ATTACHMENT 2 - 100 Drawings.pdf
PDF 10 MB Posted
- Solicitation number
- 36C24826Q0104
About this file
These documents are bid documents for the Lake Baldwin VA Clinic Electrical Distribution Improvement project located in Orlando, Florida for the U.S. Department of Veterans Affairs. The project involves addressing specific electrical deficiencies at the Lake Baldwin and Lakemont VA campuses through a comprehensive electrical infrastructure upgrade. Key scope of work includes repairing, relocating, replacing, and correcting various electrical equipment, with work encompassing architectural, civil, structural, and electrical modifications across multiple campus buildings.
The project requires replacing and upgrading multiple electrical systems, including medium voltage switches, transformers, automatic transfer switches, underground conduits, and power distribution equipment. Specific tasks include intercepting and rerouting existing electrical feeders, demolishing and replacing electrical infrastructure, extending electrical equipment pads and canopies, and ensuring seamless integration with existing electrical systems. The project involves work at two VA medical campuses, with careful coordination required to minimize service interruptions and maintain critical facility operations. The bid documents are dated March 1, 2024, with detailed engineering specifications, site plans, one-line diagrams, and technical details provided across multiple drawing sheets.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
B513
B505 B506 B507 B508
B504
B500
B503
B509
B501 B518
B3130
B3136
B517
B3133
B3134
B3135
B3132
B510
B521B520
B522
B519
B519A
B520A
B3126 B3125
B3128
B3129
B502
NASH STREET
NASH STREET
Retention
Pond
POND #1
VAULT
SW10-4
POND #2
RAYMOND STREET
S P
A C
E S
M E
R C
Y A
V E
N U
E
C O
M F
O R
T A
V E
N U
E
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Architecture, Engineering, and, Sustainable DesignAESUS 1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 454-2861 design group
/2
/2
:2
:3
A
M
GI.001
COVER SHEET
5201 Raymond St, Orlando, FL 32803
675-23-801
Mar. 1, 2024 AESUS AESUS
IMPROVE LAKE BALDWIN
ELECTRICAL DISTRIBUTION
BID DOCUMENTS
DX
A3-301
X
XX
X
DETAIL FLAG NUMBER
DOOR NUMBER
AE-501
BUILDING SECTION CUT
OTHER SECTION CUT
SHEET WHERE APPEARS (TYPICAL)
AE-301
AA
SHEET WHERE APPEARS
ELEVATION NUMBER
SHEET WHERE APPEARS
x x x x
EXISTING COLUMN CENTER LINEA
X
WINDOW TAG
AE-301
AA
AE-301
AA
ELEVATION NUMBER
AE-710
4 2
DASHED LINE
AROUND
AREA DETAILED
PLAN OR DETAIL NUMBERX
Approved: Associate Director
Approved: Chief Facilities Management
Approved: Manager / Engineer
Approved: Director
Approved: Union representative
Approved: Safety Officer
EQ-X
CPT1
W-X
E
EA EACH
E EAST
EWC ELECTRIC WATER COOLER
ELEC ELECTRIC (AL)
EL ELEVATION
ELEV ELEVATOR
EMER EMERGENCY
ENGR ENGINEER
EQ EQUAL
EQUIP EQUIPMENT
EXIST EXISTING
ETR EXISTING TO REMAIN
EXP EXPANSION
EXP BT EXPANSION BOLT
EJ EXPANSION JOINT
EXP EXPOSED
EXT EXTERIOR
EIFS EXTERIOR INSULATION AND
FINISH SYSTEM
F
FWC FABRIC WALL COVERING
FT FEET, FOOT
FGL FIBERGLASS
FIN FINISH
FIN GR FINISH GRADE
FDV FIRE DEPARTMENT VALVE
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER
CABINET
FHC FIRE HOSE CABINET
FP FIREPROOF
FIXT FIXTURE
FLASH FLASHING
FLEX FLEXIBLE
FLR FLOOR
FD FLOOR DRAIN
FLUOR FLUORESCENT
FTG FOOTING
FDTN FOUNDATION
FRMG FRAMING
FURN FURNACE, FURNITURE
G
GA GAGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GL GLASS
GL BLK GLASS BLOCK
GB GRAB BAR
GR GRADE
GRAN GRANITE
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GUT GUTTER
GYP BD GYPSUM BOARD
H
HNDRL HANDRAIL
HDW HARDWARE
HDWD HARDWOOD
HD HEAD
HVAC HEATING, VENTILATING, AIR CONDITIONING
HT HEIGHT
HPT HIGH POINT
HC HOLLOW CORE
HM HOLLOW METAL
HORIZ HORIZONTAL
HB HOSE BIBB
HOSP HOSPITAL
HR HOUR
I
IN INCH
INFO INFORMATION
ID INSIDE DIAMETER
INSUL INSULATED,INSULATION
INT INTERIOR
J
JAN JANITOR
JT JOINT
K
KPL KICKPLATE
KIT KITCHEN
KB KNEE BRACE
L
LAB LABORATORY
LAM LAMINATE
LC LAUNDRY CHUTE
LV LAVATORY
LT LIGHT
LD LINEAR DIFFUSER
L CL LINEN CLOSET
LL LIVE LOAD
LLV LONG LEG VERTICAL
LPT LOW POINT
M
MACH MACHINE
MH MANHOLE
MFD MANUFACTURED
MFR MANUFACTURER
MRB MARBLE BASE
MRF MARBLE FLOOR
MKR BD MARKER BOARD
MO MASONRY OPENING
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MED MEDICAL
MC MEDICINE CABINET
MEMB MEMBRANE
MTL METAL
MIN MINIMUM, MINUTE
MISC MISCELLANEOUS
MOD MODIFIED
MLDG MOLDING
N
NAT FIN NATURAL FINISH
NOM NOMINAL
N NORTH
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NTS NOT TO SCALE
NO NUMBER
O
OFF OFFICE
OC ON CENTER
OPNG OPENING
OPP OPPOSITE
OPH OPPOSITE HAND
ORCH ORCHESTRA
ORN ORNAMENTAL
OD OUTSIDE DIAMETER
OH OVERHANG, OVERHEAD
OF/CI OWNER FURNISHED/
CONTRACTOR INSTALLED
O OXYGEN
P
P PAINT
PR PAIR
PNL PANEL
PTD PAPER TOWEL DISPENSER
PTN PARTITION
PERF PERFORATED
PC PIECE
PLAM PLASTIC LAMINATE
PLAS PLASTIC, PLASTER
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PCC PRECAST CONCRETE
PREFAB PREFABRICATE
PREFIN PREFINISH
PROD PRODUCTION
Q
QTY QUANTITY
QT QUARRY TILE
A
AFF ABOVE FINISHED FLOOR
ACST ACOUSTIC (AL)
ACT ACOUSTICAL CEILING TILE
APC ACOUSTICAL PANEL CEILING
AWP ACOUSTICAL WALL PANEL
AWT ACOUSTICAL WALL
ADJ ADJUSTABLE
A/C AIR CONDITIONING
AHU AIR HANDLING UNIT
ALT ALTERNATE
ALUM ALUMINUM
AB ANCHOR BOLT
AL ANGLE
APPROX APPROXIMATE
ARCH ARCHITECT (URAL)
ASPH ASPHALT
ASSY ASSEMBLY
AUTO AUTOMATIC
AWN AWNING
B
BALC BALCONY
BSMT BASEMENT
BM BEAM, BENCHMARK
BR BEDROOM
BLKG BLOCKING
BD BOARD
BOT BOTTOM
BRKT BRACKET
BRK BRICK
B CL BROOM CLOSET
BLDG BUILDING
BLT IN BUILT-IN
BUR BUILT-UP ROOFING
C
CAB CABINET
CPT CARPET
CSMT CASEMENT
CI CAST IRON
CB CATCH BASIN
CLG CEILING
CEM CEMENT
CL CENTER LINE
CER CERAMIC
CT CERAMIC TILE
CO CLEANOUT, CASED OPENING
CLR CLEAR, COLOR
CLO CLOSET
COL COLUMN
CMPST COMPOSITE
CONC CONCRETE
CMU CONCRETE MASONRY UNIT
CONSTR CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
COTR CONTRACTING OFFICER
CJ CONTROL JOINT
COP COPING
CU COPPER
CG CORNER GUARD
CORR CORRIDOR
CNTR COUNTER
CSK COUNTER SUNK
D
DMPF DAMPPROOFING
DL DEAD LOAD
DEMO DEMOLITION
DET DETAIL
DIA DIAMETER
DIFF DIFFUSER
DIM DIMENSION
DR DOOR, DRAIN
DH DOUBLE HUNG
DN DOWN
DS DOWNSPOUT
DWR DRAWER
DWG DRAWING
DF DRINKING FOUNTAIN
DUPL DUPLICATE
R
R RADIUS, RISER
RWD REDWOOD
REF REFERENCE, REFRIGERATOR
REINF REINFORCE
REQD REQUIRED
RB RESILIENT BASE
RF RESILIENT FLOORING
RA RETURN AIR
REV REVISION
RD ROOF DRAIN
RM ROOM
RO ROUGH OPENING
RS ROUGH SAWN
S
SCHED SCHEDULE
SECT SECTION
SHTHG SHEATHING
SHT SHEET
SHV SHELVING
SIM SIMILAR
S SOUTH
SP FIN SPECIAL FINISH
SPEC SPECIFICATION
SQ SQUARE
SF SQUARE FEET
SST STAINLESS STEEL
STD STANDARD
STL STEEL
STL JST STEEL JOIST
STOR STORAGE
STRUCT STRUCTURAL
S4S SURFACED FOUR SIDES
SUSP SUSPEND
SW SWITCH
SYMM SYMMETRICAL
T
TK BD TACKBOARD
TEL TELEPHONE
TV TELEVISION
TMPD TEMPERED
TEMP TEMPORARY
TER TERRAZZO
THK THICKNESS
TPD TOILET PAPER DISPENSER
T&G TONGUE AND GROOVE
TOS TOP OF SLAB, STEEL
T TREAD
TYP TYPICAL
U
UC UNDERCUT
UNFIN UNFINISH
UNO UNLESS NOTED OTHERWISE
V
VAC VACUUM
VR VAPOR RETARDER
VNR VENEER
VP VENEER PLASTER
VIF VERIFY IN FIELD
VERT VERTICAL
VEST VESTIBULE
VCT VINYL COMPOSITION TILE
VWC VINYL WALL COVERING
W
W CAB WALL CABINETS
WC WALL COVERING, WATER CLOSET
WP WATERPROOFING, WEATHER
PROOF, WORKING POINT
WT WEIGHT
WWF WELDED WIRE FABRIC
W WEST
WF WIDE FLANGE
WDW WINDOW
W/ WITH
W/O WITHOUT
WD WOOD
WDP WOOD PANELING
5201 Raymond St
Department of Veterans Affairs
KEYED NOTE
WALL TYPE
X
X WINDOW TREATMENT TYPE
EQUIPMENT
INTERIOR FINISH TYPE
FURNITURE, FIXTURE, EQUIPMENT
CONTRACT LIMIT LINE
COLUMN CENTER LINE
NEW WALL
DEMOLITION
EXISTING WALL
NORTH
APPROVED FOR CONSTRUCTION
Project No: 675-2 -801
Orlando, FL 32803
DESIGN TEAM
ABBREVIATIONS OWNER
CODE REFERENCES
PROJECT DESCRIPTION
FACILITY MAP
SYMBOL LEGEND
BUILDING INFORMATION
GENERAL NOTES
VICINITY MAP
THIS PROJECT IS LOCATED IN ORLANDO FLORIDA AT THE LAKE BALDWIN VA MEDICAL
CENTER AND THE LAKEMONT VA MEDICAL CENTER. THE PROJECT'S SCOPE OF WORK
ENTAILS ADDRESSING SPECIFIC ELECTRICAL DEFICIENCIES AT THE LAKE BALDWIN
AND LAKEMONT VA CAMPUSES LOCATED IN ORLANDO, FL. THE OBJECTIVE OF THE
PROJECT IS TO RECTIFY THESE DEFICIENCIES BY UNDERTAKING A SERIES OF ACTIVITIES
SUCH AS REPAIRING, RELOCATING, REPLACING, AND CORRECTING VARIOUS ELECTRICAL
EQUIPMENT.
THIS WORK SHALL INCLUDE BUT NOT BE LIMITED TO ARCHITECTURAL, CIVIL,
STRUCTURAL, & ELECTRICAL.
DESCRIPTIONSYMBOL
IMPROVE LAKE BALDWIN ELECTRICAL DISTRIBUTION,
Lake Baldwin - Orlando VA Medical Center Department of Veterans Affairs
Architect
MPE Engineers
1050 E. Southern Ave. Suite 5, Tempe, Arizona 85282
AESUS Design Group
David Combs (dcombs@aesusdesign.com)
480-454-2861
NORTH
PROJECT AREA
Lake Baldwin - Orlando VA Medical Center
A. ANY CHANGES MUST BE APPROVED BY COR BEFORE DOING ANY
ADDITIONAL WORK. WORK SCHEDULE TO BE PERFORMED DURING
REGULAR DAY SHIFT HOURS (8AM-4:30PM) ANY WORK OUTSIDE OF
REGULAR SCHEDULE REQUIRES APPROVAL FROM COR.
B. COORDINATE STAGING AREA WITH COR, AND FIND INTERIOR
COVERED STORAGE ON SITE FOR MATERIALS THAT MUST BE
PROTECTED FROM ELEMENTS - COORDINATE WITH COR.
C. PERFORM WORK IN ACCORDANCE WITH VHA DIRECTIVE 2004-012
SAFETY AND HEALTH DURING CONSTRUCTION ACTIVITIES AND VHA
DIRECTIVE 7701 OCCUPATIONAL SAFETY AND HEALTH (OSH) .
D. WORK PERFORMED FOR THIS PROJECT MAY INTERRUPT SERVICE TO
ADJACENT AREAS AT TIMES BUT WILL NOT INTERRUPT OVERALL
FACILITY OPERATION. SEE ELECTRICAL FOR POWER INTERRUPTION
AND OUTAGE REQUIREMENTS.
E. CONTRACTOR TO VERIFY ALL DETAILS AGAINST EXISTING
CONDITIONS PRIOR TO PURCHASE OF EQUIPMENT AND PRIOR TO
CONSTRUCTION. CONTRACTOR IS RESPONSIBLE FOR BRINGING ANY
DISCREPANCIES IN PLANS AND EXISTING SITE CONDITIONS TO
IMMEDIATE ATTENTION OF CONTRACTING OFFICER
REPRESENTATIVE.
F. CONTRACTOR SHALL PERFORM ALL WORK AND PROVIDE ALL
MATERIALS IN ACCORDANCE WITH VA MASTER CONSTRUCTION
SPECIFICATIONS, WHICH CAN BE FOUND AT
HTTP://WWW.CFM.VA.GOV/TIL/. WHERE DISCREPANCIES ARE FOUND
THE MORE STRINGENT SHALL APPLY.
G. NOT ALL KEYNOTES ARE ON ALL SHEETS.
BUILDING CODE:
2020 FBC - INTERNATIONAL BUILDING CODE
2020 FBC - EXISTING BUILDING CODE
2020 FBC - INTERNATIONAL ENERGY CONSERVATION CODE
2020 FFPC - NFPA
ACCESSIBILITY CODE & GUIDELINES:
ABAAS & BFDG
MECHANICAL CODE:
2020 FBC - INTERNATIONAL MECHANICAL CODE
PLUMBING CODE:
2020 FBC - INTERNATIONAL PLUMBING CODE
ELECTRICAL CODE:
2020 FBC - INTERNATIONAL ELECTRICAL CODE
NO LIFE SAFETY WILL BE AFFECTED BY THIS PROJECT.
NFPA
NFPA 101 LIFE SAFETY CODE
NFPA NATIONAL FIRE CODES
NFPA 900 (OSHA)
ISSUED SHEETS
Sheet Number Sheet Name
GENERAL
GI.001 COVER SHEET
ARCHITECTURE
AS100 SITE PLAN
AE103 ENLARGED PLANS
STRUCTURAL
S101 FOUNDATION PLANS, GSN, AND DETAILS.
CIVIL
C002 GENERAL NOTES
C003 OVERALL SHEET MAP
C101 SITE, UTILITY AND GRADING PLAN AREA 1
C102 SITE, UTILITY AND GRADING PLAN AREA 2
C300 DETAILS
ELECTRICAL
E-001 SYMBOLS AND ABBREVIATIONS
ED-101 ELECTRICAL SITE PLAN DEMO - LAKE BALDWIN
ED-102 ELECTRICAL SITE PLAN DEMO - LAKEMONT
EP-101 ELECTRICAL SITE PLAN - LAKE BALDWIN
EP-103 ELECTRICAL SITE PLAN - LAKEMONT
EP-401 ELECTRICAL DETAILS
EP-402 GROUNDING DETAILS
EP-403 TYPICAL LABELING DETAILS
EP-601 ELECTRICAL ONE-LINE DIAGRAM DEMO - LAKE BALDWIN
EP-602 ELECTRICAL ONE-LINE DIAGRAM - LAKE BALDWIN
EP-603 ELECTRICAL ONE-LINE DIAGRAM - LAKEMONT
1050 E. Southern Ave. Suite 5, Tempe, Arizona 85282
AESUS Design Group
David Combs (dcombs@aesusdesign.com)
480-454-2861
Structural Engineers
730 N. 52nd St, #105
Phoenix, Arizona 85008
Simply Structural
Civil Engineers
4001 N. 3rd St, #165
Phoenix, Arizona 85012
SWS Engineering
Revisions: Date:
STAMPSTAMP
03.06.2024
675-2 -80103
ID
E N T
IF
Y
104.10
101.96102.10 102.64 103.09104.29104.33104.23104.31102.96
102.07
104.11104.27
104.04 C
LF
M E
TA
L
S T A
IR
S
M E
TA
L
S T A
IR
S
CC
N89°35'32"W 1326.77'
PLAT
N89°59'50"W 70.57'
PLAT S
°0 '5 "E
.4
P
LA
T
PICK
PT
PICK
PT
PICK
PT
PICK
PT
PICK
PT
PICK
PT
PICK
PT
PICK
PT
PICK
PT
PICK
PT
PICK
PT
PICK
PT
PICK
PT
PICK
PT
PICK
PT 1
NW CORNER, S. 1/2
N. 1/2, NW 1/4, NE 1/4
SECTION 16-22-30
SE CORNER, LOT 1, BLOCK "C"
PB "W", PG 71
BRICK
BRICK
D
IR
T
R O A D
DI
RT RO
AD
DIRT
ROAD
D
IR
T
D
IR
T
D
IR
T
D
IR
T
D
IR
T
CONC
CONC
S A T E L L
IT
E
A N
TE
N N A
M E T A L
L
ID
T
7 8
S
IG
N
STOP BAR
(TYP)
S
TO
P
B A R
(T Y P
S
TO
P
B A R
(T Y P
S
IG
N
STOP BAR
(TYP)
S
IG
N
MOTORCYCLE 1
11101011
MOTORCYCLE
1 1 1 1
SIGN
S
TO
P
B A R
(T Y P
SI
GN
8 8
S
IG
N
S
IG
N
B O
LL
A R D
(T Y P
B O
LL
A R D
(T Y P
F L A G
P O
LE
S
TO
P
B A R
(T Y P
B O
LL
A R D
(T Y P
B O L
LA
R D
(T Y P
B O L
LA
R D
(T Y P
B O L
LA
R D
(T Y P
M O T O R
C Y C
LE
C O N C
D W
ALIMINUM
STEPS
A L
IM
IN
U M
R A M P
C O N C
C O N C
C W
CP
C O N C
C O N C
A P R O N
C O N C
A P R O N
C O N C
A P R O N
C O N C
A P R O N
C O N C
A P R O N
C O N C
R
IP
R A P
C O N C
F
LU
M E
C O N C
F
LU
M E
C O N C
F
LU
M E
C O N C
F
LU
M E
C P
CONC
APRON
CONC
APRON
C O N C
A P R O N
F O U N
TA
IN
C O V D
C W6
C W
8'
CW
C W
C C
5' C W
M E T A L
L
ID
C O N C
C U R B
(T Y P
C C
CONC
CW
C O N C
S T E P S
R A M P
2.5'
1.4'
32.1'
.1
.6
. 8
49.3'
CC
CONC
C C
C C
CONC
CLF
C
LF
C
LF
C
LF
C
LF
D
IE
S E L
F U E L
S T O R A G E
C
LF
C
LF
C
LF
C
LF
C
LF
C
LF
C
LF
C
LF
C
LF
C
LF
C
LF
M F
M F
C
LF
C
LF
C
LF
C
LF
C
LF
C
LF
M F
1'W
0.5'W
M F
M F
0.7'W
0.4'W
1.5'W
C
LF
0.7'W
C
LF
.6
1.3'W
C
LF
C
LF
C
LF
C
LF
S89°59'23"W 333.86'
MEAS
S87°40'34"E 206.41'
MEAS
S ° 5 ' 3 " W
.2
M E A S
S ° 5 ' 4
.0
M E A S
A S P H A
LT
A S P H A
LT
A S P H A
LT
A S P H A
LTA
S P H A
LT
A S P H A
LT
A S P H A
LT
ASPHALT
A S P H A
LT
A S P H A
LT
A S P H A
LT
A S P H A
LTA
S P H A
LT
A S P H A
LT
ASP
HA
LT
ASPHALT
A S P H A
LT
A S P H A
LT
ASPHALT
A S P H A
LT
A S P H A
LT
A S P H A
LT
A S P H A
LT
A S P H A
LT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
A S P H A
LT
A S P H A
LT
A S P H A
LT
A S P H A
LT
A S P H A
LT
ASPHALT
ASPHALT
ASP
HALT
A S P H A
LT
A S P H A
LT
A S P H A
LT
A S P H A
LT
A S P H A
LT
A S P H A
LT
A S P H A
LT
A S P H A
LT
F
LU
M E
A S P H A
LT
F
LU
M E
A S P H A
LT
ASPH
ALT
ASPH
ALT
ASPHALT
.3
.7
.3
.1
.8
.3
.3
. 5
.7
R
ID
LE
Y
A V E N U E
RAYMOND
STREET
RAYMOND
STREET
R A Y M O N D
S T R E E T
PALMETTOAVENUE
C O M F O R T
A V E N U E
NASH
STREET
NASH
STREET
M E R C Y
A V E N U E
LAKE BALDWIN
LANE
N °3 '1
"W
.9
C M
L3
N87°46'09"E 1659.45'
C&M
S87°40'44"E 206.44'
CALC
S89°59'50"W 333.97'
PLAT
C1
L1
C3S89°59'50"W 692.12' C&M
C2
S89°59'50"W 692.12' C&M
L2
N87°46'09"E 1659.45'
C&M
S ° 5 ' 3
.2
C M
S ° 5 ' 3
.9
C A L C
F O
C
P S
P S
P S
P S
PS
PS
PS
P S
PS
PS
PS
P
S PS
PSPS
PS
PS PS
PS
P S
P S
PS
PS
PS
PS
PS
P S
P S
PS
P S
P S
P S
PS
P S
P S
PS
P S
P S
P S
P S
P S
P S
P S
P S
P S
PS
PSPS
P S
P S
P S
P S
PS
PS
P S
PS
PS
PS
PS
PS
PS
PS
PS
PS
PSPSPSPS
PS
PSPS
PS
PS
PS
PS
PS
PS PS PS PS
PS
PS
PS
P S
P S
P S
P S
P S
P S
P S
PS
PSPS
P S
P S
T V
PS
PS
PS
P S
P S
P S
P S
P S
P S
PS
PS
PS
PS
P S
P S
P S
P S
SD
SD
EL
SD SD
SD
P S
PS
BUILDING 500
BUILDING 504
BUILDING 502
B U
IL
D
IN
G
BUILDING 501
B U
IL
D
IN
G
BUILDING 505 BUILDING 506 BUILDING 507 BUILDING 508
BUILDING 519, 522, 521,524
BUILDING 510
B U
IL
D
IN
G
B U
IL
D
IN
G
BUILDING 3133
BUILDING 3130
B U
IL
D
IN
G
SCOPE
OF WORK
/AE103 1
/AE103 2
/AE103 6
SITE PLAN GENERAL NOTES
1. CONTRACTOR IS RESPONSIBLE FOR PROTECTING EXISTING UTILITIES
THAT ARE NOT MARKED FOR REMOVAL.
2. CONTRACTOR SHALL PHASE ROAD REMOVAL AND CONSTRUCTION SO AS
TO ALWAYS ALLOW AT LEAST ONE LANE OF TRAFFIC ON MAIN ACCESS
DRIVE. CONTRACTOR MAY CLOSE DRIVE TO ER/TRAUMA
ENTRANCE, BUT MUST COORDINATE WITH VA COR. TRAFFIC CLOSURE
SHALL MEET MUTCD REQUIREMENTS AND SHALL HAVE LIGHTED
BARRICADES FOR PROJECT.
3. CONTRACTOR SHALL INSTALL TEMPORARY 6' TALL CHAIN LINK SECURITY
FENCING TO SECURE CONSTRUCTION SITE. CONTRACTOR SHALL INSTALL
GATES TO ALLOW WORKING ACCESS FOR EQUIPMENT
AND PEOPLE.
4. CONTRACTOR SHALL BLOCK OFF SIDEWALK WITH ORANGE SNOW FENCE
AND INSTALL TEMPORARY SIGNAGE INDICATING THAT THE SIDEWALK IS
CLOSED.
5. CONTRACTOR SHALL PROVIDE TEMPORARY GRAVEL FILL, AS NEEDED, TO
ALLOW FOR VEHICULAR TRAFFIC TO USE ROADWAY WHILE NOT ACTIVELY
WORKING IN THE TRENCH. CONTRACTOR WILL BE RESPONSIBLE FOR
ENSURING THE TEMPORARY GRAVEL FILL IS AT GRADE AND WILL RESPOND
IMMEDIATELEY IF TEMPORARY GRAVEL FILL AREA SETTLES, CREATING A
HAZARD.
6. CONTRACTOR SHALL SUPPLY TRAFFIC CONTROL IN COMPLIANCE WITH
ALL MUTCD REGULATIONS. TRAFFIC CONTROL SHALL CONSIST OF AT LEAST
TYPE II BARRICADES WITH LIGHTS ON RESTRICTED
LANES OF TRAFFIC AND AT THE EDGE OF PAVEMENT WITH TEMPORARY
ACCESS OVER THE ROCKED IN LANE. TRAFFIC CONES MAY BE NEEDED ON
A TEMPORARY BASIS TO REDIRECT.
A. ANY CHANGES MUST BE APPROVED BY COR BEFORE DOING ANY
ADDITIONAL WORK. WORK SCHEDULE TO BE PERFORMED DURING
REGULAR DAY SHIFT HOURS (8AM-4:30PM) ANY WORK OUTSIDE OF
REGULAR SCHEDULE REQUIRES APPROVAL FROM COR.
B. COORDINATE STAGING AREA WITH COR, AND FIND INTERIOR
COVERED STORAGE ON SITE FOR MATERIALS THAT MUST BE
PROTECTED FROM ELEMENTS - COORDINATE WITH COR.
C. PERFORM WORK IN ACCORDANCE WITH VHA DIRECTIVE 2004-012
SAFETY AND HEALTH DURING CONSTRUCTION ACTIVITIES AND VHA
DIRECTIVE 7701 OCCUPATIONAL SAFETY AND HEALTH (OSH) .
D. WORK PERFORMED FOR THIS PROJECT MAY INTERRUPT SERVICE
TO ADJACENT AREAS AT TIMES BUT WILL NOT INTERRUPT OVERALL
FACILITY OPERATION. SEE ELECTRICAL FOR POWER INTERRUPTION
AND OUTAGE REQUIREMENTS.
E. CONTRACTOR TO VERIFY ALL DETAILS AGAINST EXISTING
CONDITIONS PRIOR TO PURCHASE OF EQUIPMENT AND PRIOR TO
CONSTRUCTION. CONTRACTOR IS RESPONSIBLE FOR BRINGING
ANY DISCREPANCIES IN PLANS AND EXISTING SITE CONDITIONS TO
IMMEDIATE ATTENTION OF CONTRACTING OFFICER
REPRESENTATIVE.
F. CONTRACTOR SHALL PERFORM ALL WORK AND PROVIDE ALL
MATERIALS IN ACCORDANCE WITH VA MASTER CONSTRUCTION
SPECIFICATIONS, WHICH CAN BE FOUND AT
HTTP://WWW.CFM.VA.GOV/TIL/. WHERE DISCREPANCIES ARE FOUND
THE MORE STRINGENT SHALL APPLY.
GENERAL NOTES
A. THE CONTRACTORS SHALL COORDINATE EQUIPMENT AND
MATERIAL TRAFFIC AND STORAGE WITH COR.
B. ALL UTILITY WORK SHALL BE COORDINATED WITH CIVIL PLANS.
C. ALL ASPECTS OF CONTRACTOR STAGING AND CONSTRUCTION
PHASING SHALL BE APPROVED BY COR.
D. ALL HOSPITAL ACCESS POINTS, AND ALL BUILDING EXITS, MUST
REMAIN ACCESSIBLE, CLEAR AND UNOBSTRUCTED THROUGHOUT
ALL PHASES OF DEMOLITION AND CONSTRUCTION. SHORT-TERM
CLOSURE MAY BE ACCEPTABLE AS COORDINATED WITH COR.
E. THE CONTRACTOR SHALL COORDINATE ALL ROOF TOP WORK AND
ROOF REPAIRS WITH THE COR.
GENERAL PHASING NOTES
FLOOR PLAN LEGEND
SCOPE OF WORK
SCOPE OF WORK ITEMS
A. PROVIDE AN EXTENSION TO THE ELECTRICAL EQUIPMENT PAD AND NEW
CANOPY FOR ELECTRICAL EQUIPMENT ON THE LAKE BALDWIN CAMPUS.
B. PROVIDE AN EXTENSION FOR THE ELECTRICAL EQUIPMENT PAD AND
EXTENSION FOR THE EXISTING CANOPY ON THE LAKEMONT CAMPUS. SEE
2/AE103
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Architecture, Engineering, and, Sustainable DesignAESUS 1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 454-2861 design group
/2
/2
:2
:3
A
M
AS100
SITE PLAN
5201 Raymond St, Orlando, FL 32803
675-23-801
Mar. 1, 2024 AESUS AESUS
IMPROVE LAKE BALDWIN
ELECTRICAL DISTRIBUTION
BID DOCUMENTS
1/64" = 1'-0"
SITE PLAN - LAKE BALDWIN
Revisions: Date:
STAMPSTAMP
03.06.2024
Level 1 0' - 0"
CORRUGATED METAL
DECK, PAINTED TO
MATCH EXISTING
COLUMN
BEAM
RAINWATER
WATER
W A
T E
R
BUILDING
FACE
AE103
B .O
C
A N
O P
Y T
O A
L
IG
N W
IT
H
B
U
IL
D
IN
G M
A T
E R
IA
L T
R A
N S
IT
IO
N
GASKETED FASTENERS
AT 12" OC
SHEET METAL TWO
PIECE REGLET AND
COUNTERFLASHING
SYSTEM
FASTENERS WITH
ANCHOR DISCS AT 6" OC
MAX OR CONT
TERMINATION BAR
WIND CLIPS AT 30" OC
SEALANT - TOOL TO
FACILITATE WATER RUN-
OFF
CONT COMPRESSIBLE
ELASTOMERIC TAPE
GASKETED FASTENERS AT
12" OC
CORRUGATED METAL CANOPY
1' - 0" 2' - 0"
5' - 8"
2' - 0" 2' - 0" 5' - 8" 1' - 0"
11' - 11"
EXISTING CONCRETE
EQUIPMENT PAD TO REMAIN
EXISTING BUILDING 504
NEW ELECTRICAL EQUIPMENT,
SEE ELECTRICAL.
NEW CONCRETE EQUIPMENT PAD
CANOPY COLUMN
AE103
Sim
19' - 4"
NEW
CONCRETE
PAD, SEE
STRUCTURAL.
EXISTING CANOPY TO REMAIN
EXISTING CONCRETE
PAD TO REMAIN
EXISTING ELECTRICAL
EQUIPMENT TO REMAIN
NEW ELECTRICAL
EQUIPMENT, SEE
ELECTRICAL.
THE GC TO PROVIDE A
2'-6" HORIZONTAL
CANOPY EXTENTION AND
SUPPORTS. THE CANOPY
EXTENTION SHALL BE
PART OF EXISTING
FRAME WITH NO
ADDITIONAL COLUMNS.
2' - 6"
ATS
NOTE:
THIS EQUIPMENT IS LOCATED 13800 VETERAN'S WAY, ORLANDO,
FL, 32827.
THE GC TO PROVIDE A 2'-0"
VERTICAL RAIN GUARD
BELOW THE CANOPY ON
THREE SIDES AS INDICATED
BY THE DASHED LINE. SEE
SECTION 5.
AE103
NOTE:
THE GC SHALL COORDINATE WITH THE CANOPY
MANUFACTURE (PEACHTREE PROTECTIVE COVERS)
FOR CANOPY EXTENTION AND VERTICAL RAIN
GUARD. PROVIDE SHOP DRAWINGS AND
CALCULATIONS FOR ALL SUPPORTING STRUCTURE.
8' - 0"
NEW CONCRETE PAD,
COORDINATE WITH
ELECTRICAL FOR
EXACT LOCATION.
EXISTING CONCRETE
PAD
EXISTING ELECTRICAL
EQUIPMENT, TYPICAL.
EXISTING MANHOLE
1' - 0"
EXISTING
CONCRETE
PAD
NEW CONCRETE PAD,
COORDINATE EXACT
LOCATION WITH
ELECTRICAL
5' - 1"
EXISTING
ELECTRICAL
EQUIPMENT
THE GC TO PROVIDE
A 2'-0" VERTICAL RAIN
GUARD BELOW THE
CANOPY ON THREE
SIDES AS INDICATED
BY THE DASHED LINE.
SEE SECTION 5.
2' - 6"
2' - 6"
EXISTING COLUMNS
NEW SLAB AND
FOOTING, SEE
STRUCTURAL.
EXISTING SLAB
THE GC TO PROVIDE A 2'-6"
HORIZONTAL CANOPY
EXTENTION AND SUPPORTS.
THE CANOPY EXTENTION
SHALL BE PART OF THE
EXISTING FRAME WITH NO
ADDITIONAL COLUMNS.
EXISTING ROOF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Architecture, Engineering, and, Sustainable DesignAESUS 1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 454-2861 design group
/2
/2
:4
:1
P
M
AE103
ENLARGED PLANS
5201 Raymond St, Orlando, FL 32803
675-23-801
Mar. 1, 2024 AESUS AESUS
IMPROVE LAKE BALDWIN
ELECTRICAL DISTRIBUTION
BID DOCUMENTS
3/8" = 1'-0"
TYPICAL CANOPY SECTION
3" = 1'-0"
CANOPY AT EXISTING BUILDING
3/16" = 1'-0"
ENLARGED EQUIPMENT PAD - LAKE
BALDWIN 1
3/16" = 1'-0"
EQUIPMENT PAD - LAKEMONT
3/16" = 1'-0"
ENLARGED EQUIPMENT PAD - LAKE
BALDWIN 2
3/16" = 1'-0"
ENLARGED EQUIPMENT PAD - LAKE
BALDWIN 3
Revisions: Date:
3/8" = 1'-0"
RAIN GUARD CANOPY SECTION
STAMPSTAMP
03.06.2024
02/29/24
02/29/24
675-23-801
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
LAKE BALDWIN VA
CLINIC
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMP
321 4 5 6 7 8 9 10
Revisions: Date:
NORTH
AESUS DESIGN GROUP
1050 E. Southern Ave., Suite D Temple, AZ, 85282 480-454-2861 David Combs
IMPROVE LAKE BALDWIN
ELECTRICAL DISTRIBUTION
MARCH 7, 2024 MS/MDS MG
5201 RAYMOND ST, ORLANDO, FL 32803
CIVIL/ENGINEER OF RECORD
C/E:
SWS ENGINEERING, INC.
2400 Maitland Center Pkwy. Suite 235, Maitland, FL, 32751 407-620-3300 Michael D. Schweitzer
Fi le
N am e
Lo ca tio n:
C :\U se rs
\m ik e.
sc hw ei tz er
.S W
SE
N
G
IN
EE
R
IN
G
\D C
\A C
C D oc s\
SW
S
En gi ne er in g\
-2
F\
Pr oj ec t F ile s\
PR
O
D \C on st ru ct
\G P\
-2
F
C
2.
dw g
L ay ou t:
C
Pr in te d:
T hu
, 0
M ar
- 7
:1
EB: 37087
90% Construction Drawing Submittal 10-10-2023
C002
GENERAL NOTES
SWS
n
P O B
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
LAKE BALDWIN VA
CLINIC
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMP
321 4 5 6 7 8 9 10
Revisions: Date:
NORTH
AESUS DESIGN GROUP
1050 E. Southern Ave., Suite D Temple, AZ, 85282 480-454-2861 David Combs
IMPROVE LAKE BALDWIN
ELECTRICAL DISTRIBUTION
MARCH 7, 2024 MS/MDS MG
5201 RAYMOND ST, ORLANDO, FL 32803
CIVIL/ENGINEER OF RECORD
C/E:
SWS ENGINEERING, INC.
2400 Maitland Center Pkwy. Suite 235, Maitland, FL, 32751 407-620-3300 Michael D. Schweitzer
Fi le
N am e
Lo ca tio n:
C :\U se rs
\m ik e.
sc hw ei tz er
.S W
SE
N
G
IN
EE
R
IN
G
\D C
\A C
C D oc s\
SW
S
En gi ne er in g\
-2
F\
Pr oj ec t F ile s\
PR
O
D \C on st ru ct
\G P\
-2
F
C
3.
ou t:
C te d:
T hu
, 0
M ar
- 7
:1
EB: 37087
90% Construction Drawing Submittal 10-10-2023
C003
OVERALL SHEET MAP 675-23-801
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
LAKE BALDWIN VA
CLINIC
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMP
321 4 5 6 7 8 9 10
Revisions: Date:
NORTH
AESUS DESIGN GROUP
1050 E. Southern Ave., Suite D Temple, AZ, 85282 480-454-2861 David Combs
IMPROVE LAKE BALDWIN
ELECTRICAL DISTRIBUTION
MARCH 7, 2024 MS/MDS MG
5201 RAYMOND ST, ORLANDO, FL 32803
CIVIL/ENGINEER OF RECORD
C/E:
SWS ENGINEERING, INC.
2400 Maitland Center Pkwy. Suite 235, Maitland, FL, 32751 407-620-3300 Michael D. Schweitzer
Fi le
N am e
Lo ca tio n:
C :\U se rs
\m ik e.
sc hw ei tz er
.S W
SE
N
G
IN
EE
R
IN
G
\D C
\A C
C D oc s\
SW
S
En gi ne er in g\
-2
F\
Pr oj ec t F ile s\
PR
O
D \C on st ru ct
\G P\
-2
F
C
1.
ou t:
C te d:
T hu
, 0
M ar
- 7
:2
EB: 37087
90% Construction Drawing Submittal 10-10-2023
C101
SITE, UTILITY AND GRADING PLAN
AREA 1
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
LAKE BALDWIN VA
CLINIC
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMP
321 4 5 6 7 8 9 10
Revisions: Date:
NORTH
AESUS DESIGN GROUP
1050 E. Southern Ave., Suite D Temple, AZ, 85282 480-454-2861 David Combs
IMPROVE LAKE BALDWIN
ELECTRICAL DISTRIBUTION
MARCH 7, 2024 MS/MDS MG
5201 RAYMOND ST, ORLANDO, FL 32803
CIVIL/ENGINEER OF RECORD
C/E:
SWS ENGINEERING, INC.
2400 Maitland Center Pkwy. Suite 235, Maitland, FL, 32751 407-620-3300 Michael D. Schweitzer
Fi le
N am e
Lo ca tio n:
C :\U se rs
\m ik e.
sc hw ei tz er
.S W
SE
N
G
IN
EE
R
IN
G
\D C
\A C
C D oc s\
SW
S
En gi ne er in g\
-2
F\
Pr oj ec t F ile s\
PR
O
D \C on st ru ct
\G P\
-2
F
C
1.
ou t:
C te d:
T hu
, 0
M ar
- 7
:2
EB: 37087
90% Construction Drawing Submittal 10-10-2023
C102
SITE, UTILITY AND GRADING PLAN
AREA 2
NOTE:
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
LAKE BALDWIN VA
CLINIC
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMP
321 4 5 6 7 8 9 10
Revisions: Date:
NORTH
AESUS DESIGN GROUP
1050 E. Southern Ave., Suite D Temple, AZ, 85282 480-454-2861 David Combs
IMPROVE LAKE BALDWIN
ELECTRICAL DISTRIBUTION
MARCH 7, 2024 MS/MDS MG
5201 RAYMOND ST, ORLANDO, FL 32803
CIVIL/ENGINEER OF RECORD
C/E:
SWS ENGINEERING, INC.
2400 Maitland Center Pkwy. Suite 235, Maitland, FL, 32751 407-620-3300 Michael D. Schweitzer
Fi le
N am e
Lo ca tio n:
C :\U se rs
\m ik e.
sc hw ei tz er
.S W
SE
N
G
IN
EE
R
IN
G
\D C
\A C
C D oc s\
SW
S
En gi ne er in g\
-2
F\
Pr oj ec t F ile s\
PR
O
D \C on st ru ct
\G P\
-2
F
C
0.
ou t:
C te d:
T hu
, 0
M ar
- 7
:2
EB: 37087
90% Construction Drawing Submittal 10-10-2023
C300
DETAILS 675-23-801
s
CR
(18"/18")
M
K1
K1
TYPICAL OUTLET SYMBOL NOTES
-STAR SYMBOL INDICATES DEVICE IS MOUNTED 4" ABOVE COUNTER,
CASEWORK, BACKSPLASH OR 46" IF NOTHING BELOW.
-INDICATES MOUNTING HEIGHT ABOVE FINISHED FLOOR.
-ISOLATED GROUND
-WEATHER PROOF
-EXPLOSION PROOF
"+84"
"IG"
"WP"
"XP"
20A, 125V, 2 POLE, 3 WIRE GROUNDING SIMPLEX RECEPTACLE
20A, 125V, 2 POLE, 3 WIRE GROUNDING DUPLEX RECEPTACLE
20A, 125V, 2 POLE, 3 WIRE GROUNDING DOUBLE DUPLEX RECEPTACLE
20A, 125V, 2 POLE 3 WIRE GROUNDING DUPLEX RECEPTACLE WITH (2) INTEGRAL
USB CHARGING PORTS
HALF SWITCHED RECEPTACLE - LOWER OUTLET SWITCHED VIA CONTROL ZONE
INDICATED OR NEAREST OCCUPANCY SENSOR. UPPER OUTLET IS UNSWITCHED -
ALWAYS HOT
20A, 125V, 2 POLE 3 WIRE GROUNDING DUPLEX RECEPTACLE CONNECTED TO
CRITICAL BRANCH
20A, 125V, 2 POLE, 3 WIRE GROUNDING GFCI DUPLEX RECEPTACLE
20A, 125V, 2 POLE, 3 WIRE GROUNDING GFCI RECEPTACLE WITH WHILE IN USE
WEATHERPROOF ENCLOSURE.
20A, 125V, 2 POLE 3 WIRE GROUNDING GFCI DUPLEX RECEPTACLE CONNECTED TO
CRITICAL BRANCH
SPECIAL OUTLET. REFER TO SCHEDULE FOR REQUIREMENTS.
CEILING MOUNTED RECEPTACLE, TYPE AS INDICATED ABOVE.
PEDESTAL MOUNTED DUPLEX OR DOUBLE DUPLEX CONVENIENCE RECEPTACLE.
FLOOR BOX - WITH DUPLEX OR DOUBLE DUPLEX RECEPTACLE
FLOOR BOX WITH POWER AND DATA FURNITURE FEED CONNECTIONS. FURNITURE
FEED CIRCUIT QUANTITY AS INDICATED ON PLANS.
ELECTRICAL POWER SWITCH
M - MOTOR RATED WITH INTEGRAL THERMAL OVERLOADS U.O.N.
SURFACE MOUNTED ENCLOSED DIVIDED RACEWAY FOR POWER AND DATA.
DUPLEX SPACING (20A, 125V, 2 POLE, 3 WIRE GROUNDING DUPLEX RECEPTACLE
U.O.N)
DATA OUTLET SPACING (PROVISINS FOR NOT LESS THAN 4 PORTS U.O.N)
POWER / TELECOM. POLE. PROVIDE JUNCTION BOX ABOVE CEILING FOR POWER
CONNECTION (CIRCUIT QUANTITY AS NOTED ON PLANS) FOR FOR TELECOM/DATA
CONNECTIONS (1 PER ASSOCATED WORKSTATION) CONNECT TO WIRING IN
POWER POLE.
EXTENSION CORD REEL.
UNISTRUT RACK
TYPICAL OUTLET SYMBOL CIRCUITING NOTES
NOTES:
1. OUTLETS LOCATED AT COUNTERS SHALL BE LOCATED 18" AFF IN KNEE SPACE IF
PROVIDED OR 4" ABOVE COUNTER OR BACK SPLASH AS APPLICABLE IF NO KNEE
SPACE IS PROVIDED UNLESS NOTED OTHERWISE.
POWER OUTLETS
IG
+30"
CIRCUIT NUMBER
ELEVATION AFF
TYPE2
D
D
M
XXX-XXX
FOOT ON DEVICE INDICATES WALL MOUNTED
MARK NUMBER FOR MECHANICAL EQUIPMENT
KEY NOTE REFERENCE SYMBOL.
XXX-XXX
GENERAL
CIRCUIT NUMBER(S)
PANEL NAME
1LN1-1,3,5
BRANCH CIRCUIT HOMERUN. PROVIDE #12 PHASE, #12
NEUTRAL AND #12 GROUND CONDUCTORS FOR EACH
INDICATED CIRCUIT UNLESS NOTED OTHERWISE. SEE
GENERAL NOTE #2 AND #3.
NO MULTI-WIRE BRANCH CIRCUITS PERMITTED. NO SHARED
NEUTRAL.
CONDUIT RUN CONCEALED IN CEILING OR WALL
CONDUIT RUN BELOW GRADE, UNDER OR CONCEALED IN
FLOOR SLAB, UNDER RAISED FLOOR
CONDUIT RISER UP
CONDUIT RISER DOWN
INDICATES CIRCUIT CONTINUATION
STUB INTO ACCESSIBLE CORRIDOR CEILING SPACE UNLESS
OTHERWISE NOTED
CAP END OF CONDUIT
CONDUIT SLEEVE
POWER CONDUIT FILL EXAMPLE
(2) 4"C, 4 #500, 1#1/0G
TOTAL QUANTITY OF IDENTICAL CONDUIT/WIRE RUNS AS SPECIFIED (AS APPLICABLE)
CONDUIT SIZE (SEE SPECIFICATIONS FOR ALLOWED TYPES)
QUANTITY OF PHASE AND NEUTRAL CONDUCTORS.
NEUTRAL CONDUCTOR MAY BE SPECIFIED SEPARATELY WITH 'N' SUFFIX
CONDUCTOR SIZE (AWG/KCMIL)
QUANTITY OF GROUND CONDUCTORS (ASSUME QTY 1 IF NOT INDICATED)
GROUND CONDUCTOR SIZE (AWG/KCMIL)
CIRCUIT DESIGNATIONS
LIGHTING
GENERAL LIGHTING FIXTURE NORMAL/EMERGENCY BRANCH CIRCUIT DESIGNATIONS
(TYPICAL FOR ALL LIGHTING FIXTURES)
LUMINAIRE CONNECTED TO NORMAL BRANCH
LIFE SAFTEY LUMINAIRE. REFER TO FIXTURE SCHEDULE. WHERE FURNISHED
WITH EMERGENCY SELF-DIAGNOSTIC BATTERY/ INVERTER BALLAST/DRIVER.
PROVIDE BATTERY SHALL BE CAPABLE OF 100% OUTPUT FOR 90 MINUTES.
WHERE NOT FURNISHED WITH INTEGRAL BATTERY BACKUP FIXTURE SHALL BE
FED FROM GENERATOR BACKED LIFE SAFTEY BRANCH CIRCUIT.
L3 a
GENERAL LIGHTING FIXTURE DESIGNATIONS (TYPICAL FOR ALL FIXTURES)
LUMINAIRE TYPE.
• DENOTED BY UPPER CASE ALPHANUMERIC DESIGNATION. REFER TO
LIGHTING FIXTURE SCHEDULE.
• “(R)” DENOTES EXISTING RELOCATED FIXTURE. REFER TO
DEMOLITION DRAWINGS FOR EXISTING TO BE RELOCATED FIXTURES
SWITCHING CONTROL ZONE (WHERE APPLICABLE)
• LOWER CASE ALPHANUMERIC SUBSCRIPT MATCHES DESIGNATION OF
CORRESPONDING SWITCHING CONTROL DEVICE (USED ONLY WHERE
NECESSARY FOR CLARIFICATION).
• 'NL' INDICATES NIGHT LIGHT. CONNECT TO HOT LEG (NON-SWITCHED)
CIRCUIT NUMBER
LIGHTING FIXTURE DESCRIPTIONS
RECESSED OR SURFACE MOUNTED LUMINAIRE
RECESSED OR SURFACE MOUNTED ROUND DOWNLIGHT LUMINAIRE
STRIP LIGHT, SURFACE MOUNTED (LENGTH AS SHOWN ON PLANS)
LINEAR LUMINAIRE, SURFACE OR RECESSED (SOLID) OR PENDANT (DASHED)
MOUNTED (LENGTH/TYPE AS SHOWN ON PLANS)
LINEAR LUMINAIRE, WALL MOUNTED (LENGTH AS SHOWN ON PLANS)
WALL SCONCE LUMINAIRE
SUSPENDED TRACK LIGHT, TRACK HEAD QUANTITY AS SHOWN ON PLANS
COVE LIGHT. PLACE IN ARCHITECTURAL COVE, COORDINATE EXACT
LOCATIONS WITH ARCHITECTURAL DRAWINGS.
DENOTES DIRECTION OF LIGHT DISTRIBUTION. PROVIDE DIRECTIONAL LIGHT
THROW (WALL WASH EFFECT) WHERE SHOWN.
EXIT SIGN CEILING OR WALL MOUNTED AS INDICATED
INDICATES DIRECTIONAL CHEVRON FOR EXIT SIGNS.
DENOTES LOCATION(S) OF ILLUMINATED EXIT FACE
EMERGENCY TWIN HEAD FLOOD LIGHTING 'BUG EYE' UNIT WITH INTEGRAL
BATTERY PACK
T
30A/3P
30A/3P/
20AF
30A/3P
12x3
CP
C
480/277V OR 480V PANEL 208/120V OR 120/240V PANEL
HEAVY DUTY DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
ENCLOSED CIRCUIT BREAKER
MANUAL MOTOR STARTER SWITCH WITH THERMAL OVERLOAD
PROTECTION.
CONTACTOR
VARIABLE FREQUENCY DRIVE
MOTOR - WITH DISCONNECT (WHERE SHOWN IN PLANS)
MOTOR DESIGNATION SHOWN IN BOX
CONTROL PANEL FURNISHED BY OTHERS, INSTALLED BY
DIVISION 26, UNLESS NOTED OTHERWISE
REDUCED VOLTAGE MOTOR STARTER
NUMBER REFERS TO NEMA STARTER SIZE
COMBINATION REDUCED VOLTAGE MOTOR STARTER/DISCONNECT
NUMBER REFERS TO NEMA STARTER SIZE
COMBINATION 2 SPEED MOTOR STARTER/DISCONNECT
MOTOR - WITH DISCONNECT (WHERE SHOWN IN PLANS)
MOTOR DESIGNATION SHOWN IN BOX
CONTROL PANEL FURNISHED BY OTHERS, PROVIDED AND INSTALLED
BY DIVISION 26, UNLESS NOTED OTHERWISE
PUSHBUTTON STATIONS. ONE, TWO, OR THREE AS INDICATED
EMERGENCY POWER OFF' BREAK GLASS STATION.
BUS DUCT, FEEDER OR PLUG-IN TYPE AS INDICATED
CABLE TRAY - WIDTH x HEIGHT AS INDICATED, OR KEY NOTED
UNDER FLOOR DUCT SYSTEM
JUNCTION BOX, ABOVE CEILING (NO FOOT) OR FLUSH WALL MOUNTED
(WITH FOOT)
T = JUNCTION BOX FOR VOICE/DATA
JUNCTION BOX WITH FLEXIBLE CONNECTION TO EQUIPMENT
INDICATED AND REQUIRED
LADDER STYLE CABLE TRAY, 4IN TALL FOR POWER, 2IN TALL FOR
DATA/SIGNAL U.O.N. WIDTH AS SHOWN ON DRAWINGS.
CONDUIT - SEE SPECIFICATIONS.
POWER DISTRIBUTION
30A/3P
30A/3P
30A/3P
TABS INDICATE FLUSH MOUNTED PANEL
INDICATES REQUIRED
CLEARANCE
VFD
JJJ
J
NOTE:
SYMBOLS SHOWN ARE FOR REFERENCE ONLY AND DO NOT CONSTITUTE A CHECK
LIST OF DEVICES REQUIRED BY THE CONTRACT
0.0"
18"
6'-0"
3'-10"
10'-0"
6'-8"
BATTERY LIGHTING UNITS AND REMOTE WALL MOUNTED LIGHT HEADS (OR
1'-0" BELOW FINISHED CEILING AT TOP OF UNIT)
WARNING AND SIGNALING FIXTURES/SIGNS (CENTERED 6IN. ABOVE
DOOR/WINDOW)
CLOCK RECEPTACLES
BOTTOM LENS FOR WALL MOUNTED FIRE ALARM STROBES SPEAKERS,
HORNS AND COMBINATION HORN/STROBES
TOP OF FLUSH AND SURFACE MOUNTED PANELBOARDS AND TELEPHONE
CABINETS. TOP OF HIGHEST DISCONNECT SWITCHES, MAGNETIC
STARTERS, CONTACTORS, ATS.
GENERATOR REMOTE ANNUNCIATOR
WALL MOUNTED LIGHTING SWITCHES, MANUAL MOTOR STARTERS, FIRE
ALARM PULL STATIONS, WALL MOUNTED TELEPHONES.
GARAGE RECEPTACLES
ELECTRICAL RECEPTACLES, VOICE/DATA OUTLETS, DATA OUTLETS, UNO
FINISHED FLOOR
7'-0"
5'-6"
24"
MOUNTING HEIGHT NOTES: MOUNTING HEIGHTS TO FINISHED FLOOR TO CENTER OF
OUTLETS, UNLESS OTHERWISE NOTED.
MOUNTING HEIGHT NOTES
GENERAL NOTES
1. ALL DEVICE MOUNTING HEIGHTS INDICATED ON THIS LEGEND ARE FROM FINISHED FLOOR
TO CENTER OF OUTLET BOX.
2. PROVIDE #10 WIRE (FOR PHASE, NEUTRAL AND GROUND) FOR ALL 20A 120V CIRCUITS
EXCEEDING 75 FEET AND FOR 20A 277V CIRCUITS THAT EXCEED 150 FEET. PROVIDE #8
WIRE (FOR PHASE, NEUTRAL AND GROUND) FOR ALL 20A 120V CIRCUITS EXCEEDING 150
FEET AND FOR ALL 20A 277V CIRCUITS EXCEEDING 250 FEET.
3. CONTRACTOR MAY COMBINE UP TO (3) 20A (SINGLE POLE) RECEPTACLE CIRCUITS WITHIN
A SINGLE CONDUIT. CONDUIT SHALL NOT BE LESS THAN 3/4". WIRING CONFIGURATIONS
SHALL BE AS FOLLOWS: (FOLLOW WIRE UPSIZING TO ACCOMMODATE VOLTAGE DROP DUE
TO LENGTH AS INDICATED IN NOTE #2.)
• FOR 3 CIRCUITS, 20A, HOMERUNS TO PANELS SHALL BE 3#12 PHASE CONDUCTORS, 3#
12 NEUTRAL CONDUCTORS AND 1#12 GROUND. (WHEN UPSIZING FOR VOLTAGE DROP
AS INDICATED IN NOTE #2 REQUIRES 3#8 PHASE CONDUCTORS, 3#8 NEUTRAL
CONDUCTORS AND 1#8 GROUND UTILIZE 1"C IN LIEU OF 3/4"C).
• FOR 2 CIRCUITS, 20A, HOMERUNS TO PANELS SHALL BE 2#12 PHASE CONDUCTORS, 2#
12 NEUTRAL CONDUCTORS, AND 1 #12 GROUND.
• 1 CIRCUIT, 20A, HOMERUNS TO PANEL SHALL BE 1#12 PHASE CONDUCTOR, 1#12
NEUTRAL CONDUCTOR AND 1#12 GROUND.
4. VERIFY LOCATION AND CONNECTION REQUIREMENTS FOR EQUIPMENT PROVIDED BY
OTHER TRADES PRIOR TO ROUGH-IN.
5. COORDINATE CEILING MOUNTED LIGHTS AND DEVICES WITH CEILING CONTRACTOR AND
INSTALL AS SHOWN ON THE REFLECTED CEILING/LIGHTING PLANS.
6. ALL FLOOR MOUNTED ELECTRICAL EQUIPMENT (SWITCHGEAR, SWITCHBOARDS, FREE
STANDING PANELBOARDS, DISTRIBUTION BOARDS, TRANSFORMERS, ETC.) SHALL BE
INSTALLED ON 4" HIGH CONCRETE PAD. CONCRETE PAD SHALL EXTEND PAST EDGE OF
EQUIPMENT 3" ON EACH SIDE U.N.O.
7. COORDINATE ALL DIMENSIONS, ELECTRICAL POINT OF CONNECTIONS, AND WIRING
REQUIREMENTS ON ALL PRE-PURCHASED EQUIPMENT WITH FINAL APPROVED SHOP
DRAWINGS.
8. FIRE SEAL ALL CONDUIT PENETRATIONS THROUGH FIRE RATED WALLS AND SLABS. FIRE
RATING SEAL SHALL BE EQUAL TO OR GREATER THAN THE FIRE RATING OF THE WALL OR
SLAB THROUGH WHICH THE CONDUIT PASSES.
9. COORDINATE THE LOCATION AND MOUNTING HEIGHTS OF OUTLETS AND MULTI-OUTLET
ASSEMBLIES WITH ARCHITECTURAL FLOOR PLANS AND ELEVATION DRAWINGS..
10. CONTRACTOR SHALL VERIFY ALL DOOR SWINGS BEFORE INSTALLING SWITCH/LIGHTING
CONTROL BOXES. DO NOT PLACE SWITCH OR LIGHTING CONTROL DEVICE BEHIND DOOR
SWING.
11. FOR MOUNTING HEIGHT OF UNDER-SHELF/CABINET LIGHTING FIXTURES REFER TO
ARCHITECTURAL DRAWINGS.
12. COORDINATE EXACT LOCATION OF SUSPENDED LIGHTING FIXTURES IN MECHANICAL AND
STORAGE AREAS WITH OTHER TRADES. DO NOT PLACE LIGHTING FIXTURE DIRECTION
ABOVE MECHANICAL EQUIPMENT OR DUCTS.
13. RACEWAYS, SLEEVES, AND BOXES FOR IT CABLING SHALL COMPLY WITH COMMERCIAL
BUILDING STANDARD FOR TELECOMMUNICATION PATHWAYS AND SPACES,
ANSI/TIA/EIA-569-A.
14. BOND FLAMMABLE LIQUID STORAGE CABINETS WITH #10 AWG WIRE TO THE NEAREST
STEEL COLUMN. INSTALL WIRE IN CONDUIT.
SITE EXTERIOR
SITE LIGHTING FIXTURE DESCRIPTIONS
POLE LUMINAIRE - ARM QUANTITY AS INDICATED ON PLANS
POLE MOUNTED POST TOP LUMINAIRE
GROUND MOUNTED LOW LEVEL LUMINAIRE - BOLLARD
IN-GRADE UP-LIGHT LUMINAIRE
DENOTES DIRECTION OF LIGHT DISTRIBUTION. PROVIDE DIRECTIONAL LIGHT
THROW (WALL WASH EFFECT) WHERE SHOWN.
GROUND MOUNTED FLOOD LUMINAIRE, TWIN OR SINGLE AS INDICATED ON PLANS
POLE MOUNTED FLOOD LUMINAIRE, TWIN OR SINGLE AS INDICATED ON PLANS
HHMH
UNDERGROUND CONDUIT AND WIRING
EXOTHERMIC COMPRESSION CONNECTION
GROUND ROD AND SYSTEM TEST WELL
GROUND ROD CONNECTION
ELECTRICAL MANHOLE OR HANDHOLE
MH=MANHOLE, HH=HANDHOLE
SITE POWER AND TELECOMMUNICATIONS
POWER ONE-LINE DIAGRAM
CIRCUIT BREAKER. AMP TRIP, FRAME AND OPTIONS AS INDICATED,
3P U.O.N.
FUSE, AMP RATING (AT) AS INDICATED. 3-POLES,
(1) FUSE PER POLE U.O.N.
DISCONNECT SWITCH. SIZE (AF) AS INDICATED. 3-POLE U.O.N.
FUSIBLE DISCONNECT SWITCH. AMP FUSE (AT) AND SWITCH RATING
(AF) AS INDICATED. 3-POLES WITH (1) FUSE PER POLE U.O.N.
AUTOMATIC TRANSFER SWITCH AMPACITY, VOLTAGE, NUMBER OF
POLES, WITHSTAND RATING AS INDICATED
LOW VOLTAGE DRAW-OUT CIRCUIT BREAKER. AMP TRIP (AT), AMP
FRAME (AF)AND OPTIONS AS INDICATED. 3-POLES U.O.N.
MEDIUM VOLTAGE DRAW-OUT CIRCUIT BREAKER. AMP TRIP, AMP
FRAME AND POLES AS INDICATED.
TRANSFORMER
PRIMARY (DELTA U.O.N) AND SECONDARY (WYE U.O.N)
VOLTAGES AS SHOWN
KVA RATING AS SHOWN
SEE TRANSFORMER SCHEDULE FOR ADDITIONAL REQUIREMENTS
480V/100A/ 4P/
25KA WCR
800AT/800AF
800AT/800AF/3P
XXX
3 LA'S
SELECTOR SWITCHES
AS - AMMETER PHASE
VS - VOLTMETER PHASE
WS - WATTMETER
DIGITAL METERING
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
KEY INTERLOCK - WITHDRAWN KEY
KEY INTERLOCK - CAPTIVE KEY
MOTOR, HP AS SHOWN
CONNECTION TO GROUND BARE #
4/0CU U.N.O
LIGHTNING
ARRESTERS
PANELBOARD/
DISTRIBUTION
BOARDS
METER WITH CURRENT TRANSFORMER
M - UTILITY OR OWNER METER
AM- A.C. AMMETER
VM- A.C. VOLTMETER
FM- FREQUENCY METER
WM- WATTMETER
SERVICE ENTRANCE SECTION OR OTHER LARGE
SWITCHBOARD OR DISTRIBUTION BOARD.
RATINGS, BREAKER QTY AND SIZE, NAMES ETC. AS
INDICATED ON PLANS
EXISTING SERVICE ENTRANCE SECTION OR OTHER
LARGE SWITCHBOARD/DISTRIBUTION BOARD. RATINGS,
BREAKER QTY AND SIZE, NAMES ETC. AS INDICATED ON
PLANS. ANY NEW WORK WITHIN EXISTING EQUIPMENT
WILL BE BOLD AND NOTATED AS NEW.
200AT/3P
200AF/3P
100AT/200AF
200AT
200AF
N.C. 100%
M
AS
DM
KEY DESIGNATION - PROVIDE ONE LESS KEY
THAN LOCKS (KIRK KEY OR EQUIVLIENT)
EQUIPMENT FEEDER TAG - REFER TO FEEDER
SCHEDULE FOR REQUIREMENTS
TRANSFORMER FEEDER TAG - REFER TO FEEDER SCHEDULE PHASE,
NUETRAL AND CONDUIT REQUIRMENTS. GROUND SHALL BE AS INDICATED
IN TAG.
175-4-CU
#4(CU)G
175-4-CU
A, AMP
AF
AFC
AFF
AIC
AM
AS
ASYM
AT
ATS
AWG
BOF
B.S.C
C
CAP
CATV
CB
CCTV
cd
CL
CU
(D)
DISC
DPST
(E)
EC
EWC
ELEC
EM
EPO
EMT
FLA
GRC
GEC
GEN
GFCI
GFI
GFP
GND, G
HOA
HP
IMC
IG
JB
KAIC
KVA
KW
KWH
LED
LTG
LV
MCA
MCB
- AMPERES
- AMP FUSE OR AMP FRAME
- AVAILABLE FAULT CURRENT
(SYMMETRICAL)
- ABOVE FINISHED FLOOR
- AMPERE INTERRUPTING
CAPACITY
- AMMETER
- AMP SWITCH
- ASYMMETRICAL
- AMP TRIP
- AUTOMATIC TRANSFER SWITCH
- AMERICAN WIRE GAUGE
- BOTTOM OF FIXTURE
- BARE STRANDED COPPER
CONDUCTOR
- CONDUIT
- CAPACITY OR CAPACITOR
- COMMUNITY ANTENNA TV
- CIRCUIT BREAKER
- CLOSED CIRCUIT TELEVISION
- CANDELA
- CURRENT LIMITING
- COPPER
- DEMOLISH
- DISCONNECT
- DOUBLE POLE SINGLE THROW
- EXISTING TO REMAIN
- ELECTRICAL CONTRACTOR
- ELECTRIC WATER COOLER
- ELECTRIC OR ELECTRICAL
- EMERGENCY
- EMERGENCY POWER OFF
- ELECTRICAL METAL TUBING
- FULL LOAD AMPERES
- GALVANIZED RIGID CONDUIT
- GROUNDING ELECTRODE
CONDUCTOR
- GENERATOR
- GROUND FAULT CIRCUIT
INTERRUPTER
- GROUND FAULT INDICATION
- GROUND FAULT PROTECTION
- GROUND
- HAND-OFF-AUTO
- HORSEPOWER
- INTERMEDIATE METAL
CONDUIT
- ISOLATED GROUND
- JUNCTION BOX
- THOUSAND AMPERE
INTERRUPTING CAPACITY
- KILOVOLT AMPERES
- KILOWATT
- KILOWATT HOUR
- LIGHT EMITTING DIODE
- LIGHTING
- LOW VOLTAGE
- MINIMUM CIRCUIT AMPS
- MAIN CIRCUIT BREAKER
ABBREVIATIONS
- MOTOR CONTROL CENTER
- MANHOLE
- MAIN LUGS ONLY
- NORMALLY CLOSED
- NATIONAL ELECTRICAL CODE
- NOT IN CONTRACT
- NOT IN SCOPE OF THIS
PROJECT
- NON FUSIBLE
- NIGHT LIGHT
- NORMALLY OPEN
- NOT TO SCALE
- OVER CURRENT
PROTECTION
- OVERLOADS
- POLE
- PULLBOX
- PHASE
- PANEL
- POINT OF CONNECTION
- POLYVINYL CHLORIDE
- POWER
- RECEPTACLE
- RIGID GALVANIZED STEEL
- SOLENOID
- SINGLE POLE DOUBLE
THROW
- SPEAKER
- SINGLE POLE SINGLE
THROW
- SWITCH
- SWITCHBOARD
- SYMMETRICAL
- TELEPHONE
- TELECOMMUNICATIONS
GROUNDING BUSBAR
- TELEPHONE MOUNTING
BOARD (PLY-WOOD)
- TELEPHONE TERMINAL
BACKBOARD
- TELEVISION
- TYPICAL
- UNDERGROUND
- UNLESS OTHERWISE NOTED
- VOLT
- VOLT AMPERES
- VOLTAGE DROP
- VOLT METER
- VOLT METER SWITCH
- WATTS OR WIRE
- WITH
- WITHOUT
- WEATHERPROOF
- TRANSFORMER
- EXPLOSION PROOF
MCC
MH
MLO
N.C.
NEC
NIC
NIS
NF
NL
N.O.
NTS
OCP
OL
P
PB
PH, Ø
PNL
POC
PVC
PWR
RCPT.
RGS
SOL
SPDT
SPKR
SPST
SW
SWBD
SYM
TEL
TGB
TMB
TTB
TV
TYP
UG
UNO/UNO
V
VA
VD
VM
VS
W
W/ W/O
WP
XFMR
XP
AIR TERMINAL P = PARAPET MOUNTED, S = SCREEN WALL MOUNTED
THRU ROOF DOWN CONDUCTOR TO GROUNDING SYSTEM
OUTSIDE UNDERGOUND GROUND RING - #4/0 BARE CU CONDUCTOR,
DIRECT BURRIED
INTERIOR GROUNDING CONNECTION - #4/0 INSULATED CU CONDUCTOR
U.O.N
MAIN CONDUCTOR SIZED PER NFPA 780
SECONDARY CONDUCTOR SIZED PER NFPA 780
INTERIOR GROUND ELECTRODE CONDUCTOR (DIAGRAMTIC) #4(CU)MIN OR
PER NEC 250.66 / 250.102
COPPER GROUND ROD 3/4"DIA. X 10'-0" LONG
GROUNDING TEST WELL WITH COPPER GROUND ROD 3/4"DIA. X 10'-0" LONG
EXOTHERMIC BONDING GROUNDING CONNECTION
P
LIGHTNING PROTECTION & GROUNDING
IN ADDITION TO ANY OTHER TESTING REQUIREMENTS, THIRD PARTY TESTING SHALL BE
REQUIRED FOR THE FOLLOWING:
GROUND FAULT PROTECTION
• SWITCHBOARDS, PANELBOARDS, MCC'S AND OTHER EQUIPMENT RATED 1000A OR MORE
OR OVER 600V
• INSULATION RESISTANCE TEST (PHASE TO PHASE, PHASE TO GROUND)
• DIELECTRIC VOLTAGE WITHSTAND TEST (PHASE TO PHASE, PHASE TO GROUND)
TRANSFORMERS RATED 100 KVA OR MORE SINGLE PHASE AND 300 KVA OR MORE THREE
PHASE
• INSULATION RESISTANCE TEST (WINDING-WINDING, WINDING-GROUND)
CONDUCTORS THAT SUPPLY EQUIPMENT RATED AT 1000 AMPERES OR MORE, OR OVER 600
VOLTS
• INSULATION RESISTANCE TEST (PHASE TO PHASE, PHASE TO GROUND)
• DC HIGH POTENTIAL TEST (PHASE TO PHASE, PHASE TO GROUND)
EMERGENCY AND STANDBY POWER SYSTEMS: SWITCHBOARDS PANELBOARDS, DISTRIBUTION
BOARDS, TRANSFER EQUIPMENT, POWER SOURCE, CONDUCTORS, FIRE PUMPS, EXHAUST
AND VENTILATION FANS.
• PHASE ROTATION TEST
• INSULATION RESISTANCE TEST ON FEEDER CONDUCTORS AND EQUIPMENT (PHASE TO
PHASE, PHASE TO GROUND)
• AUTOMATIC TRANSFER TEST
• OPERATION TEST SYSTEM UNDER LOAD CONDITIONS
TESTING AND SPECIAL INSPECTIONS
(R)(R)
NOTES:
THE FOLLOWING SYMBOLS ARE EXAMPLES INTENDED TO SHOW METHODOLOGY FOR
DEMOLITION. THIS APPROACH IS APPLICABLE TO ALL SYMBOLS INDICATED ON THIS SHEET.
NEW - SHOWN HERE FOR REFERENCE AS A COMPARISON AGAINST
EXISTING AND DEMO ITEMS
EXISTING ELECTRICAL ITEM TO BE REMOVED (BOLD AND DASHED)
EXISTING ELECTRICAL ITEM TO BE RELOCATED. HALFTONE
(R) INDICATES NEW LOCATION
EXISTING ELECTRICAL ITEM TO REMAIN. HALFTONE.
DEMOLITION AND REMODEL
ELECTRICAL SHEET LIST
Sheet Number Sheet Name
ELECTRICAL
E-001 SYMBOLS AND ABBREVIATIONS
ED-101 ELECTRICAL SITE PLAN DEMO - LAKE BALDWIN
ED-102 ELECTRICAL SITE PLAN DEMO - LAKEMONT
EP-101 ELECTRICAL SITE PLAN - LAKE BALDWIN
EP-103 ELECTRICAL SITE PLAN - LAKEMONT
EP-401 ELECTRICAL DETAILS
EP-402 GROUNDING DETAILS
EP-403 TYPICAL LABELING DETAILS
EP-601 ELECTRICAL ONE-LINE DIAGRAM DEMO - LAKE BALDWIN
EP-602 ELECTRICAL ONE-LINE DIAGRAM - LAKE BALDWIN
EP-603 ELECTRICAL ONE-LINE DIAGRAM - LAKEMONT
TOTAL:: 11
NFPA 101 - LIFE SAFETY CODE LATEST
INTERNATIONAL FIRE CODE 2018
FIRE AND LIFE SAFETY CODES EDITION
INTERNATIONAL BUILDING CODE (IBC) 2018
AMERICANS WITH DISABILITIES ACT (ADA) LATEST
OWNER SPECIFICATIONS AND STANDARDS VA TIL
LOCAL AND STATE CODES AND AMENDMENTS VA TIL
NATIONAL ELECTRICAL CODE (NFPA 70) 2023
GENERAL EDITION
ALL OF THE FOLLOWING ARE HEREBY MADE PART OF THESE SPECIFICATIONS. THEY SHALL
BE SATISFIED BY THE CONTRACTOR AT NO ADDITIONAL EXPENSE TO THE OWNER
CODES AND STANDARDS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
LAKE BALDWIN VA
CLINIC
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
AESUS DESIGN GROUP
1050 E. Southern Ave., Suite D Temple, AZ, 85282 480-454-2861 David Combs
LAKE BALDWIN SITE
ELECTRICAL UPGRADES
MARCH 1, 2024 TS TS
5201 RAYMOND ST, ORLANDO, FL 32803
A u to d e s k D o c s
/A E
S U
S P ro je c ts
/L a k e
B a ld w in -I m p ro v e
E le c D is tr ib u ti o n -E le c -R
.r v t
/2
/2
:3
:1
A
M
E-001
SYMBOLS AND ABBREVIATIONS 675-23-801
SITE
Revisions: Date:
SIGNED: 02/27/24
C
C O
N C
C
LF
M E
TA
L
S
TA
IR
S
M E
TA
L
S
TA
IR
S
CC
W O O D
D E C K
W O O D
D E C K
W O O D
D E C K
WO
OD DE
C K
WO
OD ST
EP
S
W O O D
S
TE
P S
W O O D
D E C K
W O O D
D E C K
W O O D
R A M P
WOOD
DECK
W O O D
D E C K
W O O D
D E C K
W O O D
D E C K
(T Y P
W O O D
R A M P
W O O D
S
TE
P S
(T Y P
G A Z E B O
W O O D
R A M P
W O O D
D E C K
W O O D
D E C K
WOOD
DECK
WOOD
RAMP
8' CW UNDER WOOD
RAMP
C O V E R E D
W O O D
C O V E R E D
W O O D
W O O D
S
TE
P S
WOOD
RAMP
W O O D
D O C K
8' CW UNDER WOOD
RAMP
WOOD
RAMP
WOOD
DECK
W O O D
S
TE
P S
N89°59'50"W 70.57'
PLAT S
°0 '5
.4
P
LA
T
BRICK
BRICK
RETENTION AREA
RETENTION AREA
R E
T E
N T
IO
N
A R
E A
RETENTION AREA
RETENTION AREA
RETENTION AREA
R E
T E
N T
IO
N
A R
E A
R E
T E
N T
IO
N
A R
E A
R E
T E
N T
IO
N
A R
E A
R E
T E
N T
IO
N
A R
E A
RETENTION AREA
R E
T E
N T
IO
N
A R
E A
R E
T E
N T
IO
N
A R
E A
R E T E N
TI
O N
A R E A
R E T E N
TI
O N
A R E A
D
IR
T
R O A D
DI
RT RO
AD
DIRT
ROAD
D
IR
T
D
IR
T
D
IR
T
D
IR
T
D
IR
T
S A
T E
L L
IT
E
A N
T E
N N
A
M E
T A
L L
ID
T
1 STORY
MODULAR BUILDING
ADDRESS #508
37.7'
.8 ' 8.8'
.8
26.2'
.3
72.8'
.3
.3
72.8'
.3
26.2'
.8 '8.8'
.8
37.7'
1 STORY
MODULAR BUILDING
ADDRESS #507
MODULAR BUILDING
ADDRESS #505
60.3'
.4
' MODULAR BUILDING
#506
37.7'
.8 ' 8.8'
.8
26.2'
.3
72.8'
.3
S
TO
R Y
B
LO
C K
F R A M E
A D D R E S S
( C O U R T Y A R D
N O T
LO
C A T E D
52.1'
.7
147.1'
4.5'
14.8'
66.7'
.6
15.7'
.4 '82.3'
.7
52.1'
.6
84.8'
.8
28.1'
31.9'
42.8'
.3
33'
.6
6.9'
.4
15.3'
.8
15.3'
.9
59.6'
.8
97.2'
.2
.6
97.3'
.1
.5
20'x8'
1 STORY
WOOD TRAILER
C C
C C
CC
C P
C P
' C
W
' C
W
4' CW
C O
N C
D W
C P
5' CW
C C
5' CW
C P
C P
C O
N C
C O
N C
C
W
C P
C P
C O
N C
CC
C C
CC
C C
CW
CW C
C
C O
N C
6' CW
C O
N C
C P
C P
C O
V E
R E
D L
O A
D
IN
G D
O C
K
20.7'
COVD
C C
C C
C O
N C
C O
N C
C P
C P
C P
C P
ALIMINUM STEPS
A L
IM
IN
U M
R A
M P
C P
C P
C O
N C
C O
N C
C
W
CP
C O
N C
C C
C
W
C P
C P
C P
C C
C C
C C
C O
V E
R E
D C
W 6'
C W
C
W
COVERED CW
C O
V E
R E
D C
W
6' CW
CC
S T
E P
S T
E P
S T
E P
C C
C C
CONC
CW CW
C O
N C
C O
N C
A P
R O
N
C O
N C
A P
R O
N
C O
N C
A P
R O
N
5' CW
CW
CW
C W
G A
R V
E L
C P
C W
C W
6' CW
P la n te d M o u n d
C P
C P
C O
N C
9' C W
9' C W
C C
C
W
CW
C P
4' CW
4' CW
C O
N C
A P
R O
N
C O
N C
A P
R O
N
C O
N C
C O
V D
C C
C O
N C
C P
C O
N C
C U
R B
T
Y P
C O
N C
C U
R B
T
Y P
C O
N C
R
IP
R A
P
6' CW
6' CW
C
W
5' CW 5' CW
5' CW
5' CW
5' CW
6' C
W
C O
N C
C O
N C
C O
N C
F L
U M
E
C O
N C
F L
U M
E
C O
N C
F L
U M
E
C O
N C
F L
U M
E
C O
N C
C
W
C P
C O
N C
5' C
W
C
W
C O
N C
L
ID
CONC
5' CW
5' CW
C
W C
O N
C S
T E
P S
C O
N C
S T
E P
S
C O
N C
5' CW
C
W
' C
W
8' CW
8' CW 6' CW
5' CW
CONC
APRON
CONC
APRON
C O
N C
A P
R O
N
7' CW
CW
CW
C
W
C
W
C P
C P
6' CW
C P
C P
C P
C P
C P
C W
5' CW
CP
4' CW
C W
R A
M P
C O
V D
CW
C
P 5' CW
C O
N C
5' C
W
C
W
F O
U N
T A
IN
C O
V D
C W6 C
W
8' CW
C
W
C P
C C
5' C
W
4' CW
4' CW
C O
N C
C W
C O
N C
C O
N C
C P
C W
C W
C W
C P
C
W
C C
COVERED CW
COVERED CW
C W
5' CW
CW
C W
C P
CP
C O
N C
CONC
C C
G R
A V
E L
C O
N C
S T
E P
S
C P
C P
C O
N
C CONC
CC
RAMP
C P
CW
C W
'x
C
P
'x
C
P
'x
C
P
C P
R A
M P
R A
M P
C C
C O
N C
CW
C O
N C
C C
CC
CC
C C
C C
C C
C C
R A
M P
CC
C O
N C
D
IR
T
CW
C C
C
CCONC
G E
N E
R A
T O
R A
R E
A
R A
M P
R A
M P
C O
V E
R E
D R
A M
P
CW
L O
A D
IN
G
D O
C K
C O
N C
C C
S T
E P
S
COVERED RAMP
C O
N C
C C
COVERED CW
6' CW
R A
M P
C O
N C
C O
N C
C O
N C
R A
M P
C O
N C
M E
T A
L L
ID
C O
N C
C U
R B
T
Y P
C O
N C
C R
A W
L S
P A
C E
A C
C E
S S
C
W
8' CW METAL STAIRS
C W
STAIRS
S T
A
IR
S
CW
C O
N C
C C
CONC
CW
G A
R V
E L
C O
N C
S T
E P
S
RAMP
R A
M P
CW
4' CW
'x
' C
P
C O
N C
S T
E P
S R
A M
P
'x
C
P
C W
C W
2.5'
1.4'
32.1'
.1
.6
. 8
49.3'
C W
C W
STEPS
CC
C O
V E
R E
D C
W
CONC
C C
C C
C O
N C
CONC STEPS
C W
G A
R V
E L
C P
C O
N C
S T
E P
S
C W
CPC
C
CW
CONC
CW
C W
6' CW6' CW6' CW
G A S
P U M P
CBW
C O
N C
H E
A D
W A
L L
C O
N C
H E
A D
W A
L L
C O
N C
H E
A D
W A
L L
C O
N C
H E
A D
W A
L L
CONC
HEADWALL
C O
N C
H E
A D
W A
L L
CONC
HEADWALL
C O
N C
H E
A D
W A
L L
C O
N C
H E
A D
W A
L L
C O
N C
H E
A D
W A
L L
C O
N C
H E
A D
W A
L L
.4 'x .4 C O
LU
M N
(T Y P
.4 'x .4 C O
LU
M N
(T Y P
C O
N C
H E
A D
W A
L L
B R
IC
K
W A L L
BRICK
WALL
CBW
BRICK
WALL
B R
IC
K
W A L L
BRICK
WALL
BRICK
WALL
BRICK
WALL
D
IR
T D
IR
T
D
IR
T
1'E
.8 'S
C B W
C B W
C B W
C B W
.6 'S
.0 'S
CBW CBW
A B A N D O N E D
E
T
CLF
C
LF
C
LF
C
LF
C
LF
D
IE
S E L F U E L
S
TO
R A G E
C
LF
C
LF
C
LF
C L F
C
LF
C
LF
C
LF
C
LF
C
LF
C
LF
C
LF
M F
M F
C L F
C L F
C
LF
C L F
C
LF
C
LF
M F
1'W
0.5'W
M F
M F
0.7'W
0.4'W
1.5'W
C
LF
0.7'W
C
LF
.6
1.3'W
C L F
C L F
C
LF
C
LF
S89°59'23"W 333.86'
MEAS
S87°40'34"E 206.41'
MEAS
S °5 '3
. 2
M E A S
S °5 '4
. 0
M E A S
A S
P H
A L T
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
TA
S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
T
ASPHALT
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
TA
S
P H
A L
T
A S
P H
A L
T
ASPHALT
ASPHALT
A S
P H
A L
T
A S
P H
A L
T
ASPHALT
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
T
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
ASPHALT
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
T
ASPHALT
ASPHALT
ASPHALT
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
T
A S
P H
A L
T
A S P H A
LT
F L U M E
A S P H A
LT
F L U M E
A S
P H
A L
T
ASPHALT
ASPHALT
ASPHALT
.3
.7
.3
.1
.8
.3
.3
. 5
.7
R
ID
L E
Y A
V E
N U
E
RAYMOND STREET
RAYMOND STREET
R A
Y M
O N
D S
T R
E E
T
PALMETTO AVENUE
C O
M F
O R
T A
V E
N U
E
NASH STREET
NASH STREET
M E
R C
Y A
V E
N U
E
LAKE BALDWIN LANE
E B
E B
E B
E B
E B
E B
E B
U B
U B
U B
U B
U B
UB
UB
UB
U B
U B
UP
UP
UP
UP
UP
V
G M
G V
UP
UP
UP
UP
UP
UP
UP
UP
U P
V
UP
E B
EB
E B
E B
EB
E B
E B
E B
E B
E B
E B
E B
E B
E B
E B
E B
E B
U
PU
P
UP
F O
C
E B
GV
UP
E B
GV
UP
UP
UP
UP
UP
UP
T T
T
T
EB
T
E B
T V
EB
EB
SD
SD
EL
SD SD
A. PROVIDE AND INSTALL NEW WIRING DEVICES IN ALL LOCATIONS VACATED DURING
DEMOLITION WHETHER OR NOT LOCATIONS ARE EXPLICITLY INIDCATED ON THE
PLAN DRAWINGS. UTILIZE EXISTING BRANCH CIRCUITS COILED DURING THE
DEMOLITHION PHASE AND UTILIZE EXISTING BACK BACKBOXES WHERE FEASIBLE.
WHERE BACKBOXES ARE DAMAGED OR OTHERWISE UNUSABLE PROVIDE NEW
BACKBOXES AT EXISTING WIRING DEVICES LOCATIONS.
B. REFER TO SHEET EP-001 SYMBOLS, ABBREVIATIONS, AND ADDITIONAL
REQUIREMENTS INCLUDING, BUT NOT LIMITED TO, CODE REQUIREMENTS,
EQUIPMENT AND MATERIAL SPECIFICATIONS AND INSTALLATION REQUIREMENTS,
DEVICE MOUNTING HEIGHTS, EQUIPMENT IDENTIFICATION, ETC.
C. DRAWINGS AND SPECIFICATIONS ARE COMPLEMENTARY OF EACH OTHER. WHERE
DRAWINGS AND SPECIFICATIONS DIFFER, THE MORE STRINGENT OF THE TWO
REQUIREMENTS SHALL BE FOLLOWED.
D. ALL EQUIPMENT AND FIXTURES ARE NEW UNLESS NOTED OTHERWISE.
E. CONDUIT AND WIRE IS SHOWN DIAGRAMMATICALLY. ACTUAL ROUTING AND
REQUIRED NUMBER OF SUPPORTS SHALL BE DETERMINED BY THE CONTRACTOR.
F. UNLESS CONDUIT ROUTING CLEARLY INDICATES AS SUCH, DO NOT ROUTE
CONDUIT ON OR ABOVE ROOFTOPS WITHOUT CONSULTING ENGINEER TO
DETERMINE ANY POTENTIAL IMPACT TO RACEWAY OR CONDUCTOR SIZE DUE TO
ADDITIONAL AMBIENT DERATING FOR ROOFTOP INSTALLATION.
G. CONCEAL CONDUITS IN ALL FINISHED AREAS INCLUDING CONCEALMENT WITHIN
MASONRY WALLS WHEN PRESENT. (EXCEPTION: ELECTRICAL, MECHANICAL, AND
JANITOR ROOMS).
H. FLOOR AND FIRE WALL PENETRATIONS MUST BE SEALED WITH AN APPROVED
DESIGN TESTED FIRE STOPPING SYSTEM APPROPRIATE TO THE PENETRATED WALL
TYPE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S REQUIREMENTS.
I. PRIOR TO ROUGH-IN AND FINAL CONNECTION, VERIFY ELECTRICAL
CHARACTERISTICS AND EXACT LOCATION OF THE EQUIPMENT.
J. INSTALL ALL CONDUITS PARALLEL PERPENDICULAR AND UNIFORM TO BUILDING
ELEMENTS
K. NO MORE THAN 270 DEGREES OF CONDUIT BENDS ARE ALLOWED IN ANY CONDUIT
RUNS NO MORE THAN 180 DEGREE OF CONDUIT BENDS ARE ALLOWED IN ANY
INTERIOR CONDUIT RUNS.
L. IDENTIFY ALL CONDUIT RUNS WITH MARKER TAPE.
M. VERIFY ALL EQUIPMENT LOCATIONS AND DIMENSIONS IN THE FIELD PRIOR TO
INSTALLING RACEWAYS AND WIRING
N. ELECTRICAL WORK SHALL BE DONE IN CONFORMANCE WITH THE CONSTRUCTION
DOCUMENTS, ALL APPLICABLE CODES, ISSUED DRAWINGS AND SPECIFICATIONS.
GENERAL NOTES
(E)-GEN1
(E)-GEN2
(E)-GEN3
(E)-SWBD-EM
(E)-MV-MWS-NO.1
(E)-MV-XF-NO.1
(E)-MV-ATS-NO.1
(E)-MV-MWS-NO.1A
(E)-MV-XF-517
(E)-NORTH OUC
(D)-MV-XF-504
(E)-MV-2WS-NO.4
(E)-MV-2WS-NO.4
(D)-MV-ATS-NO.4
(E)-MV-MWS-NO.4
(E)-MV-XF-NO.3
(D)-MV-ATS-NO.2
(E)-MV-MWS.NO.2 (E)-MV-MWS-NO.3
(D)-MV-ATS-NO.3
(E)-MV-XF-NO.2
(E)-MV-XF-ADMIN-T2
(E)-SOUTH OUC
(E)-MV-XF-517
(E)-MV-XF-501
(E)-MV-XF-503
BLD 503
BLD 500
BLD 509
BLD…
This is the start of the file's text. The full file is on GovTribe.