ATTACHMENT 8 - Drawings 4 of 6 - Structural.pdf
PDF 4 MB Posted
- Attached to
- Y1DZ--Construct CLC Cottage (Minor) - Sioux Falls Federal contract opportunity
- Solicitation number
- 36C77621B0016
About this file
This solicitation is for the construction of a new 11,115 square foot Hospice Cottage located on the campus of the Sioux Falls VA Medical Center. The contractor shall demolish any existing structures, prepare the site for construction, and furnish all labor and materials to build the new facility in accordance with the attached drawings and specifications. The Department of Veterans Affairs Technology Acquisition Center in Austin is the contracting agency. The solicitation includes requirements for site work, demolition, and construction of the new hospice building to house veterans receiving end-of-life care. The response date and anticipated award date are not provided in the document.
View the file
Other files for this federal contract opportunity
Show all 24
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Drawing Title
Approved:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
TSA PROJECT
NO.:
Department of Veterans Affairs
CONSTRUCT CLC COTTAGE
- HOSPICE
438-420
SIOUX FALLS, SD
06/30/2021
STRUCTURAL INFO SHEET
KMW MJN
KMW
S-000
43 90 06054.034
TRUE
NORTH
PLAN
NORTH
NORTH
NORTH
ARROW
NAME
ELEVATIONLEVEL
MATCHLINE
AREA A
AREA B
TITLE
MARKER 1
VIEW NAME
SCALE: 1/8" = 1'-0"
EXISTING
COLUMN
NEW
COLUMN
X
X
X
XX-XX
SIM
X
XX-XX
X
SECTION/
DETAIL
PLAN
DETAIL
REFERENCE
NOTE
CIP WALL
CALLOUT
WALL FOOTING
CALLOUTS
LETTER
INDICATES NEW
COLUMN LINE
LETTER INDICATES
EXISTING COLUMN
LINE
SECTION/DETAIL NUMBER
SHEET NUMBER
INDICATES DIRECTION OF VIEW
DETAIL NUMBER
SHEET NUMBER
REFERENCE
DESIGNATION
SYMBOL LEGEND
ROOM /
FRAMING
ELEVATION
EXTERIOR
ELEVATION
XX-XX
XX-XX
ELEVATION LETTER
DIRECTION OF VIEW
SHEET NUMBER
ELEVATION LETTER
DIRECTION OF VIEW
SHEET NUMBER
SHEAR WALL
CALLOUT
CMU WALL
CALLOUT
METAL STUD
WALL CALLOUT
DETAIL NUMBER
LEVEL CALLOUT
DESIGNATION
ELEVATION
DESIGNATION
GRAPHIC AREA FOR
DRAWING
TITLE
SCALE OF THE DRAWING
ABBREVIATIONS
REF. NOTES ( )REFERENCE LEGEND
PLAN VIEW
SECTION / ELEVATION VIEW
SHEAR WALL
MASONRY-CMU
MASONRY-VENEER
STUD WALL
CONCRETE
GRAVEL
EARTH / COMPACTED
EARTH / NONCOMPACTED
RIGID INSULATION
JOINT FILLER
STEEL
GYPSUM
FLEXIBLE INSULATION
GROUT
PLYWOOD
WOOD (FINISH)
MASONRY-CMU FACE
MASONRY-CMU
MASONRY-VENEER
PAD FOOTING
CALLOUTS
REFERENCE
DESIGNATION
FX-X
CONTINUOUS FOOTING
DESIGNATION
CFX-X
GBX-X
TSX-X
GRADE BEAM DESIGNATION
THICKENED SLAB
DESIGNATION
SHEAR WALL TYPE 'X'
MIN L = X'-X"
SHEAR WALL TYPE
DESIGNATION
SHEAR WALL LENGTH
HEADER CALLOUT
IN STUD WALL
LINTEL CALLOUT
IN MASONRY WALL
LETTER INDICATES
CMU WALL TYPE
LETTER INDICATES
CIP WALL TYPE
LETTER INDICATES
METAL STUD WALL
TYPE
LINTEL DESIGNATIONL-X
HEADER DESIGNATIONH-X
X
X
X
STRUCTURAL SHEET LIST
PROJECT STRUCTURAL REFERENCED NOTES
XSCHEDULES
RD ROOF DRAIN
REF REFERENCE
REINF REINFORCEMENT
REQD REQUIRED
RTU ROOF TOP UNIT
SCHED SCHEDULE
SDI STEEL DECK INSTITUTE
SF SQUARE FOOT (FEET)
SHTG SHEATHING
SIM SIMILAR
SJI STEEL JOIST INSTITUTE
SL SNOW LOAD
SLBB SHORT LEG BACK TO BACK
SPEC SPECIFICATIONS
SS STAINLESS STEEL
STD STANDARD
STGR STRINGER
STIFF STIFFENER
STIRR STIRRUPS
STL STEEL
STR STRUCTURAL
SUSP SUSPENDED
TEMP TEMPERATURE
TO TOP OF
TOB TOP OF BEAM
TOC TOP OF CONCRETE
TOF TOP OF FOOTING
TOS TOP OF STEEL
TOW TOP OF WALL
TRANS TRANSVERSE
TYP TYPICAL
UNEX UNEXCAVATED
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
VEST VESTIBULE
W WIDE (WIDTH)
W/ WITH
W/O WITHOUT
WF WIDE FLANGE
WL WIND LOAD
WP WORK POINT
WT WEIGHT
WWF WELDED WIRE FABRIC
AB ANCHOR BOLT
ACI AMERICAN CONCRETE
INSTITUTE
AFF ABOVE FINISH FLOOR
AGG AGGREGATE
AISC AMERICAN INSTITUTE OF
STEEL CONSTRUCTION
AL ALUMINUM
ANCH ANCHOR
ANSI AMERICAN NATIONAL
STANDARDS INSTITUTE
APPD APPROVED
APPROX APPROXIMATE
ARCH ARCHITECTURAL OR
ARCHITECT
AUTO AUTOMATIC
AVG AVERAGE
L ANGLE
BL BUILDING LINE
BLDG BUILDING
BLKG BLOCKING
BO BOTTOM OF
BOT BOTTOM
BRCG BRACING
BRDG BRIDGING
BRG BEARING
BS BOTH SIDES
BW BOTH WAYS
C CHANNEL (STRUCTURAL
SHEETS)
CF CUBIC FEET
CIP CAST IN PLACE
CJ CONTROL JOINT
CL CENTER LINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
COMP COMPRESSIBLE
CONC CONCRETE
CONN CONNECTION
CONSTR
JT
CONSTRUCTION JOINT
CONT CONTINUOUS
(CONTINUATION)
CU YD CUBIC YARDS
D DEPTH (DEEP)
d PENNY (as in nail - 10d)
DBL DOUBLE
DEMO DEMOLITION
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DL DEAD LOAD
DWG DRAWING
DWLS DOWELS
EF EACH FACE
EJ EXPANSION JOINT
EL ELEVATION - GRADE OR
BUILDING
ELEV ELEVATOR
EQ EQUAL
EQUIP EQUIPMENT
EW EACH WAY
EXIST EXISTING
EXPN EXPANSION
EXT EXTERIOR
F FAHRENHEIT
FD FLOOR DRAIN
FDN FOUNDATION
FIN FINISH
FLR FLOOR
FT FEET (FOOT)
FTG FOOTING
FV FIELD VERIFY
GA GAGE OR GAUGE
GALV GALVANIZED
GRTG GRATING
GWB GYPSUM WALLBOARD
H or HT HEIGHT (HIGH)
HDR HEADER
HK HOOK
HORIZ HORIZONTAL(LY)
HPT HIGH POINT
HS HIGH STRENGTH
ID INSIDE DIAMETER
IN INCH
INSUL INSULATION
INT INTERIOR
KIP or K KILOPOUND (1000 LBS)
KP KICK PLATE
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MC MISCELLANEOUS
CHANNELS
MECH MECHANICAL
MET METAL
MFG MANUFACTURING
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
NIC NOT IN CONTRACT
NO NUMBER
NR NOT REQUIRED
NTS NOT TO SCALE
OC ON CENTER(S)
OCEW ON CENTER EACH WAY
OD OUTSIDE DIAMETER
OH OVERHEAD
OPNG OPENING
OPP OPPOSITE
OZ OUNCE
PC PRECAST
PERF PERFORATED
PLWD PLYWOOD
POL POLISH(ED)
PREFAB PREFABRICATED
PS PRESSED STEEL
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
QTY QUANTITY
R RADIUS
L LENGTH (LONG)
LBS POUNDS
LDG LOADING
LL LIVE LOAD
LLBB LONG LEG BACK TO BACK
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LNTL LINTEL
LONG LONG LONGITUDINAL
LP LOW POINT
LT WT LIGHT WEIGHT
1 STRUCTURAL STOOP - SEE SHEET SB501 FOR
TYPICAL DETAIL. REFERENCE ARCHITECTURAL
DRAWINGS FOR STOOP DIMENSIONS.
2 'C.J.' INDICATES CONTROL JOINT - SEE TYPICAL
DETAIL ON SHEET SB501 AND STRUCTURAL
NOTES ON SHEET S-001 FOR MORE INFORMATION.
3 PROVIDE (2) #4 X 3'-0"-LONG BARS @ 4" O.C.
CENTERED IN SLAB AT ALL RE-ENTRANT
CORNERS WITHOUT CONTROL JOINTS (C.J.) AND
AT ENDS OF CONTROL JOINTS TERMINATED
WITHIN SLAB - TYPICAL.
4 SHEAR WALL TYPE 'A' - MIN. L = 6'-0"
5 4 1/2" CONCRETE W/ 6X6 W2.9XW2.9 W.W.F. OVER
1 1/2" TYPE 'C' 20 GAUGE NON-COMPOSITE METAL
DECK, TYPICAL (6" TOTAL THICKNESS) - SEE
METAL DECK SCHEDULE ON SHEET S-000 FOR
MORE INFORMATION.
6 SYMBOL INDICATES MOMENT CONNECTION -
TYPICAL. REFERENCE DETAIL 7/SF502.
7 LIGHT GAUGE STEEL ROOF TRUSSES @ 24" O.C.
8 LIGHT GAUGE CEE OUTRIGGERS @ 24" O.C.
9 LIGHT GAUGE CEE-STUD GABLE FRAME ABOVE
STUD WALL OR STEEL BEAM AS OCCURS. BRACE
TO ROOF STRUCTURE AS SHOWN IN DETAILS.
10 1" TYPE 'E' 26 GAUGE METAL ROOF DECK, TYPICAL
(U.N.O.) - SEE METAL DECK SCHEDULE ON SHEET
S-000 FOR MORE INFORMATION.
11 LIGHT GAUGE STEEL OVER FRAMING TRUSSES @
24" O.C.
12 PROVIDE (2) 600S162 12 GA. (50 KSI) STUDS
BELOW TRUSS GIRDER BEARING - TYPICAL
13 PROVIDE 1 1/8" THICK BASE PLATE W/ 1" DIAMETER
ANCHOR BOLTS @ THIS COLUMN - TYPICAL @
MOMENT FRAMES
15 SLEEVE THRU GRADE BEAM FOR UTILITIES AS
REQUIRED. REFERENCE TYPICAL DETAIL 8/SB501.
16 PROVIDE 3/4"-THICK CEMDECK (OR EQUAL) OVER
BOTTOM CHORD OF LIGHT GAUGE TRUSSES.
SCREW INTO TRUSS BOTTOM CHORD @ 12" ON
CENTER. PROVIDE LIGHT GAUGE STUD FRAMING
AS REQUIRED TO BOX OUT AROUND DUCT
PENETRATIONS (COORDINATE W/ MECH.). TRUSS
BOTTOM CHORDS SHALL BE DESIGNED FOR A
LIVE LOAD OF 20 PSF.
17 3" CONCRETE W/ #3 BARS @ 12" O.C. OVER 2"
TYPE 'C' 16 GAUGE NON-COMPOSITE METAL DECK,
TYPICAL (U.N.O.) - SEE METAL DECK SCHEDULE
ON SHEET S-000 FOR MORE INFORMATION.
18 FLOOR DRAIN - SEE MECH. AND SEE ARCH FOR
FLOOR SLOPE.
19 SYMBOL INDICATES FOOTING STEP - SEE TYPICAL
DETAIL 9/SB501.
20 MECHANICAL DUCTBANK - SEE MECH & SEE
DETAILS 5 & 12 ON SB502 FOR CONDITIONS AT
EXISTING BUILDINGS.
21 2 1/2" CONCRETE W/ 6X6 W2.9XW2.9 W.W.F. OVER
1 1/2" TYPE 'C' 20 GAUGE NON-COMPOSITE METAL
DECK, TYPICAL (U.N.O.) - SEE METAL DECK
SCHEDULE ON SHEET S-000 FOR MORE
INFORMATION.
22 TORIS 4A 18 GA. ROOF DECK - SEE METAL DECK
SCHEDULE ON SHEET S-000 FOR MORE
INFORMATION.
23 TORIS 5.5 18 GA. ROOF DECK - SEE METAL DECK
SCHEDULE ON SHEET S-000 FOR MORE
INFORMATION.
24 WOOD TRUSS MANUFACTURER TO PROVIDE 16X12
OPENING FOR MECHANICAL DUCT
25 8 1/2" CONCRETE W/ #4 BARS @ 12" O.C. EA. WAY
OVER 1 1/2" TYPE 'C' 20 GAUGE NON-COMPOSITE
METAL DECK, TYPICAL (10" TOTAL THICKNESS) -
SEE METAL DECK SCHEDULE ON SHEET S-000 FOR
MORE INFORMATION.
S-000 STRUCTURAL INFO SHEET
S-001 STRUCTURAL NOTES
S-002 SPECIAL INSPECTIONS
SB101 FOUNDATION PLAN
SB501 TYPICAL FOUNDATION DETAILS
SB502 FOUNDATION DETAILS
SF101 ATTIC FRAMING PLAN
SF102 ROOF FRAMING PLAN
SF501 TYPICAL FRAMING DETAILS
SF502 TYPICAL FRAMING DETAILS
SF503 FRAMING DETAILS
SF504 FRAMING DETAILS
SF505 FRAMING DETAILS
METAL STUD WALL SCHEDULE
MARK MATERIAL GAUGE
MIN. YEILD
STRENGTH SPACING NOTES
A 600S162 16 50 KSI 12" TYPICAL LOAD BEARING WALLS & EXTERIOR WALLS
TYP. SEE ARCH. SEE ARCH. SEE ARCH. SEE ARCH. TYPICAL NON-LOAD BEARING WALLS
GRADE BEAM SCHEDULE
MARK WIDTH DEPTH LONGITUDINAL REINFORCING STIRRUPS
GB1-6 1' - 6" 4' - 10" (3) #5 BARS BOT., (3) #5 BARS TOP #4 @ 24" O.C.
GB2-0 2' - 0" 4' - 10" (5) #5 BARS BOT., (5) #5 BARS TOP #4 @ 24" O.C.
GB2-6 2' - 6" 4' - 10" (6) #5 BARS BOT., (6) #5 BARS TOP #4 @ 12" O.C.
PAD FOOTING SCHEDULE
MARK PLAN SIZE DEPTH REINFORCING
F3.0B 3'-0" X 3'-0" 4' - 10" (5) #6 BARS EACH WAY, TOP & BOTTOM
F3.5 3'-6" X 3'-6" 4' - 10" (5) #6 BARS EACH WAY, TOP & BOTTOM
F4.0 4'-0" X 4'-0" 4' - 10" (5) #5 BARS EACH WAY, BOTTOM
F5.0 5'-0" X 5'-0" 4' - 10" (8) #6 BARS EACH WAY, TOP & BOTTOM
F6.0 6'-0" X 6'-0" 1' - 6" (7) #6 BARS EACH WAY, BOTTOM
THICKENED SLAB SCHEDULE
MARK WIDTH DEPTH REINFORCING
TS1-6 1' - 6" 1' - 0" (3) #5 BARS LONG. BOT
METAL DECKING SCHEDULE
LOCATION DEPTH
(IN.) GAUGE MIN. I MIN. S FINISH CONNECTION TO SUPPORTING MEMBERS SIDE LAPS
(#10 SCREWS, U.N.O.) REMARKS
ROOF 1 26 0.040 0.067 GALVANIZED 36/4 PATTERN (#12 TEK SCREWS) (1) SIDE LAP FASTENER EACH SPACE
BETWEEN SUPPORT MEMBERS TYPE "E"
ATTIC FLOOR 1 1/2 20 0.186 0.224 GALVANIZED 36/4 PATTERN (5/8" DIA. PUDDLE WELD) (1) SIDE LAP FASTENER EACH SPACE
BETWEEN SUPPORT MEMBERS TYPE "C"
ENTRANCE ROOF 4 18 3.42 1.24 GALVANIZED & NATACOAT 24/6 PATTERN (3/4" ARC PUDDLE WELD) 1 1/2" FILLET WELD @ 24" O.C. TORIS 4CA CAR PORT ROOF 5 1/2" 16 10.93 2.77 GALVANIZED & NATACOAT 24/6 PATTERN (3/4" ARC PUDDLE WELD) 1 1/2" FILLET WELD @ 24" O.C. TORIS 5.5
PATIO STOOP 2 16 0.704 0.653 GALVANIZED 36/4 PATTERN (#12 TEK SCREWS) (1) SIDE LAP FASTENER EACH SPACE
BETWEEN SUPPORT MEMBERS TYPE "C"
SINGLE ANGLE LINTEL SCHEDULE
LINTEL CLEAR
SPAN LINTEL SIZE LINTEL MINIMUM END
BEARING
3 L4X4X1/4 4" 4 L4X4X1/4 4" 5 L4X4X5/16 4" 6 L4X4X3/8 8" 7 L4X4X3/8 8" 8 L6X4X3/8 8"
METAL STUD HEADER SCHEDULE
MARK MATERIAL GAUGE MIN YIELD
STRENGTH
# OF KING
STUDS
# OF JACK
STUDS
#10 SCREWS INTO
KING STUD LEDGER ANGLE
H-1 600S162 18 33 KSI 1 1 4 SEE SCHEDULE
H-2 800S162 16 50 KSI 2 2 4 SEE SCHEDULE
H-3 1000S162 14 50 KSI 2 2 6 SEE SCHEDULE
H-4 1200S162 12 50 KSI 3 3 8 SEE SCHEDULE
SHEAR WALL SCHEDULE
MARK SHEATHING EDGE
ATTACH
FIELD
ATTACH
HOLDDOWN
ANCHOR NOTES
A 5/8" DENS-GLASS OR
5/8" GWB EACH FACE #6 @ 4" #6 @ 12" HD8 18 GAUGE DOUBLE STUDS EACH END
NOTES:
- INSTALL HEADERS PER SCHEDULE ABOVE IN LOAD BEARING EXTERIOR METAL STUD WALLS
- HEADER 'H-1' SHALL BE USED FOR CLEAR SPANS LESS THAN 4'-0"
- HEADER 'H-2' SHALL BE USED FOR CLEAR SPANS GREATER THAN OR EQUAL TO 4'-0" & LESS THAN 7'-0"
- HEADER 'H-3' SHALL BE USED FOR CLEAR SPANS GREATER THAN OR EQUAL TO 7'-0" & LESS THAN 10'-0"
- HEADER 'H-4' SHALL BE USED FOR CLEAR SPANS GREATER THAN OR EQUAL TO 10'-0" & LESS THAN 14'-0"
- CONTACT ENGINEER OF RECORD FOR ANY CLEAR SPANS IN EXCESS OF 14'-0"
- KING AND JACK STUDS SHALL BE 12 GA.
CONT. FOOTING SCHEDULE
MARK WIDTH DEPTH REINFORCING
CF2-0 2' - 0" 1' - 0" (3) #5 BARS LONG. BOT
MASONRY LINTEL SCHEDULE
MARK BEARING REINFORCING
L-1 8" 16" BOND BEAM W/ (2) #5 CONT. @ BOT.
MASONRY WALL REINF. SCHEDULE
MARK WIDTH
REINFORCING
VERTICAL HORIZONTAL
TYP. 0' - 8" #5 @ 32" O.C. MAX. LADDER TYPE - 2 - W1.7 WIRES @ 16" O.C.
*TORIS DECK TYPE IS AN EPIC METALS PRODUCT, CONTRACTOR OPTION TO SUBMIT EQUIVALENT PRODUCT FROM ANOTHER MANUFACTURER FOR APPROVAL
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
TSA PROJECT
NO.:
Department of Veterans Affairs
CONSTRUCT CLC COTTAGE
- HOSPICE
438-420
SIOUX FALLS, SD
06/30/2021
STRUCTURAL NOTES
KMW MJN
KMW
S-001
44 90 06054.034
APPLICABLE CODES AND STANDARDS
1. 2018 INTERNATIONAL BUILDING CODE
2. ACI 318-14 - BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE
3. TMS 402-2016 - BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES
4. AISC 360-16 - SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS
5. AISI S100-16 - NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF COLD-
FORMED STEEL STRUCTURAL MEMBERS
DESIGN CRITERIA
FLOOR LIVE LOAD PSF
1. CORRIDORS - FIRST FLOOR 100
2. DINNING AREA 100
3. OFFICE BUILDINGS - OFFICES 50
4. RESIDENTIAL - PRIVATE ROOMS 40
5. RESIDENTIAL - PUBLIC ROOMS 100
6. RESIDENTIAL - CORRIDORS - SAME AS AREA SERVED ---
7. SIDEWALKS, VEHICULAR DRIVEWAYS 250
8. STAIRS AND EXIT WAYS 100
9. STORAGE - LIGHT 125
ROOF LIVE LOAD PSF
1. ROOF LIVE LOAD (MINIMUM, NON-REDUCIBLE) 20
OTHER LIVE LOADS
1. OFFICE PARTITIONS (LIVE LOAD): 15 PSF
2. PARTITIONS (LATERAL LOAD): 5 PSF
3. RAILING (LATERAL LOAD AT TOP): 50 PLF OR 200 LB
4. MECHANICAL EQUIPMENT ROOM 150 PSF OR EQUIP.
WEIGHT IF
GREATER
ROOF SNOW LOAD
1. GROUND SNOW LOAD (Pg): 40 PSF
2. FLAT-ROOF SNOW LOAD (Pf): 28 PSF
3. DRIFT SNOW LOAD PER ASCE 7-16
4. SNOW EXPOSURE FACTOR (Ce): 1.0
5. SNOW LOAD IMPORTANCE FACTOR (I): 1.0
6. THERMAL FACTOR (Ct): 1.0
WIND DESIGN DATA
1. ULTIMATE DESIGN WIND SPEED (Vult): 122 MPH
2. NOMINAL DESIGN WIND SPEED (Vasd): 95 MPH
3. RISK CATEGORY: II
4. WIND EXPOSURE: CATEGORY B
5. INTERNAL PRESSURE COEFFICIENT (GCpi): +/-0.18
6. COMPONENTS AND CLADDING DESIGN WIND PRESSURE:
A. ROOF - ZONE 1 -38.18 PSF
B. ROOF - ZONE 2 -60.84 PSF
C. ROOF - ZONE 3 -78.44 PSF
D. WALL - ZONE 4 -28.1 PSF
E. WALL - ZONE 5 -34.7 PSF
EARTHQUAKE DESIGN DATA
1. SEISMIC IMPORTANCE FACTOR (I): 1.0
2. RISK CATEGORY: II
3. 0.2 SEC SPECTRAL RESPONSE ACCELERATION (SS): 0.0898
4. 1.0 SEC SPECTRAL RESPONSE ACCELERATION (S1): 0.0350
5. SITE CLASS: D
6. 0.2 SEC SPECTRAL RESPONSE COEFFICIENT (SDS): 0.096
7. 1.0 SEC SPECTRAL RESPONSE COEFFICIENT (SD1): 0.056
8. SEISMIC DESIGN CATEGORY: A
9. BASIC SEISMIC-FORCE-RESISTING SYSTEM:
A. LIGHT GAUGE SHEAR WALLS
10. DESIGN BASE SHEAR (V): 5.9 KIPS
11. SEISMIC RESPONSE COEFFICIENT (CS): 0.01
12. RESPONSE MODIFICATION FACTOR (R): 6.5
13. ANALYSIS PROCEDURE USED:
A. EQUIVALENT LATERAL FORCE PROCEDURE
STRUCTURAL NOTES
1. ALL WORK SHALL CONFORM TO THE REQUIREMENTS OF THE APPLICABLE
BUILDING CODE.
2. THE STRUCTURE HAS BEEN DESIGNED TO RESIST DESIGN LOADS ONLY AS A
COMPLETED STRUCTURE
A. APPLICATION OF ANY LOADS TO THE PARTIALLY COMPLETED
STRUCTURE SHALL BE CONSIDERED BY THE CONTRACTOR AND SO
INCLUDED IN THE DESIGN OF THE SHORING, BRACING, FORMWORK, AND
ANY OTHER SUPPORTING ELEMENTS PROVIDED FOR CONSTRUCTION OF
THE STRUCTURE.
B. WHERE CONSTRUCTION MATERIAL AND EQUIPMENT ARE TEMPORARILY
STORED ON THE ROOF OR FLOOR FRAMING, THEY SHALL BE
DISTRIBUTED SO THAT THE DESIGN LIVE LOAD AT THE LOADED AREA IS
NOT EXCEEDED.
C. DO NOT BACKFILL AGAINST WALLS OR OTHER STRUCTURAL ELEMENTS
UNTIL SUCH ELEMENTS HAVE REACHED THEIR INTENDED STRENGTH,
HAVE BEEN ADEQUATELY BRACED, AND/OR HAVE OTHER INTEGRAL
STRUCTURAL ELEMENTS IN PLACE WHICH ARE INTENDED TO RESIST THE
LATERAL EARTH LOADS.
3. LATERAL LOAD RESISTING SYSTEM: ALL LATERAL LOAD RESISTANCE AND
STABILITY IN THE COMPLETED STRUCTURE IS PROVIDED BY:
A. N-S DIRECTION: LIGHT GAUGE SHEARWALLS & CMU SHEARWALLS
B. E-W DIRECTION: LIGHT GAUGE SHEARWALLS & STEEL MOMENT FRAMES
C. ROOF DIAPHRAGM: METAL DECK
D. FLOOR DIAPHRAGM: CONCRETE OVER METAL DECK
4. STEEL STABILITY: STRUCTURAL STEEL FRAMING INDICATED IN THESE PLANS
REQUIRES INTERACTION WITH NON-STRUCTURAL STEEL ELEMENTS FOR
STRENGTH AND/OR STABILITY. SEE PLANS FOR SPECIFIC LOCATIONS OF
THESE NON-STRUCTURAL STEEL ELEMENTS WHICH ARE LISTED BELOW:
A. CMU SHEARWALLS
B. METAL FLOOR DECKING WITH CONCRETE TOPPING
C. METAL ROOF DECKING
D. LIGHT GAUGE SHEARWALLS
5. DETAILS ON THE DRAWINGS INDICATED AS "TYPICAL" APPLY IN ALL AREAS
WHERE CONDITIONS SIMILAR TO THE DETAIL OCCUR.
6. THE STRUCTURAL DRAWINGS ARE NOT INTENDED FOR USE AS SHOP
ERECTION DRAWINGS. REPRODUCTION OF THESE DRAWINGS IN LIEU OF
PREPARATION OF SHOP ERECTION DRAWINGS SIGNIFIES THE USERS'
ACCEPTANCE THAT ALL INFORMATION SHOWN IS CORRECT AND APPROPRIATE
FOR SHOP DRAWINGS AND THAT THE USER WILL BE FULLY RESPONSIBLE FOR
EXPENSES THAT MAY OCCUR FROM SAID ACCEPTANCE.
7. UNLESS SPECIFICALLY NOTED, THERE ARE NO PROVISIONS MADE FOR
FUTURE FLOORS, ROOFS, OR OTHER LOADS.
MATERIAL DATA
CONCRETE AND REINFORCING
1. CONCRETE STRENGTH (f'c @ 28 DAYS)
A. FOOTINGS 3,000 PSI
B. FOUNDATION WALLS 4,500 PSI
C. GRADE SUPPORTED SLABS 4,000 PSI
D. CONCRETE TOPPINGS 4,000 PSI
E. CONCRETE NOT SPECIFIED 3,000 PSI
2. ALL CONCRETE EXPOSED TO FREEZE-THAW CONDITIONS SHALL HAVE A
MINIMUM STRENGTH (f'c @ 28 DAYS) OF 4,500 PSI. THIS DOES NOT INCLUDE
FOOTINGS/GRADE BEAMS THAT ARE COVERED BY SOIL.
3. CEMENT TYPE: PORTLAND TYPE I
4. AGGREGATES
A. NORMAL WEIGHT, 1 1/2" MAX. SIZE - ASTM C33
B. PROVIDE AGGREGATES FREE OF MATERIALS WITH DELETERIOUS
REACTIVITY TO ALKALI IN CEMENT, FROM A SINGLE SOURCE WITH
DOCUMENTED SERVICE RECORD DATA OF AT LEAST 10 YEARS
SATISFACTORY SERVICE IN SIMILAR APPLICATIONS AND SERVICE
CONDITIONS USING SIMILAR AGGREGATES AND CEMENTITIOUS
MATERIALS.
5. REINFORCING STEEL ASTM A615, GRADE 60
6. REINFORCING STEEL ASTM A706, WELDABLE
7. WELDED WIRE FABRIC ASTM A185
8. PREFORMED EXPANSION JOINT (1/2") ASTM D1751
MASONRY
1. MASONRY STRENGTH (f'm @ 28 DAYS) 1,500 PSI
2. CONCRETE UNITS ASTM C90
NORMAL WEIGHT
3. UNIT COMPRESSIVE STRENGTH 2,000 PSI (BASED ON
NET AREA)
4. MORTAR TYPE ASTM C270, TYPE S
5. GROUT TYPE ASTM C476, 3/8" MAX.
AGGREGATE SIZE
6. MORTAR STRENGTH (28 DAYS) 1,800 PSI
7. GROUT STRENGTH (28 DAYS) ASTM C476 - 2,000 PSI
8. WIRE REINFORCING ASTM A82, STD. LADDER
TYPE - 9 GAUGE ZINC
COATED PER ASTM A116
- (DUR-O-WALL OR
APPROVED EQUAL @ 16"
O.C. VERTICAL SPACING)
STEEL
1. STRUCTURAL STEEL (WIDE FLANGES) ASTM A992, GRADE 50
2. STRUCTURAL STEEL (ALL OTHER TYPES) ASTM A36
3. STRUCTURAL STEEL PIPE ASTM A53, GRADE B,
SCH. 40
4. STRUCTURAL TUBE ASTM A500, GRADE B
5. ANCHOR RODS ASTM F1554, GRADE 55
WITH WELDING
SUPPLEMENT S1
6. BOLTED CONNECTIONS ASTM A325N
7. WELDED CONNECTIONS E70XX ELECTRODES
8. WELDED CONNECTIONS (GALVANIZED) E6010 OR E6011
ELECTRODES
9. HEADED CONCRETE ANCHORS (HCA) ASTM A108 GRADES
C1010 THROUGH C1020
(Fu=55 KSI)
10. DEFORMED BAR ANCHORS (DBA) ASTM A108 & A496
(Fy=70 KSI)
11. METAL DECKING ASTM A611 OR
ASTM A653-94
12. LIGHT GAUGE STEEL STUDS/JOISTS
A. 12 TO 16 GAUGE (G60 GALV.) ASTM A1003 GRADE ST50H
(Fy=50 KSI)
B. 18+ GAUGE (G60 GALV.) ASTM A1003 GRADE ST33H
(Fy=33 KSI)
COORDINATION/VERIFICATION
1. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND EXISTING
CONDITIONS AND REPORT ANY DISCREPANCIES TO THE ENGINEER BEFORE
PROCEEDING WITH ANY PHASE OF THE WORK.
2. ANY PROPRIETARY STRUCTURAL SYSTEMS THAT ARE COMPOSED OF
COMPONENTS TO BE FIELD ERECTED SHALL BE SUPERVISED BY THE SUPPLIER
DURING MANUFACTURING, DELIVERY, HANDLING, STORAGE, AND ERECTION IN
ACCORDANCE WITH THE INSTRUCTIONS PREPARED BY THE SUPPLIER.
3. CROSS REFERENCE STRUCTURAL DRAWINGS WITH MECHANICAL AND
ELECTRICAL DRAWINGS, AND WITH THE ACTUAL EQUIPMENT SUPPLIED TO THE
PROJECT, FOR THE LOCATION AND SIZE OF ALL SLAB OPENINGS, SLEEVES,
INSERTS, FLOOR DEPRESSIONS, BLOCK-OUTS, CURBS, ANCHORS, BOLTS, ETC.
REQUIRED FOR INSTALLATION.
4. PROVIDE ADEQUATE STRUCTURAL FRAMING AS APPROVED BY THE ENGINEER
FOR ALL REQUIRED MECHANICAL OPENINGS THROUGH SLABS, WALLS, FLOOR
DECK, ETC., AND SUPPORT OF ALL MECHANICAL EQUIPMENT. OPENINGS SHALL
NOT BE PERMITTED THROUGH BEAMS UNLESS SPECIFICALLY DETAILED BY THE
ENGINEER.
5. REFER TO ARCHITECTURAL DRAWINGS FOR ALL SURFACE FINISHES,
DIMENSIONS, AND LOCATIONS OF SLAB DROPS, MASONRY CONTROL JOINTS,
AND WALL OPENING REQUIREMENTS.
GEOTECHNICAL
1. BASIS OF DESIGN: THE FOUNDATION SYSTEM DESIGN IS BASED ON THE
RECOMMENDATIONS OF GEOTECHNICAL REPORT NO. 06054.034 DATED
SEPTEMBER 1, 2016 PREPARED BY SCHEMMER.
2. FOUNDATION SYSTEM: SHALLOW FOOTINGS
3. MAXIMUM ALLOWABLE SOIL BEARING CAPACITY 2,500 PSF
4. LATERAL EARTH PRESSURE:
A. PASSIVE RESISTANCE 180 PCF
B. ACTIVE PRESSURE 50 PCF
C. AT-REST PRESSURE 65 PCF
5. SUBGRADE PREPARATION:
A. HEAVILY ORGANIC OR ROOT INFESTED TOPSOIL SHALL BE EXCAVATED AND
DISCARDED OR STOCKPILED FOR LATER USE IN COVERING FINISHED
LANDSCAPED AREAS AFTER CONSTRUCTION. REMOVE TOPSOIL TO A
MINIMUM DEPTH OF 8 INCHES. DEEPER STRIPPING SHALL BE DONE IF
ORGANIC MATERIALS REMAIN BELOW A DEPTH OF 8 INCHES.
B. REMOVE ALL EXISTING STRUCTURES TO BE DEMOLISHED PRIOR TO
GRADING. THIS INCLUDES PAVING, SIDEWALKS, AND OTHER
MISCELLANEOUS SMALL STRUCTURES.
6. SURCHARGE REQUIREMENTS:
A. PROVIDE SURCHARGE AS OUTLINED IN GEOTECH REPORT
7. STRUCTURAL FILL REQUIREMENTS:
A. CLEAN, INORGANIC, LOW TO MEDIUM PLASTICITY LEAN CLAY (CL) OR SILT
(ML), OR A COMBINATION OF THESE TWO MATERIALS
B. MAXIMUM LIQUID LIMIT (LL) 45
C. MAXIMUM PLASTICITY INDEX 22
D. WATER CONTENT (% OF OPTIMUM) +/-3%
E. MAXIMUM LOOSE LIFT 8"
F. MINIMUM COMPACTION 95% (STANDARD
PROCTOR TEST
ASTM D-698)
8. SPREAD FOOTINGS SHALL BE PLACED ON NEAT, CLEAN AND DRY EXCAVATIONS.
EXTREME CARE SHALL BE TAKEN WHEN EXCAVATING NEAR THE BEARING
SURFACE. FOOT TRAFFIC SHALL BE KEPT TO A MINIMUM NECESSARY TO PLACE
THE FOOTING REINFORCEMENT AND CONCRETE.
9. CONTRACTOR SHALL PROVIDE FOR ADEQUATE DRAINAGE OF SURFACE WATER
AWAY FROM THE STRUCTURE AND EXCAVATED AREAS DURING CONSTRUCTION.
THIS INCLUDES NECESSARY PUMPING, TRENCHING, BACKFILL AND/OR DIKE
CONSTRUCTION.
10. GRANULAR SUBBASE UNDER SLAB ON GRADE:
A. MINIMUM THICKNESS SEE PLAN
B. MINIMUM COMPACTION 95% (STANDARD
PROCTOR TEST
ASTM D-698)
C. GRADATION REQUIREMENTS
a. 100% PASSING THE 3/4" SIEVE
b. LESS THAN 15% PASSING THE 100 SIEVE
c. LESS THAN 2% PASSING THE 200 SIEVE
CAST-IN-PLACE CONCRETE
(REFERENCE SPECIFICATION SECTION 033000 IN PROJECT MANUAL)
GENERAL CONCRETE REQUIREMENTS
1. CONCRETE BATCH DESIGN(S) SHALL BE PROPORTIONED AND PRODUCED IN
ACCORDANCE WITH ACI 318, IN PARTICULAR CHAPTER 5, AND ACI 301. MIX AND
DELIVER IN ACCORDANCE WITH ASTM C94.
2. CONCRETE STRENGTH: SEE MATERIAL DATA NOTES & SPECIFICATION SECTION
033000
3. SLUMP LIMITS: SEE SPECIFICATION SECTION 033000
4. MAXIMUM W/C RATIO: SEE SPECIFICATION SECTION 033000
5. AIR ENTRAINMENT: SEE SPECIFICATION SECTION 033000
6. ADMIXTURES: SEE SPECIFICATION SECTION 033000
7. FLY ASH: SEE SPECIFICATION SECTION 033000
8. CONCRETE TO CONCRETE COLD JOINTS - PROVIDE 1/4" INTENTIONALLY
ROUGHENED SURFACE AT ALL HORIZONTAL JOINTS.
9. EXPOSED CORNERS: PROVIDE A 3/4" CHAMFER AT ALL EXPOSED CONCRETE
CORNERS.
10. CURING: SEE SPECIFICATION SECTION 033000
11. REINFORCING BAR WELDING: ABSOLUTELY NO WELDING OF REINFORCING BARS
OR TORCHING TO BEND REINFORCING BARS SHALL BE ALLOWED WITHOUT THE
SPECIFIC APPROVAL OF THE ENGINEER.
12. MINIMUM CONCRETE CLEAR COVER:
A. FOOTINGS
a. TOP 2"
b. BOTTOM 3"
c. SIDES 3"
B. FOUNDATION WALLS
a. TOP 1-1/2"
b. BOTTOM 3"
c. SIDES 2"
C. INTERIOR SLABS (TOP) SEE TYPICAL SLAB
JOINT DETAIL
ON SHEET SB501
D. OTHER COVER REQUIREMENTS SHALL BE AS NOTED IN APPLICABLE
DETAILS.
13. NON-METALLIC, SHRINKAGE-RESISTANT GROUT: SEE SPECIFICATION SECTION
051200
14. WATERSTOPS: SEE SPECIFICATION SECTION 033000
SLAB ON GRADE REQUIREMENTS
1. SLAB THICKNESS: SEE PLAN
2. SLAB REINFORCING: SEE PLAN
3. GRANULAR SUBBASE: SEE GEOTECHNICAL NOTES
4. VAPOR RETARDER: SEE SPECIFICATION SECTION 033000. LAP AND TAPE ALL
JOINTS AND HOLES.
5. CRACK CONTROL JOINTS (WHETHER CONSTRUCTION JOINTS OR SAWED JOINTS)
IN SLABS ON GRADE SHALL OCCUR AS SHOWN AND ACROSS ALL DOOR
OPENINGS. LOCATE JOINTS AT RE-ENTRANT CORNERS OF SLABS.
A. MAXIMUM SPACING OF CONTROL JOINTS: 12 FEET
6. CURING: CONCRETE SHALL BE MAINTAINED IN A MOIST CONDITION FOR A
MINIMUM OF SEVEN DAYS AFTER ITS PLACEMENT. APPROVED CURING: SEE
SPECIFICATION SECTION 033000
7. SEAL ALL EXPOSED CONSTRUCTION/CRACK CONTROL JOINTS.
A. SEALANT: SEE ARCHITECTURE.
8. FLOOR FINISH & FLATNESS CRITERIA: SEE SPECIFICATION SECTION 033000
ANCHORAGE REQUIREMENTS
1. HEADED CONCRETE ANCHORS (HCA): AUTOMATICALLY END WELDED IN THE
SHOP OR FIELD IN ACCORDANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS. ANCHOR WELDS SHALL BE TESTED PER AWS SECTION 7.7.
2. POST-INSTALLED MECHANICAL ANCHORS: INSTALL USING MINIMUM TORQUE,
EMBEDMENTS, EDGE DISTANCES AND SPACING (UNLESS OTHERWISE NOTED) AS
RECOMMENDED BY THE ANCHOR MANUFACTURER.
3. POST-INSTALLED ADHESIVE ANCHORS: INSTALLATION TO MEET
MANUFACTURER'S RECOMMENDATIONS (UNLESS NOTED OTHERWISE)INCLUDING
MINIMUM EMBEDMENTS, EDGE DISTANCES, SPACING, PROCEDURES, AND
CURING TIME PRIOR TO LOADING.
4. POST-INSTALLED ANCHORS SHALL BE LOCATED PER THE DETAILS.
5. AVOID CUTTING OR DAMAGING EXISTING REINFORCING. SHOULD LOCATIONS OF
DRILLED HOLES BE FOUND DIRECTLY ALIGNED WITH REINFORCING BARS,
NOTIFY ENGINEER FOR NECESSARY ADJUSTMENTS TO THE DESIGN.
UNIT MASONRY
(REFERENCE SPECIFICATION SECTION 042000 IN PROJECT MANUAL)
1. DESIGN CRITERIA: MASONRY SHALL BE CONSTRUCTED PER THE REQUIREMENTS
OF ACI 530.
2. UNIT TYPES: SEE SPECIFICATION SECTION 042000
3. UNIT COMPRESSIVE STRENGTH: SEE MATERIAL DATA NOTES AND SPECIFICATION
SECTION 042000
4. MORTAR: SEE MATERIAL DATA NOTES AND SPECIFICATION SECTION 042000
5. GROUT: SEE MATERIAL DATA NOTES AND SPECIFICATION SECTION 042000
6. CMU REINFORCING: UNLESS NOTED OTHERWISE, REINFORCE ALL CMU WALLS
WITH VERTICAL #5 @ 32" O.C. FILL ALL REINFORCED CELLS WITH GROUT.
MINIMUM GROUT BETWEEN MASONRY AND REINFORCING SHALL BE 1/2". MINIMUM
GROUT BETWEEN PAIRS OF REINFORCING BARS SHALL BE 3/4".
A. PROVIDE #5 VERTICAL REINFORCING AT THE FOLLOWING LOCATIONS:
a. AT ALL CORNERS OF CMU WALLS
b. AT ALL ENDS OF CMU WALLS
c. EACH SIDE OF CONTROL JOINTS
d. EACH SIDE OF WALL OPENINGS
B. SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS OF CONTROL JOINTS.
7. BOND BEAMS
A. LOCATED AT TOP OF ALL CMU WALLS AND WHERE INDICATED IN DETAILS
B. MINIMUM DEPTH UNLESS OTHERWISE NOTED = 8".
C. REINFORCING - (2) #4 CONTINUOUS. LAP SPLICE = 28 IN.
D. CORNER DOWELS - (2) #4 RIGHT ANGLE DOWELS THAT LAP A MINIMUM OF
2'-0" WITH ADJACENT BOND BEAM REINFORCING. IF BOND BEAMS AT
INTERSECTING WALLS MEET AT DIFFERENT ELEVATIONS, EXTEND BOTH
BOND BEAMS AROUND INTERSECTING CORNER TO FIRST INTERIOR
REINFORCED CELL, BUT NOT LESS THAN 4 FEET.
E. EXTEND BOND BEAMS THROUGH CONTROL JOINTS, BUT INTERRUPT BOND
BEAM REINFORCING AT CONTROL JOINTS.
8. LINTEL BEARING: PROVIDE A MINIMUM OF 8 INCHES BEARING AT EACH END.
9. CONTROL JOINTS: EXCEPT WHERE OFFSETS OR SLIP JOINTS ARE SHOWN,
CONTROL JOINTS SHALL BE A CONTINUOUS VERTICAL LINE FROM TOP OF
FOOTING TO TOP OF MASONRY WALL. SPACE CONTROL JOINTS AS FOLLOWS:
A. INTERIOR WALLS 36 FT. O.C. MAX.
B. EXTERIOR WALLS 24 FT. O.C. MAX.
STRUCTURAL STEEL FRAMING
(REFERENCE SPECIFICATION SECTION 051200 IN PROJECT MANUAL)
GENERAL STRUCTURAL STEEL REQUIREMENTS
1. DESIGN CRITERIA: STRUCTURAL STEEL SHALL BE INSTALLED PER THE
REQUIREMENTS OF AISC 360.
2. STRUCTURAL STEEL GRADES: SEE MATERIAL DATA NOTES AND
SPECIFICATION SECTION 051200
3. ANCHOR AND BOLT GRADES: SEE MATERIAL DATA NOTES AND SPECIFICATION
SECTION 051200
4. WELD ELECTRODES: SEE MATERIAL DATA NOTES AND SPECIFICATION
SECTION 051200
5. BEARING CONNECTIONS: UNLESS OTHERWISE NOTED, ALL BEAM
CONNECTIONS SHALL BE SIMPLE FRAMED SHEAR BEARING CONNECTIONS IN
ACCORDANCE WITH THE AISC "SPECIFICATIONS FOR STRUCTURAL JOINTS
USING ASTM A325 OR A490 BOLTS."
6. DESIGN OF CONNECTIONS: BEAM CONNECTIONS SHALL BE AS DETAILED ON
THE PLANS. ALTERNATIVE CONNECTIONS, DESIGNED BY A LICENSED
ENGINEER FOR THE FABRICATOR, MAY BE UTILIZED PROVIDED THE
ALTERNATIVE CONNECTION PROVIDES THE SAME LOAD CARRYING CAPACITY
OF THE ORIGINAL DESIGN.
7. SPLICES: STEEL FABRICATOR SHALL VERIFY WITH ENGINEER ALL BEAM
SPLICES OTHER THAN THOSE SHOWN ON THE PLANS. ANY FULL
PENETRATION SHOP SPLICES APPROVED BY THE ENGINEER SHALL BE
INSPECTED BY RADIOGRAPHIC METHODS BY A TESTING LABORATORY
APPROVED BY THE ENGINEER AND PAID FOR BY THE FABRICATOR.
8. OPPOSING CONNECTIONS: WHERE BEAMS ARE BOLTED ON TWO SIDES OF A
COMMON PLATE OR WEB, THE CONNECTIONS SHALL BE DETAILED WITH AN
ADDITIONAL ROW OF BOLTS ON ONE SIDE THAT IS NOT SHARED WITH THE
OTHER SIDE TO ALLOW INDEPENDENT BOLTING DURING ERECTION.
9. STEEL PROTECTION: ALL STRUCTURAL STEEL SHALL BE CLEANED AND
PAINTED WITH PRIMER PER SPECIFICATION SECTION 051200, UNLESS NOTED
OTHERWISE.
10. STEEL PROTECTION: WHERE STEEL IS INDICATED AS GALVANIZED, PROVIDE
HOT-DIPPED GALVANIZED SURFACE PER SPECIFICATION SECTION 051200.
11. SHOP DRAWINGS: SEE SPECIFICATION SECTION 051200 FOR SUBMITTAL
REQUIREMENTS.
12. SLIDE BEARINGS: WHERE SHOWN ON THE DRAWINGS, TEFLON SLIDE BEARING
PADS SHALL BE PROVIDED. BEARING PADS SHALL BE DURA-SLIDE AS
MANUFACTURED BY TOBI ENGINEERING, INC. OR APPROVED EQUAL.
13. WELDING: ALL WELDING SHALL BE PERFORMED BY QUALIFIED WELDERS PER
AWS STANDARD QUALIFICATION PROCEDURES.
14. COMPLETE PENETRATION WELDS: COMPLETE PENETRATION WELDED
CONNECTIONS SHALL BE PROVIDED WHERE INDICATED. A MINIMUM OF 10%
OF ALL FIELD AND SHOP FULL PENETRATION WELDS SHALL BE TESTED BY X-
RAY OR ULTRASONIC PROCEDURES. (SEE SPECIFICATIONS FOR OTHER
TESTING.)
STEEL DECKING
(REFERENCE SPECIFICATION SECTION 053100 IN PROJECT MANUAL)
1. DECK GOVERNING CRITERIA: THE DESIGN, FABRICATION, AND ERECTION OF
METAL DECKING SHALL BE IN ACCORDANCE WITH THE CURRENT EDITION OF
THE SDI SPECIFICATIONS AND THE SDI DIAPHRAGM DESIGN MANUAL.
2. ROOF DECK CONNECTIONS: ROOF DECKING SHALL BE CONNECTED TO THE
STRUCTURE AS INDICATED IN THE ROOF DECK SCHEDULE. MAINTAIN
OVERALL STRUCTURAL BRACING UNTIL ALL DECKING HAS BEEN INSTALLED.
3. FLOOR DECK CONNECTIONS: FLOOR DECKING SHALL BE CONNECTED TO THE
STRUCTURE AS INDICATED IN THE FLOOR DECK SCHEDULE. MAINTAIN
OVERALL STRUCTURAL BRACING UNTIL ALL DECKING HAS BEEN INSTALLED.
4. DECK PROTECTION: SEE SPECIFICATION SECTION 053100
5. FLOOR SLAB-ON-DECK DESIGN: ALL FLOOR SLABS SUPPORTED ON STEEL
STRUCTURE AND METAL DECK SHALL HAVE A TOTAL THICKNESS AND
REINFORCING AS INDICATED ON PLAN.
COLD-FORMED METAL FRAMING
(REFERENCE SPECIFICATION SECTION 054000 IN PROJECT MANUAL)
1. DESIGN CRITERIA: COLD-FORMED METAL FRAMING SHALL BE INSTALLED PER
THE REQUIREMENTS OF AISI NAS.
2. LIGHT GAUGE STEEL STUDS/JOISTS: SEE MATERIAL DATA NOTES AND
SPECIFICATION SECTION 054000
3. REFERENCE PLANS AND SCHEDULES FOR GAUGE AND SPACING OF LIGHT
GAUGE STEEL STUDS/JOISTS.
4. LIGHT GAUGE STEEL BOTTOM TRACK AT LOAD BEARING WALLS:
A. BOTTOM TRACK SHALL BE GALVANIZED
B. FASTEN TO FOUNDATION AT SHEAR WALLS PER SHEAR WALL
SCHEDULE & TYPICAL DETAILS.
C. FASTEN AT ALL OTHER LOAD BEARING WALLS PER DETAILS INDICATED
ON PLAN.
5. FRAMING AT WALL OPENINGS: SEE TYPICAL DETAILS FOR HEAD AND SILL
FRAMING AT WALL OPENINGS.
6. FRAMING AT FLOOR/ROOF OPENINGS: PROVIDE DOUBLE HEADERS AND
DOUBLE JOISTS EACH SIDE OF ALL OPENINGS IN FLOORS AND ROOFS
UNLESS DETAILED OTHERWISE.
7. BLOCKING AND BRIDGING AT STUDS: SEE SPECIFICATION SECTION 054000
8. BLOCKING AND BRIDGING AT JOISTS: SEE SPECIFICATION SECTION 054000
COLD-FORMED METAL TRUSSES
(REFERENCE SPECIFICATION SECTION 054400 IN PROJECT MANUAL)
1. DESIGN CRITERIA: TRUSS VENDOR IS TO SUBMIT TO THE ARCHITECT,
ENGINEER, AND CITY DESIGN CALCULATIONS BY A LICENSED ENGINEER
AND SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. SHOP
DRAWINGS ARE TO SHOW ALL TEMPORARY AND PERMANENT BRACING
REQUIRED BY DESIGN. DESIGN CALCULATIONS SHALL BE SEALED BY THE
LICENSED ENGINEER.
2. DESIGN RESPONSIBILITIES - TRUSSES SHALL BE DESIGNED UNDER THE
FOLLOWING FORMAT:
A. LATERAL FORCES APPLIED TO THE TRUSSES, SUCH AS DRAG TRUSS
LOADS, COLLECTORS, ETC., ARE INDICATED ON THE PLANS WHERE
APPLICABLE.
B. ALL TRUSS-TO-TRUSS CONNECTIONS ARE THE RESPONSIBILITY OF
THE TRUSS ENGINEER.
C. DRAG LOADS (HORIZONTAL TRUSS TRANSFERS) CONNECTIONS
BETWEEN THE TRUSS AND THE STRUCTURE ARE INDICATED ON THE
PLANS WHERE APPLICABLE.
D. ALL TRUSS-TO-STRUCTURE (WALLS OR BEAMS) CONNECTIONS ARE
INDICATED ON THE PLANS WHERE APPLICABLE.
E. IT IS THE RESPONSIBILITY OF THE TRUSS ENGINEER TO DEVELOP THE
LOADING REQUIRED TO IMPLEMENT THE REQUIRED SNOW LOADS PER
IBC AND ASCE 7 SPECIFICATIONS. THIS INCLUDES ADDITIONAL SNOW
LOAD AT EAVES, AND UNBALANCED LOADING ON THE GABLE AND HIP
ROOFS.
F. IT IS THE RESPONSIBILITY OF THE TRUSS ENGINEER TO REVIEW ALL
OF THE INDICATED DESIGN SPECIFICATIONS, ROOF TRUSS SUPPORTS,
AND DRAG DETAILS AND TO INCORPORATE THESE REQUIREMENTS
INTO THE ENGINEERING DESIGN OF THE ROOF TRUSS SYSTEM.
G. THE TRUSS ENGINEER SHOULD DEVELOP A TRUSS LAYOUT PLAN FOR
THE TRUSS SYSTEM THAT CLEARLY INDICATES THE TRUSS VERTICAL
SUPPORT CONDITIONS, TRUSS-TO-TRUSS CONNECTIONS, DRAG
TRUSSES AND COLLECTORS, AND ANY OTHER FIELD-INSTALLED
REINFORCEMENT, INCLUDING FIELD-INSTALLED TOP CHORD
REINFORCEMENT AT EAVES NECESSARY TO EXECUTE THE TRUSS
SYSTEM DESIGN. THE TRUSS ROOF FRAMING PLAN SHALL BE SEALED
BY A LICENSED PROFESSIONAL ENGINEER AND BE INCLUDED WITH
THE INDIVIDUAL TRUSS CUT SHEETS. THE TRUSS ENGINEER SHOULD
ALSO PROVIDE PROPER SUPERVISION OF ANY TRUSS COMPANY
TECHNICIANS.
H. TRUSS BRACING: TEMPORARY ERECTION BRACING AND PERMANENT
WEB BRACING SHALL BE DESIGNED BY THE TRUSS MANUFACTURER.
I. THE TRUSS ENGINEER SHALL DESIGN TRUSSES AND APPLICABLE
CONNECTIONS FOR BLAST LOADS INDENTIFIED IN THE PROJECT
SPECIFICATIONS. LATTERAL BLAST LOADS FROM THE WALLS SHALL
BE CONSIDERED IN THE DESIGN.
3. METAL TRUSS DESIGN LOADS (IN ADDITION TO SELF-WEIGHT)
A. ROOF DEAD LOAD (TOP CHORD) 10 PSF
B. ROOF DEAD LOAD (BOTTOM CHORD)
A. MECHANICAL ROOMS & CORRIDORS 25 PSF
B. ALL OTHER AREAS 10 PSF
C. FLOOR DEAD LOAD (TOP CHORD) 15 PSF
D. FLOOR DEAD LOAD (BOTTOM CHORD)
A. MECHANICAL ROOMS & CORRIDORS 25 PSF
B. ALL OTHER AREAS 10 PSF
E. ROOF LIVE LOAD (TOP CHORD) SEE DESIGN
CRITERIA
NOTES
F. ROOF LIVE LOAD (BOTTOM CHORD) 10 PSF
G. FLOOR LIVE LOAD (TOP CHORD) SEE DESIGN
CRITERIA
NOTES
SHEATHING
(REFERENCE SPECIFICATION SECTION 061600 IN PROJECT MANUAL)
1. ROOF/FLOOR SHEATHING: SEE MATERIAL DATA NOTES AND SPECIFICATION
SECTION 061600
2. WALL SHEATHING: SEE MATERIAL DATA NOTES AND SPECIFICATION
SECTION 061600
3. ROOF/FLOOR SHEATHING NAILING: COMMON WIRE NAILS SHALL BE USED
AND PENETRATE SUPPORTING MEMBERS A MINIMUM OF 1-5/8". INDIVIDUAL
PIECES OF SHEATHING SHALL NOT BE LESS THAN 24" IN THEIR SHORTEST
PLAN DIRECTION NOR LESS THAN 8 SQ. FT. IN AREA:
A. ROOF SHEATHING:
a. SHEET EDGES 10d @ 6" O.C.
b. INTERMEDIATE FRAMING MEMBERS 10d @ 12" O.C.
B. FLOOR SHEATHING:
a. SHEET EDGES 10d @ 6" O.C.
b. PANEL FIELD 10d @ 12" O.C.
4. WALL SHEATHING NAILING: SEE SHEAR WALL SCHEDULE AND TYPICAL
SHEAR WALL DETAILS
5. PROVIDE BLOCKING OR PANEL EDGE CLIPS AT ALL PANEL EDGES.
6. OPENINGS IN SHEATHING: EDGES OF ALL OPENINGS THROUGH SHEATHING
SHALL BE NAILED PER THE REQUIRED EDGE NAILING ABOVE.
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
TSA PROJECT
NO.:
Department of Veterans Affairs
CONSTRUCT CLC COTTAGE
- HOSPICE
438-420
SIOUX FALLS, SD
06/30/2021
SPECIAL INSPECTIONS
KMW MJN
KMW
S-002
45 90 06054.034
SPECIAL INSPECTIONS (IBC 2018)
SPECIAL INSPECTIONS SHALL BE PROVIDED BY THE OWNER
FOR THE WORK IN ACCORDANCE WITH IBC CHAPTER 17.
CONTRACTOR SHALL NOTIFY AND ACCOMMODATE THE
APPLICABLE INSPECTOR DURING APPROPRIATE PHASES OF
THE WORK AS REQUIRED FOR EACH TYPE OF INSPECTION.
STEEL CONSTRUCTION - GENERAL
1. SHOP CUT AND FINISHED SURFACES IN ACCORDANCE
WITH SECTION M2 OF AISC 360-16.
2. SHOP HEATING FOR STRAIGHTENING, CAMBERING
AND CURVING IN ACCORDANCE WITH SECTION M2.1
OF AISC 360-16.
3. TOLERANCES FOR SHOP FABRICATION IN
ACCORDANCE WITH SECTION 6.4 OF AISC 303-16.
4. STEEL DECK IN ACCORDANCE WITH SDI-QA/QC-2017
5. FIELD CUT SURFACES IN ACCORDANCE WITH SECTION
M2.2 OF AISC 360-16.
6. FIELD HEATING FOR STRAIGHTENING IN ACCORDANCE
WITH SECTION M2.1 OF AISC 360-16.
7. TOLERANCES FOR FIELD ERECTION IN ACCORDANCE
WITH SECTION 7.13 OF AISC 303-16.
STEEL INSPECTION DEFINITIONS
O - OBSERVE THESE ITEMS ON A RANDOM BASIS.
OPERATIONS NEED NOT
BE DELAYED PENDING THESE INSPECTIONS.
P - PERFORM THESE TASKS FOR EACH WELDED JOINT OR
MEMBER, EACH
BOLTED CONNECTION, OR EACH STEEL ELEMENT.
STEEL CONSTRUCTIION - PRIOR TO WELDING
1. WELDER QUALIFICATION RECORDS AND CONTINUITY
RECORDS
(QC - P; QA - O)
2. WELDING PROCEDURE SPECIFICATIONS (WPSs)
AVAILABLE.
(QC - P; QA - P)
3. MANUFACTURER CERTIFICATIONS FOR WELDING
CONSUMABLES AVAILABLE. (QC - P; QA - P)
4. MATERIAL IDENTIFICATION (TYPE/GRADE). (QC - O;
QA - O)
5. WELDER IDENTIFICATION SYSTEM. (QC - O; QA - O)
6. FIT-UP GROOVE WELDS (INCLUDING JOINT
GEOMETRY). (QC - O; QA - O)
A. JOINT PREPARATION.
B. DIMENSIONS (ALIGNMENT, ROOT OPENING,
ROOT FACE, BEVEL).
C. CLEANLINESS (CONDITION OF STEEL
SURFACES).
D. TACKING (TACK WELD QUALITY AND LOCATION).
E. BACKING TYPE AND FIT (IF APPLICABLE).
7. FIT-UP OF CJP GROOVE WELDS OF HSS T-, Y- AND K-
JOINTS WITHOUT BACKING (INCLUDING JOINT
GEOMETRY) (QC - P; QA - O)
A. JOINT PREPARATION.
B. DIMENSIONS (ALIGNMENT, ROOT OPENING,
ROOT FACE, BEVEL).
C. CLEANLINESS (CONDITION OF STEEL
SURFACES).
D. TACKING (TACK WELD QUALITY AND LOCATION).
8. CONFIGURATION AND FINISH OF ACCESS HOLES. (QC -
O; QA - O)
9. FIT-UP FILLET WELDS. (QC - O; QA - O)
A. DIMENSIONS (ALIGNMENT, GAPS AT ROOT).
B. CLEANLINESS (CONDITION OF STEEL
SURFACES).
C. TACKING (TACK WELD QUALITY AND LOCATION).
10. CHECK WELDING EQUIPMENT. (QC - O; QA - N/A)
STEEL CONSTRUCTION - DURING WELDING
1. USE OF QUALIFIED WELDERS. (QC - O; QA - O)
2. CONTROL AND HANDLING OF WELDING
CONSUMABLES. (QC - O; QA - O)
A. PACKAGING.
B. EXPOSURE CONTROL.
3. NO WELDING OVER CRACKED TACK WELDS. (QC - O;
QA - O)
4. ENVIRONMENTAL CONDITIONS.
A. WIND SPEED WITHIN LIMITS.
B. PRECIPITATION AND TEMPERATURE.
5. WPS FOLLOWED. (QC - O; QA - O)
A. SETTINGS ON WELDING EQUIPMENT.
B. TRAVEL SPEED.
C. SELECTING WELDING MATERIALS.
D. SHIELDING GAS TYPE/FLOW RATE.
E. PREHEAT APPLIED.
F. INTERPASS TEMPERATURE MAINTAINED
(MIN./MAX.).
G. PROPER POSITION (F, V, H, OH).
6. WELDING TECHNIQUES. (QC - O; QA - O)
A. INTERPASS AND FINAL CLEANING.
B. EACH PASS WITH PROFILE LIMITATIONS.
C. EACH PASS MEETS QUALITY REQUIREMENTS.
7. PLACEMENT AND INSTALLATION OF STEEL HEADED
STUD ANCHORS
(QC - P; QA - P)
SPECIAL INSPECTIONS CONTINUED (IBC 2018)
CONCRETE CONSTRUCTION
1. INSPECTION OF REINFORCEMENT AND VERIFY
PLACEMENT. (PERIODIC)
2. REINFORCING BAR WELDING:
A. VERIFY WELDABILITY OF REINFORCING BARS
OTHER THAN ASTM A706. (PERIODIC)
B. INSPECT SINGLE-PASS FIILLET WELDS, MAXIMUM
5/16". (PERIODIC)
C. INSPECT ALL OTHER WELDS. (CONTINUOUS)
3. INSPECT ANCHORS CAST IN CONCRETE. (PERIODIC)
4. INSPECT ANCHORS POST-INSTALLED IN HARDENED
CONCRETE MEMBERS.
A. ADHESIVE ANCHORS INSTALLED IN
HORIZONTALLY OR UPWARDLY INCLINED
ORIENTATIONS TO RESIST SUSTAINED TENSION
LOADS. (CONTINUOUS)
B. MECHANICAL ANCHORS AND ADHESIVE
ANCHORS NOT DEFINED IN 4.A. (PERIODIC)
5. VERIFY USE OF REQUIRED DESIGN MIX. (PERIODIC)
6. PRIOR TO CONCRETE PLACEMENT, FABRICATE
SPECIMENS FOR STRENGTH TESTS, PERFORM SLUMP
AND AIR CONTENT TESTS, AND DETERMINE THE
TEMPERATURE OF THE CONCRETE. (CONTINUOUS)
7. VERIFY MAINTENANCE OF SPECIFIED CURING
TEMPERATURE AND TECHNIQUES. (PERIODIC)
8. INSPECT ERECTION OF PRECAST CONCRETE
MEMBERS. (PERIODIC)
9. INSPECT FORMWORK FOR SHAPE, LOCATION AND
DIMENSIONS OF THE CONCRETE MEMBER BEING
FORMED. (PERIODIC)
MASONRY CONSTRUCTION - LEVEL B
EMPIRICALLY DESIGNED MASONRY, MASONRY VENEER,
GLASS UNIT MASONRY
- RISK CATEGORY IV
ALL OTHER MASONRY - RISK CATEGORY I, II OR III
TEST: VERIFICATION OF SLUMP FLOW AND VISUAL
STABILITY INDEX (VSI) AS
DELIVERED TO THE PROJECT SITE IN ACCORDANCE WITH
SPECIFICATION ARTICLE 1.5 B.1.b.3 FOR SELF-
CONSOLIDATING GROUT.
TEST: VERIFICATION OF f'm IN ACCORDANCE WITH
SPECIFICATION
ARTICLE 1.4 B PRIOR TO CONSTRUCTION, EXCEPT WHERE
SPECIFICALLY EXEMPTED BY THIS CODE.
1. VERIFY COMPLIANCE WITH THE APPROVED
SUBMITTALS. (PERIODIC)
2. AS MASONRY CONSTRUCTION BEGINS, VERIFY THAT
THE FOLLOWING ARE IN COMPLIANCE:
A. PROPORTIONS OF SITE-PREPARED MORTAR.
(PERIODIC)
B. CONSTRUCTION OF MORTAR JOINTS.
(PERIODIC)
C. LOCATION OF REINFORCEMENT AND
CONNECTORS. (PERIODIC)
3. PRIOR TO GROUTING, VERIFY THAT THE FOLLOWING
ARE IN COMPLIANCE:
A. GROUT SPACE. (PERIODIC)
B. GRADE, TYPE, AND SIZE OF REINFORCEMENT
AND ANCHOR BOLTS. (PERIODIC)
C. PLACEMENT OF REINFORCEMENT AND
CONNECTORS. (PERIODIC)
D. PROPORTIONS OF SITE-PREPARED GROUT.
(PERIODIC)
E. CONSTRUCTION OF MORTAR JOINTS.
(PERIODIC)
4. VERIFY DURING CONSTRUCTION:
A. SIZE AND LOCATION OF STRUCTURAL
ELEMENTS. (PERIODIC)
B. TYPE, SIZE AND LOCATION OF ANCHORS,
INCLUDING OTHER DETAILS OF ANCHORAGE OF
MASONRY TO STRUCTURAL MEMBERS, FRAMES
OR OTHER CONSTRUCTION. (PERIODIC)
C. WELDING REINFORCEMENT. (CONTINUOUS)
D. PREPARATION, CONSTRUCTION, AND
PROTECTION OF MASONRY DURING COLD
WEATHER (TEMPERATURE BELOW 40 DEGREES
FAHRENHEIT (4.4 DEGREES CELSIUS)) OR HOT
WEATHER (TEMPERATURE ABOVE 90 DEGREES
FAHRENHEIT (32.2 DEGREES CELSIUS)).
(PERIODIC)
E. PLACEMENT OF GROUT IS IN COMPLIANCE.
(CONTINUOUS)
5. OBSERVE PREPARATION OF GROUT SPECIMENTS,
MORTAR SPECIMENS, AND/OR PRISMS. (PERIODIC)
SOILS
1. VERIFY MATERIALS BELOW SHALLOW FOOTINGS ARE
ADEQUATE TO ACHIEVE THE DESIGN BEARING
CAPACITY. (PERIODIC)
2. VERIFY EXCAVATIONS ARE EXTENDED TO PROPER
DEPTH AND HAVE REACHED PROPER MATERIAL.
(PERIODIC)
3. PERFORM CLASSIFICATION AND TESTING OF
COMPACTED FILL MATERIALS. (PERIODIC)
4. VERIFY USE OF PROPER MATERIALS, DENSITIES AND
LIFT THICKNESSES DURING PLACEMENT AND
COMPACTION OF COMPACTED FILL. (CONTINUOUS)
5. PRIOR TO PLACEMENT OF COMPACTED FILL, OBSERVE
SUBGRADE AND VERIFY THAT SITE HAS BEEN
PREPARED PROPERLY. (PERIODIC)
PRECAST CONCRETE STRUCTURAL ELEMENTS
1. MANUFACTURER'S CERTIFICATE OF COMPLIANCE TO
QUALITY ASSURANCE IN ACCORDANCE WITH THE
PROJECT SPECIFICATIONS IS REQUIRED.
SPECIAL INSPECTIONS CONTINUED (IBC 2018)
STEEL CONSTRUCTION - AFTER WELDING
1. WELDS CLEANED. (QC - O; QA - O)
2. SIZE, LENGTH AND LOCATION OF WELDS. (QC - P; QA -
P)
3. WELD MEET VISUAL ACCEPTANCE CRITERIA. (QC - P;
QA - P)
A. CRACK PROHIBITION.
B. WELD/BASE-METAL FUSION.
C. CRATER CROSS SECTION.
D. WELD PROFILES.
E. WELD SIZE.
F. UNDERCUT.
G. POROSITY.
4. ARC STRIKES. (QC - P; QA - P)
5. K-AREA. (QC - P; QA - P)
6. WELD ACCESS HOLES IN ROLLED HEAVY SHAPES AND
BUILT-UP HEAVY SHAPES. (QC - P; QA - P)
7. BACKING REMOVED AND WELD TABS REMOVED (IF
REQUIRED).
8. REPAIR ACTIVITIES. (QC - P; QA - P)
9. DOCUMENT ACCEPTANCE OR REJECTION OF WELDED
JOINT OR MEMBER. (QC - P; QA - P)
10. NO PROHIBITED WELDS HAVE BEEN ADDED WITHOUT
THE APPROVAL OF THE EOR. (QC - O; QA - O)
STEEL CONSTRUCTION - PRIOR TO BOLTING
1. MANUFACTURER'S CERTIFICATIONS AVAILABLE FOR
FASTENER MATERIALS. (QC - O; QA - P)
2. FASTENERS MARKED IN ACCORDANCE WITH ASTM
REQUIREMENTS.
(QC - O; QA - O)
3. CORRECT FASTENERS SELECTED FOR THE JOINT
DETAIL (GRADE, TYPE, BOLT LENGTH IF THREADS ARE
TO BE EXCLUDED FROM SHEAR PLANE).
(QC - O; QA - O)
4. CORRECT BOLTING PROCEDURE SELECTOR FOR
JOINT DETAIL.
(QC - O; QA - O)
5. CONNECTING ELEMENTS, INCLUDING THE
APPROPRIATE FAYING SURFACE CONDITION AND
HOLE PREPARATION, IF SPECIFIED, MEET APPLICABLE
REQUIREMENTS. (QC - O; QA - O)
6. PRE-INSTALLATION VERIFICATION TESTING BY
INSTALLATION PERSONNEL OBSERVED AND
DOCUMENTED FOR FASTENER ASSEMBLIES AND
METHODS USED. (QC - P; QA - O)
7. PROTECTED STORAGE PROVIDED FOR BOLTS, NUTS,
WASHERS AND OTHER FASTENER COMPONENTS.
(QC - O; QA - O)
STEEL CONSTRUCTION - DURING BOLTING
1. FASTENER ASSEMBLIES PLACED IN ALL HOLES AND
WASHERS ARE POSITIONED AS REQUIRED. (QC - O;
QA - O)
2. JOINT BROUGHT TO THE SNUG-TIGHT CONDITION
PRIOR TO THE PRETENSIONING OPERATION. (QC - O;
QA - O)
3. FASTENER COMPONENT NOT TURNED BY THE
WRENCH PREVENTED FROM ROTATING. (QC - O; QA -
O)
4. FASTENERS ARE PRETENSIONED IN ACCORDANCE
WITH THE RCSC SPECIFICATION, PROGRESSING
SYSTEMATICALLY FROM THE MOST RIGID POINT
TOWARD THE FREE EDGES. (QC - O; QA - O)
STEEL CONSTRUCTION - AFTER BOLTING
1. DOCUMENT ACCEPTANCE OR REJECTION OF BOLTED
CONNECTIONS.
(QC - P; QA - P)
COLD-FORMED STEEL DECK
1. SPECIAL INSPECTIONS AND QUALIFICATION OF
WELDING SPECIAL INSPECTORS FOR COLD-FORMED
STEEL FLOOR AND ROOF DECK SHALL BE IN
ACCORDANCE WITH THE QUALITY ASSURANCE
INSPECTION REQUIREMENTS OF SDI-QA/QC-2017.
D F G H J K L
2'-8 1/2" 8'-6 3/4" 4'-1 1/2" 16'-0" 20'-0" 16'-0" 24'-3" 15'-5" 8'-6" 8'-3" 12'-0"
'-1
3/
4"
4' -0
1'
-3
/8
5/
8"
9' -1
3/
8"
'-8
'-7
/8
'-5
/4
'-2
/4
2'
-0
C
HSS5X5X1/4
HSS5X5X1/4
HSS6X6X5/16
HSS6X6X5/16
HSS6X6X5/16
HSS6X6X5/16
HSS6X6X5/8
HSS6X6X5/8HSS6X6X5/8
HSS6X6X5/8
HSS4-1/2X4-1/2X1/4
HSS5X5X1/4
HSS5X5X1/4
HSS4X4X1/4
4" CONCRETE SLAB ON GRADE W/
6X6 W2.9XW2.9 W.W.F. ON 15 MIL.
VAPOR BARRIER OVER 4" GRANULAR
FILL - TYPICAL U.N.O.
F3.5
F3.5
F6.0
F6.0
F6.0
F6.0
F6.0
F6.0 F6.0
F6.0
F6.0
F6.0
F4.0
F4.0
C .J
C .J
C .J
C .J
. C .J
C .J
C.J.
C.J.
C.J.
C.J.
C.J.
GB2-0
G B
2-
G B
2-
G B
2-
G B
2-
G B
2-
G B
2-
G B
2-
G B
2-
1 1
4 4 4 4
4 4 4 4
T S
1-
T S
1-
T S
1-
M
IN
. L
2'
-6
S H
E A
R W
A
LL
T Y
P E
'A
M
IN
. L
2'
-6
S H
E A
R W
A
LL
T Y
P E
'A
M
IN
. L
2'
-6
S H
E A
R W
A
LL
T Y
P E
'A
M
IN
. L
6'
-0
S H
E A
R W
A
LL
T Y
P E
'A
M
IN
. L
6'
-0
S H
E A
R W
A
LL
T Y
P E
'A
SB502
SB502
SB502
SB502
SB502
SB502
SB502
SB502
SB502
SB502
M
F3.0B
HSS4X4X1/4
F3.0B
HSS4X4X1/4
T S
1-
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4 HSS4X4X1/4
3'-9" 11'-3 1/4" 7'-8 1/4" 2'-0 3/4" 4 3/4"
4 3/4" 7'-8 1/4"
8 3/4"2'-5" 12'-7 1/4"
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4 HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
G B
2-
G B
2-
GB2-0
GB2-0
GB2-0
4" CONCRETE SLAB ON GRADE
W/ 6X6 W2.9XW2.9 W.W.F. ON
15 MIL. VAPOR BARRIER OVER
4" GRANULAR FILL - TYP U.N.O
GB2-0
81"
81"
81"101"81"81"
N P
GB2-0
G B
2-
F5.0
F5.0F5.0
F5.0
F5.0F5.0
F5.0F5.0
75" 75"
HSS8X8X1/4HSS8X8X1/4
HSS8X8X1/4HSS8X8X1/4
HSS8X8X1/4HSS8X8X1/4
HSS8X8X1/4HSS8X8X1/4
1GB2-0
C F
2-
C.J.
C .J
C .J
C .J
C.J.
C.J.
C.J.
C.J.
C.J.
C .J
C .J
C .J
.C .J
F4.0
HSS4X4X1/4
C .J
C .J
C .J
C .J
C .J
C.J.
135'-9 3/4"
GB2-0
G B
2-
(T.O.F. = 98'-0") (T.O.F. = 99'-4")
(T.O.F. = 98'-0")
(T.O.F. = 99'-4")
(T.O.F. = 99'-6")
G B
1-
SB502
C .J
C.J.
SB502
SB502
SB502
SB502
AX
9'-6" 39'-11"
E B
3.78°
9' -6
SB502
C .J
CF2-0
SB502
5' -9
'-6
(T.O.F. = 98'-0")
7'-0"
(T.O.F. = 100'-8")
20'-0"
(T.O.F. = 102'-0")
9'-0"
(T.O.F. = 102'-8")
(T.O.F. = 102'-8")
(T.O.F. = 102'-0")
(T.O.F. = 100'-8")6'-0" 18'-0"
7' -6
(T.O.F. = 99'-4")
7'-0"
3.78°
SB502
SB502
SB502
22"X42" CONC.
PIER - TYP
CONC SLAB -
SEE CIVIL
M
IN
. L
4'
-0
S H
E A
R W
A
LL
T Y
P E
'A
M
IN
. L
4'
-0
S H
E A
R W
A
LL
T Y
P E
'A
14'-5 1/4"
'-6
/8
SB502
SB502
SB502
SIM
C.J.
HSS4X4X1/4
HSS4X4X1/4
F3.0B F3.0B
SB502
22"X42" CONC.
PIER - TYP
Drawing Title
Approved:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
TSA PROJECT
NO.:
Department of Veterans Affairs
CONSTRUCT CLC COTTAGE
- HOSPICE
438-420
SIOUX FALLS, SD
06/30/2021
FOUNDATION PLAN
KMW MJN
KMW
SB101
46 90 06054.034
FOUNDATION PLAN NOTES:
A REFERENCE SHEET S-001 FOR STRUCTURAL NOTES
AND SHEET S-000 FOR SCHEDULES.
B REFERENCE SHEET SB501 FOR TYPICAL FOUNDATION
DETAILS NOT NECESSARILY INDICATED ON PLAN.
C VERIFY ALL DIMENSIONS WITH ARCHITECTURAL
DRAWINGS.
REF. NOTES ( ):X
1 STRUCTURAL STOOP - SEE SHEET SB501 FOR TYPICAL
DETAIL. REFERENCE ARCHITECTURAL DRAWINGS FOR
STOOP DIMENSIONS.
2 'C.J.' INDICATES CONTROL JOINT - SEE TYPICAL DETAIL
ON SHEET SB501 AND STRUCTURAL NOTES ON SHEET
S-001 FOR MORE INFORMATION.
3 PROVIDE (2) #4 X 3'-0"-LONG BARS @ 4" O.C. CENTERED
IN SLAB AT ALL RE-ENTRANT CORNERS WITHOUT
CONTROL JOINTS (C.J.) AND AT ENDS OF CONTROL
JOINTS TERMINATED WITHIN SLAB - TYPICAL.
4 SHEAR WALL TYPE 'A' - MIN. L = 6'-0"
13 PROVIDE 1 1/8" THICK BASE PLATE W/ 1" DIAMETER
ANCHOR BOLTS @ THIS COLUMN - TYPICAL @ MOMENT
FRAMES
15 SLEEVE THRU GRADE BEAM FOR UTILITIES AS
REQUIRED. REFERENCE TYPICAL DETAIL 8/SB501.
17 3" CONCRETE W/ #3 BARS @ 12" O.C. OVER 2" TYPE 'C'
16 GAUGE NON-COMPOSITE METAL DECK, TYPICAL
(U.N.O.) - SEE METAL DECK SCHEDULE ON SHEET S-000
FOR MORE INFORMATION.
18 FLOOR DRAIN - SEE MECH. AND SEE ARCH FOR FLOOR
SLOPE.
19 SYMBOL INDICATES FOOTING STEP - SEE TYPICAL
DETAIL 9/SB501.
20 MECHANICAL DUCTBANK - SEE MECH & SEE DETAILS 5
& 12 ON SB502 FOR CONDITIONS AT EXISTING
BUILDINGS.
D ARCHITECTURAL ELEVATION 100’-0” IS EQUAL TO CIVIL
ELEVATION 1498.00’.
E TOP OF FOOTING (T.O.F.) ELEVATION IS 99'-4", TYPICAL
U.N.O.
F FINISHED FLOOR ELEVATION (F.F.E.) IS 100'-0",
TYPICAL U.N.O.
G GRADE BEAMS ARE REQUIRED AT ALL EXTERIOR
WALLS. BOTTOM OF GRADE BEAM SHALL HAVE A
MINIMUM DEPTH OF 42” BELOW EXTERIOR GRADE.
H THICKENED SLAB FOOTINGS ARE REQUIRED AT ALL
INTERIOR LOAD BEARING WALLS.
J PAD FOOTINGS ARE REQUIRED BELOW ALL
STRUCTURAL COLUMNS.
K STRUCTURAL STOOPS ARE REQUIRED AT ALL
EXTERIOR SWING DOORS. SEE TYPICAL DETAIL ON
SHEET SB501.
SCALE: 1/8" = 1'-0"
1 FOUNDATION PLAN
L SHEAR WALLS SHOWN EXTEND FROM FIRST FLOOR
UP TO ROOF, TYPICAL.
PLAN
NORTH
TRUE
NORTH
1 ADDENDUM NO 1 6/30/21
PLAN VIEW
THIS DETAIL APPLICABLE TO:
1. ALL PERIMETER FOUNDATION GRADEWALLS
2. ALL PERIMETER FOUNDATION GRADEBEAMS
3. ALL CONCRETE WALLS
REINFORCING PER
PLANS OR GENERAL
NOTES
30"X30" CORNER
BARS TO MATCH
SIZE AND SPACING
OF HORIZONTAL
REINFORCING
REINFORCING PER
PLANS OR GENERAL
NOTES
INTERIOR WALL
OR BEAM
EXTERIOR
WALL OR BEAM
ALTERNATE BEND 30"X30" CORNER BARS TO
MATCH SIZE AND SPACING
OF HORIZONTAL
REINFORCING
T
T /3
T /4
3/16".
TYPICAL CONTROL JOINT (C.J.)
TYPICAL KEYED CONSTRUCTION JOINT
SAWCUT JOINT
& SEAL
SPECIFIED SLAB
REINFORCEMENT - SEE
PLAN AND GENERAL NOTES
5/8" DIA. DOWELS
@ 12" O.C. X 1'-6"
SEALANT
NOTES:
1. ALL FLOOR SLABS SHALL BE PLACED IN PAVING LANE PATTERN.
A MAXIMUM JOINT SPACING OF 12'-0" U.N.O. AND A MAXIMUM SLAB
PANEL ASPECT RATIO (LENGTH/WIDTH) OF 1.5 SHALL BE
OBSERVED.
2. ALL JOINTS TERMINATING A POUR SHALL BE KEYED
CONSTRUCTION JOINTS.
3. TIME SAW CUTTING OPERATION TO PRECLUDE SHRINKAGE,
CRACKING AND DISLODGING OF AGGREGATE.
OPTION 'A': LEAN CONCRETE FILL OPTION 'B': STRUCTURAL SLAB
CONC. FOUNDATION -
SEE PLAN
1/2" EXPN. JT. MATL.
6" CONC. W/ #4
@ 12" O.C. E.W.
LEAN CONCRETE FILL
SEE PLANS FOR
REQUIRED WIDTH
OF EACH STOOP
1/2" EXPN. JT. MATL.
SEE PLAN
1" S
LO
P
E
V O
ID
8"
SEE PLAN
1" S
LO
P
E
CONC. FOUNDATION -
SEE PLAN
1/2" EXPN. JT. MATL.
6" CONC. W/ #4 @ 12"
O.C. E.W. OVER 1 1/2",
'C', 20 GA. GALV. (G90)
METAL DECKING
EXTERIOR PAVING
(SEE CIVIL)
1/2" EXPN. JT. MATL.
#4 BENTS @ 1'-0" O.C.
ALL SIDES TYP.
18"
8"
8" X 3'-4" CONC. FTG. W/
(2) #5 TOP & BOTTOM &
#4 VERT. @ 24" O.C.
DIA.
(IN.)
MIN. L (IN.)
U.N.O.
3/4
L
1/
2"
ANCHOR ROD
1 1/4 12
NOTE:
1. SEE TYPICAL DETAIL THIS SHEET FOR CONTROL JOINT REQUIREMENTS.
2. FOR CLARITY COLUMN OMITTED.
3. FOR CONFIGURATION OF SPECIFIC CLOSURE POURS, SEE PLAN.
1/2" EXPANSION JOINT W/
COMPRESSIBLE FILLER
CONCRETE CONTROL
JOINT (C.J.) WHERE
SHOWN ON PLAN
CENTERLINE OF COLUMN
4' - 0" (M
AX.)
2'-0" (MIN.)
6" 3'
-0
M A
X
1' -4
M
IN
1'-6" MIN.
MIN.
6"
M
IN
6"
PIPE
CONDITION NO. 1
CONDITION NO. 3
PIPE SLEEVE AS SPECIFIED
CONDITION NO. 2
LEAN CONCRETE TO BE
PLACED BEFORE FOOTING -
MAKE SAME WIDTH AS
FOOTING AND FULL WIDTH OF
PIPE TRENCH
WHERE PIPE IS LAID
BELOW THE 2:1 SLOPE
LINE, FILL TRENCH W/
LEAN CONCRETE TO
SLOPE LINE
NOTES:
THIS DETAIL COVERS THREE POSSIBLE CONDITIONS THAT
MAY OCCUR…
This is the start of the file's text. The full file is on GovTribe.