ATTACHMENT 6 - 100 Analysis Drawings.pdf
PDF 680 KB Posted
- Solicitation number
- 36C24826Q0104
About this file
These files represent electrical engineering documents for the Lake Baldwin VA Clinic Electrical Upgrades project, specifically a set of electrical one-line diagrams showing existing, demolition, and new electrical system configurations. The documents detail a complex electrical infrastructure upgrade involving medium voltage switchgear, transformers, and emergency power systems at the VA facility. Key elements include demolishing existing generator paralleling switchboards, disconnecting medium voltage transformers from multi-way switches, installing a new step-up transformer, and providing a temporary 2000kW diesel generator to maintain emergency power during construction. The proposed changes involve reconfiguring power distribution from multiple utility sources (north and south OUC) to ensure continuous electrical service while upgrading the site's electrical infrastructure.
The electrical system modifications span multiple buildings and involve sophisticated power management, including 12,470V medium voltage switches, 480V/277V and 208V/120V transformers, and emergency transfer switches. The project includes provisions for maintaining critical power systems during renovation, with specific attention to generator connections, transformer reconfigurations, and ensuring redundant power paths. Notably, the design includes a temporary generator solution to provide 24-hour emergency power during the construction phase, demonstrating careful planning to minimize disruption to the VA clinic's operations.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
s
CR
(18"/18")
M
OW
OC
L 1D6E
K1
K1
TYPICAL OUTLET SYMBOL NOTES
-STAR SYMBOL INDICATES DEVICE IS MOUNTED 4" ABOVE COUNTER,
CASEWORK, BACKSPLASH OR 46" IF NOTHING BELOW.
-INDICATES MOUNTING HEIGHT ABOVE FINISHED FLOOR.
-ISOLATED GROUND
-WEATHER PROOF
-EXPLOSION PROOF
"+84"
"IG"
"WP"
"XP"
20A, 125V, 2 POLE, 3 WIRE GROUNDING SIMPLEX RECEPTACLE
20A, 125V, 2 POLE, 3 WIRE GROUNDING DUPLEX RECEPTACLE
20A, 125V, 2 POLE, 3 WIRE GROUNDING DOUBLE DUPLEX RECEPTACLE
20A, 125V, 2 POLE 3 WIRE GROUNDING DUPLEX RECEPTACLE WITH (2) INTEGRAL
USB CHARGING PORTS
HALF SWITCHED RECEPTACLE - LOWER OUTLET SWITCHED VIA CONTROL ZONE
INDICATED OR NEAREST OCCUPANCY SENSOR. UPPER OUTLET IS UNSWITCHED -
ALWAYS HOT
20A, 125V, 2 POLE 3 WIRE GROUNDING DUPLEX RECEPTACLE CONNECTED TO
CRITICAL BRANCH
20A, 125V, 2 POLE, 3 WIRE GROUNDING GFCI DUPLEX RECEPTACLE
20A, 125V, 2 POLE, 3 WIRE GROUNDING GFCI RECEPTACLE WITH WHILE IN USE
WEATHERPROOF ENCLOSURE.
20A, 125V, 2 POLE 3 WIRE GROUNDING GFCI DUPLEX RECEPTACLE CONNECTED TO
CRITICAL BRANCH
SPECIAL OUTLET. REFER TO SCHEDULE FOR REQUIREMENTS.
CEILING MOUNTED RECEPTACLE, TYPE AS INDICATED ABOVE.
PEDESTAL MOUNTED DUPLEX OR DOUBLE DUPLEX CONVENIENCE RECEPTACLE.
FLOOR BOX - WITH DUPLEX OR DOUBLE DUPLEX RECEPTACLE
FLOOR BOX WITH POWER AND DATA FURNITURE FEED CONNECTIONS. FURNITURE
FEED CIRCUIT QUANTITY AS INDICATED ON PLANS.
ELECTRICAL POWER SWITCH
M - MOTOR RATED WITH INTEGRAL THERMAL OVERLOADS U.O.N.
SURFACE MOUNTED ENCLOSED DIVIDED RACEWAY FOR POWER AND DATA.
DUPLEX SPACING (20A, 125V, 2 POLE, 3 WIRE GROUNDING DUPLEX RECEPTACLE
U.O.N)
DATA OUTLET SPACING (PROVISINS FOR NOT LESS THAN 4 PORTS U.O.N)
POWER / TELECOM. POLE. PROVIDE JUNCTION BOX ABOVE CEILING FOR POWER
CONNECTION (CIRCUIT QUANTITY AS NOTED ON PLANS) FOR FOR TELECOM/DATA
CONNECTIONS (1 PER ASSOCATED WORKSTATION) CONNECT TO WIRING IN
POWER POLE.
EXTENSION CORD REEL.
UNISTRUT RACK
TYPICAL OUTLET SYMBOL CIRCUITING NOTES
NOTES:
1. OUTLETS LOCATED AT COUNTERS SHALL BE LOCATED 18" AFF IN KNEE SPACE IF
PROVIDED OR 4" ABOVE COUNTER OR BACK SPLASH AS APPLICABLE IF NO KNEE
SPACE IS PROVIDED UNLESS NOTED OTHERWISE.
POWER OUTLETS
IG
+30"
CIRCUIT NUMBER
ELEVATION AFF
TYPE2
D
D
M
XXX-XXX
FOOT ON DEVICE INDICATES WALL MOUNTED
MARK NUMBER FOR MECHANICAL EQUIPMENT
KEY NOTE REFERENCE SYMBOL.
XXX-XXX
GENERAL
CIRCUIT NUMBER(S)
PANEL NAME
1LN1-1,3,5
BRANCH CIRCUIT HOMERUN. PROVIDE #12 PHASE, #12
NEUTRAL AND #12 GROUND CONDUCTORS FOR EACH
INDICATED CIRCUIT UNLESS NOTED OTHERWISE. SEE
GENERAL NOTE #2 AND #3.
NO MULTI-WIRE BRANCH CIRCUITS PERMITTED. NO SHARED
NEUTRAL.
CONDUIT RUN CONCEALED IN CEILING OR WALL
CONDUIT RUN BELOW GRADE, UNDER OR CONCEALED IN
FLOOR SLAB, UNDER RAISED FLOOR
CONDUIT RISER UP
CONDUIT RISER DOWN
INDICATES CIRCUIT CONTINUATION
STUB INTO ACCESSIBLE CORRIDOR CEILING SPACE UNLESS
OTHERWISE NOTED
CAP END OF CONDUIT
CONDUIT SLEEVE
POWER CONDUIT FILL EXAMPLE
(2) 4"C, 4 #500, 1#1/0G
TOTAL QUANTITY OF IDENTICAL CONDUIT/WIRE RUNS AS SPECIFIED (AS APPLICABLE)
CONDUIT SIZE (SEE SPECIFICATIONS FOR ALLOWED TYPES)
QUANTITY OF PHASE AND NEUTRAL CONDUCTORS.
NEUTRAL CONDUCTOR MAY BE SPECIFIED SEPARATELY WITH 'N' SUFFIX
CONDUCTOR SIZE (AWG/KCMIL)
QUANTITY OF GROUND CONDUCTORS (ASSUME QTY 1 IF NOT INDICATED)
GROUND CONDUCTOR SIZE (AWG/KCMIL)
CIRCUIT DESIGNATIONS
(R)(R)
NOTES:
THE FOLLOWING SYMBOLS ARE EXAMPLES INTENDED TO SHOW METHODOLOGY FOR
DEMOLITION. THIS APPROACH IS APPLICABLE TO ALL SYMBOLS INDICATED ON THIS SHEET.
NEW - SHOWN HERE FOR REFERENCE AS A COMPARISON AGAINST
EXISTING AND DEMO ITEMS
EXISTING ELECTRICAL ITEM TO BE REMOVED (BOLD AND DASHED)
EXISTING ELECTRICAL ITEM TO BE RELOCATED. HALFTONE
(R) INDICATES NEW LOCATION
EXISTING ELECTRICAL ITEM TO REMAIN. HALFTONE.
DEMOLITION AND REMODEL
LIGHTING FIXTURE DESCRIPTIONS
RECESSED OR SURFACE MOUNTED LUMINAIRE
RECESSED OR SURFACE MOUNTED ROUND DOWNLIGHT LUMINAIRE
STRIP LIGHT, SURFACE MOUNTED (LENGTH AS SHOWN ON PLANS)
LINEAR LUMINAIRE, SURFACE OR RECESSED (SOLID) OR PENDANT (DASHED)
MOUNTED (LENGTH/TYPE AS SHOWN ON PLANS)
LINEAR LUMINAIRE, WALL MOUNTED (LENGTH AS SHOWN ON PLANS)
WALL SCONCE LUMINAIRE
SUSPENDED TRACK LIGHT, TRACK HEAD QUANTITY AS SHOWN ON PLANS
COVE LIGHT. PLACE IN ARCHITECTURAL COVE, COORDINATE EXACT
LOCATIONS WITH ARCHITECTURAL DRAWINGS.
DENOTES DIRECTION OF LIGHT DISTRIBUTION. PROVIDE DIRECTIONAL LIGHT
THROW (WALL WASH EFFECT) WHERE SHOWN.
EXIT SIGN CEILING OR WALL MOUNTED AS INDICATED
INDICATES DIRECTIONAL CHEVRON FOR EXIT SIGNS.
DENOTES LOCATION(S) OF ILLUMINATED EXIT FACE
EMERGENCY TWIN HEAD FLOOD LIGHTING 'BUG EYE' UNIT WITH INTEGRAL
BATTERY PACK
a a
OD2 WALL MOUNTED CONTROL DEVICE
ALPHANUMERIC CODE INDICATING LIGHTING CONTROL ZONE DESIGNATION. WHERE
MULTIPLE CONTROL ZONES ARE INDICATED LIGHTING CONTROL DEVICE SHALL BE
CAPABLE OF CONTROLLING EACH ZONE INDEPENDENTLY, MULTIPLE ZONES SHALL BE
SEPARATED BY A COMMA (I.E. a,a1,b,d...)
SWITCH TYPE DESIGNATION.
LIGHTING CONTROL SENSORS/DEVICES
SENSOR TYPE DESIGNATION
LIGHTING CONTROLS DEVICES
INDICATES NUMBER OF LIGHTING CONTROL ZONES(POLES) - (AS APPLICABLE)
PROVIDE INDEPENDENT CONTROLS FOR EACH ZONE
NO SUBSCRIPT - SINGLE POLE TOGGLE SWITCH WITH ON/OFF CONTROL.
D - DIMMING CONTROL.
OW - WALL MOUNTED PIR OCCUPANCY SENSOR, WITH MANUAL ON/OFF CONTROL
OD - WALL MOUNTED PIR OCCUPANCY SENSOR, WITH MANUAL DIMMING CONTROL
OWD - WALL MOUNTED DT OCCUPANCY SENSOR, WITH MANUAL ON/OFF CONTROL
ODD - WALL MOUNTED DT OCCUPANCY SENSOR, WITH MANUAL DIMMING
CONTROLS
LCD - INTERACTIVE LCD DISPLAY SCREEN FOR LIGHTING CONTROLS
WP - WEATHER PROOF ENCLOSURE
XP - EXPLOSION PROOF (SEE PLANS FOR CLASSIFICATION REQUIREMENTS)
K - KEYED SWITCH
WHERE DIMMING IS SPECIFIED PROVIDE 0-10V DIMMING CONTROL. SUPPLIER TO
CONFIRM DIMMING COMPATIBILITY BETWEEN FIXTURES AND CONTROLS
OC
OCX
OCD
OCDX
OCH
DC
NORMAL RANGE OCCUPANCY SENSOR, PIR, 12FT RADIUS COVERAGE AT 9FT
AFF
EXTENDED RANGE OCCUPANCY SENSOR, PIR, 28FT RADIUS COVERAGE AT 9FT
AFF
NORMAL RANGE OCCUPANCY SENSOR, DUAL TECHNOLOGY, 12FT RADIUS
COVERAGE AT 9FT AFF
EXTENDED RANGE OCCUPANCY SENSOR, DUAL TECHNOLOGY, 28FT RADIUS
COVERAGE AT 9FT AFF
HIGH MOUNT OCCUPANCY SENSOR, PIR, 20FT RADIUS COVERAGE AT 15FT AFF,
30FT RADIUS AT 45FT AFF.
DAYLIGHT HARVESTING PHOTOCELL. PROVIDE DIMMING WHEN USED WITH
DIMMING CONTROLS. WHERE MOUNTED OUTSIDE, INSTALL ON ROOF AND
POINT NORTH.
CEILING MOUNTED SENSOR
WALL MOUNTED SENSOR
LIGHTING CONTROL SEQUENCE OF OPERATIONS
E - EMERGENCY RELAY
TYPE:
1 - MANUAL SWITCHING ONLY
2 - OCCUPANCY SENSOR LOCATED IN WALL SWITCH
3 - OCCUPANCY SENSOR LOCATED IN CEILING
4 - OCCUPANCY SENSORS AND AUTOMATIC DAYLIGHTING
5 - OCCUPANCY SENSOR LOCATED IN CEILING AND PLUG CONTROL
6 - OCCUPANCY SENSOR LOCATED IN CEILING, AUTOMATIC DAYLIGHTING AND
PLUG CONTROL
CONTROL TYPE
D - DIMMING
S - ON/OFF ONLY
NUMBER OF ZONES
T
30A/3P
30A/3P/
20AF
30A/3P
12x3
CP
C
480/277V OR 480V PANEL 208/120V OR 120/240V PANEL
HEAVY DUTY DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
ENCLOSED CIRCUIT BREAKER
MANUAL MOTOR STARTER SWITCH WITH THERMAL OVERLOAD
PROTECTION.
CONTACTOR
VARIABLE FREQUENCY DRIVE
MOTOR - WITH DISCONNECT (WHERE SHOWN IN PLANS)
MOTOR DESIGNATION SHOWN IN BOX
CONTROL PANEL FURNISHED BY OTHERS, INSTALLED BY
DIVISION 26, UNLESS NOTED OTHERWISE
REDUCED VOLTAGE MOTOR STARTER
NUMBER REFERS TO NEMA STARTER SIZE
COMBINATION REDUCED VOLTAGE MOTOR STARTER/DISCONNECT
NUMBER REFERS TO NEMA STARTER SIZE
COMBINATION 2 SPEED MOTOR STARTER/DISCONNECT
MOTOR - WITH DISCONNECT (WHERE SHOWN IN PLANS)
MOTOR DESIGNATION SHOWN IN BOX
CONTROL PANEL FURNISHED BY OTHERS, PROVIDED AND INSTALLED
BY DIVISION 26, UNLESS NOTED OTHERWISE
PUSHBUTTON STATIONS. ONE, TWO, OR THREE AS INDICATED
EMERGENCY POWER OFF' BREAK GLASS STATION.
BUS DUCT, FEEDER OR PLUG-IN TYPE AS INDICATED
CABLE TRAY - WIDTH x HEIGHT AS INDICATED, OR KEY NOTED
UNDER FLOOR DUCT SYSTEM
JUNCTION BOX, ABOVE CEILING (NO FOOT) OR FLUSH WALL MOUNTED
(WITH FOOT)
T = JUNCTION BOX FOR VOICE/DATA
JUNCTION BOX WITH FLEXIBLE CONNECTION TO EQUIPMENT
INDICATED AND REQUIRED
LADDER STYLE CABLE TRAY, 4IN TALL FOR POWER, 2IN TALL FOR
DATA/SIGNAL U.O.N. WIDTH AS SHOWN ON DRAWINGS.
CONDUIT - SEE SPECIFICATIONS.
POWER DISTRIBUTION
30A/3P
30A/3P
30A/3P
TABS INDICATE FLUSH MOUNTED PANEL
INDICATES REQUIRED
CLEARANCE
VFD
JJJ
J
TYPICAL OUTLET SYMBOL NOTES
"*" -MOUNTED +4" ABOVE COUNTER, CASEWORK, BACKSPLASH OR 46" IF NOTHING
BELOW. COORDINATE WITH ARCHITECTURAL DETAILS AND CASEWORK CONTRACTOR.
-INDICATES MOUNTING HEIGHT TO CENTER OF OUTLET BOX ABOVE FINISHED FLOOR."+84"
NOTES:
1. OUTLETS LOCATED AT COUNTERS SHALL BE LOCATED 18" AFF IN KNEE SPACE IF
PROVIDED OR 4" ABOVE COUNTER OR BACK SPLASH AS APPLICABLE IF NO KNEE
SPACE IS PROVIDED U.O.N. PROVIDE ALL DEVICES WITH 5 CAT6A ETHERNET
PORT LOCATIONS. QUANITYT OF ACTIVE PORTS AS INDICATED. PROVIDE PORT
COVERS FOR INACTIVE PORTS.
TELECOM. WIRED INFRASTRUCTURE
VOICE(VOIP)/DATA COMBINATION OUTLET. PROVIDE 1-1/4" CONCEALED CONDUIT
TO 6" ABOVE ACCESSIBLE CEILING ACCESSIBLE WITH 90 DEG BEND TOWARDS
NEAREST IT CLOSET OR CABLE TRAY, UNO. PROVIDE (1) DEDICATED ACTIVE VOIP
PORT IN ADDITION TO DATA PORT QUANTITY INDICATED.
DATA OUTLET. PROVIDE 1-1/4" CONCEALED CONDUIT TO 6" ABOVE ACCESSIBLE
CEILING ACCESSIBLE WITH 90 DEG BEND TOWARDS NEAREST IT CLOSET OR
CABLE TRAY, UNO.
VOICE OUTLET. PROVIDE 3/4" CONCEALED CONDUIT TO 6" ABOVE ACCESSIBLE
CEILING ACCESSIBLE WITH 90 DEG BEND TOWARDS NEAREST IT CLOSET OR
CABLE TRAY, UNO.
CEILING MOUNTED COMMUNICATIONS OUTLET, VOICE, DATA OR COMBO UNIT.
PEDESTAL/BENCH MOUNTED COMMUNICATIONS OUTLET. VOICE, DATA OR COMBO
AS INDICATED.
OUTLET MOUNTED IN CAST BOX INSTALLED UNDER RAISED FLOOR.
FLOOR OUTLET. PATHWAY PROVIDE BY ELECTRICAL CONTRACTOR. REFER TO
ELECTRICAL DRAWINGS AND SCHEDULE FOR REQUIREMENTS.
TELEVISION ANTENNA TAP-OFF OUTLET AT +84", PROVIDE 1"C TO ABOVE
ACCESSIBLE CEILING.
TELEPHONE MOUNTING BOARD. 3/4" THICK FIRE-TREATED PLYWOOD (8FT HIGH)
FOR TELEPHONE MOUNTING BOARD WITH (1) DEDICATED FOURPLEX OUTLET AND
#6 COPPER BOND TO BUILDING GROUND ELECTRODE SYSTEM. TELEPHONE
CONDUIT PER UTILITY SPECIFICATIONS. PROVIDE 2"C (OR AS SPECIFIED BY
OWNER) BACK TO BUILDING'S TELECOM POINT OF CONNECTION FOR USE BY
TELECOM INSTALLER. FIELD VERIFY TELECOM POINT OF CONNECTION LOCATION
PRIOR TO STARTING CONSTRUCTION.
DESIGNATES QUANTITY OF ACTIVE PORTS. (TYPICAL)2
NOTE:
SYMBOLS SHOWN ARE FOR REFERENCE ONLY AND DO NOT CONSTITUTE A CHECK
LIST OF DEVICES REQUIRED BY THE CONTRACT
0.0"
18"
6'-0"
3'-10"
10'-0"
6'-8"
BATTERY LIGHTING UNITS AND REMOTE WALL MOUNTED LIGHT HEADS (OR
1'-0" BELOW FINISHED CEILING AT TOP OF UNIT)
WARNING AND SIGNALING FIXTURES/SIGNS (CENTERED 6IN. ABOVE
DOOR/WINDOW)
CLOCK RECEPTACLES
BOTTOM LENS FOR WALL MOUNTED FIRE ALARM STROBES SPEAKERS,
HORNS AND COMBINATION HORN/STROBES
TOP OF FLUSH AND SURFACE MOUNTED PANELBOARDS AND TELEPHONE
CABINETS. TOP OF HIGHEST DISCONNECT SWITCHES, MAGNETIC
STARTERS, CONTACTORS, ATS.
GENERATOR REMOTE ANNUNCIATOR
WALL MOUNTED LIGHTING SWITCHES, MANUAL MOTOR STARTERS, FIRE
ALARM PULL STATIONS, WALL MOUNTED TELEPHONES.
GARAGE RECEPTACLES
ELECTRICAL RECEPTACLES, VOICE/DATA OUTLETS, DATA OUTLETS, UNO
FINISHED FLOOR
7'-0"
5'-6"
24"
MOUNTING HEIGHT NOTES: MOUNTING HEIGHTS TO FINISHED FLOOR TO CENTER OF
OUTLETS, UNLESS OTHERWISE NOTED.
MOUNTING HEIGHT NOTES
GENERAL NOTES
1. ALL DEVICE MOUNTING HEIGHTS INDICATED ON THIS LEGEND ARE FROM FINISHED FLOOR
TO CENTER OF OUTLET BOX.
2. PROVIDE #10 WIRE (FOR PHASE, NEUTRAL AND GROUND) FOR ALL 20A 120V CIRCUITS
EXCEEDING 75 FEET AND FOR 20A 277V CIRCUITS THAT EXCEED 150 FEET. PROVIDE #8
WIRE (FOR PHASE, NEUTRAL AND GROUND) FOR ALL 20A 120V CIRCUITS EXCEEDING 150
FEET AND FOR ALL 20A 277V CIRCUITS EXCEEDING 250 FEET.
3. CONTRACTOR MAY COMBINE UP TO (3) 20A (SINGLE POLE) RECEPTACLE CIRCUITS WITHIN
A SINGLE CONDUIT. CONDUIT SHALL NOT BE LESS THAN 3/4". WIRING CONFIGURATIONS
SHALL BE AS FOLLOWS: (FOLLOW WIRE UPSIZING TO ACCOMMODATE VOLTAGE DROP DUE
TO LENGTH AS INDICATED IN NOTE #2.)
• FOR 3 CIRCUITS, 20A, HOMERUNS TO PANELS SHALL BE 3#12 PHASE CONDUCTORS, 3#
12 NEUTRAL CONDUCTORS AND 1#12 GROUND. (WHEN UPSIZING FOR VOLTAGE DROP
AS INDICATED IN NOTE #2 REQUIRES 3#8 PHASE CONDUCTORS, 3#8 NEUTRAL
CONDUCTORS AND 1#8 GROUND UTILIZE 1"C IN LIEU OF 3/4"C).
• FOR 2 CIRCUITS, 20A, HOMERUNS TO PANELS SHALL BE 2#12 PHASE CONDUCTORS, 2#
12 NEUTRAL CONDUCTORS, AND 1 #12 GROUND.
• 1 CIRCUIT, 20A, HOMERUNS TO PANEL SHALL BE 1#12 PHASE CONDUCTOR, 1#12
NEUTRAL CONDUCTOR AND 1#12 GROUND.
4. VERIFY LOCATION AND CONNECTION REQUIREMENTS FOR EQUIPMENT PROVIDED BY
OTHER TRADES PRIOR TO ROUGH-IN.
5. COORDINATE CEILING MOUNTED LIGHTS AND DEVICES WITH CEILING CONTRACTOR AND
INSTALL AS SHOWN ON THE REFLECTED CEILING/LIGHTING PLANS.
6. ALL FLOOR MOUNTED ELECTRICAL EQUIPMENT (SWITCHGEAR, SWITCHBOARDS, FREE
STANDING PANELBOARDS, DISTRIBUTION BOARDS, TRANSFORMERS, ETC.) SHALL BE
INSTALLED ON 4" HIGH CONCRETE PAD. CONCRETE PAD SHALL EXTEND PAST EDGE OF
EQUIPMENT 3" ON EACH SIDE U.N.O.
7. COORDINATE ALL DIMENSIONS, ELECTRICAL POINT OF CONNECTIONS, AND WIRING
REQUIREMENTS ON ALL PRE-PURCHASED EQUIPMENT WITH FINAL APPROVED SHOP
DRAWINGS.
8. FIRE SEAL ALL CONDUIT PENETRATIONS THROUGH FIRE RATED WALLS AND SLABS. FIRE
RATING SEAL SHALL BE EQUAL TO OR GREATER THAN THE FIRE RATING OF THE WALL OR
SLAB THROUGH WHICH THE CONDUIT PASSES.
9. COORDINATE THE LOCATION AND MOUNTING HEIGHTS OF OUTLETS AND MULTI-OUTLET
ASSEMBLIES WITH ARCHITECTURAL FLOOR PLANS AND ELEVATION DRAWINGS..
10. CONTRACTOR SHALL VERIFY ALL DOOR SWINGS BEFORE INSTALLING SWITCH/LIGHTING
CONTROL BOXES. DO NOT PLACE SWITCH OR LIGHTING CONTROL DEVICE BEHIND DOOR
SWING.
11. FOR MOUNTING HEIGHT OF UNDER-SHELF/CABINET LIGHTING FIXTURES REFER TO
ARCHITECTURAL DRAWINGS.
12. COORDINATE EXACT LOCATION OF SUSPENDED LIGHTING FIXTURES IN MECHANICAL AND
STORAGE AREAS WITH OTHER TRADES. DO NOT PLACE LIGHTING FIXTURE DIRECTION
ABOVE MECHANICAL EQUIPMENT OR DUCTS.
13. RACEWAYS, SLEEVES, AND BOXES FOR IT CABLING SHALL COMPLY WITH COMMERCIAL
BUILDING STANDARD FOR TELECOMMUNICATION PATHWAYS AND SPACES,
ANSI/TIA/EIA-569-A.
14. BOND FLAMMABLE LIQUID STORAGE CABINETS WITH #10 AWG WIRE TO THE NEAREST
STEEL COLUMN. INSTALL WIRE IN CONDUIT.
SITE EXTERIOR
SITE LIGHTING FIXTURE DESCRIPTIONS
POLE LUMINAIRE - ARM QUANTITY AS INDICATED ON PLANS
POLE MOUNTED POST TOP LUMINAIRE
GROUND MOUNTED LOW LEVEL LUMINAIRE - BOLLARD
IN-GRADE UP-LIGHT LUMINAIRE
DENOTES DIRECTION OF LIGHT DISTRIBUTION. PROVIDE DIRECTIONAL LIGHT
THROW (WALL WASH EFFECT) WHERE SHOWN.
GROUND MOUNTED FLOOD LUMINAIRE, TWIN OR SINGLE AS INDICATED ON PLANS
POLE MOUNTED FLOOD LUMINAIRE, TWIN OR SINGLE AS INDICATED ON PLANS
HHMH
UNDERGROUND CONDUIT AND WIRING
EXOTHERMIC COMPRESSION CONNECTION
GROUND ROD AND SYSTEM TEST WELL
GROUND ROD CONNECTION
ELECTRICAL MANHOLE OR HANDHOLE
MH=MANHOLE, HH=HANDHOLE
SITE POWER AND TELECOMMUNICATIONS
POWER ONE-LINE DIAGRAM
CIRCUIT BREAKER. AMP TRIP, FRAME AND OPTIONS AS INDICATED,
3P U.O.N.
FUSE, AMP RATING (AT) AS INDICATED. 3-POLES,
(1) FUSE PER POLE U.O.N.
DISCONNECT SWITCH. SIZE (AF) AS INDICATED. 3-POLE U.O.N.
FUSIBLE DISCONNECT SWITCH. AMP FUSE (AT) AND SWITCH RATING
(AF) AS INDICATED. 3-POLES WITH (1) FUSE PER POLE U.O.N.
AUTOMATIC TRANSFER SWITCH AMPACITY, VOLTAGE, NUMBER OF
POLES, WITHSTAND RATING AS INDICATED
LOW VOLTAGE DRAW-OUT CIRCUIT BREAKER. AMP TRIP (AT), AMP
FRAME (AF)AND OPTIONS AS INDICATED. 3-POLES U.O.N.
MEDIUM VOLTAGE DRAW-OUT CIRCUIT BREAKER. AMP TRIP, AMP
FRAME AND POLES AS INDICATED.
TRANSFORMER
PRIMARY (DELTA U.O.N) AND SECONDARY (WYE U.O.N)
VOLTAGES AS SHOWN
KVA RATING AS SHOWN
SEE TRANSFORMER SCHEDULE FOR ADDITIONAL REQUIREMENTS
480V/100A/ 4P/
25KA WCR
800AT/800AF
800AT/800AF/3P
XXX
3 LA'S
SELECTOR SWITCHES
AS - AMMETER PHASE
VS - VOLTMETER PHASE
WS - WATTMETER
DIGITAL METERING
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
KEY INTERLOCK - WITHDRAWN KEY
KEY INTERLOCK - CAPTIVE KEY
MOTOR, HP AS SHOWN
CONNECTION TO GROUND BARE #
4/0CU U.N.O
LIGHTNING
ARRESTERS
PANELBOARD/
DISTRIBUTION
BOARDS
METER WITH CURRENT TRANSFORMER
M - UTILITY OR OWNER METER
AM- A.C. AMMETER
VM- A.C. VOLTMETER
FM- FREQUENCY METER
WM- WATTMETER
SERVICE ENTRANCE SECTION OR OTHER LARGE
SWITCHBOARD OR DISTRIBUTION BOARD.
RATINGS, BREAKER QTY AND SIZE, NAMES ETC. AS
INDICATED ON PLANS
EXISTING SERVICE ENTRANCE SECTION OR OTHER
LARGE SWITCHBOARD/DISTRIBUTION BOARD. RATINGS,
BREAKER QTY AND SIZE, NAMES ETC. AS INDICATED ON
PLANS. ANY NEW WORK WITHIN EXISTING EQUIPMENT
WILL BE BOLD AND NOTATED AS NEW.
200AT/3P
200AF/3P
100AT/200AF
200AT
200AF
N.C. 100%
M
AS
DM
KEY DESIGNATION - PROVIDE ONE LESS KEY
THAN LOCKS (KIRK KEY OR EQUIVLIENT)
EQUIPMENT FEEDER TAG - REFER TO FEEDER
SCHEDULE FOR REQUIREMENTS
TRANSFORMER FEEDER TAG - REFER TO FEEDER SCHEDULE PHASE,
NUETRAL AND CONDUIT REQUIRMENTS. GROUND SHALL BE AS INDICATED
IN TAG.
175-4-CU
#4(CU)G
175-4-CU
A, AMP
AF
AFC
AFF
AIC
AM
AS
ASYM
AT
ATS
AWG
BOF
B.S.C
C
CAP
CATV
CB
CCTV
cd
CL
CU
DISC
DPST
EC
EWC
ELEC
EM
EPO
EMT
FLA
GRC
GEC
GEN
GFCI
GFI
GFP
GND, G
HOA
HP
IMC
IG
JB
KAIC
KVA
KW
KWH
LED
LTG
LV
MCA
MCB
- AMPERES
- AMP FUSE OR AMP FRAME
- AVAILABLE FAULT CURRENT
(SYMMETRICAL)
- ABOVE FINISHED FLOOR
- AMPERE INTERRUPTING
CAPACITY
- AMMETER
- AMP SWITCH
- ASYMMETRICAL
- AMP TRIP
- AUTOMATIC TRANSFER SWITCH
- AMERICAN WIRE GAUGE
- BOTTOM OF FIXTURE
- BARE STRANDED COPPER
CONDUCTOR
- CONDUIT
- CAPACITY OR CAPACITOR
- COMMUNITY ANTENNA TV
- CIRCUIT BREAKER
- CLOSED CIRCUIT TELEVISION
- CANDELA
- CURRENT LIMITING
- COPPER
- DISCONNECT
- DOUBLE POLE SINGLE THROW
- ELECTRICAL CONTRACTOR
- ELECTRIC WATER COOLER
- ELECTRIC OR ELECTRICAL
- EMERGENCY
- EMERGENCY POWER OFF
- ELECTRICAL METAL TUBING
- FULL LOAD AMPERES
- GALVANIZED RIGID CONDUIT
- GROUNDING ELECTRODE
CONDUCTOR
- GENERATOR
- GROUND FAULT CIRCUIT
INTERRUPTER
- GROUND FAULT INDICATION
- GROUND FAULT PROTECTION
- GROUND
- HAND-OFF-AUTO
- HORSEPOWER
- INTERMEDIATE METAL
CONDUIT
- ISOLATED GROUND
- JUNCTION BOX
- THOUSAND AMPERE
INTERRUPTING CAPACITY
- KILOVOLT AMPERES
- KILOWATT
- KILOWATT HOUR
- LIGHT EMITTING DIODE
- LIGHTING
- LOW VOLTAGE
- MINIMUM CIRCUIT AMPS
- MAIN CIRCUIT BREAKER
ABBREVIATIONS
- MOTOR CONTROL CENTER
- MANHOLE
- MAIN LUGS ONLY
- NORMALLY CLOSED
- NATIONAL ELECTRICAL CODE
- NOT IN CONTRACT
- NOT IN SCOPE OF THIS
PROJECT
- NON FUSIBLE
- NIGHT LIGHT
- NORMALLY OPEN
- NOT TO SCALE
- OVER CURRENT
PROTECTION
- OVERLOADS
- POLE
- PULLBOX
- PHASE
- PANEL
- POINT OF CONNECTION
- POLYVINYL CHLORIDE
- POWER
- RECEPTACLE
- RIGID GALVANIZED STEEL
- SOLENOID
- SINGLE POLE DOUBLE
THROW
- SPEAKER
- SINGLE POLE SINGLE
THROW
- SWITCH
- SWITCHBOARD
- SYMMETRICAL
- TELEPHONE
- TELECOMMUNICATIONS
GROUNDING BUSBAR
- TELEPHONE MOUNTING
BOARD (PLY-WOOD)
- TELEPHONE TERMINAL
BACKBOARD
- TELEVISION
- TYPICAL
- UNDERGROUND
- UNLESS OTHERWISE NOTED
- VOLT
- VOLT AMPERES
- VOLTAGE DROP
- VOLT METER
- VOLT METER SWITCH
- WATTS OR WIRE
- WITH
- WITHOUT
- WEATHERPROOF
- TRANSFORMER
- EXPLOSION PROOF
MCC
MH
MLO
N.C.
NEC
NIC
NIS
NF
NL
N.O.
NTS
OCP
OL
P
PB
PH, Ø
PNL
POC
PVC
PWR
RCPT.
RGS
SOL
SPDT
SPKR
SPST
SW
SWBD
SYM
TEL
TGB
TMB
TTB
TV
TYP
UG
UNO/UNO
V
VA
VD
VM
VS
W
W/ W/O
WP
XFMR
XP
AIR TERMINAL P = PARAPET MOUNTED, S = SCREEN WALL MOUNTED
THRU ROOF DOWN CONDUCTOR TO GROUNDING SYSTEM
OUTSIDE UNDERGOUND GROUND RING - #4/0 BARE CU CONDUCTOR,
DIRECT BURRIED
INTERIOR GROUNDING CONNECTION - #4/0 INSULATED CU CONDUCTOR
U.O.N
MAIN CONDUCTOR SIZED PER NFPA 780
SECONDARY CONDUCTOR SIZED PER NFPA 780
INTERIOR GROUND ELECTRODE CONDUCTOR (DIAGRAMTIC) #4(CU)MIN OR
PER NEC 250.66 / 250.102
COPPER GROUND ROD 3/4"DIA. X 10'-0" LONG
GROUNDING TEST WELL WITH COPPER GROUND ROD 3/4"DIA. X 10'-0" LONG
EXOTHERMIC BONDING GROUNDING CONNECTION
P
LIGHTNING PROTECTION & GROUNDING
IN ADDITION TO ANY OTHER TESTING REQUIREMENTS, THIRD PARTY TESTING SHALL BE
REQUIRED FOR THE FOLLOWING:
GROUND FAULT PROTECTION
• SWITCHBOARDS, PANELBOARDS, MCC'S AND OTHER EQUIPMENT RATED 1000A OR MORE
OR OVER 600V
• INSULATION RESISTANCE TEST (PHASE TO PHASE, PHASE TO GROUND)
• DIELECTRIC VOLTAGE WITHSTAND TEST (PHASE TO PHASE, PHASE TO GROUND)
TRANSFORMERS RATED 100 KVA OR MORE SINGLE PHASE AND 300 KVA OR MORE THREE
PHASE
• INSULATION RESISTANCE TEST (WINDING-WINDING, WINDING-GROUND)
CONDUCTORS THAT SUPPLY EQUIPMENT RATED AT 1000 AMPERES OR MORE, OR OVER 600
VOLTS
• INSULATION RESISTANCE TEST (PHASE TO PHASE, PHASE TO GROUND)
• DC HIGH POTENTIAL TEST (PHASE TO PHASE, PHASE TO GROUND)
EMERGENCY AND STANDBY POWER SYSTEMS: SWITCHBOARDS PANELBOARDS, DISTRIBUTION
BOARDS, TRANSFER EQUIPMENT, POWER SOURCE, CONDUCTORS, FIRE PUMPS, EXHAUST
AND VENTILATION FANS.
• PHASE ROTATION TEST
• INSULATION RESISTANCE TEST ON FEEDER CONDUCTORS AND EQUIPMENT (PHASE TO
PHASE, PHASE TO GROUND)
• AUTOMATIC TRANSFER TEST
• OPERATION TEST SYSTEM UNDER LOAD CONDITIONS
TESTING AND SPECIAL INSPECTIONS
NFPA 101 - LIFE SAFETY CODE LATEST
INTERNATIONAL FIRE CODE 2018
FIRE AND LIFE SAFETY CODES EDITION
INTERNATIONAL BUILDING CODE (IBC) 2018
AMERICANS WITH DISABILITIES ACT (ADA) LATEST
OWNER SPECIFICATIONS AND STANDARDS VA TIL
LOCAL AND STATE CODES AND AMENDMENTS VA TIL
NATIONAL ELECTRICAL CODE (NFPA 70) 2023
GENERAL EDITION
ALL OF THE FOLLOWING ARE HEREBY MADE PART OF THESE SPECIFICATIONS. THEY SHALL
BE SATISFIED BY THE CONTRACTOR AT NO ADDITIONAL EXPENSE TO THE OWNER
CODES AND STANDARDS
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
65% SUBMITTAL - NOT
FOR CONSTRUCTION
LAKE BALDWIN VA
CLINIC
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
AESUS DESIGN GROUP
1050 E. Southern Ave., Suite D Temple, AZ, 85282 480-454-2861 David Combs
June 7, 2023 TS RS
5201 RAYMOND ST, ORLANDO, FL 32803
C R e vi t\
\L a ke
B a ld w in -E le c-
R ts ch n e p f.
rv t
/1 /2
:4
:5
P M
E.000
SYMBOLS AND ABBREVIATIONS
-ELECTRICAL SHEET LIST-
Sheet Number Sheet Name
ELECTRICAL
E.000 SYMBOLS AND ABBREVIATIONS
EP.101 ELECTRICAL POWER PLAN
EP.601 ELECTRICAL ONE-LINE DIAGRAM - EXISTING CONDITIONS
EP.602 ELECTRICAL ONE-LINE DIAGRAM - DEMO
EP.603 ELECTRICAL ONE-LINE DIAGRAM - NEW
TOTAL:: 5
Revisions: Date:
LAKE BALDWIN SITE
ELECTRICAL UPGRADES
Project Number
675-23-801
FOR CONSTRUCTION
0% SUBMITTAL - NOT 10
Issue Date
OCT 13, 2023
C C
C O
N C
C
LF
M E
TA
L
S
TA
IR
S
M E
TA
L
S
TA
IR
S
CC
W O O D
D E C K
W O O D
D E C K
W O O D
D E C K
WO
OD DE
C K
WO
OD ST
EP
S
W O O D
S
TE
P S
W O O D
D E C K
W O O D
D E C K
W O O D
R A M P
WOOD
DECK
W O O D
D E C K
W O O D
D E C K
W O O D
D E C K
(T Y P
W O O D
R A M P
W O O D
S
TE
P S
(T Y P
G A Z E B O
W O O D
R A M P
W O O D
D E C K
W O O D
D E C K
WOOD
DECK
WOOD
RAMP
8' CW UNDER WOOD
RAMP
C O V E R E D
W O O D
C O V E R E D
W O O D
W O O D
S
TE
P S
WOOD
RAMP
W O O D
D O C K
8' CW UNDER WOOD
RAMP
WOOD
RAMP
WOOD
DECK
W O O D
S
TE
P S
N89°59'50"W 70.57'
PLAT S
°0 '5 "E
.4
P
LA
T
BRICK
BRICK
RETENTION AREA
RETENTION AREA
R E
T E
N T
IO
N
A R
E A
RETENTION AREA
RETENTION AREA
RETENTION AREA
R E
T E
N T
IO
N
A R
E A
R E
T E
N T
IO
N
A R
E A
R E
T E
N T
IO
N
A R
E A
R E
T E
N T
IO
N
A R
E A
RETENTION AREA
R E
T E
N T
IO
N
A R
E A
R E
T E
N T
IO
N
A R
E A
R E T E N
TI
O N
A R E A
R E T E N
TI
O N
A R E A
D
IR
T
R O A D
DI
RT RO
AD
DIRT
ROAD
D
IR
T
D
IR
T
D
IR
T
D
IR
T
D
IR
T
S A
T E
L L
IT
E
A N
T E
N N
A
M E
T A
L L
ID
T
1 STORY
MODULAR BUILDING
ADDRESS #508
37.7'
.8 ' 8.8'
.8
26.2'
.3
72.8'
.3
.3
72.8'
.3
26.2'
.8 '8.8'
.8
37.7'
1 STORY
MODULAR BUILDING
ADDRESS #507
MODULAR BUILDING
ADDRESS #505
60.3'
.4
' MODULAR BUILDING
#506
37.7'
.8 ' 8.8'
.8
26.2'
.3
72.8'
.3
S
TO
R Y
B
LO
C K
F R A M E
A D D R E S S
( C O U R T Y A R D
N O T
LO
C A T E D
52.1'
.7
147.1'
4.5'
14.8'
66.7'
.6
15.7'
.4 '82.3'
.7
52.1'
.6
84.8'
.8
28.1'
31.9'
42.8'
.3
33'
.6
6.9'
.4
15.3'
.8
15.3'
.9
59.6'
.8
97.2'
.2
.6
97.3'
.1
.5
20'x8'
1 STORY
WOOD TRAILER
C C
C C
CC
C P
C P
' C
W
' C
W
4' CW
C O
N C
D W
C P
5' CW
C C
5' CW
C P
C P
C O
N C
C O
N C
' C
W
C P
C P
C O
N C
CC
C C
CC
C C
CW
CW C
C
C O
N C
6' CW
C O
N C
C P
C P
C O
V E
R E
D L
O A
D
IN
G D
O C
K
20.7'
COVD
C C
C C
C O
N C
C O
N C
C P
C P
C P
C P
ALIMINUM STEPS
A L
IM
IN
U M
R A
M P
C P
C P
C O
N C
C O
N C
' C
W
CP
C O
N C
C C
' C
W
C P
C P
C P
C C
C C
C C
C O
V E
R E
D C
W 6'
C W
' C
W
COVERED CW
C O
V E
R E
D C
W
6' CW
CC
S T
E P
S T
E P
S T
E P
C C
C C
CONC
CW CW
C O
N C
C O
N C
A P
R O
N
C O
N C
A P
R O
N
C O
N C
A P
R O
N
5' CW
CW
CW
C W
G A
R V
E L
C P
C W
C W
6' CW
P la n te d M o u n d
C P
C P
C O
N C
9' C W
9' C W
C C
' C
W
CW
C P
4' CW
4' CW
C O
N C
A P
R O
N
C O
N C
A P
R O
N
C O
N C
C O
V D
C C
C O
N C
C P
C O
N C
C U
R B
T
Y P
C O
N C
C U
R B
T
Y P
C O
N C
R
IP
R A
P
6' CW
6' CW
' C
W
5' CW 5' CW
5' CW
5' CW
5' CW
6' C
W
C O
N C
C O
N C
C O
N C
F L
U M
E
C O
N C
F L
U M
E
C O
N C
F L
U M
E
C O
N C
F L
U M
E
C O
N C
'C
W
C P
C O
N C
5' C
W
' C
W
C O
N C
L
ID
CONC
5' CW
5' CW
' C
W C
O N
C S
T E
P S
C O
N C
S T
E P
S
C O
N C
5' CW
' C
W
' C
W
8' CW
8' CW 6' CW
5' CW
CONC
APRON
CONC
APRON
C O
N C
A P
R O
N
7' CW
CW
CW
' C
W
' C
W
C P
C P
6' CW
C P
C P
C P
C P
C P
C W
5' CW
CP
4' CW
C W
R A
M P
C O
V D
CW
C
P 5' CW
C O
N C
5' C
W
' C
W
F O
U N
T A
IN
C O
V D
C W6 ' C
W
8' CW
' C
W
C P
C C
5' C
W
4' CW
4' CW
C O
N C
C W
C O
N C
C O
N C
C P
C W
C W
C W
C P
' C
W
C C
COVERED CW
COVERED CW
C W
5' CW
CW
C W
C P
CP
C O
N C
CONC
C C
G R
A V
E L
C O
N C
S T
E P
S
C P
C P
C O
N
C CONC
CC
RAMP
C P
CW
C W
'x
' C
P
'x
' C
P
'x
' C
P
C P
R A
M P
R A
M P
C C
C O
N C
CW
C O
N C
C C
CC
CC
C C
C C
C C
C C
R A
M P
CC
C O
N C
D
IR
T
CW
C C
C
CCONC
G E
N E
R A
T O
R A
R E
A
R A
M P
R A
M P
C O
V E
R E
D R
A M
P
CW
L O
A D
IN
G
D O
C K
C O
N C
C C
S T
E P
S
COVERED RAMP
C O
N C
C C
COVERED CW
6' CW
R A
M P
C O
N C
C O
N C
C O
N C
R A
M P
C O
N C
M E
T A
L L
ID
C O
N C
C U
R B
T
Y P
C O
N C
C R
A W
L S
P A
C E
A C
C E
S S
' C
W
8' CW METAL STAIRS
C W
STAIRS
S T
A
IR
S
CW
C O
N C
C C
CONC
CW
G A
R V
E L
C O
N C
S T
E P
S
RAMP
R A
M P
CW
4' CW
'x
' C
P
C O
N C
S T
E P
S R
A M
P
'x
' C
P
C W
C W
2.5'
1.4'
32.1'
.1
.6
. 8
49.3'
C W
C W
STEPS
CC
C O
V E
R E
D C
W
CONC
C C
C C
C O
N C
CONC STEPS
C W
G A
R V
E L
C P
C O
N C
S T
E P
S
C W
CPC
C
CW
CONC
CW
C W
6' CW6' CW6' CW
G A S
P U M P
CBW
C O
N C
H E
A D
W A
L L
C O
N C
H E
A D
W A
L L
C O
N C
H E
A D
W A
L L
C O
N C
H E
A D
W A
L L
CONC
HEADWALL
C O
N C
H E
A D
W A
L L
CONC
HEADWALL
C O
N C
H E
A D
W A
L L
C O
N C
H E
A D
W A
L L
C O
N C
H E
A D
W A
L L
C O
N C
H E
A D
W A
L L
.4 'x .4 C O
LU
M N
(T Y P
.4 'x .4 C O
LU
M N
(T Y P
C O
N C
H E
A D
W A
L L
B R
IC
K
W A L L
BRICK
WALL
CBW
BRICK
WALL
B R
IC
K
W A L L
BRICK
WALL
BRICK
WALL
BRICK
WALL
D
IR
T D
IR
T
D
IR
T
1'E
.8 'S
C B W
C B W
C B W
C B W
.6 'S
.0 'S
CBW CBW
A B A N D O N E D
E
T
CLF
C
LF
C
LF
C
LF
C
LF
D
IE
S E L F U E L
S
TO
R A G E
C
LF
C
LF
C
LF
C L F
C
LF
C
LF
C
LF
C
LF
C
LF
C
LF
C
LF
M F
M F
C L F
C L F
C
LF
C L F
C
LF
C
LF
M F
1'W
0.5'W
M F
M F
0.7'W
0.4'W
1.5'W
C
LF
0.7'W
C
LF
.6
1.3'W
C L F
C L F
C
LF
C
LF
S89°59'23"W 333.86'
MEAS
S87°40'34"E 206.41'
MEAS
S °5 '3 " W
. 2
M E A S
S °5 '4 " W
. 0
M E A S
A S
P H
A L T
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
TA
S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
T
ASPHALT
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
TA
S
P H
A L
T
A S
P H
A L
T
ASPHALT
ASPHALT
A S
P H
A L
T
A S
P H
A L
T
ASPHALT
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
T
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
T
ASPHALT
ASPHALT
ASPHALT
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
T
A S P H A
LT
F L U M E
A S P H A
LT
F L U M E
A S
P H
A L
T
ASPHALT
ASPHALT
ASPHALT
.3
.7
.3
.1
.8
.3
.3
. 5
.7
R
ID
L E
Y A
V E
N U
E
RAYMOND STREET
RAYMOND STREET
R A
Y M
O N
D S
T R
E E
T
PALMETTO AVENUE
C O
M F
O R
T A
V E
N U
E
NASH STREET
NASH STREET
M E
R C
Y A
V E
N U
E
LAKE BALDWIN LANE
E B
E B
E B
E B
E B
E B
E B
U B
U B
U B
U B
U B
UB
UB
UB
U B
U B
UP
UP
UP
UP
UP
V
G M
G V
UP
UP
UP
UP
UP
UP
UP
UP
U P
V
UP
E B
EB
E B
E B
EB
E B
E B
E B
E B
E B
E B
E B
E B
E B
E B
E B
E B
U
PU
P
UP
F O
C
E B
GV
UP
E B
GV
UP
UP
UP
UP
UP
UP
T T
T
T
EB
T
E B
T V
EB
EB
SD
SD
EL
SD SD
A. PROVIDE AND INSTALL NEW WIRING DEVICES IN ALL LOCATIONS VACATED DURING
DEMOLITION WHETHER OR NOT LOCATIONS ARE EXPLICITLY INIDCATED ON THE
PLAN DRAWINGS. UTILIZE EXISTING BRANCH CIRCUITS COILED DURING THE
DEMOLITHION PHASE AND UTILIZE EXISTING BACK BACKBOXES WHERE FEASIBLE.
WHERE BACKBOXES ARE DAMAGED OR OTHERWISE UNUSABLE PROVIDE NEW
BACKBOXES AT EXISTING WIRING DEVICES LOCATIONS.
B. REFER TO SHEET E-001 SYMBOLS, ABBREVIATIONS, AND ADDITIONAL
REQUIREMENTS INCLUDING, BUT NOT LIMITED TO, CODE REQUIREMENTS,
EQUIPMENT AND MATERIAL SPECIFICATIONS AND INSTALLATION REQUIREMENTS,
DEVICE MOUNTING HEIGHTS, EQUIPMENT IDENTIFICATION, ETC.
C. DRAWINGS AND SPECIFICATIONS ARE COMPLEMENTARY OF EACH OTHER. WHERE
DRAWINGS AND SPECIFICATIONS DIFFER, THE MORE STRINGENT OF THE TWO
REQUIREMENTS SHALL BE FOLLOWED.
D. ALL EQUIPMENT AND FIXTURES ARE NEW UNLESS NOTED OTHERWISE.
E. CONDUIT AND WIRE IS SHOWN DIAGRAMMATICALLY. ACTUAL ROUTING AND
REQUIRED NUMBER OF SUPPORTS SHALL BE DETERMINED BY THE CONTRACTOR.
F. UNLESS CONDUIT ROUTING CLEARLY INDICATES AS SUCH, DO NOT ROUTE
CONDUIT ON OR ABOVE ROOFTOPS WITHOUT CONSULTING ENGINEER TO
DETERMINE ANY POTENTIAL IMPACT TO RACEWAY OR CONDUCTOR SIZE DUE TO
ADDITIONAL AMBIENT DERATING FOR ROOFTOP INSTALLATION.
G. CONCEAL CONDUITS IN ALL FINISHED AREAS INCLUDING CONCEALMENT WITHIN
MASONRY WALLS WHEN PRESENT. (EXCEPTION: ELECTRICAL, MECHANICAL, AND
JANITOR ROOMS).
H. FLOOR AND FIRE WALL PENETRATIONS MUST BE SEALED WITH AN APPROVED
DESIGN TESTED FIRE STOPPING SYSTEM APPROPRIATE TO THE PENETRATED WALL
TYPE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S REQUIREMENTS.
I. PRIOR TO ROUGH-IN AND FINAL CONNECTION, VERIFY ELECTRICAL
CHARACTERISTICS AND EXACT LOCATION OF THE EQUIPMENT.
J. INSTALL ALL CONDUITS PARALLEL PERPENDICULAR AND UNIFORM TO BUILDING
ELEMENTS
K. ALL WALL VOICE/DATA DROPS SHOWN ON TELECOM DRAWINGS SHALL HAVE A
MINIMUM 4” SQUARE JUNCTION BOX AND 1” CONDUIT WITH PULL CORD STUBBED UP
INTO CEILING SPACE OR TO THE CABLE TRAY, IF APPLICABLE.
L. NO MORE THAN 270 DEGREES OF CONDUIT BENDS ARE ALLOWED IN ANY CONDUIT
RUNS NO MORE THAN 180 DEGREE OF CONDUIT BENDS ARE ALLOWED IN ANY
INTERIOR CONDUIT RUNS.
M. IDENTIFY ALL CONDUIT RUNS WITH MARKER TAPE.
N. ALL FIRE ALARM CABLING SHALL BE IN RED EMT INCLUDING FITTINGS EXCEPT
WHERE EXPOSED AND SUBJECT TO VANDALISM WHERE IT SHALL BE RED RGS
INCLUDING FITTINGS. ALL BOXES CONTAINING FIRE ALARM CABLING SHALL BE RED.
O. ALL RECEPTACLE AND SWITCH COVER PLATES SHALL BE STAINLESS STEEL UNLESS
NOTED OTHERWISE. ALL DEVICE COVER PLATES SHALL BE LABELED WITH THE
PANEL NAME AND BRANCH CIRCUIT NUMBER IDENTIFIED
P. VERIFY ALL EQUIPMENT LOCATIONS AND DIMENSIONS IN THE FIELD PRIOR TO
INSTALLING RACEWAYS AND WIRING
Q. ELECTRICAL WORK SHALL BE DONE IN CONFORMANCE WITH THE CONSTRUCTION
DOCUMENTS, ALL APPLICABLE CODES, ISSUED DRAWINGS AND SPECIFICATIONS.
R. ALL 20A 120V RECEPTACLES WITHIN 6FT OF A SINK OR WET DAMP AREA SHALL BE
GFCI PROTECTED PER NEC 210.8(B)(5)(6).
GENERAL NOTES
(E)-GEN1
(E)-GEN2
(E)-GEN3
(E)-SWBD-EM
(E)-MV-MWS-NO.1
(E)-MV-XF-NO.1
(E)-MV-ATS-NO.1
(E)-MV-MWS-NO.1A
(E)-MV-XF-517
(E)-NORTH OUC
(E)-MV-2WS-NO.4
(E)-MV-2WS-NO.4
(E)-MV-ATS-NO.4
(E)-MV-MWS-NO.4
(E)-MV-XF-NO.3
(E)-MV-ATS-NO.2
(E)-MV-MWS.NO.2 (E)-MV-MWS-NO.3
(E)-MV-ATS-NO.3
(E)-MV-XF-NO.2
(E)-MV-XF-ADMIN-T2
(E)-SOUTH OUC
(E)-MV-XF-517
(E)-MV-XF-501
(E)-MV-XF-503
BLD 503
BLD 500
BLD 509
BLD 519A
BLD 504
BLD 502
BLD
BLD 501
BLD
BLD 3130
B
LD
BLD
B
LD
B
LD
B
LD
B
LD
BLD 3133
BLD 3136
BLD 510
BLD 521
B
LD
B
LD
BLD 519
BLD 505 BLD 506 BLD 507 BLD 508
MV-XF-ENG
519-ATS-K
MV-XF-504
EXTEND EXISTING MV YARD
REMOVE SEPARATING WALL BETWEEN MV-
MWS-NO.1 AND MV-XF-NO.1
MV-XF-EM
EXISTING U/G DUCTBANK FROM
NORTH OUC TO MV-MWS-NO.1A
(APPROX. ROUTE)
NEW CONCRETE ENCASED U/G DUCTBANK FROM MV-MWS-NO.1A (DEMOISHED)
LOCATION TO MV-MWS-NO.1
(APPROX. ROUTE)
SEE ALTERNATIVE OPTION ON EP.602 FOR ADDITIONAL INFORMATION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FOR CONSTRUCTION
LAKE BALDWIN VA
CLINIC
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
AESUS DESIGN GROUP
1050 E. Southern Ave., Suite D Temple, AZ, 85282 480-454-2861 David Combs
LAKE BALDWIN SITE
ELECTRICAL UPGRADES
OCT 13, 2023 TS TS
5201 RAYMOND ST, ORLANDO, FL 32803
C R e vi t\
\L a ke
B a ld w in -E le c-
R ts ch n e p f.
rv t
/1 /2
:4
:5
P M
EP.101
ELECTRICAL POWER PLAN
KEYNOTES
NOT USED.
1" = 60'-0"1 SITE PLAN (EXISTING)
Revisions: Date:
675-23-8010% SUBMITTAL - NOT 10
M
M M M M
M
(BLD 502 EXT)
MV-MWS-NO-3
12470V
MV-MWS-NO 1A
12470V
(BLD 502 EXT)
MV-MWS-NO.1
12470V
(BLD 502 EXT)
MV-MWS-NO.2
12470V
(EXT BLD 502)
MV-ATS-NO.1
1200A, 3P, 12470V
OUC NORTH
(BLD 3122 EXT)
MV-MWS-NO-4
12470V
MV-XF-ADMIN-T2
500KVA
12470V
208Y/120V 5.4%Z
(BLD 506 EXT)
MV-XF-ADMIN-T2
208V/120V
MV-XF-504
150KVA
12470V
208Y/120V 3.9%Z
MV-XF-NO.1
1000KVA
12470V
480Y/277V 6%Z
MV-XF-513
300KVA
12470V
208Y/120V 4.6%Z
502-ATA-A
260A, 4P, 480/277V
502-ATS-EQ
1600A, 4P, 480Y/277V
502-ATS-#1
1600A, 4P, 480Y/277V
(BLD 502 RM 101)
502-SWBD-1
480V/277V
(EXT GREEN TEAM)
MV-ATS-NO.2
1200A, 3P, 12470V
MV-XF-NO.2
1500KVA
12470V
480Y/277V 6%Z
(EXT GREEN TEAM)
MV-ATS-NO.3
1200A, 3P, 12470V
MV-XF-501
150KVA
12470V
480Y/277V
6.2%Z
MV-XF-NO.3
1500KVA
12470V
480Y/277V 6.1%Z
501-L1
480V/277V
(EXT BLD 3132)
MV-ATS-NO.4
1200A, 3P, 12470V
OUC SWITCH
12470V
MV-XF-517
150KVA
12470V
208Y/120V
6.75%Z
(EXT BLD 517)
517-FDS
208V/120V
(EXT BLD 3132)
MV-MWS-NO4
12470V
MV-XF-519
500KVA
12470V
480Y/277V
3.4%Z
MV-XF-503
500KVA
12470V
208Y/120V
4.6%Z
MV-XF-ENG
300KVA
12470V
208Y/120V 3.5%Z
(RM 113A)
521-MDP
480V/277V
(RM 141)
519-MSB
480V/277V
521-CHILLER
512-XF
45KVA
480V
208Y/120V
6%Z(EXT 510)
510-MDP
208V/120V
(RM 106)
520-H1C 480V/277V
519-T-K
45KVA
480V
208Y/120V 5.21%Z
(EMERG) 519-ATS-K
150A, 4P, 208/120V
(RM 142 EMERG)
519-K 208V/120V
(RM 106)
519A-H1D 480V/277V
501-XF-R1
30KVA
480V
208Y/120V 3.7%Z
501-R1
208V/120V
(EMERG) 501-ATS-EL1
100A, 4P, 480/277V
502-SWBD-EM
480V
502-SWBD-3-EM-MB
480V
500-SWBD3-EM-ATS-2
150A, 4P, 480/277V
500-SWBD3-EM-ATS-3
150A, 4P, 480/277V
500-SWBD3-EM-ATS-4
150A, 4P, 480/277V
500-SWBD3-EM-ATS-5
150A, 4P, 480/277V
500-ELEV-1 500-ELEV-2 500-ELEV-3 500-ELEV-4
500-SWBD-3
480V
505-XF
150KVA
480V
208Y/120V 5.8%Z
500-XF-N2T3
75KVA
480V
208Y/120V 4.5%Z
500-MCC-NMC
480V/277V
500-UNK-2
480V/277V
500-PHA
480V/277V
500-XF-NMT2
225KVA
480V
208Y/120V 6%Z
500-XF-N2T2
150KVA
480V
208Y/120V 5.53%Z
ATS-6
400A, 4P, 480/277V
ATS-7
260A, 4P, 480/277V
ATS-8
600A, 4P, 480/277V
500-MCC-AMC1
480V/277V
500-MCC-AMC2
480V/277V
500-PNL-CMH
480V/277V
500-SWBD-2
480V
500-XF-N2T1
150KVA
480V
208Y/120V
5.53%Z
(AHU #1)
500-ECB-N2T1
208V/120V
(RM 1450)
(500-PNL-N1H4)
480V/277V
500-XF-NMT1
225KVA
480V
208Y/120V 6%Z
(MEZZ)
500-ECB-NMT1
208V/120V
500-ATS-2
400A, 4P, 480/277V
(EXT ELEC RM)
500-ATS-2-LD
480V/277V
(PLEB LAB)
500-PNL-N1H1
480V/277V
500-ATS-3
600A, 4P, 480/277V
(RM G1087)
500-PNL-C1H1
480V/277V
(EXT B.500)
500-N2P5-FDS
480V/277V
500-ATS-C2P5
100A, 4P, 480/277V
(EXT-B.500 ATS)
500-ATS-C2P5-LD
480V/277V
500-ATS-1
260A, 4P, 480/277V
(ELEC RM)
500-ATS-1-LD
480V/277V
500-ATS-5
400A, 4P, 480/277V
(EXT ELEC RM)
500-ATS-5-LD
480V/277V
500-ATS-4
400A, 4P, 480/277V
(EXT ELEC RM)
500-ATS-4-LD
480V/277V
(RM 1814)
500-PNL-N1H3
480V/277V
(RENOVATION)
500-XRAY-D1029
480V/277V
(RENOVATION)
500-XRAY-D1014
480V/277V
(RENOVATION)
500-XRAY-D1006
480V/277V
(RM. 240)
500-PNL-N2H
480V/277V
(RM 1109)
500-PNL-N1H2
480V/277V
FIRE PUMP (504- RM 139)
504-MDP
208V/120V
513-MDP
208V/120V
(RM 111)
501-EL1
480V/277V
(LOC EXT B500)
500-PLS-1
208V/120V
(LOC EXT B505)
505-PL-MAIN-FDS
208V/120V
(AHU #4)
500-PNL-N2P1
208V/120V
(MEZZ)
500-PNL-NMP2
208V/120V
(RM 1109)
500-PNL-N1P6
208V/120V
502-SWBD-4
480V
519-T-K
45KVA
480V
208Y/120V 5.21%Z
(NOT VA)
STATE BLD
208V/120V
3130-FDS (ABANDONED)
208V/120V
3130-FDS
208V/120V
RISER
TO OVERHEAD
3134-PL1
208V/120V
3132-PL1
208V/120V
3133-PL1
208V/120V
3133-EXT-B-FDS
208V/120V
3129-A
208V/120V
3128-PL1
208V/120V
3125-PL1
208V/120V
3126-PL1
208V/120V
3126-EXT-A
208V/120V
(3132 EXT)
MV-2WS-NO.4
12470V
MV-MH#89
12470V
OUC SOUTH
OWNED BY UTILITY
OWNED BY VA
OWNED BY UTILITY
GENERATOR BACKED POWER
DUAL UTILITY POWER
SOUTH UTILITY POWER
NORTH UTILITY POWER
ONE-LINE LEGEND
EXISTING
NEW
KEYNOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
90% SUBMITTAL - NOT
FOR CONSTRUCTION
LAKE BALDWIN VA
CLINIC
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
AESUS DESIGN GROUP
1050 E. Southern Ave., Suite D Temple, AZ, 85282 480-454-2861 David Combs
LAKE BALDWIN SITE
ELECTRICAL UPGRADES
OCT 13, 2023 TS TS
5201 RAYMOND ST, ORLANDO, FL 32803
C R e vi t\
\L a ke
B a ld w in -E le c-
R ts ch n e p f.
rv t
/1 /2
:4
:5
P M
EP.601
ELECTRICAL ONE-LINE DIAGRAM -
EXISTING CONDITIONS
6" = 1'-0"1 ELECTRICAL ONE-LINE DIAGRAM - EXISTING CONDITIONS
NOT USED
Revisions: Date:
675-23-801
FOR CONSTRUCTION
0% SUBMITTAL - NOT 10
M
(BLD 502 EXT)
MV-MWS-NO-3
12470V
MV-MWS-NO 1A
12470V
(BLD 502 EXT)
MV-MWS-NO.1
12470V
(BLD 502 EXT)
MV-MWS-NO.2
12470V
(EXT BLD 502)
MV-ATS-NO.1
1200A, 3P, 12470V
OUC NORTH
(BLD 3122 EXT)
MV-MWS-NO-4
12470V
MV-XF-ADMIN-T2
500KVA
12470V
208Y/120V
5.4%Z
(BLD 506 EXT)
MV-XF-ADMIN-T2
208V/120V
MV-XF-504
150KVA
12470V
208Y/120V
3.9%Z
MV-XF-NO.1
1000KVA
12470V
480Y/277V 6%Z
MV-XF-513
300KVA
12470V
208Y/120V
4.6%Z
502-ATA-A
260A, 4P, 480/277V
502-ATS-EQ
1600A, 4P, 480Y/277V
502-ATS-#1
1600A, 4P, 480Y/277V
(BLD 502 RM 101)
502-SWBD-1
480V/277V
(EXT GREEN TEAM)
MV-ATS-NO.2
1200A, 3P, 12470V
MV-XF-NO.2
1500KVA
12470V
480Y/277V 6%Z
(EXT GREEN TEAM)
MV-ATS-NO.3
1200A, 3P, 12470V
MV-XF-501
150KVA
12470V
480Y/277V
6.2%Z
MV-XF-NO.3
1500KVA
12470V
480Y/277V 6.1%Z
501-L1
480V/277V
(EXT BLD 3132)
MV-ATS-NO.4
1200A, 3P, 12470V
OUC SWITCH
12470V
MV-XF-517
150KVA
12470V
208Y/120V
6.75%Z
(EXT BLD 517)
517-FDS
208V/120V
(EXT BLD 3132)
MV-MWS-NO4
12470V
MV-XF-519
500KVA
12470V
480Y/277V
3.4%Z
MV-XF-503
500KVA
12470V
208Y/120V
4.6%Z
MV-XF-ENG
300KVA
12470V
208Y/120V
3.5%Z
(RM 113A)
521-MDP
480V/277V
(RM 141)
519-MSB
480V/277V
521-CHILLER
512-XF
45KVA
480V
208Y/120V
6%Z(EXT 510)
510-MDP
208V/120V
(RM 106)
520-H1C 480V/277V
519-T-K
45KVA
480V
208Y/120V 5.21%Z
(EMERG) 519-ATS-K
150A, 4P, 208/120V
(RM 142 EMERG)
519-K
208V/120V
(RM 106)
519A-H1D 480V/277V
501-XF-R1
30KVA
480V
208Y/120V 3.7%Z
501-R1
208V/120V
(EMERG) 501-ATS-EL1
100A, 4P, 480/277V
502-SWBD-EM
480V
502-SWBD-3-EM-MB
480V
500-SWBD3-EM-ATS-2
150A, 4P, 480/277V
500-SWBD3-EM-ATS-3
150A, 4P, 480/277V
500-SWBD3-EM-ATS-4
150A, 4P, 480/277V
500-SWBD3-EM-ATS-5
150A, 4P, 480/277V
500-ELEV-1 500-ELEV-2 500-ELEV-3 500-ELEV-4
500-SWBD-3
480V
505-XF
150KVA
480V
208Y/120V 5.8%Z
500-XF-N2T3
75KVA
480V
208Y/120V
4.5%Z
500-MCC-NMC
480V/277V
500-UNK-2
480V/277V
500-PHA
480V/277V
500-XF-NMT2
225KVA
480V
208Y/120V
6%Z
500-XF-N2T2
150KVA
480V
208Y/120V
5.53%Z
ATS-6
400A, 4P, 480/277V
ATS-7
260A, 4P, 480/277V
ATS-8
600A, 4P, 480/277V
500-MCC-AMC1
480V/277V
500-MCC-AMC2
480V/277V
500-PNL-CMH
480V/277V
500-SWBD-2
480V
500-XF-N2T1
150KVA
480V
208Y/120V
5.53%Z
(AHU #1)
500-ECB-N2T1
208V/120V
(RM 1450)
(500-PNL-N1H4)
480V/277V
500-XF-NMT1
225KVA
480V
208Y/120V
6%Z
(MEZZ)
500-ECB-NMT1
208V/120V
500-ATS-2
400A, 4P, 480/277V
(EXT ELEC RM)
500-ATS-2-LD
480V/277V
(PLEB LAB)
500-PNL-N1H1
480V/277V
500-ATS-3
600A, 4P, 480/277V
(RM G1087)
500-PNL-C1H1
480V/277V
(EXT B.500)
500-N2P5-FDS
480V/277V
500-ATS-C2P5
100A, 4P, 480/277V
(EXT-B.500 ATS)
500-ATS-C2P5-LD
480V/277V
500-ATS-1
260A, 4P, 480/277V
(ELEC RM)
500-ATS-1-LD
480V/277V
500-ATS-5
400A, 4P, 480/277V
(EXT ELEC RM)
500-ATS-5-LD
480V/277V
500-ATS-4
400A, 4P, 480/277V
(EXT ELEC RM)
500-ATS-4-LD
480V/277V
(RM 1814)
500-PNL-N1H3
480V/277V
(RENOVATION)
500-XRAY-D1029
480V/277V
(RENOVATION)
500-XRAY-D1014
480V/277V
(RENOVATION)
500-XRAY-D1006
480V/277V
(RM. 240)
500-PNL-N2H
480V/277V
(RM 1109)
500-PNL-N1H2
480V/277V
FIRE PUMP (504- RM 139)
504-MDP
208V/120V
513-MDP
208V/120V
(RM 111)
501-EL1
480V/277V
(LOC EXT B500)
500-PLS-1
208V/120V
(LOC EXT B505)
505-PL-MAIN-FDS
208V/120V
(AHU #4)
500-PNL-N2P1
208V/120V
(MEZZ)
500-PNL-NMP2
208V/120V
(RM 1109)
500-PNL-N1P6
208V/120V
502-SWBD-4
480V
519-T-K
45KVA
480V
208Y/120V 5.21%Z
(NOT VA)
STATE BLD
208V/120V
3130-FDS (ABANDONED)
208V/120V
3130-FDS
208V/120V
RISER
TO OVERHEAD
3134-PL1
208V/120V
3132-PL1
208V/120V
3133-PL1
208V/120V
3133-EXT-B-FDS
208V/120V
3129-A
208V/120V
3128-PL1
208V/120V
3125-PL1
208V/120V
3126-PL1
208V/120V
3126-EXT-A
208V/120V
(3132 EXT)
MV-2WS-NO.4
12470V
MV-MH#89
12470V
OUC SOUTH
OWNED BY UTILITY
OWNED BY VA
OWNED BY UTILITY
DEMOLISH EXISTING
GENERATOR PARALLELING
SWITCHBOARD
DEMOLISH EXISTING MEDIUM
VOLTAGE MULTI-WAY SWITCH
DEMOLISH FEEDER TO
MV-XF-517
DEMOLISH FEEDER TO MV-XF-
ADMIN-T2
MV-MWS-NO 1A
12470V
OWNED BY VA
ALTERNATE OPTION:
DEMOLISH MV-MWS-NO 1A
OPTION WOULD INCLUDE EXTENDING FEEDER FROM
OUC SWITCH TO MV-MWS-NO.1 DIRECTLY
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
90% SUBMITTAL - NOT
FOR CONSTRUCTION
LAKE BALDWIN VA
CLINIC
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
AESUS DESIGN GROUP
1050 E. Southern Ave., Suite D Temple, AZ, 85282 480-454-2861 David Combs
LAKE BALDWIN SITE
ELECTRICAL UPGRADES
OCT 13, 2023 TS TS
5201 RAYMOND ST, ORLANDO, FL 32803
C R e vi t\
\L a ke
B a ld w in -E le c-
R ts ch n e p f.
rv t
/1 /2
:4
:0
P M
EP.602
ELECTRICAL ONE-LINE DIAGRAM -
DEMO
6" = 1'-0"1 ELECTRICAL ONE-LINE DIAGRAM - MV OPTION 3 (DEMO)
KEYNOTES
NOT USED
Revisions: Date:
675-23-801
M
MV-XF-504
150KVA
12470V
208Y/120V
3.9%Z
MV-XF-NO.1
1000KVA
12470V
480Y/277V 6%Z
MV-XF-513
300KVA
12470V
208Y/120V
4.6%Z
502-ATA-A
260A, 4P, 480/277V
502-ATS-EQ
1600A, 4P, 480Y/277V
502-ATS-#1
1600A, 4P, 480Y/277V
(BLD 502 RM 101)
502-SWBD-1
480V/277V
MV-XF-NO.2
1500KVA
12470V
480Y/277V 6%Z
MV-XF-501
150KVA
12470V
480Y/277V
6.2%Z
MV-XF-NO.3
1500KVA
12470V
480Y/277V 6.1%Z
501-L1
480V/277V
(EXT BLD 3132)
MV-MWS-NO4
12470V
MV-XF-519
500KVA
12470V
480Y/277V
3.4%Z
MV-XF-503
500KVA
12470V
208Y/120V
4.6%Z
MV-XF-ENG
300KVA
12470V
208Y/120V
3.5%Z
(RM 113A)
521-MDP
480V/277V
(RM 141)
519-MSB
480V/277V
521-CHILLER
512-XF
45KVA
480V
208Y/120V
6%Z(EXT 510)
510-MDP
208V/120V
(RM 106)
520-H1C 480V/277V
519-T-K
45KVA
480V
208Y/120V 5.21%Z
(EMERG) 519-ATS-K
150A, 4P, 208/120V
(RM 142 EMERG)
519-K
208V/120V
(RM 106)
519A-H1D 480V/277V
501-XF-R1
30KVA
480V
208Y/120V 3.7%Z
501-R1
208V/120V
(EMERG) 501-ATS-EL1
100A, 4P, 480/277V
502-SWBD-3-EM-MB
480V
500-SWBD3-EM-ATS-2
150A, 4P, 480/277V
500-SWBD3-EM-ATS-3
150A, 4P, 480/277V
500-SWBD3-EM-ATS-4
150A, 4P, 480/277V
500-SWBD3-EM-ATS-5
150A, 4P, 480/277V
500-ELEV-1 500-ELEV-2 500-ELEV-3 500-ELEV-4
500-SWBD-3
480V
505-XF
150KVA
480V
208Y/120V 5.8%Z
500-XF-N2T3
75KVA
480V
208Y/120V
4.5%Z
500-MCC-NMC
480V/277V
500-UNK-2
480V/277V
500-PHA
480V/277V
500-XF-NMT2
225KVA
480V
208Y/120V
6%Z
500-XF-N2T2
150KVA
480V
208Y/120V
5.53%Z
ATS-6
400A, 4P, 480/277V
ATS-7
260A, 4P, 480/277V
ATS-8
600A, 4P, 480/277V
500-MCC-AMC1
480V/277V
500-MCC-AMC2
480V/277V
500-PNL-CMH
480V/277V
500-SWBD-2
480V
500-XF-N2T1
150KVA
480V
208Y/120V
5.53%Z
(AHU #1)
500-ECB-N2T1
208V/120V
(RM 1450)
(500-PNL-N1H4)
480V/277V
500-XF-NMT1
225KVA
480V
208Y/120V
6%Z
(MEZZ)
500-ECB-NMT1
208V/120V
500-ATS-2
400A, 4P, 480/277V
(EXT ELEC RM)
500-ATS-2-LD
480V/277V
(PLEB LAB)
500-PNL-N1H1
480V/277V
500-ATS-3
600A, 4P, 480/277V
(RM G1087)
500-PNL-C1H1
480V/277V
(EXT B.500)
500-N2P5-FDS
480V/277V
500-ATS-C2P5
100A, 4P, 480/277V
(EXT-B.500 ATS)
500-ATS-C2P5-LD
480V/277V
500-ATS-1
260A, 4P, 480/277V
(ELEC RM)
500-ATS-1-LD
480V/277V
500-ATS-5
400A, 4P, 480/277V
(EXT ELEC RM)
500-ATS-5-LD
480V/277V
500-ATS-4
400A, 4P, 480/277V
(EXT ELEC RM)
500-ATS-4-LD
480V/277V
(RM 1814)
500-PNL-N1H3
480V/277V
(RENOVATION)
500-XRAY-D1029
480V/277V
(RENOVATION)
500-XRAY-D1014
480V/277V
(RENOVATION)
500-XRAY-D1006
480V/277V
(RM. 240)
500-PNL-N2H
480V/277V
(RM 1109)
500-PNL-N1H2
480V/277V
FIRE PUMP (504- RM 139)
504-MDP
208V/120V
513-MDP
208V/120V
(RM 111)
501-EL1
480V/277V
(LOC EXT B500)
500-PLS-1
208V/120V
(LOC EXT B505)
505-PL-MAIN-FDS
208V/120V
(AHU #4)
500-PNL-N2P1
208V/120V
(MEZZ)
500-PNL-NMP2
208V/120V
(RM 1109)
500-PNL-N1P6
208V/120V
502-SWBD-3-EM-MB
480V
(NOT VA)
STATE BLD
208V/120V
3130-FDS (ABANDONED)
208V/120V
3130-FDS
208V/120V
RISER
TO OVERHEAD
3134-PL1
208V/120V
3132-PL1
208V/120V
3133-PL1
208V/120V
3133-EXT-B-FDS
208V/120V
3129-A
208V/120V
3128-PL1
208V/120V
3125-PL1
208V/120V
3126-PL1
208V/120V
3126-EXT-A
208V/120V
(BLD 502 EXT)
MV-MWS-NO-3
12470V
MV-MWS-NO 1A
12470V
(BLD 502 EXT)
MV-MWS-NO.1
600 A,
12.47 KV
3PH,
3W
(BLD 502 EXT)
MV-MWS-NO.2
12470V
(EXT BLD 502)
MV-ATS-NO.1
1200A, 3P, 12470V
OUC NORTH
MV-XF-ADMIN-T2
500KVA
12470V
208Y/120V 5.4%Z
(BLD 506 EXT)
MV-XF-ADMIN-T2
208V/120V
(EXT GREEN TEAM)
MV-ATS-NO.2
1200A, 3P, 12470V
(EXT GREEN TEAM)
MV-ATS-NO.3
1200A, 3P, 12470V
(EXT BLD 3132)
MV-ATS-NO.4
1200A, 3P, 12470V
OUC SWITCH
12470V
MV-XF-517
150KVA
12470V
208Y/120V 6.75%Z
(EXT BLD 517)
517-FDS
208V/120V
MV-MH#89
12470V
OUC SOUTH
(NEW) 502-SWBD-EM
3,000A, 480Y/277V
3PH, 4W, AFC=64.65KA, SCCR=65KA
EXISTING GENERATORS (TYPICAL OF 3)
1200 AT
1200 AF
L.S.I.G, N.C., 100%
1200 AT
1200 AF
L.S.I.G, N.C., 100%
1200 AT
1200 AF
L.S.I.G, N.C., 100%
1200 AT
1200 AF
L.S.I.G, N.C., 100%
SPARE
3000 AT
3000 AF
L.S.I.G, N.C., 100%
BREAKER SIZE AND QUANTITY TO MATCH
EXISTING (TYPICAL)
MV-XF-517
2500KVA
480V
12470Y/7200V 6.75%Z
200 AT
FAULT
INTERUPTOR,
N.C.
200 AT
FAULT
INTERUPTOR,
N.C.
200 AT
FAULT
INTERUPTOR,
N.C.
200 AT
FAULT
INTERUPTOR,
N.C.
200 AT
FAULT
INTERUPTOR,
N.C.
RE-FEED FROM NEW
MV SWITCHGEAR
ATS CONTROLLER
200 AT
FAULT
INTERUPTOR,
N.C.
OWNED BY UTILITY
OWNED BY VA
OWNED BY UTILITY
DISCONNECT MV
TRANSFORMER FROM
EXISTING MULTI-WAY SWITCH
DISCONNECT MV
TRANSFORMER FROM
EXISTING MULTI-WAY SWITCH
NEW STEP UP
TRANSFORMER
REPLACE EMERGENCY
PARALLELING SWITCHBOARD
OUC NORTH
OUC SWITCH
12470V
OWNED BY UTILITY
TO MV-MWS-NO.1
TEMP GEN
2000KW
480Y/277V
3PH, 4W
(TEMP) 502-SWBD-EM
3,000A, 480Y/277V
3PH, 4W, AFC=64.65KA, SCCR=65KA
TAP AND EXTEND EXISTING FEEDERS TO TEMP
GENERATOR POWER (TYPICAL)
PROVIDE TEMPORARY EMERGENCY DEISEL
POWERED GENERATORWITH 24HR BELLY
TANK ADJACENT TO BLD 502. PROVIDE A 480,
3000A, 3PH, 4W DISTRIBUTION OUTPUT BOARD
GENERATOR TO FEED EMERGENNCY SYSTEM
DURING CONSTRUCTION
BREAKERS SHALL BE SIZED TO MATCH EXISTING
BRANCH CIRCUIT FEEDER BREAKERS (TYPICAL)
TO BLD 503
GENERATOR BACKED POWER
DUAL UTILITY POWER
SOUTH UTILITY POWER
NORTH UTILITY POWER
ONE-LINE LEGEND
EXISTING
NEW
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
90% SUBMITTAL - NOT
FOR CONSTRUCTION
LAKE BALDWIN VA
CLINIC
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
AESUS DESIGN GROUP
1050 E. Southern Ave., Suite D Temple, AZ, 85282 480-454-2861 David Combs
LAKE BALDWIN SITE
ELECTRICAL UPGRADES
OCT 13, 2023 TS TS
5201 RAYMOND ST, ORLANDO, FL 32803
C R e vi t\
\L a ke
B a ld w in -E le c-
R ts ch n e p f.
rv t
/1 /2
:4
:0
P M
EP.603
ELECTRICAL ONE-LINE DIAGRAM -
NEW
6" = 1'-0"1 ELECTRICAL ONE-LINE DIAGRAM - MV OPTION 3 (NEW)
KEYNOTES
NOT USEDALTERNATE OPTION:
• ONE (1) EXISTING SWITCH TO FEED ONE (1) NEW FEEDER
FROM OUC SWITCH TO MV-MWS-NO.1 DIRECTLY
• ONE (1) EXISTING SWITCH TO BE MARKED AS SPARE.
Revisions: Date:
675-23-801
| Sheets |
| E.000 - SYMBOLS AND ABBREVIATIONS |
| EP.101 - ELECTRICAL POWER PLAN |
| EP.601 - ELECTRICAL ONE-LINE DIAGRAM - EXISTING CONDITIONS |
| EP.602 - ELECTRICAL ONE-LINE DIAGRAM - DEMO |
| EP.603 - ELECTRICAL ONE-LINE DIAGRAM - NEW |
File details come from the government source that posted it. Updated .