Attachment 8 - Togus VAMC Building 207 Damper Inspection Report - 20.pdf
PDF 3 MB Posted
- Solicitation number
- 36C24126Q0052
About this file
This document is a Damper Inspection Report for the Togus Veterans Affairs Medical Center (VAMC) in Building 207, conducted by Life Safety Services (LSS) from October 6-12, 2022. The inspection involved examining fire dampers across multiple floors, including the penthouse and floors 2 and 3, in accordance with National Fire Protection Association (NFPA) Standard 80 Chapter 19 and 105 Chapter 7.
The comprehensive inspection covered a total of 19 fire dampers, with inspections performed on two separate dates (October 6 and 12, 2022) by technician Lashawn Jones. All dampers were located in various areas such as confined spaces, mechanical rooms, elevator floor hatches, and inside the penthouse. The inspection results were uniformly positive, with 100% of dampers passing the assessment. Each damper was photographed in both open and closed positions, and the report includes detailed location descriptions, damper tags, and specific floor locations for each inspected unit.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
908 South 8th Street Louisville, KY. 40203
888.675.4519 info@LifeSafetyServices.com
Damper Inspection Report Togus VAMC - Building 207
10/06/2022 - 10/12/2022 www.LifeSafetyServices.com
DAMPER INSPECTION REPORT
Corporate Office 908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Togus VAMC Inspection Date: 10/06/2022 Inspected By: Lashawn Jones Job ID: SB-062822-01-SS
FIRE & SMOKE DAMPER INSPECTION SERVICES
LSS Life Safety Services, LLC, in accordance with The National Fire Protection Association’s (NFPA) Standard 80 Chapter 19 and 105 Chapter 7 inspected fire and smoke dampers located in 207 during the period of 10/06/2022.
The following report and digital pictures provide the result of the inspection for the dampers that were inspected.
This report is intended to describe the location and operability of the dampers for the date in which LSS Life Safety Services’ representatives performed the inspection of the dampers, and is not intended to constitute any warranty as to the continued operation of any damper.
Thank you for contracting LSS Life Safety Services for this project and we look forward to the opportunity of working with you in the future on additional projects.
Technician Signature
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Project Summary Building Fire Smoke Combination Pass Fail Non-Accessible Total Dampers
207 19 0 0 19 0 0 19
GRAND TOTAL 19 0 0 19 0 0 19
Statistics Test Result % of Dampers
Pass 100.00%
Fail 0.00%
Non-Accessible / Decommissioned 0.00%
Type Total % of Dampers
Fire 19 100.00%
Smoke 0 0.00%
Combination 0 0.00%
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Togus VAMC Inspection Date: 10/06/2022 Inspected By: Lashawn Jones
All Dampers Date Floor Damper Number Damper
Type Damper Location
Inspection Result
Reason for Failure or Inaccessibility
10/06/2022 Penthouse PH-FD-001 Fire Inside penthouse Pass
10/06/2022 Penthouse PH-FD-002 Fire Inside penthouse by steps Pass
10/06/2022 Penthouse PH-FD-003 Fire Inside penthouse by steps Pass
10/06/2022 Penthouse PH-FD-004 Fire Inside penthouse by AHU-2 Pass
10/06/2022 Penthouse PH-FD-005 Fire Inside penthouse Pass
10/06/2022 Penthouse PH-FD-006 Fire Inside penthouse Pass
10/06/2022 Penthouse PH-FD-007 Fire Inside penthouse Pass
10/06/2022 Penthouse PH-FD-008 Fire Inside penthouse Pass
10/06/2022 Penthouse PH-FD-009 Fire Inside penthouse Pass
10/06/2022 Penthouse PH-FD-010 Fire Inside penthouse Pass
10/06/2022 Penthouse PH-FD-011 Fire Inside penthouse Pass
10/06/2022 Penthouse PH-FD-012 Fire Inside mechanical room under floor grill Pass
10/06/2022 Penthouse PH-FD-013 Fire Inside mechanical room under floor grill Pass
10/06/2022 Penthouse PH-FD-014 Fire Inside mechanical room under floor grill Pass
10/06/2022 3 3-FD-001 Fire Inside confine space room 375 Pass
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside penthouse
Tag: PH-FD-001
Type: Fire
Floor: Penthouse
Status: Pass
Open Photo
Closed Photo https://www.gocanvas.com/values/14926010883 https://www.gocanvas.com/values/14926010883 https://www.gocanvas.com/values/14926010884 https://www.gocanvas.com/values/14926010884
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside penthouse by steps
Tag: PH-FD-002
Type: Fire
Floor: Penthouse
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/14926010993 https://www.gocanvas.com/values/14926010993 https://www.gocanvas.com/values/14926010994 https://www.gocanvas.com/values/14926010994
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside penthouse by steps
Tag: PH-FD-003
Type: Fire
Floor: Penthouse
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/14926011066 https://www.gocanvas.com/values/14926011066 https://www.gocanvas.com/values/14926011067 https://www.gocanvas.com/values/14926011067
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside penthouse by AHU-2
Tag: PH-FD-004
Type: Fire
Floor: Penthouse
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/14926011099 https://www.gocanvas.com/values/14926011099 https://www.gocanvas.com/values/14926011100 https://www.gocanvas.com/values/14926011100
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside penthouse
Tag: PH-FD-005
Type: Fire
Floor: Penthouse
Status: Pass
Open Photo
Closed Photo https://www.gocanvas.com/values/14926011199 https://www.gocanvas.com/values/14926011199 https://www.gocanvas.com/values/14926011200 https://www.gocanvas.com/values/14926011200
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside penthouse
Tag: PH-FD-006
Type: Fire
Floor: Penthouse
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/14926011272 https://www.gocanvas.com/values/14926011272 https://www.gocanvas.com/values/14926011273 https://www.gocanvas.com/values/14926011273
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside penthouse
Tag: PH-FD-007
Type: Fire
Floor: Penthouse
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/14926011389 https://www.gocanvas.com/values/14926011389 https://www.gocanvas.com/values/14926011392 https://www.gocanvas.com/values/14926011392
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside penthouse
Tag: PH-FD-008
Type: Fire
Floor: Penthouse
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/14926011538 https://www.gocanvas.com/values/14926011538 https://www.gocanvas.com/values/14926011539 https://www.gocanvas.com/values/14926011539
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside penthouse
Tag: PH-FD-009
Type: Fire
Floor: Penthouse
Status: Pass
Open Photo
Closed Photo https://www.gocanvas.com/values/14926011619 https://www.gocanvas.com/values/14926011619 https://www.gocanvas.com/values/14926011620 https://www.gocanvas.com/values/14926011620
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside penthouse
Tag: PH-FD-010
Type: Fire
Floor: Penthouse
Status: Pass
Open Photo
Closed Photo https://www.gocanvas.com/values/14926011692 https://www.gocanvas.com/values/14926011692 https://www.gocanvas.com/values/14926011693 https://www.gocanvas.com/values/14926011693
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside penthouse
Tag: PH-FD-011
Type: Fire
Floor: Penthouse
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/14926011765 https://www.gocanvas.com/values/14926011765 https://www.gocanvas.com/values/14926011766 https://www.gocanvas.com/values/14926011766
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside mechanical room under floor grill
Tag: PH-FD-012
Type: Fire
Floor: Penthouse
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/14926011838 https://www.gocanvas.com/values/14926011838 https://www.gocanvas.com/values/14926011839 https://www.gocanvas.com/values/14926011839
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside mechanical room under floor grill
Tag: PH-FD-013
Type: Fire
Floor: Penthouse
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/14926011995 https://www.gocanvas.com/values/14926011995 https://www.gocanvas.com/values/14926011997 https://www.gocanvas.com/values/14926011997
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside mechanical room under floor grill
Tag: PH-FD-014
Type: Fire
Floor: Penthouse
Status: Pass
Open Photo
Closed Photo https://www.gocanvas.com/values/14926012124 https://www.gocanvas.com/values/14926012124 https://www.gocanvas.com/values/14926012126 https://www.gocanvas.com/values/14926012126
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside confine space room 375
Tag: 3-FD-001
Type: Fire
Floor: 3
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/14926012437 https://www.gocanvas.com/values/14926012437 https://www.gocanvas.com/values/14926012442 https://www.gocanvas.com/values/14926012442
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Togus VAMC Inspection Date: 10/12/2022 Inspected By: Lashawn Jones Job ID: SB-062822-01-SS
FIRE & SMOKE DAMPER INSPECTION SERVICES
LSS Life Safety Services, LLC, in accordance with The National Fire Protection Association’s (NFPA) Standard 80 Chapter 19 and 105 Chapter 7 inspected fire and smoke dampers located in 207 during the period of 10/12/2022.
The following report and digital pictures provide the result of the inspection for the dampers that were inspected.
This report is intended to describe the location and operability of the dampers for the date in which LSS Life Safety Services’ representatives performed the inspection of the dampers, and is not intended to constitute any warranty as to the continued operation of any damper.
Thank you for contracting LSS Life Safety Services for this project and we look forward to the opportunity of working with you in the future on additional projects.
Technician Signature
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Togus VAMC Inspection Date: 10/12/2022 Inspected By: Lashawn Jones
All Dampers Date Floor Damper Number Damper
Type Damper Location
Inspection Result
Reason for Failure or Inaccessibility
10/12/2022 3 3-FD-002 Fire Inside confined space 376 Pass
10/12/2022 3 3-FD-003 Fire Outside elevators floor hatch Pass
10/12/2022 3 3-FD-004 Fire Outside elevators floor hatch Pass
10/12/2022 2 2-FD-001 Fire Inside confined space 275 Pass
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside confined space 376
Tag: 3-FD-002
Type: Fire
Floor: 3
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/14960739150 https://www.gocanvas.com/values/14960739150 https://www.gocanvas.com/values/14960739154 https://www.gocanvas.com/values/14960739154
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Outside elevators floor hatch
Tag: 3-FD-003
Type: Fire
Floor: 3
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/14960739480 https://www.gocanvas.com/values/14960739480 https://www.gocanvas.com/values/14960739485 https://www.gocanvas.com/values/14960739485
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Outside elevators floor hatch
Tag: 3-FD-004
Type: Fire
Floor: 3
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/14960739863 https://www.gocanvas.com/values/14960739863 https://www.gocanvas.com/values/14960739871 https://www.gocanvas.com/values/14960739871
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside confined space 275
Tag: 2-FD-001
Type: Fire
Floor: 2
Status: Pass
Open Photo
Closed Photo https://www.gocanvas.com/values/14960740186 https://www.gocanvas.com/values/14960740186 https://www.gocanvas.com/values/14960740188 https://www.gocanvas.com/values/14960740188
908 South 8th Street Louisville, KY. 40203
888.675.4519 info@LifeSafetyServices.com
Damper Inspection Report Togus VAMC - Building 207
10/06/2022 - 10/12/2022 www.LifeSafetyServices.com
| 10_06_2022_207_10_06_2022_15_30_Damper_Inspection - 207 |
| 3 |
| Penthouse |
| 10_12_2022_207_10_13_2022_10_46_Damper_Inspection - 207 |
| 2 |
| 3 |
File details come from the government source that posted it. Updated .