This is a user manual excerpt for the Allen-Bradley PanelView 5510 operator interface terminals that can monitor and control devices connected to ControlLogix 5570/5580 or CompactLogix 5370/5380/5480 controllers over EtherNet/IP networks.

The document details the hardware features and capabilities of the PanelView 5510 terminals, which include: touch screen displays ranging from 6.5" to 19" in size, keypad options on select models, two 10/100Base-T Ethernet ports supporting Device Level Ring topology, two USB host ports, one USB device port, SD card slot, and 18-30V DC power input. The terminals can connect to up to four controllers, support up to 500 user-defined screens, handle up to 4,000 Logix-based alarms per controller (with appropriate firmware versions), and feature analog resistive touch screens for industrial applications. The manual also describes operator control features including physical keypad functionality, virtual keyboard support, and navigation capabilities.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Rockwell Automation Publication 2715P-UM001E-EN-P - October 2021 11

Chapter 1

Overview

About the PanelView 5510 Terminals

The PanelView™ 5510 terminals are operator interface devices that monitor and control devices attached to ControlLogix® 5570 or 5580 controllers or CompactLogix™ 5370, 5380, or 5480 controllers over an EtherNet/IP™ network.

Animated graphic and text displays provide a view into the operating state of a machine or process. Operators interact with the control system by using the touch screen or keypad of the terminal.

The PanelView 5510 terminals include these features and capabilities:

• Tightly integrated control and design environment allows information to be shared between the PanelView 5510 terminal and the Logix platforms.

• The Studio 5000® environment provides one point of access for both View

Designer and Logix Designer applications(1).

• Connection to up to four ControlLogix 5570 or 5580 controllers or

CompactLogix 5370, 5380, or 5480 controllers with revision 27 firmware or later.(2)

• Supports a maximum of 500 user-defined screens.

• Supports a maximum of 4,000 Logix-based alarms per controller(1).

• Ethernet communication that supports Device Level Ring (DLR), linear, or star network topologies.

• High-speed human machine interface (HMI) button control and easily configured navigation menu.

• Automatic Diagnostics capability.

• Conformal coating available for all terminal sizes.

Topic Page Topic Page

About the PanelView 5510 Terminals 11 Typical Configuration 16

Hardware Features 12 Catalog Number Explanation 16

Operator Control 12 Product Selection 17

Touch Gestures 14 Accessories 17

Studio 5000 Environment 14 Ethernet Cables 18

EtherNet/IP Communication 16

(1) PanelView 5510 firmware can support up to 4,000 Logix-based alarms per controller if you use Studio 5000 View Designer application version 5 and Studio 5000 Logix Designer application version 32 or higher. Earlier versions of the Studio 5000 View Designer or Studio 5000 Logix Designer applications can support up to 1,000 Logix-based alarms. For more information about the Logic-based alarms, see footnote 2.

(2) The PanelView 5510 terminal supports up to 4000 Logix tag-based alarms or up to 1000 Logix instruction-based alarms per controller.

12 Rockwell Automation Publication 2715P-UM001E-EN-P - October 2021

Chapter 1 Overview

• Stainless steel, brandless, DC-power, and conformal-coating are available for the 9-in. wide-screen, touch-only units and the 12-in. wide-screen, touch- only units.

Hardware Features The PanelView 5510 terminals are fixed hardware configurations that provide a range of display sizes and operator input options.

Operator Control All PanelView 5510 terminals have a color display with a touch screen and navigation key, or a touch screen, navigation key, and keypad for operator control.

• Analog, resistive, touch screens provide accurate, durable touch with excellent reliability for control of industrial applications.

L1

L2

L3

L4

L5

L6

L8

L7

R9

R10

Esc

7 98

4 5 6

1 2 3

0 .– R11

R12

R13

R14

R16

R15

Table 1 - Hardware Features

Item Feature Description

1 Display/Keypad TFT color graphic displays with a touch screen and navigation button in a range of display sizes. Some models also have a keypad and function keys providing additional operator input options.

• 6.5-in. touch or touch with keypad

• 7-in. wide screen with touch

• 9-in. wide screen with touch

• 10.4-in. touch or touch with keypad

• 12.1-in. wide screen with touch

• 15-in. touch or touch with keypad

• 19-in. touch

2 Power 18…30V DC (isolated)

3 Mounting slot The slots on the top, bottom, and sides of the terminal are used with mounting levers to mount the device to a panel or enclosure. The number of slots varies by terminal size.

4 Ethernet ports Two 10/100Base-T, Auto MDI/MDI-X, EtherNet/IP ports for controller communication that supports DLR network topology.

5 USB host ports Two USB 2.0 high-speed (type A) host ports.

6 USB device port One USB 2.0 high-speed (type B) device port to connect a host computer that is software-feature dependent.

7 Audio out IMPORTANT: The audio out feature is not functional. The feature is expected to be available in a future software release.

8 Status indicators Light-emitting diode indicators on back of unit provide status and fault conditions.

9 Secure Digital (SD) card slot One slot that supports an SD™ or SDHC™ card that is recommended in Table 6 on page 18.

Rockwell Automation Publication 2715P-UM001E-EN-P - October 2021 13

Overview Chapter 1

• Keypad models are similar except for the number of function keys to the left (L#) and right (R#) of the display. Larger models have more keys.

The physical keypad on the PanelView 5510 terminal is used during runtime to initiate actions, control navigation, and enter data. The terminal also supports a virtual keyboard and numeric keypad that opens on PanelView 5510 terminal screens during runtime.

The terminal also supports the use of a physical keyboard and mouse when connected to the USB ports.

ATTENTION: The keypad and touch screen support input from a finger, stylus, and gloved hand for operation in dry or wet environments. The plastic stylus must have a minimum tip radius of 1.3 mm (0.051 in.). Any other object or tool can damage the keypad or touch screen.

ATTENTION: Do not perform multiple operations simultaneously. Multiple simultaneous operations can result in unintended operation.

• Touch only one operating element on the screen with one finger at one time.

• Press only one key on the terminal at one time.

L84

1 4

Table 2 - PanelView 5510 Terminal Keypad

Item Feature Description

1 Navigation button Opens the navigation menu at the bottom of a screen and displays the contents of a project. The menu allows screen navigation and device configuration.

2 Numeric keypad Contains numeric, decimal, minus, and these keys:

• Backspace - deletes the character to the left of the insertion point.

• Enter - inputs the currently highlighted key or enters a blank line if the insertion point is in the text box of the virtual keyboard.

• Tab-left, Tab-right - selects the previous or next control or input element.

• Esc - cancels or dismisses a dialog.

3 Navigation keys Provides navigation control.

• Arrow keys - selects a key on the virtual keyboard that is above, below, left, or right of the selected key. Arrow keys also move the cursor if the cursor is in a text box.

• Home/End - moves the insertion point to the beginning or end of a text or numeric entry field.

• Page up/Page down - goes to the next or previous pages of a list.

4 Function keys

• 6.5-in. terminal

• 10.4-in. terminal

• 15-in. terminal

Performs specific commands when configured for a screen or any of its graphic elements. For example, L1 can be configured to go to another screen.