Attachment 1 - Togus VAMC Building 248 Damper Inspection Report - 2022.pdf

PDF 3 MB Posted

Attached to
H341--Fire and Smoke Damper Inspection and Service Contract
Solicitation number
36C24126Q0052
Issued by

About this file

This document is a Damper Inspection Report for the Togus Veterans Affairs Medical Center (VAMC) - Building 248, conducted by Life Safety Services (LSS) over two inspection dates: 10/19/2022 and 11/10/2022. The inspection was performed in accordance with National Fire Protection Association (NFPA) Standard 80 Chapter 19 and 105 Chapter 7, focusing on fire and smoke dampers.

The comprehensive report details the inspection of a total of 9 fire dampers across multiple floors, including the first floor, second floor, and basement. All dampers were located in various rooms such as women's and men's restrooms, elevator machine room, and shaft walls. Each damper was individually tagged, photographed in open and closed positions, and assigned a status. Notably, 100% of the dampers passed the inspection, with no failures or non-accessible dampers reported. The inspection was conducted by technician Lashawn Jones, with the job ID SB-062822-01-SS, and the report includes detailed photographic evidence for each damper's condition.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

908 South 8th Street Louisville, KY. 40203

888.675.4519 info@LifeSafetyServices.com

Damper Inspection Report Togus VAMC - Building 248

10/19/2022 - 11/10/2022 www.LifeSafetyServices.com

DAMPER INSPECTION REPORT

Corporate Office 908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Facility: Togus VAMC Inspection Date: 10/19/2022 Inspected By: Lashawn Jones Job ID: SB-062822-01-SS

FIRE & SMOKE DAMPER INSPECTION SERVICES

LSS Life Safety Services, LLC, in accordance with The National Fire Protection Association’s (NFPA) Standard 80 Chapter 19 and 105 Chapter 7 inspected fire and smoke dampers located in 248 during the period of 10/19/2022.

The following report and digital pictures provide the result of the inspection for the dampers that were inspected.

This report is intended to describe the location and operability of the dampers for the date in which LSS Life Safety Services’ representatives performed the inspection of the dampers, and is not intended to constitute any warranty as to the continued operation of any damper.

Thank you for contracting LSS Life Safety Services for this project and we look forward to the opportunity of working with you in the future on additional projects.

Technician Signature

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Project Summary Building Fire Smoke Combination Pass Fail Non-Accessible Total Dampers

248 8 0 0 8 0 0 8

GRAND TOTAL 8 0 0 8 0 0 8

Statistics Test Result % of Dampers

Pass 100.00%

Fail 0.00%

Non-Accessible / Decommissioned 0.00%

Type Total % of Dampers

Fire 8 100.00%

Smoke 0 0.00%

Combination 0 0.00%

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Facility: Togus VAMC Inspection Date: 10/19/2022 Inspected By: Lashawn Jones

All Dampers Date Floor Damper Number Damper

Type Damper Location

Inspection Result

Reason for Failure or Inaccessibility

10/19/2022 1 1-FD-001 Fire Inside room 114 back wall shaft Pass

10/19/2022 1 1-FD-002 Fire Inside women’s rest room 104A Pass

10/19/2022 1 1-FD-003 Fire Inside women’s rest room 104A Pass

10/19/2022 2 2-FD-001 Fire Inside women’s restroom back wall Pass

10/19/2022 2 2-FD-002 Fire Inside 201G shaft wall inside vent Pass

10/19/2022 2 2-FD-003 Fire Inside 201G shaft wall inside vent Pass

10/19/2022 2 2-FD-004 Fire Inside men’s bathroom back wall hatch

Pass

10/19/2022 2 2-FD-005 Fire Inside men’s bathroom back wall hatch

Pass

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside room 114 back wall shaft

Tag: 1-FD-001

Type: Fire

Floor: 1

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15013028718 https://www.gocanvas.com/values/15013028718 https://www.gocanvas.com/values/15013028720 https://www.gocanvas.com/values/15013028720

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside women’s rest room 104A

Tag: 1-FD-002

Type: Fire

Floor: 1

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15013028853 https://www.gocanvas.com/values/15013028853 https://www.gocanvas.com/values/15013028855 https://www.gocanvas.com/values/15013028855

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside women’s rest room 104A

Tag: 1-FD-003

Type: Fire

Floor: 1

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15013029013 https://www.gocanvas.com/values/15013029013 https://www.gocanvas.com/values/15013029016 https://www.gocanvas.com/values/15013029016

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside women’s restroom back wall

Tag: 2-FD-001

Type: Fire

Floor: 2

Status: Pass

Open Photo

Closed Photo https://www.gocanvas.com/values/15013029160 https://www.gocanvas.com/values/15013029160 https://www.gocanvas.com/values/15013029162 https://www.gocanvas.com/values/15013029162

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside 201G shaft wall inside vent

Tag: 2-FD-002

Type: Fire

Floor: 2

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15013029296 https://www.gocanvas.com/values/15013029296 https://www.gocanvas.com/values/15013029297 https://www.gocanvas.com/values/15013029297

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside 201G shaft wall inside vent

Tag: 2-FD-003

Type: Fire

Floor: 2

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15013029388 https://www.gocanvas.com/values/15013029388 https://www.gocanvas.com/values/15013029389 https://www.gocanvas.com/values/15013029389

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside men’s bathroom back wall hatch

Tag: 2-FD-004

Type: Fire

Floor: 2

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15013029468 https://www.gocanvas.com/values/15013029468 https://www.gocanvas.com/values/15013029470 https://www.gocanvas.com/values/15013029470

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside men’s bathroom back wall hatch

Tag: 2-FD-005

Type: Fire

Floor: 2

Status: Pass

Open Photo

Closed Photo https://www.gocanvas.com/values/15013029603 https://www.gocanvas.com/values/15013029603 https://www.gocanvas.com/values/15013029605 https://www.gocanvas.com/values/15013029605

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Facility: Togus VAMC Inspection Date: 11/10/2022 Inspected By: Lashawn Jones Job ID: SB-062822-01-SS

FIRE & SMOKE DAMPER INSPECTION SERVICES

LSS Life Safety Services, LLC, in accordance with The National Fire Protection Association’s (NFPA) Standard 80 Chapter 19 and 105 Chapter 7 inspected fire and smoke dampers located in 248 during the period of 11/10/2022.

The following report and digital pictures provide the result of the inspection for the dampers that were inspected.

This report is intended to describe the location and operability of the dampers for the date in which LSS Life Safety Services’ representatives performed the inspection of the dampers, and is not intended to constitute any warranty as to the continued operation of any damper.

Thank you for contracting LSS Life Safety Services for this project and we look forward to the opportunity of working with you in the future on additional projects.

Technician Signature

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Facility: Togus VAMC Inspection Date: 11/10/2022 Inspected By: Lashawn Jones

All Dampers Date Floor Damper Number Damper

Type Damper Location

Inspection Result

Reason for Failure or Inaccessibility

11/10/2022 Basement B-FD-001 Fire Inside elevator machine room Pass

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside elevator machine room

Tag: B-FD-001

Type: Fire

Floor: Basement

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15188863483 https://www.gocanvas.com/values/15188863483 https://www.gocanvas.com/values/15188863484 https://www.gocanvas.com/values/15188863484

908 South 8th Street Louisville, KY. 40203

888.675.4519 info@LifeSafetyServices.com

Damper Inspection Report Togus VAMC

10/19/2022 - 11/10/2022 www.LifeSafetyServices.com

10_19_2022_248_10_19_2022_17_47_Damper_Inspection
1
2
11_10_2022_248_11_10_2022_12_28_Damper_Inspection
Basement