This document contains a specification sheet for Cummins diesel generator sets ranging from 25 kW to 40 kW for stationary standby applications. The specification sheet provides technical details on the generator set engines, alternators, cooling systems, enclosures, fuel tanks, controls, emissions compliance, sound levels, voltage regulation and available options. It also lists standby and prime power ratings and dimensions for each model number. The related federal contract opportunity is a Request for Proposal to install NAVAIDS at Prince Sultan Air Base in Saudi Arabia. The RFP will be released on May 24, 2021 and the cover letter contains important dates and information for responding to the solicitation. The agency is the General Services Administration Federal Acquisition Service Assisted Acquisition Services Region 7.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
power.cummins.com ©2015 Cummins Power Generation Inc. | NAS-5872d-EN (8/15)
Specification sheet
Diesel generator set 25 kW - 40 kW EPA emissions stationary standby
Description
Cummins Power Generation generator sets are fully integrated power generation systems providing optimum performance, reliability and versatility for stationary standby applications.
Features
Cummins heavy-duty engine - Rugged 4-cycle, liquid-cooled, industrial diesel engine delivers reliable power, low emissions and fast response to load changes.
Alternator - Several alternator sizes offer selectable motor starting capability with low reactance 2/3 pitch windings, low waveform distortion with non-linear loads and fault clearing short-circuit capability.
Control system - The PowerCommand® 1.1 electronic control is standard equipment and provides total generator set system integration including automatic remote starting/stopping, precise frequency and voltage regulation, alarm and status message display, output metering, auto-shutdown at fault detection and NFPA 110 Level 1 compliance.
Cooling system - Standard cooling package provide reliable running at up to 50 °C (122 °F) ambient temperature.
Enclosures - The aesthetically appealing enclosure incorporates special designs that deliver one of the quietest generators of its kind.
Aluminum material plus durable powder coat paint provides the best anti-corrosion performance. The generator set enclosure has been evaluated to withstand 180 MPH wind loads in accordance with ASCE7-10. The intelligent design has removable panels and service doors to provide easy access for service and maintenance.
Fuel tanks - Two dual wall sub-base fuel tank series are offered as optional features, providing economical and flexible solutions to meet extensive code requirements on diesel fuel tanks.
NFPA - The generator set accepts full rated load in a single step in accordance with NFPA 110 for Level 1 systems.
Warranty and service - Backed by a comprehensive warranty and worldwide distributor and dealer network.
Standby rating Prime Rating Data sheets
60 Hz 60 Hz 60 Hz
Model kW kVA kW kVA
C25 D6 25 31.25 22.7 28.4 NAD-5859
C30 D6 30 37.5 27 33.75 NAD-5860
C35 D6 35 43.75 32 40 NAD-5861
C40 D6 40 50 36 45 NAD-5862
Generator set specifications Governor regulation class ISO 8528 Part 1 Class G2
Voltage regulation, no load to full load ± 1.0%
Random voltage variation ± 0.5% - 3 Phase only
Frequency regulation Isochronous
Random frequency variation ± 0.5%
Radio frequency emissions compliance FCC code Title 47 part 15 Class B
Engine specifications Bore 95.0 mm (3.74 in)
Stroke 115.1 mm (4.53 in)
Displacement 3.3 litres (199 in3)
Configuration Cast iron, in-line, 4 cylinder
Battery capacity 550 amps at ambient temperature of 0 °F to 32 °F (-18 °C to 0 °C)
Battery charging alternator 40 amps
Starting voltage 12 volt, negative ground
Fuel system Indirect injection, number 2 diesel fuel, fuel filter, electric fuel shut off
Fuel filter Single element, 10 micron filtration, spin-on fuel filter with water separator
Air cleaner type Dry replaceable element
Lube oil filter type(s) Spin-on, full flow
Standard cooling system 50 °C (122 °F) ambient cooling system
Alternator specifications Design Brushless, 4 pole, drip proof, revolving field
Stator 2/3 pitch
Rotor Direct coupled, flexible disc
Insulation system Class H per NEMA MG1-1.65
Standard temperature rise 120 ºC (248 °F) standby
Exciter type Torque match (shunt) with PMG/EBS as option
Alternator cooling Direct drive centrifugal blower
AC waveform total harmonic distortion < 5% no load to full linear load, < 3% for any single harmonic
Telephone influence factor (TIF) < 50 per NEMA MG1-22.43
Telephone harmonic factor (THF) 0.03
Available voltages Single phase 3 phase
120/240 120/208 120/240 delta 277/480 347/600
Note: Consult factory for other voltages.
Generator set options Fuel system Basic fuel tanks Regional fuel tanks
Engine Engine air cleaner – normal or heavy duty Shut down – low oil pressure Extension – oil drain
Alternator 120 °C (248 °F) temperature rise alternator 105 °C (221 °F) temperature rise alternator Excitation boost system (EBS) or
PMG
Alternator heater, 120 V
Control AC output analog meters (bargraph) Stop switch – emergency Auxiliary output relays (2) Auxiliary configurable signal inputs (8) and relay outputs (8)
Electrical Single circuit breaker Dual circuit breakers 80% rated circuit breakers 100% rated circuit breakers
Enclosure Aluminum enclosure Sound
Level 1 or Level 2, with muffler installed, sandstone or green color
Open set
Cooling system Shutdown – low coolant level Warning – low coolant level Extension – coolant drain Cold weather option for operating at <4 ° (40 °F)
Exhaust system Exhaust connector – NPT Open set with muffler mounted
Generator set application Battery rack, larger battery Radiator outlet duct adapter
Warranty Base warranty – 2 year, 400 hour, standby Standby, 3 year, 900 hour, parts Standby, 5 year, 1500 hour, parts Standby, 3 year, 900 hour, parts and labor Standby, 5 year, 1500 hour, parts and labor Standby, 3 year, 900 hour, parts, labor and travel Standby, 5 year, 1500 hour, parts, labor and travel
Note: Some options may not be available on all models - consult factory for availability.
Generator set accessories Extreme cold weather kit Battery rack, larger battery Battery heater kit HMI211RS in-home display, including pre-configured 12” harness HMI211 remote display, including pre-configured 12”harness HMI220 remote display Auxiliary output relays (2) Auxiliary configurable signal inputs (8) and relay outputs (8) Annunciator – RS485 Remote monitoring device – PowerCommand 500
Battery charger – stand-alone, 12 V Circuit breakers Enclosure Sound Level 1 to Sound Level 2 upgrade kit Enclosure paint touch up kit Mufflers – industrial, residential or critical Alternator excitation boost system (EBS) or PMG Alternator heater Maintenance and service kit Engine lift kit Various fuel tanks and accessories
Louis.Holt Highlight
Louis.Holt Highlight
Louis.Holt Highlight
Louis.Holt Highlight
Louis.Holt Highlight
Louis.Holt Highlight
Louis.Holt Highlight
Louis.Holt Highlight
Louis.Holt Highlight
Louis.Holt Highlight
Louis.Holt Highlight
Louis.Holt Highlight
Louis.Holt Highlight
Louis.Holt Highlight
Louis.Holt Highlight
Louis.Holt Highlight
Louis.Holt Highlight
Control system PowerCommand 1.1
PowerCommand control is an integrated generator set control system providing voltage regulation, engine protection, operator interface and isochronous governing (optional). Major features include:
Battery monitoring and testing features and smart starting control system.
Standard PCCNet interface to devices such as remote annunciator for NFPA 110 applications.
Control boards potted for environmental protection.
Control suitable for operation in ambient temperatures from -40 °C to +70 °C (-40 °F to +158 °F) and altitudes to 5000 meters (13,000 feet).
Prototype tested; UL, CSA, and CE compliant.
InPower™ PC-based service tool available for detailed diagnostics.
Operator/display panel
Manual off switch Alpha-numeric display with pushbutton access for viewing engine and alternator data and providing setup, controls and adjustments (English or international symbols)
LED lamps indicating generator set running, not in auto, common warning, common shutdown, manual run mode and remote start
Suitable for operation in ambient temperatures from -40 C to +70 C
Bargraph display (optional)
AC protection
Over current warning and shutdown Over and under voltage shutdown Over and under frequency shutdown Over excitation (loss of sensing) fault Field overload
Engine protection
Overspeed shutdown Low oil pressure warning and shutdown High coolant temperature warning and shutdown Low coolant level warning or shutdown Low coolant temperature warning High, low and weak battery voltage warning Fail to start (overcrank) shutdown Fail to crank shutdown Redundant start disconnect Cranking lockout Sensor failure indication Low fuel level warning or shutdown
Alternator data
Line-to-line and Line-to-neutral AC volts 3-phase AC current Frequency Total kVa
Engine data
DC voltage Lube oil pressure Coolant temperature Engine speed
Other data
Generator set model data Start attempts, starts, running hours Fault history RS485 Modbus® interface Data logging and fault simulation (requires InPower service tool)
Digital governing (optional)
Integrated digital electronic isochronous governor Temperature dynamic governing
Digital voltage regulation
Integrated digital electronic voltage regulator 2-phase line-to-line sensing Configurable torque matching
Control functions
Time delay start and cooldown Cycle cranking PCCNet interface
(2) Configurable inputs
(2) Configurable outputs Remote emergency stop Automatic transfer switch (ATS) control Generator set exercise, field adjustable
Options
Auxiliary output relays (2) Remote annunciator with (3) configurable inputs and
(4) configurable outputs PMG alternator excitation PowerCommand 500/550 for remote monitoring and alarm notification (accessory) Auxiliary, configurable signal inputs (8) and configurable relay outputs (8) Digital governing AC output analog meters (bargraph)
- Color-coded graphical display of:
- 3-phase AC voltage
- 3-phase current
- Frequency
- kVa
Remote operator panel
Louis.Holt Highlight
North America
1400 73rd Avenue N.E.
Minneapolis, MN 55432
USA
Phone 763 574 5000
Fax 763 574 5298
©2015 Cummins Power Generation Inc. All rights reserved.
Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
NAS-5872d-EN (8/15) power.cummins.com
Ratings definitions Emergency standby power (ESP):
Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source.
Emergency Standby Power (ESP) is in accordance with ISO 8528.
Fuel Stop power in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514.
Limited-time running power (LTP):
Applicable for supplying power to a constant electrical load for limited hours. Limited Time Running Power (LTP) is in accordance with ISO 8528.
Prime power (PRP):
Applicable for supplying power to varying electrical load for unlimited hours. Prime Power (PRP) is in accordance with ISO 8528. Ten percent overload capability is available in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514.
Base load (continuous) power (COP):
Applicable for supplying power continuously to a constant electrical load for unlimited hours. Continuous Power (COP) in accordance with ISO 8528, ISO 3046, AS 2789, DIN 6271 and
BS 5514.
This outline drawing is for reference only. See respective model data sheet for specific model outline drawing number.
Do not use for installation design
Model Dim “A” mm (in.)
Dim “B” mm (in.)
Dim “C” mm (in.)
Set Weight* dry kg (lbs)
Set Weight* wet kg (lbs)
Open Set C25 D6 2224 (87.5) 864 (34) 1121 (44.13) 504 (1115) 525 (1161) C30 D6 2224 (87.5) 864 (34) 1121 (44.13) 533 (1178) 553 (1224) C35 D6 2224 (87.5) 864 (34) 1121 (44.13) 552 (1221) 573 (1267) C40 D6 2224 (87.5) 864 (34) 1121 (44.13) 566 (1252) 587 (1298)
Sound Attenuated Enclosure Level 1 C25 D6 2384 (93.8) 864 (34) 1156 (45.5) 551 (1219) 572 (1265) C30 D6 2384 (93.8) 864 (34) 1156 (45.5) 580 (1282) 600 (1328) C35 D6 2384 (93.8) 864 (34) 1156 (45.5) 599 (1325) 620 (1371) C40 D6 2384 (93.8) 864 (34) 1156 (45.5) 613 (1356) 634 (1402)
Sound Attenuated Enclosure Level 2 C25 D6 2629 (103.5) 864 (34) 1156 (45.5) 570 (1261) 591 (1307) C30 D6 2629 (103.5) 864 (34) 1156 (45.5) 599 (1324) 619 (1370) C35 D6 2629 (103.5) 864 (34) 1156 (45.5) 618 (1367) 639 (1413) C40 D6 2629 (103.5) 864 (34) 1156 (45.5) 632 (1398) 653 (1444)
* Weights represent a set with standard features. See outline drawings for weights of other configurations.
Codes and standards
Codes or standards compliance may not be available with all model configurations – consult factory for availability.
The Prototype Test Support (PTS) program verifies the performance integrity of the generator set design. Cummins Power Generation products bearing the PTS symbol meet the prototype test requirements of NFPA 110 for Level 1 systems.
This generator set is designed in facilities certified to ISO 9001 and manufactured in facilities certified to ISO 9001 or ISO 9002.
The generator set is available Listed to UL 2200, Stationary Engine Generator Assemblies.
International Building Code
The generator set is certified for seismic application in accordance with International Building Code (IBC) 2012.
All low voltage models are CSA certified to product class 4215-01.
U.S. EPA
Engine certified to U.S. EPA SI Stationary Emission Regulation 40 CFR, Part 60.
Warning: Back feed to a utility system can cause electrocution and/or property damage. Do not connect to any building’s electrical system except through an approved device or after building main switch is open.
File details come from the government source that posted it. Updated .