ATTACHMENT 1 Site Investigation Report R.pdf

PDF 12 MB Posted

Attached to
BARC Elevator Assessment and Modernization Federal contract opportunity
Solicitation number
12305B24R0033
Issued by
Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery Northeast Area

About this file

The provided document is an Attachment 1 - Site Investigation Report related to the federal contract opportunity for BARC Elevator Assessment and Modernization (Solicitation #12305B24R0033).

The key details are:

  • The United States Department of Agriculture (USDA), Agricultural Research Service (ARS) has a requirement for elevator modernization at the Beltsville Agricultural Research Center (BARC) in Beltsville, MD.
  • This is a total small business set-aside opportunity with a NAICS code of 238290 (Other Building Equipment Contractors) and a construction magnitude between $1,000,000 to $5,000,000.
  • The period of performance is 275 days for one elevator or 520 days if multiple elevators are awarded, with a 2-month overlap between each elevator start.
  • A site visit is scheduled for August 8, 2024 at 9:00 AM ET for offerors to observe project conditions.
  • Proposals will be evaluated using a tradeoff process based on the factors outlined in Sections L and M of the solicitation.

View the file

Other files for this federal contract opportunity

Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Beltsville Agricultural Research

Center (BARC)

Beltsville, MD

BARC Elevator Assessment and

Modernization

Site Investigation Report

Site Investigation Dates: 31 Oct – 2 Nov 2023

Report Date: 16 December 2023

Prepared by:

The Johnson-McAdams Firm, PA

Greenwood, Mississippi

Site Investigative Report BARC Elevator Assessment and Modernization

The Johnson-McAdams Firm, PA Page | 1 16 December 2023

BARC ELEVATOR ASSESSMENT AND MODERNIZATION

BARC Campus, 10300 Baltimore Ave, Beltsville, MD 20705

PROJECT TEAM:

Jermaine Winstead USDA ARS Facilities Manager

Jermaine.winstead@usda.gov 301-504-

Chris L. Robinson, AIA Johnson McAdams

Architectural, PM Chris.robinson@jmcfirm.com 601-544-

Dallas Baker, PE Johnson McAdams

Engineering Dallas.baker@jmcfirm.com 601-953-

Scott Lacey, FPE Johnson McAdams

Life Safety Scott.lacey@jmcfirm.com 501-679-

Steve Weaver, QEI Adonai Consultants

Qualified Elevator Inspector sw@adonaiconsults.com 202-528-

PROJECT INVESTIGATION DATES: October 31, 2023 – November 2, 2023

PROJECT OVERVIEW:

The USDA engaged with The Johnson McAdams Firm to investigate 12 elevators at the Beltsville

Agricultural Research Center. These 12 elevators are in 10 different buildings and range in height from 2 landings to 6 landings. The elevators also range in age from approximately 40 years old to only a few years old. The elevators range in types from passenger to service to freight, as well as hydraulic and traction.

This investigation required assessments of all 12 elevators and modernization recommendations for 9 of the 12 elevators. The assessments contain a detailed review of every component of the elevator from the cab, hoistway, hoist equipment, equipment rooms, life safety equipment and elevator electrical service. The modernization includes a detailed list, based on the assessments of each elevator’s deficiencies and recommendations to mitigate. Details of the scope of work for each elevator can be found in the Executive Summary.

This report is organized into several components. The (1) Executive Summary includes the basic findings of the total assessment and recommendations of each elevator, as well as addressing the requirements of the PRD. The (2) Assessment Report includes the detailed findings of each elevator, including elevator basic facts, the cab finishes, life safety issues, hoistway equipment, machine room equipment and signaling equipment. The (3) Modernization Report includes a list of requirements for Modernization of

Elevators #1 - #9 based on the Assessment Report findings. The (4) Permitting Requirements includes a list of all governing and code official authorities and agencies having jurisdiction over these elevators. It also includes a list of governing documents. The (5) Qualified Elevator Inspector’s Report includes a detailed analysis of each elevator’s condition as prepared by the Qualified Elevator Inspector (QEI). The

(6) Elevator Equipment Assessments include a detailed analysis provided by the Owner’s vendor for certain elevators; this analysis is used to supplement the QEI report findings. The (7) Hazardous

Materials Report includes the testing results and recommendations of these hazardous materials investigation taken on site. The (8) Centralized Monitoring System Options includes cut sheets from various manufacturers for review. The (9) Independent Government Estimate includes an itemized list of elevator components based on the recommendations of the Assessment Report; this estimate can be found in a separate document.

mailto:Jermaine.winstead@usda.gov mailto:Chris.robinson@jmcfirm.com mailto:Dallas.baker@jmcfirm.com mailto:Scott.lacey@jmcfirm.com mailto:sw@adonaiconsults.com

The Johnson-McAdams Firm, PA Page | 2

INDEX

EXECUTIVE SUMMARY 3

ASSESSMENT REPORT 4

Elevator #1 Findings 4

Elevator #2 Findings 9

Elevator #3 Findings 14

Elevator #4 Findings 19

Elevator #5 Findings 24

Elevator #6 Findings 29

Elevator #7 Findings 34

Elevator #8 Findings 39

Elevator #9 Findings 44

Elevator #10 Findings 49

Elevator #11 Findings 54

Elevator #12 Findings 59

MODERNIZATION REPORT (ELEVATORS #1-#9) 64

PERMITTING REQUIREMENTS 66

APPENDIX A: QUALIFIED ELEVATOR INSPECTOR’S REPORT (ELEVATORS 1 – 12)

APPENDIX B: ELEVATOR EQUIPMENT ASSESSMENTS (ELEVATORS 1, 2, 3, 4, 7, 8, 11)

APPENDIX C: HAZARDOUS MATERIALS REPORT

APPENDIX D: CENTRALIZED MONITORING SYSTEM OPTIONS

INDEPENDENT GOVERNMENT ESTIMATE (SEPARATE DOCUMENT)

The Johnson-McAdams Firm, PA Page | 3

EXECUTIVE SUMMARY:

The following is a synopsis of the Elevator Assessments provided within this document for each elevator investigated. This includes 1) a brief description of deficiencies, if any, of each elevator, 2) a base recommendation for “maintenance/repair” or “modernization” based on these assessment findings, and

3) an option recommendation to add scope to fully modernize to the level of replacement. An estimated cost for correction of deficiencies can be found in a separate cost estimate document.

ASSESSMENT SYNOPSIS: Note that the elevator # below corresponds with the elevator # in the PRD.

Modernization is denoted as “MOD”; Maintenance and Repair is denoted as "M/R”.

# PRIMARY CAUSE(S)

#1 MOD HOIST/PUMP/CONTROLLER/FINISHES/DOORS/SAFETY DEVICES

#2 MOD HOIST/PUMP/CONTROLLER/FINISHES/DOORS/SAFETY DEVICES

#3 MOD HOIST/PUMP/CONTROLLER/FINISHES/DOORS/SAFETY DEVICES

#4 MOD HOIST/PUMP/CONTROLLER/FINISHES/DOORS/SAFETY DEVICES

#5 MOD HOIST/PUMP/CONTROLLER/FINISHES/DOORS/SAFETY DEVICES/CAR SLING

#6 MOD HOIST/PUMP/CONTROLLER/FINISHES/DOORS/SAFETY DEVICES

#7 MOD HOIST/PUMP/CONTROLLER/FINISHES/DOORS/SAFETY DEVICES/SIGNALING DEVICES

#8 MOD HOIST/PUMP/CONTROLLER/FINISHES/DOORS/SAFETY DEVICES/SIGNALING DEVICES

#9 MOD HOIST/PUMP/CONTROLLER/FINISHES/DOORS/SAFETY DEVICES/SIGNALING DEVICES

#10 M/R INSTALLATION NEEDS TO BE COMPLETED

#11 M/R VARIOUS ITEMS LISTED IN APPENDIX A & B

#12 M/R VARIOUS ITEMS LISTED IN APPENDIX A & B

CENTRALIZED MONITORING SYSTEM:

Most large elevator companies offer a centralized monitoring system for elevators. These systems cost in the range of $15k to $25k per elevator depending on the level of desired monitoring. These systems also require CAT-6 connectivity at the elevator location and possible fiber connectivity between multiple buildings to monitor from one location. If these connections are not already in place, they would need to be installed at an estimated cost of $50k to $100k. These systems are subscription-based running about $75 to $100 per month per elevator. Additional information and brochures are attached in

Appendix D for review on the monitoring systems from three major elevator companies.

PERMITTING REQUIREMENTS

The governing authorities and documents associated with elevator modernization are listed after the individual elevator assessments.

HAZARDOUS MATERIALS SUMMARY:

Asbestos was not detected in any component tested during the exercise. Asbestos is suspected in the flooring of certain elevators per the report. Due to the building user’s preference, samples were NOT taken inside the elevators. It is assumed that these floors contain asbestos and will be treated as such in this project. Lead was found in two elevator machine room door frames: Building 7 and Building 308.

The Johnson-McAdams Firm, PA Page | 4

ASSESSMENT REPORT:

PRD REF ELEVATOR #1: BUILDING #001; ELEVATOR #1

FINDINGS: Elevator #1 was found to be NON-OPERATIONAL.

The elevator was not operational during the site visit. The QEI opened the car doors for the assessment.

The state of the elevator signaling was unknown due to lack of operation. The elevator specifications matrix can be found below. The elevator life safety report can be found after the matrix. The elevator qualified elevator inspector’s report is attached as Appendix A. The hazardous materials report is attached as Appendix B.

REVIEWED ITEM ELEVATOR 1 ELEVATOR NOT WORKING

BUILDING # 001 Note this elevator was not accessible nor operational at the time of the site visit

ELEVATOR # 1

TYPE HYDRAULIC

CONFIGURATION

CAPACITY

MANUFACTURER

LANDINGS #

HOISTWAY MATERIAL

ELEVATOR ROOM ADJACENT

DOOR DIM (WXH)

CONFIGURATION

TYPE

MATERIAL (IN/OUT)

JAMB PLATES

LANTERN (HALL/CAB)

CAR POST. IND. (HALL/CAB)

CAB SIZE (WXDXH)

CAB FINISH (F/S/R)

CAB FLOOR

CAB CEILING/LIGHTS

RAILINGS

PAD HOOKS

*Note: All pit depths were measured at 5’-0”; All hoistways contained hoist beams

**Note: Floor to floor heights between all landings were not measured

***Note: All elevators contained phones, help buttons, and fire fighter key switches

The Johnson-McAdams Firm, PA Page | 5

PRD REF ELEVATOR #1 (CONTINUED):

PICTURE FORTHCOMING FROM QEI PICTURE FORTHCOMING FROM QEI

TYPICAL ELEVATOR ENTRY TYPICAL ELEVATOR JAMB

ELEVATOR CONTROLS ELEVATOR CONTROLS

The Johnson-McAdams Firm, PA Page | 6

PRD REF ELEVATOR #1 (CONTINUED):

CAB WALLS – REAR AND SIDES CAB WALLS – FRONT AND SIDES

ELEVATOR FLOOR ELEVATOR CEILING

ELEVATOR EQUIPMENT ROOM

The Johnson-McAdams Firm, PA Page | 7

PRD REF ELEVATOR #1 (CONTINUED): LIFE SAFETY REPORT:

The following table summarizes the findings of the referenced elevator regarding its fire alarm and fire sprinkler systems. These items relate to protection of the hazard, recall functions, shunt-trip functions, and related protection. All findings are based on visual observations only and no operational functions were tested or verified. Items that were identified to need attention are indicated as “YES” in the respective column.

During the draft report preparation there are some items that the fire protection engineer still needs to verify from the inspector’s photos inside the elevator hoistway. These items will be indicated as “TBD”.

CONDITION:

NOTES:

NEEDS

ATTENTION:

TYPE HYDRAULIC

BUILDING SPRINKLERED YES, FIRE PUMP OFF LINE

MACHINE ROOM HAS SPRINKLERS YES, OFF DOCK DRY PIPE SYSTEM

ELEVATOR PIT HAS SPRINKLER YES, SERVED BY MACHINE ROOM VALVE

TOP OF HOISTWAY SPRINKLER TBD

SHUNT-TRIP BREAKER PROVIDED YES

SHUNT-TRIP ACTIVATED BY HEAT

OR WATER FLOW?

HEAT

INSPECTOR TEST IF WATER FLOW NA

MONITORED ISOLATION VALVE ON

MACHINE ROOM SPRINKLER

YES, ON DOCK

MONITORED ISOLATION VALVE ON

PIT SPRINKLER

NOT IDENTIFIED

FIRE ALARM BRAND / MODEL NOTIFIER AFP-400

FIRE ALARM SYSTEM IS

OPERATIONAL

YES, MULTIPLE FAULTS/TROUBLES/SHORT

LOBBY SMOKE DETECTORS YES

MACHINE ROOM SMOKE

DETECTOR

YES

MACHINE ROOM HEAT DETECTOR YES

TOP OF HOISTWAY SMOKE

DETECTOR

INSTALL PER NFPA

TOP OF HOISTWAY HEAT

DETECTOR

INSTALL PER NFPA

PIT SMOKE DETECTOR INSTALL PER NFPA

PIT HEAT DETECTOR INSTALL PER NFPA

PRIMARY RECALL MODULE YES

SECONDARY RECALL MODULE YES

HELMET MODULE NO

SHUNT-TRIP BREAKER MODULE YES

SHUNT-TRIP POWER MONITORED NO

The Johnson-McAdams Firm, PA Page | 8

ADDITIONAL NOTES ELEVATOR OUT OF SERVICE. PUMP OFF LINE. DRY SYSTEM IS

NOT BEING MONITORED DUE TO FIRE ALARM SHORT.

FIRE ALARM PANEL IS NO LONGER AVAILABLE OR SUPPORTED.

FIRE ALARM SYSTEM SHOULD BE REPLACED / UPGRADED

THROUGHOUT BUILDING.

PRD REF ELEVATOR #1 (CONTINUED): RECOMMENDATIONS:

The findings of the Assessment Report recommend for this elevator: MODERNIZATION

The recommendation above is based on the following:

CAB FINISHES:

• Recommend refinishing the cab based on QEI report.

• Flooring suspect of asbestos containing materials (ACM).

LIFE SAFETY:

• Replace or upgrade fire alarm systems throughout the building.

QUALIFIED ELEVATOR INSPECTOR (QEI):

• Building No. 1 is a Dover passenger hydraulic elevator. It was out of service and inaccessible at the time of this survey. This elevator will require a complete modernization to include a new controller, all new wiring, new fixtures, new door equipment, including new linear door operator, and new machine room lighting. The condition of the Piston could not be evaluated. All electrical and mechanical would need upgrading along with the fire alarm system for the elevator.

The Independent Government estimate for this recommendation can be found in a separate document.

The Johnson-McAdams Firm, PA Page | 9

PRD REF ELEVATOR #2: BUILDING #003; ELEVATOR #1

FINDINGS: Elevator #2 was found to be OPERATIONAL.

The door frame and parts of the door finish were scratched from use. The finish on some of the jamb plates was found to be worn limiting the required contrast per ADA. The lanterns were located on the cab and one lens was missing and others were stamped in and damaged. The missing lens had a luminaire in the socket that did not appear to work. The car position indicator inside the cab did not appear to work. The floor was observed to be in poor condition through topical scratches. The elevator specifications matrix can be found below. The elevator life safety report can be found after the matrix.

The elevator qualified elevator inspector’s report is attached as Appendix A. The hazardous materials report is attached as Appendix B.

REVIEWED ITEM ELEVATOR 2 ELEVATOR WORKING

BUILDING # 003

ELEVATOR # 1

TYPE HYDRAULIC

CONFIGURATION PASSENGER

CAPACITY 3000

MANUFACTURER CEMCO/CORBETT

LANDINGS # 5

HOISTWAY MATERIAL TERRACOTTA

DOOR DIM (WXH) 36x84

CONFIGURATION FRONT ONLY

TYPE LEFT

MATERIAL (IN/OUT) SS/SS SCRATCHED

JAMB PLATES YES BRAILLE INCLUDED/CONTRAST RUBBED OFF

LANTERN (HALL/CAB) CAB THE LIGHTS ARE BROKEN AND CRACKED

CAR POST. IND. (HALL/CAB) CAB NOT WORKING

CAB SIZE (WXDXH) 5’11 X 5’8” X 7’5”

CAB FINISH (F/S/R) SS/LAM/LAM WALL & CEILING OK

CAB FLOOR VINYL FLOOR POOR

CAB CEILING/LIGHTS LAM/CAN

RAILINGS REAR WALL SS – FLAT PROFILE

PAD HOOKS NO

*Note: All pit depths were measured at 5’-0”; All hoistways contained hoist beams

The Johnson-McAdams Firm, PA Page | 10

PRD REF ELEVATOR #2 (CONTINUED):

ELEVATOR CONTROLS

The Johnson-McAdams Firm, PA Page | 11

PRD REF ELEVATOR #2 (CONTINUED):

The Johnson-McAdams Firm, PA Page | 12

PRD REF ELEVATOR #2 (CONTINUED): LIFE SAFETY REPORT:

The following table summarizes the findings of the referenced elevator regarding its fire alarm and fire sprinkler systems. These items relate to protection of the hazard, recall functions, shunt-trip functions, and related protection. All findings are based on visual observations only and no operational functions

During the draft report preparation there are some items that the fire protection engineer still needs to verify from the inspector’s photos inside the elevator hoistway. These items will be indicated as “TBD”.

(RESERVED)

BUILDING SPRINKLERED YES

MACHINE ROOM HAS SPRINKLERS YES

ELEVATOR PIT HAS SPRINKLER TBD

TOP OF HOISTWAY SPRINKLER TBD

SHUNT-TRIP BREAKER PROVIDED NO YES

SHUNT-TRIP ACTIVATED BY HEAT

OR WATER FLOW?

NOT PROVIDED

MONITORED ISOLATION VALVE ON

MACHINE ROOM SPRINKLER

YES

MONITORED ISOLATION VALVE ON

FIRE ALARM BRAND / MODEL NOTIFIER AFP 300 / 400 ADDRESSABLE

OPERATIONAL

NO, SYSTEM IN TROUBLE YES

LOBBY SMOKE DETECTORS YES

MACHINE ROOM SMOKE

DETECTOR

YES

MACHINE ROOM HEAT DETECTOR YES

TOP OF HOISTWAY SMOKE

DETECTOR

INSTALL PER NFPA

TOP OF HOISTWAY HEAT

DETECTOR

INSTALL PER NFPA

PIT SMOKE DETECTOR INSTALL PER NFPA

PIT HEAT DETECTOR INSTALL PER NFPA

PRIMARY RECALL MODULE NO YES

SECONDARY RECALL MODULE NO YES

HELMET MODULE NO YES

SHUNT-TRIP BREAKER MODULE NO YES

SHUNT-TRIP POWER MONITORED NO YES

ADDITIONAL NOTES FIRE ALARM PANEL IS DISCONTINUED AND PARTS ARE DIFFICULT

TO FIND. TROUBLE CONDITIONS INDICATE THAT THE SYSTEM IS

The Johnson-McAdams Firm, PA Page | 13

NOT FUNCTIONING PROPERLY AND MAY NOT PERFORM

INTENDED ELEVATOR FUNCTIONS. THE FIRE ALARM SYSTEM

SHOULD BE UPGRADED / REPLACED TO PROVIDE PROPER

ELEVATOR FUNCTIONS. THE CURRENT FIRE ALARM PANEL WAS

PUT IN AS A BAND-AID TO REPLACE AN OLDER PANEL THAT

LIKELY FAILED (BASED ON HOW IT IS INSTALLED). THE BUILDING

FIRE ALARM SYSTEM IS NOT COMPLIANT WITH CODE AND THUS

THE ENTIRE BUILDING FIRE ALARM SYSTEM NEEDS TO BE

REPLACED AND UPGRADED TO CURRENT CODE REQUIREMENTS.

FIRE ALARM PANEL INDICATED A TAMPER VALVE CLOSED AND

THE FIRE PUMP IS OFF-LINE. THIS GENERALLY INDICATES THAT

THE SPRINKLER SYSTEM IS ISOLATED AND THERE IS NO WATER

TO THE SYSTEM, IN VIOLATION OF CODE. IF THIS IS THE CASE,

THE BUILDING CANNOT BE LEGALLY OCCUPIED WITH THE

SPRINKLER SYSTEM OFF-LINE AND OTHER PRECAUTIONS TAKEN.

PRD REF ELEVATOR #2 (CONTINUED): RECOMMENDATIONS:

• The elevator flooring is badly scratched.

• The elevator cab lanterns are damaged beyond repair.

• The elevator entry is scratched on all sides.

• The elevator car position indicator is not working.

• The elevator jamb plates do not meet ADA.

• The fire alarm system should be upgraded/replaced for the entire building.

• The sprinkler system needs to be fully checked and verified.

• Add shunt-trip breaker.

• Address recalls, helmet, and shunt trip modules.

• Replace jack and cab interior.

• The pit needs to be cleaned.

• The cover is missing from the controller.

• Car riding lantern is missing a lens.

The Johnson-McAdams Firm, PA Page | 14

PRD REF ELEVATOR #3: BUILDING #004; ELEVATOR #1

FINDINGS: Elevator #3 was found to be OPERATIONAL.

The floor was observed to be in poor condition through topical scratches. The elevator shaft showed signs of water intrusion; this was investigated by riding the top of the car to the top of the shaft. There, it was discovered that the ventilation mechanical louver was stuck in an open position. The source of the water could not be fully determined. The lighting in the cab is fluorescent with some not working.

The elevator specifications matrix can be found below. The elevator life safety report can be found after the matrix. The elevator qualified elevator inspector’s report is attached as Appendix A. The hazardous materials report is attached as Appendix B.

REVIEWED ITEM ELEVATOR 3 ELEVATOR WORKING

BUILDING # 004

TYPE HYDRAULIC

CONFIGURATION SERVICE

CAPACITY 4500

MANUFACTURER DOVER

LANDINGS # 4

HOISTWAY MATERIAL CMU CONTAINS POSSIBLE WATER LEAK IN HOISTWAY

ELEVATOR ROOM ADJACENT ACCESS FROM OUTSIDE

DOOR DIM (WXH) 48x84

TYPE LEFT

MATERIAL (IN/OUT) SS/PAINTED STEEL

JAMB PLATES YES BRAILLE INCLUDED

LANTERN (HALL/CAB) HALL

CAR POST. IND. (HALL/CAB) HALL

CAB SIZE (WXDXH) 5’9 X 8’4” X 8’0”

CAB FINISH (F/S/R) SS/LAM/LAM WALL & CEILING OK

CAB FLOOR VCT FLOOR POOR

CAB CEILING/LIGHTS PAINTED STEEL/COVE FLUORESCENT – SOME NOT WORKING

RAILINGS SIDE WALLS SS

PAD HOOKS YES

*Note: All pit depths were measured at 5’-0”; All hoistways contained hoist beams

The Johnson-McAdams Firm, PA Page | 15

PRD REF ELEVATOR #3 (CONTINUED):

The Johnson-McAdams Firm, PA Page | 16

PRD REF ELEVATOR #3 (CONTINUED):

ELEVATOR EQUIPMENT ROOM ELEVATOR EQUIPMENT ROOM

The Johnson-McAdams Firm, PA Page | 17

PRD REF ELEVATOR #3 (CONTINUED): LIFE SAFETY REPORT:

The following table summarizes the findings of the referenced elevator regarding its fire alarm and fire sprinkler systems. These items relate to protection of the hazard, recall functions, shunt-trip functions, and related protection. All findings are based on visual observations only and no operational functions

During the draft report preparation there are some items that the fire protection engineer still needs to verify from the inspector’s photos inside the elevator hoistway. These items will be indicated as “TBD”.

MACHINE ROOM HAS SPRINKLERS YES YES

ELEVATOR PIT HAS SPRINKLER TBD

TOP OF HOISTWAY SPRINKLER YES, OSY, FLOW, TAMPER

SHUNT-TRIP BREAKER PROVIDED YES

SHUNT-TRIP ACTIVATED BY HEAT

OR WATER FLOW?

TOP OF HOISTWAY WATER FLOW AND HEAT

(PRESUMED)

INSPECTOR TEST IF WATER FLOW NO, NEEDED ON TOP OF HOISTWAY YES

MONITORED ISOLATION VALVE ON

MACHINE ROOM SPRINKLER

NO, NEEDED YES

MONITORED ISOLATION VALVE ON

FIRE ALARM BRAND / MODEL EDWARDS EST 3X

OPERATIONAL

NO, SYSTEM IN TROUBLE YES

LOBBY SMOKE DETECTORS YES

MACHINE ROOM SMOKE

DETECTOR

YES

MACHINE ROOM HEAT DETECTOR YES

TOP OF HOISTWAY SMOKE

DETECTOR

INSTALL PER NFPA

TOP OF HOISTWAY HEAT

DETECTOR

INSTALL PER NFPA

PIT SMOKE DETECTOR INSTALL PER NFPA

PIT HEAT DETECTOR INSTALL PER NFPA

PRIMARY RECALL MODULE YES

SECONDARY RECALL MODULE YES

HELMET MODULE NO YES

SHUNT-TRIP POWER MONITORED NO YES

The Johnson-McAdams Firm, PA Page | 18

ADDITIONAL NOTES TROUBLE CONDITIONS INDICATE THAT THE SYSTEM IS NOT

FUNCTIONING PROPERLY AND MAY NOT PERFORM INTENDED

ELEVATOR FUNCTIONS. FIRE ALARM SYSTEM REQUIRES

ATTENTION TO IDENTIFY AND CORRECT TROUBLE CONDITIONS.

PRD REF ELEVATOR #3 (CONTINUED): RECOMMENDATIONS:

• The elevator cab lighting is only partially working and is fluorescent.

• The elevator hoistway shows signs of water intrusion which can damage elevator equipment.

• The ventilation opening at the top of the hoistway is not working properly.

• Sprinkler in hydraulic machine room issue.

• Address fire alarm system issues.

• Install water flow monitor on hoistway sprinkler system.

• Install helmet module.

• Shunt trip power should be monitored.

• The ventilation fan in machine room needs repair (the belt for the motor is frayed and unconnected).

• The Controller is obsolete and is no longer supported by the OEM manufacturer.

• Fire caulking or firestopping is needed behind facia panel in hoistway to close the gaps.

The Johnson-McAdams Firm, PA Page | 19

PRD REF ELEVATOR #4: BUILDING #006; ELEVATOR #1

FINDINGS: Elevator #4 was found to be NON-OPERATIONAL.

This elevator was observed to not be functioning in a consistent and normal way. The elevator was called several times without response. The elevator did respond one time and at this point the elevator entry doors were observed to not be functioning normally. The “freight” type bi-parting doors had a mechanized opener that did not work for the lobby doors and the cab doors did not have straps for manual operation. The elevator entry jambs did not include plates as required by the ADA. The freight interior showed wear, which is normal in a freight-type elevator. The lighting was fluorescent. The elevator specifications matrix can be found below. The elevator life safety report can be found after the matrix. The elevator qualified elevator inspector’s report is attached as Appendix A. The hazardous

REVIEWED ITEM ELEVATOR 4 ELEVATOR NOT WORKING PROPERLY

BUILDING # 006

TYPE HYDRAULIC

CONFIGURATION FREIGHT

CAPACITY 3000

MANUFACTURER ATLANTIC

LANDINGS # 3

HOISTWAY MATERIAL CMU

ELEVATOR ROOM ADJACENT EXTERIOR ACCESS

DOOR DIM (WXH) 50x84

CONFIGURATION FRONT & REAR REAR AT BASEMENT ONLY

TYPE BI-PART HALL DOORS NOT WORKING/CAB DOORS DO

NOT INCLUDE STRAPS

MATERIAL (IN/OUT) CAGE/PAINTED STEEL

JAMB PLATES YES BRAILLE NOT INCLUDED

CAB SIZE (WXDXH) 4’2 X 5’5” X 8’0”

CAB FINISH (F/S/R) CAGE/PAINTED

STEEL/CAGE

CAB FLOOR DIAMOND TREAD

CAB CEILING/LIGHTS PAINTED STEEL/SLOT FLUORESCENT

RAILINGS NONE

PAD HOOKS NO

*Note: All pit depths were measured at 5’-0”; All hoistways contained hoist beams

The Johnson-McAdams Firm, PA Page | 20

PRD REF ELEVATOR #4 (CONTINUED):

The Johnson-McAdams Firm, PA Page | 21

PRD REF ELEVATOR #4 (CONTINUED):

The Johnson-McAdams Firm, PA Page | 22

PRD REF ELEVATOR #4 (CONTINUED): LIFE SAFETY REPORT:

The following table summarizes the findings of the referenced elevator regarding its fire alarm and fire sprinkler systems. These items relate to protection of the hazard, recall functions, shunt-trip functions, and related protection. All findings are based on visual observations only and no operational functions

During the draft report preparation there are some items that the fire protection engineer still needs to verify from the inspector’s photos inside the elevator hoistway. These items will be indicated as “TBD”.

BUILDING SPRINKLERED NO

MACHINE ROOM HAS SPRINKLERS NO

ELEVATOR PIT HAS SPRINKLER NO

TOP OF HOISTWAY SPRINKLER NO

SHUNT-TRIP BREAKER PROVIDED NO

SHUNT-TRIP ACTIVATED BY HEAT

OR WATER FLOW?

NA

INSPECTOR TEST IF WATER FLOW NA

MONITORED ISOLATION VALVE ON

MACHINE ROOM SPRINKLER

NA

MONITORED ISOLATION VALVE ON

NA

FIRE ALARM BRAND / MODEL NOTIFIER AFP-200

OPERATIONAL

YES, NO TROUBLES INDICATED

LOBBY SMOKE DETECTORS YES

MACHINE ROOM SMOKE

DETECTOR

YES

MACHINE ROOM HEAT DETECTOR NO

TOP OF HOISTWAY SMOKE

DETECTOR

INSTALL PER NFPA

TOP OF HOISTWAY HEAT

DETECTOR

INSTALL PER NFPA

PIT SMOKE DETECTOR INSTALL PER NFPA

PIT HEAT DETECTOR INSTALL PER NFPA

PRIMARY RECALL MODULE NO YES

SECONDARY RECALL MODULE NO YES

HELMET MODULE NO YES

SHUNT-TRIP BREAKER MODULE NO

SHUNT-TRIP POWER MONITORED NO

ADDITIONAL NOTES PANEL IS DISCONTINUED AND PARTS ARE HARD TO FIND. THUS,

REQUIRED MODULES FOR RECALL AND HELMET WITH NEW

The Johnson-McAdams Firm, PA Page | 23

ELEVATOR ARE LIKELY NOT AVAILABLE FOR THIS PANEL WHICH

WOULD REQUIRE A DEDICATED ELEVATOR FIRE ALARM RECALL

PANEL OR REPLACEMENT OF THE EXISTING FIRE ALARM PANEL.

REPLACEMENT OF A PANEL GENERALLY REQUIRES THE BUILDING

FIRE ALARM TO BE BROUGHT UP TO CODE.

PRD REF ELEVATOR #4 (CONTINUED): RECOMMENDATIONS:

• IT SHOULD BE NOTED THAT THIS “FREIGHT-TYPE” ELEVATOR COULD BE REPLACED WITH A

“SERVICE-TYPE” ELEVATOR WITH THE SAME CAPACITY AND FUNCTIONALITY. THE SERVICE

ELEVATOR WOULD OPERATE IN A MORE USER-FRIENDLY MANNER. A DOWNSIDE TO THIS

CONVERSION WOULD BE THE ELEVATOR ENTRANCE WOULD NEED TO BE SMALLER AND THE

ENTRANCES WOULD NEED TO BE REPLACED.

• The entrance doors do not work properly.

• The entrance jambs do not have plates required for the ADA.

• The elevator lighting is fluorescent.

• Address recalls and helmet modules.

• Install dedicated elevator fire alarm recall which would require fire alarm to be up to code building wide.

• The automatic freight doors do not work.

• The doors are missing proper pull straps.

• The key is missing to the emergency door access panel, not allowing access in the event of an emergency.

• The pit needs to be cleaned.

• The Machine Room needs to be cleaned.

• The disconnects are not labeled with the feeder location.

The Johnson-McAdams Firm, PA Page | 24

PRD REF ELEVATOR #5: BUILDING #007; ELEVATOR #1

FINDINGS: Elevator #5 was found to be OPERATIONAL.

This elevator is in a building that was observed as being vacant. The elevator cab finished appeared to be in good condition except for the flooring. The elevator entry jambs did not include plates which are required by the ADA. The elevator specifications matrix can be found below. The elevator life safety report can be found after the matrix. The elevator qualified elevator inspector’s report is attached as

Appendix A. The hazardous materials report is attached as Appendix B.

REVIEWED ITEM ELEVATOR 5 ELEVATOR WORKING

BUILDING # 007

TYPE TRACTION

CONFIGURATION PASSENGER

CAPACITY 2000

MANUFACTURER ATLANTIC/GURNEY

LANDINGS # 4

ELEVATOR ROOM OVER SHAFT

DOOR DIM (WXH) 42x84

TYPE LEFT

MATERIAL (IN/OUT) SS/PAINTED STEEL

JAMB PLATES NONE BRAILLE NOT INCLUDED

LANTERN (HALL/CAB) CAB

CAB SIZE (WXDXH) 5’6 X 4’-0” X 7’5”

CAB FINISH (F/S/R) SS/LAM/LAM

CAB FLOOR VINYL FLOOR POOR

CAB CEILING/LIGHTS SS/CANS

RAILINGS REAR SS – ROUND PROFILE

PAD HOOKS YES

*Note: All pit depths were measured at 5’-0”; All hoistways contained hoist beams

The Johnson-McAdams Firm, PA Page | 25

PRD REF ELEVATOR #5 (CONTINUED):

ELEVATOR CONTROLS

The Johnson-McAdams Firm, PA Page | 26

PRD REF ELEVATOR #5 (CONTINUED):

The Johnson-McAdams Firm, PA Page | 27

PRD REF ELEVATOR #5 (CONTINUED): LIFE SAFETY REPORT:

The following table summarizes the findings of the referenced elevator regarding its fire alarm and fire sprinkler systems. These items relate to protection of the hazard, recall functions, shunt-trip functions, and related protection. All findings are based on visual observations only and no operational functions

During the draft report preparation there are some items that the fire protection engineer still needs to verify from the inspector’s photos inside the elevator hoistway. These items will be indicated as “TBD”.

TYPE CABLE

MACHINE ROOM HAS SPRINKLERS NO

ELEVATOR PIT HAS SPRINKLER NO

TOP OF HOISTWAY SPRINKLER NOT IDENTIFIED

SHUNT-TRIP BREAKER PROVIDED NO

SHUNT-TRIP ACTIVATED BY HEAT

OR WATER FLOW?

NA

INSPECTOR TEST IF WATER FLOW NA

MONITORED ISOLATION VALVE ON

MACHINE ROOM SPRINKLER

NO SPRINKLER IN MACHINE ROOM

MONITORED ISOLATION VALVE ON

FIRE ALARM BRAND / MODEL NOTIFIER AFP-400

OPERATIONAL

YES, MULTIPLE FAULTS/TROUBLES

LOBBY SMOKE DETECTORS YES

MACHINE ROOM SMOKE

DETECTOR

YES

MACHINE ROOM HEAT DETECTOR NO

TOP OF HOISTWAY SMOKE

DETECTOR

NO NO

TOP OF HOISTWAY HEAT

DETECTOR

NO NO

PIT SMOKE DETECTOR INSTALL PER NFPA

PIT HEAT DETECTOR INSTALL PER NFPA

PRIMARY RECALL MODULE NO YES

SECONDARY RECALL MODULE NO YES

HELMET MODULE NO YES

SHUNT-TRIP BREAKER MODULE NO YES

The Johnson-McAdams Firm, PA Page | 28

ADDITIONAL NOTES MULTIPLE FIRE ALARM TROUBLES RELATED TO ATTIC

SPRINKLERS, DETECTORS, ETC. A FIRE ALARM MODULE WAS

ABOVE CEILING GROUND FLOOR AT ELEVATOR BUT COULD NOT

DETERMINE IF FOR ELEVATOR.

FIRE ALARM PANEL WAS INSTALLED TO REPLACE AN OLDER

SYSTEM AS A BAND-AID AND THE SYSTEM WAS NOT BROUGHT

UP TO CODE AS REQUIRED WITH PANEL REPLACEMENT. THIS

PANEL IS NO LONGER AVAILABLE OR SUPPORTED. THE FIRE

ALARM SYSTEM SHOULD BE REPLACED / UPGRADED

THROUGHOUT THE BUILDING.

PRD REF ELEVATOR #5 (CONTINUED): RECOMMENDATIONS:

• The elevator jambs do not have jamb plates.

• NOTE THAT DOOR FRAME TO MACHINE ROOM TESTED POSITIVE FOR LEAD.

• Replace or upgrade fire alarm system building wide.

• The geared machine is leaking oil excessively.

• The mainline disconnect is not code compliant.

• The smoke detector wiring in the Machine Room is exposed.

• The pit ladder is not code compliant.

• The Machine Room has no GFCI outlet.

• The door operator cover is missing.

• The emergency phone does not work.

The Johnson-McAdams Firm, PA Page | 29

PRD REF ELEVATOR #6: BUILDING #010A; ELEVATOR #1

FINDINGS: Elevator #6 was found to be OPERATIONAL.

The laminate finish on the elevator cab walls was observed as delaminating from the MDF backing. This was stated to be a direct violation of the elevator code requiring class fire protection of all combustible surfaces. The floor was observed to be in poor condition through topical scratches. The elevator specifications matrix can be found below. The elevator life safety report can be found after the matrix.

The elevator qualified elevator inspector’s report is attached as Appendix A. The hazardous materials

REVIEWED ITEM ELEVATOR 6 ELEVATOR WORKING

BUILDING # 010A

TYPE HYDRAULIC

CONFIGURATION SERVICE

CAPACITY 4500

MANUFACTURER ESCO

LANDINGS # 4

TYPE RIGHT

MATERIAL (IN/OUT) SS/PAINTED STEEL

JAMB PLATES YES BRAILLE INCLUDED

CAB SIZE (WXDXH) 5’8 X 7’9” X 7’5”

CAB FINISH (F/S/R) SS/LAM/LAM WALL PANELS DELAMINATING - VIOLATION

CAB FLOOR VCT FLOOR POOR

CAB CEILING/LIGHTS SS/CANS

RAILINGS SIDE AND REAR SS – BOX PROFILE

PAD HOOKS NO

*Note: All pit depths were measured at 5’-0”; All hoistways contained hoist beams

The Johnson-McAdams Firm, PA Page | 30

PRD REF ELEVATOR #6 (CONTINUED):

The Johnson-McAdams Firm, PA Page | 31

PRD REF ELEVATOR #6 (CONTINUED):

The Johnson-McAdams Firm, PA Page | 32

PRD REF ELEVATOR #6 (CONTINUED): LIFE SAFETY REPORT:

The following table summarizes the findings of the referenced elevator regarding its fire alarm and fire sprinkler systems. These items relate to protection of the hazard, recall functions, shunt-trip functions, and related protection. All findings are based on visual observations only and no operational functions

During the draft report preparation there are some items that the fire protection engineer still needs to verify from the inspector’s photos inside the elevator hoistway. These items will be indicated as “TBD”.

ELEVATOR PIT HAS SPRINKLER TBD

TOP OF HOISTWAY SPRINKLER TBD

SHUNT-TRIP BREAKER PROVIDED NO YES

SHUNT-TRIP ACTIVATED BY HEAT

OR WATER FLOW?

NA YES

INSPECTOR TEST IF WATER FLOW NA

MONITORED ISOLATION VALVE ON

MACHINE ROOM SPRINKLER

YES

MONITORED ISOLATION VALVE ON

FIRE ALARM BRAND / MODEL SIMPLEX (MODEL NOT IDENTIFIED)

OPERATIONAL

NO, TROUBLES ON SYSTEM YES

LOBBY SMOKE DETECTORS YES

MACHINE ROOM SMOKE

DETECTOR

YES

MACHINE ROOM HEAT DETECTOR YES

TOP OF HOISTWAY SMOKE

DETECTOR

INSTALL PER NFPA

TOP OF HOISTWAY HEAT

DETECTOR

INSTALL PER NFPA

PIT SMOKE DETECTOR INSTALL PER NFPA

PIT HEAT DETECTOR INSTALL PER NFPA

PRIMARY RECALL MODULE NO YES

SECONDARY RECALL MODULE NO YES

HELMET MODULE NO YES

SHUNT-TRIP BREAKER MODULE NO YES

The Johnson-McAdams Firm, PA Page | 33

ADDITIONAL NOTES THERE APPEARED TO BE A FIRE ALARM CIRCUIT GOING INTO A

CONTROL CABINET WHICH WAS NOT OPENED. NO INDICATION

OF MODULES UNLESS THEY WERE IN THIS CABINET.

PRD REF ELEVATOR #6 (CONTINUED): RECOMMENDATIONS:

• The elevator cab wall finishes are delaminating and must be replaced.

• The elevator cab wall finishes are delaminating and must be replaced.

• Address missing shunt-trip breaker.

• Address fire alarm system issues.

• The cab interior needs to be replaced; laminate has chips, which compromise the fire rating.

• Pit switch is not code compliant.

The Johnson-McAdams Firm, PA Page | 34

PRD REF ELEVATOR #7: BUILDING #307B; ELEVATOR #1

FINDINGS: Elevator #7 was found to be OPERATIONAL.

The elevator cab included several light fixtures that were observed as not working properly. The elevator specifications matrix can be found below. The elevator life safety report can be found after the matrix.

The elevator qualified elevator inspector’s report is attached as Appendix A. The hazardous materials

REVIEWED ITEM ELEVATOR 7 ELEVATOR WORKING

BUILDING # 307B

TYPE HYDRAULIC

CONFIGURATION PASSENGER

CAPACITY 2500

MANUFACTURER THYSSEN KRUPP

LANDINGS # 2

TYPE BI-PART

MATERIAL (IN/OUT) SS/PAINTED STEEL

JAMB PLATES YES BRAILLE INCLUDED

CAR POST. IND. (HALL/CAB) CAB

CAB SIZE (WXDXH) 6’9 X 4’8” X 8’0”

CAB FINISH (F/S/R) SS/PAINTED STEEL/

PAINTED STEEL

CAB FLOOR VCT OR VINYL

CAB CEILING/LIGHTS PAINT/CANS

RAILINGS SIDE AND REAR SS – ROUND PROFILE

PAD HOOKS YES

*Note: All pit depths were measured at 5’-0”; All hoistways contained hoist beams

The Johnson-McAdams Firm, PA Page | 35

PRD REF ELEVATOR #7 (CONTINUED):

The Johnson-McAdams Firm, PA Page | 36

PRD REF ELEVATOR #7 (CONTINUED):

The Johnson-McAdams Firm, PA Page | 37

PRD REF ELEVATOR #7 (CONTINUED): LIFE SAFETY REPORT:

The following table summarizes the findings of the referenced elevator regarding its fire alarm and fire sprinkler systems. These items relate to protection of the hazard, recall functions, shunt-trip functions, and related protection. All findings are based on visual observations only and no operational functions were tested or verified. Items that were identified to need attention are indicated as “YES” in the respective column.

During the draft report preparation there are some items that the fire protection engineer still needs to verify from the inspector’s photos inside the elevator hoistway. These items will be indicated as “TBD”.

ELEVATOR PIT HAS SPRINKLER TBD

TOP OF HOISTWAY SPRINKLER TBD

SHUNT-TRIP BREAKER PROVIDED YES, IN ELECTRICAL ROOM

SHUNT-TRIP ACTIVATED BY HEAT

OR WATER FLOW?

HEAT

INSPECTOR TEST IF WATER FLOW NA

MONITORED ISOLATION VALVE ON

MACHINE ROOM SPRINKLER

YES

MONITORED ISOLATION VALVE ON

FIRE ALARM BRAND / MODEL SIEMENS MXL-IQ

OPERATIONAL

YES, BUT TROUBLE ON BASEMENT MANUAL PULL

LOBBY SMOKE DETECTORS YES

MACHINE ROOM SMOKE

DETECTOR

YES

MACHINE ROOM HEAT DETECTOR YES

TOP OF HOISTWAY SMOKE

DETECTOR

INSTALL PER NFPA

TOP OF HOISTWAY HEAT

DETECTOR

INSTALL PER NFPA

PIT SMOKE DETECTOR INSTALL PER NFPA

PIT HEAT DETECTOR INSTALL PER NFPA

PRIMARY RECALL MODULE YES

SECONDARY RECALL MODULE YES

HELMET MODULE YES

SHUNT-TRIP BREAKER MODULE YES. IN ELECTRICAL ROOM

SHUNT-TRIP POWER MONITORED YES, IN ELECTRICAL ROOM

ADDITIONAL NOTES

The Johnson-McAdams Firm, PA Page | 38

PRD REF ELEVATOR #7 (CONTINUED): RECOMMENDATIONS:

• The elevator lights were not all working properly.

• No issues

• A jumper on controller circuitry is a code violation.

• Housekeeping is in poor state.

• Emergency phone box is improperly mounted on car operating panel.

• The pit is dirty and needs to be cleaned.

• Jack packing is leaking.

• Sump pump wiring in pit needs to be treed up properly.

• Machine Room has no A/C.

• Pump Motor valve is leaking.

• 110v outlet in machine room is being obstructed by the tank unit.

• Disconnects are not properly labeled with feed locations.

• Car top needs to be cleaned.

• Hoistway door pick up rollers are missing at Floor No. 2 and Floor AT.

The Johnson-McAdams Firm, PA Page | 39

PRD REF ELEVATOR #8: BUILDING #307B; ELEVATOR #2

FINDINGS: Elevator #8 was found to be OPERATIONAL.

The elevator does contain fluorescent light fixtures that were observed to be working. The elevator specifications matrix can be found below. The elevator life safety report can be found after the matrix.

The elevator qualified elevator inspector’s report is attached as Appendix A. The hazardous materials

REVIEWED ITEM ELEVATOR 8 ELEVATOR WORKING

BUILDING # 307B

ELEVATOR # 2

TYPE HYDRAULIC

CONFIGURATION SERVICE

CAPACITY 5000

MANUFACTURER THYSSEN KRUPP

LANDINGS # 3

TYPE LEFT

MATERIAL (IN/OUT) SS/SS

JAMB PLATES YES BRAILLE INCLUDED

CAB SIZE (WXDXH) 5’8 X 9’0” X 8’0”

CAB FINISH (F/S/R) SS/SS/SS

CAB FLOOR VCT OR VINYL

CAB CEILING/LIGHTS PANEL/STRIP FLUORESCENT

RAILINGS SIDE AND REAR SS – FLAT PROFILE

PAD HOOKS YES

*Note: All pit depths were measured at 5’-0”; All hoistways contained hoist beams

The Johnson-McAdams Firm, PA Page | 40

PRD REF ELEVATOR #8 (CONTINUED):

TYPICAL ELEVATOR ENTRY

The Johnson-McAdams Firm, PA Page | 41

PRD REF ELEVATOR #8 (CONTINUED):

The Johnson-McAdams Firm, PA Page | 42

PRD REF ELEVATOR #8 (CONTINUED): LIFE SAFETY REPORT:

The following table summarizes the findings of the referenced elevator regarding its fire alarm and fire sprinkler systems. These items relate to protection of the hazard, recall functions, shunt-trip functions, and related protection. All findings are based on visual observations only and no operational functions were tested or verified. Items that were identified to need attention are indicated as “YES” in the respective column.

During the draft report preparation there are some items that the fire protection engineer still needs to verify from the inspector’s photos inside the elevator hoistway. These items will be indicated as “TBD”.

ELEVATOR PIT HAS SPRINKLER TBD

TOP OF HOISTWAY SPRINKLER TBD

SHUNT-TRIP BREAKER PROVIDED YES, IN ELECTRICAL ROOM

SHUNT-TRIP ACTIVATED BY HEAT

OR WATER FLOW?

HEAT

INSPECTOR TEST IF WATER FLOW NA

MONITORED ISOLATION VALVE ON

MACHINE ROOM SPRINKLER

YES

MONITORED ISOLATION VALVE ON

OPERATIONAL

YES, BUT TROUBLE ON BASEMENT MANUAL PULL

LOBBY SMOKE DETECTORS YES

MACHINE ROOM SMOKE

DETECTOR

YES

MACHINE ROOM HEAT DETECTOR YES

TOP OF HOISTWAY SMOKE

DETECTOR

INSTALL PER NFPA

TOP OF HOISTWAY HEAT

DETECTOR

INSTALL PER NFPA

PIT SMOKE DETECTOR INSTALL PER NFPA

PIT HEAT DETECTOR INSTALL PER NFPA

PRIMARY RECALL MODULE YES

SECONDARY RECALL MODULE YES

HELMET MODULE YES

SHUNT-TRIP BREAKER MODULE YES. IN ELECTRICAL ROOM

SHUNT-TRIP POWER MONITORED YES, IN ELECTRICAL ROOM

The Johnson-McAdams Firm, PA Page | 43

PRD REF ELEVATOR #8 (CONTINUED): RECOMMENDATIONS:

• The elevator cab lighting is working but is fluorescent.

• Car emergency lighting is inoperative.

• Car emergency phone is inoperative.

• Elevator car lights and emergency lights need to be on separate circuits.

• Disconnects are not properly labeled with feed locations.

• Hoistway door pick up rollers are missing on Floors 1 and 2.

• The pump unit oil pan has excessive oil which should be removed.

The Johnson-McAdams Firm, PA Page | 44

PRD REF ELEVATOR #9: BUILDING #307C; ELEVATOR #1

FINDINGS: Elevator #9 was found to be OPERATIONAL.

The elevator does contain fluorescent light fixtures that were observed to be working. The elevator specifications matrix can be found below. The elevator life safety report can be found after the matrix.

The elevator qualified elevator inspector’s report is attached as Appendix A. The hazardous materials

REVIEWED ITEM ELEVATOR 9 ELEVATOR WORKING

BUILDING # 307C

TYPE HYDRAULIC

CONFIGURATION SERVICE

CAPACITY 5000

MANUFACTURER THYSSEN KRUPP

LANDINGS # 4

TYPE RIGHT

MATERIAL (IN/OUT) SS/SS

JAMB PLATES YES BRAILLE INCLUDED

CAB SIZE (WXDXH) 5’9 X 8’-4” X 8’0”

CAB FLOOR VCT OR VINYL

CAB CEILING/LIGHTS PANEL/STRIP FLUORESCENT

RAILINGS SIDE AND REAR SS – FLAT PROFILE

PAD HOOKS YES

*Note: All pit depths were measured at 5’-0”; All hoistways contained hoist beams

The Johnson-McAdams Firm, PA Page | 45

PRD REF ELEVATOR #9 (CONTINUED):

The Johnson-McAdams Firm, PA Page | 46

PRD REF ELEVATOR #9 (CONTINUED):

The Johnson-McAdams Firm, PA Page | 47

PRD REF ELEVATOR #9 (CONTINUED): LIFE SAFETY REPORT:

The following table summarizes the findings of the referenced elevator regarding its fire alarm and fire sprinkler systems. These items relate to protection of the hazard, recall functions, shunt-trip functions, and related protection. All findings are based on visual observations only and no operational functions were tested or verified. Items that were identified to need attention are indicated as “YES” in the respective column.

During the draft report preparation there are some items that the fire protection engineer still needs to verify from the inspector’s photos inside the elevator hoistway. These items will be indicated as “TBD”.

TYPE

ELEVATOR PIT HAS SPRINKLER YES, SERVED BY MACHINE ROOM VALVE

TOP OF HOISTWAY SPRINKLER YES, WET SYSTEM WITH NO VALVE YES

SHUNT-TRIP BREAKER PROVIDED YES

SHUNT-TRIP ACTIVATED BY HEAT

OR WATER FLOW?

HEAT

INSPECTOR TEST IF WATER FLOW NA

MONITORED ISOLATION VALVE ON

MACHINE ROOM SPRINKLER

YES

MONITORED ISOLATION VALVE ON

OPERATIONAL

NO, CIRCUIT FAULTS

LOBBY SMOKE DETECTORS YES

MACHINE ROOM SMOKE

DETECTOR

YES

MACHINE ROOM HEAT DETECTOR YES

TOP OF HOISTWAY SMOKE

DETECTOR

INSTALL PER NFPA

TOP OF HOISTWAY HEAT

DETECTOR

INSTALL PER NFPA

PIT SMOKE DETECTOR INSTALL PER NFPA

PIT HEAT DETECTOR INSTALL PER NFPA

PRIMARY RECALL MODULE YES

SECONDARY RECALL MODULE YES

HELMET MODULE YES

SHUNT-TRIP BREAKER MODULE YES

SHUNT-TRIP POWER MONITORED NO

The Johnson-McAdams Firm, PA Page | 48

PRD REF ELEVATOR #9 (CONTINUED): RECOMMENDATIONS:

• The elevator cab lighting is working but is fluorescent.

• Install valve at top of hoistway sprinkler.

• Machine Room Housekeeping requires immediate attention.

• Car emergency light and emergency bell are inoperative.

• Hydraulic Oil Tank is missing the dipstick.

• Machine Room disconnect is not labeled with feeder location.

• Shunt Trip Breaker location is missing.

• Car Top Inspection Station buttons are hard to engage.

• Hoistway door pick up rollers are missing at Floor No. B.

• Elevator Emergency Pit Switch is hard to engage.

• There is sever knocking coming from the Piston between Floors 2 and 1 in both directions.

• Car Emergency Phone should be replaced.

• Car operating panel should be properly secured.

The Johnson-McAdams Firm, PA Page | 49

PRD REF ELEVATOR #10: BUILDING #010A; ELEVATOR #2

FINDINGS: Elevator #10 was found to be NON-OPERATIONAL.

The elevator was not operational during the site visit. The QEI opened the car doors for the assessment.

The state of the elevator signaling was unknown due to lack of operation. The floor was observed to be in poor condition through topical scratches. The elevator specifications matrix can be found below. The elevator life safety report can be found after the matrix. The elevator qualified elevator inspector’s report is attached as Appendix A. The hazardous materials report is attached as Appendix B.

REVIEWED ITEM ELEVATOR 10 ELEVATOR NOT WORKING

BUILDING # 010A

ELEVATOR # 2

TYPE HYDRAULIC

CONFIGURATION SERVICE

CAPACITY 4500

MANUFACTURER VMI

LANDINGS # 6

HOISTWAY MATERIAL GYP SHAFT WALL

CONFIGURATION FRONT & REAR REAR ON LEVELS “LD” & “B” ONLY

TYPE RIGHT

MATERIAL (IN/OUT) SS/PAINTED STEEL

JAMB PLATES YES BRAILLE INCLUDED

CAB SIZE (WXDXH) 5’7 X 8’9” X 7’5”

CAB FINISH (F/S/R) SS/LAM/SS WALL & CEILING OK/SS BASE ON SIDE WALLS

CAB FLOOR VCT FLOOR POOR

CAB CEILING/LIGHTS SS/CANS

RAILINGS SIDE WALLS SS – FLAT PROFILE

PAD HOOKS YES

*Note: All pit depths were measured at 5’-0”; All hoistways contained hoist beams

The Johnson-McAdams Firm, PA Page | 50

PRD REF ELEVATOR #10 (CONTINUED):

The Johnson-McAdams Firm, PA Page | 51

PRD REF ELEVATOR #10 (CONTINUED):

The Johnson-McAdams Firm, PA Page | 52

PRD REF ELEVATOR #10 (CONTINUED): LIFE SAFETY REPORT:

The following table summarizes the findings of the referenced elevator regarding its fire alarm and fire sprinkler systems. These items relate to protection of the hazard, recall functions, shunt-trip functions, and related protection. All findings are based on visual observations only and no operational functions were tested or verified. Items that were identified to need attention are indicated as “YES” in the respective column.

During the draft report preparation there are some items that the fire protection engineer still needs to verify from the inspector’s photos inside the elevator hoistway. These items will be indicated as “TBD”.

ELEVATOR PIT HAS SPRINKLER TBD

TOP OF HOISTWAY SPRINKLER TBD

SHUNT-TRIP BREAKER PROVIDED YES

SHUNT-TRIP ACTIVATED BY HEAT

OR WATER FLOW?

HEAT

INSPECTOR TEST IF WATER FLOW NA

MONITORED ISOLATION VALVE ON

MACHINE ROOM SPRINKLER

YES

MONITORED ISOLATION VALVE ON

FIRE ALARM BRAND / MODEL SIMPLEX (MODEL NOT IDENTIFIED)

OPERATIONAL

NO, TROUBLES ON SYSTEM YES

LOBBY SMOKE DETECTORS YES

MACHINE ROOM SMOKE

DETECTOR

YES

MACHINE ROOM HEAT DETECTOR YES

TOP OF HOISTWAY SMOKE

DETECTOR

INSTALL PER NFPA

TOP OF HOISTWAY HEAT

DETECTOR

INSTALL PER NFPA

PIT SMOKE DETECTOR INSTALL PER NFPA

PIT HEAT DETECTOR INSTALL PER NFPA

PRIMARY RECALL MODULE YES

SECONDARY RECALL MODULE YES

HELMET MODULE YES

SHUNT-TRIP BREAKER MODULE YES

SHUNT-TRIP POWER MONITORED YES

ADDITIONAL NOTES ELEVATOR IS NEW AND STILL BEING INSTALLED.

The Johnson-McAdams Firm, PA Page | 53

PRD REF ELEVATOR #10 (CONTINUED): RECOMMENDATIONS:

The findings of the Assessment Report recommend for this elevator: MAINTENANCE/REPAIR

• Investigate issues with fire alarm system.

• This is a newly installed elevator.

• We were informed that the elevator has programming and fire service issues. Awaiting Elevator

Contractor to rectify these issues.

The Johnson-McAdams Firm, PA Page | 54

PRD REF ELEVATOR #11: BUILDING #306; ELEVATOR #1

FINDINGS: Elevator #11 was found to be OPERATIONAL.

The elevator lighting was observed to be fluorescent with some fixtures not illuminating. The elevator specifications matrix can be found below. The elevator life safety report can be found after the matrix.

The elevator qualified elevator inspector’s report is attached as Appendix A. The hazardous materials

REVIEWED ITEM ELEVATOR 11 ELEVATOR WORKING

BUILDING # 306

TYPE TRACTION

CONFIGURATION SERVICE

CAPACITY 4000

MANUFACTURER OTIS

LANDINGS # 4

ELEVATOR ROOM OVER SHAFT

DOOR DIM (WXH) 48x90

TYPE RIGHT

MATERIAL (IN/OUT) SS/PAINTED STEEL

JAMB PLATES YES BRAILLE INCLUDED

LANTERN (HALL/CAB) CAB

CAB SIZE (WXDXH) 5’10 X 7’5” X 7’6”

CAB FINISH (F/S/R) SS/LAM/LAM

CAB FLOOR RUBBER OR VINYL

CAB CEILING/LIGHTS PANEL/STRIP FLUORESCENT – SOME NOT WORKING

RAILINGS SIDE AND REAR SS – FLAT PROFILE; UPPER AND BASE RAILS

PAD HOOKS NO

*Note: All pit depths were measured at 5’-0”; All hoistways contained hoist beams

The Johnson-McAdams Firm, PA Page | 55

PRD REF ELEVATOR #11 (CONTINUED):

The Johnson-McAdams Firm, PA Page | 56

PRD REF ELEVATOR #11 (CONTINUED):

The Johnson-McAdams Firm, PA Page | 57

PRD REF ELEVATOR #11 (CONTINUED): LIFE SAFETY REPORT:

The following table summarizes the findings of the referenced elevator regarding its fire alarm and fire sprinkler systems. These items relate to protection of the hazard, recall functions, shunt-trip functions, and related protection. All findings are based on visual observations only and no operational functions

During the draft report preparation there are some items that the fire protection engineer still needs to verify from the inspector’s photos inside the elevator hoistway. These items will be indicated as “TBD”.

TYPE CABLE

ELEVATOR PIT HAS SPRINKLER YES, PIPE OBSERVED. PIT SPRINKLER NOT

REQUIRED FOR CABLE ELEVATOR

TOP OF HOISTWAY SPRINKLER YES, IN MACHINE ROOM

SHUNT-TRIP BREAKER PROVIDED YES

SHUNT-TRIP ACTIVATED BY HEAT

OR WATER FLOW?

HEAT

INSPECTOR TEST IF WATER FLOW NA

MONITORED ISOLATION VALVE ON

MACHINE ROOM SPRINKLER

YES

MONITORED ISOLATION VALVE ON

YES

FIRE ALARM BRAND / MODEL NOTIFIER (NOT SURE MODEL, MAYBE 320??)

OPERATIONAL

NO, MULTIPLE TROUBLES ON SYSTEM YES

LOBBY SMOKE DETECTORS YES, ONE IN TROUBLE

MACHINE ROOM SMOKE

DETECTOR

YES

MACHINE ROOM HEAT DETECTOR YES

TOP OF HOISTWAY SMOKE

DETECTOR

IN MACHINE ROOM

TOP OF HOISTWAY HEAT

DETECTOR

IN MACHINE ROOM

PIT SMOKE DETECTOR INSTALL PER NFPA

PIT HEAT DETECTOR INSTALL PER NFPA

PRIMARY RECALL MODULE YES

SECONDARY RECALL MODULE YES

HELMET MODULE NOT ESTABLISHED

The Johnson-McAdams Firm, PA Page | 58

ADDITIONAL NOTES TOP OF SHAFT SPRINKLER IS ON ATTIC DRY-PIPE SPRINKLER

ZONE.

PRD REF ELEVATOR #11 (CONTINUED): RECOMMENDATIONS:

• The elevator cab lighting is only partially working and is fluorescent.

• Address fire alarm system issues.

• The Pit requires cleaning.

• Governor is incorrectly placed, making accessibility difficult.

• Machine Room has no HVAC.

• Incorrect Pitch Switch is installed.

• Fire Extinguisher Inspection Tag is outdated.

• Hoistway Doors need proper adjustment and lubrication.

• The motor wiring in the controller is not landed properly and has excessive wiring.

• Machine Room accessibility is unsafe and ladder needs to be located for proper entry.

The Johnson-McAdams Firm, PA Page | 59

PRD REF ELEVATOR #12: BUILDING #307; ELEVATOR #1

FINDINGS: Elevator #12 was found to be OPERATIONAL.

This elevator was observed to be new with all finishes and operations meeting current codes. The elevator specifications matrix can be found below. The elevator life safety report can be found after the matrix. The elevator qualified elevator inspector’s report is attached as Appendix A. The hazardous

REVIEWED ITEM ELEVATOR 12 ELEVATOR WORKING

BUILDING # 307

TYPE TRACTION BELT-DRIVEN

CONFIGURATION PASSENGER

CAPACITY 3500

MANUFACTURER OTIS

LANDINGS # 5

HOISTWAY MATERIAL UNKNOWN

ELEVATOR ROOM REMOTE ATTIC LEVEL

TYPE RIGHT

MATERIAL (IN/OUT) SS/SS

JAMB PLATES YES BRAILLE INCLUDED

CAB SIZE (WXDXH) 6’5 X 5’9” X 7’4”

CAB FLOOR RUBBER OR VINYL

CAB CEILING/LIGHTS SS/CANS LED LIGHTS

RAILINGS SIDE AND REAR SS – FLAT PROFILE

PAD HOOKS NO

*Note: All pit depths were measured at 5’-0”; All hoistways contained hoist beams

The Johnson-McAdams Firm, PA Page | 60

PRD REF ELEVATOR #12 (CONTINUED):

The Johnson-McAdams Firm, PA Page | 61

PRD REF ELEVATOR #12 (CONTINUED):

The Johnson-McAdams Firm, PA Page | 62

PRD REF ELEVATOR #12 (CONTINUED): LIFE SAFETY REPORT:

The following table summarizes the findings of the referenced elevator regarding its fire alarm and fire sprinkler systems. These items relate to protection of the hazard, recall functions, shunt-trip functions, and related protection. All findings are based on visual observations only and no operational functions were tested or verified. Items that were identified to need attention are indicated as “YES” in the respective column.

During the draft report preparation there are some items that the fire protection engineer still needs to verify from the inspector’s photos inside the elevator hoistway. These items will be indicated as “TBD”.

TYPE BELT

ELEVATOR PIT HAS SPRINKLER YES, PIPE OBSERVED WITH VALVE BUT TAMPER

NOT CONNECTED.

TOP OF HOISTWAY SPRINKLER YES, WITH BUTTERFLY VALVE AND MONITORED

SHUNT-TRIP BREAKER…