ATTACHMENT 6 - 100 Analysis Drawings.pdf

PDF 680 KB Posted

Attached to
Y1DA--PROJECT 675-23-801, BB Improve Lake Baldwin Electrical Electrical Distribution
Solicitation number
36C24826Q0104
Issued by

About this file

These files represent electrical engineering documents for the Lake Baldwin VA Clinic Electrical Upgrades project, specifically a set of electrical one-line diagrams showing existing, demolition, and new electrical system configurations. The documents detail a complex electrical infrastructure upgrade involving medium voltage switchgear, transformers, and emergency power systems at the VA facility. Key elements include demolishing existing generator paralleling switchboards, disconnecting medium voltage transformers from multi-way switches, installing a new step-up transformer, and providing a temporary 2000kW diesel generator to maintain emergency power during construction. The proposed changes involve reconfiguring power distribution from multiple utility sources (north and south OUC) to ensure continuous electrical service while upgrading the site's electrical infrastructure.

The electrical system modifications span multiple buildings and involve sophisticated power management, including 12,470V medium voltage switches, 480V/277V and 208V/120V transformers, and emergency transfer switches. The project includes provisions for maintaining critical power systems during renovation, with specific attention to generator connections, transformer reconfigurations, and ensuring redundant power paths. Notably, the design includes a temporary generator solution to provide 24-hour emergency power during the construction phase, demonstrating careful planning to minimize disruption to the VA clinic's operations.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

s

CR

(18"/18")

M

OW

OC

L 1D6E

K1

K1

TYPICAL OUTLET SYMBOL NOTES

-STAR SYMBOL INDICATES DEVICE IS MOUNTED 4" ABOVE COUNTER,

CASEWORK, BACKSPLASH OR 46" IF NOTHING BELOW.

-INDICATES MOUNTING HEIGHT ABOVE FINISHED FLOOR.

-ISOLATED GROUND

-WEATHER PROOF

-EXPLOSION PROOF

"+84"

"IG"

"WP"

"XP"

20A, 125V, 2 POLE, 3 WIRE GROUNDING SIMPLEX RECEPTACLE

20A, 125V, 2 POLE, 3 WIRE GROUNDING DUPLEX RECEPTACLE

20A, 125V, 2 POLE, 3 WIRE GROUNDING DOUBLE DUPLEX RECEPTACLE

20A, 125V, 2 POLE 3 WIRE GROUNDING DUPLEX RECEPTACLE WITH (2) INTEGRAL

USB CHARGING PORTS

HALF SWITCHED RECEPTACLE - LOWER OUTLET SWITCHED VIA CONTROL ZONE

INDICATED OR NEAREST OCCUPANCY SENSOR. UPPER OUTLET IS UNSWITCHED -

ALWAYS HOT

20A, 125V, 2 POLE 3 WIRE GROUNDING DUPLEX RECEPTACLE CONNECTED TO

CRITICAL BRANCH

20A, 125V, 2 POLE, 3 WIRE GROUNDING GFCI DUPLEX RECEPTACLE

20A, 125V, 2 POLE, 3 WIRE GROUNDING GFCI RECEPTACLE WITH WHILE IN USE

WEATHERPROOF ENCLOSURE.

20A, 125V, 2 POLE 3 WIRE GROUNDING GFCI DUPLEX RECEPTACLE CONNECTED TO

CRITICAL BRANCH

SPECIAL OUTLET. REFER TO SCHEDULE FOR REQUIREMENTS.

CEILING MOUNTED RECEPTACLE, TYPE AS INDICATED ABOVE.

PEDESTAL MOUNTED DUPLEX OR DOUBLE DUPLEX CONVENIENCE RECEPTACLE.

FLOOR BOX - WITH DUPLEX OR DOUBLE DUPLEX RECEPTACLE

FLOOR BOX WITH POWER AND DATA FURNITURE FEED CONNECTIONS. FURNITURE

FEED CIRCUIT QUANTITY AS INDICATED ON PLANS.

ELECTRICAL POWER SWITCH

M - MOTOR RATED WITH INTEGRAL THERMAL OVERLOADS U.O.N.

SURFACE MOUNTED ENCLOSED DIVIDED RACEWAY FOR POWER AND DATA.

DUPLEX SPACING (20A, 125V, 2 POLE, 3 WIRE GROUNDING DUPLEX RECEPTACLE

U.O.N)

DATA OUTLET SPACING (PROVISINS FOR NOT LESS THAN 4 PORTS U.O.N)

POWER / TELECOM. POLE. PROVIDE JUNCTION BOX ABOVE CEILING FOR POWER

CONNECTION (CIRCUIT QUANTITY AS NOTED ON PLANS) FOR FOR TELECOM/DATA

CONNECTIONS (1 PER ASSOCATED WORKSTATION) CONNECT TO WIRING IN

POWER POLE.

EXTENSION CORD REEL.

UNISTRUT RACK

TYPICAL OUTLET SYMBOL CIRCUITING NOTES

NOTES:

1. OUTLETS LOCATED AT COUNTERS SHALL BE LOCATED 18" AFF IN KNEE SPACE IF

PROVIDED OR 4" ABOVE COUNTER OR BACK SPLASH AS APPLICABLE IF NO KNEE

SPACE IS PROVIDED UNLESS NOTED OTHERWISE.

POWER OUTLETS

IG

+30"

CIRCUIT NUMBER

ELEVATION AFF

TYPE2

D

D

M

XXX-XXX

FOOT ON DEVICE INDICATES WALL MOUNTED

MARK NUMBER FOR MECHANICAL EQUIPMENT

KEY NOTE REFERENCE SYMBOL.

XXX-XXX

GENERAL

CIRCUIT NUMBER(S)

PANEL NAME

1LN1-1,3,5

BRANCH CIRCUIT HOMERUN. PROVIDE #12 PHASE, #12

NEUTRAL AND #12 GROUND CONDUCTORS FOR EACH

INDICATED CIRCUIT UNLESS NOTED OTHERWISE. SEE

GENERAL NOTE #2 AND #3.

NO MULTI-WIRE BRANCH CIRCUITS PERMITTED. NO SHARED

NEUTRAL.

CONDUIT RUN CONCEALED IN CEILING OR WALL

CONDUIT RUN BELOW GRADE, UNDER OR CONCEALED IN

FLOOR SLAB, UNDER RAISED FLOOR

CONDUIT RISER UP

CONDUIT RISER DOWN

INDICATES CIRCUIT CONTINUATION

STUB INTO ACCESSIBLE CORRIDOR CEILING SPACE UNLESS

OTHERWISE NOTED

CAP END OF CONDUIT

CONDUIT SLEEVE

POWER CONDUIT FILL EXAMPLE

(2) 4"C, 4 #500, 1#1/0G

TOTAL QUANTITY OF IDENTICAL CONDUIT/WIRE RUNS AS SPECIFIED (AS APPLICABLE)

CONDUIT SIZE (SEE SPECIFICATIONS FOR ALLOWED TYPES)

QUANTITY OF PHASE AND NEUTRAL CONDUCTORS.

NEUTRAL CONDUCTOR MAY BE SPECIFIED SEPARATELY WITH 'N' SUFFIX

CONDUCTOR SIZE (AWG/KCMIL)

QUANTITY OF GROUND CONDUCTORS (ASSUME QTY 1 IF NOT INDICATED)

GROUND CONDUCTOR SIZE (AWG/KCMIL)

CIRCUIT DESIGNATIONS

(R)(R)

NOTES:

THE FOLLOWING SYMBOLS ARE EXAMPLES INTENDED TO SHOW METHODOLOGY FOR

DEMOLITION. THIS APPROACH IS APPLICABLE TO ALL SYMBOLS INDICATED ON THIS SHEET.

NEW - SHOWN HERE FOR REFERENCE AS A COMPARISON AGAINST

EXISTING AND DEMO ITEMS

EXISTING ELECTRICAL ITEM TO BE REMOVED (BOLD AND DASHED)

EXISTING ELECTRICAL ITEM TO BE RELOCATED. HALFTONE

(R) INDICATES NEW LOCATION

EXISTING ELECTRICAL ITEM TO REMAIN. HALFTONE.

DEMOLITION AND REMODEL

LIGHTING FIXTURE DESCRIPTIONS

RECESSED OR SURFACE MOUNTED LUMINAIRE

RECESSED OR SURFACE MOUNTED ROUND DOWNLIGHT LUMINAIRE

STRIP LIGHT, SURFACE MOUNTED (LENGTH AS SHOWN ON PLANS)

LINEAR LUMINAIRE, SURFACE OR RECESSED (SOLID) OR PENDANT (DASHED)

MOUNTED (LENGTH/TYPE AS SHOWN ON PLANS)

LINEAR LUMINAIRE, WALL MOUNTED (LENGTH AS SHOWN ON PLANS)

WALL SCONCE LUMINAIRE

SUSPENDED TRACK LIGHT, TRACK HEAD QUANTITY AS SHOWN ON PLANS

COVE LIGHT. PLACE IN ARCHITECTURAL COVE, COORDINATE EXACT

LOCATIONS WITH ARCHITECTURAL DRAWINGS.

DENOTES DIRECTION OF LIGHT DISTRIBUTION. PROVIDE DIRECTIONAL LIGHT

THROW (WALL WASH EFFECT) WHERE SHOWN.

EXIT SIGN CEILING OR WALL MOUNTED AS INDICATED

INDICATES DIRECTIONAL CHEVRON FOR EXIT SIGNS.

DENOTES LOCATION(S) OF ILLUMINATED EXIT FACE

EMERGENCY TWIN HEAD FLOOD LIGHTING 'BUG EYE' UNIT WITH INTEGRAL

BATTERY PACK

a a

OD2 WALL MOUNTED CONTROL DEVICE

ALPHANUMERIC CODE INDICATING LIGHTING CONTROL ZONE DESIGNATION. WHERE

MULTIPLE CONTROL ZONES ARE INDICATED LIGHTING CONTROL DEVICE SHALL BE

CAPABLE OF CONTROLLING EACH ZONE INDEPENDENTLY, MULTIPLE ZONES SHALL BE

SEPARATED BY A COMMA (I.E. a,a1,b,d...)

SWITCH TYPE DESIGNATION.

LIGHTING CONTROL SENSORS/DEVICES

SENSOR TYPE DESIGNATION

LIGHTING CONTROLS DEVICES

INDICATES NUMBER OF LIGHTING CONTROL ZONES(POLES) - (AS APPLICABLE)

PROVIDE INDEPENDENT CONTROLS FOR EACH ZONE

NO SUBSCRIPT - SINGLE POLE TOGGLE SWITCH WITH ON/OFF CONTROL.

D - DIMMING CONTROL.

OW - WALL MOUNTED PIR OCCUPANCY SENSOR, WITH MANUAL ON/OFF CONTROL

OD - WALL MOUNTED PIR OCCUPANCY SENSOR, WITH MANUAL DIMMING CONTROL

OWD - WALL MOUNTED DT OCCUPANCY SENSOR, WITH MANUAL ON/OFF CONTROL

ODD - WALL MOUNTED DT OCCUPANCY SENSOR, WITH MANUAL DIMMING

CONTROLS

LCD - INTERACTIVE LCD DISPLAY SCREEN FOR LIGHTING CONTROLS

WP - WEATHER PROOF ENCLOSURE

XP - EXPLOSION PROOF (SEE PLANS FOR CLASSIFICATION REQUIREMENTS)

K - KEYED SWITCH

WHERE DIMMING IS SPECIFIED PROVIDE 0-10V DIMMING CONTROL. SUPPLIER TO

CONFIRM DIMMING COMPATIBILITY BETWEEN FIXTURES AND CONTROLS

OC

OCX

OCD

OCDX

OCH

DC

NORMAL RANGE OCCUPANCY SENSOR, PIR, 12FT RADIUS COVERAGE AT 9FT

AFF

EXTENDED RANGE OCCUPANCY SENSOR, PIR, 28FT RADIUS COVERAGE AT 9FT

AFF

NORMAL RANGE OCCUPANCY SENSOR, DUAL TECHNOLOGY, 12FT RADIUS

COVERAGE AT 9FT AFF

EXTENDED RANGE OCCUPANCY SENSOR, DUAL TECHNOLOGY, 28FT RADIUS

COVERAGE AT 9FT AFF

HIGH MOUNT OCCUPANCY SENSOR, PIR, 20FT RADIUS COVERAGE AT 15FT AFF,

30FT RADIUS AT 45FT AFF.

DAYLIGHT HARVESTING PHOTOCELL. PROVIDE DIMMING WHEN USED WITH

DIMMING CONTROLS. WHERE MOUNTED OUTSIDE, INSTALL ON ROOF AND

POINT NORTH.

CEILING MOUNTED SENSOR

WALL MOUNTED SENSOR

LIGHTING CONTROL SEQUENCE OF OPERATIONS

E - EMERGENCY RELAY

TYPE:

1 - MANUAL SWITCHING ONLY

2 - OCCUPANCY SENSOR LOCATED IN WALL SWITCH

3 - OCCUPANCY SENSOR LOCATED IN CEILING

4 - OCCUPANCY SENSORS AND AUTOMATIC DAYLIGHTING

5 - OCCUPANCY SENSOR LOCATED IN CEILING AND PLUG CONTROL

6 - OCCUPANCY SENSOR LOCATED IN CEILING, AUTOMATIC DAYLIGHTING AND

PLUG CONTROL

CONTROL TYPE

D - DIMMING

S - ON/OFF ONLY

NUMBER OF ZONES

T

30A/3P

30A/3P/

20AF

30A/3P

12x3

CP

C

480/277V OR 480V PANEL 208/120V OR 120/240V PANEL

HEAVY DUTY DISCONNECT SWITCH

FUSED DISCONNECT SWITCH

ENCLOSED CIRCUIT BREAKER

MANUAL MOTOR STARTER SWITCH WITH THERMAL OVERLOAD

PROTECTION.

CONTACTOR

VARIABLE FREQUENCY DRIVE

MOTOR - WITH DISCONNECT (WHERE SHOWN IN PLANS)

MOTOR DESIGNATION SHOWN IN BOX

CONTROL PANEL FURNISHED BY OTHERS, INSTALLED BY

DIVISION 26, UNLESS NOTED OTHERWISE

REDUCED VOLTAGE MOTOR STARTER

NUMBER REFERS TO NEMA STARTER SIZE

COMBINATION REDUCED VOLTAGE MOTOR STARTER/DISCONNECT

NUMBER REFERS TO NEMA STARTER SIZE

COMBINATION 2 SPEED MOTOR STARTER/DISCONNECT

MOTOR - WITH DISCONNECT (WHERE SHOWN IN PLANS)

MOTOR DESIGNATION SHOWN IN BOX

CONTROL PANEL FURNISHED BY OTHERS, PROVIDED AND INSTALLED

BY DIVISION 26, UNLESS NOTED OTHERWISE

PUSHBUTTON STATIONS. ONE, TWO, OR THREE AS INDICATED

EMERGENCY POWER OFF' BREAK GLASS STATION.

BUS DUCT, FEEDER OR PLUG-IN TYPE AS INDICATED

CABLE TRAY - WIDTH x HEIGHT AS INDICATED, OR KEY NOTED

UNDER FLOOR DUCT SYSTEM

JUNCTION BOX, ABOVE CEILING (NO FOOT) OR FLUSH WALL MOUNTED

(WITH FOOT)

T = JUNCTION BOX FOR VOICE/DATA

JUNCTION BOX WITH FLEXIBLE CONNECTION TO EQUIPMENT

INDICATED AND REQUIRED

LADDER STYLE CABLE TRAY, 4IN TALL FOR POWER, 2IN TALL FOR

DATA/SIGNAL U.O.N. WIDTH AS SHOWN ON DRAWINGS.

CONDUIT - SEE SPECIFICATIONS.

POWER DISTRIBUTION

30A/3P

30A/3P

30A/3P

TABS INDICATE FLUSH MOUNTED PANEL

INDICATES REQUIRED

CLEARANCE

VFD

JJJ

J

TYPICAL OUTLET SYMBOL NOTES

"*" -MOUNTED +4" ABOVE COUNTER, CASEWORK, BACKSPLASH OR 46" IF NOTHING

BELOW. COORDINATE WITH ARCHITECTURAL DETAILS AND CASEWORK CONTRACTOR.

-INDICATES MOUNTING HEIGHT TO CENTER OF OUTLET BOX ABOVE FINISHED FLOOR."+84"

NOTES:

1. OUTLETS LOCATED AT COUNTERS SHALL BE LOCATED 18" AFF IN KNEE SPACE IF

PROVIDED OR 4" ABOVE COUNTER OR BACK SPLASH AS APPLICABLE IF NO KNEE

SPACE IS PROVIDED U.O.N. PROVIDE ALL DEVICES WITH 5 CAT6A ETHERNET

PORT LOCATIONS. QUANITYT OF ACTIVE PORTS AS INDICATED. PROVIDE PORT

COVERS FOR INACTIVE PORTS.

TELECOM. WIRED INFRASTRUCTURE

VOICE(VOIP)/DATA COMBINATION OUTLET. PROVIDE 1-1/4" CONCEALED CONDUIT

TO 6" ABOVE ACCESSIBLE CEILING ACCESSIBLE WITH 90 DEG BEND TOWARDS

NEAREST IT CLOSET OR CABLE TRAY, UNO. PROVIDE (1) DEDICATED ACTIVE VOIP

PORT IN ADDITION TO DATA PORT QUANTITY INDICATED.

DATA OUTLET. PROVIDE 1-1/4" CONCEALED CONDUIT TO 6" ABOVE ACCESSIBLE

CEILING ACCESSIBLE WITH 90 DEG BEND TOWARDS NEAREST IT CLOSET OR

CABLE TRAY, UNO.

VOICE OUTLET. PROVIDE 3/4" CONCEALED CONDUIT TO 6" ABOVE ACCESSIBLE

CEILING ACCESSIBLE WITH 90 DEG BEND TOWARDS NEAREST IT CLOSET OR

CABLE TRAY, UNO.

CEILING MOUNTED COMMUNICATIONS OUTLET, VOICE, DATA OR COMBO UNIT.

PEDESTAL/BENCH MOUNTED COMMUNICATIONS OUTLET. VOICE, DATA OR COMBO

AS INDICATED.

OUTLET MOUNTED IN CAST BOX INSTALLED UNDER RAISED FLOOR.

FLOOR OUTLET. PATHWAY PROVIDE BY ELECTRICAL CONTRACTOR. REFER TO

ELECTRICAL DRAWINGS AND SCHEDULE FOR REQUIREMENTS.

TELEVISION ANTENNA TAP-OFF OUTLET AT +84", PROVIDE 1"C TO ABOVE

ACCESSIBLE CEILING.

TELEPHONE MOUNTING BOARD. 3/4" THICK FIRE-TREATED PLYWOOD (8FT HIGH)

FOR TELEPHONE MOUNTING BOARD WITH (1) DEDICATED FOURPLEX OUTLET AND

#6 COPPER BOND TO BUILDING GROUND ELECTRODE SYSTEM. TELEPHONE

CONDUIT PER UTILITY SPECIFICATIONS. PROVIDE 2"C (OR AS SPECIFIED BY

OWNER) BACK TO BUILDING'S TELECOM POINT OF CONNECTION FOR USE BY

TELECOM INSTALLER. FIELD VERIFY TELECOM POINT OF CONNECTION LOCATION

PRIOR TO STARTING CONSTRUCTION.

DESIGNATES QUANTITY OF ACTIVE PORTS. (TYPICAL)2

NOTE:

SYMBOLS SHOWN ARE FOR REFERENCE ONLY AND DO NOT CONSTITUTE A CHECK

LIST OF DEVICES REQUIRED BY THE CONTRACT

0.0"

18"

6'-0"

3'-10"

10'-0"

6'-8"

BATTERY LIGHTING UNITS AND REMOTE WALL MOUNTED LIGHT HEADS (OR

1'-0" BELOW FINISHED CEILING AT TOP OF UNIT)

WARNING AND SIGNALING FIXTURES/SIGNS (CENTERED 6IN. ABOVE

DOOR/WINDOW)

CLOCK RECEPTACLES

BOTTOM LENS FOR WALL MOUNTED FIRE ALARM STROBES SPEAKERS,

HORNS AND COMBINATION HORN/STROBES

TOP OF FLUSH AND SURFACE MOUNTED PANELBOARDS AND TELEPHONE

CABINETS. TOP OF HIGHEST DISCONNECT SWITCHES, MAGNETIC

STARTERS, CONTACTORS, ATS.

GENERATOR REMOTE ANNUNCIATOR

WALL MOUNTED LIGHTING SWITCHES, MANUAL MOTOR STARTERS, FIRE

ALARM PULL STATIONS, WALL MOUNTED TELEPHONES.

GARAGE RECEPTACLES

ELECTRICAL RECEPTACLES, VOICE/DATA OUTLETS, DATA OUTLETS, UNO

FINISHED FLOOR

7'-0"

5'-6"

24"

MOUNTING HEIGHT NOTES: MOUNTING HEIGHTS TO FINISHED FLOOR TO CENTER OF

OUTLETS, UNLESS OTHERWISE NOTED.

MOUNTING HEIGHT NOTES

GENERAL NOTES

1. ALL DEVICE MOUNTING HEIGHTS INDICATED ON THIS LEGEND ARE FROM FINISHED FLOOR

TO CENTER OF OUTLET BOX.

2. PROVIDE #10 WIRE (FOR PHASE, NEUTRAL AND GROUND) FOR ALL 20A 120V CIRCUITS

EXCEEDING 75 FEET AND FOR 20A 277V CIRCUITS THAT EXCEED 150 FEET. PROVIDE #8

WIRE (FOR PHASE, NEUTRAL AND GROUND) FOR ALL 20A 120V CIRCUITS EXCEEDING 150

FEET AND FOR ALL 20A 277V CIRCUITS EXCEEDING 250 FEET.

3. CONTRACTOR MAY COMBINE UP TO (3) 20A (SINGLE POLE) RECEPTACLE CIRCUITS WITHIN

A SINGLE CONDUIT. CONDUIT SHALL NOT BE LESS THAN 3/4". WIRING CONFIGURATIONS

SHALL BE AS FOLLOWS: (FOLLOW WIRE UPSIZING TO ACCOMMODATE VOLTAGE DROP DUE

TO LENGTH AS INDICATED IN NOTE #2.)

• FOR 3 CIRCUITS, 20A, HOMERUNS TO PANELS SHALL BE 3#12 PHASE CONDUCTORS, 3#

12 NEUTRAL CONDUCTORS AND 1#12 GROUND. (WHEN UPSIZING FOR VOLTAGE DROP

AS INDICATED IN NOTE #2 REQUIRES 3#8 PHASE CONDUCTORS, 3#8 NEUTRAL

CONDUCTORS AND 1#8 GROUND UTILIZE 1"C IN LIEU OF 3/4"C).

• FOR 2 CIRCUITS, 20A, HOMERUNS TO PANELS SHALL BE 2#12 PHASE CONDUCTORS, 2#

12 NEUTRAL CONDUCTORS, AND 1 #12 GROUND.

• 1 CIRCUIT, 20A, HOMERUNS TO PANEL SHALL BE 1#12 PHASE CONDUCTOR, 1#12

NEUTRAL CONDUCTOR AND 1#12 GROUND.

4. VERIFY LOCATION AND CONNECTION REQUIREMENTS FOR EQUIPMENT PROVIDED BY

OTHER TRADES PRIOR TO ROUGH-IN.

5. COORDINATE CEILING MOUNTED LIGHTS AND DEVICES WITH CEILING CONTRACTOR AND

INSTALL AS SHOWN ON THE REFLECTED CEILING/LIGHTING PLANS.

6. ALL FLOOR MOUNTED ELECTRICAL EQUIPMENT (SWITCHGEAR, SWITCHBOARDS, FREE

STANDING PANELBOARDS, DISTRIBUTION BOARDS, TRANSFORMERS, ETC.) SHALL BE

INSTALLED ON 4" HIGH CONCRETE PAD. CONCRETE PAD SHALL EXTEND PAST EDGE OF

EQUIPMENT 3" ON EACH SIDE U.N.O.

7. COORDINATE ALL DIMENSIONS, ELECTRICAL POINT OF CONNECTIONS, AND WIRING

REQUIREMENTS ON ALL PRE-PURCHASED EQUIPMENT WITH FINAL APPROVED SHOP

DRAWINGS.

8. FIRE SEAL ALL CONDUIT PENETRATIONS THROUGH FIRE RATED WALLS AND SLABS. FIRE

RATING SEAL SHALL BE EQUAL TO OR GREATER THAN THE FIRE RATING OF THE WALL OR

SLAB THROUGH WHICH THE CONDUIT PASSES.

9. COORDINATE THE LOCATION AND MOUNTING HEIGHTS OF OUTLETS AND MULTI-OUTLET

ASSEMBLIES WITH ARCHITECTURAL FLOOR PLANS AND ELEVATION DRAWINGS..

10. CONTRACTOR SHALL VERIFY ALL DOOR SWINGS BEFORE INSTALLING SWITCH/LIGHTING

CONTROL BOXES. DO NOT PLACE SWITCH OR LIGHTING CONTROL DEVICE BEHIND DOOR

SWING.

11. FOR MOUNTING HEIGHT OF UNDER-SHELF/CABINET LIGHTING FIXTURES REFER TO

ARCHITECTURAL DRAWINGS.

12. COORDINATE EXACT LOCATION OF SUSPENDED LIGHTING FIXTURES IN MECHANICAL AND

STORAGE AREAS WITH OTHER TRADES. DO NOT PLACE LIGHTING FIXTURE DIRECTION

ABOVE MECHANICAL EQUIPMENT OR DUCTS.

13. RACEWAYS, SLEEVES, AND BOXES FOR IT CABLING SHALL COMPLY WITH COMMERCIAL

BUILDING STANDARD FOR TELECOMMUNICATION PATHWAYS AND SPACES,

ANSI/TIA/EIA-569-A.

14. BOND FLAMMABLE LIQUID STORAGE CABINETS WITH #10 AWG WIRE TO THE NEAREST

STEEL COLUMN. INSTALL WIRE IN CONDUIT.

SITE EXTERIOR

SITE LIGHTING FIXTURE DESCRIPTIONS

POLE LUMINAIRE - ARM QUANTITY AS INDICATED ON PLANS

POLE MOUNTED POST TOP LUMINAIRE

GROUND MOUNTED LOW LEVEL LUMINAIRE - BOLLARD

IN-GRADE UP-LIGHT LUMINAIRE

DENOTES DIRECTION OF LIGHT DISTRIBUTION. PROVIDE DIRECTIONAL LIGHT

THROW (WALL WASH EFFECT) WHERE SHOWN.

GROUND MOUNTED FLOOD LUMINAIRE, TWIN OR SINGLE AS INDICATED ON PLANS

POLE MOUNTED FLOOD LUMINAIRE, TWIN OR SINGLE AS INDICATED ON PLANS

HHMH

UNDERGROUND CONDUIT AND WIRING

EXOTHERMIC COMPRESSION CONNECTION

GROUND ROD AND SYSTEM TEST WELL

GROUND ROD CONNECTION

ELECTRICAL MANHOLE OR HANDHOLE

MH=MANHOLE, HH=HANDHOLE

SITE POWER AND TELECOMMUNICATIONS

POWER ONE-LINE DIAGRAM

CIRCUIT BREAKER. AMP TRIP, FRAME AND OPTIONS AS INDICATED,

3P U.O.N.

FUSE, AMP RATING (AT) AS INDICATED. 3-POLES,

(1) FUSE PER POLE U.O.N.

DISCONNECT SWITCH. SIZE (AF) AS INDICATED. 3-POLE U.O.N.

FUSIBLE DISCONNECT SWITCH. AMP FUSE (AT) AND SWITCH RATING

(AF) AS INDICATED. 3-POLES WITH (1) FUSE PER POLE U.O.N.

AUTOMATIC TRANSFER SWITCH AMPACITY, VOLTAGE, NUMBER OF

POLES, WITHSTAND RATING AS INDICATED

LOW VOLTAGE DRAW-OUT CIRCUIT BREAKER. AMP TRIP (AT), AMP

FRAME (AF)AND OPTIONS AS INDICATED. 3-POLES U.O.N.

MEDIUM VOLTAGE DRAW-OUT CIRCUIT BREAKER. AMP TRIP, AMP

FRAME AND POLES AS INDICATED.

TRANSFORMER

PRIMARY (DELTA U.O.N) AND SECONDARY (WYE U.O.N)

VOLTAGES AS SHOWN

KVA RATING AS SHOWN

SEE TRANSFORMER SCHEDULE FOR ADDITIONAL REQUIREMENTS

480V/100A/ 4P/

25KA WCR

800AT/800AF

800AT/800AF/3P

XXX

3 LA'S

SELECTOR SWITCHES

AS - AMMETER PHASE

VS - VOLTMETER PHASE

WS - WATTMETER

DIGITAL METERING

CURRENT TRANSFORMER

POTENTIAL TRANSFORMER

KEY INTERLOCK - WITHDRAWN KEY

KEY INTERLOCK - CAPTIVE KEY

MOTOR, HP AS SHOWN

CONNECTION TO GROUND BARE #

4/0CU U.N.O

LIGHTNING

ARRESTERS

PANELBOARD/

DISTRIBUTION

BOARDS

METER WITH CURRENT TRANSFORMER

M - UTILITY OR OWNER METER

AM- A.C. AMMETER

VM- A.C. VOLTMETER

FM- FREQUENCY METER

WM- WATTMETER

SERVICE ENTRANCE SECTION OR OTHER LARGE

SWITCHBOARD OR DISTRIBUTION BOARD.

RATINGS, BREAKER QTY AND SIZE, NAMES ETC. AS

INDICATED ON PLANS

EXISTING SERVICE ENTRANCE SECTION OR OTHER

LARGE SWITCHBOARD/DISTRIBUTION BOARD. RATINGS,

BREAKER QTY AND SIZE, NAMES ETC. AS INDICATED ON

PLANS. ANY NEW WORK WITHIN EXISTING EQUIPMENT

WILL BE BOLD AND NOTATED AS NEW.

200AT/3P

200AF/3P

100AT/200AF

200AT

200AF

N.C. 100%

M

AS

DM

KEY DESIGNATION - PROVIDE ONE LESS KEY

THAN LOCKS (KIRK KEY OR EQUIVLIENT)

EQUIPMENT FEEDER TAG - REFER TO FEEDER

SCHEDULE FOR REQUIREMENTS

TRANSFORMER FEEDER TAG - REFER TO FEEDER SCHEDULE PHASE,

NUETRAL AND CONDUIT REQUIRMENTS. GROUND SHALL BE AS INDICATED

IN TAG.

175-4-CU

#4(CU)G

175-4-CU

A, AMP

AF

AFC

AFF

AIC

AM

AS

ASYM

AT

ATS

AWG

BOF

B.S.C

C

CAP

CATV

CB

CCTV

cd

CL

CU

DISC

DPST

EC

EWC

ELEC

EM

EPO

EMT

FLA

GRC

GEC

GEN

GFCI

GFI

GFP

GND, G

HOA

HP

IMC

IG

JB

KAIC

KVA

KW

KWH

LED

LTG

LV

MCA

MCB

- AMPERES

- AMP FUSE OR AMP FRAME

- AVAILABLE FAULT CURRENT

(SYMMETRICAL)

- ABOVE FINISHED FLOOR

- AMPERE INTERRUPTING

CAPACITY

- AMMETER

- AMP SWITCH

- ASYMMETRICAL

- AMP TRIP

- AUTOMATIC TRANSFER SWITCH

- AMERICAN WIRE GAUGE

- BOTTOM OF FIXTURE

- BARE STRANDED COPPER

CONDUCTOR

- CONDUIT

- CAPACITY OR CAPACITOR

- COMMUNITY ANTENNA TV

- CIRCUIT BREAKER

- CLOSED CIRCUIT TELEVISION

- CANDELA

- CURRENT LIMITING

- COPPER

- DISCONNECT

- DOUBLE POLE SINGLE THROW

- ELECTRICAL CONTRACTOR

- ELECTRIC WATER COOLER

- ELECTRIC OR ELECTRICAL

- EMERGENCY

- EMERGENCY POWER OFF

- ELECTRICAL METAL TUBING

- FULL LOAD AMPERES

- GALVANIZED RIGID CONDUIT

- GROUNDING ELECTRODE

CONDUCTOR

- GENERATOR

- GROUND FAULT CIRCUIT

INTERRUPTER

- GROUND FAULT INDICATION

- GROUND FAULT PROTECTION

- GROUND

- HAND-OFF-AUTO

- HORSEPOWER

- INTERMEDIATE METAL

CONDUIT

- ISOLATED GROUND

- JUNCTION BOX

- THOUSAND AMPERE

INTERRUPTING CAPACITY

- KILOVOLT AMPERES

- KILOWATT

- KILOWATT HOUR

- LIGHT EMITTING DIODE

- LIGHTING

- LOW VOLTAGE

- MINIMUM CIRCUIT AMPS

- MAIN CIRCUIT BREAKER

ABBREVIATIONS

- MOTOR CONTROL CENTER

- MANHOLE

- MAIN LUGS ONLY

- NORMALLY CLOSED

- NATIONAL ELECTRICAL CODE

- NOT IN CONTRACT

- NOT IN SCOPE OF THIS

PROJECT

- NON FUSIBLE

- NIGHT LIGHT

- NORMALLY OPEN

- NOT TO SCALE

- OVER CURRENT

PROTECTION

- OVERLOADS

- POLE

- PULLBOX

- PHASE

- PANEL

- POINT OF CONNECTION

- POLYVINYL CHLORIDE

- POWER

- RECEPTACLE

- RIGID GALVANIZED STEEL

- SOLENOID

- SINGLE POLE DOUBLE

THROW

- SPEAKER

- SINGLE POLE SINGLE

THROW

- SWITCH

- SWITCHBOARD

- SYMMETRICAL

- TELEPHONE

- TELECOMMUNICATIONS

GROUNDING BUSBAR

- TELEPHONE MOUNTING

BOARD (PLY-WOOD)

- TELEPHONE TERMINAL

BACKBOARD

- TELEVISION

- TYPICAL

- UNDERGROUND

- UNLESS OTHERWISE NOTED

- VOLT

- VOLT AMPERES

- VOLTAGE DROP

- VOLT METER

- VOLT METER SWITCH

- WATTS OR WIRE

- WITH

- WITHOUT

- WEATHERPROOF

- TRANSFORMER

- EXPLOSION PROOF

MCC

MH

MLO

N.C.

NEC

NIC

NIS

NF

NL

N.O.

NTS

OCP

OL

P

PB

PH, Ø

PNL

POC

PVC

PWR

RCPT.

RGS

SOL

SPDT

SPKR

SPST

SW

SWBD

SYM

TEL

TGB

TMB

TTB

TV

TYP

UG

UNO/UNO

V

VA

VD

VM

VS

W

W/ W/O

WP

XFMR

XP

AIR TERMINAL P = PARAPET MOUNTED, S = SCREEN WALL MOUNTED

THRU ROOF DOWN CONDUCTOR TO GROUNDING SYSTEM

OUTSIDE UNDERGOUND GROUND RING - #4/0 BARE CU CONDUCTOR,

DIRECT BURRIED

INTERIOR GROUNDING CONNECTION - #4/0 INSULATED CU CONDUCTOR

U.O.N

MAIN CONDUCTOR SIZED PER NFPA 780

SECONDARY CONDUCTOR SIZED PER NFPA 780

INTERIOR GROUND ELECTRODE CONDUCTOR (DIAGRAMTIC) #4(CU)MIN OR

PER NEC 250.66 / 250.102

COPPER GROUND ROD 3/4"DIA. X 10'-0" LONG

GROUNDING TEST WELL WITH COPPER GROUND ROD 3/4"DIA. X 10'-0" LONG

EXOTHERMIC BONDING GROUNDING CONNECTION

P

LIGHTNING PROTECTION & GROUNDING

IN ADDITION TO ANY OTHER TESTING REQUIREMENTS, THIRD PARTY TESTING SHALL BE

REQUIRED FOR THE FOLLOWING:

GROUND FAULT PROTECTION

• SWITCHBOARDS, PANELBOARDS, MCC'S AND OTHER EQUIPMENT RATED 1000A OR MORE

OR OVER 600V

• INSULATION RESISTANCE TEST (PHASE TO PHASE, PHASE TO GROUND)

• DIELECTRIC VOLTAGE WITHSTAND TEST (PHASE TO PHASE, PHASE TO GROUND)

TRANSFORMERS RATED 100 KVA OR MORE SINGLE PHASE AND 300 KVA OR MORE THREE

PHASE

• INSULATION RESISTANCE TEST (WINDING-WINDING, WINDING-GROUND)

CONDUCTORS THAT SUPPLY EQUIPMENT RATED AT 1000 AMPERES OR MORE, OR OVER 600

VOLTS

• INSULATION RESISTANCE TEST (PHASE TO PHASE, PHASE TO GROUND)

• DC HIGH POTENTIAL TEST (PHASE TO PHASE, PHASE TO GROUND)

EMERGENCY AND STANDBY POWER SYSTEMS: SWITCHBOARDS PANELBOARDS, DISTRIBUTION

BOARDS, TRANSFER EQUIPMENT, POWER SOURCE, CONDUCTORS, FIRE PUMPS, EXHAUST

AND VENTILATION FANS.

• PHASE ROTATION TEST

• INSULATION RESISTANCE TEST ON FEEDER CONDUCTORS AND EQUIPMENT (PHASE TO

PHASE, PHASE TO GROUND)

• AUTOMATIC TRANSFER TEST

• OPERATION TEST SYSTEM UNDER LOAD CONDITIONS

TESTING AND SPECIAL INSPECTIONS

NFPA 101 - LIFE SAFETY CODE LATEST

INTERNATIONAL FIRE CODE 2018

FIRE AND LIFE SAFETY CODES EDITION

INTERNATIONAL BUILDING CODE (IBC) 2018

AMERICANS WITH DISABILITIES ACT (ADA) LATEST

OWNER SPECIFICATIONS AND STANDARDS VA TIL

LOCAL AND STATE CODES AND AMENDMENTS VA TIL

NATIONAL ELECTRICAL CODE (NFPA 70) 2023

GENERAL EDITION

ALL OF THE FOLLOWING ARE HEREBY MADE PART OF THESE SPECIFICATIONS. THEY SHALL

BE SATISFIED BY THE CONTRACTOR AT NO ADDITIONAL EXPENSE TO THE OWNER

CODES AND STANDARDS

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

65% SUBMITTAL - NOT

FOR CONSTRUCTION

LAKE BALDWIN VA

CLINIC

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

AESUS DESIGN GROUP

1050 E. Southern Ave., Suite D Temple, AZ, 85282 480-454-2861 David Combs

June 7, 2023 TS RS

5201 RAYMOND ST, ORLANDO, FL 32803

C R e vi t\

\L a ke

B a ld w in -E le c-

R ts ch n e p f.

rv t

/1 /2

:4

:5

P M

E.000

SYMBOLS AND ABBREVIATIONS

-ELECTRICAL SHEET LIST-

Sheet Number Sheet Name

ELECTRICAL

E.000 SYMBOLS AND ABBREVIATIONS

EP.101 ELECTRICAL POWER PLAN

EP.601 ELECTRICAL ONE-LINE DIAGRAM - EXISTING CONDITIONS

EP.602 ELECTRICAL ONE-LINE DIAGRAM - DEMO

EP.603 ELECTRICAL ONE-LINE DIAGRAM - NEW

TOTAL:: 5

Revisions: Date:

LAKE BALDWIN SITE

ELECTRICAL UPGRADES

Project Number

675-23-801

FOR CONSTRUCTION

0% SUBMITTAL - NOT 10

Issue Date

OCT 13, 2023

C C

C O

N C

C

LF

M E

TA

L

S

TA

IR

S

M E

TA

L

S

TA

IR

S

CC

W O O D

D E C K

W O O D

D E C K

W O O D

D E C K

WO

OD DE

C K

WO

OD ST

EP

S

W O O D

S

TE

P S

W O O D

D E C K

W O O D

D E C K

W O O D

R A M P

WOOD

DECK

W O O D

D E C K

W O O D

D E C K

W O O D

D E C K

(T Y P

W O O D

R A M P

W O O D

S

TE

P S

(T Y P

G A Z E B O

W O O D

R A M P

W O O D

D E C K

W O O D

D E C K

WOOD

DECK

WOOD

RAMP

8' CW UNDER WOOD

RAMP

C O V E R E D

W O O D

C O V E R E D

W O O D

W O O D

S

TE

P S

WOOD

RAMP

W O O D

D O C K

8' CW UNDER WOOD

RAMP

WOOD

RAMP

WOOD

DECK

W O O D

S

TE

P S

N89°59'50"W 70.57'

PLAT S

°0 '5 "E

.4

P

LA

T

BRICK

BRICK

RETENTION AREA

RETENTION AREA

R E

T E

N T

IO

N

A R

E A

RETENTION AREA

RETENTION AREA

RETENTION AREA

R E

T E

N T

IO

N

A R

E A

R E

T E

N T

IO

N

A R

E A

R E

T E

N T

IO

N

A R

E A

R E

T E

N T

IO

N

A R

E A

RETENTION AREA

R E

T E

N T

IO

N

A R

E A

R E

T E

N T

IO

N

A R

E A

R E T E N

TI

O N

A R E A

R E T E N

TI

O N

A R E A

D

IR

T

R O A D

DI

RT RO

AD

DIRT

ROAD

D

IR

T

D

IR

T

D

IR

T

D

IR

T

D

IR

T

S A

T E

L L

IT

E

A N

T E

N N

A

M E

T A

L L

ID

T

1 STORY

MODULAR BUILDING

ADDRESS #508

37.7'

.8 ' 8.8'

.8

26.2'

.3

72.8'

.3

.3

72.8'

.3

26.2'

.8 '8.8'

.8

37.7'

1 STORY

MODULAR BUILDING

ADDRESS #507

MODULAR BUILDING

ADDRESS #505

60.3'

.4

' MODULAR BUILDING

#506

37.7'

.8 ' 8.8'

.8

26.2'

.3

72.8'

.3

S

TO

R Y

B

LO

C K

F R A M E

A D D R E S S

( C O U R T Y A R D

N O T

LO

C A T E D

52.1'

.7

147.1'

4.5'

14.8'

66.7'

.6

15.7'

.4 '82.3'

.7

52.1'

.6

84.8'

.8

28.1'

31.9'

42.8'

.3

33'

.6

6.9'

.4

15.3'

.8

15.3'

.9

59.6'

.8

97.2'

.2

.6

97.3'

.1

.5

20'x8'

1 STORY

WOOD TRAILER

C C

C C

CC

C P

C P

' C

W

' C

W

4' CW

C O

N C

D W

C P

5' CW

C C

5' CW

C P

C P

C O

N C

C O

N C

' C

W

C P

C P

C O

N C

CC

C C

CC

C C

CW

CW C

C

C O

N C

6' CW

C O

N C

C P

C P

C O

V E

R E

D L

O A

D

IN

G D

O C

K

20.7'

COVD

C C

C C

C O

N C

C O

N C

C P

C P

C P

C P

ALIMINUM STEPS

A L

IM

IN

U M

R A

M P

C P

C P

C O

N C

C O

N C

' C

W

CP

C O

N C

C C

' C

W

C P

C P

C P

C C

C C

C C

C O

V E

R E

D C

W 6'

C W

' C

W

COVERED CW

C O

V E

R E

D C

W

6' CW

CC

S T

E P

S T

E P

S T

E P

C C

C C

CONC

CW CW

C O

N C

C O

N C

A P

R O

N

C O

N C

A P

R O

N

C O

N C

A P

R O

N

5' CW

CW

CW

C W

G A

R V

E L

C P

C W

C W

6' CW

P la n te d M o u n d

C P

C P

C O

N C

9' C W

9' C W

C C

' C

W

CW

C P

4' CW

4' CW

C O

N C

A P

R O

N

C O

N C

A P

R O

N

C O

N C

C O

V D

C C

C O

N C

C P

C O

N C

C U

R B

T

Y P

C O

N C

C U

R B

T

Y P

C O

N C

R

IP

R A

P

6' CW

6' CW

' C

W

5' CW 5' CW

5' CW

5' CW

5' CW

6' C

W

C O

N C

C O

N C

C O

N C

F L

U M

E

C O

N C

F L

U M

E

C O

N C

F L

U M

E

C O

N C

F L

U M

E

C O

N C

'C

W

C P

C O

N C

5' C

W

' C

W

C O

N C

L

ID

CONC

5' CW

5' CW

' C

W C

O N

C S

T E

P S

C O

N C

S T

E P

S

C O

N C

5' CW

' C

W

' C

W

8' CW

8' CW 6' CW

5' CW

CONC

APRON

CONC

APRON

C O

N C

A P

R O

N

7' CW

CW

CW

' C

W

' C

W

C P

C P

6' CW

C P

C P

C P

C P

C P

C W

5' CW

CP

4' CW

C W

R A

M P

C O

V D

CW

C

P 5' CW

C O

N C

5' C

W

' C

W

F O

U N

T A

IN

C O

V D

C W6 ' C

W

8' CW

' C

W

C P

C C

5' C

W

4' CW

4' CW

C O

N C

C W

C O

N C

C O

N C

C P

C W

C W

C W

C P

' C

W

C C

COVERED CW

COVERED CW

C W

5' CW

CW

C W

C P

CP

C O

N C

CONC

C C

G R

A V

E L

C O

N C

S T

E P

S

C P

C P

C O

N

C CONC

CC

RAMP

C P

CW

C W

'x

' C

P

'x

' C

P

'x

' C

P

C P

R A

M P

R A

M P

C C

C O

N C

CW

C O

N C

C C

CC

CC

C C

C C

C C

C C

R A

M P

CC

C O

N C

D

IR

T

CW

C C

C

CCONC

G E

N E

R A

T O

R A

R E

A

R A

M P

R A

M P

C O

V E

R E

D R

A M

P

CW

L O

A D

IN

G

D O

C K

C O

N C

C C

S T

E P

S

COVERED RAMP

C O

N C

C C

COVERED CW

6' CW

R A

M P

C O

N C

C O

N C

C O

N C

R A

M P

C O

N C

M E

T A

L L

ID

C O

N C

C U

R B

T

Y P

C O

N C

C R

A W

L S

P A

C E

A C

C E

S S

' C

W

8' CW METAL STAIRS

C W

STAIRS

S T

A

IR

S

CW

C O

N C

C C

CONC

CW

G A

R V

E L

C O

N C

S T

E P

S

RAMP

R A

M P

CW

4' CW

'x

' C

P

C O

N C

S T

E P

S R

A M

P

'x

' C

P

C W

C W

2.5'

1.4'

32.1'

.1

.6

. 8

49.3'

C W

C W

STEPS

CC

C O

V E

R E

D C

W

CONC

C C

C C

C O

N C

CONC STEPS

C W

G A

R V

E L

C P

C O

N C

S T

E P

S

C W

CPC

C

CW

CONC

CW

C W

6' CW6' CW6' CW

G A S

P U M P

CBW

C O

N C

H E

A D

W A

L L

C O

N C

H E

A D

W A

L L

C O

N C

H E

A D

W A

L L

C O

N C

H E

A D

W A

L L

CONC

HEADWALL

C O

N C

H E

A D

W A

L L

CONC

HEADWALL

C O

N C

H E

A D

W A

L L

C O

N C

H E

A D

W A

L L

C O

N C

H E

A D

W A

L L

C O

N C

H E

A D

W A

L L

.4 'x .4 C O

LU

M N

(T Y P

.4 'x .4 C O

LU

M N

(T Y P

C O

N C

H E

A D

W A

L L

B R

IC

K

W A L L

BRICK

WALL

CBW

BRICK

WALL

B R

IC

K

W A L L

BRICK

WALL

BRICK

WALL

BRICK

WALL

D

IR

T D

IR

T

D

IR

T

1'E

.8 'S

C B W

C B W

C B W

C B W

.6 'S

.0 'S

CBW CBW

A B A N D O N E D

E

T

CLF

C

LF

C

LF

C

LF

C

LF

D

IE

S E L F U E L

S

TO

R A G E

C

LF

C

LF

C

LF

C L F

C

LF

C

LF

C

LF

C

LF

C

LF

C

LF

C

LF

M F

M F

C L F

C L F

C

LF

C L F

C

LF

C

LF

M F

1'W

0.5'W

M F

M F

0.7'W

0.4'W

1.5'W

C

LF

0.7'W

C

LF

.6

1.3'W

C L F

C L F

C

LF

C

LF

S89°59'23"W 333.86'

MEAS

S87°40'34"E 206.41'

MEAS

S °5 '3 " W

. 2

M E A S

S °5 '4 " W

. 0

M E A S

A S

P H

A L T

A S

P H

A L

T

A S

P H

A L

T

A S

P H

A L

TA

S

P H

A L

T

A S

P H

A L

T

A S

P H

A L

T

ASPHALT

A S

P H

A L

T

A S

P H

A L

T

A S

P H

A L

T

A S

P H

A L

TA

S

P H

A L

T

A S

P H

A L

T

ASPHALT

ASPHALT

A S

P H

A L

T

A S

P H

A L

T

ASPHALT

A S

P H

A L

T

A S

P H

A L

T

A S

P H

A L

T

A S

P H

A L

T

A S

P H

A L

T

ASPHALT

ASPHALT

ASPHALT

ASPHALT

ASPHALT

ASPHALT

ASPHALT

ASPHALT

ASPHALT

ASPHALT

ASPHALT

ASPHALT

ASPHALT

A S

P H

A L

T

A S

P H

A L

T

A S

P H

A L

T

A S

P H

A L

T

A S

P H

A L

T

ASPHALT

ASPHALT

ASPHALT

A S

P H

A L

T

A S

P H

A L

T

A S

P H

A L

T

A S

P H

A L

T

A S

P H

A L

T

A S

P H

A L

T

A S

P H

A L

T

A S P H A

LT

F L U M E

A S P H A

LT

F L U M E

A S

P H

A L

T

ASPHALT

ASPHALT

ASPHALT

.3

.7

.3

.1

.8

.3

.3

. 5

.7

R

ID

L E

Y A

V E

N U

E

RAYMOND STREET

RAYMOND STREET

R A

Y M

O N

D S

T R

E E

T

PALMETTO AVENUE

C O

M F

O R

T A

V E

N U

E

NASH STREET

NASH STREET

M E

R C

Y A

V E

N U

E

LAKE BALDWIN LANE

E B

E B

E B

E B

E B

E B

E B

U B

U B

U B

U B

U B

UB

UB

UB

U B

U B

UP

UP

UP

UP

UP

V

G M

G V

UP

UP

UP

UP

UP

UP

UP

UP

U P

V

UP

E B

EB

E B

E B

EB

E B

E B

E B

E B

E B

E B

E B

E B

E B

E B

E B

E B

U

PU

P

UP

F O

C

E B

GV

UP

E B

GV

UP

UP

UP

UP

UP

UP

T T

T

T

EB

T

E B

T V

EB

EB

SD

SD

EL

SD SD

A. PROVIDE AND INSTALL NEW WIRING DEVICES IN ALL LOCATIONS VACATED DURING

DEMOLITION WHETHER OR NOT LOCATIONS ARE EXPLICITLY INIDCATED ON THE

PLAN DRAWINGS. UTILIZE EXISTING BRANCH CIRCUITS COILED DURING THE

DEMOLITHION PHASE AND UTILIZE EXISTING BACK BACKBOXES WHERE FEASIBLE.

WHERE BACKBOXES ARE DAMAGED OR OTHERWISE UNUSABLE PROVIDE NEW

BACKBOXES AT EXISTING WIRING DEVICES LOCATIONS.

B. REFER TO SHEET E-001 SYMBOLS, ABBREVIATIONS, AND ADDITIONAL

REQUIREMENTS INCLUDING, BUT NOT LIMITED TO, CODE REQUIREMENTS,

EQUIPMENT AND MATERIAL SPECIFICATIONS AND INSTALLATION REQUIREMENTS,

DEVICE MOUNTING HEIGHTS, EQUIPMENT IDENTIFICATION, ETC.

C. DRAWINGS AND SPECIFICATIONS ARE COMPLEMENTARY OF EACH OTHER. WHERE

DRAWINGS AND SPECIFICATIONS DIFFER, THE MORE STRINGENT OF THE TWO

REQUIREMENTS SHALL BE FOLLOWED.

D. ALL EQUIPMENT AND FIXTURES ARE NEW UNLESS NOTED OTHERWISE.

E. CONDUIT AND WIRE IS SHOWN DIAGRAMMATICALLY. ACTUAL ROUTING AND

REQUIRED NUMBER OF SUPPORTS SHALL BE DETERMINED BY THE CONTRACTOR.

F. UNLESS CONDUIT ROUTING CLEARLY INDICATES AS SUCH, DO NOT ROUTE

CONDUIT ON OR ABOVE ROOFTOPS WITHOUT CONSULTING ENGINEER TO

DETERMINE ANY POTENTIAL IMPACT TO RACEWAY OR CONDUCTOR SIZE DUE TO

ADDITIONAL AMBIENT DERATING FOR ROOFTOP INSTALLATION.

G. CONCEAL CONDUITS IN ALL FINISHED AREAS INCLUDING CONCEALMENT WITHIN

MASONRY WALLS WHEN PRESENT. (EXCEPTION: ELECTRICAL, MECHANICAL, AND

JANITOR ROOMS).

H. FLOOR AND FIRE WALL PENETRATIONS MUST BE SEALED WITH AN APPROVED

DESIGN TESTED FIRE STOPPING SYSTEM APPROPRIATE TO THE PENETRATED WALL

TYPE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S REQUIREMENTS.

I. PRIOR TO ROUGH-IN AND FINAL CONNECTION, VERIFY ELECTRICAL

CHARACTERISTICS AND EXACT LOCATION OF THE EQUIPMENT.

J. INSTALL ALL CONDUITS PARALLEL PERPENDICULAR AND UNIFORM TO BUILDING

ELEMENTS

K. ALL WALL VOICE/DATA DROPS SHOWN ON TELECOM DRAWINGS SHALL HAVE A

MINIMUM 4” SQUARE JUNCTION BOX AND 1” CONDUIT WITH PULL CORD STUBBED UP

INTO CEILING SPACE OR TO THE CABLE TRAY, IF APPLICABLE.

L. NO MORE THAN 270 DEGREES OF CONDUIT BENDS ARE ALLOWED IN ANY CONDUIT

RUNS NO MORE THAN 180 DEGREE OF CONDUIT BENDS ARE ALLOWED IN ANY

INTERIOR CONDUIT RUNS.

M. IDENTIFY ALL CONDUIT RUNS WITH MARKER TAPE.

N. ALL FIRE ALARM CABLING SHALL BE IN RED EMT INCLUDING FITTINGS EXCEPT

WHERE EXPOSED AND SUBJECT TO VANDALISM WHERE IT SHALL BE RED RGS

INCLUDING FITTINGS. ALL BOXES CONTAINING FIRE ALARM CABLING SHALL BE RED.

O. ALL RECEPTACLE AND SWITCH COVER PLATES SHALL BE STAINLESS STEEL UNLESS

NOTED OTHERWISE. ALL DEVICE COVER PLATES SHALL BE LABELED WITH THE

PANEL NAME AND BRANCH CIRCUIT NUMBER IDENTIFIED

P. VERIFY ALL EQUIPMENT LOCATIONS AND DIMENSIONS IN THE FIELD PRIOR TO

INSTALLING RACEWAYS AND WIRING

Q. ELECTRICAL WORK SHALL BE DONE IN CONFORMANCE WITH THE CONSTRUCTION

DOCUMENTS, ALL APPLICABLE CODES, ISSUED DRAWINGS AND SPECIFICATIONS.

R. ALL 20A 120V RECEPTACLES WITHIN 6FT OF A SINK OR WET DAMP AREA SHALL BE

GFCI PROTECTED PER NEC 210.8(B)(5)(6).

GENERAL NOTES

(E)-GEN1

(E)-GEN2

(E)-GEN3

(E)-SWBD-EM

(E)-MV-MWS-NO.1

(E)-MV-XF-NO.1

(E)-MV-ATS-NO.1

(E)-MV-MWS-NO.1A

(E)-MV-XF-517

(E)-NORTH OUC

(E)-MV-2WS-NO.4

(E)-MV-2WS-NO.4

(E)-MV-ATS-NO.4

(E)-MV-MWS-NO.4

(E)-MV-XF-NO.3

(E)-MV-ATS-NO.2

(E)-MV-MWS.NO.2 (E)-MV-MWS-NO.3

(E)-MV-ATS-NO.3

(E)-MV-XF-NO.2

(E)-MV-XF-ADMIN-T2

(E)-SOUTH OUC

(E)-MV-XF-517

(E)-MV-XF-501

(E)-MV-XF-503

BLD 503

BLD 500

BLD 509

BLD 519A

BLD 504

BLD 502

BLD

BLD 501

BLD

BLD 3130

B

LD

BLD

B

LD

B

LD

B

LD

B

LD

BLD 3133

BLD 3136

BLD 510

BLD 521

B

LD

B

LD

BLD 519

BLD 505 BLD 506 BLD 507 BLD 508

MV-XF-ENG

519-ATS-K

MV-XF-504

EXTEND EXISTING MV YARD

REMOVE SEPARATING WALL BETWEEN MV-

MWS-NO.1 AND MV-XF-NO.1

MV-XF-EM

EXISTING U/G DUCTBANK FROM

NORTH OUC TO MV-MWS-NO.1A

(APPROX. ROUTE)

NEW CONCRETE ENCASED U/G DUCTBANK FROM MV-MWS-NO.1A (DEMOISHED)

LOCATION TO MV-MWS-NO.1

(APPROX. ROUTE)

SEE ALTERNATIVE OPTION ON EP.602 FOR ADDITIONAL INFORMATION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FOR CONSTRUCTION

LAKE BALDWIN VA

CLINIC

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

AESUS DESIGN GROUP

1050 E. Southern Ave., Suite D Temple, AZ, 85282 480-454-2861 David Combs

LAKE BALDWIN SITE

ELECTRICAL UPGRADES

OCT 13, 2023 TS TS

5201 RAYMOND ST, ORLANDO, FL 32803

C R e vi t\

\L a ke

B a ld w in -E le c-

R ts ch n e p f.

rv t

/1 /2

:4

:5

P M

EP.101

ELECTRICAL POWER PLAN

KEYNOTES

NOT USED.

1" = 60'-0"1 SITE PLAN (EXISTING)

Revisions: Date:

675-23-8010% SUBMITTAL - NOT 10

M

M M M M

M

(BLD 502 EXT)

MV-MWS-NO-3

12470V

MV-MWS-NO 1A

12470V

(BLD 502 EXT)

MV-MWS-NO.1

12470V

(BLD 502 EXT)

MV-MWS-NO.2

12470V

(EXT BLD 502)

MV-ATS-NO.1

1200A, 3P, 12470V

OUC NORTH

(BLD 3122 EXT)

MV-MWS-NO-4

12470V

MV-XF-ADMIN-T2

500KVA

12470V

208Y/120V 5.4%Z

(BLD 506 EXT)

MV-XF-ADMIN-T2

208V/120V

MV-XF-504

150KVA

12470V

208Y/120V 3.9%Z

MV-XF-NO.1

1000KVA

12470V

480Y/277V 6%Z

MV-XF-513

300KVA

12470V

208Y/120V 4.6%Z

502-ATA-A

260A, 4P, 480/277V

502-ATS-EQ

1600A, 4P, 480Y/277V

502-ATS-#1

1600A, 4P, 480Y/277V

(BLD 502 RM 101)

502-SWBD-1

480V/277V

(EXT GREEN TEAM)

MV-ATS-NO.2

1200A, 3P, 12470V

MV-XF-NO.2

1500KVA

12470V

480Y/277V 6%Z

(EXT GREEN TEAM)

MV-ATS-NO.3

1200A, 3P, 12470V

MV-XF-501

150KVA

12470V

480Y/277V

6.2%Z

MV-XF-NO.3

1500KVA

12470V

480Y/277V 6.1%Z

501-L1

480V/277V

(EXT BLD 3132)

MV-ATS-NO.4

1200A, 3P, 12470V

OUC SWITCH

12470V

MV-XF-517

150KVA

12470V

208Y/120V

6.75%Z

(EXT BLD 517)

517-FDS

208V/120V

(EXT BLD 3132)

MV-MWS-NO4

12470V

MV-XF-519

500KVA

12470V

480Y/277V

3.4%Z

MV-XF-503

500KVA

12470V

208Y/120V

4.6%Z

MV-XF-ENG

300KVA

12470V

208Y/120V 3.5%Z

(RM 113A)

521-MDP

480V/277V

(RM 141)

519-MSB

480V/277V

521-CHILLER

512-XF

45KVA

480V

208Y/120V

6%Z(EXT 510)

510-MDP

208V/120V

(RM 106)

520-H1C 480V/277V

519-T-K

45KVA

480V

208Y/120V 5.21%Z

(EMERG) 519-ATS-K

150A, 4P, 208/120V

(RM 142 EMERG)

519-K 208V/120V

(RM 106)

519A-H1D 480V/277V

501-XF-R1

30KVA

480V

208Y/120V 3.7%Z

501-R1

208V/120V

(EMERG) 501-ATS-EL1

100A, 4P, 480/277V

502-SWBD-EM

480V

502-SWBD-3-EM-MB

480V

500-SWBD3-EM-ATS-2

150A, 4P, 480/277V

500-SWBD3-EM-ATS-3

150A, 4P, 480/277V

500-SWBD3-EM-ATS-4

150A, 4P, 480/277V

500-SWBD3-EM-ATS-5

150A, 4P, 480/277V

500-ELEV-1 500-ELEV-2 500-ELEV-3 500-ELEV-4

500-SWBD-3

480V

505-XF

150KVA

480V

208Y/120V 5.8%Z

500-XF-N2T3

75KVA

480V

208Y/120V 4.5%Z

500-MCC-NMC

480V/277V

500-UNK-2

480V/277V

500-PHA

480V/277V

500-XF-NMT2

225KVA

480V

208Y/120V 6%Z

500-XF-N2T2

150KVA

480V

208Y/120V 5.53%Z

ATS-6

400A, 4P, 480/277V

ATS-7

260A, 4P, 480/277V

ATS-8

600A, 4P, 480/277V

500-MCC-AMC1

480V/277V

500-MCC-AMC2

480V/277V

500-PNL-CMH

480V/277V

500-SWBD-2

480V

500-XF-N2T1

150KVA

480V

208Y/120V

5.53%Z

(AHU #1)

500-ECB-N2T1

208V/120V

(RM 1450)

(500-PNL-N1H4)

480V/277V

500-XF-NMT1

225KVA

480V

208Y/120V 6%Z

(MEZZ)

500-ECB-NMT1

208V/120V

500-ATS-2

400A, 4P, 480/277V

(EXT ELEC RM)

500-ATS-2-LD

480V/277V

(PLEB LAB)

500-PNL-N1H1

480V/277V

500-ATS-3

600A, 4P, 480/277V

(RM G1087)

500-PNL-C1H1

480V/277V

(EXT B.500)

500-N2P5-FDS

480V/277V

500-ATS-C2P5

100A, 4P, 480/277V

(EXT-B.500 ATS)

500-ATS-C2P5-LD

480V/277V

500-ATS-1

260A, 4P, 480/277V

(ELEC RM)

500-ATS-1-LD

480V/277V

500-ATS-5

400A, 4P, 480/277V

(EXT ELEC RM)

500-ATS-5-LD

480V/277V

500-ATS-4

400A, 4P, 480/277V

(EXT ELEC RM)

500-ATS-4-LD

480V/277V

(RM 1814)

500-PNL-N1H3

480V/277V

(RENOVATION)

500-XRAY-D1029

480V/277V

(RENOVATION)

500-XRAY-D1014

480V/277V

(RENOVATION)

500-XRAY-D1006

480V/277V

(RM. 240)

500-PNL-N2H

480V/277V

(RM 1109)

500-PNL-N1H2

480V/277V

FIRE PUMP (504- RM 139)

504-MDP

208V/120V

513-MDP

208V/120V

(RM 111)

501-EL1

480V/277V

(LOC EXT B500)

500-PLS-1

208V/120V

(LOC EXT B505)

505-PL-MAIN-FDS

208V/120V

(AHU #4)

500-PNL-N2P1

208V/120V

(MEZZ)

500-PNL-NMP2

208V/120V

(RM 1109)

500-PNL-N1P6

208V/120V

502-SWBD-4

480V

519-T-K

45KVA

480V

208Y/120V 5.21%Z

(NOT VA)

STATE BLD

208V/120V

3130-FDS (ABANDONED)

208V/120V

3130-FDS

208V/120V

RISER

TO OVERHEAD

3134-PL1

208V/120V

3132-PL1

208V/120V

3133-PL1

208V/120V

3133-EXT-B-FDS

208V/120V

3129-A

208V/120V

3128-PL1

208V/120V

3125-PL1

208V/120V

3126-PL1

208V/120V

3126-EXT-A

208V/120V

(3132 EXT)

MV-2WS-NO.4

12470V

MV-MH#89

12470V

OUC SOUTH

OWNED BY UTILITY

OWNED BY VA

OWNED BY UTILITY

GENERATOR BACKED POWER

DUAL UTILITY POWER

SOUTH UTILITY POWER

NORTH UTILITY POWER

ONE-LINE LEGEND

EXISTING

NEW

KEYNOTES

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

90% SUBMITTAL - NOT

FOR CONSTRUCTION

LAKE BALDWIN VA

CLINIC

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

AESUS DESIGN GROUP

1050 E. Southern Ave., Suite D Temple, AZ, 85282 480-454-2861 David Combs

LAKE BALDWIN SITE

ELECTRICAL UPGRADES

OCT 13, 2023 TS TS

5201 RAYMOND ST, ORLANDO, FL 32803

C R e vi t\

\L a ke

B a ld w in -E le c-

R ts ch n e p f.

rv t

/1 /2

:4

:5

P M

EP.601

ELECTRICAL ONE-LINE DIAGRAM -

EXISTING CONDITIONS

6" = 1'-0"1 ELECTRICAL ONE-LINE DIAGRAM - EXISTING CONDITIONS

NOT USED

Revisions: Date:

675-23-801

FOR CONSTRUCTION

0% SUBMITTAL - NOT 10

M

(BLD 502 EXT)

MV-MWS-NO-3

12470V

MV-MWS-NO 1A

12470V

(BLD 502 EXT)

MV-MWS-NO.1

12470V

(BLD 502 EXT)

MV-MWS-NO.2

12470V

(EXT BLD 502)

MV-ATS-NO.1

1200A, 3P, 12470V

OUC NORTH

(BLD 3122 EXT)

MV-MWS-NO-4

12470V

MV-XF-ADMIN-T2

500KVA

12470V

208Y/120V

5.4%Z

(BLD 506 EXT)

MV-XF-ADMIN-T2

208V/120V

MV-XF-504

150KVA

12470V

208Y/120V

3.9%Z

MV-XF-NO.1

1000KVA

12470V

480Y/277V 6%Z

MV-XF-513

300KVA

12470V

208Y/120V

4.6%Z

502-ATA-A

260A, 4P, 480/277V

502-ATS-EQ

1600A, 4P, 480Y/277V

502-ATS-#1

1600A, 4P, 480Y/277V

(BLD 502 RM 101)

502-SWBD-1

480V/277V

(EXT GREEN TEAM)

MV-ATS-NO.2

1200A, 3P, 12470V

MV-XF-NO.2

1500KVA

12470V

480Y/277V 6%Z

(EXT GREEN TEAM)

MV-ATS-NO.3

1200A, 3P, 12470V

MV-XF-501

150KVA

12470V

480Y/277V

6.2%Z

MV-XF-NO.3

1500KVA

12470V

480Y/277V 6.1%Z

501-L1

480V/277V

(EXT BLD 3132)

MV-ATS-NO.4

1200A, 3P, 12470V

OUC SWITCH

12470V

MV-XF-517

150KVA

12470V

208Y/120V

6.75%Z

(EXT BLD 517)

517-FDS

208V/120V

(EXT BLD 3132)

MV-MWS-NO4

12470V

MV-XF-519

500KVA

12470V

480Y/277V

3.4%Z

MV-XF-503

500KVA

12470V

208Y/120V

4.6%Z

MV-XF-ENG

300KVA

12470V

208Y/120V

3.5%Z

(RM 113A)

521-MDP

480V/277V

(RM 141)

519-MSB

480V/277V

521-CHILLER

512-XF

45KVA

480V

208Y/120V

6%Z(EXT 510)

510-MDP

208V/120V

(RM 106)

520-H1C 480V/277V

519-T-K

45KVA

480V

208Y/120V 5.21%Z

(EMERG) 519-ATS-K

150A, 4P, 208/120V

(RM 142 EMERG)

519-K

208V/120V

(RM 106)

519A-H1D 480V/277V

501-XF-R1

30KVA

480V

208Y/120V 3.7%Z

501-R1

208V/120V

(EMERG) 501-ATS-EL1

100A, 4P, 480/277V

502-SWBD-EM

480V

502-SWBD-3-EM-MB

480V

500-SWBD3-EM-ATS-2

150A, 4P, 480/277V

500-SWBD3-EM-ATS-3

150A, 4P, 480/277V

500-SWBD3-EM-ATS-4

150A, 4P, 480/277V

500-SWBD3-EM-ATS-5

150A, 4P, 480/277V

500-ELEV-1 500-ELEV-2 500-ELEV-3 500-ELEV-4

500-SWBD-3

480V

505-XF

150KVA

480V

208Y/120V 5.8%Z

500-XF-N2T3

75KVA

480V

208Y/120V

4.5%Z

500-MCC-NMC

480V/277V

500-UNK-2

480V/277V

500-PHA

480V/277V

500-XF-NMT2

225KVA

480V

208Y/120V

6%Z

500-XF-N2T2

150KVA

480V

208Y/120V

5.53%Z

ATS-6

400A, 4P, 480/277V

ATS-7

260A, 4P, 480/277V

ATS-8

600A, 4P, 480/277V

500-MCC-AMC1

480V/277V

500-MCC-AMC2

480V/277V

500-PNL-CMH

480V/277V

500-SWBD-2

480V

500-XF-N2T1

150KVA

480V

208Y/120V

5.53%Z

(AHU #1)

500-ECB-N2T1

208V/120V

(RM 1450)

(500-PNL-N1H4)

480V/277V

500-XF-NMT1

225KVA

480V

208Y/120V

6%Z

(MEZZ)

500-ECB-NMT1

208V/120V

500-ATS-2

400A, 4P, 480/277V

(EXT ELEC RM)

500-ATS-2-LD

480V/277V

(PLEB LAB)

500-PNL-N1H1

480V/277V

500-ATS-3

600A, 4P, 480/277V

(RM G1087)

500-PNL-C1H1

480V/277V

(EXT B.500)

500-N2P5-FDS

480V/277V

500-ATS-C2P5

100A, 4P, 480/277V

(EXT-B.500 ATS)

500-ATS-C2P5-LD

480V/277V

500-ATS-1

260A, 4P, 480/277V

(ELEC RM)

500-ATS-1-LD

480V/277V

500-ATS-5

400A, 4P, 480/277V

(EXT ELEC RM)

500-ATS-5-LD

480V/277V

500-ATS-4

400A, 4P, 480/277V

(EXT ELEC RM)

500-ATS-4-LD

480V/277V

(RM 1814)

500-PNL-N1H3

480V/277V

(RENOVATION)

500-XRAY-D1029

480V/277V

(RENOVATION)

500-XRAY-D1014

480V/277V

(RENOVATION)

500-XRAY-D1006

480V/277V

(RM. 240)

500-PNL-N2H

480V/277V

(RM 1109)

500-PNL-N1H2

480V/277V

FIRE PUMP (504- RM 139)

504-MDP

208V/120V

513-MDP

208V/120V

(RM 111)

501-EL1

480V/277V

(LOC EXT B500)

500-PLS-1

208V/120V

(LOC EXT B505)

505-PL-MAIN-FDS

208V/120V

(AHU #4)

500-PNL-N2P1

208V/120V

(MEZZ)

500-PNL-NMP2

208V/120V

(RM 1109)

500-PNL-N1P6

208V/120V

502-SWBD-4

480V

519-T-K

45KVA

480V

208Y/120V 5.21%Z

(NOT VA)

STATE BLD

208V/120V

3130-FDS (ABANDONED)

208V/120V

3130-FDS

208V/120V

RISER

TO OVERHEAD

3134-PL1

208V/120V

3132-PL1

208V/120V

3133-PL1

208V/120V

3133-EXT-B-FDS

208V/120V

3129-A

208V/120V

3128-PL1

208V/120V

3125-PL1

208V/120V

3126-PL1

208V/120V

3126-EXT-A

208V/120V

(3132 EXT)

MV-2WS-NO.4

12470V

MV-MH#89

12470V

OUC SOUTH

OWNED BY UTILITY

OWNED BY VA

OWNED BY UTILITY

DEMOLISH EXISTING

GENERATOR PARALLELING

SWITCHBOARD

DEMOLISH EXISTING MEDIUM

VOLTAGE MULTI-WAY SWITCH

DEMOLISH FEEDER TO

MV-XF-517

DEMOLISH FEEDER TO MV-XF-

ADMIN-T2

MV-MWS-NO 1A

12470V

OWNED BY VA

ALTERNATE OPTION:

DEMOLISH MV-MWS-NO 1A

OPTION WOULD INCLUDE EXTENDING FEEDER FROM

OUC SWITCH TO MV-MWS-NO.1 DIRECTLY

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

90% SUBMITTAL - NOT

FOR CONSTRUCTION

LAKE BALDWIN VA

CLINIC

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

AESUS DESIGN GROUP

1050 E. Southern Ave., Suite D Temple, AZ, 85282 480-454-2861 David Combs

LAKE BALDWIN SITE

ELECTRICAL UPGRADES

OCT 13, 2023 TS TS

5201 RAYMOND ST, ORLANDO, FL 32803

C R e vi t\

\L a ke

B a ld w in -E le c-

R ts ch n e p f.

rv t

/1 /2

:4

:0

P M

EP.602

ELECTRICAL ONE-LINE DIAGRAM -

DEMO

6" = 1'-0"1 ELECTRICAL ONE-LINE DIAGRAM - MV OPTION 3 (DEMO)

KEYNOTES

NOT USED

Revisions: Date:

675-23-801

M

MV-XF-504

150KVA

12470V

208Y/120V

3.9%Z

MV-XF-NO.1

1000KVA

12470V

480Y/277V 6%Z

MV-XF-513

300KVA

12470V

208Y/120V

4.6%Z

502-ATA-A

260A, 4P, 480/277V

502-ATS-EQ

1600A, 4P, 480Y/277V

502-ATS-#1

1600A, 4P, 480Y/277V

(BLD 502 RM 101)

502-SWBD-1

480V/277V

MV-XF-NO.2

1500KVA

12470V

480Y/277V 6%Z

MV-XF-501

150KVA

12470V

480Y/277V

6.2%Z

MV-XF-NO.3

1500KVA

12470V

480Y/277V 6.1%Z

501-L1

480V/277V

(EXT BLD 3132)

MV-MWS-NO4

12470V

MV-XF-519

500KVA

12470V

480Y/277V

3.4%Z

MV-XF-503

500KVA

12470V

208Y/120V

4.6%Z

MV-XF-ENG

300KVA

12470V

208Y/120V

3.5%Z

(RM 113A)

521-MDP

480V/277V

(RM 141)

519-MSB

480V/277V

521-CHILLER

512-XF

45KVA

480V

208Y/120V

6%Z(EXT 510)

510-MDP

208V/120V

(RM 106)

520-H1C 480V/277V

519-T-K

45KVA

480V

208Y/120V 5.21%Z

(EMERG) 519-ATS-K

150A, 4P, 208/120V

(RM 142 EMERG)

519-K

208V/120V

(RM 106)

519A-H1D 480V/277V

501-XF-R1

30KVA

480V

208Y/120V 3.7%Z

501-R1

208V/120V

(EMERG) 501-ATS-EL1

100A, 4P, 480/277V

502-SWBD-3-EM-MB

480V

500-SWBD3-EM-ATS-2

150A, 4P, 480/277V

500-SWBD3-EM-ATS-3

150A, 4P, 480/277V

500-SWBD3-EM-ATS-4

150A, 4P, 480/277V

500-SWBD3-EM-ATS-5

150A, 4P, 480/277V

500-ELEV-1 500-ELEV-2 500-ELEV-3 500-ELEV-4

500-SWBD-3

480V

505-XF

150KVA

480V

208Y/120V 5.8%Z

500-XF-N2T3

75KVA

480V

208Y/120V

4.5%Z

500-MCC-NMC

480V/277V

500-UNK-2

480V/277V

500-PHA

480V/277V

500-XF-NMT2

225KVA

480V

208Y/120V

6%Z

500-XF-N2T2

150KVA

480V

208Y/120V

5.53%Z

ATS-6

400A, 4P, 480/277V

ATS-7

260A, 4P, 480/277V

ATS-8

600A, 4P, 480/277V

500-MCC-AMC1

480V/277V

500-MCC-AMC2

480V/277V

500-PNL-CMH

480V/277V

500-SWBD-2

480V

500-XF-N2T1

150KVA

480V

208Y/120V

5.53%Z

(AHU #1)

500-ECB-N2T1

208V/120V

(RM 1450)

(500-PNL-N1H4)

480V/277V

500-XF-NMT1

225KVA

480V

208Y/120V

6%Z

(MEZZ)

500-ECB-NMT1

208V/120V

500-ATS-2

400A, 4P, 480/277V

(EXT ELEC RM)

500-ATS-2-LD

480V/277V

(PLEB LAB)

500-PNL-N1H1

480V/277V

500-ATS-3

600A, 4P, 480/277V

(RM G1087)

500-PNL-C1H1

480V/277V

(EXT B.500)

500-N2P5-FDS

480V/277V

500-ATS-C2P5

100A, 4P, 480/277V

(EXT-B.500 ATS)

500-ATS-C2P5-LD

480V/277V

500-ATS-1

260A, 4P, 480/277V

(ELEC RM)

500-ATS-1-LD

480V/277V

500-ATS-5

400A, 4P, 480/277V

(EXT ELEC RM)

500-ATS-5-LD

480V/277V

500-ATS-4

400A, 4P, 480/277V

(EXT ELEC RM)

500-ATS-4-LD

480V/277V

(RM 1814)

500-PNL-N1H3

480V/277V

(RENOVATION)

500-XRAY-D1029

480V/277V

(RENOVATION)

500-XRAY-D1014

480V/277V

(RENOVATION)

500-XRAY-D1006

480V/277V

(RM. 240)

500-PNL-N2H

480V/277V

(RM 1109)

500-PNL-N1H2

480V/277V

FIRE PUMP (504- RM 139)

504-MDP

208V/120V

513-MDP

208V/120V

(RM 111)

501-EL1

480V/277V

(LOC EXT B500)

500-PLS-1

208V/120V

(LOC EXT B505)

505-PL-MAIN-FDS

208V/120V

(AHU #4)

500-PNL-N2P1

208V/120V

(MEZZ)

500-PNL-NMP2

208V/120V

(RM 1109)

500-PNL-N1P6

208V/120V

502-SWBD-3-EM-MB

480V

(NOT VA)

STATE BLD

208V/120V

3130-FDS (ABANDONED)

208V/120V

3130-FDS

208V/120V

RISER

TO OVERHEAD

3134-PL1

208V/120V

3132-PL1

208V/120V

3133-PL1

208V/120V

3133-EXT-B-FDS

208V/120V

3129-A

208V/120V

3128-PL1

208V/120V

3125-PL1

208V/120V

3126-PL1

208V/120V

3126-EXT-A

208V/120V

(BLD 502 EXT)

MV-MWS-NO-3

12470V

MV-MWS-NO 1A

12470V

(BLD 502 EXT)

MV-MWS-NO.1

600 A,

12.47 KV

3PH,

3W

(BLD 502 EXT)

MV-MWS-NO.2

12470V

(EXT BLD 502)

MV-ATS-NO.1

1200A, 3P, 12470V

OUC NORTH

MV-XF-ADMIN-T2

500KVA

12470V

208Y/120V 5.4%Z

(BLD 506 EXT)

MV-XF-ADMIN-T2

208V/120V

(EXT GREEN TEAM)

MV-ATS-NO.2

1200A, 3P, 12470V

(EXT GREEN TEAM)

MV-ATS-NO.3

1200A, 3P, 12470V

(EXT BLD 3132)

MV-ATS-NO.4

1200A, 3P, 12470V

OUC SWITCH

12470V

MV-XF-517

150KVA

12470V

208Y/120V 6.75%Z

(EXT BLD 517)

517-FDS

208V/120V

MV-MH#89

12470V

OUC SOUTH

(NEW) 502-SWBD-EM

3,000A, 480Y/277V

3PH, 4W, AFC=64.65KA, SCCR=65KA

EXISTING GENERATORS (TYPICAL OF 3)

1200 AT

1200 AF

L.S.I.G, N.C., 100%

1200 AT

1200 AF

L.S.I.G, N.C., 100%

1200 AT

1200 AF

L.S.I.G, N.C., 100%

1200 AT

1200 AF

L.S.I.G, N.C., 100%

SPARE

3000 AT

3000 AF

L.S.I.G, N.C., 100%

BREAKER SIZE AND QUANTITY TO MATCH

EXISTING (TYPICAL)

MV-XF-517

2500KVA

480V

12470Y/7200V 6.75%Z

200 AT

FAULT

INTERUPTOR,

N.C.

200 AT

FAULT

INTERUPTOR,

N.C.

200 AT

FAULT

INTERUPTOR,

N.C.

200 AT

FAULT

INTERUPTOR,

N.C.

200 AT

FAULT

INTERUPTOR,

N.C.

RE-FEED FROM NEW

MV SWITCHGEAR

ATS CONTROLLER

200 AT

FAULT

INTERUPTOR,

N.C.

OWNED BY UTILITY

OWNED BY VA

OWNED BY UTILITY

DISCONNECT MV

TRANSFORMER FROM

EXISTING MULTI-WAY SWITCH

DISCONNECT MV

TRANSFORMER FROM

EXISTING MULTI-WAY SWITCH

NEW STEP UP

TRANSFORMER

REPLACE EMERGENCY

PARALLELING SWITCHBOARD

OUC NORTH

OUC SWITCH

12470V

OWNED BY UTILITY

TO MV-MWS-NO.1

TEMP GEN

2000KW

480Y/277V

3PH, 4W

(TEMP) 502-SWBD-EM

3,000A, 480Y/277V

3PH, 4W, AFC=64.65KA, SCCR=65KA

TAP AND EXTEND EXISTING FEEDERS TO TEMP

GENERATOR POWER (TYPICAL)

PROVIDE TEMPORARY EMERGENCY DEISEL

POWERED GENERATORWITH 24HR BELLY

TANK ADJACENT TO BLD 502. PROVIDE A 480,

3000A, 3PH, 4W DISTRIBUTION OUTPUT BOARD

GENERATOR TO FEED EMERGENNCY SYSTEM

DURING CONSTRUCTION

BREAKERS SHALL BE SIZED TO MATCH EXISTING

BRANCH CIRCUIT FEEDER BREAKERS (TYPICAL)

TO BLD 503

GENERATOR BACKED POWER

DUAL UTILITY POWER

SOUTH UTILITY POWER

NORTH UTILITY POWER

ONE-LINE LEGEND

EXISTING

NEW

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

90% SUBMITTAL - NOT

FOR CONSTRUCTION

LAKE BALDWIN VA

CLINIC

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

AESUS DESIGN GROUP

1050 E. Southern Ave., Suite D Temple, AZ, 85282 480-454-2861 David Combs

LAKE BALDWIN SITE

ELECTRICAL UPGRADES

OCT 13, 2023 TS TS

5201 RAYMOND ST, ORLANDO, FL 32803

C R e vi t\

\L a ke

B a ld w in -E le c-

R ts ch n e p f.

rv t

/1 /2

:4

:0

P M

EP.603

ELECTRICAL ONE-LINE DIAGRAM -

NEW

6" = 1'-0"1 ELECTRICAL ONE-LINE DIAGRAM - MV OPTION 3 (NEW)

KEYNOTES

NOT USEDALTERNATE OPTION:

• ONE (1) EXISTING SWITCH TO FEED ONE (1) NEW FEEDER

FROM OUC SWITCH TO MV-MWS-NO.1 DIRECTLY

• ONE (1) EXISTING SWITCH TO BE MARKED AS SPARE.

Revisions: Date:

675-23-801

Sheets
E.000 - SYMBOLS AND ABBREVIATIONS
EP.101 - ELECTRICAL POWER PLAN
EP.601 - ELECTRICAL ONE-LINE DIAGRAM - EXISTING CONDITIONS
EP.602 - ELECTRICAL ONE-LINE DIAGRAM - DEMO
EP.603 - ELECTRICAL ONE-LINE DIAGRAM - NEW

File details come from the government source that posted it. Updated .