This document is a detailed trip report for a backflow prevention assembly inspection conducted at the U.S. Embassy in Paris, France from April 15-19, 2024. The inspection covered nine locations including the Embassy compound, Boulogne, Neuilly Residence, CMR, OECD, Weber, Leopold II, GMC, and Deschanel, revealing multiple critical backflow prevention deficiencies.
Key findings include the need to install 24 Reduced Pressure Assemblies (RP), replace eleven existing RPs that failed backflow tests, and address multiple plumbing safety issues such as water softeners directly connected to sewer lines, coffee machines lacking proper valves, ice maker drains improperly connected, and dishwashers without required backflow prevention. The report provides specific recommendations for each location, including precise model numbers for replacement backflow prevention assemblies from manufacturers like Watts and Zurn Wilkins, along with detailed product links, ordering codes, and repair kit specifications. The inspection was conducted using a Mid-West Instrument 835 Back-flow Test Kit and involved embassy contacts including the Senior Facility Manager, Deputy Facility Manager, Data Analyst, and Plumber.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| SF30 - Amendment A0003.pdf | ||
| SF30 - Amendment A0002.pdf | ||
| SF-30 - Amendment 0001.pdf | ||
| Attachment 1 - Scope of work.pdf | ||
| RFQ 19FR6325Q0034 Backflow deficiencies prevention.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 | P a g e
U.S Embassy the Hague Date 4/29/2024 Moros Evangelos
TRIP REPORT - BACKFLOW PREVENTION ASSEMBLY INSPECTION AND
MAINTENANCE
FROM: THE HAGUE US EMBASSY-MOROS EVANGELOS
SUBJECT: Trip report – France, Paris US Embassy, April 15-19-2024
OVERVIEW AND PURPOSE OF THE TRIP
According to the International Plumbing Code (IPC), each backflow-prevention assembly is required to be tested at least annually.
EXECUTIVE SUMMARY
• The inspection covered nine locations: the Embassy compound, Boulogne, Neuilly Residence, CMR, OECD, Weber, Leopold II, GMC, and Deschanel.
• It is recommended to install Reduced Pressure Assembly (RP) in 24 locations.
• Eleven Reduced Pressure Assembly (RP) were discovered, but all failed the backflow test.
• Five water softeners are connected directly to the sewer line. Air gaps must be installed.
• One coffee machine is not equipped with a Dual Check valve, and the drain is directly connected to the sewer line. Therefore, it is necessary to install a Dual Check Valve and air gap.
• One coffee machine is equipped with a Dual Check valve and air gap, which means it is compliant.
• Six ice maker drains are directly connected to the sewer line.
Therefore, an air gap must be installed.
• Six dishwashers are using a chemical feed system and do not have a Reduced Pressure Assembly (RP) installed. Additionally, their drain is directly connected to the sewer line, which poses a safety concern.
Therefore, it is necessary to install a Reduced Pressure Assembly (RP) and air gap to ensure the safety of the system.
• The car wash area is not equipped with a Reduced Pressure Assembly (RP), and the drain is directly connected to the sewer line.
Therefore, it is necessary to install a Reduced Pressure Assembly (RP) and air gap.
• Three disinfection cleaning units have dual check valves. However, to ensure the safety of the drinking water supply, a Reduced Pressure Assembly (RP) and air gap for high-hazard chemicals must be
2 | P a g e installed between the disinfection cleaning unit and the main water supply.
• It is recommended to install a hose bibb vacuum breaker on every hose bibb to prevent the backflow of contaminated water into the main water supply.
At the Embassy, several techniques are available for measuring the size of water pipes, as different people use different methods. The Embassy generally measures nominal pipe size
(NPS) in inches, while European pipe sizes are designated in millimeters as diameter nominal (DN) under the ISO standard. The term nominal bore (NB) is also sometimes used interchangeably. This report will use NPS (inches) to refer to pipe sizes. The Embassy is strongly advised to verify all pipe diameters before ordering the backflow preventer assembly or devices.
General Installation Details
• The installation guidelines stated in this report must comply with the U.S. National Plumbing Code.
• All Reduced Pressure Assemblies (RP) shall be installed between 12 and 36 inches above the floor or finished grade, with enough clearance for easy testing and maintenance. A fixed platform, portable scaffold, or lift that meets OSHA standards must be provided if installed at a greater height.
• Account for required sided clearance from the wall of Double Check and Reduced
Pressure Assemblies (1/2"-3") are 24" from side test cocks, 12" from top mounted test cocks, with 24" access from one side. For sizes 4" and above, double these requirements.
Drainage
• Drainage for backflow prevention assemblies shall be provided for all installations of DCV or RP to accommodate discharge during testing or draining of the unit and for RP relief valve discharges, as follows:
• Discharge from relief valves must be readily detectable to maintenance personnel either visually or using water level alarms, flow indicator lights, etc.
• All drainage from Reduced Pressure Assembly (RP) must be by gravity drains.
• An air gap between the RP relief valve opening and discharge piping must be maintained. The air gap must be at least twice the dimension of the relief valve's effective opening but in no case less than 1 inch.
• The manufacturer's air gap fittings may be utilized, provided they maintain a proper air gap and do not enclose or cover the relief valve. These fittings are only sized to handle intermittent and low-flow discharges. Additional drainage capacity may be required to accommodate a catastrophic relief valve failure.
3 | P a g e
EMBASSY CONTACTS
The following individuals were contacted and provided information during the site visit.
• David Scovill: Senior Facility Manager
• Carl Vimmerstedt: Deputy Facility Manager
• Silke Klassens: Data Analyst
• Usta Suleyman: Plumber
On the final day, during the out-brief with Senior Facility Manager David Scovill, an action plan was discussed.
SITE VISIT OBSERVATIONS
Inspector work tools for site visit:
• Back-flow Test Kit Mid-West Instrument 835
4 | P a g e
ASSESSMENT AND RECOMMENDATIONS
ISSUE DESCRIPTION RECOMMENDATIONS
1.
Location: Chancery Building
Basement Rm AB1:01A4A
The water line connecting the city and the Embassy did not have a Reduced Pressure Assembly (RP) installed.
The arrow symbol is used to indicate the recommended installation location for a Reduced
Pressure Assembly (RP).
Backflow reduced pressure assembly 3” must be installed
Model: WATTS LF909-DOSY-FS 3 Ordering Code: 88009313
UPC: 098268291629
https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf909-large/lf909-dosy-fs-3
Repair kit
Model Watts
LFRK 909-CK1 2 1/2-3
Ordering code: 0794096
UPC:09826845933
https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck1- 2-12-3
LFRK 909-CK2 2 1/2-3
Ordering code:0794101
UPC:09826845938
https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck2- 2-12-3
LFRK909-S 3
Ordering code:079410
UPC:09826845943
https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk909-s-3
RK 909-RC1 2 1/2-3
Ordering code: 088722
UPC: 09826841457
https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc1-2- 12-3
RK 909-RC2 2 1/2-3
https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf909-large/lf909-dosy-fs-3 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf909-large/lf909-dosy-fs-3 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf909-large/lf909-dosy-fs-3 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf909-large/lf909-dosy-fs-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck1-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck1-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck1-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck1-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk909-s-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk909-s-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk909-s-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc1-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc1-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc1-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc1-2-12-3
5 | P a g e
1.
Ordering Code: 0887226
UPC: 098268414622
https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc2-2- 12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc2-2-12-3
6 | P a g e
2.
Location: Building B Rm B-1 45
The water line connecting the city and
The arrow symbol is used to indicate the recommended installation location for a Reduced
Pressure Assembly (RP).
Backflow reduced pressure assembly 3” must be installed
Model: Watts LF909-DOSY-FS 3 Ordering Code: 88009313
UPC: 098268291629
https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf909-large/lf909-dosy-fs-3
Repair kit
Model: Watts
LFRK 909-CK1 2 1/2-3
Ordering code: 0794096
UPC:09826845933
https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck1- 2-12-3
LFRK 909-CK2 2 1/2-3
Ordering code:0794101
UPC:09826845938
https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck2- 2-12-3
LFRK909-S 3
Orderingcode:079410
UPC:09826845943
https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk909-s-3
RK 909-RC1 2 1/2-3
Ordering code: 088722
UPC: 09826841457
https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc1-2- 12-3
RK 909-RC2 2 1/2-3
Ordering Code: 0887226
UPC: 098268414622
https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf909-large/lf909-dosy-fs-3 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf909-large/lf909-dosy-fs-3 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf909-large/lf909-dosy-fs-3 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf909-large/lf909-dosy-fs-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk909-s-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk909-s-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk909-s-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc1-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc1-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc1-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc1-2-12-3
7 | P a g e
2.
https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc2-2- 12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc2-2-12-3
8 | P a g e
3. Location: Building B Cloakroom
The Reduced Pressure Assembly (RP) did not pass the test. Check valve 2 failed.
The arrow symbol is used to indicate the recommended installation location for a Reduced Pressure
Assembly (RP).
Backflow reduced pressure assembly 3/4” must be installed.
Model: Watts LF009M3-QT 3/4 Ordering Code: 0390997
UPC: 098268177862
https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway
Mechanical – thread air gap
Model: 909AGC
UPC:098268104950
Ordering Code:0881376 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc
Repair kit
Model: Watts RK009M2-T Ordering Code: 0887302
UPC: 0982685455098
https://www.watts.com/products/plumbing-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34
9 | P a g e
4. Location: Building B Rm BB1: 9A
Coffee machine has a Dual Check valve installed that is not testable. No assessable for data information.
The arrow symbol indicates the dual check valve.
No recommendation. The coffee machine is in compliant.
12 | P a g e
ISSUE
DESCRIPTION RECOMMENDATIONS
7.
Location: Building: BB1:5B kitchen
The chemical feed system is missing a backflow preventer.
The arrow symbol indicates the recommended installation location for a Reduced Pressure Assembly
(RP).
Backflow reduced pressure assembly 1/2”
Model: Watts LF009-OT 1/2 Ordering Code: 0391002
UPC:098268051100
https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12
Mechanical - thread air gap
Model: 909AGA
UPC:098268235319
Ordering Code:0881399 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909aga
Repair kit
Model: Watts RK009M2-T Ordering Code: 0887298
UPC: 098268538205
https://www.watts.com/products/plumbing-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909aga https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909aga https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909aga https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909aga https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12
16 | P a g e
11.
Location: Building B Rm: BB1:5B kitchen.
The water line connecting the Embassy water supply to the disinfection cleaning unit is equipped with a dual check valve. For high-hazard chemicals, a reduced pressure assembly (RP) must be installed.
Model: Watts LF009-OT 1/2 Ordering Code: 0391002
UPC:098268051100
https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12
Mechanical - thread air gap
Model: 909AGA
UPC:098268235319
Ordering Code:0881399
Repair kit
Model: Watts RK009M2-T Ordering Code: 0887298
UPC: 098268538205
https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34
17 | P a g e
12a. Location: Building BR m: BB1:5B kitchen.
The coffee machine lacks a dual check valve and has a direct connection to the sewer.
for a dual check valve.
Dual check valve must be installed
Regarding the Dual Check Valves, you have 3 options
Dual Checks/Dual Checks with Atmospheric Vent
1.LF7U2-2 1 1/4X1 ¼
Ordering Code: 0792075
UPC: 098268434620
https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7u2-2-1-14x1-14
2.LF7-10-U2 1 1/4X1
OrderingCode:0792066
UPC: 098268434538
https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7-10-u2-1-14x1
3.LF7 3/8
Ordering Code:
0792076UPC: 098268434637
https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7-38 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7u2-2-1-14x1-14 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7u2-2-1-14x1-14 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7u2-2-1-14x1-14 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7u2-2-1-14x1-14 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7-10-u2-1-14x1 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7-10-u2-1-14x1 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7-10-u2-1-14x1 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7-10-u2-1-14x1 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7-38 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7-38 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7-38 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7-38
19 | P a g e
13a.
Location: CMR kitchen ground floor pantry.
The dishwasher's chemical feed system is missing a backflow preventer.
Model: Watts LF009-OT 1/2 Ordering Code: 0391002
UPC:098268051100
https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12
Mechanical - thread air gap
Model: 909AGA
UPC:098268235319
Ordering Code:0881399
Repair kit
Model: Watts RK009M2-T Ordering Code: 0887298
UPC: 098268538205
https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12
Model: Watts RK009M2-TOrdering Code:
0887302
UPC: 0982685455098
https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34
22 | P a g e
16a.
16a.
Location: CMR kitchen basement.
The dishwasher's chemical feed system is missing a backflow preventer.
Backflow reduced pressure assembly 1/2“must be installed between the water line and the chemical injection
Model: Watts LF009-OT 1/2 Ordering Code: 0391002
UPC:098268051100
https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12
Mechanical - thread air gap
Model: 909AGA
UPC:098268235319
Ordering Code:0881399
Repair kit
Model: Watts RK009M2-T Ordering Code: 0887298
UPC: 098268538205
https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12
Or
Backflow reduced pressure assembly 3/4” must be installed
Model: Watts LF009M3-QT 3/4 Ordering Code: 0390997
UPC: 098268177862
https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway
Mechanical - thread air gap
Model: 909AGC
UPC:098268104950
Ordering Code:0881376 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc
25 | P a g e
18. Location: CMR basement hall.
The water line connecting the Embassy water supply to the disinfection cleaning unit is equipped with a dual check valve. For high-hazard chemicals, a reduced pressure assembly (RP) must be installed.
for a Reduced Pressure Assembly
(RP).
Backflow reduced pressure assembly 1/2“must be installed between the water line and the chemical injection
Model: Watts LF009-OT 1/2 Ordering Code: 0391002
UPC:098268051100
https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12
Mechanical - thread air gap
Model: 909AGA
UPC:098268235319
Ordering Code:0881399
Repair kit Model: Watts RK009M2-T Ordering Code:
0887298UPC: 098268538205
https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12
26 | P a g e
19. Location: CMR main water room
The water line connecting the city and
Backflow reduced pressure assembly 4”
Model: ZURN WILKINS 4-375A
ITEM: 6CUN5
https://www.grainger.com/product/ZURN- WILKINS-Reduced-Pressure-Zone- Backflow-6CUN5
Repair kit
Model: RK4-375CK1 Item: 60AR88 https://www.grainger.com/product/ZURN- WILKINS-Valve-Repair-Kit-Valve-Repair- 60AR88?cpnuser=undefined&searchBar=t rue&searchQuery=rk4- 375ck1&suggestConfigId=6&tier=Tier+6
Model: RK4-350CK2 Item:801VG7 https://www.grainger.com/product/ZURN- WILKINS-Backflow-Preventer-Repair- 801VG7?searchQuery=rk4- 350ck2&searchBar=true&tier=Tier+6
Model: RK212-375 Item:20RJ46 https://www.grainger.com/product/ZURN- WILKINS-Valve-Repair-Kit-Valve-Repair-
20RJ46
https://www.grainger.com/product/ZURN-WILKINS-Reduced-Pressure-Zone-Backflow-6CUN5 https://www.grainger.com/product/ZURN-WILKINS-Reduced-Pressure-Zone-Backflow-6CUN5 https://www.grainger.com/product/ZURN-WILKINS-Reduced-Pressure-Zone-Backflow-6CUN5 https://www.grainger.com/product/ZURN-WILKINS-Valve-Repair-Kit-Valve-Repair-https://www.grainger.com/product/ZURN-WILKINS-Valve-Repair-Kit-Valve-Repair-https://www.grainger.com/product/ZURN-WILKINS-Backflow-Preventer-Repair-801VG7?searchQuery=rk4-350ck2&searchBar=true&tier=Tier+6 https://www.grainger.com/product/ZURN-WILKINS-Backflow-Preventer-Repair-801VG7?searchQuery=rk4-350ck2&searchBar=true&tier=Tier+6 https://www.grainger.com/product/ZURN-WILKINS-Backflow-Preventer-Repair-801VG7?searchQuery=rk4-350ck2&searchBar=true&tier=Tier+6 https://www.grainger.com/product/ZURN-WILKINS-Backflow-Preventer-Repair-801VG7?searchQuery=rk4-350ck2&searchBar=true&tier=Tier+6 https://www.grainger.com/product/ZURN-WILKINS-Valve-Repair-Kit-Valve-Repair-20RJ46 https://www.grainger.com/product/ZURN-WILKINS-Valve-Repair-Kit-Valve-Repair-20RJ46
27 | P a g e
20. Location: CMR SOUS STATION
CPCU
The Reduced Pressure Assembly (RP) did not pass the test. Test cock number 3 leaking.
Backflow preventer assembly 3/4” must be installed
Model: Watts LF009M3-QT 3/4 Ordering Code: 0390997
UPC: 098268177862
https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway
Mechanical - thread air gap
Model: 909AGC
UPC:098268104950
Ordering Code:0881376 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc
Repair kit
Model: Watts RK009M2-TOrdering Code:
0887302
UPC: 0982685455098
https://www.watts.com/products/plumbing-https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34
28 | P a g e
21a. Location: OECD Building annex A Galerie Technique Sans Issue Rm
The water line connecting the city and
Backflow reduced pressure assembly 1 1/2”” must be installed
Model: Watts LF009M2-QT-FS 1 1/2
UPC:098268349962
Ordering Code:88004114 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m2-qt-fs-1-12
Mechanical - thread air gap
Model: 909AGC-B
UPC:098268203561
Ordering Code:0881377 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc-b
Repair kit
Model: WATTSRK 009M2-T 1 1/4-1 ½ Ordering Code: 0887794
UPC: 098268538236
https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-1- 14-1-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m2-qt-fs-1-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m2-qt-fs-1-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m2-qt-fs-1-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m2-qt-fs-1-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc-b https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc-b https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc-b https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc-b https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-1-14-1-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-1-14-1-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-1-14-1-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-1-14-1-12
32 | P a g e
24. Location: OECD Building annex A did not pass the test.
Check valve 2 failed.
for a Reduced Pressure Assembly.
Drainage under the relief valve needs alignment.
Backflow reduced pressure assembly 3/4” must be installed
Model: Watts LF009M3-QT 3/4 Ordering Code: 0390997
UPC: 098268177862
https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway
Mechanical - thread air gap
Model: 909AGC
UPC:098268104950
Ordering Code:0881376 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc
Repair kit
Model: Watts RK009M2-T Ordering Code: 0887302
UPC: 0982685455098
https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34
Drainage under the relief valve needs alignment.
https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34
33 | P a g e
25. Location: OECD Building annex A did not pass the test. Check valve 2 failed.
The arrow symbol indicates the recommended installation location
Drainage under the relief valve needs alignment.
Backflow reduced pressure assembly 3/4” must be installed
Model: Watts LF009M3-QT 3/4 Ordering Code: 0390997
UPC: 098268177862
https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway
Mechanical - thread air gap
Model: 909AGC
UPC:098268104950
Ordering Code:0881376 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc
Repair kit
Model: Watts RK009M2-T Ordering Code: 0887302
UPC: 0982685455098
https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34
Drainage under the relief valve needs alignment.
https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34
34 | P a g e
26. Location: Boulogne building
The Reduced Pressure Assembly (RP) did not pass the test. Check valve 2 failed.
The arrow symbol indicates the recommended installation location for a Reduced
Pressure Assembly (RP).
Model: Watts LF009M3-QT 3/4 Ordering Code: 0390997
UPC: 098268177862
https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway
Mechanical - thread air gap
Model: 909AGC
UPC:098268104950
Ordering Code:0881376 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc
Repair kit
Model: Watts RK009M2-T Ordering Code: 0887302
UPC: 0982685455098
https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34
35 | P a g e
27. Location: Neuilly Residence.
The Reduced Pressure Assembly (RP) did not pass the test. Relief valve failed.
The arrow symbol indicates the recommended installation location
Backflow reduced pressure assembly 3”
Model: Reduced Pressure Zone Backflow Preventer: ZURN WILKINS 375A, 3 in, Flanged x Flanged, 36 1/8 in Lg
Item: 6AVY5 Mfr. Model: 3-375A https://www.grainger.com/product/ZURN- WILKINS-Reduced-Pressure-Zone- Backflow-6AVY5
Repair kit
Model: RK4-375CK1 Item: 60AR88 https://www.grainger.com/product/ZURN-
WILKINS-Valve-Repair-Kit-Valve-Repair-
60AR88
Mfr. Model: RK4-350CK2 Item 801VG7 https://www.grainger.com/product/ZURN- WILKINS-Backflow-Preventer-Repair-
801VG7
Model: RK212-375 Item:20RJ46 https://www.grainger.com/product/ZURN- WILKINS-Valve-Repair-Kit-Valve-Repair-
20RJ46
https://www.grainger.com/product/ZURN-WILKINS-Reduced-Pressure-Zone-Backflow-6AVY5 https://www.grainger.com/product/ZURN-WILKINS-Reduced-Pressure-Zone-Backflow-6AVY5 https://www.grainger.com/product/ZURN-WILKINS-Reduced-Pressure-Zone-Backflow-6AVY5 https://www.grainger.com/product/ZURN-WILKINS-Valve-Repair-Kit-Valve-Repair-60AR88 https://www.grainger.com/product/ZURN-WILKINS-Valve-Repair-Kit-Valve-Repair-60AR88 https://www.grainger.com/product/ZURN-WILKINS-Valve-Repair-Kit-Valve-Repair-60AR88 https://www.grainger.com/product/ZURN-WILKINS-Backflow-Preventer-Repair-801VG7 https://www.grainger.com/product/ZURN-WILKINS-Backflow-Preventer-Repair-801VG7 https://www.grainger.com/product/ZURN-WILKINS-Backflow-Preventer-Repair-801VG7 https://www.grainger.com/product/ZURN-WILKINS-Valve-Repair-Kit-Valve-Repair-20RJ46
36 | P a g e
28. Location: Neuilly Residence
(RP) did not pass the test. Check valve 2 failed.
The arrow symbol indicates the recommended installation location
Model: Watts LF009M3-QT 3/4 Ordering Code: 0390997
UPC: 098268177862
https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway
Mechanical - thread air gap
Model: 909AGC
UPC:098268104950
Ordering Code:0881376 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc
Repair kit
Model: Watts RK009M2-T Ordering Code: 0887302
UPC: 0982685455098
https://www.watts.com/products/plumbing-https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34
37 | P a g e
29a. Location: Car wash chancery building
The car wash area is not equipped with a Reduced Pressure Assembly (RP), and the drain is directly connected to the sewer line.
Therefore, it is necessary to install a Reduced Pressure Assembly (RP) and air gap.
for a Reduced Pressure Assembly.
Model: Watts LF009M3-QT 3/4 Ordering Code: 0390997
UPC: 098268177862
https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway
Mechanical - thread air gap
Model: 909AGC
UPC:098268104950
Ordering Code:0881376 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc
Repair kit
Model: WATTS RK009M2-T Ordering Code: 0887302
UPC: 0982685455098
https://www.watts.com/products/plumbing-https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34
38 | P a g e
30. Location: Leopold II
(RP) did not pass the test. Test cock 4 is damaged.
Model: Watts LF009M3-QT 3/4 Ordering Code: 0390997
UPC: 098268177862
https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway
Mechanical - thread air gap
Model: 909AGC
UPC:098268104950
Ordering Code:0881376 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc
Repair kit
Model: Watts RK009M2-T Ordering Code: 0887302
UPC: 0982685455098
https://www.watts.com/products/plumbing-https://www.watts.com/products/plumbing-flow-control-so…