This file is an Owner's Manual for the TC Compact Series field controllers. The document provides comprehensive technical documentation for Siemens Building Technologies TC Compact Series programmable controllers (models TC-16, TC-24, and TC-36) used in building automation systems. The TC Compact Series are Direct Digital Control (DDC) supervisory equipment controllers designed for TALON Automation Systems that support both BACnet/IP and BACnet MS/TP protocols over Ethernet and RS-485 networks. Available configurations include 16, 24, or 36 point terminations with options for Field Level Network (FLN) support, extended temperature ranges for rooftop applications, and Island Bus expansion capabilities. The controllers feature software-configurable points supporting various input/output types including analog inputs (voltage, current, RTD, thermistor), digital inputs and outputs, pulse accumulators, and analog outputs, with memory ranging from 16MB to 64MB RAM and 8MB to 16MB Flash ROM depending on model.
The manual covers hardware components including backup batteries (AA and coin cell), communication ports (10/100B Ethernet, RS-485, USB, HMI), support for optional HOA (Hand-Off-Auto) upgrade kits with manual override switches, and integration with TX-I/O modules for point expansion on TC-36 models. For smoke control applications compliant with UL864 and NFPA92A standards, the TC Compact must be mounted in a PX Series enclosure with specific power supply and modem requirements. The document includes ordering information for various field panel models, optional licenses (FLN support, Island Bus, Modbus drivers), TX-I/O modules, power supplies, and accessories; specifications for supported point types and battery backup times; networking architecture for Management, Automation, and Field Level Networks; and basic troubleshooting guidance for common operational issues.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_1305M326Q0383_Amd_0001.pdf | ||
| Attachment_1_142010-26-0151.pdf | ||
| Attachment_5_142010-26-0151.pdf | ||
| Attachment_8A_142010-26-0151.pdf | ||
| Attachment_6B_142010-26-0151.pdf | ||
| Attachment_9_142010-26-0151.pdf | ||
| Attachment_8B_142010-26-0151.pdf | ||
| Attachment_7B_142010-26-0151.pdf | ||
| Sol_1305M326Q0383.pdf | ||
| Wage_Determination_2015-4191_Burlington.txt | TXT text file | |
| Attachment_7A_142010-26-0151.pdf | ||
| Attachment_10_142010-26-0151.pdf | ||
| Attachment_2_142010-26-0151.pdf | ||
| Attachment_4_142010-26-0151.pdf | ||
| Attachment_3_142010-26-0151.pdf |
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TC Compact Series Owner's Manual
588-682 Building Technologies 2019-01-25
Copyright Notice
2 | 93 Siemens Industry, Inc. Owner's Manual 588-682
Building Technologies 2019-01-25
Notice Document information is subject to change without notice by Siemens Industry, Inc.
Companies, names, and various data used in examples are fictitious unless otherwise noted. No part of this document may be reproduced or transmitted in any form or by any means, electronic or mechanical, for any purpose, without the express written permission of Siemens Industry, Inc.
Warning This equipment generates, uses, and can radiate radio frequency energy. If equipment is not installed and used in accordance with the instructions manual, it may cause interference to radio communications. Equipment has been tested and found to comply within the limits for a Class B digital device pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference. Residential area equipment users are required to take whatever measures necessary to correct the interference at their own expense.
Service Statement Control devices are combined to make a system. Each control device is mechanical in nature and all mechanical components must be regularly serviced to optimize their operation. Siemens Industry, Inc. branch offices and authorized distributors offer Technical Support Programs that will ensure continuous, trouble-free system performance.
For further information, contact your nearest Siemens Solution Partner, Authorized TALON Dealer.
Copyright 2018 Siemens Industry, Inc.
FCC Regulations The manual for an intentional or unintentional radiator shall caution the user that changes or modifications not expressly approved by the party responsible could void the user’s authority to operate the equipment.
For a Class B digital device or peripheral, the instructions furnished the user shall include the following or similar statement, placed in a prominent location in the text of the manual:
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
This equipment generates, uses and can radiate radio frequency energy and, if not in-stalled and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
● Reorient or relocate the receiving antenna.
● Increase the separation between the equipment and receiver.
● Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
● Consult the dealer or an experienced radio/TV technician for help.
3 | 93
To the Reader Your feedback is important to us. If you have comments about this manual, please submit them to: SBT_technical.editor.us.sbt@siemens.com
Credits TALON is a registered trademark of Siemens Industry, Inc.
Desigo® and Desigo® CC™ are registered trademarks of Siemens Schweiz AG.
Other product or company names mentioned herein may be the trademarks of their respective owners.
Printed in the USA.
Cyber security disclaimer
4 | 93
Cyber security disclaimer Siemens provides a portfolio of products, solutions, systems and services that includes security functions that support the secure operation of plants, systems, machines and networks. In the field of Building Technologies, this includes building automation and control, fire safety, security management as well as physical security systems.
In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art security concept. Siemens’ portfolio only forms one element of such a concept.
You are responsible for preventing unauthorized access to your plants, systems, machines and networks which should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when appropriate security measures (e.g. firewalls and/or network segmentation) are in place. Additionally, Siemens’ guidance on appropriate security measures should be taken into account. For additional information, please contact your Siemens sales representative or visit https://www.siemens.com/global/en/home/company/topic-areas/future-of-manufacturing/industrial-security.html.
Siemens’ portfolio undergoes continuous development to make it more secure.
Siemens strongly recommends that updates are applied as soon as they are available and that the latest versions are used. Use of versions that are no longer supported, and failure to apply the latest updates may increase your exposure to cyber threats.
Siemens strongly recommends to comply with security advisories on the latest security threats, patches and other related measures, published, among others, under https://www.siemens.com/cert/en/cert-security-advisories.htm.
5 | 93
Table of Contents
How to Use This Manual
Chapter 1—Introduction TC Compact Series Product Overview
Ordering Information Compatibility with the TALON Automation System
TCP/IP Protocol Compatibility Required IP Addresses Device Registration Address Assignment
Principles of Field Panel Operation Gathering and Processing Field Inputs Executing Control Programs System Program License Manager
How does License Manager Work?
TALON Automation Networking
Management Level Network Automation Level Network
Simultaneous ALN Access How Information Moves Through the Network BACnet/IP Automation Level Network BACnet MS/TP Automation Level Network
Field Level Network
Chapter 2—Hardware Features 16- and 24-Point Compact Series Diagram 36-Point Compact Series Product Diagram Supported Point Types Compact Series Backup Batteries
AA Battery Coin Cell Battery Memory Size and Typical Battery Backup Time
Memory Flash Read-Only Memory (Flash ROM)
Compressed ROM Auto-Restore and Database Backup to Flash Auto Save File System Operations
Random Access Memory (RAM) Communication Connections
6 | 93
HMI and Tool Ports 10B/100B Ethernet Port RS-485 Port USB Host Port TX-I/O Island Bus
Compact Series Smoke Control Application Requirements HOA (Hand-Off-Auto) Upgrade Kits
HOA Specifications Using the HOA Switches Default Mapping
PXM10S/T Product Overview and Description Product Features
Communication Connections Requirements Application Menus Operator Display Layout Operator Display Menu Tree Main Menu Structure Login and Logoff
Logging In Logging Off
Viewing, Commanding, and Releasing Points Configuring Point Monitor Configuring Settings
Unitary Equipment Controller Unitary Equipment Controller Specifications
TX-I/O Product Range Overview TX-I/O Module Overview
TX-I/O Module Product Diagram TX-I/O Module LCD Symbol Chart Address Keys
TX-I/O Power Supply and Bus Modules TX-I/O Power Supply Overview Bus Connection Module Overview
PX Series Enclosures and Service Boxes PX Series Service Box Features Product Numbers PX Series Enclosure Specifications PX Series Service Box Specifications PX Series Enclosure Placement
Chapter 3—Applications Operator Interface
Field Panel Web Server
7 | 93
Powers Process Control Language (PPCL) Control Program and Point Database Control Programs Point Database
Applications Alarm Management Daylight Saving Time Loop/Loop Tuning Trend Data Collection User Access and Privileges
Controlling User Access to Field Panel Functions Customized Applications
SNMP
Chapter 4—Troubleshooting Service Information
Electrostatic Discharge Error Status Messages Ordering Replacement Parts Replacing the Batteries Reinstalling the Mounting Tabs
Troubleshooting Compact Field Panels
BATT LOW LED
RUN LED
Communication Errors
Troubleshooting the TX-I/O Island Bus
Glossary
Index
How to Use This Manual
9 | 93
About This Manual This manual is written for the owner and user of the TC Compact Series. It is designed to help you become familiar with the TC Compact and its applications.
This section covers manual organization, document conventions and symbols used in the manual, how to access help, related publications, and any other information that will help you use this manual.
Document Organization This manual contains the following chapters:
● Chapter 1—Introduction, describes each section in this manual and presents an overview of TC Compact operation.
● Chapter 2—Hardware Features, describes the TC Compact hardware components and their functions.
● Chapter 3—Applications, describes the operating system and applications available with the TC Compact.
● Chapter 4—Troubleshooting, describes basic corrective measures you should take if you encounter a problem when using a TC Compact.
NOTE:
The troubleshooting section is not meant to be a full diagnostic guide, but is designed to help you address basic troubleshooting issues. If you encounter a problem not covered in this section or require further assistance, consult your Siemens Solution Partner, Authorized TALON Dealer.
● A Glossary describes the terms and acronyms used in this manual.
● An Index is provided to assist you in finding information presented in this manual.
Prerequisites In addition to reading this owner's manual, you should also become familiar with the following technical documentation. Each document has been written to help you get the most out of your TC Compact Series hardware.
These manuals, along with information about other Siemens Industry products, technical training classes, and services can be obtained from your local Siemens Solution Partner, Authorized TALON Dealer.
● Powers Process Control Language (PPCL) User's Manual (588-583). This manual describes Powers Process Control Language (PPCL), the language used to write the control programs for the TC Compact.
● TALON Firmware User's Manual (588-580). These manuals describe the operator interface program used to communicate with TALON field panels. It contains information on defining the TC Compact database, including slopes and intercepts.
For Smoke Control Applications Smoke Control Systems Application and Engineering Manual (125-1806). This manual is a comprehensive reference on smoke control applications for TALON equipment. It contains all of the various agency requirements and recommended practices of organizations that are widely-recognized in composing standards and testing equipment involved in life safety applications.
10 | 93
When Using TALON View Software TALON View 3.x Documentation. To view TALON View 3.x documentation, see the TALON View Online Documentation window, which you can access from the TALON View Main Menu or the TALON View program group.
Document Conventions The following table lists conventions to help you use this manual in a quick and efficient manner.
Convention Examples
Numbered Lists (1, 2, 3…) indicate a procedure with sequential steps.
1. Turn OFF power to the field panel.
2. Turn ON power to the field panel.
3. Contact the local Siemens Solution Partner, Authorized TALON Dealer.
Conditions that must be completed or met before beginning a task are designated with a Intermediate results (what will happen following the execution of a step), are designated with a ⇨.
Results, which inform the user that a task was completed successfully, are designated with a
⊳Composer software is properly installed.
⊳A Valid license is available.
1. Select Start > Programs > Siemens > GMS > Composer.
⇨The Project Management window displays.
2. Open an existing project or create a new one.
⇨The project window displays.
Actions that should be performed are specified in boldface font.
Type F for Field panels.
Click OK to save changes and close the dialog box.
Error and system messages are displayed in Courier New font.
The message Report Definition successfully renamed displays in the status bar.
New terms appearing for the first time are italicized.
The field panel continuously executes a user-defined set of instructions called the control program.
This symbol signifies Notes. Notes provide additional information or helpful hints.
Cross references to other information are indicated with an arrow and the page number, enclosed in brackets: [→92]
For more information on creating flowcharts, see Flowcharts [→92].
Placeholders indicate text that can vary based on your selection. Placeholders are specified in bold print, and enclosed with brackets [ ].
Type A C D H [username] [field panel #].
Safety Symbols The following table lists the safety symbols used in this manual to draw attention to important information.
11 | 93
Symbol Meaning Description
NOTICE CAUTION Equipment damage may occur if a procedure or instruction is not followed as specified. (For online documentation, the NOTICE displays in white with a blue background.)
CAUTION Minor or moderate injury may occur if a procedure or instruction is not followed as specified.
WARNING Personal injury or property damage may occur if a procedure or instruction is not followed as specified.
DANGER Electric shock, death, or severe property damage may occur if a procedure or instruction is not followed as specified.
Getting Help For more information about TALON products, contact your local Siemens Solution Partner, Authorized TALON Dealer.
Chapter 1—Introduction TC Compact Series Product Overview
12 | 93
Chapter 1 provides an introduction to the TC Compact Series and how it is integrated with the TALON Automation System. The following topics are discussed:
● TC Compact Series Product Overview
● Compatibility with the TALON Automation System
– BACnet Protocol Compatibility
– TCP/IP Protocol Compatibility
● Principles of TC Compact Operation
– Gathering and Processing Field Inputs
– Executing Control Programs
– System Program
● TALON Automation Networking
– Management Level Network
– Automation Level Network
– Field Level Network
TC Compact Series Product Overview The TC Compact Series (Programmable Controller–Compact) for BACnet networks is a high-performance Direct Digital Control (DDC) supervisory equipment controller, which is an integral part of the TALON Automation System. The controllers are classified as either a BACnet Building Controller (B-BC) with support for BACnet/IP or BACnet MS/TP protocols.
The TC Compact Series offers integrated I/O based on state-of-the-art TX-I/O™ Technology, which provides superior flexibility of point and signal types, and makes it an optimal solution for Air Handling Unit (AHU) control. The TC Compact operates stand-alone or networked to perform complex control, monitoring, and energy management functions without relying on a higher-level processor.
The TC Compact Series communicates with other field panels or workstations on a peer-to-peer Automation Level Network (ALN), or on the Field Level Network (FLN), and supports the following communication options:
● Native BACnet/IP communications over 10/100 MB Ethernet networks
● Native BACnet MS/TP on RS-485 The TC Compact is available with 16, 24, or 36 point terminations. Selected models in the Compact Series provide the following options:
● Support for FLN devices.
● An extended temperature range for the control of rooftop devices.
● Support for Island Bus, which uses TX-I/O modules to expand the number of point terminations for high-speed loop control. For TC-36 only.
TC Compact Series Product Overview
13 | 93
Ordering Information
TC Compact Series Field Panels
Part Number Description
TC16.2-EF32.T TC Compact, 16 point, BACnet/IP ALN, FLN enabled
TC16.3-UCM.T TC Unitary Equipment Controller, 16 point, BACnet MS/TP
TC16.3-UCMR.T TC Unitary Equipment Controller, 16 point, BACnet MS/TP FLN, Rooftop Model
TC24.2-EF32.T TC Compact, 24 point, BACnet/IP ALN or MS/TP FLN
TC24.3-UCM.T TC Unitary Equipment Controller, 24 point, BACnet MS/TP
TC24.3-UCMR.T TC Unitary Equipment Controller, 24 point, BACnet MS/TP FLN, Rooftop Model
TC36-E.T TC Compact, 36 point, BACnet/IP or MS/TP ALN
TC36-EF.T TC Compact, 36 point, BACnet/IP or MS/TP ALN includes TX-I/O and FLN support licenses
Optional Licenses
Product Number Description
LSM-FLN.T License to enable FLN support on models TC-16-EF.T or TC-24-EF.T
LSM-16.T License to upgrade the UEC 16 to a TC Compact 16
LSM-24.T License to upgrade the UEC 24 to a TC Compact 24
LSM-FLN36.T License to enable FLN support on model TC36-E.A
LSM-IB36.T License to enable 4 TX-I/O modules on the Island Bus on model TC36-E.T
LSM-36.T License to enable 4 TX-I/O modules on the Island Bus and FLN support on model TC36-E.T
LSM-FPWEBPL.T License to enable any Siemens ALN controller to supply the host controller with data for FIN Builder graphics
LSM-FPWEBPLHST.T License to enable a TC Modular or TC-36 to host FIN Builder graphics For TC-36 only
LSM-INT-MDBS250.T License to support Modbus 250 Driver
LSM-INT-MDBS500.T License to support Modbus 500 Driver
TX-I/O I/O Modules
TXM1.8D TX-I/O Module, 8 DI points
TXM1.16D TX-I/O Module, 16 DI points
TXM1.8U TX-I/O Module, 8 Universal points
TXM1.8U-ML TX-I/O Module, 8 Universal points with LOID
TXM1.8X TX-I/O Module, 8 Super Universal points
TXM1.8X-ML TX-I/O Module, 8 Super Universal points with LOID
TXM1.6R TX-I/O Module, 6 DO with Relay points
TXM1.6R-M TX-I/O Module, 6 DO with Relay points with manual override
Compatibility with the TALON Automation System
14 | 93
TX-I/O Power Supply and Bus Modules
TXS1.12F4 TX-I/O Power Supply, 1.2A, 4A Fuse
TXS1.EF4 TX-I/O Bus Connection Module, 4A Fuse
Accessories
TXA1.K12 One set of address keys, numbers 1-12.
TXA1.K24 One set of address keys, numbers 1-24.
TXA1.K-48 One set of address keys, numbers 25-48.
TXA1.K-72 One set of address keys, numbers 49-72.
TXA1.LLT-P100 Labels for TX-I/O, 100 sheets/pack, letter format.
TXA1.LH Replacement label holders.
TALON BACnet is compatible with the BACnet/IP protocol.
CAUTION
When working on a network with multiple firmware revisions, always connect to the operator interface at the field panel with the newest firmware revision. Otherwise, you cannot view features in newer firmware revisions, or the field panel may coldstart.
TCP/IP Protocol Compatibility TC Compact Series controllers with BACnet/IP ALN provide the following:
● 100% compatibility with the TCP/IP protocol suite.
● Support of Dynamic Host Configuration Protocol (DHCP) and Domain Name
Servers (DNS).
● Support and auto detection of 10Base-T and 100Base-TX Ethernet.
Required IP Addresses TALON BACnet/IP ALN uses:
● One IP address per device (field panel or workstation).
● One additional shared IP address per ALN for the multicast group (when using multicast optimization).
Device Registration Devices register with the DHCP server and Domain Name Server, if either is present.
15 | 93
Address Assignment IP addresses are dynamically assigned by the DHCP server.
If an address changes or is not recognized, the field panel firmware lets you release the dynamically assigned IP address and then reconnect the field panel to the DHCP server, accepting a new IP address assignment in the process.
If there is no DHCP server at the site, you must manually assign static IP addresses as part of the startup system configuration.
Physical Addressing Each device on the BACnet/IP ALN has a hard-wired MAC address, which is printed on the product label.
Port Numbers The default TCP/IP port number for TALON BACnet/IP ALN communications is 5033.
You can change the TCP/IP port number if necessary.
All devices on the network must use the same TCP/IP port number.
You must specify a UDP port number when using multicast optimization. The default UDP port number is 8.
Network Bandwidth BACnet/IP ALN does not add significantly to your network overhead. Burst conditions for this product occur during:
● Database downloading after coldstart.
● Database uploading.
● Trend data uploading.
● Burst of alarms or COVs.
Data Exchange BACnet/IP ALN sends and receives TALON data in TCP/IP packets.
BACnet/IP ALN synchronizes global data between all devices. Each device runs a global data replication engine that communicates with peer devices to:
● Exchange new and changed global data.
● Resolve conflicts when data does not match.
Device Naming Conventions Field panel DNS node names are limited to 30 characters and cannot contain spaces.
Network Security BACnet/IP ALN uses your intranet security within the firewall and a username/password combination to restrict access outside the firewall. You can use VLAN to improve internal security.
Principles of Field Panel Operation
16 | 93
The TC Compact Series gathers information about the environment of your facility, as well as the equipment it monitors and controls. The TC Compact receives updated information, stores information, executes control programs, handles operator commands and requests, and makes control management decisions. At the same time, the TC Compact also translates decisions into actions and allows the operator to observe those actions. The operator can also override and modify the decisions made by the TC Compact.
Gathering and Processing Field Inputs The TC Compact samples the information at all field inputs, or points, approximately once each second, and stores numerical representations of the sampled values.
Under certain conditions, some points require additional handling. The TC Compact initiates required actions after these points are checked against previously-entered configuration data.
Example A log entry might be required in a point history file every 20 samples, or notification of an alarm condition could be sent to the operator as a point crossed the alarm threshold.
Executing Control Programs The TC Compact continuously executes a user-defined set of instructions called the control program. This program uses the most recent point values and the most recent clock time. The control program does the following:
● Evaluates control strategies.
● Uses an internal calendar and time clock for time-based functions.
● Updates point values and commands field points according to the program results.
● Sends messages or reports to proper terminal locations as needed.
Example During occupied hours (7:00 A.M. through 5:00 P.M.) a fan:
● Turns ON if the room temperature rises above 80°F (27°C).
● Turns OFF when the temperature drops below 73°F (23°C).
Between 5:00 P.M. and 7:00 A.M. the fan turns OFF regardless of the room temperature.
If the temperature rises to 85°F (29°C) at any time, the TC Compact sends an alarm message to an alarm printer.
These specifications can be met by:
1. Connecting a room temperature sensor/transmitter and fan starter output to the TC Compact.
2. Defining the room temperature sensor with a high alarm limit of 85°F (29°C) and the fan points in the TC Compact database.
3. Writing a short control program that defines your control strategy.
4. Enabling the execution for that portion of the control program.
To perform this control strategy, the TC Compact:
17 | 93
● Continuously executes the control program.
● Samples a current or voltage signal representing the room temperature and updates the value associated with that temperature in its memory.
– If the temperature rises to 85°F (29°C), then the TC Compact sends an alarm message to the printer.
● Checks the current time once per second.
– Between 5:00 P.M. and 7:00 A.M., the fan remains OFF.
– Between 7:00 A.M. and 5:00 P.M., the control program checks the current value of the temperature and sends the appropriate ON or OFF command to the fan starter.
If the ON command is issued, the TC Compact updates the value of the starter point in its memory to reflect the current state of the fan.
System Program The TC Compact contains a non-volatile system program called firmware, which can be upgraded in the field. The firmware is stored in Flash ROM memory, which keeps it virtually immune to all forms of power fluctuations or failure, including battery failure.
For more information on Flash ROM memory, see Memory [➙ 30].
General functionality of the firmware includes:
● Executing control programs.
● Communicating between other field panels and the workstation.
● Monitoring points.
● Managing point-related information.
● Keeping track of real time (both clock and calendar time).
● Executing self-test and error detection in the TC Compact.
License Manager License Manager adds applications or functionality to a field panel without the need to replace the hardware or perform a firmware flash. Field panels with Firmware Revision
3.1 or later support the License Management attribute.
Contact your Siemens Solution Partner, Authorized TALON Dealer for more information on applications and functionality that can be activated through License Manager.
License Manager Definitions
● A feature is an application or additional functionality that can be added to a field panel without the need to replace the hardware. Some features require a firmware flash.
● A license is the code provided by Siemens Industry to unlock a feature.
● The ID_STRING is a unique identifier that distinguishes an individual piece of hardware. It is composed of the panel's part number, revision, year and week of manufacture, and serial number. Therefore, a license for one field panel will not work on another field panel.
● An Entitlement contains the license(s) ordered.
● An Entitlement ID is the SAP Purchase Order number or Reference number from the Advanced Shipping notice and your 3 character organization code.
TALON Automation Networking
18 | 93
How does License Manager Work?
Field panels can either be ordered with licensed features and functionality pre-loaded, for example, FLN support, or upgraded to add special features, for example, TX-I/O island bus support.
The installation of some features and licenses require that the field panel be coldstarted, while others do not.
Any or all of the licensed features can be activated at any time using licenses acquired from Siemens.
When the field panel is powered, the firmware reviews the inventory of installed features, comparing that list to the License Vault, where all installed licenses are stored. Every feature with a corresponding license is initiated and run. Because licenses are loaded into non-volatile memory, powering down the field panel will not erase them.
TALON Automation Networking The following levels of networking provide varying levels of system integration in the TALON Automation System.
● Management Level Network (MLN)
● Automation Level Network (ALN)
● Field Level Network (FLN) These systems also use a number of network protocols that add functionality or provide support for third-party devices.
Management Level Network The Management Level Network (MLN) is the communications connection between individual TALON View workstations. It allows multiple TALON View users to access the entire TALON Automation System.
● An MLN is a TCP/IP Server-client network, and usually resides on the corporate
LAN.
● TALON Automation Systems without a TALON View workstation do not have a
Management Level Network.
Automation Level Network The TALON Automation Level Network (ALN) provides field panel-to-field panel and TALON View workstation-to-field panel communication. The ALN types are:
● BACnet/IP ALN
● BACnet Master-Slave/Token Passing (MS/TP) ALN
Simultaneous ALN Access More than one operator or field panel can access the network at one time. For example, as one operator accesses the system, another operator can access the system at another terminal (or from a remote site using a modem). This ensures that field panels can send alarm information to the alarm printer even as an operator accesses other information.
19 | 93
How Information Moves Through the Network When an operator issues a command over the ALN network through a field panel, that field panel validates the command, determines where to send it, and then passes the command to the destination over the network.
Example In the figure Commanding Over an Automation Level Network, the operator at the TALON View workstation, located in the lower level of the building, issues a command to control the main air-handling unit (AHU) of the building. This command is sent by the communication network to the field panel located on the top floor.
Figure 1: Figure. Commanding Over an Automation Level Network.
20 | 93
BACnet/IP Automation Level Network BACnet field panels communicate over a customer's Ethernet cabling and IP network using the ASHRAE Building Automation and Control Networking (BACnet) protocol.
● One TALON View workstation can administer up to 64 Ethernet-based BACnet/IP
ALNs.
● Up to 100 BACnet/IP field panels can reside on a BACnet/IP network (1000 maximum per TALON View workstation).
Figure 2: BACnet/IP ALN Network Example.
BACnet MS/TP Automation Level Network BACnet field panels communicate over a customer’s Ethernet cabling and IP network using the ASHRAE Building Automation and Control Networking (BACnet) MS/TP protocol.
● One TALON View workstation can administer up to 64 Ethernet based MS/TP
ALNs.
● Up to 10 BACnet MS/TP ALN field panels can reside on an MS/TP network segment (1000 maximum per TALON View workstation). Network segments must be physically separated.
● BACnet devices (field panels or TALON View workstations) can be set up as one of the following:
– A standard BACnet MS/TP device
– A BACnet Broadcast Management Device (BBMD)
– A foreign device
21 | 93
Figure 3: BACnet MS/TP ALN with MS/TP FLN Network Example.
Field Level Network The TALON Field Level Network (FLN) is a data communications network that passes information between an FLN device or devices and an Automation Level Network (ALN) device, usually within one building. FLNs consist of devices that communicate using MS/TP.
Chapter 2—Hardware Features 16- and 24-Point Compact Series Diagram 0
22 | 93
Chapter 2 describes the TC Compact Series components and functions, as well as the enclosure used for the TC field panel series. The following topics are discussed:
● Product Diagrams
● Supported Point Types
● Backup Batteries
● Memory
● Communication Connections
● 24 Vdc External Sensor Power Source
● TC Compact Series Specifications
● HOA (Hand-Off-Auto) Upgrade Kits
● Compact Series Smoke Control Application Requirements
● TX-I/O Product Range
● PX Series Enclosures and Service Boxes
16- and 24-Point Compact Series Diagram
The USB device port is now functional. It requires a computer device driver and standard computer terminal software, available on Standard Apps).
16- and 24-Point Compact Series Diagram 0
23 | 93
TC-16 and TC-24 Features and Symbols.
Terminal Block Connection Label Indicates
1 24V
Supply voltage, 24 Vac input.
2 System neutral.
Functional earth.
4 through 12 (TC-16) 4 through 18 (TC-24)
Digital Output relay.
A (22 through 24) + – RS-485 port.
B 10B/100B Ethernet port.
C USB Device port.
25, 27, 28 Universal Input (+) (UI1 through UI3).
26, 29 – Signal Common.
30, 31, 33, 34, 36 Universal Input/Output (+) (U4 through U8).
37, 39
24 Vdc external sensor power (+) source.
38, 40 – Signal Common.
41, 43, 44, 46 Universal Input/Output (+) TC-24 only (U9 through U12).
42, 45 – Signal Common (TC-24 only).
47, 49, 50, 52 Super Universal Input/Output (+) TC-24 only (X13 through X16).
48, 51 – Signal Common.
53, 55, 57 Analog Output (+) (TC-16: AO9 through AO11; TC-24: AO17 through AO19).
54, 56 - Signal Common.
58, 60 Digital Input (+)TC-16 only (DI12 through DI13).
59 – Signal Common (TC-16 only).
D HMI Human-Machine Interface port
TC-16 and TC-24 Status LEDs.
Status LED Label Indicates
RUN LED RUN (green) ON - Normal steady Green, unit is powered and running.
OFF - Error.
FAULT LED FAULT (red) (for future use)
Normal Off, not currently implemented. May be Red if processor does not complete boot.
LOW BATT LED LOW BATT (red) ON - Error.
OFF - Normal operation.
Ethernet COMM LED COMM (yellow) ON – Linked to Ethernet network.
Flashing indicates communicating with Ethernet network.
OFF - No link to Ethernet network.
RS-485 TX RS-485 TX
(yellow)
Flashing - Transmitting information over the RS-485 BACnet MS/TP ALN or MS/TP FLN (depending on how the port is defined).
36-Point Compact Series Product Diagram 0
24 | 93
TC-16 and TC-24 Status LEDs.
Status LED Label Indicates
OFF or ON solid - No device, no connection, or bad connection.
RS-485 RX RS-485 RX
(yellow)
Flashing - Receiving information over the RS-485 BACnet MS/TP ALN or MS/TP FLN (depending on how the port is defined).
OFF or ON solid - No device, no connection, or bad connection.
TC-16: DO 14 through DO 16; TC-24: DO 20 through DO 24
DO XX ON – Relay Energized.
36-Point Compact Series Product Diagram
TC-36 Features, Symbols, and Status LEDs.
1 24V
Supply voltage, 24 Vac input.
2 System neutral.
Functional earth.
4 through 27 Digital Output relay.
36-Point Compact Series Product Diagram 0
25 | 93
A 10B/100B Ethernet port.
B USB Device port.
30, 32, 33, 35, 36, 38 Super Universal (+). (X1 through X6)
31, 34, 37 – Signal Common.
39, 41, 50, 52, 53, 55, 56, 58, 59, 61, 62, 64, 65, 67, 68, 70, 71, 73
Universal Input/Output (+). (U7 through U24)
40, 51, 54, 57, 60, 63, 66, 69, 72 – Signal Common.
42, 44, 46, 48
24 Vdc external sensor power (+) source.
43, 45, 47, 49 – Signal Common.
74, 76, 77, 79 Digital Input (+). (DI25 through DI28)
75, 78 – Signal Common
82 through 84 CD CS Island Bus Communication
85 through 87 and 88 through 90 + – RS-485 port.
C USB Host port
D HMI Human-Machine Interface port
Status LEDs Label Indicates
RUN LED RUN (green) ON - Normal steady Green, unit is powered and running.
OFF - Error.
FAULT LED FAULT (red) (for future use)
Normal Off, not currently implemented. May be Red if processor does not complete boot.
LOW BATT LED LOW BATT (red) ON - Error.
OFF - Normal operation.
COMM LED COMM (yellow) ON – Linked to Ethernet network.
OFF - No link to Ethernet network.
Flashing indicates communicating with Ethernet network.
RS-485 TX A TX (yellow) Flashing - Transmitting information over MS/TP FLN.
B TX (yellow) Flashing - Transmitting information over BACnet MS/TP ALN (depending on how the port is defined).
A TX or B TX OFF or ON solid - No device, no connection, or bad connection.
RS-485 RX A RX (yellow) Flashing - Receiving information over MS/TP FLN.
B RX (yellow) Flashing - Receiving information over BACnet MS/TP ALN (depending on how the port is defined).
A RX or B RX OFF or ON solid - No device, no connection, or bad connection.
DO 29 through DO 36 DO XX ON - Relay Energized.
Supported Point Types 0
26 | 93
Supported Point Types The TC Compact Series provides software-configurable and dedicated points. The point types and their possible configurations are shown in the following tables.
TC-16 Supported Point Types.
Configurable Points Dedicated Points
Point Type Universal Input (UI) Points 1-3
Universal Input/Output (U) Points 4-8
Analog Output
(AO)
Points 9-11
Digital Input (DI) Points 12-13
Digital Output
(DO)
Points 14-16
Analog Input4)
Voltage 0 to 10 Vdc • •
Current 4 to 20 mA • •
RTD Pt 1K1) • •
RTD Ni 1K2) • •
Thermistor 10K NTC3) • •
Thermistor 100K NTC3)) • •
Digital Input
Status (Binary Input) • • •
Pulse Accumulator (Counter)
Analog Output
Voltage 0 to 10 Vdc • •
Digital Output
Binary/Digital Output •
1) Platinum 1K 375 or 385 alpha.
2) Siemens, Johnson Controls, and DIN Standard Nickel.
3) 10K and 100K Type 2 and 10K Type 3.
4) Sensor supply 24 Vdc, 4.8W
TC-24 Supported Point Types.
Point Type Universal Input (UI) Points 1-3
Universal Input/Output (U) Points 4-12
Super Universal (X) Points 13-16
Analog Output
(AO)
Points 17-19
Digital Output
(DO)
Points 20-24
Analog Input5)
Voltage 0 to 10 Vdc • • •
Current 4 to 20 mA • • •
RTD Pt 1K1) • • •
RTD Ni 1K2) • • •
Thermistor 10K NTC3) • • •
Thermistor 100K NTC3) • • •
Digital Input
Status (Binary Input) • • •
Pulse Accumulator (Counter)
Supported Point Types 0
27 | 93
TC-24 Supported Point Types.
Point Type Universal Input (UI) Points 1-3
Universal Input/Output (U) Points 4-12
Super Universal (X) Points 13-16
Analog Output
(AO)
Points 17-19
Digital Output
(DO)
Points 20-24
Analog Output
Voltage 0 to 10 Vdc • • •
Current 0 to 20 mA •
Digital Output
Binary/Digital Output •4) •
1) Platinum 1K 375 or 385 alpha.
2) Siemens, Johnson Controls, and DIN Standard Nickel.
3) 10K and 100K Type 2 and 10K Type 3.
4) Requires an external relay.
5) Sensor supply 24 Vdc, 4.8W
TC-36 Supported Point Types.
Point Type Super Universal (X) Points 1-6
Universal Input/Output (U) Points 7-24
Digital Input (DI) Points 25-28
Digital Output (DO) Points 29-36
Analog Input5)
Voltage 0 to 10 Vdc • •
Current 4 to 20 mA • •
RTD Pt 1K1) • •
RTD Ni 1K2) • •
Thermistor 10K NTC3) • •
Thermistor 100K NTC3) • •
Digital Input Status (Binary Input) • • •
Pulse Accumulator (Counter) • •
Analog Output
Voltage 0 to 10 Vdc • •
Current 0 to 20 mA •
Digital Output
Binary/Digital Output •4) •
1) Platinum 1K 375 or 385 alpha.
2) Siemens, Johnson Controls, and DIN Standard Nickel.
3) 10K and 100K Type 2 and 10K Type 3.
4) Requires an external relay.
5) Sensor supply 24 Vdc, 4.8W
Compact Series Backup Batteries 0
28 | 93
Compact Series Backup Batteries The TC Compact Series contains one non-rechargeable AA (LR6) battery and one non-rechargeable coin cell (BR2032) battery that serve as a power backup in the event of a power failure. The batteries only discharge during a power loss. They do not recharge.
Only use a 3.6 Volt lithium battery in TC Compact models with extended temperature range operation.
Only use a 1.5 Volt alkaline battery in standard TC Compact models.
• The 3.6 Volt lithium battery is designed to operate at both high and low temperature extremes, and it provides a long service life in an extended temperature environment.
• The 1.5 Volt alkaline battery is not guaranteed to provide backup protection in models with extended temperature range operation, even if the controller is operating in a room-temperature environment.
• If a 3.6 Volt lithium battery is used in standard TC Compact models, the battery quickly discharges and provides much less backup protection than a 1.5 Volt alkaline battery.
AA Battery
Batteries Failure to change DEAD alkaline battery will eventually result in battery leakage, causing permanent damage and loss of building control.
Failure to change a DEAD lithium battery will result in loss of trend and database if not backed up, causing loss of data or building control.
Establish a preventative maintenance schedule based on expected battery usage and life cycle.
● The AA battery maintains databases and volatile data, such as Trend, in RAM when power to the controller is off.
● If reserve power in the AA battery is low, the battery status is reported as LOW or DEAD and the red LOW BATT LED on the field panel is lit. When this occurs, replace the battery; do not wait until it goes dead.
● Using PPCL and the $BATT point, the TC Compact can be programmed to signal an alarm printer and an operator terminal with a battery replacement message.
For more information, see the TALON Powers Process Control Language (PPCL) User's Manual (588-583).
Compact Series Backup Batteries 0
29 | 93
Using Auto Restore and Database Backup to Flash
● RAM is cleared if the AA battery is dead, disabled, or missing when power to the field panel is off. In this case, if Auto Restore and Database Backup to Flash have been enabled, the database reloads in RAM when power returns; however, Trend data is lost.
● If a power failure lasts longer than the protection offered by the battery, and Auto Restore and Database Backup to Flash are not enabled, the information stored in RAM must be either reloaded from a TALON View workstation, Datamate Base or Datamate Advanced, or entered again by an operator.
Coin Cell Battery
Batteries Failure to change a DEAD lithium coin cell battery will result in loss of current time-date, which may cause loss of data or building control.
Establish a preventative maintenance schedule based on expected battery usage and life cycle.
● The coin cell battery maintains the current time-date in the Real Time Clock (RTC) when power to the field panel is off.
● There is no physical status on the field panel for a dead coin cell battery.
● If the coin cell battery is dead or missing when power is off, then RTC time-date is reset as follows:
– If the field panel resides on an ALN with a TALON View workstation, the
TALON View workstation sets the time-date when the field panel returns to the network.
– If the field panel resides on an ALN without a TALON View workstation, the time-date is synchronized with the network time during the next automatic daily time update.
For more information on time synchronization, see the TALON Firmware User's Manual (588-580) (588-580).
Memory 0
30 | 93
Memory Size and Typical Battery Backup Time
Memory Size and Typical Battery Backup Time.
Compact Model RAM Flash ROM Total Memory Typical Battery Backup RAM and Real Time Clock Data1
TC-16 and TC-24 16 MB 8 MB 24 MB Non-rooftop models: 180 days (accumulated) Rooftop models: 330 days (accumulated)
TC-16 and TC-24 “F” and “F32”
32 MB 8 MB 40 MB Non-rooftop models (accumulated):
110 days (accumulated) Rooftop models: (accumulated):
200 days (accumulated)
TC-36 64 MB 16 MB 80 MB 60 days (accumulated)
1) Installing a coin cell battery provides up to 10 years backup power of the Real Time Clock for non-rooftop applications, and 18 months backup power for rooftop applications. These are typical accumulated times while power is off.
Memory The TALON firmware (program), its point database, PPCL program, trend data, and other information reside in the field panel memory. Memory consists of two areas:
Flash Read-Only Memory (Flash ROM) and Random Access Memory (RAM).
Flash Read-Only Memory (Flash ROM) Flash Read-Only Memory (Flash ROM) is the non-volatile, permanent memory of the TC Compact, which stores the operating system, the TALON firmware, and the language files. A limited amount of secondary storage is provided in Electrically Erasable Programmable Read-Only Memory (EEPROM) for the field panel address or name, communication speeds, and other set-up parameters. In the event of a power surge, a power loss, or failure of the battery backup, the Flash ROM and EEPROM contents stay intact.
TC Compact Flash ROM size cannot be upgraded in the field.
Compressed ROM The TC Compact has a large amount of high performance RAM. To allow for future features and to provide high system performance, the TALON firmware is stored in ROM in a compressed state; it is de-compressed into RAM on system power-up. As a result, the entire onboard RAM is not available for the point database, the PPCL program, and trend data.
Auto-Restore and Database Backup to Flash TALON Firmware Revision 3.1 and later supports Auto-Restore and Database Backup to Flash.
● Database Backup to Flash allows the user to manually save a copy of the database in flash memory of the controller.
● The field panel may be configured to automatically restore the database from flash memory after a coldstart.
Memory 0
31 | 93
– When auto-restore is enabled, a coldstart does not result in the same downtime as with earlier revisions of TALON firmware. Because there is no waiting on a full download from the backup system, the database is restored from flash so quickly that there is little to no downtime. However, the accumulated trend data is deleted from memory.
– Database restoration from flash is disabled by default.
– When FLN Mode is selected for the PXC Compact or UEC, database restoration from flash is automatically enabled.
● The field panel may be configured to automatically restore the database from flash memory after a coldstart.
– When auto-restore is enabled, a coldstart does not result in the same downtime as with earlier revisions of TALON firmware. Because there is no waiting on a full download from the backup system, the database is restored from flash so quickly that there is little to no downtime. However, the accumulated trend data is deleted from memory.
– Database restoration from flash is disabled by default.
For procedures on using Auto-Restore and Database Backup to Flash, see the TALON Firmware User's Manual (588-580).
Auto Save This feature allows the database to be backed up automatically whenever database is changed, instead of being an operator selected function. It does not provide any safeguard and or protection against power loss while the process is underway.
However, this feature sends messages to HMI that the auto save operation is in progress or finished.
The feature may be turned on or off using a prompt similar to the existing Autorestore prompt. See the TALON Firmware User's Manual (588-580) for more information.
File System Operations File System Operations provide many features and works on three drives of a field panel.
The following is a list of supported features:
● List Drives — list the drives on the field panel where A: is the RAM drive, B: is the
USB drive if attached, and IFD: is the internal Flash Drive.
● Set_drive — identifies the drive that you want to perform other functions on.
● listDirectory — lists the files and folders contained on the selected drive.
● Change_dir — changes the current directory to allow you to view the contents of subfolders on the drive.
● File_ops — opens up the file control menu which allows you to copy, rename, delete and move files in the panel. These functions work on the drive that was selected by the Set_drive function.
● File_ops/Copy_file — allows you to copy files within a drive or to another drive.
● File_ops/Rename_file — allows you to rename a file.
● File_ops/Move_file — allows you to move a file within a drive or to another drive.
● File_ops/Delete_file — allows you to delete a file.
USB Media Support
● Support for USB mass storage devices (Memory sticks or USB hard drives).
● Backup of database, storage for graphics, Web Server upgrades
Communication Connections 0
32 | 93
Random Access Memory (RAM) Synchronous Dynamic Random Access Memory (SDRAM) is the working memory of the TC Compact. When the TC Compact has booted and is operating normally, the TALON firmware, the PPCL control program, the point database, and trend data have been transferred from Flash ROM. Information stored in RAM, such as the point database or PPCL, may be viewed, modified, deleted, activated, or deactivated from an operator terminal by any high-level authorized user. In the event of a power loss, the contents of RAM are kept intact by a backup battery.
TC Compact RAM size cannot be upgraded in the field.
The program length, number of database points, and number of trend entries is limited only by available memory.
Communication Connections The TC Compact Series provides the following communication connections:
● HMI and Tool ports
● 10B/100B Ethernet port
● RS-485 port
● USB Host Port
● TX-I/O Island Bus (TC-36 only)
In BACnet/IP ALN mode, RS-485 parameters are displayed and may be entered as a selection. However, when in RS-485 ALN mode, BACnet/IP ALN parameters are not an available selection.
HMI and Tool Ports
● The HMI port provides a connection to a laptop computer for local operation and engineering.
● The USB Device port supports a generic serial interface for an HMI or Tool connection.
Human-Machine Interface (HMI)/Tool Port The Human-Machine Interface (HMI)/Tool port provides RS-232 compliant communications through a quick-connect RJ-45 jack. The HMI port supports the following functionality:
● Connecting a machine interface device, such as an operator terminal or a text-based operator terminal, to the TC Compact.
● Executing firmware flash upgrades.
● 1200 bps to 115.2 Kbps communication is supported.
The communication speed of the port must match the communication speed of the device connected to it.
Communication Connections 0
33 | 93
USB Device Port The USB Device port supports a generic serial interface for an HMI or Tool device. The USB Device port does not support firmware flash upgrades.
10B/100B Ethernet Port The 10B/100B Ethernet port provides a path for commands and information transmitted between field panels inside a firewall. This port provides both full- and half-duplex 10Base-T or 100Base-TX compliant communications over a BACnet/IP Automation Level Network (ALN). The highest possible communication speed is automatically detected and selected.
RS-485 Port The RS-485 port provides a path for commands and information transmitted between field panels. This port provides communications over a BACnet MS/TP Automation Level Network (ALN) or MS/TP Field Level Network (FLN). The communication speed is set during startup.
The RS-485 port provides half-duplex, asynchronous serial RS-485 communications over shielded twisted pair cable. The RS-485 connector is labeled + – to indicate the positive and negative connections; is a reference pin.
● The TC-36 provides two RS-485 ports, which are labeled “A” and “B”.
● All TC-36 models and the TC-16 and TC-24 "F" models support MS/TP FLN devices on the RS-485 port.
● BACnet MS/TP routed FLN is supported for Programmable TECs (PTECs), Unitary
Equipment Controllers (UECs), and third-party BACnet devices.
– FIN Builder supports MS/TP routed FLNs and IP FLNs.
– PPCL and Point Editing are currently not available on routed FLNs.
TC-36 RS-485 A and B Ports The following table outlines the configuration options for the TC-36 RS-485 “A“ and “B“ ports.
ALN Protocol RS-485 A Port (FLN 1) RS-485 B Port (FLN 2)
BACnet/IP MS/TP FLN Not available
BACnet MS/TP MS/TP FLN Configured for MS/TP ALN
USB Host Port The USB host port supports a USB printer and connection to a modem through a USB-to-RS-232 adapter. A USB hub may be used to support both a printer and modem on the USB host port.
● On a BACnet/IP ALN, the USB Host port provides support for service modems and line printers.
HOA (Hand-Off-Auto) Upgrade Kits 0
34 | 93
TX-I/O Island Bus The TC-36 offers the flexibility of expanding the total point count through a self-forming island bus. With the addition of TX-I/O modules and a TX-I/O Power Supply, up to 16 points (or four TX-I/O modules) can be supported.
An additional license may be required to enable the Island Bus.
Compact Series Smoke Control Application Requirements
The 115V or 230V PX Series Service Box is required…