ATTACHMENT 5 - 100 Structural Calculations.pdf
PDF 764 KB Posted
- Solicitation number
- 36C24826Q0104
About this file
These are structural engineering calculations for a caisson footing for a canopy column at a project located at 5201 Raymond Street in Orlando, Florida. The documents, prepared by Simply Structural Inc. in December 2023, include detailed wind load analyses and pole footing embedded soil calculations using the 2018 IBC, 2019 CBC, and ASCE 7-16 standards. Key technical specifications include a circular 18-inch diameter caisson with an 18-foot column height, wind load of 0.810k, and an assumed soil allowable bearing pressure of 1,500 psf. The calculations evaluate various load combinations and demonstrate that the proposed footing design meets structural engineering requirements, with a minimum required embedded depth of 4.625 feet and a maximum soil pressure of 0.8403 ksf.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
730 N. 52ND ST., SUITE 105 Job Name: VA
PHOENIX, ARIZONA 85008
Job No.: 2 - Sheet No.: ______
OFFICE 602-443-0303
FAX 602-443-0404
CONSULTING STRUCTURAL ENGINEERS EMAIL MWILDA@SIMPLYSTRUCTURAL.COM By: br Date: -23
CLIENT:
AESUS Design Group 1050 E. Southern Ave, Suite D Tempe, Arizona 85282
PROJECT DESCRIPTION AND ADDRESS:
GENERAL INFORMATION:
BUILDING CODE: 20
SOILS DATA: Allowable Bearing Pressure = 1500 p.s.f.
OWNERSHIP OF DOCUMENTS: CALCULATIONS, DRAWINGS AND SPECIFICATIONS AS INSTRUMENTS OF SERVICE ARE, AND SHALL REMAIN THE PROPERTY OF THE ENGINEER. THEY ARE NOT TO BE USED ON OTHER PROJECTS OR EXTENSIONS TO THIS PROJECT EXCEPT BY AGREEMENT IN WRITING AND WITH THE
APPROPRIATE COMPENSATION TO SIMPLY STRUCTURAL, INC.
02/29/24
Simply Structural JOB TITLE VA - Orlando 730 N. 52nd St., suite 105
Phoenix, AZ 85008 JOB NO. 23-070 SHEET NO.
602-443-0303 CALCULATED BY br DATE
CHECKED BY DATE
Wind Loads - Open Buildings: 0.25 ≤ h/L ≤ 1.0 Ultimate Wind Pressures
Type of roof = Monoslope Free Roofs G = 0.85 Wind Flow = Obstructed Roof Angle = 2.4 deg
NOTE: The code requires the MWFRS be Main Wind Force Resisting System designed for a minimum pressure of 16 psf.
Kz = Kh (case 2) = 0.90 Base pressure (qh) = 35.8 psf
Roof pressures - Wind Normal to Ridge Procedure not allowed h/L is greater than 1.0
Cnw Cnl Cn = -0.50 -1.20 p = -15.2 psf -36.5 psf Cn = -1.10 -0.60 p = -33.4 psf -18.2 psf
NOTE: 1). Cnw and Cnl denote combined pressures from top and bottom roof surfaces.
2). Cnw is pressure on windward half of roof. Cnl is pressure on leeward half of roof.
3). Positive pressures act toward the roof. Negative pressures act away from the roof.
Roof pressures - Wind Parallel to Ridge, Ɣ = 90 deg h = 20.0 ft ≤ h >h ≤ 2h > 2h 2h = 40.0 ft
Cn = -1.20 -0.90 -0.60 p = -36.5 psf -27.4 psf -18.2 psf Cn = 0.50 0.50 0.30 p = 15.2 psf 15.2 psf 9.1 psf
Fascia Panels -Horizontal pressures qp = 35.8 psf Windward fascia: 53.6 psf (GCpn = +1.5)
Leeward fascia: -35.8 psf (GCpn = -1.0)
Components & Cladding - roof pressures Kz = Kh (case 1) = 0.90 a = 3.0 ft a2 = 9.0 sf
Base pressure (qh) = 35.8 psf 4a2 = 36.0 sf G = 0.85 positive negative positive negative positive negative
1.19 -4.08 0.93 -2.05 0.60 -1.36
0.93 -2.05 0.93 -2.05 0.60 -1.36
0.60 -1.36 0.60 -1.36 0.60 -1.36
36.2 psf -124.0 psf 28.2 psf -62.5 psf 18.1 psf -41.3 psf
28.2 psf -62.5 psf 28.2 psf -62.5 psf 18.1 psf -41.3 psf
18.1 psf -41.3 psf 18.1 psf -41.3 psf 18.1 psf -41.3 psf
Wind pressure zone 3 zone 2
>9, ≤ 36 sf > 36 sf ≤ 9 sf
>9, ≤ 36 sf > 36 sf
Obstructed Wind Flow
CN
zone 1 Obstructed Wind Flow
Effective Wind Area
≤ 9 sf
A
B
Horizontal Distance from Windward EdgeWind
Flow
Load Case
A
B
Load Case
Wind Flow
Obstructed Wind Flow
Ɣ = 0 & 180 deg Wind Direction
53.6 psf -35.8 psf
Pole Footing Embedded in Soil LIC# : KW-06015475, Build:20.23.05.25 SIMPLY STRUCTURAL INC. (c) ENERCALC INC 1983-2023
DESCRIPTION: caisson for canopy column
Simply Structural 730 N. 52nd Street, Suite 105 Phoenix, Arizona 85008
Project File: va - orlando (23-070).ec6
Project Title:
Engineer:
Project ID:
Project Descr:
Code References Calculations per IBC 2018 1807.3, CBC 2019, ASCE 7-16 Load Combinations Used : ASCE 7-16
General Information Circular
18.0
300.0 1,500.0
Lateral Restraint at Ground Surface
Pole Footing Shape Pole Footing Diameter . . . . . . . . . in
Allow Passive . . . . . . . . . . . . . . . pcf Max Passive . . . . . . . . . . . . . . . . psf
Calculate Min. Depth for Allowable Pressures
+D+0.60WGoverning Load Combination Lateral Load 0.4860 Moment 9.720 k-ft
Minimum Required Depth 4.625 ft k
Restraint @ Ground Surface
Pressure at Depth Actual 1,287.48 psf Allowable 1,387.50 psf
Surface Retraint Force 4,951.95 lbs
Controlling Values ft^2Footing Base Area 1.767 Maximum Soil Pressure 0.8403 ksf k k k
0.4950 k
0.990 k
Applied Loads k
Lateral Concentrated Load (k)
D : Dead Load
L : Live Lr : Roof Live
S : Snow W : Wind E : Earthquake H : Lateral Earth Load distance above
0.810
20.0 k k k k k k k ft
Lateral Distributed Loads (k
TOP of Load above ground surface
BOTTOM of Load above ground surface k/ft k/ft k/ft k/ft k/ft k/ft k/ft ft
Applied Moment (kft) k-ft k-ft k-ft k-ft k-ft k-ft k-ft ground surface ft
Vertical Load (k) k
Load Combination Results
Factor Soil IncreaseForces @ Ground Surface
Load Combination Required
Loads - (k) Moments - (ft-k) Depth - (ft) Pressure at Depth
Allow - (psf)Actual - (psf)
0.00.000 0.000D Only 0.13 1.00037.5
0.00.000 0.000+D+Lr 0.13 1.00037.5
0.00.000 0.000+D+0.750Lr 0.13 1.00037.5
1,287.50.486 9.720+D+0.60W 4.63 1.0001,387.5 1,213.90.365 7.290+D+0.750Lr+0.450W 4.13 1.0001,237.5 1,213.90.365 7.290+D+0.450W 4.13 1.0001,237.5 1,287.50.486 9.720+0.60D+0.60W 4.63 1.0001,387.5
0.00.000 0.000+1.009D 0.13 1.00037.5
0.00.000 0.000+1.007D 0.13 1.00037.5
Pole Footing Embedded in Soil LIC# : KW-06015475, Build:20.23.05.25 SIMPLY STRUCTURAL INC. (c) ENERCALC INC 1983-2023
DESCRIPTION: caisson for canopy column
Simply Structural 730 N. 52nd Street, Suite 105 Phoenix, Arizona 85008
Project File: va - orlando (23-070).ec6
Project Title:
Engineer:
Project ID:
Project Descr:
0.00.000 0.000+0.5908D 0.13 1.00037.5