Attachment 5 - SSB Building Elevator Modernization Specification Summary.pdf
PDF 343 KB Posted
- Attached to
- Elevator Maintenance Services
- Solicitation number
- RFP AAGA 2027000019 1
- Issued by
- Denver County, Denver City, Colorado
About this file
This is a Scope of Work Summary specification document for the State of Colorado's State Services Building located at 1525 Sherman Street in Denver, Colorado, detailing elevator modernization work under Project 2024-070M23. The project encompasses the replacement of car door operators and hoistway door equipment, renovation of elevator cabs, and installation of new limited access hall push button stations with security card readers on four passenger elevators and one freight elevator. The elevators operate at 500 feet per minute with 3,000-pound capacity, with Cars 1 and 3 featuring eight front openings each, Car 2 featuring nine front openings, and Car 4 (freight) featuring nine front and nine rear openings, traveling approximately 80 feet with a four-car group GAL Galaxy system. Work includes removal of existing Montgomery MAC hoistway door equipment and car door operators, installation of new GAL or approved equal components, retention of existing Otis DC gearless hoist machine controllers and SCR motor drive units, installation of new traveling cables and wiring, refinishing of bronze hoistway entrances, and installation of new elevator cab interiors.
The specification summary indicates that the existing hoistway doors and entrances will be retained with refinished bronze panels on the main floor. Cab renovations include installation of new Snap Cab ACERO interiors with multiple layers of finishes including satin bronze reveals, Wilsonart laminate in Wild Cherry matte, and bronze panels, new drop ceilings with LED illumination, bronze handrails, protective pads, and porcelain tile flooring. Car operating panels and front hall push button stations will be retained, while rear hall push button stations on Elevator 4 will be replaced with new ADA-compliant units featuring a 3 by 5 inch smoked glass security card reader cutout provided by the owner. The document notes that this summary is a brief outline and that discrepancies should be resolved in favor of the complete body of technical specifications.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
State of Colorado – State Services Building 1525 Sherman Street Install new Elevator Cab Interiors and Denver, CO 80203 Refurbish Car Door Operators and Hoistway Door Equipment Install New Elevator #4 Rear Hall Push Button Stations with Security Card Readers State of Colorado - Design & Construction Management - Project: 2024-070M23 – Replace Car Door Operators and Hoistway Door Equipment - Renovate Elevator Cabs – Install new Limited Access Hall Push Button Stations and Card Readers on Elevator #4 Rear Openings.
Passenger Elevators 1 – 4 – Scope of Work Summary and Schedule of Equipment (1
Description:
Speed/Capacity 500 FPM @ 3,000 Lbs.
Stops/Openings: Cars 1 & 3: eight (8) front openings (B, 1, 2, 3, 4, 5, 5, 6, 7)
Car 2: nine (9) front openings (SB, B, 1, 2, 3, 4, 5, 6, 7)
Car 4: Freight Elevator: nine (9) front openings (SB, B, 1, 2, 3, 4, 5, 6, 7) nine (9) rear openings (SB-R, B-R, 1-R, 2-R, 3-R, 4-R, 5-R, 6-R, 7-R)
Travel: Approximately 80 feet - Contractor to verify
Operation Four (4) Car Group - GAL - Galaxy
Machine Room:
Gearless Hoist Machine, Bedplate, Deflector Sheave, and Hoist Cables
Retain existing - Otis DC Gearless Hoist Machine
Controller Microprocessor/Computerized Elevator – Modify to accept new Car Door Operators
Power Conversion Retain existing - SCR Motor Drive Unit.
Governors Retain existing - Hollister-Whitney Governors
Hoistway:
Hoistway door equipment Remove the existing Montgomery - MAC Hoistway Door equipment and install new GAL or approved equal hoistway door tracks, hanger rollers, closers, interlocks, pickup rollers, retainers, door gibs, and fire stops.
Hoistway Doors & Entrances
Retain the existing Hoistway Doors and Entrances. Refinish the Main Floor “Bronze” Hoistway Entrances and Hoistway Door panels.
Wiring/Duct As needed, install new traveling cables, hoistway wiring, and machine room wiring.
Car:
Car Door Operator Remove the existing Montgomery MAC Car Door Operator and Header and install a new GAL - MOVFR or approved equal Car Door Operators, Headers, Track, Hanger Rollers, Clutch h, Linkage, Gate Switch, and Door Gibs.
Car Door Panels Install new #4 satin finish “Bronze” Car Door Panels.
State of Colorado – State Services Building 1525 Sherman Street Install new Elevator Cab Interiors and Denver, CO 80203 Refurbish Car Door Operators and Hoistway Door Equipment Install New Elevator #4 Rear Hall Push Button Stations with Security Card Readers State of Colorado - Design & Construction Management - Project: 2024-070M23 – Replace Car Door Operators and Hoistway Door Equipment - Renovate Elevator Cabs – Install new Limited Access Hall Push Button Stations and Card Readers on Elevator #4 Rear Openings.
Door Protection Device Provide new code compliant Janus 3D or approved equal.
Cab: Remove the existing Elevator Cab Panels, Handrails, Ceiling, and Flooring. Refinish the existing “Bronze” Front Return Panels, and Transom. Install new “Snap Cab – ACERO or approved equal (See Sketch # 70959 A - Owner to select final finishes and flooring) Install new #4 satin finish Bronze reveals. Provide new “Bronze” lower side and lower rear panels. (Layer 2) Provide Wilsonart Laminate (Wild Cherry, Matte) side and rear panels. (Layers 3 & 5) Provide new 5wl Bronze (Kelp, Clear) side and rear panels. (Layer 4) Install new Bronze drop ceiling with six (6) new LED illumination. Install new 2-inch “Bronze” rear flat Handrail. Provide new Cab Protective Pads and Pad Hooks. Install new Emer - Strands Porcelain Tile 6"x24" floor tile with base cove for wall to floor transition. Use 1/8" bed and head joints in colored grout to match tile color.
Signal Fixtures
Car Operating Panel Retain the existing Car Operating Panel.
Front Hall PB Station Retain the existing Hall Push Button Stations.
Elevator #4 Rear Hall PB Station
Remove the existing Rear Hall Push Button Stations and install new ADA compliant Rear Hall Push Button Stations with a 3 ½ X 5 inch “Smoked Glass” Security Card Reader cut-out. Security Card Reader to be provided by the Owner.