-DRV-UNV

CHAIN MOUNT AT

9'-0", UNO

INTEGRAL

WHITE LED

3200 lm 3500 K

STANDARD

ELECTRONIC LED

DRIVER

277 V 28 W 31 VA 4' LONG STRIP LIGHT WITH 11 GAUGE WIRE GUARD.

F1E

WILLIAMS 96 SERIES:

76-4-L40/835-H1AFR-DRV-UNV

CHAIN MOUNT AT

9'-0", UNO

INTEGRAL

WHITE LED

4000 lm 3500 K

STANDARD

ELECTRONIC LED

DRIVER

277 V 41 W 46 VA

4' LONG FULLY ENCLOSED AND GASKETED STRIP

LIGHT WITH 90-MINUTE BATTERY BACKUP AND

SELF-DIAGNOSTICS. COORDINATE EXACT LOCATION

OF FIXTURE IN ELEVATOR SHAFT WITH ELEVATOR

MANUFACTURER.

F4

EATON CHAMP MLL SERIES:

MLL-4/UNV1-S903-TF-P

GYP. BOARD

CEILING

INTEGRAL

WHITE LED

7100 lm 3500 K

STANDARD

ELECTRONIC LED

DRIVER

277 V 63 W 57 VA

4' LONG FULLY ENCLOSED AND GASKETED STRIP

LIGHT WITH POLYCARBONATE LENS, FEED THROUGH

HUBS AND PAINTED GRAY EPOXY FINISH.

G1

LDPI LEVP SERIES:

LEVP-14-U-53-L1-C

MOUNT TO

REFRIGERATOR

CEILING

INTEGRAL

WHITE LED

1123 lm 5300 K

STANDARD

ELECTRONIC LED

DRIVER

277 V 14 W 15 VA

5" WIDE LED GLOBE LIGHT WITH CLEAR GLASS

GLOBE AND GUARD.

P1D

EATON METALUX SERIES:

SSLED-LD5-15-M-UNV-L840-CD-1-MP/SHK-C61-SVPD3-LWR

CHAIN MOUNT AT

30'-0", UNO

INTEGRAL

WHITE LED

15000 lm 4000 K

0-10V LOW VOLTAGE

DIMMABLE

ELECTRONIC LED

DRIVER

277 V 111 W 123 VA

CLASSIC ROUND HIGH BAY LIGHT FIXTURE WITH

MEDIUM FROSTED POLYCARBONATE LENS,

DIMMABLE LED DRIVER AND INTEGRAL

OCCUPANCY/DAYLIGHT SENSORS. SET DAYLIGHT

SENSOR AT 10FC AT FLOOR LEVEL.

P1DE

EATON METALUX SERIES:

SSLED-LD5-15-M-UNV-L840-EL20W-REM-CD-1-MP/SHK-C61-SVPD3-LWR

CHAIN MOUNT AT

30'-0", UNO

INTEGRAL

WHITE LED

15000 lm 4000 K

0-10V LOW VOLTAGE

DIMMABLE

ELECTRONIC LED

DRIVER

277 V 111 W 123 VA

SAME AS TYPE "P1", EXCEPT WITH 90-MINUTE

BATTERY BACKUP AND SELF-DIAGNOSTICS OR

LASER TESTING CAPABILITIES.

2, 3

S4A

FIXTURE: NLS VUE SERIES

VUE-1-T2-32L-1-40K-UNV-DPS6-BRZ

WIRELESS LTG CNTLR: SYNAPSE DIM10-250-11

ANTENNA: SYNAPSE GLP-KIT-ANT18-03

36" AFG POLE

BASE PER DTL 3,

SHEET 165-E-501

INTEGRAL

WHITE LED

10574 lm 4000 K

STANDARD

ELECTRONIC LED

DRIVER

277 V 70 W 78 VA

LED PARKING LOT LIGHT WITH TYPE T4 LIGHT

DISTRIBUTION PATTERN AND DARK BRONZE FINISH

ON 25' TALL, 5" SQUARE STEEL POLE, WITH

WIRELESS LIGHTING CONTROLLER AND ANTENNA.

S4D

FIXTURE: NLS VUE SERIES

VUE-1-T4-32L-1-40K-UNV-DPS6-BRZ

WIRELESS LTG CNTLR: SYNAPSE DIM10-250-11

ANTENNA: SYNAPSE GLP-KIT-ANT18-03

36" AFG POLE

BASE PER DTL 3,

SHEET 165-E-501

INTEGRAL

WHITE LED

10560 lm 4000 K

STANDARD

ELECTRONIC LED

DRIVER

277 V 70 W 78 VA

LED PARKING LOT LIGHT WITH TYPE T2 LIGHT

DISTRIBUTION PATTERN AND DARK BRONZE FINISH

ON 25' TALL, 5" SQUARE STEEL POLE, WITH

WIRELESS LIGHTING CONTROLLER AND ANTENNA.

V1

EATON SHAPER SERIES:

605-25-W-L3/835-UNV-MW

WALL MOUNT 6'-6"

AFF

INTEGRAL

WHITE LED

2000 lm 3500 K

STANDARD

ELECTRONIC LED

DRIVER

277 V 20 W 22 VA

WALL MOUNTED VANITY LIGHT WITH WHITE FINISH

AND OPAQUE LENS.

W1

WILLIAMS VOLTAIRE SERIES:

VWPH-L30/740-TFT-SLV-SDGL-DRV-UNV

WALL,10'-0" ABOVE

FINISHED FIRST

FLOOR LEVEL.

INTEGRAL

WHITE LED

3000 lm 4000 K

STANDARD

ELECTRONIC LED

DRIVER

277 V 36 W 40 VA

ARCHITECTURAL WALL PACK WITH FORWARD

THROW DISTRIBUTION, SATIN ALUMINUM FINISH,

DIFFUSED TEXTURED TEMPERED GLASS LENS, AND

DIMMABLE DRIVER.

W1E

WILLIAMS VOLTAIRE SERIES:

VWPH-L30/740-EM/4W-TFT-SLV-SDGL-DRV-UNV

WALL,10'-0" ABOVE

FINISHED FIRST

FLOOR LEVEL.

INTEGRAL

WHITE LED

3000 lm 4000 K

STANDARD

ELECTRONIC LED

DRIVER

277 V 36 W 40 VA

SAME AS TYPE "W1", EXCEPT WITH 90-MINUTE

BATTERY BACKUP AND INTEGRAL

SELF-TEST/DIAGNOSTICS. PROVIDE EMERGENCY

DRIVER IN ACCESSIBLE LOCATION INSIDE BUILDING

W2

WILLIAMS VF2 SERIES:

VF2-L57-MF-CU-DBZ-WG-DIM-277

WALL MOUNT AT

9'-0" TO BOTTOM

OF FIXTURE

INTEGRAL

WHITE LED

5700 lm 4000 K

STANDARD

ELECTRONIC LED

DRIVER

277 V 53 W 59 VA

ARCHITECTURAL FLOOD LIGHT WITH MEDIUM

DISTRIBUTION, CURVED ARM WIREGUARD AND DARK

BRONZE FINISH. AIM FIXTURE FOR LIGHTING

INTERIOR OF TRUCK TRAILERS

X1E

WILLIAMS EXIT/CA SERIES:

EXIT/CA-R-AF-BA-EM-SDT

UNIVERSAL

TOP/END MOUNT

LED 0 lm 0 K

STANDARD EXIT

SIGN LED DRIVER

277 V 4 W 4 VA

UNIVERSAL MOUNT, SINGLE/DOUBLE FACE EXIT SIGN

WITH RED LETTERING BRUSHED ALUMINUM HOUSING

WITH 90-MINUTE BATTERY BACKUP AND INTEGRAL

SELF-TEST/DIAGNOSTICS.

NOTES:

1. INSTALL LIGHT FIXTURE, SYNAPSE LIGHTING CONTROLS AND LIGHT POLE FURNISHED BY GOVERNMENT. UPDATE GOVERNMENT SYNAPSE SITE LIGHTING MANAGEMENT SYSTEM WITH NEW POLE LOCATIONS

AND LIGHT MAC ADDRESSES.

2. INTEGRAL SELF-TEST/DIAGNOSTICS SHALL AUTOMATICALLY TEST EMERGENCY OPERATION OF FIXTURE AT REQUIRED INTERVALS AND INCLUDE DUAL-COLOR LED FOR INDICATION OF PROPER OPERATION - GREEN FOR PROPER OPERATION, RED FOR CHARGING, AND FLASHING RED FOR FAILURE OF INTERNAL COMPONENTS.

3. IF INTEGRAL SELF-TEST/DIAGNOSTICS BATTERY PACK IS NOT AVAILABLE FOR THIS FIXTURE, PROVIDE STANDARD 90-MINUTE BATTERY PACK WITH (2) LASERS FOR REMOTE TESTING EMERGENCY BATTERY

PACKS. PROVIDE ENCLOSURE IN ELECTRICAL ROOM FOR STORAGE OF LASERS.

4. INSTALL 180-DEGREE, TWO-HEADED LIGHT POLE FURNISHED BY GOVERNMENT. DRILL HOLES FOR TWO-HEADED, 90-DEGREE FIXTURE AS REQUIRED. PROVIDE PLUGS FOR UNUSED DRILL HOLES.

DRAWING NUMBER

VA PROJECT NUMBER

DATE

PROJECT TITLE

BUILDING NUMBER

PROJECT LOCATION

CHECKED BY DRAWN BY

APPROVED: PROJECT DIRECTOR

VA FORM 08-6231

Office of Construction and Facilities Management

Dwg.

CONSULTANT INFORMATION

F

SHEET TITLE

ARCHITECT

FULLY SPRINKLERED

PROJECT PHASE

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

U.S. Department of Veteran Affairs

F

E

D

C

B

A

E

D

C

B

A

STRUCTURAL / CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH. / ELEC. / PLUMB. / TECH. ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 W. 161ST STREET

OLATHE, KS 66062

(913) 829-8650

LANDSCAPE ARCHITECT

ARC STUDIOS INC.

3117 E. FLOWER STREET

TUCSON, AZ 85716

(520) 882-9655

COMMISSIONING

GLHN ARCHITECTS & ENGINEERS, INC.

2939 E. BROADWAY BLVD

TUCSON, AZ 85716

(520) 881-4546

R1 - CONSTRUCT REPLACEMENT

WAREHOUSE

ELECTRICAL SCHEDULES

01/06/2020 BEN ABM

500 AZ-89, PRESCOTT, AZ 86301

165-E-603

649-414

BID DOCUMENTS

MISC. EQUIPMENT (Z): 37099 VA 100.00% 37099 VA

SUPPLEMENTAL HEAT (Y):

LARGEST MOTOR (X): 4160 VA 125.00% 5200 VA

MOTORS (M): 6088 VA 100.00% 6088 VA

RECEPTACLES (R): 7740 VA 100.00% 7740 VA GF: GFCI TYPE CIRCUIT BREAKER

VD: UPSIZED FOR VOLTAGE DROP

LCK: HANDLE PADLOCKABLE-OFF DEVICE

LIGHTING (L): 0 VA 0 VA FEED THRU LUGS WITH #4/0 CONNECTION

HEATING (H); NOTES:

COOLING (C): 2080 VA 100.00% 2080 VA TOTALS: 159 A 162 A

EXISTING LOAD (E): PANELBOARD 57167 VA 58207 VA

LOAD TYPE CONNECTED LOAD NEC DEMAND DEMAND LOAD TOTAL CONNECTED TOTAL DEMAND

TOTAL PHASE LOAD (A): 187 A 136 A 161 A

TOTAL PHASE LOAD (VA) 22001 VA 16293 VA 18873 VA

PHASE A PHASE B PHASE C

83 EQUIPPED SPACE -- -- -- -- -- -- 0 1500 84

81 EQUIPPED SPACE -- -- -- -- -- -- 0 2040 82

79 EQUIPPED SPACE -- -- -- -- -- -- 0 1860

3 60 1L 1L R; Z PANELBOARD 165-EL1-2

77 EQUIPPED SPACE -- -- -- -- -- -- 0 0 -- -- -- -- -- -- EQUIPPED SPACE 78

75 EQUIPPED SPACE -- -- -- -- -- -- 0 0 -- -- -- -- -- -- EQUIPPED SPACE 76

73 EQUIPPED SPACE -- -- -- -- -- -- 0 0 -- -- -- -- -- -- EQUIPPED SPACE 74

71 EQUIPPED SPACE -- -- -- -- -- -- 0 0 -- -- -- -- -- -- EQUIPPED SPACE 72

69 SPARE -- -- -- 20 1 0 0 1 20 -- -- -- SPARE 70

67 SPARE -- -- -- 20 1 0 0 1 20 -- -- -- SPARE 68

65 SPARE -- -- -- 20 1 0 0 1 20 -- -- -- SPARE 66

63 FIRE ALARM CONTROL PNL Z FA 12 12 20 1 1000 0 1 20 -- -- -- SPARE 64

61 588 528 1 15 12 12 M EF-4 62

59 588 528 1 15 12 12 M EF-3 60

REFRIGERATOR/REEFER Z 12 12 15 3

588 1176 1 20 12 12 M EF-2 58

55 INTERCOM DEVICE Z 12 12 20 1 500 528 1 15 12 12 M EF-1 56

53 BRK RM 102 GEN. PURPOSE R 12 12 20 1 360 500 1 20 12 12 Z WH-1 CONTROLS 54

51 BRK RM 102 GEN. PURPOSE R 12 12 20 1 180 48 1 20 12 12 M RP-1 52

49 BRK RM 102 REFRIDGERATOR Z GF 12 12 20 1 1200 1040 50

47 BRK RM 102 MICROWAVE Z GF 12 12 20 1 1200 1040

2 15 12 12 C; M CU-AHU-3

45 BRK RM 102 COFFEE BREWER Z GF 12 12 20 1 1200 1040 46

43 PLOTTING RM 108 COPIER Z 12 12 20 1 1200 1040

2 15 12 12 C; M CU-AHU-2

41 AHU-1 M 12 12 15 1 1200 576 42

39 RCPT: PLOTTING 108 GEN. PURP. R 12 12 20 1 360 576 40

37 2080 576

3 15 12 12 LCK Z HYDRAULIC LIFT CCT 2

CU-AHU-1 X 10 10 30 2

2080 576 36

33 IRRIGATION CONTROL PANEL Z VD 10 10 20 1 500 576 34

31 GATE OPERATOR Z VD 4 4 30 1 2160 576

3 15 12 12 LCK Z HYDRAULIC LIFT CCT 1

29 RCPT: PERIMETER RECEPTACLES R VD 10 10 20 1 720 1200 1 20 12 12 Z RCPT: INTERCOM MASTER 30

27 RCPT: PERIMETER RECEPTACLES R VD 10 10 20 1 720 1200 1 20 10 10 VD Z GOLF CART 28

25 RCPT: WHS GEN. PURP. R VD 10 10 20 1 900 1200 1 20 10 10 VD Z PALLET JACK CCT 2 26

23 RCPT: WHS GEN. PURP. R VD 10 10 20 1 540 1200 1 20 10 10 VD Z PALLET JACK CCT 1 24

21 WHS WORKSTATION 4 Z 12 12 20 1 360 720 1 20 12 12 R SV OFFICE 22

19 WHS WORKSTATION 3 Z 12 12 20 1 360 720 1 20 12 12 R WHS GEN. PURPOSE CCT 2 20

17 WHS WORKSTATION 2 Z 12 12 20 1 360 1200 1 20 12 12 GF Z 1ST FLOOR WATER COOLER 18

15 WHS WORKSTATION 1 Z 12 12 20 1 360 180 1 15 12 12 R WRAPPING MACHINE 16

13 RCPT: EMER. PHARMACY CACHE R 12 12 20 1 360 1200 1 25 10 10 Z ELECTRICAL HAND TRUCK 14

11 RCPT: PLOT 104 PLOTTER Z 12 12 20 1 240 1200 1 25 10 10 Z ELECTRICAL HAND TRUCK 12

9 RCPT: PLOT 104 LAMINATOR Z 12 12 20 1 1500 864 1 20 12 12 Z WHS GARAGE DOOR CCT 5 10

7 RCPT: PLOT 104 BINDER Z 12 12 20 1 1200 720 1 20 12 12 R WHS GEN. PURPOSE CCT 1 8

5 RCPT: PLOT 104 PAPER CUTTER Z 12 12 20 1 1200 864 1 20 10 10 VD Z WHS GARAGE DOOR CCT 3 6

3 RCPT: PLOT 104 COLOR PRINTER Z 12 12 20 1 240 864 1 20 10 10 VD Z WHS GARAGE DOOR CCT 2 4

1 UNISEX RESTROOMS R; Z 12 12 20 1 600 864 1 20 10 10 VD Z WHS GARAGE DOOR CCT 1 2

CKT

NO.

DESCRIPTION

LOAD

TYPE

NOTE

WIRE

SIZE

GND

SIZE

BRKR

AMP

P A B C A B C P

BRKR

AMP

GND

SIZE

WIRE

SIZE

NOTE

LOAD

TYPE

DESCRIPTION

CKT

NO.

VOLT-AMPS/PHASE

SECTIONS: 2

A.I.C RATING: FCA +10% MINIMUM FULLY RATED FED FROM: XFMR 165-NL2-1

MOUNTING: SURFACE SERVES: 1ST FLOOR NORMAL LOADS

VOLTS/PHASE: 208Y/120V, 3PH, 4W LOCATION: ELEC 107

MAIN SIZE/TYPE: 225 A MCB FAULT CURRENT: RE: ONE-LINE DIAGRAM EQUIPMENT GROUND BUS

BUS SIZE: 250 A

PANELBOARD: 165-NL1-1

MISC. EQUIPMENT (Z): 88401 VA 100.00%…