Attachment 6 - Digital Modules (chop).pdf

PDF 94 KB Posted

Attached to
WATER TREATMENT PLANT (WTP) CLEARWELL REPAIR/REPLACEMENT CONSTRUCTION, GREAT LAKES, IL
Solicitation number
Not on record
Issued by

About this file

This file is a technical specification document showing details about Removable Terminal Blocks (RTBs) and digital I/O modules for Rockwell Automation's CompactLogix and GuardLogix control systems. The document includes detailed tables for RTBs compatible with CompactLogix 5380, Compact GuardLogix 5380 controllers, and Compact 5000 Adapters and I/O modules, with specifications for both screw-type and spring-type terminal blocks.

The document provides comprehensive specifications for 1734 POINT I/O modules, including AC Digital Modules, DC Digital Modules, and Relay Contact Output Modules. It details voltage categories (ranging from 24V DC to 240V AC), input/output configurations, wiring base compatibility, and POINTBus current requirements at 5V DC. The modules include various input and output options such as sink/source configurations, safety modules, and both Form A and Form C relay outputs, with current ratings typically ranging from 50mA to 190mA POINTBus current draw.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

30 Rockwell Automation Publication 1769-SG003A - March 2022

Removable Terminal Blocks

You must order removable terminal blocks (RTBs) for the CompactLogix 5380 and Compact GuardLogix 5380 controllers, and Compact 5000 Adapters and I/O modules, separately. The RTBs are used to connect wiring to the controllers and I/O modules. The following table describes the RTBs.

The CompactLogix 5480 controllers use RTBs for power supply connections.

1734 POINT I/O Modules

Additional 1734 POINT I/O modules can be installed on a CompactLogix 5370 L1 controller. The POINT I/O family is ideal for applications where flexibility and low cost of ownership are key for successful control system design and operation.

An RTB provides the wiring and terminations for field-side connections, and system power for the backplane.

1734 AC Digital Modules

Cat. Nos. Device Supported Description

5069-RTB14CJC-SCREW(1)

(1) Applies to 5069-IY4 module only.

Compact 5000 I/O module

14-pin screw type terminal block with embedded CJC thermistors

5069-RTB14CJC-SPRING(1) 14-pin spring type terminal block with embedded CJC thermistors 5069-RTB18-SCREW 18-pin screw type terminal block 5069-RTB18-SPRING 18-pin spring type terminal block

5069-RTB6-SCREW

5069-FPD module 6-pin screw type terminal block

5069-RTB6-SPRING 6-pin spring type terminal block 5069-RTB64-SCREW CompactLogix 5380 and Compact GuardLogix 5380 controllers

5069-AEN2TR EtherNet/IP adapter 4 and 6-pin screw type terminal block

5069-RTB64-SPRING 4 and 6-pin spring type terminal block

5069-RTB5-SCREW

5069-AENTR EtherNet/IP adapter 5-pin screw type terminal block

5069-RTB5-SPRING 5-pin spring type terminal block

Cat. No. Inputs/Outputs Voltage Category Wiring Base POINTBus™ Current

@ 5V DC

1734-IA2 2 inputs, nonisolated, sink

120V AC

1734-TB, 1734-TBS, 1734-TOP, 1734-TOPS 75 mA

1734-IA4 4 inputs, nonisolated, sink

1734-IM2 2 inputs, nonisolated, sink

220V AC

1734-IM4 4 inputs, nonisolated, sink

1734-OA2 2 outputs, nonisolated, source

120/220V AC

1734-OA4 4 outputs, nonisolated, source

Rockwell Automation Publication 1769-SG003A - March 2022 31

1734 DC Digital Modules

1734 Relay Contact Output Modules

Cat. No. Inputs/Outputs Voltage Category Wiring Base POINTBus Current @ 5V DC

1734-IB2 2 inputs, sink

24V DC

1734-TB, 1734-TBS, 1734-TOP, 1734-TOPS

75 mA 1734-IB4 4 inputs, sink

1734-IB4D 4 inputs, sink, diagnostic 24V DC 50 mA

1734-IB8 8 inputs, sink 24V DC 75 mA

1734-IB8S 8 inputs, sink, safety 24V DC 1734-TB, 1734-TBS, 1734-TOP, 1734-TOPS, 1734-TOP3, 1734-TOP3S 175 mA

1734-IV2 2 inputs, source

24V DC

1734-TB, 1734-TBS, 1734-TOP, 1734-TOPS

75 mA1734-IV4 4 inputs, source

1734-IV8 8 inputs, source

1734-OB2 2 outputs, nonisolated, source

12/24V DC 75 mA

1734-OB2E 2 outputs, nonisolated protected, source

1734-OB2EP 2 outputs, nonisolated protected, source

1734-OB4 4 outputs, nonisolated, source

1734-OB4E 4 outputs, nonisolated protected, source

1734-OB8 8 outputs, nonisolated, source

1734-OB8E 8 outputs, nonisolated protected, source

1734-OB8S 8 outputs, safety 24V DC 1734-TB, 1734-TBS, 1734-TOP, 1734-TOPS, 1734-TOP3, 1734-TOP3S 190 mA

1734-OV2E 2 outputs, nonisolated protected, sink

12/24V DC 1734-TB, 1734-TBS, 1734-TOP, 1734-TOPS 75 mA1734-OV4E 4 outputs, nonisolated protected, sink

1734-OV8E 8 outputs, nonisolated protected, sink

Cat. No. Inputs/Outputs Voltage Range Wiring Base POINTBus Current @ 5V DC

1734-OW2 2 Form A (normally open) relays 5…28.8V DC @ 2.0 A

48V DC @ 0.5 A

125V DC @ 0.25 A

125V DC @ 2.0 A

240V AC @ 2.0 A

1734-TB,1734-TBS, 1734-TOP, 1734-TOPS

80 mA

1734-OW4 4 Form A (normally open) relays

1734-OX2 2 Form C isolated (normally open; normally closed) electromechanical relays 100 mA

File details come from the government source that posted it. Updated .