Attachment 1 - Togus VAMC Building 248 Damper Inspection Report - 2022.pdf
PDF 3 MB Posted
- Solicitation number
- 36C24126Q0052
About this file
This document is a Damper Inspection Report for the Togus Veterans Affairs Medical Center (VAMC) - Building 248, conducted by Life Safety Services (LSS) over two inspection dates: 10/19/2022 and 11/10/2022. The inspection was performed in accordance with National Fire Protection Association (NFPA) Standard 80 Chapter 19 and 105 Chapter 7, focusing on fire and smoke dampers.
The comprehensive report details the inspection of a total of 9 fire dampers across multiple floors, including the first floor, second floor, and basement. All dampers were located in various rooms such as women's and men's restrooms, elevator machine room, and shaft walls. Each damper was individually tagged, photographed in open and closed positions, and assigned a status. Notably, 100% of the dampers passed the inspection, with no failures or non-accessible dampers reported. The inspection was conducted by technician Lashawn Jones, with the job ID SB-062822-01-SS, and the report includes detailed photographic evidence for each damper's condition.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
908 South 8th Street Louisville, KY. 40203
888.675.4519 info@LifeSafetyServices.com
Damper Inspection Report Togus VAMC - Building 248
10/19/2022 - 11/10/2022 www.LifeSafetyServices.com
DAMPER INSPECTION REPORT
Corporate Office 908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Togus VAMC Inspection Date: 10/19/2022 Inspected By: Lashawn Jones Job ID: SB-062822-01-SS
FIRE & SMOKE DAMPER INSPECTION SERVICES
LSS Life Safety Services, LLC, in accordance with The National Fire Protection Association’s (NFPA) Standard 80 Chapter 19 and 105 Chapter 7 inspected fire and smoke dampers located in 248 during the period of 10/19/2022.
The following report and digital pictures provide the result of the inspection for the dampers that were inspected.
This report is intended to describe the location and operability of the dampers for the date in which LSS Life Safety Services’ representatives performed the inspection of the dampers, and is not intended to constitute any warranty as to the continued operation of any damper.
Thank you for contracting LSS Life Safety Services for this project and we look forward to the opportunity of working with you in the future on additional projects.
Technician Signature
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Project Summary Building Fire Smoke Combination Pass Fail Non-Accessible Total Dampers
248 8 0 0 8 0 0 8
GRAND TOTAL 8 0 0 8 0 0 8
Statistics Test Result % of Dampers
Pass 100.00%
Fail 0.00%
Non-Accessible / Decommissioned 0.00%
Type Total % of Dampers
Fire 8 100.00%
Smoke 0 0.00%
Combination 0 0.00%
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Togus VAMC Inspection Date: 10/19/2022 Inspected By: Lashawn Jones
All Dampers Date Floor Damper Number Damper
Type Damper Location
Inspection Result
Reason for Failure or Inaccessibility
10/19/2022 1 1-FD-001 Fire Inside room 114 back wall shaft Pass
10/19/2022 1 1-FD-002 Fire Inside women’s rest room 104A Pass
10/19/2022 1 1-FD-003 Fire Inside women’s rest room 104A Pass
10/19/2022 2 2-FD-001 Fire Inside women’s restroom back wall Pass
10/19/2022 2 2-FD-002 Fire Inside 201G shaft wall inside vent Pass
10/19/2022 2 2-FD-003 Fire Inside 201G shaft wall inside vent Pass
10/19/2022 2 2-FD-004 Fire Inside men’s bathroom back wall hatch
Pass
10/19/2022 2 2-FD-005 Fire Inside men’s bathroom back wall hatch
Pass
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside room 114 back wall shaft
Tag: 1-FD-001
Type: Fire
Floor: 1
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15013028718 https://www.gocanvas.com/values/15013028718 https://www.gocanvas.com/values/15013028720 https://www.gocanvas.com/values/15013028720
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside women’s rest room 104A
Tag: 1-FD-002
Type: Fire
Floor: 1
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15013028853 https://www.gocanvas.com/values/15013028853 https://www.gocanvas.com/values/15013028855 https://www.gocanvas.com/values/15013028855
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside women’s rest room 104A
Tag: 1-FD-003
Type: Fire
Floor: 1
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15013029013 https://www.gocanvas.com/values/15013029013 https://www.gocanvas.com/values/15013029016 https://www.gocanvas.com/values/15013029016
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside women’s restroom back wall
Tag: 2-FD-001
Type: Fire
Floor: 2
Status: Pass
Open Photo
Closed Photo https://www.gocanvas.com/values/15013029160 https://www.gocanvas.com/values/15013029160 https://www.gocanvas.com/values/15013029162 https://www.gocanvas.com/values/15013029162
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside 201G shaft wall inside vent
Tag: 2-FD-002
Type: Fire
Floor: 2
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15013029296 https://www.gocanvas.com/values/15013029296 https://www.gocanvas.com/values/15013029297 https://www.gocanvas.com/values/15013029297
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside 201G shaft wall inside vent
Tag: 2-FD-003
Type: Fire
Floor: 2
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15013029388 https://www.gocanvas.com/values/15013029388 https://www.gocanvas.com/values/15013029389 https://www.gocanvas.com/values/15013029389
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside men’s bathroom back wall hatch
Tag: 2-FD-004
Type: Fire
Floor: 2
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15013029468 https://www.gocanvas.com/values/15013029468 https://www.gocanvas.com/values/15013029470 https://www.gocanvas.com/values/15013029470
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside men’s bathroom back wall hatch
Tag: 2-FD-005
Type: Fire
Floor: 2
Status: Pass
Open Photo
Closed Photo https://www.gocanvas.com/values/15013029603 https://www.gocanvas.com/values/15013029603 https://www.gocanvas.com/values/15013029605 https://www.gocanvas.com/values/15013029605
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Togus VAMC Inspection Date: 11/10/2022 Inspected By: Lashawn Jones Job ID: SB-062822-01-SS
FIRE & SMOKE DAMPER INSPECTION SERVICES
LSS Life Safety Services, LLC, in accordance with The National Fire Protection Association’s (NFPA) Standard 80 Chapter 19 and 105 Chapter 7 inspected fire and smoke dampers located in 248 during the period of 11/10/2022.
The following report and digital pictures provide the result of the inspection for the dampers that were inspected.
This report is intended to describe the location and operability of the dampers for the date in which LSS Life Safety Services’ representatives performed the inspection of the dampers, and is not intended to constitute any warranty as to the continued operation of any damper.
Thank you for contracting LSS Life Safety Services for this project and we look forward to the opportunity of working with you in the future on additional projects.
Technician Signature
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Togus VAMC Inspection Date: 11/10/2022 Inspected By: Lashawn Jones
All Dampers Date Floor Damper Number Damper
Type Damper Location
Inspection Result
Reason for Failure or Inaccessibility
11/10/2022 Basement B-FD-001 Fire Inside elevator machine room Pass
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside elevator machine room
Tag: B-FD-001
Type: Fire
Floor: Basement
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15188863483 https://www.gocanvas.com/values/15188863483 https://www.gocanvas.com/values/15188863484 https://www.gocanvas.com/values/15188863484
908 South 8th Street Louisville, KY. 40203
888.675.4519 info@LifeSafetyServices.com
Damper Inspection Report Togus VAMC
10/19/2022 - 11/10/2022 www.LifeSafetyServices.com
| 10_19_2022_248_10_19_2022_17_47_Damper_Inspection |
| 1 |
| 2 |
| 11_10_2022_248_11_10_2022_12_28_Damper_Inspection |
| Basement |
File details come from the government source that posted it. Updated .