Attachment 7 - Togus VAMC Building 206 Damper Inspection Report - 20.pdf
PDF 4 MB Posted
- Solicitation number
- 36C24126Q0052
About this file
This document is a Damper Inspection Report from Life Safety Services (LSS) for the Togus Veterans Affairs Medical Center (VAMC), documenting fire and smoke damper inspections performed across multiple dates in Building 206 during October and November 2022.
The inspections were conducted in accordance with National Fire Protection Association (NFPA) Standards 80 and 105, covering floors 1, 2, 3, and the penthouse. Across these floors, a total of 22 dampers were assessed, including 13 fire dampers and 9 smoke dampers. Of these, 19 dampers passed inspection (86.36%), while 3 dampers (13.64%) were marked non-accessible due to lack of authorized access doors. The inspections were performed by technician Lashawn Jones on 10/06/2022, 10/21/2022, 10/26/2022, and 11/03/2022, with dampers located in various areas such as chases, rooms, stairwells, and mechanical spaces. The report includes detailed photographic documentation of each damper's open and closed status, along with specific location and inspection results.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
908 South 8th Street Louisville, KY. 40203
888.675.4519 info@LifeSafetyServices.com
Damper Inspection Report Togus VAMC - Building 206
10/06/2022 - 11/03/2022 www.LifeSafetyServices.com
DAMPER INSPECTION REPORT
Corporate Office 908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Togus VAMC Inspection Date: 10/06/2022 Inspected By: Lashawn Jones Job ID: SB-062822-01-SS
FIRE & SMOKE DAMPER INSPECTION SERVICES
LSS Life Safety Services, LLC, in accordance with The National Fire Protection Association’s (NFPA) Standard 80 Chapter 19 and 105 Chapter 7 inspected fire and smoke dampers located in 206 during the period of 10/06/2022.
The following report and digital pictures provide the result of the inspection for the dampers that were inspected.
This report is intended to describe the location and operability of the dampers for the date in which LSS Life Safety Services’ representatives performed the inspection of the dampers, and is not intended to constitute any warranty as to the continued operation of any damper.
Thank you for contracting LSS Life Safety Services for this project and we look forward to the opportunity of working with you in the future on additional projects.
Technician Signature
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Project Summary Building Fire Smoke Combination Pass Fail Non-Accessible Total Dampers
206 13 9 0 19 0 3 22
GRAND TOTAL 13 9 0 19 0 3 22
Statistics Test Result % of Dampers
Pass 86.36%
Fail 0.00%
Non-Accessible / Decommissioned 13.64%
Type Total % of Dampers
Fire 13 59.10%
Smoke 9 40.90%
Combination 0 0.00%
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Togus VAMC Inspection Date: 10/06/2022 Inspected By: Lashawn Jones
All Dampers Date Floor Damper Number Damper
Type Damper Location
Inspection Result
Reason for Failure or Inaccessibility
10/06/2022 2 2-SD-001 Smoke Above hallway door by room 249 Pass
10/06/2022 2 2-SD-002 Smoke Inside confined space by room 214 Pass
10/06/2022 2 2-SD-003 Smoke Inside confined space by room 214 Pass
10/06/2022 2 2-SD-004 Smoke Inside confined space 249 Pass
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Above hallway door by room 249
Tag: 2-SD-001
Type: Smoke
Floor: 2
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/14926027222 https://www.gocanvas.com/values/14926027222 https://www.gocanvas.com/values/14926027223 https://www.gocanvas.com/values/14926027223
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside confined space by room 214
Tag: 2-SD-002
Type: Smoke
Floor: 2
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/14926027295 https://www.gocanvas.com/values/14926027295 https://www.gocanvas.com/values/14926027296 https://www.gocanvas.com/values/14926027296
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside confined space by room 214
Tag: 2-SD-003
Type: Smoke
Floor: 2
Status: Pass
Open Photo
Closed Photo https://www.gocanvas.com/values/14926027368 https://www.gocanvas.com/values/14926027368 https://www.gocanvas.com/values/14926027369 https://www.gocanvas.com/values/14926027369
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside confined space 249
Tag: 2-SD-004
Type: Smoke
Floor: 2
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/14926027441 https://www.gocanvas.com/values/14926027441 https://www.gocanvas.com/values/14926027442 https://www.gocanvas.com/values/14926027442
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Togus VAMC Inspection Date: 10/21/2022 Inspected By: Lashawn Jones Job ID: SB-062822-01-SS
FIRE & SMOKE DAMPER INSPECTION SERVICES
LSS Life Safety Services, LLC, in accordance with The National Fire Protection Association’s (NFPA) Standard 80 Chapter 19 and 105 Chapter 7 inspected fire and smoke dampers located in 206 during the period of 10/21/2022.
The following report and digital pictures provide the result of the inspection for the dampers that were inspected.
This report is intended to describe the location and operability of the dampers for the date in which LSS Life Safety Services’ representatives performed the inspection of the dampers, and is not intended to constitute any warranty as to the continued operation of any damper.
Thank you for contracting LSS Life Safety Services for this project and we look forward to the opportunity of
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Togus VAMC Inspection Date: 10/21/2022 Inspected By: Lashawn Jones
All Dampers Date Floor Damper Number Damper
Type Damper Location
Inspection Result
Reason for Failure or Inaccessibility
10/21/2022 2 2-FD-002 Fire Inside confined space hatch by stairs Pass
10/21/2022 2 2-FD-003 Fire Inside confined space hatch by stairs Pass
10/21/2022 2 2-FD-004 Fire Inside confined space hatch by stairs Pass
10/21/2022 2 2-FD-005 Fire Inside confined space hatch by stairs Pass
10/21/2022 2 2-FD-006 Fire Inside confined space hatch by stairs Pass
10/21/2022 2 2-FD-007 Fire Inside confined space hatch by stairs Pass
10/21/2022 2 2-FD-008 Fire Inside confined space hatch by stairs Pass
10/21/2022 2 2-FD-009 Fire Inside confined space hatch by stairs Pass
10/21/2022 2 2-SD-010 Smoke Inside room 211 above door Pass
10/21/2022 2 2-SD-011 Smoke Inside room 211 above door Pass
10/21/2022 Penthouse PH-FD-001 Fire Above elevator machine room Pass
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside confined space hatch by stairs
Tag: 2-FD-002
Type: Fire
Floor: 2
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15041696423 https://www.gocanvas.com/values/15041696423 https://www.gocanvas.com/values/15041696428 https://www.gocanvas.com/values/15041696428
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside confined space hatch by stairs
Tag: 2-FD-003
Type: Fire
Floor: 2
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15041696651 https://www.gocanvas.com/values/15041696651 https://www.gocanvas.com/values/15041696653 https://www.gocanvas.com/values/15041696653
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside confined space hatch by stairs
Tag: 2-FD-004
Type: Fire
Floor: 2
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15041696744 https://www.gocanvas.com/values/15041696744 https://www.gocanvas.com/values/15041696745 https://www.gocanvas.com/values/15041696745
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside confined space hatch by stairs
Tag: 2-FD-005
Type: Fire
Floor: 2
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15041696818 https://www.gocanvas.com/values/15041696818 https://www.gocanvas.com/values/15041696819 https://www.gocanvas.com/values/15041696819
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside confined space hatch by stairs
Tag: 2-FD-006
Type: Fire
Floor: 2
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15041696892 https://www.gocanvas.com/values/15041696892 https://www.gocanvas.com/values/15041696893 https://www.gocanvas.com/values/15041696893
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside confined space hatch by stairs
Tag: 2-FD-007
Type: Fire
Floor: 2
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15041696995 https://www.gocanvas.com/values/15041696995 https://www.gocanvas.com/values/15041696996 https://www.gocanvas.com/values/15041696996
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside confined space hatch by stairs
Tag: 2-FD-008
Type: Fire
Floor: 2
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15041697069 https://www.gocanvas.com/values/15041697069 https://www.gocanvas.com/values/15041697070 https://www.gocanvas.com/values/15041697070
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside confined space hatch by stairs
Tag: 2-FD-009
Type: Fire
Floor: 2
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15041697143 https://www.gocanvas.com/values/15041697143 https://www.gocanvas.com/values/15041697144 https://www.gocanvas.com/values/15041697144
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside room 211 above door
Tag: 2-SD-010
Type: Smoke
Floor: 2
Status: Pass
Open Photo
Closed Photo https://www.gocanvas.com/values/15041697217 https://www.gocanvas.com/values/15041697217 https://www.gocanvas.com/values/15041697218 https://www.gocanvas.com/values/15041697218
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside room 211 above door
Tag: 2-SD-011
Type: Smoke
Floor: 2
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15041697291 https://www.gocanvas.com/values/15041697291 https://www.gocanvas.com/values/15041697292 https://www.gocanvas.com/values/15041697292
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Above elevator machine room
Tag: PH-FD-001
Type: Fire
Floor: Penthouse
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15041697394 https://www.gocanvas.com/values/15041697394 https://www.gocanvas.com/values/15041697395 https://www.gocanvas.com/values/15041697395
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Togus VAMC Inspection Date: 10/26/2022 Inspected By: Lashawn Jones Job ID: SB-062822-01-SS
FIRE & SMOKE DAMPER INSPECTION SERVICES
LSS Life Safety Services, LLC, in accordance with The National Fire Protection Association’s (NFPA) Standard 80 Chapter 19 and 105 Chapter 7 inspected fire and smoke dampers located in 206 during the period of 10/26/2022.
The following report and digital pictures provide the result of the inspection for the dampers that were inspected.
This report is intended to describe the location and operability of the dampers for the date in which LSS Life Safety Services’ representatives performed the inspection of the dampers, and is not intended to constitute any warranty as to the continued operation of any damper.
Thank you for contracting LSS Life Safety Services for this project and we look forward to the opportunity of
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Togus VAMC Inspection Date: 10/26/2022 Inspected By: Lashawn Jones
All Dampers Date Floor Damper Number Damper
Type Damper Location
Inspection Result
Reason for Failure or Inaccessibility
10/26/2022 3 3-FD-001 Fire Inside chase by room 374 Pass
10/26/2022 3 3-FD-002 Fire Inside chase next to room 251 Non-Accessible No access door, access door install not authorized
10/26/2022 3 3-FD-003 Fire Inside chase next to room 251 Non-Accessible No access door, access door install not authorized
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside chase by room 374
Tag: 3-FD-001
Type: Fire
Floor: 3
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15070840477 https://www.gocanvas.com/values/15070840477 https://www.gocanvas.com/values/15070840479 https://www.gocanvas.com/values/15070840479
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside chase next to room 251
Tag: 3-FD-002
Type: Fire
Floor: 3
Status: Non-Accessible
Reason for Failure or Inaccessibility: No access door, access door install not authorized
Open Photo Closed Photo https://www.gocanvas.com/values/15070840715 https://www.gocanvas.com/values/15070840715 https://www.gocanvas.com/values/15070840719 https://www.gocanvas.com/values/15070840719
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside chase next to room 251
Tag: 3-FD-003
Type: Fire
Floor: 3
Status: Non-Accessible
Reason for Failure or Inaccessibility: No access door, access door install not authorized
Open Photo Closed Photo https://www.gocanvas.com/values/15070841089 https://www.gocanvas.com/values/15070841089 https://www.gocanvas.com/values/15070841093 https://www.gocanvas.com/values/15070841093
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Togus VAMC Inspection Date: 11/03/2022 Inspected By: Lashawn Jones Job ID: SB-062822-01-SS
FIRE & SMOKE DAMPER INSPECTION SERVICES
LSS Life Safety Services, LLC, in accordance with The National Fire Protection Association’s (NFPA) Standard 80 Chapter 19 and 105 Chapter 7 inspected fire and smoke dampers located in 206 during the period of 11/03/2022.
The following report and digital pictures provide the result of the inspection for the dampers that were inspected.
This report is intended to describe the location and operability of the dampers for the date in which LSS Life Safety Services’ representatives performed the inspection of the dampers, and is not intended to constitute any warranty as to the continued operation of any damper.
Thank you for contracting LSS Life Safety Services for this project and we look forward to the opportunity of
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Togus VAMC Inspection Date: 11/03/2022 Inspected By: Lashawn Jones
All Dampers Date Floor Damper Number Damper
Type Damper Location
Inspection Result
Reason for Failure or Inaccessibility
11/03/2022 1 1-SD-001 Smoke Above double door by room 111 Pass
11/03/2022 1 1-FD-002 Fire Inside men’s bathroom Non-Accessible No access door, access door install not authorized
11/03/2022 1 1-SD-003 Smoke Above double door near room 145 stairs side
Pass
11/03/2022 1 1-SD-004 Smoke Inside room 140 Pass
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Above double door by room 111
Tag: 1-SD-001
Type: Smoke
Floor: 1
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15153946220 https://www.gocanvas.com/values/15153946220 https://www.gocanvas.com/values/15153946221 https://www.gocanvas.com/values/15153946221
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside men’s bathroom
Tag: 1-FD-002
Type: Fire
Floor: 1
Status: Non-Accessible
Reason for Failure or Inaccessibility: No access door, access door install not authorized
Open Photo Closed Photo https://www.gocanvas.com/values/15153946345 https://www.gocanvas.com/values/15153946345 https://www.gocanvas.com/values/15153946346 https://www.gocanvas.com/values/15153946346
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Above double door near room 145 stairs side
Tag: 1-SD-003
Type: Smoke
Floor: 1
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15153946465 https://www.gocanvas.com/values/15153946465 https://www.gocanvas.com/values/15153946467 https://www.gocanvas.com/values/15153946467
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside room 140
Tag: 1-SD-004
Type: Smoke
Floor: 1
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15153946592 https://www.gocanvas.com/values/15153946592 https://www.gocanvas.com/values/15153946593 https://www.gocanvas.com/values/15153946593
908 South 8th Street Louisville, KY. 40203
888.675.4519 info@LifeSafetyServices.com
Damper Inspection Report Togus VAMC
11/03/2022 www.LifeSafetyServices.com
| 10_06_2022_206_10_11_2022_15_30_Damper_Inspection - 206 |
| 2 |
| 10_21_2022_206_10_23_2022_00_38_Damper_Inspection |
| 2 |
| Penthouse |
| 10_26_2022_206_10_26_2022_16_41_Damper_Inspection |
| 3 |
| 11_03_2022_206_11_03_2022_21_00_Damper_Inspection |
| 1 |