Attachment 5 - Trip report - France Paris US Embassy April 15-19-2024 - Backflow Prevention Assembly Inspection and Maintenance.pdf

PDF 1 MB Posted

Attached to
Backflow Deficiencies Prevention In 9 Buildings located in Paris, Boulogne and Neuilly-sur-Seine
Solicitation number
19FR6325Q0034
Issued by

About this file

This document is a detailed trip report for a backflow prevention assembly inspection conducted at the U.S. Embassy in Paris, France from April 15-19, 2024. The inspection covered nine locations including the Embassy compound, Boulogne, Neuilly Residence, CMR, OECD, Weber, Leopold II, GMC, and Deschanel, revealing multiple critical backflow prevention deficiencies.

Key findings include the need to install 24 Reduced Pressure Assemblies (RP), replace eleven existing RPs that failed backflow tests, and address multiple plumbing safety issues such as water softeners directly connected to sewer lines, coffee machines lacking proper valves, ice maker drains improperly connected, and dishwashers without required backflow prevention. The report provides specific recommendations for each location, including precise model numbers for replacement backflow prevention assemblies from manufacturers like Watts and Zurn Wilkins, along with detailed product links, ordering codes, and repair kit specifications. The inspection was conducted using a Mid-West Instrument 835 Back-flow Test Kit and involved embassy contacts including the Senior Facility Manager, Deputy Facility Manager, Data Analyst, and Plumber.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1 | P a g e

U.S Embassy the Hague Date 4/29/2024 Moros Evangelos

TRIP REPORT - BACKFLOW PREVENTION ASSEMBLY INSPECTION AND

MAINTENANCE

FROM: THE HAGUE US EMBASSY-MOROS EVANGELOS

SUBJECT: Trip report – France, Paris US Embassy, April 15-19-2024

OVERVIEW AND PURPOSE OF THE TRIP

According to the International Plumbing Code (IPC), each backflow-prevention assembly is required to be tested at least annually.

EXECUTIVE SUMMARY

• The inspection covered nine locations: the Embassy compound, Boulogne, Neuilly Residence, CMR, OECD, Weber, Leopold II, GMC, and Deschanel.

• It is recommended to install Reduced Pressure Assembly (RP) in 24 locations.

• Eleven Reduced Pressure Assembly (RP) were discovered, but all failed the backflow test.

• Five water softeners are connected directly to the sewer line. Air gaps must be installed.

• One coffee machine is not equipped with a Dual Check valve, and the drain is directly connected to the sewer line. Therefore, it is necessary to install a Dual Check Valve and air gap.

• One coffee machine is equipped with a Dual Check valve and air gap, which means it is compliant.

• Six ice maker drains are directly connected to the sewer line.

Therefore, an air gap must be installed.

• Six dishwashers are using a chemical feed system and do not have a Reduced Pressure Assembly (RP) installed. Additionally, their drain is directly connected to the sewer line, which poses a safety concern.

Therefore, it is necessary to install a Reduced Pressure Assembly (RP) and air gap to ensure the safety of the system.

• The car wash area is not equipped with a Reduced Pressure Assembly (RP), and the drain is directly connected to the sewer line.

Therefore, it is necessary to install a Reduced Pressure Assembly (RP) and air gap.

• Three disinfection cleaning units have dual check valves. However, to ensure the safety of the drinking water supply, a Reduced Pressure Assembly (RP) and air gap for high-hazard chemicals must be

2 | P a g e installed between the disinfection cleaning unit and the main water supply.

• It is recommended to install a hose bibb vacuum breaker on every hose bibb to prevent the backflow of contaminated water into the main water supply.

At the Embassy, several techniques are available for measuring the size of water pipes, as different people use different methods. The Embassy generally measures nominal pipe size

(NPS) in inches, while European pipe sizes are designated in millimeters as diameter nominal (DN) under the ISO standard. The term nominal bore (NB) is also sometimes used interchangeably. This report will use NPS (inches) to refer to pipe sizes. The Embassy is strongly advised to verify all pipe diameters before ordering the backflow preventer assembly or devices.

General Installation Details

• The installation guidelines stated in this report must comply with the U.S. National Plumbing Code.

• All Reduced Pressure Assemblies (RP) shall be installed between 12 and 36 inches above the floor or finished grade, with enough clearance for easy testing and maintenance. A fixed platform, portable scaffold, or lift that meets OSHA standards must be provided if installed at a greater height.

• Account for required sided clearance from the wall of Double Check and Reduced

Pressure Assemblies (1/2"-3") are 24" from side test cocks, 12" from top mounted test cocks, with 24" access from one side. For sizes 4" and above, double these requirements.

Drainage

• Drainage for backflow prevention assemblies shall be provided for all installations of DCV or RP to accommodate discharge during testing or draining of the unit and for RP relief valve discharges, as follows:

• Discharge from relief valves must be readily detectable to maintenance personnel either visually or using water level alarms, flow indicator lights, etc.

• All drainage from Reduced Pressure Assembly (RP) must be by gravity drains.

• An air gap between the RP relief valve opening and discharge piping must be maintained. The air gap must be at least twice the dimension of the relief valve's effective opening but in no case less than 1 inch.

• The manufacturer's air gap fittings may be utilized, provided they maintain a proper air gap and do not enclose or cover the relief valve. These fittings are only sized to handle intermittent and low-flow discharges. Additional drainage capacity may be required to accommodate a catastrophic relief valve failure.

3 | P a g e

EMBASSY CONTACTS

The following individuals were contacted and provided information during the site visit.

• David Scovill: Senior Facility Manager

• Carl Vimmerstedt: Deputy Facility Manager

• Silke Klassens: Data Analyst

• Usta Suleyman: Plumber

On the final day, during the out-brief with Senior Facility Manager David Scovill, an action plan was discussed.

SITE VISIT OBSERVATIONS

Inspector work tools for site visit:

• Back-flow Test Kit Mid-West Instrument 835

4 | P a g e

ASSESSMENT AND RECOMMENDATIONS

ISSUE DESCRIPTION RECOMMENDATIONS

1.

Location: Chancery Building

Basement Rm AB1:01A4A

The water line connecting the city and the Embassy did not have a Reduced Pressure Assembly (RP) installed.

The arrow symbol is used to indicate the recommended installation location for a Reduced

Pressure Assembly (RP).

Backflow reduced pressure assembly 3” must be installed

Model: WATTS LF909-DOSY-FS 3 Ordering Code: 88009313

UPC: 098268291629

https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf909-large/lf909-dosy-fs-3

Repair kit

Model Watts

LFRK 909-CK1 2 1/2-3

Ordering code: 0794096

UPC:09826845933

https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck1- 2-12-3

LFRK 909-CK2 2 1/2-3

Ordering code:0794101

UPC:09826845938

https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck2- 2-12-3

LFRK909-S 3

Ordering code:079410

UPC:09826845943

https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk909-s-3

RK 909-RC1 2 1/2-3

Ordering code: 088722

UPC: 09826841457

https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc1-2- 12-3

RK 909-RC2 2 1/2-3

https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf909-large/lf909-dosy-fs-3 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf909-large/lf909-dosy-fs-3 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf909-large/lf909-dosy-fs-3 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf909-large/lf909-dosy-fs-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck1-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck1-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck1-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck1-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk909-s-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk909-s-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk909-s-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc1-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc1-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc1-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc1-2-12-3

5 | P a g e

1.

Ordering Code: 0887226

UPC: 098268414622

https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc2-2- 12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc2-2-12-3

6 | P a g e

2.

Location: Building B Rm B-1 45

The water line connecting the city and

The arrow symbol is used to indicate the recommended installation location for a Reduced

Pressure Assembly (RP).

Backflow reduced pressure assembly 3” must be installed

Model: Watts LF909-DOSY-FS 3 Ordering Code: 88009313

UPC: 098268291629

https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf909-large/lf909-dosy-fs-3

Repair kit

Model: Watts

LFRK 909-CK1 2 1/2-3

Ordering code: 0794096

UPC:09826845933

https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck1- 2-12-3

LFRK 909-CK2 2 1/2-3

Ordering code:0794101

UPC:09826845938

https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck2- 2-12-3

LFRK909-S 3

Orderingcode:079410

UPC:09826845943

https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk909-s-3

RK 909-RC1 2 1/2-3

Ordering code: 088722

UPC: 09826841457

https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc1-2- 12-3

RK 909-RC2 2 1/2-3

Ordering Code: 0887226

UPC: 098268414622

https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf909-large/lf909-dosy-fs-3 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf909-large/lf909-dosy-fs-3 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf909-large/lf909-dosy-fs-3 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf909-large/lf909-dosy-fs-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk909-s-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk909-s-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk909-s-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc1-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc1-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc1-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc1-2-12-3

7 | P a g e

2.

https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc2-2- 12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc2-2-12-3

8 | P a g e

3. Location: Building B Cloakroom

The Reduced Pressure Assembly (RP) did not pass the test. Check valve 2 failed.

The arrow symbol is used to indicate the recommended installation location for a Reduced Pressure

Assembly (RP).

Backflow reduced pressure assembly 3/4” must be installed.

Model: Watts LF009M3-QT 3/4 Ordering Code: 0390997

UPC: 098268177862

https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway

Mechanical – thread air gap

Model: 909AGC

UPC:098268104950

Ordering Code:0881376 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc

Repair kit

Model: Watts RK009M2-T Ordering Code: 0887302

UPC: 0982685455098

https://www.watts.com/products/plumbing-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34

9 | P a g e

4. Location: Building B Rm BB1: 9A

Coffee machine has a Dual Check valve installed that is not testable. No assessable for data information.

The arrow symbol indicates the dual check valve.

No recommendation. The coffee machine is in compliant.

12 | P a g e

ISSUE

DESCRIPTION RECOMMENDATIONS

7.

Location: Building: BB1:5B kitchen

The chemical feed system is missing a backflow preventer.

The arrow symbol indicates the recommended installation location for a Reduced Pressure Assembly

(RP).

Backflow reduced pressure assembly 1/2”

Model: Watts LF009-OT 1/2 Ordering Code: 0391002

UPC:098268051100

https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12

Mechanical - thread air gap

Model: 909AGA

UPC:098268235319

Ordering Code:0881399 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909aga

Repair kit

Model: Watts RK009M2-T Ordering Code: 0887298

UPC: 098268538205

https://www.watts.com/products/plumbing-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909aga https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909aga https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909aga https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909aga https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12

16 | P a g e

11.

Location: Building B Rm: BB1:5B kitchen.

The water line connecting the Embassy water supply to the disinfection cleaning unit is equipped with a dual check valve. For high-hazard chemicals, a reduced pressure assembly (RP) must be installed.

Model: Watts LF009-OT 1/2 Ordering Code: 0391002

UPC:098268051100

https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12

Mechanical - thread air gap

Model: 909AGA

UPC:098268235319

Ordering Code:0881399

Repair kit

Model: Watts RK009M2-T Ordering Code: 0887298

UPC: 098268538205

https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34

17 | P a g e

12a. Location: Building BR m: BB1:5B kitchen.

The coffee machine lacks a dual check valve and has a direct connection to the sewer.

for a dual check valve.

Dual check valve must be installed

Regarding the Dual Check Valves, you have 3 options

Dual Checks/Dual Checks with Atmospheric Vent

1.LF7U2-2 1 1/4X1 ¼

Ordering Code: 0792075

UPC: 098268434620

https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7u2-2-1-14x1-14

2.LF7-10-U2 1 1/4X1

OrderingCode:0792066

UPC: 098268434538

https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7-10-u2-1-14x1

3.LF7 3/8

Ordering Code:

0792076UPC: 098268434637

https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7-38 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7u2-2-1-14x1-14 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7u2-2-1-14x1-14 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7u2-2-1-14x1-14 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7u2-2-1-14x1-14 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7-10-u2-1-14x1 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7-10-u2-1-14x1 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7-10-u2-1-14x1 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7-10-u2-1-14x1 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7-38 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7-38 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7-38 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/dual-checksdual-checks-with-atmospheric-vent/lf7/lf7-38

19 | P a g e

13a.

Location: CMR kitchen ground floor pantry.

The dishwasher's chemical feed system is missing a backflow preventer.

Model: Watts LF009-OT 1/2 Ordering Code: 0391002

UPC:098268051100

https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12

Mechanical - thread air gap

Model: 909AGA

UPC:098268235319

Ordering Code:0881399

Repair kit

Model: Watts RK009M2-T Ordering Code: 0887298

UPC: 098268538205

https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12

Model: Watts RK009M2-TOrdering Code:

0887302

UPC: 0982685455098

https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34

22 | P a g e

16a.

16a.

Location: CMR kitchen basement.

The dishwasher's chemical feed system is missing a backflow preventer.

Backflow reduced pressure assembly 1/2“must be installed between the water line and the chemical injection

Model: Watts LF009-OT 1/2 Ordering Code: 0391002

UPC:098268051100

https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12

Mechanical - thread air gap

Model: 909AGA

UPC:098268235319

Ordering Code:0881399

Repair kit

Model: Watts RK009M2-T Ordering Code: 0887298

UPC: 098268538205

https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12

Or

Backflow reduced pressure assembly 3/4” must be installed

Model: Watts LF009M3-QT 3/4 Ordering Code: 0390997

UPC: 098268177862

https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway

Mechanical - thread air gap

Model: 909AGC

UPC:098268104950

Ordering Code:0881376 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc

25 | P a g e

18. Location: CMR basement hall.

The water line connecting the Embassy water supply to the disinfection cleaning unit is equipped with a dual check valve. For high-hazard chemicals, a reduced pressure assembly (RP) must be installed.

for a Reduced Pressure Assembly

(RP).

Backflow reduced pressure assembly 1/2“must be installed between the water line and the chemical injection

Model: Watts LF009-OT 1/2 Ordering Code: 0391002

UPC:098268051100

https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12

Mechanical - thread air gap

Model: 909AGA

UPC:098268235319

Ordering Code:0881399

Repair kit Model: Watts RK009M2-T Ordering Code:

0887298UPC: 098268538205

https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009-qt-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009-t-14-12

26 | P a g e

19. Location: CMR main water room

The water line connecting the city and

Backflow reduced pressure assembly 4”

Model: ZURN WILKINS 4-375A

ITEM: 6CUN5

https://www.grainger.com/product/ZURN- WILKINS-Reduced-Pressure-Zone- Backflow-6CUN5

Repair kit

Model: RK4-375CK1 Item: 60AR88 https://www.grainger.com/product/ZURN- WILKINS-Valve-Repair-Kit-Valve-Repair- 60AR88?cpnuser=undefined&searchBar=t rue&searchQuery=rk4- 375ck1&suggestConfigId=6&tier=Tier+6

Model: RK4-350CK2 Item:801VG7 https://www.grainger.com/product/ZURN- WILKINS-Backflow-Preventer-Repair- 801VG7?searchQuery=rk4- 350ck2&searchBar=true&tier=Tier+6

Model: RK212-375 Item:20RJ46 https://www.grainger.com/product/ZURN- WILKINS-Valve-Repair-Kit-Valve-Repair-

20RJ46

https://www.grainger.com/product/ZURN-WILKINS-Reduced-Pressure-Zone-Backflow-6CUN5 https://www.grainger.com/product/ZURN-WILKINS-Reduced-Pressure-Zone-Backflow-6CUN5 https://www.grainger.com/product/ZURN-WILKINS-Reduced-Pressure-Zone-Backflow-6CUN5 https://www.grainger.com/product/ZURN-WILKINS-Valve-Repair-Kit-Valve-Repair-https://www.grainger.com/product/ZURN-WILKINS-Valve-Repair-Kit-Valve-Repair-https://www.grainger.com/product/ZURN-WILKINS-Backflow-Preventer-Repair-801VG7?searchQuery=rk4-350ck2&searchBar=true&tier=Tier+6 https://www.grainger.com/product/ZURN-WILKINS-Backflow-Preventer-Repair-801VG7?searchQuery=rk4-350ck2&searchBar=true&tier=Tier+6 https://www.grainger.com/product/ZURN-WILKINS-Backflow-Preventer-Repair-801VG7?searchQuery=rk4-350ck2&searchBar=true&tier=Tier+6 https://www.grainger.com/product/ZURN-WILKINS-Backflow-Preventer-Repair-801VG7?searchQuery=rk4-350ck2&searchBar=true&tier=Tier+6 https://www.grainger.com/product/ZURN-WILKINS-Valve-Repair-Kit-Valve-Repair-20RJ46 https://www.grainger.com/product/ZURN-WILKINS-Valve-Repair-Kit-Valve-Repair-20RJ46

27 | P a g e

20. Location: CMR SOUS STATION

CPCU

The Reduced Pressure Assembly (RP) did not pass the test. Test cock number 3 leaking.

Backflow preventer assembly 3/4” must be installed

Model: Watts LF009M3-QT 3/4 Ordering Code: 0390997

UPC: 098268177862

https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway

Mechanical - thread air gap

Model: 909AGC

UPC:098268104950

Ordering Code:0881376 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc

Repair kit

Model: Watts RK009M2-TOrdering Code:

0887302

UPC: 0982685455098

https://www.watts.com/products/plumbing-https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34

28 | P a g e

21a. Location: OECD Building annex A Galerie Technique Sans Issue Rm

The water line connecting the city and

Backflow reduced pressure assembly 1 1/2”” must be installed

Model: Watts LF009M2-QT-FS 1 1/2

UPC:098268349962

Ordering Code:88004114 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m2-qt-fs-1-12

Mechanical - thread air gap

Model: 909AGC-B

UPC:098268203561

Ordering Code:0881377 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc-b

Repair kit

Model: WATTSRK 009M2-T 1 1/4-1 ½ Ordering Code: 0887794

UPC: 098268538236

https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-1- 14-1-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m2-qt-fs-1-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m2-qt-fs-1-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m2-qt-fs-1-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m2-qt-fs-1-12 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc-b https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc-b https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc-b https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc-b https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-1-14-1-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-1-14-1-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-1-14-1-12 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-1-14-1-12

32 | P a g e

24. Location: OECD Building annex A did not pass the test.

Check valve 2 failed.

for a Reduced Pressure Assembly.

Drainage under the relief valve needs alignment.

Backflow reduced pressure assembly 3/4” must be installed

Model: Watts LF009M3-QT 3/4 Ordering Code: 0390997

UPC: 098268177862

https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway

Mechanical - thread air gap

Model: 909AGC

UPC:098268104950

Ordering Code:0881376 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc

Repair kit

Model: Watts RK009M2-T Ordering Code: 0887302

UPC: 0982685455098

https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34

Drainage under the relief valve needs alignment.

https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34

33 | P a g e

25. Location: OECD Building annex A did not pass the test. Check valve 2 failed.

The arrow symbol indicates the recommended installation location

Drainage under the relief valve needs alignment.

Backflow reduced pressure assembly 3/4” must be installed

Model: Watts LF009M3-QT 3/4 Ordering Code: 0390997

UPC: 098268177862

https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway

Mechanical - thread air gap

Model: 909AGC

UPC:098268104950

Ordering Code:0881376 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc

Repair kit

Model: Watts RK009M2-T Ordering Code: 0887302

UPC: 0982685455098

https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34

Drainage under the relief valve needs alignment.

https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34

34 | P a g e

26. Location: Boulogne building

The Reduced Pressure Assembly (RP) did not pass the test. Check valve 2 failed.

The arrow symbol indicates the recommended installation location for a Reduced

Pressure Assembly (RP).

Model: Watts LF009M3-QT 3/4 Ordering Code: 0390997

UPC: 098268177862

https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway

Mechanical - thread air gap

Model: 909AGC

UPC:098268104950

Ordering Code:0881376 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc

Repair kit

Model: Watts RK009M2-T Ordering Code: 0887302

UPC: 0982685455098

https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34

35 | P a g e

27. Location: Neuilly Residence.

The Reduced Pressure Assembly (RP) did not pass the test. Relief valve failed.

The arrow symbol indicates the recommended installation location

Backflow reduced pressure assembly 3”

Model: Reduced Pressure Zone Backflow Preventer: ZURN WILKINS 375A, 3 in, Flanged x Flanged, 36 1/8 in Lg

Item: 6AVY5 Mfr. Model: 3-375A https://www.grainger.com/product/ZURN- WILKINS-Reduced-Pressure-Zone- Backflow-6AVY5

Repair kit

Model: RK4-375CK1 Item: 60AR88 https://www.grainger.com/product/ZURN-

WILKINS-Valve-Repair-Kit-Valve-Repair-

60AR88

Mfr. Model: RK4-350CK2 Item 801VG7 https://www.grainger.com/product/ZURN- WILKINS-Backflow-Preventer-Repair-

801VG7

Model: RK212-375 Item:20RJ46 https://www.grainger.com/product/ZURN- WILKINS-Valve-Repair-Kit-Valve-Repair-

20RJ46

https://www.grainger.com/product/ZURN-WILKINS-Reduced-Pressure-Zone-Backflow-6AVY5 https://www.grainger.com/product/ZURN-WILKINS-Reduced-Pressure-Zone-Backflow-6AVY5 https://www.grainger.com/product/ZURN-WILKINS-Reduced-Pressure-Zone-Backflow-6AVY5 https://www.grainger.com/product/ZURN-WILKINS-Valve-Repair-Kit-Valve-Repair-60AR88 https://www.grainger.com/product/ZURN-WILKINS-Valve-Repair-Kit-Valve-Repair-60AR88 https://www.grainger.com/product/ZURN-WILKINS-Valve-Repair-Kit-Valve-Repair-60AR88 https://www.grainger.com/product/ZURN-WILKINS-Backflow-Preventer-Repair-801VG7 https://www.grainger.com/product/ZURN-WILKINS-Backflow-Preventer-Repair-801VG7 https://www.grainger.com/product/ZURN-WILKINS-Backflow-Preventer-Repair-801VG7 https://www.grainger.com/product/ZURN-WILKINS-Valve-Repair-Kit-Valve-Repair-20RJ46

36 | P a g e

28. Location: Neuilly Residence

(RP) did not pass the test. Check valve 2 failed.

The arrow symbol indicates the recommended installation location

Model: Watts LF009M3-QT 3/4 Ordering Code: 0390997

UPC: 098268177862

https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway

Mechanical - thread air gap

Model: 909AGC

UPC:098268104950

Ordering Code:0881376 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc

Repair kit

Model: Watts RK009M2-T Ordering Code: 0887302

UPC: 0982685455098

https://www.watts.com/products/plumbing-https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34

37 | P a g e

29a. Location: Car wash chancery building

The car wash area is not equipped with a Reduced Pressure Assembly (RP), and the drain is directly connected to the sewer line.

Therefore, it is necessary to install a Reduced Pressure Assembly (RP) and air gap.

for a Reduced Pressure Assembly.

Model: Watts LF009M3-QT 3/4 Ordering Code: 0390997

UPC: 098268177862

https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway

Mechanical - thread air gap

Model: 909AGC

UPC:098268104950

Ordering Code:0881376 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc

Repair kit

Model: WATTS RK009M2-T Ordering Code: 0887302

UPC: 0982685455098

https://www.watts.com/products/plumbing-https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34

38 | P a g e

30. Location: Leopold II

(RP) did not pass the test. Test cock 4 is damaged.

Model: Watts LF009M3-QT 3/4 Ordering Code: 0390997

UPC: 098268177862

https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway

Mechanical - thread air gap

Model: 909AGC

UPC:098268104950

Ordering Code:0881376 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc

Repair kit

Model: Watts RK009M2-T Ordering Code: 0887302

UPC: 0982685455098

https://www.watts.com/products/plumbing-https://www.watts.com/products/plumbing-flow-control-so…