This is a Technical Specification Sheet for the Siemens TNM® 834 Controller, a compact embedded Internet of Things (IoT) controller designed for smaller applications and plant control. The TNM-834 is a bundled system combining a specially licensed TNM-8000 controller with an IO-R-34 remote 34-point input/output module. The controller operates on the Niagara 4 Framework, providing integrated control, supervision, data logging, alarming, scheduling, and network management with web-based access via Ethernet, wireless LAN, or Internet connectivity. The system features a TI AM3352 1000 MHz ARM Cortex-A8 processor, 1 GB DDR3 RAM, 4GB removable micro-SD card storage, dual isolated RS-485 ports, dual 10/100 MB Ethernet ports, Wi-Fi (IEEE 802.11 a/b/g/n), USB connectivity, 24 VAC/DC power supply, and secure boot capability. The licensing model allows 0 to 5 device licenses in increments of one, with the bundle including licensing for a 16 input/output device count.
The IO-R-34 remote module provides 16 universal inputs (supporting Type 3 thermistors, 0-100kΩ, 0-10VDC, and 0-20mA with external resistor), 10 Form A relay outputs rated 24VAC @ 0.5A, and 8 analog outputs (0-10VDC), with RS-485 communication and ability to power up to 4 additional IO-R-16 modules. The TNM-834 supports maximum expansion of four communication modules (combinations of RS-485, RS-232, and LON modules) and can accommodate up to 8 IO-R-34 modules or 14 IO-R-16 modules for expanded input/output capacity. Both units operate across -20°C to 60°C with 5% to 95% relative humidity, feature 10-year MTTF reliability, and comply with UL 916, CE, FCC, cUL, and CCC standards. The specification sheet includes detailed product ordering information for the base controller, device licenses, expansion modules, power supplies, and optional accessories.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_1305M326Q0383_Amd_0001.pdf | ||
| Attachment_9_142010-26-0151.pdf | ||
| Attachment_8B_142010-26-0151.pdf | ||
| Attachment_7B_142010-26-0151.pdf | ||
| Attachment_1_142010-26-0151.pdf | ||
| Attachment_5_142010-26-0151.pdf | ||
| Attachment_8A_142010-26-0151.pdf | ||
| Sol_1305M326Q0383.pdf | ||
| Wage_Determination_2015-4191_Burlington.txt | TXT text file | |
| Attachment_7A_142010-26-0151.pdf | ||
| Attachment_10_142010-26-0151.pdf | ||
| Attachment_2_142010-26-0151.pdf | ||
| Attachment_4_142010-26-0151.pdf | ||
| Attachment_6A_142010-26-0151.pdf | ||
| Attachment_3_142010-26-0151.pdf |
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Technical Specification Sheet Document No. A6V11420332
April 19, 2018
Siemens Industry, Inc.
TNM® 834 Controller
Description
The Siemens TNM® 834 is a compact, embedded IoT (Internet of Things) controller bundled from a special licensed TNM-8000 and an IO-R-34 remote 34 IO module for smaller applications and plant control.
Based on the TNM-8000 it includes Internet connectivity and Web serving capability providing integrated control, supervision, data logging, alarming, scheduling and network management. It streams data and rich graphical displays to a standard Web browser via an Ethernet or wireless LAN, or remotely over the Internet.
Features
The licensing model for the TNM 834 controller is simplified and features standard drivers.
Special licensing allows 0 to 5 device licenses and increments of 1 device.
Bundle includes one TNM-834 (TNM-8000 with special license) and one IO-R-34 module.
Operates with Niagara 4, the latest version of the Niagara Framework®, for optimum performance in larger facilities.
Licensed for small systems and plant control.
Niagara 4 Supervisors can be used with TNM 834 controllers to aggregate information, including real-time data, history and alarms, to create a single and unified application.
Specifications
TNM-834
Processor TI AM3352: 1000 MHz ARM®
Cortex™-A8
1 GB DDR3 SD RAM
Removable micro-SD card with
4GB flash total storage/2 GB user storage
Wi-Fi (Client or WAP) IEEE802.11a/b/g/n
IEEE802.11n HT20 @ 2.4 GHz
IEEE802.11n HT20/HT40 @ 5
GHz
Configurable radio (Off, WAP, or
Client) WPAPSK/WPA2PSK supported
USB type A connector
Back-up and restore support
(2) Isolated RS-485 with selectable bias and termination
(2) 10/100 MB Ethernet ports
Secure boot
Power Supply 24 VAC/DC
Operating System Runs Niagara 4.1 and later
Real time clock
Batteryless
Niagara NiCS accept.station.in “*” (all) accept.station.out “*” (all) accept.wb.in “*” (all) accept.wb.out “*” (all)
Agency Listings
UL Listings UL 916, PAZX
CE EN 61326-1, 1999/5/EC R&TTE
Directive, ROHS
FCC Compliance FCC Part 15 Subpart B, Class B
FCC Part 15 Subpart C cUL Listed Canadian Standards Association
C22.2 No. 205-M1983 (PAZX7)
CCC (China)
Optional SRRC, RSS
Ambient Conditions
Operating Temperature -20°C to 60°C
Storage Temperature -40°C to 85°C
Relative Humidity Range 5% to 95% — Non condensing
Shipping and vibration: ASTM D4169, Assurance Level II
MTTF 10 years+
Expansion and I/O Module Combinations
Maximum Expansion
Modules Supported
Maximum I/O Modules
Supported
NPB-8000-LON: 4 588-692 : 16
NPB-8000-232: 4 IO-R-34 (1 included) : 8 total
NPB-8000-2X-485: 2 IO-R-16 : 16
Maximum Expansion
Modules Supported
Maximum I/O Modules
Supported
NPB-8000-LON: 4 588-692 : 16
NPB-8000-232: 4 IO-R-34 (1 included) : 8
NPB-8000-2X-485: 2 IO-R-16 : 16
Maximum Combinations Communication Modules
Expansion 1 Expansion 2 Expansion 3 Expansion 4
232 or
LON
232 or
LON
232 or
LON
232 or
LON
232 or
LON
232 or
LON
232 or
LON
232 or
LON
Remote IO modules
Included with the TNM-834 is licensing for an 16 IO device count.
- 1 IO-R-16 = device count 1
- 1 IO-R-34 = device count 2 (one module included)
Therefore, the maximum Expansion is
- 7 IO-R-34 ((7+1) * device count 2) or
- 14 IO-R-16 ((14+2)* device count 1) or a combination
- E.g. 4 IO-R-34 and 8 IO-R-16 (4* device count 2 + 8* device count 1 = device count 16)
Specifications
IO-R-34
Operating System
Niagara 4 Requires Niagara 4.3 or later
Niagara AX Requires Niagara 3.8u3 or later
I/O
16 Universal inputs Type 3 (10k) thermistors
0-100kΩ
0-10VDC
0-20mA with external resistor
10 Relay outputs Form A contacts 24VAC @ 0.5A rated
8 Analog outputs 0-10VDC
Power Supply 24 VAC/DC
Can provide power to up to 4 attached IO-R-16 modules
Communication RS-485
Agency Listings
UL Listings UL 916, C-UL
CE EN 61326-1:2013,
FCC Compliance FCC Part 15, Class B
RoHS RoHS2
China ROHS
Other RCM; REACH; WEEE; Open
Energy Management Class 2
Ambient Conditions
Operating Temperature -20°C to 60°C
Storage Temperature -40°C to 85°C
Relative Humidity Range 5% to 95% — Non condensing
Shipping and vibration: ASTM D4169, Assurance Level II
MTTF 10 years+
Mounting and Dimensions
TNM-834
1. Controller. Allow at least 1.5 in. (38 mm) clearance around all sides and minimum of 3 in.
(76 mm) at bottom for Wi-Fi antenna.
2. Expansion module. Up to four (4) can be used.
See Expansion Module and I/O Configurations.
3. Distances between center of tabs from one unit to another unit.
Compatible with (DIN43880) enclosures. Suitable for mounting to a panel or to an EN50022 standard 35 mm rail.
IO-R-34
162mm (w) x 116mm (h) x 61mm (d) (6.8 in x 4.5 in x 2.4 in.
Information in this document is based on specifications believed correct at the time of publication. The right is reserved to make changes as design improvements are introduced. Product or company names mentioned herein may be the trademarks of their respective owners.
© 2018 Siemens Industry, Inc.
Siemens Industry, Inc.
Building Technologies Division
1000 Deerfield Parkway
Buffalo Grove, IL 60089-4513
USA
Tel. 1 + 847-215-1000
Your feedback is important to us. If you have comments about this document, please send them to SBT_technical.editor.us.sbt@siemens.com.
Document No. A6V11420332
Printed in the USA
Product Ordering Information Description Part Number
Base unit includes two isolated RS485 ports, two 10/100 MB Ethernet ports, USB Backup & Restore and Wi-Fi connectivity
TNM-834
Up to 0 Devices and 0 point core. NC-8000-NC*
Up to 10 devices/500 point upgrade
(can be purchased during initial licensing).
DEVICE-1
Up to 10 devices/500 point upgrade
(can be purchased during initial licensing).
DEVICE-10
Up to 25 devices/1,250 point upgrade
(can be purchased during initial licensing).
DEVICE-25
Up to 50 devices/2,500 point upgrade
(can be purchased during initial licensing).
DEVICE-50
Up to 1 devices/50 point upgrade (can be purchased post initial licensing).
DEVICE-UP-1
Up to 10 devices/500 point upgrade
(can be purchased post initial licensing).
DEVICE-UP-10
Up to 25 devices/1,250 point upgrade
(can be purchased post initial licensing).
DEVICE-UP-25
Up to 50 devices/2,500 point upgrade
(can be purchased post initial licensing).
DEVICE-UP-50
Enables TNM ® 8000 controller to run
Niagara AX (3.8U). 3.8U Build with TNM
8000 controller support.
JACE -8000-AX
TNM 8000 controller — add on dual port
RS-485 module.
NPB-8000-2X-485
TNM 8000 controller — add on single port LON FTT10A module.
NPB-8000-LON
TNM 8000 controller — add on single port RS-232 module.
NPB-8000-232
Remote IO module with 16 points.
Communication using RS 485, maximum IO-R-16 modules supported:
16.
IO-R-16
Remote IO module with 34 points.
Communication using RS 485, maximum IO-R-34 modules supported:
8.
IO-R-34
Remote IO module, compatible with the
TNM 8000 controller. Communication using RS 485, maximum I/O supported
T-IO-16-485 modules: 16.
588-692
Smart II Driver for Niagara 4 SMART2-N4
Downgrade license for Niagara AX JACE-8000-AX
TNM-8000 Plug In power supply WPM-8000
Universal power supply for TNM 8000 controller.
588-679
24V power supply for T-IO-16-485. 588-678
Universal power supply for T-IO-16-485. 588-679
TNM-8000 Accessory Kit NPB-8000-KIT
TNM-8000 Expansion Module Kit NPB-8000-OPT-KIT
*All NC-8XXX parts include a Niagara 4 license and Tridium’s standard driver suite. Please see Tridium standard driver suite documentation for more information.