Attachment 6 - Togus VAMC Building 205 Damper Inspection Report - 20.pdf
PDF 3 MB Posted
- Solicitation number
- 36C24126Q0052
About this file
This document is a Damper Inspection Report for the Togus Veterans Affairs Medical Center (VAMC) - Building 205, conducted by Life Safety Services (LSS) from 10/22/2022 to 11/03/2022. The inspection was performed in accordance with the National Fire Protection Association's (NFPA) Standard 80 Chapter 19 and 105 Chapter 7, focusing on fire and smoke dampers throughout the building.
The comprehensive report details the inspection of 11 total dampers across two floors (2nd and 3rd), with 8 fire dampers (72.73%) and 3 smoke dampers (27.27%). Of these, 9 dampers (81.82%) passed inspection, while 2 dampers (18.18%) were marked as non-accessible due to lack of authorized access doors. Specifically, on the 3rd floor, dampers 3-FD-008 and 3-FD-009 in room 300A were inaccessible because access door installation was not authorized. The inspection was conducted by technician Lashawn Jones, with the job ID SB-062822-01-SS, and included detailed photographic documentation of each damper's open and closed states.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
908 South 8th Street Louisville, KY. 40203
888.675.4519 info@LifeSafetyServices.com
Damper Inspection Report Togus VAMC - Building 205
10/22/2022 - 11/03/2022 www.LifeSafetyServices.com
DAMPER INSPECTION REPORT
Corporate Office 908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Togus VAMC Inspection Date: 10/22/2022 Inspected By: Lashawn Jones Job ID: SB-062822-01-SS
FIRE & SMOKE DAMPER INSPECTION SERVICES
LSS Life Safety Services, LLC, in accordance with The National Fire Protection Association’s (NFPA) Standard 80 Chapter 19 and 105 Chapter 7 inspected fire and smoke dampers located in 205 during the period of 10/22/2022.
The following report and digital pictures provide the result of the inspection for the dampers that were inspected.
This report is intended to describe the location and operability of the dampers for the date in which LSS Life Safety Services’ representatives performed the inspection of the dampers, and is not intended to constitute any warranty as to the continued operation of any damper.
Thank you for contracting LSS Life Safety Services for this project and we look forward to the opportunity of working with you in the future on additional projects.
Technician Signature
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Project Summary Building Fire Smoke Combination Pass Fail Non-Accessible Total Dampers
205 8 3 0 9 0 2 11
GRAND TOTAL 8 3 0 9 0 2 11
Statistics Test Result % of Dampers
Pass 81.82%
Fail 0.00%
Non-Accessible / Decommissioned 18.18%
Type Total % of Dampers
Fire 8 72.73%
Smoke 3 27.27%
Combination 0 0.00%
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Togus VAMC Inspection Date: 10/22/2022 Inspected By: Lashawn Jones
All Dampers Date Floor Damper Number Damper
Type Damper Location
Inspection Result
Reason for Failure or Inaccessibility
10/22/2022 2 2-FD-001 Fire Above door leading to room 200/203 by stairs case Pass
10/22/2022 2 2-SD-002 Smoke Above door leading to room 200/203 by stairs case Pass
10/22/2022 2 2-FD-003 Fire Above door by room 231 Pass
10/22/2022 2 2-SD-004 Fire Outside room 235 Pass
10/22/2022 3 3-FD-001 Fire Above corridor door by room 307 Pass
10/22/2022 3 3-SD-002 Smoke Above corridor door by room 307 Pass
10/22/2022 3 3-SD-003 Smoke Inside wall vent across from 307 Pass
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Above door leading to room 200/203 by stairs case
Tag: 2-FD-001
Type: Fire
Floor: 2
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15041704975 https://www.gocanvas.com/values/15041704975 https://www.gocanvas.com/values/15041704976 https://www.gocanvas.com/values/15041704976
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Above door leading to room 200/203 by stairs case
Tag: 2-SD-002
Type: Smoke
Floor: 2
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15041705049 https://www.gocanvas.com/values/15041705049 https://www.gocanvas.com/values/15041705050 https://www.gocanvas.com/values/15041705050
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Above door by room 231
Tag: 2-FD-003
Type: Fire
Floor: 2
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15041705163 https://www.gocanvas.com/values/15041705163 https://www.gocanvas.com/values/15041705165 https://www.gocanvas.com/values/15041705165
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Outside room 235
Tag: 2-SD-004
Type: Fire
Floor: 2
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15041705310 https://www.gocanvas.com/values/15041705310 https://www.gocanvas.com/values/15041705312 https://www.gocanvas.com/values/15041705312
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Above corridor door by room 307
Tag: 3-FD-001
Type: Fire
Floor: 3
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15041705452 https://www.gocanvas.com/values/15041705452 https://www.gocanvas.com/values/15041705454 https://www.gocanvas.com/values/15041705454
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Above corridor door by room 307
Tag: 3-SD-002
Type: Smoke
Floor: 3
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15041705570 https://www.gocanvas.com/values/15041705570 https://www.gocanvas.com/values/15041705572 https://www.gocanvas.com/values/15041705572
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside wall vent across from 307
Tag: 3-SD-003
Type: Smoke
Floor: 3
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15041705704 https://www.gocanvas.com/values/15041705704 https://www.gocanvas.com/values/15041705706 https://www.gocanvas.com/values/15041705706
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Togus VAMC Inspection Date: 11/03/2022 Inspected By: Lashawn Jones Job ID: SB-062822-01-SS
FIRE & SMOKE DAMPER INSPECTION SERVICES
LSS Life Safety Services, LLC, in accordance with The National Fire Protection Association’s (NFPA) Standard 80 Chapter 19 and 105 Chapter 7 inspected fire and smoke dampers located in 205 during the period of 11/03/2022.
The following report and digital pictures provide the result of the inspection for the dampers that were inspected.
This report is intended to describe the location and operability of the dampers for the date in which LSS Life Safety Services’ representatives performed the inspection of the dampers, and is not intended to constitute any warranty as to the continued operation of any damper.
Thank you for contracting LSS Life Safety Services for this project and we look forward to the opportunity of working with you in the future on additional projects.
Technician Signature
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Togus VAMC Inspection Date: 11/03/2022 Inspected By: Lashawn Jones
All Dampers Date Floor Damper Number Damper
Type Damper Location
Inspection Result
Reason for Failure or Inaccessibility
11/03/2022 3 3–FD-006 Fire Inside room 300A Pass
11/03/2022 3 3-FD-007 Fire Inside room 300A Pass
11/03/2022 3 3-FD-008 Fire Inside room 300A Non-Accessible No access door, access door install not authorized
11/03/2022 3 3-FD-009 Fire Inside room 300A Non-Accessible No access door, access door install not authorized
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside room 300A
Tag: 3–FD-006
Type: Fire
Floor: 3
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15131594030 https://www.gocanvas.com/values/15131594030 https://www.gocanvas.com/values/15131594032 https://www.gocanvas.com/values/15131594032
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside room 300A
Tag: 3-FD-007
Type: Fire
Floor: 3
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/15131594190 https://www.gocanvas.com/values/15131594190 https://www.gocanvas.com/values/15131594194 https://www.gocanvas.com/values/15131594194
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside room 300A
Tag: 3-FD-008
Type: Fire
Floor: 3
Status: Non-Accessible
Reason for Failure or Inaccessibility: No access door, access door install not authorized
Open Photo Closed Photo https://www.gocanvas.com/values/15131594418 https://www.gocanvas.com/values/15131594418 https://www.gocanvas.com/values/15131594421 https://www.gocanvas.com/values/15131594421
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside room 300A
Tag: 3-FD-009
Type: Fire
Floor: 3
Status: Non-Accessible
Reason for Failure or Inaccessibility: No access door, access door install not authorized
Open Photo Closed Photo https://www.gocanvas.com/values/15131594709 https://www.gocanvas.com/values/15131594709 https://www.gocanvas.com/values/15131594711 https://www.gocanvas.com/values/15131594711
908 South 8th Street Louisville, KY. 40203
888.675.4519 info@LifeSafetyServices.com
Damper Inspection Report Togus VAMC - Building 205
10/22/2022 - 11/03/2022 www.LifeSafetyServices.com
| 10_22_2022_205_10_23_2022_00_41_Damper_Inspection |
| 2 |
| 3 |
| 11_03_2022_205_11_03_2022_09_55_Damper_Inspection |
| 3 |
File details come from the government source that posted it. Updated .