Attachment 7 - Togus VAMC Building 206 Damper Inspection Report - 20.pdf

PDF 4 MB Posted

Attached to
H341--Fire and Smoke Damper Inspection and Service Contract
Solicitation number
36C24126Q0052
Issued by

About this file

This document is a Damper Inspection Report from Life Safety Services (LSS) for the Togus Veterans Affairs Medical Center (VAMC), documenting fire and smoke damper inspections performed across multiple dates in Building 206 during October and November 2022.

The inspections were conducted in accordance with National Fire Protection Association (NFPA) Standards 80 and 105, covering floors 1, 2, 3, and the penthouse. Across these floors, a total of 22 dampers were assessed, including 13 fire dampers and 9 smoke dampers. Of these, 19 dampers passed inspection (86.36%), while 3 dampers (13.64%) were marked non-accessible due to lack of authorized access doors. The inspections were performed by technician Lashawn Jones on 10/06/2022, 10/21/2022, 10/26/2022, and 11/03/2022, with dampers located in various areas such as chases, rooms, stairwells, and mechanical spaces. The report includes detailed photographic documentation of each damper's open and closed status, along with specific location and inspection results.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

908 South 8th Street Louisville, KY. 40203

888.675.4519 info@LifeSafetyServices.com

Damper Inspection Report Togus VAMC - Building 206

10/06/2022 - 11/03/2022 www.LifeSafetyServices.com

DAMPER INSPECTION REPORT

Corporate Office 908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Facility: Togus VAMC Inspection Date: 10/06/2022 Inspected By: Lashawn Jones Job ID: SB-062822-01-SS

FIRE & SMOKE DAMPER INSPECTION SERVICES

LSS Life Safety Services, LLC, in accordance with The National Fire Protection Association’s (NFPA) Standard 80 Chapter 19 and 105 Chapter 7 inspected fire and smoke dampers located in 206 during the period of 10/06/2022.

The following report and digital pictures provide the result of the inspection for the dampers that were inspected.

This report is intended to describe the location and operability of the dampers for the date in which LSS Life Safety Services’ representatives performed the inspection of the dampers, and is not intended to constitute any warranty as to the continued operation of any damper.

Thank you for contracting LSS Life Safety Services for this project and we look forward to the opportunity of working with you in the future on additional projects.

Technician Signature

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Project Summary Building Fire Smoke Combination Pass Fail Non-Accessible Total Dampers

206 13 9 0 19 0 3 22

GRAND TOTAL 13 9 0 19 0 3 22

Statistics Test Result % of Dampers

Pass 86.36%

Fail 0.00%

Non-Accessible / Decommissioned 13.64%

Type Total % of Dampers

Fire 13 59.10%

Smoke 9 40.90%

Combination 0 0.00%

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Facility: Togus VAMC Inspection Date: 10/06/2022 Inspected By: Lashawn Jones

All Dampers Date Floor Damper Number Damper

Type Damper Location

Inspection Result

Reason for Failure or Inaccessibility

10/06/2022 2 2-SD-001 Smoke Above hallway door by room 249 Pass

10/06/2022 2 2-SD-002 Smoke Inside confined space by room 214 Pass

10/06/2022 2 2-SD-003 Smoke Inside confined space by room 214 Pass

10/06/2022 2 2-SD-004 Smoke Inside confined space 249 Pass

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Above hallway door by room 249

Tag: 2-SD-001

Type: Smoke

Floor: 2

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/14926027222 https://www.gocanvas.com/values/14926027222 https://www.gocanvas.com/values/14926027223 https://www.gocanvas.com/values/14926027223

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside confined space by room 214

Tag: 2-SD-002

Type: Smoke

Floor: 2

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/14926027295 https://www.gocanvas.com/values/14926027295 https://www.gocanvas.com/values/14926027296 https://www.gocanvas.com/values/14926027296

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside confined space by room 214

Tag: 2-SD-003

Type: Smoke

Floor: 2

Status: Pass

Open Photo

Closed Photo https://www.gocanvas.com/values/14926027368 https://www.gocanvas.com/values/14926027368 https://www.gocanvas.com/values/14926027369 https://www.gocanvas.com/values/14926027369

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside confined space 249

Tag: 2-SD-004

Type: Smoke

Floor: 2

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/14926027441 https://www.gocanvas.com/values/14926027441 https://www.gocanvas.com/values/14926027442 https://www.gocanvas.com/values/14926027442

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Facility: Togus VAMC Inspection Date: 10/21/2022 Inspected By: Lashawn Jones Job ID: SB-062822-01-SS

FIRE & SMOKE DAMPER INSPECTION SERVICES

LSS Life Safety Services, LLC, in accordance with The National Fire Protection Association’s (NFPA) Standard 80 Chapter 19 and 105 Chapter 7 inspected fire and smoke dampers located in 206 during the period of 10/21/2022.

The following report and digital pictures provide the result of the inspection for the dampers that were inspected.

This report is intended to describe the location and operability of the dampers for the date in which LSS Life Safety Services’ representatives performed the inspection of the dampers, and is not intended to constitute any warranty as to the continued operation of any damper.

Thank you for contracting LSS Life Safety Services for this project and we look forward to the opportunity of

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Facility: Togus VAMC Inspection Date: 10/21/2022 Inspected By: Lashawn Jones

All Dampers Date Floor Damper Number Damper

Type Damper Location

Inspection Result

Reason for Failure or Inaccessibility

10/21/2022 2 2-FD-002 Fire Inside confined space hatch by stairs Pass

10/21/2022 2 2-FD-003 Fire Inside confined space hatch by stairs Pass

10/21/2022 2 2-FD-004 Fire Inside confined space hatch by stairs Pass

10/21/2022 2 2-FD-005 Fire Inside confined space hatch by stairs Pass

10/21/2022 2 2-FD-006 Fire Inside confined space hatch by stairs Pass

10/21/2022 2 2-FD-007 Fire Inside confined space hatch by stairs Pass

10/21/2022 2 2-FD-008 Fire Inside confined space hatch by stairs Pass

10/21/2022 2 2-FD-009 Fire Inside confined space hatch by stairs Pass

10/21/2022 2 2-SD-010 Smoke Inside room 211 above door Pass

10/21/2022 2 2-SD-011 Smoke Inside room 211 above door Pass

10/21/2022 Penthouse PH-FD-001 Fire Above elevator machine room Pass

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside confined space hatch by stairs

Tag: 2-FD-002

Type: Fire

Floor: 2

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15041696423 https://www.gocanvas.com/values/15041696423 https://www.gocanvas.com/values/15041696428 https://www.gocanvas.com/values/15041696428

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside confined space hatch by stairs

Tag: 2-FD-003

Type: Fire

Floor: 2

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15041696651 https://www.gocanvas.com/values/15041696651 https://www.gocanvas.com/values/15041696653 https://www.gocanvas.com/values/15041696653

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside confined space hatch by stairs

Tag: 2-FD-004

Type: Fire

Floor: 2

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15041696744 https://www.gocanvas.com/values/15041696744 https://www.gocanvas.com/values/15041696745 https://www.gocanvas.com/values/15041696745

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside confined space hatch by stairs

Tag: 2-FD-005

Type: Fire

Floor: 2

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15041696818 https://www.gocanvas.com/values/15041696818 https://www.gocanvas.com/values/15041696819 https://www.gocanvas.com/values/15041696819

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside confined space hatch by stairs

Tag: 2-FD-006

Type: Fire

Floor: 2

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15041696892 https://www.gocanvas.com/values/15041696892 https://www.gocanvas.com/values/15041696893 https://www.gocanvas.com/values/15041696893

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside confined space hatch by stairs

Tag: 2-FD-007

Type: Fire

Floor: 2

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15041696995 https://www.gocanvas.com/values/15041696995 https://www.gocanvas.com/values/15041696996 https://www.gocanvas.com/values/15041696996

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside confined space hatch by stairs

Tag: 2-FD-008

Type: Fire

Floor: 2

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15041697069 https://www.gocanvas.com/values/15041697069 https://www.gocanvas.com/values/15041697070 https://www.gocanvas.com/values/15041697070

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside confined space hatch by stairs

Tag: 2-FD-009

Type: Fire

Floor: 2

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15041697143 https://www.gocanvas.com/values/15041697143 https://www.gocanvas.com/values/15041697144 https://www.gocanvas.com/values/15041697144

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside room 211 above door

Tag: 2-SD-010

Type: Smoke

Floor: 2

Status: Pass

Open Photo

Closed Photo https://www.gocanvas.com/values/15041697217 https://www.gocanvas.com/values/15041697217 https://www.gocanvas.com/values/15041697218 https://www.gocanvas.com/values/15041697218

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside room 211 above door

Tag: 2-SD-011

Type: Smoke

Floor: 2

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15041697291 https://www.gocanvas.com/values/15041697291 https://www.gocanvas.com/values/15041697292 https://www.gocanvas.com/values/15041697292

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Above elevator machine room

Tag: PH-FD-001

Type: Fire

Floor: Penthouse

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15041697394 https://www.gocanvas.com/values/15041697394 https://www.gocanvas.com/values/15041697395 https://www.gocanvas.com/values/15041697395

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Facility: Togus VAMC Inspection Date: 10/26/2022 Inspected By: Lashawn Jones Job ID: SB-062822-01-SS

FIRE & SMOKE DAMPER INSPECTION SERVICES

LSS Life Safety Services, LLC, in accordance with The National Fire Protection Association’s (NFPA) Standard 80 Chapter 19 and 105 Chapter 7 inspected fire and smoke dampers located in 206 during the period of 10/26/2022.

The following report and digital pictures provide the result of the inspection for the dampers that were inspected.

This report is intended to describe the location and operability of the dampers for the date in which LSS Life Safety Services’ representatives performed the inspection of the dampers, and is not intended to constitute any warranty as to the continued operation of any damper.

Thank you for contracting LSS Life Safety Services for this project and we look forward to the opportunity of

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Facility: Togus VAMC Inspection Date: 10/26/2022 Inspected By: Lashawn Jones

All Dampers Date Floor Damper Number Damper

Type Damper Location

Inspection Result

Reason for Failure or Inaccessibility

10/26/2022 3 3-FD-001 Fire Inside chase by room 374 Pass

10/26/2022 3 3-FD-002 Fire Inside chase next to room 251 Non-Accessible No access door, access door install not authorized

10/26/2022 3 3-FD-003 Fire Inside chase next to room 251 Non-Accessible No access door, access door install not authorized

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside chase by room 374

Tag: 3-FD-001

Type: Fire

Floor: 3

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15070840477 https://www.gocanvas.com/values/15070840477 https://www.gocanvas.com/values/15070840479 https://www.gocanvas.com/values/15070840479

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside chase next to room 251

Tag: 3-FD-002

Type: Fire

Floor: 3

Status: Non-Accessible

Reason for Failure or Inaccessibility: No access door, access door install not authorized

Open Photo Closed Photo https://www.gocanvas.com/values/15070840715 https://www.gocanvas.com/values/15070840715 https://www.gocanvas.com/values/15070840719 https://www.gocanvas.com/values/15070840719

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside chase next to room 251

Tag: 3-FD-003

Type: Fire

Floor: 3

Status: Non-Accessible

Reason for Failure or Inaccessibility: No access door, access door install not authorized

Open Photo Closed Photo https://www.gocanvas.com/values/15070841089 https://www.gocanvas.com/values/15070841089 https://www.gocanvas.com/values/15070841093 https://www.gocanvas.com/values/15070841093

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Facility: Togus VAMC Inspection Date: 11/03/2022 Inspected By: Lashawn Jones Job ID: SB-062822-01-SS

FIRE & SMOKE DAMPER INSPECTION SERVICES

LSS Life Safety Services, LLC, in accordance with The National Fire Protection Association’s (NFPA) Standard 80 Chapter 19 and 105 Chapter 7 inspected fire and smoke dampers located in 206 during the period of 11/03/2022.

The following report and digital pictures provide the result of the inspection for the dampers that were inspected.

This report is intended to describe the location and operability of the dampers for the date in which LSS Life Safety Services’ representatives performed the inspection of the dampers, and is not intended to constitute any warranty as to the continued operation of any damper.

Thank you for contracting LSS Life Safety Services for this project and we look forward to the opportunity of

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Facility: Togus VAMC Inspection Date: 11/03/2022 Inspected By: Lashawn Jones

All Dampers Date Floor Damper Number Damper

Type Damper Location

Inspection Result

Reason for Failure or Inaccessibility

11/03/2022 1 1-SD-001 Smoke Above double door by room 111 Pass

11/03/2022 1 1-FD-002 Fire Inside men’s bathroom Non-Accessible No access door, access door install not authorized

11/03/2022 1 1-SD-003 Smoke Above double door near room 145 stairs side

Pass

11/03/2022 1 1-SD-004 Smoke Inside room 140 Pass

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Above double door by room 111

Tag: 1-SD-001

Type: Smoke

Floor: 1

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15153946220 https://www.gocanvas.com/values/15153946220 https://www.gocanvas.com/values/15153946221 https://www.gocanvas.com/values/15153946221

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside men’s bathroom

Tag: 1-FD-002

Type: Fire

Floor: 1

Status: Non-Accessible

Reason for Failure or Inaccessibility: No access door, access door install not authorized

Open Photo Closed Photo https://www.gocanvas.com/values/15153946345 https://www.gocanvas.com/values/15153946345 https://www.gocanvas.com/values/15153946346 https://www.gocanvas.com/values/15153946346

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Above double door near room 145 stairs side

Tag: 1-SD-003

Type: Smoke

Floor: 1

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15153946465 https://www.gocanvas.com/values/15153946465 https://www.gocanvas.com/values/15153946467 https://www.gocanvas.com/values/15153946467

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside room 140

Tag: 1-SD-004

Type: Smoke

Floor: 1

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15153946592 https://www.gocanvas.com/values/15153946592 https://www.gocanvas.com/values/15153946593 https://www.gocanvas.com/values/15153946593

908 South 8th Street Louisville, KY. 40203

888.675.4519 info@LifeSafetyServices.com

Damper Inspection Report Togus VAMC

11/03/2022 www.LifeSafetyServices.com

10_06_2022_206_10_11_2022_15_30_Damper_Inspection - 206
2
10_21_2022_206_10_23_2022_00_38_Damper_Inspection
2
Penthouse
10_26_2022_206_10_26_2022_16_41_Damper_Inspection
3
11_03_2022_206_11_03_2022_21_00_Damper_Inspection
1

File details come from the government source that posted it. Updated .