This document provides details for a federal contract opportunity to construct a replacement warehouse at the Northern Arizona VA Health Care System in Prescott, Arizona. The Department of Veterans Affairs seeks to award a firm-fixed-price contract through a Request for Proposal as a total Service-Disabled Veteran-Owned Small Business set-aside to construct a new approximately 10,930 square foot warehouse facility. The new warehouse will replace existing structures and provide efficient storage and loading areas for critical supply needs. The contract period of performance is approximately 360 calendar days with the solicitation to be issued on or around July 27, 2020 and a magnitude of construction between $5 million and $10 million. Questions must be submitted in writing by the specified date.
View the file
Other files for this federal contract opportunity
Show all 43
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
M/G 400A/3P
M/G 400A/3P
UE
C
PC
R
TS
T
100/3
100/3/70
100/3/70/1
100/3/CB
PP
J
GF
OR
OR
OR
AM
VM
DM
ST
KK
GFR
M
SPD
R
BAT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISH FLOOR
BIL BASIC INSULATION LEVEL
BLDG BUILDING
BPIP BOILER PLANT
INSTRUMENTATION PANEL
BRKR BREAKER
BYP BY PASS
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
A/C AIR CONDITIONING
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED
CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
ADO AUTOMATIC DOOR OPENER
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, AUTOMATIC
FREQUENCY CONTROL, OR
AVAILABLE FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB OR A AMBIENT
AMP AMPERE
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
1P SINGLE POLE
1PH SINGLE-PHASE
3P THREE POLE
3PH THREE-PHASE
3W THREE WIRE
4W FOUR WIRE
P POLE
PA PUBLIC ADDRESS
PB PANELBOARD, PULL BOX, OR
PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT UNIT
PCB POLYCHLORINATED BIPHENYL
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
POD POWER OPERATED DAMPER
PT POTENTIAL TRANSFORMER
PTRV POWER TYPE ROOF VENTILATION
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
SCC SHORT CIRCUIT CAPACITY
SES SERVICE ENTRANCE SECTION
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
G OR GND GROUND OR GENERATOR
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GTB GROUND TERMINAL BOX
IESNA ILLUMINATION ENGINEERING SOCIETY
OF NORTH AMERICA
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
W WATT
WH WATER HEATER
WP WEATHERPROOF
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LM LUMEN
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LTCP LOCAL TEMPERATURE CONTROL PANEL
LT LIGHT
LTG LIGHTING
LTG PNL LIGHTING PANEL
LTNG LIGHTNING
LV LOW VOLTAGE
XFER TRANSFER
XFMR TRANSFORMER
XP EXPLOSION PROOF
JB JUNCTION BOX
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT AMPERE
KVAH KILOVOLT AMPERE PER HOUR
KVAR KILOVOLT AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
KWHM KILOWATT HOUR METER
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MLO MAIN LUGS ONLY
MT MOUNT
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT
OC ON CENTER
OD OUTSIDE DIAMETER
OL OVERLOAD
N NEUTRAL
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REC RECESSED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
REQD REQUIRED
TC TIME CLOCK
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
ABBREVIATIONS
A
B
C
C CONDUIT
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/
CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER
CFE CONTRACTOR FURNISHED
EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CKT BRKR CIRCUIT BREAKER
CLF CURRENT LIMITING FUSE
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAX CABLE
COMM COMMUNICATION
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR DISTRIBUTION
DISTR PNL DISTRIBUTION PANEL
DN DOWN
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMCP EMER. MONITORING CONTROL PANEL
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
ESMT EASEMENT
ETD EXISTING TO BE DEMOLISHED
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST EXISTING
D
E
F
G
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FABL FIRE ALARM BELL
FABX FIRE ALARM BOX
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FI FILM ILLUMINATOR
FIXT FIXTURE
FLA FULL LOAD AMPS
FLEX FLEXIBLE METALLIC CONDUIT
FLUOR FLUORESCENT
FP FIRE PROTECTION
FT FEET OR FOOT
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
H
I
J
K
L
M
N
O
P
STANDARD MOUNTING HEIGHTSANNOTATION
CIRCUITING SYMBOLS
R
S
T
U
V
W
X
CU
M100
M100
MECHANICAL OR FIRE SPRINKLER PLAN NOTE CALL OUT
PLUMBING PLAN NOTE CALL OUT
ELECTRICAL, TECHNOLOGY OR FIRE ALARM PLAN NOTE
CALL OUT
PLUMBING EQUIPMENT DESIGNATION
EQUIPMENT DESIGNATION TAG
OWNER FURNISHED, CONTRACTOR INSTALLED
EQUIPMENT DESIGNATION
NEW WORK TO EXISTING WORK CONNECTION POINT
DETAIL REFERENCE
SECTION CUT DESIGNATION
ELECTRICAL:
AUDIBLE APPLIANCES (CENTERLINE) 84"
ALARMS (TOP) 48"
ANNUNCIATOR PANELS (TOP) 48"
CLOCK OUTLETS (CENTERLINE) 84"
CONTROLS (TOP) 48"
EXIT SIGNS (WALL-MOUNTED, BOTTOM) 80"
FIRE ALARM ANNUNCIATOR PANEL (DISPLAY) 60"
FIRE ALARM BELL (EXTERIOR) 120"
FIRE ALARM CONTROL PANEL/UNIT (DISPLAY) 60"
INTERCOM (AFEA ONLY) 36"
INTERCOMS (TOP) 48"
PANELS & PANELBOARDS (TOP) 72"
PULL STATIONS (TOP) 48"
PHOTOCELLS 144"
RECEPTACLES (BOTTOM) 18"
RECEPTACLES, EXTERIOR (BOTTOM) 24"
RECEPTACLES, GARAGES (BOTTOM) 26"
RECEPTACLES IN EQUIPMENT ROOMS (TOP) 48"
REMOTE INDICATING LIGHT, EQUIPMENT ROOMS (TOP) 48"
REMOTE INDICATING LIGHT, FINISHED AREAS (TOP) CEILING
SAFETY SWITCHES & STARTERS 48"
SWITCHES (TOP) 48"
TELEPHONE/DATA/TV OUTLETS (BOTTOM) 18"
VISIBLE APPLIANCES (CENTERLINE) 84"
(AFF, AFG UNLESS NOTED OTHERWISE)
WIRING DEVICE SYMBOLS
POWER EQUIPMENT SYMBOLS
LIGHTING SYMBOLS
LP1
A1
LIGHT FIXTURE, CEILING MOUNTED
a
LIGHTING TRACK WITH TRACK LIGHT FIXTURES
LIGHT FIXTURE, POLE MOUNTED
LIGHT FIXTURE, WALL MOUNTED
EMERGENCY BATTERY PACK LIGHT FIXTURE,
WALL MOUNTED
EMERGENCY BATTERY PACK LIGHT FIXTURE,
CEILING MOUNTED
EXIT SIGN, WALL MOUNTED, FACE/ARROWS AS INDICATED
EXIT SIGN, CEILING MOUNTED, FACE/ARROWS AS INDICATED
ELECTRICAL ONE-LINE DIAGRAM SYMBOLS
EMERGENCY LIGHT FIXTURE, CEILING MOUNTED
A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT
FIXTURE SCHEDULE
a = SWITCHED BY SWITCH "a"
NL = NIGHT LIGHT
= ARROW INDICATES AIMING DIRECTION
A1E = LIGHT FIXTURE TYPE "A1E" REFER TO LIGHT
FIXTURE SCHEDULE
a = SWITCHED BY SWITCH "a"
NL = NIGHT LIGHT
A1E a
A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT
FIXTURE SCHEDULE
a = SWITCHED BY SWITCH "a"
A1 a
A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT
FIXTURE SCHEDULE
A1
A1
A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT
FIXTURE SCHEDULE
X1E
X1E
X1E = LIGHT FIXTURE TYPE "X1E" REFER TO LIGHT
FIXTURE SCHEDULE
Y1E
X1E = LIGHT FIXTURE TYPE "X1E" REFER TO LIGHT
FIXTURE SCHEDULE
Y1E
Y1E = LIGHT FIXTURE TYPE "Y1E" REFER TO
LIGHT FIXTURE SCHEDULE
Y1E = LIGHT FIXTURE TYPE "Y1E" REFER TO LIGHT
FIXTURE SCHEDULE
HOMERUN TO PANELBOARD, ARROWS INDICATE
NUMBER OF CIRCUITS, TICK MARKS INDICATE
NUMBER OF CONDUCTORS. DESIGNATIONS ARE
PANELBOARD AND CIRCUIT NUMBERS.
UNSWITCHED HOT CONDUCTORS SHOWN LEADING
NEUTRAL CONDUCTOR
NEUTRAL CONDUCTOR
SWITCHED HOT CONDUCTORS SHOWN TRAILING
GROUND CONDUCTOR
EQUIPMENT GROUNDING CONDUCTOR IN RACEWAY
ISOLATED GROUNDING CONDUCTOR IN RACEWAY
CONCEALED RACEWAY
EXPOSED RACEWAY
RACEWAY TURNING DOWN
RACEWAY TURNING UP
EQUIPMENT TERMINATION
CONCEALED RACEWAY
LIGHT FIXTURE, BOLLARDA1
A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT
FIXTURE SCHEDULE
RECEPTACLE, SIMPLEX, NEMA 5-20R, UNO
RECEPTACLE, DUPLEX, NEMA 5-20R, UNO
RECEPTACLE, DOUBLE-DUPLEX, NEMA 5-20R, UNO
RECEPTACLE, DUPLEX, CEILING MOUNTED, NEMA 5-20R, UNO
RECEPTACLE, SPECIAL PURPOSE
RECEPTACLE, TWIST-LOCK
RECEPTACLE, DUPLEX, FLOOR MOUNTED, NEMA 5-20R, UNO
RECEPTACLE, DUPLEX, DROP CORD, NEMA 5-20R, UNO
RECEPTACLE, MOUNTED 6" ABOVE COUNTER,
TYPE AS INDICATED ABOVE
RECEPTACLE DESIGNATIONS AS FOLLOWS:
C = CLOCK HANGER
E = EMERGENCY POWER
GF = GROUND FAULT CIRCUIT INTERRUPTER
IG = ISOLATED GROUND
S = SWITCHED
TR = TAMPER RESISTANT
WP = WEATHER PROOF COVER
WR = WEATHER RESISTANT
XP = EXPLOSION PROOF
SWITCH, SINGLE POLE
SWITCH DESIGNATIONS AS FOLLOWS:
2 = TWO-POLE WALL SWITCH
3 = THREE-WAY WALL SWITCH
4 = FOUR-WAY WALL SWITCH
D = DIMMER SWITCH
OS# = OCCUPANCY SENSOR WALL SWITCH, REFER
TO OCCUPANCY SENSOR SCHEDULE
P = SINGLE-POLE, SINGLE-THROW PILOT LIGHT
WALL SWITCH
K = KEYED WALL SWITCH
M = MOTOR RATED SWITCH
WP = WEATHER PROOF SWITCH AND COVER
OCCUPANCY SENSOR, CEILING MOUNTED
POWER PACK FOR LIGHTING CONTROL
JUNCTION BOX
RECEPTACLE ON EMERGENCY POWER
RECEPTACLE, ISOLATED GROUND TYPE
OS# = OCCUPANCY SENSOR WALL SWITCH, REFER
TO OCCUPANCY SENSOR SCHEDULE
MULTI-OUTLET, SURFACE RACEWAY, 24" ON CENTER,
NEMA 5-20R, UNO
SWITCHBOARD, MOTOR CONTROL CENTER OR
DISTRIBUTION PANELBOARD ON HOUSEKEEPING PAD
PANELBOARD, RECESS MOUNTED
PANELBOARD, SURFACE MOUNTED
TRANSFORMER
DISCONNECT SWITCH, NON-FUSED, 100/3 INDICATES
AMPERES/POLES, CB = CIRCUIT BREAKER TYPE
DISCONNECT SWITCH, FUSED, 100/3/70 INDICATES
AMPERES/POLES/FUSE, CB = CIRCUIT BREAKER TYPE
COMBINATION DISCONNECT SWITCH WITH MOTOR
STARTER 100/3/70/1 INDICATES AMPERES/POLES/FUSE/
NEMA STARTER SIZE, NF = NON-FUSED, CB = CIRCUIT
BREAKER TYPE
MAGNETIC MOTOR STARTER, NEMA SIZE AS NOTED,
3-POLE, UNO
CONTACTOR
PHOTOCELL
RELAY
TIME SWITCH
LOW-VOLTAGE TRANSFORMER
PUSH BUTTON, TYPE AS NOTED
LIGHTNING PROTECTION SYMBOLS
LIGHTNING PROTECTION AIR TERMINAL
LIGHTNING PROTECTION CABLE CONNECTION
LIGHTNING PROTECTION GROUND ROD
LIGHTNING PROTECTION CONDUCTOR
AUTOMATIC TRANSFER SWITCH
TYPE AND RATINGS AS INDICATED
TX#
600AF
3P
500AT
400AS
3P
225AF
275KW STANDBY
480Y/277V, 3PH, 4W
GENERATOR, SEPARATELY DERIVED
SOURCE, TYPE AND RATINGS AS INDICATED
275KW STANDBY
480Y/277V, 3PH, 4W
GENERATOR, NON-SEPARATELY DERIVED
SOURCE, TYPE AND RATINGS AS INDICATED
DRAWOUT CIRCUIT
BREAKER, RATINGS
AS INDICATED
600AF
3P
500AT
CIRCUIT BREAKER,
RATINGS AS
INDICATED
LPS-R
FUSED DISCONNECT
SWITCH, RATINGS
AS INDICATED
400AS
3P
225AF
LPS-R
COMBINATION FUSED
SWITCH AND STARTER,
RATINGS AS
PANELBOARD,
SINGLE-SECTION,
RATINGS PER
SCHEDULES
PANELBOARD,
MULTI-SECTION,
RATINGS PER
SCHEDULES
NEMA 1
AMMETER
VOLTMETER
COMBINATION DIGITAL
SHUNT-TRIP RELAY
KIRK-KEY INTERLOCK
GROUND-FAULT RELAY
UTILITY METER
RELAY
SURGE PROTECTION
AMMETER/VOLTMETER
DEVICE
AUTOMATIC TRANSFER SWITCH WITH BYPASS
TYPE AND RATINGS AS INDICATED
VARIABLE FREQUENCY
DRIVE WITH
DISCONNECT, RATINGS
GROUND CONNECTION
POTENTIAL TRANSFORMER
CURRENT TRANSFORMER
GROUND CONNECTION
WITH TEST WELL
CONTACT, OPEN
CONTACT, CLOSED
MOTOR
FEEDER TAGCAPACITOR
LIGHTNING ARRESTER
HEATER
VARIABLE FREQUENCY DRIVE WITH DISCONNECT
SWITCH 100/3/70 INDICATES AMPERES/POLES/FUSE
SIZE, NF = NON-FUSED, CB = CIRCUIT BREAKER TYPE
225A 3P
NEMA 1
INDICATED
COMBINATION CIRCUIT
BREAKER AND
STARTER, RATINGS AS
INDICATED AS INDICATED
225A 3P
UNDERGROUND ELECTRIC LINE
MULTI-SERVICE FLOOR BOX/POKE-THRU WITH POWER/DATA,
TYPE AS NOTED AND/OR SCHEDULED
CABINET, RECESS MOUNTED
CABINET, SURFACE MOUNTED
RECEPTACLE, DUPLEX, GROUND-FAULT CIRCUIT
INTERRUPTER, NEMA 5-20R, UNO
MULTI-SERVICE POWER POLE WITH POWER/DATA,
TYPE AS NOTED AND/OR SCHEDULED
200A 3P
ATS#
200A 3P
ATS#
TRANSFORMER
TX#
TRANSFORMER,
SHIELDED
S
S
INSTALLED
RECEPTACLES ABOVE COUNTERTOPS (TOP) 44"
MUSHROOM TYPE PUSH BUTTON, TYPE AS NOTED
SPD = SURGE PROTECTION DEVICE
DRAWING NUMBER
VA PROJECT NUMBER
DATE
PROJECT TITLE
BUILDING NUMBER
PROJECT LOCATION
CHECKED BY DRAWN BY
APPROVED: PROJECT DIRECTOR
VA FORM 08-6231
Office of Construction and Facilities Management
Dwg.
CONSULTANT INFORMATION
F
SHEET TITLE
ARCHITECT
FULLY SPRINKLERED
PROJECT PHASE
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
U.S. Department of Veteran Affairs
F
E
D
C
B
A
E
D
C
B
A
STRUCTURAL / CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH. / ELEC. / PLUMB. / TECH. ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 W. 161ST STREET
OLATHE, KS 66062
(913) 829-8650
LANDSCAPE ARCHITECT
ARC STUDIOS INC.
3117 E. FLOWER STREET
TUCSON, AZ 85716
(520) 882-9655
COMMISSIONING
GLHN ARCHITECTS & ENGINEERS, INC.
2939 E. BROADWAY BLVD
TUCSON, AZ 85716
(520) 881-4546
R1 - CONSTRUCT REPLACEMENT
WAREHOUSE
ELECTRICAL LEGEND
01/06/2020 BEN ABM
500 AZ-89, PRESCOTT, AZ 86301
165-E-000
649-414
BID DOCUMENTS
Revision # Date
J
1" = 30'
903015 600
FO
F O
FO
FO
FO
FO
FO
FO
FO
SS
SS
SS
SS
SS
SS
SS
FO
FO FO
FO
FO
FO
S
DS
DS
DS
D
S
DS
DS
DS
D
SD
SDW W W W
W
W
SD
W
W
W
G G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G G
G
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
TRAILER AREATRAILER MANEUVER AREA
EXISTING PARKING LOT
DR. KENDALL WAY
UE
UE UE
UE
UE
U E
U E
U E
UE
UE
UE
UE
UEUE
UE UE UE
UE UEUE
UE UE
UE
UE
UE
UE
UE
UE
UE
UE
UE
UE
UE
UE
UE
UE
U E
U E
U E
UE
UE
U E
U E
U E
U E
U E
UE
UE
UE
UE
G
G
UE
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR ETR
ETR
ETR
S4D
S4A
S4A
S4D
S4A
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
HH-6
(ETR)
TANKS
U E
U E
U E
U E
UE
UE
UE
UE
MH
MH
UEUE
UE
UE
U E
U E
U E
PM-39
(ETR)
PM-45
(NEW)
PM-8
(ETR)
PM-7
(ETR)
HH-9
(ETR)
W M
W M
MAIN DISTRIBUTION PANEL
(165-NDB)
UC
UE
UE
U E
U E
U E
U E
UE UE
165-E-501
(TYP.)
U C
U C
U C
U C
U C
G
G
G G
G
S
IV
A
MV
165-NL1-1
165-NL1-1
U E
U E
U E
U E
UEUEUE
U E
BF
UE
U E
U E
UE UE UE UE UE UE
S4A
U E
UE
S4A S4A
165-NH1-1
U E
U E
U E
U E
U E
U E
U E
U E
UE
UE
UE
UE
UE
U E
U E
DRAWING NUMBER
VA PROJECT NUMBER
DATE
PROJECT TITLE
BUILDING NUMBER
PROJECT LOCATION
CHECKED BY DRAWN BY
APPROVED: PROJECT DIRECTOR
VA FORM 08-6231
Office of Construction and Facilities Management
Dwg.
CONSULTANT INFORMATION
F
SHEET TITLE
ARCHITECT
FULLY SPRINKLERED
PROJECT PHASE
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
U.S. Department of Veteran Affairs
F
E
D
C
B
A
E
D
C
B
A
STRUCTURAL / CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH. / ELEC. / PLUMB. / TECH. ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 W. 161ST STREET
OLATHE, KS 66062
(913) 829-8650
LANDSCAPE ARCHITECT
ARC STUDIOS INC.
3117 E. FLOWER STREET
TUCSON, AZ 85716
(520) 882-9655
COMMISSIONING
GLHN ARCHITECTS & ENGINEERS, INC.
2939 E. BROADWAY BLVD
TUCSON, AZ 85716
(520) 881-4546
R1 - CONSTRUCT REPLACEMENT
WAREHOUSE
ELECTRICAL SITE PLAN
01/06/2020 BEN ABM
500 AZ-89, PRESCOTT, AZ 86301
165-ES-101
649-414
BID DOCUMENTS
1" = 30'-0"
ELECTRICAL SITE PLAN
N
GENERAL NOTES:
1 COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER'S
REPRESENTATIVE.
2 COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES. VERIFY
ALL EXISTING CONDITIONS BEFORE THE START OF WORK.
3 SEE SHEET 165-G-001 FOR ADDITIONAL INFORMATION REGARDING
SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK ON EXISTING
EQUIPMENT AND IN EXISTING BUILDINGS TO MINIMIZE DISRUPTION OF
SERVICES.
4 DRAWINGS ARE DIAGRAMMATIC ONLY AND REPRESENT THE GENERAL SCOPE
OF WORK. REVIEW THE GENERAL NOTES, SPECIFICATIONS AND PLANS FOR
ADDITIONAL REQUIREMENTS THAT MAY NOT BE SPECIFICALLY CALLED OUT IN
THIS PORTION OF THE CONSTRUCTION DOCUMENTS. NOTIFY THE
CONTRACTING OFFICER'S REPRESENTATIVE (COR) OF ANY CONFLICTS OR
DISCREPENCIES PRIOR TO SUBMISSION OF BID.
5 DRAWINGS AND SPECIFICATIONS GOVERN WHERE THEY EXCEED CODE
REQUIREMENTS.
6 UTILITIES PRESENTED ON THESE DRAWINGS ARE SHOWN BASED ON
THE BEST AVAILABLE INFORMATION. FIELD VERIFY THE EXACT
LOCATIONS IN THE FIELD PRIOR TO COMMENCING CONSTRUCTION.
CONTRACTOR SHALL NOTIFY LOCAL UTILITY LOCATING SERVICES AT
LEAST 48 HOURS BEFORE PROCEEDING WITH ANY EXCAVATION.
7 DAMAGE TO ANY EXISTING UTILITIES SHALL BE REPAIRED IN ACCORDANCE
WITH THE VA'S STANDARD CONSTRUCTION SPECIFICATIONS AT NO
ADDITIONAL COST.
8 TAKE NECESSARY PRECAUTIONS TO PROTECT ROOT SYSTEMS OF SHRUBS,
PLANTS, AND TREES ALONG THE AREA OF EXCAVATION.
9 DISPOSE OF ALL DEMOLISHED MATERIAL OFF-SITE.
ELECTRICAL PLAN NOTES
1 PROVIDE NEW 500KVA TRANSFORMER AND TRANSFORMER
HOUSEKEEPING PAD. PROVIDE PAD DIMENSIONS PER MANUFACTURER'S
RECOMMENDATIONS. PROVIDE GROUND ROD WITHIN TRANSFORMER
PRIMARY CABINET OPENING AND #2/0 COPPER GROUND CONNECTION
FROM ROD TO #2/0 COPPER GROUND RING WITH (2) GROUND RODS AT
OPPOSITE CORNERS. REFER TO ELECTRICAL ONE-LINE DIAGRAM, SHEET
165-E-601 FOR ADDITIONAL INFORMATION.
2 PROVIDE NEW CONCRETE-ENCASED DUCT BANK AND FEEDERS FROM
NEW TRANSFORMER TO EXISTING TRANSFORMER AS INDICATED ON
DETAIL 1, SHEET 165-E-501 AND ELECTRICAL ONE-LINE DIAGRAM, SHEET
165-E-601.
3 PROVIDE POWER TO GATE OPERATOR. COORDINATE EXACT
REQUIREMENTS WITH GATE MANUFACTURER.
4 COORDINATE EXACT ROUTING AND BURY DEPTH OF NEW MEDIUM
VOLTAGE DUCT BANK WITH EXISTING BURIED UTILITIES. MAINTAIN
MINIMUM BURY DEPTH AS NOTED IN THE DUCT BANK DETAIL.
PP
PP
TC
PP
PP
PP
PP
A
B
C
D
1 3
PLOTTING
WAREHOUSE
WRAPPING
STORAGE (AMMUNITION)
STORAGE (SHRED)
A1D
A1D
A1D A1D
F4F1
OS1
RC1
W1E
W1E W1E
W1
W1
W1E
W1E
D1
D1E
D1
D1
X1E
F1
F1
F1 F1
T T T
W2 W2 W2
T
T
RC1
OS1
T T
4 5
F
OS1
OS1
D1D1E
G1
LV1
D1 D1
E
165-NH1-1
X1E
W1
HAC
OS1
WORKSPACE
MECHANICAL
STORAGE (FLAM.)
A1D
A1D
A1D
RC1
LVD
IT ROOM
ELECTRICAL
SECURE STOR.
CORRIDOR
CORRIDOR
D1E
D1
D1E
D1
WALK-IN REF.
BREAK ROOM
SV OFFICE
OS2
OS2
A1D
A1D
LVOD
RC1
A1D
RC1
LVOD
F1E
F1E
F1E
F1E
OS1
W1
165-NH1-1
W1
W1W1W1
165-NH1-1
165-NH1-1
P1D
P1DEP1DP1DE
P1D
P1DE P1D P1DE P1D
P1DE
P1DP1DE
P1DP1DE
P1DP1DE
P1D
PS PS
X1EX1E
C1
165-NH1-1
A1D
F1E F1E F1E F1E
UNISEX TOILET
UNISEX TOILET
F1 F1
RC1
V1
V1
LV1
OS1
DRAWING NUMBER
VA PROJECT NUMBER
DATE
PROJECT TITLE
BUILDING NUMBER
PROJECT LOCATION
CHECKED BY DRAWN BY
APPROVED: PROJECT DIRECTOR
VA FORM 08-6231
Office of Construction and Facilities Management
Dwg.
CONSULTANT INFORMATION
F
SHEET TITLE
ARCHITECT
FULLY SPRINKLERED
PROJECT PHASE
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
U.S. Department of Veteran Affairs
F
E
D
C
B
A
E
D
C
B
A
STRUCTURAL / CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH. / ELEC. / PLUMB. / TECH. ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 W. 161ST STREET
OLATHE, KS 66062
(913) 829-8650
LANDSCAPE ARCHITECT
ARC STUDIOS INC.
3117 E. FLOWER STREET
TUCSON, AZ 85716
(520) 882-9655
COMMISSIONING
GLHN ARCHITECTS & ENGINEERS, INC.
2939 E. BROADWAY BLVD
TUCSON, AZ 85716
(520) 881-4546
R1 - CONSTRUCT REPLACEMENT
WAREHOUSE
ELECTRICAL LIGHTING
FIRST FLOOR PLAN
01/06/2020 BEN ABM
500 AZ-89, PRESCOTT, AZ 86301
165-EL-101
649-414
BID DOCUMENTS
1/8" = 1'-0"
ELECTRICAL LIGHTING
FIRST FLOOR PLAN
N
ELECTRICAL PLAN NOTES
1 REFER TO DETAIL 10, SHEET 165-E-501 FOR WIRING DIAGRAM OF
ALL TYPICAL ROOM CONTROLLERS WITH SWITCHES, OCCUPANCY
SENSORS AND DAYLIGHT SENSORS.
2 REFER TO DETAIL 10, SHEET 165-E-501 FOR WIRING DIAGRAM OF
ALL TYPICAL ROOM CONTROLLERS WITH SWITCHES, OCCUPANCY
SENSORS AND DAYLIGHT SENSORS. LOCATE CONTROLLER IN
ADJACENT ACCESSIBLE CEILING.
3 PROVIDE RIGID METAL CONDUIT TO LIGHT FIXTURE WITHIN
FLAMMABLE STORAGE ROOM AND TO LIGHT SWITCH. ROUTE
CONDUIT OUT THROUGH TOP OF ROOM AND PROVIDE SEAL-OFF
FITTING BEFORE EXTENDING TO LIGHT SWITCH. DO NOT ROUTE
ANY OTHER CIRCUITS THROUGH THIS ROOM.
4 CIRCUIT TO EXIT SIGNS SHALL BE UNSWITCHED, TAKEN OFF
AHEAD OF THE POWER PACK.
GENERAL NOTES:
1 COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER'S
REPRESENTATIVE.
2 COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES. VERIFY
ALL EXISTING CONDITIONS BEFORE THE START OF WORK.
3 SEE SHEET 165-G-001 FOR ADDITIONAL INFORMATION REGARDING
SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK ON
EXISTING EQUIPMENT AND IN EXISTING BUILDINGS TO MINIMIZE
DISRUPTION OF SERVICES.
J J J
FACP
J
A
B
C
D
1 3
WAREHOUSE
WRAPPING
STORAGE (SHRED)
114 STORAGE (FLAM.)
STORAGE (AMMUNITION)
+48"
+48" +48" +48"
+48" +48"
+48"+48"
+48"
WP/WR
WP/WR
WP/WRWP/WR
+48"
+48"
1 1
+48"
+48"
WP/WR
WP/WR
WP/WR
165-NL1-1
165-NL1-1
165-NH1-1
9,11,13
165-NDB
+48"
165-NH1-1
2,4,6
60/3
165-NH1-1
8,10,12
60/3
165-NH1-1
14,16,18
60/3
165-NH1-1
20,22,24
60/3
165-NL1-1
165-NL1-1
165-NL1-1
4 165-NL1-1
165-NL1-1
30/3/3R
+48"
4 5
F
165-NL1-1
165-NL1-1
165-NL1-1
165-NL1-1
E
165-NL1-1
165-NL1-1
165-NL1-1
DIV. 23
+48"
165-EP-101
2SECURE STOR.
WALK-IN REF.
RECYCLING AREA
+40"
165-NL1-1
165-NL1-1
165-NL1-1
165-NL1-1
165-NL1-1
PLOTTING
HAC
UNISEX TOILET
UNISEX TOILET
WORKSPACE
IT ROOM
ELECTRICAL
165-NL1-1
57,59,61
165-NL1-1
38,40,42
165-NL1-1
32,34,36
SV OFFICE
BREAK ROOM
MECHANICAL
SPD
SPD
SPD
SPD
165-NL1-1
165-NL1-1
165-NL1-1
165-NL1-1
+48"
165-NL1-1
+40"
165-NL1-1
+40"
165-NL1-1
+40"
165-NL1-1
CU-DS
CU-DS
CU-ARU
AHU
CU-AHU
30/2/3R
165-NL1-1
35,37
30/2/3R
30/2/3R
MM DS
DS
165-NL1-1
48,50
165-NL1-1
44,46
165-NL1-1
48,50
165-NL1-1
44,46
(PART) (PART)
165-NDB
165-NL1-1
165-NL1-1
165-NL1-1
165-NL1-1
165-NL1-1
165-NL1-1
SPD
ARU
RP-1
WH-1 ET-1
165-NL1-1
M
165-NL1-1
M
165-NL1-1
165-NL1-1
165-NL1-1
CORRIDOR
CORRIDOR
WP/WR
DIV. 23
AC
AC
AC
AC
M
165-NL1-1
165-NL1-1
E
165-NL1-1
165-NH1-1
XFMR
165-NL2-1
165-NDB
165-NL1-2
165-NL1-2
2165-NL1-2
ELECTRICAL
IT ROOM
IDS
IDS
PACS
PACS
MATV
165-NL1-2
165-NL1-2
165-NL1-2
DRAWING NUMBER
VA PROJECT NUMBER
DATE
PROJECT TITLE
BUILDING NUMBER
PROJECT LOCATION
CHECKED BY DRAWN BY
APPROVED: PROJECT DIRECTOR
VA FORM 08-6231
Office of Construction and Facilities Management
Dwg.
CONSULTANT INFORMATION
F
SHEET TITLE
ARCHITECT
FULLY SPRINKLERED
PROJECT PHASE
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
U.S. Department of Veteran Affairs
F
E
D
C
B
A
E
D
C
B
A
STRUCTURAL / CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH. / ELEC. / PLUMB. / TECH. ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 W. 161ST STREET
OLATHE, KS 66062
(913) 829-8650
LANDSCAPE ARCHITECT
ARC STUDIOS INC.
3117 E. FLOWER STREET
TUCSON, AZ 85716
(520) 882-9655
COMMISSIONING
GLHN ARCHITECTS & ENGINEERS, INC.
2939 E. BROADWAY BLVD
TUCSON, AZ 85716
(520) 881-4546
R1 - CONSTRUCT REPLACEMENT
WAREHOUSE
ELECTRICAL POWER
FIRST FLOOR PLAN
01/06/2020 BEN ABM
500 AZ-89, PRESCOTT, AZ 86301
165-EP-101
649-414
BID DOCUMENTS
1/8" = 1'-0"
ELECTRICAL POWER FIRST FLOOR PLAN
N
# ELECTRICAL PLAN NOTES
1 PROVIDE RECEPTACLE FOR COILING OVERHEAD DOOR.
COORDINATE EXACT MOUNTING HEIGHT WITH GARAGE DOOR
INSTALLER.
2 PROVIDE POWER TO, AND INSTALL, HYDRAULIC LIFT CONTROL BOX.
COORDINATE EXACT LOCATION OF CONTROL BOX WITH HYDRAULIC
LIFT INSTALLER.
3 PROVIDE POWER TO HYDRAULIC LIFT PUSH BUTTON FURNISHED BY
HYDRAULIC LIFT MANUFACTURER.
4 PROVIDE WALL MOUNTED REACH TRUCK CHARGER WITH SB350
CONNECTOR. COORDINATE EXACT REQUIREMENTS WITH
FORKLIFT MANUFACTURER. COORDINATE EXACT MOUNTING
HEIGHT WITH GOVERNMENT.
5 PROVIDE NEMA L16-20R TWIST LOCKING RECEPTACLE.
COORDINATE EXACT REQUIREMENTS WITH BALER
MANUFACTURER. COORDINATE EXACT MOUNTING HEIGHT WITH
GOVERNMENT.
6 COORDINATE EXACT MOUNTING HEIGHT WITH INTERCOM MASTER
STATION. REFER TO DETAIL 1, SHEET 165-TI-101 FOR ADDITIONAL
INFORMATION.
7 PROVIDE POWER AND DISCONNECTING MEANS TO
REFRIGERATOR/REEFER. COORDINATE EXACT REQUIREMENTS
WITH MANUFACTURER.
8 PROVIDE 12"x24"xAPPROXIMATELY 5' H FLOOR-MOUNTED CHANNEL
STRUT FRAME FOR EQUIPMENT RECEPTACLES.
9 PROVIDE POWER FOR INTERCOM DEVICE. COORDINATE EXACT
LOCATION WITH DIVISION 27 CONTRACTOR.
GENERAL NOTES:
1 COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER'S
REPRESENTATIVE.
2 COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES. VERIFY
ALL EXISTING CONDITIONS BEFORE THE START OF WORK.
3 SEE SHEET 165-G-001 FOR ADDITIONAL INFORMATION REGARDING
SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK ON
EXISTING EQUIPMENT AND IN EXISTING BUILDINGS TO MINIMIZE
DISRUPTION OF SERVICES.
Revision # Date
1/4" = 1'-0"
ELECTRICAL ROOM 107 & IT ROOM 106
PARTIAL FLOOR PLAN
N
A
B
C
D
1 32
165-E-502
165-E-502
165-E-502
165-E-502
(TYP.)
(TYP.)
165-E-502
(TYP.)
4 5
F
165-E-502
165-E-502
(TYP.)
(TYP.)
165-E-502
(TYP.)
165-E-502
(TYP.)
E
RECYCLING AREA
EF
EF
EF
EF
EF
EF
165-NL1-1
165-NL1-1
IH
165-NL1-1
165-NL1-1
165-NH1-1
15,17,19
165-NH1-1
21,23,25
DRAWING NUMBER
VA PROJECT NUMBER
DATE
PROJECT TITLE
BUILDING NUMBER
PROJECT LOCATION
CHECKED BY DRAWN BY
APPROVED: PROJECT DIRECTOR
VA FORM 08-6231
Office of Construction and Facilities Management
Dwg.
CONSULTANT INFORMATION
F
SHEET TITLE
ARCHITECT
FULLY SPRINKLERED
PROJECT PHASE
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
U.S. Department of Veteran Affairs
F
E
D
C
B
A
E
D
C
B
A
STRUCTURAL / CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH. / ELEC. / PLUMB. / TECH. ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 W. 161ST STREET
OLATHE, KS 66062
(913) 829-8650
LANDSCAPE ARCHITECT
ARC STUDIOS INC.
3117 E. FLOWER STREET
TUCSON, AZ 85716
(520) 882-9655
COMMISSIONING
GLHN ARCHITECTS & ENGINEERS, INC.
2939 E. BROADWAY BLVD
TUCSON, AZ 85716
(520) 881-4546
R1 - CONSTRUCT REPLACEMENT
WAREHOUSE
ELECTRICAL ROOF PLAN
01/06/2020 BEN ABM
500 AZ-89, PRESCOTT, AZ 86301
165-EP-102
649-414
BID DOCUMENTS
1/8" = 1'-0"
ELECTRICAL ROOF PLAN
N
GENERAL NOTES:
1 COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER'S
REPRESENTATIVE.
2 COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES. VERIFY
ALL EXISTING CONDITIONS BEFORE THE START OF WORK.
3 SEE SHEET 165-G-001 FOR ADDITIONAL INFORMATION REGARDING
SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK ON
EXISTING EQUIPMENT AND IN EXISTING BUILDINGS TO MINIMIZE
DISRUPTION OF SERVICES.
ELECTRICAL PLAN NOTES:
1 DISCONNECT INTEGRAL TO UNIT.
Switch
LMRC-211
Dimming Room
Controller Neutral Wht
Unswitched
Hot Blk 120/277 Grn
Earth Ground
Normal Lights
V io
G ry
Vio Gry
Class 2 0-10 Volt Control Wiring
Leg #1
LMDM-101
WATTSTOPPER
LMLS-400
Photosensor
LMDC-100
CH1PC CH2 CH3 CH4 COM COM 24V GND
REMOTE OVERRIDE
(3) #12, (1)#12G, 3/4"C
TYPICAL
LOW-VOLTAGE PHOTOCELL.
REFER TO PLANS FOR
LOCATION.
CH1
NC
CH3
CH4
N
H
O
C
N
NO
CH2
120 - 277V
C
O
TIMESWITCH
CH2CH1 CH3 CH4
C
NC
NO
C
NC
NO
C
NC
NO
C
165-NH2-1 - 11
NOTES:
1. PROVIDE 365/7 DAY ASTRONOMICAL,
4-CHANNEL LIGHTING CONTROLLER.
PROVIDE 120V OR 277V POWER FROM
UNSWITCHED PORTION OF A CONTROLLED
LIGHTING CIRCUIT.
2. PROVIDE 30A, MECHANICALLY HELD,
ELECTRICALLY CONTROLLED LIGHTING
CONTACTORS WITH NUMBER OF POLES AS
SHOWN.
CONTACTOR C1
SET CHANNEL 1, "BUILDING
PERIMETER" FOR PHOTOCELL
ON, TIMESWITCH OFF AND
TIMESWITCH ON, PHOTOCELL
OFF FOR OPERATION OF
LIGHTS FOR EVENING AND
MORNING HOURS.
COORDINATE EXACT TIMES
WITH OWNER.
305mm m m
LINE SIDES OF EXCAVATION
WITH 13.6 KG (30 LBS.) FELT
PAPER
PULLBOX (SEE SPECIFICATIONS)
FINISHED PAVING
CLEAN 19mm (3/4")
CRUSHED ROCK
CONDUIT(S) WITH BELL
ENDS (TYP). SIZE,
QUANTITY AND WIRING
AS INDICATED ON PLANS
(4) CONCRETE BRICKS
51mmx203mmx406mm
(2"x8"x16")
(12")
(1
V
A R
IE
S
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS
AND USING THE RECOMMENDED MOUNTING HARDWARE.
DRYWALL BORDER
LUMINAIRE.
REFER TO
SCHEDULE
CEILING CROSS BEAM
GYPSUM BOARD
CEILING CROSS BEAM
LUMINAIRE MANUFACTURER'S
MOUNTING HARDWARE
REFER TO SPECIFICATION SECTION
26 51 00
LUMINAIRE.
REFER TO
SCHEDULE
GYPSUM BOARD (TYP)
CEILING MAIN BEAM
FIXTURE WHIP FROM
JUNCTION BOX
(1829mm (6') LONG
MAX.)
3 TWIST MINIMUM
(TYP)
LUMINAIRE SUSPENSION
WIRES REFER TO
SPECIFICATION
SECTION 26 51 00
DRYWALL CEILING
CROSS TEE, TYP.
HANGER WIRE AND MOUNTING
CHANNEL ATTACHED TO STRUCTURE
REFER TO SPECIFICATION SECTION
26 51 00
CEILING MAIN
BEAM.
DRYWALL CEILING
CROSS TEE, TYP.
GYPSUM
BOARD
WIRE TIE THROUGH
MOUNTING CHANNEL &
CROSS BEAM, TYP.
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS
AND USING THE RECOMMENDED MOUNTING HARDWARE.
LOCKING SQUARE
WASHER & NUT
6.35mm (1/4") SCREW
JUNCTION BOX
INTEGRAL GALVANIZED LIPPED
STEEL MOUNTING CHANNEL
FIXTURE WHIP FROM JUNCTION BOX
(1829mm (6') LONG MAX)
CEILING HANGER WIRE
ARCHITECTURAL
CEILING GRID
HANGER WIRE AND MOUNTING
CHANNEL ATTACHED TO STRUCTURE
REFER TO SPECIFICATION SECTION
26 51 00
ARCHITECTURAL
CEILING GRID
ACOUSTICAL
CEILING
TILE (TYP)
ARCHITECTURAL
CEILING GRID
WIRE TIE THROUGH
MOUNTING CHANNEL &
CROSS BEAM, TYP.
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS
AND USING THE RECOMMENDED MOUNTING HARDWARE.
LOCKING SQUARE
WASHER & NUT
6.35mm (1/4") SCREW
JUNCTION BOX
INTEGRAL GALVANIZED LIPPED
STEEL MOUNTING CHANNEL
FIXTURE WHIP FROM JUNCTION BOX
(1829mm (6') LONG MAX)
CEILING HANGER WIRE
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
WASHER &
LOCKNUT
9.52mm (3/8") MIN
GALVANIZED THREADED
ROD, TYP.
LOCKING SQUARE
WASHER & LOCKNUT
LENGTH AS REQUIRED
GENERAL NOTES:
1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING CHANNEL
LONGER THAN 915mm (36") SHALL BE INSTALLED WITH A CENTER
SUPPORT ROD.
2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED
METHOD PER SPECIFICATION 26 05 33, RACEWAY AND BOXES
FOR ELECTRICAL SYSTEMS. FIELD VERIFY EXACT CONDITIONS.
3. FOR TRAPEZE INSTALLATIONS IN SEISMIC AREAS REFER TO
SPECIFICATION SECTION 13 05 41, SEISMIC RESTRAINT
REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.
REFER TO PLANS FOR
QUANTITY & SIZE OF
CONDUITS
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
CONDUIT CLAMP. SIZE
AS REQUIRED
1. CONCRETE SHALL BE 2000 P.S.I. @ 28 DAYS, OR AS SPECIFIED.
2. PROVIDE #4 REINFORCING RODS ON TOP AND BOTTOM OF DUCTS WHEN
CROSSING OR PLACED IN ROADWAYS.
3. MINIMUM COVER TO TOP OF ENVELOPE SHALL BE 610mm (24") OR AS
OTHERWISE SPECIFIED IN SECTION 26 05 41.
4. PROVIDE MINIMUM 152mm (6") SPACE BETWEEN POWER AND
TELECOMMUNICATION DUCTS. INCREASE SIZE AS REQUIRED.
5. INNERDUCT QUANTITY AND SIZE AS INDICATED ON PLANS.
76mm 3"
76mm 3"
76mm 3" m m m m
4-WAY DUCT LINE
76mm
76mm m m
3"
3"
76mm
3" m m m m
WIRE TIE OR SCREW
BAR HANGER TO CROSS
BEAM TYP.
CEILING MAIN
BEAM
CEILING
CROSS BEAM
FIXTURE WHIP FROM
JUNCTION BOX (1829mm (6')
LONG MAX)
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS
AND USING THE RECOMMENDED MOUNTING HARDWARE.
RECESSED CAN
LUMINAIRE
CEILING BEAM
RECESSED CAN
LUMINAIRE
REFER TO
SCHEDULE.
GYPSUM
BOARD (TYP)
LUMINAIRE
BAR HANGERS
CEILING HANGER
WIRE, TYP.
LUMINAIRE SUSPENSION WIRES
REFER TO SPECIFICATION SECTION 26 51 00
(3
FINISHED GRADE
CONCRETE BASE &
REINFORCING STEEL,
SEE NOTE BELOW.
25mm (1") EMPTY
CONDUIT WITH CAP
(WHERE SHOWN ON
PLANS)
#4 BARE COPPER GROUND
6069mm(20'-0") COILED
BELOW BASE
GENERAL NOTES:
1. BACKFILL, CONCRETE, REINFORCING STEEL, AND ANCHOR BOLTS ARE
SHOWN FOR REFERENCE ONLY. STRUCTURAL DESIGN IS SHOWN ON
STRUCTURAL DRAWINGS.
2. REFER TO SPECIFICATION SECTION 26 56 00 FOR MOUNTING AND
LEVELING REQUIREMENTS.
(2
UNDISTURBED SOIL OR
SELECT BACKFILL
COMPACTED, SEE NOTE
BELOW.
PVC CONDUIT ADAPTER
COUPLING
RIGID STEEL CONDUIT
PVC CONDUIT
ANCHOR BOLTS PER POLE
MANUFACTURER'S REQUIREMENTS
WITH LEVELING NUTS ABOVE &
BELOW BASE PLATE
LIGHT POLE PER LIGHT
FIXTURE SCHEDULE
2-PIECE BOLT COVER PLATE.
POLE GROUNDING STUD
76x127mm (3"x5") REINFORCED
HAND HOLE WITH TAMPER
RESISTANT SCREWS. PROVIDE
IN-LINE SCREW-TYPE FUSE
HOLDER(S) WITH FUSE(S).
m m M
IN
m m M
IN
TOP OF HANDLE
6'-6" AFF MAXIMUM
4'-0" +/- AFF
FRONT VIEWSIDE VIEW
DISCONNECT SWITCH, CIRCUIT
BREAKER ENCLOSURE, OR
MOTOR CONTROLLER
CHANNEL STRUT POST BASE W
(4) 1/4" EXPANSION ANCHORS.
(TYPICAL)
PROVIDE RIGID CONDUIT TO
MECHANICAL/PLUMBING
EQUIPMENT. CONVERT TO
FLEXIBLE CONDUIT WITH BOND
WIRE FOR FINAL CONNECTION TO
EQUIPMENT.
FLOOR
STRUCTURAL CEILING
CHANNEL STRUT SUPPORT
FRAME.
1'-7" (MIN.)
OPTION 3: CHANNEL STRUT
ANGLE BRACKET SUPPORT
FOR EACH SUPPORT LEG WITH
1/2" FLOOR EXPANSION
ANCHOR.
PROVIDE RIGID CONDUIT BACK
TO ELECTRICAL SOURCE.
NOTE:
1. DISCONNECT SWITCHES, CIRCUIT BREAKER ENCLOSURES, MOTOR CONTROLLERS & VARIABLE FREQUENCY DRIVES, AND CONTROL CABINETS MAY BE DIRECTLY MOUNTED TO STRUCTURAL WALLS, OR TO MECHANICAL EQUIPMENT WHEN PERMITTED BY THE MECHANICAL EQUIPMENT MANUFACTURER AND WHERE IT DOES NOT BLOCK ACCESS OR OPERATION OF THE EQUIPMENT. WHERE A SUITABLE STRUCTURAL WALL IS NOT AVAILABLE, PROVIDE SUPPORT FRAME AND CONNECT THE SUPPORT FRAME WITH A MINIMUM OF (4) POINTS OF CONTACT TO THE BUILDING STRUCTURE TO PROVIDE A RIGID ASSEMBLY. OPTION 1, 2, OR 3 MAY BE UTILIZED TO PROVIDE THE ADDITIONAL (2) POINTS OF CONTACT IN ADDITION TO
THE (2) POINTS OF CONTACT AT THE FLOOR.
OPTION 1: EXTEND CHANNEL
STRUT FRAME TO STRUCTURAL
CEILING AND CONNECT TO STEEL
STRUCTURE OR CONCRETE
SLAB.
S T
R U
C T
U R
A L W
A L L
OPTION 2: PROVIDE CHANNEL
STRUT FRAME TO WALL AND
CONNECT TO STRUCTURE OF
WALL.
1. DAYLIGHT SENSORS SHALL CONTROL ALL LIGHT FIXTURES LOCATED WITHIN THE DAYLIGHT ZONES OF THE WINDOWS. FIXTURES
SHALL AUTOMATICALLY DIM BASED ON AMOUNT OF DAYLIGHT.
2. OCCUPANCY SENSORS SHALL CONTROL ALL LIGHTS WITHIN THE SPACE.
3. SWITCH $-LVOD SHALL PROVIDE AUTOMATIC OFF, MANUAL ON AND DIMMING CONTROL OF ALL FIXTURES WITHIN THE SPACE.
1. REFER TO OCCUPANCY SENSOR AND SWITCH SCHEDULE FOR ADDITIONAL INFORMATION. COMPONENTS SHOWN ARE FOR BASIS OF DESIGN MANUFACTURER. FOR OTHER MANUFACTURERS, PROVIDE A COMPLETE AND FUNCITIONING SYSTEM.
2. NOT ALL LIGHT FIXTURES, OCCUPANCY SENSORS, DAY LIGHT SENSORS, AND LIGHT SWITCH CONTROL DEVICES ARE SHOWN, REFER TO PLANS FOR LOCATIONS OF ALL DEVICES. PROVIDE WIRING BETWEEN ALL FIXTURES AND DEVICES FOR A COMPLETE AND FUNCTIONING SYSTEM. GROUND CONDUCTOR NOT SHOWN, PROVIDE GROUND CONDUCTOR IN ALL RACEWAYS.
NOTE:
SEQUENCE OF OPERATIONS:
DRAWING NUMBER
VA PROJECT NUMBER
DATE
PROJECT TITLE
BUILDING NUMBER
PROJECT LOCATION
CHECKED BY DRAWN BY
APPROVED: PROJECT DIRECTOR
VA FORM 08-6231
Office of Construction and Facilities Management
Dwg.
CONSULTANT INFORMATION
F
SHEET TITLE
ARCHITECT
FULLY SPRINKLERED
PROJECT PHASE
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
U.S. Department of Veteran Affairs
F
E
D
C
B
A
E
D
C
B
A
STRUCTURAL / CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH. / ELEC. / PLUMB. / TECH. ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 W. 161ST STREET
OLATHE, KS 66062
(913) 829-8650
LANDSCAPE ARCHITECT
ARC STUDIOS INC.
3117 E. FLOWER STREET
TUCSON, AZ 85716
(520) 882-9655
COMMISSIONING
GLHN ARCHITECTS & ENGINEERS, INC.
2939 E. BROADWAY BLVD
TUCSON, AZ 85716
(520) 881-4546
R1 - CONSTRUCT REPLACEMENT
WAREHOUSE
ELECTRICAL DETAILS
01/06/2020 BEN ABM
500 AZ-89, PRESCOTT, AZ 86301
165-E-501
649-414
BID DOCUMENTS
NOT TO SCALE
UNDERGROUND CONCRETE PULLBOX- TURF AREAS
NOT TO SCALE
LUMINAIRE MOUNTING - GYPBOARD CEILING
NOT TO SCALE
EXIT SIGN MOUNTING - GYPBOARD CEILING
NOT TO SCALE
EXIT SIGN MOUNTING - LAY - IN CEILING
NOT TO SCALE
CONDUIT TRAPEZE MOUNTING DETAIL
NOT TO SCALE
DUCT BANK DETAIL
NOT TO SCALE
DOWNLIGHT MOUNTING - GYPBOARD CEILING
NOT TO SCALE
POLE BASE DETAIL- TURF AREAS
NOT TO SCALE
ELECTRICAL EQUIPMENT MOUNTING DETAIL
NOT TO SCALE
TYPICAL ROOM CONTROLLER - LIGHTING CONTROL WIRING DIAGRAM
NOT TO SCALE
TIME SWITCH - LIGHTING CONTROL DIAGRAM
BONDING CONDUCTOR
PIPE BONDING STRAP
CLAMP, SIZE AS REQUIRED
FOR PIPE
LIGHTNING PROTECTION
CONDUCTOR
UNIVERSAL PARALLEL
CABLE SPLICER
BUTT END STRAIGHT
CABLE SPLICER
PARALLEL CABLE
SPLICER
LIGHTNING PROTECTION
BONDING CONDUCTOR
TO BONDS
CABLE TO SURFACE
EXOTHERMIC CONNECTION
(FIELD INSTALLED), GRIND TO
BARE STEEL SURFACE
MAIN LIGHTNING CONDUCTOR
TO GROUND ROD
STEEL COLUMN
CABLE TO SURFACE
EXOTHERMIC CONNECTION
(FIELD INSTALLED), GRIND TO
BARE STEEL SURFACE
TO THROUGH ROOF
CONNECTION
JGW
M
IN
IM
U
M
24"MINIMUM
W
ALL
GRADE
GROUND ROD
CABLE TO GROUND
ROD CLAMP
1" SCHEDULE 40 PVC
RACEWAY
LIGHTNING PROTECTION
CONDUCTOR
M
IN
IM
U
M
PARAPET WALL
ROOF
AIR TERMINAL
ADHESIVE TYPE AIR TERMINAL
BASE MOUNTED VERTICALLY
LIGHTNING PROTECTION
CONDUCTOR
ADHESIVE STYLE
CABLE FASTENER
ADHESIVE STYLE CABLE
FASTENER MOUNTED TO
ROOF
LIGHTNING PROTECTION
CONDUCTOR
CABLE FASTENER WITH
STAINLESS STEEL
HARDWARE, CAULK
PENETRATIONS
BONDING PLATE MOUNTED
WITH STAINLESS STEEL
FASTENERS, CAULK
PENETRATIONS
M
IN
IM
U
M
LIGHTNING PROTECTION
CONDUCTOR
FLAT SURFACE AIR TERMINAL
BASE MOUNTED WITH
STAINLESS STEEL FASTENERS,
CAULK PENETRATIONS
TOP OF EQUIPMENT
AIR TERMINAL
THROUGH ROOF CABLE
CONNECTING ASSEMBLY
ROOF PENETRATION FLASHING
BOOT
LIGHTNING PROTECTION
CONDUCTOR
LIGHTNING PROTECTION
CONDUCTOR
M
IN
IM
U
M
ADHESIVE STYLE
CABLE FASTENER
LIGHTNING PROTECTION
CONDUCTOR
ADHESIVE TYPE AIR TERMINAL
AIR TERMINAL
FLAT ROOF
DRAWING NUMBER
VA PROJECT NUMBER
DATE
PROJECT TITLE
BUILDING NUMBER
PROJECT LOCATION
CHECKED BY DRAWN BY
APPROVED: PROJECT DIRECTOR
VA FORM 08-6231
Office of Construction and Facilities Management
Dwg.
CONSULTANT INFORMATION
F
SHEET TITLE
ARCHITECT
FULLY SPRINKLERED
PROJECT PHASE
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
U.S. Department of Veteran Affairs
F
E
D
C
B
A
E
D
C
B
A
STRUCTURAL / CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH. / ELEC. / PLUMB. / TECH. ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 W. 161ST STREET
OLATHE, KS 66062
(913) 829-8650
LANDSCAPE ARCHITECT
ARC STUDIOS INC.
3117 E. FLOWER STREET
TUCSON, AZ 85716
(520) 882-9655
COMMISSIONING
GLHN ARCHITECTS & ENGINEERS, INC.
2939 E. BROADWAY BLVD
TUCSON, AZ 85716
(520) 881-4546
R1 - CONSTRUCT REPLACEMENT
WAREHOUSE
ELECTRICAL DETAILS
01/06/2020 BEN ABM
500 AZ-89, PRESCOTT, AZ 86301
165-E-502
649-414
BID DOCUMENTS
NOT TO SCALE
VENT THRU ROOF DETAIL
NOT TO SCALE
SPLICERS/CONDUCTORS
NOT TO SCALE
COLUMN GROUNDING DETAIL
NOT TO SCALE
DOWNLEAD TO GRND ROD
NOT TO SCALE
TYPICAL PARAPET AIR TERMINAL
NOT TO SCALE
MECHANICAL UNIT BONDING TERMINAL
NOT TO SCALE
AIR TERMINAL ON EQUIPMENT
NOT TO SCALE
TYPICAL THROUGH ROOF CONNECTION
NOT TO SCALE
TYPICAL FLAT ROOF AIR TERMINAL
LV1
LVOD
OS1
T
PS
OS1
OS2
RC1
PP
WALL SWITCH SENSOR REQUIRES NEUTRAL CONDUCTOR FOR OPERATION1.
NOTES:
DO NOT INSTALL LINE VOLTAGE SENSORS ON GFCI PROTECTED CIRCUITS.E.
ALL SENSORS SHALL HAVE AN ADJUSTABLE TIME DELAY RANGE OF 30 SECONDS TO 30 MINUTES, UNLESS NOTED OTHERWISE.D.
VERIFY COLOR(S) FOR WALL SWITCHES WITH ARCHITECT.C.
PROVIDE ALL SENSORS FROM SAME MANUFACTURER.B.
SENSOR LAYOUT BASED ON COVERAGE PATTERNS OF MANUFACTURERS INDICATED ABOVE. ADJUSTS QUANTITIES AND LOCATIONS FOR ALTERNATE MANUFACTURERS.A.
GENERAL NOTES:
SINGLE-POLE, AUTO-OFF IN-WALL TIMER WITH ADJUSTABLE TIMING
FROM 5 MINUTES TO 12 HOURS AND VISUAL AND AUDIBLE WARNING.
MINUTES
MANUALN/A120/277VWATTSTOPPER: TS-400-W
LINE VOLTAGE, 1-BUTTON DUAL TECHNOLOGY OCCUPANCY LIGHT
SWITCH.
MINUTES
MANUALN/A120/277VWATTSTOPPER: DW-100-U
LOW VOLTAGE, 2-BUTTON DIMMING DIGITAL DUAL TECHNOLOGY
OCCUPANCY SENSOR LIGHT SWITCH COMPATIBLE WITH DIGITAL ROOM
CONTROLLER WITH CAT5E NETWORKING.
MINUTES
MANUALN/A
24V DC
INPUT
WATTSTOPPER: LMDW-102-U
LOW VOLTAGE, 1-BUTTON DIGITAL LIGHT SWITCH COMPATIBLE WITH
DIGITAL ROOM CONTROLLER WITH CAT5E NETWORKING.
N/AMANUALN/A
24V DC
INPUT
WATTSTOPPER: LMSW-101-U
CEILING MOUNTED, DUAL TECHNOLOGY DIGITAL OCCUPANCY SENSOR
COMPATIBLE WITH DIGITAL ROOM CONTROLLER WITH CAT5E
NETWORKING.
MINUTES
AUTO
MINIMUM 28', 360 DEGREE
RADIAL COVERAGE AT 9'
MOUNTING HEIGHT
24V DC
INPUT
WATTSTOPPER: LMDC-100-U
CEILING MOUNTED, DUAL TECHNOLOGY DIGITAL OCCUPANCY SENSOR
COMPATIBLE WITH DIGITAL ROOM CONTROLLER WITH CAT5E
NETWORKING.
MINUTES
MANUAL
MINIMUM 28', 360 DEGREE
RADIAL COVERAGE AT 9'
MOUNTING HEIGHT
24V DC
INPUT
WATTSTOPPER: LMDC-100-U
CEILING MOUNTED, AUTOMATIC DIMMING DIGITAL PHOTOSENSOR
COMPATIBLE WITH DIGITAL ROOM CONTROLLER WITH CAT5E
NETWORKING AND WITH FULL RANGE DIMMING WITH FOOTCANDLE
SETPOINTS FROM 20-60 FC. SET SENSOR FOR 35 FC.
N/AN/AN/A
24V DC
INPUT
WATTSTOPPER: LMLS-400-U
ONE RELAY/ZONE DIGITAL ROOM CONTROLLER WITH 0-10V DIMMING
OUTPUT AND CAT5E NETWORKING WITH CONTROL DEVICES.
N/AN/AN/A
120/277V, 24V DC,
0-10V DC
DIMMING
WATTSTOPPER: LMRC-211-U
NOTESDESCRIPTION
TIME
DELAY
ON MODECOVERAGEVOLTAGE
BASIS OF DESIGN:
MANUFACTURER AND MODEL
SYMBOL
TYPE
OCCUPANCY SENSOR AND SWITCH SCHEDULE
DRAWING NUMBER
VA PROJECT NUMBER
DATE
PROJECT TITLE
BUILDING NUMBER
PROJECT LOCATION
CHECKED BY DRAWN BY
APPROVED: PROJECT DIRECTOR
VA FORM 08-6231
Office of Construction and Facilities Management
Dwg.
CONSULTANT INFORMATION
F
SHEET TITLE
ARCHITECT
FULLY SPRINKLERED
PROJECT PHASE
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
U.S. Department of Veteran Affairs
F
E
D
C
B
A
E
D
C
B
A
STRUCTURAL / CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH. / ELEC. / PLUMB. / TECH. ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 W. 161ST STREET
OLATHE, KS 66062
(913) 829-8650
LANDSCAPE ARCHITECT
ARC STUDIOS INC.
3117 E. FLOWER STREET
TUCSON, AZ 85716
(520) 882-9655
COMMISSIONING
GLHN ARCHITECTS & ENGINEERS, INC.
2939 E. BROADWAY BLVD
TUCSON, AZ 85716
(520) 881-4546
R1 - CONSTRUCT REPLACEMENT
WAREHOUSE
ELECTRICAL SCHEDULES
01/06/2020 BEN ABM
500 AZ-89, PRESCOTT, AZ 86301
165-E-602
649-414
BID DOCUMENTS
LIGHT FIXTURE SCHEDULE
TYPE
BASIS OF DESIGN:
MANUFACTURER AND MODEL
MOUNTING
LAMP BALLAST/DRIVER
DESCRIPTION NOTES
TYPE LUMENS
COLOR
TEMP
TYPE VOLTAGE
INPUT
WATTS
INPUT
VA
A1D
WILLIAMS 50 STATIC SERIES:
50G-S24-L33/835-S-AF12125-DIM-UNV
LAY-IN GRID
CEILING PER DTL 9,
SHEET 165-E-501
INTEGRAL
WHITE LED
3300 lm 3500 K
0-10V LOW VOLTAGE
DIMMABLE
ELECTRONIC LED
DRIVER
277 V 26 W 29 VA
2'X4' RECESSED STATIC LED LIGHT FIXTURE WITH
WHITE TRIM AND FROSTED ACRYLIC SHIELDING AND
DIMMABLE DRIVER.
D1
WILLIAMS 6DR SERIES:
6DR-L10/835-DRV-UNV-O-M-OF-N-F2
LAY-IN GRID/ GYP.
BOARD CEILING
INTEGRAL
WHITE LED
1000 lm 3500 K
0-10V LOW VOLTAGE
DIMMABLE
ELECTRONIC LED
DRIVER
277 V 9 W 10 VA
6" MEDIUM DISTRIBUTION DOWNLIGHT WITH CLEAR
SEMI-SPECULAR REFLECTOR FINISH.
D1E
WILLIAMS 6DR SERIES:
6DR-L10/835-EM/10W-DIM-UNV-O-M-OF-WET/CC-N-F2
LAY-IN GRID/ GYP.
BOARD CEILING
INTEGRAL
WHITE LED
1000 lm 3500 K
0-10V LOW VOLTAGE
DIMMABLE
ELECTRONIC LED
DRIVER
277 V 9 W 10 VA
SAME AS TYPE "D1", EXCEPT WITH 90-MINUTE
BATTERY BACKUP AND INTEGRAL
SELF-TEST/DIAGNOSTICS.
F1
WILLIAMS 76 SERIES:
76-4-L32/840-WG-7611-DRV-UNV
CHAIN MOUNT AT
9'-0", UNO
INTEGRAL
WHITE LED
3200 lm 3500 K
STANDARD
ELECTRONIC LED
DRIVER
277 V 28 W 31 VA 4' LONG STRIP LIGHT WITH 11 GAUGE WIRE GUARD.
F1E
WILLIAMS 96 SERIES:
76-4-L40/835-H1AFR-DRV-UNV
CHAIN MOUNT AT
9'-0", UNO
INTEGRAL
WHITE LED
4000 lm 3500 K
STANDARD
ELECTRONIC LED
DRIVER
277 V 41 W 46 VA
4' LONG FULLY ENCLOSED AND GASKETED STRIP
LIGHT WITH 90-MINUTE BATTERY BACKUP AND
SELF-DIAGNOSTICS. COORDINATE EXACT LOCATION
OF FIXTURE IN ELEVATOR SHAFT WITH ELEVATOR
MANUFACTURER.
F4
EATON CHAMP MLL SERIES:
MLL-4/UNV1-S903-TF-P
GYP. BOARD
CEILING
INTEGRAL
WHITE LED
7100 lm 3500 K
STANDARD
ELECTRONIC LED
DRIVER
277 V 63 W 57 VA
4' LONG FULLY ENCLOSED AND GASKETED STRIP
LIGHT WITH POLYCARBONATE LENS, FEED THROUGH
HUBS AND PAINTED GRAY EPOXY FINISH.
G1
LDPI LEVP SERIES:
LEVP-14-U-53-L1-C
MOUNT TO
REFRIGERATOR
CEILING
INTEGRAL
WHITE LED
1123 lm 5300 K
STANDARD
ELECTRONIC LED
DRIVER
277 V 14 W 15 VA
5" WIDE LED GLOBE LIGHT WITH CLEAR GLASS
GLOBE AND GUARD.
P1D
EATON METALUX SERIES:
SSLED-LD5-15-M-UNV-L840-CD-1-MP/SHK-C61-SVPD3-LWR
CHAIN MOUNT AT
30'-0", UNO
INTEGRAL
WHITE LED
15000 lm 4000 K
0-10V LOW VOLTAGE
DIMMABLE
ELECTRONIC LED
DRIVER
277 V 111 W 123 VA
CLASSIC ROUND HIGH BAY LIGHT FIXTURE WITH
MEDIUM FROSTED POLYCARBONATE LENS,
DIMMABLE LED DRIVER AND INTEGRAL
OCCUPANCY/DAYLIGHT SENSORS. SET DAYLIGHT
SENSOR AT 10FC AT FLOOR LEVEL.
P1DE
EATON METALUX SERIES:
SSLED-LD5-15-M-UNV-L840-EL20W-REM-CD-1-MP/SHK-C61-SVPD3-LWR
CHAIN MOUNT AT
30'-0", UNO
INTEGRAL
WHITE LED
15000 lm 4000 K
0-10V LOW VOLTAGE
DIMMABLE
ELECTRONIC LED
DRIVER
277 V 111 W 123 VA
SAME AS TYPE "P1", EXCEPT WITH 90-MINUTE
BATTERY BACKUP AND SELF-DIAGNOSTICS OR
LASER TESTING CAPABILITIES.
2, 3
S4A
FIXTURE: NLS VUE SERIES
VUE-1-T2-32L-1-40K-UNV-DPS6-BRZ
WIRELESS LTG CNTLR: SYNAPSE DIM10-250-11
ANTENNA: SYNAPSE GLP-KIT-ANT18-03
36" AFG POLE
BASE PER DTL 3,
SHEET 165-E-501
INTEGRAL
WHITE LED
10574 lm 4000 K
STANDARD
ELECTRONIC LED
DRIVER
277 V 70 W 78 VA
LED PARKING LOT LIGHT WITH TYPE T4 LIGHT
DISTRIBUTION PATTERN AND DARK BRONZE FINISH
ON 25' TALL, 5" SQUARE STEEL POLE, WITH
WIRELESS LIGHTING CONTROLLER AND ANTENNA.
S4D
FIXTURE: NLS VUE SERIES
VUE-1-T4-32L-1-40K-UNV-DPS6-BRZ
WIRELESS LTG CNTLR: SYNAPSE DIM10-250-11
ANTENNA: SYNAPSE GLP-KIT-ANT18-03
36" AFG POLE
BASE PER DTL 3,
SHEET 165-E-501
INTEGRAL
WHITE LED
10560 lm 4000 K
STANDARD
ELECTRONIC LED
DRIVER
277 V 70 W 78 VA
LED PARKING LOT LIGHT WITH TYPE T2 LIGHT
DISTRIBUTION PATTERN AND DARK BRONZE FINISH
ON 25' TALL, 5" SQUARE STEEL POLE, WITH
WIRELESS LIGHTING CONTROLLER AND ANTENNA.
V1
EATON SHAPER SERIES:
605-25-W-L3/835-UNV-MW
WALL MOUNT 6'-6"
AFF
INTEGRAL
WHITE LED
2000 lm 3500 K
STANDARD
ELECTRONIC LED
DRIVER
277 V 20 W 22 VA
WALL MOUNTED VANITY LIGHT WITH WHITE FINISH
AND OPAQUE LENS.
W1
WILLIAMS VOLTAIRE SERIES:
VWPH-L30/740-TFT-SLV-SDGL-DRV-UNV
WALL,10'-0" ABOVE
FINISHED FIRST
FLOOR LEVEL.
INTEGRAL
WHITE LED
3000 lm 4000 K
STANDARD
ELECTRONIC LED
DRIVER
277 V 36 W 40 VA
ARCHITECTURAL WALL PACK WITH FORWARD
THROW DISTRIBUTION, SATIN ALUMINUM FINISH,
DIFFUSED TEXTURED TEMPERED GLASS LENS, AND
DIMMABLE DRIVER.
W1E
WILLIAMS VOLTAIRE SERIES:
VWPH-L30/740-EM/4W-TFT-SLV-SDGL-DRV-UNV
WALL,10'-0" ABOVE
FINISHED FIRST
FLOOR LEVEL.
INTEGRAL
WHITE LED
3000 lm 4000 K
STANDARD
ELECTRONIC LED
DRIVER
277 V 36 W 40 VA
SAME AS TYPE "W1", EXCEPT WITH 90-MINUTE
BATTERY BACKUP AND INTEGRAL
SELF-TEST/DIAGNOSTICS. PROVIDE EMERGENCY
DRIVER IN ACCESSIBLE LOCATION INSIDE BUILDING
W2
WILLIAMS VF2 SERIES:
VF2-L57-MF-CU-DBZ-WG-DIM-277
WALL MOUNT AT
9'-0" TO BOTTOM
OF FIXTURE
INTEGRAL
WHITE LED
5700 lm 4000 K
STANDARD
ELECTRONIC LED
DRIVER
277 V 53 W 59 VA
ARCHITECTURAL FLOOD LIGHT WITH MEDIUM
DISTRIBUTION, CURVED ARM WIREGUARD AND DARK
BRONZE FINISH. AIM FIXTURE FOR LIGHTING
INTERIOR OF TRUCK TRAILERS
X1E
WILLIAMS EXIT/CA SERIES:
EXIT/CA-R-AF-BA-EM-SDT
UNIVERSAL
TOP/END MOUNT
LED 0 lm 0 K
STANDARD EXIT
SIGN LED DRIVER
277 V 4 W 4 VA
UNIVERSAL MOUNT, SINGLE/DOUBLE FACE EXIT SIGN
WITH RED LETTERING BRUSHED ALUMINUM HOUSING
WITH 90-MINUTE BATTERY BACKUP AND INTEGRAL
SELF-TEST/DIAGNOSTICS.
NOTES:
1. INSTALL LIGHT FIXTURE, SYNAPSE LIGHTING CONTROLS AND LIGHT POLE FURNISHED BY GOVERNMENT. UPDATE GOVERNMENT SYNAPSE SITE LIGHTING MANAGEMENT SYSTEM WITH NEW POLE LOCATIONS
AND LIGHT MAC ADDRESSES.
2. INTEGRAL SELF-TEST/DIAGNOSTICS SHALL AUTOMATICALLY TEST EMERGENCY OPERATION OF FIXTURE AT REQUIRED INTERVALS AND INCLUDE DUAL-COLOR LED FOR INDICATION OF PROPER OPERATION - GREEN FOR PROPER OPERATION, RED FOR CHARGING, AND FLASHING RED FOR FAILURE OF INTERNAL COMPONENTS.
3. IF INTEGRAL SELF-TEST/DIAGNOSTICS BATTERY PACK IS NOT AVAILABLE FOR THIS FIXTURE, PROVIDE STANDARD 90-MINUTE BATTERY PACK WITH (2) LASERS FOR REMOTE TESTING EMERGENCY BATTERY
PACKS. PROVIDE ENCLOSURE IN ELECTRICAL ROOM FOR STORAGE OF LASERS.
4. INSTALL 180-DEGREE, TWO-HEADED LIGHT POLE FURNISHED BY GOVERNMENT. DRILL HOLES FOR TWO-HEADED, 90-DEGREE FIXTURE AS REQUIRED. PROVIDE PLUGS FOR UNUSED DRILL HOLES.
DRAWING NUMBER
VA PROJECT NUMBER
DATE
PROJECT TITLE
BUILDING NUMBER
PROJECT LOCATION
CHECKED BY DRAWN BY
APPROVED: PROJECT DIRECTOR
VA FORM 08-6231
Office of Construction and Facilities Management
Dwg.
CONSULTANT INFORMATION
F
SHEET TITLE
ARCHITECT
FULLY SPRINKLERED
PROJECT PHASE
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
U.S. Department of Veteran Affairs
F
E
D
C
B
A
E
D
C
B
A
STRUCTURAL / CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH. / ELEC. / PLUMB. / TECH. ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 W. 161ST STREET
OLATHE, KS 66062
(913) 829-8650
LANDSCAPE ARCHITECT
ARC STUDIOS INC.
3117 E. FLOWER STREET
TUCSON, AZ 85716
(520) 882-9655
COMMISSIONING
GLHN ARCHITECTS & ENGINEERS, INC.
2939 E. BROADWAY BLVD
TUCSON, AZ 85716
(520) 881-4546
R1 - CONSTRUCT REPLACEMENT
WAREHOUSE
ELECTRICAL SCHEDULES
01/06/2020 BEN ABM
500 AZ-89, PRESCOTT, AZ 86301
165-E-603
649-414
BID DOCUMENTS
MISC. EQUIPMENT (Z): 37099 VA 100.00% 37099 VA
SUPPLEMENTAL HEAT (Y):
LARGEST MOTOR (X): 4160 VA 125.00% 5200 VA
MOTORS (M): 6088 VA 100.00% 6088 VA
RECEPTACLES (R): 7740 VA 100.00% 7740 VA GF: GFCI TYPE CIRCUIT BREAKER
VD: UPSIZED FOR VOLTAGE DROP
LCK: HANDLE PADLOCKABLE-OFF DEVICE
LIGHTING (L): 0 VA 0 VA FEED THRU LUGS WITH #4/0 CONNECTION
HEATING (H); NOTES:
COOLING (C): 2080 VA 100.00% 2080 VA TOTALS: 159 A 162 A
EXISTING LOAD (E): PANELBOARD 57167 VA 58207 VA
LOAD TYPE CONNECTED LOAD NEC DEMAND DEMAND LOAD TOTAL CONNECTED TOTAL DEMAND
TOTAL PHASE LOAD (A): 187 A 136 A 161 A
TOTAL PHASE LOAD (VA) 22001 VA 16293 VA 18873 VA
PHASE A PHASE B PHASE C
83 EQUIPPED SPACE -- -- -- -- -- -- 0 1500 84
81 EQUIPPED SPACE -- -- -- -- -- -- 0 2040 82
79 EQUIPPED SPACE -- -- -- -- -- -- 0 1860
3 60 1L 1L R; Z PANELBOARD 165-EL1-2
77 EQUIPPED SPACE -- -- -- -- -- -- 0 0 -- -- -- -- -- -- EQUIPPED SPACE 78
75 EQUIPPED SPACE -- -- -- -- -- -- 0 0 -- -- -- -- -- -- EQUIPPED SPACE 76
73 EQUIPPED SPACE -- -- -- -- -- -- 0 0 -- -- -- -- -- -- EQUIPPED SPACE 74
71 EQUIPPED SPACE -- -- -- -- -- -- 0 0 -- -- -- -- -- -- EQUIPPED SPACE 72
69 SPARE -- -- -- 20 1 0 0 1 20 -- -- -- SPARE 70
67 SPARE -- -- -- 20 1 0 0 1 20 -- -- -- SPARE 68
65 SPARE -- -- -- 20 1 0 0 1 20 -- -- -- SPARE 66
63 FIRE ALARM CONTROL PNL Z FA 12 12 20 1 1000 0 1 20 -- -- -- SPARE 64
61 588 528 1 15 12 12 M EF-4 62
59 588 528 1 15 12 12 M EF-3 60
REFRIGERATOR/REEFER Z 12 12 15 3
588 1176 1 20 12 12 M EF-2 58
55 INTERCOM DEVICE Z 12 12 20 1 500 528 1 15 12 12 M EF-1 56
53 BRK RM 102 GEN. PURPOSE R 12 12 20 1 360 500 1 20 12 12 Z WH-1 CONTROLS 54
51 BRK RM 102 GEN. PURPOSE R 12 12 20 1 180 48 1 20 12 12 M RP-1 52
49 BRK RM 102 REFRIDGERATOR Z GF 12 12 20 1 1200 1040 50
47 BRK RM 102 MICROWAVE Z GF 12 12 20 1 1200 1040
2 15 12 12 C; M CU-AHU-3
45 BRK RM 102 COFFEE BREWER Z GF 12 12 20 1 1200 1040 46
43 PLOTTING RM 108 COPIER Z 12 12 20 1 1200 1040
2 15 12 12 C; M CU-AHU-2
41 AHU-1 M 12 12 15 1 1200 576 42
39 RCPT: PLOTTING 108 GEN. PURP. R 12 12 20 1 360 576 40
37 2080 576
3 15 12 12 LCK Z HYDRAULIC LIFT CCT 2
CU-AHU-1 X 10 10 30 2
2080 576 36
33 IRRIGATION CONTROL PANEL Z VD 10 10 20 1 500 576 34
31 GATE OPERATOR Z VD 4 4 30 1 2160 576
3 15 12 12 LCK Z HYDRAULIC LIFT CCT 1
29 RCPT: PERIMETER RECEPTACLES R VD 10 10 20 1 720 1200 1 20 12 12 Z RCPT: INTERCOM MASTER 30
27 RCPT: PERIMETER RECEPTACLES R VD 10 10 20 1 720 1200 1 20 10 10 VD Z GOLF CART 28
25 RCPT: WHS GEN. PURP. R VD 10 10 20 1 900 1200 1 20 10 10 VD Z PALLET JACK CCT 2 26
23 RCPT: WHS GEN. PURP. R VD 10 10 20 1 540 1200 1 20 10 10 VD Z PALLET JACK CCT 1 24
21 WHS WORKSTATION 4 Z 12 12 20 1 360 720 1 20 12 12 R SV OFFICE 22
19 WHS WORKSTATION 3 Z 12 12 20 1 360 720 1 20 12 12 R WHS GEN. PURPOSE CCT 2 20
17 WHS WORKSTATION 2 Z 12 12 20 1 360 1200 1 20 12 12 GF Z 1ST FLOOR WATER COOLER 18
15 WHS WORKSTATION 1 Z 12 12 20 1 360 180 1 15 12 12 R WRAPPING MACHINE 16
13 RCPT: EMER. PHARMACY CACHE R 12 12 20 1 360 1200 1 25 10 10 Z ELECTRICAL HAND TRUCK 14
11 RCPT: PLOT 104 PLOTTER Z 12 12 20 1 240 1200 1 25 10 10 Z ELECTRICAL HAND TRUCK 12
9 RCPT: PLOT 104 LAMINATOR Z 12 12 20 1 1500 864 1 20 12 12 Z WHS GARAGE DOOR CCT 5 10
7 RCPT: PLOT 104 BINDER Z 12 12 20 1 1200 720 1 20 12 12 R WHS GEN. PURPOSE CCT 1 8
5 RCPT: PLOT 104 PAPER CUTTER Z 12 12 20 1 1200 864 1 20 10 10 VD Z WHS GARAGE DOOR CCT 3 6
3 RCPT: PLOT 104 COLOR PRINTER Z 12 12 20 1 240 864 1 20 10 10 VD Z WHS GARAGE DOOR CCT 2 4
1 UNISEX RESTROOMS R; Z 12 12 20 1 600 864 1 20 10 10 VD Z WHS GARAGE DOOR CCT 1 2
CKT
NO.
DESCRIPTION
LOAD
TYPE
NOTE
WIRE
SIZE
GND
SIZE
BRKR
AMP
P A B C A B C P
BRKR
AMP
GND
SIZE
WIRE
SIZE
NOTE
LOAD
TYPE
DESCRIPTION
CKT
NO.
VOLT-AMPS/PHASE
SECTIONS: 2
A.I.C RATING: FCA +10% MINIMUM FULLY RATED FED FROM: XFMR 165-NL2-1
MOUNTING: SURFACE SERVES: 1ST FLOOR NORMAL LOADS
VOLTS/PHASE: 208Y/120V, 3PH, 4W LOCATION: ELEC 107
MAIN SIZE/TYPE: 225 A MCB FAULT CURRENT: RE: ONE-LINE DIAGRAM EQUIPMENT GROUND BUS
BUS SIZE: 250 A
PANELBOARD: 165-NL1-1
MISC. EQUIPMENT (Z): 88401 VA 100.00%…