SF30 - Amendment A0002.pdf

PDF 2 MB Posted

Attached to
Backflow Deficiencies Prevention In 9 Buildings located in Paris, Boulogne and Neuilly-sur-Seine
Solicitation number
19FR6325Q0034
Issued by

About this file

This document is an Amendment of Solicitation (Standard Form 30) for a Request for Quote (RFQ) 19FR6325Q0034 for backflow deficiencies' prevention in 9 buildings located in Paris, Boulogne, and Neuilly-sur-Seine, France. The amendment, dated September 2, 2025, provides additional site visit pictures and revises requirements in the trip report attachment. Key findings from the site inspection include multiple locations requiring backflow prevention assembly installations or repairs, such as Building B Room B-1-45 needing a 3" Reduced Pressure (RP) Assembly (Watts LF909-DOSY-FS 3 model) and the CMR Sous Station CPCU requiring a 3/4" backflow preventer assembly (Watts LF009M3-QT 3/4 model). The solicitation is issued by the Contracts Office at the American Embassy in Paris, with the contracting officer identified as Craig N. Deatrick.

The site visit documentation includes detailed photographic evidence of existing plumbing configurations in various buildings, highlighting specific valve locations, potential backflow risks, and recommended mitigation strategies. Each identified issue is accompanied by precise product recommendations, including specific manufacturer models, ordering codes, UPC numbers, and links to product specifications. The amendment indicates that while some locations require new installations or repairs, others like the coffee machine in Building B Room BB1:9A are considered compliant. The comprehensive report provides technical details to support the procurement of necessary backflow prevention equipment across multiple embassy buildings in the Paris area.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE

PAGE OF PAGES

1/10

2. AMENDMENT/MODIFICATION NO.

19FR6325Q0034-A0002

3. EFFECTIVE DATE

September 2, 2025

4. REQUISITION/PURCHASE REQ. NO.

PR15370914

5. PROJECT NO. (If applicable)

6. ISSUED BY

CODE

7. ADMINISTERED BY (If other than Item 6)

CODE

Contracts Office A-M8, American Embassy, 2 Ave Gabriel, 75008 Paris

8. NAME AND ADDRESS OF CONTRACTOR (NO., street,city,county,State,and ZIP Code)

X

9a. AMENDMENT OF SOLICITATION NO.

19FR6325Q0034

9b. DATED (SEE ITEM 11)

July 30, 2025

10a. MODIFICATION OF CONTRACT/ORDER NO.

10b. DATED (SEE ITEM 13)

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

[ x ] The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

[ ] [ X ] is not extended Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods: (a) By completing Items 8 and 15, and returning ____1___ copies of the amendment;(b) By acknowledging receipt of this amendment on each copy of the offer submitted; or(c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers.

FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (If required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE

CONTRACT ORDER NO. IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b)

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor [ ] is not, [ X ] is required to sign this document and return ___ copies to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

The purpose of this amendment is to:

- Provide additional pictures following the site visit

- Revise the requirements in the “Attachment 5 - Trip report - France, Paris US Embassy, April 15-19-2024 - Backflow

Prevention Assembly Inspection and Maintenance” as shown in red and strikethrough in this document

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER (Type or print) 16A. NAME OF CONTRACTING OFFICER

CRAIG N. DEATRICK

15B. NAME OF CONTRACTOR/OFFEROR

BY

(Signature of person authorized to sign)

15C.DATE SIGNED 16B. UNITED STATES OF AMERICA

BY

(Signature of Contracting Officer)

16C.DATE SIGNED

NSN 7540-01-152-8070 Standard Form 30 (revised 10/83) Previous edition unusable Prescribed by GSA FAR (48 CFR

RFQ 19FR6325Q0034 - Backflow deficiencies' prevention in 9 buildings located in Paris, Boulogne and Neuilly-sur-Seine, France

RFQ 19FR6325Q0034 - Backflow deficiencies' prevention in 9 buildings located in Paris, Boulogne and Neuilly-sur-Seine, France

A BUILDING

PICTURES TAKEN DURING THE SITE VISIT

RFQ 19FR6325Q0034 - Backflow deficiencies' prevention in 9 buildings located in Paris, Boulogne and Neuilly-sur-Seine, France

B BUILDING

RFQ 19FR6325Q0034 - Backflow deficiencies' prevention in 9 buildings located in Paris, Boulogne and Neuilly-sur-Seine, France

CMR

RFQ 19FR6325Q0034 - Backflow deficiencies' prevention in 9 buildings located in Paris, Boulogne and Neuilly-sur-Seine, France

RFQ 19FR6325Q0034 - Backflow deficiencies' prevention in 9 buildings located in Paris, Boulogne and Neuilly-sur-Seine, France

6 | P a g e

ISSUE DESCRIPTION RECOMMENDATIONS

2. Location: Building B Rm B-1 45

The water line connecting the city and the Embassy did not have a Reduced Pressure Assembly (RP) installed.

The arrow symbol is used to indicate the recommended installation location for a

Reduced Pressure Assembly

(RP).

Backflow reduced pressure assembly 3” must be installed

Model: Watts LF909-DOSY-FS 3 Ordering Code: 88009313

UPC: 098268291629

https://www.watts.com/products/ plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf909-large/lf909-dosy-fs-3

Repair kit

Model: Watts

LFRK 909-CK1 2 1/2-3

Ordering code: 0794096

UPC:09826845933

https://www.watts.com/products/ plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck1-2-12-3

LFRK 909-CK2 2 1/2-3

Ordering code:0794101

UPC:09826845938

https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck2- 2-12-3

LFRK909-S 3

Orderingcode:07941

0 UPC:09826845943

https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk909-s-3

RK 909-RC1 2 1/2-3

Ordering code:

088722 UPC:

09826841457 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc1-2- 12-3

RK 909-RC2 2 1/2-3

Ordering Code:

0887226 UPC:

098268414622

Pages 6, 7, 9 & 27 of Attachment 5 - Trip report - France, Paris US Embassy, April 15-19-2024 - Backflow

Prevention Assembly Inspection and Maintenance https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf909-large/lf909-dosy-fs-3 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf909-large/lf909-dosy-fs-3 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf909-large/lf909-dosy-fs-3 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf909-large/lf909-dosy-fs-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk-909-ck2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk909-s-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk909-s-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-lf909/lfrk909-s-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc1-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc1-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc1-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc1-2-12-3 SagboTU Cross-Out

SagboTU Line

SagboTU Line

7 | P a g e

2.

https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc2-2- 12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc2-2-12-3 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-909/rk-909-rc2-2-12-3 SagboTU Cross-Out

SagboTU Line

9 | P a g e

4. Location: Building B Rm BB1: 9A

Coffee machine has a Dual Check valve installed that is not testable. No assessable for data information.

The arrow symbol indicates the dual check valve.

No recommendation. The coffee machine is in compliant.

SagboTU Cross-Out

SagboTU Line

27 | P a g e

20. Location: CMR SOUS

STATION CPCU

The Reduced Pressure Assembly (RP) did not pass the test. Test cock number 3 leaking.

The arrow symbol indicates the recommended installation location for a Reduced Pressure

Assembly (RP).

Backflow preventer assembly 3/4” must be installed

Model: Watts LF009M3-QT 3/4 Ordering Code: 0390997

UPC: 098268177862

https://www.watts.com/products/ plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway

Mechanical - thread air gap

Model: 909AGC

UPC:098268104950

Ordering Code:0881376 https://www.watts.com/products/ plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc

Repair kit

Model: Watts RK009M2-TOrdering Code:

0887302

UPC: 0982685455098

https://www.watts.com/products/ plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/reduced-pressure-zone-assemblies/lf009/lf009m3-qt-34-cutaway https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/backflow-preventers/backflow-preventer-accessories/air-gaps-watts/909agc https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 https://www.watts.com/products/plumbing-flow-control-solutions/repair-kits/backflow-preventer-repair-kits/rk-009/rk-009m2-t-34 SagboTU Cross-Out

SagboTU Line

SF30 - Amendment A0002
Attachment 5 - Trip report - France, Paris US Embassy, April 15-19-2024 - Backflow Prevention Assembly Inspection and Maintenance