ATTACHMENT 6 MODERNIZATION DRAWINGS SET 2.pdf

PDF 34 MB Posted

Attached to
BARC Elevator Assessment and Modernization Federal contract opportunity
Solicitation number
12305B24R0033
Issued by
Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery Northeast Area

About this file

This document is a set of modernization drawings related to a federal contract opportunity for the Elevator Modernization at the Beltsville Agricultural Research Center (BARC) in Beltsville, MD. The associated federal contract opportunity, Solicitation 12305B24R0033, is a Request for Proposals (RFP) issued by the United States Department of Agriculture (USDA) Agricultural Research Service (ARS) Northeast Area. The requirement is for elevator modernization at the BARC facility, with a construction magnitude between $1,000,000 to $5,000,000. The period of performance is 275 days for one elevator or 520 days if multiple elevators are awarded, with the start of each additional elevator overlapping the previous by 2 months. The solicitation is a total small business set-aside with NAICS code 238290. Offerors are encouraged to attend a site visit on August 8, 2024 to observe existing conditions.

View the file

Other files for this federal contract opportunity

Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

THIRD FLOOR PLAN

SCALE: 1/16"=1'-0"

PLAN

NORTH

M-105

0' 2' 4' 8' 12'

SCALE: 1/4"=1'-0"

ELEVATOR MACHINE ROOM

SCALE: 1/4"=1'-0"

PLAN

NORTH

M-105

M-105

ELEVATOR

ELEVATOR EQUIPMENT

0' 48'

SCALE: 1/16"=1'-0"

16'8' 32'

PPM

REVISIONS

DESCRIPTION

SHEET

DATE

U

NO.

D

REAL PROPERTY

SAFETY & HEALTH

A

SUSDA

BY

OF

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

EPM

USDA ARS

NORTHEAST AREA

BELTSVILLE, MARYLAND

Agricultural

Service Research

USDA AGRICULTURAL RESEARCH SERVICE

BELTSVILLE AGRICULTURAL RESEARCH CENTER (BARC)

ELEVATOR MODERNIZATION - BELTSVILLE, MD

SME

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

P.A.

FIRMJohnson-McAdamsTHE

CLR

JGM

7523-A

--- 04/30/24

DATE

PROJECT NO.

A-E FIRM

ELEVATOR 005 | BUILDING 007 | #1

MECHANICAL PLAN

M-105

IDU-5

1. ALL PENETRATIONS OF FLOORS, WALLS, AND

CEILING FOR REFRIGERANT PIPING AND

CONTROLS WIRING SHALL BE SEALED WITH

2-HOUR MINIMUM FIRESTOPPING.

GENERAL NOTES

1. INSTALL CONDENSING UNIT IN EXISTING

MECHANICAL ROOM.

2. INSTALL WALL-MOUNTED UNIT 6'-8" ABOVE

FINISH FLOOR.

KEYED NOTES

EXIST.

SERVICE SINK

ROUTE 3/4" CONDENSATE ALONG EXISTING

I-BEAM BEFORE ROUTING DOWN WALL TO

CONNECTION TO EXISTING SANITARY PIPING.

CU-5

LEGEND:

POINT OF CONNECTION

THERMOSTAT

PPM

REVISIONS

DESCRIPTION

SHEET

DATE

U

NO.

D

REAL PROPERTY

SAFETY & HEALTH

A

SUSDA

BY

OF

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

EPM

USDA ARS

NORTHEAST AREA

BELTSVILLE, MARYLAND

Agricultural

Service Research

USDA AGRICULTURAL RESEARCH SERVICE

BELTSVILLE AGRICULTURAL RESEARCH CENTER (BARC)

ELEVATOR MODERNIZATION - BELTSVILLE, MD

SME

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

P.A.

FIRMJohnson-McAdamsTHE

CLR

JGM

7523-A

--- 04/30/24

DATE

PROJECT NO.

A-E FIRM

BUILDING 007 MECHANICAL DETAILS

M-501

MIN

MIN

3.5"

2" MIN

6.5"

DRAIN PAN

UNION

PITCH DOWN TOWARD FLOOR

DRAIN. SPILL AT FLOOR DRAIN.

UNION FOR DRAINING

CLEAN OUT

DRAIN LINE SHALL BE AT LEAST THE

SAME SIZE AS THE NIPPLE ON THE

DRAIN PAN. SEE PLANS FOR SIZES.

SCALE:

CONDENSATE DRAIN P-TRAP DETAIL

NOT TO SCALE

M-501

PLAN

ELEVATION

SCALE:

DUCTLESS WALL MOUNT UNIT DETAIL

NOT TO SCALE

M-501

BACK LEFT PIPE

BOTTOM LEFT

PIPE

BACK RIGHT

PIPE

BOTTOM RIGHT

PIPE

GROUNDING TERMINAL

AIR OUTLET

PIPING AND WIRING INTAKE

DRAIN HOSE

LIQUID PIPE

GAS PIPE

LEFT SIDE PIPE

CONNECTION

HOLE

FRONT GRILLE

PIPING AND WIRING INTAKE

3-1/8Ø HOLE

FULL OPEN FRONT PANEL

FIELD INSTALLED

CONDENSATE PUMP

EQUAL TO

RECTORSEAL 83939

FIELD INSTALLED

CONDENSATE PUMP

EQUAL TO

RECTORSEAL 83939

GROUNDING TERMINAL

POWER CORD ROUTING HOLE

(KNOCK-OUT

HOLE)

SCALE:

CONDENSING UNIT DETAIL

NOT TO SCALE

M-501

CONCRETE PAD (MIN. 6" THICK

AND MIN. 6" WIDER THAN

EQUIPMENT EACH END AND 12"

WIDER FRONT AND BACK)

REFRIGERANT PIPING

1/2" CHAMFER

ALL SIDES

WALL COVER INLET FASTENED TO

WALL PER MANUFACTURER'S

INSTALLATION INSTRUCTIONS

REFRIGERANT PIPING AND

WIRING INSTALLED IN LINE SET

COVER

WALL COVER BASE WITH TOP PVC

COVER REMOVED

COUPLINGS USED TO

LENGTHEN AND EXTEND

TUBES (TYP.)

OUTDOOR PVC (WEATHER AND

UV RESISTANT) LINE SET

COVERING SECURED TO

BUILDING EXTERIOR WALL PER

MANUFACTURER'S INSTALLATION

INSTRUCTIONS

90 DEGREE ELBOWS AS

REQUIRED (TYP.)

END SOCKET USED TO

ACCOMMODATE VARIOUS LINE

SET COMBINATIONS. ROUTE TO

WITH 12" OF OUTDOOR

CONDENSING UNIT.

REFRIGERANT PIPING AND

WIRING TO OUTDOOR

CONDENSING UNIT.

SCALE:

TYPICAL REFRIGERANT PIPING LINE SET

OUTSIDE INSTALLATION DETAIL

NOT TO SCALE

M-501

CONCRETE PAD (MIN. 6" THICK

AND MIN. 6" WIDER THAN

EQUIPMENT EACH END AND 12"

WIDER FRONT AND BACK)

NOTE:

INSULATE ALL CONDENSATE PIPING.

PPM

REVISIONS

DESCRIPTION

SHEET

DATE

U

NO.

D

REAL PROPERTY

SAFETY & HEALTH

A

SUSDA

BY

OF

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

EPM

USDA ARS

NORTHEAST AREA

BELTSVILLE, MARYLAND

Agricultural

Service Research

USDA AGRICULTURAL RESEARCH SERVICE

BELTSVILLE AGRICULTURAL RESEARCH CENTER (BARC)

ELEVATOR MODERNIZATION - BELTSVILLE, MD

SME

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

P.A.

FIRMJohnson-McAdamsTHE

CLR

JGM

7523-A

--- 04/30/24

DATE

PROJECT NO.

A-E FIRM

BUILDING 007 MECHANICAL

SCHEDULES AND CONTROLS

DIAGRAM

M-601

INDOOR HVAC UNIT SCHEDULE

MARK

ELEVATOR

MACHINE ROOM

SERVED

BASIS OF DESIGN

SYSTEM

TYPE

NOMINAL

TONNAGE TYPE OUTDOOR

UNIT

SUPPLY FAN

AIR FLOW RATE

(CFM)

COOLING CAPACITY DIMENSIONS

H x W x D

(INCHES)

WEIGHT

(LB) NOTES

MANUFACTURER MODEL NO. TOTAL

BTU/HR

SENSIBLE

BTU/HR

ENTERING AIR

DB (°F ) WB (°F )

IDU-5 005 DAIKIN FTKB09AXVJU 1 ZONE

MINISPLIT 0.75 WALL MOUNT CU-5 330 8,800 7,165 80 67 11-11/16 x 35-1/16 x

8-1/4 20 ALL

AIR-COOLED CONDENSING UNIT SCHEDULE

MARK

BASIS OF DESIGN

SYSTEM

TYPE

NOMINAL

TONNAGE

COOLING CAPACITY REFRIGERANT DATA SYSTEM ELECTRICAL DATA

DIMENSIONS

HxWxD

(INCHES)

WEIGHT

(LB) SEER / EER NOTES

MANUFACTURER MODEL

NO. BTU/HR

AMBIENT

DESIGN

DRY BULB

(°F)

TYPE

FACTORY

CHARGE

(LB)

ADD'L

CHARGE

(LB)

VOLTAGE MCA MOP

CU-5 DAIKIN RKB09AXVJU 1 ZONE

MINISPLIT 0.75 8,800 95 R410A 1.625 N/A 208-230V/1 6.95 15 21-5/8 x 25-15/16 x 10-3/4 53 17 / 11 ALL

NOTES

1. MANUFACTURER MUST BE CERTIFIED, LISTED, AND LABELED PER AHRI 1230.

2. SYSTEM RATING DATA BASED ON DESIGN AMBIENT CONDITIONS FOR COOLING AND FOR HEATING.

3. MODULATING INVERTER COMPRESSORS.

4. MANUFACTURER'S SUBMITTAL MUST INCLUDE REFRIGERANT PIPING DIAGRAM WITH PIPE DIAMETERS, LENGTHS, AND REFRIGERANT VOLUME.

5. CONTRACTOR TO VERIFY PIPING DIMENSIONS.

6. CONTRACTOR TO FURNISH AND INSTALL INSULATION ON ALL REFRIGERANT PIPING AND FITTINGS.

7. 10 YEARS PARTS WARRANTY.

8. BASIS OF DESIGN: DAIKIN. NOTE: EQUIPMENT SHOWN IN THE SCHEDULE IS SHOWN TO ESTABLISH A STANDARD OF QUALITY, NOT TO LIMIT

COMPETITION. EQUIVALENT EQUIPMENT OF OTHER MANUFACTURERS SHALL BE ACCEPTABLE.

NOTES

1. PROVIDE CONDENSATE PUMP.

2. 10 YEAR PARTS WARRANTY.

3. BASIS OF DESIGN: DAIKIN. NOTE: EQUIPMENT SHOWN IN THE SCHEDULE IS SHOWN TO ESTABLISH A STANDARD OF

QUALITY, NOT TO LIMIT COMPETITION. EQUIVALENT EQUIPMENT OF OTHER MANUFACTURERS SHALL BE ACCEPTABLE.

SCALE:

AIR CONDITIONER CONTROLS

NTS

DDC

ZN-T

ZN-T-SP

ZN-T-HL

ZN-T-LL

FUNCTION

PROOFS

& SAFETIES

NOTES:

1. THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS INDICATED IN THE SPECIFICATION AND IN ACCORDANCE WITH THIS DRAWING.

POINT NAME DESCRIPTION

SETTING

(WITH UNITS)

RANGE

(WITH UNITS)

IO

TYPE

ALARM CONDITION

(SEE NOTES)

ALARM

PRIORITY

ALARMING

ZONE TEMPERATURE

CONTROL

ZN-T

ZN-T-SP

ZONE TEMPERATURE

ZONE TEMPERATURE SET POINT

-- 40 TO 100 DEG F AI

AI55 DEG F HEATING (ADJ)

68 DEG F COOLING (ADJ)

ZN-T-HL ZONE TEMPERATURE HIGH LIMIT 80°F 40 TO 100 DEG F AI

ZN-T-LL ZONE TEMPERATURE LOW LIMIT 40 TO 100 DEG F AI45°F

ZONE TEMPERATURE ABOVE HIGH LIMIT

ZONE TEMPERATURE BELOW LOW LIMIT

CRITICAL

CRITICAL

SEQUENCE OF OPERATION

CONTROL OF IDU-5

1. AIR CONDITIONERS SHALL BE AVAILABLE AT ALL TIMES AND SHALL NOT BE

SUBJECT TO ANY OCCUPANCY SCHEDULES.

2. AIR CONDITIONERS SHALL OPERATE BASED ON SPACE THERMOSTAT AND

SHALL SWAP FROM COOLING TO HEATING MODE BASED ON THERMOSTAT

SET POINTS. AIR CONDITIONER SHALL NOT BE CONNECTED TO THE BAS

DIRECTLY BUT SHALL BE MONITORED VIA THE IN ROOM THERMOSTAT.

GENERAL NOTES:

A. INFORMATION SHOWN ON THE DEMOLITION DRAWINGS IS BASED ON

THE BEST INFORMATION AVAILABLE AT THE TIME OF DESIGN.

PERFORM A COMPREHENSIVE SITE SURVEY PRIOR TO SUBMITTING

ELECTRICAL BROCHURES FOR REVIEW, AND MAKE NECESSARY

ADJUSTMENTS TO FACILITATE THE WORK.

B. EACH ELEVATOR IN THIS PROJECT IS CONNECTED TO A TELEPHONE

LINE FOR THE EMERGENCY CALL FUNCTIONALITY. THESE

TELEPHONE LINES SHALL BE DEMOLISHED ALONG WITH ALL

RACEWAYS AND CIRCUITRY BACK TO THE TELEPHONE BACKBOARD

AT WHICH THEY ARE CONNECTED. ALLOW DEMOLITION PRICE OF 300

FEET OF 1" CONDUIT CONTAINING ONE CAT 3 TELEPHONE CABLE FOR

EACH ELEVATOR.

C. DO NOT DEMOLISH ANY CEILINGS TO ACCOMPLISH DEMOLITION OF

RACEWAYS. WHERE RACEWAYS RUN ABOVE HARD CEILINGS,

DEMOLISH THE CABLES AND LEAVE THE CONDUITS ABOVE THE HARD

CEILINGS. REPAIR ALL OPENINGS IN CEILINGS TO MATCH EXISTING

CONSTRUCTION.

D. ALL RECEPTACLES IN ELEVATOR EQUIPMENT ROOMS AND IN

ELEVATOR PITS MUST BE DEMOLISHED UNLESS OTHERWISE NOTED.

PROVIDE NEW AS SHOWN ON NEW WORK DRAWINGS.

E. ALL LIGHT FIXTURES IN ELEVATOR EQUIPMENT ROOMS AND IN

ELEVATOR PITS MUST BE REPLACED WITH NEW FIXTURES AS SHOWN

ON NEW WORK DRAWINGS. ALL EXISTING CIRCUITRY MUST BE

DEMOLISHED BACK TO THE PANELBOARD OR THE NEAREST COMMON

JUNCTION BOX TO OTHER FIXTURES ON THE CIRCUIT.

F. ALL ELEVATOR DISCONNECTS AND POWER CIRCUIT BREAKERS IN

ELEVATOR EQUIPMENT ROOMS MUST BE REPLACED WITH THE NEW

EQUIPMENT SHOWN ON THE NEW WORK DRAWINGS.

G. ALL ELEVATOR PIT LIGHTS, PIT RECEPTACLES, AND SUMP PUMP

CONNECTIONS MUST BE DEMOLISHED. DEMOLISH ALL DEVICES,

BOXES, EQUIPMENT, RACEWAYS, AND CIRCUITRY, AND REPLACE WITH

NEW EQUIPMENT AS SHOWN ON NEW WORK PLANS.

H. ALL UNUSED ELECTRICAL EQUIPMENT, RACEWAYS, AND CIRCUITRY

MUST BE DEMOLISHED FROM ALL ELEVATOR EQUIPMENT ROOMS,

HOISTWAYS, AND PITS BACK TO THE PANEL OF ORIGINATION OR THE

NEAREST COMMON JUNCTION BOX TO OTHER EQUIPMENT ON THAT

CIRCUIT.

I. DEMOLISH ALL CONNECTIONS TO MECHANICAL EQUIPMENT THAT IS

BEING DEMOLISHED, INCLUDING ALL DISCONNECTS, MOTOR

STARTERS, RACEWAYS, CIRCUITRY, ETC. BACK TO THE PANEL OF

ORIGINATION.

J. ALL CONDUIT OPENINGS IN JUNCTION BOXES AND PANELBOARDS

SHALL BE PLUGGED WITH MATERIAL AS SUBSTANTIAL AS THE WALL

OF THE ENCLOSURE IN ACCORDANCE WITH NATIONAL ELECTRICAL

CODE (NEC) REQUIREMENTS.

K. ALL LIGHTING AND RECEPTACLE STYLE PANELBOARDS AFFECTED BY

THE WORK MUST HAVE UPDATED TYPED CIRCUIT DIRECTORIES.

L. ALL SWITCHBOARDS AND POWER STYLE PANELBOARDS AFFECTED BY

THE WORK MUST HAVE NEW ENGRAVED PHENOLIC NAMEPLATES TO

IDENTIFY CIRCUIT CHANGES.

M. ALL PENETRATIONS OF FLOORS, WALLS, AND CEILINGS SHALL BE

SEALED WITH MINIMUM 2-HOUR FIRESTOPPING.

PPM

REVISIONS

DESCRIPTION

SHEET

DATE

U

NO.

D

REAL PROPERTY

SAFETY & HEALTH

A

SUSDA

BY

OF

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

EPM

USDA ARS

NORTHEAST AREA

BELTSVILLE, MARYLAND

Agricultural

Service Research

USDA AGRICULTURAL RESEARCH SERVICE

BELTSVILLE AGRICULTURAL RESEARCH CENTER (BARC)

ELEVATOR MODERNIZATION - BELTSVILLE, MD

GAC

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

P.A.

FIRMJohnson-McAdamsTHE

CLR

JGM

7523-A

--- 04/30/24

DATE

PROJECT NO.

A-E FIRM

"PROFESSIONAL

CERTIFICATION. I HEREBY

CERTIFY THAT THESE

DOCUMENTS WERE

PREPARED OR APPROVED BY

ME, AND THAT I AM DULY

LICENSED PROFESSIONAL

ENGINEER UNDER THE LAWS

OF THE STATE OF MARYLAND,

LICENSE NO. , EXPIRATION

DATE: 2/24/2025."

ELECTRICAL DEMOLITION LEGEND

ED-000

LEGEND

DISCONNECT (A.K.A. SAFETY SWITCH) TO BE DEMOLISHED. TEXT INDICATES AMPACITY/NUMBER OF POLES/NEMA

ENCLOSURE TYPE.

XX/X/X

ENCLOSED CIRCUIT BREAKER TO BE DEMOLISHED. TEXT INDICATES AMPACITY/NUMBER OF POLES/NEMA ENCLOSURE

TYPE.

S

COMBINATION DISCONNECT AND MAGNETIC MOTOR STARTER TO BE DEMOLISHED.

DUPLEX RECEPTACLE TO BE DEMOLISHED AND REPLACED WITH A NEW GFCI NEMA 5-20R RECEPTACLE CONNECTED TO

EXISTING CIRCUITRY.

SINGLE-POLE SWITCH TO BE DEMOLISHED.

4 FOOT LONG SURFACE OR SUSPENDED LIGHT FIXTURE TO BE DEMOLISHED.

XX

AT

S

T

XX/X/X

WALL-MOUNTED LIGHT FIXTURE TO BE DEMOLISHED.

MOTOR TO BE DEMOLISHED. TEXT INDICATES HORSEPOWER RATING.

OMCS OIL MINDER CONTROL SYSTEM TO REMAIN.

PANELBOARD TO REMAIN. TEXT INDICATES PANELBOARD DESIGNATION.

SWBD SWITCHBOARD TO REMAIN. TEXT INDICATES PANELBOARD DESIGNATION IF LABELED, OR JUST THE ABBREVIATION FOR

SWITCHBOARD "SWBD" IF NOT LABELED WITH A NAME DESIGNATION.

AUTOMATIC TRANSFER SWITCH TO REMAIN.

DISCONNECT (A.K.A. SAFETY SWITCH) TO REMAIN. TEXT INDICATES AMPACITY/NUMBER OF POLES/NEMA ENCLOSURE

TYPE.

TRANSFORMER TO REMAIN.

ENCLOSED CIRCUIT BREAKER TO BE DEMOLISHED. TEXT INDICATES AMPACITY/NUMBER OF POLES/NEMA ENCLOSURE

TYPE.

XX/X/X

TELEPHONE OUTLET TO REMAIN.

COMBINATION TELEPHONE AND DATA OUTLET TO REMAIN.

PANELBOARD TO BE DEMOLISHED AND REPLACED WITH NEW PANELBOARD AS SHOWN ON NEW WORK DRAWINGS. TEXT

INDICATES PANELBOARD NAME DESIGNATION.

XX/X/X

XXX

DATA ROOM

MSB1

SW

BD

S

SPMP

ELEVATOR

EQUIPMENT TO BE

REPLACED

0/

3/

/2

/1

DISC. FOR CAB

LIGHTS &

ELEVATOR

CONTROLS

ELEVATOR

POWER

DISCONNECT

S

30/2/1

EP-2

DISC. FED FROM

EP-2, CIRCUIT #20

ME

LOWEST LEVEL FLOOR PLAN (BASEMENT)

SCALE: 1/8"=1'-0"

PLAN

NORTH

ED-105

0' 2' 4' 8' 12'

SCALE: 1/4"=1'-0"

GENERAL NOTES:

ELEVATOR MACHINE ROOM (IN ATTIC)

SCALE: 1/4"=1'-0"

PLAN

NORTH

ED-105

0' 24'

SCALE: 1/8"=1'-0"

8'4' 16'

PPM

REVISIONS

DESCRIPTION

SHEET

DATE

U

NO.

D

REAL PROPERTY

SAFETY & HEALTH

A

SUSDA

BY

OF

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

EPM

USDA ARS

NORTHEAST AREA

BELTSVILLE, MARYLAND

Agricultural

Service Research

USDA AGRICULTURAL RESEARCH SERVICE

BELTSVILLE AGRICULTURAL RESEARCH CENTER (BARC)

ELEVATOR MODERNIZATION - BELTSVILLE, MD

GAC

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

P.A.

FIRMJohnson-McAdamsTHE

CLR

JGM

7523-A

--- 04/30/24

DATE

PROJECT NO.

A-E FIRM

"PROFESSIONAL

CERTIFICATION. I HEREBY

CERTIFY THAT THESE

DOCUMENTS WERE

PREPARED OR APPROVED BY

ME, AND THAT I AM DULY

LICENSED PROFESSIONAL

ENGINEER UNDER THE LAWS

OF THE STATE OF MARYLAND,

LICENSE NO. , EXPIRATION

DATE: 2/24/2025."

ELEVATOR 005 | BUILDING 007| #1

ELECTRICAL DEMOLITION PLAN

ED-105

A. CERTAIN PANELS ARE SHOWN FOR GENERAL INFORMATION WHICH

MAY NOT BE AFFECTED BY THIS PROJECT.

KEYED NOTES:

1. THE ELEVATOR IS FED FROM A 200/3 EATON HFDE CIRCUIT BREAKER

IN SECTION 3 OF MSB1 IN ELECTRICAL ROOM 002. RETAIN CONDUIT,

CIRCUITRY, AND BREAKER IN MSB1. DEMOLISH 200/3 DISCONNECT IN

THE ELEVATOR EQUIPMENT ROOM, AND REPLACE IT WITH THE NEW

EQUIPMENT SHOWN ON NEW WORK DRAWINGS.

2. ASSUME FOR BIDDING THAT THE ELEVATOR CAB LIGHTS ARE FED

FROM PANEL P-2. WE WERE UNABLE TO DETERMINE FROM THE SITE

SURVEY AND OLD DRAWINGS THE SOURCE OF THE CIRCUITRY.

DEMOLISH THE CONDUIT AND CIRCUITRY BACK TO PANEL P-2 CUT

OFF THE BREAKER, AND LABEL IT AS SPARE.

3. DEMOLISH DISCONNECT, CONDUIT, AND CIRCUITRY BACK TO PANEL

P-2. CUT OFF THE BREAKER, AND LABEL IT AS SPARE. ALSO

DEMOLISH CONDUIT, CIRCUITRY, AND CONNECTION TO LOADS

DOWNSTREAM OF DISCONNECT.

4. DEMOLISH PIT LIGHT ALONG WITH SWITCH, PIT MAINTENANCE

RECEPTACLE, AND PIT SUMP PUMP RECEPTACLE. DEMOLISH ALL

ASSOCIATED DEVICES, BOXES, CONDUITS, AND CIRCUITRY BACK TO

THE PANEL OF ORIGINATION. CUT OFF THE BREAKER AND LABEL IT

AS SPARE. ASSUME FOR BIDDING THAT THE EQUIPMENT IS FED FROM

PANEL P-2 IN THE ATTIC.

XXX

AT

S

SWBD

LEGEND (EXISTING-TO-REMAIN EQUIPMENT)

SWITCHBOARD

AUTOMATIC TRANSFER SWITCH

PANELBOARD

LEGEND (NEW EQUIPMENT AND CIRCUITRY)

T TRANSFORMER

COMBINATION TELEPHONE AND DATA OUTLET

TELEPHONE OUTLET

XXX PANELBOARD

ED ELEVATOR DISCONNECT POWER MODULE SWITCH. REQUIRED FEATURES ARE DESCRIBED ON SHEET E-001.

CL

30/2/1

30A, 2-POLE, FUSED HEAVY-DUTY SAFETY SWITCH IN NEMA 1 ENCLOSURE CONTAINING ONE 20A FUSE - SERVED BY A

20A, 1-POLE CIRCUIT. "CL" INDICATES THAT IT SERVES THE CAB LIGHTS.

CNTRL

30/2/1

30A, 2-POLE, FUSED HEAVY-DUTY SAFETY SWITCH IN NEMA 1 ENCLOSURE CONTAINING ONE 20A FUSE - SERVED BY A

20A, 1-POLE CIRCUIT. "CNTRL" INDICATES THAT IT SERVES ELEVATOR CONTROLS.

GFI

ME

GROUND FAULT CIRCUIT INTERRUPTER TYPE NEMA 5-20R RECEPTACLE FOR MAINTENANCE IN ELEVATOR EQUIPMENT

ROOM.

GFI

MP GROUND FAULT CIRCUIT INTERRUPTER TYPE NEMA 5-20R RECEPTACLE FOR MAINTENANCE IN ELEVATOR PIT.

GFI

SP GROUND FAULT CIRCUIT INTERRUPTER TYPE NEMA 5-20R RECEPTACLE FOR SUMP PUMP IN ELEVATOR PIT.

30/2/3R 30A, 2-POLE, NON-FUSED HEAVY-DUTY SAFETY SWITCH IN NEMA 3R ENCLOSURE.

XXX/X ENCLOSED CIRCUIT BREAKER. TEXT INDICATES AMPACITY AND

NUMBER OF POLES.

GFI

WP

GROUND FAULT CIRCUIT INTERRUPTER TYPE NEMA 5-20R RECEPTACLE WITH METALLIC

WEATHERPROOF-WHILE-IN-USE COVER (PLASTIC COVERS ARE NOT ACCEPTABLE).

3-POLE, 20A SWITCH USED FOR DISCONNECT AT INDOOR UNITS OF HVAC SYSTEMS.S3P

S 1-POLE 120/277V, 20A SINGLE-THROW LIGHT SWITCH.

S 1-POLE 120/277V, 20A INFRARED VACANCY-SENSOR-TYPE MOTION DETECTOR SWITCHM

MD CEILING-MOUNTED INFRARED OCCUPANCY SENSOR WITH COVERAGE PATTERN SUFFICIENT FOR SPACE IN WHICH IT

IS LOCATED.

PP POWER PACK FOR CEILING-MOUNTED OCCUPANCY SENSOR MATCHED TO SYSTEM VOLTAGE AND OPERATING

PARAMETERS OF OCCUPANCY SENSOR.

SURFACE OR SUSPENDED LINEAR LED FIXTURE. SEE FIXTURE SCHEDULE.

CONDUCTORS IN CONDUIT CONCEALED WITHIN WALL OR CEILING. TIC MARKS INDICATE NUMBER OF CONDUCTORS.

THE EQUIPMENT GROUNDING CONDUCTOR IS NOT SHOWN, BUT SHALL BE PROVIDED. SIZE THE EQUIPMENT GROUNDING CONDUCTOR AND THE CONDUIT PER THE NEC. THE ABSENCE OF TIC MARKS SIGNIFIES THAT TWO CONDUCTORS PLUS AN EQUIPMENT GROUNDING CONDUCTOR SHOULD BE PROVIDED. FOR EXAMPLE, THE MARKINGS TO THE LEFT SIGNIFY THAT THREE CONDUCTORS PLUS AN EQUIPMENT GROUNDING CONDUCTOR SHOULD BE

PROVIDED.

THE TEXT INSIDE THE ARC INDICATES THE AWG SIZE OF THE CONDUCTORS THAT SHALL BE RUN IN THE CONDUIT. THE

ABSENCE OF TEXT SIGNIFIES THAT THE CONDUCTORS SHOULD BE #12 AWG.

CIRCUITRY RUN IN STRAIGHT LINE SEGMENTS SIGNIFIES EXPOSED SURFACE-MOUNTED RACEWAY (SEE

SPECIFICATIONS).

HOMERUN TO PANELBOARD. ARC DENOTES CONCEALED CIRCUITRY. TEXT DENOTES PANELBOARD NAME WITH CIRCUIT NUMBER. DEVICES HAVING CIRCUIT NUMBERS LOCATED BESIDE THEM MAY NOT SHOW THE CIRCUIT

NUMBERS AT THE HOMERUN ARROWS.

LOW VOLTAGE CONDUCTORS USED FOR MOTION DETECTOR CIRCUITRY. SEE MANUFACTURER'S RECOMMENDATIONS

FOR CONDUCTOR REQUIREMENTS.

1" EMT CONDUIT CONTAINING THREE CAT 6 DATA CABLES - ONE FOR EMERGENCY TWO-WAY ELEVATOR COMMUNICATION, ONE FOR ELEVATOR MONITORING SERVICE, AND ONE FOR CONNECTION OF MINI-SPLIT HVAC UNIT TO ENERGY MANAGEMENT SYSTEM. PROVIDE JUNCTION BOXES IN CONDUIT RUN SO THAT BENDS DO NOT EXCEED 180 DEGREE BETWEEN PULL POINTS. ROUTE CONCEALED ABOVE CEILINGS UNLESS NO CEILING EXISTS.

COORDINATE EXACT ROUTING WITH CONTRACTING OFFICER'S REPRESENTATIVE. PROVIDE PROTECTIVE BUSHING ON CONDUIT ENDS. PROVIDE RJ-45 MALE JACKS ON EACH END OF CABLE. CONNECT TO APPROPRIATE EQUIPMENT IN ELEVATOR EQUIPMENT ROOM. COORDINATE WITH GOVERNMENT IT PROFESSIONAL THROUGH THE CONTRACTING

OFFICER FOR EXACT TERMINATION POINTS IN THE DATA ROOM.

WALL-MOUNTED LINEAR VAPORTIGHT LED FIXTURE. SEE FIXTURE SCHEDULE.

PPM

REVISIONS

DESCRIPTION

SHEET

DATE

U

NO.

D

REAL PROPERTY

SAFETY & HEALTH

A

SUSDA

BY

OF

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

EPM

USDA ARS

NORTHEAST AREA

BELTSVILLE, MARYLAND

Agricultural

Service Research

USDA AGRICULTURAL RESEARCH SERVICE

BELTSVILLE AGRICULTURAL RESEARCH CENTER (BARC)

ELEVATOR MODERNIZATION - BELTSVILLE, MD

GAC

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

P.A.

FIRMJohnson-McAdamsTHE

CLR

JGM

7523-A

--- 04/30/24

DATE

PROJECT NO.

A-E FIRM

"PROFESSIONAL

CERTIFICATION. I HEREBY

CERTIFY THAT THESE

DOCUMENTS WERE

PREPARED OR APPROVED BY

ME, AND THAT I AM DULY

LICENSED PROFESSIONAL

ENGINEER UNDER THE LAWS

OF THE STATE OF MARYLAND,

LICENSE NO. , EXPIRATION

DATE: 2/24/2025."

ELECTRICAL LEGEND AND DETAILS

E-000

GENERAL NOTES:

A. UNLESS OTHERWISE NOTED, WHERE ITEMS ARE SHOWN IN DIM PRINT,

THEY ARE EXISTING-TO-REMAIN. ITEMS SHOWN IN BOLD PRINT ARE

NEW.

B. EXCEPT IN ELEVATOR EQUIPMENT ROOMS, ALL RACEWAYS AND

CIRCUITRY SHALL BE RUN CONCEALED EXCEPT IN AREAS WHERE THE

CEILINGS ARE OPEN WITH EXPOSED STRUCTURE. COORDINATE

EXACT ROUTING OF RACEWAYS AND CIRCUITRY WITH CONTRACTING

OFFICER.

ABBREVIATIONS

CL CAB LIGHTS

CNTRL CONTROLS

ETR EXISTING-TO-REMAIN

GFI GROUND FAULT INTERRUPTER (ALSO CALLED GROUND FAULT

CIRCUIT INTERRUPTER)

NEC NATIONAL ELECTRICAL CODE

SP SUMP PUMP

WP WEATHERPROOF

RR FT

INSTALL TWO HEAT DETECTORS IN THE PIT OF ALL

ELEVATORS WITHIN 24" OF SPRINKLER HEAD. ONE

RATE OF RISE AND ONE FIXED TEMPERATURE.

5 6

LEQ7-8

SUMP PUMP

KEYED NOTES

Mark Description

PROVIDE 3-POLE, ELEVATOR DISCONNECT POWER MODULE UNIT WITH THE FOLLOWING

FEATURES: 100VA CONTROL TRANSFORMER FOR SHUNT TRIP CONTROL POWER; 3-PPOLE

DOUBLE-THROW, 10A, 120V FIRE SAFETY INTERFACE RELAY WITH 120V COIL; RED "ON" PILOT

LIGHT; THREE-POLE FIRE ALARM VOLTAGE MONITORING RELAY TO MONITOR SHUNT TRIP

VOLTAGE; TWO SETS OF NORMALLY-OPEN AND TWO SETS OF NORMALLY-CLOSED AUXILIARY

CONTACTS; SURGE PROTECTIVE DEVICE. COORDINATE VOLTAGE WITH ELEVATOR POWER FEED

FOR EACH BUILDING. CONSULT ELEVATOR VENDOR FOR EXACT FUSE SIZE AND ALL ELEVATOR

ELECTRICAL REQUIREMENTS.

ELEVATOR FEEDER AND EQUIPMENT SIZES ARE BASED ON BEST INFORMATION AVAILABLE AT

THE TIME OF DESIGN. VERIFY ALL ELECTRICAL REQUIREMENTS WITH ELEVATOR VENDOR PRIOR

TO SUBMITTING BROCHURES AND/OR INSTALLING ELECTRICAL GEAR. GROUND WIRE SHALL BE

THE SAME SIZE AS THE PHASE WIRES.

A 120V CONTROL CIRCUIT MUST BE PROVIDED AND ROUTED THROUGH THE CONTACTS OF THE

HEAT DETECTOR AT THE TOP OF THE ELEVATOR SHAFT, THE HEAT DETECTOR IN THE PIT AND THE HEAT DETECTOR IN THE ELEVATOR EQUIPMENT ROOM (ALL SETS OF CONTACTS SHALL BE WIRED IN PARALLEL) TO SHUNT TRIP THE BREAKER UPON AN ALARM CONDITION OF ANY OF THESE HEAT

DETECTORS.

MOUNT SWITCH ADJACENT TO PIT LADDER 48" ABOVE ACCESS FLOOR.

MOUNT RECEPTACLE 18" ABOVE PIT FLOOR.

MOUNT LIGHT FIXTURE 48" ABOVE PIT FLOOR OR AS DIRECTED BY ELEVATOR VENDOR.

CONNECT ELEVATOR EMERGENCY TELEPHONE TO EXISTING TELEPHONE LINE SERVING EXISTING

CONTROL PANEL.

ROUTE TO ELEVATOR CONTROL PANEL FOR ELEVATOR CONTROL CIRCUIT.

ROUTE TO ELEVATOR CONTROL PANEL FOR CAB LIGHTS.

ROUTE TO ELEVATOR CONTROLLER

MOUNT WHERE DIRECTED BY ELEVATOR VENDOR.

VERIFY SUMP PUMP CONNECTION TYPE WITH APPROPRIATE VENDOR.

SEE INDIVIDUAL BUILDING DRAWINGS FOR INFORMATION ON ELEVATOR POWER DISCONNECT AND

CIRCUITRY.

WHERE THE EXISTING CIRCUIT BREAKER HAS A SHUNT TRIP COIL, IT IS PREFERRED TO USE THAT BREAKER'S SHUNT TRIP COIL TO KILL POWER TO THE ELEVATOR UPON ACTIVATION OF A HEAT DETECTOR.

WHERE THE CIRCUIT BREAKER DOES NOT HAVE SHUNT TRIP COIL, USE THE SHUNT TRIP PROVISIONS IN

THE ELEVATOR DISCONNECT POWER MODULE UNIT.

WHERE THE ELEVATOR CIRCUIT BREAKER HAS AUXILIARY CONTACTS FOR MONITORING THE BATTERY LOWERING CIRCUIT, USE THEM. WHERE THE BREAKER DOES NOT HAVE THESE CONTACTS, PROVIDE A YELLOW WARNING LABEL ENGRAVED WITH ¼” HIGH BLACK LETTERS IMMEDIATELY ADJACENT THE BREAKER WITH THE FOLLOWING TEXT: “DO NOT USE AS ELEVATOR DISCONNECT FOR SERVICING THE ELEVATOR. USE THE ELEVATOR DISCONNECT POWER MODULE UNIT IN THE ELEVATOR EQUIPMENT

ROOM.”

15WP

S

EP

DOWN TO PIT LIGHT

INSTALL ONE THERMAL DETECTOR AND ONE SMOKE DETECTOR IN THE

TOP OF THE ELEVATOR SHAFT WITHIN 24" OF SPRINKLER HEAD. IF SHAFT IS

NOT SPRINKLED, ONLY PROVIDE THE THERMAL DETECTOR. COORDINATE

WITH FIRE SUPPRESSION VENDOR.

T

WP

NOTES:

1.

2.

R1 IS A FIRE ALARM SYSTEM RELAY. THE COIL VOLTAGE IS BASED ON THE

OUTPUT OF THE FIRE ALARM CONTROL PANEL. IT SHALL HAVE NORMALLY

OPEN CONTACTS THAT ARE

CLOSED BY THE FACP AFTER AN ALARM SIGNAL FROM ONE OF THE

THERMAL DETECTORS HAS BEEN RECEIVED AND THE TIME DELAY

REQUIRED BY NFPA 72, PARAGRAPH 21.4.3 HAS EXPIRED.

R2 SHALL HAVE A 120V COIL. IT SHALL HAVE NORMALLY-CLOSED

CONTACTS; HOWEVER, UNDER NORMAL OPERATING CONDITIONS, THE

CONTACTS ARE HELD-OPEN WHEN CONTROL VOLTAGE IS PRESENT.

ELEVATOR MOTOR

ELEVATOR

CONTROLLER

NO NC

TO BATTERY LOWERING CIRCUIT IN

ELEVATOR CONTROLLER (IF USED)

EOL

EOL

FIRE ALARM

CONTROL PANEL

T HEAT DETECTOR

IN ELEVATOR PIT

T HEAT DETECTOR TOP

OF SHAFT

H

NSHUNT TRIP

CIRCUIT

(LEQ-2)

T HEAT DETECTOR IN

MACHINE ROOM

120V SHUNT TRIP COIL

ELEVATOR

CIRCUIT

BREAKER

AUX. CONTACTS OF

ELEVATOR BREAKER

FUSED DISCONNECT

WITH AUXILIARY

CONTACTS

3 #12

S

WP

TYPICAL ELEVATOR SHUNT TRIP DETAIL

SCALE: NONE

E-001

TYPICAL TOP OF HOISTWAY CONNECTIONS

SCALE: NONE

E-001

TYPICAL ELEVATOR PIT CONNECTIONS

SCALE: NONE

E-001

T

F-20 30/1/1

F-20 30/1/1

1 2 13

9 GFI

E

TYPICAL ELEVATOR MACHINE ROOM CONNECTIONS

SCALE: NONE

E-001

INSTALL ONE THERMAL DETECTOR AND ONE

SMOKE DETECTOR IN THE MACHINE ROOM WITHIN

24" OF SPRINKLER HEAD.

TO LIGHT IN ELEVATOR

EQUIPMENT ROOM

UP TO LIGHT AT TOP

OF HOISTWAY

LEQ7-6

LEQ7-4

LEQ7-5

S

TO LIGHT IN

ELEVATOR PIT

LEQ7-1

LEQ7-3

PANEL LEQ73

GFI

GFI

WP

ED

LUMINAIRE REQUIREMENTS:

1. HOUSING - DIE-FORMED, COLD ROLLED STEEL, WITH DIFFUSE

ACRYLIC POLYMER LENS.

2. LIGHT SOURCE - HIGH OUTPUT LEDs WITH MINIMUM 50K HOURS

RATED LIFE AT L70, 4000K COLOR TEMPERATURE , EFFICACY OF 119

LUMENS/WATT, WITH A MINIMUM CRI OF 80. INITIAL LUMEN OUTPUT

OF 8,000 LUMENS.

3. DRIVER - OPERATING VOLTAGE OF 120-277V. DIMMABLE TO 1%.

(0-10 VOLT DIMMING)

4. CERTIFICATION - UL 1598, DAMP LOCATION, DLC QUALIFIED, AND

ROHS COMPLIANT. COMPLIES UL 924.

5. MOUNTING - CEILING-SUSPENDED USING AIRCRAFT CABLE AT 10'

AFF.

6. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION

OF A LUMINAIRE THAT MAY MEET THE SPECIFICATION

REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A CERTAIN

MANUFACTURER OR PREFERENCE.

7. 10W BATTERY PACK WITH WITH SELF-DIAGNOSTIC TESTING

FEATURE AND 90 MINUTES BATTERY BACKUP.

LUMINAIRE REQUIREMENTS:

1. HOUSING - FIBERGLASS OR FIBERGLASS-REINFORCED POLYESTER

OUTER HOUSING, WITH ALUMINUM COMPONENT TRAY AND HEAT

SINK. OPTIONAL LENGTHS OF 4FT OR 8FT.

2. LENS - IMPACT-RESISTANT ACRYLIC, WITH CONTINUOUS

CLOSED-CELL POLYURETHANE GASKET, SECURED WITH STAINLESS

STEEL OR POLYCARBONATE LATCHES.

3. LIGHT SOURCE - SOLID STATE LEDS WITH MINIMUM 50K HOURS

RATED LIFE AT L70, 4000K CCT UON, MINIMUM 80 CRI, MAXIMUM

4-STEP MCADAM ELLIPSE BINNING TOLERANCE FOR COLOR

CONSISTENCY, AND MINIMUM EFFICACY OF 100 LUMENS/WATT.

INITIAL LUMEN OUTPUT OF 6,000 LUMENS.

4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DRIVER WITH

MINIMUM 0.9 PF, OPERATING VOLTAGE OF 120V, THERMAL

MANAGEMENT, < 20% TOTAL HARMONIC DISTORTION. ON-OFF

CONTROL.

5. CERTIFICATION - UL 1598, WET LOCATION (IP65, IP66, IP67), DLC

QUALIFIED, AND ROHS COMPLIANT. COMPLIES WITH LM79, LM80 AND

TM21 TESTING STANDARDS. UL 924 WHEN EQUIPPED WITH

EMERGENCY BATTERY BACK-UP.

6. MOUNTING - SURFACE-MOUNTED OR SUSPENDED FROM CEILING.

7. 10W EMERGENCY BATTERY PACK WITH SELF-DIAGNOSTIC TESTING

FEATURE AND 90 MINUTES BATTERY BACKUP.

8. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF

A LUMINAIRE THAT MAY MEET THE SPECIFICATION REQUIREMENTS.

IT IS NOT INTENDED TO INDICATE A CERTAIN MANUFACTURER OR

PREFERENCE.

3 #123 #12

3 #12

1514 GENERAL NOTES:

A. THE PANELBOARD SCHEDULE USED ON THIS SHEET SHALL BE USED

FOR PANELBOARDS IN MULTIPLE BUILDINGS. THE "#" SYMBOL IN THE

PANELBOARD NAME IS REPLACED BY THE BUILDING NUMBER FOR

EACH RESPECTIVE BUILDING. FOR EXAMPLE, IN BUILDING 001, THE

PANELBOARD IS NAMED LEQ1; IN BUILDING 003, THE PANELBOARD IS

NAMES LEQ3. BUILDING 307B MUST HAVE TWO OF THESE PANELS;

THE ONE IN THE BASEMENT IS NAMED LEQ307BB, AND THE ONE ON

THE FIRST FLOOR IS NAMED LEQ307B1.

PPM

REVISIONS

DESCRIPTION

SHEET

DATE

U

NO.

D

REAL PROPERTY

SAFETY & HEALTH

A

SUSDA

BY

OF

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

EPM

USDA ARS

NORTHEAST AREA

BELTSVILLE, MARYLAND

Agricultural

Service Research

USDA AGRICULTURAL RESEARCH SERVICE

BELTSVILLE AGRICULTURAL RESEARCH CENTER (BARC)

ELEVATOR MODERNIZATION - BELTSVILLE, MD

GAC

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

P.A.

FIRMJohnson-McAdamsTHE

CLR

JGM

7523-A

--- 04/30/24

DATE

PROJECT NO.

A-E FIRM

"PROFESSIONAL

CERTIFICATION. I HEREBY

CERTIFY THAT THESE

DOCUMENTS WERE

PREPARED OR APPROVED BY

ME, AND THAT I AM DULY

LICENSED PROFESSIONAL

ENGINEER UNDER THE LAWS

OF THE STATE OF MARYLAND,

LICENSE NO. , EXPIRATION

DATE: 2/24/2025."

ELECTRICAL DETAILS

E-001

DATA ROOM

MSB1

SW

BD

S

SP

MP

UP TO

ELEVATOR

EQUIPMENT

ROOM

EP3

GFI

GFI

NEW ELEVATOR

EQUIPMENT

/2

/1

ELEVATOR

POWER

DISCONNECT

S

30/2/1

EP-2

GFI

ME

ED

C U

-5

30/2/3R

TO 3P

SWITCH

FOR

DISCONNECT

FOR

IDU-5 IN

ELEVATOR

EQUIPMENT

ROOM

LEQ7-7,9

2 #10, #10(G), 3/4" C.

3 #12, #12(G), 3/4" C.

GFI

WP

LEQ7

CNTRL

CL

DOWN TO

DATA

ROOM IN

BASEMENT

AE

AE

IDU-5S3P

LEQ7-10

2 #10, #10(G), 3/4" C.

LOWEST LEVEL FLOOR PLAN (BASEMENT)

SCALE: 1/8"=1'-0"

PLAN

NORTH

E-105

0' 2' 4' 8' 12'

SCALE: 1/4"=1'-0"

ELEVATOR MACHINE ROOM IN ATTIC (SEE M-105)

SCALE: 1/4"=1'-0"

PLAN

NORTH

E-105

0' 24'

SCALE: 1/8"=1'-0"

8'4' 16'

PPM

REVISIONS

DESCRIPTION

SHEET

DATE

U

NO.

D

REAL PROPERTY

SAFETY & HEALTH

A

SUSDA

BY

OF

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

EPM

USDA ARS

NORTHEAST AREA

BELTSVILLE, MARYLAND

Agricultural

Service Research

USDA AGRICULTURAL RESEARCH SERVICE

BELTSVILLE AGRICULTURAL RESEARCH CENTER (BARC)

ELEVATOR MODERNIZATION - BELTSVILLE, MD

GAC

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

P.A.

FIRMJohnson-McAdamsTHE

CLR

JGM

7523-A

--- 04/30/24

DATE

PROJECT NO.

A-E FIRM

"PROFESSIONAL

CERTIFICATION. I HEREBY

CERTIFY THAT THESE

DOCUMENTS WERE

PREPARED OR APPROVED BY

ME, AND THAT I AM DULY

LICENSED PROFESSIONAL

ENGINEER UNDER THE LAWS

OF THE STATE OF MARYLAND,

LICENSE NO. , EXPIRATION

DATE: 2/24/2025."

ELEVATOR 005 | BUILDING 007| #1

ELECTRICAL PLANS

E-105

KEYED NOTES:

GENERAL NOTES:

A. SEE SHEET E-001 FOR CIRCUITRY INFORMATION FOR ALL DEVICES

AND EQUIPMENT.

1. THE CONDENSING UNIT IS IN THE MECHANICAL ROOM. SEE SHEET

M-105 FOR MORE DETAILED INFORMATION ON THE LOCATION.

2. CONFIRM EXACT CIRCUITRY REQUIREMENTS WITH EQUIPMENT

VENDOR PRIOR TO BEGINNING CONSTRUCTION.

3. PROVIDE AN IDENTICAL LIGHT FIXTURE (TYPE EP) AND SWITCH AT THE

TOP OF THE HOISTWAY AND CIRCUIT AS SHOWN ON E-001.

EXISTING

SWITCHBOARD

MSB1

NEW PANEL

LEQ7

4 #1, #8(G), 1 1/2" C.

100/3

0' 2' 4' 8' 12'

SCALE: 1/4"=1'-0"

GENERAL NOTES:

0' 24'

SCALE: 1/8"=1'-0"

8'4' 16'

PPM

REVISIONS

DESCRIPTION

SHEET

DATE

U

NO.

D

REAL PROPERTY

SAFETY & HEALTH

A

SUSDA

BY

OF

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

EPM

USDA ARS

NORTHEAST AREA

BELTSVILLE, MARYLAND

Agricultural

Service Research

USDA AGRICULTURAL RESEARCH SERVICE

BELTSVILLE AGRICULTURAL RESEARCH CENTER (BARC)

ELEVATOR MODERNIZATION - BELTSVILLE, MD

GAC

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

P.A.

FIRMJohnson-McAdamsTHE

CLR

JGM

7523-A

--- 04/30/24

DATE

PROJECT NO.

A-E FIRM

"PROFESSIONAL

CERTIFICATION. I HEREBY

CERTIFY THAT THESE

DOCUMENTS WERE

PREPARED OR APPROVED BY

ME, AND THAT I AM DULY

LICENSED PROFESSIONAL

ENGINEER UNDER THE LAWS

OF THE STATE OF MARYLAND,

LICENSE NO. , EXPIRATION

DATE: 2/24/2025."

SINGLE-LINE DIAGRAM

E-601

A. COORDINATE CONDUIT ROUTING WITH COR.

KEYED NOTES: #

1. USE EXISTING SPARE 100/3 BREAKER.

2. ENSURE THAT LEQ7 HAS PROVISIONS FOR BEING FED FROM THE

BOTTOM OF THE PANEL.

BUILDING 007 PARTIAL SINGLE LINE DIAGRAM

SCALE: NONE

E-601

ELEVATOR LOBBY

MACHINE ROOM

SPRINKLER NO MORE THAN

24" ABOVE PIT FLOOR

ELEVATOR LOBBY

HYDRAULIC PIPING

SD

TO ELEVATOR

SHUNT TRIP TO FIRE RECALL PANEL

SD

ELEVATOR CAB

SD

THIS DETAIL APPLIES TO THE PROTECTION OF HYDRAULIC ELEVATORS IN A SPRINKLERED BUILDING, UNLESS OTHERWISE

INDICATED BY SPECIFIC NOTES FOR A PARTICULAR ELEVATOR / BUILDING.

MACHINE ROOM SPRINKLER LINE WILL HAVE A INDICATING AND MONITORED ISOLATION VALVE, CHECK-VALVE, DOUBLE-POLE

FLOW SWITCH LOCATED OUTSIDE AND ADJACENT TO MACHINE ROOM.

ZERO DELAY ON FLOW SWITCH.

MONITOR SHUNT POWER WITH FIRE ALARM MODULE / RELAY. COORDINATE SHUNTING MEANS WITH SPECIFIC SHUNT BREAKER

CONFIGURATION PROVIDED.

INSPECTOR TEST ROUTED TO EXTERIOR SPLASH BLOCK.

PROVIDE MONITORED ISOLATION VALVE ON ELEVATOR PIT SPRINKLER. MAY BE SERVED FROM MACHINE ROOM ISOLATION

VALVE.

SMOKE DETECTOR IN MACHINE ROOM AND ELEVATOR LOBBIES TO INITIATE RECALL, WATER FLOW SWITCH TO INITIATE POWER SHUNT TO ELEVATOR. NO SMOKE OR HEAT DETECTORS ARE REQUIRED IN THE SHAFT OF HYDRAULIC ELEVATOR WHEN

FOLLOWING THIS CRITERIA.

INSPECTOR TEST WITH

PRESSURE RELIEF FOR

TESTING FLOW SWITCH

OUTSIDE MACHIE ROOM.

SPRINKLER WITH

LISTED GUARD

SMOKE DETECTOR ON

RECALL PANEL (TYP)

EXISTING LOBBY

SPRINKLER

SPRINKLER LINE

SERVING PIT , WITH

MONITORED ISOLATION

VALVE

PROVIDE SURGE

PROTECTION (OUTSIDE

CABINET) FOR 120VAC

FARP

SYSTEM CAPABLE OF A SECOND CLASS "A"

SLC FOR FUTURE EXPANSION WITHOUT

IMPACTING ELEVATOR CIRCUIT

FA-2

SPARE

FA-3

SPARE

FA-4

SPARE

PANEL

"FA"

LOCATION PER

BUILDING

CAPABLE OF

CLASS "A"

NOTIFICATION

CIRCUITS

FA-1

SPARE

MUST INCORPORATE

ABILITY TO ADD A FIBER

NETWORK CARD

CAPABLE OF INTEGRATION

WITH VOICE MNS IN FUTURE

SIGNALING LINE CIRCUIT (SLC DEVICES AS REQUIRED)

PPM

REVISIONS

DESCRIPTION

SHEET

DATE

U

NO.

D

REAL PROPERTY

SAFETY & HEALTH

A

SUSDA

BY

OF

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

EPM

USDA ARS

NORTHEAST AREA

BELTSVILLE, MARYLAND

Agricultural

Service Research

USDA AGRICULTURAL RESEARCH SERVICE

BELTSVILLE AGRICULTURAL RESEARCH CENTER (BARC)

ELEVATOR MODERNIZATION - BELTSVILLE, MD

SWL

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

P.A.

FIRMJohnson-McAdamsTHE

CLR

JGM

7523-A

--- 04/30/24

DATE

PROJECT NO.

A-E FIRM

4/30/24

FIRE PROTECTION GENERAL NOTES

FP001

ACCEPTABLE PRODUCTS:

SEE SPECIFICATIONS FOR ACCEPTABLE MANUFACTURES OF FIRE ALARM

PANELS ALLOWED FOR THIS PROJECT. PROVIDE GOVERNMENT WITH ALL

PASSWORDS AND SOFTWARE TO SERVICE / SUPPORT THE FA PANEL. DO NOT

BID IF NOT GOING TO PROVIDE.

S p

WF TS

MM

H rr

FACU

LEGEND:

EXISTING FIRE ALARM CONTROL UNIT

FIRE ALARM RECALL PANEL, SURGE PROTECTION, AS-BUILT CABINET

WATER FLOW/TAMPER MODULES

MONITOR/CONTROL/RELAY MODULE

PHOTOELECTRIC SMOKE DETECTOR WITH CALIBRATION DIAGNOSTICS

RATE OF RISE HEAT DETECTOR

FARP

FIRE PROTECTION GENERAL NOTES:

1. THIS PROJECT INVOLVES THE MODERNIZATION, REPAIR, OR

REPLACEMENT OF ELEVATORS WITHIN MULTIPLE BUILDINGS.

CONTRACTOR IS RESPONSIBLE TO COORDINATE THE LEVEL OF

WORK WITH EACH DISCIPLINES DRAWINGS.

2. BUILDINGS WILL LIKELY BE BID IN SEPARATE PACKAGES AND/OR

WITH BID ALTERNATES. COORDINATE WITH FRONT-END

DOCUMENTS AND DIRECTION FOR WHICH BUILDING AND ELEVATOR

IS INCLUDED IN SOLICITATIONS.

3. NOTES ON THIS SHEET ARE GENERAL AND APPLY TO THE PROJECT

AS A WHOLE, WITH MULTIPLE ELEVATORS, TYPES, AND CONDITIONS

IDENTIFIED. CONTRACTOR TO REVIEW EACH ELEVATORS FLOOR

PLAN SHEET (FP1##) FOR APPLICABLE CONDITIONS BASED ON THE

TYPE OF ELEVATOR, IF BUILDING IS SPRINKLERED, OR UNIQUE

CONDITIONS FOR THAT ELEVATOR.

4. ALL NEW WORK MUST COMPLY WITH APPLICABLE STANDARDS TO

INCLUDE BUT NOT LIMITED TO:

4.1. NFPA 13 STANDARD FOR THE INSTALLATION OF SPRINKLER

SYSTEMS, 2022.

4.2. NFPA 70 NATIONAL ELECTRICAL CODE, 2023.

4.3. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE, 2022.

4.4. ASME A17.1 SAFETY CODE FOR ELEVATORS AND ESCALATORS,

AS CURRENTLY ADOPTED BY THE STATE.

5. INFORMATION PROVIDED AS EXISTING IS BASED ON FIELD

OBSERVATION. HOWEVER, NOT ALL AREAS WERE ACCESSIBLE,

INCLUDING SOME HOISTWAYS. INFORMATION IS INDICATED AS

OBSERVED AND ALL INFORMATION MUST BE FIELD VERIFIED.

6. MOST EXISTING FIRE ALARM PANELS WERE IN TROUBLE AT THE TIME

OF EVALUATION. SOME DUE TO PAST STORM DAMAGE, AND OTHERS

APPARENTLY FROM LACK OF MAINTENANCE OR PAST SERVICE LIFE.

IN ORDER TO COMMISSION THE NEW ELEVATOR WORK, A

FUNCTIONAL PANEL WITH RECALL AND SHUNT SERVICE IS

REQUIRED. IT IS NOT THE INTENT OF THE ELEVATOR PROJECT TO

CORRECT BUILDING FIRE ALARM DEFICIENCIES, OR TO BRING

EXISTING FIRE ALARM SYSTEMS UP TO CODE AS WOULD BE

REQUIRED BY PROVIDING A NEW "BUILDING FIRE ALARM PANEL". AS

A RESULT, MANY BUILDINGS WILL INCLUDE NEW "ELEVATOR RECALL

CONTROL AND SUPERVISORY CONTROL UNITS" IN ACCORDANCE

WITH NFPA 72, 21.3.2. THIS WILL BE SPECIFICALLY IDENTIFIED IN

"FIRE PROTECTION NEW WORK NOTES" ON THE RESPECTIVE FIRE

PROTECTION FLOOR PLAN SHEET.

7. UNLESS OTHERWISE INDICATED, THE NEW "ELEVATOR RECALL

CONTROL AND SUPERVISORY CONTROL UNIT" (RECALL PANEL) MUST

BE SIZED TO ACCOMMODATE THE FOLLOWING AT A MINIMUM

(ALLOWING FOR FUTURE BUILDING UPGRADE):

7.1. ANALOG ADDRESSABLE ALLOWING FOR MINIMUM 300

INTELLIGENT DEVICES.

7.2. CAPABLE OF INTEGRATION WITH A MASS NOTIFICATION VOICE

SYSTEM IN THE FUTURE.

7.3. CLASS "A" SLC AND NOTIFICATION CIRCUITS.

7.4. CAPABLE OF A SECOND CLASS A SLC CIRCUIT.

7.5. SMOKE DETECTORS INDICATING SENSITIVITY STATUS.

7.6. DACT / UDACT CAPABILITY.

7.7. ABILITY FOR FIBER OPTIC NETWORK INTEGRATION.

8. CONTRACTOR WILL PROVIDE MODULES AND CONNECT THE NEW

RECALL PANEL WITH THE EXISTING BUILDING FIRE ALARM PANEL.

8.1. ELEVATOR RECALL PANEL WILL REPORT TROUBLE, SPRINKLER

VALVE SUPERVISORY, AND ALARM CONDITIONS TO BUILDING

FIRE ALARM PANEL FOR OFF-SITE REPORTING AND BUILDING

EVACUATION.

8.2. BUILDING FIRE ALARM PANEL WILL NOT REPORT ANY SIGNALS

TO THE ELEVATOR RECALL PANEL.

8.3. ADDRESS OF OLD DEVICES BEING REMOVED CAN BE

REASSIGNED TO NEW MODULES.

9. UNLESS INDICATED OTHERWISE FOR A BUILDING, ALL NEW FIRE

ALARM COMPONENTS ASSOCIATED WITH THE ELEVATOR WILL BE

SERVED BY THE ELEVATOR RECALL PANEL. THIS IS TO INCLUDE:

9.1. LOBBY AND MACHINE ROOM SMOKE DETECTORS.

9.2. MONITOR / CONTROL / RELAY MODULES

9.3. MONITORING OF SPRINKLER FLOW SWITCHES / VALVES

RELATED TO ELEVATOR.

9.4. SHUNT TRIP AND SHUNT POWER MONITORING.

9.5. SMOKE DETECTOR AT PANEL PER NFPA 72.

9.6. HEAT DETECTORS IF SPECIFICALLY IDENTIFIED BY ELEVATOR

PLAN.

10. FIRE ALARM AND SPRINKLER INSTALLERS MUST COORDINATE WITH

FOR EXACT QUANTITY AND LOCATION OF ANY VALVES OR FLOW

SWITCHES TO BE MONITORED, AND ANY HOISTWAY OR MACHINE

ROOM SPRINKLERS NEEDING HEAT DETECTORS WITHIN 12".

11. DO NOT PROVIDE SMOKE OR HEAT DETECTORS THAT ARE NOT

SPECIFICALLY REQUIRED BY EITHER CURRENT NFPA 13 OR 72, OR

SPECIFICALLY INDICATED ON THAT ELEVATORS FIRE PROTECTION

FLOOR PLAN. IF SPRINKLER IS NOT PROVIDED AT TOP OF HOISTWAY

THAN NO DETECTION IS REQUIRED. NO DETECTION IS REQUIRED IN

PIT WHEN SPRINKLER IS PROPERLY LOCATED.

CIRCUIT NOTES:

1. FIRE ALARM RECALL PANELS MUST BE PROVIDED WITH EXTERNAL

120VAC SURGE PROTECTION ON A DEDICATED FIRE ALARM CIRCUIT

WITH RED LOCK PER NEC 760 AND NFPA 72. COORDINATE WITH

ELECTRICAL DRAWINGS FOR CIRCUITS.

2. ALL NEW FIRE ALARM CONDUIT TO BE FACTORY RED CONDUIT,

MINIMUM 3/4", WITH COMPRESSION FITTINGS.

3. JUNCTION BOXES ARE TO BE RED UNLESS LOCATED IN A FINISHED

AREA IN WHICH CASE THEY ARE TO BE PAINTED TO MATCH THE

FINISHED SURFACE. IF PANTED OTHER THAN RED, THE INSIDE OF

COVER IS TO BE LABELED "FA ELEVATOR".

4. ELEVATOR RELATED CONDUIT MUST INCLUDE ADDITIONAL LABELS,

SUCH AS FROM LABEL MAKER, THAT INDICATES IT SERVES THE

ELEVATOR. THIS IS SO IT IS NOT ACCIDENTALLY DEMOLISHED

DURING FUTURE FIRE ALARM UPGRADES.

5. LABEL CONDUIT AT LEAST EVERY 20 FEET "ELEVATOR FIRE ALARM".

6. CONDUIT IS TO BE CONCEALED IN WALLS / CEILINGS UNLESS

OTHERWISE APPROVED OR IN A MECHANICAL SPACE.

7. ALL CIRCUITS ARE TO BE CLASS "A" PER USDA CRITERIA. T-TAPS

ARE NOT ALLOWED.

8. CIRCUITS MUST BE PULLED DEVICE-TO-DEVICE WITHOUT SPLICES.

9. WIRE NUTS ARE PROHIBITED. IF REQUIRED, TERMINAL STRIPS ARE

TO BE USED.

10. ALL CONDUCTORS ARE TO BE LABELED WITHIN 4" OF TERMINATION

WITH A MACHINE GENERATED SHRINK-WRAPPED LABEL CLEARLY

INDICATING CIRCUIT FUNCTION. ANY COLOR OF WIRE OTHER THAN

RED / BLACK MUST BE LABELED AS TO POLARITY UNDER NORMAL

OPERATION.

11. MONITOR/CONTROL/RELAY MODULES MUST BE WITHIN 3' OF DEVICE

BEING CONTROLLED UNLESS CIRCUIT IS SUPERVISED.

12. NEW DEVICES REQUIRE NEW WIRE. REMOVE ALL OLD DEVICES AND

WIRING. REMOVE OLD CONDUIT / BOXES NOT RE-USED.

EVALUATE & MAINTAIN EXISTING SYSTEMS:

1. EXISTING FIRE ALARM SYSTEMS ARE TO BE EVALUATED AND ANY

ABNORMAL CONDITIONS DOCUMENTED AND SUBMITTED TO

CONTRACTING OFFICER PRIOR TO STARTING WORK. THIS WILL

SERVE AS A BENCHMARK FOR EXISTING VS NEW CONDITIONS.

2. CONTRACTOR IS RESPONSIBLE FOR OBTAINING SERVICES OF

QUALIFIED TECHNICIANS TO MODIFY PROGRAMMING OF EXISTING

FIRE ALARM PANELS AS APPROPRIATE. AT MINIMUM, BUT NOT

LIMITED TO:

2.1. REMOVE ADDRESSES OF EXISTING DETECTORS, MODULES,

ETC.

2.2. REMOVE PROGRAM FUNCTIONS UPON ACTIVATION OF SUCH

DEVICES.

2.3. REPROGRAM TO MONITOR TROUBLE, SUPERVISORY, AND

ALARM CONDITIONS OF RECALL PANEL TO INITIATE BUILDING

ALARM AS APPROPRIATE AND NOTIFY OFF-SITE MONITORING

OF CONDITIONS.

2.4. PROVIDE NEW MODULES AS NEEDED TO MONITOR NEW RECALL

PANELS.

2.5. THIS WILL REQUIRE SERVICES AT BEGINNING TO DISABLE

THESE DEVICES, AND FOR FINAL TESTING / COMMISSIONING /

VERIFICATION OF MONITORING.

3. EXISTING SMOKE DETECTORS, HEAT DETECTORS, MODULES,

RELAYS, ETC. ARE CONNECTED TO THE EXITING BUILDING FIRE

ALARM PANELS, AND MOST WILL BE REPLACED WITH NEW RECALL

PANEL DEVICES.

4. CONTRACTOR IS TO REMOVE / DISCONNECT THESE

ELEVATOR-RELATED COMPONENTS FROM THE EXISTING SYSTEMS

WITHOUT IMPACTING THE REST OF THE BUILDING FIRE ALARM

SYSTEMS. THIS WILL REQUIRE FIELD EVALUATION OF EACH

BUILDING FOR VARYING CONDITIONS.

5. EXISTING SLC'S PASSING THROUGH AN ELEVATOR RELATED

JUNCTION BOX MAY REMAIN WITH A TERMINAL STRIP ONLY IF

SERVING EQUIPMENT BEYOND THE ELEVATORS. CIRCUITS MUST BE

LABELED TO IDENTIFY FUNCTION AND PANEL CONNECTED TO.

6. EXISTING CIRCUITS THAT TERMINATE AT ELEVATOR DEVICES MUST

BE REMOVED BACK TO PREVIOUS NON-ELEVATOR DEVICE /

JUNCTION.

SUBMITTALS:

1. SHOP DRAWINGS ARE REQUIRED TO BE SUBMITTED AND APPROVED

PER NFPA 72, NFPA 13, AND SPECIFICATIONS.

2. SHOP DRAWINGS MUST INCLUDE ENGINEERS NOTES FROM THIS

SHEET AND SPECIFIC BUILDING SHEET RELATED TO INSTALLATION

AND SYSTEM PERFORMANCE.

3. PROVIDE AS-BUILT DRAWINGS IN AN APPROVED AS-BUILT CABINET

ADJACENT TO NEW FA PANEL.

4. PROVIDE GOVERNMENT WITH ALL USER MANUALS.

BATTERIES:

1. BATTERIES MUST HAVE MANUFACTURER DATE PER NFPA 72.

2. PROVIDE LABEL INSIDE BATTERY SPACE INDICATING WHAT SIZE

BATTERIES ARE REQUIRED BASED ON SYSTEM DEMAND PER NFPA

72. THIS IS TO ENSURE PROPER BATTERIES ARE PROVIDED IN THE

FUTURE.

ADDITIONAL SPRINKLER NOTES:

1. SEE OTHER SPRINKLER NOTES AND CRITERIA ON THIS SHEET

INTEGRATED WITH OTHER CRITERIA, IN SPECIFICATIONS, AND ON

FIRE PROTECTION FLOOR PLANS FOR EACH ELEVATOR.

2. FIELD EVALUATE AND ADJUST / ADD / REMOVE SPRINKLERS AND

PIPING AS INDICATED.

2.1. ENSURE ALL PIT SPRINKLERS ARE WITHIN 24" OF THE BOTTOM

OF THE PIT.

2.2. REMOVE ANY SPRINKLERS FROM TOP OF HOISTWAY IN A

HYDRAULIC ELEVATOR HOISTWAY.

2.3. ADD NEW SPRINKLERS WHERE INDICATED OR REQUIRED

BASED ON TYPE OF ELEVATOR BEING INSTALLED.

2.4. ADD MONITORED ISOLATION VALVE TO EXISTING PIT

SPRINKLERS TO REMAIN THAT DON'T HAVE A VALVE.

3. IF REMOVING, REMOVE ALL PIPE, HANGERS, AND RELATED

EQUIPMENT BACK TO BRANCH LINE OR MAIN AS APPROPRIATE.

4. IF ADDING NEW SPRINKLER COMPONENTS, SYSTEM IS TO COMPLY

WITH INDICATED CODES AND THE FOLLOWING:

4.1. PIPE TO BE SCHEDULE 40, BLACK STEEL.

4.2. ISOLATION VALVES TO BE BUTTERFLY WITH TAMPER

MONITORED BY RECALL ALARM PANEL.

4.3. ANY PIT SPRINKLERS TO BE LESS THAN 24" ABOVE FLOOR OF

PIT AND HAVE AN ISOLATION VALVE LOCATED OUTSIDE THE PIT.

4.4. PROVIDE SIGNAGE FOR ALL VALVES INDICATING FUNCTION

AND NORMALLY OPEN/CLOSED.

4.5. IF PROVIDING WATER FLOW FOR SHUNTING, WATER FLOW

SWITCH MUST HAVE NO TIME DELAY, INCORPORATE A CHECK

VALVE BEFORE THE FLOW SWITCH, BUTTERFLY VALVE, AN

INSPECTOR TEST TO EXTERIOR, AND HAVE PRESSURE RELIEF

DOWNSTREAM OF CHECK VALVE.

4.6. PIT SPRINKLERS TO BE SIDEWALL WITH GUARD, STANDARD

RESPONSE, INTERMEDIATE TEMPERATURE (MINIMUM).

5. DO NOT PROVIDE SPRINKLERS IN HOISTWAY UNLESS SPECIFICALLY

REQUIRED BY CURRENT NFPA 13, 9.3.6 (PIT FOR HYDRAULIC, TOP /

BOTTOM OF HOISTWAY FOR COMBUSTIBLE BELTS).

HYDRAULIC ELEVATOR IN SPRINKLERED BUILDING

NTS

FP001

ELEVATOR RECALL AND CONTROL PANEL GENERAL CRITERIA

NTS

FP001

LOWEST LEVEL FLOOR PLAN (BASEMENT)

SCALE: 1/16"=1'-0"

PLAN

NORTH

FP105

HIGHEST LEVEL FLOOR PLAN (THIRD)

SCALE: 1/16"=1'-0"

PLAN

NORTH

FP105

ELEVATOR SHAFT

SCALE: 1/4"=1'-0"

FP105

- 1

5'- 0"

(F

IE

LD

V

ER

IF

Y)

- 1 5'-

0" (F

IE

LD

V

ER

IF

Y)

- 1

5'- 0"

(F

IE

LD

V

ER

IF

Y)

EX

IS

TI

NG

P

IT

D

EP

TH

(F

IE

LD

V

ER

IF

Y)

EX

IS

TI

NG

O

VE

RH

EA

D

CL

EA

RA

NC

E (F

IE

LD

V

ER

IF

Y)

THIS IS A TRACTION

ELEVATOR WITH

MECHANICAL ROOM

OVER HOISTWAY.

BASEMENT LEVEL

FIRST LEVEL

SECOND LEVEL

THIRD LEVEL

TOP OF SHAFT

BOTTOM OF PIT

ELEVATOR MACHINE ROOM

SCALE: 1/4"=1'-0"

PLAN

NORTH

FP105

FP105

FP105

ELEVATOR

ELEVATOR

MACHINE

ROOM

TOP OF ELEVATOR

SHAFT IN ATTIC

ELEVATOR EQUIPMENT

PPM

REVISIONS

DESCRIPTION

SHEET

DATE

U

NO.

D

REAL PROPERTY

SAFETY & HEALTH

A

SUSDA

BY

OF

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

EPM

USDA ARS

NORTHEAST AREA

BELTSVILLE, MARYLAND

Agricultural

Service Research

USDA AGRICULTURAL RESEARCH SERVICE

BELTSVILLE AGRICULTURAL RESEARCH CENTER (BARC)

ELEVATOR MODERNIZATION - BELTSVILLE, MD

SWL

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

P.A.

FIRMJohnson-McAdamsTHE

CLR

JGM

7523-A

--- 04/30/24

DATE

PROJECT NO.

A-E FIRM

4/30/24

FP105

REMOVE ANY EXISTING

SMOKE OR HEAT

DETECTORS FROM PIT.

REPLACE EXISTING

SMOKE DETECTOR

WITH NEW ON RECALL

PANEL

MACHINE ROOM OVER

HOISTWAY IN ATTIC.

DATA SERVICE

LOCATION

(ROOM 690)

ELECTRICAL SERVICE

LOCATION (ROOM 123)

FIRE PROTECTION EXISTING CONDITIONS:

1. BELOW INFORMATION IS BASED ON FIELD OBSERVATION OF AREAS THAT COULD BE ACCESSED.

2. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY ALL CONDITIONS.

3. "TBD" INDICATES THIS ITEM COULD NOT BE VERIFIED AT TIME OF REVIEW.

4. BUILDING SPRINKLERED: YES

5. MACHINE ROOM HAS SPRINKLERS: NO

6. MACHINE ROOM ISOLATION VALVE: NO

9. SHUNT TRIP BREAKER: NO

10. FLOW SWITCH FOR POWER SHUNT: NO

11. HEAT DETECTOR(S) USED FOR POWER SHUNT BREAKER: NO

12. MACHINE ROOM SMOKE / HEAT DETECTOR: YES, SMOKE

13. ELEVATOR PIT SMOKE / HEAT DETECTOR: TBD

14. TOP OF HOISTWAY SMOKE / HEAT DETECTOR: TBD

15. ELEVATOR PIT SPRINKLER: TBD

16. ELEVATOR PIT SPRINKLER IS < 24" ABOVE BOTTOM OF PIT: TBD

17. TOP OF HOISTWAY SPRINKLER: TBD

18. TOP OF HOISTWAY SPRINKLER ISOLATION VALVE: TBD

19. EXISTING LOBBY SMOKE DETECTORS: YES

20. WERE ANY RECALL / HELMET MODULES IDENTIFIED: NO, RELAY OPERATED ELEVATOR

21. EXISTING BUILDING FIRE ALARM PANEL: NOTIFIER AFP-400 CONTROLLING OLDER CIRCUITS FROM

OLD FCI CONVENTIONAL PANEL.

22. TROUBLES / FAULTS ON EXISTING FIRE ALARM SYSTEM: YES

23. WILL EXISTING FIRE ALARM PANEL BE USED FOR NEW ELEVATOR WORK: NO, PAST USEFUL LIFE

SPAN.

24. TYPE OF ELEVATOR: CABLE SUSPENSION

FIRE PROTECTION NEW WORK NOTES:

1. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY ALL CONDITIONS TO ESTABLISH IF THERE ARE

ANY EXISTING CONDUITS THAT CAN BE RE-USED WITH FULL WARRANTY TO ACHIEVE INTENDED

LEVEL OF PROTECTION.

2. PROVIDE NEW ELEVATOR RECALL FIRE ALARM PANEL: YES

3. BUILDING SPRINKLERED: YES

4. MACHINE ROOM SPRINKLER PROTECTION: NO, NOT REQUIRED PER NFPA 13, 9.3.6.3. A NEW RATED

DOOR WILL BE REQUIRED (SEE ARCHITECTURAL).

5. MACHINE ROOM ISOLATION VALVE: NO

6. SHUNT TRIP BREAKER: ONE WILL BE PROVIDED, BUT NOT REQUIRED AT THIS TIME DUE TO NO

SPRINKLERS IN HOISTWAY.

7. FLOW SWITCH FOR POWER SHUNT: NO

8. HEAT DETECTOR(S) USED FOR POWER SHUNT BREAKER: NO

9. MACHINE ROOM SMOKE / HEAT DETECTOR: YES, PROVIDE NEW SMOKE ON RECALL PANEL

10. ELEVATOR PIT SMOKE / HEAT DETECTOR: NO, REMOVE ANY EXISTING.

11. TOP OF HOISTWAY SMOKE / HEAT DETECTOR: NO, REMOVE ANY EXISTING.

12. ELEVATOR PIT SPRINKLER: NO, REMOVE IF EXISTING

13. TOP OF HOISTWAY SPRINKLER: NO, REMOVE IF EXISTING.

14. ELEVATOR LOBBY SMOKE DETECTORS: PROVIDE NEW ON NEW RECALL PANEL

15. PROVIDE MODULES FOR PRIMARY & SECONDARY RECALL, HELMET LAMP

16. SEE PLANS FOR PROPOSED LOCATION OF NEW RECALL PANEL. FIELD COORDINATE FOR BEST

LOCATION ENSURING: MINIMUM 36" CLEARANCE IN FRONT PER NEC; DO NOT LOCATE INSIDE

ELEVATOR MACHINE ROOM; DO NOT LOCATE IN CORRIDOR, LOBBY, OFFICE, LAB, OR OTHER

SIMILAR WORK SPACE OR PUBLIC SPACE UNLESS SHOWN ON THIS SHEET OR OTHERWISE

APPROVED. FINAL LOCATION MUST BE APPROVED BY CONTRACTING OFFICER BEFORE FINAL

SELECTION AND MOUNTING. GOOD LOCATION WOULD ALLOW FOR ADDITIONAL FUTURE PANELS

(AMPLIFIERS / NAC'S, ETC.) WITH FIRE ALARM UPGRADE.

17. EXISTING CONDUIT MAY BE RE-USED IF PROVIDED WITH 3/4" RED BANDS ON EACH SECTION AND

NOT MORE THAN 5' APART, AND FULLY WARRANTED AGAINST ANY GROUND FAULTS.

18. ANY JUNCTION BOXES / CONDUIT TO BE RE-USED MUST BE LOCATED TO COMPLY WITH CONTRACT

REQUIREMENTS AND CODE. (I.E. RELOCATING AS NECESSARY.)

19. MONITOR NEW ELEVATOR RECALL PANEL WITH BUILDING PANEL.

FIRE PROTECTION GENERAL NOTES:

1. SEE FP001 FIRE PROTECTION GENERAL NOTES FOR TYPICAL CRITERIA RELATED TO ELEVATOR

MODERNIZATION PROJECT.

2. THIS DRAWING OUTLINES SPECIFIC INFORMATION RELATED TO THIS BUILDING / ELEVATOR AND

WILL SUPERCEDE GENERAL CRITERIA ON FP001 OR SPECIFICATIONS IF THERE IS A CONFLICT.

S p

S p

S p

S p

S p

S p

S p

REMOVE ANY EXISTING

SMOKE OR HEAT

DETECTORS FROM TOP OF

HISTWAY.

S p

VERIFY IF DETECTOR OUTSIDE HOISTWAY IN ATTIC IS

CONNECTED FOR ELEVATOR FUNCTION OR BUILDING. NOT

REQUIRED FOR ELEVATOR IF THERE IS NO DOOR HERE.

THERE IS A MONITOR MODULE ABOVE

CEILING BY LIGHT THIS AREA. IDENTIFY

IF GOING INTO HOISTWAY AND FUNCTION.

FARP

MM MM

MM MM

MMMMMM

MM

S p

ELEVATOR 005 | BUILDING 007 | #1

FIRE PROTECTION

0' 2' 4' 8' 12'

SCALE: 1/4"=1'-0"

0' 48'

SCALE: 1/16"=1'-0"

16'8' 32'

S p

WF TS

MM

H rr

FARP

LEGEND:

EXISTING FIRE ALARM CONTROL UNIT

FIRE ALARM RECALL PANEL

WATER FLOW/TAMPER MODULES

MONITOR/CONTROL MODULE

PHOTOELECTRIC SMOKE DETECTOR

RATE OF RISE HEAT DETECTOR

FACU

EXISTING FACU

NTS

FP105

EXISTING FACU

NTS

FP105

FACU

EXISTING FACU

EVALUATE SPACE FOR NEW FARP

FIRESTOPPING:

INSTALLING A NEW RECALL PANEL WILL REQUIRE RUNNING NEW CONDUIT INCLUDING WALL/FLOOR PENETRATIONS

THAT ARE TO BE SEALED PER THE LISTED ASSEMBLY BASED ON THE MANUFACTURES DETAIL SHEET.

FLOOR PENETRATIONS THROUGH FLOORS ARE TO BE A MINIMUM 1-HOUR.

PENETRATIONS THROUGH MECHANICAL / ELEVATOR SHAFTS ARE TO BE 2-HOURS WHEN CONNECTING FOUR OR

MORE FLOORS, OR 1-HOUR WHEN CONNECTING UP TO THREE FLOORS.

FOR OTHER THAN SPECIFIC FIRE SERVICE ELEVATORS, MACHINE ROOMS THAT ARE ADJACENT TO AND HAVE ANY PENETRATIONS TO A HOISTWAY ARE TO HAVE AT LEAST THE SAME RATING OF THE HOISTWAY. WHEN THE MACHINE

ROOM DOES NOT ABUT OR HAVE OPENINGS TO THE HOISTWAY, THE MINIMUM RATING IS TO BE 1-HOUR.

SEE SPECIFIC FIRE STOP SPECIFICATIONS FOR ADDITIONAL CRITERIA.

File details come from the government source that posted it. Updated .