Attachment 9_Drawings_201-400_11x17_040323.pdf

PDF 38 MB Posted

Attached to
Leadville Water Treatment Plant
Solicitation number
140R4023R0011
Issued by

View the file

Other files

File Type Posted
2_-_LMDT-WTP_Field_Investigation_Travel_Report_0003.pdf PDF
DB-_Building_0003.pdf PDF
1_-_Geotechnical_Recommendations_2022__7-6-2022_FINAL_0003.pdf PDF
Summary_of_changes_-_0003_0003.pdf PDF
4_-_Test_Pits_at_LMDT_WTP_Leadville__CO_Travel_Report_0003.pdf PDF
3_-_Leadville_Mine_Drainage_Tunnel-Preconstruction_Geologic_Design_Data_Water_Treatment_Plant_0003.pdf PDF
DB-_Heavy_0003.pdf PDF
5_-_TM-85-832000-2020-15_PhaseII_SRT-ERT_Leadville-WTP_FINAL-RDM_0003.pdf PDF
Sol_140R4023R0011_Amd_0003.pdf PDF
140R4023R0011_RFP_27June23_0003.pdf PDF
Amendment_0002_Description_of_changes_0002.pdf PDF
Drawings-AMD0002_0002.pdf PDF
Questions_11_Amendment_0002_0002.pdf PDF
Specs-AMD0002_0002.pdf PDF
Price_Schedule_B-AMD0002_0002.pdf PDF
Sol_140R4023R0011_Amd_0002.pdf PDF
Leadville_WTP_Visit_Information_(1)_0001.pdf PDF
Sol_140R4023R0011_Amd_0001.pdf PDF
Pre-bid_Site_Visit_LMDT_WTP_Prebid_Presentation_-_TSC_0001.pptx PPTX presentation
Sign-in_Sheet_0001.pdf PDF
140R4023R0011-_Questions_1-10_Amendment_1_0001.pdf PDF
Attachment_21_-_00_00_02_Drawings_1261-1307_11x17_LeadvilleWTP_09-16-2022_0001.pdf PDF
Attachment 15_Dwgs-Info_1001-1100_11x17_Set5_091622.pdf PDF
Attachment___2_Specifications2.pdf PDF
RFP_17APR23.pdf PDF
Attachment 7 Specifications.pdf PDF
Attachment__10_Drawings_401-678_11x17_040323.pdf PDF
Attachment__17_-_Past_Performance_Questionnaire.pdf PDF
Attachment___3_Specifications3.pdf PDF
Attachment___20_-_Wage_Determination.pdf PDF
Sol_140R4023R0011.pdf PDF
Attachment 13_Dwgs-Info_801-875_11x17_Set3_091622zip.pdf PDF
Attachment 8_Drawings_001-200_11x17_040323.pdf PDF
Attachment___1_Specifications1.pdf PDF
Attachment__18_-_Project_Experience_Form.docx DOCX document
Attachment 14_Dwgs-Info_876-900_11x17_Set4_091622zip.pdf PDF
Attachment__5_Specification5.pdf PDF
Attachment 11_Dwgs-Info_679-745_11x17_Set1_091622.pdf PDF
Attachment___4_Specifications4.pdf PDF
Attachment 12_Dwgs-Info_746-800_11x17_Set2_091622zip.pdf PDF
Attachment 16_Dwgs-Info_1101-1260_11x17_Set6_091622.pdf PDF
Attachment__19_-_Subcontracting_Plan_Template.docx DOCX document
Attachment 6 Specifications6.pdf PDF
Show all 43

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

HFB

K

E

JG

W14x48

JG

JG

JG

W14x48

JG

JG

W14x48

W14x48

W14x48 W14x48

W10x17

W x1

JG

JG

W14x48

W14x48W14x48

W14x48

K

2'

M ax O

C

K

2'

M ax O

C

K

2'

M ax O

C

K

2'

M ax O

C

K

2'

M ax O

C

K

2'

M ax O

C

K

2'

M ax O

C

2.

5K

2'

M ax O

C

K

2'

M ax O

C

6'-6"

Stair Down

0"

0"

0"

A 60688

A 60688

B 60688

B 60688

C 60689

C 60689

D 60689

D 60689

E 60690

11'-0" 8'-0" 21'-0" 22'-0"

60697

SIM

Joist top chord extension (R-type) See Detail 4 (60695)

Joist top chord extension (R-type) See Detail 4 (60695)

60695

Joist top chord extension (R-type) See Detail 7 (60697)

Joist top chord extension (R-type) See Detail 7 (60695)

60697

60695

60697

60697

60812

60697

60697

Angle Kickers @5'-0" OC max See Detail 1 (60697)

H 60690

H 60690

I 60691

I 60691

J 60692

J 60692

See Drawing (60696) For HVAC Platform

SIM1

60812

60697

60812

SIM

Steel Stair or prefabricated stair by contractor

60697

HSS4½x4½x (Typ.)

62'-0"

D

C

B

D

C

B

A

A

SA

FE

TY

AL

W

AY

S

TH

IN

K

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

AR

TM

EN

T O

F

TH

E

IN

TE

R

IO

R

DESIGNED

CHECKED

DRAWN

TECH. APPR.

APPROVED

LE

A D

V

IL

LE

M

IN

E

D R A

IN

A G

E

TU

N N

EL

LE

A D

V

IL

LE

C O

LE

A D

V

IL

LE

M

IN

E

TR

EA

TM

EN

T

PL

A N

T A N

D F

A C

IL

IT

IE

S W

A

TE

R T

R

EA

TM

EN

T

PL

A N

T

Brandon Jackson, P.E.

Brandon Bowman, P.E.

Lisa Orgren, P.E.

Brandon Jackson, P.E.

David Kresin, P.E.

Peer Reviewer - Plant Structures Group

DENVER, CO 2022-09-30

STRUCTURAL STEEL

FRAMING PLAN

LEVEL 03

OFFICE

1335-D-60684

Scale: 3/16" = 1'-0"

FRAMING PLAN - LEVEL 03 - OFFICE

NOTES

1. For structural design data, see (60589) - (60592).

2. For structural steel general notes and abbreviations, see (60662).

3. See (60693) - (60695) for Joist Girder Schedules

K

E

Stair Down

0"

0"

0"

40'-0"

11'-0" 8'-0" 21'-0"

9 1/2" EOS

1'-6" EOS

1' -6

EO

S

1" EJ 1" EJ

Slab-on-Deck (5" total thickness) See Note 4,5

Slab-on-Deck (5" total thickness) See Note 4,5

#4x3'-0"@24"OC

#4x3'-0"@24"OC

#4x3'-0"@24"OC

#4x3'-0"@24"OC

(2)#4 cont.

(2)#4 cont.

(2)#4 cont.

Slab-on-Deck (5" total thickness) See Note 4,5

Reinforce slab with

#4@12" OC EW,

centered. See note 4

#4x3'-0"@24"OC

6'-8" EOS

9' -6

/8

EO

S

5/ 8"

E O

S

1/

2" E

O S

(2)#4 cont.

See Drawing (60696) For HVAC Platform

D

C

B

D

C

B

A

A

SA

FE

TY

AL

W

AY

S

TH

IN

K

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

AR

TM

EN

T O

F

TH

E

IN

TE

R

IO

R

DESIGNED

CHECKED

DRAWN

TECH. APPR.

APPROVED

LE

A D

V

IL

LE

M

IN

E

D R A

IN

A G

E

TU

N N

EL

LE

A D

V

IL

LE

C O

LE

A D

V

IL

LE

M

IN

E

TR

EA

TM

EN

T

PL

A N

T A N

D F

A C

IL

IT

IE

S W

A

TE

R T

R

EA

TM

EN

T

PL

A N

T

Brandon Jackson, P.E.

Brandon Bowman, P.E.

Lisa Orgren, P.E.

Brandon Jackson, P.E.

David Kresin, P.E.

Peer Reviewer - Plant Structures Group

DENVER, CO 2022-09-30

STRUCTURAL STEEL

SLAB-ON-DECK

REINFORCING

LEVEL 03

OFFICE

1335-D-60685

Scale: 3/16" = 1'-0"

SLAB-ON-DECK REINFORCING - LEVEL 03 - OFFICE

NOTES

1. For structural design data, see (60589) - (60592).

2. For structural steel general notes and abbreviations, see (60662).

3. For Reinforcement General Notes, see (60629).

4. Floor Construction: 5" thick normal weight concrete slab: 3 1/2" concrete over 1 1/2"x22Ga (1.5C) non-composite galvanized deck.

5. Reinforce slab with #4@12" OC each way, centered in slab.

6. Floor deck attachments: 5/8"ø puddle welds in 36/4 pattern at

S

K P

E M Q

W14x48 W14x48

W14x48

W14x48 W14x48 W14x48

W x7

W x7

W14x48 W14x48

W14x48W14x48W14x48 W14x48

W14x48

W14x48

W14x48

W14x48

W14x48

W14x48

W14x48

W x7

W x7

W x7

W x7

W x7

W x7

W x7

W x7

W x7

W T5 x2 2.

W T5 x2 2.

W T5 x2 2.

W T5x22.5

W T5x22.5

W T5x22.5

WT5x22.5

WT5x22.5

WT5x22.5

WT5

x2

2.5

WT5

x2

2.5

WT5

x2

2.5

W x7

W16x67

W16x67

W16x67

W16x67

W16x67

W16x67

W16x67

W16x67 W16x67

W16x67W16x67 W16x67

W16x67 W16x67

W16x67 W16x67

W16x67 W16x67

0"

0"

0"

W16x67

W16x67

W x7

116'-5"

11'-0" 8'-0" 21'-0" 22'-0" 16'-0" 9'-10" 15'-6" 13'-1"

A 60688

A 60688

B 60688

B 60688

C 60689

C 60689

D 60689

D 60689

E 60690

E 60690

F 60690

F 60690

G 60690

G 60690

J 60692

J 60692

H 60690

H 60690

EQ

EQ

EQ

EQ

EQ

EQ

3:

3:

3:

3:

3:

3:

3:

3:

3:

3:

3:

12 3:

3:

W8x28 (Wind Girt)

W16x67

W16x67

I 60691

I 60691

W8X15 Hoist Beam

W x1

W x1

W x1

W x1

WT5x22.5

WT5x22.5

WT5x22.5

0"

EQ

EQ

EQ

60757

(60692)

60757

60757

For Continuation See Drawing (60668)

For Masonry and hoist beam See Drawing (60827) See Detail 2 (60834)

HSS4½x4½x (Typ.)

D

C

B

D

C

B

A

A

SA

FE

TY

AL

W

AY

S

TH

IN

K

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

AR

TM

EN

T O

F

TH

E

IN

TE

R

IO

R

DESIGNED

CHECKED

DRAWN

TECH. APPR.

APPROVED

LE

A D

V

IL

LE

M

IN

E

D R A

IN

A G

E

TU

N N

EL

LE

A D

V

IL

LE

C O

LE

A D

V

IL

LE

M

IN

E

TR

EA

TM

EN

T

PL

A N

T A N

D F

A C

IL

IT

IE

S W

A

TE

R T

R

EA

TM

EN

T

PL

A N

T

Brandon Jackson, P.E.

Brandon Bowman, P.E.

Lisa Orgren, P.E.

Brandon Jackson, P.E.

David Kresin, P.E.

Peer Reviewer - Plant Structures Group

DENVER, CO 2022-09-30

STRUCTURAL STEEL

ROOF FRAMING PLAN

OFFICE

1335-D-60686

Scale: 3/16" = 1'-0"

ROOF FRAMING PLAN - OFFICE

NOTES

1. For structural design data, see (60589) - (60592).

2. For structural steel general notes and abbreviations, see (60662).

FB

S

E Q

B 60688

B 60688

C 60689

C 60689

G 60690

G 60690

J 60692

J 60692

I 60691

I 60691

WT5x22.5 (Typ.)

HB20 HB20

HB20

HB20HB20

HB20 HB20

HB20

HB21

HB21

HB21

HB21

HB21

HB20HB20

HB21

HB21

HB21

HB21 HB21

HB21

HB21 HB21

HB21HB21

HB21 HB21

HB21HB21

HB21

H 60690

H 60690

A 60688

A 60688

0"

0"

0"

EQ

EQ

EQ

EQ

EQ

EQ

19'-0" 13'-1"

11'-0" 8'-0"

60799

60799

60799

SIM

D

C

B

D

C

B

A

A

SA

FE

TY

AL

W

AY

S

TH

IN

K

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

AR

TM

EN

T O

F

TH

E

IN

TE

R

IO

R

DESIGNED

CHECKED

DRAWN

TECH. APPR.

APPROVED

LE

A D

V

IL

LE

M

IN

E

D R A

IN

A G

E

TU

N N

EL

LE

A D

V

IL

LE

C O

LE

A D

V

IL

LE

M

IN

E

TR

EA

TM

EN

T

PL

A N

T A N

D F

A C

IL

IT

IE

S W

A

TE

R T

R

EA

TM

EN

T

PL

A N

T

Brandon Jackson, P.E.

Brandon Bowman, P.E.

Lisa Orgren, P.E.

Brandon Jackson, P.E.

David Kresin, P.E.

Peer Reviewer - Plant Structures Group

DENVER, CO 2022-09-30

STRUCTURAL STEEL

FRAMING PLAN

ROOF BRACING OFFICE

1335-D-60687

Scale: 3/16" = 1'-0"

ROOF FRAMING PLAN - OFFICE - BRACING

NOTES

1. For structural design data, see (60589) - (60592).

2. For structural steel general notes and abbreviations, see (60662).

15 2019

TO COLUMN

El. 24.30

JG9 JG13

JG5JG1

W x1

W x1

W x1

W18x76 W18x76

58'-0"

29'-0" 29'-0"

I 60691

H 60690

J 60692

A t

Jo is t G ir de rs

1/ 2"

Ty p.

A t

S te el J oi st s 5"

Ty p.

3:12

TO COLUMN

El. 31.08

3" / 12"

60717

60717

15 2019

TO COLUMN

El. 33.30

58'-0"

29'-0" 29'-0"

W18x76 W18x76

W18x76 W18x76

JG10 JG14

JG6JG2

TO COLUMN

El. 40.25

H 60690

J 60692

A t

Jo is t G ir de rs

1/ 2"

Ty p.

A t

S te el J oi st

5"

Ty p.

A t

W F be am s, U

N O

5"

Ty p.

W x1

W x1

W x1

I 60691

3:12

3:12 3:12

3:12

60717

60717

5 SIM

60717

60717

SIM

60757

D

C

B

D

C

B

A

A

SA

FE

TY

AL

W

AY

S

TH

IN

K

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

AR

TM

EN

T O

F

TH

E

IN

TE

R

IO

R

DESIGNED

CHECKED

DRAWN

TECH. APPR.

APPROVED

LE

A D

V

IL

LE

M

IN

E

D R A

IN

A G

E

TU

N N

EL

LE

A D

V

IL

LE

C O

LE

A D

V

IL

LE

M

IN

E

TR

EA

TM

EN

T

PL

A N

T A N

D F

A C

IL

IT

IE

S W

A

TE

R T

R

EA

TM

EN

T

PL

A N

T

Brandon Jackson, P.E.

Brandon Bowman, P.E.

Lisa Orgren, P.E.

Brandon Jackson, P.E.

David Kresin, P.E.

Peer Reviewer - Plant Structures Group

DENVER, CO 2022-09-30

STRUCTURAL STEEL

SECTIONS

1335-D-60688

60681 Scale: 3/16" = 1'-0"

A SECTION - OFFICE

60681 Scale: 3/16" = 1'-0"

B SECTION - OFFICE

LEVEL 03

El. 22.50

LEVEL 02

El. 10.50

LEVEL 01

El. 0.00

NOTES

1. For structural design data, see (60589) - (60592).

2. For structural steel general notes and abbreviations, see (60662).

3. For dimensions, see framing plans.

15 2019

58'-0"

29'-0" 29'-0"

W18x76W18x76

JG11 JG15

JG3 JG7

W x1

W x1

W x1

I 60691

H 60690

J 60692

A t

W F be am s, U

N O

5"

Ty p.

A t

Jo is t G ir de rs

1/ 2"

Ty p.

A t

S te el J oi st s 5"

Ty p.

3:12 3:12

60717

SIM60717

60717

60757

15 2019

W18x76 W18x76

JG12 JG16

JG4 JG8

W x1

W x1

W x1

58'-0"

29'-0" 29'-0"

A t

W F be am s, U

N O

5"

Ty p.

A t

Jo is t G ir de rs

1/ 2"

Ty p.

A t

S te el J oi st s 5"

Ty p.

H 60690

I 60691

J 60692

60697

3:12 3:12

60717

SIM

60757

60757

60717

60717

D

C

B

D

C

B

A

A

SA

FE

TY

AL

W

AY

S

TH

IN

K

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

AR

TM

EN

T O

F

TH

E

IN

TE

R

IO

R

DESIGNED

CHECKED

DRAWN

TECH. APPR.

APPROVED

LE

A D

V

IL

LE

M

IN

E

D R A

IN

A G

E

TU

N N

EL

LE

A D

V

IL

LE

C O

LE

A D

V

IL

LE

M

IN

E

TR

EA

TM

EN

T

PL

A N

T A N

D F

A C

IL

IT

IE

S W

A

TE

R T

R

EA

TM

EN

T

PL

A N

T

Brandon Jackson, P.E.

Brandon Bowman, P.E.

Lisa Orgren, P.E.

Brandon Jackson, P.E.

David Kresin, P.E.

Peer Reviewer - Plant Structures Group

DENVER, CO 2022-09-30

STRUCTURAL STEEL

SECTIONS

1335-D-60689

60681 Scale: 3/16" = 1'-0"

C SECTION - OFFICE

60681 Scale: 3/16" = 1'-0"

D SECTION - OFFICE

LEVEL 03

El. 22.50

LEVEL 02

El. 10.50

LEVEL 01

El. 0.00

TO COLUMN

El. 33.30

TO COLUMN

El. 40.25

NOTES

1. For structural design data, see (60589) - (60592).

2. For structural steel general notes and abbreviations, see (60662).

El. 22.50

LEVEL 03

TO COLUMN

El. 33.30

J 60692

29'-0"

W18x76

TO COLUMN

El. 40.25

W8x28 (Wind Girt)

I 60691

2' -3

/2

3:12

SIM60717

60717

60757

W x8 7W x8

El. 22.50

LEVEL 03

TO COLUMN

El. 33.30

J 60692

TO COLUMN

El. 40.25

29'-0"

W18x76

W x8

W x8

I 60691

3:12

60717

SIM

60717

60757

El. 22.50

LEVEL 03

TO COLUMN

El. 33.30

J 60692

TO COLUMN

El. 40.25

W18x76

W x8

H S S 4½ x4 ½ x

H S S 4½ x4 ½ x

W x8

I 60691

29'-0"

3:12

TO COLUMN

El. 31.08

60757

SIM60717

60717 360757

El. 0.00

LEVEL 01

El. 22.50

LEVEL 03

El. 10.50

LEVEL 02

HFB E

TO COLUMN

El. 33.30

A 60688

B 60688

C 60689

D 60689

TO COLUMN

El. 24.30

W14x48W14x48 W14x48

W14x48W14x48W14x48

40'-0"

21'-0"8'-0"11'-0"

W14x48

TOS El. 9.87A t

W F be am s, U

N O

5"

Ty p.

W x1

W x1

W x1

W x1

TO COLUMN

El. 27.67

1/

2" 2"

W14x48

1' -3

/8

8' -1

7/

8"

5/ 8"

1/

2"

1' -3

W14x48 W14x48

CB8

VB21

VB20

VB22

VB23

VB24

60811

60811

60715

60757

SIM

D

C

B

D

C

B

A

A

SA

FE

TY

AL

W

AY

S

TH

IN

K

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

AR

TM

EN

T O

F

TH

E

IN

TE

R

IO

R

DESIGNED

CHECKED

DRAWN

TECH. APPR.

APPROVED

LE

A D

V

IL

LE

M

IN

E

D R A

IN

A G

E

TU

N N

EL

LE

A D

V

IL

LE

C O

LE

A D

V

IL

LE

M

IN

E

TR

EA

TM

EN

T

PL

A N

T A N

D F

A C

IL

IT

IE

S W

A

TE

R T

R

EA

TM

EN

T

PL

A N

T

Brandon Jackson, P.E.

Brandon Bowman, P.E.

Lisa Orgren, P.E.

Brandon Jackson, P.E.

David Kresin, P.E.

Peer Reviewer - Plant Structures Group

DENVER, CO 2022-09-30

STRUCTURAL STEEL

SECTIONS

1335-D-60690

60681 Scale: 3/16" = 1'-0"

E SECTION - OFFICE

60686 Scale: 3/16" = 1'-0"

F SECTION - OFFICE

60686 Scale: 3/16" = 1'-0"

G SECTION - OFFICE

60681 Scale: 3/16" = 1'-0"

H SECTION - OFFICE

NOTES

1. For structural design data, see (60589) - (60592).

2. For structural steel general notes and abbreviations, see (60662).

El. 0.00

LEVEL 01

El. 22.50

LEVEL 03

El. 22.50

LEVEL 03

El. 10.50

LEVEL 02

HFB SK PE M Q

TO COLUMN

El. 40.25

TO COLUMN

El. 40.25

116'-5"

13'-1"15'-6"9'-10"16'-0"22'-0"21'-0"8'-0"11'-0"

W x8

W x8

W x8

W x8

W14x48W14x48W14x48

W14x48 W14x48 W14x48

W14x48W14x48

W14x48

W14x48 W14x48 W14x48 W14x48

W x1

W x1

W x1

W x1

B 60688

C 60689

D 60689

E 60690

F 60690

G 60690

A 60688

A t

W F be am s, U

N O

5"

Ty p.

7" 2"

/8

/8

9' -2

2"

/8

/8

TO COLUMN

El. 31.08

3/

8"

W14x48

SIM.

CB10

VB27

VB26

EQ

EQ

60811

60811

60715

60757 160757

W x8

D

C

B

D

C

B

A

A

SA

FE

TY

AL

W

AY

S

TH

IN

K

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

AR

TM

EN

T O

F

TH

E

IN

TE

R

IO

R

DESIGNED

CHECKED

DRAWN

TECH. APPR.

APPROVED

LE

A D

V

IL

LE

M

IN

E

D R A

IN

A G

E

TU

N N

EL

LE

A D

V

IL

LE

C O

LE

A D

V

IL

LE

M

IN

E

TR

EA

TM

EN

T

PL

A N

T A N

D F

A C

IL

IT

IE

S W

A

TE

R T

R

EA

TM

EN

T

PL

A N

T

Brandon Jackson, P.E.

Brandon Bowman, P.E.

Lisa Orgren, P.E.

Brandon Jackson, P.E.

David Kresin, P.E.

Peer Reviewer - Plant Structures Group

DENVER, CO 2022-09-30

STRUCTURAL STEEL

SECTION

1335-D-60691

60681 Scale: 3/16" = 1'-0"

I SECTION - OFFICE

NOTES

1. For structural design data, see (60589) - (60592).

2. For structural steel general notes and abbreviations, see (60662).

El. 22.50

LEVEL 03

El. 22.50

LEVEL 03

El. 10.50

LEVEL 02

HFB SK PE M Q

TO COLUMN

El. 33.30

TO COLUMN

El. 33.30

TO COLUMN

El. 24.30

W14x48 W14x48 W14x48 W10x17

116'-5"

13'-1"15'-6"9'-10"16'-0"22'-0"21'-0"8'-0"11'-0"

W14x48 W14x48 W14x48 W14x48

W x8

W x8

W x8

W x8

A 60688

B 60688

C 60689

E 60690

F 60690

G 60690

W14x48 W14x48

W14x48

W14x48W14x48

W14x48 W8x28 (Wind Girt)

W14x48

A t

W F be am s, U

N O

5"

Ty p.

TOS El. 9.87

W x1

W x1

W x1

W x1

2' -3

/2

8' -1

7/

8"

5/ 8"

2"

1' -3

1' -3

/8

/8

/8

W14x48

1/

2" 2"

HSS4½x4½x (Typ.)

60812

CB8

VB20

VB21

VB22

VB23

VB24

60811

60811

1 VB25

CB9

60811

HSS4½x4½x

60715

60715

60766

60757

1SIM

60757

SIM

60766

1SIM

W x8

D

C

B

D

C

B

A

A

SA

FE

TY

AL

W

AY

S

TH

IN

K

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

AR

TM

EN

T O

F

TH

E

IN

TE

R

IO

R

DESIGNED

CHECKED

DRAWN

TECH. APPR.

APPROVED

LE

A D

V

IL

LE

M

IN

E

D R A

IN

A G

E

TU

N N

EL

LE

A D

V

IL

LE

C O

LE

A D

V

IL

LE

M

IN

E

TR

EA

TM

EN

T

PL

A N

T A N

D F

A C

IL

IT

IE

S W

A

TE

R T

R

EA

TM

EN

T

PL

A N

T

Brandon Jackson, P.E.

Brandon Bowman, P.E.

Lisa Orgren, P.E.

Brandon Jackson, P.E.

David Kresin, P.E.

Peer Reviewer - Plant Structures Group

DENVER, CO 2022-09-30

STRUCTURAL STEEL

SECTION

1335-D-60692

60681 Scale: 3/16" = 1'-0"

J SECTION - OFFICE -GRID 20

NOTES

1. For structural design data, see (60589) - (60592).

2. For structural steel general notes and abbreviations, see (60662).

JOIST GIRDER SCHEDULE

End Moments

Wind Moment 1.0W (kip-ft)

Seismic Moment 1.0E (kip-ft)

Floor Live Load Moment (kip-ft)

Dead Load Moment (kip-ft)

Left Right Left Right Left Right Left Right

Axial Loads

Wind Axial Load 1.0W

(kip)

Seismic Axial Load 1.0E

(kip)

Girder Mark

Number Designation (Total Load/Live Load)

JG1

JG2

JG3

JG4

JG5

JG6

JG7

JG8

JG9

JG10

JG11

JG12

(1) Manufacturer to design Joist Girders using ASD. Nominal design loads shown are to be used in the applicable ASD code load combinations

(2) Deflection Criteria: Live Load Deflections L/360

(3) See framing plan for joist spacing along girder

(4) Top chord axial load, Tension or Compression Load

(5) End Moment Sign Convention, Positive moments:

±22.5

JG13

JG14

JG15

JG16

20BG 15N 2.5K/1.3K

20BG 15N 3.6K/1.9K

20BG-See loading diagram 20BG-See loading diagram

20BG 15N 2.5K/1.3K

20BG 15N 3.6K/1.9K

20BG 15N 5.4K/2.9K

20BG-See loading diagram

30.9 44.929.8 41.9±18.9 ±132.7 ±111.7

48.7 73.350.2 73.3

87.6 126.8

7.1 46.2

47.5 27.8

75.9 45.5

116.8 66.4

102.3 87.8

95.3 132.4

4.7 43.0

44.5 26.6

76.1 46.9

121.1 71.7

105.2 94.4

±23.0 ±19.2

±23.8 ±19.9

±24.4 ±20.6

±19.1 ±22.9

±19.9 ±24.0

±20.2 ±24.7

±21.1 ±25.5

±134.0 ±113.1

±135.8 ±114.4

±137.1 ±116.3

±111.7 ±132.7

±113.3 ±134.2

±114.0 ±135.4

±116.4 ±137.1

24BG 15N 3.0K/1.9K

24BG 15N 4.5K/2.9K

24BG 15N 3.0K/1.9K

24BG 15N 4.5K/2.9K

24BG 15N 6.9K/4.4K

24BG-See loading diagram

24BG 15N 6.9K/4.4K

24BG 15N 5.8K/3.7K

29.1 46.3

49.3 73.7

71.6 109.9

48.1 98.7

47.8 27.1

75.3 47.3

110.1 68.5

145.6 97.6

40.7 64.7

70.1 112.2

96.6 176.7

61.5 146.3

66.2 38.8

113.9 68.0

176.8 93.2

184.3 111.0

±10.7 ±8.4

±11.1 ±8.5

±12.5 ±10.3

±18.7 ±13.4

±8.2 ±10.5

±8.7 ±11.1

±9.8 ±11.9

±13.1 ±18.1

±68.1 ±53.0

±71.7 ±53.1

±78.0 ±61.3

±101.2 ±74.7

±53.1 ±68.1

±54.4 ±73.3

±60.4 ±77.1

±75.0 ±101.6

±28.8

±28.8

±20.2

±20.2

±2.6

±2.6

±4.9

±4.9

±1.1

±1.1

±9.5

±9.5

±3.0 ±16.9

±3.0 ±16.9

±9.9±2.4

±9.9±2.4

±3.5±1.6

±3.5±1.6

±6.2±2.9

±6.2±2.9

±10.5±4.9

±10.8±4.9

JOIST GIRDER ADDITIONAL REQUIREMENTS

Girder Mark Number

JG1-JG8

Min. Moment of Inertia IG (in4)

JG9-JG16

Min. Top chord thickness

(in)

Min. Top chord Horiz Leg

(in)

Min. Bot chord thickness

(in)

Min. Bot chord Horiz Leg

(in)

1343.3

2026.6

0.5 4 0.375 3

30.37540.5

15 19

60695

60695

SIM

27'-10 7/8" CLEARSPAN

60695

TYP BLOCKING

BTWN JOISTS

15 19

60695

60695

SIM

60695

27'-10 7/8" CLEARSPAN

TYP BLOCKING

BTWN JOISTS

15 19

60695

60695

SIM

27'-10 7/8" CLEARSPAN

60695

TYP BLOCKING

BTWN JOISTS

15 19

60695

60695

SIM

27'-10 7/8" CLEARSPAN

60695

TYP BLOCKING

BTWN JOISTS

60695

60695

SIM

27'-10 7/8" CLEARSPAN

60695

TYP BLOCKING

BTWN JOISTS

60695

60695

SIM

27'-10 7/8" CLEARSPAN

60695

TYP BLOCKING

BTWN JOISTS

60695

60695

SIM

27'-10 7/8" CLEARSPAN

60695

TYP BLOCKING

BTWN JOISTS

60695

60695

SIM

27'-10 7/8" CLEARSPAN

60695

TYP BLOCKING

BTWN JOISTS

(4 .2

K /2

.2 K

(4 .2

K /2

.2 K

(4 .2

K /2

.2 K

(4 .2

K /2

.2 K

(4 .2

K /2

.2 K

(4 .2

K /2

.2 K

(4 .2

K /2

.2 K

(4 .2

K /2

.2 K

(4 .2

K /2

.2 K

(5 .5

K /2

.9 K

(5 .5

K /2

.9 K

(5 .5

K /2

.9 K

(5 .5

K /2

.9 K

(5 .5

K /2

.9 K

JOIST GIRDER LOADING DIAGRAM

Per plan for joist spacing

See Joist Girder Schedule for Axial Loads, End Moments and Min. Moment of Inertia

(T L/

LL

EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ

(0 .8

K /0

.5 K

(4 .0

K /2

.1 K

JOIST GIRDER LOADING DIAGRAM

Per plan for joist spacing

See Joist Girder Schedule for Axial Loads, End Moments and Min. Moment of Inertia

(T L/

LL

(4 .0

K /2

.1 K

(4 .0

K /2

.1 K

(4 .0

K /2

.1 K

(4 .0

K /2

.1 K

No Chord Bracing in this zone

17'-5 1/2" No Gravity Loading

EQ EQ EQ EQ EQ EQ

HSS Blocking not required

(4 .6

K /2

.4 K

(5 .2

K /2

.8 K

JOIST GIRDER LOADING DIAGRAM

Per plan for joist spacing

See Joist Girder Schedule for Axial Loads, End Moments and Min. Moment of Inertia

(T L/

LL

(5 .2

K /2

.8 K

(5 .2

K /2

.8 K

(5 .2

K /2

.8 K

(5 .2

K /2

.8 K

(7 .9

K /4

.2 K

(4 .6

K /2

.4 K

(4 .6

K /2

.4 K

(4 .6

K /2

.4 K

(4 .6

K /2

.4 K

(7 .9

K /4

.2 K

(7 .9

K /4

.2 K

(7 .9

K /4

.2 K

D

C

B

D

C

B

A

A

SA

FE

TY

AL

W

AY

S

TH

IN

K

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

AR

TM

EN

T O

F

TH

E

IN

TE

R

IO

R

DESIGNED

CHECKED

DRAWN

TECH. APPR.

APPROVED

LE

A D

V

IL

LE

M

IN

E

D R A

IN

A G

E

TU

N N

EL

LE

A D

V

IL

LE

C O

LE

A D

V

IL

LE

M

IN

E

TR

EA

TM

EN

T

PL

A N

T A N

D F

A C

IL

IT

IE

S W

A

TE

R T

R

EA

TM

EN

T

PL

A N

T

Brandon Bowman, P.E.

Brandon Bowman, P.E.

Lisa Orgren, P.E.

Brandon Jackson, P.E.

David Kresin, P.E.

Peer Reviewer - Plant Structures Group

DENVER, CO 2022-09-30

STRUCTURAL STEEL

JOIST GIRDER

SCHEDULE

1335-D-60693

JOIST GIRDER SCHEDULE

JOIST GIRDER: JG1

JOIST GIRDER: JG2

JOIST GIRDER: JG3 JOIST GIRDER: JG4

JOIST GIRDER: JG5

JOIST GIRDER: JG6

JOIST GIRDER: JG7

JOIST GIRDER: JG8

JOIST GIRDER SCHEDULE

End Moments

Wind Moment 1.0W (kip-ft)

Seismic Moment 1.0E (kip-ft)

Floor Live Load Moment (kip-ft)

Dead Load Moment (kip-ft)

Left Right Left Right Left Right Left Right

Axial Loads

Wind Axial Load 1.0W

(kip)

Seismic Axial Load 1.0E

(kip)

Girder Mark

Number Designation (Total Load/Live Load)

JG1

JG2

JG3

JG4

JG5

JG6

JG7

JG8

JG9

JG10

JG11

JG12

(1) Manufacturer to design Joist Girders using ASD. Nominal design loads shown are to be used in the applicable ASD code load combinations

(2) Deflection Criteria: Live Load Deflections L/360

(3) See framing plan for joist spacing along girder

(4) Top chord axial load, Tension or Compression Load

(5) End Moment Sign Convention, Positive moments:

±22.5

JG13

JG14

JG15

JG16

20BG 15N 2.5K/1.3K

20BG 15N 3.6K/1.9K

20BG-See loading diagram 20BG-See loading diagram

20BG 15N 2.5K/1.3K

20BG 15N 3.6K/1.9K

20BG 15N 5.4K/2.9K

20BG-See loading diagram

30.9 44.929.8 41.9±18.9 ±132.7 ±111.7

48.7 73.350.2 73.3

87.6 126.8

7.1 46.2

47.5 27.8

75.9 45.5

116.8 66.4

102.3 87.8

95.3 132.4

4.7 43.0

44.5 26.6

76.1 46.9

121.1 71.7

105.2 94.4

±23.0 ±19.2

±23.8 ±19.9

±24.4 ±20.6

±19.1 ±22.9

±19.9 ±24.0

±20.2 ±24.7

±21.1 ±25.5

±134.0 ±113.1

±135.8 ±114.4

±137.1 ±116.3

±111.7 ±132.7

±113.3 ±134.2

±114.0 ±135.4

±116.4 ±137.1

24BG 15N 3.0K/1.9K

24BG 15N 4.5K/2.9K

24BG 15N 3.0K/1.9K

24BG 15N 4.5K/2.9K

24BG 15N 6.9K/4.4K

24BG-See loading diagram

24BG 15N 6.9K/4.4K

24BG 15N 5.8K/3.7K

29.1 46.3

49.3 73.7

71.6 109.9

48.1 98.7

47.8 27.1

75.3 47.3

110.1 68.5

145.6 97.6

40.7 64.7

70.1 112.2

96.6 176.7

61.5 146.3

66.2 38.8

113.9 68.0

176.8 93.2

184.3 111.0

±10.7 ±8.4

±11.1 ±8.5

±12.5 ±10.3

±18.7 ±13.4

±8.2 ±10.5

±8.7 ±11.1

±9.8 ±11.9

±13.1 ±18.1

±68.1 ±53.0

±71.7 ±53.1

±78.0 ±61.3

±101.2 ±74.7

±53.1 ±68.1

±54.4 ±73.3

±60.4 ±77.1

±75.0 ±101.6

±28.8

±28.8

±20.2

±20.2

±2.6

±2.6

±4.9

±4.9

±1.1

±1.1

±9.5

±9.5

±3.0 ±16.9

±3.0 ±16.9

±9.9±2.4

±9.9±2.4

±3.5±1.6

±3.5±1.6

±6.2±2.9

±6.2±2.9

±10.5±4.9

±10.8±4.9

JOIST GIRDER ADDITIONAL REQUIREMENTS

Girder Mark Number

JG1-JG8

Min. Moment of Inertia IG (in4)

JG9-JG16

Min. Top chord thickness

(in)

Min. Top chord Horiz Leg

(in)

Min. Bot chord thickness

(in)

Min. Bot chord Horiz Leg

(in)

1343.3

2026.6

0.5 4 0.375 3

30.37540.5

15 19

60695

60695

SIM

27'-10 7/8" CLEARSPAN

TYP BLOCKING

BTWN JOISTS

60695

15 19

60695

60695

SIM

27'-10 7/8"CLEARSPAN

TYP BLOCKING

BTWN JOISTS

60695

15 19

60695

60695

SIM

TYP BLOCKING

BTWN JOISTS

60695

27'-10 7/8" CLEARSPAN

15 19

60695

60695

SIM

TYP BLOCKING

BTWN JOISTS

60695

27'-10 7/8" CLEARSPAN

60695

60695

SIM

TYP BLOCKING

BTWN JOISTS

60695

27'-10 7/8"CLEARSPAN

60695

60695

SIM

TYP BLOCKING

BTWN JOISTS

60695

27'-10 7/8" CLEARSPAN

60695

60695

SIM

27'-10 7/8" CLEARSPAN

TYP BLOCKING

BTWN JOISTS

60695

60695

60695

SIM

TYP BLOCKING

BTWN JOISTS

60695

27'-10 7/8" CLEARSPAN

JOIST GIRDER LOADING DIAGRAM

Per plan for joist spacing

See Joist Girder Schedule for Axial Loads, End Moments and Min. Moment of Inertia

(T L/

LL

(5 .8

K /3

.7 K

(8 .9

K /5

.3 K

(5 .8

K /3

.7 K

(5 .8

K /3

.7 K

(5 .8

K /3

.7 K

(5 .8

K /3

.7 K

EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ

(6 .2

K /3

.8 K

(8 .9

K /5

.3 K

(8 .9

K /5

.3 K

(8 .9

K /5

.3 K

(6 .2

K /3

.8 K

(6 .2

K /3

.8 K

(6 .2

K /3

.8 K

(6 .2

K /3

.8 K

D

C

B

D

C

B

A

A

SA

FE

TY

AL

W

AY

S

TH

IN

K

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

AR

TM

EN

T O

F

TH

E

IN

TE

R

IO

R

DESIGNED

CHECKED

DRAWN

TECH. APPR.

APPROVED

LE

A D

V

IL

LE

M

IN

E

D R A

IN

A G

E

TU

N N

EL

LE

A D

V

IL

LE

C O

LE

A D

V

IL

LE

M

IN

E

TR

EA

TM

EN

T

PL

A N

T A N

D F

A C

IL

IT

IE

S W

A

TE

R T

R

EA

TM

EN

T

PL

A N

T

Brandon Bowman, P.E.

Brandon Bowman, P.E.

Lisa Orgren, P.E.

Brandon Jackson, P.E.

David Kresin, P.E.

Peer Reviewer - Plant Structures Group

DENVER, CO 2022-09-30

STRUCTURAL STEEL

JOIST GIRDER

SCHEDULE

1335-D-60694

JOIST GIRDER SCHEDULEJOIST GIRDER: JG12

JOIST GIRDER: JG9

JOIST GIRDER: JG10

JOIST GIRDER: JG11

JOIST GIRDER: JG13

JOIST GIRDER: JG14 JOIST GIRDER: JG15 JOIST GIRDER: JG16

1/2

1/2

PL1x10x1'-0"

BOTH ANGLES

5/16 10

5/16 10

1/2

1/2

5/16

5/16

3"

PL1x8x1'-8"

3/8 18

3/8 18

CJP

Bearing Plate, PL5/8x7x0'-10"

Stiffener Plate, PL1x7x0'-6"

WF Column

CL 7/8"ø A325 bolts, 5" gage

Steel Joists not shown for clarity

HSS blocking not shown for clarity, no blocking required where top chord plate occurs

At SIM:

Moment Connection only occurs on one side of WF Column

6"

1/2

1/2

PL1x10x1'-0"

BOTH ANGLES

5/16 10

5/16 10

1/2

1/2

5/16

5/16

PL7/8x8x1'-8"

3/8 18

3/8 18

CJP

Bearing Plate, PL5/8x7x0'-10"

Stiffener Plate, PL1x7x0'-3"

WF Column

CL 7/8" A325

bolts, 5" gage

Steel Joists not shown for clarity

HSS blocking not shown for clarity, no blocking required where top chord plate occurs

At SIM:

Moment Connection only occurs on one side of WF Column

3"

3"

Joist Girder, see schedule

HSS 2 1/2x 2 1/2x1/4 blocking between all steel joists

3/16 2-12

3/16 2-12

Slab-on-deck, reinforcement not shown for clarity

Steel Joist, per plan for size and spacing

B

Joist top chord extension (R-type), typ at each joist

Continuous bent plate, PL1/4x0'-5 1/2" with 1/2" x6" HAS at 2'-0"OC

Joist girder, see schedule

Steel Joists, per plan for size and spacing

HSS blocking, typ.

between joists, See Detail 3 (60695)

3/16 2-12

9 1/2"

#4x3'-0" top bar at 2'-0"OC w/ std hook

(2)#4 cont chord bars, typ at edge of slab

Slab-on-deck, typ. mat reinforcement not shown, see (60683)

GRID

WF Beam, Per plan

Steel Joists, per plan for size and spacing

Continuous bent plate, PL1/4x0'-5 1/2" for connection

4"

HSS blocking, typ.

between joists, See Detail 3 (60695)

See Detail 4 (60695) Slab-on-deck, typ. mat reinforcement not shown, see

Perimeter top bars and chord bars, see See Detail 4 (60695)

(60683) (60685)

Steel Joists, per plan for size and spacing

Continuous bent plate, PL1/4x0'-5 1/2" for connection

Slab-on-deck, typ. mat reinforcement not shown, see

Perimeter top bars and chord bars, see See Detail 4 (60695)

(60683) (60685)

See Detail 4 (60695)

H Continuous bent plate, PL1/4x0'-5 1/2", see for additional detailing

Slab-on-deck, typ. mat reinforcement not shown, see

Perimeter top bars and chord bars, see

GRID

Steel joist, per plan for size and spacing

Joist girder, see schedule

Joist top chord extension (R-type), typ at each joist

Masonry wall

1'-7"1" EJ (Typ.)

HSS blocking, typ.

between joists, See Detail 3 (60695)

See Detail 4 (60695)

(60683) (60685)

See Detail 4 (60695)

D

C

B

D

C

B

A

A

SA

FE

TY

AL

W

AY

S

TH

IN

K

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

AR

TM

EN

T O

F

TH

E

IN

TE

R

IO

R

DESIGNED

CHECKED

DRAWN

TECH. APPR.

APPROVED

LE

A D

V

IL

LE

M

IN

E

D R A

IN

A G

E

TU

N N

EL

LE

A D

V

IL

LE

C O

LE

A D

V

IL

LE

M

IN

E

TR

EA

TM

EN

T

PL

A N

T A N

D F

A C

IL

IT

IE

S W

A

TE

R T

R

EA

TM

EN

T

PL

A N

T

Brandon Bowman, P.E.

Brandon Bowman, P.E.

Lisa Orgren, P.E.

Brandon Jackson, P.E.

David Kresin, P.E.

Peer Reviewer - Plant Structures Group

DENVER, CO 2022-09-30

STRUCTURAL STEEL

JOIST GIRDER DETAILS

1335-D-60695

60694 Scale: 1 1/2" = 1'-0"

2 24" DEEP JOIST GIRDER - MOMENT CONNECTION

60693 Scale: 1 1/2" = 1'-0"

1 20" DEEP JOIST GIRDER MOMENT CONNECTION

60693 Scale: 3/4" = 1'-0"

3 HSS BLOCKING AT JOIST GIRDERS

60682 Scale: 3/4" = 1'-0"

4 SLAB EDGE DETAIL

60682 Scale: 3/4" = 1'-0"

5 SLAB EDGE DETAIL

60682 Scale: 3/4" = 1'-0"

6 SLAB EDGE DETAIL

60682 Scale: 3/4" = 1'-0"

7 SLAB EDGE DETAIL

HFDB

JE

(60684)

1'-10" 3'-0"W14x48 @ 3'-6" Max O.C. 3'-0" 1'-8" 3'-6" Max O.C.

W14x48

Office framing see sheet:

10" 3'-3"W14x48 @ 3'-6" Max O.C.

3'-2" 7'-10" 8'-0" 21'-0" 3'-2"

Outline of HVAC Re: Mech. dwgs.

43'-2"

CMU walls see Masonry Sheets: (---)

HFDB

E I

40'-0"

11'-0" 8'-0" 21'-0"

(2)#4 cont.

Slab-on-Deck (5.5" total thickness) See Note 4,5

Reinforce slab with

#4@12" OC S,

centered. See note 4

#4x3'-0"@24"OC

#4x3'-0"@24"OC

(2)#4 cont.

#4x3'-0"@24"OC

8" EOS 2'-2" EOS

4' -6

EO

S 1'

-4

EO

S

3' -2

0"

Office slab-on-deck reinf. see sheet: (60685)

CMU walls see Masonry Sheets: (---)

Outline of HVAC Re: Mech. dwgs.

Bent plate continuous from beyond

Floor decking per plan and notes 4 & 5

Steel beam per plan

CMU wall per plan 1" ± drypack

(2) 3/4" bolts in slotted holes -tack weld bolts to bottom of steel plate and tighten nuts finger tight

Bearing plate w/ 2-layers of 15 pound building paper between beam and plate

Slotted holes each side of beam gage -

(2) 3/4" anchor bolts

(2) #5 X 4'-0" long in 8" deep grouted bond beam centered on beam - bend around corners where necessary

Floor decking per plan

CMU wall per plan

1" ± drypack

PL.1/4x0'-4"Continuous w/ 3/4" anchors @ 48" OCContinuous 8" deep grouted bond beam w/ (2) #5's continuous

Deck edge attachment Bent plate continuous from beyond

Floor decking per plan and notes 4 & 5

CMU wall per plan

1" ± drypack

(2) #5 X 4'-0" long in 8" deep grouted bond beam centered on beam - bend around corners where necessary Steel beam per plan

Floor decking per plan and notes 4 & 5

Steel beam per plan

CMU wall per plan

1" ± drypack

(2) 3/4" anchor bolts

(2) #5 X 4'-0" long in 8" deep grouted bond beam centered on beam - bend around corners where necessary

Steel beam per plan

1" Setback

D

C

B

D

C

B

A

A

SA

FE

TY

AL

W

AY

S

TH

IN

K

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

AR

TM

EN

T O

F

TH

E

IN

TE

R

IO

R

DESIGNED

CHECKED

DRAWN

TECH. APPR.

APPROVED

LE

A D

V

IL

LE

M

IN

E

D R A

IN

A G

E

TU

N N

EL

LE

A D

V

IL

LE

C O

LE

A D

V

IL

LE

M

IN

E

TR

EA

TM

EN

T

PL

A N

T A N

D F

A C

IL

IT

IE

S W

A

TE

R T

R

EA

TM

EN

T

PL

A N

T

Claire Gemperline

Claire Gemperline

Brandon Jackson, P.E.

Brandon Jackson, P.E.

David Kresin, P.E.

Peer Reviewer - Plant Structures Group

DENVER, CO 2022-09-30

STRUCTURAL STEEL

HVAC PLATFORM -

FRAMING &

SLAB-ON-DECK PLAN

1335-D-60696

Scale: 3/16" = 1'-0"

FRAMING PLAN - HVAC PLATFORM (TO SLAB: EL. 18.0')

Scale: 3/16" = 1'-0"

SLAB-ON-DECK REINFORCING - HVAC PLATFORM (TO SLAB: EL. 18.0')

NOTES

1. For structural design data, see (60589) - (60592).

2. For structural steel general notes and abbreviations, see (60662).

3. For Reinforcement General Notes, see (60629).

4. Floor Construction: 5.5" thick normal weight concrete slab: 4" concrete over 1 1/2"x22Ga (1.5C) non-composite galvanized deck.

Reinforce slab with #4@12" OC each way, centered in slab.

5. Floor deck attachments: 5/8"ø puddle welds in 36/4 pattern at supports, Side Laps - #10 TEK Screws at 12" OC.

A STEEL BEAM CONNECTION TO CMU WALL AT FLOOR DECK

D CONC. ON METAL DECK AT CMU WALL

B CONCRETE ON METAL DECK TO CMU WALL C STEEL BEAM TO CMU WALL AT FLOOR DECK

Masonry wall

L2 1/2x 2 1/2x 1/4 kicker angles at 5'-0"OC max

1/4" shear tab typ at kicker angle connection to beam flange

3/16

3/16

3/16 1" return

3/16

Continuous bent plate, PL1/4x0'-5 1/2", see for additional detailing

See Detail 4 (60695)

Slab-on-deck, typ. mat reinforcement not shown, see

Attachment from masonry to slab edge not allowed

WF Beam

Steel Joist, per plan for size and spacing

4" EJ (Typ.)

Plan

See

(60683)

Perimeter top bars and chord bars, seeSee Detail 4 (60695)At Sim:

CFS wall in lieu of Masonry wall. Attachment from CFS wall to Slab edge not allowed

1" EJ (Typ.)

Steel Joist, per plan for size and spacing

Masonry wall

Do not weld or attach decking to support angle.

2"

5/8"ø expansion anchors with 4" min embed @24"OC max.

Continuous L4x4x5/16 with STD holes @24"OC max.

Locate first and last holes 4" from each end of angle

SDI pour stop

Slab-on-deck, typ. mat reinforcement not shown, see

(60683) (60685)

SDI pour stop

Masonry Wall 1" EJ (Typ.)

Steel Joist

1/

2" Jo is t

S ea t

Bearing Plate at each joist, PL1/2x4x0'-7" with (2)1/2øx6" HSA (4" gage)

Joist bearing pocket to be adequately sized for joist erection, grout solid after installation

Bond Beam w/ (2)#4 continuous directly below bearing

SDI pour stop

Steel joist, per plan for size and spacing

WF Beam, Per Plan

HI

Joist girder, see schedule

HSS blocking, typ.

between joists, See Detail 3 (60695)

Steel joist substitutes, see plan for size and spacing

WF Beam, per plan

Steel stair or prefabricated stair by contractor

Steel joist, see plan for size and spacing

2" 6'-6"Continuous bent plate, PL1/4x0'-5 1/2" for connection

Slab-on-deck, typ. mat reinforcement not shown, see

(60683) (60685)

See Detail 4 (60695) Perimeter top bars and chord bars, seeSee Detail 4 (60695)

Steel Joist substitute, per plan for size and spacingConcrete Wall

1" EJ (Typ.)

Steel angle and attachment to wall, See Detail 5 (60697)

Do not weld or attach decking to support angle.

SDI pour stop

(60683) (60685)

Slab-on-deck, typ. mat reinforcement not shown, see

Concrete Wall

1" EJ (Typ.) See Plan

WF Beam, per plan

Continuous bent plate, PL1/4x0'-5 1/2" for connection See Detail 4 (60695)

Perimeter top bars and chord bars, see Slab-on-deck, typ. mat reinforcement not shown, see (60683)

(60683)

HI

1'-6"

Water Treatment Plant CFS wall

Joist top chord extension (R-type), typ at each joist

HSS blocking, typ.

between joists, See Detail 3 (60695)

Joist girder, see schedule

±1" EJ

Continuous bent plate, PL1/4x0'-5 1/2", see for additional detailing

Slab-on-deck, typ. mat reinforcement not shown, see

Perimeter top bars and chord bars, see

See Detail 4 (60695)

(60683) (60685)

See Detail 4 (60695)

Attachment from CFS wall to slab edge not allowed

9 1/2"

WF Beam

Continuous bent plate, PL1/4x0'-5 1/2", see for additional detailing Slab-on-deck, typ. mat reinforcement not shown, see

Perimeter top bars and chord bars, see

See Detail 4 (60695)

See Detail 4 (60695)

(60685)

D

C

B

D

C

B

A

A

SA

FE

TY

AL

W

AY

S

TH

IN

K

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

AR

TM

EN

T O

F

TH

E

IN

TE

R

IO

R

DESIGNED

CHECKED

DRAWN

TECH. APPR.

APPROVED

LE

A D

V

IL

LE

M

IN

E

D R A

IN

A G

E

TU

N N

EL

LE

A D

V

IL

LE

C O

LE

A D

V

IL

LE

M

IN

E

TR

EA

TM

EN

T

PL

A N

T A N

D F

A C

IL

IT

IE

S W

A

TE

R T

R

EA

TM

EN

T

PL

A N

T

Brandon Bowman, P.E.

Brandon Bowman, P.E.

Lisa Orgren, P.E.

Brandon Jackson, P.E.

David Kresin, P.E.

Peer Reviewer - Plant Structures Group

DENVER, CO 2022-09-30

STRUCTURAL STEEL

FLOOR FRAMING

DETAILS

1335-D-60697

60682 Scale: 3/4" = 1'-0"

1 SLAB EDGE DETAIL

60682 Scale: 3/4" = 1'-0"

5 SLAB EDGE DETAIL

60682 Scale: 3/4" = 1'-0"

4 JOIST POCKET DETAIL

60682 Scale: 3/4" = 1'-0"

3 SLAB EDGE DETAIL

60682 Scale: 3/4" = 1'-0"

2 FRAMING DETAIL

60682 Scale: 3/4" = 1'-0"

8 SLAB EDGE DETAIL

60682 Scale: 3/4" = 1'-0"

9 SLAB EDGE DETAIL

60682 Scale: 3/4" = 1'-0"

7 SLAB EDGE DETAIL

60684 Scale: 3/4" = 1'-0"

6 SLAB EDGE DETAIL

1'-0 1/2" 1'-0 1/2"

2'-1"

CL. Base Pl.

and W14

9" 9"

1' -6

3 1/2" Plate Washer (Typ.)

5/16

5/16

TYP. T & B Flange 5/16

5/16

Non-shrink grout (Typ.)

1 3/4" Pl.

(4) 1 1/4" Ø Anchor Rod (Double-nut) w/ 2 1/8" Ø Hole in Base Pl.

A 60714

A 60714

1/

2" 1'

-1

1/

2"

2 1/2" 1'-8" 2 1/2"

TYP. @ PL. WASHER

1/4

1/4

W14x145

4 1/2" 6" 4 1/2"

7 1/2" 7 1/2"

1'-3"

1/

2" 6"

1/

2"

1/

2"

1/ 2"

1' -3

CL. Base Pl.

and W12

3 1/2" Plate Washer (Typ.)

Non-shrink grout (Typ.)

5/16

5/16

Typ. T & B Flange 5/16

5/16

B 60714

B 60714

1" Pl.

(4) 1 1/4" Ø Anchor Rod w/ 2 1/8" Ø Hole in Base Pl.

Typ. @ PL. Washer 1/4

1/4

W12x120

CL. Base Pl. and W12

Non-shrink grout (Typ.)

3 1/2" Plate Washer (Typ.)

7 1/2" 7 1/2"

1'-3"

1/

2"

1/ 2"

1' -3

C 60714

C 60714

(4) 1 1/4" Ø Anchor Rod w/ 2 1/8" Ø Hole in Base Pl.

1" Pl.

4 1/2" 6" 4 1/2"

W12x87

5/16

5/16

Typ. T & B Flange 5/16

5/16

Typ. @ PL. Washer 1/4

1/4

1/

2" 6"

1/

2"

8 1/2" 8 1/2"

1'-5"

1/

2"

1/ 2"

1' -5

CL. Base Pl.

and W14

Non-shrink grout (Typ.)

3 1/2" Plate Washer (Typ.)

TYP. T & B Flange

5/16

5/16

5/16

5/16

D 60714

D 60714

TYP. @ PL. WASHER

1/4

1/4

1" Pl.

(4) 1 1/4" Ø Anchor Rod w/ 2 1/8" Ø Hole in Base Pl.

W14x145

5" 7" 5"

5" 7"

5"

4" 4"

8"

1/

4"

1/ 4"

1/

2"

Non-shrink grout (Typ.)

5/16

HSS3x3x5/16

(4) 1/2"Ø Expansion w/ 5/8"Ø Hole in Base Pl.

E 60714

E 60714

1/2" Pl.

1"

1/ 2"

1"

CL. Base Pl. and HSS3x3x5/16

1" 6" 1"

HSS4½x4½x

Non-shrink grout (Typ.)

(4) 1/2" Ø Expansion Anchors w/ 5/8" Ø Hole in Base Pl.

CL. Base Pl. and Col.

10" 5"

5"

5/16

Typ. @ PL. Washer 1/4

1/4

F 60714

F 60714

1/2" Pl.

1 1/2" 7" 1 1/2"

1/

2" 7"

1/

2"

Pr o j ec ti o n

7"

2' -1

Em be dm en t

1' -6

Heavy hex nut (Double-nut)

3 1/2" Plate Washer

1 1/4" F1554 Gr.36 Anchor Rod

Heavy Hex head

3 1/2" Plate Washer (Tack weld to head)

1/2"Pl. with 1 3/8"Ø hole in the center

3 1/2"

1/

2"

6" P ro je ct io n

2' -0

Em be dm en t

1' -6

Heavy hex nut

3 1/2" Plate Washer

1 1/4" F1554 Gr.36 Anchor Rod

Heavy Hex head

3 1/2" Plate Washer (Tack weld to head)

D

C

B

D

C

B

A

A

SA

FE

TY

AL

W

AY

S

TH

IN

K

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

AR

TM

EN

T O

F

TH

E

IN

TE

R

IO

R

DESIGNED

CHECKED

DRAWN

TECH. APPR.

APPROVED

LE

A D

V

IL

LE

M

IN

E

D R A

IN

A G

E

TU

N N

EL

LE

A D

V

IL

LE

C O

LE

A D

V

IL

LE

M

IN

E

TR

EA

TM

EN

T

PL

A N

T A N

D F

A C

IL

IT

IE

S W

A

TE

R T

R

EA

TM

EN

T

PL

A N

T

Brandon Jackson, P.E.

Claire Gemperline

Lisa Orgren, P.E.

Brandon Jackson, P.E.

David Kresin, P.E.

Peer Reviewer - Plant Structures Group

DENVER, CO 2022-09-30

STRUCTURAL STEEL

CONNECTION DETAILS

1335-D-60698

60663 Scale: 1 1/2" = 1'-0" 1 DETAIL - BP1 60663 Scale: 1 1/2" = 1'-0"

2 DETAIL - BP2

60663 Scale: 1 1/2" = 1'-0"

3 DETAIL - BP3

60663 Scale: 1 1/2" = 1'-0"

4 DETAIL - BP4

60681 Scale: 3" = 1'-0"

5 DETAIL - BP5

60681 Scale: 1 1/2" = 1'-0"

7 DETAIL - BP6

1 1/4" ANCHOR ROD (DOUBLE NUT)

3 1/2" PLATE WASHER

1 1/4" ANCHOR ROD

CL. Base Pl. and W14

W x1

1/ 4"

N on

-s hr in k

Pa d

1 3/4" Pl.

CL. 1 1/4" Anchor Bolts, see (60698)

Ef fe ct iv e Em be dm en t

1' -6

3"

El. 0.00

LEVEL 01

W x1

CL. Base Pl. and W12

1" Pl.

1"

N on

-s hr in k

Pa d

Ef fe ct iv e Em be dm en t

1' -6

CL. 1 1/4" Anchor Bolts, see (60698)

2"

El. 0.00

LEVEL 01

1" Pl.

CL. Base Pl. and W12

W x1

Ef fe ct iv e Em be dm en t

1' -6

CL. 1 1/4" Anchor Bolts, see (60698)

1"

N on

-s hr in k

Pa d

2"

El. 0.00

LEVEL 01

CL. Base Plate and HSS

CL. 1/2" Expansion Anchors, see (60698)

1/2" Pl.

Em be d

6"

1/ 2"

N on

-S hr in k

Pa d

H S S 3X

3X 5/

1"

El. 22.50

LEVEL 03

CL. 1 1/4" Anchor Bolts, see

1"

N on

-s hr in k

Pa d

1" Pl.

Ef fe ct iv e Em be dm en t

1' -6

CL Base Pl. and W12

(60698)

2"

El. 22.50

LEVEL 03

H S S 4½ x4 ½ x

CL. Base Plate and HSS

1/2" Pl.

1/

2" N on -s hr in k Pa d

Em be d

6"

CL. 1/2"Ø Expansion Anchors, see (60698)

1"

D

C

B

D

C

B

A

A

SA

FE

TY

AL

W

AY

S

TH

IN

K

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

AR

TM

EN

T O

F

TH

E

IN

TE

R

IO

R

DESIGNED

CHECKED

DRAWN

TECH. APPR.

APPROVED

LE

A D

V

IL

LE

M

IN

E

D R A

IN

A G

E

TU

N N

EL

LE

A D

V

IL

LE

C O

LE

A D

V

IL

LE

M

IN

E

TR

EA

TM

EN

T

PL

A N

T A N

D F

A C

IL

IT

IE

S W

A

TE

R T

R

EA

TM

EN

T

PL

A N

T

Brandon Jackson, P.E.

Claire Gemperline

Lisa Orgren, P.E.

Brandon Jackson, P.E.

David Kresin, P.E.

Peer Reviewer - Plant Structures Group

DENVER, CO 2022-09-30

STRUCTURAL STEEL

CONNECTION DETAILS

1335-D-60714

60698 Scale: 1 1/2" = 1'-0"

A SECTION - BP1

60698 Scale: 1 1/2" = 1'-0"

B SECTION - BP2

60698 Scale: 1 1/2" = 1'-0"

D SECTION - BP4

60698 Scale: 1 1/2" = 1'-0"

E SECTION - BP5

60698 Scale: 1 1/2" = 1'-0"

C SECTION - BP3

60698 Scale: 1 1/2" = 1'-0"

F SECTION - BP6

4 1 /4"

3 1 /2"

4 1 /4"

A

B

C

D

E

1 1/2"

3 1/2"

CL. 7/8"Ø Bolts

90°

WP

CL. 2MC8

2M C8x18.7

5/16

5/16

CL. WF Col.

CB Pl.

W F

C ol

P er P la n

Vertical Brace Connection, where occurs, SIM to opposite side

(60715)

6 1/2"

"B

S ee

S ch ed ul e

W F

C ol

P er P la n

(T yp

CL. WF Col.

WP

HS

S4

½ x4

½ x

7" m in

5/16

5/16

CL. HSS

Erection bolt at contractors option

HSS brace slotted at gusset, typ.

5/16

5/16

CB-H Pl.

"B

S ee

S ch ed ul e

A

B

C

D

E 90°

D

C

B

D

C

B

A

A

SA

FE

TY

AL

W

AY

S

TH

IN

K

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

AR

TM

EN

T O

F

TH

E

IN

TE

R

IO

R

DESIGNED

CHECKED

DRAWN

TECH. APPR.

APPROVED

LE

A D

V

IL

LE

M

IN

E

D R A

IN

A G

E

TU

N N

EL

LE

A D

V

IL

LE

C O

LE

A D

V

IL

LE

M

IN

E

TR

EA

TM

EN

T

PL

A N

T A N

D F

A C

IL

IT

IE

S W

A

TE

R T

R

EA

TM

EN

T

PL

A N

T

Brandon Jackson, P.E.

Claire Gemperline

Lisa Orgren, P.E.

Brandon Jackson, P.E.

David Kresin, P.E.

Peer Reviewer - Plant Structures Group

DENVER, CO 2022-09-30

STRUCTURAL STEEL

CONNECTION DETAILS

1335-D-60715

GUSSET TYPE CB

60672 Scale: 1 1/2" = 1'-0"

1 DETAIL

60690 Scale: 1 1/2" = 1'-0"

2 DETAIL

PLATE SCHEDULE

Mark No.

Gusset Type

No.

Req'd

Thickness A B C D E

CB1 CB 4 3/4" 9" 1'-5" 8 13/16" 1'-0" 11 5/8"

CB2 CB 4 3/4" 9" 1'-10" 7 3/4" 1'-0" 1'-5 3/8"

CB3 CB 4 3/4" 7" 1'-9" 7 7/16" 1'-0" 1'-5 1/4"

CB4 CB 2 3/4" 7" 1'-7" 8 7/8" 1'-0" 1'-3 5/16"

CB5 CB 4 3/4" 7" 1'-9" 6 11/16" 1'-0" 1'-5 1/4"

CB6 CB 2 3/4" 7" 1'-6" 1'-0 15/16" 1'-0" 1'-3 13/16"

CB7 CB 2 3/4" 7" 1'-7" 8 11/16" 1'-0" 1'-3 5/16"

Note: Ref. to framing elevations for Mark No. locations.

PLATE SCHEDULE

Mark No.

Gusset Type

No.

Req'd

Thickness A B C D E

CB8 CB-H 2 1/2" 7" 1'-3" 8 1/4" 6 1/2" 1'-0 3/8"

CB9 CB-H 1 1/2" 7" 1'-0" 1'-1 7/8" 6 1/2" 1'-0"

CB10 CB-H 1 1/2" 7" 1'-1" 10 1/8" 6 1/2" 10 7/8"

Note: Ref. to framing elevations for Mark No. locations.

GUSSET TYPE CB-H

FP1 (60777)

WP

CL. W12

SP4 (60777)

A 0.221" EFFECTIVE

THROAT IS REQ'D

1/2" Stiffener Pl. each side

3- Sided 5/16

5/16

CL. W27

and Pl.

W27x114

W27x114

W x8

1' -6

/8

Frame Connection, where occurs, SIM to opposite side

El. Varies

TO COLUMN

5/16

5/16

4"

3"

TO COLUMN

El. 27.67

WP

CL. W12/W14

CL. W24

and Pl.

FP1 (60777)

SP4 (60777)

5/16

5/16

A 0.221" EFFECTIVE

THROAT IS REQ'D

W x1

W24x131

W x1

1' -4

/8

4"

3"

WP

CL. W12

FP2 (60777)

CL. W24

A 0.221" EFFECTIVE

THROAT IS REQ'D

TYP T & B Flange 5/16

5/16

W x1

CL. W24

SP6 (60777)

TYP

5/16

5/16

TYP @ Column Flange 5/16

5/16

TO COLUMN

El. 37.17

1' -2

/8

3"

1" Setback (Typ.)

10"

CL. W12

FP1 (60777)

A 0.221" EFFECTIVE

THROAT IS REQ'D

Typ.

5/16

5/16

1/2" Stiffener Pl. each side

3- Sided 5/16

5/16

CL. W18

and Pl.

W18x76 W18x76

CL. W18

and Pl.

SP3 (60777)

W x1

3"

1"Setback (Typ.)

TO COLUMN

El. Varies

3/

8"

4"

WP

CL. W12

5/16

5/16

A 0.221" EFFECTIVE

THROAT IS REQ'D

FP1 (60777)

W18x76

WPCL. W18

and Pl.

1/2" Stiffener Pl.

each side

TO COLUMN

El. Varies

SP3 (60777)

W x1

3- Sided 5/16

5/16

4"

1' -3

/8

W x8

3"

1"Setback

D

C

B

D

C

B

A

A

SA

FE

TY

AL

W

AY

S

TH

IN

K

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

AR

TM

EN

T O

F

TH

E

IN

TE

R

IO

R

DESIGNED

CHECKED

DRAWN

TECH. APPR.

APPROVED

LE

A D

V

IL

LE

M

IN

E

D R A

IN

A G

E

TU

N N

EL

LE

A D

V

IL

LE

C O

LE

A D

V

IL

LE

M

IN

E

TR

EA

TM

EN

T

PL

A N

T A N

D F

A C

IL

IT

IE

S W

A

TE

R T

R

EA

TM

EN

T

PL

A N

T

Brandon Bowman, P.E.

Claire Gemperline

Lisa Orgren, P.E.

Brandon Jackson, P.E.

David Kresin, P.E.

Peer Reviewer - Plant Structures Group

DENVER, CO 2022-09-30

STRUCTURAL STEEL

CONNECTION DETAILS

1335-D-60717

60677 Scale: 1 1/2" = 1'-0"

1 DETAIL

60675 Scale: 1 1/2" = 1'-0"

2 DETAIL

60675 Scale: 1 1/2" = 1'-0"

4 DETAIL

60688 Scale: 1 1/2" = 1'-0"

5 DETAIL

60688 Scale: 1 1/2" = 1'-0"

3 DETAIL

CL. W18

WP

5/16

5/16

CL. W16

and Pl.

W16x67

1/2" Stiffener Pl.

SP3 (60777)

3"

1" Setback W18x76

5/16

5/16

WP

CL. WF Beam and Pl.

W F

C ol

P er P la n

WF Beam, Per Plan

3"

1"Setback

SP5 (60777)

CL. WF Col.

SP5 (60777)

W F

C ol

P er P la nWF Beam, Per Plan WF Beam, Per Plan

TYP

5/16

5/16

WP CL. WF Beam and Pl.

CL. WF Beam and Pl.

3"

1"Setback

CL. WF Col.

W18x46 W18x46

WF Beam, Per Plan

CL. W18, WF

Beam, and Pl.

CL. W18, WF

Beam, and Pl.

CL. WF Beam

SP3 (60777)

TYP

5/16

5/16

3"

1"Setback (Typ.)

W18x76

W16x67W16x67

SP3 (60777)

CL. W18

CL. W16

and Pl.

CL. W16

and Pl.

TYP

5/16

5/16

Cope as req'd (Typ.)

3"

1"Setback (Typ.)

WP

CL. W14

CL. WF Beam and Pl.

SP4 (60777)

5/16

5/16

WF Beam, Per Plan

W x1

3"

CL. WF Beam

WF Beam, Per Plan

W18x46

1" Setback

5/16

5/16

SP3 (60777)

WP

CL. W18, WF

Beam, and Pl.

3"

W18x76

1/2" Pl.

CP2 (60777)5/16

H S S 4½ x4 ½ x

3- Sided 5/16

5/16

WP

CL. W18 Stiffener Pl. each side, extend to edge of flange.

CL. HSS

3- Sided 5/16

5/16

W8x28

CL. W8, WF

Beam and Pl.

CL. WF Beam

WP

3"

1" Setback (Typ.)

SP8 (60777)

WF Beam, Per Plan

W8x28

CL. W8, WF

Beam and Pl.

D

C

B

D

C

B

A

A

SA

FE

TY

AL

W

AY

S

TH

IN

K

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

AR

TM

EN

T O

F

TH

E

IN

TE

R

IO

R

DESIGNED

CHECKED

DRAWN

TECH. APPR.

APPROVED

LE

A D

V

IL

LE

M

IN

E

D R A

IN

A G

E

TU

N N

EL

LE

A D

V

IL

LE

C O

LE

A D

V

IL

LE

M

IN

E

TR

EA

TM

EN

T

PL

A N

T A N

D F

A C

IL

IT

IE

S W

A

TE

R T

R

EA

TM

EN

T

PL

A N

T

Brandon Bowman, P.E.

Claire Gemperline

Lisa Orgren, P.E.

Brandon Jackson, P.E.

David Kresin, P.E.

Peer Reviewer - Plant Structures Group

DENVER, CO 2022-09-30

STRUCTURAL STEEL

CONNECTION DETAILS

1335-D-60757

60686 Scale: 1 1/2" = 1'-0"

9 DETAIL

60672 Scale: 1 1/2" = 1'-0"

1 DETAIL

60672 Scale: 1 1/2" = 1'-0"

2 DETAIL

60677 Scale: 1 1/2" = 1'-0"

5 DETAIL

60686 Scale: 1 1/2" = 1'-0"

8 DETAIL

60676 Scale: 1 1/2" = 1'-0"

3 DETAIL

60676 Scale: 1 1/2" = 1'-0"

6 DETAIL

60690 Scale: 1 1/2" = 1'-0"

7 CP2 - DETAIL

60669 Scale: 1 1/2" = 1'-0"

4 DETAIL

SP2 (60777)

5/16

5/16

CL. WF Beam

WP

1" S et ba ck

W x1

1/2" Stiffener Pl.

3- Sided 5/16

5/16

See Detail 4 (60757)

W8x28

(3) 7/8"Ø bolts.

Provide LSL holes in WF Column

CL. WF Col. and W10

W10x54

W8x28

W x1

A 60766

A 60766

CL. W12

5/16

5/16

L4x3x3/8

(2) 7/8"Ø bolts.

Provide LSL Holes in W8 Beam

W8x28

CL. W8

WP

3/

4"

Max

6"

1"Setback

M ax

CL. WF Col.

WF Col., Per Plan

3/ 8"

C L.

L

1/

4"

1/ 2"

1/

4"

5"

L4x4x3/8

2 1/2"

4"

4"

CL. 7/8" Ø Bolts

CL. 7/8" Ø Bolts

CL. WF Col. and W24

WP

SP2 (60777)

5/16

5/16

CL. WF Beam

W x1

1" S et ba ck

1/2" Stiffener Pl.

W18x46

SeeSee Detail 6 (60757)

(3) 7/8"Ø bolts.

Provide LSL holes in WF Column

W24x131

3- Sided 5/16

5/16

D

C

B

D

C

B

A

A

SA

FE

TY

AL

W

AY

S

TH

IN

K

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

AR

TM

EN

T O

F

TH

E

IN

TE

R

IO

R

DESIGNED

CHECKED

DRAWN

TECH. APPR.

APPROVED

LE

A D

V

IL

LE

M

IN

E

D R A

IN

A G

E

TU

N N

EL

LE

A D

V

IL

LE

C O

LE

A D

V

IL

LE

M

IN

E

TR

EA

TM

EN

T

PL

A N

T A N

D F

A C

IL

IT

IE

S W

A

TE

R T

R

EA

TM

EN

T

PL

A N

T

Brandon Bowman, P.E.

Claire Gemperline

Lisa Orgren, P.E.

Brandon Jackson, P.E.

David Kresin, P.E.

Peer Reviewer - Plant Structures Group

DENVER, CO 2022-09-30

STRUCTURAL STEEL

CONNECTION DETAILS

1335-D-60766

60669 Scale: 1 1/2" = 1'-0"

2 DETAIL

60692 Scale: 1 1/2" = 1'-0"

1 DETAIL

Scale: 1 1/2" = 1'-0"A DETAIL L4x4x3/8

60675 Scale: 1 1/2" = 1'-0"

3" 2"

5"

1/

2" 3"

3" 3"

3"

1/ 2"

1' -3

CL. 7/8" Ø Bolts

1/2" Pl.

1'-3"

3/4" Pl.

4" 3" 3" 3" 2"

2" 6"

2"

CL. 7/8" Ø Bolts

3" 2"

5"

1/

2" 3"

3" 3"

1/

2"

1' -0

1/2" Pl.

CL. 7/8" Ø Bolts

1/2" Pl.

CL. 7/8"Ø Bolts

"L" See Schedule

1/

2" 3"

1/

2"

6"

S ee

S ch ed ul e

"W

See Schedule

"a" 5"

3" 3" 2"

Chamfer as req'd (Typ.)

±5 13/16" 3"

10 13/16"

1/

2" 3"

3" 3"

3"

1/ 2" ±

9/

1' -3

1/

8"

CL. 7/8"Ø Bolts

1/2" Pl.

2'

-2

1/

Fi t to

W

.0

4°

.0 4°

8 13/16" 2"

3" 2"

5"

1/

2" 3"

3"

1/ 2"

9"

1/2" Pl.

CL. 7/8" Ø Bolts 3" 2"

5"

1/ 2"

3"

1/ 2"

6"

1/2" Pl.

CL. 7/8" Ø Bolts

"L" See Schedule

1/

2" 3"

3"

1/ 2"

9"

See Schedule

"a" 3" 2"

CL. 7/8" Ø Bolts

3/4" Pl.

"L" See Schedule

1/

2" 3"

3"

1/ 2"

9"

See Schedule

"a" 3" 2"

CL. 7/8" Ø Bolts

1/2" Pl.

1'-9"

3/4" Pl.

10" 3" 3" 3" 2"

7/

6"

7/

CL. 7/8" Ø Bolts

Fi t to W

/8

Chamfer as req'd (Typ.)

1/2" Pl.

CL. 7/8"Ø Bolts

Fi t to W

1'

-0

/8

1/

4" 8"

1/

4"

1/

2" 5"

1/

2"

±1'-0 3/8"

Fit to W14

±7 3/8" 5"

3" 2"

D

C

B

D

C

B

A

A

SA

FE

TY

AL

W

AY

S

TH

IN

K

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

AR

TM

EN

T O

F

TH

E

IN

TE

R

IO

R

DESIGNED

CHECKED

DRAWN

TECH. APPR.

APPROVED

LE

A D

V

IL

LE

M

IN

E

D R A

IN

A G

E

TU

N N

EL

LE

A D

V

IL

LE

C O

LE

A D

V

IL

LE

M

IN

E

TR

EA

TM

EN

T

PL

A N

T A N

D F

A C

IL

IT

IE

S W

A

TE

R T

R

EA

TM

EN

T

PL

A N

T

Brandon Bowman, P.E.

Claire Gemperline

Lisa Orgren, P.E.

Brandon Jackson, P.E.

David Kresin, P.E.

Peer Reviewer - Plant Structures Group

DENVER, CO 2022-09-30

STRUCTURAL STEEL

CONNECTION DETAILS

1335-D-60777

SP4 - SHEAR PLATE

FP1 - FLANGE PLATE

SP3 - SHEAR PLATE

SP8 - SHEAR PLATE

SP7 - SHEAR PLATE

SP2 - SHEAR PLATESP1 - SHEAR PLATE

SP6 - SHEAR PLATESP5 - SHEAR PLATE

FP2 - FLANGE PLATE

PLATE SCHEDULE - SHEAR PLATE EXTENDED

Mark No.

No.

Req'd Column Thickness W L a

SP5 90 W12 1/2" 9" 1'-1 13/16" 8 13/16"

SP5 112 W14 1/2" 9" 1'-3 7/16" 10 7/16"

SP6 46 W12 3/4" 9" 1'-1 13/16" 8 13/16"

SP6 70 W14 3/4" 9" 1'-3 7/16" 10 7/16"

SP8 8 W8 1/2" 7 1/8" 11 1/8" 6 1/8"

SP8 152 W10 1/2" 8 7/8" 1'-0 13/16" 7 13/16"

PLATE SCHEDULE - FLANGE PLATE

Mark No.

No.

Req'd Thickness W L

FP1 130 3/4" 10" 1'-3"

FP2 8 3/4" 10 7/8" 1'-9"

FP3 36 1/2" 12 7/16" 1'-0 5/8"

PLATE SCHEDULE - STANDARD SHEAR PLATE

Mark No.

No.

Req'd Column Thickness W L a

SP1 4 1/2" 5" 6" 3"

SP2 10 1/2" 5" 9" 3"

SP3 102 1/2" 5" 1'-0" 3"

SP4 52 1/2" 5" 1'-3" 3"

SP7 4 1/2" 10 13/16" 2'-2 11/16" 8 13/16"

FP3 - FLANGE PLATE

J

TO COLUMN

El. 47.33

B 60796

W x1

W10x54

2MC8x18.7

WP

GP2

GP1

5/16

5/16

3/

4"

2"

S ee

S ch ed ul e

"A

/8

1" E xt en si on

1' -1

3/

8"

6 1/2"

Back-to-back channel connection to gusset Pl.

shall provide Class A faying surface, per AISC J3.8

3/4" Pl.

5/16

5/16

Typ. T & B Flange 5/16

5/16

11"

W10x54

/8

4" 4"

3/

8" 3"

3" 2"

CL. 7/8"Ø Bolts

5 1/2" 5 1/2"

2 1/2" 6" 2 1/2"

W x1

CL. W14, W10 and Pl.

1' -1

3/

8"

U

TO COLUMN

El. 55.33

A 60796

WP

W x1

2MC8x18.7

W10x54

5/16

5/16

GP10

3/

4"

1' -1

3/

8"

1" E xt en si on

/8

S ee

S ch ed ul e

"A

1"

6 1/2"Back-to-back channel connection to gusset Pl.

shall provide Class A faying surface, per AISC J3.8

/8

1' -0

4" 4"

3/

8" 3"

3" 2"

11"

W x1

5 1/2"5 1/2"

2 1/2"6"2 1/2"

CL. W14, W10 and Pl.

CL. 7/8"Ø Bolts

5/16

5/16

Typ. T & B Flange 5/16

5/16

3/4" Pl.

W10x54

1' -1

3/

8"

11"

1' -0

5 1/2"5 1/2"

2 1/2"6"2 1/2"

W x1

5/16

5/16

Typ. T & B Flange 5/16

5/16

CL. W14, W10 and Pl.

6" 6"

4" 4"

4"

CL. 7/8"Ø Bolts

CL. W10 and Pl.

W10x54

3/4" Pl.

CL

WP

W10x54

2M C8 x1 8.

2M C

8x

.7

2MC8x18.7

"A", See Schedule

CL. W10

CL. 2MC8

CL. 2MC8

5/16

5/16

1/

2"

6 1/2"

1/

2"

CL. 2MC8

Back-to-back channel connection to gusset Pl.

shall provide Class A faying surface, per AISC J3.8

W10x54

2M C8x

.7

2M C

8x

.7

1/

2"

6 1 /2"

WP CL. W10

CL. 2MC8

CL. 2MC8

5/16

5/16

"A", See Schedule

Back-to-back channel connection to gusset Pl.

shall provide Class A faying surface, per AISC J3.8

W10x54

2M C8x

.7

2M C

8x

.7

1/ 2"

6 1 /2"

5/16

5/16

WP

CL. W10

CL. 2MC8

CL. 2MC8

"A", See Schedule

Back-to-back channel connection to gusset Pl.

shall provide Class A faying surface, per AISC J3.8

D

C

B

D

C

B

A

A

SA

FE

TY

AL

W

AY

S

TH

IN

K

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

AR

TM

EN

T O

F

TH

E

IN

TE

R

IO

R

DESIGNED

CHECKED

DRAWN

TECH. APPR.

APPROVED

LE

A D

V

IL

LE

M

IN

E

D R A

IN

A G

E

TU

N N

EL

LE

A D

V

IL

LE

C O

LE

A D

V

IL

LE

M

IN

E

TR

EA

TM

EN

T

PL

A N

T A N

D F

A C

IL

IT

IE

S W

A

TE

R T

R

EA

TM

EN

T

PL

A N

T

Brandon Jackson, P.E.

Brandon Jackson, P.E.

Lisa Orgren, P.E.

Brandon Jackson, P.E.

David Kresin, P.E.

Peer Reviewer - Plant Structures Group

DENVER, CO 2022-09-30

STRUCTURAL STEEL

CONNECTION DETAILS

1335-D-60796

60680 Scale: 1 1/2" = 1'-0"

3 DETAIL

60796 Scale: 1 1/2" = 1'-0"

B DETAIL

60680 Scale: 1 1/2" = 1'-0"

1 DETAIL

60796 Scale: 1 1/2" = 1'-0"

A DETAIL

60680 Scale: 1 1/2" = 1'-0"

2 DETAIL

60680 Scale: 1 1/2" = 1'-0"

4 DETAIL

60680 Scale: 1 1/2" = 1'-0" 5 Main Truss - GP Bottom Chord - DETAIL

60680 Scale: 1 1/2" = 1'-0"

6 DETAIL

E

A

B

C

4 1/4"

3 1/2"

4 1/4"

D

90°

3 1/2"

1 1/2"

CL. 7

/8"Ø Bolts

A

B

1/

4"

1/

2"

1/

4"

C

D

4 1/4"

3 1/2"

4 1/4"

E

3 1/2"

F

CL

. 7

/8 "Ø

B olt s

1/

2"

1/

2"

CL. 7/8"Ø Bolts

3 1/2"

1 1/2"

CL. 7/8"Ø Bolts

1/

2"

1/ 2"

90° 90

1" 1"

BA

E

D

C

6 3/4" 3 1/2" 6 3/4"

1/

2"

1/ 2"

CL. 7/8"Ø Bolts

A

C

D

1 1 /2"

3 1 /2"

3 1/2"

B

1/

2"

1/ 2"

CL. 7/8"Ø Bolts

E

CL.

7/8

"Ø Bolt s

4 1/4"

3 1/2"

4 1/4"

90° 90

A

B

E

D

C

1 1/2"

3 1/2"

1/

2"

1/ 2"

3 1/2"

CL. 7/8"Ø Bolts

CL. 7

/8"Ø Bolts

4 1/4"

3 1/2"

4 1/4"

1/

2"

1/ 2"

D

C

B

D

C

B

A

A

SA

FE

TY

AL

W

AY

S

TH

IN

K

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

AR

TM

EN

T O

F

TH

E

IN

TE

R

IO

R

DESIGNED

CHECKED

DRAWN

TECH. APPR.

APPROVED

LE

A D

V

IL

LE

M

IN

E

D R A

IN

A G

E

TU

N N

EL

LE

A D

V

IL

LE

C O

LE

A D

V

IL

LE

M

IN

E

TR

EA

TM

EN

T

PL

A N

T A N

D F

A C

IL

IT

IE

S W

A

TE

R T

R

EA

TM

EN

T

PL

A N

T

Brandon Jackson, P.E.

Brandon Jackson, P.E.

Lisa Orgren, P.E.

Brandon Jackson, P.E.

David Kresin, P.E.

Peer Reviewer - Plant Structures Group

DENVER, CO 2022-09-30

STRUCTURAL STEEL

CONNECTION DETAILS

1335-D-60797

PLATE SCHEDULE

Mark No.

Gusset Type

No.

Req'd

Thickness A B C D E F

GP1 BCF 10 3/4" 9" 1'-0 13/16" 1'-0" 7" 1'-4 1/8"

GP2 KN 30 3/4" 3'-4" 1'-2" 2'-10 5/8" 1'-0" 3'-0 1/4"

GP3 KN 20 3/4" 2'-7" 7 5/8" 1'-11 7/8" 1'-0" 4 5/16"

GP4 KN 20 3/4" 2'-4" 9 1/2" 1'-7 1/4" 1'-0" 6 9/16"

GP5 KN 20 3/4" 2'-8 5/8" 1'-2" 2'-1 7/16" 1'-0" 4 3/8"

GP6 KN 20 3/4" 2'-2" 9 11/16" 1'-4 3/16" 1'-0" 7 7/16"

GP7 KT 10 3/4" 3'-2 1/8" 5 1/2" 1'-0" 1'-9 1/8" 1'-0" 5 1/2"

GP8 T 10 3/4" 10" 10" 10 7/16" 1'-5" 10 7/16"

GP9 KN 10 3/4" 2'-9 1/2" 14'-0" 2'-2 9/16" 1'-0" 4 3/16"

GP10 BCF 10 3/4" 11" 11 11/16" 1'-0" 11 1/16" 1'-2 3/4"

GUSSET TYPE BCF

GUSSET TYPE KT

GUSSET TYPE T

GUSSET TYPE KN

Note: Ref. to framing elevation for Mark No. locations.

WT5x22.5 WT5 x2

2.5

WT5x22.5WT5 x2

2.5

W F

B ea m

Pe r

Pl an

W F

B ea m

Pe r

Pl an

WF Beam, Per Plan

NS Flange not shown (Typ.)

1 1 /2

" M in.

1 1/2" Min.

1" S et ba ck

Ty p.

WP

CL. WF Beam

CL. WT5

CL. WT5

Roof bracing, where occurs, SIM to opposite side

1"Setback

1"Setback

"A

S ee

S ch ed ul e "A

S ee

S ch ed ul e

Va rie s

Varies

HB Pl. (Typ.) (60800)

3"

1 1/2"

60798

60798

3"

1 1 /2

L4x3x3/8 (Typ.)

60798

See Detail 4 (60757)

WT5

x2

2.5

WT5x22.5

6"

6"

HB Pl.

WP

W F

B ea m

Pe r

Pl an

"A

S ee

S ch ed ul e

5/16

5/16

CL. WT5

CL. WT5

(60800)

Roof bracing, where occurs, SIM to opposite side

WT5x22.5WT5x22.5

CL. WF Beam

WF Beam, Per Plan WF Beam, Per Plan

HB Pl. (60800) HB Pl.(60800)

1/

2"

CL. 7/8"Ø Bolts L4x3x3/8 (Typ.)

CL. 7/8"Ø Bolts

4"

2 1/2"

4"

2 1/2"

See Detail 4 (60757)

WF Beam, Per Plan

WT5x22.5

WT5x22.5

WF Beam, Per Plan

HB Pl. (Typ.)

1/

2" 3"

1/

2"

6"

L4x3x3/8

2 1/2"

4"

3"

1/

2"CL. 7/8" Ø Bolts

CL. 7/8" Ø Bolts

1/

2" 3"

3"

1/ 2"

9"

L4x3x3/8

2 1/2"

4"

3"

1/

2"CL. 7/8" Ø Bolts

CL. 7/8" Ø Bolts

D

C

B

D

C

B

A

A

SA

FE

TY

AL

W

AY

S

TH

IN

K

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

AR

TM

EN

T O

F

TH

E

IN

TE

R

IO

R

DESIGNED

CHECKED

DRAWN

TECH. APPR.

APPROVED

LE

A D

V

IL

LE

M

IN

E

D R A

IN

A G

E

TU

N N

EL

LE

A D

V

IL

LE

C O

LE

A D

V

IL

LE

M

IN

E

TR

EA

TM

EN

T

PL

A N

T A N

D F

A C

IL

IT

IE

S W

A

TE

R T

R

EA

TM

EN

T

PL

A N

T

Brandon Bowman, P.E.

Brandon Jackson, P.E.

Lisa Orgren, P.E.

Brandon Jackson, P.E.

David Kresin, P.E.

Peer Reviewer - Plant Structures Group

DENVER, CO 2022-09-30

STRUCTURAL STEEL

CONNECTION DETAILS

1335-D-60798

60669 Scale: 1 1/2" = 1'-0"

1 DETAIL

60669 Scale: 1 1/2" = 1'-0"

2 DETAIL

60798 Scale: 1 1/2" = 1'-0"

3 DETAIL

HORIZONTAL BRACING ISOMETRIC

Scale: 3" = 1'-0" L4x3x3/8 - 2 BOLT

Scale: 3" = 1'-0" L4x3x3/8 - 3 BOLT

60799

1" Setback (Typ.)

WP

HB Pl. (60800)

Min . 1 1/

2"

CL. WF Beam

C L.

W F

B ea m

Pe r

Pl an

W T5 x2 2.

CL. WT5

3"

1/

2"

WT5x22.5

WP

WF Beam, Per Plan

W F

B ea m

Pe r

Pl an

WF Column, Per Plan

CL. WT5

"A

S ee

S ch ed ul e

Va rie s

CL. WF Beam

NS Flange not shown (Typ.)

HB Pl.

1" Setback (Typ.)

A 60799

(60800)

B 60799

1 1/2" Min.

1 1/2"

3"

1" Setback

HB Pl.(60800)

L4x3x3/8, See(60798)

1/

2"

2 1/2"

4"

CL. 7/8"Ø Bolts

CL. 7/8"Ø Bolts

WT5x22.5

WF Beam, Per Plan

1" Setback

1 1/2"

WP

HB Pl. (Typ.) (60800) WF Beam, Per Plan

V ar ie s

R9 /1

6"

1/

4"

3 3/8"

CL. 7/8"Ø Bolts

CL. 7/8"Ø Bolts

1/

2" 3"

1/

2"

6"

CL. 7/8"Ø Bolts

3/8" Pl.

1 1/2"

1/

2"

3/8" Pl.

1 1/2"

1/

2" 3"

3"

1/ 2"

9"

1 1/2"

CL. 7/8"Ø Bolts

R9 /1

6"

1/

4"

3 3/8"

CL. 7/8"Ø Bolts

CL. 7/8"Ø Bolts

1 1/2"

1/

2"

B 60799

A 60799

WP

1 1/2" Min.

HB Pl.

3"

1 1/2"

WF Beam, Per Plan

W F

B ea m

Pe r

Pl an

CL. WF Beam

W T5x22.5

CL. WT5

Va rie s

"A

S ee

S ch ed ul e

1" Setback, (Typ.)

CL. WF Beam

(60800)

D

C

B

D

C

B

A

A

SA

FE

TY

AL

W

AY

S

TH

IN

K

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

AR

TM

EN

T O

F

TH

E

IN

TE

R

IO

R

DESIGNED

CHECKED

DRAWN

TECH. APPR.

APPROVED

LE

A D

V

IL

LE

M

IN

E

D R A

IN

A G

E

TU

N N

EL

LE

A D

V

IL

LE

C O

LE

A D

V

IL

LE

M

IN

E

TR

EA

TM

EN

T

PL

A N

T A N

D F

A C

IL

IT

IE

S W

A

TE

R T

R

EA

TM

EN

T

PL

A N

T

Brandon Bowman, P.E.

Brandon Bowman, P.E.

Lisa Orgren, P.E.

Brandon Jackson, P.E.

David Kresin, P.E.

Peer Reviewer - Plant Structures Group

DENVER, CO 2022-09-30

STRUCTURAL STEEL

CONNECTION DETAILS

1335-D-60799

60687 Scale: 1 1/2" = 1'-0"

2 DETAIL

60687 Scale: 1 1/2" = 1'-0"

3 DETAIL

Scale: 3" = 1'-0"A DETAIL Scale: 3" = 1'-0"B DETAIL 3/8" BENT PLATE

60671 Scale: 1 1/2" = 1'-0"

1 DETAIL

B

C

5 1 /2

3"

A

1/

2" M in

3" 3"

3" 3"

D

1/

2" M in

1 1/2"

1/

2"

CL. 7/8" Ø Bolts

CL. 7/8" Ø BoltsCL. WT5

1/2" Pl.

A

BF

D

E

EQ

EQ 5 1/2"

C

EQ

EQ

1/

2"

1/

2"

CL

. 7

/8 "Ø

B olt s

1/

2"

1 1/2"

3 1/2"CL. 7/8"Ø Bolts

3"

B

A

D

C3"

CL. WT5

1/

2"

1 1/2" Min.

1/

2" M in

1/

2"

CL. 7/8" Ø Bolts

1 1/2"

CL. 7/8" Ø Bolts

1/2" Pl.

D

C

B

D

C

B

A

A

SA

FE

TY

AL

W

AY

S

TH

IN

K

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

AR

TM

EN

T O

F

TH

E

IN

TE

R

IO

R

DESIGNED

CHECKED

DRAWN

TECH. APPR.

APPROVED

LE

A D

V

IL

LE

M

IN

E

D R A

IN

A G

E

TU

N N

EL

LE

A D

V

IL

LE

C O

LE

A D

V

IL

LE

M

IN

E

TR

EA

TM

EN

T

PL

A N

T A N

D F

A C

IL

IT

IE

S W

A

TE

R T

R

EA

TM

EN

T

PL

A N

T

Brandon Bowman, P.E.

Brandon Bowman, P.E.

Lisa Orgren, P.E.

Brandon Jackson, P.E.

David Kresin, P.E.

Peer Reviewer - Plant Structures Group

DENVER, CO 2022-09-30

STRUCTURAL STEEL

CONNECTION DETAILS

1335-D-60800

PLATE SCHEDULE

Gusset Type

Mark No.

No.

Req'd

Thickness A B C D E F

CVR HB1 16 1/2" 2'-4" 8" 10 1/4" 1'-0 1/4" 10 1/4" 8"

CVR HB2 2 1/2" 2'-8" 5 1/2" 11 1/4" 1'-5 3/8" 11 1/4" 5 1/2"

CVR HB3 6 1/2" 2'-4" 8" 1'-0 1/8" 7 3/4" 1'-0 1/8" 8"

CVR HB4 2 1/2" 2'-8" 4 3/8" 10" 1'-8 7/8" 10" 4 3/8"

CVR HB5 12 1/2" 2'-4" 7" 10'-0 5/8" 1'-0 1/4" 10 5/8" 7"

CVR HB6 4 1/2" 2'-4" 5 1/2" 1'-1 3/4" 4 3/4" 1'-1 3/4" 5 1/2"

CVR HB7 4 1/2" 2'-4" 8" 1'-0" 8" 1'-0" 8"

CVR HB8 4 1/2" 2'-4" 8" 10 3/8" 1'-0" 10 3/8" 8"

CVR HB9 8 1/2" 2'-4" 6" 11 1/4" 11 1/2" 11 1/4" 6"

CVR HB10 1 1/2" 2'-8" 5 1/2" 10 1/2" 1'-6 7/8" 10 1/2" 5 1/2"

CVR HB11 1 1/2" 2'-4" 5 1/2" 9 7/8" 1'-3" 9 7/8" 5 1/2"

CVR HB12 1 1/2" 2'-8" 4 5/8" 10 1/4" 1'-8" 10 1/4" 4 5/8"

CVR HB13 1 1/2" 2'-4" 6" 10 1/2" 1'-1" 10 1/2" 6'-0"

WG HB14 84 1/2" 2'-0" 1'-0" 10" 1'-7" 0" 0"

WG HB15 16 1/2" 1'-5" 1'-2" 11" 1'-8" 0" 0"

WG HB16 16 1/2" 1'-5" 1'-0" 1'-0" 1'-5" 0" 0"

WG HB17 4 1/2" 1'-5" 10" 10" 1'-5" 0" 0"

WG HB18 4 1/2" 2'-2" 11" 11" 2'-2"

WG-O HB20 7 1/2" 1'-11" 9" 11" 1'-11" 0" 0"

WG-O HB21 20 1/2" 1'-4" 11" 11" 1'-4" 0" 0"

GUSSET TYPE WGGUSSET TYPE CVR

WG-O

Note: Ref. to framing plan for Mark No. locations.

Vertical Braced Frame Connection, where occurs, SIM to opposite side

W12x40

W F

C ol

P er P la n

2MC8x18.7

W12x40

2M C8 x1 8.

CL. 2MC8

CL. W12

and Pl.

5/16

5/16

WP

CL. WF Col.

6" Va rie s

3"(Typ.)

1"Setback (Typ.)

"A", See Schedule

TYP

5/16

5/16

SP6 (60777)

6 1/2"

VB Pl. (60808)

Back-to-back channel connection to gusset Pl. shall provide Class A faying surface, per AISC J3.8

W12x40

2M C8 x1 8.

7 2MC8x18.7

CL. 2MC8

CL. W12

5/16

5/16

WP

Varies Va rie s

(60808)

CL. 2MC8

1/

2" 6 1/2"

"A", See Schedule

VB Pl.

Back-to-back channel connection to gusset Pl. shall provide Class A faying surface, per AISC J3.8

W12x40

2M C8x

.7

W x1

6…