Attachment 6 - Togus VAMC Building 205 Damper Inspection Report - 20.pdf

PDF 3 MB Posted

Attached to
H341--Fire and Smoke Damper Inspection and Service Contract
Solicitation number
36C24126Q0052
Issued by

About this file

This document is a Damper Inspection Report for the Togus Veterans Affairs Medical Center (VAMC) - Building 205, conducted by Life Safety Services (LSS) from 10/22/2022 to 11/03/2022. The inspection was performed in accordance with the National Fire Protection Association's (NFPA) Standard 80 Chapter 19 and 105 Chapter 7, focusing on fire and smoke dampers throughout the building.

The comprehensive report details the inspection of 11 total dampers across two floors (2nd and 3rd), with 8 fire dampers (72.73%) and 3 smoke dampers (27.27%). Of these, 9 dampers (81.82%) passed inspection, while 2 dampers (18.18%) were marked as non-accessible due to lack of authorized access doors. Specifically, on the 3rd floor, dampers 3-FD-008 and 3-FD-009 in room 300A were inaccessible because access door installation was not authorized. The inspection was conducted by technician Lashawn Jones, with the job ID SB-062822-01-SS, and included detailed photographic documentation of each damper's open and closed states.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

908 South 8th Street Louisville, KY. 40203

888.675.4519 info@LifeSafetyServices.com

Damper Inspection Report Togus VAMC - Building 205

10/22/2022 - 11/03/2022 www.LifeSafetyServices.com

DAMPER INSPECTION REPORT

Corporate Office 908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Facility: Togus VAMC Inspection Date: 10/22/2022 Inspected By: Lashawn Jones Job ID: SB-062822-01-SS

FIRE & SMOKE DAMPER INSPECTION SERVICES

LSS Life Safety Services, LLC, in accordance with The National Fire Protection Association’s (NFPA) Standard 80 Chapter 19 and 105 Chapter 7 inspected fire and smoke dampers located in 205 during the period of 10/22/2022.

The following report and digital pictures provide the result of the inspection for the dampers that were inspected.

This report is intended to describe the location and operability of the dampers for the date in which LSS Life Safety Services’ representatives performed the inspection of the dampers, and is not intended to constitute any warranty as to the continued operation of any damper.

Thank you for contracting LSS Life Safety Services for this project and we look forward to the opportunity of working with you in the future on additional projects.

Technician Signature

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Project Summary Building Fire Smoke Combination Pass Fail Non-Accessible Total Dampers

205 8 3 0 9 0 2 11

GRAND TOTAL 8 3 0 9 0 2 11

Statistics Test Result % of Dampers

Pass 81.82%

Fail 0.00%

Non-Accessible / Decommissioned 18.18%

Type Total % of Dampers

Fire 8 72.73%

Smoke 3 27.27%

Combination 0 0.00%

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Facility: Togus VAMC Inspection Date: 10/22/2022 Inspected By: Lashawn Jones

All Dampers Date Floor Damper Number Damper

Type Damper Location

Inspection Result

Reason for Failure or Inaccessibility

10/22/2022 2 2-FD-001 Fire Above door leading to room 200/203 by stairs case Pass

10/22/2022 2 2-SD-002 Smoke Above door leading to room 200/203 by stairs case Pass

10/22/2022 2 2-FD-003 Fire Above door by room 231 Pass

10/22/2022 2 2-SD-004 Fire Outside room 235 Pass

10/22/2022 3 3-FD-001 Fire Above corridor door by room 307 Pass

10/22/2022 3 3-SD-002 Smoke Above corridor door by room 307 Pass

10/22/2022 3 3-SD-003 Smoke Inside wall vent across from 307 Pass

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Above door leading to room 200/203 by stairs case

Tag: 2-FD-001

Type: Fire

Floor: 2

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15041704975 https://www.gocanvas.com/values/15041704975 https://www.gocanvas.com/values/15041704976 https://www.gocanvas.com/values/15041704976

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Above door leading to room 200/203 by stairs case

Tag: 2-SD-002

Type: Smoke

Floor: 2

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15041705049 https://www.gocanvas.com/values/15041705049 https://www.gocanvas.com/values/15041705050 https://www.gocanvas.com/values/15041705050

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Above door by room 231

Tag: 2-FD-003

Type: Fire

Floor: 2

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15041705163 https://www.gocanvas.com/values/15041705163 https://www.gocanvas.com/values/15041705165 https://www.gocanvas.com/values/15041705165

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Outside room 235

Tag: 2-SD-004

Type: Fire

Floor: 2

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15041705310 https://www.gocanvas.com/values/15041705310 https://www.gocanvas.com/values/15041705312 https://www.gocanvas.com/values/15041705312

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Above corridor door by room 307

Tag: 3-FD-001

Type: Fire

Floor: 3

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15041705452 https://www.gocanvas.com/values/15041705452 https://www.gocanvas.com/values/15041705454 https://www.gocanvas.com/values/15041705454

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Above corridor door by room 307

Tag: 3-SD-002

Type: Smoke

Floor: 3

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15041705570 https://www.gocanvas.com/values/15041705570 https://www.gocanvas.com/values/15041705572 https://www.gocanvas.com/values/15041705572

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside wall vent across from 307

Tag: 3-SD-003

Type: Smoke

Floor: 3

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15041705704 https://www.gocanvas.com/values/15041705704 https://www.gocanvas.com/values/15041705706 https://www.gocanvas.com/values/15041705706

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Facility: Togus VAMC Inspection Date: 11/03/2022 Inspected By: Lashawn Jones Job ID: SB-062822-01-SS

FIRE & SMOKE DAMPER INSPECTION SERVICES

LSS Life Safety Services, LLC, in accordance with The National Fire Protection Association’s (NFPA) Standard 80 Chapter 19 and 105 Chapter 7 inspected fire and smoke dampers located in 205 during the period of 11/03/2022.

The following report and digital pictures provide the result of the inspection for the dampers that were inspected.

This report is intended to describe the location and operability of the dampers for the date in which LSS Life Safety Services’ representatives performed the inspection of the dampers, and is not intended to constitute any warranty as to the continued operation of any damper.

Thank you for contracting LSS Life Safety Services for this project and we look forward to the opportunity of working with you in the future on additional projects.

Technician Signature

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Facility: Togus VAMC Inspection Date: 11/03/2022 Inspected By: Lashawn Jones

All Dampers Date Floor Damper Number Damper

Type Damper Location

Inspection Result

Reason for Failure or Inaccessibility

11/03/2022 3 3–FD-006 Fire Inside room 300A Pass

11/03/2022 3 3-FD-007 Fire Inside room 300A Pass

11/03/2022 3 3-FD-008 Fire Inside room 300A Non-Accessible No access door, access door install not authorized

11/03/2022 3 3-FD-009 Fire Inside room 300A Non-Accessible No access door, access door install not authorized

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside room 300A

Tag: 3–FD-006

Type: Fire

Floor: 3

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15131594030 https://www.gocanvas.com/values/15131594030 https://www.gocanvas.com/values/15131594032 https://www.gocanvas.com/values/15131594032

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside room 300A

Tag: 3-FD-007

Type: Fire

Floor: 3

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/15131594190 https://www.gocanvas.com/values/15131594190 https://www.gocanvas.com/values/15131594194 https://www.gocanvas.com/values/15131594194

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside room 300A

Tag: 3-FD-008

Type: Fire

Floor: 3

Status: Non-Accessible

Reason for Failure or Inaccessibility: No access door, access door install not authorized

Open Photo Closed Photo https://www.gocanvas.com/values/15131594418 https://www.gocanvas.com/values/15131594418 https://www.gocanvas.com/values/15131594421 https://www.gocanvas.com/values/15131594421

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside room 300A

Tag: 3-FD-009

Type: Fire

Floor: 3

Status: Non-Accessible

Reason for Failure or Inaccessibility: No access door, access door install not authorized

Open Photo Closed Photo https://www.gocanvas.com/values/15131594709 https://www.gocanvas.com/values/15131594709 https://www.gocanvas.com/values/15131594711 https://www.gocanvas.com/values/15131594711

908 South 8th Street Louisville, KY. 40203

888.675.4519 info@LifeSafetyServices.com

Damper Inspection Report Togus VAMC - Building 205

10/22/2022 - 11/03/2022 www.LifeSafetyServices.com

10_22_2022_205_10_23_2022_00_41_Damper_Inspection
2
3
11_03_2022_205_11_03_2022_09_55_Damper_Inspection
3